Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44

Tabular Output Report in Format: HTML

Building: Warehouse

Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2023-10-16 10:44:06


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 520.39 107.63 107.63
Net Site Energy 520.39 107.63 107.63
Total Source Energy 1281.89 265.12 265.12
Net Source Energy 1281.89 265.12 265.12


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4835.13
Net Conditioned Building Area 4835.13
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 175.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 95.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 136.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 22.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 344.59 175.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 175.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 95.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 61.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 136.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 22.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 26.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 175.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 95.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 61.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 136.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 22.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 26.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.61
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 32.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 10.42 36.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Other 28.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 71.27 36.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 32.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 10.42 36.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Other 28.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 71.27 36.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 344.591 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 344.591 100.00
     
Total On-Site and Utility Electric Sources 344.591 100.00
Total Electricity End Uses 344.591 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 51.61 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 51.61 100.00
Total Water End Uses 51.61 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 19.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2707.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

| Environment |

ZoneCoolingSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

ZoneHeatingSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

ZoneElectricSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

SpaceGainsMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

PeakSpaceGainsMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

SpaceGainComponentsAtCoolingPeakMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

ComfortReportSimple55Monthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

OccupantComfortDataSummaryMonthly

| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |

DXReportMonthly

| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |

WindowReportMonthly

| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |

WindowEnergyReportMonthly

| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |

WindowZoneSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

WindowEnergyZoneSummaryMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |

CoilReportMonthly

| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |

FanReportMonthly

| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |

ZoneTemperatureOscillationReportMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-OFFICE | PSZ-FINE STORAGE |

AirLoopSystemComponentLoadsMonthly

| PSZ-OFFICE | PSZ-FINE STORAGE |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-OFFICE | PSZ-FINE STORAGE |

MechanicalVentilationLoadsMonthly

| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44
RunPeriod RUNPERIOD 1
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Above Ground Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Window Opening Area [m2] 17.66 6.51 0.00 0.00 11.15
Gross Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86
Above Ground Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Above Ground Wall Area [m2] 2496.99 858.34 390.15 858.34 390.15
Window Opening Area [m2] 17.66 6.51 0.00 0.00 11.15
Gross Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86
Above Ground Window-Wall Ratio [%] 0.71 0.76 0.00 0.00 2.86


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 4598.25
Skylight Area [m2] 68.38
Skylight-Roof Ratio [%] 1.49


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
ZONE1 OFFICE 236.88 Yes Yes 1010.76 1.00 149.56 0.00 17.66 17.66 6.0858 18.58 8.0737
ZONE2 FINE STORAGE 1393.41 Yes Yes 2953.02 1.00 760.80 0.00 0.00 0.00 6.6844 46.45 0.0000
ZONE3 BULK STORAGE 3204.84 Yes Yes 35277.63 1.00 1586.63 0.00 0.00 0.00 3.1969 46.45 2.5587
Total 4835.13     39241.41   2496.99 0.00 17.66 17.66 4.3435 43.27 2.0915
Conditioned Total 4835.13     39241.41   2496.99 0.00 17.66 17.66 4.3435 43.27 2.0915
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
ZONE1 OFFICE 236.88 Yes Yes 1.00 ZONE1 OFFICE GENERAL ZONE1 OFFICE 6.0858 18.58 8.0737  
ZONE2 FINE STORAGE 1393.41 Yes Yes 1.00 ZONE2 FINE STORAGE GENERAL ZONE2 FINE STORAGE 6.6844 46.45 0.0000  
ZONE3 BULK STORAGE 3204.84 Yes Yes 1.00 ZONE3 BULK STORAGE GENERAL ZONE3 BULK STORAGE 3.1969 46.45 2.5587  
Total 4835.13             4.3435 21.63 2.0915  
Conditioned Total 4835.13             4.3435 21.63 2.0915  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4835.13 4835.13 0.00 0.00 4.3435 43.27 2.0915
Total 4835.13 4835.13 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 30-DEC-08:09 10-JAN-17:00 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 93682.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8876.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 5492.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 10035.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2103.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1649.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 28158.46 93682.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 93682.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 8876.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 5492.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 10035.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 2103.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 1649.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 190.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 303.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 196.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 432.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 72.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 82.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1091.32 190.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 39.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 89.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 14.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 17.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 225.71 39.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 39.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 62.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 89.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 14.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 17.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 225.71 39.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ZONE1 OFFICE DIRECT AIR 0.902445
ZONE2 FINE STORAGE DIRECT AIR 1.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
ZONE3 BULK STORAGE UNIT HEATER 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
ZONE3UNITHEATER ZONE3HIRADIANT FAN 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL 42089.11
PSZ-OFFICE HEATING COIL 23613.96
PSZ-FINE STORAGE HEATING COIL 60020.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:HighTemperatureRadiant

User-Specified Heating Design Capacity [W]
ZONE3 BULK STORAGE HIRADIANT 42089.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-OFFICE 0.902445 0.902445 0.902445 0.902445 0.902445 0.902445 1.00 1.00 0.902445
PSZ-FINE STORAGE 1.71 1.71 1.71 1.71 1.71 1.71 1.00 1.00 1.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-OFFICE_OA_CONTROLLER 0.902445 0.102285
PSZ-FINE STORAGE_OA_CONTROLLER 1.71  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-OFFICE_ADDAQ SUPPLY FAN 0.902445 999.15
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN 1.71 1825.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-OFFICE_UNITARY_PACKAGE_DX 0.902445 0.902445 0.902445 0.902445 14938.66 23613.96 40.00 1.00
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX 1.71 1.71 1.71 1.13 32887.87 60020.11 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-OFFICE COOLING COIL 0.902440 0.451222 0.601627 14938.66 7469.33 0.800660 0.800660
PSZ-FINE STORAGE COOLING COIL 1.71 0.853075 1.14 32887.87 16443.94 0.790730 0.790730
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
OFFICE FRONT WALL OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 |
OFFICE LEFT WALL OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 |
FINE STORAGE FRONT WALL FINE STORAGE OVERHEAD DOOR1 |
FINE STORAGE RIGHT WALL FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR |
FINE STORAGE LEFT WALL FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR |
FINE STORAGE ROOF FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 |
BULK STORAGE RIGHT WALL BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 |
BULK STORAGE REAR WALL BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 |
BULK STORAGE LEFT WALL BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 |
BULK STORAGE ROOF SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.30 6.70 4.10 4.20 4.20 5.90 9.00 10.00 13.30 15.00 15.70 13.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 William R Fairchild WA USA TMY3 WMO#=727885 48.12 -123.50 -8.00 91.00 100237 1.1914


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.23 11.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Warehouse 90.000 Urban 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.220 370.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 3 102 78


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 ZONE1 OFFICE 0.0 0.00 0.00 0.00 4.57 -12.95 2.13 1 1 1 0.00 9.14 -25.91 5.60E-016 0.00 4.27 4.27 1010.76 TARP TARP 236.88 149.56 128.00 17.66 6 6 0 Yes
2 ZONE2 FINE STORAGE 0.0 0.00 0.00 0.00 14.29 -22.82 4.51 1 1 1 0.00 30.48 -45.72 1.87E-015 0.00 8.53 7.81 2953.02 TARP TARP 1393.41 760.80 727.17 20.81 11 20 0 Yes
3 ZONE3 BULK STORAGE 0.0 0.00 0.00 0.00 65.53 -22.86 4.27 1 1 1 30.48 100.58 -45.72 6.16E-015 0.00 8.53 8.53 35277.63 TARP TARP 3204.84 1586.63 1471.35 47.57 6 52 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 ZONE1 OFFICE 236.88 12.7 18.581 5.382E-002 6.086 8.074 0.000 0.000 0.000 0.000 14.160 No
2 ZONE2 FINE STORAGE 1393.41 30.0 46.447 2.153E-002 6.684 0.000 0.000 0.000 0.000 0.000 6.684 No
3 ZONE3 BULK STORAGE 3204.84 69.0 46.447 2.153E-002 3.197 2.559 0.000 0.000 0.000 0.000 5.756 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 OFFICE PEOPLE BLDG_OCC_SCH ZONE1 OFFICE 236.88 12.7 12.7 5.382E-002 18.581 0.300 0.700 AutoCalculate OFFICE ACTIVITY SCHEDULE No 3.8200E-008 0 13
2 ZONE2 FINE STORAGEPEOPLE BLDG_OCC_SCH ZONE2 FINE STORAGE 1393.41 30.0 30.0 2.153E-002 46.447 0.300 0.700 AutoCalculate ZONE2 FINE STORAGE ACTIVITY SCHEDULE No 3.8200E-008 0 30
3 ZONE3 BULK STORAGEPEOPLE BLDG_OCC_SCH ZONE3 BULK STORAGE 3204.84 69.0 69.0 2.153E-002 46.447 0.300 0.700 AutoCalculate ZONE3 BULK STORAGE ACTIVITY SCHEDULE No 3.8200E-008 0 69


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 OFFICE LIGHTS LTG_SCH_OFFICE ZONE1 OFFICE 236.88 12.7 1441.602 6.086 113.078 0.000 0.370 0.180 0.450 1.000 LightsWired 0.000 1441.602
2 FINE STORAGE AREA LIGHTS LTG_SCH_FINE_STORAGE ZONE2 FINE STORAGE 1393.41 30.0 9314.081 6.684 310.469 0.000 0.420 0.180 0.400 1.000 LightsWired 0.000 9314.081
3 BULK STORAGE AREA LIGHTS LTG_SCH_BULK_STORAGE ZONE3 BULK STORAGE 3204.84 69.0 10245.499 3.197 148.485 0.000 0.420 0.180 0.400 1.000 LightsWired 0.000 10245.499


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 OFFICE PLUG LOAD OFFICE_PLUG_SCH ZONE1 OFFICE 236.88 12.7 1912.500 8.074 150.015 0.000 0.000 0.000 1.000 MiscPlug 0.000 1912.500
2 BULK STORAGE PLUG LOAD BULK STORAGE PLUG SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 8200.120 2.559 118.842 0.000 0.000 0.000 1.000 MiscPlug 0.000 8200.120


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 NONRES_ROOF 16 2 2 0.167 0.2043 0.900 0.900 0.770 0.700 Smooth
2 SEMIHEATED_ROOF 18 2 2 0.167 0.2043 0.900 0.900 0.770 0.700 Smooth
3 NONRES_EXT_WALL_GRD 19 3 4 0.167 0.3969 0.900 0.900 0.700 0.700 Smooth
4 SEMIHEATED_EXT_WALL_GRD 25 3 4 0.167 0.3969 0.900 0.900 0.700 0.700 Smooth
5 SWINGING DOOR_CON 41 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
6 SWINGING DOOR_SEMI 42 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
7 OVERHEAD DOOR_SEMI 44 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
8 OVERHEAD DOOR_CON 45 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
9 BULK STORAGE PRODUCTS 46 1 18 0.500 0.5914 0.900 0.900 0.700 0.700 Rough
10 INTERIOR WALL 47 5 5 2.167 0.7747 0.900 0.900 0.700 0.700 Smooth
11 INSULATEDCEILING 48 2 3 0.333 10.06 0.900 0.900 0.700 0.700 MediumRough
12 OFFICEFLOOR_FFACTOR 49 2 7 0.167 0.1360 0.000 0.900 0.000 0.700 MediumRough
13 FINESTORAGEFLOOR_FFACTOR 50 2 7 0.167 0.5623E-01 0.000 0.900 0.000 0.700 MediumRough
14 BULKSTORAGEFLOOR_FFACTOR 51 2 7 0.167 0.5264E-01 0.000 0.900 0.000 0.700 MediumRough
15 iz-INTERIOR WALL 52 5 5 2.167 0.7747 0.900 0.900 0.700 0.700 MediumSmooth
16 iz-SEMIHEATED_EXT_WALL_GRD 53 3 4 0.167 0.3969 0.900 0.900 0.700 0.700 MediumSmooth
17 iz-INSULATEDCEILING 54 2 3 0.333 10.06 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 F08 METAL ROOF SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
2 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.894
3 F08 METAL ROOF SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
4 SEMIHEATED_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.894
5 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
6 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.420
7 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.420
10 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
11 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
12 OPAQUE DOOR PANEL_SEMI 0.0000 0.000 0.000 0.000 0.4760
13 OVERHEAD DOOR_SEMI PANEL 0.0000 0.000 0.000 0.000 0.5681
14 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
15 BULK STORAGE PRODUCTS MATERIAL 2.4384 1.442 200.231 836.800 1.691
16 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
17 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
18 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06
19 STEEL FRAME/CAVITY 0.0889 0.084 641.379 502.080 1.057
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 7.276
24 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
25 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 17.71
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 18.92
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
30 STEEL FRAME/CAVITY 0.0889 0.084 641.379 502.080 1.057
31 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06
32 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
33 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
34 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
35 SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.420
36 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
37 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
38 INTERIOR WALL ADDI INSUL 0.0000 0.043 22.426 836.800 0.5871E-06


CTF

Time Outside Cross Inside Flux (except final one)
1 2 0.93400083E-12 0.71827744E-17 0.33026303E-17 0.0000000
2 1 -5.2160660 0.53236032E-04 -0.78408200E-04 0.17906231E-12
3 0 5.4203831 0.20426382 0.20439547  
4 2 0.93400083E-12 0.71827744E-17 0.33026303E-17 0.0000000
5 1 -5.2160660 0.53236032E-04 -0.78408200E-04 0.17906231E-12
6 0 5.4203831 0.20426382 0.20439547  
7 4 0.79902452E-12 0.91741022E-16 -0.20424744E-14 0.11342756E-15
8 3 -0.39057407E-03 0.28070621E-06 -0.56712558E-04 0.15331003E-12
9 2 1.7533726 0.60989376E-02 1.1509734 -0.74879759E-04
10 1 -7.1105134 0.15738863 -17.165248 0.33605900
11 0 5.6211023 0.10008308 16.277902  
12 4 0.79902452E-12 0.91741022E-16 -0.20424744E-14 0.11342756E-15
13 3 -0.39057407E-03 0.28070621E-06 -0.56712558E-04 0.15331003E-12
14 2 1.7533726 0.60989376E-02 1.1509734 -0.74879759E-04
15 1 -7.1105134 0.15738863 -17.165248 0.33605900
16 0 5.6211023 0.10008308 16.277902  
17 1 0.0000000 0.0000000 -0.0000000 -0.0000000
18 0 2.1009573 2.1009573 2.1009573  
19 1 0.0000000 0.0000000 -0.0000000 -0.0000000
20 0 2.1009573 2.1009573 2.1009573  
21 1 0.0000000 0.0000000 -0.0000000 -0.0000000
22 0 1.7602615 1.7602615 1.7602615  
23 1 0.0000000 0.0000000 -0.0000000 -0.0000000
24 0 1.7602615 1.7602615 1.7602615  
25 18 0.12003549E-12 -0.36149852E-21 0.11999160E-12 -0.69171859E-14
26 17 -0.26702818E-10 0.22043783E-17 -0.26702965E-10 0.15647703E-11
27 16 0.26199194E-08 0.46087291E-16 0.26199192E-08 -0.15597178E-09
28 15 -0.14918350E-06 -0.27301975E-15 -0.14918350E-06 0.90448703E-08
29 14 0.54929883E-05 0.10218664E-13 0.54929883E-05 -0.34010628E-06
30 13 -0.13812653E-03 0.13886261E-11 -0.13812653E-03 0.87613853E-05
31 12 0.24466257E-02 0.76740851E-10 0.24466257E-02 -0.15954016E-03
32 11 -0.31099262E-01 0.20215154E-08 -0.31099262E-01 0.20926433E-02
33 10 0.28694928 0.26940884E-07 0.28694928 -0.20002833E-01
34 9 -1.9353699 0.18750649E-06 -1.9353699 0.14030665
35 8 9.5767226 0.68900696E-06 9.5767226 -0.72468789
36 7 -34.784653 0.13258951E-05 -34.784653 2.7565275
37 6 92.438040 0.12976568E-05 92.438040 -7.6923258
38 5 -178.18614 0.60985027E-06 -178.18614 15.604270
39 4 245.02895 0.12430126E-06 245.02895 -22.615757
40 3 -233.27712 0.91617964E-08 -233.27712 22.714127
41 2 145.61910 0.16319500E-09 145.61910 -14.964058
42 1 -53.478849 0.26256209E-11 -53.478849 5.7996512
43 0 8.7411694 -0.39181092E-12 8.7411694  
44 5 -0.68112304E-12 0.61645773E-13 -0.20199983E-12 0.95058421E-15
45 4 0.71499529E-06 0.73238302E-07 0.28552134E-06 -0.33479849E-12
46 3 -0.58529659E-02 0.62218017E-03 -0.21917430E-02 0.29169470E-06
47 2 1.2914758 0.88958368E-01 0.40042664 -0.15953103E-02
48 1 -8.6129398 0.38073474 -3.1694576 0.22491773
49 0 7.9317533 0.13060792 3.3724149  
50 3 -0.49407978E-15 0.44230608E-16 -0.53860842E-16 0.0000000
51 2 0.54884850E-03 0.14309697E-03 0.26444340E-03 -0.39739853E-15
52 1 -3.9407614 2.0053241 -3.6132068 0.31450573E-03
53 0 13.994357 8.0573072 13.672611  
54 7 -0.31240856E-08 -0.21887765E-14 0.14182747E-14 -0.45258500E-16
55 6 0.39303604E-05 0.26006625E-08 0.31948254E-02 -0.26800873E-04
56 5 -0.27546567E-03 0.15375372E-05 -0.22400621 0.19586362E-02
57 4 0.62896480E-02 0.69930755E-04 4.8342361 -0.45310069E-01
58 3 -0.55086064E-01 0.55565958E-03 -38.047911 0.39894661
59 2 0.19539610 0.92379386E-03 116.53551 -1.4186290
60 1 -0.28189481 0.28115072E-03 -143.93766 2.0495388
61 0 0.13740557 0.68297879E-05 60.838472  
62 7 -0.76172223E-08 0.19992769E-15 -0.36679418E-14 0.15936503E-16
63 6 0.20832875E-05 0.10921259E-08 0.32010154E-02 -0.26852800E-04
64 5 -0.12434769E-03 0.63986796E-06 -0.22435781 0.19617397E-02
65 4 0.26900562E-02 0.28962460E-04 4.8400881 -0.45366326E-01
66 3 -0.23075003E-01 0.22921474E-03 -38.080948 0.39931181
67 2 0.81154666E-01 0.37960809E-03 116.59978 -1.4194888
68 1 -0.11662584 0.11498440E-03 -143.97548 2.0501605
69 0 0.56734574E-01 0.27738523E-05 60.838472  
70 7 -0.81392023E-08 0.28718252E-15 -0.25842544E-14 0.71742475E-17
71 6 0.20245979E-05 0.10259199E-08 0.32012942E-02 -0.26855138E-04
72 5 -0.11816234E-03 0.60006224E-06 -0.22437362 0.19618793E-02
73 4 0.25345016E-02 0.27140048E-04 4.8403509 -0.45368853E-01
74 3 -0.21665828E-01 0.21464768E-03 -38.082430 0.39932820
75 2 0.76088909E-01 0.35527252E-03 116.60266 -1.4195273
76 1 -0.10927342 0.10751462E-03 -143.97718 2.0501884
77 0 0.53139756E-01 0.25964760E-05 60.838472  
78 5 -0.20199983E-12 0.61645773E-13 -0.68112304E-12 0.95058421E-15
79 4 0.28552134E-06 0.73238302E-07 0.71499529E-06 -0.33479849E-12
80 3 -0.21917430E-02 0.62218017E-03 -0.58529659E-02 0.29169470E-06
81 2 0.40042664 0.88958368E-01 1.2914758 -0.15953103E-02
82 1 -3.1694576 0.38073474 -8.6129398 0.22491773
83 0 3.3724149 0.13060792 7.9317533  
84 4 -0.20424744E-14 0.91741022E-16 0.79902452E-12 0.11342756E-15
85 3 -0.56712558E-04 0.28070621E-06 -0.39057407E-03 0.15331003E-12
86 2 1.1509734 0.60989376E-02 1.7533726 -0.74879759E-04
87 1 -17.165248 0.15738863 -7.1105134 0.33605900
88 0 16.277902 0.10008308 5.6211023  
89 3 -0.53860842E-16 0.44230608E-16 -0.49407978E-15 0.0000000
90 2 0.26444340E-03 0.14309697E-03 0.54884850E-03 -0.39739853E-15
91 1 -3.6132068 2.0053241 -3.9407614 0.31450573E-03
92 0 13.672611 8.0573072 13.994357  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3624_SHGC_SOUTH_0.38 34 1 VerySmooth 2.059 2.059 1.000 0.381    
2 NONRESWINDOW_U_0.3624_SHGC_NORTH_0.38 35 1 VerySmooth 2.059 2.059 1.000 0.381    
3 NONRESWINDOW_U_0.3624_SHGC_EAST_0.38 36 1 VerySmooth 2.059 2.059 1.000 0.381    
4 NONRESWINDOW_U_0.3624_SHGC_WEST_0.38 37 1 VerySmooth 2.059 2.059 1.000 0.381    
5 SKYLIGHT_U_0.75_SHGC_0.6 38 1 VerySmooth 4.262 4.262 1.000 0.605    
6 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 39 1 VerySmooth 4.262 4.262 1.000 0.605    
7 SKYLIGHT DOUBLE CLEAR 43 3 VerySmooth 3.715 3.715 1.000 0.720    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SOUTH SpectralAverage   3.63294E-002 0.29373 0.50046 0.50046 0.38000 0.13982 0.18519 0.00000 0.84000 0.84000 0.11606 1.00000 No
2 NONRES WINDOW GLAZING LAYER NORTH SpectralAverage   3.63294E-002 0.29373 0.50046 0.50046 0.38000 0.13982 0.18519 0.00000 0.84000 0.84000 0.11606 1.00000 No
3 NONRES WINDOW GLAZING LAYER EAST SpectralAverage   3.63294E-002 0.29373 0.50046 0.50046 0.38000 0.13982 0.18519 0.00000 0.84000 0.84000 0.11606 1.00000 No
4 NONRES WINDOW GLAZING LAYER WEST SpectralAverage   3.63294E-002 0.29373 0.50046 0.50046 0.38000 0.13982 0.18519 0.00000 0.84000 0.84000 0.11606 1.00000 No
5 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.47441 0.15233 0.15233 0.60000 0.13030 0.15164 0.00000 0.84000 0.84000 2.99465E-002 1.00000 No
6 SEMIHEATED SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.47441 0.15233 0.15233 0.60000 0.13030 0.15164 0.00000 0.84000 0.84000 2.99465E-002 1.00000 No
7 CLEAR 2.5MM SpectralAverage   2.50000E-003 0.80000 7.50000E-002 7.50000E-002 0.90100 8.10000E-002 8.10000E-002 0.00000 0.84000 0.84000 0.90000 1.00000 No
8 CLEAR 2.5MM SpectralAverage   2.50000E-003 0.80000 7.50000E-002 7.50000E-002 0.90100 8.10000E-002 8.10000E-002 0.00000 0.84000 0.84000 0.90000 1.00000 No


WindowMaterial:Gas

Material Name GasType Thickness {m}
1 AIR 3MM Air 3.200E-003


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 ZONE1 OFFICE 4 0
2 ZONE2 FINE STORAGE 14 0
3 ZONE3 BULK STORAGE 32 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 ZONE1 OFFICE 0  
2 ZONE2 FINE STORAGE 0  
3 ZONE3 BULK STORAGE 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 7.5708E-002 6154.7 1.056 0.5354


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES CurtainWall 4.099 0.605 0.602
2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED CurtainWall 4.099 0.605 0.602


