Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 10:43:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1907.74 | 394.56 | 394.56 |
Net Site Energy | 1907.74 | 394.56 | 394.56 |
Total Source Energy | 3112.55 | 643.74 | 643.74 |
Net Source Energy | 3112.55 | 643.74 | 643.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1406.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 203.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 501.47 | 1406.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1406.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 9.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 203.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1406.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 9.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 203.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 29.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.61 | 290.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 103.71 | 290.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.61 | 290.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 103.71 | 290.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 501.467 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 501.467 | 100.00 |
Total On-Site and Utility Electric Sources | 501.467 | 100.00 |
Total Electricity End Uses | 501.467 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 78.50 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3091.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.9961 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.6188 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.9961 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 9.2031 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.6188 | 46.45 | 2.5587 | |
Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 6.8172 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:00 | 18-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 406442.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11673.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14472.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4094.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1770.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42122.25 | 406442.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 406442.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 11673.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 14472.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1788.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1770.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1524.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 645.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 292.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1588.15 | 1524.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 315.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 328.46 | 315.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 315.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 328.46 | 315.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.06 |
ZONE2 FINE STORAGE DIRECT AIR | 2.02 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.61 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.61 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 219034.29 |
PSZ-OFFICE HEATING COIL | 28689.14 |
PSZ-FINE STORAGE HEATING COIL | 77430.50 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 219034.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-FINE STORAGE | 2.02 | 2.02 | 2.02 | 2.02 | 2.02 | 2.02 | 1.00 | 1.00 | 2.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.06 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.02 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.06 | 1169.83 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.02 | 2160.09 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.697362 | 20415.12 | 28689.14 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.02 | 2.02 | 2.02 | 1.33 | 50128.70 | 77430.50 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.06 | 0.528304 | 0.704407 | 20415.12 | 10207.56 | 0.789990 | 0.789990 |
PSZ-FINE STORAGE COOLING COIL | 2.02 | 1.01 | 1.35 | 50128.70 | 25064.35 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 9.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.203 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.619 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.177 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2131.000 | 8.996 | 167.154 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2131.000 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 12823.730 | 9.203 | 427.458 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12823.730 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 18007.220 | 5.619 | 260.974 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 18007.220 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
5 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
6 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3618_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3618_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3618_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3618_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2283E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9042E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9415E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3600E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3572E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1547E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1869E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0055E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6654E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6109E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6533E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9968E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3296E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0265E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2705E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6679E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4040E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9028E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5054E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9188E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4865E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3654E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3750E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3193E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1096E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0789E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6603E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0596E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8459E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4055E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5442E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6112E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9434E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9416E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.7694E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7072E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8599E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.0221E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7583E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.1621E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.2411E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.1715E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8289E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.1250E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9649E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8464E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2760E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7951E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9686E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9893E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6769E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2452E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.5869E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0592E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4594E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8018E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0578E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9928E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4916E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2414E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5869E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0592E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10206.45152 | 12247.74182 | 0.88051 | 1.05661 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 29.85733 | 1.53626E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 13146.59576 | 15775.91491 | 0.38704 | 0.46444 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 25011.72312 | 30014.06774 | 1.68224 | 2.01868 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 47900.65185 | 57480.78222 | 1.18717 | 1.42461 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 182528.57439 | 219034.28927 | 4.67496 | 5.60995 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15229.63 | 1.05661 | 1.05661 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15736.55 | 0.46444 | 0.46444 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 36425.02 | 2.01868 | 2.01868 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 60666.06 | 1.42461 | 1.42461 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05661 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01868 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.60995 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.60995 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 219034.28607 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 219034.28927 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05661 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05661 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05661 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05661 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05661 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.05661 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01868 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01868 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01868 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01868 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01868 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.01868 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.05661 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.01868 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05661 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05661 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1169.83327 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05661 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05661 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05661 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69736 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05661 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52830 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70441 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20415.12000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10207.56000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78999 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78999 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20415.12000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28689.14463 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28689.14463 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01868 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01868 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2160.08595 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01868 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01868 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01868 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33233 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01868 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00934 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34579 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 50128.70000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25064.35000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50128.70000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 77430.50072 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 77430.50072 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19594.8 | 11.75 | 11.49 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 48559.6 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2332136737 | 0.2041932487 | Pass | Pass | 0.9332110583 | 5.8512332888 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5106757308 | 0.4717009553 | Pass | Pass | 0.4640680884 | 0.6627178063 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.4446018064E-005 | 6.4571400067E-005 | Pass | Pass | 2.3600018500E-002 | 2.8370901139E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8278.66 | 1112.70 | 0.00 | 84.17 | 368.14 | 9843.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.176 | 0.180 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3618_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.055 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3618_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.055 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3618_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.055 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3618_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.055 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.064 | 0.494 | 0.493 | |||||||||||||||||
North Total or Average | 6.51 | 2.055 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.316 | 0.517 | 0.516 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.9961 | 236.88 | 2131.00 | LightsWired | LTG_SCH_OFFICE | 51.55 | 168.00 | 46.16 | 0.0000 | Y | 18.47 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 9.2031 | 1393.41 | 12823.73 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 33.37 | 0.0000 | Y | 80.33 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.6188 | 3204.84 | 18007.22 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 31.08 | 0.0000 | Y | 105.07 |
