Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 10:43:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1390.53 | 287.59 | 287.59 |
Net Site Energy | 1390.53 | 287.59 | 287.59 |
Total Source Energy | 2747.20 | 568.17 | 568.17 |
Net Source Energy | 2747.20 | 568.17 | 568.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 795.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 246.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 595.23 | 795.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 795.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 246.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 109.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 795.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 246.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 109.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 59.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 73.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.58 | 164.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 123.11 | 164.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 73.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.58 | 164.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 123.11 | 164.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 595.232 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 595.232 | 100.00 |
Total On-Site and Utility Electric Sources | 595.232 | 100.00 |
Total Electricity End Uses | 595.232 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 35.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3077.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 96.62 |
Skylight-Roof Ratio [%] | 2.10 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.6485 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 12.8090 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.4896 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.6485 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 12.8090 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.4896 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.7537 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JAN-16:00 | 06-FEB-17:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 293574.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1623.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 51157.39 | 293574.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 293574.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1623.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 862.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 781.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 347.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1885.10 | 862.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 178.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 161.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 389.88 | 178.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 178.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 161.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 389.88 | 178.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.08 |
ZONE2 FINE STORAGE DIRECT AIR | 2.87 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.88 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.88 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 154629.94 |
PSZ-OFFICE HEATING COIL | 28587.43 |
PSZ-FINE STORAGE HEATING COIL | 98759.28 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 154629.95 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.000000 | 1.08 |
PSZ-FINE STORAGE | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 1.00 | 1.00 | 2.87 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.08 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.87 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.08 | 1192.61 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.87 | 3072.17 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 1.08 | 19895.42 | 28587.43 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.87 | 2.87 | 2.87 | 2.87 | 66486.81 | 98759.28 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.08 | 0.538592 | 1.08 | 19895.42 | 10206.53 | 19895.42 | 0.800510 | 0.800510 |
PSZ-FINE STORAGE COOLING COIL | 2.87 | 1.44 | 2.87 | 66486.81 | 33019.87 | 66486.81 | 0.722810 | 0.722810 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 121 | 97 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 25.27 | 11 | 23 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 71.35 | 6 | 68 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.649 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.722 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 12.809 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.809 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.490 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.048 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2048.656 | 8.649 | 160.695 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2048.656 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 17848.242 | 12.809 | 594.941 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17848.242 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 17593.267 | 5.490 | 254.975 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17593.267 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3818_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3818_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 17 | 0 |
2 | ZONE3 BULK STORAGE | 48 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4525E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9448E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2749E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2430E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2340E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1183E-003 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5725E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2024E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6649E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.9348E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2192E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3997E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4399E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4763E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7630E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3734E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6742E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5386E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7239E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7891E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0434E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9942E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2192E-003 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2547E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2662E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0607E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0391E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0812E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9181E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0232E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8630E-004 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2390E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2032E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2212E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0713E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3735E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7728E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0831E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2190E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.7788E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7929E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4667E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7655E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5693E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9717E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5574E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4614E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5876E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7271E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8070E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1000E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0242E-004 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9333E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9264E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8040E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6552E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7991E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2712E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1633E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3735E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8476E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0124E-004 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7107E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9791E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3456E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1077E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1926E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3924E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5590E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3657E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3923E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9374E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1643E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.1116E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6071E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1134E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1658E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6391E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4880E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3401E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9147E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5159E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8525E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6308E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5536E-003 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2293E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0518E-003 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7636E-005 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7189E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0991E-004 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8253E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1528E-004 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3043E-003 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7554E-005 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3049E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9336E-005 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6983E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2073E-005 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1940E-004 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4744E-005 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.4775E-004 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8050E-005 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9122E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6407E-005 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3358E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4999E-003 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7409E-004 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8355E-003 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1281E-004 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8006E-004 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2547E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9447E-004 |
113 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5891E-004 |
114 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6217E-003 |
115 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3788E-004 |
116 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0354E-003 |
117 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3413E-004 |
118 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3552E-003 |
119 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7668E-004 |
120 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
121 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0604E-004 |
122 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6372E-003 |
123 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7903E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5785E-003 |
125 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5803E-005 |
126 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8149E-003 |
127 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0951E-004 |
128 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8074E-003 |
129 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0274E-004 |
130 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0446E-003 |
131 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5408E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5628E-004 |
133 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3630E-005 |
134 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6386E-003 |
135 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0605E-004 |
136 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9054E-003 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5344E-005 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1875E-005 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8116E-005 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7778E-005 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5771E-005 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1857E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6185E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6959E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7897E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4832E-005 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4745E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5496E-005 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8734E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3970E-005 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1584E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7968E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1268E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7782E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0256E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7519E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2466E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9994E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4307E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1795E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8530E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3663E-004 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2692E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7101E-004 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9449E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5646E-004 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2821E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8769E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0675E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8045E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1002E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8015E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0010E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4187E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6655E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8382E-005 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5874E-005 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8619E-005 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5695E-005 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8490E-005 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6729E-005 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0795E-005 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4335E-005 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1799E-005 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4338E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8303E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3450E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2031E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2316E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8361E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2799E-005 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6059E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5344E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2354E-003 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5365E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5011E-003 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6585E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1020E-004 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0480E-004 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5884E-004 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1127E-004 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0559E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9566E-004 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5603E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0246E-004 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2971E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2530E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5333E-004 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5917E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0928E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1509E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1098E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9091E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0773E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2517E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1866E-005 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7467E-005 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8803E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6848E-005 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8600E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9053E-005 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1044E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5878E-005 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1998E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5600E-003 