Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 10:43:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1144.29 | 236.66 | 236.66 |
Net Site Energy | 1144.29 | 236.66 | 236.66 |
Total Source Energy | 3623.73 | 749.46 | 749.46 |
Net Source Energy | 3623.73 | 749.46 | 749.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 205.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1144.17 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 205.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 110.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 205.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 126.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.30 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 236.64 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.30 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 236.64 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1144.174 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1144.174 | 100.00 |
Total On-Site and Utility Electric Sources | 1144.174 | 100.00 |
Total Electricity End Uses | 1144.174 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 66.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3155.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-14:00 | 16-MAR-06:10 | - | - | - | - | - | - | - | - | - | - | 22-JUN-11:00 |
Heating | 0.00 | 9262.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26365.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10817.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1674.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87152.59 | 9262.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 9262.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 26365.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8512.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1674.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 650.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 425.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 399.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 72.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3623.60 | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 134.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 82.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 749.43 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 134.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 82.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 749.43 | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.29 |
ZONE2 FINE STORAGE DIRECT AIR | 3.69 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39930.58 |
PSZ-OFFICE HEATING COIL | 31185.86 |
PSZ-FINE STORAGE HEATING COIL | 112432.32 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.000000 | 1.29 |
PSZ-FINE STORAGE | 3.69 | 3.69 | 3.69 | 3.69 | 3.69 | 3.69 | 1.00 | 1.00 | 3.69 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.29 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.69 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.29 | 1473.85 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.69 | 7038.48 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 1.29 | 26670.79 | 31185.86 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.69 | 3.69 | 3.69 | 3.69 | 91558.60 | 112432.32 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.29 | 0.646363 | 1.29 | 26670.79 | 13659.97 | 26670.79 | 0.763990 | 0.763990 |
PSZ-FINE STORAGE COOLING COIL | 3.69 | 1.84 | 3.69 | 91558.60 | 45779.24 | 91558.60 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6762 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6762 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6762 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.380 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.380 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.380 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.74295144E-12 | -0.15622792E-15 | 0.15818062E-14 | 0.12467337E-15 |
8 | 3 | -0.37175021E-03 | 0.46723563E-06 | -0.53800768E-04 | 0.14257918E-12 |
9 | 2 | 1.7087087 | 0.10360435E-01 | 1.1170133 | -0.71269727E-04 |
10 | 1 | -7.1697731 | 0.27078767 | -16.948219 | 0.32746695 |
11 | 0 | 5.9162373 | 0.17365257 | 16.286061 | |
12 | 4 | 0.74295144E-12 | -0.15622792E-15 | 0.15818062E-14 | 0.12467337E-15 |
13 | 3 | -0.37175021E-03 | 0.46723563E-06 | -0.53800768E-04 | 0.14257918E-12 |
14 | 2 | 1.7087087 | 0.10360435E-01 | 1.1170133 | -0.71269727E-04 |
15 | 1 | -7.1697731 | 0.27078767 | -16.948219 | 0.32746695 |
16 | 0 | 5.9162373 | 0.17365257 | 16.286061 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.15818062E-14 | -0.15622792E-15 | 0.74295144E-12 | 0.12467337E-15 |
85 | 3 | -0.53800768E-04 | 0.46723563E-06 | -0.37175021E-03 | 0.14257918E-12 |
86 | 2 | 1.1170133 | 0.10360435E-01 | 1.7087087 | -0.71269727E-04 |
87 | 1 | -16.948219 | 0.27078767 | -7.1697731 | 0.32746695 |
88 | 0 | 16.286061 | 0.17365257 | 5.9162373 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.113_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
2 | NONRESWINDOW_U_1.113_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
3 | NONRESWINDOW_U_1.113_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
4 | NONRESWINDOW_U_1.113_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.35 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.350 | 0.352 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13075.29564 | 15690.35477 | 1.07727 | 1.29273 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 32.44067 | 1.71658E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7105.00413 | 8526.00495 | 0.19947 | 0.23937 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70000 | 6.99286E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 47830.24651 | 57396.29582 | 3.07255 | 3.68706 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.20000 | 1.71672E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 13673.06526 | 16407.67831 | 0.32370 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70000 | 6.99286E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.20000 | 1.71672E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 8.70000 | 6.99286E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19642.78 | 1.29273 | 1.29273 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7014.91 | 0.23937 | 0.23937 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 68812.69 | 3.68706 | 3.68706 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 16066.25 | 0.42471 | 0.42471 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29273 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.68706 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39930.58449 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29273 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29273 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29273 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29273 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29273 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.29273 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.68706 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.68706 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.68706 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.68706 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.68706 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.68706 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.29273 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.68706 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29273 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29273 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1473.84878 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29273 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29273 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29273 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29273 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29273 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64636 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29273 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26670.79000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 13659.97008 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26670.79000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76399 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76399 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26670.79000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31185.85979 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31185.85979 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.68706 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.68706 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 7038.47519 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.68706 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.68706 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.68706 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.68706 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.68706 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.84353 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.68706 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 91558.60000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 45779.24013 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 91558.60000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 91558.60000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 112432.31905 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 112432.31905 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 25666.8 | 11.05 | 10.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 88692.7 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.1844813303E-002 | 3.4628701632E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1195211833 | 0.1901844574 | Pass | Pass | 6.4040986515E-002 | 0.3144750774 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.8744346228E-002 | 3.9409797815E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10579.27 | 465.97 | 0.00 | -75.4 | 927.31 | 11897.16 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.582 | 0.676 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.582 | 0.676 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.113_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.315 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.113_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.315 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.113_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.315 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.113_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.315 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 5.377 | 0.299 | 0.297 | |||||||||||||||||
North Total or Average | 6.51 | 6.315 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 26.02 | 5.142 | 0.311 | 0.309 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.82 | 83.82 | 134.25 | |
Exterior Lighting Total | 8532.22 | 134.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26670.79 | 20376.22 | 6294.57 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 91558.60 | 64189.90 | 27368.70 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 25666.8 | 11.05 | 10.41 | ||||