Interior Lighting Total | 6.8172 | 4835.13 | 32961.95 | 203.86 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 18007.22 | 2088.84 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2131.00 | 309.00 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 2131.00 | 106.55 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 94.73 | AstronomicalClock | - | 42.24 | 42.24 | 0.75 | |
EXTERIOR_LIGHTS_B | 6863.48 | AstronomicalClock | - | 83.63 | 71.21 | 91.75 | |
Exterior Lighting Total | 6958.21 | 92.50 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20415.12 | 16127.74 | 4287.38 | 0.79 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 50128.70 | 35144.23 | 14984.47 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19594.8 | 11.75 | 11.49 | ||||
PSZ-FINE STORAGE COOLING COIL | 48559.6 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 219034.29 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28689.14 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 77430.50 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.61 | 521.22 | 92.91 | 1.00 | 3.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1169.83 | 1107.16 | 1.00 | 1.39 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.02 | 2160.09 | 1070.05 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10206.45 | 12247.74 | 51.70 | 0.881 | 1.057 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00876 | 29.86 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 25011.72 | 30014.07 | 21.54 | 1.682 | 2.019 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.69 | 0.00994 | 31.09 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.39 | 0.01543 | 31.09 | 0.01536 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13146.60 | 15775.91 | 66.60 | 0.387 | 0.464 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00718 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 47900.65 | 57480.78 | 41.25 | 1.187 | 1.425 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00576 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 182528.57 | 219034.29 | 68.34 | 4.675 | 5.610 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00484 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.06 | 1.06 | 0.46 | 0.46 | 1.0566 | 1.0566 | 1.0566 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.02 | 2.02 | 1.42 | 1.42 | 2.0187 | 2.0187 | 2.0187 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 219034.286 | 219034.286 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 219034.29 | 219034.29 | 5.609949 | 9.99 | 6.47 | 0.00484307 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00484307 | 60.8286 | 219034.29 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20415.120 | 16127.741 | 1.056610 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 10207.56 | 8322.91 | 0.704407 | 25.45 | 17.15 | 0.00940047 | 12.00 | 10.84 | 0.00800000 | 30.14 | 0.01536312 | 22.84 | 14.5207 | 23.90 | 0.00876063 | 45.2414 | 10195.46 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28689.145 | 28689.145 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28689.14 | 28689.14 | 1.056608 | 16.47 | 11.20 | 0.00651638 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 9.6805 | 21.10 | 0.00717608 | 44.0457 | 13146.60 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 50128.700 | 35144.229 | 2.018680 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 25064.35 | 17699.72 | 1.345787 | 28.55 | 19.44 | 0.01108366 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 31.5586 | 26.69 | 0.00994205 | 43.3903 | 24997.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 77430.501 | 77430.501 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 77430.50 | 77430.50 | 2.018683 | 6.77 | 4.59 | 0.00462092 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.0390 | 15.55 | 0.00575588 | 50.1529 | 47900.65 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 219034.286 | 219034.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.609949 | 6.44333911 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 219034.29 | 219034.29 | 1.0000 | 6.44333911 | 5.609949 | 9.99 | 6.47 | 0.00484307 | 22243.8 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 219034.29 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00484307 | 9.99 | 0.00484307 | 60.8286 | 219034.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20415.120 | 16127.741 | 1.056610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3150 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.056608 | 1.21357378 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 10207.56 | 8322.91 | 1.0000 | 0.80905038 | 0.704407 | 25.45 | 17.15 | 0.00940047 | 49522.9 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10207.56 | 30.14 | 0.01536312 | 22.84 | 0.10228463 | 14.5207 | 23.90 | 0.00876063 | 23.90 | 0.00876063 | 45.2414 | 10195.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28689.145 | 28689.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.056608 | 1.21357378 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28689.14 | 28689.14 | 1.0000 | 1.21357378 | 1.056608 | 16.47 | 11.20 | 0.00651638 | 33050.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28689.14 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 9.6805 | 21.05 | 0.00717608 | 21.10 | 0.00717608 | 44.0457 | 13146.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 50128.700 | 35144.229 | 2.018680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4440 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.018683 | 2.31856982 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 25064.35 | 17699.72 | 1.0000 | 1.54571112 | 1.345787 | 28.55 | 19.44 | 0.01108366 | 56997.8 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25064.35 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 31.5586 | 26.69 | 0.00994205 | 26.69 | 0.00994205 | 43.3903 | 24997.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 77430.501 | 77430.501 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.018683 | 2.31856982 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 77430.50 | 77430.50 | 1.0000 | 2.31856982 | 2.018683 | 6.77 | 4.59 | 0.00462092 | 18413.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77430.50 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 21.0390 | 15.55 | 0.00575588 | 15.55 | 0.00575588 | 50.1529 | 47900.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.06 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3011.83 | 2863.17 | 2366.33 |
ZONE2 FINE STORAGE | 3285.33 | 3186.00 | 2879.17 |
ZONE3 BULK STORAGE | 3360.67 | 3244.83 | 3038.33 |
Facility | 3490.67 | 3297.33 | 3091.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 200.00 | 0.17 | 48.83 | 0.17 |
ZONE2 FINE STORAGE | 563.83 | 1.83 | 26.33 | 0.00 |
ZONE3 BULK STORAGE | 46.67 | 0.00 | 17.33 | 0.00 |
Facility | 743.83 | 2.00 | 78.50 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.501 | 0.496 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.481 | 0.352 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.215 | 0.000 | 0.086 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.03 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1806822.05 | 0.00 | 1806822.05 | 2841321.04 | 4648143.08 | 3225648.14 | 5720.82 | 2479.08 | 560.10 | 0.00 |
ZONE2 FINE STORAGE | 5126239.06 | 0.00 | 5126239.06 | 9790874.37 | 14917113.43 | 13393694.68 | 5725.86 | 2737.00 | 297.14 | 3.48 |
ZONE3 BULK STORAGE | 0.00 | 24081542.40 | 24081542.40 | 56304356.95 | 80385899.35 | 30805497.77 | 6740.67 | 131.33 | 1888.00 | 5100.17 |
Total Facility | 6933061.11 | 24081542.40 | 31014603.51 | 68936552.35 | 99951155.86 | 47424840.58 | 7883.50 | 2999.56 | 2564.43 | 5100.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1380 | 0.0000 | 0.1380 | 0.1374 | 0.2755 | 0.1023 | 596.82 | 2479.08 | 560.10 |
ZONE2 FINE STORAGE | 0.3907 | 0.0000 | 0.3907 | 0.2881 | 0.6789 | 0.4247 | 605.33 | 2737.00 | 293.67 |
ZONE3 BULK STORAGE | 0.0000 | 0.8492 | 0.8492 | 2.1287 | 2.9780 | 0.9768 | 2642.33 | 53.00 | 940.67 |
Total Facility | 0.5288 | 0.8492 | 1.3780 | 2.5543 | 3.9323 | 1.5038 | 2759.50 | 2921.22 | 1613.80 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2383485.93 | 0.00 | 2383485.93 | 3225648.14 | 5718.49 | 0.17 | 3041.35 | 0.00 |
PSZ-FINE STORAGE | 6762566.29 | 0.00 | 6762566.29 | 13393694.68 | 5725.19 | 0.00 | 3034.81 | 3.48 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1821 | 0.0000 | 0.1821 | 0.1023 | 594.49 | 0.17 | 3041.35 |
PSZ-FINE STORAGE | 0.5154 | 0.0000 | 0.5154 | 0.4247 | 604.67 | 0.00 | 3031.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2909.77 | 136.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2969.39 | 66.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2107 | 0.3619 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6123 | 0.8916 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
Electricity:Building | 343.20 | 2396.55 | 19-MAR-14:10 | 26916.27 | 04-AUG-13:30 |
Electricity:Zone:ZONE1 OFFICE | 50.41 | 815.73 | 20-FEB-16:10 | 3198.43 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 343.16 | 2396.55 | 19-MAR-14:10 | 25802.97 | 12-DEC-16:00 |
InteriorLights:Electricity | 203.87 | 1822.80 | 19-MAR-14:10 | 15690.35 | 12-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.47 | 241.98 | 20-FEB-16:10 | 1285.93 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 203.87 | 1822.80 | 19-MAR-14:10 | 15690.35 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 203.87 | 1822.80 | 19-MAR-14:10 | 15690.35 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.47 | 241.98 | 20-FEB-16:10 | 1285.93 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 203.87 | 1822.80 | 19-MAR-14:10 | 15690.35 | 12-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 212.46 | 875.51 | 01-JAN-10:20 | 17947.26 | 04-AUG-12:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 105.07 | 875.51 | 01-JAN-10:20 | 8418.38 | 02-JAN-14:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 105.07 | 875.51 | 01-JAN-10:20 | 8418.38 | 02-JAN-14:00 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 29.93 | 0.00 | 24-FEB-18:10 | 4268.25 | 04-AUG-15:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.04 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-AUG-12:30 |
Ventilation (simple):Fans:Electricity | 0.04 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-AUG-12:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.04 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-AUG-12:30 |
ElectricityPurchased:Facility | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
ElectricityPurchased:Plant | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
Cogeneration:ElectricityPurchased | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
ElectricityNet:Plant | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
Cogeneration:ElectricityNet | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
General:Cogeneration:ElectricityNet | 501.47 | 2879.55 | 19-MAR-14:20 | 42122.25 | 04-AUG-15:00 |
Electricity:HVAC | 38.92 | 0.00 | 24-FEB-18:10 | 14519.81 | 04-AUG-15:40 |
General:Fans:Electricity | 29.89 | 0.00 | 24-FEB-18:10 | 3851.14 | 18-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 9.04 | 0.00 | 01-JAN-00:10 | 12558.47 | 04-AUG-15:50 |
General:Cooling:Electricity | 9.04 | 0.00 | 01-JAN-00:10 | 12558.47 | 04-AUG-15:50 |
ExteriorLights:Electricity | 92.50 | 0.00 | 01-JAN-08:00 | 6958.21 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.50 | 0.00 | 01-JAN-08:00 | 6958.21 | 01-JAN-06:10 |
Electricity:Plant | 26.84 | 483.00 | 02-JAN-06:10 | 2940.30 | 21-FEB-12:50 |
WaterSystems:Electricity | 26.84 | 483.00 | 02-JAN-06:10 | 2940.30 | 21-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.84 | 483.00 | 02-JAN-06:10 | 2940.30 | 21-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1406.27 | 0.00 | 24-FEB-18:10 | 406442.41 | 18-JAN-18:00 |
NaturalGas:HVAC | 1406.27 | 0.00 | 24-FEB-18:10 | 406442.41 | 18-JAN-18:00 |
Heating:NaturalGas | 1406.27 | 0.00 | 24-FEB-18:10 | 406442.41 | 18-JAN-18:00 |
General:Heating:NaturalGas | 1406.27 | 0.00 | 24-FEB-18:10 | 406442.41 | 18-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2206.84 | 0.00 | 24-FEB-18:10 | 634100.79 | 18-JAN-18:00 |
EnergyTransfer:Building | 1083.91 | 0.00 | 24-FEB-18:10 | 310691.14 | 09-DEC-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 76.11 | 0.00 | 01-JAN-00:40 | 30050.55 | 03-FEB-07:20 |
Heating:EnergyTransfer | 1045.14 | 0.00 | 24-FEB-18:10 | 310691.14 | 09-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 59.54 | 0.00 | 01-JAN-00:40 | 30050.55 | 03-FEB-07:20 |
General:Heating:EnergyTransfer | 1045.14 | 0.00 | 24-FEB-18:10 | 310691.14 | 09-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 59.54 | 0.00 | 01-JAN-00:40 | 30050.55 | 03-FEB-07:20 |
Cooling:EnergyTransfer | 38.78 | 0.00 | 01-JAN-00:10 | 25380.27 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.57 | 0.00 | 01-JAN-00:10 | 9748.15 | 04-AUG-16:10 |
General:Cooling:EnergyTransfer | 38.78 | 0.00 | 01-JAN-00:10 | 25380.27 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.57 | 0.00 | 01-JAN-00:10 | 9748.15 | 04-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 215.89 | 0.00 | 01-JAN-00:40 | 78423.15 | 09-DEC-01:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 193.68 | 0.00 | 01-JAN-00:40 | 78423.15 | 09-DEC-01:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 193.68 | 0.00 | 01-JAN-00:40 | 78423.15 | 09-DEC-01:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 22.21 | 0.00 | 01-JAN-00:10 | 16573.25 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 22.21 | 0.00 | 01-JAN-00:10 | 16573.25 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 791.91 | 0.00 | 24-FEB-09:40 | 221443.76 | 08-DEC-17:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 791.91 | 0.00 | 24-FEB-09:40 | 221443.76 | 08-DEC-17:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 791.91 | 0.00 | 24-FEB-09:40 | 221443.76 | 08-DEC-17:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1122.92 | 0.00 | 24-FEB-18:10 | 325153.93 | 18-JAN-18:00 |
HeatingCoils:EnergyTransfer | 1085.05 | 0.00 | 24-FEB-18:10 | 325153.93 | 18-JAN-18:00 |
CoolingCoils:EnergyTransfer | 37.88 | 0.00 | 01-JAN-00:10 | 50109.75 | 04-AUG-15:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 59.537 | -16.569 | 0.000 | 0.000 | 10.204 | 18.466 | 31.946 | 11.480 | 0.000 | 0.747 | 0.000 | 0.000 | -9.890 | 0.000 | -50.309 | -55.612 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 193.684 | -22.209 | 0.000 | 0.000 | 26.740 | 80.328 | 0.000 | 0.000 | 0.000 | 1.128 | 0.002 | 0.000 | 0.000 | 0.000 | -153.909 | -125.762 |
