Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 10:43:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1142.09 | 236.21 | 236.21 |
Net Site Energy | 1142.09 | 236.21 | 236.21 |
Total Source Energy | 3337.79 | 690.32 | 690.32 |
Net Source Energy | 3337.79 | 690.32 | 690.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 134.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 80.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 113.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1008.05 | 134.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 134.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 80.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 7.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 106.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 134.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 80.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 113.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 45.17 | 27.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 208.48 | 27.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 45.17 | 27.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 208.48 | 27.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1008.047 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1008.047 | 100.00 |
Total On-Site and Utility Electric Sources | 1008.047 | 100.00 |
Total Electricity End Uses | 1008.047 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 30.83 |
Time Setpoint Not Met During Occupied Cooling | 22.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3035.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:50 | 12-FEB-06:19 | - | - | - | - | - | - | - | - | - | - | 18-SEP-11:39 |
Heating | 0.00 | 234464.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25017.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10654.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1705.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 85672.10 | 234464.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 234464.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25017.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8348.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1705.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 145.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 254.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 358.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3192.49 | 145.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 30.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 660.27 | 30.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 30.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 660.27 | 30.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.23 |
ZONE2 FINE STORAGE DIRECT AIR | 3.64 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.06 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.06 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 120633.47 |
PSZ-OFFICE HEATING COIL | 30356.64 |
PSZ-FINE STORAGE HEATING COIL | 114697.48 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 120633.47 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.000000 | 1.23 |
PSZ-FINE STORAGE | 3.64 | 3.64 | 3.64 | 3.64 | 3.64 | 3.64 | 1.00 | 1.000000 | 3.64 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.23 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.64 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.23 | 1397.08 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.64 | 6951.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 24114.31 | 30356.64 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.64 | 3.64 | 3.64 | 3.64 | 89155.85 | 114697.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.23 | 0.612694 | 1.23 | 24114.31 | 12377.77 | 24114.31 | 0.782260 | 0.782260 |
PSZ-FINE STORAGE COOLING COIL | 3.64 | 1.82 | 3.64 | 89155.85 | 45214.54 | 89155.85 | 0.705580 | 0.705580 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6162 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6162 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6162 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.75489070E-12 | 0.18678307E-15 | -0.24646719E-14 | 0.12171915E-15 |
8 | 3 | -0.37579879E-03 | 0.42795087E-06 | -0.54426377E-04 | 0.14486322E-12 |
9 | 2 | 1.7183777 | 0.94469845E-02 | 1.1243623 | -0.72046233E-04 |
10 | 1 | -7.1567890 | 0.24622403 | -16.995305 | 0.32932838 |
11 | 0 | 5.8520676 | 0.15760904 | 16.284278 | |
12 | 4 | 0.75489070E-12 | 0.18678307E-15 | -0.24646719E-14 | 0.12171915E-15 |
13 | 3 | -0.37579879E-03 | 0.42795087E-06 | -0.54426377E-04 | 0.14486322E-12 |
14 | 2 | 1.7183777 | 0.94469845E-02 | 1.1243623 | -0.72046233E-04 |
15 | 1 | -7.1567890 | 0.24622403 | -16.995305 | 0.32932838 |
16 | 0 | 5.8520676 | 0.15760904 | 16.284278 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.24646719E-14 | 0.18678307E-15 | 0.75489070E-12 | 0.12171915E-15 |
85 | 3 | -0.54426377E-04 | 0.42795087E-06 | -0.37579879E-03 | 0.14486322E-12 |
86 | 2 | 1.1243623 | 0.94469845E-02 | 1.7183777 | -0.72046233E-04 |
87 | 1 | -16.995305 | 0.24622403 | -7.1567890 | 0.32932838 |
88 | 0 | 16.284278 | 0.15760904 | 5.8520676 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
3 | NONRESWINDOW_U_0.6283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
4 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
5 | SKYLIGHT_U_0.65_SHGC_0.35 | 38 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.352 | ||
6 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 39 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.352 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 3.575 | 0.353 | 0.351 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11964.97606 | 14357.97127 | 1.02116 | 1.22539 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.19667 | 1.44711E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11863.11881 | 14235.74257 | 0.34544 | 0.41453 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 45608.03204 | 54729.63845 | 3.03465 | 3.64158 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 41402.59682 | 49683.11618 | 1.01517 | 1.21820 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -6.30000 | 2.29779E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 100527.89409 | 120633.47291 | 2.54742 | 3.05690 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18136.58 | 1.22539 | 1.22539 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 12428.52 | 0.41453 | 0.41453 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 66199.69 | 3.64158 | 3.64158 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 45573.85 | 1.21820 | 1.21820 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22539 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.64158 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.05690 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.05690 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 120633.46947 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 120633.47291 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22539 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22539 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22539 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22539 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22539 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.22539 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.64158 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.64158 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.64158 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.64158 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.64158 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.64158 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.22539 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.64158 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22539 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22539 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1397.07680 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22539 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22539 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22539 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22539 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22539 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61269 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22539 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24114.31000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12377.77215 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24114.31000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78226 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78226 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24114.31000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30356.64235 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 30356.64235 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.64158 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.64158 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6951.64487 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.64158 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.64158 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.64158 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.64158 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.64158 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.82079 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.64158 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 89155.85000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 45214.54227 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 89155.85000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70558 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70558 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 89155.85000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 114697.48339 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 114697.48339 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23162.8 | 10.98 | 10.35 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 86325.5 | 10.51 | 9.90 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 8.3825165185E-002 | 0.1193926961 | Pass | Pass | 2.6647088388 | 18.4227854678 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2505251768 | 0.2764190297 | Pass | Pass | 6.4454124555E-002 | 0.2976977273 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.3954293092E-002 | 3.9696660050E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9902.12 | 599.60 | 0.00 | 53.78 | 391.72 | 10947.24 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.537 | 0.616 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.537 | 0.616 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.628 | 0.298 | 0.297 | |||||||||||||||||
North Total or Average | 6.51 | 3.572 | 0.252 | 0.251 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.642 | 0.309 | 0.308 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.77 | 83.77 | 134.17 | |
Exterior Lighting Total | 8532.22 | 134.17 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24114.31 | 18863.66 | 5250.65 | 0.78 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 89155.85 | 62906.58 | 26249.27 | 0.71 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23162.8 | 10.98 | 10.35 | ||||
