Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 10:44:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 563.44 | 116.53 | 116.53 |
Net Site Energy | 563.44 | 116.53 | 116.53 |
Total Source Energy | 1391.99 | 287.89 | 287.89 |
Net Source Energy | 1391.99 | 287.89 | 287.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 188.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 108.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 375.04 | 188.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 188.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 108.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 188.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 108.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 37.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.14 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.57 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 37.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.14 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.57 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 375.043 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 375.043 | 100.00 |
Total On-Site and Utility Electric Sources | 375.043 | 100.00 |
Total Electricity End Uses | 375.043 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 15.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2596.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6766 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 7.6766 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.3906 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.5498 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JAN-16:00 | 19-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 110593.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9388.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2295.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1614.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28903.36 | 110593.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 110593.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9388.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2295.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1614.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 204.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 344.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 231.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 79.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 81.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1187.76 | 204.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 245.65 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 71.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 245.65 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.975456 |
ZONE2 FINE STORAGE DIRECT AIR | 1.91 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.79 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.79 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 72235.56 |
PSZ-OFFICE HEATING COIL | 25172.70 |
PSZ-FINE STORAGE HEATING COIL | 65809.76 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 72235.56 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.975456 | 0.975456 | 0.975456 | 0.975456 | 0.975456 | 0.975456 | 1.00 | 1.00 | 0.975456 |
PSZ-FINE STORAGE | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 | 1.00 | 1.000000 | 1.91 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.975456 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.91 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.975456 | 1079.98 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.91 | 2047.93 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.975456 | 0.975456 | 0.975456 | 0.975456 | 16354.57 | 25172.70 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.91 | 1.91 | 1.91 | 1.26 | 39644.16 | 65809.76 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.975460 | 0.487728 | 0.650307 | 16354.57 | 8177.28 | 0.800990 | 0.800990 |
PSZ-FINE STORAGE COOLING COIL | 1.91 | 0.956936 | 1.28 | 39644.16 | 19822.08 | 0.762810 | 0.762810 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 7.677 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.750 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1818.427 | 7.677 | 142.636 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1818.427 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10866.415 | 3.391 | 157.484 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3818_SHGC_SOUTH_0.36 | 34 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.361 | ||
2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.36 | 35 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.361 | ||
3 | NONRESWINDOW_U_0.3818_SHGC_EAST_0.36 | 36 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.361 | ||
4 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.361 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44070E-002 | 0.27318 | 0.51761 | 0.51761 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44070E-002 | 0.27318 | 0.51761 | 0.51761 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44070E-002 | 0.27318 | 0.51761 | 0.51761 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44070E-002 | 0.27318 | 0.51761 | 0.51761 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4951E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3083E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2948E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7458E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2797E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1357E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5727E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2026E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8078E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5295E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3216E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2140E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6361E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5256E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7631E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3735E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9358E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0040E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9461E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4230E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8090E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0297E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2192E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2548E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0032E-003 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7835E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9953E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9947E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6741E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2483E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0518E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7651E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9944E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2324E-004 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0209E-003 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3344E-004 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3326E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8401E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3050E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9351E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2812E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8015E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9932E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0292E-004 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5311E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8359E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9123E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6423E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2739E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0713E-004 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5197E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1494E-004 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4840E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9520E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8041E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6567E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1907E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5043E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3981E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6936E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5219E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0205E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7108E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9807E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1085E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6894E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9264E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1927E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5415E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3825E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3923E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9389E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5881E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4394E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8941E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6224E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2445E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5368E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4880E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3403E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5937E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1002E-003 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9159E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3232E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3039E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6596E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2548E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9448E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6620E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0143E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4177E-004 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2658E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3783E-004 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0577E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7670E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0707E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2874E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7200E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1719E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6655E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6835E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0952E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8074E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0291E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0543E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4174E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6947E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4770E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7430E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0607E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9054E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6421E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7016E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8439E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0889E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7826E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4324E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6204E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6978E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2027E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8179E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7230E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7208E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1576E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5083E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1603E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7987E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5976E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3058E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8214E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0960E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8312E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4175E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6179E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6280E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4594E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1087E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1049E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3937E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9665E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4535E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2840E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8788E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2087E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3548E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2844E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6077E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0334E-004 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3352E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6674E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8401E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3030E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9675E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4065E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9187E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0581E-004 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0926E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6649E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6333E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8608E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2425E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6408E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4882E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0245E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5675E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2818E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6078E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7052E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0245E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7532E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2372E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7305E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2742E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0481E-004 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5886E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6505E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4212E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7275E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7686E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9600E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9950E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2532E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5335E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2723E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0095E-004 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5515E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0098E-004 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1024E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0334E-004 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2519E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1885E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8312E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2864E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9121E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1605E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7810E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5745E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0473E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9439E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2033E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1654E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3203E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1163E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3272E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3701E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8908E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8211E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1307E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9549E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2267E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0827E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2945E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1270E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8995E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7855E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3547E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5031E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3121E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2849E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9217E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9895E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8972E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3063E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2247E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7690E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1557E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0008E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8330E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7878E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9000E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0465E-003 