ZONE3 BULK STORAGE | 791.912 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.365 | 105.071 | 107.344 | 141.713 | 0.000 | 23.846 | 0.000 | 0.000 | -73.348 | 0.000 | -905.299 | -259.604 |
Total Facility | 791.912 | 0.000 | 253.221 | -38.778 | 0.000 | 0.000 | 105.308 | 203.866 | 139.290 | 153.193 | 0.000 | 25.721 | 0.002 | 0.000 | -83.238 | 0.000 | -1109.517 | -440.978 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -21917.92 | 0.00 | 0.00 | 806.81 | 1167.03 | 1912.50 | 22.20 | 0.00 | 0.00 | 18511.18 | 0.00 | -0.00 | 0.00 | -501.80 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -34718.37 | 0.00 | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 34023.01 | 0.00 | -0.00 | 0.00 | -9.95 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -34718.37 | 0.00 | 0.00 | 0.00 | 1861.09 | 2623.78 | 33623.24 | 0.00 | 69.62 | 0.00 | 0.00 | 0.00 | 0.00 | -2948.36 | -511.01 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-FEB-06:31 | 0.00 | 0.00 | 30904.40 | 0.00 | 0.00 | 0.00 | 154.89 | 384.11 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1428.45 | 0.00 | -5297.20 | -25291.50 |
ZONE2 FINE STORAGE | 19-JAN-06:01 | 0.00 | 0.00 | 82777.43 | 0.00 | 0.00 | 0.00 | 392.71 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25221.20 | -58654.25 |
ZONE3 BULK STORAGE | 09-DEC-08:25 | 221858.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8664.40 | 7427.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 46968.92 | 0.00 | -12915.50 | 0.00 | -280204.75 | 0.00 |
Total Facility | 19-JAN-06:01 | 218806.81 | 0.00 | 113293.39 | 0.00 | 0.00 | 0.00 | 1472.44 | 2079.82 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11050.43 | 0.00 | -198731.86 | -128493.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0566 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0566 | 0.0968 | 1.0000 | Not calculated | 0.1023 | 0.0968 | ||
PSZ-FINE STORAGE | 2.0187 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.0187 | 0.2104 | 1.0000 | Not calculated | 0.4247 | 0.2104 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0566 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0566 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0968 | ||
PSZ-FINE STORAGE | 2.0187 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.0187 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2104 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0566 | 1.0566 | 1.0566 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0187 | 2.0187 | 2.0187 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0566 | 1.0566 | 1.0566 | 1.0566 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.0187 | 2.0187 | 2.0187 | 2.0187 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0566 | 1.0566 | 1.0566 | No | 0.1023 | 0.2202 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0187 | 2.0187 | 2.0187 | No | 0.4247 | 0.2981 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0566 | 1.0566 | 1.0566 | 1.0566 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.0187 | 2.0187 | 2.0187 | 2.0187 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 78.50 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 78.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1406.27 | 406442.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 9.04 | 12558.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 203.87 | 15690.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.50 | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.04 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 29.89 | 3851.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.84 | 2940.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 501.47 |
Natural Gas | 0.00 | 1406.27 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1907.74 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 42.16 |
Space Heating | 0.00 |
Space Cooling | 1.87 |
Fans (All) | 6.19 |
Service Water Heating | 5.55 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 103.71 |
Subtotal | 103.71 |
Natural Gas [MJ/m2] | |
Space Heating | 290.84 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 290.84 |
Subtotal | 290.84 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.69 |
Space Heating | 73.71 |
Space Cooling | 0.47 |
Fans (All) | 1.57 |
Service Water Heating | 1.41 |
Receptacle Equipment | 7.30 |
Miscellaneous | 4.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2688. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8343.50 | 416.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8115.83 | 644.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8237.50 | 504.67 | 17.83 | 0.00 | 0.00 |
Min | 8115.83 | 416.50 | 0.00 | 0.00 | 0.00 |
Max | 8343.50 | 644.17 | 17.83 | 0.00 | 0.00 |
Average | 8232.28 | 521.78 | 5.94 | 0.00 | 0.00 |
Sum | 24696.83 | 1565.33 | 17.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33018.00 | 9.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 71086.50 | 11632.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 172707.17 | 17623.83 | 862.00 | 0.00 | 0.00 |
Min | 33018.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Max | 172707.17 | 17623.83 | 862.00 | 0.00 | 0.00 |
Average | 92270.56 | 9755.11 | 287.33 | 0.00 | 0.00 |
Sum | 276811.67 | 29265.33 | 862.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7716.83 | 1043.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7246.17 | 1513.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7456.50 | 1296.00 | 7.50 | 0.00 | 0.00 |
Min | 7246.17 | 1043.17 | 0.00 | 0.00 | 0.00 |
Max | 7716.83 | 1513.83 | 7.50 | 0.00 | 0.00 |
Average | 7473.17 | 1284.33 | 2.50 | 0.00 | 0.00 |
Sum | 22419.50 | 3853.00 | 7.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32020.17 | 1006.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 64854.50 | 17864.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 157908.67 | 32854.67 | 429.67 | 0.00 | 0.00 |
Min | 32020.17 | 1006.83 | 0.00 | 0.00 | 0.00 |
Max | 157908.67 | 32854.67 | 429.67 | 0.00 | 0.00 |
Average | 84927.78 | 17242.00 | 143.22 | 0.00 | 0.00 |
Sum | 254783.33 | 51726.00 | 429.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 722994.47 | 1785.49 | 13-JAN-08:05 | -1.0 | -2.0 | 0.492764E+09 | 603.25 | 31-JAN-13:09 | -20.9 | -21.4 |
February | 1751893.36 | 2144.17 | 25-FEB-08:05 | 0.10 | -0.7 | 0.452757E+09 | 603.26 | 25-FEB-08:20 | 0.20 | -0.7 |
March | 4427119.27 | 2208.71 | 09-MAR-08:05 | -1.0 | -2.0 | 0.533174E+09 | 644.20 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.192558E+09 | 3961.11 | 18-APR-15:10 | 27.75 | 20.46 | 0.509272E+09 | 768.96 | 18-APR-10:20 | 27.75 | 20.46 |
May | 0.573548E+09 | 4986.81 | 31-MAY-15:40 | 28.87 | 19.09 | 0.585376E+09 | 769.02 | 31-MAY-12:00 | 28.87 | 19.09 |
June | 0.332382E+10 | 18689.96 | 24-JUN-07:02 | 19.27 | 15.28 | 0.643606E+09 | 879.39 | 27-JUN-07:10 | 24.08 | 20.96 |
July | 0.476905E+10 | 20303.15 | 22-JUL-07:02 | 15.18 | 13.12 | 0.637741E+09 | 879.39 | 29-JUL-07:10 | 19.87 | 17.85 |
August | 0.491609E+10 | 18529.62 | 19-AUG-07:02 | 17.57 | 15.03 | 0.686811E+09 | 879.39 | 05-AUG-07:10 | 17.57 | 15.03 |
September | 0.266573E+10 | 21920.00 | 02-SEP-07:02 | 13.53 | 11.74 | 0.597591E+09 | 879.39 | 09-SEP-07:10 | 16.05 | 14.85 |
October | 78142986.59 | 2295.78 | 23-OCT-07:05 | -1.2 | -2.6 | 0.502128E+09 | 768.96 | 20-OCT-15:00 | -1.2 | -2.6 |
November | 41843333.51 | 2231.61 | 04-NOV-07:05 | 0.37 | -1.2 | 0.475417E+09 | 678.82 | 04-NOV-15:09 | 14.13 | 6.72 |
December | 1275898.99 | 2586.41 | 23-DEC-08:05 | -6.8 | -7.3 | 0.493348E+09 | 603.25 | 30-DEC-08:20 | -1.1 | -1.8 |
Annual Sum or Average | 0.165689E+11 | 0.660998E+10 | ||||||||
Minimum of Months | 722994.47 | 1785.49 | -6.8 | -7.3 | 0.452757E+09 | 603.25 | -20.9 | -21.4 | ||
Maximum of Months | 0.491609E+10 | 21920.00 | 28.87 | 20.46 | 0.686811E+09 | 879.39 | 28.87 | 20.96 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56580626.86 | 2717.73 | 13-JAN-14:50 | 3.90 | 1.72 | 0.649015E+09 | 787.42 | 25-JAN-11:39 | -15.2 | -15.5 |
February | 0.245570E+09 | 7366.17 | 21-FEB-11:35 | -2.1 | -4.2 | 0.598367E+09 | 884.88 | 24-FEB-15:39 | 8.30 | 5.79 |
March | 0.694144E+09 | 4343.93 | 31-MAR-11:00 | 5.00 | 2.03 | 0.723116E+09 | 1149.02 | 25-MAR-15:20 | 5.00 | 2.03 |
April | 0.159911E+10 | 6311.18 | 22-APR-13:40 | 2.03 | -0.4 | 0.797222E+09 | 2052.91 | 18-APR-15:20 | 2.03 | -0.4 |
May | 0.129069E+10 | 4190.39 | 02-MAY-09:20 | 5.37 | 2.77 | 0.115722E+10 | 2246.80 | 31-MAY-14:50 | 29.90 | 19.65 |
June | 0.342424E+10 | 33557.80 | 30-JUN-17:10 | 28.30 | 20.22 | 0.165438E+10 | 2246.92 | 30-JUN-15:00 | 28.30 | 20.22 |
July | 0.501019E+10 | 34724.03 | 05-JUL-17:10 | 26.70 | 20.64 | 0.179616E+10 | 2246.91 | 03-JUL-14:30 | 26.70 | 20.64 |
August | 0.399759E+10 | 30978.81 | 04-AUG-17:10 | 27.93 | 23.69 | 0.191963E+10 | 2246.93 | 04-AUG-13:20 | 27.93 | 23.69 |
September | 0.293037E+10 | 25951.74 | 10-SEP-14:15 | 27.07 | 17.41 | 0.143413E+10 | 2246.88 | 09-SEP-13:30 | 27.07 | 17.41 |
October | 0.207821E+10 | 5521.99 | 23-OCT-09:20 | 2.70 | 0.39 | 0.775866E+09 | 1403.20 | 20-OCT-15:20 | 2.70 | 0.39 |
November | 0.793165E+09 | 5277.15 | 09-NOV-14:30 | 3.05 | 1.00 | 0.671920E+09 | 1215.23 | 03-NOV-14:00 | 3.05 | 1.00 |
December | 89824685.51 | 3958.31 | 02-DEC-15:40 | 5.77 | 3.20 | 0.648856E+09 | 787.43 | 09-DEC-09:20 | -22.6 | -22.8 |
Annual Sum or Average | 0.222097E+11 | 0.128259E+11 | ||||||||
Minimum of Months | 56580626.86 | 2717.73 | -2.1 | -4.2 | 0.598367E+09 | 787.42 | -22.6 | -22.8 | ||
Maximum of Months | 0.501019E+10 | 34724.03 | 28.30 | 23.69 | 0.191963E+10 | 2246.93 | 29.90 | 23.69 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.641562E+09 | 780.71 | 12-JAN-13:20 | 2.20 | 0.51 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.596426E+09 | 981.67 | 24-FEB-15:50 | 8.30 | 5.84 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.762750E+09 | 1583.93 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 | 0.106778E+10 | 3648.38 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.15 | 0.196107E+10 | 4133.30 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.338444E+10 | 6166.55 | 30-JUN-15:20 | 29.23 | 21.33 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.424279E+10 | 6263.93 | 03-JUL-15:30 | 29.45 | 24.36 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.437908E+10 | 7688.85 | 04-AUG-15:00 | 33.90 | 26.33 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.308219E+10 | 5544.09 | 08-SEP-14:50 | 30.10 | 19.14 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.110701E+10 | 2255.79 | 02-OCT-15:30 | 17.45 | 14.25 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 | -0.5 | 0.777807E+09 | 1689.61 | 03-NOV-14:00 | 16.10 | 9.59 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.632352E+09 | 860.30 | 02-DEC-16:10 | 4.95 | 2.78 |
Annual Sum or Average | 0.00 | 0.226353E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.596426E+09 | 780.71 | 2.20 | 0.51 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.437908E+10 | 7688.85 | 33.90 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148111E+11 | 30515.88 | 19-JAN-06:01 | -27.8 |
February | 0.108071E+11 | 30904.29 | 01-FEB-06:31 | -31.5 |
March | 0.823196E+10 | 29785.35 | 01-MAR-06:32 | -4.4 |
April | 0.399533E+10 | 29265.39 | 03-APR-06:01 | -7.1 |
May | 0.736091E+09 | 28907.83 | 02-MAY-06:01 | 2.30 |
June | 0.111464E+09 | 28188.81 | 05-JUN-06:02 | 8.98 |
July | 33157035.04 | 997.82 | 05-JUL-06:05 | 19.60 |
August | 44631618.10 | 973.82 | 07-AUG-06:13 | 9.43 |
September | 0.382774E+09 | 28864.12 | 29-SEP-06:01 | 0.10 |
October | 0.242535E+10 | 28965.43 | 23-OCT-06:01 | -3.0 |
November | 0.665214E+10 | 29526.25 | 24-NOV-07:01 | -13.9 |
December | 0.113071E+11 | 30332.63 | 12-DEC-06:31 | -19.6 |
Annual Sum or Average | 0.595383E+11 | |||
Minimum of Months | 33157035.04 | 973.82 | -31.5 | |
Maximum of Months | 0.148111E+11 | 30904.29 | 19.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523432E+11 | 82777.42 | 19-JAN-06:01 | -27.8 |
February | 0.369999E+11 | 81303.79 | 03-FEB-06:41 | -33.9 |
March | 0.239037E+11 | 81622.12 | 06-MAR-06:41 | -13.1 |
April | 0.914350E+10 | 79327.80 | 03-APR-04:22 | -7.0 |
May | 0.898247E+09 | 68862.14 | 02-MAY-05:01 | 2.20 |
June | 0.101055E+09 | 2100.05 | 09-JUN-12:00 | 28.30 |
July | 60691506.68 | 843.16 | 18-JUL-07:00 | 16.70 |
August | 65633752.39 | 863.01 | 25-AUG-07:00 | 13.90 |
September | 0.302761E+09 | 25977.02 | 30-SEP-05:55 | 0.60 |
October | 0.484193E+10 | 77635.70 | 24-OCT-05:01 | 2.03 |
November | 0.237132E+11 | 80599.56 | 25-NOV-06:01 | -16.9 |
December | 0.413106E+11 | 80951.41 | 13-DEC-06:01 | -10.4 |
Annual Sum or Average | 0.193684E+12 | |||
Minimum of Months | 60691506.68 | 843.16 | -33.9 | |
Maximum of Months | 0.523432E+11 | 82777.42 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240540E+12 | 220959.61 | 18-JAN-13:20 | -16.3 |
February | 0.163033E+12 | 219568.95 | 01-FEB-20:56 | -28.9 |
March | 0.907128E+11 | 172799.75 | 06-MAR-08:62 | -11.8 |
April | 0.197369E+11 | 96442.04 | 02-APR-24:00 | -5.6 |
May | 0.515420E+09 | 20569.79 | 02-MAY-02:53 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.148776E+10 | 22726.56 | 24-OCT-06:00 | 2.20 |
November | 0.930999E+11 | 170745.81 | 25-NOV-11:00 | -17.2 |
December | 0.182788E+12 | 221858.84 | 09-DEC-08:25 | -22.8 |
Annual Sum or Average | 0.791913E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.240540E+12 | 221858.84 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159805E+10 | 1285.93 | 02-JAN-16:40 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.143560E+10 | 1269.42 | 11-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.160281E+10 | 1248.52 | 01-MAR-16:00 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.150985E+10 | 1251.18 | 10-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.153384E+10 | 1202.29 | 25-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.149660E+10 | 1236.82 | 13-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.149198E+10 | 1237.63 | 20-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.156309E+10 | 1223.69 | 31-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.150660E+10 | 1251.60 | 21-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.155373E+10 | 1266.28 | 21-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.154347E+10 | 1285.93 | 06-NOV-16:00 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.163086E+10 | 1285.93 | 01-DEC-16:30 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.184665E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.143560E+10 | 1202.29 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.163086E+10 | 1285.93 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.668164E+10 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.611542E+10 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.706504E+10 | 5995.09 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.662070E+10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.687334E+10 | 5995.09 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.681240E+10 | 5995.09 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.668164E+10 | 5995.09 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.706504E+10 | 5995.09 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.662070E+10 | 5995.09 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.668164E+10 | 5995.09 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.642900E+10 | 5995.09 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.668164E+10 | 5995.09 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.803282E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.611542E+10 | 5995.09 | 0.00 | 0.00 | |