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2544E-004 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7700E-003 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2195E-004 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5140E-003 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4236E-004 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8906E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8192E-005 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1398E-003 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8755E-004 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2301E-003 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2070E-004 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3163E-003 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7012E-004 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8993E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7853E-004 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8345E-005 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8880E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7239E-005 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8611E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0772E-005 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1178E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7501E-005 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2167E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0635E-004 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2022E-003 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9615E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5462E-003 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6726E-004 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0114E-003 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8998E-004 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0464E-003 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8171E-005 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8832E-005 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6697E-005 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8515E-005 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1023E-005 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1153E-005 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8593E-005 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2267E-005 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6045E-003 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2588E-004 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5820E-003 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1673E-004 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3225E-003 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5696E-004 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4290E-003 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2387E-004 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3631E-003 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0335E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2948E-003 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7129E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0697E-003 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1062E-004 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4336E-003 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8358E-004 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2927E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3840E-003 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0518E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3793E-003 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2644E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3624E-003 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9973E-004 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9789E-003 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6969E-005 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8664E-005 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5359E-005 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8328E-005 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9548E-005 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0967E-005 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8581E-005 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2266E-005 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9825E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2299E-003 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7000E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0476E-003 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5501E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7318E-003 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9808E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9042E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9528E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0925E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6782E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8263E-005 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3298E-003 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3315E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2353E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5785E-004 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1415E-004 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2454E-004 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5815E-004 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2170E-003 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2393E-004 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3967E-003 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7649E-004 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4087E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5886E-004 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1889E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6913E-004 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4453E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9610E-004 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8769E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0145E-003 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8061E-004 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2720E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0658E-004 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8960E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0316E-004 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6607E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6870E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7146E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6869E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4029E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4245E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0023E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0093E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1277E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1563E-005 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5833E-005 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5116E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8407E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3596E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8076E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7027E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0667E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7470E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2165E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3205E-005 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8332E-004 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9875E-005 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4801E-004 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1392E-005 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5332E-004 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0361E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5245E-004 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6672E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2230E-004 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3520E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0289E-004 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3749E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1261E-004 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2022E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5076E-004 |
369 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3094E-005 |
370 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8099E-005 |
371 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1805E-005 |
372 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7796E-005 |
373 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4467E-005 |
374 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0322E-005 |
375 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5844E-005 |
376 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1994E-005 |
377 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7685E-004 |
378 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6356E-005 |
379 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0673E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7133E-005 |
381 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2900E-004 |
382 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3869E-005 |
383 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6786E-004 |
384 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7579E-005 |
385 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6402E-004 |
386 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6966E-005 |
387 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3403E-004 |
388 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0565E-005 |
389 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4297E-004 |
390 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5683E-005 |
391 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2010E-004 |
392 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1431E-005 |
393 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0610E-004 |
394 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5333E-005 |
395 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-004 |
396 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4599E-005 |
397 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9039E-004 |
398 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
399 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0471E-004 |
400 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9420E-005 |
401 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6828E-004 |
402 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7136E-005 |
403 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4902E-004 |
404 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4633E-005 |
405 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7837E-004 |
406 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1672E-005 |
407 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9913E-004 |
408 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5683E-005 |
409 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4012E-004 |
410 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0875E-005 |
411 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2035E-004 |
412 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8312E-005 |
413 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5993E-004 |
414 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3009E-005 |
415 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8742E-004 |
416 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2973E-005 |
417 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1061E-005 |
418 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6967E-005 |
419 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9151E-005 |
420 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4883E-005 |
421 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6833E-005 |
422 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7833E-005 |
423 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0353E-004 |
424 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9347E-005 |
425 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4048E-005 |
426 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3669E-005 |
427 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7530E-005 |
428 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2118E-005 |
429 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7673E-005 |
430 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4169E-005 |
431 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6160E-005 |
432 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6261E-005 |
433 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6400E-004 |
434 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7365E-005 |
435 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6501E-004 |
436 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5650E-005 |
437 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1072E-004 |
438 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0733E-005 |
439 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8970E-004 |
440 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3044E-005 |
441 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4283E-004 |
442 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1967E-005 |
443 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5595E-004 |
444 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2007E-005 |
445 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1168E-004 |
446 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1642E-005 |
447 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6630E-005 |
448 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6314E-005 |
449 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1007E-004 |
450 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4651E-005 |
451 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8412E-004 |
452 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1873E-005 |
453 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9060E-004 |
454 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8489E-005 |
455 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9748E-004 |
456 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5651E-005 |
457 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0083E-005 |
458 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2856E-005 |
459 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5160E-005 |
460 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2025E-005 |
461 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1541E-005 |
462 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5182E-005 |
463 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6324E-005 |
464 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4806E-005 |
465 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4979E-005 |
466 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0434E-005 |
467 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1202E-005 |
468 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9677E-005 |
469 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4951E-005 |
470 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2217E-005 |
471 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7525E-005 |
472 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3673E-005 |
473 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4314E-005 |
474 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2615E-005 |
475 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3915E-005 |
476 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2179E-005 |
477 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4905E-005 |
478 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4491E-005 |
479 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7712E-005 |
480 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3688E-005 |
481 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5590E-005 |
482 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1908E-005 |
483 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6632E-005 |
484 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1701E-005 |
485 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2171E-005 |
486 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3483E-005 |
487 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0328E-005 |
488 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2974E-005 |
489 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4016E-005 |
490 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1425E-005 |
491 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9024E-005 |
492 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0564E-005 |
493 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7573E-005 |
494 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3413E-005 |
495 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7666E-005 |
496 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4362E-005 |
497 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3563E-005 |
498 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2294E-005 |
499 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7927E-005 |
500 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1399E-005 |
501 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2689E-005 |
502 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4522E-005 |
503 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6218E-005 |
504 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4801E-005 |
505 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0258E-005 |
506 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2969E-005 |
507 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7488E-005 |
508 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2304E-005 |
509 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7454E-005 |
510 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5152E-005 |
511 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7883E-005 |
512 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4374E-005 |
513 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8146E-005 |
514 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9484E-005 |
515 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5555E-005 |
516 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8862E-005 |
517 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7296E-005 |
518 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1197E-005 |