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4897E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5303E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2748E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2379E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6472E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1074E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9915E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5702E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3685E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1990E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3059E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0997E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1897E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5318E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4291E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2389E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3250E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4010E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2544E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9960E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1426E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6694E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4336E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8360E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4069E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0721E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1804E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0119E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5383E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2503E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9975E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9790E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0772E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3481E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8040E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0251E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8902E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8219E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9750E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5670E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0586E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2288E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7779E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0393E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8116E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8575E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9810E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9042E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8345E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0791E-004 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4977E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6187E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3675E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3226E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2355E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7886E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0866E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4317E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4987E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3430E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2481E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3968E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7651E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4617E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9604E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2351E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9618E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5859E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3634E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8771E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0145E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0761E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4009E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2756E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9815E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4554E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7333E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6872E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7148E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1678E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4656E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7045E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9766E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1938E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1563E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1582E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5852E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4534E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0191E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2341E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7105E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6219E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2959E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8744E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2992E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6122E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9861E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1906E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5865E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6983E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6274E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0363E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5247E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7853E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3048E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4367E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0812E-004 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4803E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1578E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2024E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5078E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5293E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6437E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1529E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3793E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8318E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7851E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0355E-004 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9366E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0537E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7698E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2669E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7401E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5174E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4370E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6788E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7598E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7752E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8407E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4316E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0922E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4942E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6220E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2011E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1450E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5243E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4196E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0716E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.8970E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.6217E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4421E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5740E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.5211E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.6989E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.9315E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3744E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0902E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5566E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0357E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4696E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4619E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2251E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6573E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9281E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8798E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5175E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1235E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2283E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.7542E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.2870E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6594E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9598E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8809E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4627E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1222E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2283E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7542E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9739.46435 | 11687.35722 | 0.81288 | 0.97546 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8450.33135 | 10140.39762 | 0.24049 | 0.28859 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 24514.09981 | 29416.91977 | 1.59489 | 1.91387 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22507.53339 | 27009.04007 | 0.53986 | 0.64783 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 60196.30336 | 72235.56403 | 1.49204 | 1.79045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14383.98 | 0.97546 | 0.97546 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9612.83 | 0.28859 | 0.28859 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 34922.42 | 1.91387 | 1.91387 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 28896.14 | 0.64783 | 0.64783 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97546 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.91387 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.79045 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.79045 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 72235.55946 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 72235.56403 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97546 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97546 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97546 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97546 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97546 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.97546 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.91387 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.91387 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.91387 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.91387 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.91387 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.91387 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.97546 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.91387 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97546 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97546 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1079.98419 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97546 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97546 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97546 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97546 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97546 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48773 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65031 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16354.57000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8177.28500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80099 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80099 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16354.57000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25172.70257 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25172.70257 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.91387 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.91387 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2047.93351 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.91387 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.91387 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.91387 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26316 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.91387 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95694 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.27591 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39644.16000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19822.08000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76281 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76281 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39644.16000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65809.75558 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 65809.75558 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15597.6 | 12.19 | 11.91 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 38157.8 | 11.72 | 11.46 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1690433537 | 0.1730389798 | Pass | Pass | 1.7770321966 | 14.2132553750 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3475152317 | 0.3202949005 | Pass | Pass | 0.2120198574 | 0.6002197502 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.0557004741E-005 | 1.3793121445E-005 | Pass | Pass | 4.9850625724E-002 | 4.6808994997E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7148.79 | 412.33 | 0.00 | 69.78 | 68.50 | 7699.42 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.36 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.361 | 0.361 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.36 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.361 | 0.361 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.36 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.361 | 0.361 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.36 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.361 | 0.361 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 3.832 | 0.555 | 0.552 | |||||||||||||||||
North Total or Average | 6.51 | 2.169 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 79.53 | 3.968 | 0.571 | 0.568 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 7.6766 | 236.88 | 1818.43 | LightsWired | LTG_SCH_OFFICE | 49.99 | 168.00 | 45.45 | 0.0000 | Y | 15.51 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 26.41 | 0.0000 | Y | 46.18 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.3906 | 3204.84 | 10866.42 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 23.15 | 0.0000 | Y | 47.22 |
Interior Lighting Total | 4.5498 | 4835.13 | 21998.92 | 108.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1818.43 | 263.67 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 1818.43 | 90.92 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 42.59 | 42.59 | 0.74 | |
EXTERIOR_LIGHTS_B | 5399.43 | AstronomicalClock | - | 83.55 | 71.26 | 72.23 | |
Exterior Lighting Total | 5492.60 | 72.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16354.57 | 13099.85 | 3254.72 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39644.16 | 30240.96 | 9403.20 | 0.76 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15597.6 | 12.19 | 11.91 | ||||