Maximum of Months | 0.706504E+10 | 5995.09 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.904646E+10 | 8418.38 | 02-JAN-13:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.818890E+10 | 8418.38 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.918441E+10 | 8418.38 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.850674E+10 | 8092.87 | 10-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.875000E+10 | 7767.35 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.864454E+10 | 7767.35 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.850140E+10 | 7767.35 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.902062E+10 | 8092.87 | 29-AUG-08:20 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.856338E+10 | 8092.87 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.884933E+10 | 8418.38 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.862325E+10 | 8418.38 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.919204E+10 | 8418.38 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.105071E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.818890E+10 | 7767.35 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.919204E+10 | 8418.38 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.159805E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989780E+10 |
February | 0.127628E+10 | 0.143560E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735283E+10 |
March | 0.149825E+10 | 0.160281E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401411.23 | 0.606425E+10 |
April | 0.138726E+10 | 0.150985E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47205232.49 | 0.347450E+10 |
May | 0.144276E+10 | 0.153384E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45341418.17 | 0.176424E+10 |
June | 0.144276E+10 | 0.149660E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186478E+09 | 0.117390E+10 |
July | 0.138726E+10 | 0.149198E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140408E+09 | 0.842489E+09 |
August | 0.149825E+10 | 0.156309E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206038E+09 | 0.113625E+10 |
September | 0.138726E+10 | 0.150660E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121307E+09 | 0.185969E+10 |
October | 0.138726E+10 | 0.155373E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311700E+10 |
November | 0.133177E+10 | 0.154347E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559386E+10 |
December | 0.138726E+10 | 0.163086E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803256E+10 |
Annual Sum or Average | 0.168137E+11 | 0.184665E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747180E+09 | 0.503094E+11 |
Minimum of Months | 0.127628E+10 | 0.143560E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842489E+09 |
Maximum of Months | 0.149825E+10 | 0.163086E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206038E+09 | 0.989780E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310236E+11 |
February | 0.300332E+10 | 0.611542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227151E+11 |
March | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12873056.12 | 0.176761E+11 |
April | 0.326447E+10 | 0.662070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309823E+09 | 0.936208E+10 |
May | 0.339505E+10 | 0.687334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122367E+09 | 0.443874E+10 |
June | 0.339505E+10 | 0.681240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356575E+09 | 0.371371E+10 |
July | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85821114.53 | 0.333035E+10 |
August | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129793E+09 | 0.449672E+10 |
September | 0.326447E+10 | 0.662070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98193420.77 | 0.563523E+10 |
October | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12797823.51 | 0.794574E+10 |
November | 0.313390E+10 | 0.642900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177816E+11 |
December | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257896E+11 |
Annual Sum or Average | 0.395654E+11 | 0.803282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112824E+10 | 0.153909E+12 |
Minimum of Months | 0.300332E+10 | 0.611542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333035E+10 |
Maximum of Months | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356575E+09 | 0.310236E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.904646E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141618E+12 |
February | 0.690763E+10 | 0.818890E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987297E+11 |
March | 0.810895E+10 | 0.918441E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135153E+10 | 0.665154E+11 |
April | 0.750829E+10 | 0.850674E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571195E+10 | 0.312771E+11 |
May | 0.780862E+10 | 0.875000E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387569E+10 | 0.131530E+11 |
June | 0.780862E+10 | 0.864454E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263142E+10 | 0.146335E+11 |
July | 0.750829E+10 | 0.850140E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241313E+09 | 0.181332E+11 |
August | 0.810895E+10 | 0.902062E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331543E+09 | 0.220871E+11 |
September | 0.750829E+10 | 0.856338E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839611E+09 | 0.268094E+11 |
October | 0.750829E+10 | 0.884933E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132633E+10 | 0.246515E+11 |
November | 0.720796E+10 | 0.862325E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211153E+09 | 0.690094E+11 |
December | 0.750829E+10 | 0.919204E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110869E+12 |
Annual Sum or Average | 0.910005E+11 | 0.105071E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165205E+11 | 0.637486E+12 |
Minimum of Months | 0.690763E+10 | 0.818890E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131530E+11 |
Maximum of Months | 0.810895E+10 | 0.919204E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571195E+10 | 0.141618E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1285.93 | 02-JAN-16:40 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 24403.61 | 19-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1269.42 | 11-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 26314.23 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1248.52 | 01-MAR-16:00 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.53 | 19-MAR-14:00 | 18397.64 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 1251.18 | 10-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.72 | 18-APR-12:00 | 13321.83 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1202.29 | 25-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1998.68 | 31-MAY-17:00 | 8206.49 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1236.82 | 13-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3037.11 | 26-JUN-16:10 | 5705.67 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1237.63 | 20-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2491.27 | 25-JUL-16:10 | 4534.14 | 24-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1223.69 | 31-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3619.87 | 04-AUG-16:10 | 5933.87 | 07-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1251.60 | 21-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.19 | 06-SEP-16:10 | 8549.36 | 29-SEP-06:04 |
October | 1680.92 | 02-OCT-07:10 | 1266.28 | 21-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 9766.53 | 23-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1285.93 | 06-NOV-16:00 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 16629.30 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1285.93 | 01-DEC-16:30 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 24138.27 | 08-DEC-17:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1202.29 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4534.14 | |||||
Maximum of Months | 1680.92 | 1285.93 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3619.87 | 26314.23 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 53337.86 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 33244.30 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 5995.09 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.82 | 19-MAR-16:00 | 32673.63 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.57 | 15-APR-15:10 | 20410.75 | 25-APR-06:01 |
May | 3955.50 | 01-MAY-07:10 | 5995.09 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3145.06 | 05-MAY-15:10 | 8630.09 | 01-MAY-24:00 |
June | 3955.50 | 01-JUN-07:10 | 5995.09 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4421.65 | 11-JUN-15:00 | 8205.45 | 02-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 5995.09 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.13 | 25-JUL-16:00 | 5406.09 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 5995.09 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.51 | 04-AUG-16:15 | 6411.83 | 30-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 5995.09 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.91 | 06-SEP-15:40 | 8219.39 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 5995.09 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.41 | 20-OCT-15:10 | 13974.87 | 24-OCT-06:01 |
November | 3955.50 | 01-NOV-07:10 | 5995.09 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 29671.83 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 5995.09 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 57048.18 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5406.09 | ||||
Maximum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.57 | 57048.18 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 8418.38 | 02-JAN-13:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 186484.59 | 18-JAN-13:10 |
February | 9097.65 | 01-FEB-08:09 | 8418.38 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 137022.97 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 8418.38 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23904.34 | 25-MAR-15:00 | 124914.74 | 06-MAR-08:05 |
April | 9097.65 | 01-APR-07:10 | 8092.87 | 10-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53827.17 | 15-APR-15:00 | 59362.67 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 7767.35 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37010.66 | 04-MAY-14:00 | 32637.34 | 13-MAY-12:55 |
June | 9097.65 | 01-JUN-07:10 | 7767.35 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27705.04 | 11-JUN-14:55 | 33565.32 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 7767.35 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7609.53 | 25-JUL-16:00 | 34604.25 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 8092.87 | 29-AUG-08:20 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6433.26 | 21-AUG-13:00 | 28659.99 | 06-AUG-06:00 |
September | 9097.65 | 01-SEP-07:10 | 8092.87 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13324.21 | 06-SEP-14:00 | 35922.07 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 8418.38 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21157.95 | 20-OCT-15:00 | 34512.69 | 24-OCT-07:05 |
November | 9097.65 | 01-NOV-07:10 | 8418.38 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10865.69 | 20-NOV-10:00 | 134635.29 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 8418.38 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 218490.37 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 7767.35 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28659.99 | |||||
Maximum of Months | 9097.65 | 8418.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 53827.17 | 218490.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1785.49 | 13-JAN-08:05 | 6723.69 | 5046.15 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2670.25 |
February | 2144.17 | 25-FEB-08:05 | 6723.69 | 4832.01 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.83 |
March | 2208.71 | 09-MAR-08:05 | 6723.69 | 4769.02 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.18 |
April | 3961.11 | 18-APR-15:10 | 1680.92 | 1035.17 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 826.09 | 0.00 |
May | 4986.81 | 31-MAY-15:40 | 1680.92 | 1035.17 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 638.08 | 0.00 |
June | 18689.96 | 24-JUN-07:02 | 8404.61 | 5572.12 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.94 |
July | 20303.15 | 22-JUL-07:02 | 8404.61 | 5686.52 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.85 |
August | 18529.62 | 19-AUG-07:02 | 8404.61 | 5907.01 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.09 |
September | 21920.00 | 02-SEP-07:02 | 8404.61 | 5835.14 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.80 |
October | 2295.78 | 23-OCT-07:05 | 6723.69 | 4977.16 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2494.43 |
November | 2231.61 | 04-NOV-07:05 | 6723.69 | 5029.53 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.42 |
December | 2586.41 | 23-DEC-08:05 | 6723.69 | 5114.71 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1785.49 | 1680.92 | 1035.17 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21920.00 | 8404.61 | 5907.01 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 826.09 | 2670.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2717.73 | 13-JAN-14:50 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2456.74 |
February | 7366.17 | 21-FEB-11:35 | 7911.00 | 11990.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2294.75 |
March | 4343.93 | 31-MAR-11:00 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3493.30 |
April | 6311.18 | 22-APR-13:40 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.87 |
May | 4190.39 | 02-MAY-09:20 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2597.71 |
June | 33557.80 | 30-JUN-17:10 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.32 | 0.00 |