PSZ-FINE STORAGE COOLING COIL | 88692.7 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39930.58 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31185.86 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 112432.32 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.29 | 1473.85 | 1140.11 | 1.00 | 1.31 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.69 | 7038.48 | 1908.96 | 1.00 | 1.14 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13075.30 | 15690.35 | 66.24 | 1.077 | 1.293 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.90 | 23.90 | 0.00880 | 32.44 | 0.01717 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 47830.25 | 57396.30 | 41.19 | 3.073 | 3.687 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.69 | 0.00959 | 33.20 | 0.01717 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 0.00 | 33.55 | 0.01724 | 33.20 | 0.01717 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7105.00 | 8526.00 | 35.99 | 0.199 | 0.239 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00808 | 8.70 | 0.00699 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 13673.07 | 16407.68 | 11.78 | 0.324 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00738 | 8.70 | 0.00699 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 10.43 | 0.00702 | 8.70 | 0.00699 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.29 | 1.29 | 0.24 | 0.24 | 1.2927 | 1.2927 | 1.2927 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.69 | 3.69 | 0.42 | 0.42 | 3.6871 | 3.6871 | 3.6871 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39930.584 | 39930.584 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 39930.58 | 39930.58 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.13 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 26670.790 | 20376.217 | 1.292730 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 26670.79 | 21385.93 | 1.292730 | 25.50 | 17.70 | 0.00946547 | 12.00 | 11.25 | 0.00800000 | 32.44 | 0.01716576 | 25.13 | 7.9123 | 23.90 | 0.00880385 | 47.6083 | 13075.30 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31185.860 | 31185.860 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31185.86 | 31185.86 | 1.292725 | 20.04 | 14.47 | 0.00799578 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.9123 | 21.10 | 0.00808196 | 51.8588 | 7105.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 91558.600 | 64189.903 | 3.687060 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 91558.60 | 68453.85 | 3.687060 | 28.99 | 19.63 | 0.01046696 | 12.00 | 11.25 | 0.00800000 | 33.20 | 0.01716721 | 25.32 | 11.5190 | 26.69 | 0.00959469 | 43.8793 | 47830.25 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 112432.319 | 112432.319 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 112432.32 | 112432.32 | 3.687065 | 14.77 | 11.73 | 0.00733273 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 11.5190 | 15.56 | 0.00737698 | 67.0948 | 13463.95 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39930.584 | 39930.584 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17487860 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 39930.58 | 39930.58 | 1.0000 | 1.17487860 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.13 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39930.58 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26670.790 | 20376.217 | 1.292730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4358 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.292725 | 1.55481093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 26670.79 | 21385.93 | 1.0000 | 1.55481670 | 1.292730 | 25.50 | 17.70 | 0.00946547 | 49744.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26670.79 | 32.44 | 0.01716576 | 25.13 | 0.10228463 | 7.9123 | 23.90 | 0.00880385 | 23.90 | 0.00880385 | 47.6083 | 13075.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31185.860 | 31185.860 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.292725 | 1.55481093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 31185.86 | 31185.86 | 1.0000 | 1.55481093 | 1.292725 | 20.04 | 14.47 | 0.00799578 | 40431.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31185.86 | 8.70 | 0.00699286 | 8.70 | 0.10228463 | 7.9123 | 21.01 | 0.00808196 | 21.10 | 0.00808196 | 51.8588 | 7105.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 91558.600 | 64189.903 | 3.687060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2976 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.687065 | 4.43457639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 91558.60 | 68453.85 | 1.0000 | 4.43457062 | 3.687060 | 28.99 | 19.63 | 0.01046696 | 55873.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91558.60 | 33.20 | 0.01716721 | 25.32 | 0.42471127 | 11.5190 | 26.69 | 0.00959469 | 26.69 | 0.00959469 | 43.8793 | 47830.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 112432.319 | 112432.319 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.687065 | 4.43457639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 112432.32 | 112432.32 | 1.0000 | 4.43457639 | 3.687065 | 14.77 | 11.73 | 0.00733273 | 33380.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112432.32 | 8.70 | 0.00699286 | 8.70 | 0.42471127 | 11.5190 | 15.56 | 0.00737698 | 15.56 | 0.00737698 | 67.0948 | 13463.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3304.83 | 650.00 | 504.00 |
ZONE2 FINE STORAGE | 3516.50 | 3174.67 | 3082.83 |
ZONE3 BULK STORAGE | 3401.00 | 3250.00 | 3084.00 |
Facility | 3529.17 | 3355.17 | 3155.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 69.33 | 0.00 | 66.83 |
ZONE2 FINE STORAGE | 0.00 | 251.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 320.50 | 0.00 | 66.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.350 | 0.521 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.491 | 0.451 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.203 | 0.000 | 1.302 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1260239.85 | 0.00 | 1260239.85 | 3081126.43 | 4341366.28 | 3225648.14 | 5390.91 | 3369.09 | 0.00 | 82.89 |
ZONE2 FINE STORAGE | 5545091.17 | 0.00 | 5545091.17 | 11739418.50 | 17284509.67 | 13393694.68 | 5413.32 | 3346.68 | 0.00 | 1568.78 |
ZONE3 BULK STORAGE | 0.00 | 0.25E+09 | 0.25E+09 | 48387127.55 | 0.30E+09 | 30805497.77 | 6586.77 | 44.08 | 2129.14 | 4870.81 |
Total Facility | 6805331.02 | 0.25E+09 | 0.26E+09 | 63207672.48 | 0.32E+09 | 47424840.58 | 7367.64 | 3397.61 | 2129.14 | 4924.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0960 | 0.0000 | 0.0960 | 0.1428 | 0.2388 | 0.1023 | 266.91 | 3369.09 | 0.00 |
ZONE2 FINE STORAGE | 0.3900 | 0.0000 | 0.3900 | 0.3583 | 0.7483 | 0.4247 | 302.78 | 3333.22 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 12.0642 | 12.0642 | 1.9057 | 13.9698 | 0.9768 | 2237.60 | 29.81 | 1368.60 |
Total Facility | 0.4860 | 12.0642 | 12.5502 | 2.4068 | 14.9569 | 1.5038 | 2243.64 | 3369.87 | 1368.60 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1823038.96 | 0.00 | 1823038.96 | 3225648.14 | 5377.05 | 0.62 | 3382.34 | 81.18 |
PSZ-FINE STORAGE | 8021423.23 | 0.00 | 8021423.23 | 13393694.68 | 5387.98 | 1.25 | 3370.77 | 1565.69 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1389 | 0.0000 | 0.1389 | 0.1023 | 253.35 | 0.55 | 3382.10 |
PSZ-FINE STORAGE | 0.5642 | 0.0000 | 0.5642 | 0.4247 | 302.04 | 0.04 | 3333.92 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3606.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4949.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1432 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6064 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1144.17 | 5771.67 | 01-JAN-07:20 | 87152.59 | 28-JUL-15:00 |
Electricity:Building | 670.82 | 5288.67 | 01-JAN-00:10 | 50600.89 | 01-APR-14:40 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 363.89 | 2117.83 | 01-JAN-00:10 | 28507.00 | 07-APR-14:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 126.24 | 0.00 | 01-JAN-00:10 | 10817.62 | 17-APR-11:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 15.34 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-APR-17:30 |
Ventilation (simple):Fans:Electricity | 15.34 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-APR-17:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 15.34 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-APR-17:30 |
ElectricityPurchased:Facility | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
ElectricityPurchased:Plant | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
Cogeneration:ElectricityPurchased | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
General:Cogeneration:ElectricityPurchased | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
ElectricityNet:Plant | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
Cogeneration:ElectricityNet | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
General:Cogeneration:ElectricityNet | 1144.17 | 5771.67 | 01-JAN-13:20 | 87152.59 | 28-JUL-15:00 |
Electricity:HVAC | 316.30 | 0.00 | 01-JAN-00:10 | 37091.69 | 27-JUL-16:00 |
General:Fans:Electricity | 110.90 | 0.00 | 01-JAN-00:10 | 8512.32 | 02-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 205.40 | 0.00 | 01-JAN-00:10 | 28579.36 | 27-JUL-16:00 |
General:Cooling:Electricity | 205.40 | 0.00 | 01-JAN-00:10 | 28579.36 | 27-JUL-16:00 |
ExteriorLights:Electricity | 134.25 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.25 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 22.79 | 483.00 | 27-MAR-05:10 | 1741.19 | 19-JAN-12:40 |
WaterSystems:Electricity | 22.79 | 483.00 | 27-MAR-05:10 | 1741.19 | 19-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 22.79 | 483.00 | 27-MAR-05:10 | 1741.19 | 19-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.12 | 0.00 | 01-JAN-00:10 | 9262.32 | 16-MAR-06:10 |
NaturalGas:HVAC | 0.12 | 0.00 | 01-JAN-00:10 | 9262.32 | 16-MAR-06:10 |
Heating:NaturalGas | 0.12 | 0.00 | 01-JAN-00:10 | 9262.32 | 16-MAR-06:10 |
General:Heating:NaturalGas | 0.12 | 0.00 | 01-JAN-00:10 | 9262.32 | 16-MAR-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 22-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1121.53 | 0.00 | 01-JAN-00:10 | 147294.18 | 27-JUL-16:00 |
EnergyTransfer:Building | 399.58 | 0.00 | 01-JAN-00:10 | 55264.61 | 27-JUL-16:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 95.74 | 0.00 | 01-JAN-00:10 | 14251.44 | 27-JUL-16:10 |
Heating:EnergyTransfer | 1.13 | 0.00 | 01-JAN-00:10 | 5595.54 | 16-MAR-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.16 | 0.00 | 01-JAN-00:10 | 5595.54 | 16-MAR-06:10 |
General:Heating:EnergyTransfer | 1.13 | 0.00 | 01-JAN-00:10 | 5595.54 | 16-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.16 | 0.00 | 01-JAN-00:10 | 5595.54 | 16-MAR-06:10 |
Cooling:EnergyTransfer | 398.45 | 0.00 | 01-JAN-00:10 | 55264.61 | 27-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 95.58 | 0.00 | 01-JAN-00:10 | 14251.44 | 27-JUL-16:10 |
General:Cooling:EnergyTransfer | 398.45 | 0.00 | 01-JAN-00:10 | 55264.61 | 27-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 95.58 | 0.00 | 01-JAN-00:10 | 14251.44 | 27-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 303.84 | 0.00 | 01-JAN-00:10 | 42432.72 | 27-JUL-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.97 | 0.00 | 01-JAN-00:10 | 4469.65 | 23-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.97 | 0.00 | 01-JAN-00:10 | 4469.65 | 23-DEC-07:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 302.87 | 0.00 | 01-JAN-00:10 | 42432.72 | 27-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 302.87 | 0.00 | 01-JAN-00:10 | 42432.72 | 27-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 721.95 | 0.00 | 01-JAN-00:10 | 93113.63 | 16-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.08 | 0.00 | 01-JAN-00:10 | 6223.64 | 16-MAR-06:10 |
CoolingCoils:EnergyTransfer | 721.87 | 0.00 | 01-JAN-00:10 | 93113.63 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.164 | -95.574 | 0.000 | 0.000 | 9.126 | 30.293 | 31.946 | 13.198 | 0.000 | 6.218 | 19.051 | 0.000 | -6.439 | 0.000 | -7.985 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.971 | -302.860 | 0.000 | 0.000 | 17.214 | 244.699 | 0.000 | 0.000 | 0.000 | 9.791 | 67.821 | 0.000 | 0.000 | 0.000 | -37.635 | -0.006 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.962 | 241.203 | 107.344 | 102.549 | 0.000 | 2.504 | 38.365 | 0.000 | -30.206 | 0.000 | -492.720 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.135 | -398.434 | 0.000 | 0.000 | 57.301 | 516.195 | 139.290 | 115.747 | 0.000 | 18.513 | 125.238 | 0.000 | -36.645 | 0.000 | -538.340 | -0.007 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | -24067.74 | 0.00 | 0.00 | 90.03 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 24604.41 | 0.00 | -865.26 | 0.00 | -908.36 | 0.00 |
ZONE2 FINE STORAGE | 09-APR-15:53 | 0.00 | 0.00 | 0.00 | -76826.93 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 74722.19 | 0.00 | -0.00 | 0.00 | -43.79 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-APR-16:33 | 0.00 | 0.00 | 0.00 | -85781.79 | 0.00 | 0.00 | 0.00 | 4714.92 | 573.75 | 9439.44 | 0.00 | 0.00 | 76378.97 | 0.00 | 0.00 | 0.00 | -5325.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-FEB-06:03 | 0.00 | 0.00 | 15557.00 | 0.00 | 0.00 | 0.00 | 124.57 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1279.96 | 0.00 | -2153.27 | -13395.26 |
ZONE2 FINE STORAGE | 23-DEC-07:13 | 0.00 | 0.00 | 5086.97 | 0.00 | 0.00 | 0.00 | 388.18 | 12891.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1803.36 | -16562.94 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-06:03 | 0.00 | 0.00 | 15557.00 | 0.00 | 0.00 | 0.00 | 1143.56 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 45883.93 | 0.00 | -6462.55 | 0.00 | -63585.25 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2927 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2927 | 0.0791 | 1.0000 | Not calculated | 0.1023 | 0.0791 | ||
PSZ-FINE STORAGE | 3.6871 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.6871 | 0.1152 | 1.0000 | Not calculated | 0.4247 | 0.1152 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2927 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2927 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0791 | ||