PSZ-FINE STORAGE COOLING COIL | 86325.5 | 10.51 | 9.90 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 120633.47 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 30356.64 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 114697.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.06 | 284.02 | 92.91 | 1.00 | 3.35 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.23 | 1397.08 | 1140.11 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.64 | 6951.64 | 1908.96 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11964.98 | 14357.97 | 60.61 | 1.021 | 1.225 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00863 | 33.20 | 0.01447 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 45608.03 | 54729.64 | 39.28 | 3.035 | 3.642 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.69 | 0.00911 | 34.30 | 0.01447 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 34.41 | 0.01455 | 34.30 | 0.01447 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11863.12 | 14235.74 | 60.10 | 0.345 | 0.415 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00698 | -6.30 | 0.00230 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 41402.60 | 49683.12 | 35.66 | 1.015 | 1.218 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00555 | -6.30 | 0.00230 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 100527.89 | 120633.47 | 37.64 | 2.547 | 3.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00474 | -6.30 | 0.00230 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.23 | 1.23 | 0.41 | 0.41 | 1.2254 | 1.2254 | 1.2254 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.64 | 3.64 | 1.22 | 1.22 | 3.6416 | 3.6416 | 3.6416 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 120633.469 | 120633.469 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 120633.47 | 120633.47 | 3.056902 | 10.00 | 6.43 | 0.00474359 | 43.33 | 21.72 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 10.00 | 0.00474359 | 60.2210 | 120633.47 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 24114.310 | 18863.660 | 1.225390 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24114.31 | 20434.43 | 1.225390 | 25.66 | 17.10 | 0.00911723 | 12.00 | 10.94 | 0.00800000 | 33.45 | 0.01447152 | 23.29 | 8.3471 | 23.90 | 0.00862925 | 45.0538 | 11957.05 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 30356.642 | 30356.642 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 30356.64 | 30356.64 | 1.225388 | 18.77 | 12.31 | 0.00658895 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 8.3471 | 21.10 | 0.00697976 | 43.3185 | 11863.12 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 89155.850 | 62906.585 | 3.641580 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 89155.85 | 72554.54 | 3.641580 | 29.19 | 18.75 | 0.00973856 | 12.00 | 10.94 | 0.00800000 | 34.30 | 0.01447309 | 23.52 | 11.6628 | 26.69 | 0.00911348 | 40.2567 | 45608.03 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 114697.483 | 114697.483 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 114697.48 | 114697.48 | 3.641579 | 13.00 | 8.35 | 0.00517502 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 11.6628 | 15.55 | 0.00555489 | 48.9383 | 41402.60 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 120633.469 | 120633.469 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.056902 | 3.54899187 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 120633.47 | 120633.47 | 1.0000 | 3.54899187 | 3.056902 | 10.00 | 6.43 | 0.00474359 | 21996.1 | 43.33 | 21.72 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 120633.47 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00474359 | 10.00 | 0.00474359 | 60.2210 | 120633.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24114.310 | 18863.660 | 1.225390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7885 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.225388 | 1.42264654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 24114.31 | 20434.43 | 1.0000 | 1.42264904 | 1.225390 | 25.66 | 17.10 | 0.00911723 | 49017.0 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24114.31 | 33.45 | 0.01447152 | 23.29 | 0.10228463 | 8.3471 | 23.90 | 0.00862925 | 23.90 | 0.00862925 | 45.0538 | 11957.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30356.642 | 30356.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.225388 | 1.42264654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 30356.64 | 30356.64 | 1.0000 | 1.42264654 | 1.225388 | 18.77 | 12.31 | 0.00658895 | 35564.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30356.64 | -6.30 | 0.00229779 | -6.30 | 0.10228463 | 8.3471 | 21.05 | 0.00697976 | 21.10 | 0.00697976 | 43.3185 | 11863.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 89155.850 | 62906.585 | 3.641580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9435 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.641579 | 4.22778806 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 89155.85 | 72554.54 | 1.0000 | 4.22778895 | 3.641580 | 29.19 | 18.75 | 0.00973856 | 54215.2 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89155.85 | 34.30 | 0.01447309 | 23.52 | 0.42471127 | 11.6628 | 26.69 | 0.00911348 | 26.69 | 0.00911348 | 40.2567 | 45608.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 114697.483 | 114697.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.641579 | 4.22778806 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 114697.48 | 114697.48 | 1.0000 | 4.22778806 | 3.641579 | 13.00 | 8.35 | 0.00517502 | 26132.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 114697.48 | -6.30 | 0.00229779 | -6.30 | 0.42471127 | 11.6628 | 15.55 | 0.00555489 | 15.55 | 0.00555489 | 48.9383 | 41402.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.10 | 1.23 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 3.64 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2450.67 | 1939.17 | 990.17 |
ZONE2 FINE STORAGE | 3001.17 | 2907.67 | 2382.50 |
ZONE3 BULK STORAGE | 3197.67 | 3311.83 | 2926.67 |
Facility | 3533.67 | 3416.83 | 3035.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 40.00 | 23.17 | 26.17 | 22.67 |
ZONE2 FINE STORAGE | 131.17 | 118.00 | 9.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 162.83 | 141.17 | 30.83 | 22.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.792 | 0.528 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.900 | 0.445 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.192 | 0.000 | 0.630 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2852291.96 | 0.00 | 2852291.96 | 3185880.48 | 6038172.45 | 3225648.14 | 5678.63 | 2154.26 | 927.10 | 0.49 |
ZONE2 FINE STORAGE | 9455629.06 | 0.00 | 9455629.06 | 12137894.78 | 21593523.84 | 13393694.68 | 5659.34 | 2245.92 | 854.74 | 7.63 |
ZONE3 BULK STORAGE | 0.00 | 0.13E+09 | 0.13E+09 | 49067972.62 | 0.17E+09 | 30805497.77 | 7476.52 | 36.47 | 1247.01 | 4988.08 |
Total Facility | 12307921.03 | 0.13E+09 | 0.14E+09 | 64391747.89 | 0.20E+09 | 47424840.58 | 7988.64 | 2549.15 | 2449.15 | 4988.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2178 | 0.0000 | 0.2178 | 0.1457 | 0.3635 | 0.1023 | 555.12 | 2154.26 | 926.61 |
ZONE2 FINE STORAGE | 0.7173 | 0.0000 | 0.7173 | 0.3584 | 1.0757 | 0.4247 | 542.89 | 2245.75 | 847.36 |
ZONE3 BULK STORAGE | 0.0000 | 5.8547 | 5.8547 | 1.8568 | 7.7115 | 0.9768 | 2845.44 | 18.75 | 771.81 |
Total Facility | 0.9351 | 5.8547 | 6.7898 | 2.3608 | 9.1506 | 1.5038 | 2864.64 | 2531.26 | 1966.44 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3844508.87 | 0.00 | 3844508.87 | 3225648.14 | 5676.69 | 0.00 | 3083.31 | 0.49 |
PSZ-FINE STORAGE | 12744925.91 | 0.00 | 12744925.91 | 13393694.68 | 5657.79 | 0.00 | 3102.21 | 7.63 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2936 | 0.0000 | 0.2936 | 0.1023 | 553.18 | 0.00 | 3082.82 |
PSZ-FINE STORAGE | 0.9668 | 0.0000 | 0.9668 | 0.4247 | 541.41 | 0.00 | 3094.59 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2568.29 | 522.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2647.13 | 458.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3016 | 0.5614 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.0005 | 1.9105 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1008.05 | 5771.67 | 01-JAN-08:00 | 85672.10 | 08-JUL-14:50 |
Electricity:Building | 662.63 | 5288.67 | 01-JAN-00:10 | 50600.89 | 18-MAY-12:50 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 355.69 | 2117.83 | 01-JAN-00:10 | 28507.00 | 18-MAY-13:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 113.34 | 0.00 | 01-JAN-00:40 | 10654.02 | 18-MAY-14:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.15 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-MAY-14:50 |
Ventilation (simple):Fans:Electricity | 7.15 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-MAY-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.15 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-MAY-14:50 |
ElectricityPurchased:Facility | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
ElectricityPurchased:Plant | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
Cogeneration:ElectricityPurchased | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
General:Cogeneration:ElectricityPurchased | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
ElectricityNet:Plant | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
Cogeneration:ElectricityNet | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
General:Cogeneration:ElectricityNet | 1008.05 | 5771.67 | 16-APR-11:50 | 85672.10 | 08-JUL-14:50 |
Electricity:HVAC | 186.69 | 0.00 | 01-JAN-00:40 | 33782.98 | 03-AUG-16:00 |
General:Fans:Electricity | 106.19 | 0.00 | 01-JAN-00:40 | 8632.74 | 05-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 80.50 | 0.00 | 01-JAN-00:10 | 25434.26 | 03-AUG-16:00 |
General:Cooling:Electricity | 80.50 | 0.00 | 01-JAN-00:10 | 25434.26 | 03-AUG-16:00 |
ExteriorLights:Electricity | 134.17 | 0.00 | 01-JAN-07:50 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.17 | 0.00 | 01-JAN-07:50 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 24.56 | 483.00 | 09-JAN-06:40 | 2121.91 | 01-FEB-13:00 |
WaterSystems:Electricity | 24.56 | 483.00 | 09-JAN-06:40 | 2121.91 | 01-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 24.56 | 483.00 | 09-JAN-06:40 | 2121.91 | 01-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 134.04 | 0.00 | 01-JAN-00:40 | 234464.14 | 12-FEB-06:20 |
NaturalGas:HVAC | 134.04 | 0.00 | 01-JAN-00:40 | 234464.14 | 12-FEB-06:20 |
Heating:NaturalGas | 134.04 | 0.00 | 01-JAN-00:40 | 234464.14 | 12-FEB-06:20 |
General:Heating:NaturalGas | 134.04 | 0.00 | 01-JAN-00:40 | 234464.14 | 12-FEB-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 18-SEP-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 679.18 | 0.00 | 01-JAN-00:40 | 365404.75 | 12-FEB-06:20 |
EnergyTransfer:Building | 302.00 | 0.00 | 01-JAN-00:40 | 184582.45 | 12-FEB-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 62.70 | 0.00 | 01-JAN-00:30 | 24832.76 | 13-FEB-07:30 |
Heating:EnergyTransfer | 114.18 | 0.00 | 01-JAN-00:40 | 184582.45 | 12-FEB-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 14.39 | 0.00 | 01-JAN-00:30 | 24832.76 | 13-FEB-07:30 |
General:Heating:EnergyTransfer | 114.18 | 0.00 | 01-JAN-00:40 | 184582.45 | 12-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 14.39 | 0.00 | 01-JAN-00:30 | 24832.76 | 13-FEB-07:30 |
Cooling:EnergyTransfer | 187.83 | 0.00 | 01-JAN-00:10 | 51359.85 | 03-AUG-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 48.31 | 0.00 | 01-JAN-00:10 | 13490.13 | 01-AUG-17:00 |
General:Cooling:EnergyTransfer | 187.83 | 0.00 | 01-JAN-00:10 | 51359.85 | 03-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 48.31 | 0.00 | 01-JAN-00:10 | 13490.13 | 01-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 182.28 | 0.00 | 01-JAN-00:40 | 62612.10 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.76 | 0.00 | 01-JAN-00:40 | 62612.10 | 12-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.76 | 0.00 | 01-JAN-00:40 | 62612.10 | 12-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.51 | 0.00 | 01-JAN-00:10 | 39769.06 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.51 | 0.00 | 01-JAN-00:10 | 39769.06 | 02-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 57.02 | 0.00 | 01-JAN-00:10 | 121119.12 | 12-FEB-05:50 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 57.02 | 0.00 | 01-JAN-00:10 | 121119.12 | 12-FEB-05:50 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 57.02 | 0.00 | 01-JAN-00:10 | 121119.12 | 12-FEB-05:50 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 377.18 | 0.00 | 01-JAN-00:40 | 180822.30 | 12-FEB-06:20 |
HeatingCoils:EnergyTransfer | 100.00 | 0.00 | 01-JAN-00:40 | 180822.30 | 12-FEB-06:20 |
CoolingCoils:EnergyTransfer | 277.18 | 0.00 | 01-JAN-00:10 | 82513.41 | 03-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 14.390 | -48.313 | 0.000 | 0.000 | 9.528 | 30.293 | 31.946 | 9.051 | 0.000 | 2.902 | 0.000 | 0.000 | -9.290 | 0.000 | -28.207 | -12.301 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 42.764 | -139.504 | 0.000 | 0.000 | 20.489 | 244.699 | 0.000 | 0.000 | 0.000 | 4.881 | 0.000 | 0.000 | 0.000 | 0.000 | -106.219 | -67.110 |
ZONE3 BULK STORAGE | 57.021 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 50.400 | 241.203 | 107.344 | 89.349 | 0.000 | 15.338 | 0.008 | 0.000 | -34.444 | 0.000 | -475.700 | -50.511 |
Total Facility | 57.021 | 0.000 | 57.154 | -187.817 | 0.000 | 0.000 | 80.418 | 516.195 | 139.290 | 98.400 | 0.000 | 23.121 | 0.008 | 0.000 | -43.734 | 0.000 | -610.125 | -129.922 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 10-JUN-05:02 | 0.00 | 0.00 | 0.00 | -28759.16 | 0.00 | 0.00 | 89.40 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 28359.29 | 0.00 | -742.91 | 0.00 | -93.55 | 0.00 |
ZONE2 FINE STORAGE | 13-MAY-18:11 | 0.00 | 0.00 | 0.00 | -82794.70 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 81389.64 | 0.00 | -0.00 | 0.00 | -743.47 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JUL-17:03 | 0.00 | 0.00 | 0.00 | -85830.64 | 0.00 | 0.00 | 0.00 | 4714.92 | 573.75 | 11724.43 | 0.00 | 1625.34 | 75086.16 | 0.00 | 0.00 | 0.00 | -7893.96 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:31 | 0.00 | 0.00 | 31270.01 | 0.00 | 0.00 | 0.00 | 118.54 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1171.17 | 0.00 | -5977.87 | -25386.44 |
ZONE2 FINE STORAGE | 07-JAN-05:22 | 0.00 | 0.00 | 120545.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18929.80 | -103764.68 |
ZONE3 BULK STORAGE | 12-FEB-05:50 | 121117.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3589.17 | 0.00 | -111088.73 | -8557.89 |
Total Facility | 12-FEB-06:01 | 120930.43 | 0.00 | 116921.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4714.92 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7394.42 | 0.00 | -147673.00 | -88072.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2254 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2254 | 0.0835 | 1.0000 | Not calculated | 0.1023 | 0.0835 | ||