519 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0211E-005 |
520 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2960E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10635.73649 | 12762.88379 | 0.89765 | 1.07718 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 29.37000 | 1.33653E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11159.46164 | 13391.35397 | 0.32133 | 0.38559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36362.54071 | 43635.04885 | 2.39255 | 2.87106 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38542.05720 | 46250.46864 | 0.93465 | 1.12158 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -16.30000 | 9.24091E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 128858.28952 | 154629.94742 | 3.22920 | 3.87504 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15784.67 | 1.07718 | 1.07718 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 13126.52 | 0.38559 | 0.38559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 51578.51 | 2.87106 | 2.87106 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 48304.04 | 1.12158 | 1.12158 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07718 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.87106 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.87504 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.87504 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 154629.94078 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 154629.94742 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07718 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07718 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07718 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07718 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07718 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.07718 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87106 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.87106 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.87106 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.87106 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.87106 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.87106 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.07718 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.87106 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07718 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07718 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1192.61279 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07718 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07718 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07718 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07718 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07718 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53859 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07718 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19895.42000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10206.53255 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19895.42000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80051 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80051 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19895.42000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28587.42509 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28587.42509 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.87106 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.87106 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3072.16618 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.87106 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.87106 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.87106 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.87106 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.87106 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43553 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.87106 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 66486.81000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 33019.86526 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 66486.81000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72281 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72281 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66486.81000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 98759.27818 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 98759.27818 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19059.2 | 11.68 | 11.00 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 64255.9 | 11.87 | 11.18 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2068132145 | 0.1798069523 | Pass | Pass | 0.4367490107 | 2.5376642284 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4378057529 | 0.3997651087 | Pass | Pass | 0.2231310459 | 0.5636785865 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.6350109953E-005 | 2.5252610744E-005 | Pass | Pass | 4.1656353224E-002 | 3.5357612610E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8196.24 | 868.31 | 0.00 | 95.07 | 256.69 | 9416.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1368.14 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3133.49 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_17 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_16 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_15 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 114.28 | 3.939 | 0.573 | 0.571 | |||||||||||||||||
North Total or Average | 6.51 | 2.169 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 107.77 | 4.045 | 0.584 | 0.581 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_17 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_16 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_15 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.6485 | 236.88 | 2048.66 | LightsWired | LTG_SCH_OFFICE | 51.24 | 168.00 | 50.44 | 0.0000 | Y | 19.40 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 12.8090 | 1393.41 | 17848.24 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 38.38 | 0.0000 | Y | 128.58 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.4896 | 3204.84 | 17593.27 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 29.90 | 0.0000 | Y | 98.74 |
Interior Lighting Total | 7.7537 | 4835.13 | 37490.17 | 246.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6986.42 | AstronomicalClock | - | 83.67 | 83.67 | 109.73 | |
Exterior Lighting Total | 6986.42 | 109.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19895.42 | 15926.48 | 3968.94 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66486.81 | 48057.33 | 18429.48 | 0.72 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19059.2 | 11.68 | 11.00 | ||||
PSZ-FINE STORAGE COOLING COIL | 64255.9 | 11.87 | 11.18 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 154629.94 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28587.43 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 98759.28 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.88 | 360.03 | 92.91 | 1.00 | 3.25 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1192.61 | 1107.16 | 1.00 | 1.38 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.87 | 3072.17 | 1070.05 | 1.00 | 1.27 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10635.74 | 12762.88 | 53.88 | 0.898 | 1.077 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00857 | 29.37 | 0.01337 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 36362.54 | 43635.05 | 31.32 | 2.393 | 2.871 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00903 | 30.30 | 0.01337 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 0.00 | 30.93 | 0.01343 | 30.30 | 0.01337 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11159.46 | 13391.35 | 56.53 | 0.321 | 0.386 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00721 | -16.30 | 0.00092 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 38542.06 | 46250.47 | 33.19 | 0.935 | 1.122 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00579 | -16.30 | 0.00092 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 128858.29 | 154629.95 | 48.25 | 3.229 | 3.875 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00469 | -16.30 | 0.00092 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.08 | 1.08 | 0.39 | 0.39 | 1.0772 | 1.0772 | 1.0772 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.87 | 2.87 | 1.12 | 1.12 | 2.8711 | 2.8711 | 2.8711 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 154629.941 | 154629.941 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 154629.94 | 154629.94 | 3.875036 | 10.00 | 6.45 | 0.00469169 | 43.33 | 21.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 10.00 | 0.00469169 | 60.2360 | 154629.95 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19895.420 | 15926.483 | 1.077180 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 19895.42 | 17002.40 | 1.077180 | 25.35 | 17.04 | 0.00902390 | 12.00 | 11.04 | 0.00800000 | 29.49 | 0.01336553 | 21.60 | 9.4956 | 23.90 | 0.00856809 | 45.2364 | 10629.48 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28587.425 | 28587.425 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28587.43 | 28587.43 | 1.077183 | 17.50 | 11.92 | 0.00661182 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.4956 | 21.10 | 0.00720857 | 45.2181 | 11159.46 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 66486.810 | 48057.331 | 2.871060 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 66486.81 | 53847.52 | 2.871060 | 28.12 | 18.47 | 0.00966907 | 12.00 | 11.04 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 14.7928 | 26.70 | 0.00902708 | 40.3223 | 36362.54 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 98759.278 | 98759.278 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 98759.28 | 98759.28 | 2.871057 | 10.84 | 7.31 | 0.00507010 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.7929 | 15.55 | 0.00578989 | 51.5534 | 38542.06 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 154629.941 | 154629.941 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.875036 | 4.54900305 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 154629.94 | 154629.94 | 1.0000 | 4.54900305 | 3.875036 | 10.00 | 6.45 | 0.00469169 | 21864.2 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 154629.94 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 10.00 | 0.00469169 | 10.00 | 0.00469169 | 60.2360 | 154629.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19895.420 | 15926.483 | 1.077180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6150 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.077183 | 1.26453262 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 19895.42 | 17002.40 | 1.0000 | 1.26452887 | 1.077180 | 25.35 | 17.04 | 0.00902390 | 48469.0 | 12.00 | 11.04 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19895.42 | 29.49 | 0.01336553 | 21.60 | 0.10228463 | 9.4956 | 23.90 | 0.00856809 | 23.90 | 0.00856809 | 45.2364 | 10629.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28587.425 | 28587.425 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.077183 | 1.26453262 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28587.43 | 28587.43 | 1.0000 | 1.26453262 | 1.077183 | 17.50 | 11.92 | 0.00661182 | 34337.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28587.43 | -16.30 | 0.00092409 | -16.30 | 0.10228463 | 9.4956 | 21.05 | 0.00720857 | 21.10 | 0.00720857 | 45.2181 | 11159.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66486.810 | 48057.331 | 2.871060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8143 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.871057 | 3.37040591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 66486.81 | 53847.52 | 1.0000 | 3.37041001 | 2.871060 | 28.12 | 18.47 | 0.00966907 | 52943.9 | 12.00 | 11.04 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66486.81 | 30.30 | 0.01336696 | 21.83 | 0.42471127 | 14.7928 | 26.70 | 0.00902708 | 26.70 | 0.00902708 | 40.3223 | 36362.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98759.278 | 98759.278 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.871057 | 3.37040591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 98759.28 | 98759.28 | 1.0000 | 3.37040591 | 2.871057 | 10.84 | 7.31 | 0.00507010 | 23674.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98759.28 | -16.30 | 0.00092409 | -16.30 | 0.42471127 | 14.7929 | 15.55 | 0.00578989 | 15.55 | 0.00578989 | 51.5534 | 38542.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.08 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.87 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2783.00 | 2629.67 | 1965.50 |
ZONE2 FINE STORAGE | 3182.33 | 3049.67 | 2657.33 |
ZONE3 BULK STORAGE | 3227.83 | 3343.17 | 2991.00 |
Facility | 3521.00 | 3424.33 | 3077.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 73.17 | 0.00 | 21.50 | 0.00 |
ZONE2 FINE STORAGE | 390.50 | 13.67 | 17.67 | 0.00 |
ZONE3 BULK STORAGE | 4.00 | 0.00 | 4.00 | 0.00 |
Facility | 448.17 | 13.67 | 35.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.774 | 0.480 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.716 | 0.327 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.200 | 0.000 | 0.133 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2787026.86 | 0.00 | 2787026.86 | 2693698.63 | 5480725.49 | 3225648.14 | 5702.87 | 2131.56 | 925.57 | 0.00 |
ZONE2 FINE STORAGE | 7692347.91 | 0.00 | 7692347.91 | 8966050.58 | 16658398.49 | 13393694.68 | 5677.06 | 2342.77 | 740.17 | 23.79 |
ZONE3 BULK STORAGE | 0.00 | 29613285.90 | 29613285.90 | 51693260.18 | 81306546.07 | 30805497.77 | 7046.87 | 128.17 | 1584.96 | 5048.67 |
Total Facility | 10479374.77 | 29613285.90 | 40092660.67 | 63353009.38 | 0.10E+09 | 47424840.58 | 7933.74 | 2613.87 | 2608.80 | 5048.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2129 | 0.0000 | 0.2129 | 0.1331 | 0.3460 | 0.1023 | 578.87 | 2131.56 | 925.57 |
ZONE2 FINE STORAGE | 0.5753 | 0.0000 | 0.5753 | 0.2664 | 0.8417 | 0.4247 | 576.59 | 2342.77 | 716.64 |
ZONE3 BULK STORAGE | 0.0000 | 1.2827 | 1.2827 | 1.9717 | 3.2544 | 0.9768 | 2734.07 | 65.33 | 836.60 |
Total Facility | 0.7882 | 1.2827 | 2.0709 | 2.3712 | 4.4421 | 1.5038 | 2809.74 | 2551.04 | 1839.48 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3840803.51 | 0.00 | 3840803.51 | 3225648.14 | 5699.95 | 0.58 | 3059.46 | 0.00 |
PSZ-FINE STORAGE | 10600829.59 | 0.00 | 10600829.59 | 13393694.68 | 5670.62 | 0.33 | 3089.05 | 23.79 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2934 | 0.0000 | 0.2934 | 0.1023 | 575.95 | 0.58 | 3059.46 |
PSZ-FINE STORAGE | 0.7928 | 0.0000 | 0.7928 | 0.4247 | 570.24 | 0.33 | 3065.43 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2658.24 | 408.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2701.36 | 400.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3192 | 0.5356 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.8612 | 1.4439 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 69 | 69 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 444 |
Defaulted Fields | 429 |
Fields with Defaults | 1213 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 147 |
Autocalculatable Fields | 244 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
Electricity:Building | 386.54 | 1782.47 | 29-JAN-11:40 | 41466.67 | 03-JAN-16:00 |
Electricity:Zone:ZONE1 OFFICE | 51.34 | 860.99 | 01-JAN-00:10 | 3141.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 386.01 | 1782.47 | 29-JAN-11:40 | 41466.67 | 03-JAN-16:00 |
InteriorLights:Electricity | 246.72 | 1208.72 | 29-JAN-11:40 | 31354.05 | 03-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 246.72 | 1208.72 | 29-JAN-11:40 | 31354.05 | 03-JAN-16:00 |
LightsWired:InteriorLights:Electricity | 246.72 | 1208.72 | 29-JAN-11:40 | 31354.05 | 03-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 246.72 | 1208.72 | 29-JAN-11:40 | 31354.05 | 03-JAN-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 128.58 | 464.05 | 29-JAN-11:40 | 15171.01 | 02-JAN-15:40 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 128.58 | 464.05 | 29-JAN-11:40 | 15171.01 | 02-JAN-15:40 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 128.58 | 464.05 | 29-JAN-11:40 | 15171.01 | 02-JAN-15:40 |
Electricity:Zone:ZONE3 BULK STORAGE | 206.62 | 457.42 | 01-JAN-11:00 | 23154.40 | 03-JAN-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 98.74 | 457.42 | 01-JAN-11:00 | 14954.28 | 03-JAN-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 98.74 | 457.42 | 01-JAN-11:00 | 14954.28 | 03-JAN-16:00 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 59.11 | 0.00 | 11-JAN-18:10 | 6570.07 | 14-JUL-14:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.53 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
Ventilation (simple):Fans:Electricity | 0.53 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.53 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-JUL-14:10 |
ElectricityPurchased:Facility | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
ElectricityPurchased:Plant | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
Cogeneration:ElectricityPurchased | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
General:Cogeneration:ElectricityPurchased | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
ElectricityNet:Plant | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
Cogeneration:ElectricityNet | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
General:Cogeneration:ElectricityNet | 595.23 | 2265.47 | 12-MAR-10:30 | 51157.39 | 13-JAN-17:00 |
Electricity:HVAC | 72.70 | 0.00 | 11-JAN-18:10 | 17414.54 | 19-JUL-15:10 |
General:Fans:Electricity | 58.58 | 0.00 | 11-JAN-18:10 | 4624.81 | 11-DEC-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 14.12 | 0.00 | 01-JAN-00:10 | 13149.77 | 19-JUL-15:10 |
General:Cooling:Electricity | 14.12 | 0.00 | 01-JAN-00:10 | 13149.77 | 19-JUL-15:10 |
ExteriorLights:Electricity | 109.73 | 0.00 | 01-JAN-08:00 | 6986.42 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 109.73 | 0.00 | 01-JAN-08:00 | 6986.42 | 01-JAN-00:10 |
Electricity:Plant | 26.27 | 483.00 | 08-FEB-06:20 | 2704.96 | 16-FEB-12:50 |
WaterSystems:Electricity | 26.27 | 483.00 | 08-FEB-06:20 | 2704.96 | 16-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.27 | 483.00 | 08-FEB-06:20 | 2704.96 | 16-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 795.29 | 0.00 | 11-JAN-18:10 | 293574.38 | 06-FEB-17:20 |
NaturalGas:HVAC | 795.29 | 0.00 | 11-JAN-18:10 | 293574.38 | 06-FEB-17:20 |
Heating:NaturalGas | 795.29 | 0.00 | 11-JAN-18:10 | 293574.38 | 06-FEB-17:20 |
General:Heating:NaturalGas | 795.29 | 0.00 | 11-JAN-18:10 | 293574.38 | 06-FEB-17:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1330.37 | 0.00 | 11-JAN-18:10 | 445827.42 | 13-FEB-06:10 |
EnergyTransfer:Building | 662.80 | 0.00 | 11-JAN-18:10 | 223555.20 | 13-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.43 | 0.00 | 01-JAN-00:10 | 28224.33 | 07-FEB-07:10 |