PSZ-FINE STORAGE | 3.6871 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.6871 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1152 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2927 | 1.2927 | 1.2927 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.6871 | 3.6871 | 3.6871 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2927 | 1.2927 | 1.2927 | 1.2927 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.6871 | 3.6871 | 3.6871 | 3.6871 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2927 | 1.2927 | 1.2927 | No | 0.1023 | 0.4273 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.6871 | 3.6871 | 3.6871 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2927 | 1.2927 | 1.2927 | 1.2927 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.6871 | 3.6871 | 3.6871 | 3.6871 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 66.83 |
Number of hours not met | 66.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.12 | 9262.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 205.40 | 28579.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.25 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 15.34 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 110.90 | 8512.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.79 | 1741.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1144.17 |
Natural Gas | 0.00 | 0.12 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1144.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 42.48 |
Fans (All) | 26.11 |
Service Water Heating | 4.71 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 236.64 |
Subtotal | 236.64 |
Natural Gas [MJ/m2] | |
Space Heating | 0.02 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.02 |
Subtotal | 0.02 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.11 |
Space Heating | 0.01 |
Space Cooling | 17.95 |
Fans (All) | 11.03 |
Service Water Heating | 1.99 |
Receptacle Equipment | 12.17 |
Miscellaneous | 11.73 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4991.17 | 3470.50 | 298.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2244.33 | 6515.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2112.00 | 3350.17 | 3297.83 | 0.00 | 0.00 |
Min | 2112.00 | 3350.17 | 0.00 | 0.00 | 0.00 |
Max | 4991.17 | 6515.67 | 3297.83 | 0.00 | 0.00 |
Average | 3115.83 | 4445.44 | 1198.72 | 0.00 | 0.00 |
Sum | 9347.50 | 13336.33 | 3596.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33026.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 12922.50 | 69796.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 31283.50 | 76244.17 | 83665.33 | 0.00 | 0.00 |
Min | 12922.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Max | 33026.50 | 76244.17 | 83665.33 | 0.00 | 0.00 |
Average | 25744.17 | 48680.39 | 27888.44 | 0.00 | 0.00 |
Sum | 77232.50 | 146041.17 | 83665.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 3895.67 | 4832.50 | 31.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 1412.33 | 7347.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1309.67 | 5915.17 | 1535.17 | 0.00 | 0.00 |
Min | 1309.67 | 4832.50 | 0.00 | 0.00 | 0.00 |
Max | 3895.67 | 7347.67 | 1535.17 | 0.00 | 0.00 |
Average | 2205.89 | 6031.78 | 522.33 | 0.00 | 0.00 |
Sum | 6617.67 | 18095.33 | 1567.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 30842.33 | 2184.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 11154.00 | 71565.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 22397.33 | 119204.17 | 49591.50 | 0.00 | 0.00 |
Min | 11154.00 | 2184.67 | 0.00 | 0.00 | 0.00 |
Max | 30842.33 | 119204.17 | 49591.50 | 0.00 | 0.00 |
Average | 21464.56 | 64317.94 | 16530.50 | 0.00 | 0.00 |
Sum | 64393.67 | 192953.83 | 49591.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479100E+10 | 21676.68 | 19-JAN-06:02 | 18.30 | 16.26 | 0.632256E+09 | 769.05 | 17-JAN-16:30 | 18.30 | 16.26 |
February | 0.507844E+10 | 23903.66 | 28-FEB-06:02 | 16.88 | 13.54 | 0.582146E+09 | 776.26 | 09-FEB-08:09 | 16.88 | 13.54 |
March | 0.642155E+10 | 20511.64 | 03-MAR-06:02 | 21.10 | 16.96 | 0.683048E+09 | 769.05 | 11-MAR-16:40 | 22.40 | 16.46 |
April | 0.784612E+10 | 24068.25 | 19-APR-05:02 | 15.10 | 11.88 | 0.635074E+09 | 769.07 | 10-APR-15:00 | 15.10 | 11.88 |
May | 0.953600E+10 | 21331.24 | 08-MAY-05:01 | 23.90 | 19.12 | 0.660609E+09 | 769.09 | 22-MAY-12:09 | 33.48 | 23.09 |
June | 0.991840E+10 | 18349.46 | 17-JUN-05:01 | 25.50 | 21.57 | 0.660717E+09 | 768.97 | 05-JUN-07:30 | 25.50 | 21.57 |
July | 0.102428E+11 | 18564.37 | 06-JUL-05:01 | 23.90 | 22.23 | 0.635337E+09 | 769.10 | 31-JUL-12:09 | 32.93 | 25.13 |
August | 0.106769E+11 | 19204.07 | 30-AUG-05:01 | 24.90 | 22.92 | 0.686168E+09 | 768.97 | 25-AUG-12:39 | 24.90 | 22.92 |
September | 0.973165E+10 | 18832.81 | 05-SEP-05:01 | 23.12 | 21.64 | 0.635317E+09 | 768.97 | 05-SEP-12:30 | 25.85 | 23.46 |
October | 0.897684E+10 | 22126.35 | 18-OCT-05:01 | 24.50 | 18.64 | 0.635237E+09 | 769.06 | 18-OCT-15:20 | 27.20 | 19.53 |
November | 0.705132E+10 | 19851.84 | 28-NOV-06:02 | 20.60 | 17.54 | 0.609061E+09 | 769.08 | 06-NOV-15:50 | 20.60 | 17.54 |
December | 0.530610E+10 | 22589.39 | 02-DEC-06:01 | 20.10 | 18.90 | 0.632747E+09 | 769.03 | 13-DEC-16:00 | 20.60 | 15.54 |
Annual Sum or Average | 0.955771E+11 | 0.768772E+10 | ||||||||
Minimum of Months | 0.479100E+10 | 18349.46 | 15.10 | 11.88 | 0.582146E+09 | 768.97 | 15.10 | 11.88 | ||
Maximum of Months | 0.106769E+11 | 24068.25 | 25.50 | 22.92 | 0.686168E+09 | 776.26 | 33.48 | 25.13 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.954638E+10 | 30840.90 | 01-JAN-12:45 | 27.02 | 21.50 | 0.182277E+10 | 2259.51 | 05-JAN-08:39 | 17.03 | 15.88 |
February | 0.110564E+11 | 59225.44 | 19-FEB-13:33 | 26.83 | 21.86 | 0.167947E+10 | 2247.01 | 27-FEB-15:20 | 26.10 | 16.96 |
March | 0.160325E+11 | 55777.11 | 28-MAR-17:06 | 25.92 | 20.77 | 0.197260E+10 | 2247.00 | 11-MAR-14:50 | 25.92 | 20.77 |
April | 0.244556E+11 | 76828.33 | 09-APR-15:53 | 27.20 | 18.64 | 0.185333E+10 | 2247.08 | 17-APR-15:50 | 31.78 | 20.21 |
May | 0.325156E+11 | 69552.03 | 20-MAY-17:42 | 28.48 | 21.59 | 0.192880E+10 | 2246.81 | 15-MAY-07:10 | 28.48 | 21.59 |
June | 0.362048E+11 | 66750.75 | 25-JUN-16:53 | 29.40 | 24.47 | 0.192889E+10 | 2246.81 | 19-JUN-07:10 | 29.40 | 24.47 |
July | 0.397937E+11 | 67368.87 | 21-JUL-17:42 | 30.50 | 23.96 | 0.185466E+10 | 2247.09 | 29-JUL-15:20 | 35.20 | 24.24 |
August | 0.378790E+11 | 64917.93 | 19-AUG-17:42 | 29.68 | 24.17 | 0.200300E+10 | 2246.80 | 12-AUG-08:30 | 29.68 | 24.17 |
September | 0.356163E+11 | 69786.76 | 04-SEP-11:53 | 28.90 | 23.70 | 0.185479E+10 | 2246.81 | 26-SEP-07:10 | 23.48 | 21.87 |
October | 0.293100E+11 | 69777.84 | 15-OCT-15:32 | 29.07 | 20.86 | 0.185467E+10 | 2246.81 | 12-OCT-07:10 | 29.07 | 20.86 |
November | 0.186347E+11 | 60396.97 | 19-NOV-12:53 | 26.70 | 21.27 | 0.177298E+10 | 2246.81 | 30-NOV-08:09 | 25.68 | 24.45 |
December | 0.118276E+11 | 59492.59 | 03-DEC-14:13 | 24.40 | 18.45 | 0.182587E+10 | 2246.96 | 12-DEC-15:09 | 18.30 | 12.87 |
Annual Sum or Average | 0.302873E+12 | 0.223518E+11 | ||||||||
Minimum of Months | 0.954638E+10 | 30840.90 | 24.40 | 18.45 | 0.167947E+10 | 2246.80 | 17.03 | 12.87 | ||
Maximum of Months | 0.397937E+11 | 76828.33 | 30.50 | 24.47 | 0.200300E+10 | 2259.51 | 35.20 | 24.47 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.407300E+10 | 6073.26 | 02-JAN-15:09 | 28.35 | 22.91 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.379988E+10 | 6194.52 | 22-FEB-15:30 | 27.80 | 14.62 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.469273E+10 | 6314.26 | 30-MAR-13:30 | 26.70 | 20.31 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.504061E+10 | 7488.98 | 17-APR-15:20 | 32.03 | 19.94 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.550840E+10 | 8297.71 | 22-MAY-13:30 | 34.15 | 23.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.560836E+10 | 7441.61 | 10-JUN-15:39 | 31.70 | 24.31 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 | 0.569714E+10 | 8863.22 | 29-JUL-15:00 | 35.60 | 24.39 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.600116E+10 | 8211.35 | 23-AUG-13:09 | 33.62 | 25.44 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 | 24.00 | 0.545933E+10 | 7614.13 | 13-SEP-14:09 | 32.12 | 24.21 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.525459E+10 | 7503.79 | 14-OCT-13:30 | 31.95 | 24.19 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.464966E+10 | 6500.38 | 03-NOV-13:50 | 29.40 | 24.41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.425399E+10 | 6363.08 | 08-DEC-13:30 | 27.50 | 22.61 |
Annual Sum or Average | 0.00 | 0.600388E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.379988E+10 | 6073.26 | 26.70 | 14.62 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.600116E+10 | 8863.22 | 35.60 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39512839.78 | 3183.35 | 25-JAN-07:20 | 9.60 |
February | 34984320.55 | 15557.00 | 04-FEB-06:03 | 5.50 |
March | 38784599.61 | 5595.54 | 16-MAR-06:10 | 6.70 |
April | 1566827.94 | 884.28 | 19-APR-06:10 | 15.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 7059112.31 | 1679.75 | 13-NOV-07:30 | 12.50 |
December | 42233480.85 | 4037.62 | 27-DEC-07:10 | 8.98 |
Annual Sum or Average | 0.164141E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 42233480.85 | 15557.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197243E+09 | 4636.89 | 13-JAN-07:13 | 22.07 |
February | 0.277325E+09 | 4990.70 | 02-FEB-07:13 | 22.97 |
March | 0.140400E+09 | 4324.77 | 23-MAR-06:30 | 21.70 |
April | 23820038.86 | 3886.77 | 22-APR-06:05 | 23.12 |
May | 1616616.12 | 2993.44 | 01-MAY-06:05 | 20.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 972271.73 | 3240.91 | 28-OCT-06:05 | 21.70 |
November | 59504481.40 | 4145.14 | 28-NOV-07:13 | 20.77 |
December | 0.269697E+09 | 5086.85 | 23-DEC-07:13 | 22.97 |
Annual Sum or Average | 0.970578E+09 | |||
Minimum of Months | 0.00 | 0.00 | 20.77 | |
Maximum of Months | 0.277325E+09 | 5086.85 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65464971.80 | 0.134301E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146006E+09 | 0.125967E+10 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168191E+09 | 0.137708E+10 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353186E+09 | 0.678477E+09 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811277E+09 | 0.389421E+09 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852294E+09 | 0.140019E+09 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928281E+09 | 0.137942E+09 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102049E+10 | 0.113294E+09 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805347E+09 | 0.136564E+09 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636704E+09 | 0.281858E+09 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352505E+09 | 0.778624E+09 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78739731.92 | 0.134854E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621849E+10 | 0.798451E+10 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65464971.80 | 0.113294E+09 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102049E+10 | 0.137708E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12533608.19 | 0.566615E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28545528.02 | 0.678343E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67535493.83 | 0.711320E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312141E+09 | 0.371523E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122412E+10 | 0.170922E+10 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165269E+10 | 0.491105E+09 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175587E+10 | 0.359129E+09 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195307E+10 | 0.345706E+09 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176403E+10 | 0.524891E+09 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845897E+09 | 0.115466E+10 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141802E+09 | 0.383490E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32628373.02 | 0.593754E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979085E+10 | 0.376352E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12533608.19 | 0.345706E+09 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195307E+10 | 0.711320E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41571950.06 | 0.210836E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92906471.00 | 0.225551E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 899090.09 | 0.292574E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1951592.14 | 0.222380E+11 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46027935.87 | 0.154716E+11 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 