PSZ-FINE STORAGE COOLING COIL | 38157.8 | 11.72 | 11.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 72235.56 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25172.70 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 65809.76 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.79 | 166.35 | 92.91 | 1.00 | 3.65 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1079.98 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.91 | 2047.93 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9739.46 | 11687.36 | 49.34 | 0.813 | 0.975 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00834 | 28.22 | 0.00882 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 24514.10 | 29416.92 | 21.11 | 1.595 | 1.914 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00852 | 29.40 | 0.00882 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 29.79 | 0.00888 | 29.40 | 0.00882 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8450.33 | 10140.40 | 42.81 | 0.240 | 0.289 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00734 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22507.53 | 27009.04 | 19.38 | 0.540 | 0.648 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00594 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 60196.30 | 72235.56 | 22.54 | 1.492 | 1.790 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00477 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.98 | 0.98 | 0.29 | 0.29 | 0.9755 | 0.9755 | 0.9755 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.91 | 1.91 | 0.65 | 0.65 | 1.9139 | 1.9139 | 1.9139 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 72235.559 | 72235.559 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 72235.56 | 72235.56 | 1.790446 | 10.00 | 6.64 | 0.00477365 | 43.33 | 21.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 10.00 | 0.00477365 | 61.9512 | 72235.56 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16354.570 | 13099.847 | 0.975460 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 8177.28 | 7675.18 | 0.650307 | 25.30 | 16.60 | 0.00838785 | 12.00 | 11.13 | 0.00800000 | 28.50 | 0.00882005 | 18.05 | 15.7287 | 23.90 | 0.00833714 | 44.5206 | 9724.49 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25172.703 | 25172.703 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 25172.70 | 25172.70 | 0.975456 | 18.36 | 12.61 | 0.00685663 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 10.4858 | 21.10 | 0.00734468 | 46.5715 | 8450.33 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 39644.160 | 30240.962 | 1.913870 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 19822.08 | 18306.20 | 1.275913 | 28.18 | 17.75 | 0.00858532 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00882150 | 18.34 | 33.2868 | 26.70 | 0.00851797 | 38.4972 | 24514.10 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 65809.756 | 65809.756 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 65809.76 | 65809.76 | 1.913872 | 11.17 | 7.73 | 0.00522194 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.1912 | 15.56 | 0.00594396 | 53.4886 | 22507.53 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 72235.559 | 72235.559 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.790446 | 2.12524249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 72235.56 | 72235.56 | 1.0000 | 2.12524249 | 1.790446 | 10.00 | 6.64 | 0.00477365 | 22073.4 | 43.33 | 21.98 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 72235.56 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 10.00 | 0.00477365 | 10.00 | 0.00477365 | 61.9512 | 72235.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16354.570 | 13099.847 | 0.975460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4326 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.975456 | 1.15785680 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 8177.28 | 7675.18 | 1.0000 | 0.77190802 | 0.650307 | 25.30 | 16.60 | 0.00838785 | 46790.4 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8177.28 | 28.50 | 0.00882005 | 18.05 | 0.10228463 | 15.7287 | 23.90 | 0.00833714 | 23.90 | 0.00833714 | 44.5206 | 9724.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25172.703 | 25172.703 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.975456 | 1.15785680 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 25172.70 | 25172.70 | 1.0000 | 1.15785680 | 0.975456 | 18.36 | 12.61 | 0.00685663 | 35835.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25172.70 | -4.20 | 0.00269032 | -4.20 | 0.10228463 | 10.4858 | 21.01 | 0.00734468 | 21.10 | 0.00734468 | 46.5715 | 8450.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39644.160 | 30240.962 | 1.913870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7997 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.913872 | 2.27174843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 19822.08 | 18306.20 | 1.0000 | 1.51449737 | 1.275913 | 28.18 | 17.75 | 0.00858532 | 50238.8 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19822.08 | 29.40 | 0.00882150 | 18.34 | 0.42471127 | 33.2868 | 26.70 | 0.00851797 | 26.70 | 0.00851797 | 38.4972 | 24514.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65809.756 | 65809.756 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.913872 | 2.27174843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 65809.76 | 65809.76 | 1.0000 | 2.27174843 | 1.913872 | 11.17 | 7.73 | 0.00522194 | 24393.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65809.76 | -4.20 | 0.00269032 | -4.20 | 0.42471127 | 22.1912 | 15.56 | 0.00594396 | 15.56 | 0.00594396 | 53.4886 | 22507.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.98 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2296.33 | 2875.67 | 1864.33 |
ZONE2 FINE STORAGE | 2800.50 | 2966.33 | 2241.67 |
ZONE3 BULK STORAGE | 2854.50 | 3163.50 | 2498.67 |
Facility | 3166.50 | 3265.33 | 2596.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 12.83 | 0.00 | 9.17 | 0.00 |
ZONE2 FINE STORAGE | 158.67 | 0.67 | 10.50 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 167.33 | 0.67 | 15.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.679 | 0.427 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.458 | 0.224 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.136 | 0.000 | 0.051 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.30 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.05 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2445644.54 | 0.00 | 2445644.54 | 2251774.11 | 4697418.65 | 3225648.14 | 5727.42 | 2095.98 | 936.60 | 0.00 |
ZONE2 FINE STORAGE | 4888331.32 | 0.00 | 4888331.32 | 6389014.32 | 11277345.64 | 13393694.68 | 5726.80 | 2862.83 | 170.37 | 3.20 |
ZONE3 BULK STORAGE | 0.00 | 15191358.05 | 15191358.05 | 36404708.86 | 51596066.91 | 30805497.77 | 8454.33 | 47.00 | 258.67 | 4996.00 |
Total Facility | 7333975.86 | 15191358.05 | 22525333.91 | 45045497.29 | 67570831.20 | 47424840.58 | 8605.33 | 2956.33 | 1251.13 | 4996.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1868 | 0.0000 | 0.1868 | 0.1182 | 0.3051 | 0.1023 | 603.42 | 2095.98 | 936.60 |
ZONE2 FINE STORAGE | 0.3726 | 0.0000 | 0.3726 | 0.1829 | 0.5555 | 0.4247 | 606.00 | 2862.83 | 167.17 |
ZONE3 BULK STORAGE | 0.0000 | 0.5039 | 0.5039 | 1.3391 | 1.8431 | 0.9768 | 3471.00 | 26.83 | 138.17 |
Total Facility | 0.5595 | 0.5039 | 1.0634 | 1.6402 | 2.7037 | 1.5038 | 3481.33 | 2936.17 | 1127.43 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3445783.83 | 0.00 | 3445783.83 | 3225648.14 | 5726.75 | 0.00 | 3033.25 | 0.00 |
PSZ-FINE STORAGE | 6887280.63 | 0.00 | 6887280.63 | 13393694.68 | 5726.80 | 0.00 | 3033.20 | 3.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2632 | 0.0000 | 0.2632 | 0.1023 | 602.75 | 0.00 | 3033.25 |
PSZ-FINE STORAGE | 0.5250 | 0.0000 | 0.5250 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2496.08 | 539.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2990.70 | 42.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2755 | 0.5001 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6255 | 0.9663 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
Electricity:Building | 248.21 | 1328.97 | 26-MAR-14:20 | 20605.14 | 16-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 47.46 | 774.00 | 26-FEB-15:30 | 2976.64 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 248.21 | 1328.97 | 26-MAR-14:20 | 20605.14 | 16-DEC-16:00 |
InteriorLights:Electricity | 108.92 | 755.22 | 26-MAR-14:20 | 10492.52 | 16-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.51 | 200.25 | 26-FEB-15:30 | 1064.14 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 108.92 | 755.22 | 26-MAR-14:20 | 10492.52 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 108.92 | 755.22 | 26-MAR-14:20 | 10492.52 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.51 | 200.25 | 26-FEB-15:30 | 1064.14 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 108.92 | 755.22 | 26-MAR-14:20 | 10492.52 | 16-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 46.18 | 256.14 | 20-FEB-11:50 | 4354.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 46.18 | 256.14 | 20-FEB-11:50 | 4354.33 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 46.18 | 256.14 | 20-FEB-11:50 | 4354.33 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 154.57 | 298.83 | 16-JAN-12:00 | 13280.17 | 02-JAN-15:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.22 | 298.83 | 16-JAN-12:00 | 5080.05 | 02-JAN-15:40 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.22 | 298.83 | 16-JAN-12:00 | 5080.05 | 02-JAN-15:40 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 25.19 | 0.00 | 02-JAN-18:40 | 2418.08 | 18-FEB-18:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
ElectricityPurchased:Plant | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
Cogeneration:ElectricityPurchased | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
General:Cogeneration:ElectricityPurchased | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
ElectricityNet:Plant | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
Cogeneration:ElectricityNet | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
General:Cogeneration:ElectricityNet | 375.04 | 1811.97 | 26-MAR-14:20 | 28903.36 | 14-JAN-17:00 |
Electricity:HVAC | 28.26 | 0.00 | 02-JAN-18:40 | 8956.05 | 10-AUG-15:10 |
General:Fans:Electricity | 25.19 | 0.00 | 02-JAN-18:40 | 2418.08 | 18-FEB-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3.07 | 0.00 | 01-JAN-00:10 | 7056.89 | 10-AUG-15:10 |
General:Cooling:Electricity | 3.07 | 0.00 | 01-JAN-00:10 | 7056.89 | 10-AUG-15:10 |
ExteriorLights:Electricity | 72.97 | 0.00 | 01-JAN-08:10 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.97 | 0.00 | 01-JAN-08:10 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 25.60 | 483.00 | 01-JAN-00:10 | 2319.71 | 11-FEB-13:00 |
WaterSystems:Electricity | 25.60 | 483.00 | 01-JAN-00:10 | 2319.71 | 11-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.60 | 483.00 | 01-JAN-00:10 | 2319.71 | 11-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 188.40 | 0.00 | 02-JAN-18:40 | 110593.92 | 19-FEB-07:30 |
NaturalGas:HVAC | 188.40 | 0.00 | 02-JAN-18:40 | 110593.92 | 19-FEB-07:30 |
Heating:NaturalGas | 188.40 | 0.00 | 02-JAN-18:40 | 110593.92 | 19-FEB-07:30 |
General:Heating:NaturalGas | 188.40 | 0.00 | 02-JAN-18:40 | 110593.92 | 19-FEB-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 319.29 | 0.00 | 02-JAN-18:40 | 173503.00 | 19-FEB-07:30 |
EnergyTransfer:Building | 168.61 | 0.00 | 02-JAN-18:40 | 87130.45 | 19-FEB-07:30 |
EnergyTransfer:Zone:ZONE1 OFFICE | 35.98 | 0.00 | 01-JAN-00:10 | 18241.11 | 26-DEC-07:10 |
Heating:EnergyTransfer | 129.38 | 0.00 | 02-JAN-18:40 | 87130.45 | 19-FEB-07:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 23.06 | 0.00 | 01-JAN-00:10 | 18241.11 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 129.38 | 0.00 | 02-JAN-18:40 | 87130.45 | 19-FEB-07:30 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 23.06 | 0.00 | 01-JAN-00:10 | 18241.11 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 39.22 | 0.00 | 01-JAN-00:10 | 22535.89 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.93 | 0.00 | 01-JAN-00:10 | 9047.30 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer | 39.22 | 0.00 | 01-JAN-00:10 | 22535.89 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.93 | 0.00 | 01-JAN-00:10 | 9047.30 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 74.52 | 0.00 | 01-JAN-00:40 | 28419.30 | 19-FEB-07:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 48.22 | 0.00 | 01-JAN-00:40 | 28419.30 | 19-FEB-07:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 48.22 | 0.00 | 01-JAN-00:40 | 28419.30 | 19-FEB-07:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.30 | 0.00 | 01-JAN-00:10 | 14670.67 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 26.30 | 0.00 | 01-JAN-00:10 | 14670.67 | 10-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 58.11 | 0.00 | 02-JAN-08:10 | 56815.62 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 58.11 | 0.00 | 02-JAN-08:10 | 56815.62 | 19-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 58.11 | 0.00 | 02-JAN-08:10 | 56815.62 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 150.69 | 0.00 | 02-JAN-18:40 | 86372.55 | 19-FEB-07:30 |
HeatingCoils:EnergyTransfer | 136.83 | 0.00 | 02-JAN-18:40 | 86372.55 | 19-FEB-07:30 |
CoolingCoils:EnergyTransfer | 13.86 | 0.00 | 01-JAN-00:10 | 29800.55 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 23.056 | -12.927 | 0.000 | 0.000 | 10.089 | 15.513 | 31.946 | 9.140 | 0.000 | 0.226 | 0.001 | 0.000 | -6.601 | 0.000 | -26.397 | -44.045 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 48.221 | -26.296 | 0.000 | 0.000 | 26.583 | 46.183 | 0.000 | 43.045 | 0.000 | 0.192 | 0.002 | 0.000 | -15.038 | 0.000 | -60.126 | -62.766 |
ZONE3 BULK STORAGE | 58.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67.343 | 47.224 | 107.344 | 409.606 | 0.000 | 5.071 | 0.001 | 0.000 | -102.139 | 0.000 | -300.128 | -292.426 |
Total Facility | 58.105 | 0.000 | 71.277 | -39.223 | 0.000 | 0.000 | 104.016 | 108.921 | 139.290 | 461.791 | 0.000 | 5.489 | 0.004 | 0.000 | -123.777 | 0.000 | -386.651 | -399.237 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19698.99 | 0.00 | 0.00 | 801.79 | 1033.84 | 1912.50 | 0.00 | 0.00 | 0.00 | 16661.68 | 0.00 | -290.12 | 0.00 | -420.71 | 0.00 |
ZONE2 FINE STORAGE | 10-AUG-17:43 | 0.00 | 0.00 | 0.00 | -34839.34 | 0.00 | 0.00 | 0.00 | 512.27 | 0.00 | 1234.95 | 0.00 | 715.25 | 32376.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-17:43 | 0.00 | 0.00 | 0.00 | -34839.34 | 0.00 | 0.00 | 0.00 | 1260.38 | 2623.78 | 19014.60 | 0.00 | 4840.62 | 7099.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-DEC-07:01 | 0.00 | 0.00 | 25624.19 | 0.00 | 0.00 | 0.00 | 261.91 | 580.44 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -589.32 | 0.00 | -8252.76 | -18580.71 |
ZONE2 FINE STORAGE | 19-FEB-07:23 | 0.00 | 0.00 | 67098.52 | 0.00 | 0.00 | 0.00 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1364.33 | 0.00 | -7751.17 | -58495.29 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 56815.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8976.07 | 0.00 | -40688.43 | -7748.27 |
Total Facility | 19-FEB-07:23 | 55706.91 | 0.00 | 79114.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.75 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14289.59 | 0.00 | -49812.77 | -72649.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9755 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9755 | 0.1049 | 1.0000 | Not calculated | 0.1023 | 0.1049 | ||
PSZ-FINE STORAGE | 1.9139 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.9139 | 0.2219 | 1.0000 | Not calculated | 0.4247 | 0.2219 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9755 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9755 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1049 | ||
PSZ-FINE STORAGE | 1.9139 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.9139 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2219 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9755 | 0.9755 | 0.9755 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9139 | 1.9139 | 1.9139 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9755 | 0.9755 | 0.9755 | 0.9755 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.9139 | 1.9139 | 1.9139 | 1.9139 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9755 | 0.9755 | 0.9755 | No | 0.1023 | 0.3544 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9139 | 1.9139 | 1.9139 | No | 0.4247 | 0.6556 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9755 | 0.9755 | 0.9755 | 0.9755 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.9139 | 1.9139 | 1.9139 | 1.9139 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 15.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 15.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 188.40 | 110593.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3.07 | 7056.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 108.92 | 10492.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.97 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.19 | 2418.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.60 | 2319.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 375.04 |
Natural Gas | 0.00 | 188.40 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 563.44 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 22.53 |
Space Heating | 0.00 |
Space Cooling | 0.63 |
Fans (All) | 5.21 |
Service Water Heating | 5.30 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 77.57 |
Subtotal | 77.57 |
Natural Gas [MJ/m2] | |
Space Heating | 38.96 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 38.96 |
Subtotal | 38.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.33 |
Space Heating | 33.44 |
Space Cooling | 0.54 |
Fans (All) | 4.47 |
Service Water Heating | 4.54 |
Receptacle Equipment | 24.72 |
Miscellaneous | 12.95 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2607. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8635.50 | 124.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8569.00 | 191.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8676.50 | 83.50 | 0.00 | 0.00 | 0.00 |
Min | 8569.00 | 83.50 | 0.00 | 0.00 | 0.00 |
Max | 8676.50 | 191.00 | 0.00 | 0.00 | 0.00 |
Average | 8627.00 | 133.00 | 0.00 | 0.00 | 0.00 |