Heating:EnergyTransfer | 598.02 | 0.00 | 11-JAN-18:10 | 223555.20 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 39.51 | 0.00 | 01-JAN-00:10 | 28224.33 | 07-FEB-07:10 |
General:Heating:EnergyTransfer | 598.02 | 0.00 | 11-JAN-18:10 | 223555.20 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 39.51 | 0.00 | 01-JAN-00:10 | 28224.33 | 07-FEB-07:10 |
Cooling:EnergyTransfer | 64.78 | 0.00 | 01-JAN-00:10 | 32499.70 | 02-AUG-18:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 21.92 | 0.00 | 01-JAN-00:10 | 9485.46 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer | 64.78 | 0.00 | 01-JAN-00:10 | 32499.70 | 02-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 21.92 | 0.00 | 01-JAN-00:10 | 9485.46 | 17-JUL-07:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 150.03 | 0.00 | 01-JAN-00:40 | 53963.03 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 107.17 | 0.00 | 01-JAN-00:40 | 53963.03 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 107.17 | 0.00 | 01-JAN-00:40 | 53963.03 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.86 | 0.00 | 01-JAN-00:10 | 32499.70 | 02-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.86 | 0.00 | 01-JAN-00:10 | 32499.70 | 02-AUG-18:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 451.35 | 0.00 | 06-JAN-10:50 | 155781.78 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 451.35 | 0.00 | 06-JAN-10:50 | 155781.78 | 06-FEB-10:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 451.35 | 0.00 | 06-JAN-10:50 | 155781.78 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 667.57 | 0.00 | 11-JAN-18:10 | 229122.51 | 06-FEB-17:20 |
HeatingCoils:EnergyTransfer | 610.15 | 0.00 | 11-JAN-18:10 | 229122.51 | 06-FEB-17:20 |
CoolingCoils:EnergyTransfer | 57.42 | 0.00 | 01-JAN-00:10 | 50545.81 | 19-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 39.510 | -21.919 | 0.000 | 0.000 | 10.019 | 19.398 | 31.946 | 10.477 | 0.000 | 0.501 | 0.000 | 0.000 | -8.473 | 0.000 | -41.234 | -40.226 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 107.167 | -42.857 | 0.000 | 0.000 | 25.121 | 128.580 | 0.000 | 55.696 | 0.000 | 0.436 | 0.001 | 0.000 | -23.341 | 0.000 | -123.103 | -127.699 |
ZONE3 BULK STORAGE | 451.345 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 65.234 | 98.741 | 107.344 | 559.818 | 0.000 | 9.481 | 0.006 | 0.000 | -232.596 | 0.000 | -685.337 | -374.029 |
Total Facility | 451.345 | 0.000 | 146.678 | -64.776 | 0.000 | 0.000 | 100.374 | 246.719 | 139.290 | 625.992 | 0.000 | 10.418 | 0.008 | 0.000 | -264.410 | 0.000 | -849.675 | -541.954 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JUN-07:02 | 0.00 | 0.00 | 0.00 | -25776.96 | 0.00 | 0.00 | 801.53 | 1228.76 | 1912.50 | 2.07 | 0.00 | 0.00 | 22579.19 | 0.00 | -0.00 | 0.00 | -747.10 | 0.00 |
ZONE2 FINE STORAGE | 06-JUL-17:34 | 0.00 | 0.00 | 0.00 | -68096.92 | 0.00 | 0.00 | 0.00 | 1564.70 | 0.00 | 2947.11 | 0.00 | 0.00 | 65158.20 | 0.00 | -0.00 | 0.00 | -1573.09 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-JUL-17:34 | 0.00 | 0.00 | 0.00 | -68096.92 | 0.00 | 0.00 | 0.00 | 2960.31 | 2623.78 | 98171.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15892.86 | -19765.78 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:31 | 0.00 | 0.00 | 30668.63 | 0.00 | 0.00 | 0.00 | 153.53 | 367.04 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -796.73 | 0.00 | -5501.64 | -25464.58 |
ZONE2 FINE STORAGE | 06-FEB-06:01 | 0.00 | 0.00 | 103081.40 | 0.00 | 0.00 | 0.00 | 382.03 | 1784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2530.55 | 0.00 | -16487.36 | -86230.35 |
ZONE3 BULK STORAGE | 06-FEB-10:00 | 155782.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8380.16 | 3888.11 | 8200.12 | 1730.84 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -173421.44 | -4560.61 |
Total Facility | 13-FEB-06:01 | 154992.05 | 0.00 | 127102.62 | 0.00 | 0.00 | 0.00 | 1449.54 | 3911.19 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27758.80 | 0.00 | -169846.59 | -92473.80 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0772 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0772 | 0.0950 | 1.0000 | Not calculated | 0.1023 | 0.0950 | ||
PSZ-FINE STORAGE | 2.8711 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8711 | 0.1479 | 1.0000 | Not calculated | 0.4247 | 0.1479 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0772 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0772 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0950 | ||
PSZ-FINE STORAGE | 2.8711 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8711 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1479 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0772 | 1.0772 | 1.0772 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8711 | 2.8711 | 2.8711 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0772 | 1.0772 | 1.0772 | 1.0772 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8711 | 2.8711 | 2.8711 | 2.8711 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0772 | 1.0772 | 1.0772 | No | 0.1023 | 0.2653 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8711 | 2.8711 | 2.8711 | No | 0.4247 | 0.3787 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0772 | 1.0772 | 1.0772 | 1.0772 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8711 | 2.8711 | 2.8711 | 2.8711 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 35.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 35.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 795.29 | 293574.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 14.12 | 13149.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 246.72 | 31354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 109.73 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.53 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 58.58 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.27 | 2704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 595.23 |
Natural Gas | 0.00 | 795.29 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1390.53 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 51.03 |
Space Heating | 0.00 |
Space Cooling | 2.92 |
Fans (All) | 12.23 |
Service Water Heating | 5.43 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 123.11 |
Subtotal | 123.11 |
Natural Gas [MJ/m2] | |
Space Heating | 164.48 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 164.48 |
Subtotal | 164.48 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.74 |
Space Heating | 57.19 |
Space Cooling | 1.02 |
Fans (All) | 4.25 |
Service Water Heating | 1.89 |
Receptacle Equipment | 10.02 |
Miscellaneous | 7.89 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2672. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8014.50 | 745.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7825.00 | 935.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7577.17 | 1165.67 | 17.17 | 0.00 | 0.00 |
Min | 7577.17 | 745.50 | 0.00 | 0.00 | 0.00 |
Max | 8014.50 | 1165.67 | 17.17 | 0.00 | 0.00 |
Average | 7805.56 | 948.72 | 5.72 | 0.00 | 0.00 |
Sum | 23416.67 | 2846.17 | 17.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33005.83 | 21.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 67998.00 | 14721.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 159112.50 | 31319.83 | 760.67 | 0.00 | 0.00 |
Min | 33005.83 | 21.17 | 0.00 | 0.00 | 0.00 |
Max | 159112.50 | 31319.83 | 760.67 | 0.00 | 0.00 |
Average | 86705.44 | 15354.00 | 253.56 | 0.00 | 0.00 |
Sum | 260116.33 | 46062.00 | 760.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7629.17 | 1130.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7298.17 | 1461.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7178.67 | 1581.33 | 0.00 | 0.00 | 0.00 |
Min | 7178.67 | 1130.83 | 0.00 | 0.00 | 0.00 |
Max | 7629.17 | 1581.33 | 0.00 | 0.00 | 0.00 |
Average | 7368.67 | 1391.33 | 0.00 | 0.00 | 0.00 |
Sum | 22106.00 | 4174.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31870.00 | 1157.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 65955.00 | 16764.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 152228.33 | 38964.67 | 0.00 | 0.00 | 0.00 |
Min | 31870.00 | 1157.00 | 0.00 | 0.00 | 0.00 |
Max | 152228.33 | 38964.67 | 0.00 | 0.00 | 0.00 |
Average | 83351.11 | 18961.89 | 0.00 | 0.00 | 0.00 |
Sum | 250053.33 | 56885.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 256498.00 | 1070.04 | 14-JAN-08:07 | 3.40 | 2.64 | 0.493463E+09 | 603.25 | 07-JAN-15:50 | 3.40 | 2.64 |
February | 416420.47 | 1216.42 | 18-FEB-08:07 | -1.6 | -1.9 | 0.453961E+09 | 603.25 | 02-FEB-11:20 | -1.6 | -1.9 |
March | 38555923.44 | 1640.79 | 15-MAR-15:10 | 25.50 | 16.19 | 0.545779E+09 | 768.96 | 16-MAR-15:00 | 15.60 | 13.95 |
April | 75030769.01 | 1526.62 | 22-APR-15:00 | 15.60 | 7.04 | 0.518762E+09 | 768.96 | 26-APR-15:30 | 14.70 | 9.01 |
May | 0.127328E+10 | 10342.40 | 27-MAY-07:03 | 13.07 | 9.33 | 0.628299E+09 | 825.01 | 27-MAY-07:10 | 13.07 | 9.33 |
June | 0.441399E+10 | 25784.34 | 03-JUN-07:02 | 11.78 | 7.72 | 0.661186E+09 | 879.39 | 12-JUN-07:10 | 24.08 | 18.79 |
July | 0.602775E+10 | 20979.69 | 12-JUL-07:03 | 16.97 | 12.15 | 0.639697E+09 | 879.39 | 21-JUL-07:10 | 26.20 | 22.38 |
August | 0.605480E+10 | 20375.60 | 12-AUG-07:02 | 15.37 | 13.54 | 0.689980E+09 | 879.39 | 28-AUG-07:10 | 20.10 | 17.33 |
September | 0.357053E+10 | 23359.45 | 02-SEP-07:02 | 12.07 | 10.60 | 0.633050E+09 | 879.39 | 14-SEP-07:10 | 20.60 | 19.08 |
October | 0.440814E+09 | 2881.87 | 11-OCT-16:00 | 21.70 | 14.52 | 0.556939E+09 | 768.99 | 11-OCT-15:00 | 21.70 | 14.52 |
November | 22267934.95 | 1504.31 | 25-NOV-08:07 | -0.2 | -1.7 | 0.480021E+09 | 745.67 | 04-NOV-15:09 | -0.2 | -1.7 |
December | 2059046.60 | 1548.69 | 16-DEC-08:07 | 0.60 | -0.5 | 0.493480E+09 | 604.30 | 01-DEC-08:20 | 0.60 | -0.5 |
Annual Sum or Average | 0.219197E+11 | 0.679462E+10 | ||||||||
Minimum of Months | 256498.00 | 1070.04 | -1.6 | -1.9 | 0.453961E+09 | 603.25 | -1.6 | -1.9 | ||
Maximum of Months | 0.605480E+10 | 25784.34 | 25.50 | 16.19 | 0.689980E+09 | 879.39 | 26.20 | 22.38 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501845E+09 | 6043.79 | 06-JAN-15:30 | -2.2 | -4.9 | 0.654650E+09 | 957.72 | 11-JAN-16:10 | 11.60 | 10.09 |
February | 0.440262E+09 | 5182.47 | 28-FEB-14:50 | 0.00 | -2.8 | 0.600471E+09 | 962.89 | 22-FEB-16:10 | 0.00 | -2.8 |
March | 0.154258E+10 | 6413.39 | 07-MAR-15:00 | -2.2 | -5.2 | 0.827390E+09 | 1782.05 | 15-MAR-14:20 | 25.93 | 16.12 |
April | 0.142537E+10 | 4848.20 | 03-APR-08:70 | 0.55 | -0.1 | 0.908249E+09 | 1645.88 | 22-APR-15:09 | 15.68 | 7.07 |
May | 0.106294E+10 | 5251.19 | 27-MAY-14:00 | 21.70 | 12.35 | 0.146960E+10 | 2246.80 | 26-MAY-15:00 | 21.70 | 12.35 |
June | 0.622210E+10 | 66255.59 | 30-JUN-17:11 | 23.70 | 12.26 | 0.186812E+10 | 2246.88 | 20-JUN-13:20 | 23.70 | 12.26 |
July | 0.132734E+11 | 68096.94 | 06-JUL-17:34 | 22.93 | 13.50 | 0.185219E+10 | 2246.91 | 12-JUL-14:50 | 22.20 | 15.80 |
August | 0.112031E+11 | 66344.64 | 03-AUG-19:11 | 24.27 | 14.31 | 0.199313E+10 | 2246.95 | 08-AUG-15:00 | 27.80 | 17.52 |
September | 0.304040E+10 | 53158.00 | 21-SEP-17:25 | 24.45 | 16.74 | 0.174525E+10 | 2246.86 | 22-SEP-15:39 | 23.90 | 15.35 |
October | 0.157161E+10 | 5913.50 | 17-OCT-08:70 | -0.0 | -1.3 | 0.109929E+10 | 1941.94 | 11-OCT-15:09 | -0.0 | -1.3 |
November | 0.173703E+10 | 4728.98 | 24-NOV-10:30 | 0.25 | -1.2 | 0.761862E+09 | 1393.67 | 04-NOV-15:00 | 0.25 | -1.2 |
December | 0.838207E+09 | 5170.49 | 04-DEC-16:00 | -0.6 | -3.3 | 0.663985E+09 | 1110.08 | 01-DEC-11:20 | -0.6 | -3.3 |
Annual Sum or Average | 0.428589E+11 | 0.144442E+11 | ||||||||
Minimum of Months | 0.440262E+09 | 4728.98 | -2.2 | -5.2 | 0.600471E+09 | 957.72 | -0.6 | -3.3 | ||
Maximum of Months | 0.132734E+11 | 68096.94 | 24.45 | 16.74 | 0.199313E+10 | 2246.95 | 27.80 | 17.52 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.648743E+09 | 1007.61 | 11-JAN-16:49 | 11.20 | 9.89 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.593429E+09 | 1018.86 | 22-FEB-16:00 | 11.70 | 5.56 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 | -6.9 | 0.882131E+09 | 2327.63 | 15-MAR-14:20 | 25.93 | 16.12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.107201E+10 | 2121.53 | 08-APR-14:20 | 20.20 | 13.55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.228892E+10 | 3997.13 | 27-MAY-15:30 | 21.70 | 12.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.374303E+10 | 6088.52 | 27-JUN-13:30 | 28.90 | 23.32 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.481352E+10 | 7209.73 | 21-JUL-14:20 | 31.33 | 22.12 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.507393E+10 | 6756.53 | 10-AUG-14:30 | 30.30 | 20.01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.345958E+10 | 5321.51 | 16-SEP-14:20 | 27.03 | 19.74 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.169609E+10 | 3341.95 | 03-OCT-14:00 | 18.90 | 12.68 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.837643E+09 | 1799.49 | 04-NOV-15:00 | 18.30 | 13.48 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.95 | 3.07 | 0.657663E+09 | 1267.48 | 01-DEC-11:39 | 14.27 | 12.08 |
Annual Sum or Average | 0.00 | 0.257667E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.593429E+09 | 1007.61 | 11.20 | 5.56 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.507393E+10 | 7209.73 | 31.33 | 23.32 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.939093E+10 | 30240.91 | 24-JAN-06:31 | -11.9 |
February | 0.905571E+10 | 30668.60 | 13-FEB-06:31 | -9.4 |
March | 0.548496E+10 | 29322.36 | 01-MAR-06:32 | -7.6 |
April | 0.236145E+10 | 28950.05 | 17-APR-06:02 | -4.2 |
May | 0.335254E+09 | 28503.34 | 01-MAY-06:02 | 2.35 |
June | 89946586.37 | 1861.45 | 13-JUN-06:15 | 8.70 |
July | 59524637.22 | 2006.57 | 18-JUL-06:05 | 18.17 |
August | 85943767.81 | 1879.69 | 08-AUG-06:05 | 20.68 |
September | 0.106188E+09 | 5209.04 | 29-SEP-07:03 | 10.10 |
October | 0.947989E+09 | 28758.85 | 18-OCT-06:01 | 3.40 |
November | 0.316525E+10 | 28802.37 | 24-NOV-07:02 | -3.2 |
December | 0.842799E+10 | 30402.55 | 26-DEC-06:31 | -12.2 |
Annual Sum or Average | 0.395111E+11 | |||
Minimum of Months | 59524637.22 | 1861.45 | -12.2 | |
Maximum of Months | 0.939093E+10 | 30668.60 | 20.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281538E+11 | 102974.59 | 24-JAN-06:01 | -12.1 |
February | 0.288609E+11 | 103081.90 | 06-FEB-06:01 | -13.9 |
March | 0.126158E+11 | 100206.40 | 05-MAR-01:22 | -7.8 |
April | 0.358553E+10 | 98509.80 | 16-APR-03:53 | -2.2 |
May | 0.408358E+09 | 3136.91 | 10-MAY-15:00 | 26.10 |
June | 0.160304E+09 | 3090.30 | 13-JUN-07:00 | 8.30 |
July | 45083357.03 | 3517.02 | 20-JUL-06:03 | 24.08 |
August | 80341895.93 | 3137.76 | 15-AUG-06:04 | 22.30 |
September | 0.210655E+09 | 3111.26 | 28-SEP-07:00 | 12.20 |
October | 0.539154E+09 | 34052.82 | 17-OCT-06:02 | -2.8 |
November | 0.573465E+10 | 58324.96 | 24-NOV-04:13 | -3.1 |
December | 0.267729E+11 | 103038.64 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.107167E+12 | |||
Minimum of Months | 45083357.03 | 3090.30 | -13.9 | |
Maximum of Months | 0.288609E+11 | 103081.90 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128461E+12 | 155596.35 | 12-JAN-09:00 | -11.1 |
February | 0.137258E+12 | 155781.78 | 06-FEB-10:00 | -15.0 |
March | 0.469436E+11 | 87127.40 | 05-MAR-01:00 | -7.2 |
April | 0.635165E+10 | 62947.57 | 16-APR-06:55 | -3.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.999108E+10 | 29891.59 | 25-NOV-06:00 | -1.7 |
December | 0.122340E+12 | 149036.05 | 09-DEC-15:00 | -5.6 |
Annual Sum or Average | 0.451346E+12 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.137258E+12 | 155781.78 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162246E+10 | 1228.76 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.147976E+10 | 1228.76 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.169071E+10 | 1228.76 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.159765E+10 | 1228.76 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.165659E+10 | 1228.76 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.163177E+10 | 1228.76 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.162246E+10 | 1228.76 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.169071E+10 | 1228.76 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.159765E+10 | 1228.76 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.162246E+10 | 1228.76 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.156352E+10 | 1228.76 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.162246E+10 | 1228.76 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.193982E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.147976E+10 | 1228.76 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.169071E+10 | 1228.76 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.136033E+11 | 15171.01 | 02-JAN-15:39 | 0.00 | 0.00 |
February | 0.103946E+11 | 15171.01 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.112386E+11 | 15171.01 | 21-MAR-08:09 | 0.00 | 0.00 |
April | 0.949988E+10 | 13386.18 | 01-APR-07:10 | 0.00 | 0.00 |
May | 0.916144E+10 | 11735.22 | 01-MAY-07:10 | 0.00 | 0.00 |
June | 0.832763E+10 | 11735.22 | 06-JUN-07:10 | 0.00 | 0.00 |
July | 0.840649E+10 | 11735.22 | 01-JUL-07:10 | 0.00 | 0.00 |
August | 0.929404E+10 | 13386.18 | 02-AUG-07:10 | 0.00 | 0.00 |
September | 0.989479E+10 | 13386.18 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.117313E+11 | 15171.01 | 11-OCT-08:09 | 0.00 | 0.00 |
November | 0.131910E+11 | 15171.01 | 02-NOV-08:09 | 0.00 | 0.00 |
December | 0.138366E+11 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128580E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.832763E+10 | 11735.22 | 0.00 | 0.00 | |
Maximum of Months | 0.138366E+11 | 15171.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106734E+11 | 14954.28 | 03-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.819974E+10 | 13194.95 | 01-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.843260E+10 | 13194.95 | 17-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.702660E+10 | 10555.96 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.680620E+10 | 10555.96 | 12-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.636940E+10 | 9254.06 | 26-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.648496E+10 | 10555.96 | 21-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.707354E+10 | 10555.96 | 17-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.757438E+10 | 11567.57 | 26-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.889614E+10 | 13194.95 | 02-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.102515E+11 | 14954.28 | 18-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.109525E+11 | 14954.28 | 01-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.987409E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.636940E+10 | 9254.06 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.109525E+11 | 14954.28 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677734E+10 |
February | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676208E+10 |
March | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6053724.09 | 0.468800E+10 |
April | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319440E+10 |