361967.29 | 0.775333E+10 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33981550.50 | 0.537294E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6642187.26 | 0.630942E+10 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1157200.82 | 0.671717E+10 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4906100.68 | 0.112633E+11 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184623.09 | 0.196648E+11 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27684987.37 | 0.231683E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258276E+09 | 0.190855E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184623.09 | 0.537294E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92906471.00 | 0.292574E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.16 | 02-JAN-12:10 | 5752.39 | 25-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.38 | 02-FEB-13:00 | 6086.31 | 03-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2893.24 | 13-MAR-17:00 | 7580.07 | 16-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.55 | 17-APR-17:00 | 3643.44 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.48 | 22-MAY-16:10 | 1179.73 | 01-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3456.37 | 08-JUN-16:10 | 713.64 | 18-JUN-20:00 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.54 | 27-JUL-16:10 | 652.97 | 02-JUL-15:13 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3997.97 | 16-AUG-16:10 | 868.23 | 14-AUG-03:00 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4027.71 | 18-SEP-16:10 | 636.81 | 05-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3768.55 | 03-OCT-16:10 | 979.39 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2144.00 | 03-NOV-16:10 | 5491.09 | 27-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1276.00 | 08-DEC-13:00 | 6826.45 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.16 | 636.81 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.54 | 7580.07 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.27 | 07-JAN-13:00 | 13835.56 | 24-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.92 | 02-FEB-14:00 | 15982.84 | 03-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3133.28 | 13-MAR-17:00 | 15878.82 | 15-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5108.76 | 15-APR-17:00 | 7733.38 | 18-APR-08:00 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8262.90 | 22-MAY-15:20 | 5573.09 | 10-MAY-15:10 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4314.90 | 08-JUN-16:00 | 3332.44 | 18-JUN-20:00 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7152.82 | 27-JUL-16:00 | 2671.56 | 02-JUL-15:40 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5527.05 | 16-AUG-16:00 | 4097.19 | 14-AUG-03:00 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5522.41 | 18-SEP-16:00 | 2402.35 | 19-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5443.00 | 03-OCT-15:10 | 4084.45 | 16-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.03 | 03-NOV-16:00 | 12958.61 | 11-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.13 | 10-DEC-14:57 | 13438.36 | 27-DEC-08:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.27 | 2402.35 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8262.90 | 15982.84 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3276.51 | 29-JAN-12:05 | 42647.19 | 24-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5804.25 | 08-FEB-13:10 | 47854.43 | 03-FEB-09:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 835.35 | 05-MAR-11:53 | 53256.31 | 15-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 806.64 | 16-APR-12:53 | 33382.41 | 18-APR-09:00 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2620.11 | 29-MAY-12:32 | 36208.76 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.86 | 11-JUN-12:55 | 23912.76 | 22-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.88 | 23-JUL-10:52 | 17670.80 | 14-JUL-15:00 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 849.35 | 07-AUG-14:55 | 21795.17 | 12-AUG-08:00 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 704.44 | 07-SEP-17:55 | 17477.81 | 02-SEP-12:10 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.69 | 03-OCT-10:55 | 19699.92 | 10-OCT-12:52 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.24 | 17-NOV-15:00 | 47664.17 | 11-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1901.90 | 24-DEC-11:25 | 42180.26 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 236.24 | 17477.81 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5804.25 | 53256.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21676.68 | 19-JAN-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.85 |
February | 23903.66 | 28-FEB-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.96 |
March | 20511.64 | 03-MAR-06:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.05 |
April | 24068.25 | 19-APR-05:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.36 |
May | 21331.24 | 08-MAY-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.42 |
June | 18349.46 | 17-JUN-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.86 |
July | 18564.37 | 06-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.86 |
August | 19204.07 | 30-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.16 |
September | 18832.81 | 05-SEP-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.30 |
October | 22126.35 | 18-OCT-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.58 |
November | 19851.84 | 28-NOV-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.92 |
December | 22589.39 | 02-DEC-06:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18349.46 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24068.25 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30840.90 | 01-JAN-12:45 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 | 0.00 |
February | 59225.44 | 19-FEB-13:33 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 0.00 |
March | 55777.11 | 28-MAR-17:06 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.95 |
April | 76828.33 | 09-APR-15:53 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.79 |
May | 69552.03 | 20-MAY-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.30 | 0.00 |
June | 66750.75 | 25-JUN-16:53 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.21 | 0.00 |
July | 67368.87 | 21-JUL-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.17 | 0.00 |
August | 64917.93 | 19-AUG-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.56 | 0.00 |
September | 69786.76 | 04-SEP-11:53 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69777.84 | 15-OCT-15:32 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.14 | 0.00 |
November | 60396.97 | 19-NOV-12:53 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.83 |
December | 59492.59 | 03-DEC-14:13 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 30840.90 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76828.33 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.56 | 786.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11858.85 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8838.07 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8851.72 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7006.73 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3238.72 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1739.41 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.70 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3043.02 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.11 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9412.05 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4652.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11858.85 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.847698E+11 | 76044.73 | 02-JAN-14:39 | 18799859.90 | 4673.28 | 25-JAN-07:19 |
February | 0.785338E+11 | 77696.06 | 11-FEB-14:09 | 24407367.32 | 5677.08 | 04-FEB-06:10 |
March | 0.913486E+11 | 77598.34 | 27-MAR-14:00 | 39787472.81 | 9262.32 | 16-MAR-06:10 |
April | 0.910304E+11 | 82857.31 | 14-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.100966E+12 | 84689.18 | 31-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.104339E+12 | 84603.41 | 08-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.105976E+12 | 87152.59 | 28-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.109886E+12 | 86658.60 | 22-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.103210E+12 | 86315.12 | 20-SEP-13:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.991540E+11 | 84744.09 | 03-OCT-14:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.886172E+11 | 81294.86 | 03-NOV-13:50 | 3339085.83 | 1957.20 | 13-NOV-07:30 |
December | 0.863437E+11 | 78824.82 | 08-DEC-13:00 | 34505040.87 | 6015.12 | 15-DEC-07:10 |
Annual Sum or Average | 0.114417E+13 | 0.120839E+09 | ||||
Minimum of Months | 0.785338E+11 | 76044.73 | 0.00 | 0.00 | ||
Maximum of Months | 0.109886E+12 | 87152.59 | 39787472.81 | 9262.32 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.128086E+11 | 0.115358E+11 | 0.00 | 0.847873E+10 | 0.00 | 0.00 | 0.701752E+10 | 0.00 | 0.00 | 0.00 | 0.197855E+10 | 0.00 |
February | 0.393028E+11 | 0.110526E+11 | 0.105871E+11 | 0.00 | 0.782958E+10 | 0.00 | 0.00 | 0.797073E+10 | 0.00 | 0.00 | 0.00 | 0.179098E+10 | 0.00 |
March | 0.453764E+11 | 0.115390E+11 | 0.123431E+11 | 0.00 | 0.927132E+10 | 0.00 | 0.00 | 0.108218E+11 | 0.00 | 0.00 | 0.00 | 0.199696E+10 | 0.00 |
April | 0.425433E+11 | 0.104844E+11 | 0.114862E+11 | 0.00 | 0.943071E+10 | 0.00 | 0.00 | 0.152066E+11 | 0.00 | 0.00 | 0.00 | 0.187931E+10 | 0.00 |
May | 0.441635E+11 | 0.102182E+11 | 0.119357E+11 | 0.00 | 0.112762E+11 | 0.00 | 0.00 | 0.214562E+11 | 0.00 | 0.00 | 0.00 | 0.191574E+10 | 0.00 |
June | 0.437562E+11 | 0.960899E+10 | 0.118862E+11 | 0.00 | 0.127352E+11 | 0.00 | 0.00 | 0.245053E+11 | 0.00 | 0.00 | 0.00 | 0.184728E+10 | 0.00 |
July | 0.429506E+11 | 0.100185E+11 | 0.115358E+11 | 0.00 | 0.131972E+11 | 0.00 | 0.00 | 0.264097E+11 | 0.00 | 0.00 | 0.00 | 0.186376E+10 | 0.00 |
August | 0.453764E+11 | 0.105612E+11 | 0.123357E+11 | 0.00 | 0.134532E+11 | 0.00 | 0.00 | 0.262516E+11 | 0.00 | 0.00 | 0.00 | 0.190813E+10 | 0.00 |
September | 0.425433E+11 | 0.108786E+11 | 0.114788E+11 | 0.00 | 0.124538E+11 | 0.00 | 0.00 | 0.240104E+11 | 0.00 | 0.00 | 0.00 | 0.184489E+10 | 0.00 |
October | 0.429506E+11 | 0.119485E+11 | 0.115432E+11 | 0.00 | 0.108545E+11 | 0.00 | 0.00 | 0.199395E+11 | 0.00 | 0.00 | 0.00 | 0.191772E+10 | 0.00 |
November | 0.413304E+11 | 0.121942E+11 | 0.110862E+11 | 0.00 | 0.865610E+10 | 0.00 | 0.00 | 0.134707E+11 | 0.00 | 0.00 | 0.00 | 0.187959E+10 | 0.00 |
December | 0.429506E+11 | 0.129417E+11 | 0.115358E+11 | 0.00 | 0.860657E+10 | 0.00 | 0.00 | 0.833965E+10 | 0.00 | 0.00 | 0.00 | 0.196943E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134254E+12 | 0.139290E+12 | 0.00 | 0.126243E+12 | 0.00 | 0.00 | 0.205400E+12 | 0.00 | 0.00 | 0.00 | 0.227923E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.960899E+10 | 0.105871E+11 | 0.00 | 0.782958E+10 | 0.00 | 0.00 | 0.701752E+10 | 0.00 | 0.00 | 0.00 | 0.179098E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.129417E+11 | 0.123431E+11 | 0.00 | 0.134532E+11 | 0.00 | 0.00 | 0.264097E+11 | 0.00 | 0.00 | 0.00 | 0.199696E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 18799859.90 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 24407367.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 39787472.81 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 3339085.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 34505040.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120839E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 39787472.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 8512.32 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 8512.32 | 01-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 10817.62 | 13-MAR-15:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10817.62 | 12-APR-10:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10817.62 | 01-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10817.62 | 01-JUN-10:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10817.62 | 01-JUL-07:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10817.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10817.62 | 01-SEP-10:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10817.62 | 02-OCT-15:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10817.62 | 02-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10817.62 | 08-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 8512.32 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 10817.62 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 17552.18 | 02-JAN-14:39 | 0.00 | 0.00 | 0.00 | 1741.19 | 19-JAN-12:39 | 0.00 |