Sum | 25881.00 | 399.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 78844.00 | 3875.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 187635.50 | 3557.50 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 187635.50 | 3875.00 | 0.00 | 0.00 | 0.00 |
Average | 99835.50 | 2477.50 | 0.00 | 0.00 | 0.00 |
Sum | 299506.50 | 7432.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8613.67 | 146.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8413.67 | 346.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8580.83 | 179.17 | 0.00 | 0.00 | 0.00 |
Min | 8413.67 | 146.33 | 0.00 | 0.00 | 0.00 |
Max | 8613.67 | 346.33 | 0.00 | 0.00 | 0.00 |
Average | 8536.06 | 223.94 | 0.00 | 0.00 | 0.00 |
Sum | 25608.17 | 671.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75724.00 | 6995.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 183779.00 | 7414.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 183779.00 | 7414.00 | 0.00 | 0.00 | 0.00 |
Average | 97510.00 | 4803.00 | 0.00 | 0.00 | 0.00 |
Sum | 292530.00 | 14409.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4837407.92 | 1691.27 | 21-JAN-08:07 | -0.7 | -0.9 | 0.493593E+09 | 603.88 | 11-JAN-08:20 | -0.7 | -0.9 |
February | 4060596.94 | 1653.75 | 18-FEB-08:07 | -1.5 | -2.1 | 0.455784E+09 | 708.92 | 27-FEB-16:10 | 19.32 | 12.38 |
March | 15651158.07 | 1408.20 | 02-MAR-08:07 | 2.15 | 1.10 | 0.537945E+09 | 745.30 | 18-MAR-15:00 | 20.60 | 10.43 |
April | 0.174655E+09 | 3272.81 | 27-APR-16:00 | 27.20 | 16.90 | 0.524122E+09 | 768.98 | 29-APR-15:09 | 21.83 | 15.11 |
May | 0.866185E+09 | 4567.73 | 15-MAY-16:00 | 23.90 | 12.85 | 0.618526E+09 | 781.74 | 06-MAY-07:10 | 23.90 | 12.85 |
June | 0.196440E+10 | 19516.59 | 24-JUN-07:03 | 13.58 | 10.70 | 0.647102E+09 | 865.74 | 24-JUN-07:10 | 13.58 | 10.70 |
July | 0.359426E+10 | 19164.89 | 01-JUL-07:02 | 15.00 | 11.57 | 0.634485E+09 | 879.38 | 29-JUL-07:10 | 15.60 | 13.33 |
August | 0.413014E+10 | 18769.83 | 19-AUG-07:03 | 13.82 | 11.59 | 0.685811E+09 | 879.39 | 26-AUG-07:10 | 16.38 | 15.20 |
September | 0.195957E+10 | 19704.54 | 16-SEP-07:02 | 10.68 | 10.68 | 0.622267E+09 | 879.13 | 16-SEP-07:10 | 10.68 | 10.68 |
October | 0.200751E+09 | 2723.85 | 04-OCT-15:00 | 21.70 | 11.49 | 0.533475E+09 | 768.96 | 04-OCT-15:30 | 21.40 | 11.45 |
November | 7903928.65 | 1470.97 | 24-NOV-08:05 | 1.97 | 1.45 | 0.477469E+09 | 768.97 | 04-NOV-14:00 | 1.97 | 1.45 |
December | 5167147.95 | 1622.15 | 26-DEC-08:05 | -1.1 | -1.2 | 0.493631E+09 | 603.99 | 16-DEC-08:20 | -1.1 | -1.2 |
Annual Sum or Average | 0.129276E+11 | 0.672421E+10 | ||||||||
Minimum of Months | 4060596.94 | 1408.20 | -1.5 | -2.1 | 0.455784E+09 | 603.88 | -1.1 | -1.2 | ||
Maximum of Months | 0.413014E+10 | 19704.54 | 27.20 | 16.90 | 0.685811E+09 | 879.39 | 23.90 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.790596E+09 | 7225.71 | 06-JAN-10:10 | -1.0 | -1.0 | 0.652770E+09 | 927.91 | 11-JAN-14:30 | 14.40 | 10.49 |
February | 0.111522E+10 | 4768.80 | 08-FEB-11:40 | 4.63 | 2.88 | 0.631554E+09 | 1236.26 | 27-FEB-15:39 | 19.60 | 12.34 |
March | 0.211352E+10 | 4719.44 | 02-MAR-09:10 | 4.78 | 3.27 | 0.803638E+09 | 1297.61 | 18-MAR-15:00 | 20.60 | 10.43 |
April | 0.196021E+10 | 4285.68 | 18-APR-09:30 | 5.55 | 4.06 | 0.897158E+09 | 1926.80 | 27-APR-15:30 | 27.20 | 17.10 |
May | 0.246678E+10 | 5373.80 | 08-MAY-07:03 | 9.68 | 9.59 | 0.127352E+10 | 2165.95 | 15-MAY-15:00 | 23.90 | 12.85 |
June | 0.245700E+10 | 6621.46 | 28-JUN-15:00 | 26.10 | 15.54 | 0.151200E+10 | 2246.82 | 28-JUN-13:09 | 26.10 | 15.54 |
July | 0.394509E+10 | 34435.17 | 24-JUL-17:10 | 28.40 | 17.93 | 0.168792E+10 | 2246.89 | 31-JUL-12:09 | 26.28 | 18.27 |
August | 0.429858E+10 | 34837.97 | 10-AUG-17:43 | 30.88 | 19.37 | 0.183634E+10 | 2246.88 | 10-AUG-12:09 | 30.88 | 19.37 |
September | 0.253511E+10 | 5836.47 | 16-SEP-07:02 | 10.68 | 10.68 | 0.143035E+10 | 2246.84 | 14-SEP-13:30 | 10.68 | 10.68 |
October | 0.197505E+10 | 4831.35 | 12-OCT-07:03 | 6.38 | 5.17 | 0.917573E+09 | 1803.18 | 04-OCT-15:09 | 6.38 | 5.17 |
November | 0.152109E+10 | 4113.50 | 22-NOV-11:50 | 5.92 | 5.20 | 0.681327E+09 | 1387.35 | 04-NOV-14:50 | 5.92 | 5.20 |
December | 0.111710E+10 | 4853.39 | 06-DEC-12:00 | 3.30 | 3.23 | 0.658366E+09 | 936.94 | 02-DEC-13:00 | 3.30 | 3.23 |
Annual Sum or Average | 0.262953E+11 | 0.129825E+11 | ||||||||
Minimum of Months | 0.790596E+09 | 4113.50 | -1.0 | -1.0 | 0.631554E+09 | 927.91 | 3.30 | 3.23 | ||
Maximum of Months | 0.429858E+10 | 34837.97 | 30.88 | 19.37 | 0.183634E+10 | 2246.89 | 30.88 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.700425E+09 | 1189.52 | 11-JAN-15:30 | 14.40 | 10.49 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.738652E+09 | 1629.75 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.117142E+10 | 1976.63 | 18-MAR-15:00 | 20.60 | 10.43 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.143642E+10 | 2983.94 | 29-APR-15:30 | 21.10 | 14.85 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.234374E+10 | 3815.64 | 15-MAY-15:00 | 23.90 | 12.85 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.286963E+10 | 4688.65 | 28-JUN-15:00 | 26.10 | 16.29 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.350958E+10 | 5659.70 | 31-JUL-15:00 | 28.90 | 19.18 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.410048E+10 | 5739.23 | 10-AUG-15:00 | 31.20 | 18.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.319761E+10 | 4894.87 | 15-SEP-15:00 | 23.90 | 17.57 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.182357E+10 | 3458.07 | 04-OCT-15:20 | 21.50 | 11.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 | 8.04 | 0.101492E+10 | 2159.56 | 04-NOV-15:20 | 20.73 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 | 3.48 | 0.750659E+09 | 1154.46 | 02-DEC-14:30 | 11.95 | 5.66 |
Annual Sum or Average | 0.00 | 0.236571E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.700425E+09 | 1154.46 | 11.95 | 5.66 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.410048E+10 | 5739.23 | 31.20 | 19.18 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510556E+10 | 25601.79 | 09-JAN-07:01 | -0.5 |
February | 0.394529E+10 | 25562.76 | 21-FEB-07:01 | 1.60 |
March | 0.301081E+10 | 25501.56 | 24-MAR-06:01 | 1.78 |
April | 0.151924E+10 | 25400.57 | 07-APR-06:01 | 6.88 |
May | 0.322862E+09 | 24944.06 | 24-MAY-06:02 | 7.98 |
June | 0.157557E+09 | 9395.92 | 14-JUN-07:03 | 10.68 |
July | 96691321.38 | 1499.41 | 10-JUL-06:15 | 12.97 |
August | 0.107832E+09 | 1681.92 | 01-AUG-06:15 | 11.33 |
September | 0.142833E+09 | 9727.43 | 28-SEP-07:03 | 9.08 |
October | 0.115966E+10 | 25408.56 | 16-OCT-06:01 | 6.60 |
November | 0.308780E+10 | 25520.71 | 24-NOV-07:01 | 1.20 |
December | 0.440037E+10 | 25624.56 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.230565E+11 | |||
Minimum of Months | 96691321.38 | 1499.41 | -1.6 | |
Maximum of Months | 0.510556E+10 | 25624.56 | 12.97 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144335E+11 | 66292.90 | 06-JAN-06:01 | -1.8 |
February | 0.101098E+11 | 67098.44 | 19-FEB-07:23 | -5.0 |
March | 0.403416E+10 | 52376.35 | 24-MAR-05:53 | 1.70 |
April | 0.101165E+10 | 35439.60 | 01-APR-05:08 | 7.38 |
May | 73167471.86 | 911.70 | 17-MAY-07:00 | 8.90 |
June | 64723772.76 | 846.46 | 13-JUN-07:00 | 11.70 |
July | 60965568.57 | 844.43 | 28-JUL-06:50 | 15.50 |
August | 67108446.89 | 943.39 | 31-AUG-07:00 | 14.00 |
September | 65211816.44 | 882.44 | 27-SEP-07:00 | 8.90 |
October | 0.427090E+09 | 42929.14 | 24-OCT-06:01 | 6.28 |
November | 0.590843E+10 | 55243.75 | 29-NOV-20:43 | 4.90 |
December | 0.119658E+11 | 58421.75 | 26-DEC-03:53 | -1.1 |
Annual Sum or Average | 0.482216E+11 | |||
Minimum of Months | 60965568.57 | 844.43 | -5.0 | |
Maximum of Months | 0.144335E+11 | 67098.44 | 15.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250174E+11 | 38938.28 | 15-JAN-01:53 | -1.7 |
February | 0.176812E+11 | 56815.62 | 19-FEB-07:00 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.114576E+10 | 21468.27 | 29-NOV-21:00 | 5.00 |
December | 0.142607E+11 | 31612.40 | 22-DEC-23:00 | 1.10 |
Annual Sum or Average | 0.581051E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.250174E+11 | 56815.62 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135444E+10 | 1064.14 | 02-JAN-16:30 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.120979E+10 | 1055.69 | 04-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.135146E+10 | 1049.43 | 22-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.124785E+10 | 1038.50 | 03-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.127552E+10 | 1018.43 | 17-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.125693E+10 | 1011.62 | 29-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.125820E+10 | 1036.96 | 12-JUL-08:30 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.132106E+10 | 1032.51 | 02-AUG-07:30 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.125870E+10 | 1050.03 | 25-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.131296E+10 | 1063.21 | 31-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.130315E+10 | 1064.14 | 06-NOV-16:49 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.136326E+10 | 1064.14 | 01-DEC-16:19 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.155133E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.120979E+10 | 1011.62 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.136326E+10 | 1064.14 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.449673E+10 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.383175E+10 | 4354.33 | 01-FEB-15:00 | 0.00 | 0.00 |
March | 0.403513E+10 | 4354.33 | 02-MAR-09:09 | 0.00 | 0.00 |
April | 0.342909E+10 | 3991.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.333388E+10 | 3991.47 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.328523E+10 | 3628.61 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.342416E+10 | 4354.33 | 12-JUL-08:09 | 0.00 | 0.00 |
August | 0.372826E+10 | 3991.47 | 10-AUG-08:09 | 0.00 | 0.00 |
September | 0.365335E+10 | 4354.33 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.410898E+10 | 4354.33 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 0.425782E+10 | 4354.33 | 02-NOV-08:09 | 0.00 | 0.00 |
December | 0.459905E+10 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.461834E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.328523E+10 | 3628.61 | 0.00 | 0.00 | |
Maximum of Months | 0.459905E+10 | 4354.33 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470469E+10 | 5080.05 | 02-JAN-15:39 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.392516E+10 | 5080.05 | 06-FEB-15:39 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.404236E+10 | 4656.71 | 02-MAR-15:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.347619E+10 | 3735.33 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.345029E+10 | 3585.92 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.335147E+10 | 2988.26 | 01-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.344463E+10 | 4233.37 | 12-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.369290E+10 | 3735.33 | 02-AUG-07:19 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.368017E+10 | 4482.40 | 21-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.412109E+10 | 5080.05 | 27-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.440224E+10 | 5080.05 | 03-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.493273E+10 | 5080.05 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.472239E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.335147E+10 | 2988.26 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.493273E+10 | 5080.05 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.135444E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332055E+10 |
February | 0.127628E+10 | 0.120979E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278703E+10 |
March | 0.149825E+10 | 0.135146E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271631E+10 |
April | 0.138726E+10 | 0.124785E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13034005.22 | 0.217263E+10 |
May | 0.144276E+10 | 0.127552E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1229555.74 | 0.204893E+10 |
June | 0.144276E+10 | 0.125693E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9430533.45 | 0.173195E+10 |
July | 0.138726E+10 | 0.125820E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53807819.46 | 0.134244E+10 |
August | 0.149825E+10 | 0.132106E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146754E+09 | 0.126341E+10 |
September | 0.138726E+10 | 0.125870E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2094690.85 | 0.131688E+10 |
October | 0.138726E+10 | 0.131296E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208860E+10 |
November | 0.133177E+10 | 0.130315E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262169E+10 |
December | 0.138726E+10 | 0.136326E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298696E+10 |
Annual Sum or Average | 0.168137E+11 | 0.155133E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226351E+09 | 0.263974E+11 |
Minimum of Months | 0.127628E+10 | 0.120979E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126341E+10 |
Maximum of Months | 0.149825E+10 | 0.136326E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146754E+09 | 0.332055E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.449673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731680E+10 |
February | 0.300332E+10 | 0.383175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55897.57 | 0.614588E+10 |
March | 0.352563E+10 | 0.403513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663414.49 | 0.529028E+10 |
April | 0.326447E+10 | 0.342909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75829179.38 | 0.482709E+10 |
May | 0.339505E+10 | 0.333388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521570E+10 |
June | 0.339505E+10 | 0.328523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490623E+10 |
July | 0.326447E+10 | 0.342416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28823425.81 | 0.451816E+10 |
August | 0.352563E+10 | 0.372826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86708530.09 | 0.406809E+10 |
September | 0.326447E+10 | 0.365335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273994E+10 |
October | 0.326447E+10 | 0.410898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426785E+10 |
November | 0.313390E+10 | 0.425782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46259.91 | 0.489474E+10 |
December | 0.326447E+10 | 0.459905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593500E+10 |
Annual Sum or Average | 0.395654E+11 | 0.461834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192127E+09 | 0.601258E+11 |
Minimum of Months | 0.300332E+10 | 0.328523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273994E+10 |
Maximum of Months | 0.352563E+10 | 0.459905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86708530.09 | 0.731680E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.470469E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106820E+09 | 0.196987E+11 |
February | 0.690763E+10 | 0.392516E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477773E+09 | 0.166911E+11 |
March | 0.810895E+10 | 0.404236E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377620E+09 | 0.160115E+11 |
April | 0.750829E+10 | 0.347619E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144836E+10 | 0.158645E+11 |
May | 0.780862E+10 | 0.345029E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319008E+09 | 0.209666E+11 |
June | 0.780862E+10 | 0.335147E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73833435.38 | 0.191016E+11 |
July | 0.750829E+10 | 0.344463E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197143E+09 | 0.196272E+11 |
August | 0.810895E+10 | 0.369290E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467839E+09 | 0.205639E+11 |
September | 0.750829E+10 | 0.368017E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42907.50 | 0.147960E+11 |
October | 0.750829E+10 | 0.412109E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 390736.19 | 0.189488E+11 |
November | 0.720796E+10 | 0.440224E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88567825.29 | 0.143014E+11 |
December | 0.750829E+10 | 0.493273E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50310565.09 | 0.145048E+11 |
Annual Sum or Average | 0.910005E+11 | 0.472239E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360771E+10 | 0.211076E+12 |
Minimum of Months | 0.690763E+10 | 0.335147E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42907.50 | 0.143014E+11 |
Maximum of Months | 0.810895E+10 | 0.493273E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144836E+10 | 0.209666E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1064.14 | 02-JAN-16:30 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8994.50 | 06-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1055.69 | 04-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9205.11 | 13-FEB-18:00 |
March | 1680.92 | 01-MAR-08:09 | 1049.43 | 22-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8483.84 | 24-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1038.50 | 03-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1217.15 | 27-APR-16:10 | 7363.36 | 19-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1018.43 | 17-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.27 | 05-MAY-16:10 | 6190.24 | 18-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1011.62 | 29-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.25 | 28-JUN-17:00 | 5029.04 | 06-JUN-16:03 |
July | 1680.92 | 01-JUL-07:10 | 1036.96 | 12-JUL-08:30 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1952.10 | 24-JUL-16:10 | 4556.14 | 12-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1032.51 | 02-AUG-07:30 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2890.67 | 10-AUG-17:00 | 5478.83 | 01-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1050.03 | 25-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.89 | 14-SEP-17:00 | 4775.65 | 26-SEP-16:03 |