PSZ-FINE STORAGE | 3.6416 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.6416 | 0.1166 | 1.0000 | Not calculated | 0.4247 | 0.1166 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2254 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2254 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0835 | ||
PSZ-FINE STORAGE | 3.6416 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.6416 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1166 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2254 | 1.2254 | 1.2254 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.6416 | 3.6416 | 3.6416 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2254 | 1.2254 | 1.2254 | 1.2254 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.6416 | 3.6416 | 3.6416 | 3.6416 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2254 | 1.2254 | 1.2254 | No | 0.1023 | 0.2468 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.6416 | 3.6416 | 3.6416 | No | 0.4247 | 0.3486 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2254 | 1.2254 | 1.2254 | 1.2254 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.6416 | 3.6416 | 3.6416 | 3.6416 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 30.83 |
Number of hours cooling loads not met | 22.67 |
Number of hours not met | 53.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 134.04 | 234464.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 80.50 | 25434.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.17 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 7.15 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 106.19 | 8632.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.56 | 2121.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1008.05 |
Natural Gas | 0.00 | 134.04 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1142.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 16.65 |
Fans (All) | 23.44 |
Service Water Heating | 5.08 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 208.48 |
Subtotal | 208.48 |
Natural Gas [MJ/m2] | |
Space Heating | 27.72 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 27.72 |
Subtotal | 27.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.20 |
Space Heating | 11.74 |
Space Cooling | 7.05 |
Fans (All) | 9.92 |
Service Water Heating | 2.15 |
Receptacle Equipment | 12.20 |
Miscellaneous | 11.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7101.00 | 1645.83 | 13.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6025.33 | 2734.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5674.50 | 2357.00 | 728.50 | 0.00 | 0.00 |
Min | 5674.50 | 1645.83 | 0.00 | 0.00 | 0.00 |
Max | 7101.00 | 2734.67 | 728.50 | 0.00 | 0.00 |
Average | 6266.94 | 2245.83 | 247.22 | 0.00 | 0.00 |
Sum | 18800.83 | 6737.50 | 741.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 49636.00 | 33083.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 116495.83 | 49600.17 | 25097.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 116495.83 | 49600.17 | 25097.00 | 0.00 | 0.00 |
Average | 66386.28 | 27561.06 | 8365.67 | 0.00 | 0.00 |
Sum | 199158.83 | 82683.17 | 25097.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 6552.83 | 2206.67 | 0.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5355.17 | 3404.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5287.33 | 3307.17 | 165.50 | 0.00 | 0.00 |
Min | 5287.33 | 2206.67 | 0.00 | 0.00 | 0.00 |
Max | 6552.83 | 3404.83 | 165.50 | 0.00 | 0.00 |
Average | 5731.78 | 2972.89 | 55.33 | 0.00 | 0.00 |
Sum | 17195.33 | 8918.67 | 166.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32028.50 | 998.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 46866.00 | 35853.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 110281.00 | 72921.83 | 7990.17 | 0.00 | 0.00 |
Min | 32028.50 | 998.50 | 0.00 | 0.00 | 0.00 |
Max | 110281.00 | 72921.83 | 7990.17 | 0.00 | 0.00 |
Average | 63058.50 | 36591.11 | 2663.39 | 0.00 | 0.00 |
Sum | 189175.50 | 109773.33 | 7990.17 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38603035.89 | 967.19 | 20-JAN-16:00 | 17.20 | 12.77 | 0.510998E+09 | 768.96 | 20-JAN-16:00 | 16.70 | 11.48 |
February | 0.284453E+09 | 4350.08 | 28-FEB-16:30 | 23.60 | 12.74 | 0.496867E+09 | 768.96 | 23-FEB-16:19 | 23.60 | 12.74 |
March | 0.153561E+10 | 7491.09 | 30-MAR-16:00 | 27.80 | 17.47 | 0.646344E+09 | 769.04 | 30-MAR-15:20 | 27.80 | 17.47 |
April | 0.327473E+10 | 23925.91 | 18-APR-05:03 | 14.22 | 12.17 | 0.624883E+09 | 769.05 | 19-APR-15:39 | 26.70 | 16.98 |
May | 0.550204E+10 | 24114.07 | 17-MAY-05:02 | 16.70 | 13.07 | 0.658650E+09 | 769.07 | 06-MAY-15:00 | 16.70 | 13.07 |
June | 0.812112E+10 | 28764.62 | 10-JUN-05:02 | 11.28 | 8.79 | 0.660234E+09 | 769.09 | 27-JUN-15:00 | 32.80 | 23.20 |
July | 0.856731E+10 | 22372.60 | 03-JUL-05:01 | 17.88 | 16.41 | 0.635133E+09 | 769.09 | 07-JUL-12:09 | 33.40 | 24.94 |
August | 0.957415E+10 | 22241.14 | 26-AUG-05:01 | 21.70 | 17.15 | 0.685982E+09 | 769.09 | 16-AUG-15:00 | 21.70 | 17.15 |
September | 0.678211E+10 | 26223.21 | 15-SEP-05:01 | 14.90 | 12.38 | 0.634809E+09 | 769.06 | 25-SEP-15:09 | 29.40 | 19.56 |
October | 0.322437E+10 | 19986.19 | 10-OCT-05:03 | 15.92 | 14.94 | 0.622342E+09 | 769.02 | 05-OCT-12:50 | 15.92 | 14.94 |
November | 0.119837E+10 | 5215.81 | 06-NOV-16:00 | 20.60 | 10.48 | 0.567087E+09 | 769.01 | 01-NOV-14:50 | 20.60 | 10.48 |
December | 0.211531E+09 | 2800.85 | 12-DEC-15:00 | 22.80 | 16.17 | 0.542371E+09 | 768.99 | 13-DEC-13:20 | 19.83 | 17.21 |
Annual Sum or Average | 0.483144E+11 | 0.728570E+10 | ||||||||
Minimum of Months | 38603035.89 | 967.19 | 11.28 | 8.79 | 0.496867E+09 | 768.96 | 15.92 | 10.48 | ||
Maximum of Months | 0.957415E+10 | 28764.62 | 27.80 | 17.47 | 0.685982E+09 | 769.09 | 33.40 | 24.94 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408360E+09 | 3129.02 | 14-JAN-09:50 | -2.7 | -5.2 | 0.901543E+09 | 1854.09 | 31-JAN-15:20 | 20.73 | 13.19 |
February | 0.235240E+09 | 3398.54 | 03-FEB-11:00 | -3.3 | -6.2 | 0.100562E+10 | 2246.80 | 28-FEB-13:20 | 23.87 | 13.06 |
March | 0.124439E+10 | 18088.92 | 30-MAR-14:20 | 27.80 | 17.60 | 0.165343E+10 | 2246.85 | 11-MAR-13:20 | 27.80 | 17.60 |
April | 0.632975E+10 | 80133.76 | 15-APR-17:11 | 26.13 | 15.35 | 0.175375E+10 | 2246.99 | 17-APR-13:39 | 28.53 | 16.73 |
May | 0.149393E+11 | 82793.88 | 13-MAY-18:11 | 25.03 | 14.25 | 0.190976E+10 | 2247.06 | 19-MAY-15:00 | 30.60 | 19.37 |
June | 0.272276E+11 | 82158.97 | 07-JUN-17:12 | 23.70 | 14.04 | 0.192617E+10 | 2247.10 | 05-JUN-15:00 | 23.70 | 14.04 |
July | 0.312207E+11 | 70833.65 | 03-JUL-17:42 | 29.50 | 21.08 | 0.185416E+10 | 2247.14 | 08-JUL-15:50 | 36.70 | 23.90 |
August | 0.336764E+11 | 70079.46 | 26-AUG-17:42 | 30.60 | 20.75 | 0.200294E+10 | 2247.06 | 25-AUG-13:09 | 30.60 | 20.75 |
September | 0.183308E+11 | 81027.63 | 13-SEP-17:11 | 22.93 | 15.03 | 0.184949E+10 | 2247.00 | 13-SEP-15:09 | 22.93 | 15.03 |
October | 0.537372E+10 | 82375.27 | 11-OCT-17:12 | 23.67 | 13.73 | 0.170286E+10 | 2246.87 | 03-OCT-13:39 | 23.67 | 13.73 |
November | 0.410438E+09 | 6993.76 | 06-NOV-15:00 | 20.60 | 10.48 | 0.140063E+10 | 2246.80 | 18-NOV-15:50 | 21.10 | 9.87 |
December | 0.115998E+09 | 3348.19 | 01-DEC-09:15 | 0.17 | -2.0 | 0.111577E+10 | 2174.34 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.139513E+12 | 0.190761E+11 | ||||||||
Minimum of Months | 0.115998E+09 | 3129.02 | -3.3 | -6.2 | 0.901543E+09 | 1854.09 | 20.73 | 9.87 | ||
Maximum of Months | 0.336764E+11 | 82793.88 | 30.60 | 21.08 | 0.200294E+10 | 2247.14 | 36.70 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 | 4.97 | 0.888632E+09 | 2046.09 | 31-JAN-15:50 | 20.18 | 13.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.110854E+10 | 3499.84 | 28-FEB-15:30 | 24.15 | 13.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.240603E+10 | 4440.56 | 30-MAR-15:00 | 27.80 | 17.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 | 0.330750E+10 | 5644.56 | 19-APR-15:09 | 26.70 | 17.45 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.448748E+10 | 6761.75 | 19-MAY-15:09 | 30.60 | 18.82 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.551879E+10 | 8204.26 | 06-JUN-15:20 | 34.23 | 22.26 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.552443E+10 | 9097.65 | 08-JUL-14:30 | 36.40 | 24.19 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 21.87 | 0.594634E+10 | 8560.42 | 18-AUG-15:00 | 35.00 | 23.11 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 | 0.489625E+10 | 7300.71 | 07-SEP-15:39 | 31.70 | 23.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.329629E+10 | 5749.15 | 02-OCT-14:00 | 26.70 | 20.22 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 | 0.200402E+10 | 3722.17 | 06-NOV-15:39 | 20.60 | 10.48 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.121591E+10 | 2572.44 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.00 | 0.406002E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.888632E+09 | 2046.09 | 20.18 | 10.48 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.594634E+10 | 9097.65 | 36.40 | 24.19 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556269E+10 | 31109.15 | 09-JAN-06:12 | -2.6 |
February | 0.373037E+10 | 31269.99 | 13-FEB-06:31 | -5.6 |
March | 0.792810E+09 | 30594.32 | 22-MAR-05:01 | 6.02 |
April | 0.263287E+09 | 29932.40 | 06-APR-05:02 | 0.18 |
May | 69091064.85 | 2465.48 | 11-MAY-06:20 | 8.53 |
June | 16409154.13 | 1772.99 | 07-JUN-06:10 | 13.48 |
July | 845949.10 | 934.33 | 28-JUL-06:03 | 19.40 |
August | 897559.58 | 1032.67 | 25-AUG-06:15 | 18.50 |
September | 21348489.45 | 1802.57 | 14-SEP-06:10 | 12.30 |
October | 0.233235E+09 | 29200.80 | 26-OCT-05:02 | 2.20 |
November | 0.100646E+10 | 30767.27 | 22-NOV-06:12 | -3.3 |
December | 0.269230E+10 | 30854.50 | 18-DEC-06:12 | -5.0 |
Annual Sum or Average | 0.143897E+11 | |||
Minimum of Months | 845949.10 | 934.33 | -5.6 | |
Maximum of Months | 0.556269E+10 | 31269.99 | 19.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169352E+11 | 120545.68 | 07-JAN-05:22 | -0.9 |
February | 0.112775E+11 | 120497.68 | 11-FEB-22:42 | -8.2 |
March | 0.175483E+10 | 7367.28 | 18-MAR-07:00 | 2.20 |
April | 0.882641E+09 | 6907.40 | 15-APR-06:25 | 12.80 |
May | 0.477968E+09 | 6897.17 | 03-MAY-06:25 | 16.10 |
June | 0.134232E+09 | 6926.84 | 09-JUN-06:25 | 15.25 |
July | 15286768.08 | 5932.00 | 03-JUL-06:03 | 18.68 |
August | 4759046.73 | 6000.78 | 25-AUG-06:03 | 18.40 |
September | 0.241151E+09 | 6656.23 | 14-SEP-07:00 | 12.80 |
October | 0.976094E+09 | 7148.24 | 25-OCT-07:00 | 8.30 |
November | 0.229644E+10 | 57736.69 | 22-NOV-05:33 | -3.1 |
December | 0.776826E+10 | 115690.92 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.427644E+11 | |||
Minimum of Months | 4759046.73 | 5932.00 | -8.2 | |
Maximum of Months | 0.169352E+11 | 120545.68 | 18.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326401E+11 | 93072.96 | 07-JAN-10:00 | -3.9 |
February | 0.229188E+11 | 121119.12 | 12-FEB-05:50 | -12.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.146228E+10 | 23264.96 | 03-DEC-09:00 | -1.1 |