February | 19230.94 | 11-FEB-14:30 | 0.00 | 0.00 | 0.00 | 1740.53 | 01-FEB-12:50 | 0.00 |
March | 19114.91 | 13-MAR-15:50 | 0.00 | 0.00 | 0.00 | 1735.32 | 01-MAR-12:09 | 0.00 |
April | 23238.86 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 | 1725.04 | 01-APR-11:00 | 0.00 |
May | 25940.44 | 22-MAY-15:50 | 0.00 | 0.00 | 0.00 | 1713.51 | 01-MAY-11:20 | 0.00 |
June | 26076.90 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1702.94 | 01-JUN-11:39 | 0.00 |
July | 28579.36 | 27-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1696.86 | 01-JUL-11:20 | 0.00 |
August | 26905.24 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1701.30 | 31-AUG-11:09 | 0.00 |
September | 26209.95 | 18-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1710.84 | 30-SEP-11:20 | 0.00 |
October | 24283.73 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1722.79 | 31-OCT-11:30 | 0.00 |
November | 20544.18 | 03-NOV-13:30 | 0.00 | 0.00 | 0.00 | 1733.24 | 30-NOV-12:39 | 0.00 |
December | 18004.31 | 08-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1739.99 | 30-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17552.18 | 0.00 | 0.00 | 0.00 | 1696.86 | 0.00 | ||
Maximum of Months | 28579.36 | 0.00 | 0.00 | 0.00 | 1741.19 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 76044.73 | 02-JAN-14:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8512.32 | 0.00 | 0.00 | 17552.18 | 0.00 |
February | 77696.06 | 11-FEB-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8512.32 | 0.00 | 0.00 | 19204.63 | 0.00 |
March | 77598.34 | 27-MAR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9664.97 | 0.00 | 0.00 | 18770.73 | 0.00 |
April | 82857.31 | 14-APR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 22049.59 | 0.00 |
May | 84689.18 | 31-MAY-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 23896.09 | 0.00 |
June | 84603.41 | 08-JUN-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 23811.78 | 0.00 |
July | 87152.59 | 28-JUL-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 26365.27 | 0.00 |
August | 86658.60 | 22-AUG-12:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 25868.82 | 0.00 |
September | 86315.12 | 20-SEP-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 25540.81 | 0.00 |
October | 84744.09 | 03-OCT-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 23943.36 | 0.00 |
November | 81294.86 | 03-NOV-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 20508.80 | 0.00 |
December | 78824.82 | 08-DEC-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 18004.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 76044.73 | 38182.97 | 10112.62 | 0.00 | 0.00 | 8512.32 | 0.00 | 0.00 | 17552.18 | 0.00 | |
Maximum of Months | 87152.59 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10817.62 | 0.00 | 0.00 | 26365.27 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 4673.28 | 25-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 5677.08 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 9262.32 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1957.20 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 6015.12 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 9262.32 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.67 | 24.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.57 | 2.17 | 24.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.65 | 5.00 | 24.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.03 | 8.33 | 24.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.48 | 8.50 | 25.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.35 | 8.50 | 25.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.36 | 8.83 | 25.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.35 | 8.67 | 25.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.02 | 8.33 | 24.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.84 | 5.17 | 24.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.70 | 2.00 | 24.70 |
Annual Sum or Average | 0.00 | 0.00 | 69.33 | 25.14 | 66.83 | 25.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.48 | 8.83 | 25.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.30 | 0.00 | 27.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.45 | 0.00 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.40 | 0.00 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.57 | 0.00 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.52 | 0.00 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 27.52 | 0.00 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 27.66 | 0.00 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 27.56 | 0.00 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 27.55 | 0.00 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.52 | 0.00 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.41 | 0.00 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.44 | 0.00 | 27.44 |
Annual Sum or Average | 0.00 | 0.00 | 251.17 | 27.54 | 0.00 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.30 | 0.00 | 27.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 27.66 | 0.00 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.50 | 23.37 | 199.33 | 23.78 | 12.50 | 23.79 |
February | 50.00 | 23.49 | 213.83 | 23.81 | 21.00 | 23.81 |
March | 58.50 | 23.41 | 249.83 | 23.82 | 21.67 | 23.83 |
April | 14.33 | 24.09 | 295.83 | 23.92 | 14.33 | 23.93 |
May | 45.83 | 24.08 | 312.00 | 23.95 | 45.83 | 23.96 |
June | 71.50 | 24.07 | 312.00 | 23.96 | 71.50 | 23.98 |
July | 64.67 | 24.09 | 300.00 | 23.97 | 64.67 | 23.99 |
August | 78.17 | 24.08 | 324.00 | 23.97 | 78.17 | 23.99 |
September | 65.83 | 24.08 | 300.00 | 23.97 | 65.83 | 23.98 |
October | 55.67 | 24.05 | 300.00 | 23.95 | 55.67 | 23.96 |
November | 43.50 | 23.81 | 273.33 | 23.90 | 35.83 | 23.91 |
December | 44.50 | 23.36 | 224.67 | 23.82 | 17.00 | 23.83 |
Annual Sum or Average | 650.00 | 23.84 | 3304.83 | 23.91 | 504.00 | 23.93 |
Minimum of Months | 14.33 | 23.36 | 199.33 | 23.78 | 12.50 | 23.79 |
Maximum of Months | 78.17 | 24.09 | 324.00 | 23.97 | 78.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 164.83 | 26.01 | 263.83 | 26.36 | 136.83 | 26.43 |
February | 207.50 | 26.21 | 253.33 | 26.36 | 190.50 | 26.40 |
March | 249.00 | 26.31 | 297.17 | 26.47 | 227.17 | 26.52 |
April | 275.17 | 26.70 | 300.00 | 26.68 | 275.17 | 26.69 |
May | 311.00 | 26.71 | 312.00 | 26.71 | 311.00 | 26.71 |
June | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
July | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
August | 322.83 | 26.71 | 324.00 | 26.71 | 322.83 | 26.71 |
September | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
October | 295.83 | 26.71 | 300.00 | 26.71 | 295.83 | 26.71 |
November | 257.67 | 26.58 | 281.00 | 26.62 | 251.50 | 26.63 |
December | 178.83 | 26.19 | 273.17 | 26.42 | 160.00 | 26.47 |
Annual Sum or Average | 3174.67 | 26.57 | 3516.50 | 26.62 | 3082.83 | 26.64 |
Minimum of Months | 164.83 | 26.01 | 253.33 | 26.36 | 136.83 | 26.40 |
Maximum of Months | 322.83 | 26.72 | 324.00 | 26.72 | 322.83 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.67 | 25.80 | 228.83 | 26.22 | 121.17 | 26.41 |
February | 224.83 | 25.97 | 226.50 | 26.25 | 184.83 | 26.37 |
March | 246.67 | 27.04 | 274.33 | 27.18 | 212.33 | 27.35 |
April | 293.67 | 28.96 | 300.00 | 28.93 | 293.67 | 28.94 |
May | 312.00 | 29.65 | 312.00 | 29.65 | 312.00 | 29.65 |
June | 312.00 | 29.99 | 312.00 | 29.99 | 312.00 | 29.99 |
July | 300.00 | 30.75 | 300.00 | 30.75 | 300.00 | 30.75 |
August | 324.00 | 30.39 | 324.00 | 30.39 | 324.00 | 30.39 |
September | 300.00 | 30.16 | 300.00 | 30.16 | 300.00 | 30.16 |
October | 300.00 | 29.58 | 300.00 | 29.58 | 300.00 | 29.58 |
November | 255.00 | 28.57 | 281.83 | 28.47 | 252.00 | 28.52 |
December | 208.17 | 26.95 | 241.50 | 27.03 | 172.00 | 27.25 |
Annual Sum or Average | 3250.00 | 28.92 | 3401.00 | 28.93 | 3084.00 | 29.03 |
Minimum of Months | 173.67 | 25.80 | 226.50 | 26.22 | 121.17 | 26.37 |
Maximum of Months | 324.00 | 30.75 | 324.00 | 30.75 | 324.00 | 30.75 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.752252E+10 | 0.198329E+10 | 262.82 | 0.586735E+10 | 0.165517E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 33841.67 | 07-JAN-06:01 | 23668.50 | 19-JAN-06:02 | 16917.71 | 07-JAN-06:04 | 7536.62 | 07-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.813744E+10 | 0.214845E+10 | 245.84 | 0.631293E+10 | 0.182451E+10 | 0.00 | 1.00 | 02-FEB-06:02 | 0.00 | 01-FEB-00:10 | 33877.63 | 11-FEB-06:01 | 25934.13 | 28-FEB-06:02 | 16549.56 | 11-FEB-06:04 | 7541.73 | 11-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.103542E+11 | 0.271023E+10 | 293.61 | 0.782368E+10 | 0.253050E+10 | 0.00 | 1.00 | 03-MAR-06:02 | 0.00 | 01-MAR-00:10 | 34240.98 | 14-MAR-05:01 | 23090.83 | 03-MAR-06:02 | 17343.10 | 14-MAR-05:04 | 7585.22 | 14-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.125769E+11 | 0.333017E+10 | 296.29 | 0.953379E+10 | 0.304314E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 34333.35 | 13-APR-05:01 | 26244.21 | 19-APR-05:02 | 16361.57 | 13-APR-05:04 | 7625.07 | 13-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.164056E+11 | 0.439020E+10 | 313.04 | 0.116206E+11 | 0.478494E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 34710.25 | 30-MAY-05:02 | 23185.10 | 08-MAY-05:01 | 19221.81 | 27-MAY-05:04 | 7676.28 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.181162E+11 | 0.482659E+10 | 316.00 | 0.121107E+11 | 0.600556E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 34655.92 | 19-JUN-05:01 | 20168.17 | 17-JUN-05:01 | 18251.00 | 24-JUN-05:04 | 7802.52 | 08-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.184731E+11 | 0.501603E+10 | 317.91 | 0.125391E+11 | 0.593409E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 34804.10 | 24-JUL-05:01 | 20188.56 | 06-JUL-05:01 | 17529.79 | 31-JUL-05:04 | 7752.39 | 14-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.195701E+11 | 0.525687E+10 | 330.90 | 0.130476E+11 | 0.652253E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 34807.40 | 14-AUG-05:01 | 20990.10 | 30-AUG-05:01 | 18391.20 | 28-AUG-05:06 | 7802.52 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.175766E+11 | 0.470148E+10 | 313.09 | 0.118620E+11 | 0.571460E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 34655.92 | 20-SEP-05:02 | 20300.21 | 05-SEP-05:01 | 18847.70 | 23-SEP-05:06 | 7778.77 | 09-SEP-05:01 | 0.00 | 01-SEP-00:05 |
October | 0.157365E+11 | 0.419131E+10 | 305.07 | 0.109662E+11 | 0.477031E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 34807.40 | 31-OCT-05:01 | 24078.84 | 18-OCT-05:01 | 20428.27 | 04-OCT-05:08 | 7748.91 | 30-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.122192E+11 | 0.321515E+10 | 276.27 | 0.864956E+10 | 0.356968E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 34448.59 | 04-NOV-05:01 | 21976.07 | 28-NOV-06:02 | 19102.58 | 30-NOV-06:05 | 7693.75 | 30-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.842004E+10 | 0.221189E+10 | 269.05 | 0.645592E+10 | 0.196413E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 34269.39 | 11-DEC-06:01 | 24055.21 | 02-DEC-06:01 | 16976.32 | 23-DEC-06:02 | 7644.72 | 09-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.165109E+12 | 0.439817E+11 | 3539.89 | 0.116789E+12 | 0.483191E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.752252E+10 | 0.198329E+10 | 245.84 | 0.586735E+10 | 0.165517E+10 | 0.00 | 1.00 | 0.00 | 33841.67 | 20168.17 | 16361.57 | 7536.62 | 0.00 | |||||||
Maximum of Months | 0.195701E+11 | 0.525687E+10 | 330.90 | 0.130476E+11 | 0.652253E+10 | 0.00 | 1.00 | 0.00 | 34807.40 | 26244.21 | 20428.27 | 7802.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.175272E+11 | 0.503423E+10 | 243.39 | 0.133850E+11 | 0.414211E+10 | 0.00 | 0.51 | 01-JAN-12:45 | 0.00 | 01-JAN-00:10 | 48980.60 | 01-JAN-12:45 | 35415.76 | 01-JAN-12:45 | 17260.63 | 01-JAN-10:03 | 13862.35 | 01-JAN-12:45 | 0.00 | 01-JAN-00:10 |
February | 0.202587E+11 | 0.582228E+10 | 231.33 | 0.155222E+11 | 0.473642E+10 | 0.00 | 0.99 | 19-FEB-13:33 | 0.00 | 01-FEB-00:10 | 105722.58 | 19-FEB-13:33 | 68926.47 | 19-FEB-13:33 | 36796.11 | 19-FEB-13:33 | 27172.13 | 19-FEB-13:33 | 0.00 | 01-FEB-00:10 |
March | 0.285183E+11 | 0.811160E+10 | 293.78 | 0.212548E+11 | 0.726357E+10 | 0.00 | 0.99 | 05-MAR-11:53 | 0.00 | 01-MAR-00:10 | 107263.41 | 05-MAR-11:53 | 65672.40 | 05-MAR-11:53 | 41591.01 | 05-MAR-11:53 | 27869.70 | 05-MAR-11:53 | 0.00 | 01-MAR-00:10 |
April | 0.412889E+11 | 0.118764E+11 | 359.48 | 0.312118E+11 | 0.100771E+11 | 0.00 | 1.00 | 01-APR-17:06 | 0.00 | 01-APR-00:10 | 116114.46 | 12-APR-05:05 | 86271.74 | 09-APR-15:53 | 55569.24 | 12-APR-05:05 | 28132.63 | 12-APR-05:05 | 0.00 | 01-APR-00:10 |
May | 0.588371E+11 | 0.170660E+11 | 460.93 | 0.413537E+11 | 0.174834E+11 | 0.00 | 1.00 | 03-MAY-17:06 | 0.00 | 01-MAY-00:10 | 112709.57 | 23-MAY-05:01 | 79284.13 | 02-MAY-17:06 | 47741.78 | 23-MAY-05:01 | 29236.58 | 29-MAY-13:13 | 0.00 | 01-MAY-00:10 |
