Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 10:43:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1184.68 | 245.02 | 245.02 |
Net Site Energy | 1184.68 | 245.02 | 245.02 |
Total Source Energy | 3631.39 | 751.04 | 751.04 |
Net Source Energy | 3631.39 | 751.04 | 751.04 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 57.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 147.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 166.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1126.83 | 57.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 57.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 147.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 144.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 57.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 147.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 166.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 69.73 | 11.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 233.05 | 11.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 69.73 | 11.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 233.05 | 11.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1126.834 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1126.834 | 100.00 |
Total On-Site and Utility Electric Sources | 1126.834 | 100.00 |
Total Electricity End Uses | 1126.834 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 4.33 |
Time Setpoint Not Met During Occupied Cooling | 26.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2607.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 15.50 |
Skylight-Roof Ratio [%] | 0.34 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 11-OCT-11:30 |
Heating | 0.00 | 39840.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33014.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13555.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1168.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 96034.19 | 39840.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 39840.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33014.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11250.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1168.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 62.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 466.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 527.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3568.68 | 62.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 96.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 109.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 738.07 | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 96.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 109.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 738.07 | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.57 |
ZONE2 FINE STORAGE DIRECT AIR | 5.08 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.30 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.30 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 48172.08 |
PSZ-OFFICE HEATING COIL | 35300.89 |
PSZ-FINE STORAGE HEATING COIL | 142246.12 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 48172.08 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
PSZ-FINE STORAGE | 5.08 | 5.08 | 5.08 | 5.08 | 5.08 | 5.08 | 1.00 | 1.000000 | 5.08 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.57 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 5.08 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.57 | 1713.30 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 5.08 | 9537.01 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.57 | 28292.74 | 35300.89 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 5.08 | 5.08 | 5.08 | 5.08 | 110110.60 | 142246.12 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.57 | 0.782683 | 1.57 | 28292.74 | 14585.31 | 28292.74 | 0.800720 | 0.800720 |
PSZ-FINE STORAGE COOLING COIL | 5.08 | 2.54 | 5.08 | 110110.60 | 56512.14 | 110110.60 | 0.745760 | 0.745760 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
8 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
9 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
10 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
11 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
12 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
13 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
14 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
15 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
16 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.21548121E-14 | -0.16827101E-15 | 0.71656587E-12 | 0.12539735E-15 |
85 | 3 | -0.52378714E-04 | 0.55487071E-06 | -0.36253864E-03 | 0.13752504E-12 |
86 | 2 | 1.1001971 | 0.12432070E-01 | 1.6865760 | -0.69502831E-04 |
87 | 1 | -16.840218 | 0.32704464 | -7.1998246 | 0.32320315 |
88 | 0 | 16.290177 | 0.21062598 | 6.0637144 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.7283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
2 | NONRESWINDOW_U_0.7283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
3 | NONRESWINDOW_U_0.7283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