October | 1680.92 | 02-OCT-07:10 | 1063.21 | 31-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5949.52 | 31-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1064.14 | 06-NOV-16:49 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 8379.11 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1064.14 | 01-DEC-16:19 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 8983.32 | 26-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1011.62 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4556.14 | |||||
Maximum of Months | 1680.92 | 1064.14 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2890.67 | 9205.11 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10098.00 | 28-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 4354.33 | 01-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 | 27-FEB-15:00 | 8753.23 | 13-FEB-08:00 |
March | 3955.50 | 01-MAR-08:09 | 4354.33 | 02-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.10 | 18-MAR-16:00 | 7984.02 | 24-MAR-06:01 |
April | 3955.50 | 01-APR-07:10 | 3991.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3171.38 | 01-APR-16:00 | 6717.18 | 08-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3991.47 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 7673.13 | 10-MAY-15:10 |
June | 3955.50 | 01-JUN-07:10 | 3628.61 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 8077.72 | 13-JUN-03:00 |
July | 3955.50 | 01-JUL-07:10 | 4354.33 | 12-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.18 | 24-JUL-15:10 | 5009.92 | 03-JUL-16:00 |
August | 3955.50 | 01-AUG-07:10 | 3991.47 | 10-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.12 | 08-AUG-17:00 | 7360.01 | 11-AUG-04:00 |
September | 3955.50 | 01-SEP-07:10 | 4354.33 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5099.32 | 26-SEP-16:00 |
October | 3955.50 | 02-OCT-07:10 | 4354.33 | 03-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5932.79 | 31-OCT-20:00 |
November | 3955.50 | 01-NOV-07:10 | 4354.33 | 02-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 04-NOV-15:00 | 9471.90 | 29-NOV-18:00 |
December | 3955.50 | 01-DEC-08:09 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7013.85 | 22-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5009.92 | ||||
Maximum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3171.38 | 10098.00 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 5080.05 | 02-JAN-15:39 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8054.43 | 11-JAN-14:00 | 22974.05 | 14-JAN-19:57 |
February | 9097.65 | 01-FEB-08:09 | 5080.05 | 06-FEB-15:39 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5990.65 | 27-FEB-15:00 | 28936.04 | 13-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 4656.71 | 02-MAR-15:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11436.50 | 18-MAR-16:00 | 27469.08 | 22-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3735.33 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30070.78 | 01-APR-16:00 | 20956.52 | 18-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 3585.92 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.62 | 04-MAY-14:00 | 29550.62 | 17-MAY-19:00 |
June | 9097.65 | 01-JUN-07:10 | 2988.26 | 01-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.27 | 20-JUN-17:00 | 31655.88 | 13-JUN-10:00 |
July | 9097.65 | 01-JUL-07:10 | 4233.37 | 12-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4914.00 | 23-JUL-13:55 | 21311.38 | 28-JUL-07:10 |
August | 9097.65 | 01-AUG-07:10 | 3735.33 | 02-AUG-07:19 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5955.09 | 08-AUG-17:00 | 31721.66 | 11-AUG-04:00 |
September | 9097.65 | 01-SEP-07:10 | 4482.40 | 21-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 | 22-SEP-15:50 | 24174.17 | 26-SEP-15:40 |
October | 9097.65 | 02-OCT-07:10 | 5080.05 | 27-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.27 | 08-OCT-16:00 | 18569.59 | 31-OCT-16:00 |
November | 9097.65 | 01-NOV-07:10 | 5080.05 | 03-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5356.17 | 27-NOV-02:55 | 20938.30 | 29-NOV-17:00 |
December | 9097.65 | 01-DEC-08:09 | 5080.05 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7620.26 | 14-DEC-12:00 | 29491.24 | 26-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2988.26 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 | 18569.59 | |||||
Maximum of Months | 9097.65 | 5080.05 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 30070.78 | 31721.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1691.27 | 21-JAN-08:07 | 5042.77 | 3135.58 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.24 |
February | 1653.75 | 18-FEB-08:07 | 5042.77 | 3109.61 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.89 |
March | 1408.20 | 02-MAR-08:07 | 5042.77 | 3064.15 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.08 |
April | 3272.81 | 27-APR-16:00 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 351.11 | 0.00 |
May | 4567.73 | 15-MAY-16:00 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 19516.59 | 24-JUN-07:03 | 6723.69 | 3787.60 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.82 |
July | 19164.89 | 01-JUL-07:02 | 8404.61 | 4983.22 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.36 |
August | 18769.83 | 19-AUG-07:03 | 6723.69 | 3854.92 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.35 |
September | 19704.54 | 16-SEP-07:02 | 8404.61 | 5169.20 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.71 |
October | 2723.85 | 04-OCT-15:00 | 1680.92 | 875.11 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
November | 1470.97 | 24-NOV-08:05 | 6723.69 | 4126.00 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.77 |
December | 1622.15 | 26-DEC-08:05 | 6723.69 | 4242.40 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2295.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1408.20 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19704.54 | 8404.61 | 5169.20 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 351.11 | 2295.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7225.71 | 06-JAN-10:10 | 7911.00 | 7982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.44 |
February | 4768.80 | 08-FEB-11:40 | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852.96 |
March | 4719.44 | 02-MAR-09:10 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.05 |
April | 4285.68 | 18-APR-09:30 | 3955.50 | 2540.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.84 |
May | 5373.80 | 08-MAY-07:03 | 11866.50 | 9605.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.29 |
June | 6621.46 | 28-JUN-15:00 | 3955.50 | 2177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.74 |
July | 34435.17 | 24-JUL-17:10 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.00 | 0.00 |
August | 34837.97 | 10-AUG-17:43 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.25 | 0.00 |
September | 5836.47 | 16-SEP-07:02 | 19777.50 | 19210.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2373.03 |
October | 4831.35 | 12-OCT-07:03 | 11866.50 | 11526.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2510.82 |
November | 4113.50 | 22-NOV-11:50 | 3955.50 | 3265.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.23 |
December | 4853.39 | 06-DEC-12:00 | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4113.50 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34837.97 | 19777.50 | 19210.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.25 | 2510.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1792.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10444.40 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4044.29 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7338.56 |
April | 0.00 | 01-APR-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5545.11 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12622.89 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4329.90 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5996.34 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8329.29 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10182.18 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6242.97 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7809.39 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4333.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4044.29 | |
Maximum of Months | 0.00 | 0.00 | 1792.96 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12622.89 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.351975E+11 | 28903.36 | 14-JAN-16:00 | 0.642571E+11 | 74762.61 | 14-JAN-20:10 |
February | 0.305206E+11 | 24135.02 | 06-FEB-15:00 | 0.452096E+11 | 110593.92 | 19-FEB-07:30 |
March | 0.325964E+11 | 23656.16 | 02-MAR-15:00 | 0.111545E+11 | 35885.83 | 24-MAR-06:10 |
April | 0.288839E+11 | 22320.22 | 19-APR-07:10 | 0.354932E+10 | 24916.10 | 11-APR-06:10 |
May | 0.287166E+11 | 22033.27 | 05-MAY-14:30 | 0.287912E+09 | 9489.62 | 24-MAY-06:10 |
June | 0.279853E+11 | 22908.84 | 28-JUN-15:00 | 36346695.25 | 5015.75 | 14-JUN-07:10 |
July | 0.289208E+11 | 27528.21 | 31-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.317343E+11 | 28023.62 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.299462E+11 | 23297.02 | 21-SEP-08:09 | 29979658.06 | 5238.75 | 28-SEP-07:10 |
October | 0.320934E+11 | 24159.02 | 27-OCT-08:09 | 0.221406E+10 | 22272.99 | 24-OCT-06:10 |
November | 0.328364E+11 | 28881.51 | 29-NOV-16:49 | 0.163026E+11 | 58441.48 | 29-NOV-17:00 |
December | 0.356116E+11 | 28900.14 | 26-DEC-16:19 | 0.453579E+11 | 67829.78 | 26-DEC-07:10 |
Annual Sum or Average | 0.375043E+12 | 0.188399E+12 | ||||
Minimum of Months | 0.279853E+11 | 22033.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.356116E+11 | 28903.36 | 0.642571E+11 | 110593.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.105559E+11 | 0.821896E+10 | 0.115358E+11 | 0.00 | 0.267374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221321E+10 | 0.00 |
February | 0.896670E+10 | 0.668548E+10 | 0.105871E+11 | 0.00 | 0.226453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201678E+10 | 0.00 |
March | 0.942895E+10 | 0.638992E+10 | 0.123431E+11 | 0.00 | 0.216381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227063E+10 | 0.00 |
April | 0.815312E+10 | 0.516802E+10 | 0.114862E+11 | 0.00 | 0.191000E+10 | 0.00 | 0.00 | 29393309.10 | 0.00 | 0.00 | 0.00 | 0.213714E+10 | 0.00 |
May | 0.805970E+10 | 0.451334E+10 | 0.119357E+11 | 0.00 | 0.195537E+10 | 0.00 | 0.00 | 74858646.55 | 0.00 | 0.00 | 0.00 | 0.217756E+10 | 0.00 |
June | 0.789363E+10 | 0.394404E+10 | 0.118862E+11 | 0.00 | 0.195537E+10 | 0.00 | 0.00 | 0.207897E+09 | 0.00 | 0.00 | 0.00 | 0.209822E+10 | 0.00 |
July | 0.812699E+10 | 0.424658E+10 | 0.115358E+11 | 0.00 | 0.189765E+10 | 0.00 | 0.00 | 0.102181E+10 | 0.00 | 0.00 | 0.00 | 0.209200E+10 | 0.00 |
August | 0.874222E+10 | 0.494048E+10 | 0.123357E+11 | 0.00 | 0.204641E+10 | 0.00 | 0.00 | 0.152973E+10 | 0.00 | 0.00 | 0.00 | 0.213977E+10 | 0.00 |
September | 0.859222E+10 | 0.574145E+10 | 0.114788E+11 | 0.00 | 0.188017E+10 | 0.00 | 0.00 | 0.201083E+09 | 0.00 | 0.00 | 0.00 | 0.205250E+10 | 0.00 |
October | 0.954303E+10 | 0.698312E+10 | 0.115432E+11 | 0.00 | 0.189266E+10 | 0.00 | 0.00 | 3310736.04 | 0.00 | 0.00 | 0.00 | 0.212817E+10 | 0.00 |
November | 0.996321E+10 | 0.767924E+10 | 0.110862E+11 | 0.00 | 0.202204E+10 | 0.00 | 0.00 | 14.70 | 0.00 | 0.00 | 0.00 | 0.208569E+10 | 0.00 |
December | 0.108950E+11 | 0.845953E+10 | 0.115358E+11 | 0.00 | 0.253036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219095E+10 | 0.00 |
Annual Sum or Average | 0.108921E+12 | 0.729702E+11 | 0.139290E+12 | 0.00 | 0.251921E+11 | 0.00 | 0.00 | 0.306808E+10 | 0.00 | 0.00 | 0.00 | 0.256026E+11 | 0.00 |
Minimum of Months | 0.789363E+10 | 0.394404E+10 | 0.105871E+11 | 0.00 | 0.188017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201678E+10 | 0.00 |
Maximum of Months | 0.108950E+11 | 0.845953E+10 | 0.123431E+11 | 0.00 | 0.267374E+10 | 0.00 | 0.00 | 0.152973E+10 | 0.00 | 0.00 | 0.00 | 0.227063E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.642571E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.452096E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.111545E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.354932E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.287912E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 36346695.25 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 29979658.06 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.221406E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.163026E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.453579E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188399E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.642571E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 10488.63 | 03-JAN-15:00 | 5492.60 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2407.57 | 07-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 10319.44 | 06-FEB-15:00 | 5492.60 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2418.08 | 18-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9885.85 | 02-MAR-15:00 | 5492.60 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2137.72 | 24-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8615.89 | 03-APR-07:10 | 5492.60 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2016.60 | 11-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7957.48 | 04-MAY-08:20 | 5492.60 | 01-MAY-19:19 | 10112.62 | 01-MAY-07:10 | 0.00 | 1899.16 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7521.77 | 29-JUN-07:10 | 5492.60 | 01-JUN-19:00 | 10112.62 | 01-JUN-07:10 | 0.00 | 1899.16 | 28-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 9624.11 | 12-JUL-08:09 | 5492.60 | 01-JUL-20:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 1899.16 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8609.90 | 02-AUG-07:30 | 5492.60 | 01-AUG-19:40 | 10112.62 | 01-AUG-07:10 | 0.00 | 1899.16 | 07-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 9623.48 | 21-SEP-08:09 | 5492.60 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 1899.16 | 02-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 10479.59 | 31-OCT-08:09 | 5492.60 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 1997.84 | 24-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10491.15 | 30-NOV-15:00 | 5492.60 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2342.84 | 29-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10492.52 | 16-DEC-15:00 | 5492.60 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2398.27 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7521.77 | 5492.60 | 10112.62 | 0.00 | 1899.16 | 0.00 | 0.00 | |||||
Maximum of Months | 10492.52 | 5492.60 | 10112.62 | 0.00 | 2418.08 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2308.15 | 26-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2319.71 | 11-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2304.69 | 01-MAR-12:00 | 0.00 |
April | 1092.65 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2210.50 | 01-APR-11:00 | 0.00 |
May | 1136.62 | 15-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2061.08 | 01-MAY-11:00 | 0.00 |
June | 3261.29 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1870.07 | 01-JUN-11:00 | 0.00 |
July | 6457.70 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1798.81 | 03-JUL-11:20 | 0.00 |
August | 7056.89 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1793.39 | 31-AUG-11:09 | 0.00 |
September | 2617.18 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 1801.00 | 28-SEP-11:39 | 0.00 |
October | 429.29 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1917.06 | 31-OCT-11:00 | 0.00 |
November | 0.02 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2091.27 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2234.73 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1793.39 | 0.00 | ||
Maximum of Months | 7056.89 | 0.00 | 0.00 | 0.00 | 2319.71 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28903.36 | 14-JAN-16:00 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 2295.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24135.02 | 06-FEB-15:00 | 10319.44 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23656.16 | 02-MAR-15:00 | 9885.85 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22320.22 | 19-APR-07:10 | 8580.79 | 10112.62 | 0.00 | 0.00 | 1983.66 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22033.27 | 05-MAY-14:30 | 7218.00 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 1021.23 | 0.00 |
June | 22908.84 | 28-JUN-15:00 | 6032.74 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 3261.29 | 0.00 |
July | 27528.21 | 31-JUL-15:00 | 7457.64 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 6457.70 | 0.00 |
August | 28023.62 | 10-AUG-15:00 | 7420.15 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 6990.61 | 0.00 |