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 OFFICE INFILTRATION OFFICE INFIL SCHEDULE ZONE1 OFFICE 236.88 12.7 8.518E-002 3.596E-004 5.551E-004 0.303 0.000 0.000 0.224 0.000
2 OFFICE DOOR INFILTRATION INFIL_DOOR_OPENING_SCH ZONE1 OFFICE 236.88 12.7 0.289 1.219E-003 1.882E-003 1.029 1.000 0.000 0.000 0.000
3 FINE STORAGE INFILTRATION FINE SORAGE INFIL SCHEDULE ZONE2 FINE STORAGE 1393.41 30.0 0.433 3.110E-004 1.981E-004 0.528 0.000 0.000 0.224 0.000
4 BULK STORAGE INFILTRATION BULK STORAGE INFIL_BASE SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 2.710 8.455E-004 5.523E-004 0.277 0.000 0.000 0.224 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 BULK STORAGE VENTILATION-1 ALWAYS ON SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 37.760 1.178E-002 0.547 3.853 Exhaust 31.136 0.5 1.000 0.000 0.000 0.000 29.44 100.00 -100.00 -100.00 100.00 40.00
2 BULK STORAGE VENTILATION-2 ALWAYS ON SCHEDULE ZONE3 BULK STORAGE 3204.84 69.0 0.944 2.945E-004 1.368E-002 9.632E-002 Natural 0.000 1.0 0.000 0.000 0.224 0.000 -73.33 29.44 -100.00 -100.00 100.00 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 ZONE1 OFFICE Mixing/Well-Stirred
2 ZONE2 FINE STORAGE Mixing/Well-Stirred
3 ZONE3 BULK STORAGE Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone ZONE1 OFFICE 1.2000
3 Zone ZONE2 FINE STORAGE 1.2000
4 Zone ZONE3 BULK STORAGE 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone ZONE1 OFFICE 1.2000
3 Zone ZONE2 FINE STORAGE 1.2000
4 Zone ZONE3 BULK STORAGE 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.4929E-004
2 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 8.6970E-004
3 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.2995E-004
4 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 8.9663E-004
5 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.2585E-004
6 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 1.1017E-003
7 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT1 1.5727E-004
8 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_1 ZONE2 FINE STORAGE_DAYLREFPT2 7.2026E-004
9 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 2.7842E-004
10 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 4.9658E-004
11 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 2.3055E-004
12 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 5.4669E-004
13 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 2.5411E-004
14 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 4.4095E-004
15 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT1 3.7631E-004
16 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_6 ZONE2 FINE STORAGE_DAYLREFPT2 2.3735E-004
17 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 5.8699E-004
18 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 2.6509E-004
19 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 4.8790E-004
20 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 2.9501E-004
21 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 7.4045E-004
22 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 1.9853E-004
23 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT1 1.2192E-003
24 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_7 ZONE2 FINE STORAGE_DAYLREFPT2 1.2548E-004
25 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 9.7941E-004
26 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 1.5988E-004
27 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 8.7269E-004
28 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 1.7464E-004
29 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 1.5928E-003
30 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 1.2306E-004
31 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT1 2.0518E-003
32 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_8 ZONE2 FINE STORAGE_DAYLREFPT2 9.7651E-005
33 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 9.4230E-004
34 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 1.1445E-004
35 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 9.4920E-004
36 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 1.2160E-004
37 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 1.2897E-003
38 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 9.7684E-005
39 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT1 9.3050E-004
40 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_9 ZONE2 FINE STORAGE_DAYLREFPT2 8.9351E-005
41 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 5.6824E-004
42 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 9.4163E-005
43 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 6.2032E-004
44 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 9.7704E-005
45 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 5.3867E-004
46 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 8.8078E-005
47 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT1 2.9123E-004
48 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_10 ZONE2 FINE STORAGE_DAYLREFPT2 8.6423E-005
49 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 1.4487E-003
50 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 1.0358E-004
51 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 1.7475E-003
52 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 1.1004E-004
53 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 9.0099E-004
54 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 8.9453E-005
55 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT1 3.8041E-004
56 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_5 ZONE2 FINE STORAGE_DAYLREFPT2 8.6567E-005
57 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 2.4280E-003
58 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 1.4118E-004
59 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 2.6999E-003
60 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 1.5664E-004
61 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 2.6438E-003
62 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 1.0184E-004
63 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT1 1.7108E-003
64 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_4 ZONE2 FINE STORAGE_DAYLREFPT2 8.9807E-005
65 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 2.2078E-003
66 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 2.4956E-004
67 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 2.0385E-003
68 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 2.9243E-004
69 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 3.5647E-003
70 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 1.3823E-004
71 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT1 5.3923E-003
72 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_3 ZONE2 FINE STORAGE_DAYLREFPT2 9.9389E-005
73 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 9.4487E-004
74 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 6.0730E-004
75 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 7.8210E-004
76 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 7.4479E-004
77 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 1.2249E-003
78 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 2.6547E-004
79 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT1 2.4880E-003
80 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_2 ZONE2 FINE STORAGE_DAYLREFPT2 1.3403E-004
81 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 3.5062E-004
82 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 1.2546E-003
83 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 2.8644E-004
84 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 1.5247E-003
85 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 3.2635E-004
86 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 7.0728E-004
87 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT1 5.2548E-004
88 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_14 ZONE2 FINE STORAGE_DAYLREFPT2 2.9448E-004
89 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.6412E-004
90 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 2.2500E-003
91 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.4119E-004
92 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 2.5685E-003
93 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.3705E-004
94 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 2.1679E-003
95 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT1 1.7670E-004
96 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_13 ZONE2 FINE STORAGE_DAYLREFPT2 1.2140E-003
97 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 1.0721E-004
98 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 2.4304E-003
99 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 9.8156E-005
100 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 2.3386E-003
101 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 9.6506E-005
102 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 3.7454E-003
103 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT1 1.0952E-004
104 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_12 ZONE2 FINE STORAGE_DAYLREFPT2 4.8074E-003
105 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 1.0362E-004
106 Clear Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.0233E-003
107 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 9.5452E-005
108 Clear Turbid Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 9.3375E-004
109 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 9.4249E-005
110 Intermediate Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.6646E-003
111 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT1 1.0607E-004
112 Overcast Sky 01/21 ZONE2 FINE STORAGE_DAYLCTRL ZONE2 FINE STORAGE FINESTORAGE_SKYLIGHT_11 ZONE2 FINE STORAGE_DAYLREFPT2 1.9054E-003
113 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 6.6756E-005
114 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 9.5564E-005
115 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 5.8934E-005
116 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 8.0263E-005
117 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 5.6747E-005
118 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 7.3652E-005
119 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT1 6.6204E-005
120 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C1 ZONE3 BULK STORAGE_DAYLREFPT2 9.6978E-005
121 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 9.1243E-005
122 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.6955E-005
123 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.6980E-005
124 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 6.6849E-005
125 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.0402E-005
126 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 6.5275E-005
127 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT1 9.1603E-005
128 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.7987E-005
129 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 6.5272E-005
130 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.3448E-005
131 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 5.8217E-005
132 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.1686E-005
133 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 5.8608E-005
134 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.4353E-005
135 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT1 6.6179E-005
136 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.6280E-005
137 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.9923E-004
138 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.4408E-004
139 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 3.4746E-004
140 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.8261E-004
141 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.9203E-004
142 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.5376E-004
143 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT1 9.2840E-005
144 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.8788E-005
145 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0977E-004
146 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 5.1407E-004
147 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.1414E-004
148 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 6.2994E-004
149 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0045E-004
150 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.3661E-004
151 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT1 6.6674E-005
152 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C1 ZONE3 BULK STORAGE_DAYLREFPT2 9.8401E-005
153 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.4626E-004
154 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1947E-005
155 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.6116E-004
156 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.2010E-005
157 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.1063E-004
158 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1658E-005
159 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT1 6.6649E-005
160 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.6333E-005
161 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 4.6582E-004
162 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 8.9631E-005
163 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 5.6894E-004
164 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.3995E-005
165 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.1738E-004
166 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.8108E-005
167 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT1 9.2818E-005
168 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R1C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.6078E-005
169 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.5604E-004
170 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0796E-003
171 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.5720E-004
172 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.3067E-003
173 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.6679E-004
174 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 6.5185E-004
175 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0481E-004
176 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.5886E-004
177 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 6.0199E-004
178 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.9786E-004
179 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 6.8791E-004
180 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 4.4864E-004
181 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 4.8710E-004
182 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.1988E-004
183 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.2532E-004
184 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.5335E-004
185 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 8.7057E-004
186 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.0981E-004
187 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.0427E-003
188 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.1189E-004
189 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 5.5084E-004
190 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.0742E-004
191 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.2519E-004
192 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.1885E-005
193 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.0599E-004
194 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.5223E-005
195 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.2006E-004
196 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.4470E-005
197 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.8785E-004
198 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.6708E-005
199 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.0473E-004
200 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R2C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.9439E-005
201 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.3896E-003
202 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 1.2524E-004
203 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.5589E-003
204 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 1.2189E-004
205 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.4175E-003
206 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 1.4263E-004
207 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT1 7.8908E-004
208 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C4 ZONE3 BULK STORAGE_DAYLREFPT2 9.8211E-005
209 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.0751E-003
210 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.6299E-004
211 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.1533E-003
212 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.9221E-004
213 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.2722E-003
214 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 6.5211E-004
215 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.8995E-004
216 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.7855E-004
217 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.6029E-004
218 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.7180E-005
219 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.6119E-004
220 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.5409E-005
221 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 3.0805E-004
222 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.1000E-005
223 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.8972E-004
224 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.3063E-005
225 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.0782E-004
226 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.8963E-003
227 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.9820E-004
228 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.1624E-003
229 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.7081E-004
230 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.8540E-003
231 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.9000E-004
232 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R3C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0465E-003
233 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.6549E-004
234 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.6945E-005
235 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.4622E-004
236 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.4352E-005
237 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 3.8093E-004
238 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 6.2122E-005
239 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.9915E-004
240 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.5702E-005
241 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.4898E-003
242 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.2581E-004
243 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.4486E-003
244 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.1671E-004
245 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.2733E-003
246 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.5872E-004
247 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.4291E-003
248 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.2389E-004
249 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.3009E-003
250 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.8459E-004
251 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.2252E-003
252 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 5.5066E-004
253 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.0700E-003
254 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 9.0781E-004
255 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.4336E-003
256 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.8360E-004
257 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.3114E-004
258 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.1741E-003
259 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.0735E-004
260 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.1321E-003
261 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 3.3552E-004
262 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.2753E-003
263 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.9975E-004
264 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R4C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.9790E-003
265 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.1173E-004
266 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.4511E-005
267 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.8564E-004
268 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.1605E-005
269 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.9781E-004
270 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.9026E-005
271 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT1 2.9750E-004
272 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.5670E-005
273 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.0263E-004
274 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.2302E-003
275 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.7396E-004
276 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0441E-003
277 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.6564E-004
278 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.8114E-003
279 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT1 2.9810E-004
280 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.9042E-003
281 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 8.9414E-004
282 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.1001E-004
283 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.6472E-004
284 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.8929E-005
285 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.3758E-003
286 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.3587E-004
287 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.3923E-003
288 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C3 ZONE3 BULK STORAGE_DAYLREFPT2 1.2355E-004
289 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 8.6853E-004
290 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 4.1603E-004
291 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.3255E-004
292 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.5958E-004
293 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.2753E-003
294 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 6.4113E-004
295 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.3968E-003
296 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R5C2 ZONE3 BULK STORAGE_DAYLREFPT2 7.7651E-004
297 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.4567E-004
298 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 4.8375E-004
299 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.2270E-004
300 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 3.8793E-004
301 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.5079E-004
302 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 5.2357E-004
303 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.8771E-004
304 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.0145E-003
305 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 4.0090E-004
306 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.3527E-004
307 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 3.2206E-004
308 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.9598E-004
309 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 4.2581E-004
310 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 2.7687E-004
311 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT1 7.6872E-004
312 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C2 ZONE3 BULK STORAGE_DAYLREFPT2 3.7148E-004
313 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 9.0076E-005
314 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.4493E-005
315 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.6385E-005
316 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.0132E-005
317 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.1764E-005
318 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.1847E-005
319 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT1 9.1582E-005
320 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R8C3 ZONE3 BULK STORAGE_DAYLREFPT2 5.5852E-005
321 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.4367E-004
322 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.0772E-005
323 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.2320E-004
324 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.8036E-005
325 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.6518E-004
326 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.3481E-005
327 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.8744E-004
328 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C4 ZONE3 BULK STORAGE_DAYLREFPT2 5.2992E-005
329 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 9.6244E-005
330 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.9373E-004
331 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 8.2032E-005
332 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.5559E-004
333 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 8.3993E-005
334 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 1.6000E-004
335 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT1 1.0363E-004
336 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C1 ZONE3 BULK STORAGE_DAYLREFPT2 2.5247E-004
337 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.7577E-004
338 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.2720E-004
339 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.4180E-004
340 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.0647E-004
341 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 1.4346E-004
342 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.1651E-004
343 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT1 2.2024E-004
344 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C2 ZONE3 BULK STORAGE_DAYLREFPT2 1.5078E-004
345 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 9.3607E-005
346 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.6831E-005
347 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 8.0955E-005
348 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.4545E-005
349 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 8.9207E-005
350 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.8157E-005
351 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT1 1.0355E-004
352 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C4 ZONE3 BULK STORAGE_DAYLREFPT2 4.9366E-005
353 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 3.9469E-004
354 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 8.7583E-005
355 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 3.2040E-004
356 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.8040E-005
357 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 4.5027E-004
358 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.6053E-005
359 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT1 7.6788E-004
360 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R6C3 ZONE3 BULK STORAGE_DAYLREFPT2 9.7598E-005
361 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.7254E-004
362 Clear Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.7931E-005
363 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.4025E-004
364 Clear Turbid Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.1134E-005
365 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 1.4882E-004
366 Intermediate Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 6.6900E-005
367 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT1 2.2011E-004
368 Overcast Sky 01/21 ZONE3 BULK STORAGE_DAYLCTRL ZONE3 BULK STORAGE SKYLIGHT_R7C3 ZONE3 BULK STORAGE_DAYLREFPT2 7.1450E-005
369 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 5.3800E-003
370 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 6.4203E-004
371 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 4.8269E-003
372 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 5.7797E-004
373 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 4.5934E-003
374 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 5.4797E-004
375 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT1 2.7169E-003
376 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW 1 ZONE1 OFFICE_DAYLREFPT2 4.7716E-004
377 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 6.5989E-004
378 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 6.0175E-003
379 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 6.1277E-004
380 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 5.0753E-003
381 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 5.5954E-004
382 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 4.9782E-003
383 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 4.7173E-004
384 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE FRONT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 3.6541E-003
385 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 5.2751E-003
386 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 3.7694E-004
387 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 3.9865E-003
388 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 2.9718E-004
389 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 2.6791E-003
390 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 2.2069E-004
391 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT1 3.4076E-003
392 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW1 ZONE1 OFFICE_DAYLREFPT2 2.9067E-004
393 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 5.5063E-003
394 Clear Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 3.7774E-004
395 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 4.1028E-003
396 Clear Turbid Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 2.9761E-004
397 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 2.4646E-003
398 Intermediate Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 2.2022E-004
399 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT1 3.4076E-003
400 Overcast Sky 01/21 ZONE1 OFFICE_DAYLCTRL ZONE1 OFFICE OFFICE LEFT WALL WINDOW2 ZONE1 OFFICE_DAYLREFPT2 2.9067E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 ZONE1 OFFICE Cooling 9043.98212 10852.77855 0.75204 0.90244 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 25.24733 8.40527E-003 236.87965 12.74874 0.10228 0.00000
2 ZONE1 OFFICE Heating 7609.34613 9131.21536 0.21572 0.25886 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -4.30000 2.65759E-003 236.87965 12.74874 0.10228 0.00000
3 ZONE2 FINE STORAGE Cooling 21934.73538 26321.68246 1.42179 1.70615 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.40000 8.40708E-003 1393.40969 30.00000 0.42471 0.00000
4 ZONE2 FINE STORAGE Heating 17349.77150 20819.72580 0.41465 0.49758 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -4.30000 2.65759E-003 1393.40969 30.00000 0.42471 0.00000
5 ZONE3 BULK STORAGE Cooling 0.00000 0.00000 0.00000 0.97684 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:10:00 25.33833 8.40541E-003 3204.84228 69.00000 0.97684 0.00000
6 ZONE3 BULK STORAGE Heating 35074.26181 42089.11418 0.86619 1.03943 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 3204.84228 69.00000 0.97684 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-OFFICE Cooling Sensible 13030.15 0.90244 0.90244 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-OFFICE Heating Sensible 8983.90 0.25886 0.25886 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00
3 PSZ-FINE STORAGE Cooling Sensible 29871.30 1.70615 1.70615 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-FINE STORAGE Heating Sensible 24656.47 0.49758 0.49758 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONE1 OFFICE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.90244
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONE2 FINE STORAGE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.70615
3 ZoneHVAC:UnitHeater ZONE3 BULK STORAGE UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 1.03943
4 Fan:ConstantVolume ZONE3UNITHEATER ZONE3HIRADIANT FAN Design Size Maximum Flow Rate [m3/s] 1.03943
5 Coil:Heating:Fuel ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL Design Size Nominal Capacity [W] 42089.11105
6 ZoneHVAC:HighTemperatureRadiant ZONE3 BULK STORAGE HIRADIANT User-Specified Heating Design Capacity [W] 42089.11418
7 AirLoopHVAC PSZ-OFFICE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.90244
8 AirLoopHVAC PSZ-OFFICE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.90244
9 AirLoopHVAC PSZ-OFFICE Sum of Air Terminal Maximum Flow Rates [m3/s] 0.90244
10 AirLoopHVAC PSZ-OFFICE Adjusted Heating Design Air Flow Rate [m3/s] 0.90244
11 AirLoopHVAC PSZ-OFFICE Adjusted Cooling Design Air Flow Rate [m3/s] 0.90244
12 AirLoopHVAC PSZ-OFFICE Adjusted Main Design Air Flow Rate [m3/s] 0.90244
13 AirLoopHVAC PSZ-OFFICE User Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-OFFICE Calculated Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC PSZ-FINE STORAGE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.70615
16 AirLoopHVAC PSZ-FINE STORAGE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.70615
17 AirLoopHVAC PSZ-FINE STORAGE Sum of Air Terminal Maximum Flow Rates [m3/s] 1.70615
18 AirLoopHVAC PSZ-FINE STORAGE Adjusted Heating Design Air Flow Rate [m3/s] 1.70615
19 AirLoopHVAC PSZ-FINE STORAGE Adjusted Cooling Design Air Flow Rate [m3/s] 1.70615
20 AirLoopHVAC PSZ-FINE STORAGE Adjusted Main Design Air Flow Rate [m3/s] 1.70615
21 AirLoopHVAC PSZ-FINE STORAGE User Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-FINE STORAGE Calculated Heating Air Flow Ratio [] 1.00000
23 AirLoopHVAC PSZ-OFFICE Design Supply Air Flow Rate [m3/s] 0.90244
24 AirLoopHVAC PSZ-FINE STORAGE Design Supply Air Flow Rate [m3/s] 1.70615
25 Controller:OutdoorAir PSZ-OFFICE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.90244
26 Controller:OutdoorAir PSZ-OFFICE_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.10228
27 Fan:SystemModel PSZ-OFFICE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.90244
28 Fan:SystemModel PSZ-OFFICE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 999.14953
29 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.90244
30 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.90244
31 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.90244
32 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.90244
33 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.90244
34 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.45122
35 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.60163
36 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 14938.66000
37 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 7469.33000
38 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
39 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
40 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 14938.66000
41 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 23613.95680
42 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
43 AirLoopHVAC:UnitarySystem PSZ-OFFICE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
44 Coil:Heating:Fuel PSZ-OFFICE HEATING COIL Design Size Nominal Capacity [W] 23613.95680
45 Controller:OutdoorAir PSZ-FINE STORAGE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.70615
46 Fan:SystemModel PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.70615
47 Fan:SystemModel PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 1825.66143
48 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.70615
49 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.70615
50 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.70615
51 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.12606
52 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.70615
53 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.85308
54 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.13743
55 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 32887.87000
56 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 16443.93500
57 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.79073
58 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.79073
59 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 32887.87000
60 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 60020.11189
61 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
62 AirLoopHVAC:UnitarySystem PSZ-FINE STORAGE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
63 Coil:Heating:Fuel PSZ-FINE STORAGE HEATING COIL Design Size Nominal Capacity [W] 60020.11189


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-OFFICE COOLING COIL 14238.4     13.09 12.79  
2 Coil:Cooling:DX:MultiSpeed PSZ-FINE STORAGE COOLING COIL 31563.2     12.70 12.41  


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 ZONE1 OFFICE RunPeriod: RUNPERIOD 1 0.1850416847 0.1831419159 Pass Pass 0.8926145885 7.0830587858 Pass Pass
2 ZONE2 FINE STORAGE RunPeriod: RUNPERIOD 1 0.2924340328 0.2712397077 Pass Pass 1.5121899963 6.3875367348 Pass Pass
3 ZONE3 BULK STORAGE RunPeriod: RUNPERIOD 1 1.9565675236E-005 3.8250643173E-005 Pass Pass 5.6786083325E-002 5.4965345504E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 7307.35 325.64 0.00 98.39 59.76 7791.19