Annual Sum or Average | 0.570212E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.326401E+11 | 121119.12 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541730E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3431936.28 | 0.434368E+10 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25709311.98 | 0.306196E+10 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95606967.15 | 0.194864E+10 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227060E+09 | 0.126508E+10 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729691E+09 | 0.639742E+09 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709220E+09 | 0.470443E+09 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794687E+09 | 0.355173E+09 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263849E+09 | 0.803921E+09 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53001601.19 | 0.239788E+10 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139366.06 | 0.320767E+10 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429536E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290240E+10 | 0.282069E+11 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355173E+09 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794687E+09 | 0.541730E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183204E+11 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9712670.53 | 0.154509E+11 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7970029.78 | 0.115784E+11 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32980627.53 | 0.821934E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194462E+09 | 0.573137E+10 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139117E+10 | 0.314835E+10 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146741E+10 | 0.228500E+10 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147549E+10 | 0.169184E+10 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271750E+09 | 0.373155E+10 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24211426.53 | 0.968466E+10 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5523196.83 | 0.111412E+11 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152360E+11 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488068E+10 | 0.106219E+12 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169184E+10 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147549E+10 | 0.183204E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128355E+10 | 0.425533E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181966E+10 | 0.323656E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142059E+10 | 0.263261E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732338E+09 | 0.237971E+11 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75182375.73 | 0.209104E+11 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101803E+09 | 0.169670E+11 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63899823.11 | 0.136838E+11 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54612227.53 | 0.120672E+11 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 921182.79 | 0.189693E+11 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125446E+09 | 0.310742E+11 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959677E+09 | 0.273900E+11 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878701E+09 | 0.303342E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751638E+10 | 0.296438E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 921182.79 | 0.120672E+11 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181966E+10 | 0.425533E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14076.10 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.71 | 26-FEB-13:00 | 16056.19 | 13-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1880.94 | 30-MAR-16:10 | 9671.83 | 22-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.63 | 17-APR-16:10 | 9527.06 | 06-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2997.39 | 19-MAY-16:10 | 6266.79 | 11-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5166.64 | 06-JUN-17:00 | 5129.82 | 08-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4524.85 | 07-JUL-16:10 | 2644.32 | 28-JUL-17:00 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5263.89 | 01-AUG-17:00 | 2374.54 | 25-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3177.88 | 08-SEP-16:10 | 5051.23 | 14-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2449.32 | 10-OCT-16:10 | 8914.89 | 26-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.06 | 19-NOV-15:00 | 12116.31 | 21-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 12352.73 | 18-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.54 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5263.89 | 16056.19 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 32334.45 | 07-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.82 | 26-FEB-13:00 | 36125.35 | 11-FEB-17:40 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164.42 | 30-MAR-16:00 | 18086.56 | 18-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.43 | 16-APR-12:10 | 20579.29 | 05-APR-15:03 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3005.47 | 19-MAY-16:00 | 12364.77 | 10-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8866.47 | 06-JUN-15:10 | 11632.40 | 07-JUN-07:00 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5340.23 | 10-JUL-15:10 | 8755.76 | 28-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7538.07 | 01-AUG-17:00 | 4626.21 | 25-AUG-06:10 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3369.82 | 08-SEP-16:00 | 9466.49 | 30-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.21 | 10-OCT-16:00 | 20703.45 | 25-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.53 | 19-NOV-15:00 | 21124.83 | 20-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 28844.36 | 02-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4626.21 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8866.47 | 36125.35 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19019.06 | 19-JAN-16:00 | 88486.18 | 07-JAN-10:00 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18865.04 | 16-FEB-17:00 | 88291.19 | 11-FEB-17:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15199.32 | 11-MAR-16:00 | 55141.04 | 18-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9649.98 | 07-APR-15:00 | 68969.61 | 05-APR-11:00 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2724.19 | 06-MAY-16:00 | 39220.62 | 10-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2491.87 | 25-JUN-15:52 | 43840.89 | 30-JUN-15:55 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.39 | 22-JUL-10:55 | 33195.14 | 28-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.29 | 01-AUG-17:00 | 22850.35 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.74 | 25-SEP-13:55 | 32891.37 | 28-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4425.10 | 10-OCT-16:00 | 62639.66 | 25-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15078.25 | 27-NOV-13:10 | 57132.87 | 20-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12384.35 | 11-DEC-14:00 | 67729.40 | 02-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 452.74 | 22850.35 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19019.06 | 88486.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 967.19 | 20-JAN-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.68 |
February | 4350.08 | 28-FEB-16:30 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.84 |
March | 7491.09 | 30-MAR-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 884.21 | 0.00 |
April | 23925.91 | 18-APR-05:03 | 739.61 | 2292.70 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.63 |
May | 24114.07 | 17-MAY-05:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.39 |
June | 28764.62 | 10-JUN-05:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.55 |
July | 22372.60 | 03-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.11 |
August | 22241.14 | 26-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.76 |
September | 26223.21 | 15-SEP-05:01 | 1294.31 | 4012.23 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.54 |
October | 19986.19 | 10-OCT-05:03 | 739.61 | 2292.70 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.20 |
November | 5215.81 | 06-NOV-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.03 |
December | 2800.85 | 12-DEC-15:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 967.19 | 739.61 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28764.62 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 884.21 | 893.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3129.02 | 14-JAN-09:50 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3511.38 |
February | 3398.54 | 03-FEB-11:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6852.48 |
March | 18088.92 | 30-MAR-14:20 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.31 | 0.00 |
April | 80133.76 | 15-APR-17:11 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.05 |
May | 82793.88 | 13-MAY-18:11 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.47 |
June | 82158.97 | 07-JUN-17:12 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1379.51 |
July | 70833.65 | 03-JUL-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.54 | 0.00 |
August | 70079.46 | 26-AUG-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.41 | 0.00 |
September | 81027.63 | 13-SEP-17:11 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.63 |
October | 82375.27 | 11-OCT-17:12 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.37 |
November | 6993.76 | 06-NOV-15:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.64 |
December | 3348.19 | 01-DEC-09:15 | 7911.00 | 36524.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4021.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3129.02 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82793.88 | 7911.00 | 36524.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.41 | 6852.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 6353.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12858.66 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8552.70 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6291.82 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12270.83 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6852.77 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7899.71 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8515.34 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.94 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10061.41 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16044.54 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16649.66 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32929.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.94 | |
Maximum of Months | 0.00 | 0.00 | 6353.50 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32929.46 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.795326E+11 | 58715.32 | 17-JAN-13:09 | 0.705363E+11 | 179637.83 | 07-JAN-18:49 |
February | 0.716793E+11 | 61190.82 | 28-FEB-15:09 | 0.468757E+11 | 234464.14 | 12-FEB-06:19 |
March | 0.810345E+11 | 70433.02 | 30-MAR-14:50 | 0.918548E+09 | 19135.95 | 22-MAR-05:10 |
April | 0.774807E+11 | 71774.47 | 17-APR-14:00 | 0.209198E+09 | 12711.40 | 06-APR-06:10 |
May | 0.843503E+11 | 77956.81 | 30-MAY-14:50 | 2069372.86 | 828.99 | 11-MAY-06:30 |
June | 0.939159E+11 | 82849.97 | 06-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.968332E+11 | 85672.10 | 08-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.103775E+12 | 84361.06 | 02-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.862597E+11 | 81638.59 | 07-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.791717E+11 | 72940.62 | 11-OCT-14:09 | 0.166973E+09 | 11392.70 | 26-OCT-06:10 |
November | 0.751504E+11 | 60087.48 | 02-NOV-14:20 | 0.198315E+10 | 42594.85 | 22-NOV-06:19 |
December | 0.788641E+11 | 59432.35 | 12-DEC-14:30 | 0.133491E+11 | 72408.34 | 03-DEC-08:50 |
Annual Sum or Average | 0.100805E+13 | 0.134041E+12 | ||||
Minimum of Months | 0.716793E+11 | 58715.32 | 0.00 | 0.00 | ||
Maximum of Months | 0.103775E+12 | 85672.10 | 0.705363E+11 | 234464.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.132795E+11 | 0.115358E+11 | 0.00 | 0.957802E+10 | 0.00 | 0.00 | 610.16 | 0.00 | 0.00 | 0.00 | 0.218864E+10 | 0.00 |
February | 0.393028E+11 | 0.113342E+11 | 0.105871E+11 | 0.00 | 0.841344E+10 | 0.00 | 0.00 | 53423218.58 | 0.00 | 0.00 | 0.00 | 0.198836E+10 | 0.00 |
March | 0.453764E+11 | 0.115902E+11 | 0.123431E+11 | 0.00 | 0.893669E+10 | 0.00 | 0.00 | 0.575332E+09 | 0.00 | 0.00 | 0.00 | 0.221278E+10 | 0.00 |
April | 0.425433E+11 | 0.102591E+11 | 0.114862E+11 | 0.00 | 0.830952E+10 | 0.00 | 0.00 | 0.282704E+10 | 0.00 | 0.00 | 0.00 | 0.205557E+10 | 0.00 |
May | 0.441635E+11 | 0.976769E+10 | 0.119357E+11 | 0.00 | 0.893384E+10 | 0.00 | 0.00 | 0.748446E+10 | 0.00 | 0.00 | 0.00 | 0.206505E+10 | 0.00 |
June | 0.437562E+11 | 0.908681E+10 | 0.118862E+11 | 0.00 | 0.110286E+11 | 0.00 | 0.00 | 0.161969E+11 | 0.00 | 0.00 | 0.00 | 0.196123E+10 | 0.00 |
July | 0.429506E+11 | 0.952708E+10 | 0.115358E+11 | 0.00 | 0.117360E+11 | 0.00 | 0.00 | 0.191325E+11 | 0.00 | 0.00 | 0.00 | 0.195126E+10 | 0.00 |
August | 0.453764E+11 | 0.102233E+11 | 0.123357E+11 | 0.00 | 0.122907E+11 | 0.00 | 0.00 | 0.215562E+11 | 0.00 | 0.00 | 0.00 | 0.199270E+10 | 0.00 |
September | 0.425433E+11 | 0.108018E+11 | 0.114788E+11 | 0.00 | 0.914295E+10 | 0.00 | 0.00 | 0.103591E+11 | 0.00 | 0.00 | 0.00 | 0.193371E+10 | 0.00 |
October | 0.429506E+11 | 0.121533E+11 | 0.115432E+11 | 0.00 | 0.829356E+10 | 0.00 | 0.00 | 0.219710E+10 | 0.00 | 0.00 | 0.00 | 0.203391E+10 | 0.00 |
November | 0.413304E+11 | 0.126294E+11 | 0.110862E+11 | 0.00 | 0.797753E+10 | 0.00 | 0.00 | 0.102708E+09 | 0.00 | 0.00 | 0.00 | 0.202409E+10 | 0.00 |
December | 0.429506E+11 | 0.135150E+11 | 0.115358E+11 | 0.00 | 0.869581E+10 | 0.00 | 0.00 | 12256775.67 | 0.00 | 0.00 | 0.00 | 0.215461E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134167E+12 | 0.139290E+12 | 0.00 | 0.113337E+12 | 0.00 | 0.00 | 0.804970E+11 | 0.00 | 0.00 | 0.00 | 0.245619E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.908681E+10 | 0.105871E+11 | 0.00 | 0.797753E+10 | 0.00 | 0.00 | 610.16 | 0.00 | 0.00 | 0.00 | 0.193371E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.135150E+11 | 0.123431E+11 | 0.00 | 0.122907E+11 | 0.00 | 0.00 | 0.215562E+11 | 0.00 | 0.00 | 0.00 | 0.221278E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.705363E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.468757E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.918548E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209198E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2069372.86 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.166973E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198315E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.133491E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134041E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.705363E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 8632.74 | 05-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 8632.74 | 01-FEB-08:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 8348.72 | 14-MAR-15:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 8348.72 | 03-APR-11:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10654.02 | 18-MAY-14:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10654.02 | 01-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10654.02 | 01-JUL-09:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10654.02 | 01-AUG-09:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10654.02 | 05-SEP-12:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 8348.72 | 02-OCT-11:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 8348.72 | 04-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 8632.74 | 02-DEC-07:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 8348.72 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 10654.02 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.14 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 2119.59 | 28-JAN-12:00 | 0.00 |