4 | NONRESWINDOW_U_0.7283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 4.139 | 4.139 | 1.000 | 0.254 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.4 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.12675 | 0.51233 | 0.51233 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.71778E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.483 | 0.390 | 0.391 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 14395.59210 | 17274.71053 | 1.30447 | 1.56537 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 39.47000 | 5.62903E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8433.99507 | 10120.79409 | 0.26067 | 0.31281 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 59931.37315 | 71917.64778 | 4.23303 | 5.07964 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23393.15286 | 28071.78343 | 0.60927 | 0.73113 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 40143.39893 | 48172.07871 | 1.08041 | 1.29650 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 22543.67 | 1.56537 | 1.56537 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9227.96 | 0.31281 | 0.31281 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 87494.05 | 5.07964 | 5.07964 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 25485.40 | 0.73113 | 0.73113 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56537 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.07964 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.29650 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.29650 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 48172.07622 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 48172.07871 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56537 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56537 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56537 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56537 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56537 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.56537 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.07964 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.07964 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.07964 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 5.07964 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.07964 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 5.07964 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.56537 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 5.07964 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56537 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56537 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1713.30220 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56537 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56537 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56537 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56537 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56537 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78268 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.56537 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28292.74000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14585.30668 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28292.74000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80072 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80072 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28292.74000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35300.88602 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 35300.88602 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.07964 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.07964 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 9537.00978 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.07964 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.07964 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.07964 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.07964 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.07964 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.53982 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.07964 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 110110.60000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 56512.13589 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 110110.60000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74576 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74576 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 110110.60000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 142246.12468 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 142246.12468 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 27077.7 | 10.85 | 10.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 106164.8 | 10.37 | 9.77 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1212732698 | 0.1086629104 | Pass | Pass | 0.5473728128 | 4.7882835889 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2535605714 | 0.3063759491 | Pass | Pass | 0.7459604388 | 6.0021166984 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.8114401764E-002 | 4.4724535904E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10485.34 | 508.95 | 0.00 | 64.65 | 657.47 | 11716.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.34 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.7283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.139 | 0.254 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.7283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.139 | 0.254 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.7283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.139 | 0.254 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.7283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.139 | 0.254 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.483 | 0.390 | 0.391 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 33.16 | 4.915 | 0.323 | 0.322 | |||||||||||||||||
North Total or Average | 6.51 | 4.139 | 0.254 | 0.251 | |||||||||||||||||
Non-North Total or Average | 26.65 | 5.104 | 0.339 | 0.339 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.79 | 83.79 | 134.19 | |
Exterior Lighting Total | 8532.22 | 134.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28292.74 | 22654.56 | 5638.18 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 110110.60 | 82116.08 | 27994.52 | 0.75 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 27077.7 | 10.85 | 10.22 | ||||