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 42.00 35      
Mar 0.00 0      
Apr 0.00 0      
May 40.00 22      
Jun 4.00 8      
Jul 5.00 4      
Aug 7.00 8      
Sep 17.00 10      
Oct 50.00 49      
Nov 69.00 59      
Dec 95.00 53      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
OFFICE FRONT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 110.54 97.44 270.00 90.00 W
OFFICE LEFT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 39.02 30.56 0.00 90.00 N
OFFICE FLOOR OFFICEFLOOR_FFACTOR 1.00 0.133 0.136 236.88 236.88 90.00 180.00  
FINE STORAGE FRONT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 169.07 161.64 270.00 90.00 W
FINE STORAGE RIGHT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 260.10 243.29 180.00 90.00 S
FINE STORAGE LEFT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 182.07 172.69 0.00 90.00 N
FINE STORAGE OFFICE FRONT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 110.54 110.54 270.00 90.00 W
FINE STORAGE OFFICE LEFT WALL NONRES_EXT_WALL_GRD 0.30 0.375 0.397 39.02 39.02 0.00 90.00 N
FINE STORAGE FLOOR FINESTORAGEFLOOR_FFACTOR 1.00 0.056 0.056 1156.53 1156.53 90.00 180.00  
FINE STORAGE ROOF NONRES_ROOF 0.23 0.199 0.204 1393.41 1372.60 90.00 0.00  
BULK STORAGE RIGHT WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.375 0.397 598.24 568.60 180.00 90.00 S
BULK STORAGE REAR WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.375 0.397 390.15 358.48 90.00 90.00 E
BULK STORAGE LEFT WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.375 0.397 598.24 544.27 0.00 90.00 N
BULK STORAGE FLOOR BULKSTORAGEFLOOR_FFACTOR 1.00 0.052 0.053 3204.84 3204.84 90.00 180.00  
BULK STORAGE ROOF SEMIHEATED_ROOF 0.23 0.199 0.204 3204.84 3157.28 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
OFFICE RIGHT WALL INTERIOR WALL 0.30 0.653 0.775 39.02 39.02 180.00 90.00 S
OFFICE REAR WALL INTERIOR WALL 0.30 0.653 0.775 110.54 110.54 90.00 90.00 E
OFFICE ROOF INSULATEDCEILING 0.30 2.711 10.063 236.88 236.88 90.00 0.00  
iz-OFFICE RIGHT WALL iz-INTERIOR WALL 0.30 0.653 0.775 39.02 39.02 0.00 90.00 N
iz-OFFICE REAR WALL iz-INTERIOR WALL 0.30 0.653 0.775 110.54 110.54 270.00 90.00 W
iz-BULK STORAGE FRONT WALL iz-SEMIHEATED_EXT_WALL_GRD 0.30 0.362 0.397 390.15 390.15 270.00 90.00 W
iz-OFFICE ROOF iz-INSULATEDCEILING 0.30 2.711 10.063 236.88 236.88 270.00 180.00  
BULK STORAGE FRONT WALL SEMIHEATED_EXT_WALL_GRD 0.30 0.362 0.397 390.15 390.15 90.00 90.00 E
BULK STORAGE PRODUCTS SURFACE BULK STORAGE PRODUCTS 0.30   0.591 6028.45   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
OFFICE FRONT WALL WINDOW 1 NONRESWINDOW_U_0.3624_SHGC_WEST_0.38   5.58 0.00 0.00 5.58 5.58 2.059 0.381 0.381             No OFFICE FRONT WALL 270.00 90.00 W
OFFICE FRONT WALL WINDOW2 NONRESWINDOW_U_0.3624_SHGC_WEST_0.38   5.58 0.00 0.00 5.58 5.58 2.059 0.381 0.381             No OFFICE FRONT WALL 270.00 90.00 W
OFFICE LEFT WALL WINDOW1 NONRESWINDOW_U_0.3624_SHGC_NORTH_0.38   3.25 0.00 0.00 3.25 3.25 2.059 0.381 0.381             No OFFICE LEFT WALL 0.00 90.00 N
OFFICE LEFT WALL WINDOW2 NONRESWINDOW_U_0.3624_SHGC_NORTH_0.38   3.25 0.00 0.00 3.25 3.25 2.059 0.381 0.381             No OFFICE LEFT WALL 0.00 90.00 N
FINESTORAGE_SKYLIGHT_1 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_6 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_7 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_8 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_9 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_10 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_5 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_4 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_3 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_2 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_14 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_13 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_12 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
FINESTORAGE_SKYLIGHT_11 SKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No FINE STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R1C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R2C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R3C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R4C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R5C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R8C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C1 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C2 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C4 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R6C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
SKYLIGHT_R7C3 SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 SKYLIGHT_FRAME_SEMIHEATED 1.49 0.00 0.00 1.49 1.49 4.262 0.605 0.602 0.000 0.000 CurtainWall 4.099 0.605 0.602 No BULK STORAGE ROOF 180.00 0.00  
Total or Average             86.04 3.810 0.559 0.557                      
North Total or Average             6.51 2.059 0.381 0.381                      
Non-North Total or Average             79.53 3.953 0.573 0.571                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
OFFICE FRONT DOOR SWINGING DOOR_CON 1.598 2.101 1.95 OFFICE FRONT WALL
OFFICE LEFT WALL DOOR SWINGING DOOR_CON 1.598 2.101 1.95 OFFICE LEFT WALL
FINE STORAGE OVERHEAD DOOR1 OVERHEAD DOOR_CON 1.393 1.760 7.43 FINE STORAGE FRONT WALL
FINE STORAGE OVERHEAD DOOR2 OVERHEAD DOOR_CON 1.393 1.760 7.43 FINE STORAGE RIGHT WALL
FINE STORAGE OVERHEAD DOOR3 OVERHEAD DOOR_CON 1.393 1.760 7.43 FINE STORAGE RIGHT WALL
FINE STORAGE RIGHT DOOR SWINGING DOOR_CON 1.598 2.101 1.95 FINE STORAGE RIGHT WALL
FINE STORAGE OVERHEAD DOOR4 OVERHEAD DOOR_CON 1.393 1.760 7.43 FINE STORAGE LEFT WALL
FINE STORAGE LEFT DOOR SWINGING DOOR_CON 1.598 2.101 1.95 FINE STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR8 OVERHEAD DOOR_SEMI 1.393 1.760 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR9 OVERHEAD DOOR_SEMI 1.393 1.760 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR10 OVERHEAD DOOR_SEMI 1.393 1.760 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR11 OVERHEAD DOOR_SEMI 1.393 1.760 5.95 BULK STORAGE RIGHT WALL
BULK STORAGE DOOR1 SWINGING DOOR_SEMI 1.598 2.101 1.95 BULK STORAGE RIGHT WALL
BULK STORAGE DOOR2 SWINGING DOOR_SEMI 1.598 2.101 1.95 BULK STORAGE RIGHT WALL
BULK STORAGE DOOR3 SWINGING DOOR_SEMI 1.598 2.101 1.95 BULK STORAGE RIGHT WALL
BULK STORAGE OVERHEAD DOOR12 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR13 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR14 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR15 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE REAR WALL
BULK STORAGE DOOR4 SWINGING DOOR_SEMI 1.598 2.101 1.95 BULK STORAGE REAR WALL
BULK STORAGE OVERHEAD DOOR1 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR2 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR3 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR4 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR5 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR6 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE OVERHEAD DOOR7 OVERHEAD DOOR_SEMI 1.393 1.760 7.43 BULK STORAGE LEFT WALL
BULK STORAGE DOOR5 SWINGING DOOR_SEMI 1.598 2.101 1.95 BULK STORAGE LEFT WALL


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
OFFICE FRONT WALL WINDOW 1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
OFFICE FRONT WALL WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
OFFICE LEFT WALL WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OFFICE LEFT WALL WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FINESTORAGE_SKYLIGHT_1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_6 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_7 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_8 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_9 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_10 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_14 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_13 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FINESTORAGE_SKYLIGHT_11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R1C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R2C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R3C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R4C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R5C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R8C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R6C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHT_R7C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
OFFICE LIGHTS ZONE1 OFFICE ZONE1 OFFICE GENERAL 6.0858 236.88 1441.60 LightsWired LTG_SCH_OFFICE 47.92 168.00 39.44 0.0000 Y 10.67
FINE STORAGE AREA LIGHTS ZONE2 FINE STORAGE ZONE2 FINE STORAGE GENERAL 6.6844 1393.41 9314.08 LightsWired LTG_SCH_FINE_STORAGE 34.09 168.00 24.45 0.0000 Y 42.75
BULK STORAGE AREA LIGHTS ZONE3 BULK STORAGE ZONE3 BULK STORAGE GENERAL 3.1969 3204.84 10245.50 LightsWired LTG_SCH_BULK_STORAGE 34.09 168.00 22.04 0.0000 Y 42.38
Interior Lighting Total       4.3435 4835.13 21001.18               95.80


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
ZONE2 FINE STORAGE_DAYLREFPT1 ZONE2 FINE STORAGE ZONE2 FINE STORAGE_DAYLCTRL SplitFlux Continuous/Off 0.25 9314.08 2328.52
ZONE2 FINE STORAGE_DAYLREFPT2 ZONE2 FINE STORAGE ZONE2 FINE STORAGE_DAYLCTRL SplitFlux Continuous/Off 0.25 9314.08 2328.52
ZONE3 BULK STORAGE_DAYLREFPT1 ZONE3 BULK STORAGE ZONE3 BULK STORAGE_DAYLCTRL SplitFlux Continuous/Off 0.25 10245.50 2561.37
ZONE3 BULK STORAGE_DAYLREFPT2 ZONE3 BULK STORAGE ZONE3 BULK STORAGE_DAYLCTRL SplitFlux Continuous/Off 0.25 10245.50 2561.37
ZONE1 OFFICE_DAYLREFPT1 ZONE1 OFFICE ZONE1 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.29 1441.60 418.06
ZONE1 OFFICE_DAYLREFPT2 ZONE1 OFFICE ZONE1 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.10 1441.60 144.16


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 93.17 AstronomicalClock -   42.50 42.50 0.74
EXTERIOR_LIGHTS_B 4307.58 AstronomicalClock -   83.54 63.02 50.96
EXTERIOR_LIGHTS_C 1091.85 AstronomicalClock -   83.54 49.88 10.22
Exterior Lighting Total 5492.60           61.92



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed   14938.66 11960.79 2977.87 0.80 4.53    
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed   32887.87 26005.43 6882.44 0.79 4.18    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-OFFICE COOLING COIL   14238.4     13.09 12.79  
PSZ-FINE STORAGE COOLING COIL   31563.2     12.70 12.41  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL Coil:Heating:Fuel   42089.11 0.80
PSZ-OFFICE HEATING COIL Coil:Heating:Fuel   23613.96 0.80
PSZ-FINE STORAGE HEATING COIL Coil:Heating:Fuel   60020.11 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE3UNITHEATER ZONE3HIRADIANT FAN Fan:ConstantVolume 0.54 49.80 1.04 96.57 92.91 1.00 4.11 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-OFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 0.90 999.15 1107.16 1.00 1.43 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Fan:SystemModel 0.58 622.50 1.71 1825.66 1070.05 1.00 1.34 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.08 6154.75 1.00 1.06 0.54



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
ZONE1 OFFICE 9043.98 10852.78 45.82 0.752 0.902 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 23.90 23.90 0.00834 25.25 0.00841 0.102 0.00
ZONE2 FINE STORAGE 21934.74 26321.68 18.89 1.422 1.706 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.70 26.70 0.00850 26.40 0.00841 0.425 0.00
ZONE3 BULK STORAGE 0.00 0.00 0.00 0.000 0.977 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:10:00 0.00 29.41 0.00901 25.34 0.00841 0.977 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
ZONE1 OFFICE 7609.35 9131.22 38.55 0.216 0.259 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.10 21.10 0.00797 -4.30 0.00266 0.102 0.00
ZONE2 FINE STORAGE 17349.77 20819.73 14.94 0.415 0.498 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 15.56 15.56 0.00700 -4.30 0.00266 0.425 0.00
ZONE3 BULK STORAGE 35074.26 42089.11 13.13 0.866 1.039 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 10.00 10.00 0.00564 -4.30 0.00266 0.977 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-OFFICE 0.90 0.90 0.26 0.26 0.9024 0.9024 0.9024 1.0000 1.0000
PSZ-FINE STORAGE 1.71 1.71 0.50 0.50 1.7062 1.7062 1.7062 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL COIL:HEATING:FUEL ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT 42089.111 42089.111 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 42089.11 42089.11 1.039434 10.00 7.69 0.00563815 43.33 22.02 0.00800000 -4.30 0.00265759 -4.30 0.0000 10.00 0.00563815 73.3329 42089.11 0.00 -999.00 -999.00
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-OFFICE 14938.660 11960.788 0.902440 -999.0 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 7469.33 7045.83 0.601627 24.98 16.49 0.00834743 12.00 11.16 0.00800000 25.37 0.00840546 16.68 17.0013 23.90 0.00834000 44.6999 9040.30 0.00 -999.00 -999.00
PSZ-OFFICE HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-OFFICE 23613.957 23613.957 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 23613.96 23613.96 0.902445 18.14 13.05 0.00736938 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 11.3342 21.10 0.00797169 50.6777 7609.35 0.00 -999.00 -999.00
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-FINE STORAGE 32887.870 26005.425 1.706150 -999.0 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 16443.94 15365.13 1.137433 27.50 17.47 0.00847601 12.00 11.16 0.00800000 26.40 0.00840708 17.04 37.3394 26.70 0.00849885 38.5534 21934.74 0.00 -999.00 -999.00
PSZ-FINE STORAGE HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-FINE STORAGE 60020.112 60020.112 -999.0 -999.0 -999.000 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 60020.11 60020.11 1.706150 10.61 8.30 0.00591951 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 24.8930 15.56 0.00700062 63.1116 17349.77 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL COIL:HEATING:FUEL Zone Equipment ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT ZONE3 BULK STORAGE N/A N/A N/A Yes No unknown No 42089.111 42089.111 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ZONE3UNITHEATER ZONE3HIRADIANT FAN Fan:ConstantVolume 1.039434 1.23835242   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 42089.11 42089.11 1.0000 1.23835242 1.039434 10.00 7.69 0.00563815 24252.9 43.33 22.02 0.00800000 64191.6 -999.0 -999.00 -999.00 -999.00 0.000 42089.11 -4.30 0.00265759 -4.30 0.00000000 0.0000 10.00 0.00563815 10.00 0.00563815 73.3329 42089.11 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-OFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-OFFICE ZONE1 OFFICE Coincident CoolingDesignCapacity N/A No No unknown No 14938.660 11960.788 0.902440 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3574 1004.8586 1.1914 PSZ-OFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.902445 1.07514735   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 Sensible 7469.33 7045.83 1.0000 0.71676117 0.601627 24.98 16.49 0.00834743 46361.4 12.00 11.16 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 7469.33 25.37 0.00840546 16.68 0.10228460 17.0013 23.90 0.00834000 23.90 0.00834000 44.6999 9040.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-OFFICE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-OFFICE ZONE1 OFFICE Coincident HeatingDesignCapacity N/A Yes No unknown No 23613.957 23613.957 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 PSZ-OFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.902445 1.07514735   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 09:00:00 Sensible 23613.96 23613.96 1.0000 1.07514735 0.902445 18.14 13.05 0.00736938 36909.5 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 23613.96 -4.30 0.00265759 -4.30 0.10228460 11.3342 21.01 0.00797169 21.10 0.00797169 50.6777 7609.35 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-FINE STORAGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-FINE STORAGE ZONE2 FINE STORAGE Coincident CoolingDesignCapacity N/A No No unknown No 32887.870 26005.425 1.706150 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.5965 1004.8586 1.1914 PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Fan:SystemModel 1.706150 2.03265967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 16443.94 15365.13 1.0000 1.35510624 1.137433 27.50 17.47 0.00847601 49269.1 12.00 11.16 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 16443.94 26.40 0.00840708 17.04 0.42471127 37.3394 26.70 0.00849885 26.70 0.00849885 38.5534 21934.74 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-FINE STORAGE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-FINE STORAGE ZONE2 FINE STORAGE Coincident HeatingDesignCapacity N/A Yes No unknown No 60020.112 60020.112 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 PSZ-FINE STORAGE_ADDAQ SUPPLY FAN Fan:SystemModel 1.706150 2.03265967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 06:00:00 Sensible 60020.11 60020.11 1.0000 2.03265967 1.706150 10.61 8.30 0.00591951 25587.4 40.00 21.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 60020.11 -4.30 0.00265759 -4.30 0.42471127 24.8930 15.56 0.00700062 15.56 0.00700062 63.1116 17349.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PSZ-FINE STORAGE_OA_CONTROLLER DifferentialDryBulb 0.00 1.71 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
ZONE2 FINE STORAGE ZONE2_FINE_STORAGE_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
ZONE1 OFFICE 2237.00 3269.00 2117.00
ZONE2 FINE STORAGE 2712.00 3199.00 2376.83
ZONE3 BULK STORAGE 2745.00 3552.50 2696.67
Facility 3046.17 3563.00 2707.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
ZONE1 OFFICE 15.17 0.00 11.67 0.00
ZONE2 FINE STORAGE 142.83 0.50 9.17 0.00
ZONE3 BULK STORAGE 0.00 0.00 0.00 0.00
Facility 156.17 0.50 19.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
ZONE1 OFFICE 9.48 12.75 1010.76 0.340 0.384 0.000 0.000
ZONE2 FINE STORAGE 22.30 30.00 2953.02 0.434 0.135 0.000 0.000
ZONE3 BULK STORAGE 51.30 69.00 35277.63 0.000 0.083 0.000 0.031
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
ZONE1 OFFICE 9.48 12.75 1010.76 0.000 0.000 0.000 0.000
ZONE2 FINE STORAGE 22.30 30.00 2953.02 0.000 0.000 0.000 0.000
ZONE3 BULK STORAGE 51.30 69.00 35277.63 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
ZONE1 OFFICE PSZ-OFFICE 9.48 12.75 1010.76 236.88 0.1023 0.072
ZONE2 FINE STORAGE PSZ-FINE STORAGE 22.30 30.00 2953.02 1393.41 0.4247 0.425
ZONE3 BULK STORAGE   51.30 69.00 35277.63 3204.84   0.977
Total Facility   83.08 111.75 39241.41 4835.13 0.5270 1.474


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
ZONE1 OFFICE 1235564.58 0.00 1235564.58 1841204.07 3076768.64 2577844.23 5421.16 2424.11 914.73 46.15
ZONE2 FINE STORAGE 4651047.02 0.00 4651047.02 3862596.58 8513643.60 13393694.68 5729.34 3014.17 16.49 1.16
ZONE3 BULK STORAGE 0.00 9256655.69 9256655.69 22204480.09 31461135.78 30805497.77 8693.33 7.17 59.50 4172.83
Total Facility 5886611.60 9256655.69 15143267.29 27908280.74 43051548.03 46777036.68 8717.17 3030.44 977.55 4175.69


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
ZONE1 OFFICE 0.0943 0.0000 0.0943 0.1068 0.2011 0.0952 297.16 2424.11 914.73
ZONE2 FINE STORAGE 0.3551 0.0000 0.3551 0.1100 0.4651 0.4247 606.00 3014.17 15.83
ZONE3 BULK STORAGE 0.0000 0.3089 0.3089 0.8217 1.1307 0.9768 3592.00 4.50 39.50
Total Facility 0.4494 0.3089 0.7584 1.0386 1.7969 1.4967 3593.17 3027.78 956.89


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-OFFICE 1753719.92 0.00 1753719.92 2577844.23 5420.48 0.14 3339.39 44.07
PSZ-FINE STORAGE 6601448.07 0.00 6601448.07 13393694.68 5729.34 0.00 3030.66 1.16


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-OFFICE 0.1338 0.0000 0.1338 0.0952 296.48 0.14 3339.39
PSZ-FINE STORAGE 0.5041 0.0000 0.5041 0.4247 606.00 0.00 3030.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-OFFICE 0.00 3458.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-FINE STORAGE 0.00 8.16 11.17 0.00 0.00 0.00 3011.83 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-OFFICE 0.0000 0.1425 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-FINE STORAGE 0.0000 1.1987 0.8848 0.0000 0.0000 0.0000 0.6030 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Surfaces by Class

Total Outdoors
Wall 16 10
Floor 4 3
Roof 3 2
Internal Mass 1 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 50 50
Door 28 28
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 3
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 430
Defaulted Fields 389
Fields with Defaults 1172
Autosized Fields 42
Autosizable Fields 97
Autocalculated Fields 128
Autocalculatable Fields 206



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
Electricity:Building 232.31 1123.07 16-APR-13:50 19987.84 25-NOV-15:30
Electricity:Zone:ZONE1 OFFICE 39.84 585.18 19-FEB-15:30 2643.62 02-JAN-08:10
Electricity:SpaceType:GENERAL 232.31 1123.07 16-APR-13:50 19987.84 25-NOV-15:30
InteriorLights:Electricity 95.80 653.19 16-APR-13:50 9952.67 25-NOV-15:30
InteriorLights:Electricity:Zone:ZONE1 OFFICE 10.67 115.30 19-FEB-15:30 808.57 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 95.80 653.19 16-APR-13:50 9952.67 25-NOV-15:30
LightsWired:InteriorLights:Electricity 95.80 653.19 16-APR-13:50 9952.67 25-NOV-15:30
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE 10.67 115.30 19-FEB-15:30 808.57 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 95.80 653.19 16-APR-13:50 9952.67 25-NOV-15:30
Electricity:Zone:ZONE2 FINE STORAGE 42.75 256.14 12-FEB-11:50 4354.33 25-NOV-15:30
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE 42.75 256.14 12-FEB-11:50 4354.33 25-NOV-15:30
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE 42.75 256.14 12-FEB-11:50 4354.33 25-NOV-15:30
Electricity:Zone:ZONE3 BULK STORAGE 149.73 281.75 01-JAN-12:20 12989.89 25-NOV-15:30
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE 42.38 281.75 01-JAN-12:20 4789.77 25-NOV-15:30
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE 42.38 281.75 01-JAN-12:20 4789.77 25-NOV-15:30
InteriorEquipment:Electricity 136.51 469.88 01-JAN-00:10 10035.17 02-JAN-08:10
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE 29.16 469.88 01-JAN-00:10 1835.05 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 136.51 469.88 01-JAN-00:10 10035.17 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 136.51 469.88 01-JAN-00:10 10035.17 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE 29.16 469.88 01-JAN-00:10 1835.05 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 136.51 469.88 01-JAN-00:10 10035.17 02-JAN-08:10
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE 107.34 0.00 01-JAN-00:10 8200.12 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE 107.34 0.00 01-JAN-00:10 8200.12 02-JAN-08:10
Fans:Electricity 22.75 0.00 04-JAN-18:10 2225.44 10-JAN-18:00
Fans:Electricity:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
ElectricityPurchased:Plant 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
Cogeneration:ElectricityPurchased 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
General:Cogeneration:ElectricityPurchased 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
ElectricityNet:Plant 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
Cogeneration:ElectricityNet 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
General:Cogeneration:ElectricityNet 344.59 1606.07 16-APR-13:50 28158.46 30-DEC-08:10
Electricity:HVAC 24.31 0.00 04-JAN-18:10 5750.95 22-JUL-15:10
General:Fans:Electricity 22.75 0.00 04-JAN-18:10 2225.44 10-JAN-18:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1.57 0.00 01-JAN-00:10 4021.54 22-JUL-15:10
General:Cooling:Electricity 1.57 0.00 01-JAN-00:10 4021.54 22-JUL-15:10
ExteriorLights:Electricity 61.92 0.00 01-JAN-08:20 5492.60 01-JAN-06:10
General:ExteriorLights:Electricity 61.92 0.00 01-JAN-08:20 5492.60 01-JAN-06:10
Electricity:Plant 26.05 483.00 01-JAN-00:10 2416.95 14-FEB-12:10
WaterSystems:Electricity 26.05 483.00 01-JAN-00:10 2416.95 14-FEB-12:10
Water Heater:WaterSystems:Electricity 26.05 483.00 01-JAN-00:10 2416.95 14-FEB-12:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 175.80 0.00 04-JAN-18:10 93682.66 10-JAN-18:00
NaturalGas:HVAC 175.80 0.00 04-JAN-18:10 93682.66 10-JAN-18:00
Heating:NaturalGas 175.80 0.00 04-JAN-18:10 93682.66 10-JAN-18:00
General:Heating:NaturalGas 175.80 0.00 04-JAN-18:10 93682.66 10-JAN-18:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 51.61 0.00 02-JAN-00:10 0.00 02-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 280.30 0.00 04-JAN-18:10 131507.64 28-DEC-07:10
EnergyTransfer:Building 146.31 0.00 04-JAN-18:10 65510.08 28-DEC-07:10
EnergyTransfer:Zone:ZONE1 OFFICE 32.70 0.00 01-JAN-00:10 18424.44 10-JAN-07:10
Heating:EnergyTransfer 113.54 0.00 04-JAN-18:10 65510.08 28-DEC-07:10
Heating:EnergyTransfer:Zone:ZONE1 OFFICE 25.98 0.00 01-JAN-00:10 18424.44 10-JAN-07:10
General:Heating:EnergyTransfer 113.54 0.00 04-JAN-18:10 65510.08 28-DEC-07:10
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE 25.98 0.00 01-JAN-00:10 18424.44 10-JAN-07:10
Cooling:EnergyTransfer 32.76 0.00 01-JAN-00:10 15262.71 22-JUL-15:10
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE 6.71 0.00 01-JAN-00:10 7035.64 22-JUL-07:10
General:Cooling:EnergyTransfer 32.76 0.00 01-JAN-00:10 15262.71 22-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE 6.71 0.00 01-JAN-00:10 7035.64 22-JUL-07:10
EnergyTransfer:Zone:ZONE2 FINE STORAGE 74.25 0.00 01-JAN-00:10 21381.99 29-DEC-20:50
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE 48.20 0.00 01-JAN-00:10 21381.99 29-DEC-20:50
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE 48.20 0.00 01-JAN-00:10 21381.99 29-DEC-20:50
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE 26.05 0.00 01-JAN-00:10 10941.10 23-JUL-11:10
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE 26.05 0.00 01-JAN-00:10 10941.10 23-JUL-11:10
EnergyTransfer:Zone:ZONE3 BULK STORAGE 39.36 0.00 02-JAN-08:10 37877.37 30-DEC-01:00
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE 39.36 0.00 02-JAN-08:10 37877.37 30-DEC-01:00
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE 39.36 0.00 02-JAN-08:10 37877.37 30-DEC-01:00
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:HVAC 133.99 0.00 04-JAN-18:10 70548.49 10-JAN-18:00
HeatingCoils:EnergyTransfer 125.80 0.00 04-JAN-18:10 70548.49 10-JAN-18:00
CoolingCoils:EnergyTransfer 8.19 0.00 01-JAN-00:10 19027.62 22-JUL-15:10
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
ZONE1 OFFICE 0.000 0.000 25.984 -6.714 0.000 0.000 10.238 10.672 29.165 9.870 0.000 0.020 0.000 0.000 -6.994 0.000 -24.140 -48.100
ZONE2 FINE STORAGE 0.000 0.000 48.196 -26.051 0.000 0.000 27.622 42.747 0.000 43.377 0.000 0.010 0.001 0.000 -16.752 0.000 -41.605 -77.543
ZONE3 BULK STORAGE 39.362 0.000 0.000 0.000 0.000 0.000 69.580 42.382 107.344 424.373 0.000 0.753 0.002 0.000 -119.360 0.000 -231.271 -333.163
Total Facility 39.362 0.000 74.180 -32.765 0.000 0.000 107.440 95.800 136.508 477.619 0.000 0.783 0.002 0.000 -143.106 0.000 -297.017 -458.806