February | 2914.63 | 28-FEB-14:50 | 0.00 | 0.00 | 0.00 | 2121.91 | 01-FEB-12:00 | 0.00 |
March | 12020.63 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 1993.09 | 09-MAR-12:00 | 0.00 |
April | 13837.26 | 17-APR-14:00 | 0.00 | 0.00 | 0.00 | 1805.61 | 01-APR-11:09 | 0.00 |
May | 17423.01 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1779.44 | 01-MAY-11:09 | 0.00 |
June | 23935.64 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1753.92 | 01-JUN-11:00 | 0.00 |
July | 25387.39 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1735.43 | 01-JUL-11:09 | 0.00 |
August | 25434.26 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1733.79 | 31-AUG-11:39 | 0.00 |
September | 21879.68 | 07-SEP-15:50 | 0.00 | 0.00 | 0.00 | 1750.76 | 30-SEP-11:50 | 0.00 |
October | 14581.17 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1776.39 | 31-OCT-11:20 | 0.00 |
November | 1758.83 | 02-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1802.98 | 30-NOV-12:20 | 0.00 |
December | 1053.88 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 | 1998.60 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.14 | 0.00 | 0.00 | 0.00 | 1733.79 | 0.00 | ||
Maximum of Months | 25434.26 | 0.00 | 0.00 | 0.00 | 2121.91 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58715.32 | 17-JAN-13:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8632.74 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61190.82 | 28-FEB-15:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 2762.69 | 0.00 |
March | 70433.02 | 30-MAR-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 12020.63 | 0.00 |
April | 71774.47 | 17-APR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 13837.26 | 0.00 |
May | 77956.81 | 30-MAY-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10654.02 | 0.00 | 0.00 | 17282.72 | 0.00 |
June | 82849.97 | 06-JUN-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10654.02 | 0.00 | 0.00 | 22180.54 | 0.00 |
July | 85672.10 | 08-JUL-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10654.02 | 0.00 | 0.00 | 25017.31 | 0.00 |
August | 84361.06 | 02-AUG-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10654.02 | 0.00 | 0.00 | 23710.08 | 0.00 |
September | 81638.59 | 07-SEP-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10654.02 | 0.00 | 0.00 | 20980.76 | 0.00 |
October | 72940.62 | 11-OCT-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 14569.05 | 0.00 |
November | 60087.48 | 02-NOV-14:20 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 1699.45 | 0.00 |
December | 59432.35 | 12-DEC-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 1053.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 58715.32 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8348.72 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85672.10 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10654.02 | 0.00 | 0.00 | 25017.31 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 179637.83 | 07-JAN-18:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 234464.14 | 12-FEB-06:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 19135.95 | 22-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 12711.40 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 828.99 | 11-MAY-06:30 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 11392.70 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 42594.85 | 22-NOV-06:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 72408.34 | 03-DEC-08:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 234464.14 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.50 | 17.65 | 8.67 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
February | 12.83 | 16.90 | 5.83 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
March | 2.00 | 20.31 | 2.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
April | 0.33 | 20.35 | 0.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.89 | 3.50 | 24.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.99 | 7.17 | 24.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.87 | 8.33 | 24.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.66 | 3.33 | 24.66 |
October | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
November | 2.00 | 20.12 | 2.00 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
December | 7.83 | 18.98 | 6.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 40.00 | 17.99 | 26.17 | 18.64 | 23.17 | 20.26 | 22.67 | 21.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 | 0.00 | 17.70 |
Maximum of Months | 14.50 | 20.47 | 8.67 | 20.47 | 8.33 | 24.99 | 8.33 | 24.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.17 | 14.53 | 3.50 | 14.52 | 0.00 | 14.52 | 0.00 | 14.52 |
February | 34.17 | 14.37 | 2.17 | 14.38 | 0.00 | 14.38 | 0.00 | 14.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.32 | 0.00 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.39 | 0.00 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.56 | 0.00 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 27.65 | 0.00 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 27.59 | 0.00 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.41 | 0.00 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
November | 2.50 | 14.89 | 0.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
December | 27.33 | 14.74 | 3.17 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
Annual Sum or Average | 131.17 | 14.54 | 9.33 | 14.53 | 118.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.17 | 14.89 | 3.50 | 14.86 | 35.83 | 27.65 | 0.00 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.30 | 260.00 | 21.19 | 260.00 | 21.15 |
February | 276.00 | 21.84 | 179.00 | 21.54 | 179.00 | 21.41 |
March | 264.33 | 22.75 | 81.17 | 22.57 | 55.33 | 22.37 |
April | 141.17 | 23.17 | 114.00 | 23.41 | 12.50 | 23.36 |
May | 76.00 | 23.61 | 249.00 | 23.83 | 49.67 | 23.83 |
June | 31.83 | 23.90 | 297.67 | 23.90 | 28.33 | 23.91 |
July | 59.00 | 23.99 | 300.00 | 23.93 | 59.00 | 23.94 |
August | 65.67 | 24.03 | 324.00 | 23.94 | 65.67 | 23.95 |
September | 15.50 | 23.94 | 288.50 | 23.91 | 13.50 | 23.91 |
October | 157.17 | 23.18 | 110.33 | 23.44 | 30.00 | 23.46 |
November | 254.17 | 22.65 | 67.17 | 22.46 | 57.33 | 22.30 |
December | 298.33 | 21.85 | 179.83 | 21.61 | 179.83 | 21.50 |
Annual Sum or Average | 1939.17 | 22.45 | 2450.67 | 22.80 | 990.17 | 22.62 |
Minimum of Months | 15.50 | 21.30 | 67.17 | 21.19 | 12.50 | 21.15 |
Maximum of Months | 300.00 | 24.03 | 324.00 | 23.94 | 260.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 17.98 | 270.33 | 17.74 | 270.33 | 17.66 |
February | 253.17 | 19.09 | 200.33 | 18.70 | 188.67 | 18.41 |
March | 195.83 | 21.85 | 177.33 | 22.70 | 75.50 | 22.21 |
April | 132.83 | 24.61 | 232.50 | 25.56 | 83.67 | 25.56 |
May | 228.00 | 26.43 | 293.67 | 26.49 | 215.17 | 26.53 |
June | 283.50 | 26.68 | 308.33 | 26.67 | 283.17 | 26.67 |
July | 297.00 | 26.70 | 300.00 | 26.70 | 297.00 | 26.70 |
August | 321.83 | 26.71 | 324.00 | 26.71 | 321.83 | 26.71 |
September | 241.00 | 26.67 | 296.83 | 26.64 | 240.00 | 26.65 |
October | 167.00 | 24.32 | 203.33 | 25.27 | 90.33 | 25.33 |
November | 195.50 | 21.37 | 168.33 | 21.94 | 95.83 | 21.47 |
December | 292.00 | 19.78 | 226.17 | 19.45 | 221.00 | 19.27 |
Annual Sum or Average | 2907.67 | 23.50 | 3001.17 | 23.85 | 2382.50 | 23.79 |
Minimum of Months | 132.83 | 17.98 | 168.33 | 17.74 | 75.50 | 17.66 |
Maximum of Months | 321.83 | 26.71 | 324.00 | 26.71 | 321.83 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.61 | 300.00 | 11.61 | 300.00 | 11.61 |
February | 276.00 | 13.37 | 274.17 | 13.35 | 274.17 | 13.34 |
March | 322.00 | 18.75 | 245.33 | 18.34 | 245.33 | 18.17 |
April | 201.17 | 21.91 | 157.83 | 22.54 | 84.00 | 22.27 |
May | 218.67 | 26.82 | 269.33 | 26.98 | 185.67 | 27.14 |
June | 299.50 | 29.76 | 312.00 | 29.69 | 299.50 | 29.72 |
July | 300.00 | 30.31 | 300.00 | 30.31 | 300.00 | 30.31 |
August | 324.00 | 30.27 | 324.00 | 30.27 | 324.00 | 30.27 |
September | 260.83 | 28.87 | 300.00 | 28.65 | 260.83 | 28.72 |
October | 221.67 | 22.28 | 183.67 | 22.84 | 121.83 | 22.76 |
November | 288.00 | 18.09 | 231.33 | 17.72 | 231.33 | 17.58 |
December | 300.00 | 13.58 | 300.00 | 13.58 | 300.00 | 13.58 |
Annual Sum or Average | 3311.83 | 22.06 | 3197.67 | 22.21 | 2926.67 | 22.16 |
Minimum of Months | 201.17 | 11.61 | 157.83 | 11.61 | 84.00 | 11.61 |
Maximum of Months | 324.00 | 30.31 | 324.00 | 30.31 | 324.00 | 30.31 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2194.32 | 610.16 | 2.83 | 1883.41 | 310.90 | 0.00 | 0.00 | 31-JAN-13:30 | 0.00 | 01-JAN-00:03 | 0.51 | 20-JAN-14:00 | 0.44 | 31-JAN-13:30 | 0.11 | 20-JAN-14:00 | 0.14 | 20-JAN-14:00 | 0.00 | 01-JAN-00:03 |
February | 0.170015E+09 | 46222692.05 | 22.08 | 0.170015E+09 | 132.73 | 0.00 | 0.31 | 28-FEB-14:50 | 0.00 | 01-FEB-00:10 | 6485.31 | 28-FEB-14:50 | 6485.31 | 28-FEB-14:50 | 0.13 | 22-FEB-16:15 | 1761.10 | 28-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 0.993828E+09 | 0.268825E+09 | 73.67 | 0.839310E+09 | 0.154518E+09 | 0.00 | 0.47 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10251.54 | 30-MAR-16:00 | 9356.81 | 30-MAR-16:00 | 2152.92 | 31-MAR-11:00 | 2839.24 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.312719E+10 | 0.848052E+09 | 146.97 | 0.277391E+10 | 0.353274E+09 | 0.00 | 1.00 | 18-APR-05:03 | 0.00 | 01-APR-00:10 | 24119.20 | 19-APR-05:03 | 16504.61 | 18-APR-05:03 | 8581.10 | 19-APR-05:03 | 5707.56 | 19-APR-05:03 | 0.00 | 01-APR-00:10 |
May | 0.686666E+10 | 0.184783E+10 | 234.63 | 0.549659E+10 | 0.137007E+10 | 0.00 | 1.00 | 04-MAY-05:03 | 0.00 | 01-MAY-00:10 | 27597.87 | 31-MAY-05:01 | 18049.40 | 17-MAY-05:02 | 14313.87 | 26-MAY-05:02 | 6377.53 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.126521E+11 | 0.344480E+10 | 294.25 | 0.966769E+10 | 0.298438E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 29795.40 | 26-JUN-05:01 | 24246.99 | 25-JUN-15:52 | 16539.29 | 23-JUN-05:04 | 7174.96 | 25-JUN-15:52 | 0.00 | 01-JUN-00:10 |
July | 0.140216E+11 | 0.382569E+10 | 303.95 | 0.101802E+11 | 0.384137E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 30347.53 | 27-JUL-05:01 | 21780.95 | 02-JUL-17:03 | 18638.69 | 27-JUL-05:02 | 6998.26 | 02-JUL-17:03 | 0.00 | 01-JUL-00:10 |
August | 0.163152E+11 | 0.439790E+10 | 325.40 | 0.116391E+11 | 0.467611E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:05 | 30865.56 | 24-AUG-05:01 | 21043.76 | 13-AUG-15:15 | 18999.85 | 24-AUG-05:03 | 7056.86 | 13-AUG-13:32 | 0.00 | 01-AUG-00:05 |
September | 0.964752E+10 | 0.255469E+10 | 256.83 | 0.733393E+10 | 0.231359E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 29270.27 | 07-SEP-05:01 | 22178.16 | 16-SEP-05:01 | 15633.76 | 07-SEP-05:03 | 6910.47 | 04-SEP-16:43 | 0.00 | 01-SEP-00:10 |
October | 0.288632E+10 | 0.760842E+09 | 126.76 | 0.217951E+10 | 0.706807E+09 | 0.00 | 1.00 | 02-OCT-05:02 | 0.00 | 01-OCT-00:10 | 29444.84 | 19-OCT-05:01 | 15130.86 | 11-OCT-05:02 | 17936.34 | 19-OCT-05:01 | 6661.51 | 19-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.379583E+09 | 0.102611E+09 | 49.75 | 0.308432E+09 | 71150717.74 | 0.00 | 0.28 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6444.07 | 02-NOV-14:00 | 4962.76 | 02-NOV-14:00 | 2297.83 | 04-NOV-16:00 | 1705.62 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 45197003.50 | 12256775.67 | 7.33 | 35086949.33 | 10110054.16 | 0.00 | 0.18 | 12-DEC-14:40 | 0.00 | 01-DEC-00:10 | 3910.54 | 12-DEC-14:30 | 3075.82 | 12-DEC-15:00 | 993.41 | 12-DEC-14:00 | 1053.88 | 12-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.671051E+11 | 0.181097E+11 | 1844.46 | 0.506237E+11 | 0.164814E+11 | 0.00 | ||||||||||||||
Minimum of Months | 2194.32 | 610.16 | 2.83 | 1883.41 | 132.73 | 0.00 | 0.00 | 0.00 | 0.51 | 0.44 | 0.11 | 0.14 | 0.00 | |||||||