June | 0.678597E+11 | 0.196788E+11 | 527.61 | 0.458597E+11 | 0.220000E+11 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:15 | 110563.97 | 18-JUN-12:23 | 78100.30 | 11-JUN-13:23 | 48556.19 | 22-JUN-05:01 | 28533.71 | 25-JUN-14:13 | 0.00 | 01-JUN-00:10 |
July | 0.725514E+11 | 0.213937E+11 | 556.84 | 0.502099E+11 | 0.223415E+11 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:15 | 111313.26 | 12-JUL-05:06 | 78222.69 | 16-JUL-13:23 | 46752.43 | 26-JUL-05:07 | 29002.15 | 30-JUL-14:23 | 0.00 | 01-JUL-00:10 |
August | 0.718704E+11 | 0.209947E+11 | 556.20 | 0.483011E+11 | 0.235693E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:15 | 112554.56 | 15-AUG-05:05 | 78103.15 | 06-AUG-13:02 | 51203.26 | 15-AUG-05:05 | 29174.66 | 20-AUG-11:43 | 0.00 | 01-AUG-00:10 |
September | 0.663303E+11 | 0.193089E+11 | 514.03 | 0.450831E+11 | 0.212473E+11 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:15 | 110717.49 | 25-SEP-05:08 | 79697.64 | 04-SEP-12:32 | 45661.85 | 25-SEP-05:08 | 28729.77 | 18-SEP-17:05 | 0.00 | 01-SEP-00:05 |
October | 0.543684E+11 | 0.157482E+11 | 457.70 | 0.377107E+11 | 0.166577E+11 | 0.00 | 1.00 | 01-OCT-12:03 | 0.00 | 01-OCT-00:15 | 116002.45 | 03-OCT-05:06 | 79356.63 | 15-OCT-15:32 | 62906.91 | 03-OCT-05:06 | 28847.58 | 01-OCT-13:23 | 0.00 | 01-OCT-00:10 |
November | 0.358845E+11 | 0.102555E+11 | 323.78 | 0.248753E+11 | 0.110092E+11 | 0.00 | 1.00 | 23-NOV-12:03 | 0.00 | 01-NOV-00:10 | 111436.62 | 23-NOV-12:03 | 69796.96 | 19-NOV-12:53 | 47310.41 | 23-NOV-11:23 | 28233.72 | 23-NOV-12:03 | 0.00 | 01-NOV-00:10 |
December | 0.214666E+11 | 0.612776E+10 | 262.73 | 0.159569E+11 | 0.550970E+10 | 0.00 | 0.97 | 10-DEC-11:33 | 0.00 | 01-DEC-00:10 | 105965.01 | 10-DEC-11:33 | 66743.36 | 03-DEC-14:13 | 42370.74 | 10-DEC-11:33 | 27293.47 | 10-DEC-11:33 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.556761E+12 | 0.161418E+12 | 4787.80 | 0.390724E+12 | 0.166037E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.175272E+11 | 0.503423E+10 | 231.33 | 0.133850E+11 | 0.414211E+10 | 0.00 | 0.51 | 0.00 | 48980.60 | 35415.76 | 17260.63 | 13862.35 | 0.00 | |||||||
Maximum of Months | 0.725514E+11 | 0.213937E+11 | 556.84 | 0.502099E+11 | 0.235693E+11 | 0.00 | 1.00 | 0.00 | 116114.46 | 86271.74 | 62906.91 | 29236.58 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.62 | 19.41 | 25.21 | 90.27 | 123.77 | 0.83 | 0.00 | 0.00 |
February | 55.47 | 25.16 | 30.32 | 132.96 | 99.26 | 0.00 | 0.00 | 0.00 |
March | 68.80 | 31.30 | 37.50 | 164.98 | 86.77 | 0.00 | 0.00 | 0.00 |
April | 75.20 | 34.47 | 40.74 | 202.80 | 65.25 | 0.00 | 0.00 | 0.00 |
May | 69.11 | 26.55 | 42.56 | 208.79 | 41.88 | 0.00 | 0.00 | 0.00 |
June | 58.69 | 16.48 | 42.21 | 188.61 | 26.20 | 0.00 | 0.00 | 0.00 |
July | 65.57 | 20.33 | 45.24 | 220.24 | 33.34 | 0.00 | 0.00 | 0.00 |
August | 65.27 | 21.18 | 44.09 | 202.53 | 32.49 | 1.83 | 0.00 | 0.00 |
September | 55.71 | 16.42 | 39.28 | 181.19 | 34.71 | 0.00 | 0.00 | 0.00 |
October | 55.38 | 21.57 | 33.81 | 162.22 | 51.60 | 2.50 | 0.00 | 0.00 |
November | 45.82 | 16.86 | 28.96 | 119.32 | 73.13 | 0.00 | 0.00 | 0.00 |
December | 46.08 | 20.74 | 25.34 | 101.37 | 106.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 22.53 | 36.30 | 164.78 | 64.49 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 44.62 | 16.42 | 25.21 | 90.27 | 26.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.20 | 34.47 | 45.24 | 220.24 | 123.77 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.62 | 19.41 | 25.21 | 90.27 | 123.77 | 0.83 | 0.00 | 0.00 |
February | 55.47 | 25.16 | 30.32 | 132.96 | 99.26 | 0.00 | 0.00 | 0.00 |
March | 68.80 | 31.30 | 37.50 | 164.98 | 86.77 | 0.00 | 0.00 | 0.00 |
April | 75.20 | 34.47 | 40.74 | 202.80 | 65.25 | 0.00 | 0.00 | 0.00 |
May | 69.11 | 26.55 | 42.56 | 208.79 | 41.88 | 0.00 | 0.00 | 0.00 |
June | 58.69 | 16.48 | 42.21 | 188.61 | 26.20 | 0.00 | 0.00 | 0.00 |
July | 65.57 | 20.33 | 45.24 | 220.24 | 33.34 | 0.00 | 0.00 | 0.00 |
August | 65.27 | 21.18 | 44.09 | 202.53 | 32.49 | 1.83 | 0.00 | 0.00 |
September | 55.71 | 16.42 | 39.28 | 181.19 | 34.71 | 0.00 | 0.00 | 0.00 |
October | 55.38 | 21.57 | 33.81 | 162.22 | 51.60 | 2.50 | 0.00 | 0.00 |
November | 45.82 | 16.86 | 28.96 | 119.32 | 73.13 | 0.00 | 0.00 | 0.00 |
December | 46.08 | 20.74 | 25.34 | 101.37 | 106.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 22.53 | 36.30 | 164.78 | 64.49 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 44.62 | 16.42 | 25.21 | 90.27 | 26.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.20 | 34.47 | 45.24 | 220.24 | 123.77 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.94 | 0.00 | 11.94 | 13.65 | 75.64 | 0.83 | 0.00 | 0.00 |
February | 14.13 | 0.00 | 14.13 | 23.38 | 60.35 | 0.00 | 0.00 | 0.00 |
March | 16.86 | 0.00 | 16.85 | 28.20 | 53.30 | 0.00 | 0.00 | 0.00 |
April | 18.99 | 0.17 | 18.82 | 42.44 | 39.22 | 0.00 | 0.00 | 0.00 |
May | 21.84 | 1.22 | 20.62 | 64.81 | 23.84 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 2.13 | 21.39 | 76.13 | 14.49 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 1.48 | 22.17 | 82.80 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 20.81 | 0.35 | 20.46 | 65.72 | 18.79 | 1.83 | 0.00 | 0.00 |
September | 18.31 | 0.01 | 18.30 | 60.73 | 20.10 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 43.14 | 30.63 | 2.50 | 0.00 | 0.00 |
November | 13.33 | 0.00 | 13.33 | 28.17 | 43.47 | 0.00 | 0.00 | 0.00 |
December | 11.81 | 0.00 | 11.81 | 15.94 | 65.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.56 | 0.45 | 17.11 | 45.54 | 38.65 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 11.81 | 0.00 | 11.81 | 13.65 | 14.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.65 | 2.13 | 22.17 | 82.80 | 75.64 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.94 | 0.00 | 11.94 | 13.65 | 75.64 | 0.83 | 0.00 | 0.00 |
February | 14.13 | 0.00 | 14.13 | 23.38 | 60.34 | 0.00 | 0.00 | 0.00 |
March | 16.86 | 0.00 | 16.85 | 28.20 | 53.30 | 0.00 | 0.00 | 0.00 |
April | 18.99 | 0.17 | 18.82 | 42.44 | 39.22 | 0.00 | 0.00 | 0.00 |
May | 21.84 | 1.22 | 20.62 | 64.81 | 23.84 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 2.13 | 21.38 | 76.13 | 14.49 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 1.48 | 22.17 | 82.80 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 20.81 | 0.35 | 20.46 | 65.72 | 18.79 | 1.83 | 0.00 | 0.00 |
September | 18.31 | 0.01 | 18.30 | 60.73 | 20.10 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 43.14 | 30.62 | 2.50 | 0.00 | 0.00 |
November | 13.33 | 0.00 | 13.33 | 28.17 | 43.47 | 0.00 | 0.00 | 0.00 |
December | 11.81 | 0.00 | 11.81 | 15.94 | 65.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.56 | 0.45 | 17.11 | 45.54 | 38.65 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 11.81 | 0.00 | 11.81 | 13.65 | 14.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.65 | 2.13 | 22.17 | 82.80 | 75.64 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.48 | 22.58 | 14.90 | 58.75 | 34.32 | 5.67 | 0.00 | 0.00 |
February | 45.93 | 27.96 | 17.97 | 76.61 | 28.70 | 0.00 | 0.00 | 0.00 |
March | 57.37 | 34.98 | 22.39 | 95.00 | 26.81 | 0.17 | 0.00 | 0.00 |
April | 66.87 | 41.59 | 25.28 | 112.96 | 26.22 | 0.00 | 0.00 | 0.00 |
May | 66.04 | 37.21 | 28.83 | 114.41 | 20.59 | 0.00 | 0.00 | 0.00 |
June | 62.77 | 31.42 | 31.35 | 109.57 | 17.55 | 0.00 | 0.00 | 0.00 |
July | 68.38 | 35.90 | 32.48 | 121.42 | 19.33 | 0.00 | 0.00 | 0.00 |
August | 62.17 | 30.84 | 31.33 | 105.65 | 19.00 | 0.00 | 0.00 | 0.00 |
September | 54.78 | 26.74 | 28.04 | 95.94 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 48.12 | 26.90 | 21.21 | 80.82 | 25.90 | 0.00 | 0.00 | 0.00 |
November | 38.34 | 19.93 | 18.41 | 62.52 | 28.10 | 2.67 | 0.00 | 0.00 |
December | 34.34 | 18.84 | 15.50 | 54.43 | 30.74 | 21.50 | 0.00 | 0.00 |
Annual Sum or Average | 53.59 | 29.58 | 24.00 | 90.74 | 24.77 | 30.00 | 0.00 | 0.00 |
Minimum of Months | 34.34 | 18.84 | 14.90 | 54.43 | 17.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.38 | 41.59 | 32.48 | 121.42 | 34.32 | 21.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119514E+09 | 51989820.64 | 67524471.88 | 0.241789E+09 | 0.331502E+09 |
February | 0.134200E+09 | 60857118.44 | 73342704.95 | 0.321650E+09 | 0.240138E+09 |
March | 0.184282E+09 | 83838571.27 | 0.100443E+09 | 0.441894E+09 | 0.232393E+09 |
April | 0.194930E+09 | 89339790.75 | 0.105590E+09 | 0.525649E+09 | 0.169115E+09 |
May | 0.185102E+09 | 71103770.22 | 0.113998E+09 | 0.559217E+09 | 0.112178E+09 |
June | 0.152126E+09 | 42716516.55 | 0.109409E+09 | 0.488884E+09 | 67910071.96 |
July | 0.175613E+09 | 54447372.73 | 0.121165E+09 | 0.589903E+09 | 89299279.38 |
August | 0.174829E+09 | 56727446.87 | 0.118102E+09 | 0.542452E+09 | 87027232.26 |
September | 0.144390E+09 | 42573599.93 | 0.101816E+09 | 0.469644E+09 | 89967382.31 |
October | 0.148334E+09 | 57777091.23 | 90557215.98 | 0.434489E+09 | 0.138215E+09 |
November | 0.118770E+09 | 43696238.03 | 75073278.39 | 0.309288E+09 | 0.189549E+09 |
December | 0.123420E+09 | 55560149.66 | 67860092.45 | 0.271516E+09 | 0.286522E+09 |
Annual Sum or Average | 0.185551E+10 | 0.710627E+09 | 0.114488E+10 | 0.519638E+10 | 0.203382E+10 |
Minimum of Months | 0.118770E+09 | 42573599.93 | 67524471.88 | 0.241789E+09 | 67910071.96 |
Maximum of Months | 0.194930E+09 | 89339790.75 | 0.121165E+09 | 0.589903E+09 | 0.331502E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119514E+09 | 51989820.64 | 67524471.88 | 0.241789E+09 | 0.331502E+09 |
February | 0.134200E+09 | 60857118.44 | 73342704.95 | 0.321650E+09 | 0.240138E+09 |
March | 0.184282E+09 | 83838571.27 | 0.100443E+09 | 0.441894E+09 | 0.232393E+09 |
April | 0.194930E+09 | 89339790.75 | 0.105590E+09 | 0.525649E+09 | 0.169115E+09 |
May | 0.185102E+09 | 71103770.22 | 0.113998E+09 | 0.559217E+09 | 0.112178E+09 |
June | 0.152126E+09 | 42716516.55 | 0.109409E+09 | 0.488884E+09 | 67910071.96 |
July | 0.175613E+09 | 54447372.73 | 0.121165E+09 | 0.589903E+09 | 89299279.38 |
August | 0.174829E+09 | 56727446.87 | 0.118102E+09 | 0.542452E+09 | 87027232.26 |
September | 0.144390E+09 | 42573599.93 | 0.101816E+09 | 0.469644E+09 | 89967382.31 |
October | 0.148334E+09 | 57777091.23 | 90557215.98 | 0.434489E+09 | 0.138215E+09 |
November | 0.118770E+09 | 43696238.03 | 75073278.39 | 0.309288E+09 | 0.189549E+09 |
December | 0.123420E+09 | 55560149.66 | 67860092.45 | 0.271516E+09 | 0.286522E+09 |
Annual Sum or Average | 0.185551E+10 | 0.710627E+09 | 0.114488E+10 | 0.519638E+10 | 0.203382E+10 |
Minimum of Months | 0.118770E+09 | 42573599.93 | 67524471.88 | 0.241789E+09 | 67910071.96 |
Maximum of Months | 0.194930E+09 | 89339790.75 | 0.121165E+09 | 0.589903E+09 | 0.331502E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31970577.54 | 0.00 | 31970577.54 | 36559426.23 | 0.202598E+09 |
February | 34180133.89 | 0.00 | 34180133.89 | 56559549.90 | 0.145988E+09 |
March | 45149631.54 | 6085.77 | 45143545.78 | 75526528.27 | 0.142766E+09 |
April | 49225591.75 | 448589.94 | 48777001.81 | 0.110015E+09 | 0.101662E+09 |
May | 58488871.22 | 3271850.94 | 55217020.28 | 0.173596E+09 | 63852220.85 |
June | 60941883.82 | 5510456.11 | 55431427.71 | 0.197330E+09 | 37551478.72 |
July | 63350739.75 | 3962798.65 | 59387941.09 | 0.221772E+09 | 51100735.78 |
August | 55728085.89 | 935564.41 | 54792521.48 | 0.176019E+09 | 50328057.17 |
September | 47458565.99 | 17908.27 | 47440657.72 | 0.157418E+09 | 52103967.72 |
October | 41059420.72 | 0.00 | 41059420.72 | 0.115549E+09 | 82027442.30 |
November | 34549726.50 | 0.00 | 34549726.50 | 73016982.82 | 0.112675E+09 |
December | 31622888.14 | 0.00 | 31622888.14 | 42695108.61 | 0.176339E+09 |
Annual Sum or Average | 0.553726E+09 | 14153254.09 | 0.539573E+09 | 0.143606E+10 | 0.121899E+10 |
Minimum of Months | 31622888.14 | 0.00 | 31622888.14 | 36559426.23 | 37551478.72 |
Maximum of Months | 63350739.75 | 5510456.11 | 59387941.09 | 0.221772E+09 | 0.202598E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31969646.60 | 0.00 | 31969646.60 | 36558118.58 | 0.202597E+09 |
February | 34179156.05 | 0.00 | 34179156.05 | 56557911.66 | 0.145987E+09 |
March | 45148353.52 | 6085.48 | 45142268.04 | 75524143.05 | 0.142765E+09 |
April | 49224220.79 | 448568.91 | 48775651.88 | 0.110012E+09 | 0.101661E+09 |
May | 58487079.46 | 3271697.58 | 55215381.88 | 0.173592E+09 | 63851065.44 |
June | 60939905.25 | 5510197.83 | 55429707.41 | 0.197325E+09 | 37550406.35 |
July | 63348754.24 | 3962612.91 | 59386141.33 | 0.221767E+09 | 51099541.62 |
August | 55726373.33 | 935520.56 | 54790852.77 | 0.176016E+09 | 50326988.42 |
September | 47457114.51 | 17907.43 | 47439207.08 | 0.157415E+09 | 52102798.79 |
October | 41058204.21 | 0.00 | 41058204.21 | 0.115546E+09 | 82025906.44 |