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
ZONE1 OFFICE 22-JUL-07:02 0.00 0.00 0.00 -13784.79 0.00 0.00 801.54 643.05 1835.05 379.71 0.00 0.00 10147.94 0.00 -0.00 0.00 -22.51 0.00
ZONE2 FINE STORAGE 22-JUL-17:20 0.00 0.00 0.00 -22508.60 0.00 0.00 0.00 358.08 0.00 3373.95 0.00 304.05 18472.52 0.00 -0.00 0.00 0.00 0.00
ZONE3 BULK STORAGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 22-JUL-17:20 0.00 0.00 0.00 -22508.60 0.00 0.00 0.00 790.72 2519.91 78626.05 0.00 3257.10 0.00 0.00 0.00 0.00 0.00 -62685.19


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
ZONE1 OFFICE 20-OCT-06:01 0.00 0.00 23083.78 0.00 0.00 0.00 268.12 441.04 917.53 0.00 0.00 0.00 0.00 0.00 -213.52 0.00 -2638.60 -21858.34
ZONE2 FINE STORAGE 28-NOV-06:01 0.00 0.00 60596.71 0.00 0.00 0.00 361.13 512.27 0.00 0.00 0.00 0.00 0.00 0.00 -1234.99 0.00 -4494.91 -55740.23
ZONE3 BULK STORAGE 30-DEC-01:00 37876.86 0.00 0.00 0.00 0.00 0.00 0.00 563.50 2050.03 0.00 0.00 0.00 0.00 0.00 -7809.56 0.00 -25720.60 -6960.23
Total Facility 10-JAN-06:01 34590.23 0.00 81902.87 0.00 0.00 0.00 1427.96 1317.30 2600.55 0.00 0.00 0.00 0.00 0.00 -16350.21 0.00 -27595.29 -77893.41



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-OFFICE 0.9024 0.0000 12.7487 1.0000 Calculated from schedules 0.1023 0.9024 0.1133 1.0000 Not calculated 0.1023 0.1133    
PSZ-FINE STORAGE 1.7062 0.0000 30.0000 1.0000 Calculated from schedules 0.4247 1.7062 0.2489 1.0000 Not calculated 0.4247 0.2489    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-OFFICE 0.9024 0.0000 12.7487 1.0000 Calculated from schedules 0.1023 0.9024 1.0000 1.0000 Not calculated 0.1023 0.1133    
PSZ-FINE STORAGE 1.7062 0.0000 30.0000 1.0000 Calculated from schedules 0.4247 1.7062 1.0000 1.0000 Not calculated 0.4247 0.2489    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
ZONE1 OFFICE PSZ-OFFICE 0.002360 12.7487 0.000305 236.88 0.1023 1.0000 0.1023 1.000 0.1023
ZONE2 FINE STORAGE PSZ-FINE STORAGE 0.000000 30.0000 0.000305 1393.41 0.4247 1.0000 0.4247 1.000 0.4247


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-OFFICE 0.002360 12.75 0.000305 236.8796 0.1023 0.1023 0.1023
PSZ-FINE STORAGE 0.000000 30.00 0.000305 1393.4097 0.4247 0.4247 0.4247


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
ZONE1 OFFICE PSZ-OFFICE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.9024 0.9024 0.9024 No 0.1023 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ZONE2 FINE STORAGE PSZ-FINE STORAGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.7062 1.7062 1.7062 No 0.4247 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-OFFICE 0.9024 0.9024 0.9024 0.9024 0.1023 1.0000
PSZ-FINE STORAGE 1.7062 1.7062 1.7062 1.7062 0.4247 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
ZONE1 OFFICE PSZ-OFFICE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.9024 0.9024 0.9024 No 0.1023 0.3951 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ZONE2 FINE STORAGE PSZ-FINE STORAGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.7062 1.7062 1.7062 No 0.4247 0.8536 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-OFFICE 0.9024 0.9024 0.9024 0.9024 0.1023 1.0000
PSZ-FINE STORAGE 1.7062 1.7062 1.7062 1.7062 0.4247 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Total gross floor area [m2] 4835.13
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
ZONE1 OFFICE 236.88 236.88 0.00 69.73
ZONE2 FINE STORAGE 1393.41 1393.41 0.00 69.73
ZONE3 BULK STORAGE 3204.84 3204.84 0.00 69.73
Totals 4835.13 4835.13 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 19.00
Number of hours cooling loads not met 0.00
Number of hours not met 19.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 175.80 93682.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1.57 4021.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 95.80 9952.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 61.92 5492.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 136.51 10035.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 22.75 2225.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 26.05 2416.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 136.51 344.59
Natural Gas 0.00 175.80
Additional 0.00 0.00
Total 136.51 520.39


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 19.81
Space Heating 0.00
Space Cooling 0.32
Fans (All) 4.70
Service Water Heating 5.39
Receptacle Equipment 28.23
Miscellaneous (All) 71.27
Subtotal 71.27


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 36.36
Service Water Heating 0.00
Miscellaneous (All) 36.36
Subtotal 36.36


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 18.41
Space Heating 33.78
Space Cooling 0.30
Fans (All) 4.37
Service Water Heating 5.01
Receptacle Equipment 26.23
Miscellaneous 11.90


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2499. 8760.
LTG_SCH_BULK_STORAGE 1777. 8760.
LTG_SCH_FINE_STORAGE 1777. 8760.
OFFICE_PLUG_SCH 4298. 8760.
BULK STORAGE PLUG SCHEDULE 3744. 7488.
BLDG_OCC_SCH 2861. 3744.
OFFICE PEOPLE SCHEDULE 2861. 3744.
FANSCHED 3432. 3432.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
OFFICE DHW SCHEDULE 1825. 5016.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 5550. 8760.
EXTERIOR LIGHT SCHEDULE 5475. 5475.
ALWAYS OFF SCHEDULE 0. 0.
OA DAMPER OFF DURING OFF HRS SCHEDULE 2808. 2808.
OA DAMPER ALWAYS ON SCHEDULE 8760. 8760.
MINOA_SCHED 8760. 8760.
ALWAYS ON SCHEDULE 8760. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
INFIL_DOOR_OPENING_SCH 1154. 3380.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 2600. 2600.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6935. 8760.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6132. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
BULK STORAGE HEATING SETPOINT SCHEDULE ZONE3 BULK STORAGE HEATING SP January 10.00 365 10.00 365
OFFICE HEATING SCHEDULE ZONE1 OFFICE DUAL SP CONTROL January 21.10 365 15.60 365
OFFICE COOLING SCHEDULE ZONE1 OFFICE DUAL SP CONTROL July 23.90 365 29.40 365
FINE STORAGE HEATING SETPOINT SCHEDULE ZONE2 FINE STORAGE DUAL SP CONTROL January 15.56 365 15.56 365
FINE STORAGE COOLING SETPOINT SCHEDULE ZONE2 FINE STORAGE DUAL SP CONTROL July 26.70 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
ZONE1 OFFICE 8743.33 16.67 0.00 0.00 0.00
ZONE2 FINE STORAGE 8737.33 22.67 0.00 0.00 0.00
ZONE3 BULK STORAGE 8760.00 0.00 0.00 0.00 0.00
Min 8737.33 0.00 0.00 0.00 0.00
Max 8760.00 22.67 0.00 0.00 0.00
Average 8746.89 13.11 0.00 0.00 0.00
Sum 26240.67 39.33 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
ZONE1 OFFICE 33027.00 0.00 0.00 0.00 0.00
ZONE2 FINE STORAGE 82294.00 425.00 0.00 0.00 0.00
ZONE3 BULK STORAGE 191193.00 0.00 0.00 0.00 0.00
Min 33027.00 0.00 0.00 0.00 0.00
Max 191193.00 425.00 0.00 0.00 0.00
Average 102171.33 141.67 0.00 0.00 0.00
Sum 306514.00 425.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
ZONE1 OFFICE 8738.17 21.83 0.00 0.00 0.00
ZONE2 FINE STORAGE 8654.83 105.17 0.00 0.00 0.00
ZONE3 BULK STORAGE 8760.00 0.00 0.00 0.00 0.00
Min 8654.83 0.00 0.00 0.00 0.00
Max 8760.00 105.17 0.00 0.00 0.00
Average 8717.67 42.33 0.00 0.00 0.00
Sum 26153.00 127.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
ZONE1 OFFICE 33027.00 0.00 0.00 0.00 0.00
ZONE2 FINE STORAGE 80280.00 2439.00 0.00 0.00 0.00
ZONE3 BULK STORAGE 191193.00 0.00 0.00 0.00 0.00
Min 33027.00 0.00 0.00 0.00 0.00
Max 191193.00 2439.00 0.00 0.00 0.00
Average 101500.00 813.00 0.00 0.00 0.00
Sum 304500.00 2439.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 10:44:06

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
ZONE1 OFFICE 0.00 0.00 8760.00 0.00
ZONE2 FINE STORAGE 0.00 0.00 8760.00 0.00
ZONE3 BULK STORAGE 0.00 8760.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 8760.00 0.00
Average 0.00 2920.00 5840.00 0.00
Sum 0.00 8760.00 17520.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
ZONE1 OFFICE 0.00 0.00 33027.00 0.00
ZONE2 FINE STORAGE 0.00 0.00 82719.00 0.00
ZONE3 BULK STORAGE 0.00 191193.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 191193.00 82719.00 0.00
Average 0.00 63731.00 38582.00 0.00
Sum 0.00 191193.00 115746.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8467206.82 1932.17 09-JAN-08:05 -2.0 -2.5 0.492188E+09 603.59 28-JAN-08:20 7.03 6.45
February 7712024.04 2042.26 17-FEB-08:05 -2.3 -2.4 0.452810E+09 603.30 01-FEB-08:20 -2.3 -2.4
March 8312854.28 1708.39 25-MAR-06:05 1.17 0.75 0.531622E+09 606.95 25-MAR-13:30 13.00 10.25
April 0.171460E+09 2740.55 29-APR-15:50 20.00 12.39 0.520308E+09 768.97 29-APR-15:20 20.00 12.39
May 0.376913E+09 2568.32 25-MAY-16:00 18.00 13.90 0.562461E+09 768.99 23-MAY-15:09 18.00 13.90
June 0.117623E+10 5138.01 13-JUN-16:00 26.50 17.70 0.631648E+09 768.99 27-JUN-08:00 13.00 13.00
July 0.197412E+10 13784.46 22-JUL-07:02 23.17 16.28 0.625913E+09 879.38 22-JUL-07:10 23.17 16.28
August 0.208398E+10 4901.88 14-AUG-16:00 26.00 15.86 0.678648E+09 779.77 19-AUG-07:10 12.67 11.93
September 0.831492E+09 3616.26 13-SEP-16:00 23.00 16.22 0.606380E+09 768.99 12-SEP-14:09 23.00 16.22
October 59091836.41 1704.95 07-OCT-06:05 3.00 2.93 0.508917E+09 768.96 07-OCT-15:00 18.00 9.66
November 7383065.37 1795.64 29-NOV-08:05 -0.7 -1.6 0.472541E+09 603.89 09-NOV-08:20 -0.7 -1.6
December 8483389.13 1819.55 27-DEC-08:05 -1.0 -1.4 0.492130E+09 603.50 02-DEC-08:20 -1.0 -1.4
                     
Annual Sum or Average 0.671365E+10         0.657557E+10        
Minimum of Months 7383065.37 1704.95   -2.3 -2.5 0.452810E+09 603.30   -2.3 -2.4
Maximum of Months 0.208398E+10 13784.46   26.50 17.70 0.678648E+09 879.38   23.17 16.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.129713E+10 6381.52 09-JAN-15:45 1.00 -1.0 0.662029E+09 926.52 19-JAN-15:20 8.67 7.45
February 0.175964E+10 4954.82 23-FEB-15:30 4.50 4.26 0.609040E+09 921.34 27-FEB-16:10 8.00 6.56
March 0.229921E+10 4709.02 14-MAR-14:00 5.00 2.42 0.730246E+09 1019.12 25-MAR-13:20 13.33 10.57
April 0.263765E+10 5919.85 08-APR-07:03 2.50 1.05 0.913449E+09 1822.89 29-APR-15:09 20.00 12.69
May 0.307650E+10 5931.16 01-MAY-15:00 8.00 6.98 0.106785E+10 1831.36 23-MAY-14:30 18.50 14.58
June 0.293844E+10 5321.49 07-JUN-10:00 7.00 6.47 0.139088E+10 2246.81 13-JUN-14:30 25.55 17.64
July 0.296350E+10 22508.90 22-JUL-17:20 29.33 16.65 0.151978E+10 2246.82 22-JUL-10:30 29.33 16.65
August 0.236646E+10 4499.66 19-AUG-07:10 12.67 11.93 0.165779E+10 2246.80 14-AUG-15:50 12.67 11.93
September 0.207181E+10 5453.21 28-SEP-07:03 8.17 7.16 0.126978E+10 2041.29 13-SEP-15:09 8.17 7.16
October 0.206826E+10 5963.72 06-OCT-07:03 3.83 3.69 0.822474E+09 1477.99 07-OCT-15:20 18.67 9.96
November 0.174922E+10 4467.56 29-NOV-14:40 4.67 3.06 0.649419E+09 1000.86 10-NOV-14:30 4.67 3.06
December 0.822733E+09 3851.25 08-DEC-11:30 6.50 4.42 0.651184E+09 839.84 21-DEC-14:50 8.00 6.98
                     
Annual Sum or Average 0.260506E+11         0.119439E+11        
Minimum of Months 0.822733E+09 3851.25   1.00 -1.0 0.609040E+09 839.84   4.67 3.06
Maximum of Months 0.307650E+10 22508.90   29.33 16.65 0.165779E+10 2246.82   29.33 17.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92 1.45 0.789431E+09 1191.48 19-JAN-15:50 8.17 7.46
February 0.00 0.00 01-FEB-00:05 7.00 5.79 0.744556E+09 1169.09 04-FEB-14:00 9.00 6.57
March 0.00 0.00 01-MAR-00:05 3.80 3.71 0.100616E+10 1525.10 25-MAR-13:39 12.67 9.93
April 0.00 0.00 01-APR-00:05 4.23 1.84 0.163114E+10 3204.04 29-APR-15:50 20.00 12.39
May 0.00 0.00 01-MAY-00:10 10.47 8.15 0.198804E+10 3061.95 26-MAY-15:30 15.00 12.39
June 0.00 0.00 01-JUN-00:10 9.27 7.39 0.264028E+10 4200.10 26-JUN-15:30 22.50 17.36
July 0.00 0.00 01-JUL-00:10 11.00 9.95 0.306858E+10 5003.61 22-JUL-15:50 29.00 16.64
August 0.00 0.00 01-AUG-00:10 11.43 9.82 0.348009E+10 4514.05 21-AUG-13:00 21.00 15.01
September 0.00 0.00 01-SEP-00:10 12.43 10.95 0.266293E+10 3928.27 13-SEP-15:50 23.00 16.22
October 0.00 0.00 01-OCT-00:10 7.57 5.83 0.171788E+10 2936.98 07-OCT-15:39 18.33 9.81
November 0.00 0.00 01-NOV-00:05 6.57 4.29 0.964284E+09 1616.57 10-NOV-14:00 12.00 8.42
December 0.00 0.00 01-DEC-00:05 4.00 3.53 0.726948E+09 1055.80 02-DEC-14:50 9.00 7.93
                     
Annual Sum or Average 0.00         0.214203E+11        
Minimum of Months 0.00 0.00   1.92 1.45 0.726948E+09 1055.80   8.17 6.57
Maximum of Months 0.00 0.00   12.43 10.95 0.348009E+10 5003.61   29.00 17.36



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.474510E+10 22684.41 17-JAN-06:01 6.07
February 0.395137E+10 22668.11 27-FEB-06:01 6.00
March 0.411262E+10 22765.45 18-MAR-06:01 9.00
April 0.143527E+10 22677.62 10-APR-06:01 7.17
May 0.866550E+09 22865.56 19-MAY-06:01 9.00
June 0.147139E+09 22210.84 08-JUN-06:02 7.50
July 51811386.63 9392.52 03-JUL-07:03 13.17
August 40231283.09 3992.51 31-AUG-07:03 13.00
September 0.216043E+09 10560.78 07-SEP-07:03 10.33
October 0.182056E+10 23083.33 20-OCT-06:01 11.17
November 0.363565E+10 22899.99 24-NOV-07:02 11.00
December 0.496221E+10 22498.27 05-DEC-07:01 6.00
         
Annual Sum or Average 0.259846E+11      
Minimum of Months 40231283.09 3992.51   6.00
Maximum of Months 0.496221E+10 23083.33   13.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103830E+11 60415.69 10-JAN-06:01 -4.0
February 0.904161E+10 60228.02 17-FEB-04:13 -2.0
March 0.600145E+10 45344.75 27-MAR-05:01 0.83
April 0.491658E+09 39714.93 03-APR-06:01 3.17
May 61506636.47 765.25 30-MAY-07:00 8.00
June 55703430.01 763.04 28-JUN-07:00 11.00
July 55249516.84 784.29 11-JUL-06:50 12.83
August 60760030.25 779.06 19-AUG-07:00 12.00
September 55651471.14 764.91 27-SEP-06:50 9.67
October 0.126980E+10 44323.24 24-OCT-06:01 6.00
November 0.705290E+10 60596.75 28-NOV-06:01 1.00
December 0.136673E+11 60573.67 27-DEC-06:01 -2.0
         
Annual Sum or Average 0.481966E+11      
Minimum of Months 55249516.84 763.04   -4.0
Maximum of Months 0.136673E+11 60596.75   12.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107137E+11 36436.91 10-JAN-05:53 -4.0
February 0.604908E+10 24902.68 19-FEB-22:00 0.00
March 0.449616E+09 12260.17 04-MAR-06:00 3.00
April 0.00 0.00 01-APR-00:05 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.199874E+10 22837.53 29-NOV-03:57 -1.0
December 0.201513E+11 37877.37 30-DEC-01:00 -2.0
         
Annual Sum or Average 0.393624E+11      
Minimum of Months 0.00 0.00   -4.0
Maximum of Months 0.201513E+11 37877.37   12.43



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.980074E+09 808.57 02-JAN-08:09 0.244223E+10 1835.05 02-JAN-08:09
February 0.851766E+09 802.15 01-FEB-08:09 0.222575E+10 1835.05 01-FEB-08:09
March 0.945990E+09 791.35 15-MAR-07:10 0.253693E+10 1835.05 01-MAR-08:09
April 0.824659E+09 777.78 10-APR-07:10 0.240164E+10 1835.05 01-APR-07:10
May 0.838121E+09 730.74 04-MAY-07:10 0.248958E+10 1835.05 01-MAY-07:10
June 0.810937E+09 702.41 14-JUN-07:10 0.244899E+10 1835.05 01-JUN-07:10
July 0.815069E+09 727.73 07-JUL-07:30 0.244223E+10 1835.05 01-JUL-07:10
August 0.869111E+09 763.56 22-AUG-07:30 0.253693E+10 1835.05 01-AUG-07:10
September 0.851074E+09 770.28 08-SEP-07:30 0.240164E+10 1835.05 01-SEP-07:10
October 0.924788E+09 807.98 31-OCT-07:10 0.244223E+10 1835.05 02-OCT-07:10
November 0.944915E+09 808.57 06-NOV-16:49 0.235429E+10 1835.05 01-NOV-07:10
December 0.101521E+10 808.57 01-DEC-15:30 0.244223E+10 1835.05 01-DEC-08:09
             
Annual Sum or Average 0.106717E+11     0.291647E+11    
Minimum of Months 0.810937E+09 702.41   0.222575E+10 1835.05  
Maximum of Months 0.101521E+10 808.57   0.253693E+10 1835.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.424560E+10 4261.55 03-JAN-15:00 0.00 0.00
February 0.355283E+10 4025.10 01-FEB-09:09 0.00 0.00
March 0.367680E+10 3854.24 15-MAR-08:09 0.00 0.00
April 0.315252E+10 3675.14 10-APR-08:09 0.00 0.00
May 0.312555E+10 3233.92 05-MAY-08:09 0.00 0.00
June 0.302965E+10 3126.79 01-JUN-08:09 0.00 0.00
July 0.301208E+10 3239.24 21-JUL-08:09 0.00 0.00
August 0.332386E+10 3606.33 08-AUG-08:09 0.00 0.00
September 0.338306E+10 3775.84 27-SEP-08:09 0.00 0.00
October 0.377380E+10 4085.91 31-OCT-08:09 0.00 0.00
November 0.404615E+10 4354.33 25-NOV-15:30 0.00 0.00
December 0.442512E+10 4354.33 01-DEC-15:30 0.00 0.00
           
Annual Sum or Average 0.427470E+11     0.00 0.00
Minimum of Months 0.301208E+10 3126.79   0.00 0.00
Maximum of Months 0.442512E+10 4354.33   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.419121E+10 4606.47 03-JAN-15:00 0.885613E+10 8200.12 02-JAN-08:09
February 0.345666E+10 4122.90 01-FEB-09:09 0.814764E+10 8200.12 01-FEB-08:09
March 0.359492E+10 3878.74 15-MAR-07:10 0.957200E+10 8200.12 01-MAR-08:09
April 0.314225E+10 3597.46 10-APR-07:10 0.885613E+10 8200.12 01-APR-07:10
May 0.314205E+10 2857.11 01-MAY-06:10 0.921037E+10 8200.12 01-MAY-07:10
June 0.306733E+10 2821.26 17-JUN-06:10 0.921037E+10 8200.12 01-JUN-07:10
July 0.303599E+10 2648.26 25-JUL-06:10 0.885613E+10 8200.12 01-JUL-07:10
August 0.330386E+10 3306.84 22-AUG-07:30 0.956462E+10 8200.12 01-AUG-07:10
September 0.329082E+10 3580.13 27-SEP-07:10 0.884875E+10 8200.12 01-SEP-07:10
October 0.367716E+10 4246.73 31-OCT-08:09 0.886351E+10 8200.12 02-OCT-07:10
November 0.398582E+10 4789.77 25-NOV-15:30 0.850188E+10 8200.12 01-NOV-07:10
December 0.449370E+10 4789.77 01-DEC-15:30 0.885613E+10 8200.12 01-DEC-08:09
             
Annual Sum or Average 0.423818E+11     0.107344E+12    
Minimum of Months 0.303599E+10 2648.26   0.814764E+10 8200.12  
Maximum of Months 0.449370E+10 4789.77   0.957200E+10 8200.12  