PSZ-FINE STORAGE COOLING COIL | 106164.8 | 10.37 | 9.77 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 48172.08 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 35300.89 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 142246.12 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.30 | 120.46 | 92.91 | 1.00 | 3.90 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.57 | 1713.30 | 1094.51 | 1.00 | 1.32 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 5.08 | 9537.01 | 1877.50 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14395.59 | 17274.71 | 72.93 | 1.304 | 1.565 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00807 | 39.47 | 0.00563 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 59931.37 | 71917.65 | 51.61 | 4.233 | 5.080 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00788 | 40.67 | 0.00563 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 39.91 | 0.00572 | 40.67 | 0.00563 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8434.00 | 10120.79 | 42.73 | 0.261 | 0.313 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00782 | 0.50 | 0.00432 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 23393.15 | 28071.78 | 20.15 | 0.609 | 0.731 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00680 | 0.50 | 0.00432 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 40143.40 | 48172.08 | 15.03 | 1.080 | 1.296 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00595 | 0.50 | 0.00432 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.57 | 1.57 | 0.31 | 0.31 | 1.5654 | 1.5654 | 1.5654 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 5.08 | 5.08 | 0.73 | 0.73 | 5.0796 | 5.0796 | 5.0796 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 48172.076 | 48172.076 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 48172.08 | 48172.08 | 1.296498 | 10.00 | 7.37 | 0.00594872 | 43.33 | 21.00 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 10.00 | 0.00594872 | 70.9616 | 48172.08 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 28292.740 | 22654.563 | 1.565370 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 28292.74 | 28292.74 | 1.565370 | 26.11 | 15.61 | 0.00787866 | 12.00 | 10.29 | 0.00787866 | 39.82 | 0.00562958 | 18.28 | 7.6873 | 23.90 | 0.00806618 | 39.6851 | 14378.96 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 35300.886 | 35300.886 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 35300.89 | 35300.89 | 1.565366 | 19.47 | 12.93 | 0.00754958 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.6873 | 21.10 | 0.00781889 | 45.6226 | 8434.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 110110.600 | 82116.081 | 5.079640 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 110110.60 | 110110.60 | 5.079640 | 29.37 | 16.58 | 0.00772356 | 12.00 | 10.13 | 0.00772356 | 40.80 | 0.00563111 | 18.58 | 6.9675 | 26.70 | 0.00788030 | 32.8303 | 59918.42 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 142246.125 | 142246.125 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 142246.12 | 142246.12 | 5.079638 | 14.51 | 10.07 | 0.00662780 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.9675 | 15.56 | 0.00680097 | 56.2812 | 23393.15 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 48172.076 | 48172.076 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.296498 | 1.41732374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 48172.08 | 48172.08 | 1.0000 | 1.41732374 | 1.296498 | 10.00 | 7.37 | 0.00594872 | 25035.3 | 43.33 | 21.00 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48172.08 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 10.00 | 0.00594872 | 10.00 | 0.00594872 | 70.9616 | 48172.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28292.740 | 22654.563 | 1.565370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4860 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.565366 | 1.71124957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 28292.74 | 28292.74 | 1.0000 | 1.71125343 | 1.565370 | 26.11 | 15.61 | 0.00787866 | 46320.1 | 12.00 | 10.29 | 0.00787866 | 31937.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28292.74 | 39.82 | 0.00562958 | 18.28 | 0.12033486 | 7.6873 | 23.90 | 0.00806618 | 23.90 | 0.00806618 | 39.6851 | 14378.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35300.886 | 35300.886 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.565366 | 1.71124957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 35300.89 | 35300.89 | 1.0000 | 1.71124957 | 1.565366 | 19.47 | 12.93 | 0.00754958 | 38719.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35300.89 | 0.50 | 0.00431558 | 0.50 | 0.12033486 | 7.6873 | 21.05 | 0.00781889 | 21.10 | 0.00781889 | 45.6226 | 8434.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 110110.600 | 82116.081 | 5.079640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1977 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.079638 | 5.55303098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 110110.60 | 110110.60 | 1.0000 | 5.55303307 | 5.079640 | 29.37 | 16.58 | 0.00772356 | 49248.3 | 12.00 | 10.13 | 0.00772356 | 31546.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 110110.60 | 40.80 | 0.00563111 | 18.58 | 0.35392606 | 6.9675 | 26.70 | 0.00788030 | 26.70 | 0.00788030 | 32.8303 | 59918.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 142246.125 | 142246.125 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.079638 | 5.55303098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 142246.12 | 142246.12 | 1.0000 | 5.55303098 | 5.079638 | 14.51 | 10.07 | 0.00662780 | 31332.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 142246.12 | 0.50 | 0.00431558 | 0.50 | 0.35392606 | 6.9675 | 15.56 | 0.00680097 | 15.56 | 0.00680097 | 56.2812 | 23393.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.12 | 1.57 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.35 | 5.08 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1768.83 | 1408.33 | 167.83 |
ZONE2 FINE STORAGE | 3082.00 | 2125.17 | 1738.17 |
ZONE3 BULK STORAGE | 2808.17 | 3314.50 | 2590.00 |