November | 34548666.66 | 0.00 | 34548666.66 | 73014937.08 | 0.112674E+09 |
December | 31621931.21 | 0.00 | 31621931.21 | 42693518.53 | 0.176338E+09 |
Annual Sum or Average | 0.553709E+09 | 14152590.71 | 0.539557E+09 | 0.143602E+10 | 0.121898E+10 |
Minimum of Months | 31621931.21 | 0.00 | 31621931.21 | 36558118.58 | 37550406.35 |
Maximum of Months | 63348754.24 | 5510197.83 | 59386141.33 | 0.221767E+09 | 0.202597E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100393E+09 | 60479166.63 | 39914008.87 | 0.157361E+09 | 91927698.91 |
February | 0.111115E+09 | 67644061.73 | 43471306.20 | 0.185337E+09 | 69420726.49 |
March | 0.153667E+09 | 93686804.12 | 59979758.16 | 0.254443E+09 | 71814319.56 |
April | 0.173330E+09 | 0.107801E+09 | 65528848.77 | 0.292787E+09 | 67952902.11 |
May | 0.176888E+09 | 99676305.02 | 77211689.34 | 0.306436E+09 | 55148499.36 |
June | 0.162698E+09 | 81442935.44 | 81255536.51 | 0.284007E+09 | 45478869.41 |
July | 0.183159E+09 | 96154437.24 | 87004726.38 | 0.325199E+09 | 51774775.02 |
August | 0.166516E+09 | 82607654.05 | 83908841.62 | 0.282976E+09 | 50901665.01 |
September | 0.141991E+09 | 69301476.52 | 72689138.37 | 0.248685E+09 | 52122169.61 |
October | 0.128876E+09 | 72061404.17 | 56814758.04 | 0.216467E+09 | 69368051.85 |
November | 99366717.37 | 51656675.27 | 47710042.10 | 0.162043E+09 | 72842668.04 |
December | 91965164.47 | 50459667.12 | 41505497.34 | 0.145776E+09 | 82335457.85 |
Annual Sum or Average | 0.168997E+10 | 0.932972E+09 | 0.756994E+09 | 0.286152E+10 | 0.781088E+09 |
Minimum of Months | 91965164.47 | 50459667.12 | 39914008.87 | 0.145776E+09 | 45478869.41 |
Maximum of Months | 0.183159E+09 | 0.107801E+09 | 87004726.38 | 0.325199E+09 | 91927698.91 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.28 | 393.26 | 113.12 | 38.82 | 74.29 | 0.00 | 0.00 |
February | 309.70 | 316.24 | 139.20 | 50.31 | 88.89 | 0.00 | 0.00 |
March | 381.93 | 275.71 | 171.32 | 62.61 | 108.71 | 0.00 | 0.00 |
April | 488.20 | 206.65 | 188.39 | 69.28 | 119.11 | 0.00 | 0.00 |
May | 546.25 | 130.50 | 181.89 | 55.54 | 126.35 | 0.00 | 0.00 |
June | 528.18 | 80.07 | 164.40 | 37.21 | 127.19 | 0.00 | 0.00 |
July | 605.41 | 104.16 | 178.44 | 43.62 | 134.82 | 0.00 | 0.00 |
August | 536.22 | 102.29 | 172.16 | 43.06 | 129.10 | 0.00 | 0.00 |
September | 483.70 | 109.48 | 148.03 | 32.86 | 115.17 | 0.00 | 0.00 |
October | 409.91 | 163.65 | 141.42 | 43.14 | 98.28 | 0.00 | 0.00 |
November | 293.80 | 232.01 | 118.30 | 33.72 | 84.59 | 0.00 | 0.00 |
December | 229.98 | 340.98 | 115.77 | 41.49 | 74.29 | 0.00 | 0.00 |
Annual Sum or Average | 418.52 | 204.19 | 152.79 | 45.97 | 106.83 | 0.00 | 0.00 |
Minimum of Months | 202.28 | 80.07 | 113.12 | 32.86 | 74.29 | 0.00 | 0.00 |
Maximum of Months | 605.41 | 393.26 | 188.39 | 69.28 | 134.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1919.17 | 1136.79 | 374.83 | 225.80 | 149.02 | 0.00 | 0.00 |
February | 2532.80 | 957.12 | 459.31 | 279.61 | 179.69 | 0.00 | 0.00 |
March | 3177.46 | 903.51 | 573.73 | 349.79 | 223.94 | 0.00 | 0.00 |
April | 4799.75 | 992.02 | 668.71 | 415.90 | 252.81 | 0.00 | 0.00 |
May | 4424.76 | 963.73 | 660.42 | 372.15 | 288.28 | 0.00 | 0.00 |
June | 4284.83 | 977.07 | 627.69 | 314.21 | 313.49 | 0.00 | 0.00 |
July | 5234.21 | 1160.29 | 683.84 | 359.00 | 324.84 | 0.00 | 0.00 |
August | 4131.58 | 1101.86 | 621.70 | 308.42 | 313.28 | 0.00 | 0.00 |
September | 4103.41 | 1081.48 | 547.80 | 267.37 | 280.44 | 0.00 | 0.00 |
October | 3214.02 | 1227.21 | 481.17 | 269.05 | 212.12 | 0.00 | 0.00 |
November | 2345.37 | 1058.99 | 383.36 | 199.29 | 184.07 | 0.00 | 0.00 |
December | 1969.80 | 1046.99 | 343.36 | 188.39 | 154.96 | 0.00 | 0.00 |
Annual Sum or Average | 3515.40 | 1051.61 | 535.88 | 295.84 | 240.04 | 0.00 | 0.00 |
Minimum of Months | 1919.17 | 903.51 | 343.36 | 188.39 | 149.02 | 0.00 | 0.00 |
Maximum of Months | 5234.21 | 1227.21 | 683.84 | 415.90 | 324.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.541791E+09 | 0.105329E+10 | 0.302969E+09 | 0.103980E+09 | 0.198989E+09 | 0.00 | 0.00 |
February | 0.749214E+09 | 0.765047E+09 | 0.336759E+09 | 0.121714E+09 | 0.215045E+09 | 0.00 | 0.00 |
March | 0.102297E+10 | 0.738448E+09 | 0.458862E+09 | 0.167689E+09 | 0.291173E+09 | 0.00 | 0.00 |
April | 0.126542E+10 | 0.535648E+09 | 0.488310E+09 | 0.179577E+09 | 0.308733E+09 | 0.00 | 0.00 |
May | 0.146308E+10 | 0.349519E+09 | 0.487179E+09 | 0.148751E+09 | 0.338428E+09 | 0.00 | 0.00 |
June | 0.136905E+10 | 0.207547E+09 | 0.426133E+09 | 96453687.04 | 0.329679E+09 | 0.00 | 0.00 |
July | 0.162153E+10 | 0.278985E+09 | 0.477925E+09 | 0.116820E+09 | 0.361105E+09 | 0.00 | 0.00 |
August | 0.143621E+10 | 0.273977E+09 | 0.461113E+09 | 0.115326E+09 | 0.345787E+09 | 0.00 | 0.00 |
September | 0.125376E+10 | 0.283784E+09 | 0.383696E+09 | 85183015.56 | 0.298513E+09 | 0.00 | 0.00 |
October | 0.109790E+10 | 0.438307E+09 | 0.378786E+09 | 0.115554E+09 | 0.263232E+09 | 0.00 | 0.00 |
November | 0.761536E+09 | 0.601374E+09 | 0.306637E+09 | 87392476.06 | 0.219245E+09 | 0.00 | 0.00 |
December | 0.615973E+09 | 0.913275E+09 | 0.310085E+09 | 0.111120E+09 | 0.198965E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131984E+11 | 0.643921E+10 | 0.481845E+10 | 0.144956E+10 | 0.336889E+10 | 0.00 | 0.00 |
Minimum of Months | 0.541791E+09 | 0.207547E+09 | 0.302969E+09 | 85183015.56 | 0.198965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162153E+10 | 0.105329E+10 | 0.488310E+09 | 0.179577E+09 | 0.361105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.514032E+10 | 0.304479E+10 | 0.100393E+10 | 0.604792E+09 | 0.399140E+09 | 0.00 | 0.00 |
February | 0.612735E+10 | 0.231546E+10 | 0.111115E+10 | 0.676441E+09 | 0.434713E+09 | 0.00 | 0.00 |
March | 0.851052E+10 | 0.241995E+10 | 0.153667E+10 | 0.936868E+09 | 0.599798E+09 | 0.00 | 0.00 |
April | 0.124410E+11 | 0.257133E+10 | 0.173330E+10 | 0.107801E+10 | 0.655288E+09 | 0.00 | 0.00 |
May | 0.118513E+11 | 0.258127E+10 | 0.176888E+10 | 0.996763E+09 | 0.772117E+09 | 0.00 | 0.00 |
June | 0.111063E+11 | 0.253258E+10 | 0.162698E+10 | 0.814429E+09 | 0.812555E+09 | 0.00 | 0.00 |
July | 0.140193E+11 | 0.310771E+10 | 0.183159E+10 | 0.961544E+09 | 0.870047E+09 | 0.00 | 0.00 |
August | 0.110660E+11 | 0.295123E+10 | 0.166516E+10 | 0.826077E+09 | 0.839088E+09 | 0.00 | 0.00 |
September | 0.106360E+11 | 0.280320E+10 | 0.141991E+10 | 0.693015E+09 | 0.726891E+09 | 0.00 | 0.00 |
October | 0.860843E+10 | 0.328696E+10 | 0.128876E+10 | 0.720614E+09 | 0.568148E+09 | 0.00 | 0.00 |
November | 0.607921E+10 | 0.274491E+10 | 0.993667E+09 | 0.516567E+09 | 0.477100E+09 | 0.00 | 0.00 |
December | 0.527592E+10 | 0.280426E+10 | 0.919652E+09 | 0.504597E+09 | 0.415055E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110862E+12 | 0.331636E+11 | 0.168997E+11 | 0.932972E+10 | 0.756994E+10 | 0.00 | 0.00 |
Minimum of Months | 0.514032E+10 | 0.231546E+10 | 0.919652E+09 | 0.504597E+09 | 0.399140E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140193E+11 | 0.328696E+10 | 0.183159E+10 | 0.107801E+10 | 0.870047E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.684855E+09 | -611934499.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72920204.9 | 58.99 | 0.00 | 0.00 |
February | 0.622843E+09 | -556834941.1 | 0.00 | 0.00 | 672.00 | 0.00 | -66007648.1 | 58.99 | 0.00 | 0.00 |
March | 0.702943E+09 | -630606056.6 | 0.00 | 0.00 | 744.00 | 0.00 | -72337040.1 | 58.99 | 0.00 | 0.00 |
April | 0.627158E+09 | -558834117.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68323842.8 | 58.99 | 0.00 | 0.00 |
May | 0.622012E+09 | -552236735.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69775449.8 | 58.98 | 0.00 | 0.00 |
June | 0.595147E+09 | -527949768.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67197020.8 | 58.99 | 0.00 | 0.00 |
July | 0.570106E+09 | -501271634.6 | 0.00 | 0.00 | 744.00 | 0.00 | -68834652.3 | 58.99 | 0.00 | 0.00 |
August | 0.614161E+09 | -544820169.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69341178.7 | 58.99 | 0.00 | 0.00 |
September | 0.592884E+09 | -525945642.5 | 0.00 | 0.00 | 720.00 | 0.00 | -66938795.8 | 58.99 | 0.00 | 0.00 |
October | 0.623898E+09 | -554347931.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69550163.9 | 58.99 | 0.00 | 0.00 |
November | 0.627906E+09 | -559017400.2 | 0.00 | 0.00 | 720.00 | 0.00 | -68888488.3 | 58.99 | 0.00 | 0.00 |
December | 0.675414E+09 | -603013273.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72401054.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.755933E+10 | -0.672681E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -832515540.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.570106E+09 | -630606056.6 | 0.00 | 0.00 | 672.00 | 0.00 | -72920204.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.702943E+09 | -501271634.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66007648.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12246680.29 | 3064.37 | 25-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16165314.98 | 16449.81 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26221533.26 | 6223.64 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2152139.36 | 1265.31 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22669440.78 | 3972.26 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79455108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26221533.26 | 16449.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.752252E+10 | 0.586735E+10 | 33841.67 | 07-JAN-06:01 | 16945.62 | 0.00 |
February | 0.00 | 0.00 | 0.813744E+10 | 0.631293E+10 | 33877.63 | 11-FEB-06:01 | 17388.58 | 0.00 |
March | 0.00 | 0.00 | 0.103542E+11 | 0.782368E+10 | 34240.98 | 14-MAR-05:01 | 16925.87 | 0.00 |
April | 0.00 | 0.00 | 0.125769E+11 | 0.953379E+10 | 34333.35 | 13-APR-05:01 | 18124.31 | 0.00 |
May | 0.00 | 0.00 | 0.164056E+11 | 0.116206E+11 | 34710.25 | 30-MAY-05:02 | 16801.04 | 0.00 |
June | 0.00 | 0.00 | 0.181162E+11 | 0.121107E+11 | 34655.92 | 19-JUN-05:01 | 17023.60 | 0.00 |
July | 0.00 | 0.00 | 0.184731E+11 | 0.125391E+11 | 34804.10 | 24-JUL-05:01 | 18345.95 | 0.00 |
August | 0.00 | 0.00 | 0.195701E+11 | 0.130476E+11 | 34807.40 | 14-AUG-05:01 | 17344.31 | 0.00 |
September | 0.00 | 0.00 | 0.175766E+11 | 0.118620E+11 | 34655.92 | 20-SEP-05:02 | 17108.34 | 0.00 |
October | 0.00 | 0.00 | 0.157365E+11 | 0.109662E+11 | 34807.40 | 31-OCT-05:01 | 16831.98 | 0.00 |
November | 0.00 | 0.00 | 0.122192E+11 | 0.864956E+10 | 34448.59 | 04-NOV-05:01 | 16232.86 | 0.00 |
December | 0.00 | 0.00 | 0.842004E+10 | 0.645592E+10 | 34269.39 | 11-DEC-06:01 | 18062.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165109E+12 | 0.116789E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.752252E+10 | 0.586735E+10 | 33841.67 | 16232.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195701E+11 | 0.130476E+11 | 34807.40 | 18345.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.175272E+11 | 0.133850E+11 | 48980.60 | 01-JAN-12:45 | 35415.76 | 0.00 |
February | 0.00 | 0.00 | 0.202587E+11 | 0.155222E+11 | 105722.58 | 19-FEB-13:33 | 68926.47 | 0.00 |
March | 0.00 | 0.00 | 0.285183E+11 | 0.212548E+11 | 107263.41 | 05-MAR-11:53 | 65672.40 | 0.00 |
April | 0.00 | 0.00 | 0.412889E+11 | 0.312118E+11 | 116114.46 | 12-APR-05:05 | 60545.22 | 0.00 |
May | 0.00 | 0.00 | 0.588371E+11 | 0.413537E+11 | 112709.57 | 23-MAY-05:01 | 64967.79 | 0.00 |
June | 0.00 | 0.00 | 0.678597E+11 | 0.458597E+11 | 110563.97 | 18-JUN-12:23 | 65253.51 | 0.00 |
July | 0.00 | 0.00 | 0.725514E+11 | 0.502099E+11 | 111313.26 | 12-JUL-05:06 | 65480.60 | 0.00 |
August | 0.00 | 0.00 | 0.718704E+11 | 0.483011E+11 | 112554.56 | 15-AUG-05:05 | 61351.29 | 0.00 |
September | 0.00 | 0.00 | 0.663303E+11 | 0.450831E+11 | 110717.49 | 25-SEP-05:08 | 65055.64 | 0.00 |
October | 0.00 | 0.00 | 0.543684E+11 | 0.377107E+11 | 116002.45 | 03-OCT-05:06 | 53095.54 | 0.00 |
November | 0.00 | 0.00 | 0.358845E+11 | 0.248753E+11 | 111436.62 | 23-NOV-12:03 | 64909.92 | 0.00 |
December | 0.00 | 0.00 | 0.214666E+11 | 0.159569E+11 | 105965.01 | 10-DEC-11:33 | 63594.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.556761E+12 | 0.390724E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.175272E+11 | 0.133850E+11 | 48980.60 | 35415.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.725514E+11 | 0.502099E+11 | 116114.46 | 68926.47 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146943E+10 | 0.35 | 1473.85 | 09-JAN-08:17 | 0.93 |
February | 0.135321E+10 | 0.36 | 1473.85 | 02-FEB-07:20 | 0.92 |
March | 0.159423E+10 | 0.39 | 1473.85 | 02-MAR-11:40 | 0.93 |
April | 0.149200E+10 | 0.39 | 1473.85 | 05-APR-07:20 | 0.92 |
May | 0.156829E+10 | 0.39 | 1473.85 | 02-MAY-06:40 | 0.92 |
June | 0.158144E+10 | 0.41 | 1473.85 | 08-JUN-11:30 | 0.92 |
July | 0.153288E+10 | 0.40 | 1473.85 | 03-JUL-16:30 | 0.92 |
August | 0.164943E+10 | 0.41 | 1473.85 | 12-AUG-11:10 | 0.92 |