Table of Contents

Report: SpaceGainsMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.138726E+10 0.980074E+09 0.244223E+10 0.00 0.00 0.00 0.00 0.00 0.238564E+10
February 0.127628E+10 0.851766E+09 0.222575E+10 0.00 0.00 0.00 0.00 0.00 0.221701E+10
March 0.149825E+10 0.945990E+09 0.253693E+10 0.00 0.00 0.00 0.00 0.00 0.225961E+10
April 0.138726E+10 0.824659E+09 0.240164E+10 0.00 0.00 0.00 0.00 0.00 0.165630E+10
May 0.144276E+10 0.838121E+09 0.248958E+10 0.00 0.00 0.00 0.00 3690.07 0.231155E+10
June 0.144276E+10 0.810937E+09 0.244899E+10 0.00 0.00 0.00 0.00 4286684.55 0.186148E+10
July 0.138726E+10 0.815069E+09 0.244223E+10 0.00 0.00 0.00 0.00 12137654.60 0.160585E+10
August 0.149825E+10 0.869111E+09 0.253693E+10 0.00 0.00 0.00 0.00 3299748.89 0.146775E+10
September 0.138726E+10 0.851074E+09 0.240164E+10 0.00 0.00 0.00 0.00 0.00 0.146599E+10
October 0.138726E+10 0.924788E+09 0.244223E+10 0.00 0.00 0.00 0.00 0.00 0.179785E+10
November 0.133177E+10 0.944915E+09 0.235429E+10 0.00 0.00 0.00 0.00 0.00 0.230844E+10
December 0.138726E+10 0.101521E+10 0.244223E+10 0.00 0.00 0.00 0.00 0.00 0.280270E+10
                   
Annual Sum or Average 0.168137E+11 0.106717E+11 0.291647E+11 0.00 0.00 0.00 0.00 19727778.11 0.241402E+11
Minimum of Months 0.127628E+10 0.810937E+09 0.222575E+10 0.00 0.00 0.00 0.00 0.00 0.146599E+10
Maximum of Months 0.149825E+10 0.101521E+10 0.253693E+10 0.00 0.00 0.00 0.00 12137654.60 0.280270E+10



Table of Contents

Report: SpaceGainsMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.326447E+10 0.424560E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.205389E+10
February 0.300332E+10 0.355283E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.284787E+10
March 0.352563E+10 0.367680E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.180765E+10
April 0.326447E+10 0.315252E+10 0.00 0.00 0.00 0.00 0.00 61975.41 0.202957E+10
May 0.339505E+10 0.312555E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.530275E+10
June 0.339505E+10 0.302965E+10 0.00 0.00 0.00 0.00 0.00 379517.59 0.481319E+10
July 0.326447E+10 0.301208E+10 0.00 0.00 0.00 0.00 0.00 8703783.12 0.471563E+10
August 0.352563E+10 0.332386E+10 0.00 0.00 0.00 0.00 0.00 636659.73 0.385402E+10
September 0.326447E+10 0.338306E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.321702E+10
October 0.326447E+10 0.377380E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.256112E+10
November 0.313390E+10 0.404615E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.338098E+10
December 0.326447E+10 0.442512E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.502173E+10
                   
Annual Sum or Average 0.395654E+11 0.427470E+11 0.00 0.00 0.00 0.00 0.00 9781935.86 0.416054E+11
Minimum of Months 0.300332E+10 0.301208E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.180765E+10
Maximum of Months 0.352563E+10 0.442512E+10 0.00 0.00 0.00 0.00 0.00 8703783.12 0.530275E+10



Table of Contents

Report: SpaceGainsMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.750829E+10 0.419121E+10 0.885613E+10 0.00 0.00 0.00 0.00 31247279.73 0.663836E+10
February 0.690763E+10 0.345666E+10 0.814764E+10 0.00 0.00 0.00 0.00 0.00 0.870226E+10
March 0.810895E+10 0.359492E+10 0.957200E+10 0.00 0.00 0.00 0.00 1200681.18 0.582471E+10
April 0.750829E+10 0.314225E+10 0.885613E+10 0.00 0.00 0.00 0.00 39456580.37 0.842164E+10
May 0.780862E+10 0.314205E+10 0.921037E+10 0.00 0.00 0.00 0.00 94400977.57 0.227682E+11
June 0.780862E+10 0.306733E+10 0.921037E+10 0.00 0.00 0.00 0.00 0.144204E+09 0.198662E+11
July 0.750829E+10 0.303599E+10 0.885613E+10 0.00 0.00 0.00 0.00 0.145817E+09 0.204204E+11
August 0.810895E+10 0.330386E+10 0.956462E+10 0.00 0.00 0.00 0.00 23966793.03 0.177687E+11
September 0.750829E+10 0.329082E+10 0.884875E+10 0.00 0.00 0.00 0.00 15567213.77 0.153638E+11
October 0.750829E+10 0.367716E+10 0.886351E+10 0.00 0.00 0.00 0.00 0.00 0.120123E+11
November 0.720796E+10 0.398582E+10 0.850188E+10 0.00 0.00 0.00 0.00 30479843.31 0.104474E+11
December 0.750829E+10 0.449370E+10 0.885613E+10 0.00 0.00 0.00 0.00 11964236.52 0.142429E+11
                   
Annual Sum or Average 0.910005E+11 0.423818E+11 0.107344E+12 0.00 0.00 0.00 0.00 0.538305E+09 0.162477E+12
Minimum of Months 0.690763E+10 0.303599E+10 0.814764E+10 0.00 0.00 0.00 0.00 0.00 0.582471E+10
Maximum of Months 0.810895E+10 0.449370E+10 0.957200E+10 0.00 0.00 0.00 0.00 0.145817E+09 0.227682E+11



Table of Contents

Report: PeakSpaceGainsMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1680.92 02-JAN-08:09 808.57 02-JAN-08:09 1835.05 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 10061.60 10-JAN-18:00
February 1680.92 01-FEB-08:09 802.15 01-FEB-08:09 1835.05 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 9056.75 17-FEB-07:10
March 1680.92 01-MAR-08:09 791.35 15-MAR-07:10 1835.05 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 7665.52 08-MAR-07:10
April 1680.92 01-APR-07:10 777.78 10-APR-07:10 1835.05 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:05 6303.53 20-APR-06:10
May 1680.92 01-MAY-07:10 730.74 04-MAY-07:10 1835.05 01-MAY-07:10 0.00 0.00 0.00 0.00 6.15 22-MAY-15:00 6781.53 01-MAY-16:03
June 1680.92 01-JUN-07:10 702.41 14-JUN-07:10 1835.05 01-JUN-07:10 0.00 0.00 0.00 0.00 923.55 13-JUN-16:03 5443.87 08-JUN-06:10
July 1680.92 01-JUL-07:10 727.73 07-JUL-07:30 1835.05 01-JUL-07:10 0.00 0.00 0.00 0.00 1468.29 21-JUL-17:00 4691.80 20-JUL-06:03
August 1680.92 01-AUG-07:10 763.56 22-AUG-07:30 1835.05 01-AUG-07:10 0.00 0.00 0.00 0.00 751.52 14-AUG-17:00 4876.26 24-AUG-06:03
September 1680.92 01-SEP-07:10 770.28 08-SEP-07:30 1835.05 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 5585.38 20-SEP-06:10
October 1680.92 02-OCT-07:10 807.98 31-OCT-07:10 1835.05 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 6933.54 04-OCT-06:05
November 1680.92 01-NOV-07:10 808.57 06-NOV-16:49 1835.05 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 8980.68 29-NOV-08:00
December 1680.92 01-DEC-08:09 808.57 01-DEC-15:30 1835.05 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 9157.19 29-DEC-18:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1680.92   702.41   1835.05   0.00 0.00 0.00 0.00 0.00   4691.80  
Maximum of Months 1680.92   808.57   1835.05   0.00 0.00 0.00 0.00 1468.29   10061.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3955.50 02-JAN-08:09 4261.55 03-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7181.69 10-JAN-18:00
February 3955.50 01-FEB-08:09 4025.10 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 4535.64 01-FEB-16:10
March 3955.50 01-MAR-08:09 3854.24 15-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 7242.05 31-MAR-08:00
April 3955.50 01-APR-07:10 3675.14 10-APR-08:09 0.00 0.00 0.00 0.00 0.00 37.08 30-APR-19:00 4128.98 24-APR-15:10
May 3955.50 01-MAY-07:10 3233.92 05-MAY-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 9213.13 01-MAY-15:05
June 3955.50 01-JUN-07:10 3126.79 01-JUN-08:09 0.00 0.00 0.00 0.00 0.00 129.19 12-JUN-18:00 6199.30 07-JUN-15:05
July 3955.50 01-JUL-07:10 3239.24 21-JUL-08:09 0.00 0.00 0.00 0.00 0.00 584.09 22-JUL-15:10 5678.37 30-JUL-19:00
August 3955.50 01-AUG-07:10 3606.33 08-AUG-08:09 0.00 0.00 0.00 0.00 0.00 184.93 14-AUG-18:00 5981.91 22-AUG-16:00
September 3955.50 01-SEP-07:10 3775.84 27-SEP-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 5521.77 29-SEP-15:10
October 3955.50 02-OCT-07:10 4085.91 31-OCT-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 4650.82 01-OCT-24:00
November 3955.50 01-NOV-07:10 4354.33 25-NOV-15:30 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 6488.71 15-NOV-07:03
December 3955.50 01-DEC-08:09 4354.33 01-DEC-15:30 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 10545.41 02-DEC-18:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 3955.50   3126.79   0.00 0.00 0.00 0.00 0.00 0.00   4128.98  
Maximum of Months 3955.50   4354.33   0.00 0.00 0.00 0.00 0.00 584.09   10545.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 9097.65 02-JAN-08:09 4606.47 03-JAN-15:00 8200.12 02-JAN-08:09 0.00 0.00 0.00 0.00 3413.74 29-JAN-06:00 24888.88 10-JAN-16:00
February 9097.65 01-FEB-08:09 4122.90 01-FEB-09:09 8200.12 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 13063.50 01-FEB-16:00
March 9097.65 01-MAR-08:09 3878.74 15-MAR-07:10 8200.12 01-MAR-08:09 0.00 0.00 0.00 0.00 244.68 19-MAR-12:00 22600.32 31-MAR-08:00
April 9097.65 01-APR-07:10 3597.46 10-APR-07:10 8200.12 01-APR-07:10 0.00 0.00 0.00 0.00 1939.82 30-APR-14:00 15306.07 24-APR-12:10
May 9097.65 01-MAY-07:10 2857.11 01-MAY-06:10 8200.12 01-MAY-07:10 0.00 0.00 0.00 0.00 4288.22 22-MAY-15:00 36760.33 01-MAY-13:00
June 9097.65 01-JUN-07:10 2821.26 17-JUN-06:10 8200.12 01-JUN-07:10 0.00 0.00 0.00 0.00 5966.27 13-JUN-15:00 24929.19 07-JUN-15:00
July 9097.65 01-JUL-07:10 2648.26 25-JUL-06:10 8200.12 01-JUL-07:10 0.00 0.00 0.00 0.00 3577.23 22-JUL-15:00 22249.23 30-JUL-19:00
August 9097.65 01-AUG-07:10 3306.84 22-AUG-07:30 8200.12 01-AUG-07:10 0.00 0.00 0.00 0.00 2431.08 14-AUG-18:00 23177.10 22-AUG-16:00
September 9097.65 01-SEP-07:10 3580.13 27-SEP-07:10 8200.12 01-SEP-07:10 0.00 0.00 0.00 0.00 962.96 24-SEP-16:00 20035.47 19-SEP-15:00
October 9097.65 02-OCT-07:10 4246.73 31-OCT-08:09 8200.12 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 19784.94 01-OCT-24:00
November 9097.65 01-NOV-07:10 4789.77 25-NOV-15:30 8200.12 01-NOV-07:10 0.00 0.00 0.00 0.00 5484.52 24-NOV-12:00 17230.28 03-NOV-07:10
December 9097.65 01-DEC-08:09 4789.77 01-DEC-15:30 8200.12 01-DEC-08:09 0.00 0.00 0.00 0.00 5363.35 23-DEC-11:00 21044.54 02-DEC-17:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 9097.65   2648.26   8200.12   0.00 0.00 0.00 0.00 0.00   13063.50  
Maximum of Months 9097.65   4789.77   8200.12   0.00 0.00 0.00 0.00 5966.27   36760.33  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1932.17 09-JAN-08:05 6723.69 3224.91 7340.22 0.00 0.00 0.00 0.00 0.00 1234.04
February 2042.26 17-FEB-08:05 6723.69 3031.30 7340.22 0.00 0.00 0.00 0.00 0.00 1280.84
March 1708.39 25-MAR-06:05 2117.96 2646.26 5505.16 0.00 0.00 0.00 0.00 0.00 0.00
April 2740.55 29-APR-15:50 1680.92 493.23 1835.05 0.00 0.00 0.00 0.00 0.00 91.11
May 2568.32 25-MAY-16:00 1680.92 493.23 1835.05 0.00 0.00 0.00 0.00 0.00 525.19
June 5138.01 13-JUN-16:00 1680.92 493.23 1835.05 0.00 0.00 0.00 0.00 278.93 0.00
July 13784.46 22-JUL-07:02 8404.61 3215.26 9175.27 0.00 0.00 0.00 0.00 0.00 22.51
August 4901.88 14-AUG-16:00 1680.92 493.23 1835.05 0.00 0.00 0.00 0.00 211.32 0.00
September 3616.26 13-SEP-16:00 1680.92 493.23 1835.05 0.00 0.00 0.00 0.00 0.00 85.25
October 1704.95 07-OCT-06:05 1411.97 1764.18 3670.11 0.00 0.00 0.00 0.00 0.00 0.00
November 1795.64 29-NOV-08:05 6723.69 3201.88 7340.22 0.00 0.00 0.00 0.00 0.00 2081.35
December 1819.55 27-DEC-08:05 6723.69 3234.26 7340.22 0.00 0.00 0.00 0.00 0.00 1802.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1704.95   1411.97 493.23 1835.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13784.46   8404.61 3234.26 9175.27 0.00 0.00 0.00 0.00 278.93 2081.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6381.52 09-JAN-15:45 7911.00 7889.80 0.00 0.00 0.00 0.00 0.00 0.00 887.09
February 4954.82 23-FEB-15:30 3955.50 2933.57 0.00 0.00 0.00 0.00 0.00 0.00 737.21
March 4709.02 14-MAR-14:00 3955.50 2177.17 0.00 0.00 0.00 0.00 0.00 0.00 835.89
April 5919.85 08-APR-07:03 15822.00 13741.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 5931.16 01-MAY-15:00 3955.50 2177.17 0.00 0.00 0.00 0.00 0.00 0.00 3740.93
June 5321.49 07-JUN-10:00 3955.50 2426.71 0.00 0.00 0.00 0.00 0.00 0.00 2258.09
July 22508.90 22-JUL-17:20 0.00 1074.25 0.00 0.00 0.00 0.00 0.00 304.05 0.00
August 4499.66 19-AUG-07:10 3955.50 3303.87 0.00 0.00 0.00 0.00 0.00 0.00 2395.65
September 5453.21 28-SEP-07:03 11866.50 10360.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 5963.72 06-OCT-07:03 11866.50 10955.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 4467.56 29-NOV-14:40 3955.50 4044.63 0.00 0.00 0.00 0.00 0.00 0.00 409.57
December 3851.25 08-DEC-11:30 3955.50 3472.37 0.00 0.00 0.00 0.00 0.00 0.00 605.39
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3851.25   0.00 1074.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22508.90   15822.00 13741.15 0.00 0.00 0.00 0.00 0.00 304.05 3740.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 1127.00 0.00 0.00 0.00 0.00 0.00 0.00 3124.06
February 0.00 01-FEB-00:05 0.00 1127.00 4100.06 0.00 0.00 0.00 0.00 0.00 2822.09
March 0.00 01-MAR-00:05 0.00 1127.00 4100.06 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 01-APR-00:05 0.00 1127.00 4100.06 0.00 0.00 0.00 0.00 0.00 3652.99
May 0.00 01-MAY-00:10 0.00 563.50 2050.03 0.00 0.00 0.00 0.00 0.00 7094.66
June 0.00 01-JUN-00:10 0.00 563.50 2050.03 0.00 0.00 0.00 0.00 0.00 9016.30
July 0.00 01-JUL-00:10 0.00 563.50 2050.03 0.00 0.00 0.00 0.00 0.00 15821.08
August 0.00 01-AUG-00:10 0.00 563.50 2050.03 0.00 0.00 0.00 0.00 0.00 7591.20
September 0.00 01-SEP-00:10 0.00 563.50 2050.03 0.00 0.00 0.00 0.00 0.00 9044.97
October 0.00 01-OCT-00:10 0.00 563.50 0.00 0.00 0.00 0.00 0.00 0.00 12826.14
November 0.00 01-NOV-00:05 0.00 1127.00 4100.06 0.00 0.00 0.00 0.00 0.00 5432.85
December 0.00 01-DEC-00:05 0.00 1127.00 4100.06 0.00 0.00 0.00 0.00 0.00 2490.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 563.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 1127.00 4100.06 0.00 0.00 0.00 0.00 0.00 15821.08



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.324216E+11 28146.90 10-JAN-16:00 0.403977E+11 93682.66 10-JAN-17:00
February 0.280627E+11 22448.31 01-FEB-09:09 0.296857E+11 54556.43 17-FEB-03:00
March 0.301147E+11 21960.18 15-MAR-08:09 0.179508E+11 33960.42 04-MAR-06:19
April 0.264974E+11 21259.62 10-APR-08:09 0.312458E+10 27011.13 03-APR-06:10
May 0.264315E+11 19902.84 04-MAY-07:10 0.143070E+10 16508.87 05-MAY-06:10
June 0.258518E+11 20398.59 13-JUN-14:00 0.180946E+09 11719.91 08-JUN-06:10
July 0.259205E+11 22377.03 22-JUL-14:20 35264903.68 6784.95 05-JUL-06:10
August 0.281089E+11 21512.67 08-AUG-08:09 5639517.59 2293.88 31-AUG-07:10
September 0.275748E+11 21285.73 25-SEP-07:10 0.283825E+09 9334.61 20-SEP-06:10
October 0.296368E+11 22448.66 27-OCT-08:09 0.489922E+10 26583.82 23-OCT-06:10
November 0.306295E+11 27903.66 28-NOV-16:49 0.203239E+11 62186.83 28-NOV-07:10
December 0.333408E+11 28158.46 30-DEC-08:09 0.574811E+11 86594.99 28-DEC-07:10
             
Annual Sum or Average 0.344591E+12     0.175799E+12    
Minimum of Months 0.258518E+11 19902.84   5639517.59 2293.88  
Maximum of Months 0.333408E+11 28158.46   0.574811E+11 93682.66  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.941688E+10 0.730160E+10 0.112984E+11 0.00 0.217132E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.223348E+10 0.00
February 0.786126E+10 0.583861E+10 0.103734E+11 0.00 0.195358E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.203584E+10 0.00
March 0.821770E+10 0.542642E+10 0.121089E+11 0.00 0.206467E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.229702E+10 0.00
April 0.711943E+10 0.420505E+10 0.112578E+11 0.00 0.172849E+10 0.00 0.00 18903694.39 0.00 0.00 0.00 0.216776E+10 0.00
May 0.710572E+10 0.358010E+10 0.117000E+11 0.00 0.178127E+10 0.00 0.00 43370784.77 0.00 0.00 0.00 0.222108E+10 0.00
June 0.690792E+10 0.310567E+10 0.116594E+11 0.00 0.178060E+10 0.00 0.00 0.251038E+09 0.00 0.00 0.00 0.214716E+10 0.00
July 0.686313E+10 0.334049E+10 0.112984E+11 0.00 0.171754E+10 0.00 0.00 0.556617E+09 0.00 0.00 0.00 0.214430E+10 0.00
August 0.749683E+10 0.396026E+10 0.121016E+11 0.00 0.184909E+10 0.00 0.00 0.505349E+09 0.00 0.00 0.00 0.219577E+10 0.00
September 0.752495E+10 0.479595E+10 0.112504E+11 0.00 0.171212E+10 0.00 0.00 0.190022E+09 0.00 0.00 0.00 0.210135E+10 0.00
October 0.837574E+10 0.603281E+10 0.113057E+11 0.00 0.175250E+10 0.00 0.00 1314374.80 0.00 0.00 0.00 0.216867E+10 0.00
November 0.897689E+10 0.677988E+10 0.108562E+11 0.00 0.189983E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.211674E+10 0.00
December 0.993403E+10 0.755536E+10 0.112984E+11 0.00 0.233614E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.221688E+10 0.00
                           
Annual Sum or Average 0.958005E+11 0.619222E+11 0.136508E+12 0.00 0.227472E+11 0.00 0.00 0.156662E+10 0.00 0.00 0.00 0.260460E+11 0.00
Minimum of Months 0.686313E+10 0.310567E+10 0.103734E+11 0.00 0.171212E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.203584E+10 0.00
Maximum of Months 0.993403E+10 0.755536E+10 0.121089E+11 0.00 0.233614E+10 0.00 0.00 0.556617E+09 0.00 0.00 0.00 0.229702E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.403977E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.296857E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.179508E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.312458E+10 0.00 0.00 0.00 0.00
May 0.00 0.00 0.143070E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.180946E+09 0.00 0.00 0.00 0.00
July 0.00 0.00 35264903.68 0.00 0.00 0.00 0.00
August 0.00 0.00 5639517.59 0.00 0.00 0.00 0.00
September 0.00 0.00 0.283825E+09 0.00 0.00 0.00 0.00
October 0.00 0.00 0.489922E+10 0.00 0.00 0.00 0.00
November 0.00 0.00 0.203239E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.574811E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.175799E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 5639517.59 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.574811E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 9668.24 03-JAN-15:00 5492.60 01-JAN-06:10 10035.17 02-JAN-08:09 0.00 2225.44 10-JAN-17:00 0.00 0.00 01-JAN-00:10
February 8928.12 01-FEB-09:09 5492.60 01-FEB-06:10 10035.17 01-FEB-08:09 0.00 2043.71 24-FEB-07:10 0.00 0.00 01-FEB-00:10
March 8372.98 15-MAR-08:09 5492.60 01-MAR-06:10 10035.17 01-MAR-08:09 0.00 1975.58 04-MAR-07:19 0.00 0.00 01-MAR-00:10
April 7908.92 10-APR-07:10 5492.60 01-APR-05:10 10035.17 01-APR-07:10 0.00 1835.09 11-APR-06:10 0.00 0.00 01-APR-00:10
May 6603.58 04-MAY-07:10 4946.68 01-MAY-19:19 10035.17 01-MAY-07:10 0.00 1729.41 06-MAY-06:10 0.00 0.00 01-MAY-00:10
June 6151.94 01-JUN-08:09 4946.68 01-JUN-19:00 10035.17 01-JUN-07:10 0.00 1729.41 13-JUN-14:39 0.00 0.00 01-JUN-00:10
July 6456.59 07-JUL-07:10 4946.68 01-JUL-20:19 10035.17 01-JUL-07:10 0.00 1729.41 21-JUL-12:20 0.00 0.00 01-JUL-00:10
August 7578.48 08-AUG-08:09 5492.60 14-AUG-05:10 10035.17 01-AUG-07:10 0.00 1729.41 14-AUG-15:30 0.00 0.00 01-AUG-00:10
September 7937.59 27-SEP-07:10 5492.60 01-SEP-05:10 10035.17 01-SEP-07:10 0.00 1729.41 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 9118.04 31-OCT-08:09 5492.60 01-OCT-05:10 10035.17 02-OCT-07:10 0.00 1855.34 28-OCT-07:10 0.00 0.00 01-OCT-00:10
November 9952.67 25-NOV-15:30 5492.60 01-NOV-05:10 10035.17 01-NOV-07:10 0.00 2114.12 29-NOV-08:09 0.00 0.00 01-NOV-00:10
December 9952.67 01-DEC-15:30 5492.60 01-DEC-06:10 10035.17 01-DEC-08:09 0.00 2159.56 28-DEC-08:09 0.00 0.00 01-DEC-00:10
                         