May | 0.144276E+10 | 0.165659E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2446115.23 | 0.209033E+10 |
June | 0.144276E+10 | 0.163177E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91236230.93 | 0.143187E+10 |
July | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219440E+09 | 0.764005E+09 |
August | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169697E+09 | 0.103243E+10 |
September | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11747614.80 | 0.151087E+10 |
October | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8003.85 | 0.269607E+10 |
November | 0.133177E+10 | 0.156352E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50194.71 | 0.367718E+10 |
December | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660965E+10 |
Annual Sum or Average | 0.168137E+11 | 0.193982E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500679E+09 | 0.412342E+11 |
Minimum of Months | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764005E+09 |
Maximum of Months | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219440E+09 | 0.677734E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.136033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199472E+11 |
February | 0.300332E+10 | 0.103946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214778E+11 |
March | 0.352563E+10 | 0.112386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30166745.78 | 0.124374E+11 |
April | 0.326447E+10 | 0.949988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875106E+10 |
May | 0.339505E+10 | 0.916144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3430676.70 | 0.624845E+10 |
June | 0.339505E+10 | 0.832763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57106875.20 | 0.527448E+10 |
July | 0.326447E+10 | 0.840649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179805E+09 | 0.300061E+10 |
August | 0.352563E+10 | 0.929404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144449E+09 | 0.363931E+10 |
September | 0.326447E+10 | 0.989479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121518.19 | 0.518441E+10 |
October | 0.326447E+10 | 0.117313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7744434.38 | 0.705190E+10 |
November | 0.313390E+10 | 0.131910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12490872.58 | 0.937049E+10 |
December | 0.326447E+10 | 0.138366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207201E+11 |
Annual Sum or Average | 0.395654E+11 | 0.128580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436316E+09 | 0.123103E+12 |
Minimum of Months | 0.300332E+10 | 0.832763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300061E+10 |
Maximum of Months | 0.352563E+10 | 0.138366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179805E+09 | 0.214778E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.106734E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3715013.60 | 0.798307E+11 |
February | 0.690763E+10 | 0.819974E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61405309.60 | 0.881465E+11 |
March | 0.810895E+10 | 0.843260E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178711E+10 | 0.450314E+11 |
April | 0.750829E+10 | 0.702660E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100984E+10 | 0.245955E+11 |
May | 0.780862E+10 | 0.680620E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597325E+09 | 0.184865E+11 |
June | 0.780862E+10 | 0.636940E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520158E+09 | 0.218823E+11 |
July | 0.750829E+10 | 0.648496E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9304734.79 | 0.208015E+11 |
August | 0.810895E+10 | 0.707354E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9114931.22 | 0.235912E+11 |
September | 0.750829E+10 | 0.757438E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8102736.58 | 0.226927E+11 |
October | 0.750829E+10 | 0.889614E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716383E+09 | 0.256785E+11 |
November | 0.720796E+10 | 0.102515E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181055E+10 | 0.271618E+11 |
December | 0.750829E+10 | 0.109525E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116021E+09 | 0.809040E+11 |
Annual Sum or Average | 0.910005E+11 | 0.987409E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664903E+10 | 0.478803E+12 |
Minimum of Months | 0.690763E+10 | 0.636940E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3715013.60 | 0.184865E+11 |
Maximum of Months | 0.810895E+10 | 0.109525E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181055E+10 | 0.881465E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1228.76 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 17283.52 | 12-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1228.76 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 19736.97 | 06-FEB-17:10 |
March | 1680.92 | 01-MAR-08:09 | 1228.76 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.05 | 15-MAR-16:10 | 14569.51 | 07-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1228.76 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 10212.36 | 04-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1228.76 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.06 | 10-MAY-15:10 | 6449.26 | 01-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1228.76 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2292.60 | 27-JUN-12:00 | 6608.54 | 13-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1228.76 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2447.62 | 19-JUL-16:10 | 4901.91 | 03-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1228.76 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2412.88 | 18-AUG-17:00 | 5314.64 | 03-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1228.76 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.18 | 15-SEP-12:00 | 6621.88 | 05-SEP-06:03 |
October | 1680.92 | 02-OCT-07:10 | 1228.76 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 22-OCT-12:00 | 9337.54 | 17-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1228.76 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27-NOV-06:00 | 9544.62 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1228.76 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 17155.46 | 26-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4901.91 | |||||
Maximum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2447.62 | 19736.97 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 15171.01 | 02-JAN-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 34740.19 | 12-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 15171.01 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 31484.42 | 13-FEB-07:02 |
March | 3955.50 | 01-MAR-08:09 | 15171.01 | 21-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.72 | 14-MAR-15:10 | 16450.53 | 03-MAR-18:00 |
April | 3955.50 | 01-APR-07:10 | 13386.18 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 15436.18 | 04-APR-17:00 |
May | 3955.50 | 01-MAY-07:10 | 11735.22 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.03 | 14-MAY-15:00 | 10336.02 | 11-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 11735.22 | 06-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.52 | 12-JUN-15:10 | 11304.49 | 13-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 11735.22 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3947.18 | 15-JUL-15:10 | 6377.76 | 06-JUL-02:00 |
August | 3955.50 | 01-AUG-07:10 | 13386.18 | 02-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2678.02 | 13-AUG-12:57 | 6777.05 | 30-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 13386.18 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.76 | 16-SEP-17:40 | 9061.64 | 29-SEP-06:20 |
October | 3955.50 | 02-OCT-07:10 | 15171.01 | 11-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.44 | 22-OCT-12:00 | 10008.73 | 23-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 15171.01 | 02-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1100.72 | 27-NOV-06:00 | 15680.48 | 17-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 31103.50 | 09-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 11735.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6377.76 | ||||
Maximum of Months | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3947.18 | 34740.19 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 14954.28 | 03-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1968.90 | 11-JAN-16:00 | 131956.23 | 12-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 13194.95 | 01-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6777.83 | 22-FEB-18:20 | 129687.07 | 07-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 13194.95 | 17-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29216.50 | 14-MAR-14:00 | 62483.79 | 01-MAR-15:00 |
April | 9097.65 | 01-APR-07:10 | 10555.96 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16968.68 | 07-APR-14:00 | 45870.95 | 16-APR-07:00 |
May | 9097.65 | 01-MAY-07:10 | 10555.96 | 12-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15784.12 | 14-MAY-15:00 | 31538.07 | 11-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 9254.06 | 26-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10478.55 | 12-JUN-12:10 | 43102.37 | 13-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 10555.96 | 21-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3716.82 | 15-JUL-13:55 | 29540.81 | 06-JUL-02:00 |
August | 9097.65 | 01-AUG-07:10 | 10555.96 | 17-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2502.89 | 13-AUG-12:53 | 28588.18 | 30-AUG-18:00 |
September | 9097.65 | 01-SEP-07:10 | 11567.57 | 26-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.39 | 16-SEP-12:10 | 33351.79 | 29-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 13194.95 | 02-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12754.21 | 22-OCT-12:00 | 34283.45 | 23-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 14954.28 | 18-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17930.55 | 27-NOV-06:00 | 38933.69 | 17-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 14954.28 | 01-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11764.75 | 01-DEC-11:00 | 119417.27 | 09-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 9254.06 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.39 | 28588.18 | |||||
Maximum of Months | 9097.65 | 14954.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 29216.50 | 131956.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1070.04 | 14-JAN-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1606.98 |
February | 1216.42 | 18-FEB-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.53 |
March | 1640.79 | 15-MAR-15:10 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 175.25 | 0.00 |
April | 1526.62 | 22-APR-15:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.94 |
May | 10342.40 | 27-MAY-07:03 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.22 |
June | 25784.34 | 03-JUN-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.10 |
July | 20979.69 | 12-JUL-07:03 | 6723.69 | 4915.05 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.80 |
August | 20375.60 | 12-AUG-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.71 |
September | 23359.45 | 02-SEP-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.53 |
October | 2881.87 | 11-OCT-16:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.99 |
November | 1504.31 | 25-NOV-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1189.45 |
December | 1548.69 | 16-DEC-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1070.04 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25784.34 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 175.25 | 1606.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6043.79 | 06-JAN-15:30 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.19 |
February | 5182.47 | 28-FEB-14:50 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3736.01 |
March | 6413.39 | 07-MAR-15:00 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2520.13 |
April | 4848.20 | 03-APR-08:70 | 3955.50 | 13299.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.76 |
May | 5251.19 | 27-MAY-14:00 | 3955.50 | 7686.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.46 |
June | 66255.59 | 30-JUN-17:11 | 0.00 | 11244.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.49 |
July | 68096.94 | 06-JUL-17:34 | 0.00 | 15646.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1573.09 |
August | 66344.64 | 03-AUG-19:11 | 0.00 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.15 |
September | 53158.00 | 21-SEP-17:25 | 0.00 | 3569.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.98 |
October | 5913.50 | 17-OCT-08:70 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1337.64 |
November | 4728.98 | 24-NOV-10:30 | 3955.50 | 9557.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.32 |
December | 5170.49 | 04-DEC-16:00 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3180.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4728.98 | 0.00 | 3569.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.98 | |
Maximum of Months | 68096.94 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3736.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 7037.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16854.84 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 7037.31 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22636.07 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 5277.98 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19949.82 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5544.97 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3461.52 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3983.10 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11529.39 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8480.47 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11425.61 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8152.28 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10349.55 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 3518.65 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10396.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3461.52 | |
Maximum of Months | 0.00 | 0.00 | 7037.31 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22636.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.573065E+11 | 51157.39 | 13-JAN-16:00 | 0.222062E+12 | 277503.04 | 12-JAN-08:00 |
February | 0.480031E+11 | 44210.79 | 08-FEB-08:09 | 0.233035E+12 | 293574.38 | 06-FEB-17:19 |
March | 0.511618E+11 | 44154.97 | 21-MAR-07:10 | 0.870881E+11 | 151919.38 | 05-MAR-01:30 |
April | 0.444363E+11 | 40950.63 | 05-APR-07:19 | 0.162648E+11 | 118322.78 | 16-APR-03:00 |
May | 0.437394E+11 | 37302.59 | 11-MAY-07:19 | 0.262573E+09 | 14097.87 | 01-MAY-06:10 |
June | 0.438493E+11 | 36962.95 | 27-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.481954E+11 | 42121.77 | 21-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.500351E+11 | 43281.16 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.465149E+11 | 43213.23 | 16-SEP-07:10 | 1840559.75 | 3067.60 | 29-SEP-07:10 |
October | 0.503821E+11 | 43829.93 | 31-OCT-07:10 | 0.158194E+10 | 27169.01 | 17-OCT-06:10 |
November | 0.536229E+11 | 51150.37 | 30-NOV-16:40 | 0.254697E+11 | 66484.85 | 25-NOV-06:00 |
December | 0.579858E+11 | 51155.48 | 29-DEC-16:49 | 0.209529E+12 | 253833.25 | 09-DEC-16:00 |
Annual Sum or Average | 0.595232E+12 | 0.795295E+12 | ||||
Minimum of Months | 0.437394E+11 | 36962.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.579858E+11 | 51157.39 | 0.233035E+12 | 293574.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.258991E+11 | 0.115234E+11 | 0.115358E+11 | 0.00 | 0.604334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230487E+10 | 0.00 |
February | 0.200741E+11 | 0.961611E+10 | 0.105871E+11 | 0.00 | 0.561739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210844E+10 | 0.00 |
March | 0.213619E+11 | 0.955323E+10 | 0.123431E+11 | 0.00 | 0.551507E+10 | 0.00 | 0.00 | 16876631.90 | 0.00 | 0.00 | 0.00 | 0.237163E+10 | 0.00 |
April | 0.181241E+11 | 0.814058E+10 | 0.114862E+11 | 0.00 | 0.446620E+10 | 0.00 | 0.00 | 30.39 | 0.00 | 0.00 | 0.00 | 0.221916E+10 | 0.00 |
May | 0.176242E+11 | 0.744054E+10 | 0.119357E+11 | 0.00 | 0.439107E+10 | 0.00 | 0.00 | 0.108452E+09 | 0.00 | 0.00 | 0.00 | 0.223934E+10 | 0.00 |
June | 0.163288E+11 | 0.673211E+10 | 0.118862E+11 | 0.00 | 0.445206E+10 | 0.00 | 0.00 | 0.231633E+10 | 0.00 | 0.00 | 0.00 | 0.213385E+10 | 0.00 |
July | 0.165139E+11 | 0.714292E+10 | 0.115358E+11 | 0.00 | 0.473068E+10 | 0.00 | 0.00 | 0.616227E+10 | 0.00 | 0.00 | 0.00 | 0.210981E+10 | 0.00 |
August | 0.180583E+11 | 0.797709E+10 | 0.123357E+11 | 0.00 | 0.490898E+10 | 0.00 | 0.00 | 0.460413E+10 | 0.00 | 0.00 | 0.00 | 0.215095E+10 | 0.00 |
September | 0.190668E+11 | 0.876935E+10 | 0.114788E+11 | 0.00 | 0.422536E+10 | 0.00 | 0.00 | 0.907481E+09 | 0.00 | 0.00 | 0.00 | 0.206710E+10 | 0.00 |
October | 0.222499E+11 | 0.101946E+11 | 0.115432E+11 | 0.00 | 0.422933E+10 | 0.00 | 0.00 | 6626924.51 | 0.00 | 0.00 | 0.00 | 0.215843E+10 | 0.00 |
November | 0.250060E+11 | 0.108485E+11 | 0.110862E+11 | 0.00 | 0.454615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213598E+10 | 0.00 |
December | 0.264115E+11 | 0.117875E+11 | 0.115358E+11 | 0.00 | 0.598478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226620E+10 | 0.00 |
Annual Sum or Average | 0.246719E+12 | 0.109726E+12 | 0.139290E+12 | 0.00 | 0.591104E+11 | 0.00 | 0.00 | 0.141222E+11 | 0.00 | 0.00 | 0.00 | 0.262658E+11 | 0.00 |
Minimum of Months | 0.163288E+11 | 0.673211E+10 | 0.105871E+11 | 0.00 | 0.422536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206710E+10 | 0.00 |
Maximum of Months | 0.264115E+11 | 0.117875E+11 | 0.123431E+11 | 0.00 | 0.604334E+10 | 0.00 | 0.00 | 0.616227E+10 | 0.00 | 0.00 | 0.00 | 0.237163E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.222062E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.233035E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.870881E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.162648E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.262573E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1840559.75 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.158194E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.254697E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.209529E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.795295E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.233035E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31354.05 | 03-JAN-15:00 | 6986.42 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4624.81 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27809.90 | 01-FEB-08:09 | 6986.42 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4624.81 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27809.90 | 17-MAR-07:10 | 6986.42 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4624.81 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24555.14 | 03-APR-07:10 | 6986.42 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4624.81 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 21935.14 | 12-MAY-06:10 | 6986.42 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4264.78 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 20633.24 | 26-JUN-06:10 | 6986.42 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4264.78 | 01-JUN-10:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 21935.14 | 21-JUL-06:10 | 6986.42 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6570.07 | 14-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24555.14 | 17-AUG-07:10 | 6986.42 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6570.07 | 18-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26182.52 | 26-SEP-07:10 | 6986.42 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4264.78 | 01-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27809.90 | 02-OCT-07:10 | 6986.42 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4264.78 | 06-OCT-16:49 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31354.05 | 18-NOV-15:00 | 6986.42 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4624.81 | 15-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31354.05 | 01-DEC-15:00 | 6986.42 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4624.81 | 11-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 20633.24 | 6986.42 | 10112.62 | 0.00 | 4264.78 | 0.00 | 0.00 | |||||