Facility | 3503.83 | 3437.33 | 2607.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 4.50 | 47.50 | 4.33 | 26.50 |
ZONE2 FINE STORAGE | 3.33 | 287.50 | 0.17 | 1.17 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 7.67 | 327.33 | 4.33 | 26.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 1.177 | 0.481 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1.264 | 0.361 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.151 | 0.000 | 1.464 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 4248778.21 | 0.00 | 4248778.21 | 2774240.53 | 7023018.74 | 3794880.16 | 5616.78 | 1931.61 | 1211.61 | 0.73 |
ZONE2 FINE STORAGE | 13848921.91 | 0.00 | 13848921.91 | 9791994.30 | 23640916.21 | 11161412.23 | 5559.33 | 1932.89 | 1267.79 | 52.77 |
ZONE3 BULK STORAGE | 0.00 | 0.35E+09 | 0.35E+09 | 38699785.83 | 0.39E+09 | 25671248.14 | 5922.27 | 15.91 | 2821.82 | 5116.00 |
Total Facility | 18097700.12 | 0.35E+09 | 0.37E+09 | 51266020.66 | 0.42E+09 | 40627540.53 | 7305.74 | 2251.34 | 4280.29 | 5116.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.3244 | 0.0000 | 0.3244 | 0.1325 | 0.4569 | 0.1203 | 493.51 | 1931.61 | 1210.88 |
ZONE2 FINE STORAGE | 1.0077 | 0.0000 | 1.0077 | 0.2883 | 1.2960 | 0.3539 | 488.09 | 1932.89 | 1215.02 |
ZONE3 BULK STORAGE | 0.0000 | 13.6228 | 13.6228 | 1.4276 | 15.0503 | 0.8140 | 2134.83 | 8.38 | 1492.80 |
Total Facility | 1.3321 | 13.6228 | 14.9549 | 1.8483 | 16.8032 | 1.2883 | 2181.74 | 2243.81 | 2912.88 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 5077602.65 | 0.00 | 5077602.65 | 3794880.16 | 5614.37 | 0.42 | 3145.22 | 0.73 |
PSZ-FINE STORAGE | 16550480.90 | 0.00 | 16550480.90 | 11161412.23 | 5558.51 | 0.17 | 3201.32 | 52.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3876 | 0.0000 | 0.3876 | 0.1203 | 491.09 | 0.42 | 3144.49 |
PSZ-FINE STORAGE | 1.2043 | 0.0000 | 1.2043 | 0.3539 | 487.28 | 0.17 | 3148.55 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2450.56 | 702.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2499.06 | 704.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3895 | 0.6489 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.2290 | 1.9490 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1126.83 | 5771.67 | 01-JAN-08:00 | 96034.19 | 28-JUN-15:00 |
Electricity:Building | 677.27 | 5288.67 | 01-JAN-00:10 | 50600.89 | 05-APR-14:20 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 370.34 | 2117.83 | 01-JAN-00:10 | 28507.00 | 05-APR-14:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 166.46 | 0.00 | 01-JAN-00:40 | 13555.61 | 13-APR-11:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 21.79 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
Ventilation (simple):Fans:Electricity | 21.79 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 21.79 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-AUG-05:10 |
ElectricityPurchased:Facility | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
ElectricityNet:Plant | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1126.83 | 5771.67 | 19-MAR-14:50 | 96034.19 | 28-JUN-15:00 |
Electricity:HVAC | 291.94 | 0.00 | 01-JAN-00:40 | 47712.64 | 30-JUN-16:00 |
General:Fans:Electricity | 144.67 | 0.00 | 01-JAN-00:40 | 11250.31 | 04-JAN-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 147.27 | 0.00 | 01-JAN-00:10 | 36462.33 | 30-JUN-16:00 |
General:Cooling:Electricity | 147.27 | 0.00 | 01-JAN-00:10 | 36462.33 | 30-JUN-16:00 |
ExteriorLights:Electricity | 134.19 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.19 | 0.00 | 01-JAN-07:30 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 23.43 | 483.00 | 26-APR-05:10 | 1789.08 | 21-JAN-12:10 |
WaterSystems:Electricity | 23.43 | 483.00 | 26-APR-05:10 | 1789.08 | 21-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 23.43 | 483.00 | 26-APR-05:10 | 1789.08 | 21-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 57.85 | 1750.00 | 26-APR-05:10 | 39840.47 | 02-JAN-06:10 |
NaturalGas:HVAC | 57.85 | 1750.00 | 26-APR-05:10 | 39840.47 | 02-JAN-06:10 |
Heating:NaturalGas | 57.85 | 1750.00 | 26-APR-05:10 | 39840.47 | 02-JAN-06:10 |
General:Heating:NaturalGas | 57.85 | 1750.00 | 26-APR-05:10 | 39840.47 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 831.92 | 0.00 | 01-JAN-00:40 | 175268.56 | 30-JUN-16:00 |
EnergyTransfer:Building | 376.03 | 0.00 | 01-JAN-00:40 | 78076.80 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 82.09 | 0.00 | 01-JAN-00:10 | 18792.13 | 30-JUN-16:10 |
Heating:EnergyTransfer | 18.23 | 0.00 | 01-JAN-00:40 | 28421.23 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.37 | 0.00 | 01-JAN-00:10 | 16043.71 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 18.23 | 0.00 | 01-JAN-00:40 | 28421.23 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.37 | 0.00 | 01-JAN-00:10 | 16043.71 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 357.80 | 0.00 | 01-JAN-00:10 | 78076.80 | 30-JUN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 79.72 | 0.00 | 01-JAN-00:10 | 18792.13 | 30-JUN-16:10 |
General:Cooling:EnergyTransfer | 357.80 | 0.00 | 01-JAN-00:10 | 78076.80 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 79.72 | 0.00 | 01-JAN-00:10 | 18792.13 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 293.94 | 0.00 | 01-JAN-00:40 | 61924.04 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.86 | 0.00 | 01-JAN-00:40 | 20205.34 | 01-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.86 | 0.00 | 01-JAN-00:40 | 20205.34 | 01-JAN-07:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 278.08 | 0.00 | 01-JAN-00:10 | 61924.04 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 278.08 | 0.00 | 01-JAN-00:10 | 61924.04 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 455.90 | 0.00 | 01-JAN-00:40 | 97191.76 | 30-JUN-16:00 |