Annual Sum or Average             0.00     0.00    
Minimum of Months 6151.94   4946.68   10035.17   0.00 1729.41   0.00 0.00  
Maximum of Months 9952.67   5492.60   10035.17   0.00 2225.44   0.00 0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 0.00 01-JAN-00:10 0.00 0.00 0.00 2409.16 31-JAN-12:30 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 2416.95 14-FEB-12:09 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 2409.02 01-MAR-12:09 0.00
April 636.40 29-APR-15:50 0.00 0.00 0.00 2345.92 03-APR-11:00 0.00
May 698.60 22-MAY-15:39 0.00 0.00 0.00 2232.47 05-MAY-11:00 0.00
June 2059.95 13-JUN-15:00 0.00 0.00 0.00 2104.13 05-JUN-11:00 0.00
July 4021.54 22-JUL-15:09 0.00 0.00 0.00 1998.96 01-JUL-11:00 0.00
August 1395.91 14-AUG-15:00 0.00 0.00 0.00 1925.06 28-AUG-11:00 0.00
September 943.21 13-SEP-15:00 0.00 0.00 0.00 1954.22 13-SEP-11:00 0.00
October 216.50 07-OCT-15:30 0.00 0.00 0.00 2101.47 26-OCT-11:09 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 2246.35 30-NOV-12:09 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 2349.33 30-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 0.00   0.00 0.00 0.00 1925.06   0.00
Maximum of Months 4021.54   0.00 0.00 0.00 2416.95   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 28146.90 10-JAN-16:00 8876.89 10035.17 5492.60 0.00 2126.04 0.00 0.00 0.00 0.00
February 22448.31 01-FEB-09:09 8928.12 10035.17 0.00 0.00 1796.17 0.00 0.00 0.00 0.00
March 21960.18 15-MAR-08:09 8372.98 10035.17 0.00 0.00 1863.71 0.00 0.00 0.00 0.00
April 21259.62 10-APR-08:09 7805.02 10035.17 0.00 0.00 1734.17 0.00 0.00 0.00 0.00
May 19902.84 04-MAY-07:10 6603.58 10035.17 0.00 0.00 1729.41 0.00 0.00 0.00 0.00
June 20398.59 13-JUN-14:00 5065.28 10035.17 0.00 0.00 1729.41 0.00 0.00 1783.99 0.00
July 22377.03 22-JUL-14:20 5065.28 10035.17 0.00 0.00 1729.41 0.00 0.00 3771.22 0.00
August 21512.67 08-AUG-08:09 7578.48 10035.17 0.00 0.00 1729.41 0.00 0.00 499.93 0.00
September 21285.73 25-SEP-07:10 7881.86 10035.17 0.00 0.00 1729.41 0.00 0.00 0.00 0.00
October 22448.66 27-OCT-08:09 9007.49 10035.17 0.00 0.00 1729.41 0.00 0.00 0.00 0.00
November 27903.66 28-NOV-16:49 8876.89 10035.17 5492.60 0.00 1885.83 0.00 0.00 0.00 0.00
December 28158.46 30-DEC-08:09 8876.89 10035.17 5492.60 0.00 2103.87 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00   0.00     0.00
Minimum of Months 19902.84   5065.28 10035.17 0.00 0.00 1729.41 0.00 0.00 0.00 0.00
Maximum of Months 28158.46   9007.49 10035.17 5492.60 0.00 2126.04 0.00 0.00 3771.22 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 93682.66 10-JAN-17:00 0.00 0.00 0.00
February 0.00 0.00 54556.43 17-FEB-03:00 0.00 0.00 0.00
March 0.00 0.00 33960.42 04-MAR-06:19 0.00 0.00 0.00
April 0.00 0.00 27011.13 03-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 16508.87 05-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 11719.91 08-JUN-06:10 0.00 0.00 0.00
July 0.00 0.00 6784.95 05-JUL-06:10 0.00 0.00 0.00
August 0.00 0.00 2293.88 31-AUG-07:10 0.00 0.00 0.00
September 0.00 0.00 9334.61 20-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 26583.82 23-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 62186.83 28-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 86594.99 28-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 2293.88   0.00 0.00 0.00
Maximum of Months 0.00 0.00 93682.66   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 16.44 2.67 16.78 0.00 16.78 0.00 16.78
February 2.17 16.64 1.67 16.86 0.00 16.86 0.00 16.86
March 1.00 17.18 1.00 17.18 0.00 17.18 0.00 17.18
April 0.33 17.19 0.33 17.19 0.00 17.19 0.00 17.19
May 0.17 17.24 0.17 17.24 0.00 17.24 0.00 17.24
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.67 17.14 0.67 17.14 0.00 17.14 0.00 17.14
November 1.33 17.32 1.33 17.32 0.00 17.32 0.00 17.32
December 5.17 16.52 3.83 16.75 0.00 16.75 0.00 16.75
                 
Annual Sum or Average 15.17 16.68 11.67 16.90 0.00 16.90 0.00 16.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.17 17.32 3.83 17.32 0.00 17.32 0.00 17.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 27.00 14.87 2.00 14.87 0.00 14.87 0.00 14.87
February 23.67 14.92 1.33 14.91 0.00 14.91 0.00 14.91
March 8.67 14.96 0.50 14.96 0.00 14.96 0.00 14.96
April 1.67 14.96 0.00 14.96 0.00 14.96 0.00 14.96
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.27 0.00 27.27
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 5.17 14.96 0.00 14.96 0.00 14.96 0.00 14.96
November 24.17 14.92 1.17 14.92 0.00 14.92 0.00 14.92
December 52.50 14.87 4.17 14.87 0.00 14.87 0.00 14.87
                 
Annual Sum or Average 142.83 14.90 9.17 14.90 0.50 14.94 0.00 14.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 52.50 14.96 4.17 14.96 0.50 27.27 0.00 27.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 300.00 20.63 300.00 20.63 300.00 20.63
February 276.00 20.63 276.00 20.63 276.00 20.63
March 324.00 20.64 324.00 20.64 324.00 20.64
April 299.17 21.19 214.00 20.94 214.00 20.83
May 312.00 21.61 138.50 21.25 138.50 21.06
June 261.33 22.88 26.33 22.80 14.17 22.67
July 145.67 23.16 76.83 23.37 6.00 23.29
August 180.50 23.36 34.67 23.49 0.00 23.49
September 282.33 22.92 28.83 22.69 26.50 22.49
October 300.00 20.97 229.83 20.80 229.83 20.73
November 288.00 20.63 288.00 20.63 288.00 20.63
December 300.00 20.62 300.00 20.62 300.00 20.62
             
Annual Sum or Average 3269.00 21.45 2237.00 21.18 2117.00 21.02
Minimum of Months 145.67 20.62 26.33 20.62 0.00 20.62
Maximum of Months 324.00 23.36 324.00 23.49 324.00 23.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 300.00 15.67 300.00 15.67 300.00 15.67
February 276.00 15.67 276.00 15.67 276.00 15.67
March 324.00 15.82 324.00 15.82 324.00 15.82
April 300.00 18.24 260.33 17.98 260.33 17.89
May 309.83 19.37 219.50 18.94 219.50 18.76
June 243.33 21.61 88.50 21.86 40.67 21.58
July 143.00 22.50 151.17 23.81 20.17 23.78
August 140.17 22.76 141.83 23.99 0.00 23.99
September 274.67 21.47 78.67 21.23 64.17 20.95
October 300.00 17.35 284.00 17.25 284.00 17.22
November 288.00 15.82 288.00 15.82 288.00 15.82
December 300.00 15.56 300.00 15.56 300.00 15.56
             
Annual Sum or Average 3199.00 18.01 2712.00 17.84 2376.83 17.47
Minimum of Months 140.17 15.56 78.67 15.56 0.00 15.56
Maximum of Months 324.00 22.76 324.00 23.99 324.00 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 300.00 11.00 300.00 11.00 300.00 11.00
February 276.00 11.13 276.00 11.13 276.00 11.13
March 324.00 11.97 324.00 11.97 324.00 11.97
April 300.00 15.97 298.67 15.96 298.67 15.96
May 312.00 17.44 312.00 17.44 312.00 17.44
June 312.00 20.23 152.50 19.78 152.50 19.55
July 254.33 21.87 69.67 21.95 35.33 21.72
August 286.17 22.73 14.00 22.82 0.00 22.82
September 300.00 20.76 110.17 20.41 110.17 20.21
October 300.00 16.48 300.00 16.48 300.00 16.48
November 288.00 12.45 288.00 12.45 288.00 12.45
December 300.00 10.57 300.00 10.57 300.00 10.57
             
Annual Sum or Average 3552.50 15.99 2745.00 15.22 2696.67 14.87
Minimum of Months 254.33 10.57 14.00 10.57 0.00 10.57
Maximum of Months 324.00 22.73 324.00 22.82 324.00 22.82



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: OFFICE PEOPLE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 300.00000 0.00000 0.00000 0.00000 0.00000
February 276.00000 0.00000 0.00000 0.00000 0.00000
March 324.00000 0.00000 0.00000 0.00000 0.00000
April 300.00000 0.00000 0.00000 0.00000 0.00000
May 312.00000 0.00000 0.00000 0.00000 0.00000
June 312.00000 0.00000 0.00000 0.00000 0.00000
July 300.00000 0.00000 0.00000 0.00000 0.00000
August 324.00000 0.00000 0.00000 0.00000 0.00000
September 300.00000 0.00000 0.00000 0.00000 0.00000
October 300.00000 0.00000 0.00000 0.00000 0.00000
November 288.00000 0.00000 0.00000 0.00000 0.00000
December 300.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3636.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 276.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 324.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ZONE2 FINE STORAGEPEOPLE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 300.00000 0.00000 0.00000 0.00000 0.00000
February 276.00000 0.00000 0.00000 0.00000 0.00000
March 324.00000 0.00000 0.00000 0.00000 0.00000
April 300.00000 0.00000 0.00000 0.00000 0.00000
May 312.00000 0.00000 0.00000 0.00000 0.00000
June 312.00000 0.00000 0.00000 0.00000 0.00000
July 300.00000 0.00000 0.00000 0.00000 0.00000
August 324.00000 0.00000 0.00000 0.00000 0.00000
September 300.00000 0.00000 0.00000 0.00000 0.00000
October 300.00000 0.00000 0.00000 0.00000 0.00000
November 288.00000 0.00000 0.00000 0.00000 0.00000
December 300.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3636.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 276.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 324.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ZONE3 BULK STORAGEPEOPLE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 300.00000 0.00000 0.00000 0.00000 0.00000
February 276.00000 0.00000 0.00000 0.00000 0.00000
March 324.00000 0.00000 0.00000 0.00000 0.00000
April 300.00000 0.00000 0.00000 0.00000 0.00000
May 312.00000 0.00000 0.00000 0.00000 0.00000
June 312.00000 0.00000 0.00000 0.00000 0.00000
July 300.00000 0.00000 0.00000 0.00000 0.00000
August 324.00000 0.00000 0.00000 0.00000 0.00000
September 300.00000 0.00000 0.00000 0.00000 0.00000
October 300.00000 0.00000 0.00000 0.00000 0.00000
November 288.00000 0.00000 0.00000 0.00000 0.00000
December 300.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3636.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 276.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 324.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-OFFICE COOLING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 96955369.25 18903694.39 17.00 95428565.90 1526803.35 0.00 0.45 29-APR-15:50 0.00 01-APR-00:05 3352.61 29-APR-15:50 3255.53 29-APR-15:50 107.89 29-APR-15:00 636.40 29-APR-15:50 0.00 01-APR-00:05
May 0.223480E+09 43370784.77 38.00 0.198884E+09 24595706.51 0.00 0.48 22-MAY-15:50 0.00 01-MAY-00:10 3710.72 22-MAY-15:40 3324.32 22-MAY-15:50 529.97 23-MAY-15:00 698.60 22-MAY-15:40 0.00 01-MAY-00:10
June 0.128957E+10 0.245567E+09 146.50 0.111249E+10 0.177080E+09 0.00 0.89 13-JUN-16:00 0.00 01-JUN-00:10 7296.78 13-JUN-16:00 6457.20 13-JUN-16:00 1221.32 27-JUN-07:30 1337.96 13-JUN-16:00 0.00 01-JUN-00:10
July 0.242885E+10 0.456089E+09 195.44 0.211567E+10 0.313186E+09 0.00 1.00 21-JUL-16:08 0.00 01-JUL-00:10 15415.09 22-JUL-07:02 15145.94 22-JUL-07:02 1263.62 24-JUL-16:00 2809.83 22-JUL-07:02 0.00 01-JUL-00:10
August 0.267784E+10 0.504839E+09 232.78 0.232873E+10 0.349104E+09 0.00 0.82 14-AUG-16:00 0.00 01-AUG-00:10 6560.59 14-AUG-16:00 6158.44 14-AUG-16:00 1119.60 18-AUG-16:00 1211.02 14-AUG-16:00 0.00 01-AUG-00:10
September 0.987757E+09 0.190022E+09 138.17 0.857896E+09 0.129861E+09 0.00 0.64 13-SEP-16:00 0.00 01-SEP-00:10 5151.40 13-SEP-16:00 4501.24 13-SEP-16:00 818.91 12-SEP-14:20 943.21 13-SEP-16:00 0.00 01-SEP-00:10
October 6578537.76 1314374.80 2.17 6578537.76 0.00 0.00 0.16 07-OCT-15:40 0.00 01-OCT-00:10 1087.14 07-OCT-15:30 1087.14 07-OCT-15:30 0.00 07-OCT-14:50 216.50 07-OCT-15:30 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05
                                         
Annual Sum or Average 0.771103E+10 0.146011E+10 770.05 0.671568E+10 0.995353E+09 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.267784E+10 0.504839E+09 232.78 0.232873E+10 0.349104E+09 0.00 1.00   0.00   15415.09   15145.94   1263.62   2809.83   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-FINE STORAGE COOLING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05 0.00 01-MAR-00:05
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:05 0.00 01-APR-00:05 0.00 01-APR-00:05 0.00 01-APR-00:05 0.00 01-APR-00:05 0.00 01-APR-00:05 0.00 01-APR-00:05
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 23299834.77 5471443.61 3.33 20503785.72 2796049.05 0.00 0.20 13-JUN-16:00 0.00 01-JUN-00:10 3089.14 13-JUN-16:00 2761.18 13-JUN-16:00 333.90 13-JUN-15:00 722.00 13-JUN-16:00 0.00 01-JUN-00:10
July 0.453266E+09 0.100528E+09 15.11 0.430479E+09 22787374.84 0.00 1.00 22-JUL-17:20 0.00 01-JUL-00:10 34663.64 23-JUL-16:15 27449.00 23-JUL-12:32 8494.81 23-JUL-17:15 6827.82 23-JUL-16:15 0.00 01-JUL-00:10
August 2112400.70 510479.94 1.50 2100184.97 12215.73 0.00 0.05 14-AUG-16:00 0.00 01-AUG-00:10 772.14 14-AUG-16:00 772.14 14-AUG-16:00 9.26 14-AUG-15:40 184.89 14-AUG-16:00 0.00 01-AUG-00:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05 0.00 01-NOV-00:05
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05
                                         
Annual Sum or Average 0.478678E+09 0.106510E+09 19.94 0.453082E+09 25595639.63 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.453266E+09 0.100528E+09 15.11 0.430479E+09 22787374.84 0.00 1.00   0.00   34663.64   27449.00   8494.81   6827.82   0.00  



Table of Contents

Report: WindowReportMonthly

For: OFFICE FRONT WALL WINDOW 1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.23 14.45 29.78 32.86 95.86 0.00 0.00 0.00
February 78.24 33.23 45.01 71.58 89.50 0.00 0.00 0.00
March 70.51 13.55 56.96 55.84 70.28 0.00 0.00 0.00
April 165.92 65.74 100.19 189.77 61.74 0.00 0.00 0.00
May 194.61 78.90 115.71 218.06 54.67 0.00 0.00 0.00
June 210.56 86.88 123.68 244.07 48.84 0.00 0.00 0.00
July 214.45 94.61 119.85 254.28 49.30 0.00 0.00 0.00
August 179.98 77.84 102.14 214.50 55.08 0.00 0.00 0.00
September 145.69 65.85 79.84 170.84 63.05 0.00 0.00 0.00
October 77.36 27.91 49.45 78.03 68.93 0.00 0.00 0.00
November 41.87 12.33 29.55 31.76 82.33 0.00 0.00 0.00
December 23.52 4.90 18.62 11.06 108.16 0.00 0.00 0.00
                 
Annual Sum or Average 120.70 48.03 72.67 131.24 70.56 0.00 0.00 0.00
Minimum of Months 23.52 4.90 18.62 11.06 48.84 0.00 0.00 0.00
Maximum of Months 214.45 94.61 123.68 254.28 108.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICE FRONT WALL WINDOW2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.23 14.45 29.78 32.86 95.86 0.00 0.00 0.00
February 78.24 33.23 45.01 71.58 89.50 0.00 0.00 0.00
March 70.51 13.55 56.96 55.84 70.28 0.00 0.00 0.00
April 165.92 65.74 100.19 189.77 61.74 0.00 0.00 0.00
May 194.61 78.90 115.71 218.06 54.67 0.00 0.00 0.00
June 210.56 86.88 123.68 244.07 48.84 0.00 0.00 0.00
July 214.45 94.61 119.85 254.28 49.30 0.00 0.00 0.00
August 179.98 77.84 102.14 214.50 55.08 0.00 0.00 0.00
September 145.69 65.85 79.84 170.84 63.05 0.00 0.00 0.00
October 77.36 27.91 49.45 78.03 68.93 0.00 0.00 0.00
November 41.87 12.33 29.55 31.76 82.33 0.00 0.00 0.00
December 23.52 4.90 18.62 11.06 108.16 0.00 0.00 0.00
                 
Annual Sum or Average 120.70 48.03 72.67 131.24 70.56 0.00 0.00 0.00
Minimum of Months 23.52 4.90 18.62 11.06 48.84 0.00 0.00 0.00
Maximum of Months 214.45 94.61 123.68 254.28 108.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICE LEFT WALL WINDOW1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.91 0.00 12.91 2.58 58.45 0.00 0.00 0.00
February 20.15 0.00 20.15 6.42 53.80 0.00 0.00 0.00
March 27.89 0.00 27.89 15.13 42.26 0.00 0.00 0.00
April 45.48 0.25 45.23 37.83 35.64 0.00 0.00 0.00
May 57.02 2.95 54.07 47.13 30.14 0.00 0.00 0.00
June 62.59 3.83 58.76 57.86 27.18 0.00 0.00 0.00
July 59.51 3.36 56.14 55.71 27.27 0.00 0.00 0.00
August 47.01 0.91 46.10 42.51 31.01 0.00 0.00 0.00
September 35.64 0.02 35.62 29.95 37.31 0.00 0.00 0.00
October 22.82 0.00 22.82 14.14 40.82 0.00 0.00 0.00
November 13.71 0.00 13.71 3.75 48.94 0.00 0.00 0.00
December 9.34 0.00 9.34 0.65 63.69 0.00 0.00 0.00
                 
Annual Sum or Average 34.57 0.95 33.62 26.23 41.32 0.00 0.00 0.00
Minimum of Months 9.34 0.00 9.34 0.65 27.18 0.00 0.00 0.00
Maximum of Months 62.59 3.83 58.76 57.86 63.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: OFFICE LEFT WALL WINDOW2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.91 0.00 12.91 2.58 58.45 0.00 0.00 0.00
February 20.15 0.00 20.15 6.42 53.80 0.00 0.00 0.00
March 27.89 0.00 27.89 15.13 42.26 0.00 0.00 0.00
April 45.47 0.25 45.23 37.83 35.64 0.00 0.00 0.00
May 57.02 2.95 54.07 47.13 30.14 0.00 0.00 0.00
June 62.59 3.83 58.76 57.85 27.18 0.00 0.00 0.00
July 59.50 3.36 56.14 55.71 27.27 0.00 0.00 0.00
August 47.01 0.91 46.10 42.51 31.01 0.00 0.00 0.00
September 35.64 0.02 35.62 29.94 37.31 0.00 0.00 0.00
October 22.82 0.00 22.82 14.14 40.82 0.00 0.00 0.00
November 13.71 0.00 13.71 3.75 48.94 0.00 0.00 0.00
December 9.34 0.00 9.34 0.65 63.69 0.00 0.00 0.00
                 
Annual Sum or Average 34.57 0.95 33.62 26.23 41.32 0.00 0.00 0.00
Minimum of Months 9.34 0.00 9.34 0.65 27.18 0.00 0.00 0.00
Maximum of Months 62.59 3.83 58.76 57.85 63.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_6

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_7

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_8

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_9

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_10

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_5

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_14

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_13

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_12

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FINESTORAGE_SKYLIGHT_11

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 18.30 48.25 6.17 0.00 0.00
February 41.52 14.78 26.74 38.11 46.34 0.00 0.00 0.00
March 51.96 9.87 42.09 50.78 35.47 6.00 0.00 0.00
April 126.06 67.38 58.68 147.85 33.48 0.00 0.00 0.00
May 151.02 83.30 67.72 172.91 30.70 0.00 0.00 0.00
June 160.88 86.59 74.29 186.47 27.61 0.00 0.00 0.00
July 163.10 94.79 68.32 190.43 29.16 0.00 0.00 0.00
August 140.58 84.74 55.84 164.33 34.14 0.00 0.00 0.00
September 103.57 61.62 41.95 119.61 38.05 0.67 0.00 0.00
October 53.09 23.23 29.86 55.78 37.34 22.67 0.00 0.00
November 26.11 7.63 18.48 21.49 41.67 1.33 0.00 0.00
December 16.63 4.10 12.53 9.77 53.57 0.00 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 98.25 37.94 36.83 0.00 0.00
Minimum of Months 16.63 4.10 12.53 9.77 27.61 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 190.43 53.57 22.67 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R1C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R2C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R3C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R4C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R5C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R8C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R6C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHT_R7C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.87 6.61 17.26 23.58 33.03 119.00 0.00 0.00
February 41.52 14.78 26.74 44.80 31.99 41.67 0.00 0.00
March 51.96 9.87 42.09 57.63 25.02 10.83 0.00 0.00
April 126.06 67.38 58.68 153.81 28.73 0.00 0.00 0.00
May 151.02 83.30 67.72 178.77 26.98 0.00 0.00 0.00
June 160.88 86.59 74.29 193.12 23.60 0.00 0.00 0.00
July 163.10 94.79 68.32 195.56 26.24 0.00 0.00 0.00
August 140.58 84.74 55.84 167.84 32.21 0.00 0.00 0.00
September 103.57 61.62 41.95 122.20 36.46 2.50 0.00 0.00
October 53.09 23.23 29.86 57.45 35.43 27.33 0.00 0.00
November 26.11 7.63 18.48 25.52 30.26 35.00 0.00 0.00
December 16.63 4.10 12.53 13.96 35.26 6.17 0.00 0.00
                 
Annual Sum or Average 88.41 45.52 42.88 103.10 30.43 242.50 0.00 0.00
Minimum of Months 16.63 4.10 12.53 13.96 23.60 0.00 0.00 0.00
Maximum of Months 163.10 94.79 74.29 195.56 36.46 119.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE FRONT WALL WINDOW 1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.118466E+09 38704346.47 79761221.34 88019834.57 0.256741E+09
February 0.189279E+09 80398761.05 0.108881E+09 0.173157E+09 0.216508E+09
March 0.188864E+09 36303582.83 0.152560E+09 0.149563E+09 0.188229E+09
April 0.430071E+09 0.170391E+09 0.259680E+09 0.491892E+09 0.160039E+09
May 0.521245E+09 0.211320E+09 0.309924E+09 0.584047E+09 0.146425E+09
June 0.545784E+09 0.225196E+09 0.320587E+09 0.632625E+09 0.126583E+09
July 0.574394E+09 0.253401E+09 0.320993E+09 0.681069E+09 0.132052E+09
August 0.482070E+09 0.208490E+09 0.273580E+09 0.574528E+09 0.147525E+09
September 0.377622E+09 0.170679E+09 0.206943E+09 0.442827E+09 0.163415E+09
October 0.207202E+09 74752083.80 0.132450E+09 0.209004E+09 0.184612E+09
November 0.108539E+09 31953652.74 76585343.64 82329757.66 0.213403E+09
December 62991728.83 13111787.98 49879940.85 29626854.36 0.289696E+09
           