September | 23297.02 | 21-SEP-08:09 | 9623.48 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24159.02 | 27-OCT-08:09 | 10478.86 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28881.51 | 29-NOV-16:49 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 2277.66 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28900.14 | 26-DEC-16:19 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 2293.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22033.27 | 6032.74 | 10112.62 | 0.00 | 0.00 | 1899.16 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28903.36 | 10478.86 | 10112.62 | 5492.60 | 0.00 | 2295.36 | 0.00 | 0.00 | 6990.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 74762.61 | 14-JAN-20:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 110593.92 | 19-FEB-07:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 35885.83 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 24916.10 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 9489.62 | 24-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5015.75 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5238.75 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 22272.99 | 24-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 58441.48 | 29-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 67829.78 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 110593.92 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 16.05 | 2.83 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
February | 3.33 | 16.50 | 2.50 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
March | 0.67 | 17.14 | 0.67 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
April | 0.50 | 17.21 | 0.50 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 17.17 | 1.17 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
December | 1.83 | 16.75 | 1.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
Annual Sum or Average | 12.83 | 16.47 | 9.17 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 17.21 | 2.83 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.00 | 14.85 | 3.50 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
February | 42.33 | 14.82 | 2.33 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
March | 9.33 | 14.96 | 0.83 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
April | 1.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
November | 9.67 | 14.95 | 1.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 32.67 | 14.91 | 2.83 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
Annual Sum or Average | 158.67 | 14.87 | 10.50 | 14.87 | 0.67 | 14.92 | 0.00 | 14.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.00 | 14.99 | 3.50 | 14.99 | 0.50 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
February | 276.00 | 20.75 | 269.00 | 20.73 | 269.00 | 20.73 |
March | 324.00 | 20.81 | 307.83 | 20.77 | 307.83 | 20.76 |
April | 300.00 | 21.30 | 202.33 | 21.04 | 202.33 | 20.92 |
May | 292.67 | 22.66 | 38.33 | 22.36 | 38.33 | 22.12 |
June | 211.00 | 23.22 | 23.00 | 23.23 | 3.83 | 23.18 |
July | 56.33 | 23.56 | 158.17 | 23.91 | 0.00 | 23.91 |
August | 39.17 | 23.48 | 211.33 | 23.96 | 0.50 | 23.96 |
September | 188.50 | 23.23 | 48.50 | 23.30 | 4.67 | 23.24 |
October | 300.00 | 21.50 | 168.00 | 21.18 | 168.00 | 21.02 |
November | 288.00 | 20.79 | 269.83 | 20.75 | 269.83 | 20.74 |
December | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
Annual Sum or Average | 2875.67 | 21.52 | 2296.33 | 21.43 | 1864.33 | 21.23 |
Minimum of Months | 39.17 | 20.72 | 23.00 | 20.72 | 0.00 | 20.72 |
Maximum of Months | 324.00 | 23.56 | 307.83 | 23.96 | 307.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.58 | 300.00 | 15.58 | 300.00 | 15.58 |
February | 276.00 | 15.92 | 276.00 | 15.92 | 276.00 | 15.92 |
March | 324.00 | 16.53 | 324.00 | 16.53 | 324.00 | 16.53 |
April | 297.17 | 18.01 | 266.00 | 17.77 | 266.00 | 17.69 |
May | 282.67 | 20.92 | 114.00 | 20.77 | 90.50 | 20.47 |
June | 190.17 | 22.10 | 106.17 | 23.04 | 15.50 | 22.88 |
July | 104.50 | 24.67 | 217.00 | 25.55 | 43.50 | 25.68 |
August | 112.67 | 25.28 | 259.50 | 25.69 | 70.00 | 25.85 |
September | 191.17 | 21.99 | 104.33 | 22.88 | 22.67 | 22.72 |
October | 300.00 | 18.32 | 248.50 | 17.99 | 248.50 | 17.87 |
November | 288.00 | 16.16 | 285.00 | 16.14 | 285.00 | 16.13 |
December | 300.00 | 15.64 | 300.00 | 15.64 | 300.00 | 15.64 |
Annual Sum or Average | 2966.33 | 18.33 | 2800.50 | 18.55 | 2241.67 | 18.14 |
Minimum of Months | 104.50 | 15.58 | 104.33 | 15.58 | 15.50 | 15.58 |
Maximum of Months | 324.00 | 25.28 | 324.00 | 25.69 | 324.00 | 25.85 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.39 | 300.00 | 10.39 | 300.00 | 10.39 |
February | 276.00 | 11.08 | 276.00 | 11.08 | 276.00 | 11.08 |
March | 324.00 | 12.96 | 324.00 | 12.96 | 324.00 | 12.96 |
April | 300.00 | 14.97 | 300.00 | 14.97 | 300.00 | 14.97 |
May | 312.00 | 19.03 | 263.67 | 18.83 | 263.67 | 18.76 |
June | 301.83 | 21.00 | 121.67 | 20.58 | 117.83 | 20.31 |
July | 156.33 | 22.88 | 108.33 | 24.01 | 6.67 | 24.10 |
August | 76.67 | 24.08 | 222.00 | 25.27 | 17.17 | 25.40 |
September | 228.67 | 22.27 | 64.00 | 22.53 | 18.50 | 22.36 |
October | 300.00 | 17.00 | 286.83 | 16.91 | 286.83 | 16.88 |
November | 288.00 | 12.75 | 288.00 | 12.75 | 288.00 | 12.75 |
December | 300.00 | 10.72 | 300.00 | 10.72 | 300.00 | 10.72 |
Annual Sum or Average | 3163.50 | 15.69 | 2854.50 | 15.53 | 2498.67 | 15.06 |
Minimum of Months | 76.67 | 10.39 | 64.00 | 10.39 | 6.67 | 10.39 |
Maximum of Months | 324.00 | 24.08 | 324.00 | 25.27 | 324.00 | 25.40 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.135344E+09 | 29393309.10 | 15.67 | 0.130319E+09 | 5025731.03 | 0.00 | 0.61 | 27-APR-16:00 | 0.00 | 01-APR-00:10 | 5082.75 | 27-APR-16:00 | 4759.83 | 27-APR-16:00 | 323.48 | 27-APR-15:50 | 1092.65 | 27-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.360437E+09 | 74858646.55 | 36.50 | 0.328006E+09 | 32431121.36 | 0.00 | 0.69 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 | 5647.36 | 15-MAY-16:00 | 5647.36 | 15-MAY-16:00 | 1055.48 | 06-MAY-13:00 | 1136.62 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.840984E+09 | 0.174017E+09 | 81.38 | 0.815028E+09 | 25955850.35 | 0.00 | 1.00 | 24-JUN-07:03 | 0.00 | 01-JUN-00:10 | 15044.64 | 24-JUN-07:03 | 12232.45 | 24-JUN-07:03 | 2812.18 | 24-JUN-07:03 | 3027.59 | 24-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.264716E+10 | 0.538639E+09 | 159.10 | 0.231930E+10 | 0.327858E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 16953.07 | 31-JUL-07:02 | 12750.21 | 08-JUL-07:02 | 5841.26 | 15-JUL-07:02 | 3397.25 | 31-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.371778E+10 | 0.761886E+09 | 203.22 | 0.322789E+10 | 0.489889E+09 | 0.00 | 1.00 | 07-AUG-16:00 | 0.00 | 01-AUG-00:10 | 17020.86 | 10-AUG-07:02 | 13453.27 | 09-AUG-07:03 | 6570.13 | 26-AUG-07:02 | 3409.03 | 10-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.897447E+09 | 0.182454E+09 | 69.57 | 0.754379E+09 | 0.143068E+09 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 15354.36 | 02-SEP-07:02 | 10966.36 | 02-SEP-07:02 | 5736.53 | 16-SEP-07:02 | 3092.80 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 15239464.57 | 3310736.04 | 5.33 | 15239463.53 | 1.03 | 0.00 | 0.27 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1995.97 | 04-OCT-15:00 | 1995.97 | 04-OCT-15:00 | 0.00 | 07-OCT-16:50 | 429.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 66.15 | 14.70 | 0.17 | 50.85 | 15.31 | 0.00 | 0.00 | 04-NOV-15:00 | 0.00 | 01-NOV-00:05 | 0.11 | 04-NOV-15:00 | 0.08 | 04-NOV-15:00 | 0.03 | 04-NOV-15:00 | 0.02 | 04-NOV-15:00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.861439E+10 | 0.176456E+10 | 570.93 | 0.759016E+10 | 0.102423E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.371778E+10 | 0.761886E+09 | 203.22 | 0.322789E+10 | 0.489889E+09 | 0.00 | 1.00 | 0.00 | 17020.86 | 13453.27 | 6570.13 | 3409.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.131717E+09 | 33879923.27 | 13.50 | 0.126650E+09 | 5066731.69 | 0.00 | 0.38 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6789.95 | 28-JUN-15:00 | 6789.95 | 28-JUN-15:00 | 327.41 | 28-JUN-13:10 | 1737.52 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.196459E+10 | 0.483171E+09 | 76.28 | 0.171722E+10 | 0.247365E+09 | 0.00 | 1.00 | 20-JUL-17:20 | 0.00 | 01-JUL-00:10 | 43423.68 | 27-JUL-18:05 | 39681.57 | 23-JUL-13:25 | 10927.01 | 27-JUL-18:05 | 9802.02 | 31-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.307468E+10 | 0.767843E+09 | 95.21 | 0.267330E+10 | 0.401387E+09 | 0.00 | 1.00 | 08-AUG-17:10 | 0.00 | 01-AUG-00:10 | 42148.03 | 13-AUG-12:43 | 39880.99 | 08-AUG-18:45 | 7551.51 | 13-AUG-10:35 | 10002.98 | 10-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 73222913.76 | 18628673.28 | 10.50 | 57397756.65 | 15825157.11 | 0.00 | 0.23 | 14-SEP-15:00 | 0.00 | 01-SEP-00:10 | 4269.20 | 14-SEP-15:00 | 3356.00 | 14-SEP-15:00 | 941.26 | 14-SEP-14:20 | 1068.84 | 14-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.524421E+10 | 0.130352E+10 | 195.49 | 0.457457E+10 | 0.669643E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.307468E+10 | 0.767843E+09 | 95.21 | 0.267330E+10 | 0.401387E+09 | 0.00 | 1.00 | 0.00 | 43423.68 | 39880.99 | 10927.01 | 10002.98 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 10.42 | 24.67 | 18.04 | 98.76 | 0.00 | 0.00 | 0.00 |
February | 62.33 | 23.21 | 39.11 | 51.47 | 83.92 | 0.00 | 0.00 | 0.00 |
March | 87.79 | 29.66 | 58.13 | 85.87 | 65.43 | 0.00 | 0.00 | 0.00 |
April | 133.27 | 50.85 | 82.42 | 151.04 | 53.56 | 0.00 | 0.00 | 0.00 |
May | 171.90 | 69.91 | 101.99 | 201.37 | 53.75 | 0.00 | 0.00 | 0.00 |
June | 165.27 | 64.18 | 101.09 | 192.76 | 46.69 | 0.00 | 0.00 | 0.00 |
July | 204.53 | 107.67 | 96.86 | 254.92 | 48.64 | 0.00 | 0.00 | 0.00 |
August | 168.84 | 86.12 | 82.72 | 212.83 | 48.95 | 0.00 | 0.00 | 0.00 |
September | 138.01 | 66.39 | 71.61 | 162.66 | 61.35 | 0.00 | 0.00 | 0.00 |
October | 78.59 | 32.15 | 46.44 | 81.25 | 62.59 | 0.00 | 0.00 | 0.00 |
November | 39.11 | 11.14 | 27.97 | 27.27 | 75.14 | 0.00 | 0.00 | 0.00 |
December | 33.18 | 11.64 | 21.54 | 21.26 | 99.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 110.12 | 47.13 | 62.99 | 122.18 | 66.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.18 | 10.42 | 21.54 | 18.04 | 46.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.53 | 107.67 | 101.99 | 254.92 | 99.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 10.42 | 24.67 | 18.04 | 98.76 | 0.00 | 0.00 | 0.00 |
February | 62.33 | 23.21 | 39.11 | 51.47 | 83.92 | 0.00 | 0.00 | 0.00 |
March | 87.79 | 29.66 | 58.13 | 85.87 | 65.43 | 0.00 | 0.00 | 0.00 |
April | 133.27 | 50.85 | 82.42 | 151.04 | 53.56 | 0.00 | 0.00 | 0.00 |
May | 171.90 | 69.91 | 101.99 | 201.37 | 53.75 | 0.00 | 0.00 | 0.00 |
June | 165.27 | 64.18 | 101.09 | 192.76 | 46.69 | 0.00 | 0.00 | 0.00 |
July | 204.53 | 107.67 | 96.86 | 254.92 | 48.64 | 0.00 | 0.00 | 0.00 |
August | 168.84 | 86.12 | 82.72 | 212.83 | 48.95 | 0.00 | 0.00 | 0.00 |
September | 138.01 | 66.39 | 71.61 | 162.66 | 61.35 | 0.00 | 0.00 | 0.00 |
October | 78.59 | 32.15 | 46.44 | 81.25 | 62.59 | 0.00 | 0.00 | 0.00 |
November | 39.11 | 11.14 | 27.97 | 27.27 | 75.14 | 0.00 | 0.00 | 0.00 |
December | 33.18 | 11.64 | 21.54 | 21.26 | 99.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 110.12 | 47.13 | 62.99 | 122.18 | 66.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.18 | 10.42 | 21.54 | 18.04 | 46.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.53 | 107.67 | 101.99 | 254.92 | 99.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.02 | 0.00 | 12.02 | 1.03 | 60.65 | 0.00 | 0.00 | 0.00 |
February | 18.70 | 0.00 | 18.70 | 6.16 | 51.45 | 0.00 | 0.00 | 0.00 |
March | 27.56 | 0.00 | 27.56 | 16.63 | 39.21 | 0.00 | 0.00 | 0.00 |
April | 39.06 | 0.19 | 38.87 | 32.70 | 30.96 | 0.00 | 0.00 | 0.00 |
May | 50.16 | 1.47 | 48.69 | 45.64 | 30.33 | 0.00 | 0.00 | 0.00 |
June | 52.76 | 3.47 | 49.29 | 49.67 | 25.79 | 0.00 | 0.00 | 0.00 |
July | 50.19 | 3.95 | 46.24 | 49.53 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 40.77 | 1.24 | 39.53 | 40.79 | 27.08 | 0.00 | 0.00 | 0.00 |
September | 31.55 | 0.02 | 31.53 | 24.53 | 36.34 | 0.00 | 0.00 | 0.00 |
October | 21.61 | 0.00 | 21.61 | 13.19 | 37.31 | 0.00 | 0.00 | 0.00 |
November | 13.61 | 0.00 | 13.61 | 3.80 | 45.38 | 0.00 | 0.00 | 0.00 |
December | 10.21 | 0.00 | 10.21 | 0.71 | 60.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.74 | 0.87 | 29.87 | 23.80 | 39.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.21 | 0.00 | 10.21 | 0.71 | 25.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.76 | 3.95 | 49.29 | 49.67 | 60.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.02 | 0.00 | 12.02 | 1.03 | 60.65 | 0.00 | 0.00 | 0.00 |
February | 18.70 | 0.00 | 18.70 | 6.16 | 51.45 | 0.00 | 0.00 | 0.00 |
March | 27.56 | 0.00 | 27.56 | 16.63 | 39.21 | 0.00 | 0.00 | 0.00 |
April | 39.06 | 0.19 | 38.87 | 32.70 | 30.96 | 0.00 | 0.00 | 0.00 |
May | 50.15 | 1.47 | 48.69 | 45.64 | 30.33 | 0.00 | 0.00 | 0.00 |
June | 52.76 | 3.47 | 49.29 | 49.67 | 25.79 | 0.00 | 0.00 | 0.00 |
July | 50.19 | 3.95 | 46.24 | 49.53 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 40.77 | 1.24 | 39.53 | 40.79 | 27.08 | 0.00 | 0.00 | 0.00 |
September | 31.55 | 0.02 | 31.53 | 24.53 | 36.34 | 0.00 | 0.00 | 0.00 |
October | 21.60 | 0.00 | 21.60 | 13.19 | 37.31 | 0.00 | 0.00 | 0.00 |
November | 13.61 | 0.00 | 13.61 | 3.80 | 45.38 | 0.00 | 0.00 | 0.00 |
December | 10.21 | 0.00 | 10.21 | 0.71 | 60.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.74 | 0.87 | 29.87 | 23.80 | 39.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.21 | 0.00 | 10.21 | 0.71 | 25.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.76 | 3.95 | 49.29 | 49.67 | 60.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 15.37 | 47.04 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 38.22 | 41.69 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 75.64 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 129.20 | 27.45 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 168.20 | 28.30 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 183.47 | 25.75 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 194.74 | 27.81 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.72 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.61 | 34.30 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 60.44 | 32.25 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 23.73 | 35.32 | 8.67 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 13.58 | 47.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 97.50 | 34.06 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 13.58 | 25.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 194.74 | 47.57 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 21.26 | 30.44 | 10.50 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 45.27 | 27.68 | 34.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 82.31 | 23.87 | 8.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 136.45 | 21.11 | 0.83 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 174.37 | 23.89 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 190.08 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 199.41 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 158.85 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 108.03 | 34.02 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 62.82 | 29.45 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 28.15 | 24.91 | 31.50 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.73 | 30.47 | 34.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 102.46 | 26.71 | 120.33 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.73 | 21.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 199.41 | 34.02 | 34.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93962435.22 | 27899184.65 | 66063250.57 | 48313006.27 | 0.264524E+09 |
February | 0.150779E+09 | 56160404.07 | 94618428.74 | 0.124525E+09 | 0.203017E+09 |
March | 0.235144E+09 | 79445444.68 | 0.155699E+09 | 0.229993E+09 | 0.175237E+09 |
April | 0.345440E+09 | 0.131806E+09 | 0.213634E+09 | 0.391503E+09 | 0.138824E+09 |
May | 0.460427E+09 | 0.187257E+09 | 0.273170E+09 | 0.539344E+09 | 0.143954E+09 |
June | 0.428390E+09 | 0.166356E+09 | 0.262034E+09 | 0.499632E+09 | 0.121019E+09 |
July | 0.547813E+09 | 0.288381E+09 | 0.259432E+09 | 0.682771E+09 | 0.130287E+09 |
August | 0.452220E+09 | 0.230667E+09 | 0.221553E+09 | 0.570037E+09 | 0.131105E+09 |
September | 0.357712E+09 | 0.172092E+09 | 0.185620E+09 | 0.421622E+09 | 0.159021E+09 |
October | 0.210502E+09 | 86116027.52 | 0.124386E+09 | 0.217622E+09 | 0.167644E+09 |
November | 0.101362E+09 | 28874304.36 | 72488011.09 | 70671648.52 | 0.194767E+09 |
December | 88862112.56 | 31170525.27 | 57691587.29 | 56935346.29 | 0.267104E+09 |
Annual Sum or Average | 0.347261E+10 | 0.148622E+10 | 0.198639E+10 | 0.385297E+10 | 0.209650E+10 |
Minimum of Months | 88862112.56 | 27899184.65 | 57691587.29 | 48313006.27 | 0.121019E+09 |
Maximum of Months | 0.547813E+09 | 0.288381E+09 | 0.273170E+09 | 0.682771E+09 | 0.267104E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93962435.22 | 27899184.65 | 66063250.57 | 48313006.27 | 0.264524E+09 |
February | 0.150779E+09 | 56160404.07 | 94618428.74 | 0.124525E+09 | 0.203017E+09 |
March | 0.235144E+09 | 79445444.68 | 0.155699E+09 | 0.229993E+09 | 0.175237E+09 |
April | 0.345440E+09 | 0.131806E+09 | 0.213634E+09 | 0.391503E+09 | 0.138824E+09 |
May | 0.460427E+09 | 0.187257E+09 | 0.273170E+09 | 0.539344E+09 | 0.143954E+09 |
June | 0.428390E+09 | 0.166356E+09 | 0.262034E+09 | 0.499632E+09 | 0.121019E+09 |
July | 0.547813E+09 | 0.288381E+09 | 0.259432E+09 | 0.682771E+09 | 0.130287E+09 |
August | 0.452220E+09 | 0.230667E+09 | 0.221553E+09 | 0.570037E+09 | 0.131105E+09 |
September | 0.357712E+09 | 0.172092E+09 | 0.185620E+09 | 0.421622E+09 | 0.159021E+09 |
October | 0.210502E+09 | 86116027.52 | 0.124386E+09 | 0.217622E+09 | 0.167644E+09 |
November | 0.101362E+09 | 28874304.36 | 72488011.09 | 70671648.52 | 0.194767E+09 |
December | 88862112.56 | 31170525.27 | 57691587.29 | 56935346.29 | 0.267104E+09 |
Annual Sum or Average | 0.347261E+10 | 0.148622E+10 | 0.198639E+10 | 0.385297E+10 | 0.209650E+10 |
Minimum of Months | 88862112.56 | 27899184.65 | 57691587.29 | 48313006.27 | 0.121019E+09 |
Maximum of Months | 0.547813E+09 | 0.288381E+09 | 0.273170E+09 | 0.682771E+09 | 0.267104E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32195724.94 | 0.00 | 32195724.94 | 2768168.60 | 0.162440E+09 |