HeatingCoils:EnergyTransfer | 1.77 | 0.00 | 01-JAN-00:40 | 27781.35 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 454.13 | 0.00 | 01-JAN-00:10 | 97191.76 | 30-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.368 | -79.716 | 0.000 | 0.000 | 9.197 | 30.293 | 31.946 | 14.086 | 0.000 | 8.279 | 5.302 | 0.000 | -8.674 | 0.000 | -13.080 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 15.861 | -278.070 | 0.000 | 0.000 | 17.821 | 244.699 | 0.000 | 0.000 | 0.000 | 21.724 | 27.144 | 0.000 | 0.000 | 0.000 | -49.178 | -0.003 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 34.559 | 241.203 | 107.344 | 140.618 | 0.000 | 76.416 | 0.021 | 0.000 | -59.624 | 0.000 | -504.325 | -36.190 |
Total Facility | 0.000 | 0.000 | 18.229 | -357.786 | 0.000 | 0.000 | 61.577 | 516.195 | 139.290 | 154.704 | 0.000 | 106.419 | 32.466 | 0.000 | -68.298 | 0.000 | -566.583 | -36.194 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | -35882.31 | 0.00 | 0.00 | 88.87 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 36583.31 | 0.00 | -806.39 | 0.00 | -1130.41 | 0.00 |
ZONE2 FINE STORAGE | 16-APR-11:41 | 0.00 | 0.00 | 0.00 | -107919.54 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 107067.14 | 0.00 | -0.00 | 0.00 | -1296.13 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUN-05:01 | 0.00 | 0.00 | 0.00 | -122389.31 | 0.00 | 0.00 | 542.26 | 4839.54 | 2623.78 | 0.00 | 0.00 | 289.45 | 219449.57 | 0.00 | -3675.29 | 0.00 | -101680.01 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-DEC-06:01 | 0.00 | 0.00 | 35326.24 | 0.00 | 0.00 | 0.00 | 138.26 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1070.96 | 0.00 | -2140.28 | -33400.18 |
ZONE2 FINE STORAGE | 02-JAN-06:01 | 0.00 | 0.00 | 67900.14 | 0.00 | 0.00 | 0.00 | 358.68 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2209.73 | -68197.61 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-06:01 | 0.00 | 0.00 | 103225.23 | 0.00 | 0.00 | 0.00 | 1380.68 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5216.62 | 0.00 | -10321.11 | -96531.50 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5654 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5654 | 0.0769 | 1.0000 | Not calculated | 0.1203 | 0.0769 | ||
PSZ-FINE STORAGE | 5.0796 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 5.0796 | 0.0697 | 1.0000 | Not calculated | 0.3539 | 0.0697 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5654 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5654 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0769 | ||
PSZ-FINE STORAGE | 5.0796 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 5.0796 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.0697 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5654 | 1.5654 | 1.5654 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0796 | 5.0796 | 5.0796 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5654 | 1.5654 | 1.5654 | 1.5654 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 5.0796 | 5.0796 | 5.0796 | 5.0796 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5654 | 1.5654 | 1.5654 | No | 0.1203 | 0.3847 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0796 | 5.0796 | 5.0796 | No | 0.3539 | 0.4841 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5654 | 1.5654 | 1.5654 | 1.5654 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 5.0796 | 5.0796 | 5.0796 | 5.0796 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 4.33 |
Number of hours cooling loads not met | 26.67 |
Number of hours not met | 31.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 57.85 | 39840.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 147.27 | 36462.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.19 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 21.79 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 144.67 | 11250.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.43 | 1789.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1126.83 |
Natural Gas | 0.00 | 57.85 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1184.68 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 30.46 |
Fans (All) | 34.43 |
Service Water Heating | 4.85 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 233.05 |
Subtotal | 233.05 |
Natural Gas [MJ/m2] | |
Space Heating | 11.96 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.96 |
Subtotal | 11.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 43.57 |
Space Heating | 4.88 |
Space Cooling | 12.43 |
Fans (All) | 14.05 |
Service Water Heating | 1.98 |
Receptacle Equipment | 11.76 |
Miscellaneous | 11.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 6862.50 | 1897.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7901.50 | 858.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 4498.33 | 3493.33 | 767.33 | 1.00 | 0.00 |
Min | 4498.33 | 858.50 | 0.00 | 0.00 | 0.00 |
Max | 7901.50 | 3493.33 | 767.33 | 1.00 | 0.00 |
Average | 6420.78 | 2083.11 | 255.78 | 0.33 | 0.00 |
Sum | 19262.33 | 6249.33 | 767.33 | 1.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 73914.00 | 8805.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 89746.33 | 71511.00 | 29890.17 | 45.50 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 89746.33 | 71511.00 | 29890.17 | 45.50 | 0.00 |
Average | 65562.44 | 26772.00 | 9963.39 | 15.17 | 0.00 |
Sum | 196687.33 | 80316.00 | 29890.17 | 45.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7642.50 | 1117.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7713.33 | 1046.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5957.17 | 2765.00 | 37.83 | 0.00 | 0.00 |
Min | 5957.17 | 1046.67 | 0.00 | 0.00 | 0.00 |
Max | 7713.33 | 2765.00 | 37.83 | 0.00 | 0.00 |
Average | 7104.33 | 1643.06 | 12.61 | 0.00 | 0.00 |
Sum | 21313.00 | 4929.17 | 37.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32907.67 | 119.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 71565.50 | 11153.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 118642.50 | 70502.50 | 2048.00 | 0.00 | 0.00 |
Min | 32907.67 | 119.33 | 0.00 | 0.00 | 0.00 |
Max | 118642.50 | 70502.50 | 2048.00 | 0.00 | 0.00 |
Average | 74371.89 | 27258.44 | 682.67 | 0.00 | 0.00 |