July | 34724.03 | 05-JUL-17:10 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 |
August | 30978.81 | 04-AUG-17:10 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.68 | 0.00 |
September | 25951.74 | 10-SEP-14:15 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.76 | 0.00 |
October | 5521.99 | 23-OCT-09:20 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1788.85 |
November | 5277.15 | 09-NOV-14:30 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6431.98 |
December | 3958.31 | 02-DEC-15:40 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2717.73 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34724.03 | 7911.00 | 11990.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.68 | 6431.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 3961.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24532.35 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 5942.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60205.96 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 5942.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62313.18 |
April | 0.00 | 01-APR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11316.09 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1980.79 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5919.19 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7280.81 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7466.09 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8940.52 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11179.63 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12005.16 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 1980.79 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7868.18 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 3961.59 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25208.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5919.19 | |
Maximum of Months | 0.00 | 0.00 | 5942.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62313.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.459847E+11 | 36095.60 | 18-JAN-16:00 | 0.410792E+12 | 406442.41 | 18-JAN-17:00 |
February | 0.406460E+11 | 30676.90 | 03-FEB-15:00 | 0.282777E+12 | 355725.09 | 01-FEB-21:30 |
March | 0.441438E+11 | 29890.52 | 11-MAR-15:00 | 0.167004E+12 | 312151.17 | 06-MAR-08:09 |
April | 0.392407E+11 | 29364.46 | 18-APR-14:00 | 0.466319E+11 | 169860.58 | 02-APR-23:49 |
May | 0.389004E+11 | 30363.49 | 31-MAY-14:00 | 0.276721E+10 | 51352.16 | 02-MAY-05:10 |
June | 0.396480E+11 | 35892.19 | 27-JUN-14:39 | 0.120079E+09 | 9083.48 | 05-JUN-06:10 |
July | 0.404912E+11 | 37712.39 | 03-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.429074E+11 | 42122.25 | 04-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.400035E+11 | 34005.53 | 08-SEP-14:09 | 0.103551E+10 | 24935.01 | 30-SEP-07:10 |
October | 0.411799E+11 | 28838.09 | 30-OCT-08:09 | 0.138224E+11 | 64399.47 | 24-OCT-06:10 |
November | 0.423654E+11 | 35654.60 | 25-NOV-16:49 | 0.165868E+12 | 285967.98 | 25-NOV-16:10 |
December | 0.459564E+11 | 36107.57 | 08-DEC-16:49 | 0.315455E+12 | 399655.34 | 09-DEC-08:09 |
Annual Sum or Average | 0.501467E+12 | 0.140627E+13 | ||||
Minimum of Months | 0.389004E+11 | 28838.09 | 0.00 | 0.00 | ||
Maximum of Months | 0.459847E+11 | 42122.25 | 0.410792E+12 | 406442.41 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.173261E+11 | 0.100973E+11 | 0.115358E+11 | 0.00 | 0.466642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235903E+10 | 0.00 |
February | 0.157399E+11 | 0.831225E+10 | 0.105871E+11 | 0.00 | 0.384244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216421E+10 | 0.00 |
March | 0.178523E+11 | 0.808501E+10 | 0.123431E+11 | 0.00 | 0.342247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244097E+10 | 0.00 |
April | 0.166373E+11 | 0.667866E+10 | 0.114862E+11 | 0.00 | 0.210558E+10 | 0.00 | 0.00 | 52016166.60 | 0.00 | 0.00 | 0.00 | 0.228099E+10 | 0.00 |
May | 0.171572E+11 | 0.596097E+10 | 0.119357E+11 | 0.00 | 0.142873E+10 | 0.00 | 0.00 | 0.116808E+09 | 0.00 | 0.00 | 0.00 | 0.230093E+10 | 0.00 |
June | 0.169535E+11 | 0.532539E+10 | 0.118862E+11 | 0.00 | 0.139863E+10 | 0.00 | 0.00 | 0.189928E+10 | 0.00 | 0.00 | 0.00 | 0.218498E+10 | 0.00 |
July | 0.166750E+11 | 0.566783E+10 | 0.115358E+11 | 0.00 | 0.136408E+10 | 0.00 | 0.00 | 0.309874E+10 | 0.00 | 0.00 | 0.00 | 0.214971E+10 | 0.00 |
August | 0.176488E+11 | 0.646097E+10 | 0.123357E+11 | 0.00 | 0.148832E+10 | 0.00 | 0.00 | 0.278681E+10 | 0.00 | 0.00 | 0.00 | 0.218689E+10 | 0.00 |
September | 0.166907E+11 | 0.731325E+10 | 0.114788E+11 | 0.00 | 0.133724E+10 | 0.00 | 0.00 | 0.108450E+10 | 0.00 | 0.00 | 0.00 | 0.209901E+10 | 0.00 |
October | 0.170847E+11 | 0.874048E+10 | 0.115432E+11 | 0.00 | 0.161758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219395E+10 | 0.00 |
November | 0.165957E+11 | 0.948004E+10 | 0.110862E+11 | 0.00 | 0.303129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217208E+10 | 0.00 |
December | 0.175045E+11 | 0.103770E+11 | 0.115358E+11 | 0.00 | 0.422730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231172E+10 | 0.00 |
Annual Sum or Average | 0.203866E+12 | 0.924992E+11 | 0.139290E+12 | 0.00 | 0.299301E+11 | 0.00 | 0.00 | 0.903816E+10 | 0.00 | 0.00 | 0.00 | 0.268445E+11 | 0.00 |
Minimum of Months | 0.157399E+11 | 0.532539E+10 | 0.105871E+11 | 0.00 | 0.133724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209901E+10 | 0.00 |
Maximum of Months | 0.178523E+11 | 0.103770E+11 | 0.123431E+11 | 0.00 | 0.466642E+10 | 0.00 | 0.00 | 0.309874E+10 | 0.00 | 0.00 | 0.00 | 0.244097E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.410792E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.282777E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167004E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.466319E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.276721E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120079E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.103551E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.138224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165868E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.315455E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140627E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.410792E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 15676.78 | 17-JAN-15:00 | 6958.21 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3851.14 | 18-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15634.75 | 08-FEB-09:09 | 6958.21 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3685.02 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15628.36 | 13-MAR-08:09 | 6958.21 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3313.51 | 06-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 15316.55 | 10-APR-08:09 | 6958.21 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2858.77 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 14960.05 | 15-MAY-08:30 | 6958.21 | 01-MAY-19:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2373.49 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 14972.41 | 05-JUN-08:09 | 6958.21 | 01-JUN-19:40 | 10112.62 | 01-JUN-07:10 | 0.00 | 1688.66 | 26-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 14980.22 | 20-JUL-08:09 | 6958.21 | 01-JUL-19:00 | 10112.62 | 01-JUL-07:10 | 0.00 | 3834.49 | 03-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 15265.55 | 29-AUG-08:20 | 6958.21 | 01-AUG-19:40 | 10112.62 | 01-AUG-07:10 | 0.00 | 4268.25 | 04-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 15328.85 | 21-SEP-08:30 | 6958.21 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 1731.46 | 29-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15631.35 | 30-OCT-08:09 | 6958.21 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2463.57 | 24-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 15678.12 | 27-NOV-15:00 | 6958.21 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3109.17 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 15690.35 | 12-DEC-15:00 | 6958.21 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3729.88 | 08-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 14960.05 | 6958.21 | 10112.62 | 0.00 | 1688.66 | 0.00 | 0.00 | |||||
Maximum of Months | 15690.35 | 6958.21 | 10112.62 | 0.00 | 4268.25 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2916.32 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2940.30 | 21-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2934.51 | 01-MAR-12:09 | 0.00 |
April | 1683.90 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 2838.17 | 01-APR-11:00 | 0.00 |
May | 2850.74 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2639.01 | 01-MAY-11:20 | 0.00 |
June | 8420.13 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2351.07 | 01-JUN-11:00 | 0.00 |
July | 9305.46 | 03-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2067.01 | 01-JUL-11:50 | 0.00 |
August | 12558.47 | 04-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1831.92 | 09-AUG-11:00 | 0.00 |
September | 6655.39 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1962.34 | 27-SEP-11:00 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2258.05 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2543.71 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2768.79 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1831.92 | 0.00 | ||
Maximum of Months | 12558.47 | 0.00 | 0.00 | 0.00 | 2940.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 36095.60 | 18-JAN-16:00 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 3390.74 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30676.90 | 03-FEB-15:00 | 15471.97 | 10112.62 | 0.00 | 0.00 | 2733.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29890.52 | 11-MAR-15:00 | 15304.41 | 10112.62 | 0.00 | 0.00 | 2023.24 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29364.46 | 18-APR-14:00 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1331.97 | 0.00 | 0.00 | 1603.99 | 0.00 |
May | 30363.49 | 31-MAY-14:00 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1331.97 | 0.00 | 0.00 | 2639.34 | 0.00 |
June | 35892.19 | 27-JUN-14:39 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1407.67 | 0.00 | 0.00 | 8112.57 | 0.00 |
July | 37712.39 | 03-JUL-15:30 | 12891.30 | 10112.62 | 0.00 | 0.00 | 3831.28 | 0.00 | 0.00 | 9267.41 | 0.00 |
August | 42122.25 | 04-AUG-14:00 | 14472.11 | 10112.62 | 0.00 | 0.00 | 4094.03 | 0.00 | 0.00 | 11673.38 | 0.00 |
September | 34005.53 | 08-SEP-14:09 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1331.97 | 0.00 | 0.00 | 6318.61 | 0.00 |
October | 28838.09 | 30-OCT-08:09 | 15631.35 | 10112.62 | 0.00 | 0.00 | 1411.69 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35654.60 | 25-NOV-16:49 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 2960.17 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36107.57 | 08-DEC-16:49 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 3409.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28838.09 | 12891.30 | 10112.62 | 0.00 | 0.00 | 1331.97 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42122.25 | 15631.35 | 10112.62 | 6958.21 | 0.00 | 4094.03 | 0.00 | 0.00 | 11673.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 406442.41 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 355725.09 | 01-FEB-21:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 312151.17 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 169860.58 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 51352.16 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9083.48 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 24935.01 | 30-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 64399.47 | 24-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 285967.98 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 399655.34 | 09-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 406442.41 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.33 | 15.32 | 13.33 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
February | 47.50 | 15.77 | 14.83 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
March | 20.00 | 15.35 | 5.67 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
April | 6.33 | 15.60 | 2.50 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
May | 0.33 | 17.07 | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 17.11 | 1.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
November | 22.67 | 15.19 | 4.33 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
December | 32.67 | 15.17 | 6.67 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
Annual Sum or Average | 200.00 | 15.41 | 48.83 | 15.81 | 0.17 | 15.82 | 0.17 | 15.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.33 | 17.11 | 14.83 | 17.11 | 0.17 | 24.57 | 0.17 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.17 | 13.93 | 4.33 | 13.93 | 0.00 | 13.93 | 0.00 | 13.93 |
February | 101.83 | 14.18 | 4.17 | 14.18 | 0.00 | 14.18 | 0.00 | 14.18 |
March | 84.83 | 14.47 | 4.83 | 14.46 | 0.00 | 14.46 | 0.00 | 14.46 |
April | 41.83 | 14.73 | 3.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
May | 2.33 | 14.86 | 0.17 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.30 | 0.00 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.67 | 14.97 | 0.17 | 14.96 | 0.17 | 17.03 | 0.00 | 17.03 |
October | 16.83 | 14.93 | 1.67 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
November | 76.50 | 14.35 | 2.67 | 14.35 | 0.00 | 14.35 | 0.00 | 14.35 |
December | 117.83 | 14.20 | 5.33 | 14.20 | 0.00 | 14.20 | 0.00 | 14.20 |
Annual Sum or Average | 563.83 | 14.26 | 26.33 | 14.26 | 1.83 | 14.30 | 0.00 | 14.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.17 | 14.97 | 5.33 | 14.96 | 0.83 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.83 | 8.83 | 4.67 | 8.81 | 0.00 | 8.81 | 0.00 | 8.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22.83 | 7.74 | 12.67 | 7.60 | 0.00 | 7.60 | 0.00 | 7.60 |
Annual Sum or Average | 46.67 | 8.30 | 17.33 | 8.14 | 0.00 | 8.14 | 0.00 | 8.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.83 | 8.83 | 12.67 | 8.81 | 0.00 | 8.81 | 0.00 | 8.81 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.65 | 300.00 | 20.65 | 300.00 | 20.65 |
February | 276.00 | 20.64 | 276.00 | 20.64 | 276.00 | 20.64 |
March | 324.00 | 20.71 | 324.00 | 20.71 | 324.00 | 20.71 |
April | 297.50 | 21.01 | 258.83 | 20.91 | 258.83 | 20.87 |
May | 301.50 | 22.02 | 106.50 | 21.73 | 103.67 | 21.55 |
June | 153.83 | 23.07 | 172.50 | 23.45 | 61.33 | 23.46 |
July | 68.00 | 24.43 | 286.67 | 24.18 | 63.00 | 24.24 |
August | 99.83 | 24.15 | 288.33 | 24.08 | 87.67 | 24.12 |