Maximum of Months | 0.163152E+11 | 0.439790E+10 | 325.40 | 0.116391E+11 | 0.467611E+10 | 0.00 | 1.00 | 0.00 | 30865.56 | 24246.99 | 18999.85 | 7174.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 23614111.91 | 7200526.53 | 3.00 | 23614111.91 | 0.00 | 0.00 | 0.06 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4129.13 | 28-FEB-15:00 | 4129.13 | 28-FEB-15:00 | 0.00 | 28-FEB-15:00 | 1261.71 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.102361E+10 | 0.306507E+09 | 33.29 | 0.867779E+09 | 0.155827E+09 | 0.00 | 0.38 | 30-MAR-14:50 | 0.00 | 01-MAR-00:10 | 31051.93 | 30-MAR-14:50 | 28280.10 | 30-MAR-14:50 | 5736.06 | 30-MAR-12:40 | 9362.85 | 30-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 0.664665E+10 | 0.197898E+10 | 116.28 | 0.601459E+10 | 0.632061E+09 | 0.00 | 1.00 | 12-APR-17:12 | 0.00 | 01-APR-00:10 | 101594.52 | 23-APR-13:35 | 88119.79 | 16-APR-14:55 | 37578.33 | 23-APR-13:35 | 25441.80 | 23-APR-13:35 | 0.00 | 01-APR-00:10 |
May | 0.191072E+11 | 0.563663E+10 | 222.51 | 0.154200E+11 | 0.368727E+10 | 0.00 | 1.00 | 07-MAY-17:05 | 0.00 | 01-MAY-00:10 | 104912.53 | 28-MAY-10:45 | 87345.83 | 15-MAY-18:31 | 43518.84 | 28-MAY-10:45 | 26253.28 | 28-MAY-10:45 | 0.00 | 01-MAY-00:10 |
June | 0.426499E+11 | 0.127521E+11 | 364.58 | 0.327299E+11 | 0.991993E+10 | 0.00 | 1.00 | 01-JUN-19:45 | 0.00 | 01-JUN-00:10 | 110641.91 | 18-JUN-09:45 | 86552.47 | 11-JUN-09:35 | 57546.26 | 18-JUN-09:45 | 27152.47 | 25-JUN-16:03 | 0.00 | 01-JUN-00:10 |
July | 0.509799E+11 | 0.153068E+11 | 428.77 | 0.377788E+11 | 0.132011E+11 | 0.00 | 1.00 | 02-JUL-08:65 | 0.00 | 01-JUL-00:10 | 114869.20 | 30-JUL-10:05 | 80449.61 | 03-JUL-17:42 | 65886.02 | 30-JUL-10:05 | 27700.26 | 30-JUL-10:05 | 0.00 | 01-JUL-00:10 |
August | 0.578953E+11 | 0.171583E+11 | 482.60 | 0.418275E+11 | 0.160678E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:10 | 114437.79 | 12-AUG-01:05 | 79911.75 | 25-AUG-17:06 | 68227.57 | 12-AUG-01:05 | 27632.71 | 01-AUG-17:05 | 0.00 | 01-AUG-00:05 |
September | 0.267863E+11 | 0.780444E+10 | 276.17 | 0.200715E+11 | 0.671477E+10 | 0.00 | 1.00 | 01-SEP-19:05 | 0.00 | 01-SEP-00:10 | 112440.91 | 17-SEP-09:35 | 83359.95 | 14-SEP-17:12 | 61015.14 | 17-SEP-09:35 | 27334.61 | 17-SEP-09:35 | 0.00 | 01-SEP-00:10 |
October | 0.496115E+10 | 0.143625E+10 | 84.13 | 0.355660E+10 | 0.140455E+10 | 0.00 | 1.00 | 09-OCT-12:55 | 0.00 | 01-OCT-00:10 | 98221.54 | 09-OCT-12:55 | 85784.55 | 11-OCT-17:12 | 25704.91 | 15-OCT-14:35 | 25528.93 | 09-OCT-12:55 | 0.00 | 01-OCT-00:10 |
November | 323061.52 | 96388.75 | 11.00 | 239262.38 | 83799.13 | 0.00 | 0.00 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 | 178.53 | 02-NOV-14:00 | 129.68 | 02-NOV-14:00 | 48.85 | 02-NOV-14:00 | 53.21 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.210074E+12 | 0.623873E+11 | 2022.33 | 0.158291E+12 | 0.517833E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.578953E+11 | 0.171583E+11 | 482.60 | 0.418275E+11 | 0.160678E+11 | 0.00 | 1.00 | 0.00 | 114869.20 | 88119.79 | 68227.57 | 27700.26 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.00 | 24.27 | 27.74 | 43.67 | 166.36 | 0.00 | 0.00 | 0.00 |
February | 59.25 | 27.70 | 31.55 | 65.14 | 139.69 | 0.00 | 0.00 | 0.00 |
March | 87.06 | 41.97 | 45.09 | 113.98 | 97.03 | 0.00 | 0.00 | 0.00 |
April | 97.90 | 44.67 | 53.23 | 146.31 | 87.30 | 0.00 | 0.00 | 0.00 |
May | 98.69 | 37.39 | 61.29 | 161.78 | 64.64 | 0.00 | 0.00 | 0.00 |
June | 103.91 | 40.10 | 63.81 | 194.66 | 48.28 | 0.00 | 0.00 | 0.00 |
July | 97.71 | 36.17 | 61.54 | 190.07 | 38.04 | 0.00 | 0.00 | 0.00 |
August | 95.74 | 35.74 | 60.01 | 188.70 | 34.58 | 0.00 | 0.00 | 0.00 |
September | 78.26 | 32.65 | 45.61 | 128.81 | 62.99 | 0.00 | 0.00 | 0.00 |
October | 69.33 | 35.88 | 33.45 | 95.62 | 109.51 | 0.00 | 0.00 | 0.00 |
November | 55.26 | 24.66 | 30.60 | 63.44 | 126.78 | 0.00 | 0.00 | 0.00 |
December | 45.98 | 20.21 | 25.78 | 41.45 | 141.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.52 | 33.48 | 45.05 | 119.76 | 92.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.98 | 20.21 | 25.78 | 41.45 | 34.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.91 | 44.67 | 63.81 | 194.66 | 166.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.00 | 24.27 | 27.74 | 43.67 | 166.36 | 0.00 | 0.00 | 0.00 |
February | 59.25 | 27.70 | 31.55 | 65.14 | 139.69 | 0.00 | 0.00 | 0.00 |
March | 87.06 | 41.97 | 45.09 | 113.98 | 97.03 | 0.00 | 0.00 | 0.00 |
April | 97.90 | 44.67 | 53.23 | 146.31 | 87.30 | 0.00 | 0.00 | 0.00 |
May | 98.69 | 37.39 | 61.29 | 161.78 | 64.64 | 0.00 | 0.00 | 0.00 |
June | 103.91 | 40.10 | 63.81 | 194.66 | 48.28 | 0.00 | 0.00 | 0.00 |
July | 97.71 | 36.17 | 61.54 | 190.07 | 38.04 | 0.00 | 0.00 | 0.00 |
August | 95.74 | 35.74 | 60.01 | 188.70 | 34.58 | 0.00 | 0.00 | 0.00 |
September | 78.26 | 32.65 | 45.61 | 128.81 | 62.99 | 0.00 | 0.00 | 0.00 |
October | 69.33 | 35.88 | 33.45 | 95.62 | 109.51 | 0.00 | 0.00 | 0.00 |
November | 55.26 | 24.66 | 30.60 | 63.44 | 126.78 | 0.00 | 0.00 | 0.00 |
December | 45.98 | 20.21 | 25.78 | 41.45 | 141.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.52 | 33.48 | 45.05 | 119.76 | 92.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.98 | 20.21 | 25.78 | 41.45 | 34.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.91 | 44.67 | 63.81 | 194.66 | 166.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.33 | 0.00 | 13.33 | 2.24 | 107.77 | 0.00 | 0.00 | 0.00 |
February | 14.78 | 0.00 | 14.78 | 6.35 | 88.17 | 0.00 | 0.00 | 0.00 |
March | 20.75 | 0.00 | 20.75 | 12.75 | 59.83 | 0.00 | 0.00 | 0.00 |
April | 25.14 | 0.14 | 24.99 | 26.08 | 51.96 | 0.00 | 0.00 | 0.00 |
May | 30.07 | 0.99 | 29.08 | 40.28 | 36.56 | 0.00 | 0.00 | 0.00 |
June | 33.01 | 2.16 | 30.85 | 60.13 | 26.33 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 1.59 | 29.65 | 60.47 | 21.17 | 0.00 | 0.00 | 0.00 |
August | 27.81 | 0.38 | 27.43 | 55.08 | 19.67 | 0.00 | 0.00 | 0.00 |
September | 20.97 | 0.01 | 20.96 | 28.38 | 37.54 | 0.00 | 0.00 | 0.00 |
October | 15.93 | 0.00 | 15.93 | 10.90 | 66.41 | 0.00 | 0.00 | 0.00 |
November | 14.26 | 0.00 | 14.26 | 5.59 | 77.98 | 0.00 | 0.00 | 0.00 |
December | 12.32 | 0.00 | 12.32 | 1.76 | 88.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.67 | 0.44 | 21.23 | 25.95 | 56.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.32 | 0.00 | 12.32 | 1.76 | 19.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.01 | 2.16 | 30.85 | 60.47 | 107.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.33 | 0.00 | 13.33 | 2.24 | 107.77 | 0.00 | 0.00 | 0.00 |
February | 14.78 | 0.00 | 14.78 | 6.35 | 88.17 | 0.00 | 0.00 | 0.00 |
March | 20.75 | 0.00 | 20.75 | 12.75 | 59.83 | 0.00 | 0.00 | 0.00 |
April | 25.14 | 0.14 | 24.99 | 26.08 | 51.96 | 0.00 | 0.00 | 0.00 |
May | 30.07 | 0.99 | 29.08 | 40.28 | 36.56 | 0.00 | 0.00 | 0.00 |
June | 33.01 | 2.16 | 30.85 | 60.13 | 26.33 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 1.59 | 29.65 | 60.47 | 21.17 | 0.00 | 0.00 | 0.00 |
August | 27.81 | 0.38 | 27.43 | 55.08 | 19.66 | 0.00 | 0.00 | 0.00 |
September | 20.97 | 0.01 | 20.96 | 28.38 | 37.54 | 0.00 | 0.00 | 0.00 |
October | 15.93 | 0.00 | 15.93 | 10.90 | 66.41 | 0.00 | 0.00 | 0.00 |
November | 14.26 | 0.00 | 14.26 | 5.59 | 77.98 | 0.00 | 0.00 | 0.00 |
December | 12.32 | 0.00 | 12.32 | 1.76 | 88.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.67 | 0.44 | 21.23 | 25.95 | 56.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.32 | 0.00 | 12.32 | 1.76 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.01 | 2.16 | 30.85 | 60.47 | 107.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.93 | 18.26 | 14.67 | 39.46 | 34.46 | 19.33 | 0.00 | 0.00 |
February | 40.22 | 24.62 | 15.60 | 52.90 | 29.33 | 34.17 | 0.00 | 0.00 |
March | 59.82 | 36.66 | 23.15 | 81.22 | 26.20 | 0.00 | 0.00 | 0.00 |
April | 75.00 | 46.31 | 28.69 | 104.19 | 27.83 | 0.00 | 0.00 | 0.00 |
May | 83.74 | 48.43 | 35.31 | 116.96 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 89.44 | 52.79 | 36.65 | 126.30 | 24.10 | 0.00 | 0.00 | 0.00 |
July | 83.37 | 47.28 | 36.08 | 118.66 | 21.18 | 0.00 | 0.00 | 0.00 |
August | 76.74 | 42.10 | 34.64 | 109.93 | 20.94 | 0.00 | 0.00 | 0.00 |
September | 56.31 | 31.11 | 25.20 | 74.81 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 48.84 | 32.89 | 15.95 | 63.79 | 33.04 | 0.00 | 0.00 | 0.00 |
November | 35.21 | 19.50 | 15.71 | 45.18 | 32.78 | 16.00 | 0.00 | 0.00 |
December | 29.09 | 15.60 | 13.48 | 36.53 | 30.50 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 59.33 | 34.68 | 24.65 | 80.98 | 27.75 | 99.67 | 0.00 | 0.00 |
Minimum of Months | 29.09 | 15.60 | 13.48 | 36.53 | 20.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.44 | 52.79 | 36.65 | 126.30 | 34.46 | 34.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139282E+09 | 64995832.32 | 74286035.75 | 0.116953E+09 | 0.445574E+09 |
February | 0.143332E+09 | 67017261.61 | 76315085.38 | 0.157590E+09 | 0.337945E+09 |
March | 0.233189E+09 | 0.112410E+09 | 0.120779E+09 | 0.305282E+09 | 0.259890E+09 |
April | 0.253755E+09 | 0.115780E+09 | 0.137975E+09 | 0.379246E+09 | 0.226293E+09 |
May | 0.264321E+09 | 0.100157E+09 | 0.164164E+09 | 0.433302E+09 | 0.173135E+09 |
June | 0.269331E+09 | 0.103942E+09 | 0.165388E+09 | 0.504563E+09 | 0.125134E+09 |
July | 0.261715E+09 | 96890229.71 | 0.164825E+09 | 0.509078E+09 | 0.101884E+09 |
August | 0.256441E+09 | 95714505.16 | 0.160726E+09 | 0.505406E+09 | 92621514.82 |
September | 0.202852E+09 | 84641085.97 | 0.118211E+09 | 0.333878E+09 | 0.163272E+09 |
October | 0.185689E+09 | 96101141.77 | 89587858.08 | 0.256108E+09 | 0.293304E+09 |
November | 0.143239E+09 | 63915280.35 | 79323328.85 | 0.164430E+09 | 0.328614E+09 |
December | 0.123160E+09 | 54124271.24 | 69036157.76 | 0.111022E+09 | 0.378953E+09 |
Annual Sum or Average | 0.247631E+10 | 0.105569E+10 | 0.142062E+10 | 0.377686E+10 | 0.292662E+10 |
Minimum of Months | 0.123160E+09 | 54124271.24 | 69036157.76 | 0.111022E+09 | 92621514.82 |
Maximum of Months | 0.269331E+09 | 0.115780E+09 | 0.165388E+09 | 0.509078E+09 | 0.445574E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139282E+09 | 64995832.32 | 74286035.75 | 0.116953E+09 | 0.445574E+09 |
February | 0.143332E+09 | 67017261.61 | 76315085.38 | 0.157590E+09 | 0.337945E+09 |
March | 0.233189E+09 | 0.112410E+09 | 0.120779E+09 | 0.305282E+09 | 0.259890E+09 |
April | 0.253755E+09 | 0.115780E+09 | 0.137975E+09 | 0.379246E+09 | 0.226293E+09 |
May | 0.264321E+09 | 0.100157E+09 | 0.164164E+09 | 0.433302E+09 | 0.173135E+09 |
June | 0.269331E+09 | 0.103942E+09 | 0.165388E+09 | 0.504563E+09 | 0.125134E+09 |
July | 0.261715E+09 | 96890229.71 | 0.164825E+09 | 0.509078E+09 | 0.101884E+09 |
August | 0.256441E+09 | 95714505.16 | 0.160726E+09 | 0.505406E+09 | 92621514.82 |
September | 0.202852E+09 | 84641085.97 | 0.118211E+09 | 0.333878E+09 | 0.163272E+09 |
October | 0.185689E+09 | 96101141.77 | 89587858.08 | 0.256108E+09 | 0.293304E+09 |
November | 0.143239E+09 | 63915280.35 | 79323328.85 | 0.164430E+09 | 0.328614E+09 |
December | 0.123160E+09 | 54124271.24 | 69036157.76 | 0.111022E+09 | 0.378953E+09 |
Annual Sum or Average | 0.247631E+10 | 0.105569E+10 | 0.142062E+10 | 0.377686E+10 | 0.292662E+10 |
Minimum of Months | 0.123160E+09 | 54124271.24 | 69036157.76 | 0.111022E+09 | 92621514.82 |
Maximum of Months | 0.269331E+09 | 0.115780E+09 | 0.165388E+09 | 0.509078E+09 | 0.445574E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35709943.11 | 0.00 | 35709943.11 | 5992542.20 | 0.288664E+09 |
February | 35750577.63 | 0.00 | 35750577.63 | 15361341.66 | 0.213307E+09 |
March | 55585916.74 | 3409.20 | 55582507.54 | 34161162.54 | 0.160260E+09 |
April | 65156731.66 | 370634.04 | 64786097.61 | 67603534.40 | 0.134679E+09 |
May | 80530018.08 | 2648603.54 | 77881414.54 | 0.107888E+09 | 97930325.94 |
June | 85565717.62 | 5605794.37 | 79959923.25 | 0.155850E+09 | 68257005.22 |
July | 83692408.22 | 4264794.13 | 79427614.09 | 0.161961E+09 | 56705092.71 |
August | 74486958.34 | 1005829.66 | 73481128.68 | 0.147530E+09 | 52671307.16 |
September | 54345646.40 | 24891.36 | 54320755.04 | 73555424.13 | 97315961.75 |
October | 42666692.97 | 0.00 | 42666692.97 | 29184730.60 | 0.177869E+09 |
November | 36953352.17 | 0.00 | 36953352.17 | 14501783.56 | 0.202120E+09 |
December | 33011186.24 | 0.00 | 33011186.24 | 4713965.76 | 0.238072E+09 |
Annual Sum or Average | 0.683455E+09 | 13923956.30 | 0.669531E+09 | 0.818304E+09 | 0.178785E+10 |
Minimum of Months | 33011186.24 | 0.00 | 33011186.24 | 4713965.76 | 52671307.16 |
Maximum of Months | 85565717.62 | 5605794.37 | 79959923.25 | 0.161961E+09 | 0.288664E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35708868.51 | 0.00 | 35708868.51 | 5992205.11 | 0.288664E+09 |
February | 35749553.24 | 0.00 | 35749553.24 | 15360711.16 | 0.213307E+09 |
March | 55584318.02 | 3409.04 | 55580908.98 | 34159601.61 | 0.160260E+09 |
April | 65154883.21 | 370616.67 | 64784266.54 | 67601361.03 | 0.134679E+09 |
May | 80527616.12 | 2648479.39 | 77879136.73 | 0.107885E+09 | 97929801.69 |
June | 85563121.63 | 5605531.62 | 79957590.01 | 0.155846E+09 | 68256285.38 |
July | 83689855.20 | 4264594.23 | 79425260.96 | 0.161958E+09 | 56704390.06 |
August | 74484731.65 | 1005782.52 | 73478949.14 | 0.147526E+09 | 52670503.76 |
September | 54344019.90 | 24890.19 | 54319129.71 | 73553351.09 | 97315117.78 |
October | 42665528.53 | 0.00 | 42665528.53 | 29183710.07 | 0.177868E+09 |
November | 36952236.57 | 0.00 | 36952236.57 | 14500988.45 | 0.202119E+09 |
December | 33010182.46 | 0.00 | 33010182.46 | 4713588.56 | 0.238072E+09 |