Sum | 223115.67 | 81775.33 | 2048.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255687E+10 | 6971.10 | 31-JAN-16:30 | 29.00 | 10.73 | 0.618347E+09 | 768.96 | 03-JAN-13:09 | 29.00 | 10.73 |
February | 0.150596E+10 | 5253.63 | 25-FEB-17:00 | 17.00 | 8.59 | 0.568568E+09 | 769.02 | 18-FEB-14:09 | 17.00 | 8.59 |
March | 0.296227E+10 | 7870.70 | 18-MAR-16:00 | 27.20 | 11.10 | 0.671916E+09 | 769.01 | 18-MAR-10:09 | 27.20 | 11.10 |
April | 0.698830E+10 | 35591.10 | 24-APR-05:01 | 15.17 | 4.62 | 0.634333E+09 | 768.97 | 03-APR-07:10 | 15.17 | 4.62 |
May | 0.911161E+10 | 35880.78 | 01-MAY-05:02 | 13.00 | 4.59 | 0.659951E+09 | 768.97 | 13-MAY-09:20 | 22.67 | 10.91 |
June | 0.120772E+11 | 33937.94 | 21-JUN-05:01 | 18.00 | 8.30 | 0.660292E+09 | 769.04 | 30-JUN-08:30 | 32.00 | 19.49 |
July | 0.113937E+11 | 33516.85 | 01-JUL-05:01 | 18.83 | 6.90 | 0.635258E+09 | 769.09 | 17-JUL-10:30 | 32.00 | 20.99 |
August | 0.116874E+11 | 31972.20 | 24-AUG-05:01 | 19.83 | 9.70 | 0.685955E+09 | 769.09 | 16-AUG-10:20 | 19.83 | 9.70 |
September | 0.991536E+10 | 31545.71 | 16-SEP-05:01 | 19.90 | 12.48 | 0.634939E+09 | 769.09 | 11-SEP-14:30 | 19.90 | 12.48 |
October | 0.632653E+10 | 34821.77 | 19-OCT-05:02 | 14.00 | 6.85 | 0.632295E+09 | 769.08 | 03-OCT-12:20 | 14.00 | 6.85 |
November | 0.339650E+10 | 26504.08 | 03-NOV-05:03 | 16.00 | 12.46 | 0.602388E+09 | 769.03 | 01-NOV-12:20 | 16.00 | 12.46 |
December | 0.179627E+10 | 6116.08 | 22-DEC-16:30 | 24.50 | 9.81 | 0.612152E+09 | 768.96 | 20-DEC-13:09 | 24.50 | 9.81 |
Annual Sum or Average | 0.797180E+11 | 0.761640E+10 | ||||||||
Minimum of Months | 0.150596E+10 | 5253.63 | 13.00 | 4.59 | 0.568568E+09 | 768.96 | 14.00 | 4.62 | ||
Maximum of Months | 0.120772E+11 | 35880.78 | 29.00 | 12.48 | 0.685955E+09 | 769.09 | 32.00 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305650E+10 | 14412.97 | 31-JAN-15:40 | 28.67 | 10.84 | 0.171098E+10 | 2248.77 | 04-JAN-13:50 | 28.67 | 10.84 |
February | 0.922835E+09 | 10340.98 | 23-FEB-14:00 | 18.00 | 10.78 | 0.155403E+10 | 2246.80 | 14-FEB-13:09 | 18.00 | 10.78 |
March | 0.427848E+10 | 91814.69 | 18-MAR-17:11 | 26.63 | 12.71 | 0.188381E+10 | 2246.89 | 18-MAR-10:50 | 26.63 | 12.71 |
April | 0.244279E+11 | 107921.38 | 16-APR-11:41 | 22.83 | 13.09 | 0.184481E+10 | 2246.80 | 27-APR-15:30 | 26.50 | 12.08 |
May | 0.346583E+11 | 100361.03 | 17-MAY-23:42 | 22.50 | 10.51 | 0.192586E+10 | 2246.80 | 23-MAY-09:20 | 26.67 | 11.17 |
June | 0.519216E+11 | 103657.21 | 07-JUN-02:21 | 23.00 | 10.72 | 0.192841E+10 | 2246.97 | 30-JUN-08:50 | 32.67 | 19.33 |
July | 0.496732E+11 | 97999.59 | 02-JUL-00:03 | 22.62 | 8.36 | 0.185400E+10 | 2247.13 | 27-JUL-15:20 | 32.67 | 21.38 |
August | 0.465594E+11 | 97976.90 | 24-AUG-23:21 | 24.50 | 10.23 | 0.200258E+10 | 2247.10 | 01-AUG-12:20 | 24.50 | 10.23 |
September | 0.375797E+11 | 105035.75 | 20-SEP-01:01 | 23.80 | 13.76 | 0.185390E+10 | 2247.15 | 01-SEP-12:39 | 23.80 | 13.76 |
October | 0.184482E+11 | 104185.89 | 08-OCT-11:22 | 22.50 | 12.61 | 0.182639E+10 | 2247.10 | 03-OCT-12:30 | 22.50 | 12.61 |
November | 0.549229E+10 | 99364.80 | 01-NOV-17:11 | 25.33 | 14.39 | 0.170944E+10 | 2246.96 | 01-NOV-12:20 | 25.33 | 14.39 |
December | 0.106097E+10 | 10657.83 | 22-DEC-15:40 | 25.33 | 10.21 | 0.165027E+10 | 2246.80 | 14-DEC-13:20 | 25.33 | 10.21 |
Annual Sum or Average | 0.278080E+12 | 0.217445E+11 | ||||||||
Minimum of Months | 0.922835E+09 | 10340.98 | 18.00 | 8.36 | 0.155403E+10 | 2246.80 | 18.00 | 10.21 | ||
Maximum of Months | 0.519216E+11 | 107921.38 | 28.67 | 14.39 | 0.200258E+10 | 2248.77 | 32.67 | 21.38 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 | 1.81 | 0.271149E+10 | 4603.55 | 31-JAN-16:10 | 29.00 | 10.73 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.239368E+10 | 4119.03 | 01-FEB-14:50 | 15.17 | 7.01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.330846E+10 | 5172.86 | 18-MAR-15:30 | 27.20 | 11.82 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.500473E+10 | 8513.67 | 14-APR-15:00 | 35.00 | 14.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.601477E+10 | 9097.65 | 31-MAY-15:00 | 37.00 | 13.71 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 | 0.696530E+10 | 9097.65 | 01-JUN-12:00 | 37.00 | 17.36 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.648976E+10 | 9097.65 | 01-JUL-12:30 | 36.00 | 13.69 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.696957E+10 | 9097.65 | 01-AUG-14:09 | 36.00 | 21.41 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 | 16.66 | 0.605084E+10 | 9097.65 | 01-SEP-13:00 | 36.60 | 22.01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 | 15.51 | 0.479516E+10 | 8670.66 | 02-OCT-14:30 | 35.00 | 19.50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.327992E+10 | 5625.51 | 01-NOV-15:20 | 28.67 | 16.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.245798E+10 | 4097.67 | 01-DEC-15:39 | 23.20 | 10.01 |
Annual Sum or Average | 0.00 | 0.564417E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.239368E+10 | 4097.67 | 15.17 | 7.01 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.696957E+10 | 9097.65 | 37.00 | 22.01 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469630E+09 | 35325.10 | 02-JAN-06:01 | 4.33 |
February | 0.430556E+09 | 34257.31 | 13-FEB-06:02 | 8.00 |
March | 0.416405E+09 | 34929.90 | 27-MAR-05:01 | 2.52 |
April | 56606786.15 | 6551.19 | 29-APR-05:50 | 19.00 |
May | 28120162.05 | 8735.18 | 03-MAY-05:50 | 17.83 |
June | 5879937.02 | 3064.36 | 22-JUN-06:05 | 22.67 |
July | 1792530.38 | 3066.00 | 01-JUL-05:50 | 18.17 |
August | 2118317.19 | 2488.20 | 24-AUG-05:50 | 19.17 |
September | 8371931.17 | 2284.23 | 13-SEP-06:05 | 22.47 |
October | 92837492.87 | 8984.29 | 17-OCT-05:50 | 18.00 |
November | 0.201004E+09 | 25154.03 | 24-NOV-06:02 | 3.17 |
December | 0.654515E+09 | 35326.20 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 0.236784E+10 | |||
Minimum of Months | 1792530.38 | 2284.23 | -0.7 | |