September | 154.50 | 22.10 | 166.50 | 22.50 | 59.33 | 22.23 |
October | 300.00 | 20.88 | 262.33 | 20.79 | 262.33 | 20.76 |
November | 288.00 | 20.74 | 270.17 | 20.71 | 270.17 | 20.70 |
December | 300.00 | 20.69 | 300.00 | 20.69 | 300.00 | 20.69 |
Annual Sum or Average | 2863.17 | 21.29 | 3011.83 | 21.48 | 2366.33 | 21.34 |
Minimum of Months | 68.00 | 20.64 | 106.50 | 20.64 | 59.33 | 20.64 |
Maximum of Months | 324.00 | 24.43 | 324.00 | 24.18 | 324.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.55 | 276.00 | 15.55 | 276.00 | 15.55 |
March | 324.00 | 15.75 | 324.00 | 15.75 | 324.00 | 15.75 |
April | 300.00 | 17.03 | 279.67 | 16.86 | 279.67 | 16.80 |
May | 309.83 | 20.13 | 189.50 | 19.84 | 187.33 | 19.69 |
June | 220.33 | 23.80 | 227.83 | 24.45 | 147.00 | 24.48 |
July | 214.33 | 26.31 | 286.83 | 26.26 | 207.83 | 26.30 |
August | 179.33 | 25.98 | 296.33 | 26.08 | 164.50 | 26.12 |
September | 174.17 | 20.89 | 217.17 | 22.09 | 104.83 | 21.62 |
October | 300.00 | 16.84 | 300.00 | 16.84 | 300.00 | 16.84 |
November | 288.00 | 16.07 | 288.00 | 16.07 | 288.00 | 16.07 |
December | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
Annual Sum or Average | 3186.00 | 18.49 | 3285.33 | 18.80 | 2879.17 | 18.59 |
Minimum of Months | 174.17 | 15.53 | 189.50 | 15.53 | 104.83 | 15.53 |
Maximum of Months | 324.00 | 26.31 | 324.00 | 26.26 | 324.00 | 26.30 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.98 | 300.00 | 9.98 | 300.00 | 9.98 |
February | 276.00 | 10.03 | 276.00 | 10.03 | 276.00 | 10.03 |
March | 324.00 | 10.43 | 324.00 | 10.43 | 324.00 | 10.43 |
April | 300.00 | 12.62 | 300.00 | 12.62 | 300.00 | 12.62 |
May | 312.00 | 17.16 | 302.50 | 17.08 | 302.50 | 17.05 |
June | 261.00 | 22.46 | 207.17 | 22.72 | 175.67 | 22.70 |
July | 199.50 | 26.91 | 286.67 | 26.69 | 194.00 | 26.78 |
August | 191.83 | 26.03 | 284.83 | 26.07 | 170.17 | 26.15 |
September | 192.50 | 20.27 | 191.50 | 21.06 | 108.00 | 20.57 |
October | 300.00 | 13.04 | 300.00 | 13.04 | 300.00 | 13.04 |
November | 288.00 | 11.12 | 288.00 | 11.12 | 288.00 | 11.12 |
December | 300.00 | 9.89 | 300.00 | 9.89 | 300.00 | 9.89 |
Annual Sum or Average | 3244.83 | 14.94 | 3360.67 | 15.23 | 3038.33 | 14.99 |
Minimum of Months | 191.83 | 9.89 | 191.50 | 9.89 | 108.00 | 9.89 |
Maximum of Months | 324.00 | 26.91 | 324.00 | 26.69 | 324.00 | 26.78 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.208596E+09 | 52016166.60 | 14.00 | 0.142314E+09 | 66282217.10 | 0.00 | 0.68 | 18-APR-15:10 | 0.00 | 01-APR-00:10 | 6952.21 | 18-APR-15:10 | 4887.09 | 18-APR-15:10 | 2250.45 | 18-APR-12:00 | 1683.90 | 18-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 0.446246E+09 | 0.110351E+09 | 36.50 | 0.331990E+09 | 0.114256E+09 | 0.00 | 0.76 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 | 7485.88 | 31-MAY-17:00 | 6128.17 | 31-MAY-15:10 | 1679.91 | 31-MAY-09:00 | 1873.56 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 |
June | 0.414582E+10 | 0.970899E+09 | 181.09 | 0.297233E+10 | 0.117349E+10 | 0.00 | 1.00 | 13-JUN-15:10 | 0.00 | 01-JUN-00:10 | 24948.90 | 26-JUN-07:02 | 15483.35 | 24-JUN-07:02 | 13165.97 | 26-JUN-07:02 | 5197.47 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.663398E+10 | 0.151311E+10 | 242.68 | 0.450315E+10 | 0.213083E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 24038.56 | 20-JUL-07:03 | 14096.95 | 01-JUL-07:02 | 14006.12 | 20-JUL-07:03 | 5073.46 | 20-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.674105E+10 | 0.155870E+10 | 262.18 | 0.458948E+10 | 0.215157E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 26576.49 | 04-AUG-07:03 | 13888.30 | 19-AUG-07:02 | 17413.24 | 04-AUG-07:03 | 5401.23 | 04-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.251871E+10 | 0.605899E+09 | 125.37 | 0.213199E+10 | 0.386725E+09 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22473.95 | 11-SEP-07:02 | 14049.11 | 02-SEP-07:02 | 9401.62 | 11-SEP-07:02 | 4830.13 | 11-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.206944E+11 | 0.481097E+10 | 861.81 | 0.146713E+11 | 0.602315E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.674105E+10 | 0.155870E+10 | 262.18 | 0.458948E+10 | 0.215157E+10 | 0.00 | 1.00 | 0.00 | 26576.49 | 15483.35 | 17413.24 | 5401.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 23401074.43 | 6456376.28 | 3.17 | 16618944.10 | 6782130.32 | 0.00 | 0.15 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 | 3553.16 | 31-MAY-15:10 | 2535.03 | 31-MAY-15:10 | 1018.12 | 31-MAY-15:10 | 977.18 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 |
June | 0.373516E+10 | 0.928384E+09 | 88.29 | 0.244100E+10 | 0.129416E+10 | 0.00 | 1.00 | 18-JUN-15:15 | 0.00 | 01-JUN-00:10 | 58111.33 | 26-JUN-19:33 | 37971.08 | 28-JUN-19:15 | 23292.36 | 26-JUN-19:33 | 13035.87 | 26-JUN-19:33 | 0.00 | 01-JUN-00:10 |
July | 0.658224E+10 | 0.158563E+10 | 161.50 | 0.401758E+10 | 0.256465E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 61483.97 | 03-JUL-20:05 | 39497.00 | 30-JUL-16:42 | 31870.43 | 03-JUL-20:05 | 13322.40 | 03-JUL-20:05 | 0.00 | 01-JUL-00:10 |
August | 0.501572E+10 | 0.122811E+10 | 134.91 | 0.304926E+10 | 0.196647E+10 | 0.00 | 1.00 | 01-AUG-17:12 | 0.00 | 01-AUG-00:10 | 63194.09 | 03-AUG-19:45 | 38524.35 | 05-AUG-17:23 | 36632.27 | 03-AUG-19:45 | 13509.09 | 03-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.182527E+10 | 0.478602E+09 | 64.99 | 0.143766E+10 | 0.387607E+09 | 0.00 | 1.00 | 08-SEP-17:17 | 0.00 | 01-SEP-00:10 | 52147.43 | 10-SEP-14:15 | 42680.13 | 10-SEP-14:15 | 9467.31 | 10-SEP-14:15 | 12092.31 | 10-SEP-14:15 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.171818E+11 | 0.422718E+10 | 452.85 | 0.109621E+11 | 0.621967E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.658224E+10 | 0.158563E+10 | 161.50 | 0.401758E+10 | 0.256465E+10 | 0.00 | 1.00 | 0.00 | 63194.09 | 42680.13 | 36632.27 | 13509.09 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 34.94 | 222.63 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 72.65 | 171.77 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 105.72 | 102.89 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 199.56 | 66.98 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 220.15 | 39.96 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 268.65 | 36.63 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 291.34 | 38.58 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 255.32 | 44.37 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 193.11 | 64.10 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 117.59 | 76.34 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 47.87 | 128.00 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 31.09 | 198.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 153.56 | 98.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 31.09 | 36.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 291.34 | 222.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 34.94 | 222.63 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 72.65 | 171.77 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 105.72 | 102.89 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 199.56 | 66.98 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 220.15 | 39.96 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 268.65 | 36.63 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 291.34 | 38.58 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 255.32 | 44.37 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 193.11 | 64.10 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 117.59 | 76.34 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 47.87 | 128.00 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 31.09 | 198.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 153.56 | 98.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 31.09 | 36.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 291.34 | 222.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.20 | 141.88 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 2.42 | 110.07 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 16.20 | 63.86 | 0.00 | 0.00 | 0.00 |
April | 42.75 | 0.29 | 42.45 | 30.47 | 39.82 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 58.48 | 22.24 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 75.54 | 20.27 | 0.00 | 0.00 | 0.00 |
July | 60.94 | 4.09 | 56.85 | 70.20 | 21.48 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 58.63 | 24.93 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 36.89 | 38.00 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 18.74 | 46.12 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 5.27 | 79.15 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.10 | 123.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 31.26 | 60.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.10 | 20.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 75.54 | 141.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.20 | 141.88 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 2.42 | 110.07 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 16.20 | 63.86 | 0.00 | 0.00 | 0.00 |
April | 42.74 | 0.29 | 42.45 | 30.47 | 39.82 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 58.48 | 22.24 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 75.53 | 20.27 | 0.00 | 0.00 | 0.00 |
July | 60.93 | 4.09 | 56.85 | 70.20 | 21.48 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 58.63 | 24.93 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 36.89 | 38.00 | 0.00 | 0.00 | 0.00 |
October | 29.09 | 0.00 | 29.09 | 18.74 | 46.12 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 5.27 | 79.15 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.10 | 123.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 31.26 | 60.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.10 | 20.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 75.53 | 141.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.15 | 89.53 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.03 | 68.79 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.62 | 39.30 | 9.50 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.64 | 25.63 | 34.00 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 180.85 | 18.20 | 37.00 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 202.96 | 20.59 | 21.67 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 199.52 | 26.35 | 12.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 168.24 | 27.07 | 14.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.15 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.33 | 31.75 | 4.83 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.71 | 48.64 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.44 | 75.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.06 | 42.30 | 133.83 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.44 | 18.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 202.96 | 89.53 | 37.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 93595248.03 | 0.596296E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.175744E+09 | 0.415551E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.283166E+09 | 0.275582E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.517261E+09 | 0.173608E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.589650E+09 | 0.107020E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.696351E+09 | 94955255.45 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.780337E+09 | 0.103335E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.683842E+09 | 0.118842E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.500534E+09 | 0.166144E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.314944E+09 | 0.204477E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.124083E+09 | 0.331767E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 83265993.48 | 0.531805E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.484277E+10 | 0.311938E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 83265993.48 | 94955255.45 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.780337E+09 | 0.596296E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 93595248.03 | 0.596296E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.175744E+09 | 0.415551E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.283166E+09 | 0.275582E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.517261E+09 | 0.173608E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.589650E+09 | 0.107020E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.696351E+09 | 94955255.45 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.780337E+09 | 0.103335E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.683842E+09 | 0.118842E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.500534E+09 | 0.166144E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.314944E+09 | 0.204477E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.124083E+09 | 0.331767E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 83265993.48 | 0.531805E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.484277E+10 | 0.311938E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 83265993.48 | 94955255.45 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.780337E+09 | 0.596296E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52073982.96 | 0.00 | 52073982.96 | 540289.69 | 0.380021E+09 |
February | 59630661.61 | 0.00 | 59630661.61 | 5846592.73 | 0.266278E+09 |
March | 98960829.24 | 2684.40 | 98958144.85 | 43385121.03 | 0.171053E+09 |
April | 0.110796E+09 | 754006.91 | 0.110042E+09 | 78973656.61 | 0.103219E+09 |
May | 0.149190E+09 | 5777377.20 | 0.143413E+09 | 0.156630E+09 | 59562996.63 |
June | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.195792E+09 | 52546826.75 |
July | 0.163211E+09 | 10950639.71 | 0.152260E+09 | 0.188035E+09 | 57538853.17 |
August | 0.137186E+09 | 2858059.88 | 0.134328E+09 | 0.157032E+09 | 66782325.87 |
September | 0.101528E+09 | 67832.33 | 0.101460E+09 | 95609516.07 | 98493234.06 |
October | 77929157.78 | 0.00 | 77929157.78 | 50187027.90 | 0.123520E+09 |
November | 52753737.13 | 0.00 | 52753737.13 | 13671127.18 | 0.205145E+09 |
December | 35359907.87 | 0.00 | 35359907.87 | 255466.28 | 0.330471E+09 |
Annual Sum or Average | 0.120698E+10 | 35619645.52 | 0.117136E+10 | 0.985959E+09 | 0.191463E+10 |
Minimum of Months | 35359907.87 | 0.00 | 35359907.87 | 255466.28 | 52546826.75 |
Maximum of Months | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.195792E+09 | 0.380021E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52072306.59 | 0.00 | 52072306.59 | 540158.68 | 0.380022E+09 |
February | 59628805.47 | 0.00 | 59628805.47 | 5845929.85 | 0.266279E+09 |