Maximum of Months | 31354.05 | 6986.42 | 10112.62 | 0.00 | 6570.07 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2681.66 | 27-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2704.96 | 16-FEB-12:50 | 0.00 |
March | 847.99 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 2692.54 | 01-MAR-12:20 | 0.00 |
April | 0.04 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 2578.44 | 01-APR-11:50 | 0.00 |
May | 1489.03 | 10-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2358.55 | 02-MAY-11:20 | 0.00 |
June | 11754.34 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 2081.50 | 01-JUN-11:00 | 0.00 |
July | 13149.77 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1806.69 | 01-JUL-11:00 | 0.00 |
August | 11065.12 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1794.26 | 03-AUG-11:39 | 0.00 |
September | 8281.11 | 16-SEP-17:40 | 0.00 | 0.00 | 0.00 | 1805.85 | 29-SEP-11:30 | 0.00 |
October | 619.64 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2072.03 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2354.06 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2567.52 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1794.26 | 0.00 | ||
Maximum of Months | 13149.77 | 0.00 | 0.00 | 0.00 | 2704.96 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 51157.39 | 13-JAN-16:00 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44210.79 | 08-FEB-08:09 | 27809.90 | 10112.62 | 0.00 | 0.00 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44154.97 | 21-MAR-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40950.63 | 05-APR-07:19 | 24555.14 | 10112.62 | 0.00 | 0.00 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37302.59 | 11-MAY-07:19 | 21276.80 | 10112.62 | 0.00 | 0.00 | 4264.78 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36962.95 | 27-JUN-12:00 | 9061.34 | 10112.62 | 0.00 | 0.00 | 4264.78 | 0.00 | 0.00 | 11754.34 | 0.00 |
July | 42121.77 | 21-JUL-07:10 | 16371.08 | 10112.62 | 0.00 | 0.00 | 4264.78 | 0.00 | 0.00 | 9741.80 | 0.00 |
August | 43281.16 | 10-AUG-15:00 | 14720.12 | 10112.62 | 0.00 | 0.00 | 6570.07 | 0.00 | 0.00 | 10988.59 | 0.00 |
September | 43213.23 | 16-SEP-07:10 | 24555.14 | 10112.62 | 0.00 | 0.00 | 4264.78 | 0.00 | 0.00 | 2648.49 | 0.00 |
October | 43829.93 | 31-OCT-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 4264.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51150.37 | 30-NOV-16:40 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51155.48 | 29-DEC-16:49 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4624.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36962.95 | 9061.34 | 10112.62 | 0.00 | 0.00 | 4264.78 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51157.39 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 6570.07 | 0.00 | 0.00 | 11754.34 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 277503.04 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 293574.38 | 06-FEB-17:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 151919.38 | 05-MAR-01:30 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 118322.78 | 16-APR-03:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 14097.87 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3067.60 | 29-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 27169.01 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 66484.85 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 253833.25 | 09-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 293574.38 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 15.42 | 4.83 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
February | 31.17 | 15.20 | 5.33 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
March | 5.83 | 15.97 | 3.83 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
April | 1.83 | 15.96 | 1.00 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 17.21 | 0.50 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
November | 1.33 | 16.58 | 1.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
December | 15.17 | 15.62 | 5.00 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
Annual Sum or Average | 73.17 | 15.46 | 21.50 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.17 | 17.21 | 5.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 107.00 | 14.43 | 4.33 | 14.43 | 0.00 | 14.43 | 0.00 | 14.43 |
February | 99.83 | 14.34 | 3.83 | 14.33 | 0.00 | 14.33 | 0.00 | 14.33 |
March | 53.00 | 14.62 | 2.67 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
April | 14.33 | 14.81 | 0.83 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.31 | 0.00 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.35 | 0.00 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.38 | 0.00 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 14.98 | 0.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
November | 15.17 | 14.90 | 1.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
December | 100.67 | 14.47 | 4.00 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
Annual Sum or Average | 390.50 | 14.48 | 17.67 | 14.47 | 13.67 | 14.89 | 0.00 | 14.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.00 | 14.98 | 4.33 | 14.98 | 7.50 | 27.38 | 0.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 9.31 | 1.17 | 9.31 | 0.00 | 9.31 | 0.00 | 9.31 |
February | 2.83 | 9.25 | 2.83 | 9.25 | 0.00 | 9.25 | 0.00 | 9.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 9.27 | 4.00 | 9.27 | 0.00 | 9.27 | 0.00 | 9.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 9.31 | 2.83 | 9.31 | 0.00 | 9.31 | 0.00 | 9.31 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.71 | 300.00 | 20.71 | 300.00 | 20.71 |
February | 276.00 | 20.70 | 276.00 | 20.70 | 276.00 | 20.70 |
March | 324.00 | 20.94 | 286.83 | 20.82 | 286.83 | 20.78 |
April | 300.00 | 21.18 | 218.50 | 20.95 | 218.50 | 20.86 |
May | 284.00 | 22.86 | 35.33 | 22.58 | 35.33 | 22.35 |
June | 66.67 | 23.77 | 207.83 | 24.05 | 32.17 | 24.07 |
July | 74.17 | 24.64 | 299.67 | 24.32 | 74.17 | 24.37 |
August | 44.33 | 24.78 | 315.17 | 24.27 | 43.33 | 24.33 |
September | 72.50 | 23.57 | 164.33 | 23.91 | 19.83 | 23.95 |
October | 300.00 | 21.96 | 112.17 | 21.58 | 112.17 | 21.36 |
November | 288.00 | 20.84 | 267.17 | 20.78 | 267.17 | 20.76 |
December | 300.00 | 20.71 | 300.00 | 20.71 | 300.00 | 20.71 |
Annual Sum or Average | 2629.67 | 21.52 | 2783.00 | 21.72 | 1965.50 | 21.54 |
Minimum of Months | 44.33 | 20.70 | 35.33 | 20.70 | 19.83 | 20.70 |
Maximum of Months | 324.00 | 24.78 | 315.17 | 24.32 | 300.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.60 | 300.00 | 15.60 | 300.00 | 15.60 |
February | 276.00 | 15.58 | 276.00 | 15.58 | 276.00 | 15.58 |
March | 324.00 | 16.72 | 297.17 | 16.50 | 297.17 | 16.43 |
April | 300.00 | 18.16 | 266.33 | 17.96 | 266.33 | 17.88 |
May | 213.17 | 21.69 | 127.17 | 22.20 | 54.33 | 21.84 |
June | 154.00 | 26.27 | 281.00 | 26.32 | 137.83 | 26.39 |
July | 255.83 | 26.70 | 300.00 | 26.66 | 255.83 | 26.67 |
August | 229.83 | 26.67 | 322.83 | 26.61 | 229.83 | 26.63 |
September | 110.83 | 25.04 | 236.00 | 25.87 | 64.17 | 25.96 |
October | 298.00 | 20.04 | 189.17 | 19.53 | 189.17 | 19.31 |
November | 288.00 | 17.01 | 286.67 | 17.00 | 286.67 | 16.99 |
December | 300.00 | 15.69 | 300.00 | 15.69 | 300.00 | 15.69 |
Annual Sum or Average | 3049.67 | 19.62 | 3182.33 | 19.99 | 2657.33 | 19.76 |
Minimum of Months | 110.83 | 15.58 | 127.17 | 15.58 | 54.33 | 15.58 |
Maximum of Months | 324.00 | 26.70 | 322.83 | 26.66 | 300.00 | 26.67 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.03 | 300.00 | 10.03 | 300.00 | 10.03 |
February | 276.00 | 10.01 | 276.00 | 10.01 | 276.00 | 10.01 |
March | 324.00 | 11.13 | 324.00 | 11.13 | 324.00 | 11.13 |
April | 300.00 | 12.80 | 300.00 | 12.80 | 300.00 | 12.80 |
May | 312.00 | 18.70 | 232.83 | 18.29 | 232.83 | 18.13 |
June | 233.00 | 23.85 | 159.50 | 24.66 | 94.83 | 24.92 |
July | 260.83 | 28.56 | 300.00 | 28.38 | 260.83 | 28.44 |
August | 277.17 | 28.22 | 321.50 | 28.05 | 277.17 | 28.10 |
September | 172.17 | 23.03 | 141.83 | 23.78 | 53.17 | 23.82 |
October | 300.00 | 16.34 | 284.17 | 16.21 | 284.17 | 16.17 |
November | 288.00 | 11.56 | 288.00 | 11.56 | 288.00 | 11.56 |
December | 300.00 | 10.09 | 300.00 | 10.09 | 300.00 | 10.09 |
Annual Sum or Average | 3343.17 | 16.48 | 3227.83 | 16.50 | 2991.00 | 16.29 |
Minimum of Months | 172.17 | 10.01 | 141.83 | 10.01 | 53.17 | 10.01 |
Maximum of Months | 324.00 | 28.56 | 324.00 | 28.38 | 324.00 | 28.44 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 65966606.50 | 16876631.90 | 9.67 | 59045381.49 | 6921225.00 | 0.00 | 0.19 | 15-MAR-14:20 | 0.00 | 01-MAR-00:03 | 3294.04 | 15-MAR-15:10 | 3071.30 | 15-MAR-14:20 | 357.05 | 14-MAR-14:10 | 847.99 | 15-MAR-14:20 | 0.00 | 01-MAR-00:03 |
April | 118.38 | 30.39 | 0.33 | 116.21 | 2.18 | 0.00 | 0.00 | 08-APR-13:00 | 0.00 | 01-APR-00:10 | 0.14 | 08-APR-13:00 | 0.14 | 08-APR-13:00 | 0.00 | 08-APR-13:00 | 0.04 | 08-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.435183E+09 | 0.108452E+09 | 47.14 | 0.412048E+09 | 23134389.89 | 0.00 | 0.32 | 10-MAY-15:10 | 0.00 | 01-MAY-00:10 | 5948.42 | 10-MAY-15:10 | 5495.13 | 23-MAY-14:50 | 993.28 | 10-MAY-15:10 | 1489.03 | 10-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 0.415401E+10 | 0.100550E+10 | 185.66 | 0.321309E+10 | 0.940922E+09 | 0.00 | 1.00 | 02-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24086.78 | 27-JUN-07:02 | 16116.19 | 03-JUN-07:02 | 12026.71 | 27-JUN-07:02 | 5035.43 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.879988E+10 | 0.210627E+10 | 253.42 | 0.627745E+10 | 0.252243E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 25011.31 | 21-JUL-06:02 | 16143.44 | 12-JUL-07:03 | 13521.42 | 29-JUL-07:02 | 5230.92 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.726731E+10 | 0.175899E+10 | 250.83 | 0.580026E+10 | 0.146705E+10 | 0.00 | 1.00 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24641.10 | 14-AUG-06:02 | 16021.96 | 18-AUG-07:02 | 13374.37 | 14-AUG-06:03 | 5106.60 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.262194E+10 | 0.633024E+09 | 140.91 | 0.199117E+10 | 0.630775E+09 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22798.75 | 14-SEP-07:02 | 13800.17 | 02-SEP-07:02 | 11138.44 | 14-SEP-07:04 | 4851.19 | 14-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 26276774.92 | 6626924.51 | 5.50 | 25392443.93 | 884330.99 | 0.00 | 0.14 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2467.85 | 11-OCT-15:00 | 2345.48 | 11-OCT-15:00 | 164.55 | 11-OCT-16:00 | 619.64 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.233706E+11 | 0.563573E+10 | 893.46 | 0.177785E+11 | 0.559212E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.879988E+10 | 0.210627E+10 | 253.42 | 0.627745E+10 | 0.252243E+10 | 0.00 | 1.00 | 0.00 | 25011.31 | 16143.44 | 13521.42 | 5230.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 1937.27 | 504.73 | 2.17 | 1799.83 | 137.44 | 0.00 | 0.00 | 26-MAY-16:00 | 0.00 | 01-MAY-00:10 | 0.86 | 26-MAY-16:00 | 0.82 | 26-MAY-16:00 | 0.05 | 31-MAY-13:40 | 0.22 | 26-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.528114E+10 | 0.131084E+10 | 97.99 | 0.378634E+10 | 0.149481E+10 | 0.00 | 1.00 | 11-JUN-11:35 | 0.00 | 01-JUN-00:10 | 81231.07 | 27-JUN-17:12 | 63287.43 | 30-JUN-17:11 | 43038.03 | 27-JUN-20:15 | 17635.87 | 27-JUN-17:12 | 0.00 | 01-JUN-00:10 |
July | 0.164408E+11 | 0.405600E+10 | 229.84 | 0.113779E+11 | 0.506293E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 84427.76 | 20-JUL-23:15 | 64116.11 | 06-JUL-18:05 | 47283.01 | 20-JUL-21:55 | 18007.98 | 21-JUL-03:55 | 0.00 | 01-JUL-00:10 |
August | 0.112447E+11 | 0.284514E+10 | 194.90 | 0.896487E+10 | 0.227983E+10 | 0.00 | 1.00 | 01-AUG-17:11 | 0.00 | 01-AUG-00:10 | 80279.51 | 14-AUG-23:45 | 64918.14 | 16-AUG-17:12 | 38921.52 | 14-AUG-23:45 | 17594.64 | 13-AUG-16:55 | 0.00 | 01-AUG-00:10 |
September | 0.108495E+10 | 0.274456E+09 | 40.22 | 0.801673E+09 | 0.283280E+09 | 0.00 | 1.00 | 16-SEP-17:12 | 0.00 | 01-SEP-00:10 | 74832.81 | 16-SEP-17:12 | 57495.79 | 21-SEP-17:25 | 28373.35 | 17-SEP-15:35 | 16657.76 | 16-SEP-17:12 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.340516E+11 | 0.848644E+10 | 565.13 | 0.249307E+11 | 0.912085E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.164408E+11 | 0.405600E+10 | 229.84 | 0.113779E+11 | 0.506293E+10 | 0.00 | 1.00 | 0.00 | 84427.76 | 64918.14 | 47283.01 | 18007.98 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.24 | 12.30 | 39.94 | 17.72 | 155.38 | 0.00 | 0.00 | 0.00 |
February | 84.65 | 21.85 | 62.80 | 43.50 | 145.27 | 0.00 | 0.00 | 0.00 |
March | 133.07 | 57.20 | 75.86 | 119.14 | 96.26 | 0.00 | 0.00 | 0.00 |
April | 161.87 | 66.25 | 95.62 | 168.23 | 67.37 | 0.00 | 0.00 | 0.00 |
May | 191.10 | 86.29 | 104.81 | 217.38 | 53.35 | 0.00 | 0.00 | 0.00 |
June | 230.87 | 108.62 | 122.26 | 280.82 | 45.18 | 0.00 | 0.00 | 0.00 |
July | 206.17 | 90.26 | 115.90 | 263.65 | 35.54 | 0.00 | 0.00 | 0.00 |
August | 186.26 | 78.99 | 107.27 | 234.50 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 146.66 | 63.37 | 83.29 | 167.07 | 64.12 | 0.00 | 0.00 | 0.00 |
October | 95.04 | 33.48 | 61.56 | 89.95 | 76.41 | 0.00 | 0.00 | 0.00 |
November | 55.86 | 15.86 | 40.00 | 39.79 | 91.01 | 0.00 | 0.00 | 0.00 |
December | 48.73 | 10.56 | 38.17 | 16.89 | 148.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.93 | 53.91 | 79.02 | 138.72 | 85.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.73 | 10.56 | 38.17 | 16.89 | 35.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.87 | 108.62 | 122.26 | 280.82 | 155.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.24 | 12.30 | 39.94 | 17.72 | 155.38 | 0.00 | 0.00 | 0.00 |
February | 84.65 | 21.85 | 62.80 | 43.50 | 145.27 | 0.00 | 0.00 | 0.00 |
March | 133.07 | 57.20 | 75.86 | 119.14 | 96.26 | 0.00 | 0.00 | 0.00 |
April | 161.87 | 66.25 | 95.62 | 168.23 | 67.37 | 0.00 | 0.00 | 0.00 |
May | 191.10 | 86.29 | 104.81 | 217.38 | 53.35 | 0.00 | 0.00 | 0.00 |
June | 230.87 | 108.62 | 122.26 | 280.82 | 45.18 | 0.00 | 0.00 | 0.00 |
July | 206.17 | 90.26 | 115.90 | 263.65 | 35.54 | 0.00 | 0.00 | 0.00 |
August | 186.26 | 78.99 | 107.27 | 234.50 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 146.66 | 63.37 | 83.29 | 167.07 | 64.12 | 0.00 | 0.00 | 0.00 |
October | 95.04 | 33.48 | 61.56 | 89.95 | 76.41 | 0.00 | 0.00 | 0.00 |
November | 55.86 | 15.86 | 40.00 | 39.79 | 91.01 | 0.00 | 0.00 | 0.00 |
December | 48.73 | 10.56 | 38.17 | 16.89 | 148.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.93 | 53.91 | 79.02 | 138.72 | 85.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.73 | 10.56 | 38.17 | 16.89 | 35.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.87 | 108.62 | 122.26 | 280.82 | 155.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.37 | 0.00 | 19.37 | 0.67 | 96.77 | 0.00 | 0.00 | 0.00 |
February | 29.51 | 0.00 | 29.51 | 3.63 | 89.65 | 0.00 | 0.00 | 0.00 |
March | 35.80 | 0.00 | 35.80 | 15.99 | 60.40 | 0.00 | 0.00 | 0.00 |
April | 45.64 | 0.22 | 45.42 | 31.74 | 39.85 | 0.00 | 0.00 | 0.00 |
May | 53.02 | 2.28 | 50.73 | 45.98 | 29.65 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 5.42 | 58.32 | 66.38 | 24.63 | 0.00 | 0.00 | 0.00 |
July | 59.36 | 4.04 | 55.33 | 69.67 | 19.35 | 0.00 | 0.00 | 0.00 |
August | 51.40 | 0.99 | 50.40 | 56.79 | 25.40 | 0.00 | 0.00 | 0.00 |
September | 38.95 | 0.02 | 38.94 | 33.53 | 38.11 | 0.00 | 0.00 | 0.00 |
October | 29.11 | 0.00 | 29.11 | 17.01 | 45.97 | 0.00 | 0.00 | 0.00 |
November | 19.56 | 0.00 | 19.56 | 6.65 | 54.64 | 0.00 | 0.00 | 0.00 |
December | 18.13 | 0.00 | 18.13 | 0.75 | 91.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.67 | 1.09 | 37.58 | 29.21 | 51.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.13 | 0.00 | 18.13 | 0.67 | 19.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.74 | 5.42 | 58.32 | 69.67 | 96.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.37 | 0.00 | 19.37 | 0.67 | 96.77 | 0.00 | 0.00 | 0.00 |
February | 29.51 | 0.00 | 29.51 | 3.63 | 89.65 | 0.00 | 0.00 | 0.00 |
March | 35.80 | 0.00 | 35.80 | 15.99 | 60.40 | 0.00 | 0.00 | 0.00 |
April | 45.64 | 0.22 | 45.42 | 31.74 | 39.85 | 0.00 | 0.00 | 0.00 |
May | 53.01 | 2.28 | 50.73 | 45.98 | 29.65 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 5.42 | 58.32 | 66.37 | 24.63 | 0.00 | 0.00 | 0.00 |
July | 59.36 | 4.04 | 55.32 | 69.66 | 19.35 | 0.00 | 0.00 | 0.00 |
August | 51.39 | 0.99 | 50.40 | 56.79 | 25.40 | 0.00 | 0.00 | 0.00 |
September | 38.95 | 0.02 | 38.93 | 33.53 | 38.11 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 17.01 | 45.97 | 0.00 | 0.00 | 0.00 |
November | 19.56 | 0.00 | 19.56 | 6.65 | 54.64 | 0.00 | 0.00 | 0.00 |
December | 18.13 | 0.00 | 18.13 | 0.75 | 91.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.67 | 1.09 | 37.58 | 29.21 | 51.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.13 | 0.00 | 18.13 | 0.67 | 19.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.74 | 5.42 | 58.32 | 69.66 | 96.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 20.20 | 73.24 | 0.00 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 42.33 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 89.04 | 49.38 | 3.83 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 129.07 | 34.79 | 0.00 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 171.70 | 29.96 | 0.33 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 204.75 | 27.26 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 196.48 | 22.26 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 164.14 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 113.47 | 36.94 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 64.22 | 39.33 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 30.60 | 44.24 | 0.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 16.72 | 69.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 103.89 | 43.54 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 16.72 | 22.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 204.75 | 73.24 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.82 | 10.70 | 25.12 | 27.06 | 54.51 | 2.83 | 0.00 | 0.00 |