Annual Sum or Average | 0.683435E+09 | 13923303.66 | 0.669512E+09 | 0.818281E+09 | 0.178784E+10 |
Minimum of Months | 33010182.46 | 0.00 | 33010182.46 | 4713588.56 | 52670503.76 |
Maximum of Months | 85563121.63 | 5605531.62 | 79957590.01 | 0.161958E+09 | 0.288664E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88191789.76 | 48909307.51 | 39282482.25 | 0.105700E+09 | 92296247.59 |
February | 97297145.50 | 59562261.79 | 37734883.71 | 0.127968E+09 | 70951988.00 |
March | 0.160211E+09 | 98197156.20 | 62013927.94 | 0.217538E+09 | 70176788.26 |
April | 0.194410E+09 | 0.120035E+09 | 74374591.48 | 0.270052E+09 | 72130956.48 |
May | 0.224291E+09 | 0.129725E+09 | 94566172.63 | 0.313277E+09 | 64801620.78 |
June | 0.231832E+09 | 0.136828E+09 | 95004358.25 | 0.327360E+09 | 62454310.16 |
July | 0.223286E+09 | 0.126643E+09 | 96642837.42 | 0.317825E+09 | 56725914.77 |
August | 0.205550E+09 | 0.112772E+09 | 92777296.16 | 0.294426E+09 | 56097484.00 |
September | 0.145952E+09 | 80640437.90 | 65312008.64 | 0.193910E+09 | 74212147.50 |
October | 0.130819E+09 | 88099248.87 | 42719934.09 | 0.170848E+09 | 88499658.45 |
November | 91255914.17 | 50544859.70 | 40711054.47 | 0.117100E+09 | 84969947.40 |
December | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 81681534.31 |
Annual Sum or Average | 0.187100E+10 | 0.109375E+10 | 0.777255E+09 | 0.255384E+10 | 0.874999E+09 |
Minimum of Months | 77908308.53 | 41792426.70 | 36115881.82 | 97835253.61 | 56097484.00 |
Maximum of Months | 0.231832E+09 | 0.136828E+09 | 96642837.42 | 0.327360E+09 | 92296247.59 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 77.44 | 533.90 | 130.67 | 48.53 | 82.14 | 0.00 | 0.00 |
February | 133.35 | 446.10 | 148.05 | 55.40 | 92.65 | 0.00 | 0.00 |
March | 248.97 | 309.24 | 215.63 | 83.94 | 131.69 | 0.00 | 0.00 |
April | 341.81 | 275.55 | 246.07 | 89.62 | 156.45 | 0.00 | 0.00 |
May | 403.21 | 201.50 | 257.50 | 76.77 | 180.74 | 0.00 | 0.00 |
June | 508.06 | 147.70 | 273.84 | 84.53 | 189.31 | 0.00 | 0.00 |
July | 499.87 | 117.21 | 257.92 | 75.53 | 182.39 | 0.00 | 0.00 |
August | 487.30 | 108.24 | 247.11 | 72.22 | 174.89 | 0.00 | 0.00 |
September | 313.38 | 200.07 | 198.45 | 65.33 | 133.13 | 0.00 | 0.00 |
October | 209.25 | 348.05 | 170.52 | 71.76 | 98.76 | 0.00 | 0.00 |
November | 133.43 | 404.89 | 139.04 | 49.32 | 89.72 | 0.00 | 0.00 |
December | 78.00 | 452.32 | 116.62 | 40.42 | 76.20 | 0.00 | 0.00 |
Annual Sum or Average | 287.01 | 294.58 | 200.39 | 67.83 | 132.56 | 0.00 | 0.00 |
Minimum of Months | 77.44 | 108.24 | 116.62 | 40.42 | 76.20 | 0.00 | 0.00 |
Maximum of Months | 508.06 | 533.90 | 273.84 | 89.62 | 189.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1290.91 | 2262.63 | 329.27 | 182.61 | 146.66 | 0.00 | 0.00 |
February | 1818.38 | 1839.63 | 402.19 | 246.21 | 155.98 | 0.00 | 0.00 |
March | 2725.20 | 904.62 | 598.16 | 366.63 | 231.53 | 0.00 | 0.00 |
April | 3549.15 | 911.49 | 750.04 | 463.10 | 286.94 | 0.00 | 0.00 |
May | 4070.69 | 815.19 | 837.41 | 484.34 | 353.07 | 0.00 | 0.00 |
June | 5208.83 | 986.38 | 894.41 | 527.88 | 366.53 | 0.00 | 0.00 |
July | 5169.51 | 1069.04 | 833.65 | 472.83 | 360.82 | 0.00 | 0.00 |
August | 4741.10 | 1071.55 | 767.43 | 421.04 | 346.39 | 0.00 | 0.00 |
September | 2929.78 | 1086.40 | 563.09 | 311.11 | 251.98 | 0.00 | 0.00 |
October | 2092.04 | 1106.48 | 488.42 | 328.92 | 159.50 | 0.00 | 0.00 |
November | 1473.91 | 1203.85 | 352.07 | 195.00 | 157.06 | 0.00 | 0.00 |
December | 1228.81 | 1512.36 | 290.88 | 156.04 | 134.84 | 0.00 | 0.00 |
Annual Sum or Average | 3031.87 | 1227.81 | 593.29 | 346.83 | 246.47 | 0.00 | 0.00 |
Minimum of Months | 1228.81 | 815.19 | 290.88 | 156.04 | 134.84 | 0.00 | 0.00 |
Maximum of Months | 5208.83 | 2262.63 | 894.41 | 527.88 | 366.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207416E+09 | 0.143000E+10 | 0.349983E+09 | 0.129992E+09 | 0.219991E+09 | 0.00 | 0.00 |
February | 0.322604E+09 | 0.107920E+10 | 0.358165E+09 | 0.134035E+09 | 0.224130E+09 | 0.00 | 0.00 |
March | 0.666844E+09 | 0.828259E+09 | 0.577548E+09 | 0.224827E+09 | 0.352721E+09 | 0.00 | 0.00 |
April | 0.885984E+09 | 0.714229E+09 | 0.637821E+09 | 0.232301E+09 | 0.405520E+09 | 0.00 | 0.00 |
May | 0.107995E+10 | 0.539700E+09 | 0.689699E+09 | 0.205610E+09 | 0.484089E+09 | 0.00 | 0.00 |
June | 0.131688E+10 | 0.382841E+09 | 0.709790E+09 | 0.219096E+09 | 0.490694E+09 | 0.00 | 0.00 |
July | 0.133884E+10 | 0.313945E+09 | 0.690812E+09 | 0.202310E+09 | 0.488502E+09 | 0.00 | 0.00 |
August | 0.130518E+10 | 0.289901E+09 | 0.661853E+09 | 0.193441E+09 | 0.468412E+09 | 0.00 | 0.00 |
September | 0.812284E+09 | 0.518594E+09 | 0.514394E+09 | 0.169332E+09 | 0.345062E+09 | 0.00 | 0.00 |
October | 0.560455E+09 | 0.932218E+09 | 0.456710E+09 | 0.192202E+09 | 0.264508E+09 | 0.00 | 0.00 |
November | 0.345861E+09 | 0.104947E+10 | 0.360383E+09 | 0.127831E+09 | 0.232552E+09 | 0.00 | 0.00 |
December | 0.208914E+09 | 0.121149E+10 | 0.312342E+09 | 0.108249E+09 | 0.204094E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.905122E+10 | 0.928985E+10 | 0.631950E+10 | 0.213922E+10 | 0.418028E+10 | 0.00 | 0.00 |
Minimum of Months | 0.207416E+09 | 0.289901E+09 | 0.312342E+09 | 0.108249E+09 | 0.204094E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133884E+10 | 0.143000E+10 | 0.709790E+09 | 0.232301E+09 | 0.490694E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345758E+10 | 0.606022E+10 | 0.881918E+09 | 0.489093E+09 | 0.392825E+09 | 0.00 | 0.00 |
February | 0.439903E+10 | 0.445043E+10 | 0.972971E+09 | 0.595623E+09 | 0.377349E+09 | 0.00 | 0.00 |
March | 0.729917E+10 | 0.242293E+10 | 0.160211E+10 | 0.981972E+09 | 0.620139E+09 | 0.00 | 0.00 |
April | 0.919941E+10 | 0.236258E+10 | 0.194410E+10 | 0.120035E+10 | 0.743746E+09 | 0.00 | 0.00 |
May | 0.109029E+11 | 0.218341E+10 | 0.224291E+10 | 0.129725E+10 | 0.945662E+09 | 0.00 | 0.00 |
June | 0.135013E+11 | 0.255671E+10 | 0.231832E+10 | 0.136828E+10 | 0.950044E+09 | 0.00 | 0.00 |
July | 0.138460E+11 | 0.286331E+10 | 0.223286E+10 | 0.126643E+10 | 0.966428E+09 | 0.00 | 0.00 |
August | 0.126986E+11 | 0.287003E+10 | 0.205550E+10 | 0.112772E+10 | 0.927773E+09 | 0.00 | 0.00 |
September | 0.759398E+10 | 0.281594E+10 | 0.145952E+10 | 0.806404E+09 | 0.653120E+09 | 0.00 | 0.00 |
October | 0.560332E+10 | 0.296359E+10 | 0.130819E+10 | 0.880992E+09 | 0.427199E+09 | 0.00 | 0.00 |
November | 0.382038E+10 | 0.312038E+10 | 0.912559E+09 | 0.505449E+09 | 0.407111E+09 | 0.00 | 0.00 |
December | 0.329126E+10 | 0.405071E+10 | 0.779083E+09 | 0.417924E+09 | 0.361159E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.956129E+11 | 0.387202E+11 | 0.187100E+11 | 0.109375E+11 | 0.777255E+10 | 0.00 | 0.00 |
Minimum of Months | 0.329126E+10 | 0.218341E+10 | 0.779083E+09 | 0.417924E+09 | 0.361159E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138460E+11 | 0.606022E+10 | 0.231832E+10 | 0.136828E+10 | 0.966428E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.895079E+09 | -808229825.1 | 0.00 | 0.00 | 744.00 | 0.00 | -86848691.4 | 59.00 | 0.00 | 0.00 |
February | 0.819974E+09 | -744041481.0 | 0.00 | 0.00 | 672.00 | 0.00 | -75932223.4 | 59.00 | 0.00 | 0.00 |
March | 0.918950E+09 | -840254921.2 | 0.00 | 0.00 | 744.00 | 0.00 | -78694747.8 | 58.99 | 0.00 | 0.00 |
April | 0.803421E+09 | -730846325.1 | 0.00 | 0.00 | 720.00 | 0.00 | -72574466.8 | 59.00 | 0.00 | 0.00 |
May | 0.771512E+09 | -699074974.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72437043.4 | 58.99 | 0.00 | 0.00 |
June | 0.709345E+09 | -641063771.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68281659.6 | 58.99 | 0.00 | 0.00 |
July | 0.657199E+09 | -587550203.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69648462.1 | 58.99 | 0.00 | 0.00 |
August | 0.698662E+09 | -628946642.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69714949.0 | 58.99 | 0.00 | 0.00 |
September | 0.681810E+09 | -613271769.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68538390.9 | 58.99 | 0.00 | 0.00 |
October | 0.740113E+09 | -665283266.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74829897.2 | 58.99 | 0.00 | 0.00 |
November | 0.772275E+09 | -695376022.7 | 0.00 | 0.00 | 720.00 | 0.00 | -76899253.5 | 58.99 | 0.00 | 0.00 |
December | 0.860639E+09 | -775893639.4 | 0.00 | 0.00 | 744.00 | 0.00 | -84745805.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.932898E+10 | -0.842983E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -899145590.9 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.657199E+09 | -840254921.2 | 0.00 | 0.00 | 672.00 | 0.00 | -86848691.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.918950E+09 | -587550203.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68281659.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.584845E+10 | 30356.64 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.379067E+10 | 30356.64 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622301E+09 | 30356.64 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141181E+09 | 30356.64 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1329509.25 | 991.54 | 11-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111338E+09 | 29902.63 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874775E+09 | 30356.64 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258754E+10 | 30356.64 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.584845E+10 | 30356.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148438E+11 | 114697.48 | 05-JAN-02:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.895800E+10 | 114697.48 | 03-FEB-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468025E+09 | 55625.09 | 22-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528502E+10 | 113017.77 | 26-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148438E+11 | 114697.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323253E+11 | 92788.99 | 07-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227212E+11 | 120633.47 | 12-FEB-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142025E+10 | 22979.20 | 03-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323253E+11 | 120633.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2194.32 | 1883.41 | 0.51 | 20-JAN-14:00 | 0.40 | 0.00 |
February | 0.00 | 0.00 | 0.170015E+09 | 0.170015E+09 | 6485.31 | 28-FEB-14:50 | 6485.31 | 0.00 |
March | 0.00 | 0.00 | 0.993828E+09 | 0.839310E+09 | 10251.54 | 30-MAR-16:00 | 9356.81 | 0.00 |
April | 0.00 | 0.00 | 0.312719E+10 | 0.277391E+10 | 24119.20 | 19-APR-05:03 | 15538.10 | 0.00 |
May | 0.00 | 0.00 | 0.686666E+10 | 0.549659E+10 | 27597.87 | 31-MAY-05:01 | 13612.48 | 0.00 |
June | 0.00 | 0.00 | 0.126521E+11 | 0.966769E+10 | 29795.40 | 26-JUN-05:01 | 14246.87 | 0.00 |
July | 0.00 | 0.00 | 0.140216E+11 | 0.101802E+11 | 30347.53 | 27-JUL-05:01 | 11709.57 | 0.00 |
August | 0.00 | 0.00 | 0.163152E+11 | 0.116391E+11 | 30865.56 | 24-AUG-05:01 | 11894.63 | 0.00 |
September | 0.00 | 0.00 | 0.964752E+10 | 0.733393E+10 | 29270.27 | 07-SEP-05:01 | 13739.13 | 0.00 |
October | 0.00 | 0.00 | 0.288632E+10 | 0.217951E+10 | 29444.84 | 19-OCT-05:01 | 11508.50 | 0.00 |
November | 0.00 | 0.00 | 0.379583E+09 | 0.308432E+09 | 6444.07 | 02-NOV-14:00 | 4962.76 | 0.00 |
December | 0.00 | 0.00 | 45197003.50 | 35086949.33 | 3910.54 | 12-DEC-14:30 | 3025.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.671051E+11 | 0.506237E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2194.32 | 1883.41 | 0.51 | 0.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.163152E+11 | 0.116391E+11 | 30865.56 | 15538.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23614111.91 | 23614111.91 | 4129.13 | 28-FEB-15:00 | 4129.13 | 0.00 |
March | 0.00 | 0.00 | 0.102361E+10 | 0.867779E+09 | 31051.93 | 30-MAR-14:50 | 28280.10 | 0.00 |
April | 0.00 | 0.00 | 0.664665E+10 | 0.601459E+10 | 101594.52 | 23-APR-13:35 | 64016.19 | 0.00 |
May | 0.00 | 0.00 | 0.191072E+11 | 0.154200E+11 | 104912.53 | 28-MAY-10:45 | 61393.70 | 0.00 |
June | 0.00 | 0.00 | 0.426499E+11 | 0.327299E+11 | 110641.91 | 18-JUN-09:45 | 53095.65 | 0.00 |
July | 0.00 | 0.00 | 0.509799E+11 | 0.377788E+11 | 114869.20 | 30-JUL-10:05 | 48983.18 | 0.00 |
August | 0.00 | 0.00 | 0.578953E+11 | 0.418275E+11 | 114437.79 | 12-AUG-01:05 | 46210.22 | 0.00 |
September | 0.00 | 0.00 | 0.267863E+11 | 0.200715E+11 | 112440.91 | 17-SEP-09:35 | 51425.77 | 0.00 |
October | 0.00 | 0.00 | 0.496115E+10 | 0.355660E+10 | 98221.54 | 09-OCT-12:55 | 72570.01 | 0.00 |
November | 0.00 | 0.00 | 323061.52 | 239262.38 | 178.53 | 02-NOV-14:00 | 129.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210074E+12 | 0.158291E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.578953E+11 | 0.418275E+11 | 114869.20 | 72570.01 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.313724E+09 | 0.03 | 284.02 | 04-JAN-21:10 | 0.08 |
February | 0.196404E+09 | 0.02 | 284.02 | 01-FEB-06:50 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 41540496.43 | 0.00 | 284.02 | 02-DEC-07:30 | 0.08 |
Annual Sum or Average | 0.551668E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313724E+09 | 0.03 | 284.02 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146482E+10 | 0.52 | 1397.08 | 02-JAN-17:10 | 0.97 |