Annual Sum or Average 0.380653E+10 0.151470E+10 0.229183E+10 0.413869E+10 0.222523E+10
Minimum of Months 62991728.83 13111787.98 49879940.85 29626854.36 0.126583E+09
Maximum of Months 0.574394E+09 0.253401E+09 0.320993E+09 0.681069E+09 0.289696E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE FRONT WALL WINDOW2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.118466E+09 38704346.47 79761221.34 88019834.57 0.256741E+09
February 0.189279E+09 80398761.05 0.108881E+09 0.173157E+09 0.216508E+09
March 0.188864E+09 36303582.83 0.152560E+09 0.149563E+09 0.188229E+09
April 0.430071E+09 0.170391E+09 0.259680E+09 0.491892E+09 0.160039E+09
May 0.521245E+09 0.211320E+09 0.309924E+09 0.584047E+09 0.146425E+09
June 0.545784E+09 0.225196E+09 0.320587E+09 0.632625E+09 0.126583E+09
July 0.574394E+09 0.253401E+09 0.320993E+09 0.681069E+09 0.132052E+09
August 0.482070E+09 0.208490E+09 0.273580E+09 0.574528E+09 0.147525E+09
September 0.377622E+09 0.170679E+09 0.206943E+09 0.442827E+09 0.163415E+09
October 0.207202E+09 74752083.80 0.132450E+09 0.209004E+09 0.184612E+09
November 0.108539E+09 31953652.74 76585343.64 82329757.66 0.213403E+09
December 62991728.83 13111787.98 49879940.85 29626854.36 0.289696E+09
           
Annual Sum or Average 0.380653E+10 0.151470E+10 0.229183E+10 0.413869E+10 0.222523E+10
Minimum of Months 62991728.83 13111787.98 49879940.85 29626854.36 0.126583E+09
Maximum of Months 0.574394E+09 0.253401E+09 0.320993E+09 0.681069E+09 0.289696E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE LEFT WALL WINDOW1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 34569656.69 0.00 34569656.69 6902216.26 0.156552E+09
February 48757919.88 0.00 48757919.88 15527669.46 0.130153E+09
March 74709325.25 1058.91 74708266.34 40514396.75 0.113179E+09
April 0.117874E+09 637971.16 0.117236E+09 98047223.36 92381034.35
May 0.152729E+09 7902725.09 0.144826E+09 0.126235E+09 80721898.72
June 0.162240E+09 9923470.49 0.152317E+09 0.149964E+09 70459395.37
July 0.159382E+09 9012731.00 0.150370E+09 0.149225E+09 73042051.90
August 0.125916E+09 2439432.28 0.123477E+09 0.113871E+09 83059017.22
September 92386794.19 55538.11 92331256.08 77620313.19 96703698.31
October 61129597.21 0.00 61129597.21 37870675.02 0.109330E+09
November 35544954.04 0.00 35544954.04 9710008.76 0.126856E+09
December 25012887.13 0.00 25012887.13 1747380.52 0.170592E+09
           
Annual Sum or Average 0.109025E+10 29972927.05 0.106028E+10 0.827234E+09 0.130303E+10
Minimum of Months 25012887.13 0.00 25012887.13 1747380.52 70459395.37
Maximum of Months 0.162240E+09 9923470.49 0.152317E+09 0.149964E+09 0.170592E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: OFFICE LEFT WALL WINDOW2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 34568471.84 0.00 34568471.84 6901484.08 0.156552E+09
February 48756291.65 0.00 48756291.65 15526274.58 0.130153E+09
March 74706663.97 1058.86 74705605.11 40511522.27 0.113179E+09
April 0.117870E+09 637941.26 0.117232E+09 98042934.31 92380683.85
May 0.152724E+09 7902354.68 0.144822E+09 0.126229E+09 80721576.54
June 0.162235E+09 9923005.37 0.152312E+09 0.149957E+09 70459134.66
July 0.159378E+09 9012308.57 0.150365E+09 0.149219E+09 73041676.80
August 0.125913E+09 2439317.94 0.123473E+09 0.113866E+09 83058489.30
September 92384093.86 55535.51 92328558.35 77617329.17 96703027.21
October 61127603.02 0.00 61127603.02 37868633.06 0.109329E+09
November 35543732.70 0.00 35543732.70 9709124.07 0.126856E+09
December 25012016.75 0.00 25012016.75 1747064.60 0.170592E+09
           
Annual Sum or Average 0.109022E+10 29971522.18 0.106025E+10 0.827195E+09 0.130303E+10
Minimum of Months 25012016.75 0.00 25012016.75 1747064.60 70459134.66
Maximum of Months 0.162235E+09 9923005.37 0.152312E+09 0.149957E+09 0.170592E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_6

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_7

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_8

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_9

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_10

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_5

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_14

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_13

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_12

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FINESTORAGE_SKYLIGHT_11

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 49016954.16 0.129226E+09
February 0.100442E+09 35762613.77 64678973.30 92186529.81 0.112108E+09
March 0.139178E+09 26436240.06 0.112741E+09 0.136010E+09 94997510.25
April 0.326752E+09 0.174661E+09 0.152092E+09 0.383217E+09 86776019.49
May 0.404492E+09 0.223111E+09 0.181380E+09 0.463129E+09 82215292.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.483318E+09 71553925.41
July 0.436855E+09 0.253878E+09 0.182977E+09 0.510036E+09 78112871.41
August 0.376542E+09 0.226975E+09 0.149567E+09 0.440130E+09 91438191.71
September 0.268449E+09 0.159711E+09 0.108738E+09 0.310027E+09 98627168.28
October 0.142209E+09 62225511.32 79983293.24 0.149394E+09 0.100024E+09
November 67664725.88 19770168.54 47894557.34 55703719.75 0.107999E+09
December 44529470.18 10970547.99 33558922.19 26171992.12 0.143484E+09
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.309834E+10 0.119656E+10
Minimum of Months 44529470.18 10970547.99 33558922.19 26171992.12 71553925.41
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.510036E+09 0.143484E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R1C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R2C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R3C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R4C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R5C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R8C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C1

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C2

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C4

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R6C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHT_R7C3

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63936073.71 17702201.82 46233871.89 63147840.78 88464568.71
February 0.100442E+09 35762613.77 64678973.30 0.108375E+09 77389854.56
March 0.139178E+09 26436240.06 0.112741E+09 0.154367E+09 67011493.08
April 0.326752E+09 0.174661E+09 0.152092E+09 0.398664E+09 74470069.20
May 0.404492E+09 0.223111E+09 0.181380E+09 0.478828E+09 72270082.31
June 0.416994E+09 0.224447E+09 0.192547E+09 0.500572E+09 61176456.19
July 0.436855E+09 0.253878E+09 0.182977E+09 0.523796E+09 70276440.27
August 0.376542E+09 0.226975E+09 0.149567E+09 0.449553E+09 86269235.87
September 0.268449E+09 0.159711E+09 0.108738E+09 0.316731E+09 94497529.78
October 0.142209E+09 62225511.32 79983293.24 0.153870E+09 94901886.90
November 67664725.88 19770168.54 47894557.34 66142290.38 78422454.82
December 44529470.18 10970547.99 33558922.19 37385635.68 94442508.67
           
Annual Sum or Average 0.278804E+10 0.143565E+10 0.135239E+10 0.325143E+10 0.959593E+09
Minimum of Months 44529470.18 10970547.99 33558922.19 37385635.68 61176456.19
Maximum of Months 0.436855E+09 0.253878E+09 0.192547E+09 0.523796E+09 94901886.90



Table of Contents

Report: WindowZoneSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 66.79 304.52 114.27 28.90 85.37 0.00 0.00
February 153.28 283.89 196.79 66.47 130.32 0.00 0.00
March 139.99 223.12 196.81 27.11 169.70 0.00 0.00
April 454.16 193.73 422.80 131.97 290.83 0.00 0.00
May 527.84 167.08 503.26 163.70 339.57 0.00 0.00
June 601.45 149.64 546.31 181.42 364.89 0.00 0.00
July 617.70 150.86 547.92 195.95 351.97 0.00 0.00
August 512.90 171.04 453.99 157.50 296.49 0.00 0.00
September 400.20 199.33 362.66 131.74 230.92 0.00 0.00
October 183.05 218.20 200.37 55.82 144.55 0.00 0.00
November 69.36 260.89 111.18 24.66 86.52 0.00 0.00
December 22.19 342.47 65.71 9.79 55.92 0.00 0.00
               
Annual Sum or Average 312.96 221.79 310.55 97.96 212.59 0.00 0.00
Minimum of Months 22.19 149.64 65.71 9.79 55.92 0.00 0.00
Maximum of Months 617.70 342.47 547.92 195.95 364.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 256.21 675.47 334.19 92.53 241.66 0.00 0.00
February 533.49 648.77 581.26 206.96 374.30 0.00 0.00
March 710.93 496.55 727.48 138.18 589.30 0.00 0.00
April 2069.84 468.70 1764.87 943.38 821.48 0.00 0.00
May 2420.77 429.74 2114.28 1166.20 948.08 0.00 0.00
June 2610.52 386.48 2252.28 1212.29 1039.99 0.00 0.00
July 2665.96 408.30 2283.44 1327.02 956.42 0.00 0.00
August 2300.56 477.95 1968.19 1186.40 781.79 0.00 0.00
September 1674.53 532.71 1449.96 862.64 587.32 0.00 0.00
October 780.88 522.82 743.33 325.25 418.07 0.00 0.00
November 300.87 583.33 365.47 106.78 258.69 0.00 0.00
December 136.80 749.99 232.76 57.34 175.41 0.00 0.00
               
Annual Sum or Average 1375.47 531.20 1237.72 637.34 600.38 0.00 0.00
Minimum of Months 136.80 386.48 232.76 57.34 175.41 0.00 0.00
Maximum of Months 2665.96 749.99 2283.44 1327.02 1039.99 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3231.16 6156.20 763.87 211.50 552.38 0.00 0.00
February 5933.72 5819.08 1328.59 473.05 855.54 0.00 0.00
March 7700.44 4178.05 1662.81 315.85 1346.97 0.00 0.00
April 20536.02 3040.20 4033.98 2156.30 1877.68 0.00 0.00
May 24518.77 2613.92 4832.64 2665.61 2167.03 0.00 0.00
June 27253.91 2265.94 5148.07 2770.95 2377.12 0.00 0.00
July 25363.60 2519.20 5219.29 3033.19 2186.11 0.00 0.00
August 21392.43 3114.15 4498.71 2711.76 1786.95 0.00 0.00
September 16551.12 3543.34 3314.19 1971.74 1342.45 0.00 0.00
October 7704.42 4345.19 1699.03 743.44 955.59 0.00 0.00
November 3210.55 5228.93 835.37 244.08 591.29 0.00 0.00
December 2001.83 6708.63 532.01 131.07 400.94 0.00 0.00
               
Annual Sum or Average 13813.65 4120.50 2829.06 1456.77 1372.29 0.00 0.00
Minimum of Months 2001.83 2265.94 532.01 131.07 400.94 0.00 0.00
Maximum of Months 27253.91 6708.63 5219.29 3033.19 2377.12 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.178891E+09 0.815633E+09 0.306069E+09 77408692.93 0.228661E+09 0.00 0.00
February 0.370821E+09 0.686777E+09 0.476073E+09 0.160798E+09 0.315275E+09 0.00 0.00
March 0.374938E+09 0.597602E+09 0.527144E+09 72609283.44 0.454535E+09 0.00 0.00
April 0.117717E+10 0.502137E+09 0.109589E+10 0.342057E+09 0.753829E+09 0.00 0.00
May 0.141378E+10 0.447513E+09 0.134794E+10 0.438446E+09 0.909496E+09 0.00 0.00
June 0.155896E+10 0.387869E+09 0.141604E+10 0.470239E+09 0.945803E+09 0.00 0.00
July 0.165446E+10 0.404065E+09 0.146755E+10 0.524828E+09 0.942721E+09 0.00 0.00
August 0.137375E+10 0.458125E+09 0.121597E+10 0.421860E+09 0.794110E+09 0.00 0.00
September 0.103732E+10 0.516660E+09 0.940016E+09 0.341469E+09 0.598546E+09 0.00 0.00
October 0.490281E+09 0.584415E+09 0.536661E+09 0.149504E+09 0.387156E+09 0.00 0.00
November 0.179791E+09 0.676230E+09 0.288167E+09 63907305.49 0.224259E+09 0.00 0.00
December 59434083.10 0.917261E+09 0.176008E+09 26223575.96 0.149785E+09 0.00 0.00
               
Annual Sum or Average 0.986958E+10 0.699429E+10 0.979353E+10 0.308935E+10 0.670418E+10 0.00 0.00
Minimum of Months 59434083.10 0.387869E+09 0.176008E+09 26223575.96 0.149785E+09 0.00 0.00
Maximum of Months 0.165446E+10 0.917261E+09 0.146755E+10 0.524828E+09 0.945803E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.686237E+09 0.180917E+10 0.895105E+09 0.247831E+09 0.647274E+09 0.00 0.00
February 0.129061E+10 0.156951E+10 0.140618E+10 0.500677E+09 0.905506E+09 0.00 0.00
March 0.190414E+10 0.132997E+10 0.194849E+10 0.370107E+09 0.157838E+10 0.00 0.00
April 0.536504E+10 0.121486E+10 0.457453E+10 0.244525E+10 0.212929E+10 0.00 0.00
May 0.648380E+10 0.115101E+10 0.566289E+10 0.312356E+10 0.253932E+10 0.00 0.00
June 0.676646E+10 0.100175E+10 0.583792E+10 0.314226E+10 0.269566E+10 0.00 0.00
July 0.714050E+10 0.109358E+10 0.611597E+10 0.355429E+10 0.256168E+10 0.00 0.00
August 0.616182E+10 0.128013E+10 0.527159E+10 0.317765E+10 0.209394E+10 0.00 0.00
September 0.434038E+10 0.138078E+10 0.375829E+10 0.223595E+10 0.152234E+10 0.00 0.00
October 0.209151E+10 0.140033E+10 0.199092E+10 0.871157E+09 0.111977E+10 0.00 0.00
November 0.779852E+09 0.151198E+10 0.947306E+09 0.276782E+09 0.670524E+09 0.00 0.00
December 0.366408E+09 0.200877E+10 0.623413E+09 0.153588E+09 0.469825E+09 0.00 0.00
               
Annual Sum or Average 0.433768E+11 0.167519E+11 0.390326E+11 0.200991E+11 0.189335E+11 0.00 0.00
Minimum of Months 0.366408E+09 0.100175E+10 0.623413E+09 0.153588E+09 0.469825E+09 0.00 0.00
Maximum of Months 0.714050E+10 0.200877E+10 0.611597E+10 0.355429E+10 0.269566E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.865434E+10 0.164888E+11 0.204595E+10 0.566470E+09 0.147948E+10 0.00 0.00
February 0.143548E+11 0.140775E+11 0.321413E+10 0.114440E+10 0.206973E+10 0.00 0.00
March 0.206248E+11 0.111905E+11 0.445368E+10 0.845960E+09 0.360772E+10 0.00 0.00
April 0.532294E+11 0.788021E+10 0.104561E+11 0.558914E+10 0.486694E+10 0.00 0.00
May 0.656711E+11 0.700112E+10 0.129437E+11 0.713957E+10 0.580417E+10 0.00 0.00
June 0.706421E+11 0.587332E+10 0.133438E+11 0.718231E+10 0.616150E+10 0.00 0.00
July 0.679339E+11 0.674741E+10 0.139794E+11 0.812409E+10 0.585527E+10 0.00 0.00
August 0.572975E+11 0.834094E+10 0.120494E+11 0.726319E+10 0.478616E+10 0.00 0.00
September 0.429005E+11 0.918433E+10 0.859038E+10 0.511075E+10 0.347963E+10 0.00 0.00
October 0.206355E+11 0.116381E+11 0.455068E+10 0.199122E+10 0.255947E+10 0.00 0.00
November 0.832175E+10 0.135534E+11 0.216527E+10 0.632645E+09 0.153263E+10 0.00 0.00
December 0.536171E+10 0.179684E+11 0.142494E+10 0.351058E+09 0.107389E+10 0.00 0.00
               
Annual Sum or Average 0.435627E+12 0.129944E+12 0.892174E+11 0.459408E+11 0.432766E+11 0.00 0.00
Minimum of Months 0.536171E+10 0.587332E+10 0.142494E+10 0.351058E+09 0.107389E+10 0.00 0.00
Maximum of Months 0.706421E+11 0.179684E+11 0.139794E+11 0.812409E+10 0.616150E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.18 3.23 2.03 1.05 -4.0 28.28 62.93 0.00
February 4.25 3.55 2.74 1.60 -5.0 43.80 86.73 0.02
March 5.90 4.45 2.76 1.18 -1.9 68.95 35.00 0.00
April 8.96 6.24 3.38 1.56 -0.7 96.13 186.12 0.00
May 9.99 8.07 6.28 3.35 -0.9 110.92 199.68 0.02
June 13.31 11.27 9.70 3.33 3.35 121.69 199.28 0.00
July 15.02 12.39 10.49 3.21 4.49 111.91 220.83 0.00
August 15.65 12.75 10.65 2.92 3.95 91.47 211.91 0.00
September 13.43 11.01 9.10 2.64 1.43 68.72 198.32 0.01
October 9.33 8.03 6.81 1.97 -1.0 48.92 91.86 0.04
November 6.66 5.66 4.54 2.05 -2.3 30.27 53.24 0.04
December 4.10 3.14 1.95 2.36 -5.1 20.52 40.74 0.04
                 
Annual Sum or Average 9.26 7.50 5.89 2.27 -0.6 70.25 132.30 0.02
Minimum of Months 4.10 3.14 1.95 1.05 -5.1 20.52 35.00 0.00
Maximum of Months 15.65 12.75 10.65 3.35 4.49 121.69 220.83 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 29-JAN-05:00 9.37 5.00 3.60 8.35 0.00 0.00
February 11.00 07-FEB-14:00 9.86 9.00 2.10 6.35 138.00 225.00
March 14.00 25-MAR-12:00 11.22 9.00 2.60 7.35 287.00 93.00
April 24.00 30-APR-14:00 13.13 4.00 1.50 7.75 167.50 716.00
May 24.00 22-MAY-14:00 16.08 11.00 2.60 9.33 159.00 769.00
June 27.00 13-JUN-16:00 17.53 12.00 3.10 12.41 141.50 652.50
July 30.00 22-JUL-17:00 16.80 8.00 0.00 14.28 122.00 407.00
August 27.00 14-AUG-17:19 14.18 3.33 2.60 10.37 133.00 358.83
September 23.00 11-SEP-16:00 16.22 12.00 2.60 8.74 108.00 325.50
October 19.00 07-OCT-14:00 10.10 1.00 1.50 2.22 131.00 540.50
November 16.00 24-NOV-11:00 12.01 9.00 4.10 9.33 61.50 0.00
December 13.00 23-DEC-10:00 7.64 2.00 7.70 6.75 70.50 0.00
                 
Annual Sum or Average                
Minimum of Months 11.00   7.64 1.00 0.00 2.22 0.00 0.00
Maximum of Months 30.00   17.53 12.00 7.70 14.28 287.00 769.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.0 10-JAN-07:00 -7.0 -9.0 0.00 -20.0 0.00 0.00
February -4.0 17-FEB-06:00 -4.0 -4.0 0.00 -20.5 0.00 0.00
March -1.0 08-MAR-06:00 -1.4 -2.0 0.00 -14.4 17.50 184.50
April 0.00 08-APR-04:00 -0.9 -2.0 0.00 -12.7 0.00 0.00
May 2.00 06-MAY-04:00 1.57 1.00 3.60 -13.7 12.50 117.00
June 6.00 01-JUN-03:00 5.05 4.00 0.00 -9.2 0.00 0.00
July 7.00 05-JUL-04:00 6.47 6.00 3.10 -7.8 28.00 155.00
August 8.00 20-AUG-04:00 7.45 7.00 0.00 -6.6 0.00 0.00
September 5.00 20-SEP-03:00 5.00 5.00 2.60 -10.0 0.00 0.00
October 2.00 07-OCT-03:00 2.00 2.00 0.00 -13.4 0.00 0.00
November -2.0 29-NOV-01:00 -2.0 -2.0 3.10 -10.7 0.00 0.00
December -3.0 29-DEC-20:00 -4.5 -7.0 3.60 -20.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -6.0   -7.0 -9.0 0.00 -20.5 0.00 0.00
Maximum of Months 8.00   7.45 7.00 3.60 -6.6 28.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.44 29-JAN-04:00 13.00 12.00 0.00 9.13 0.00 0.00
February 9.86 07-FEB-14:00 11.00 9.00 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.39 28-APR-07:00 16.00 15.00 0.00 5.54 119.50 626.00
May 16.08 22-MAY-14:00 24.00 11.00 2.60 9.33 159.00 769.00
June 19.93 25-JUN-17:00 22.00 19.00 0.00 15.94 136.50 360.50
July 17.31 22-JUL-09:00 26.00 12.00 4.60 11.46 224.50 619.50
August 17.06 14-AUG-12:00 24.00 13.00 2.60 9.91 205.50 669.50
September 16.54 10-SEP-15:00 21.00 14.00 3.60 8.54 160.50 483.00
October 13.58 17-OCT-14:00 16.00 12.00 0.00 12.03 144.00 44.50
November 12.01 24-NOV-11:00 16.00 9.00 4.10 9.33 61.50 0.00
December 7.93 02-DEC-12:00 9.00 7.00 0.00 2.01 135.50 84.00
                 
Annual Sum or Average                
Minimum of Months 7.93   9.00 7.00 0.00 2.01 0.00 0.00
Maximum of Months 19.93   26.00 19.00 4.60 15.94 224.50 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 29-JAN-04:00 13.00 12.44 0.00 9.13 0.00 0.00
February 9.00 07-FEB-14:00 11.00 9.86 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.00 28-APR-07:00 16.00 15.39 0.00 5.54 119.50 626.00
May 12.00 23-MAY-07:00 17.00 13.95 3.10 5.13 112.00 719.50
June 19.00 25-JUN-17:00 22.00 19.93 0.00 15.94 136.50 360.50
July 14.00 17-JUL-17:00 18.00 15.45 3.60 9.91 120.00 0.00
August 16.00 08-AUG-12:00 18.00 16.70 1.50 11.46 154.00 0.00
September 14.00 10-SEP-15:00 21.00 16.54 3.60 8.54 160.50 483.00
October 13.00 17-OCT-18:00 13.00 13.00 2.60 9.33 0.00 0.00
November 12.00 08-NOV-14:00 12.00 12.00 0.00 8.15 93.00 106.00
December 7.00 02-DEC-11:00 8.00 7.45 3.10 1.16 144.50 146.50
                 
Annual Sum or Average                
Minimum of Months 7.00   8.00 7.45 0.00 1.16 0.00 0.00
Maximum of Months 19.00   22.00 19.93 3.60 15.94 160.50 719.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.33 8.85 0.00
February 18.00 13.00 16.00 10.00 14.79 0.00
March 18.00 13.00 16.00 10.33 17.09 0.00
April 18.00 13.00 16.00 11.26 40.86 0.00
May 18.00 13.00 16.00 12.54 47.73 0.00
June 18.00 13.00 16.00 13.82 50.98 0.00
July 18.00 13.00 16.00 14.77 51.67 0.00
August 18.00 13.00 16.00 15.12 44.67 0.00
September 18.00 13.00 16.00 14.78 34.25 0.00
October 18.00 13.00 16.00 13.84 17.71 0.00
November 18.00 13.00 16.00 12.55 9.34 0.00
December 18.00 13.00 16.00 11.27 6.14 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.57 28.73 0.00
Minimum of Months 18.00 13.00 16.00 10.00 6.14 0.00
Maximum of Months 18.00 13.00 16.00 15.12 51.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.939897E+09 -869209174.2 0.00 0.00 744.00 0.00 -70687494.5 58.99 0.00 0.00
February 0.867651E+09 -803824819.3 0.00 0.00 672.00 0.00 -63826290.3 58.99 0.00 0.00
March 0.100315E+10 -933151985.0 0.00 0.00 744.00 0.00 -69995367.8 58.99 0.00 0.00
April 0.915847E+09 -850512630.0 0.00 0.00 720.00 0.00 -65334079.5 58.99 0.00 0.00
May 0.927165E+09 -860902991.7 0.00 0.00 744.00 0.00 -66262264.7 58.99 0.00 0.00
June 0.894995E+09 -834447313.4 0.00 0.00 720.00 0.00 -60548129.5 58.99 0.00 0.00
July 0.850570E+09 -789596030.5 0.00 0.00 744.00 0.00 -60974451.2 58.99 0.00 0.00
August 0.902177E+09 -841405599.7 0.00 0.00 744.00 0.00 -60771405.6 59.00 0.00 0.00
September 0.849206E+09 -788047003.3 0.00 0.00 720.00 0.00 -61159418.1 59.00 0.00 0.00
October 0.875124E+09 -806694832.0 0.00 0.00 744.00 0.00 -68429291.2 58.99 0.00 0.00
November 0.864703E+09 -796621880.5 0.00 0.00 720.00 0.00 -68080867.2 58.99 0.00 0.00
December 0.922857E+09 -851915327.8 0.00 0.00 744.00 0.00 -70941405.1 58.99 0.00 0.00
                     