February | 45249296.56 | 0.00 | 45249296.56 | 14900429.31 | 0.124460E+09 |
March | 73821286.49 | 1472.31 | 73819814.18 | 44537308.57 | 0.105014E+09 |
April | 0.101248E+09 | 490444.32 | 0.100757E+09 | 84761436.25 | 80236024.85 |
May | 0.134339E+09 | 3928001.28 | 0.130411E+09 | 0.122251E+09 | 81240720.03 |
June | 0.136761E+09 | 8998905.24 | 0.127762E+09 | 0.128743E+09 | 66844561.39 |
July | 0.134430E+09 | 10580536.41 | 0.123849E+09 | 0.132660E+09 | 71658171.40 |
August | 0.109200E+09 | 3330241.48 | 0.105870E+09 | 0.109243E+09 | 72530153.76 |
September | 81775968.37 | 52935.53 | 81723032.83 | 63586071.41 | 94198414.28 |
October | 57867268.17 | 0.00 | 57867268.17 | 35333731.37 | 99927911.02 |
November | 35274819.75 | 0.00 | 35274819.75 | 9847054.06 | 0.117616E+09 |
December | 27358063.69 | 0.00 | 27358063.69 | 1911036.45 | 0.161248E+09 |
Annual Sum or Average | 0.969520E+09 | 27382536.57 | 0.942138E+09 | 0.750542E+09 | 0.123741E+10 |
Minimum of Months | 27358063.69 | 0.00 | 27358063.69 | 1911036.45 | 66844561.39 |
Maximum of Months | 0.136761E+09 | 10580536.41 | 0.130411E+09 | 0.132660E+09 | 0.162440E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32194597.66 | 0.00 | 32194597.66 | 2767753.87 | 0.162440E+09 |
February | 45247787.43 | 0.00 | 45247787.43 | 14899199.39 | 0.124460E+09 |
March | 73818890.12 | 1472.24 | 73817417.88 | 44534823.73 | 0.105014E+09 |
April | 0.101245E+09 | 490421.33 | 0.100754E+09 | 84757786.04 | 80235803.27 |
May | 0.134335E+09 | 3927817.17 | 0.130407E+09 | 0.122245E+09 | 81240486.92 |
June | 0.136757E+09 | 8998483.44 | 0.127758E+09 | 0.128738E+09 | 66844344.51 |
July | 0.134426E+09 | 10580040.49 | 0.123846E+09 | 0.132655E+09 | 71657935.30 |
August | 0.109197E+09 | 3330085.39 | 0.105867E+09 | 0.109239E+09 | 72529811.95 |
September | 81773496.92 | 52933.05 | 81720563.86 | 63583300.35 | 94197965.72 |
October | 57865420.78 | 0.00 | 57865420.78 | 35331803.92 | 99927463.37 |
November | 35273593.76 | 0.00 | 35273593.76 | 9846147.81 | 0.117616E+09 |
December | 27357119.54 | 0.00 | 27357119.54 | 1910763.10 | 0.161248E+09 |
Annual Sum or Average | 0.969490E+09 | 27381253.11 | 0.942109E+09 | 0.750509E+09 | 0.123741E+10 |
Minimum of Months | 27357119.54 | 0.00 | 27357119.54 | 1910763.10 | 66844344.51 |
Maximum of Months | 0.136757E+09 | 10580040.49 | 0.130407E+09 | 0.132655E+09 | 0.162440E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 41168560.87 | 0.126002E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 92460761.26 | 0.100847E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.202603E+09 | 87386199.40 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.334880E+09 | 71142157.05 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.450505E+09 | 75798927.96 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.475558E+09 | 66756037.48 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.521591E+09 | 74488933.26 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419763E+09 | 77466117.85 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.276331E+09 | 88918008.53 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.161892E+09 | 86366562.35 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 61509508.44 | 91536765.96 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 36385482.64 | 0.127422E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.307465E+10 | 0.107413E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 36385482.64 | 66756037.48 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.521591E+09 | 0.127422E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56947491.09 | 81527915.10 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.109521E+09 | 66953439.97 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.220450E+09 | 63937641.13 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.353668E+09 | 54720349.50 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.467038E+09 | 63981731.82 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.492680E+09 | 56093040.94 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.534107E+09 | 66759187.20 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.425474E+09 | 75193264.84 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.280007E+09 | 88169070.79 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.168260E+09 | 78872994.83 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 72960971.21 | 64568083.44 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 50167715.83 | 81603827.32 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.323128E+10 | 0.842381E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 50167715.83 | 54720349.50 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.534107E+09 | 88169070.79 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.72 | 314.40 | 94.20 | 20.83 | 73.37 | 0.00 | 0.00 |
February | 112.08 | 267.55 | 162.06 | 46.43 | 115.63 | 0.00 | 0.00 |
March | 203.25 | 207.52 | 230.71 | 59.32 | 171.38 | 0.00 | 0.00 |
April | 366.82 | 168.36 | 344.67 | 102.08 | 242.58 | 0.00 | 0.00 |
May | 492.63 | 166.76 | 444.12 | 142.76 | 301.36 | 0.00 | 0.00 |
June | 482.44 | 142.54 | 436.07 | 135.30 | 300.77 | 0.00 | 0.00 |
July | 606.39 | 148.29 | 509.44 | 223.24 | 286.20 | 0.00 | 0.00 |
August | 506.25 | 151.08 | 419.22 | 174.73 | 244.49 | 0.00 | 0.00 |
September | 373.22 | 194.21 | 339.11 | 132.83 | 206.28 | 0.00 | 0.00 |
October | 187.31 | 198.23 | 200.39 | 64.30 | 136.09 | 0.00 | 0.00 |
November | 60.04 | 238.95 | 105.43 | 22.28 | 83.15 | 0.00 | 0.00 |
December | 40.54 | 316.46 | 86.78 | 23.28 | 63.51 | 0.00 | 0.00 |
Annual Sum or Average | 289.83 | 209.31 | 281.72 | 95.99 | 185.72 | 0.00 | 0.00 |
Minimum of Months | 33.72 | 142.54 | 86.78 | 20.83 | 63.51 | 0.00 | 0.00 |
Maximum of Months | 606.39 | 316.46 | 509.44 | 223.24 | 301.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.19 | 658.61 | 325.08 | 72.96 | 252.12 | 0.00 | 0.00 |
February | 535.07 | 583.60 | 580.18 | 205.89 | 374.29 | 0.00 | 0.00 |
March | 1059.01 | 456.77 | 988.85 | 428.66 | 560.20 | 0.00 | 0.00 |
April | 1808.77 | 384.26 | 1557.53 | 790.65 | 766.87 | 0.00 | 0.00 |
May | 2354.79 | 396.20 | 2010.83 | 1028.09 | 982.74 | 0.00 | 0.00 |
June | 2568.60 | 360.57 | 2195.80 | 1276.76 | 919.04 | 0.00 | 0.00 |
July | 2726.35 | 389.35 | 2291.44 | 1503.01 | 788.44 | 0.00 | 0.00 |
August | 2194.10 | 404.92 | 1848.48 | 1171.59 | 676.89 | 0.00 | 0.00 |
September | 1492.53 | 480.27 | 1315.02 | 733.30 | 581.73 | 0.00 | 0.00 |
October | 846.21 | 451.44 | 788.22 | 376.47 | 411.75 | 0.00 | 0.00 |
November | 332.23 | 494.41 | 388.19 | 103.95 | 284.24 | 0.00 | 0.00 |
December | 190.19 | 666.04 | 283.85 | 78.43 | 205.42 | 0.00 | 0.00 |
Annual Sum or Average | 1364.95 | 476.85 | 1218.03 | 650.25 | 567.78 | 0.00 | 0.00 |
Minimum of Months | 190.19 | 360.57 | 283.85 | 72.96 | 205.42 | 0.00 | 0.00 |
Maximum of Months | 2726.35 | 666.04 | 2291.44 | 1503.01 | 982.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3142.69 | 5801.25 | 743.04 | 166.77 | 576.26 | 0.00 | 0.00 |
February | 6265.64 | 5123.14 | 1326.12 | 470.60 | 855.52 | 0.00 | 0.00 |
March | 10522.05 | 3515.37 | 2260.24 | 979.78 | 1280.45 | 0.00 | 0.00 |
April | 17817.01 | 2369.92 | 3560.06 | 1807.21 | 1752.85 | 0.00 | 0.00 |
May | 24713.50 | 2300.24 | 4596.19 | 2349.93 | 2246.26 | 0.00 | 0.00 |
June | 24594.68 | 2078.82 | 5018.97 | 2918.31 | 2100.66 | 0.00 | 0.00 |
July | 24311.87 | 2398.29 | 5237.59 | 3435.45 | 1802.14 | 0.00 | 0.00 |
August | 19297.05 | 2716.08 | 4225.10 | 2677.91 | 1547.19 | 0.00 | 0.00 |
September | 13682.39 | 3345.50 | 3005.77 | 1676.11 | 1329.66 | 0.00 | 0.00 |
October | 8412.08 | 3152.48 | 1801.64 | 860.49 | 941.14 | 0.00 | 0.00 |
November | 3600.67 | 3967.38 | 887.28 | 237.60 | 649.69 | 0.00 | 0.00 |
December | 2570.82 | 5446.53 | 648.80 | 179.26 | 469.54 | 0.00 | 0.00 |
Annual Sum or Average | 13283.16 | 3511.05 | 2784.06 | 1486.28 | 1297.79 | 0.00 | 0.00 |
Minimum of Months | 2570.82 | 2078.82 | 648.80 | 166.77 | 469.54 | 0.00 | 0.00 |
Maximum of Months | 24713.50 | 5801.25 | 5237.59 | 3435.45 | 2246.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 90318892.66 | 0.842085E+09 | 0.252315E+09 | 55798369.30 | 0.196517E+09 | 0.00 | 0.00 |
February | 0.271147E+09 | 0.647250E+09 | 0.392055E+09 | 0.112321E+09 | 0.279734E+09 | 0.00 | 0.00 |
March | 0.544378E+09 | 0.555820E+09 | 0.617929E+09 | 0.158894E+09 | 0.459035E+09 | 0.00 | 0.00 |
April | 0.950802E+09 | 0.436397E+09 | 0.893373E+09 | 0.264593E+09 | 0.628780E+09 | 0.00 | 0.00 |
May | 0.131945E+10 | 0.446656E+09 | 0.118953E+10 | 0.382369E+09 | 0.807157E+09 | 0.00 | 0.00 |
June | 0.125048E+10 | 0.369463E+09 | 0.113030E+10 | 0.350709E+09 | 0.779589E+09 | 0.00 | 0.00 |
July | 0.162416E+10 | 0.397192E+09 | 0.136448E+10 | 0.597922E+09 | 0.766559E+09 | 0.00 | 0.00 |
August | 0.135594E+10 | 0.404651E+09 | 0.112284E+10 | 0.467995E+09 | 0.654842E+09 | 0.00 | 0.00 |
September | 0.967377E+09 | 0.503403E+09 | 0.878973E+09 | 0.344290E+09 | 0.534683E+09 | 0.00 | 0.00 |
October | 0.501696E+09 | 0.530930E+09 | 0.536736E+09 | 0.172232E+09 | 0.364504E+09 | 0.00 | 0.00 |
November | 0.155632E+09 | 0.619361E+09 | 0.273273E+09 | 57748608.72 | 0.215524E+09 | 0.00 | 0.00 |
December | 0.108582E+09 | 0.847594E+09 | 0.232439E+09 | 62341050.53 | 0.170098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.913996E+10 | 0.660080E+10 | 0.888424E+10 | 0.302721E+10 | 0.585702E+10 | 0.00 | 0.00 |
Minimum of Months | 90318892.66 | 0.369463E+09 | 0.232439E+09 | 55798369.30 | 0.170098E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162416E+10 | 0.847594E+09 | 0.136448E+10 | 0.597922E+09 | 0.807157E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.576360E+09 | 0.176403E+10 | 0.870689E+09 | 0.195424E+09 | 0.675265E+09 | 0.00 | 0.00 |
February | 0.129445E+10 | 0.141186E+10 | 0.140356E+10 | 0.498082E+09 | 0.905479E+09 | 0.00 | 0.00 |
March | 0.283645E+10 | 0.122341E+10 | 0.264854E+10 | 0.114811E+10 | 0.150043E+10 | 0.00 | 0.00 |
April | 0.468832E+10 | 0.995990E+09 | 0.403711E+10 | 0.204937E+10 | 0.198773E+10 | 0.00 | 0.00 |
May | 0.630708E+10 | 0.106118E+10 | 0.538581E+10 | 0.275364E+10 | 0.263217E+10 | 0.00 | 0.00 |
June | 0.665781E+10 | 0.934585E+09 | 0.569151E+10 | 0.330937E+10 | 0.238214E+10 | 0.00 | 0.00 |
July | 0.730227E+10 | 0.104285E+10 | 0.613740E+10 | 0.402566E+10 | 0.211175E+10 | 0.00 | 0.00 |
August | 0.587669E+10 | 0.108453E+10 | 0.495098E+10 | 0.313798E+10 | 0.181300E+10 | 0.00 | 0.00 |
September | 0.386864E+10 | 0.124485E+10 | 0.340854E+10 | 0.190070E+10 | 0.150783E+10 | 0.00 | 0.00 |
October | 0.226649E+10 | 0.120913E+10 | 0.211116E+10 | 0.100833E+10 | 0.110283E+10 | 0.00 | 0.00 |
November | 0.861133E+09 | 0.128151E+10 | 0.100618E+10 | 0.269433E+09 | 0.736748E+09 | 0.00 | 0.00 |
December | 0.509397E+09 | 0.178391E+10 | 0.760259E+09 | 0.210054E+09 | 0.550205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.430451E+11 | 0.150378E+11 | 0.384117E+11 | 0.205062E+11 | 0.179056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.509397E+09 | 0.934585E+09 | 0.760259E+09 | 0.195424E+09 | 0.550205E+09 | 0.00 | 0.00 |
Maximum of Months | 0.730227E+10 | 0.178391E+10 | 0.613740E+10 | 0.402566E+10 | 0.263217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.841738E+10 | 0.155381E+11 | 0.199015E+10 | 0.446683E+09 | 0.154346E+10 | 0.00 | 0.00 |
February | 0.151578E+11 | 0.123939E+11 | 0.320814E+10 | 0.113847E+10 | 0.206967E+10 | 0.00 | 0.00 |
March | 0.281823E+11 | 0.941558E+10 | 0.605381E+10 | 0.262425E+10 | 0.342956E+10 | 0.00 | 0.00 |
April | 0.461817E+11 | 0.614283E+10 | 0.922768E+10 | 0.468428E+10 | 0.454339E+10 | 0.00 | 0.00 |
May | 0.661926E+11 | 0.616096E+10 | 0.123104E+11 | 0.629404E+10 | 0.601639E+10 | 0.00 | 0.00 |
June | 0.637494E+11 | 0.538831E+10 | 0.130092E+11 | 0.756427E+10 | 0.544490E+10 | 0.00 | 0.00 |
July | 0.651169E+11 | 0.642358E+10 | 0.140284E+11 | 0.920151E+10 | 0.482685E+10 | 0.00 | 0.00 |
August | 0.516852E+11 | 0.727474E+10 | 0.113165E+11 | 0.717253E+10 | 0.414399E+10 | 0.00 | 0.00 |
September | 0.354648E+11 | 0.867154E+10 | 0.779094E+10 | 0.434446E+10 | 0.344648E+10 | 0.00 | 0.00 |
October | 0.225309E+11 | 0.844359E+10 | 0.482550E+10 | 0.230475E+10 | 0.252076E+10 | 0.00 | 0.00 |
November | 0.933293E+10 | 0.102835E+11 | 0.229984E+10 | 0.615848E+09 | 0.168399E+10 | 0.00 | 0.00 |
December | 0.688569E+10 | 0.145880E+11 | 0.173773E+10 | 0.480123E+09 | 0.125761E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.418898E+12 | 0.110725E+12 | 0.877983E+11 | 0.468712E+11 | 0.409271E+11 | 0.00 | 0.00 |
Minimum of Months | 0.688569E+10 | 0.538831E+10 | 0.173773E+10 | 0.446683E+09 | 0.125761E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661926E+11 | 0.155381E+11 | 0.140284E+11 | 0.920151E+10 | 0.601639E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.919574E+09 | -848751780.4 | 0.00 | 0.00 | 744.00 | 0.00 | -70822142.1 | 58.99 | 0.00 | 0.00 |
February | 0.848692E+09 | -785126550.0 | 0.00 | 0.00 | 672.00 | 0.00 | -63565088.7 | 58.99 | 0.00 | 0.00 |
March | 0.976541E+09 | -907214835.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69325984.3 | 58.99 | 0.00 | 0.00 |
April | 0.884995E+09 | -819648947.8 | 0.00 | 0.00 | 720.00 | 0.00 | -65345711.5 | 58.99 | 0.00 | 0.00 |
May | 0.884276E+09 | -820647805.8 | 0.00 | 0.00 | 744.00 | 0.00 | -63627696.0 | 59.00 | 0.00 | 0.00 |
June | 0.845985E+09 | -786758552.5 | 0.00 | 0.00 | 720.00 | 0.00 | -59226310.8 | 59.00 | 0.00 | 0.00 |
July | 0.798243E+09 | -739285155.5 | 0.00 | 0.00 | 744.00 | 0.00 | -58957432.7 | 58.99 | 0.00 | 0.00 |
August | 0.846124E+09 | -787236725.3 | 0.00 | 0.00 | 744.00 | 0.00 | -58887624.7 | 59.00 | 0.00 | 0.00 |
September | 0.800629E+09 | -741744964.4 | 0.00 | 0.00 | 720.00 | 0.00 | -58884247.8 | 58.99 | 0.00 | 0.00 |
October | 0.833963E+09 | -767150509.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66812545.2 | 59.00 | 0.00 | 0.00 |
November | 0.833601E+09 | -766227359.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67373140.9 | 58.99 | 0.00 | 0.00 |
December | 0.897688E+09 | -827214919.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70472968.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.103703E+11 | -0.959701E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -773300893.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.798243E+09 | -907214835.9 | 0.00 | 0.00 | 672.00 | 0.00 | -70822142.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.976541E+09 | -739285155.5 | 0.00 | 0.00 | 744.00 | 0.00 | -58884247.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.89 | 0.58 | 31-JAN-12:09 | 141.25 | 0.00 | 0.00 | 0.50 | 107.93 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.82 | 0.50 | 13-FEB-11:50 | 181.41 | 0.00 | 0.00 | 30.33 | 450.09 | 0.00 | 0.00 | 25.00 |
March | 247.00 | 0.75 | 0.50 | 04-MAR-11:00 | 255.01 | 0.00 | 0.00 | 91.50 | 297.35 | 0.00 | 0.00 | 57.50 |
April | 379.50 | 0.72 | 0.50 | 01-APR-10:50 | 297.92 | 0.00 | 0.00 | 161.67 | 233.71 | 0.00 | 0.00 | 117.67 |
May | 427.83 | 0.69 | 0.50 | 01-MAY-09:30 | 360.50 | 0.00 | 0.00 | 220.83 | 279.08 | 0.00 | 0.00 | 162.83 |
June | 375.17 | 0.70 | 0.50 | 01-JUN-09:00 | 327.20 | 0.00 | 0.00 | 210.67 | 1132.58 | 0.00 | 0.00 | 162.50 |
July | 471.00 | 0.75 | 0.50 | 01-JUL-11:39 | 281.19 | 0.00 | 0.00 | 170.00 | 220.91 | 0.00 | 0.00 | 123.17 |
August | 366.67 | 0.76 | 0.50 | 01-AUG-08:30 | 399.76 | 0.00 | 0.00 | 134.50 | 205.13 | 0.00 | 0.00 | 87.83 |
September | 301.17 | 0.73 | 0.50 | 01-SEP-11:50 | 1230.85 | 0.00 | 0.00 | 117.17 | 211.67 | 0.00 | 0.00 | 63.00 |
October | 245.33 | 0.81 | 0.50 | 01-OCT-11:00 | 193.85 | 0.00 | 0.00 | 41.33 | 158.83 | 0.00 | 0.00 | 15.33 |
November | 242.67 | 0.87 | 0.58 | 19-NOV-11:20 | 155.16 | 0.00 | 0.00 | 0.50 | 118.08 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.91 | 0.58 | 10-DEC-12:30 | 120.96 | 0.00 | 0.00 | 0.17 | 97.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.77 | 346.80 | 0.00 | 0.00 | 1179.17 | 316.41 | 0.00 | 0.00 | 814.83 | ||
Minimum of Months | 160.33 | 0.69 | 0.50 | 120.96 | 0.00 | 0.00 | 0.17 | 97.23 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.91 | 0.58 | 1230.85 | 0.00 | 0.00 | 220.83 | 1132.58 | 0.00 | 0.00 | 162.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.74 | 0.50 | 02-JAN-11:30 | 160.70 | 11.37 | 0.00 | 61.00 | 133.06 | 14.41 | 0.00 | 28.50 |
February | 259.50 | 0.69 | 0.50 | 01-FEB-11:30 | 208.18 | 12.72 | 0.00 | 116.67 | 171.90 | 16.03 | 9.17 | 85.17 |
March | 247.00 | 0.63 | 0.50 | 01-MAR-10:20 | 826.38 | 15.15 | 14.50 | 208.33 | 799.91 | 17.74 | 53.17 | 172.00 |
April | 379.50 | 0.61 | 0.50 | 01-APR-08:30 | 618.85 | 15.29 | 17.50 | 268.17 | 592.27 | 18.20 | 104.67 | 225.83 |
May | 427.83 | 0.60 | 0.50 | 01-MAY-07:30 | 1329.92 | 16.58 | 44.50 | 323.33 | 339.80 | 18.47 | 113.50 | 272.50 |
June | 375.17 | 0.60 | 0.50 | 01-JUN-07:49 | 378.41 | 14.68 | 3.00 | 318.83 | 595.21 | 19.75 | 121.67 | 288.17 |
July | 471.00 | 0.65 | 0.50 | 01-JUL-09:39 | 320.97 | 13.03 | 5.00 | 283.33 | 1170.19 | 18.46 | 105.83 | 249.00 |
August | 366.67 | 0.64 | 0.50 | 01-AUG-06:30 | 296.81 | 13.54 | 1.67 | 274.17 | 591.47 | 18.02 | 87.33 | 228.00 |
September | 301.17 | 0.62 | 0.50 | 01-SEP-07:00 | 303.74 | 14.18 | 0.00 | 232.00 | 244.38 | 17.91 | 61.00 | 182.17 |
October | 245.33 | 0.67 | 0.50 | 01-OCT-08:50 | 226.65 | 12.84 | 0.00 | 166.33 | 594.55 | 18.07 | 44.17 | 124.83 |
November | 242.67 | 0.72 | 0.50 | 01-NOV-10:50 | 176.34 | 12.01 | 0.00 | 81.83 | 146.26 | 15.10 | 0.00 | 45.33 |
December | 160.33 | 0.79 | 0.50 | 01-DEC-10:20 | 141.66 | 11.06 | 0.00 | 25.83 | 116.51 | 14.45 | 0.00 | 7.67 |
Annual Sum or Average | 3714.00 | 0.65 | 461.70 | 13.83 | 86.17 | 2359.83 | 513.99 | 17.58 | 700.50 | 1909.17 | ||
Minimum of Months | 160.33 | 0.60 | 0.50 | 141.66 | 11.06 | 0.00 | 25.83 | 116.51 | 14.41 | 0.00 | 7.67 | |