February | 56.74 | 16.63 | 40.11 | 50.68 | 53.00 | 0.00 | 0.00 | 0.00 |
March | 88.47 | 45.88 | 42.59 | 99.08 | 35.63 | 31.33 | 0.00 | 0.00 |
April | 116.46 | 61.94 | 54.52 | 140.08 | 23.82 | 3.67 | 0.00 | 0.00 |
May | 149.21 | 91.98 | 57.23 | 181.39 | 22.71 | 5.50 | 0.00 | 0.00 |
June | 172.62 | 108.27 | 64.36 | 210.90 | 23.42 | 0.00 | 0.00 | 0.00 |
July | 160.55 | 97.68 | 62.86 | 194.97 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 136.53 | 75.95 | 60.58 | 162.78 | 29.48 | 0.00 | 0.00 | 0.00 |
September | 101.00 | 54.81 | 46.19 | 117.42 | 33.34 | 0.00 | 0.00 | 0.00 |
October | 63.00 | 27.17 | 35.83 | 69.95 | 31.55 | 0.00 | 0.00 | 0.00 |
November | 36.26 | 11.12 | 25.14 | 37.86 | 29.44 | 12.00 | 0.00 | 0.00 |
December | 31.50 | 6.76 | 24.74 | 23.30 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.88 | 50.93 | 44.95 | 109.92 | 34.23 | 55.33 | 0.00 | 0.00 |
Minimum of Months | 31.50 | 6.76 | 24.74 | 23.30 | 22.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.62 | 108.27 | 64.36 | 210.90 | 54.51 | 31.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139919E+09 | 32952487.93 | 0.106966E+09 | 47452110.00 | 0.416158E+09 |
February | 0.204775E+09 | 52848294.32 | 0.151927E+09 | 0.105240E+09 | 0.351432E+09 |
March | 0.356407E+09 | 0.153211E+09 | 0.203196E+09 | 0.319115E+09 | 0.257836E+09 |
April | 0.419570E+09 | 0.171726E+09 | 0.247844E+09 | 0.436055E+09 | 0.174629E+09 |
May | 0.511831E+09 | 0.231114E+09 | 0.280717E+09 | 0.582236E+09 | 0.142885E+09 |
June | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.727884E+09 | 0.117102E+09 |
July | 0.552197E+09 | 0.241761E+09 | 0.310436E+09 | 0.706151E+09 | 95180513.73 |
August | 0.498887E+09 | 0.211580E+09 | 0.287307E+09 | 0.628079E+09 | 0.120463E+09 |
September | 0.380150E+09 | 0.164254E+09 | 0.215896E+09 | 0.433040E+09 | 0.166186E+09 |
October | 0.254548E+09 | 89664914.14 | 0.164883E+09 | 0.240913E+09 | 0.204669E+09 |
November | 0.144786E+09 | 41102820.45 | 0.103683E+09 | 0.103146E+09 | 0.235902E+09 |
December | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 45231989.27 | 0.398230E+09 |
Annual Sum or Average | 0.419201E+10 | 0.170003E+10 | 0.249198E+10 | 0.437454E+10 | 0.268067E+10 |
Minimum of Months | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 45231989.27 | 95180513.73 |
Maximum of Months | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.727884E+09 | 0.416158E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139919E+09 | 32952487.93 | 0.106966E+09 | 47452110.00 | 0.416158E+09 |
February | 0.204775E+09 | 52848294.32 | 0.151927E+09 | 0.105240E+09 | 0.351432E+09 |
March | 0.356407E+09 | 0.153211E+09 | 0.203196E+09 | 0.319115E+09 | 0.257836E+09 |
April | 0.419570E+09 | 0.171726E+09 | 0.247844E+09 | 0.436055E+09 | 0.174629E+09 |
May | 0.511831E+09 | 0.231114E+09 | 0.280717E+09 | 0.582236E+09 | 0.142885E+09 |
June | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.727884E+09 | 0.117102E+09 |
July | 0.552197E+09 | 0.241761E+09 | 0.310436E+09 | 0.706151E+09 | 95180513.73 |
August | 0.498887E+09 | 0.211580E+09 | 0.287307E+09 | 0.628079E+09 | 0.120463E+09 |
September | 0.380150E+09 | 0.164254E+09 | 0.215896E+09 | 0.433040E+09 | 0.166186E+09 |
October | 0.254548E+09 | 89664914.14 | 0.164883E+09 | 0.240913E+09 | 0.204669E+09 |
November | 0.144786E+09 | 41102820.45 | 0.103683E+09 | 0.103146E+09 | 0.235902E+09 |
December | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 45231989.27 | 0.398230E+09 |
Annual Sum or Average | 0.419201E+10 | 0.170003E+10 | 0.249198E+10 | 0.437454E+10 | 0.268067E+10 |
Minimum of Months | 0.130516E+09 | 28279684.90 | 0.102236E+09 | 45231989.27 | 95180513.73 |
Maximum of Months | 0.598424E+09 | 0.281536E+09 | 0.316888E+09 | 0.727884E+09 | 0.416158E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51883723.12 | 0.00 | 51883723.12 | 1790717.12 | 0.259199E+09 |
February | 71401207.49 | 0.00 | 71401207.49 | 8791721.57 | 0.216892E+09 |
March | 95882380.03 | 3395.69 | 95878984.34 | 42835545.73 | 0.161767E+09 |
April | 0.118292E+09 | 570344.86 | 0.117722E+09 | 82268781.55 | 0.103281E+09 |
May | 0.141998E+09 | 6114251.01 | 0.135883E+09 | 0.123156E+09 | 79406774.24 |
June | 0.165215E+09 | 14048294.05 | 0.151167E+09 | 0.172048E+09 | 63846769.85 |
July | 0.159000E+09 | 10816116.12 | 0.148184E+09 | 0.186595E+09 | 51818114.83 |
August | 0.137658E+09 | 2657383.74 | 0.135001E+09 | 0.152117E+09 | 68038772.18 |
September | 0.100967E+09 | 44682.67 | 0.100922E+09 | 86912921.86 | 98785070.30 |
October | 77956163.66 | 0.00 | 77956163.66 | 45555611.55 | 0.123118E+09 |
November | 50694748.92 | 0.00 | 50694748.92 | 17231639.89 | 0.141615E+09 |
December | 48561592.26 | 0.00 | 48561592.26 | 2004854.06 | 0.244941E+09 |
Annual Sum or Average | 0.121951E+10 | 34254468.14 | 0.118526E+10 | 0.921307E+09 | 0.161271E+10 |
Minimum of Months | 48561592.26 | 0.00 | 48561592.26 | 1790717.12 | 51818114.83 |
Maximum of Months | 0.165215E+09 | 14048294.05 | 0.151167E+09 | 0.186595E+09 | 0.259199E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51881948.64 | 0.00 | 51881948.64 | 1790318.54 | 0.259200E+09 |
February | 71398776.49 | 0.00 | 71398776.49 | 8790253.04 | 0.216893E+09 |
March | 95879392.80 | 3395.53 | 95875997.27 | 42832759.66 | 0.161767E+09 |
April | 0.118289E+09 | 570318.12 | 0.117718E+09 | 82264816.11 | 0.103281E+09 |
May | 0.141994E+09 | 6113964.42 | 0.135880E+09 | 0.123151E+09 | 79406460.38 |
June | 0.165210E+09 | 14047635.58 | 0.151163E+09 | 0.172041E+09 | 63846383.27 |
July | 0.158995E+09 | 10815609.16 | 0.148180E+09 | 0.186589E+09 | 51817684.74 |
August | 0.137654E+09 | 2657259.19 | 0.134996E+09 | 0.152112E+09 | 68038389.19 |
September | 0.100964E+09 | 44680.58 | 0.100919E+09 | 86909486.83 | 98784696.50 |
October | 77953629.82 | 0.00 | 77953629.82 | 45552998.19 | 0.123117E+09 |
November | 50693011.42 | 0.00 | 50693011.42 | 17230335.70 | 0.141615E+09 |
December | 48559892.96 | 0.00 | 48559892.96 | 2004466.10 | 0.244942E+09 |
Annual Sum or Average | 0.121947E+10 | 34252862.59 | 0.118522E+10 | 0.921268E+09 | 0.161271E+10 |
Minimum of Months | 48559892.96 | 0.00 | 48559892.96 | 1790318.54 | 51817684.74 |
Maximum of Months | 0.165210E+09 | 14047635.58 | 0.151163E+09 | 0.186589E+09 | 0.259200E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 54110027.00 | 0.196175E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.102397E+09 | 0.169916E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.238482E+09 | 0.132246E+09 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.334540E+09 | 90187064.32 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.459894E+09 | 80251630.79 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.530721E+09 | 70659185.94 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.526259E+09 | 59616359.90 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.439621E+09 | 72502908.07 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.294110E+09 | 95737575.01 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.172006E+09 | 0.105348E+09 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 79319306.32 | 0.114681E+09 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 44789988.82 | 0.185687E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.327625E+10 | 0.137301E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 44789988.82 | 59616359.90 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.530721E+09 | 0.196175E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95935596.03 | 28652938.24 | 67282657.79 | 72470543.73 | 0.145993E+09 |
February | 0.137257E+09 | 40220934.97 | 97035733.31 | 0.122609E+09 | 0.128216E+09 |
March | 0.236951E+09 | 0.122877E+09 | 0.114074E+09 | 0.265389E+09 | 95435801.52 |
April | 0.301872E+09 | 0.160559E+09 | 0.141313E+09 | 0.363093E+09 | 61736496.89 |
May | 0.399652E+09 | 0.246356E+09 | 0.153296E+09 | 0.485840E+09 | 60822878.71 |
June | 0.447436E+09 | 0.280626E+09 | 0.166810E+09 | 0.546648E+09 | 60709264.58 |
July | 0.430008E+09 | 0.261631E+09 | 0.168377E+09 | 0.522213E+09 | 65646748.92 |
August | 0.365673E+09 | 0.203413E+09 | 0.162260E+09 | 0.435999E+09 | 78964452.34 |
September | 0.261790E+09 | 0.142074E+09 | 0.119716E+09 | 0.304346E+09 | 86427519.72 |
October | 0.168744E+09 | 72776279.30 | 95967969.14 | 0.187367E+09 | 84512041.80 |
November | 93979969.59 | 28822863.05 | 65157106.54 | 98138756.89 | 76314888.55 |
December | 84359973.07 | 18103988.55 | 66255984.51 | 62408175.29 | 0.134641E+09 |
Annual Sum or Average | 0.302366E+10 | 0.160611E+10 | 0.141754E+10 | 0.346652E+10 | 0.107942E+10 |
Minimum of Months | 84359973.07 | 18103988.55 | 65157106.54 | 62408175.29 | 60709264.58 |
Maximum of Months | 0.447436E+09 | 0.280626E+09 | 0.168377E+09 | 0.546648E+09 | 0.145993E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.05 | 497.58 | 143.22 | 24.61 | 118.61 | 0.00 | 0.00 |
February | 86.90 | 462.47 | 228.32 | 43.69 | 184.63 | 0.00 | 0.00 |
March | 263.01 | 306.06 | 337.73 | 114.41 | 223.32 | 0.00 | 0.00 |
April | 398.16 | 212.65 | 415.02 | 132.94 | 282.07 | 0.00 | 0.00 |
May | 525.05 | 164.31 | 488.22 | 177.14 | 311.08 | 0.00 | 0.00 |
June | 691.05 | 136.28 | 589.23 | 228.07 | 361.15 | 0.00 | 0.00 |
July | 663.96 | 107.10 | 531.06 | 188.60 | 342.46 | 0.00 | 0.00 |
August | 581.72 | 139.89 | 475.32 | 159.97 | 315.34 | 0.00 | 0.00 |
September | 399.79 | 203.05 | 371.23 | 126.77 | 244.46 | 0.00 | 0.00 |
October | 211.93 | 242.78 | 248.28 | 66.95 | 181.33 | 0.00 | 0.00 |
November | 90.38 | 288.79 | 150.83 | 31.72 | 119.12 | 0.00 | 0.00 |
December | 29.19 | 474.18 | 133.72 | 21.12 | 112.60 | 0.00 | 0.00 |
Annual Sum or Average | 332.24 | 268.66 | 343.20 | 109.99 | 233.21 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 107.10 | 133.72 | 21.12 | 112.60 | 0.00 | 0.00 |
Maximum of Months | 691.05 | 497.58 | 589.23 | 228.07 | 361.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 343.44 | 1245.14 | 608.91 | 181.86 | 427.05 | 0.00 | 0.00 |
February | 719.55 | 1194.02 | 964.52 | 282.64 | 681.88 | 0.00 | 0.00 |
March | 1513.66 | 839.38 | 1503.95 | 779.91 | 724.03 | 0.00 | 0.00 |
April | 2194.13 | 591.50 | 1979.87 | 1053.05 | 926.82 | 0.00 | 0.00 |
May | 2918.98 | 509.36 | 2536.62 | 1563.64 | 972.98 | 0.00 | 0.00 |
June | 3480.81 | 463.43 | 2934.57 | 1840.53 | 1094.04 | 0.00 | 0.00 |
July | 3340.20 | 378.39 | 2729.29 | 1660.59 | 1068.70 | 0.00 | 0.00 |
August | 2790.31 | 460.18 | 2320.95 | 1291.08 | 1029.87 | 0.00 | 0.00 |
September | 1928.96 | 627.91 | 1716.98 | 931.81 | 785.17 | 0.00 | 0.00 |
October | 1091.73 | 668.65 | 1071.03 | 461.92 | 609.12 | 0.00 | 0.00 |
November | 520.23 | 752.15 | 616.38 | 189.04 | 427.34 | 0.00 | 0.00 |
December | 284.29 | 1178.57 | 535.44 | 114.91 | 420.53 | 0.00 | 0.00 |
Annual Sum or Average | 1766.12 | 740.14 | 1629.95 | 865.80 | 764.15 | 0.00 | 0.00 |
Minimum of Months | 284.29 | 378.39 | 535.44 | 114.91 | 420.53 | 0.00 | 0.00 |
Maximum of Months | 3480.81 | 1245.14 | 2934.57 | 1840.53 | 1094.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4767.30 | 19227.81 | 1719.28 | 513.49 | 1205.78 | 0.00 | 0.00 |
February | 8535.44 | 20625.31 | 2723.35 | 798.03 | 1925.31 | 0.00 | 0.00 |
March | 15795.77 | 11035.66 | 4246.44 | 2202.10 | 2044.33 | 0.00 | 0.00 |
April | 22314.92 | 4798.86 | 5590.22 | 2973.32 | 2616.90 | 0.00 | 0.00 |
May | 29031.58 | 3276.04 | 7162.22 | 4414.99 | 2747.24 | 0.00 | 0.00 |
June | 36317.83 | 3402.55 | 8285.85 | 5196.78 | 3089.07 | 0.00 | 0.00 |
July | 39583.08 | 3931.33 | 7706.24 | 4688.73 | 3017.51 | 0.00 | 0.00 |
August | 29074.87 | 4624.73 | 6553.28 | 3645.40 | 2907.88 | 0.00 | 0.00 |
September | 17267.10 | 4977.87 | 4847.95 | 2631.00 | 2216.96 | 0.00 | 0.00 |
October | 10691.71 | 5041.06 | 3024.09 | 1304.23 | 1719.86 | 0.00 | 0.00 |
November | 5798.58 | 6771.05 | 1740.37 | 533.76 | 1206.61 | 0.00 | 0.00 |
December | 4239.81 | 18213.54 | 1511.83 | 324.44 | 1187.38 | 0.00 | 0.00 |
Annual Sum or Average | 18681.24 | 8772.26 | 4602.22 | 2444.62 | 2157.60 | 0.00 | 0.00 |
Minimum of Months | 4239.81 | 3276.04 | 1511.83 | 324.44 | 1187.38 | 0.00 | 0.00 |
Maximum of Months | 39583.08 | 20625.31 | 8285.85 | 5196.78 | 3089.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 80475955.24 | 0.133271E+10 | 0.383603E+09 | 65904975.85 | 0.317698E+09 | 0.00 | 0.00 |
February | 0.210221E+09 | 0.111881E+10 | 0.552350E+09 | 0.105697E+09 | 0.446653E+09 | 0.00 | 0.00 |
March | 0.704452E+09 | 0.819758E+09 | 0.904575E+09 | 0.306429E+09 | 0.598146E+09 | 0.00 | 0.00 |
April | 0.103202E+10 | 0.551200E+09 | 0.107572E+10 | 0.344592E+09 | 0.731128E+09 | 0.00 | 0.00 |
May | 0.140629E+10 | 0.440098E+09 | 0.130765E+10 | 0.474456E+09 | 0.833198E+09 | 0.00 | 0.00 |
June | 0.179119E+10 | 0.353233E+09 | 0.152727E+10 | 0.591168E+09 | 0.936105E+09 | 0.00 | 0.00 |
July | 0.177835E+10 | 0.286861E+09 | 0.142239E+10 | 0.505155E+09 | 0.917235E+09 | 0.00 | 0.00 |
August | 0.155808E+10 | 0.374693E+09 | 0.127309E+10 | 0.428475E+09 | 0.844611E+09 | 0.00 | 0.00 |
September | 0.103626E+10 | 0.526298E+09 | 0.962232E+09 | 0.328598E+09 | 0.633634E+09 | 0.00 | 0.00 |
October | 0.567632E+09 | 0.650272E+09 | 0.665005E+09 | 0.179330E+09 | 0.485675E+09 | 0.00 | 0.00 |
November | 0.234273E+09 | 0.748553E+09 | 0.390959E+09 | 82205640.90 | 0.308753E+09 | 0.00 | 0.00 |
December | 78171385.94 | 0.127004E+10 | 0.358153E+09 | 56559369.81 | 0.301594E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104774E+11 | 0.847252E+10 | 0.108230E+11 | 0.346857E+10 | 0.735443E+10 | 0.00 | 0.00 |
Minimum of Months | 78171385.94 | 0.286861E+09 | 0.358153E+09 | 56559369.81 | 0.301594E+09 | 0.00 | 0.00 |
Maximum of Months | 0.179119E+10 | 0.133271E+10 | 0.152727E+10 | 0.591168E+09 | 0.936105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.919870E+09 | 0.333498E+10 | 0.163091E+10 | 0.487100E+09 | 0.114381E+10 | 0.00 | 0.00 |
February | 0.174075E+10 | 0.288857E+10 | 0.233336E+10 | 0.683756E+09 | 0.164961E+10 | 0.00 | 0.00 |
March | 0.405420E+10 | 0.224819E+10 | 0.402817E+10 | 0.208891E+10 | 0.193925E+10 | 0.00 | 0.00 |
April | 0.568717E+10 | 0.153318E+10 | 0.513182E+10 | 0.272951E+10 | 0.240231E+10 | 0.00 | 0.00 |
May | 0.781821E+10 | 0.136428E+10 | 0.679409E+10 | 0.418805E+10 | 0.260603E+10 | 0.00 | 0.00 |
June | 0.902225E+10 | 0.120121E+10 | 0.760641E+10 | 0.477065E+10 | 0.283576E+10 | 0.00 | 0.00 |
July | 0.894640E+10 | 0.101348E+10 | 0.731014E+10 | 0.444773E+10 | 0.286241E+10 | 0.00 | 0.00 |
August | 0.747356E+10 | 0.123255E+10 | 0.621644E+10 | 0.345803E+10 | 0.275842E+10 | 0.00 | 0.00 |
September | 0.499987E+10 | 0.162754E+10 | 0.445042E+10 | 0.241526E+10 | 0.203517E+10 | 0.00 | 0.00 |
October | 0.292410E+10 | 0.179092E+10 | 0.286865E+10 | 0.123720E+10 | 0.163146E+10 | 0.00 | 0.00 |
November | 0.134843E+10 | 0.194958E+10 | 0.159766E+10 | 0.489989E+09 | 0.110767E+10 | 0.00 | 0.00 |
December | 0.761430E+09 | 0.315668E+10 | 0.143412E+10 | 0.307768E+09 | 0.112635E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.556962E+11 | 0.233411E+11 | 0.514022E+11 | 0.273039E+11 | 0.240982E+11 | 0.00 | 0.00 |
Minimum of Months | 0.761430E+09 | 0.101348E+10 | 0.143412E+10 | 0.307768E+09 | 0.110767E+10 | 0.00 | 0.00 |
Maximum of Months | 0.902225E+10 | 0.333498E+10 | 0.760641E+10 | 0.477065E+10 | 0.286241E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127687E+11 | 0.514998E+11 | 0.460491E+10 | 0.137534E+10 | 0.322957E+10 | 0.00 | 0.00 |
February | 0.206489E+11 | 0.498968E+11 | 0.658832E+10 | 0.193060E+10 | 0.465772E+10 | 0.00 | 0.00 |
March | 0.423074E+11 | 0.295579E+11 | 0.113737E+11 | 0.589811E+10 | 0.547554E+10 | 0.00 | 0.00 |
April | 0.578403E+11 | 0.124387E+11 | 0.144898E+11 | 0.770685E+10 | 0.678300E+10 | 0.00 | 0.00 |
May | 0.777582E+11 | 0.877454E+10 | 0.191833E+11 | 0.118251E+11 | 0.735821E+10 | 0.00 | 0.00 |
June | 0.941358E+11 | 0.881941E+10 | 0.214769E+11 | 0.134701E+11 | 0.800686E+10 | 0.00 | 0.00 |
July | 0.106019E+12 | 0.105297E+11 | 0.206404E+11 | 0.125583E+11 | 0.808210E+10 | 0.00 | 0.00 |
August | 0.778741E+11 | 0.123869E+11 | 0.175523E+11 | 0.976384E+10 | 0.778847E+10 | 0.00 | 0.00 |
September | 0.447563E+11 | 0.129026E+11 | 0.125659E+11 | 0.681955E+10 | 0.574635E+10 | 0.00 | 0.00 |
October | 0.286367E+11 | 0.135020E+11 | 0.809972E+10 | 0.349326E+10 | 0.460646E+10 | 0.00 | 0.00 |
November | 0.150299E+11 | 0.175506E+11 | 0.451104E+10 | 0.138350E+10 | 0.312754E+10 | 0.00 | 0.00 |
December | 0.113559E+11 | 0.487832E+11 | 0.404928E+10 | 0.868991E+09 | 0.318029E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.589132E+12 | 0.276642E+12 | 0.145136E+12 | 0.770935E+11 | 0.680421E+11 | 0.00 | 0.00 |
Minimum of Months | 0.113559E+11 | 0.877454E+10 | 0.404928E+10 | 0.868991E+09 | 0.312754E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106019E+12 | 0.514998E+11 | 0.214769E+11 | 0.134701E+11 | 0.808210E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.101132E+10 | -922986360.5 | 0.00 | 0.00 | 744.00 | 0.00 | -88335275.6 | 58.99 | 0.00 | 0.00 |
February | 0.939837E+09 | -860108442.5 | 0.00 | 0.00 | 672.00 | 0.00 | -79728099.8 | 58.99 | 0.00 | 0.00 |
March | 0.107807E+10 | -991506207.4 | 0.00 | 0.00 | 744.00 | 0.00 | -86559131.8 | 58.99 | 0.00 | 0.00 |
April | 0.966944E+09 | -884831537.9 | 0.00 | 0.00 | 720.00 | 0.00 | -82112680.5 | 58.99 | 0.00 | 0.00 |
May | 0.946015E+09 | -868066792.4 | 0.00 | 0.00 | 744.00 | 0.00 | -77947777.2 | 58.99 | 0.00 | 0.00 |
June | 0.881463E+09 | -811341181.3 | 0.00 | 0.00 | 720.00 | 0.00 | -70121389.8 | 58.99 | 0.00 | 0.00 |
July | 0.816410E+09 | -745940894.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70469551.1 | 58.99 | 0.00 | 0.00 |
August | 0.857143E+09 | -786004416.4 | 0.00 | 0.00 | 744.00 | 0.00 | -71138826.4 | 59.00 | 0.00 | 0.00 |
September | 0.814873E+09 | -744037897.8 | 0.00 | 0.00 | 720.00 | 0.00 | -70835324.7 | 59.00 | 0.00 | 0.00 |
October | 0.864756E+09 | -783065292.0 | 0.00 | 0.00 | 744.00 | 0.00 | -81690630.9 | 58.99 | 0.00 | 0.00 |
November | 0.884194E+09 | -800541348.3 | 0.00 | 0.00 | 720.00 | 0.00 | -83652379.5 | 58.99 | 0.00 | 0.00 |
December | 0.972261E+09 | -884020240.4 | 0.00 | 0.00 | 744.00 | 0.00 | -88240699.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.110333E+11 | -0.100825E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -950831766.5 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.814873E+09 | -991506207.4 | 0.00 | 0.00 | 672.00 | 0.00 | -88335275.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.107807E+10 | -744037897.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70121389.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.72 | 0.26 | 25-JAN-11:50 | 194.69 | 0.00 | 0.00 | 20.17 | 370.71 | 0.00 | 0.00 | 16.17 |
February | 262.50 | 0.59 | 0.26 | 02-FEB-11:30 | 273.32 | 0.00 | 0.00 | 110.83 | 343.38 | 0.00 | 0.00 | 56.00 |
March | 339.33 | 0.59 | 0.26 | 02-MAR-11:50 | 283.00 | 0.00 | 0.00 | 136.00 | 216.53 | 0.00 | 0.00 | 78.00 |
April | 371.17 | 0.57 | 0.26 | 01-APR-10:50 | 321.87 | 0.00 | 0.00 | 181.00 | 243.41 | 0.00 | 0.00 | 114.67 |