Annual Sum or Average 0.108133E+11 -0.100263E+11 0.00 0.00 8760.00 0.00 -787010464.8 58.99 0.00 0.00
Minimum of Months 0.849206E+09 -933151985.0 0.00 0.00 672.00 0.00 -70941405.1 58.99 0.00 0.00
Maximum of Months 0.100315E+10 -788047003.3 0.00 0.00 744.00 0.00 -60548129.5 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: ZONE2 FINE STORAGE_DAYLCTRL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.81 0.55 25-JAN-12:30 134.81 0.00 0.00 0.00 107.37 0.00 0.00 0.00
February 217.00 0.73 0.50 09-FEB-12:30 186.10 0.00 0.00 14.50 1069.75 0.00 0.00 44.17
March 215.50 0.68 0.50 01-MAR-11:50 259.96 0.00 0.00 101.17 225.79 0.00 0.00 51.33
April 359.67 0.65 0.50 01-APR-09:39 315.23 0.00 0.00 180.83 251.56 0.00 0.00 125.17
May 417.17 0.64 0.50 01-MAY-09:09 339.50 0.00 0.00 226.50 262.84 0.00 0.00 159.83
June 410.67 0.62 0.50 01-JUN-09:00 376.12 0.00 0.00 238.00 289.89 0.00 0.00 173.00
July 429.00 0.63 0.50 01-JUL-10:20 341.93 0.00 0.00 234.67 266.18 0.00 0.00 158.33
August 396.33 0.65 0.50 01-AUG-09:30 306.97 0.00 0.00 191.17 244.65 0.00 0.00 134.67
September 337.67 0.68 0.50 01-SEP-09:30 251.51 0.00 0.00 110.17 206.47 0.00 0.00 69.50
October 234.00 0.70 0.50 01-OCT-10:30 218.17 0.00 0.00 42.67 177.66 0.00 0.00 15.17
November 171.33 0.78 0.54 05-NOV-11:39 153.26 0.00 0.00 0.00 123.72 0.00 0.00 0.00
December 131.67 0.83 0.67 02-DEC-11:30 122.43 0.00 0.00 0.00 99.37 0.00 0.00 0.00
                         
Annual Sum or Average 3515.67 0.68     278.45 0.00 0.00 1339.67 278.10 0.00 0.00 931.17
Minimum of Months 131.67 0.62 0.50   122.43 0.00 0.00 0.00 99.37 0.00 0.00 0.00
Maximum of Months 429.00 0.83 0.67   376.12 0.00 0.00 238.00 1069.75 0.00 0.00 173.00



Table of Contents

Report: DaylightingReportMonthly

For: ZONE3 BULK STORAGE_DAYLCTRL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.68 0.50 01-JAN-12:20 157.02 11.50 0.00 55.83 127.66 14.77 0.00 20.33
February 217.00 0.62 0.50 01-FEB-11:39 216.77 13.22 0.00 122.67 176.25 16.76 17.33 81.67
March 215.50 0.59 0.50 01-MAR-11:39 527.24 14.98 8.67 219.00 439.86 17.62 42.83 184.50
April 359.67 0.57 0.50 01-APR-07:40 661.06 15.99 16.50 287.33 559.68 19.18 131.67 244.67
May 417.17 0.56 0.50 01-MAY-06:00 391.40 15.47 2.17 339.83 784.36 19.90 136.00 286.83
June 410.67 0.54 0.50 01-JUN-06:40 430.82 16.00 1.83 347.67 1368.17 21.40 139.67 295.67
July 429.00 0.56 0.50 01-JUL-06:49 395.73 15.55 3.17 350.50 948.78 20.42 141.83 295.67
August 396.33 0.57 0.50 01-AUG-07:19 355.80 15.08 0.17 307.50 291.12 18.91 118.33 260.33
September 337.67 0.59 0.50 01-SEP-07:00 295.06 14.57 0.00 242.00 242.91 18.51 99.67 193.83
October 234.00 0.59 0.50 01-OCT-08:30 862.33 14.12 0.00 165.67 443.95 19.17 52.17 126.00
November 171.33 0.64 0.50 01-NOV-11:00 179.14 12.38 0.00 68.83 146.20 15.71 0.00 31.50
December 131.67 0.69 0.50 02-DEC-10:30 143.99 11.55 0.00 21.83 118.85 14.84 0.00 1.33
                         
Annual Sum or Average 3515.67 0.59     407.09 14.69 32.50 2528.67 568.14 18.76 879.50 2022.33
Minimum of Months 131.67 0.54 0.50   143.99 11.50 0.00 21.83 118.85 14.77 0.00 1.33
Maximum of Months 429.00 0.69 0.50   862.33 16.00 16.50 350.50 1368.17 21.40 141.83 295.67



Table of Contents

Report: DaylightingReportMonthly

For: ZONE1 OFFICE_DAYLCTRL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 195.67 0.84 0.65 19-JAN-15:30 197.64 22.22 77.33 14.00 88.81 19.45 58.17 0.00
February 217.00 0.79 0.61 09-FEB-15:30 461.25 24.04 111.83 42.17 131.23 20.89 107.00 4.00
March 215.50 0.78 0.61 02-MAR-16:40 287.78 23.05 139.17 33.50 197.43 23.46 157.50 13.83
April 359.67 0.73 0.61 01-APR-13:00 364.85 22.50 223.50 119.83 326.96 23.64 269.00 78.50
May 417.17 0.72 0.61 01-MAY-13:50 333.03 21.83 236.83 123.17 362.31 22.90 305.67 95.33
June 410.67 0.71 0.61 01-JUN-14:09 360.65 22.15 243.17 143.50 459.82 23.19 301.00 96.33
July 429.00 0.71 0.61 01-JUL-14:00 350.75 21.91 239.17 145.33 471.37 23.01 309.00 109.17
August 396.33 0.73 0.61 01-AUG-14:09 354.72 22.08 225.00 127.67 354.74 23.00 280.67 97.00
September 337.67 0.75 0.61 01-SEP-14:09 431.03 23.79 186.67 103.83 331.83 24.27 215.83 70.83
October 234.00 0.78 0.61 01-OCT-14:20 312.52 23.66 127.67 48.67 168.19 22.76 132.67 16.50
November 171.33 0.83 0.64 03-NOV-15:20 196.39 21.93 72.50 10.00 97.84 19.92 58.33 0.00
December 131.67 0.87 0.66 25-DEC-14:30 140.15 18.69 28.83 0.00 75.09 18.68 23.67 0.00
                         
Annual Sum or Average 3515.67 0.75     335.89 22.40 1911.67 911.67 303.45 22.57 2218.50 581.50
Minimum of Months 131.67 0.71 0.61   140.15 18.69 28.83 0.00 75.09 18.68 23.67 0.00
Maximum of Months 429.00 0.87 0.66   461.25 24.04 243.17 145.33 471.37 24.27 309.00 109.17



Table of Contents

Report: CoilReportMonthly

For: PSZ-OFFICE HEATING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.570374E+10 23613.96 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.473913E+10 23613.96 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.486116E+10 23613.96 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.167211E+10 23613.96 01-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.975264E+09 23613.96 05-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.121838E+09 23613.96 08-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 23649777.82 10458.75 05-JUL-07:03 0.00 0.00 0.00 0.00 0.00
August 3743423.98 4619.66 31-AUG-07:03 0.00 0.00 0.00 0.00 0.00
September 0.190857E+09 11876.69 20-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.203542E+10 23613.96 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.423783E+10 23613.96 01-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.589491E+10 23613.96 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.304597E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3743423.98 4619.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.589491E+10 23613.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-FINE STORAGE HEATING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128796E+11 60020.11 09-JAN-22:43 0.00 0.00 0.00 0.00 0.00
February 0.104244E+11 60020.11 17-FEB-04:13 0.00 0.00 0.00 0.00 0.00
March 0.694585E+10 44698.26 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.459324E+09 39178.91 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.128564E+10 43712.03 24-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.794654E+10 60020.11 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.164069E+11 60020.11 12-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.563482E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164069E+11 60020.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106164E+11 36340.35 10-JAN-05:53 0.00 0.00 0.00 0.00 0.00
February 0.597437E+10 24806.06 19-FEB-22:00 0.00 0.00 0.00 0.00 0.00
March 0.438902E+09 12163.62 04-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.197367E+10 22740.96 29-NOV-03:57 0.00 0.00 0.00 0.00 0.00
December 0.199870E+11 37780.72 30-DEC-01:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.389903E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.199870E+11 37780.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-OFFICE COOLING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 96955369.25 95428565.90 3352.61 29-APR-15:50 3255.53 0.00
May 0.00 0.00 0.223480E+09 0.198884E+09 3710.72 22-MAY-15:40 3321.18 0.00
June 0.00 0.00 0.128957E+10 0.111249E+10 7296.78 13-JUN-16:00 6457.20 0.00
July 0.00 0.00 0.242885E+10 0.211567E+10 15415.09 22-JUL-07:02 15145.94 0.00
August 0.00 0.00 0.267784E+10 0.232873E+10 6560.59 14-AUG-16:00 6158.44 0.00
September 0.00 0.00 0.987757E+09 0.857896E+09 5151.40 13-SEP-16:00 4501.24 0.00
October 0.00 0.00 6578537.76 6578537.76 1087.14 07-OCT-15:30 1087.14 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.771103E+10 0.671568E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.267784E+10 0.232873E+10 15415.09   15145.94 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-FINE STORAGE COOLING COIL

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:05 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00
June 0.00 0.00 23299834.77 20503785.72 3089.14 13-JUN-16:00 2761.18 0.00
July 0.00 0.00 0.453266E+09 0.430479E+09 34663.64 23-JUL-16:15 26732.10 0.00
August 0.00 0.00 2112400.70 2100184.97 772.14 14-AUG-16:00 772.14 0.00
September 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.478678E+09 0.453082E+09       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.453266E+09 0.430479E+09 34663.64   26732.10 0.00



Table of Contents

Report: FanReportMonthly

For: ZONE3UNITHEATER ZONE3HIRADIANT FAN

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 97126119.59 0.03 96.57 01-JAN-00:05 0.08
February 74178694.20 0.02 96.57 02-FEB-04:20 0.08
March 10690771.32 0.00 96.57 03-MAR-20:20 0.08
April 0.00 0.00 0.00 01-APR-00:05 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 24974105.35 0.01 96.57 19-NOV-06:50 0.08
December 0.163804E+09 0.05 96.57 01-DEC-00:05 0.08
           
Annual Sum or Average 0.370774E+09 0.01      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.163804E+09 0.05 96.57   0.08



Table of Contents

Report: FanReportMonthly

For: PSZ-OFFICE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.100916E+10 0.39 999.15 02-JAN-11:30 0.92
February 0.926053E+09 0.38 999.15 01-FEB-11:10 0.91
March 0.108172E+10 0.39 999.15 01-MAR-08:30 0.92
April 0.992349E+09 0.36 999.15 01-APR-07:03 0.92
May 0.102939E+10 0.35 999.15 01-MAY-06:40 0.92
June 0.102872E+10 0.36 999.15 05-JUN-11:30 0.91
July 0.989158E+09 0.34 999.15 01-JUL-12:10 0.91
August 0.106829E+10 0.36 999.15 01-AUG-08:40 0.91
September 0.989158E+09 0.35 999.15 01-SEP-08:00 0.91
October 0.992847E+09 0.34 999.15 02-OCT-06:10 0.92
November 0.961342E+09 0.36 999.15 01-NOV-10:10 0.91
December 0.101238E+10 0.39 999.15 02-DEC-14:00 0.91
           
Annual Sum or Average 0.120806E+11 0.36      
Minimum of Months 0.926053E+09 0.34 999.15   0.91
Maximum of Months 0.108172E+10 0.39 999.15   0.92



Table of Contents

Report: FanReportMonthly

For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.106503E+10 0.51 1825.66 09-JAN-22:43 0.89
February 0.953344E+09 0.51 1825.66 17-FEB-04:13 0.89
March 0.972260E+09 0.44 1359.61 27-MAR-05:01 0.89
April 0.736140E+09 0.23 1445.30 03-APR-06:01 0.80
May 0.751880E+09 0.21 730.26 01-MAY-06:10 0.54
June 0.751880E+09 0.21 730.26 13-JUN-15:20 0.53
July 0.728386E+09 0.20 1280.19 22-JUL-17:20 0.74
August 0.780799E+09 0.21 730.26 14-AUG-16:30 0.53
September 0.722962E+09 0.20 730.26 01-SEP-06:05 0.53
October 0.759658E+09 0.25 1528.03 24-OCT-06:01 0.82
November 0.913511E+09 0.44 1825.66 28-NOV-06:01 0.89
December 0.115996E+10 0.55 1825.66 12-DEC-06:01 0.89
           
Annual Sum or Average 0.102958E+11 0.33      
Minimum of Months 0.722962E+09 0.20 730.26   0.53
Maximum of Months 0.115996E+10 0.55 1825.66   0.89



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.100916E+10 0.00 0.00
February 0.00 0.00 0.00 0.926053E+09 0.00 0.00
March 0.00 0.00 0.00 0.108172E+10 0.00 0.00
April 0.00 0.00 0.00 0.101125E+10 0.00 0.00
May 0.00 0.00 0.00 0.107276E+10 0.00 0.00
June 0.00 0.00 0.00 0.127429E+10 0.00 0.00
July 0.00 0.00 0.00 0.144525E+10 0.00 0.00
August 0.00 0.00 0.00 0.157313E+10 0.00 0.00
September 0.00 0.00 0.00 0.117918E+10 0.00 0.00
October 0.00 0.00 0.00 0.994161E+09 0.00 0.00
November 0.00 0.00 0.00 0.961342E+09 0.00 0.00
December 0.00 0.00 0.00 0.101238E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.135407E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.926053E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.157313E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.106503E+10 0.00 0.00
February 0.00 0.00 0.00 0.953344E+09 0.00 0.00
March 0.00 0.00 0.00 0.972260E+09 0.00 0.00
April 0.00 0.00 0.00 0.736140E+09 0.00 0.00
May 0.00 0.00 0.00 0.751880E+09 0.00 0.00
June 0.00 0.00 0.00 0.757352E+09 0.00 0.00
July 0.00 0.00 0.00 0.828913E+09 0.00 0.00
August 0.00 0.00 0.00 0.781309E+09 0.00 0.00
September 0.00 0.00 0.00 0.722962E+09 0.00 0.00
October 0.00 0.00 0.00 0.759658E+09 0.00 0.00
November 0.00 0.00 0.00 0.913511E+09 0.00 0.00
December 0.00 0.00 0.00 0.115996E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.104023E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.722962E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.115996E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.100916E+10 0.00 0.570374E+10 0.00 0.00 0.00 0.00 0.00
February 0.926053E+09 0.00 0.473913E+10 0.00 0.00 0.00 0.00 0.00
March 0.108172E+10 0.00 0.486116E+10 0.00 0.00 0.00 0.00 0.00
April 0.992349E+09 96955369.25 0.167211E+10 0.00 0.00 0.00 0.00 0.00
May 0.102939E+10 0.223480E+09 0.975264E+09 0.00 0.00 0.00 0.00 0.00
June 0.102872E+10 0.128957E+10 0.121838E+09 0.00 0.00 0.00 0.00 0.00
July 0.989158E+09 0.242885E+10 23649777.82 0.00 0.00 0.00 0.00 0.00
August 0.106829E+10 0.267784E+10 3743423.98 0.00 0.00 0.00 0.00 0.00
September 0.989158E+09 0.987757E+09 0.190857E+09 0.00 0.00 0.00 0.00 0.00
October 0.992847E+09 6578537.76 0.203542E+10 0.00 0.00 0.00 0.00 0.00
November 0.961342E+09 0.00 0.423783E+10 0.00 0.00 0.00 0.00 0.00
December 0.101238E+10 0.00 0.589491E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.120806E+11 0.771103E+10 0.304597E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.926053E+09 0.00 3743423.98 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108172E+10 0.267784E+10 0.589491E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.106503E+10 0.00 0.128796E+11 0.00 0.00 0.00 0.00 0.00
February 0.953344E+09 0.00 0.104244E+11 0.00 0.00 0.00 0.00 0.00
March 0.972260E+09 0.00 0.694585E+10 0.00 0.00 0.00 0.00 0.00
April 0.736140E+09 0.00 0.459324E+09 0.00 0.00 0.00 0.00 0.00
May 0.751880E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.751880E+09 23299834.77 0.00 0.00 0.00 0.00 0.00 0.00
July 0.728386E+09 0.428442E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.780799E+09 2112400.70 0.00 0.00 0.00 0.00 0.00 0.00
September 0.722962E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.759658E+09 0.00 0.128564E+10 0.00 0.00 0.00 0.00 0.00
November 0.913511E+09 0.00 0.794654E+10 0.00 0.00 0.00 0.00 0.00
December 0.115996E+10 0.00 0.164069E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102958E+11 0.453854E+09 0.563482E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.722962E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115996E+10 0.428442E+09 0.164069E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.100916E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.926053E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.108172E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.992349E+09 0.00 0.00 0.00 18903694.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.102939E+10 0.00 0.00 0.00 43370784.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.102872E+10 0.00 0.00 0.00 0.245567E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.989158E+09 0.00 0.00 0.00 0.456089E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.106829E+10 0.00 0.00 0.00 0.504839E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.989158E+09 0.00 0.00 0.00 0.190022E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.992847E+09 0.00 0.00 0.00 1314374.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.961342E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.101238E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.120806E+11 0.00 0.00 0.00 0.146011E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.926053E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108172E+10 0.00 0.00 0.00 0.504839E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.106503E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.953344E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.972260E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.736140E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.751880E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.751880E+09 0.00 0.00 0.00 5471443.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.728386E+09 0.00 0.00 0.00 0.100528E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.780799E+09 0.00 0.00 0.00 510479.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.722962E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.759658E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.913511E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.115996E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.102958E+11 0.00 0.00 0.00 0.106510E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.722962E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115996E+10 0.00 0.00 0.00 0.100528E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ZONE1 OFFICE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 26458461.62 0.00 0.00 0.00 0.00 0.216912E+10 0.00 0.00 0.14
February 21742973.13 0.00 0.00 0.00 0.00 0.189100E+10 0.00 0.00 0.14
March 37560559.99 0.00 0.00 0.00 0.00 0.204168E+10 0.00 0.00 0.15
April 0.639407E+09 0.00 0.00 125528.42 258657.74 0.812642E+09 71899743.10 0.00 0.14
May 0.873096E+09 0.00 0.00 304513.94 0.00 0.481005E+09 0.159309E+09 0.00 0.14
June 0.582338E+09 3676188.75 0.00 1632308.12 126184.99 52231635.90 0.598391E+09 0.00 0.15
July 0.301298E+09 5663848.63 0.00 2909135.11 46198.35 12012565.51 0.630669E+09 0.00 0.14
August 0.224854E+09 1531.25 0.00 3455123.88 0.00 1580014.61 0.664436E+09 0.00 0.15
September 0.514990E+09 0.00 0.00 1262956.50 0.00 83278079.53 0.491599E+09 0.00 0.14
October 0.463710E+09 0.00 0.00 7128.84 0.00 0.996464E+09 11507958.13 0.00 0.14
November 26654044.48 0.00 0.00 0.00 0.00 0.173302E+10 0.00 0.00 0.14
December 24264968.13 0.00 0.00 0.00 0.00 0.212931E+10 0.00 0.00 0.14
                   
Annual Sum or Average 0.373637E+10 9341568.62 0.00 9696694.81 431041.08 0.124033E+11 0.262781E+10 0.00 0.14
Minimum of Months 21742973.13 0.00 0.00 0.00 0.00 1580014.61 0.00 0.00 0.14
Maximum of Months 0.873096E+09 5663848.63 0.00 3455123.88 258657.74 0.216912E+10 0.664436E+09 0.00 0.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ZONE2 FINE STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.287091E+10 0.00 0.00 0.00 0.00 0.239895E+10 0.00 0.00 0.17
February 0.336017E+10 0.00 0.00 0.00 0.00 0.104501E+10 0.00 0.00 0.18
March 0.414538E+10 0.00 0.00 0.00 0.00 0.541237E+09 0.00 0.00 0.19
April 0.391344E+10 0.00 0.00 0.00 4290047.33 0.00 0.00 0.00 0.18
May 0.429821E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
June 0.428986E+10 0.00 0.00 58082.97 17496.90 0.00 61055079.46 0.00 0.19
July 0.382228E+10 0.00 0.00 869675.70 556824.91 0.00 0.307093E+09 0.00 0.18
August 0.396001E+10 0.00 0.00 13108.65 0.00 0.00 59755707.29 0.00 0.19
September 0.340000E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
October 0.329645E+10 0.00 0.00 0.00 0.00 43048101.76 0.00 0.00 0.17
November 0.299737E+10 0.00 0.00 0.00 0.00 0.868539E+09 0.00 0.00 0.17
December 0.206970E+10 0.00 0.00 0.00 0.00 0.292163E+10 0.00 0.00 0.17
                   
Annual Sum or Average 0.424238E+11 0.00 0.00 940867.32 4864369.14 0.781842E+10 0.427903E+09 0.00 0.18
Minimum of Months 0.206970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.429821E+10 0.00 0.00 869675.70 4290047.33 0.292163E+10 0.307093E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ZONE3 BULK STORAGE

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 10:44:06

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.146209E+12 0.149106E+11 0.00 0.103185E+11 0.111972E+11
February 0.255751E+12 0.187956E+11 0.00 0.892225E+10 0.854787E+10
March 0.333961E+12 0.140927E+11 0.00 0.937780E+10 0.570490E+10
April 0.954534E+12 0.174352E+11 0.00 0.793118E+10 0.110900E+10
May 0.114115E+13 0.423355E+11 0.00 0.821596E+10 0.722283E+09
June 0.116505E+13 0.380374E+11 0.00 0.774970E+10 0.162302E+10
July 0.119532E+13 0.390439E+11 0.00 0.725857E+10 0.345035E+10
August 0.988984E+12 0.346587E+11 0.00 0.702792E+10 0.318719E+10
September 0.716256E+12 0.301656E+11 0.00 0.678543E+10 0.127075E+10
October 0.314046E+12 0.241190E+11 0.00 0.709327E+10 0.158606E+10
November 0.931516E+11 0.221764E+11 0.00 0.790360E+10 0.616583E+10
December 0.293689E+10 0.298682E+11 0.00 0.980451E+10 0.151923E+11
           
Annual Sum or Average 0.730735E+13 0.325639E+12 0.00 0.983887E+11 0.597568E+11
Minimum of Months 0.293689E+10 0.140927E+11 0.00 0.678543E+10 0.722283E+09
Maximum of Months 0.119532E+13 0.423355E+11 0.00 0.103185E+11 0.151923E+11