Maximum of Months | 471.00 | 0.79 | 0.50 | 1329.92 | 16.58 | 44.50 | 323.33 | 1170.19 | 19.75 | 121.67 | 288.17 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.94 | 0.83 | 20-JAN-15:30 | 149.19 | 20.68 | 61.50 | 7.17 | 71.54 | 18.61 | 27.83 | 0.00 |
February | 259.50 | 0.91 | 0.80 | 26-FEB-15:30 | 290.37 | 22.89 | 116.17 | 25.17 | 100.35 | 20.04 | 84.50 | 0.00 |
March | 247.00 | 0.88 | 0.80 | 01-MAR-15:30 | 343.97 | 23.47 | 134.67 | 60.00 | 226.25 | 23.56 | 149.00 | 23.33 |
April | 379.50 | 0.88 | 0.80 | 01-APR-14:30 | 294.11 | 21.59 | 189.33 | 86.50 | 370.38 | 23.48 | 229.83 | 57.17 |
May | 427.83 | 0.87 | 0.80 | 02-MAY-14:39 | 302.66 | 21.11 | 217.50 | 124.17 | 306.45 | 22.16 | 262.00 | 79.50 |
June | 375.17 | 0.87 | 0.80 | 01-JUN-14:20 | 298.72 | 21.06 | 200.83 | 97.67 | 342.97 | 22.21 | 266.67 | 71.67 |
July | 471.00 | 0.88 | 0.80 | 01-JUL-14:09 | 262.69 | 19.89 | 187.00 | 103.67 | 410.83 | 21.14 | 240.00 | 95.67 |
August | 366.67 | 0.88 | 0.80 | 02-AUG-14:20 | 286.62 | 21.06 | 175.83 | 79.00 | 358.63 | 22.11 | 212.50 | 68.83 |
September | 301.17 | 0.87 | 0.80 | 01-SEP-14:50 | 472.41 | 24.27 | 172.33 | 98.00 | 391.52 | 24.72 | 191.00 | 64.83 |
October | 245.33 | 0.90 | 0.80 | 01-OCT-15:09 | 297.24 | 23.39 | 132.83 | 41.33 | 149.44 | 21.64 | 125.83 | 7.33 |
November | 242.67 | 0.93 | 0.83 | 04-NOV-15:30 | 152.58 | 19.74 | 53.50 | 5.00 | 77.24 | 18.99 | 40.83 | 0.00 |
December | 160.33 | 0.94 | 0.86 | 06-DEC-14:30 | 137.84 | 19.18 | 42.00 | 0.00 | 74.37 | 19.03 | 21.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.89 | 283.28 | 21.48 | 1683.50 | 727.67 | 271.81 | 21.71 | 1851.00 | 468.33 | ||
Minimum of Months | 160.33 | 0.87 | 0.80 | 137.84 | 19.18 | 42.00 | 0.00 | 71.54 | 18.61 | 21.00 | 0.00 | |
Maximum of Months | 471.00 | 0.94 | 0.86 | 472.41 | 24.27 | 217.50 | 124.17 | 410.83 | 24.72 | 266.67 | 95.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.574986E+10 | 25172.70 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435613E+10 | 25172.70 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.319348E+10 | 25172.70 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150416E+10 | 25172.70 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193282E+09 | 25172.70 | 24-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24619755.98 | 10648.69 | 14-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20026360.66 | 11174.69 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109922E+10 | 25172.70 | 13-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.336716E+10 | 25172.70 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.494598E+10 | 25172.70 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.574986E+10 | 25172.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171072E+11 | 65809.76 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116518E+11 | 65809.76 | 13-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432965E+10 | 52033.36 | 24-MAR-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.892722E+09 | 34989.54 | 01-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.391262E+09 | 42282.21 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.670154E+10 | 54960.65 | 29-NOV-20:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139547E+11 | 58180.88 | 26-DEC-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171072E+11 | 65809.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247195E+11 | 38771.95 | 15-JAN-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174900E+11 | 56649.17 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112498E+10 | 21301.89 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140108E+11 | 31446.00 | 22-DEC-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247195E+11 | 56649.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.135344E+09 | 0.130319E+09 | 5082.75 | 27-APR-16:00 | 4759.83 | 0.00 |
May | 0.00 | 0.00 | 0.360437E+09 | 0.328006E+09 | 5647.36 | 15-MAY-16:00 | 5647.36 | 0.00 |
June | 0.00 | 0.00 | 0.840984E+09 | 0.815028E+09 | 15044.64 | 24-JUN-07:03 | 12232.45 | 0.00 |
July | 0.00 | 0.00 | 0.264716E+10 | 0.231930E+10 | 16953.07 | 31-JUL-07:02 | 12356.28 | 0.00 |
August | 0.00 | 0.00 | 0.371778E+10 | 0.322789E+10 | 17020.86 | 10-AUG-07:02 | 12352.32 | 0.00 |
September | 0.00 | 0.00 | 0.897447E+09 | 0.754379E+09 | 15354.36 | 02-SEP-07:02 | 10966.36 | 0.00 |
October | 0.00 | 0.00 | 15239464.57 | 15239463.53 | 1995.97 | 04-OCT-15:00 | 1995.97 | 0.00 |
November | 0.00 | 0.00 | 66.15 | 50.85 | 0.11 | 04-NOV-15:00 | 0.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.861439E+10 | 0.759016E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.371778E+10 | 0.322789E+10 | 17020.86 | 12356.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.131717E+09 | 0.126650E+09 | 6789.95 | 28-JUN-15:00 | 6789.95 | 0.00 |
July | 0.00 | 0.00 | 0.196459E+10 | 0.171722E+10 | 43423.68 | 27-JUL-18:05 | 32496.67 | 0.00 |
August | 0.00 | 0.00 | 0.307468E+10 | 0.267330E+10 | 42148.03 | 13-AUG-12:43 | 35894.84 | 0.00 |
September | 0.00 | 0.00 | 73222913.76 | 57397756.65 | 4269.20 | 14-SEP-15:00 | 3356.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.524421E+10 | 0.457457E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.307468E+10 | 0.267330E+10 | 43423.68 | 35894.84 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.296942E+09 | 0.05 | 166.35 | 01-JAN-00:03 | 0.08 |
February | 0.190655E+09 | 0.04 | 166.35 | 01-FEB-00:05 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 20560996.92 | 0.00 | 166.35 | 23-NOV-22:40 | 0.08 |
December | 0.249282E+09 | 0.04 | 166.35 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.757440E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296942E+09 | 0.05 | 166.35 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109585E+10 | 0.41 | 1079.98 | 02-JAN-06:01 | 0.92 |
February | 0.100347E+10 | 0.40 | 1079.98 | 01-FEB-06:02 | 0.92 |
March | 0.116414E+10 | 0.39 | 1079.98 | 15-MAR-13:50 | 0.92 |
April | 0.107326E+10 | 0.36 | 1079.98 | 11-APR-13:00 | 0.92 |
May | 0.111195E+10 | 0.35 | 1079.98 | 01-MAY-06:50 | 0.92 |
June | 0.111195E+10 | 0.36 | 1079.98 | 01-JUN-06:10 | 0.92 |
July | 0.106918E+10 | 0.34 | 1079.98 | 01-JUL-06:05 | 0.92 |
August | 0.115472E+10 | 0.36 | 1079.98 | 01-AUG-06:05 | 0.91 |
September | 0.106918E+10 | 0.35 | 1079.98 | 01-SEP-06:10 | 0.91 |
October | 0.107052E+10 | 0.34 | 1079.98 | 02-OCT-06:10 | 0.92 |
November | 0.103410E+10 | 0.35 | 1079.98 | 01-NOV-06:01 | 0.92 |
December | 0.108428E+10 | 0.37 | 1079.98 | 01-DEC-06:02 | 0.92 |
Annual Sum or Average | 0.130426E+11 | 0.37 | |||
Minimum of Months | 0.100347E+10 | 0.34 | 1079.98 | 0.91 | |
Maximum of Months | 0.116414E+10 | 0.41 | 1079.98 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128095E+10 | 0.55 | 2047.93 | 02-JAN-06:01 | 0.89 |
February | 0.107040E+10 | 0.49 | 2047.93 | 13-FEB-06:11 | 0.89 |
March | 0.999669E+09 | 0.36 | 1619.23 | 24-MAR-05:53 | 0.89 |
April | 0.836742E+09 | 0.24 | 1420.23 | 17-APR-06:02 | 0.75 |
May | 0.843421E+09 | 0.21 | 819.17 | 01-MAY-06:10 | 0.54 |
June | 0.843421E+09 | 0.21 | 819.17 | 28-JUN-12:50 | 0.54 |
July | 0.828462E+09 | 0.21 | 2047.93 | 31-JUL-17:10 | 0.88 |
August | 0.891695E+09 | 0.22 | 2047.93 | 10-AUG-17:08 | 0.88 |
September | 0.810982E+09 | 0.20 | 819.17 | 12-SEP-14:50 | 0.53 |
October | 0.822141E+09 | 0.21 | 1608.64 | 24-OCT-06:01 | 0.79 |
November | 0.967384E+09 | 0.41 | 1710.32 | 29-NOV-20:43 | 0.89 |
December | 0.119679E+10 | 0.54 | 1810.53 | 26-DEC-03:53 | 0.89 |
Annual Sum or Average | 0.113921E+11 | 0.32 | |||
Minimum of Months | 0.810982E+09 | 0.20 | 819.17 | 0.53 | |
Maximum of Months | 0.128095E+10 | 0.55 | 2047.93 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109585E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100347E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116414E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.110265E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118681E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.128597E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.160782E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.191660E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125164E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107383E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.103410E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.108428E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148072E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191660E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.128095E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107040E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.999669E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.836742E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.843421E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.877301E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131163E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.165954E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.829610E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.822141E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.967384E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119679E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.126956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.822141E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.165954E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109585E+10 | 0.00 | 0.574986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100347E+10 | 0.00 | 0.435613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116414E+10 | 0.00 | 0.319348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107326E+10 | 0.135344E+09 | 0.150416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111195E+10 | 0.360437E+09 | 0.193282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111195E+10 | 0.840984E+09 | 24619755.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106918E+10 | 0.264716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115472E+10 | 0.371778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106918E+10 | 0.897447E+09 | 20026360.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107052E+10 | 15239464.57 | 0.109922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103410E+10 | 66.15 | 0.336716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108428E+10 | 0.00 | 0.494598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130426E+11 | 0.861439E+10 | 0.244539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116414E+10 | 0.371778E+10 | 0.574986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128095E+10 | 0.00 | 0.171072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107040E+10 | 0.00 | 0.116518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.999669E+09 | 0.00 | 0.432965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.836742E+09 | 0.00 | 0.892722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.843421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843421E+09 | 0.131717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.828462E+09 | 0.188360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891695E+09 | 0.301679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.810982E+09 | 73222913.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.822141E+09 | 0.00 | 0.391262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967384E+09 | 0.00 | 0.670154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119679E+10 | 0.00 | 0.139547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113921E+11 | 0.510532E+10 | 0.550289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.810982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128095E+10 | 0.301679E+10 | 0.171072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107326E+10 | 0.00 | 0.00 | 0.00 | 29393309.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111195E+10 | 0.00 | 0.00 | 0.00 | 74858646.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111195E+10 | 0.00 | 0.00 | 0.00 | 0.174017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106918E+10 | 0.00 | 0.00 | 0.00 | 0.538639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115472E+10 | 0.00 | 0.00 | 0.00 | 0.761886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106918E+10 | 0.00 | 0.00 | 0.00 | 0.182454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107052E+10 | 0.00 | 0.00 | 0.00 | 3310736.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103410E+10 | 0.00 | 0.00 | 0.00 | 14.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130426E+11 | 0.00 | 0.00 | 0.00 | 0.176456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116414E+10 | 0.00 | 0.00 | 0.00 | 0.761886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.999669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.836742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.843421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843421E+09 | 0.00 | 0.00 | 0.00 | 33879923.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.828462E+09 | 0.00 | 0.00 | 0.00 | 0.483171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891695E+09 | 0.00 | 0.00 | 0.00 | 0.767843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.810982E+09 | 0.00 | 0.00 | 0.00 | 18628673.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.822141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113921E+11 | 0.00 | 0.00 | 0.00 | 0.130352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.810982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128095E+10 | 0.00 | 0.00 | 0.00 | 0.767843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10271509.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191113E+10 | 0.00 | 0.00 | 0.12 |
February | 61348960.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152726E+10 | 0.00 | 0.00 | 0.13 |
March | 0.253985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132231E+10 | 0.00 | 0.00 | 0.13 |
April | 0.521420E+09 | 4245061.80 | 0.00 | 146491.45 | 0.00 | 0.657090E+09 | 0.147027E+09 | 0.00 | 0.15 |
May | 0.694978E+09 | 4806289.61 | 0.00 | 1149690.26 | 0.00 | 40248488.73 | 0.109574E+10 | 0.00 | 0.28 |
June | 0.245946E+09 | 4072273.56 | 0.00 | 3121135.27 | 0.00 | 1738317.69 | 0.234847E+10 | 0.00 | 0.49 |
July | 32582872.04 | 53509063.57 | 0.00 | 5004138.46 | 0.00 | 0.00 | 0.249462E+10 | 0.00 | 0.61 |
August | 19921838.84 | 0.130246E+09 | 0.00 | 4309801.05 | 0.00 | 0.00 | 0.226007E+10 | 0.00 | 0.58 |
September | 0.270821E+09 | 6340973.73 | 0.00 | 2999594.83 | 0.00 | 2607474.10 | 0.222353E+10 | 0.00 | 0.47 |
October | 0.615145E+09 | 0.00 | 0.00 | 219547.32 | 0.00 | 0.517365E+09 | 0.306801E+09 | 0.00 | 0.16 |
November | 0.131935E+09 | 0.00 | 0.00 | 503.15 | 0.00 | 0.135347E+10 | 8119297.08 | 0.00 | 0.12 |
December | 10294542.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181337E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.286865E+10 | 0.203219E+09 | 0.00 | 16950901.79 | 0.00 | 0.914658E+10 | 0.108844E+11 | 0.00 | 0.28 |
Minimum of Months | 10271509.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.694978E+09 | 0.130246E+09 | 0.00 | 5004138.46 | 0.00 | 0.191113E+10 | 0.249462E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252968E+10 | 0.00 | 0.00 | 0.17 |
February | 0.246334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153407E+10 | 0.00 | 0.00 | 0.18 |
March | 0.358421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258979E+09 | 0.00 | 0.00 | 0.19 |
April | 0.315009E+10 | 0.00 | 0.00 | 0.00 | 28055752.67 | 39910594.78 | 0.00 | 0.00 | 0.18 |
May | 0.393102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.376319E+10 | 0.00 | 0.00 | 404584.43 | 0.00 | 0.00 | 0.350899E+09 | 0.00 | 0.20 |
July | 0.251777E+10 | 27961387.25 | 0.00 | 2777883.32 | 0.00 | 0.00 | 0.147897E+10 | 0.00 | 0.23 |
August | 0.268689E+10 | 85062818.80 | 0.00 | 2550293.83 | 0.00 | 0.00 | 0.862178E+09 | 0.00 | 0.24 |
September | 0.376449E+10 | 0.00 | 0.00 | 382049.87 | 0.00 | 0.00 | 0.393489E+09 | 0.00 | 0.20 |
October | 0.328105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21316365.11 | 0.00 | 0.00 | 0.17 |
November | 0.280383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775940E+09 | 0.00 | 0.00 | 0.17 |
December | 0.259511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197843E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.369786E+11 | 0.113024E+09 | 0.00 | 6114811.45 | 28055752.67 | 0.713833E+10 | 0.308554E+10 | 0.00 | 0.19 |
Minimum of Months | 0.243761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.393102E+10 | 85062818.80 | 0.00 | 2777883.32 | 28055752.67 | 0.252968E+10 | 0.147897E+10 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:44:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.831044E+11 | 0.399733E+11 | 0.00 | 0.688869E+10 | 0.166795E+11 |
February | 0.236361E+12 | 0.332983E+11 | 0.00 | 0.558603E+10 | 0.117117E+11 |
March | 0.490071E+12 | 0.321399E+11 | 0.00 | 0.541948E+10 | 0.363134E+10 |
April | 0.803442E+12 | 0.294231E+11 | 0.00 | 0.448338E+10 | 0.131717E+10 |
May | 0.108943E+13 | 0.395154E+11 | 0.00 | 0.575833E+10 | 0.529926E+09 |
June | 0.111025E+13 | 0.370980E+11 | 0.00 | 0.670970E+10 | 0.119232E+10 |
July | 0.119528E+13 | 0.373507E+11 | 0.00 | 0.644943E+10 | 0.563355E+10 |
August | 0.939039E+12 | 0.383874E+11 | 0.00 | 0.561999E+10 | 0.832220E+10 |
September | 0.654164E+12 | 0.287297E+11 | 0.00 | 0.665197E+10 | 0.118171E+10 |
October | 0.377111E+12 | 0.360099E+11 | 0.00 | 0.474189E+10 | 0.742135E+09 |
November | 0.120284E+12 | 0.294927E+11 | 0.00 | 0.507330E+10 | 0.510887E+10 |
December | 0.502423E+11 | 0.309095E+11 | 0.00 | 0.639721E+10 | 0.124463E+11 |
Annual Sum or Average | 0.714879E+13 | 0.412328E+12 | 0.00 | 0.697794E+11 | 0.684968E+11 |
Minimum of Months | 0.502423E+11 | 0.287297E+11 | 0.00 | 0.448338E+10 | 0.529926E+09 |
Maximum of Months | 0.119528E+13 | 0.399733E+11 | 0.00 | 0.688869E+10 | 0.166795E+11 |