May | 332.17 | 0.54 | 0.26 | 01-MAY-10:09 | 345.78 | 0.00 | 0.00 | 212.67 | 908.56 | 0.00 | 0.00 | 145.83 |
June | 430.67 | 0.53 | 0.26 | 01-JUN-09:09 | 367.22 | 0.00 | 0.00 | 235.50 | 1732.37 | 0.00 | 0.00 | 182.17 |
July | 439.00 | 0.53 | 0.26 | 01-JUL-09:50 | 363.85 | 0.00 | 0.00 | 237.67 | 1242.29 | 0.00 | 0.00 | 185.17 |
August | 406.00 | 0.54 | 0.26 | 01-AUG-09:09 | 359.51 | 0.00 | 0.00 | 216.00 | 276.07 | 0.00 | 0.00 | 160.83 |
September | 289.17 | 0.56 | 0.26 | 01-SEP-09:39 | 310.71 | 0.00 | 0.00 | 159.50 | 703.01 | 0.00 | 0.00 | 108.50 |
October | 314.33 | 0.63 | 0.26 | 01-OCT-11:00 | 247.55 | 0.00 | 0.00 | 105.00 | 341.35 | 0.00 | 0.00 | 48.50 |
November | 258.33 | 0.73 | 0.26 | 01-NOV-11:00 | 193.11 | 0.00 | 0.00 | 26.67 | 146.11 | 0.00 | 0.00 | 0.83 |
December | 230.67 | 0.72 | 0.26 | 09-DEC-12:39 | 199.76 | 0.00 | 0.00 | 26.83 | 150.68 | 0.00 | 0.00 | 1.83 |
Annual Sum or Average | 3928.50 | 0.59 | 300.18 | 0.00 | 0.00 | 1667.83 | 620.33 | 0.00 | 0.00 | 1098.50 | ||
Minimum of Months | 230.67 | 0.53 | 0.26 | 193.11 | 0.00 | 0.00 | 20.17 | 146.11 | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 439.00 | 0.73 | 0.26 | 367.22 | 0.00 | 0.00 | 237.67 | 1732.37 | 0.00 | 0.00 | 185.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.26 | 01-JAN-10:00 | 225.47 | 16.89 | 9.50 | 138.50 | 185.96 | 17.50 | 23.50 | 104.50 |
February | 262.50 | 0.41 | 0.26 | 01-FEB-12:39 | 314.86 | 18.44 | 64.67 | 192.00 | 257.65 | 19.07 | 85.83 | 163.17 |
March | 339.33 | 0.42 | 0.26 | 01-MAR-09:00 | 326.93 | 18.42 | 83.67 | 244.67 | 271.06 | 19.15 | 107.33 | 212.33 |
April | 371.17 | 0.41 | 0.26 | 01-APR-07:49 | 371.93 | 18.66 | 119.83 | 279.33 | 309.66 | 19.41 | 140.67 | 247.33 |
May | 332.17 | 0.40 | 0.26 | 01-MAY-07:40 | 1164.79 | 19.08 | 123.00 | 313.17 | 2047.71 | 21.08 | 142.83 | 278.00 |
June | 430.67 | 0.40 | 0.26 | 01-JUN-06:30 | 2235.12 | 19.11 | 137.33 | 330.33 | 2408.82 | 19.91 | 162.00 | 293.17 |
July | 439.00 | 0.40 | 0.26 | 01-JUL-07:10 | 1651.04 | 19.03 | 139.33 | 329.50 | 1999.19 | 20.36 | 161.50 | 297.83 |
August | 406.00 | 0.39 | 0.26 | 01-AUG-06:00 | 418.57 | 19.37 | 146.83 | 309.83 | 723.83 | 20.66 | 170.33 | 274.00 |
September | 289.17 | 0.41 | 0.26 | 01-SEP-07:00 | 744.73 | 20.39 | 107.00 | 252.50 | 1055.43 | 20.14 | 121.67 | 217.67 |
October | 314.33 | 0.44 | 0.26 | 01-OCT-08:20 | 661.70 | 18.42 | 61.83 | 213.67 | 538.86 | 18.49 | 80.50 | 177.83 |
November | 258.33 | 0.49 | 0.26 | 01-NOV-09:09 | 807.27 | 16.38 | 11.67 | 142.00 | 516.05 | 16.97 | 27.50 | 106.50 |
December | 230.67 | 0.48 | 0.26 | 01-DEC-12:09 | 530.87 | 16.87 | 4.00 | 135.67 | 467.93 | 17.46 | 16.67 | 97.67 |
Annual Sum or Average | 3928.50 | 0.42 | 862.35 | 18.56 | 1008.67 | 2881.17 | 999.60 | 19.38 | 1240.33 | 2470.00 | ||
Minimum of Months | 230.67 | 0.39 | 0.26 | 225.47 | 16.38 | 4.00 | 135.67 | 185.96 | 16.97 | 16.67 | 97.67 | |
Maximum of Months | 439.00 | 0.49 | 0.26 | 2235.12 | 20.39 | 146.83 | 330.33 | 2408.82 | 21.08 | 170.33 | 297.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107824E+11 | 28587.43 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103664E+11 | 28587.43 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623024E+10 | 28587.43 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.248439E+10 | 28587.43 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178016E+09 | 28587.43 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1241925.91 | 6209.63 | 29-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.881888E+09 | 28587.43 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351729E+10 | 28587.43 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966248E+10 | 28587.43 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107824E+11 | 28587.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325318E+11 | 98759.28 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330422E+11 | 98759.28 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136943E+11 | 98759.28 | 01-MAR-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.326350E+10 | 98759.28 | 16-APR-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186133E+09 | 32814.08 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545666E+10 | 57912.66 | 24-NOV-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301842E+11 | 98759.28 | 05-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.330422E+11 | 98759.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127529E+12 | 154629.94 | 12-JAN-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136410E+12 | 154629.94 | 06-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464032E+11 | 86767.50 | 05-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.622809E+10 | 62587.55 | 16-APR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.969458E+10 | 29531.54 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121419E+12 | 148676.10 | 09-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136410E+12 | 154629.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 65966606.50 | 59045381.49 | 3294.04 | 15-MAR-15:10 | 3028.66 | 0.00 |
April | 0.00 | 0.00 | 118.38 | 116.21 | 0.14 | 08-APR-13:00 | 0.14 | 0.00 |
May | 0.00 | 0.00 | 0.435183E+09 | 0.412048E+09 | 5948.42 | 10-MAY-15:10 | 4955.14 | 0.00 |
June | 0.00 | 0.00 | 0.415401E+10 | 0.321309E+10 | 24086.78 | 27-JUN-07:02 | 12060.06 | 0.00 |
July | 0.00 | 0.00 | 0.879988E+10 | 0.627745E+10 | 25011.31 | 21-JUL-06:02 | 12477.23 | 0.00 |
August | 0.00 | 0.00 | 0.726731E+10 | 0.580026E+10 | 24641.10 | 14-AUG-06:02 | 11298.39 | 0.00 |
September | 0.00 | 0.00 | 0.262194E+10 | 0.199117E+10 | 22798.75 | 14-SEP-07:02 | 11683.65 | 0.00 |
October | 0.00 | 0.00 | 26276774.92 | 25392443.93 | 2467.85 | 11-OCT-15:00 | 2345.48 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233706E+11 | 0.177785E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.879988E+10 | 0.627745E+10 | 25011.31 | 12477.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1937.27 | 1799.83 | 0.86 | 26-MAY-16:00 | 0.82 | 0.00 |
June | 0.00 | 0.00 | 0.528114E+10 | 0.378634E+10 | 81231.07 | 27-JUN-17:12 | 42164.91 | 0.00 |
July | 0.00 | 0.00 | 0.164408E+11 | 0.113779E+11 | 84427.76 | 20-JUL-23:15 | 37708.05 | 0.00 |
August | 0.00 | 0.00 | 0.112447E+11 | 0.896487E+10 | 80279.51 | 14-AUG-23:45 | 41357.99 | 0.00 |
September | 0.00 | 0.00 | 0.108495E+10 | 0.801673E+09 | 74832.81 | 16-SEP-17:12 | 50561.10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.340516E+11 | 0.249307E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164408E+11 | 0.113779E+11 | 84427.76 | 50561.10 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.931365E+09 | 0.08 | 360.03 | 01-JAN-00:03 | 0.08 |
February | 0.848270E+09 | 0.08 | 360.03 | 01-FEB-00:03 | 0.08 |
March | 0.539615E+09 | 0.04 | 360.03 | 01-MAR-00:03 | 0.08 |
April | 0.123131E+09 | 0.01 | 360.03 | 01-APR-02:35 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.295471E+09 | 0.02 | 360.03 | 11-NOV-04:40 | 0.08 |
December | 0.920424E+09 | 0.07 | 360.03 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.365827E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.931365E+09 | 0.08 | 360.03 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128220E+10 | 0.62 | 1192.61 | 02-JAN-14:20 | 0.93 |
February | 0.119403E+10 | 0.63 | 1192.61 | 01-FEB-08:30 | 0.93 |
March | 0.131470E+10 | 0.48 | 1192.61 | 31-MAR-08:30 | 0.93 |
April | 0.119162E+10 | 0.38 | 1192.61 | 01-APR-07:30 | 0.93 |
May | 0.122797E+10 | 0.36 | 1192.61 | 01-MAY-06:08 | 0.93 |
June | 0.122791E+10 | 0.37 | 1192.61 | 01-JUN-11:00 | 0.92 |
July | 0.118069E+10 | 0.34 | 1192.61 | 01-JUL-06:20 | 0.92 |
August | 0.127514E+10 | 0.37 | 1192.61 | 01-AUG-07:05 | 0.92 |
September | 0.118069E+10 | 0.35 | 1192.61 | 01-SEP-13:00 | 0.92 |
October | 0.118159E+10 | 0.35 | 1192.61 | 06-OCT-16:45 | 0.92 |
November | 0.114286E+10 | 0.36 | 1192.61 | 01-NOV-07:50 | 0.93 |
December | 0.127030E+10 | 0.58 | 1192.61 | 01-DEC-07:07 | 0.93 |
Annual Sum or Average | 0.146697E+11 | 0.43 | |||
Minimum of Months | 0.114286E+10 | 0.34 | 1192.61 | 0.92 | |
Maximum of Months | 0.131470E+10 | 0.63 | 1192.61 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.382978E+10 | 0.77 | 3072.17 | 02-JAN-07:10 | 0.90 |
February | 0.357508E+10 | 0.78 | 3072.17 | 01-FEB-07:20 | 0.90 |
March | 0.366075E+10 | 0.65 | 3072.17 | 01-MAR-07:08 | 0.90 |
April | 0.315144E+10 | 0.46 | 3072.17 | 13-APR-06:08 | 0.90 |
May | 0.316310E+10 | 0.34 | 3072.17 | 27-MAY-16:50 | 0.90 |
June | 0.322415E+10 | 0.37 | 3072.17 | 01-JUN-14:00 | 0.89 |
July | 0.325395E+10 | 0.38 | 3072.17 | 01-JUL-07:08 | 0.89 |
August | 0.339904E+10 | 0.38 | 3072.17 | 01-AUG-11:30 | 0.89 |
September | 0.304467E+10 | 0.34 | 3072.17 | 02-SEP-16:20 | 0.90 |
October | 0.304774E+10 | 0.34 | 3072.17 | 17-OCT-06:02 | 0.90 |
November | 0.310782E+10 | 0.56 | 3072.17 | 13-NOV-07:08 | 0.90 |
December | 0.379406E+10 | 0.77 | 3072.17 | 02-DEC-07:02 | 0.90 |
Annual Sum or Average | 0.402516E+11 | 0.51 | |||
Minimum of Months | 0.304467E+10 | 0.34 | 3072.17 | 0.89 | |
Maximum of Months | 0.382978E+10 | 0.78 | 3072.17 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.128220E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.119403E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133158E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119162E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.133642E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.223341E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.328696E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.303413E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181371E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118822E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.114286E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.127030E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.203054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114286E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.328696E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.382978E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.357508E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.366075E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.315144E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.316310E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.453499E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.730995E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.624418E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.331913E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.304774E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.310782E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.379406E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.487380E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.304774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.730995E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128220E+10 | 0.00 | 0.107824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119403E+10 | 0.00 | 0.103664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131470E+10 | 65966606.50 | 0.623024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119162E+10 | 118.38 | 0.248439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122797E+10 | 0.435183E+09 | 0.178016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122791E+10 | 0.415401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118069E+10 | 0.879988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127514E+10 | 0.726731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118069E+10 | 0.262194E+10 | 1241925.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118159E+10 | 26276774.92 | 0.881888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114286E+10 | 0.00 | 0.351729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127030E+10 | 0.00 | 0.966248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146697E+11 | 0.233706E+11 | 0.441044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131470E+10 | 0.879988E+10 | 0.107824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.382978E+10 | 0.00 | 0.325318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357508E+10 | 0.00 | 0.330422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366075E+10 | 0.00 | 0.136943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315144E+10 | 0.00 | 0.326350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316310E+10 | 1937.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.322415E+10 | 0.528114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325395E+10 | 0.164408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.339904E+10 | 0.112447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304467E+10 | 0.108495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304774E+10 | 0.00 | 0.186133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310782E+10 | 0.00 | 0.545666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379406E+10 | 0.00 | 0.301842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402516E+11 | 0.340516E+11 | 0.118359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.382978E+10 | 0.164408E+11 | 0.330422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131470E+10 | 0.00 | 0.00 | 0.00 | 16876631.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119162E+10 | 0.00 | 0.00 | 0.00 | 30.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122797E+10 | 0.00 | 0.00 | 0.00 | 0.108452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122791E+10 | 0.00 | 0.00 | 0.00 | 0.100550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118069E+10 | 0.00 | 0.00 | 0.00 | 0.210627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127514E+10 | 0.00 | 0.00 | 0.00 | 0.175899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118069E+10 | 0.00 | 0.00 | 0.00 | 0.633024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118159E+10 | 0.00 | 0.00 | 0.00 | 6626924.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146697E+11 | 0.00 | 0.00 | 0.00 | 0.563573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131470E+10 | 0.00 | 0.00 | 0.00 | 0.210627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.382978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316310E+10 | 0.00 | 0.00 | 0.00 | 504.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.322415E+10 | 0.00 | 0.00 | 0.00 | 0.131084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325395E+10 | 0.00 | 0.00 | 0.00 | 0.405600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.339904E+10 | 0.00 | 0.00 | 0.00 | 0.284514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304467E+10 | 0.00 | 0.00 | 0.00 | 0.274456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402516E+11 | 0.00 | 0.00 | 0.00 | 0.848644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.382978E+10 | 0.00 | 0.00 | 0.00 | 0.405600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 728362.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281321E+10 | 0.00 | 0.00 | 0.12 |
February | 910629.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264221E+10 | 0.00 | 0.00 | 0.13 |
March | 0.141730E+09 | 116275.13 | 0.00 | 26237.31 | 0.00 | 0.205211E+10 | 13731882.44 | 0.00 | 0.14 |
April | 0.581449E+09 | 0.00 | 0.00 | 29889.54 | 0.00 | 0.918357E+09 | 70598079.48 | 0.00 | 0.14 |
May | 0.514625E+09 | 3768671.68 | 0.00 | 1946998.60 | 0.00 | 36898760.71 | 0.175329E+10 | 0.00 | 0.39 |
June | 44657870.62 | 0.301154E+09 | 0.00 | 4902055.31 | 42957.30 | 0.00 | 0.252455E+10 | 0.00 | 0.66 |
July | 5430809.12 | 0.105003E+10 | 0.00 | 3610160.98 | 61516.18 | 0.00 | 0.635327E+09 | 0.00 | 0.54 |
August | 13209833.44 | 0.546203E+09 | 0.00 | 5884164.14 | 0.00 | 0.00 | 0.150145E+10 | 0.00 | 0.63 |
September | 70569984.44 | 0.188939E+09 | 0.00 | 4736891.99 | 0.00 | 265309.01 | 0.276276E+10 | 0.00 | 0.69 |
October | 0.859498E+09 | 0.00 | 0.00 | 464718.94 | 0.00 | 0.326519E+09 | 0.593199E+09 | 0.00 | 0.19 |
November | 0.225181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144131E+10 | 0.00 | 0.00 | 0.12 |
December | 19320610.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264178E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.247731E+10 | 0.209021E+10 | 0.00 | 21601116.81 | 104473.48 | 0.128727E+11 | 0.985491E+10 | 0.00 | 0.32 |
Minimum of Months | 728362.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.859498E+09 | 0.105003E+10 | 0.00 | 5884164.14 | 61516.18 | 0.281321E+10 | 0.276276E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667039E+10 | 0.00 | 0.00 | 0.17 |
February | 0.181946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642812E+10 | 0.00 | 0.00 | 0.17 |
March | 0.468982E+10 | 0.00 | 0.00 | 0.00 | 14478809.92 | 0.179414E+10 | 0.00 | 0.00 | 0.19 |
April | 0.433900E+10 | 0.00 | 0.00 | 0.00 | 411423.64 | 0.185106E+09 | 0.00 | 0.00 | 0.18 |
May | 0.431698E+10 | 0.00 | 0.00 | 106815.74 | 0.00 | 0.00 | 0.239158E+09 | 0.00 | 0.19 |
June | 0.175407E+10 | 0.455817E+09 | 0.00 | 6128734.67 | 0.00 | 0.00 | 0.472033E+10 | 0.00 | 0.50 |
July | 49329188.23 | 0.160720E+10 | 0.00 | 10420129.26 | 41327.76 | 0.00 | 0.519999E+10 | 0.00 | 0.70 |
August | 0.382420E+09 | 0.565025E+09 | 0.00 | 13421307.70 | 0.00 | 0.00 | 0.615679E+10 | 0.00 | 0.63 |
September | 0.226880E+10 | 60269174.68 | 0.00 | 3263817.41 | 0.00 | 0.00 | 0.378523E+10 | 0.00 | 0.37 |
October | 0.477042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
November | 0.450587E+10 | 0.00 | 0.00 | 0.00 | 595755.78 | 0.298866E+09 | 0.00 | 0.00 | 0.17 |
December | 0.244222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569591E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.334150E+11 | 0.268831E+10 | 0.00 | 33340804.78 | 15527317.11 | 0.210725E+11 | 0.201015E+11 | 0.00 | 0.30 |
Minimum of Months | 49329188.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.477042E+10 | 0.160720E+10 | 0.00 | 13421307.70 | 14478809.92 | 0.667039E+10 | 0.615679E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.222397E+12 | 0.141841E+12 | 0.00 | 0.115610E+11 | 0.512167E+11 |
February | 0.407833E+12 | 0.154496E+12 | 0.00 | 0.108907E+11 | 0.532164E+11 |
March | 0.691191E+12 | 0.796076E+11 | 0.00 | 0.867696E+10 | 0.208432E+11 |
April | 0.858224E+12 | 0.472923E+11 | 0.00 | 0.609413E+10 | 0.428879E+10 |
May | 0.110021E+13 | 0.367713E+11 | 0.00 | 0.685924E+10 | 0.628194E+09 |
June | 0.122510E+13 | 0.405942E+11 | 0.00 | 0.830825E+10 | 0.117515E+11 |
July | 0.116028E+13 | 0.377575E+11 | 0.00 | 0.323841E+10 | 0.314029E+11 |
August | 0.984094E+12 | 0.446288E+11 | 0.00 | 0.697246E+10 | 0.231161E+11 |
September | 0.720133E+12 | 0.428794E+11 | 0.00 | 0.864642E+10 | 0.461498E+10 |
October | 0.447439E+12 | 0.478820E+11 | 0.00 | 0.655010E+10 | 0.546824E+09 |
November | 0.192424E+12 | 0.508036E+11 | 0.00 | 0.647063E+10 | 0.680117E+10 |
December | 0.186922E+12 | 0.143761E+12 | 0.00 | 0.107992E+11 | 0.482634E+11 |
Annual Sum or Average | 0.819624E+13 | 0.868314E+12 | 0.00 | 0.950675E+11 | 0.256690E+12 |
Minimum of Months | 0.186922E+12 | 0.367713E+11 | 0.00 | 0.323841E+10 | 0.546824E+09 |
Maximum of Months | 0.122510E+13 | 0.154496E+12 | 0.00 | 0.115610E+11 | 0.532164E+11 |