September | 0.152847E+10 | 0.41 | 1473.85 | 19-SEP-11:20 | 0.92 |
October | 0.151219E+10 | 0.38 | 1473.85 | 17-OCT-06:40 | 0.93 |
November | 0.143010E+10 | 0.36 | 1473.85 | 02-NOV-06:20 | 0.92 |
December | 0.147521E+10 | 0.36 | 1473.85 | 01-DEC-08:40 | 0.93 |
Annual Sum or Average | 0.181869E+11 | 0.38 | |||
Minimum of Months | 0.135321E+10 | 0.35 | 1473.85 | 0.92 | |
Maximum of Months | 0.164943E+10 | 0.41 | 1473.85 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.700930E+10 | 0.60 | 7038.48 | 05-JAN-15:30 | 1.55 |
February | 0.647637E+10 | 0.62 | 7038.48 | 04-FEB-13:40 | 1.56 |
March | 0.766511E+10 | 0.69 | 7038.48 | 02-MAR-13:00 | 1.56 |
April | 0.740311E+10 | 0.81 | 7038.48 | 05-APR-15:30 | 1.55 |
May | 0.813506E+10 | 1.01 | 7038.48 | 01-MAY-08:30 | 1.55 |
June | 0.849875E+10 | 1.20 | 7038.48 | 01-JUN-10:30 | 1.55 |
July | 0.849969E+10 | 1.24 | 7038.48 | 03-JUL-07:50 | 1.54 |
August | 0.887519E+10 | 1.23 | 7038.48 | 12-AUG-14:10 | 1.54 |
September | 0.826406E+10 | 1.17 | 7038.48 | 02-SEP-12:17 | 1.54 |
October | 0.781427E+10 | 1.00 | 7038.48 | 05-OCT-17:00 | 1.55 |
November | 0.697751E+10 | 0.74 | 7038.48 | 08-NOV-11:05 | 1.55 |
December | 0.709909E+10 | 0.64 | 7038.48 | 01-DEC-14:07 | 1.55 |
Annual Sum or Average | 0.927175E+11 | 0.91 | |||
Minimum of Months | 0.647637E+10 | 0.60 | 7038.48 | 1.54 | |
Maximum of Months | 0.887519E+10 | 1.24 | 7038.48 | 1.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.345272E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.350166E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.430446E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.482217E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.595849E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.640803E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.654891E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.690630E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.622996E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.570349E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.464525E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.368710E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.621685E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.345272E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.690630E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120435E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122986E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157767E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.192795E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.252011E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.281775E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.298934E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.298699E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.275730E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.235624E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172330E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132268E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.254136E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120435E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.298934E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146943E+10 | 0.752252E+10 | 12246680.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135321E+10 | 0.813744E+10 | 16165314.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159423E+10 | 0.103542E+11 | 26221533.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149200E+10 | 0.125769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156829E+10 | 0.164056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158144E+10 | 0.181162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153288E+10 | 0.184731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164943E+10 | 0.195701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152847E+10 | 0.175766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151219E+10 | 0.157365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143010E+10 | 0.122192E+11 | 2152139.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147521E+10 | 0.842004E+10 | 22669440.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181869E+11 | 0.165109E+12 | 79455108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135321E+10 | 0.752252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164943E+10 | 0.195701E+11 | 26221533.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.700930E+10 | 0.175272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.647637E+10 | 0.202587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.766511E+10 | 0.285183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740311E+10 | 0.412889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.813506E+10 | 0.588371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.849875E+10 | 0.678597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.849969E+10 | 0.725514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.887519E+10 | 0.718704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.826406E+10 | 0.663303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781427E+10 | 0.543684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697751E+10 | 0.358845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.709909E+10 | 0.214666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927175E+11 | 0.556761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.647637E+10 | 0.175272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.887519E+10 | 0.725514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146943E+10 | 0.00 | 0.00 | 0.00 | 0.198329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135321E+10 | 0.00 | 0.00 | 0.00 | 0.214845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159423E+10 | 0.00 | 0.00 | 0.00 | 0.271023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149200E+10 | 0.00 | 0.00 | 0.00 | 0.333017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156829E+10 | 0.00 | 0.00 | 0.00 | 0.439020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158144E+10 | 0.00 | 0.00 | 0.00 | 0.482659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153288E+10 | 0.00 | 0.00 | 0.00 | 0.501603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164943E+10 | 0.00 | 0.00 | 0.00 | 0.525687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152847E+10 | 0.00 | 0.00 | 0.00 | 0.470148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151219E+10 | 0.00 | 0.00 | 0.00 | 0.419131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143010E+10 | 0.00 | 0.00 | 0.00 | 0.321515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147521E+10 | 0.00 | 0.00 | 0.00 | 0.221189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181869E+11 | 0.00 | 0.00 | 0.00 | 0.439817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135321E+10 | 0.00 | 0.00 | 0.00 | 0.198329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164943E+10 | 0.00 | 0.00 | 0.00 | 0.525687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.700930E+10 | 0.00 | 0.00 | 0.00 | 0.503423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.647637E+10 | 0.00 | 0.00 | 0.00 | 0.582228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.766511E+10 | 0.00 | 0.00 | 0.00 | 0.811160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740311E+10 | 0.00 | 0.00 | 0.00 | 0.118764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.813506E+10 | 0.00 | 0.00 | 0.00 | 0.170660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.849875E+10 | 0.00 | 0.00 | 0.00 | 0.196788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.849969E+10 | 0.00 | 0.00 | 0.00 | 0.213937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.887519E+10 | 0.00 | 0.00 | 0.00 | 0.209947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.826406E+10 | 0.00 | 0.00 | 0.00 | 0.193089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781427E+10 | 0.00 | 0.00 | 0.00 | 0.157482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697751E+10 | 0.00 | 0.00 | 0.00 | 0.102555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.709909E+10 | 0.00 | 0.00 | 0.00 | 0.612776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927175E+11 | 0.00 | 0.00 | 0.00 | 0.161418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.647637E+10 | 0.00 | 0.00 | 0.00 | 0.503423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.887519E+10 | 0.00 | 0.00 | 0.00 | 0.213937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 82431987.31 | 0.464544E+09 | 0.00 | 3571741.84 | 0.00 | 10591846.34 | 0.306034E+09 | 0.00 | 0.14 |
February | 57017791.46 | 0.544649E+09 | 0.00 | 2541069.39 | 0.00 | 10011133.14 | 0.130963E+09 | 0.00 | 0.14 |
March | 64775278.68 | 0.737539E+09 | 0.00 | 3547326.54 | 0.00 | 16203311.99 | 0.205038E+09 | 0.00 | 0.15 |
April | 2961287.45 | 0.114986E+10 | 0.00 | 3139202.43 | 0.00 | 0.00 | 34556109.33 | 0.00 | 0.15 |
May | 0.00 | 0.196275E+10 | 0.00 | 1820393.14 | 0.00 | 0.00 | 183792.77 | 0.00 | 0.15 |
June | 0.00 | 0.260166E+10 | 0.00 | 531872.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.288912E+10 | 0.00 | 139086.56 | 0.00 | 0.00 | 10961.52 | 0.00 | 0.14 |
August | 0.00 | 0.293526E+10 | 0.00 | 402677.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.257508E+10 | 0.00 | 694153.73 | 0.00 | 0.00 | 131663.26 | 0.00 | 0.15 |
October | 0.00 | 0.203120E+10 | 0.00 | 1099886.82 | 0.00 | 0.00 | 237214.47 | 0.00 | 0.14 |
November | 11012856.69 | 0.137455E+10 | 0.00 | 2625229.59 | 0.00 | 3022531.84 | 18835858.89 | 0.00 | 0.14 |
December | 74027984.79 | 0.599428E+09 | 0.00 | 3949449.61 | 0.00 | 12369873.56 | 0.260953E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.292227E+09 | 0.198656E+11 | 0.00 | 24062089.65 | 0.00 | 52198696.87 | 0.956944E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.464544E+09 | 0.00 | 139086.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 82431987.31 | 0.293526E+10 | 0.00 | 3949449.61 | 0.00 | 16203311.99 | 0.306034E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.895622E+09 | 0.872776E+09 | 0.00 | 7037588.63 | 0.00 | 0.00 | 0.163159E+10 | 0.00 | 0.20 |
February | 0.650645E+09 | 0.100151E+10 | 0.00 | 7320432.68 | 0.00 | 0.00 | 0.763708E+09 | 0.00 | 0.20 |
March | 0.724011E+09 | 0.159179E+10 | 0.00 | 7383092.79 | 0.00 | 0.00 | 0.109023E+10 | 0.00 | 0.22 |
April | 62518507.51 | 0.313196E+10 | 0.00 | 5574772.78 | 0.00 | 0.00 | 0.361129E+09 | 0.00 | 0.22 |
May | 1408382.53 | 0.628748E+10 | 0.00 | 682175.81 | 0.00 | 0.00 | 31167924.52 | 0.00 | 0.23 |
June | 0.00 | 0.961815E+10 | 0.00 | 68700.48 | 0.00 | 0.00 | 2462501.54 | 0.00 | 0.25 |
July | 0.00 | 0.113365E+11 | 0.00 | 15727.14 | 0.00 | 0.00 | 106156.86 | 0.00 | 0.24 |
August | 0.00 | 0.109506E+11 | 0.00 | 32932.12 | 0.00 | 0.00 | 472768.66 | 0.00 | 0.25 |
September | 0.00 | 0.952336E+10 | 0.00 | 78651.50 | 0.00 | 0.00 | 5523074.28 | 0.00 | 0.24 |
October | 717858.57 | 0.665739E+10 | 0.00 | 692238.58 | 0.00 | 0.00 | 38286312.37 | 0.00 | 0.22 |
November | 0.126611E+09 | 0.391033E+10 | 0.00 | 2874347.91 | 0.00 | 0.00 | 0.320687E+09 | 0.00 | 0.20 |
December | 0.863233E+09 | 0.139779E+10 | 0.00 | 5907580.55 | 0.00 | 0.00 | 0.143832E+10 | 0.00 | 0.20 |
Annual Sum or Average | 0.332477E+10 | 0.662797E+11 | 0.00 | 37668240.97 | 0.00 | 0.00 | 0.568368E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.872776E+09 | 0.00 | 15727.14 | 0.00 | 0.00 | 106156.86 | 0.00 | 0.20 |
Maximum of Months | 0.895622E+09 | 0.113365E+11 | 0.00 | 7383092.79 | 0.00 | 0.00 | 0.163159E+10 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:20
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.653203E+12 | 0.382973E+11 | 0.00 | 0.825205E+10 | 0.320737E+11 |
February | 0.711335E+12 | 0.390401E+11 | 0.00 | 0.487941E+10 | 0.363751E+11 |
March | 0.983128E+12 | 0.474196E+11 | 0.00 | 0.386394E+10 | 0.497079E+11 |
April | 0.108022E+13 | 0.417266E+11 | 0.00 | -0.204591E+10 | 0.690724E+11 |
May | 0.106362E+13 | 0.354019E+11 | 0.00 | -0.963019E+10 | 0.966989E+11 |
June | 0.969708E+12 | 0.377966E+11 | 0.00 | -0.165816E+11 | 0.110481E+12 |
July | 0.106481E+13 | 0.427137E+11 | 0.00 | -0.194828E+11 | 0.117434E+12 |
August | 0.110827E+13 | 0.385531E+11 | 0.00 | -0.190173E+11 | 0.117692E+12 |
September | 0.863513E+12 | 0.366420E+11 | 0.00 | -0.166664E+11 | 0.107917E+12 |
October | 0.832459E+12 | 0.328248E+11 | 0.00 | -0.115055E+11 | 0.900444E+11 |
November | 0.621310E+12 | 0.343858E+11 | 0.00 | -0.298223E+10 | 0.615756E+11 |
December | 0.627688E+12 | 0.411651E+11 | 0.00 | 0.550745E+10 | 0.382381E+11 |
Annual Sum or Average | 0.105793E+14 | 0.465967E+12 | 0.00 | -0.754092E+11 | 0.927311E+12 |
Minimum of Months | 0.621310E+12 | 0.328248E+11 | 0.00 | -0.194828E+11 | 0.320737E+11 |
Maximum of Months | 0.110827E+13 | 0.474196E+11 | 0.00 | 0.825205E+10 | 0.117692E+12 |