February | 0.133198E+10 | 0.48 | 1397.08 | 01-FEB-08:70 | 0.97 |
March | 0.150302E+10 | 0.40 | 1397.08 | 04-MAR-17:50 | 0.96 |
April | 0.138538E+10 | 0.37 | 1397.08 | 25-APR-16:20 | 0.97 |
May | 0.145123E+10 | 0.38 | 1397.08 | 02-MAY-17:00 | 0.96 |
June | 0.147206E+10 | 0.41 | 1397.08 | 02-JUN-06:30 | 0.96 |
July | 0.143245E+10 | 0.40 | 1397.08 | 28-JUL-12:00 | 0.95 |
August | 0.154977E+10 | 0.42 | 1397.08 | 01-AUG-05:01 | 0.95 |
September | 0.141243E+10 | 0.38 | 1397.08 | 01-SEP-08:20 | 0.96 |
October | 0.138834E+10 | 0.36 | 1397.08 | 02-OCT-06:10 | 0.95 |
November | 0.133855E+10 | 0.37 | 1397.08 | 01-NOV-13:00 | 0.96 |
December | 0.142187E+10 | 0.41 | 1397.08 | 02-DEC-12:00 | 0.97 |
Annual Sum or Average | 0.171519E+11 | 0.41 | |||
Minimum of Months | 0.133198E+10 | 0.36 | 1397.08 | 0.95 | |
Maximum of Months | 0.154977E+10 | 0.52 | 1397.08 | 0.97 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.779948E+10 | 1.16 | 6951.64 | 02-JAN-07:20 | 1.62 |
February | 0.688506E+10 | 0.94 | 6951.64 | 01-FEB-08:50 | 1.63 |
March | 0.743367E+10 | 0.65 | 6951.64 | 14-MAR-15:30 | 1.61 |
April | 0.692413E+10 | 0.63 | 6951.64 | 03-APR-11:50 | 1.60 |
May | 0.733311E+10 | 0.70 | 6951.64 | 01-MAY-14:40 | 1.60 |
June | 0.779145E+10 | 0.91 | 6951.64 | 01-JUN-08:20 | 1.60 |
July | 0.789052E+10 | 1.03 | 6951.64 | 01-JUL-07:55 | 1.59 |
August | 0.843863E+10 | 1.12 | 6951.64 | 01-AUG-08:70 | 1.60 |
September | 0.721216E+10 | 0.79 | 6951.64 | 01-SEP-12:02 | 1.60 |
October | 0.690522E+10 | 0.61 | 6951.64 | 02-OCT-11:50 | 1.60 |
November | 0.663898E+10 | 0.63 | 6951.64 | 04-NOV-17:00 | 1.60 |
December | 0.723240E+10 | 0.89 | 6951.64 | 02-DEC-07:50 | 1.63 |
Annual Sum or Average | 0.884848E+11 | 0.84 | |||
Minimum of Months | 0.663898E+10 | 0.61 | 6951.64 | 1.59 | |
Maximum of Months | 0.843863E+10 | 1.16 | 6951.64 | 1.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.146482E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137820E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177185E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223344E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.329906E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.491685E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.525814E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.594766E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.396711E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.214918E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144116E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.143412E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.352616E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137820E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.594766E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.779948E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.689226E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.774018E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.890312E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129697E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.205436E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.231973E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.255969E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150166E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.834147E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.663908E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.723240E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150872E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.663908E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.255969E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146482E+10 | 2194.32 | 0.584845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133198E+10 | 0.170015E+09 | 0.379067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150302E+10 | 0.993828E+09 | 0.622301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138538E+10 | 0.312719E+10 | 0.141181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145123E+10 | 0.686666E+10 | 1329509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147206E+10 | 0.126521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143245E+10 | 0.140216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154977E+10 | 0.163152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141243E+10 | 0.964752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138834E+10 | 0.288632E+10 | 0.111338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133855E+10 | 0.379583E+09 | 0.874775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142187E+10 | 45197003.50 | 0.258754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171519E+11 | 0.671051E+11 | 0.139776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133198E+10 | 2194.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154977E+10 | 0.163152E+11 | 0.584845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.779948E+10 | 0.00 | 0.148438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688506E+10 | 23614111.91 | 0.895800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743367E+10 | 0.102361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692413E+10 | 0.664665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.733311E+10 | 0.191072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.779145E+10 | 0.426499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.789052E+10 | 0.509799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.843863E+10 | 0.578953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.721216E+10 | 0.267863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690522E+10 | 0.496115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663898E+10 | 323061.52 | 0.468025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723240E+10 | 0.00 | 0.528502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884848E+11 | 0.210074E+12 | 0.295548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.663898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.843863E+10 | 0.578953E+11 | 0.148438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146482E+10 | 0.00 | 0.00 | 0.00 | 610.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133198E+10 | 0.00 | 0.00 | 0.00 | 46222692.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150302E+10 | 0.00 | 0.00 | 0.00 | 0.268825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138538E+10 | 0.00 | 0.00 | 0.00 | 0.848052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145123E+10 | 0.00 | 0.00 | 0.00 | 0.184783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147206E+10 | 0.00 | 0.00 | 0.00 | 0.344480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143245E+10 | 0.00 | 0.00 | 0.00 | 0.382569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154977E+10 | 0.00 | 0.00 | 0.00 | 0.439790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141243E+10 | 0.00 | 0.00 | 0.00 | 0.255469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138834E+10 | 0.00 | 0.00 | 0.00 | 0.760842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133855E+10 | 0.00 | 0.00 | 0.00 | 0.102611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142187E+10 | 0.00 | 0.00 | 0.00 | 12256775.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171519E+11 | 0.00 | 0.00 | 0.00 | 0.181097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133198E+10 | 0.00 | 0.00 | 0.00 | 610.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154977E+10 | 0.00 | 0.00 | 0.00 | 0.439790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.779948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688506E+10 | 0.00 | 0.00 | 0.00 | 7200526.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743367E+10 | 0.00 | 0.00 | 0.00 | 0.306507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692413E+10 | 0.00 | 0.00 | 0.00 | 0.197898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.733311E+10 | 0.00 | 0.00 | 0.00 | 0.563663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.779145E+10 | 0.00 | 0.00 | 0.00 | 0.127521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.789052E+10 | 0.00 | 0.00 | 0.00 | 0.153068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.843863E+10 | 0.00 | 0.00 | 0.00 | 0.171583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.721216E+10 | 0.00 | 0.00 | 0.00 | 0.780444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690522E+10 | 0.00 | 0.00 | 0.00 | 0.143625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663898E+10 | 0.00 | 0.00 | 0.00 | 96388.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884848E+11 | 0.00 | 0.00 | 0.00 | 0.623873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.663898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.843863E+10 | 0.00 | 0.00 | 0.00 | 0.171583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335005E+09 | 0.00 | 0.00 | 22775.49 | 0.00 | 0.154056E+10 | 70163836.43 | 0.00 | 0.13 |
February | 0.322985E+09 | 225549.71 | 0.00 | 427690.87 | 0.00 | 0.952794E+09 | 0.391151E+09 | 0.00 | 0.23 |
March | 0.535113E+09 | 18025152.69 | 0.00 | 1906892.59 | 0.00 | 0.101135E+09 | 0.163568E+10 | 0.00 | 0.43 |
April | 0.140903E+09 | 67526008.81 | 0.00 | 2868023.27 | 0.00 | 9460445.25 | 0.187505E+10 | 0.00 | 0.51 |
May | 24394494.79 | 0.407220E+09 | 0.00 | 4002341.33 | 0.00 | 0.00 | 0.148166E+10 | 0.00 | 0.53 |
June | 2105908.77 | 0.131903E+10 | 0.00 | 6161732.79 | 0.00 | 0.00 | 0.390009E+09 | 0.00 | 0.27 |
July | 91818.16 | 0.171398E+10 | 0.00 | 7168668.71 | 0.00 | 0.00 | 0.230939E+09 | 0.00 | 0.20 |
August | 0.00 | 0.202699E+10 | 0.00 | 6618977.97 | 0.00 | 0.00 | 40765596.04 | 0.00 | 0.15 |
September | 15971672.99 | 0.850339E+09 | 0.00 | 6214624.96 | 0.00 | 0.00 | 0.956586E+09 | 0.00 | 0.37 |
October | 0.237997E+09 | 0.168465E+09 | 0.00 | 3767225.63 | 0.00 | 12475331.75 | 0.233666E+10 | 0.00 | 0.52 |
November | 0.517766E+09 | 0.00 | 0.00 | 1899690.43 | 0.00 | 0.175912E+09 | 0.167913E+10 | 0.00 | 0.43 |
December | 0.678407E+09 | 0.00 | 0.00 | 271336.28 | 0.00 | 0.647768E+09 | 0.316477E+09 | 0.00 | 0.18 |
Annual Sum or Average | 0.281074E+10 | 0.657180E+10 | 0.00 | 41329980.31 | 0.00 | 0.344011E+10 | 0.114043E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22775.49 | 0.00 | 0.00 | 40765596.04 | 0.00 | 0.13 |
Maximum of Months | 0.678407E+09 | 0.202699E+10 | 0.00 | 7168668.71 | 0.00 | 0.154056E+10 | 0.233666E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.519591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984654E+09 | 0.00 | 0.00 | 0.17 |
February | 0.424751E+10 | 0.00 | 0.00 | 40121.66 | 0.00 | 0.469751E+09 | 0.144292E+09 | 0.00 | 0.20 |
March | 0.438799E+10 | 9156884.34 | 0.00 | 1464285.37 | 0.00 | 0.00 | 0.212722E+10 | 0.00 | 0.33 |
April | 0.183225E+10 | 23690325.39 | 0.00 | 8094804.39 | 0.00 | 0.00 | 0.517441E+10 | 0.00 | 0.61 |
May | 0.436706E+09 | 0.912455E+09 | 0.00 | 9144845.10 | 0.00 | 0.00 | 0.618758E+10 | 0.00 | 0.59 |
June | 72082085.25 | 0.386880E+10 | 0.00 | 7900073.61 | 0.00 | 0.00 | 0.282269E+10 | 0.00 | 0.48 |
July | 11498571.22 | 0.539950E+10 | 0.00 | 4122843.21 | 0.00 | 0.00 | 0.220320E+10 | 0.00 | 0.35 |
August | 1725421.74 | 0.653247E+10 | 0.00 | 2943646.59 | 0.00 | 0.00 | 0.120098E+10 | 0.00 | 0.32 |
September | 0.224187E+09 | 0.208130E+10 | 0.00 | 10797022.30 | 0.00 | 0.00 | 0.475831E+10 | 0.00 | 0.58 |
October | 0.249652E+10 | 0.289733E+09 | 0.00 | 6078269.47 | 0.00 | 0.00 | 0.581181E+10 | 0.00 | 0.48 |
November | 0.435535E+10 | 0.00 | 0.00 | 524132.80 | 0.00 | 29529699.10 | 0.139884E+10 | 0.00 | 0.24 |
December | 0.478406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193105E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.280458E+11 | 0.191171E+11 | 0.00 | 51110044.50 | 0.00 | 0.167704E+10 | 0.318293E+11 | 0.00 | 0.38 |
Minimum of Months | 1725421.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.519591E+10 | 0.653247E+10 | 0.00 | 10797022.30 | 0.00 | 0.984654E+09 | 0.618758E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.518240E+12 | 0.800900E+11 | 0.00 | 0.812632E+10 | 0.175148E+11 |
February | 0.544238E+12 | 0.626816E+11 | 0.00 | 0.653170E+10 | 0.116529E+11 |
March | 0.874340E+12 | 0.507783E+11 | 0.00 | 0.876359E+10 | 0.288901E+10 |
April | 0.102883E+13 | 0.437524E+11 | 0.00 | 0.896337E+10 | 0.126689E+11 |
May | 0.116803E+13 | 0.382824E+11 | 0.00 | 0.688236E+10 | 0.334591E+11 |
June | 0.117248E+13 | 0.360807E+11 | 0.00 | -0.186709E+10 | 0.714989E+11 |
July | 0.113349E+13 | 0.416307E+11 | 0.00 | -0.463702E+10 | 0.841339E+11 |
August | 0.105114E+13 | 0.380727E+11 | 0.00 | -0.729392E+10 | 0.957666E+11 |
September | 0.786097E+12 | 0.377339E+11 | 0.00 | 0.305665E+10 | 0.467929E+11 |
October | 0.714660E+12 | 0.570642E+11 | 0.00 | 0.104614E+11 | 0.101002E+11 |
November | 0.484679E+12 | 0.521702E+11 | 0.00 | 0.817056E+10 | 0.112296E+10 |
December | 0.425891E+12 | 0.612637E+11 | 0.00 | 0.662009E+10 | 0.411370E+10 |
Annual Sum or Average | 0.990212E+13 | 0.599601E+12 | 0.00 | 0.537780E+11 | 0.391714E+12 |
Minimum of Months | 0.425891E+12 | 0.360807E+11 | 0.00 | -0.729392E+10 | 0.112296E+10 |
Maximum of Months | 0.117248E+13 | 0.800900E+11 | 0.00 | 0.104614E+11 | 0.957666E+11 |