March | 98957687.10 | 2684.27 | 98955002.83 | 43382232.17 | 0.171054E+09 |
April | 0.110793E+09 | 753971.57 | 0.110039E+09 | 78970503.09 | 0.103219E+09 |
May | 0.149186E+09 | 5777106.41 | 0.143409E+09 | 0.156625E+09 | 59562660.49 |
June | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.195785E+09 | 52546428.72 |
July | 0.163206E+09 | 10950126.44 | 0.152256E+09 | 0.188029E+09 | 57538320.81 |
August | 0.137182E+09 | 2857925.91 | 0.134324E+09 | 0.157027E+09 | 66781914.54 |
September | 0.101525E+09 | 67829.15 | 0.101457E+09 | 95606251.16 | 98492690.46 |
October | 77926706.53 | 0.00 | 77926706.53 | 50184477.84 | 0.123520E+09 |
November | 52751976.39 | 0.00 | 52751976.39 | 13670081.42 | 0.205145E+09 |
December | 35358789.52 | 0.00 | 35358789.52 | 255403.55 | 0.330471E+09 |
Annual Sum or Average | 0.120695E+10 | 35617975.98 | 0.117133E+10 | 0.985921E+09 | 0.191463E+10 |
Minimum of Months | 35358789.52 | 0.00 | 35358789.52 | 255403.55 | 52546428.72 |
Maximum of Months | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.195785E+09 | 0.380022E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64680465.70 | 0.239810E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111345E+09 | 0.166411E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256107E+09 | 0.105256E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.369722E+09 | 66421121.58 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.484386E+09 | 48733562.02 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.526074E+09 | 53378449.44 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.534383E+09 | 70589224.44 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.450624E+09 | 72493117.42 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.324394E+09 | 97228966.18 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.209787E+09 | 85037878.64 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95159197.66 | 0.126086E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 0.202480E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.347070E+10 | 0.133393E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44039114.31 | 48733562.02 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.534383E+09 | 0.239810E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 54.19 | 712.93 | 180.96 | 57.63 | 123.32 | 0.00 | 0.00 |
February | 133.44 | 547.00 | 255.97 | 101.37 | 154.59 | 0.00 | 0.00 |
March | 238.03 | 327.70 | 322.05 | 92.44 | 229.60 | 0.00 | 0.00 |
April | 458.29 | 211.84 | 447.24 | 179.34 | 267.90 | 0.00 | 0.00 |
May | 555.65 | 122.79 | 474.13 | 149.24 | 324.90 | 0.00 | 0.00 |
June | 686.01 | 111.44 | 554.88 | 195.56 | 359.32 | 0.00 | 0.00 |
July | 721.41 | 118.44 | 579.13 | 225.48 | 353.65 | 0.00 | 0.00 |
August | 627.18 | 137.90 | 500.96 | 184.40 | 316.56 | 0.00 | 0.00 |
September | 458.57 | 202.78 | 401.73 | 153.36 | 248.36 | 0.00 | 0.00 |
October | 269.94 | 242.22 | 284.54 | 100.90 | 183.64 | 0.00 | 0.00 |
November | 100.01 | 408.00 | 176.10 | 50.29 | 125.81 | 0.00 | 0.00 |
December | 51.14 | 632.65 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Annual Sum or Average | 364.02 | 313.62 | 359.51 | 128.36 | 231.15 | 0.00 | 0.00 |
Minimum of Months | 51.14 | 111.44 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 721.41 | 712.93 | 579.13 | 225.48 | 359.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1473.18 | 8623.77 | 403.36 | 174.15 | 229.21 | 0.00 | 0.00 |
February | 2584.51 | 6626.02 | 554.23 | 276.06 | 278.17 | 0.00 | 0.00 |
March | 4581.43 | 3006.61 | 874.78 | 418.82 | 455.96 | 0.00 | 0.00 |
April | 5907.07 | 1399.52 | 1188.83 | 715.21 | 473.62 | 0.00 | 0.00 |
May | 7363.19 | 594.16 | 1428.48 | 803.79 | 624.69 | 0.00 | 0.00 |
June | 8377.18 | 621.61 | 1624.18 | 951.06 | 673.12 | 0.00 | 0.00 |
July | 7899.76 | 800.18 | 1636.75 | 1008.04 | 628.72 | 0.00 | 0.00 |
August | 6579.84 | 817.90 | 1362.77 | 776.93 | 585.84 | 0.00 | 0.00 |
September | 4842.71 | 1201.21 | 1058.38 | 614.80 | 443.58 | 0.00 | 0.00 |
October | 3064.91 | 1532.20 | 670.66 | 331.90 | 338.76 | 0.00 | 0.00 |
November | 1691.37 | 3877.40 | 399.04 | 146.61 | 252.42 | 0.00 | 0.00 |
December | 885.07 | 6414.61 | 272.93 | 132.73 | 140.20 | 0.00 | 0.00 |
Annual Sum or Average | 4614.20 | 2942.45 | 958.28 | 530.40 | 427.88 | 0.00 | 0.00 |
Minimum of Months | 885.07 | 594.16 | 272.93 | 132.73 | 140.20 | 0.00 | 0.00 |
Maximum of Months | 8377.18 | 8623.77 | 1636.75 | 1008.04 | 673.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145155E+09 | 0.190952E+10 | 0.484677E+09 | 0.154367E+09 | 0.330310E+09 | 0.00 | 0.00 |
February | 0.322829E+09 | 0.132331E+10 | 0.619234E+09 | 0.245241E+09 | 0.373992E+09 | 0.00 | 0.00 |
March | 0.637553E+09 | 0.877723E+09 | 0.862567E+09 | 0.247600E+09 | 0.614966E+09 | 0.00 | 0.00 |
April | 0.118789E+10 | 0.549078E+09 | 0.115925E+10 | 0.464862E+09 | 0.694385E+09 | 0.00 | 0.00 |
May | 0.148826E+10 | 0.328870E+09 | 0.126992E+10 | 0.399715E+09 | 0.870204E+09 | 0.00 | 0.00 |
June | 0.177813E+10 | 0.288855E+09 | 0.143825E+10 | 0.506899E+09 | 0.931352E+09 | 0.00 | 0.00 |
July | 0.193223E+10 | 0.317234E+09 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
August | 0.167985E+10 | 0.369355E+09 | 0.134177E+10 | 0.493892E+09 | 0.847878E+09 | 0.00 | 0.00 |
September | 0.118861E+10 | 0.525600E+09 | 0.104128E+10 | 0.397522E+09 | 0.643756E+09 | 0.00 | 0.00 |
October | 0.723020E+09 | 0.648753E+09 | 0.762111E+09 | 0.270243E+09 | 0.491868E+09 | 0.00 | 0.00 |
November | 0.259216E+09 | 0.105753E+10 | 0.456463E+09 | 0.130355E+09 | 0.326108E+09 | 0.00 | 0.00 |
December | 0.136970E+09 | 0.169448E+10 | 0.350817E+09 | 0.133214E+09 | 0.217603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114797E+11 | 0.989031E+10 | 0.113375E+11 | 0.404784E+10 | 0.728963E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136970E+09 | 0.288855E+09 | 0.350817E+09 | 0.130355E+09 | 0.217603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193223E+10 | 0.190952E+10 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.394577E+10 | 0.230979E+11 | 0.108036E+10 | 0.466456E+09 | 0.613909E+09 | 0.00 | 0.00 |
February | 0.625244E+10 | 0.160297E+11 | 0.134079E+10 | 0.667834E+09 | 0.672952E+09 | 0.00 | 0.00 |
March | 0.122709E+11 | 0.805291E+10 | 0.234300E+10 | 0.112176E+10 | 0.122123E+10 | 0.00 | 0.00 |
April | 0.153111E+11 | 0.362755E+10 | 0.308145E+10 | 0.185382E+10 | 0.122763E+10 | 0.00 | 0.00 |
May | 0.197216E+11 | 0.159141E+10 | 0.382604E+10 | 0.215288E+10 | 0.167317E+10 | 0.00 | 0.00 |
June | 0.217136E+11 | 0.161122E+10 | 0.420987E+10 | 0.246514E+10 | 0.174474E+10 | 0.00 | 0.00 |
July | 0.211587E+11 | 0.214320E+10 | 0.438388E+10 | 0.269993E+10 | 0.168396E+10 | 0.00 | 0.00 |
August | 0.176234E+11 | 0.219067E+10 | 0.365005E+10 | 0.208093E+10 | 0.156911E+10 | 0.00 | 0.00 |
September | 0.125523E+11 | 0.311353E+10 | 0.274331E+10 | 0.159356E+10 | 0.114975E+10 | 0.00 | 0.00 |
October | 0.820906E+10 | 0.410383E+10 | 0.179630E+10 | 0.888967E+09 | 0.907330E+09 | 0.00 | 0.00 |
November | 0.438402E+10 | 0.100502E+11 | 0.103431E+10 | 0.380025E+09 | 0.654282E+09 | 0.00 | 0.00 |
December | 0.237056E+10 | 0.171809E+11 | 0.731010E+09 | 0.355501E+09 | 0.375509E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.145514E+12 | 0.927930E+11 | 0.302204E+11 | 0.167268E+11 | 0.134936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237056E+10 | 0.159141E+10 | 0.731010E+09 | 0.355501E+09 | 0.375509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217136E+11 | 0.230979E+11 | 0.438388E+10 | 0.269993E+10 | 0.174474E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106564E+10 | -977158654.2 | 0.00 | 0.00 | 744.00 | 0.00 | -88482554.4 | 58.99 | 0.00 | 0.00 |
February | 0.995476E+09 | -915644940.5 | 0.00 | 0.00 | 672.00 | 0.00 | -79831297.5 | 59.00 | 0.00 | 0.00 |
March | 0.114709E+10 | -0.105948E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87610847.9 | 58.99 | 0.00 | 0.00 |
April | 0.102932E+10 | -946417740.4 | 0.00 | 0.00 | 720.00 | 0.00 | -82904262.9 | 58.99 | 0.00 | 0.00 |
May | 0.100715E+10 | -926240553.4 | 0.00 | 0.00 | 744.00 | 0.00 | -80907046.8 | 58.99 | 0.00 | 0.00 |
June | 0.932733E+09 | -860527908.4 | 0.00 | 0.00 | 720.00 | 0.00 | -72204617.2 | 58.99 | 0.00 | 0.00 |
July | 0.856248E+09 | -784702035.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71545843.9 | 58.99 | 0.00 | 0.00 |
August | 0.892984E+09 | -820504985.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72479157.2 | 58.99 | 0.00 | 0.00 |
September | 0.846904E+09 | -773209024.8 | 0.00 | 0.00 | 720.00 | 0.00 | -73695020.5 | 58.99 | 0.00 | 0.00 |
October | 0.900038E+09 | -814132389.8 | 0.00 | 0.00 | 744.00 | 0.00 | -85906060.0 | 58.99 | 0.00 | 0.00 |
November | 0.920666E+09 | -835950892.3 | 0.00 | 0.00 | 720.00 | 0.00 | -84715053.8 | 58.99 | 0.00 | 0.00 |
December | 0.101759E+10 | -929162844.2 | 0.00 | 0.00 | 744.00 | 0.00 | -88426522.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.116118E+11 | -0.106431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -968708284.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.846904E+09 | -0.105948E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88482554.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114709E+10 | -773209024.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71545843.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.95 | 0.88 | 01-JAN-10:20 | 133.19 | 9.59 | 0.00 | 39.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.94 | 0.88 | 03-FEB-10:00 | 143.06 | 9.70 | 0.00 | 73.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.92 | 0.88 | 01-MAR-08:50 | 234.69 | 12.22 | 0.00 | 179.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.91 | 0.88 | 02-APR-14:39 | 261.70 | 12.20 | 0.00 | 220.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.91 | 0.88 | 01-MAY-07:19 | 871.08 | 12.98 | 0.00 | 280.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.91 | 0.88 | 01-JUN-07:30 | 2170.42 | 13.29 | 0.00 | 295.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.91 | 0.88 | 01-JUL-07:40 | 1999.60 | 14.01 | 20.00 | 293.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.91 | 0.88 | 01-AUG-08:20 | 1203.33 | 13.41 | 14.67 | 270.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.92 | 0.88 | 01-SEP-07:30 | 231.97 | 12.10 | 0.00 | 189.83 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.93 | 0.88 | 02-OCT-09:09 | 177.52 | 10.75 | 0.00 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.94 | 0.88 | 01-NOV-09:50 | 152.10 | 10.22 | 0.00 | 65.17 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.97 | 0.88 | 13-DEC-11:30 | 86.58 | 7.45 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.92 | 779.45 | 11.94 | 34.67 | 2016.33 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.91 | 0.88 | 86.58 | 7.45 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.97 | 0.88 | 2170.42 | 14.01 | 20.00 | 295.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.89 | 0.82 | 24-JAN-14:39 | 336.14 | 23.96 | 118.17 | 29.83 | 121.26 | 21.07 | 103.50 | 0.00 |
February | 226.83 | 0.89 | 0.80 | 20-FEB-16:10 | 615.57 | 24.87 | 137.50 | 53.33 | 141.64 | 21.31 | 131.83 | 1.67 |
March | 334.33 | 0.87 | 0.80 | 03-MAR-16:10 | 385.10 | 23.52 | 198.33 | 88.83 | 281.96 | 23.89 | 216.83 | 37.17 |
April | 285.17 | 0.86 | 0.80 | 03-APR-14:09 | 454.48 | 22.96 | 164.00 | 108.50 | 445.15 | 23.84 | 219.67 | 76.67 |
May | 428.67 | 0.87 | 0.80 | 01-MAY-13:50 | 312.65 | 21.57 | 223.17 | 118.00 | 296.14 | 22.67 | 291.33 | 70.50 |
June | 400.67 | 0.85 | 0.80 | 01-JUN-16:19 | 366.60 | 22.08 | 246.00 | 163.17 | 444.92 | 23.36 | 309.17 | 96.33 |
July | 414.00 | 0.85 | 0.80 | 01-JUL-13:39 | 372.15 | 22.35 | 246.00 | 171.83 | 492.91 | 23.58 | 326.17 | 121.67 |
August | 410.83 | 0.86 | 0.80 | 01-AUG-14:30 | 371.76 | 22.15 | 240.50 | 145.33 | 386.49 | 23.15 | 284.83 | 97.33 |
September | 326.50 | 0.87 | 0.80 | 01-SEP-14:30 | 532.04 | 24.63 | 197.17 | 105.17 | 454.55 | 25.15 | 244.33 | 69.83 |
October | 325.17 | 0.88 | 0.80 | 01-OCT-14:50 | 426.92 | 24.31 | 188.50 | 69.17 | 176.40 | 23.22 | 195.17 | 19.33 |
November | 254.83 | 0.91 | 0.82 | 03-NOV-15:30 | 249.30 | 22.45 | 120.83 | 19.50 | 110.36 | 20.70 | 108.33 | 0.00 |
December | 186.17 | 0.92 | 0.83 | 02-DEC-14:30 | 208.20 | 22.07 | 68.00 | 13.17 | 88.36 | 19.40 | 34.83 | 0.00 |
Annual Sum or Average | 3807.33 | 0.87 | 386.76 | 22.96 | 2148.17 | 1085.83 | 314.58 | 22.88 | 2466.00 | 590.50 | ||
Minimum of Months | 186.17 | 0.85 | 0.80 | 208.20 | 21.57 | 68.00 | 13.17 | 88.36 | 19.40 | 34.83 | 0.00 | |
Maximum of Months | 428.67 | 0.92 | 0.83 | 615.57 | 24.87 | 246.00 | 171.83 | 492.91 | 25.15 | 326.17 | 121.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174904E+11 | 28689.14 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128268E+11 | 28689.14 | 01-FEB-02:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.972089E+10 | 28689.14 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.481966E+10 | 28689.14 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.779714E+09 | 28689.14 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80488606.56 | 28689.14 | 05-JUN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.434351E+09 | 28689.14 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305366E+10 | 28689.14 | 02-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.792081E+10 | 28689.14 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134767E+11 | 28689.14 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174904E+11 | 28689.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.627224E+11 | 77430.50 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.443882E+11 | 77430.50 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284594E+11 | 77430.50 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105625E+11 | 77430.50 | 02-APR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.678226E+09 | 68474.01 | 02-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259075E+09 | 25640.11 | 30-SEP-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.507642E+10 | 77430.50 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275378E+11 | 77430.50 | 10-NOV-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493239E+11 | 77430.50 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.627224E+11 | 77430.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.239140E+12 | 219034.29 | 18-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161797E+12 | 219034.29 | 01-FEB-20:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.896526E+11 | 172279.68 | 06-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193335E+11 | 95920.86 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495369E+09 | 20048.60 | 02-MAY-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139738E+10 | 22205.30 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.922138E+11 | 170224.69 | 25-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181406E+12 | 219034.29 | 08-DEC-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785436E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239140E+12 | 219034.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.208596E+09 | 0.142314E+09 | 6952.21 | 18-APR-15:10 | 4887.09 | 0.00 |
May | 0.00 | 0.00 | 0.446246E+09 | 0.331990E+09 | 7485.88 | 31-MAY-17:00 | 6007.95 | 0.00 |
June | 0.00 | 0.00 | 0.414582E+10 | 0.297233E+10 | 24948.90 | 26-JUN-07:02 | 11782.92 | 0.00 |
July | 0.00 | 0.00 | 0.663398E+10 | 0.450315E+10 | 24038.56 | 20-JUL-07:03 | 10032.44 | 0.00 |
August | 0.00 | 0.00 | 0.674105E+10 | 0.458948E+10 | 26576.49 | 04-AUG-07:03 | 9163.25 | 0.00 |
September | 0.00 | 0.00 | 0.251871E+10 | 0.213199E+10 | 22473.95 | 11-SEP-07:02 | 13072.33 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206944E+11 | 0.146713E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.674105E+10 | 0.458948E+10 | 26576.49 | 13072.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 23401074.43 | 16618944.10 | 3553.16 | 31-MAY-15:10 | 2535.03 | 0.00 |
June | 0.00 | 0.00 | 0.373516E+10 | 0.244100E+10 | 58111.33 | 26-JUN-19:33 | 34818.97 | 0.00 |
July | 0.00 | 0.00 | 0.658224E+10 | 0.401758E+10 | 61483.97 | 03-JUL-20:05 | 29613.55 | 0.00 |
August | 0.00 | 0.00 | 0.501572E+10 | 0.304926E+10 | 63194.09 | 03-AUG-19:45 | 26561.82 | 0.00 |
September | 0.00 | 0.00 | 0.182527E+10 | 0.143766E+10 | 52147.43 | 10-SEP-14:15 | 42680.13 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171818E+11 | 0.109621E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.658224E+10 | 0.401758E+10 | 63194.09 | 42680.13 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139604E+10 | 0.08 | 521.22 | 01-JAN-00:03 | 0.08 |
February | 0.123540E+10 | 0.08 | 521.22 | 01-FEB-00:02 | 0.08 |
March | 0.105915E+10 | 0.06 | 521.22 | 01-MAR-00:02 | 0.08 |
April | 0.402410E+09 | 0.02 | 521.22 | 01-APR-00:10 | 0.08 |
May | 20014956.76 | 0.00 | 521.22 | 01-MAY-20:25 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 90145488.82 | 0.01 | 521.22 | 17-OCT-00:10 | 0.08 |
November | 0.885083E+09 | 0.05 | 521.22 | 10-NOV-00:33 | 0.08 |
December | 0.138478E+10 | 0.08 | 521.22 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.647304E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139604E+10 | 0.08 | 521.22 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.965206E+09 | 0.63 | 1169.83 | 02-JAN-06:01 | 0.95 |
February | 0.787699E+09 | 0.56 | 1169.83 | 01-FEB-02:31 | 0.96 |
March | 0.763633E+09 | 0.45 | 1169.83 | 01-MAR-06:01 | 0.96 |
April | 0.589606E+09 | 0.30 | 1169.83 | 01-APR-05:01 | 0.95 |
May | 0.501594E+09 | 0.23 | 1169.83 | 01-MAY-05:01 | 0.95 |
June | 0.490455E+09 | 0.23 | 1169.83 | 05-JUN-06:02 | 0.95 |
July | 0.472180E+09 | 0.21 | 1169.83 | 01-JUL-07:02 | 0.94 |
August | 0.516937E+09 | 0.23 | 1169.83 | 03-AUG-06:03 | 0.93 |
September | 0.474639E+09 | 0.22 | 1169.83 | 02-SEP-07:02 | 0.95 |
October | 0.540743E+09 | 0.25 | 1169.83 | 02-OCT-06:01 | 0.95 |
November | 0.663801E+09 | 0.42 | 1169.83 | 01-NOV-06:02 | 0.95 |
December | 0.841245E+09 | 0.56 | 1169.83 | 01-DEC-06:01 | 0.95 |
Annual Sum or Average | 0.760774E+10 | 0.36 | |||
Minimum of Months | 0.472180E+09 | 0.21 | 1169.83 | 0.93 | |
Maximum of Months | 0.965206E+09 | 0.63 | 1169.83 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230517E+10 | 0.68 | 2160.09 | 01-JAN-00:42 | 0.92 |
February | 0.181934E+10 | 0.65 | 2160.09 | 01-FEB-00:02 | 0.93 |
March | 0.159968E+10 | 0.57 | 2160.09 | 01-MAR-00:02 | 0.93 |
April | 0.111356E+10 | 0.42 | 2160.09 | 02-APR-09:02 | 0.92 |
May | 0.907123E+09 | 0.23 | 1910.23 | 02-MAY-05:01 | 0.92 |
June | 0.908177E+09 | 0.23 | 1926.78 | 30-JUN-17:10 | 0.86 |
July | 0.887750E+09 | 0.22 | 2160.09 | 03-JUL-17:10 | 0.91 |
August | 0.931621E+09 | 0.22 | 2160.09 | 03-AUG-17:10 | 0.90 |
September | 0.862599E+09 | 0.22 | 1139.28 | 08-SEP-17:17 | 0.66 |
October | 0.986696E+09 | 0.37 | 2160.09 | 24-OCT-05:01 | 0.92 |
November | 0.148241E+10 | 0.53 | 2160.09 | 10-NOV-02:42 | 0.92 |
December | 0.200127E+10 | 0.65 | 2160.09 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.158054E+11 | 0.41 | |||
Minimum of Months | 0.862599E+09 | 0.22 | 1139.28 | 0.66 | |
Maximum of Months | 0.230517E+10 | 0.68 | 2160.09 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.965206E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.787699E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.763633E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.641622E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.611945E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146135E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.198529E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.207563E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.108054E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.540743E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.663801E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.841245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.124187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.540743E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.207563E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.230517E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.181934E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159968E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111356E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.913579E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183656E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.247338E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.215973E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134120E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.986696E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.148241E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.200127E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.200326E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.913579E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.247338E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.965206E+09 | 0.00 | 0.174904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787699E+09 | 0.00 | 0.128268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763633E+09 | 0.00 | 0.972089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589606E+09 | 0.208596E+09 | 0.481966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.501594E+09 | 0.446246E+09 | 0.779714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490455E+09 | 0.414582E+10 | 80488606.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.472180E+09 | 0.663398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.516937E+09 | 0.674105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.474639E+09 | 0.251871E+10 | 0.434351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540743E+09 | 0.00 | 0.305366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663801E+09 | 0.00 | 0.792081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841245E+09 | 0.00 | 0.134767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.760774E+10 | 0.206944E+11 | 0.706035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.472180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.965206E+09 | 0.674105E+10 | 0.174904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.230517E+10 | 0.00 | 0.627224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181934E+10 | 0.00 | 0.443882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159968E+10 | 0.00 | 0.284594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111356E+10 | 0.00 | 0.105625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.907123E+09 | 23401074.43 | 0.678226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.908177E+09 | 0.371146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.887750E+09 | 0.641985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.931621E+09 | 0.498626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.862599E+09 | 0.181995E+10 | 0.259075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.986696E+09 | 0.00 | 0.507642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148241E+10 | 0.00 | 0.275378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200127E+10 | 0.00 | 0.493239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158054E+11 | 0.169609E+11 | 0.229008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.862599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230517E+10 | 0.641985E+10 | 0.627224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.965206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589606E+09 | 0.00 | 0.00 | 0.00 | 52016166.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.501594E+09 | 0.00 | 0.00 | 0.00 | 0.110351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490455E+09 | 0.00 | 0.00 | 0.00 | 0.970899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.472180E+09 | 0.00 | 0.00 | 0.00 | 0.151311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.516937E+09 | 0.00 | 0.00 | 0.00 | 0.155870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.474639E+09 | 0.00 | 0.00 | 0.00 | 0.605899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.760774E+10 | 0.00 | 0.00 | 0.00 | 0.481097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.472180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.965206E+09 | 0.00 | 0.00 | 0.00 | 0.155870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.230517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.907123E+09 | 0.00 | 0.00 | 0.00 | 6456376.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.908177E+09 | 0.00 | 0.00 | 0.00 | 0.928384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.887750E+09 | 0.00 | 0.00 | 0.00 | 0.158563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.931621E+09 | 0.00 | 0.00 | 0.00 | 0.122811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.862599E+09 | 0.00 | 0.00 | 0.00 | 0.478602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.986696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158054E+11 | 0.00 | 0.00 | 0.00 | 0.422718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.862599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230517E+10 | 0.00 | 0.00 | 0.00 | 0.158563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1813505.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377704E+10 | 0.00 | 0.00 | 0.12 |
February | 3778481.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293575E+10 | 0.00 | 0.00 | 0.13 |
March | 16585652.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238555E+10 | 0.00 | 0.00 | 0.13 |
April | 0.197034E+09 | 28516520.08 | 0.00 | 31404.51 | 5082682.46 | 0.141414E+10 | 35659034.51 | 0.00 | 0.13 |
May | 0.565481E+09 | 35996156.95 | 0.00 | 264668.84 | 143678.17 | 0.193770E+09 | 0.218272E+09 | 0.00 | 0.17 |
June | 0.204723E+09 | 0.487229E+09 | 0.00 | 2162406.38 | 3170.07 | 19595000.96 | 0.757789E+09 | 0.00 | 0.34 |
July | 4315302.78 | 0.800905E+09 | 0.00 | 2644605.00 | 0.00 | 0.00 | 0.601981E+09 | 0.00 | 0.38 |
August | 5702590.51 | 0.795602E+09 | 0.00 | 2887655.63 | 15213.84 | 0.00 | 0.672181E+09 | 0.00 | 0.43 |
September | 0.307520E+09 | 0.158187E+09 | 0.00 | 2120221.15 | 0.00 | 0.146179E+09 | 0.911415E+09 | 0.00 | 0.29 |
October | 0.311417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111874E+10 | 0.00 | 0.00 | 0.12 |
November | 0.137741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200475E+10 | 0.00 | 0.00 | 0.12 |
December | 3768432.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315751E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.175988E+10 | 0.230644E+10 | 0.00 | 10110961.51 | 5244744.54 | 0.171530E+11 | 0.319730E+10 | 0.00 | 0.21 |
Minimum of Months | 1813505.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.565481E+09 | 0.800905E+09 | 0.00 | 2887655.63 | 5082682.46 | 0.377704E+10 | 0.911415E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125404E+11 | 0.00 | 0.00 | 0.17 |
February | 0.713520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881135E+10 | 0.00 | 0.00 | 0.18 |
March | 0.176376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519343E+10 | 0.00 | 0.00 | 0.19 |
April | 0.288015E+10 | 0.00 | 0.00 | 0.00 | 95794990.53 | 0.160475E+10 | 0.00 | 0.00 | 0.18 |
May | 0.235220E+10 | 31757.82 | 0.00 | 71.51 | 32267260.23 | 43005440.51 | 70540.51 | 0.00 | 0.18 |
June | 0.206885E+10 | 0.508491E+09 | 0.00 | 628906.54 | 2733711.66 | 0.00 | 0.431697E+09 | 0.00 | 0.22 |
July | 0.937325E+09 | 0.878662E+09 | 0.00 | 2701814.77 | 0.00 | 0.00 | 0.143723E+10 | 0.00 | 0.28 |
August | 0.117522E+10 | 0.785191E+09 | 0.00 | 2317366.99 | 577892.22 | 0.00 | 0.135374E+10 | 0.00 | 0.28 |
September | 0.273701E+10 | 0.159514E+09 | 0.00 | 849990.21 | 0.00 | 20373874.57 | 0.402500E+09 | 0.00 | 0.20 |
October | 0.330378E+10 | 0.00 | 0.00 | 0.00 | 2728318.70 | 0.313520E+09 | 0.00 | 0.00 | 0.17 |
November | 0.159435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473047E+10 | 0.00 | 0.00 | 0.17 |
December | 0.369665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982561E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.201270E+11 | 0.233189E+10 | 0.00 | 6498150.02 | 0.134102E+09 | 0.430829E+11 | 0.362523E+10 | 0.00 | 0.20 |
Minimum of Months | 0.231217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.330378E+10 | 0.878662E+09 | 0.00 | 2701814.77 | 95794990.53 | 0.125404E+11 | 0.143723E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.337126E+12 | 0.243984E+12 | 0.00 | 0.165505E+11 | 0.914374E+11 |
February | 0.417796E+12 | 0.171337E+12 | 0.00 | 0.124644E+11 | 0.637654E+11 |
March | 0.715919E+12 | 0.118084E+12 | 0.00 | 0.935932E+10 | 0.391707E+11 |
April | 0.888709E+12 | 0.505013E+11 | 0.00 | 0.600238E+10 | 0.121769E+11 |
May | 0.106520E+13 | 0.215775E+11 | 0.00 | 0.330462E+10 | 0.140036E+10 |
June | 0.112801E+13 | 0.243681E+11 | 0.00 | 0.248699E+10 | 0.981985E+10 |
July | 0.115536E+13 | 0.326395E+11 | 0.00 | 0.129222E+10 | 0.163150E+11 |
August | 0.999771E+12 | 0.396123E+11 | 0.00 | 0.163066E+10 | 0.145436E+11 |
September | 0.688205E+12 | 0.490766E+11 | 0.00 | 0.421027E+10 | 0.577056E+10 |
October | 0.477718E+12 | 0.461653E+11 | 0.00 | 0.504473E+10 | 0.429493E+10 |
November | 0.248725E+12 | 0.122646E+12 | 0.00 | 0.846732E+10 | 0.381951E+11 |
December | 0.156120E+12 | 0.192710E+12 | 0.00 | 0.133566E+11 | 0.712484E+11 |
Annual Sum or Average | 0.827866E+13 | 0.111270E+13 | 0.00 | 0.841699E+11 | 0.368138E+12 |
Minimum of Months | 0.156120E+12 | 0.215775E+11 | 0.00 | 0.129222E+10 | 0.140036E+10 |
Maximum of Months | 0.115536E+13 | 0.243984E+12 | 0.00 | 0.165505E+11 | 0.914374E+11 |