Maximum of Months | 0.654515E+09 | 35326.20 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319192E+10 | 67900.15 | 02-JAN-06:01 | 4.33 |
February | 0.318115E+10 | 9491.03 | 11-FEB-07:25 | 14.50 |
March | 0.244295E+10 | 9686.70 | 16-MAR-06:25 | 13.55 |
April | 0.610078E+09 | 9496.64 | 05-APR-06:25 | 16.50 |
May | 0.136540E+09 | 8761.47 | 30-MAY-06:12 | 19.33 |
June | 11021990.68 | 8324.59 | 13-JUN-06:02 | 20.50 |
July | 11049420.75 | 8382.94 | 08-JUL-06:12 | 27.00 |
August | 7343774.47 | 8385.99 | 31-AUG-06:12 | 26.17 |
September | 26840479.68 | 9001.77 | 22-SEP-06:12 | 17.17 |
October | 0.836093E+09 | 9623.38 | 20-OCT-06:25 | 15.00 |
November | 0.170297E+10 | 9405.28 | 13-NOV-07:25 | 16.00 |
December | 0.370256E+10 | 9561.76 | 07-DEC-07:25 | 2.00 |
Annual Sum or Average | 0.158605E+11 | |||
Minimum of Months | 7343774.47 | 8324.59 | 2.00 | |
Maximum of Months | 0.370256E+10 | 67900.15 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21820352.83 | 0.178582E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196479E+10 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64644702.85 | 0.206169E+10 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596421E+09 | 0.796174E+09 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107769E+10 | 0.457304E+09 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196423E+10 | 0.142202E+09 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159365E+10 | 0.155653E+09 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144837E+10 | 0.215375E+09 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103338E+10 | 0.362599E+09 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431296E+09 | 0.120585E+10 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44741649.56 | 0.179202E+10 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2347524.80 | 0.214099E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827858E+10 | 0.130805E+11 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142202E+09 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196423E+10 | 0.214099E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5660009.43 | 0.684101E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654117E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26637776.32 | 0.818400E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125677E+10 | 0.330481E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279129E+10 | 0.198127E+10 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588968E+10 | 0.603607E+09 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498592E+10 | 0.540442E+09 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342630E+10 | 0.892088E+09 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251792E+10 | 0.150773E+10 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809213E+09 | 0.499300E+10 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14031041.13 | 0.705043E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693750.79 | 0.673821E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217241E+11 | 0.491778E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540442E+09 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588968E+10 | 0.818400E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112156E+10 | 0.147206E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170794E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463636E+09 | 0.219883E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105561E+10 | 0.149790E+11 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258047E+09 | 0.114043E+11 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101491E+10 | 0.510893E+10 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750811E+09 | 0.591780E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570404E+09 | 0.762804E+10 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272994E+09 | 0.107197E+11 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140255E+09 | 0.220745E+11 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201986E+09 | 0.212909E+11 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298005E+09 | 0.169621E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614822E+10 | 0.169874E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510893E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112156E+10 | 0.220745E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.40 | 31-JAN-17:10 | 6467.90 | 12-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6850.38 | 01-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1905.26 | 16-MAR-16:10 | 8268.73 | 27-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4271.00 | 10-APR-16:10 | 5587.24 | 21-APR-06:03 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5523.34 | 18-MAY-16:10 | 4089.66 | 01-MAY-06:03 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.61 | 30-JUN-16:10 | 1843.44 | 21-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7499.93 | 20-JUL-17:00 | 1113.08 | 17-JUL-19:52 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7290.78 | 25-AUG-17:00 | 1753.02 | 24-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6063.04 | 08-SEP-16:10 | 2668.76 | 22-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4624.74 | 04-OCT-17:00 | 6845.32 | 25-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.18 | 01-NOV-16:10 | 6776.49 | 24-NOV-07:40 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.16 | 21-DEC-15:00 | 8344.13 | 14-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.08 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.61 | 8344.13 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.81 | 31-JAN-16:50 | 9369.03 | 11-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 14729.69 | 02-FEB-16:55 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1195.94 | 16-MAR-16:00 | 11711.76 | 24-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6721.44 | 10-APR-16:00 | 7816.08 | 28-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9306.01 | 10-MAY-16:00 | 5581.64 | 23-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17955.75 | 30-JUN-16:00 | 3443.84 | 13-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18139.32 | 22-JUL-16:00 | 4677.34 | 26-JUL-24:00 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12615.32 | 12-AUG-16:00 | 9324.71 | 28-AUG-16:55 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10604.45 | 01-SEP-16:00 | 5300.24 | 15-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6816.63 | 10-OCT-15:10 | 11922.84 | 25-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.44 | 19-NOV-15:30 | 11354.14 | 29-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.81 | 25-DEC-14:00 | 10425.98 | 07-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3443.84 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18139.32 | 14729.69 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16074.54 | 06-JAN-13:10 | 20245.11 | 11-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 33590.09 | 02-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10583.53 | 15-MAR-13:00 | 30380.84 | 24-MAR-14:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16063.10 | 01-APR-15:00 | 25979.56 | 26-APR-18:00 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2924.15 | 20-MAY-14:00 | 20714.30 | 23-MAY-05:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5154.98 | 16-JUN-16:00 | 14732.02 | 13-JUN-06:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4030.78 | 17-JUL-15:00 | 27904.84 | 17-JUL-19:52 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3719.31 | 25-AUG-16:00 | 34279.23 | 28-AUG-17:00 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3932.70 | 17-SEP-11:53 | 22821.70 | 03-SEP-05:00 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3272.52 | 15-OCT-11:53 | 45069.41 | 07-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6020.71 | 19-NOV-15:00 | 48328.29 | 22-NOV-11:55 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6115.89 | 21-DEC-14:00 | 26814.20 | 07-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14732.02 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16074.54 | 48328.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6971.10 | 31-JAN-16:30 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 478.61 | 0.00 |
February | 5253.63 | 25-FEB-17:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.15 |
March | 7870.70 | 18-MAR-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 116.85 | 0.00 |
April | 35591.10 | 24-APR-05:01 | 1479.21 | 4585.41 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.28 |
May | 35880.78 | 01-MAY-05:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.41 |
June | 33937.94 | 21-JUN-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.60 |
July | 33516.85 | 01-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.66 |
August | 31972.20 | 24-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.39 |
September | 31545.71 | 16-SEP-05:01 | 1664.11 | 5158.58 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.80 |
October | 34821.77 | 19-OCT-05:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.22 |
November | 26504.08 | 03-NOV-05:03 | 739.61 | 2292.70 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.18 |
December | 6116.08 | 22-DEC-16:30 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5253.63 | 739.61 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35880.78 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 478.61 | 1130.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14412.97 | 31-JAN-15:40 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.36 | 0.00 |
February | 10340.98 | 23-FEB-14:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.09 |
March | 91814.69 | 18-MAR-17:11 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.80 | 0.00 |
April | 107921.38 | 16-APR-11:41 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.13 |
May | 100361.03 | 17-MAY-23:42 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.58 |
June | 103657.21 | 07-JUN-02:21 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.20 |
July | 97999.59 | 02-JUL-00:03 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.86 |
August | 97976.90 | 24-AUG-23:21 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.62 |
September | 105035.75 | 20-SEP-01:01 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.87 |
October | 104185.89 | 08-OCT-11:22 | 0.00 | 12891.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.49 |
November | 99364.80 | 01-NOV-17:11 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.86 |
December | 10657.83 | 22-DEC-15:40 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 10340.98 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107921.38 | 3955.50 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.36 | 1296.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 4235.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12637.67 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9376.73 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7225.29 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5868.85 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8174.41 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2753.07 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.98 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.00 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2605.66 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 21178.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4714.79 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4671.94 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8320.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.00 | |
Maximum of Months | 0.00 | 0.00 | 21178.33 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12637.67 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.821762E+11 | 71929.79 | 31-JAN-15:00 | 0.586173E+10 | 39840.47 | 02-JAN-06:10 |
February | 0.733418E+11 | 62379.62 | 18-FEB-15:09 | 0.457333E+10 | 9104.35 | 13-FEB-06:10 |
March | 0.852342E+11 | 73739.46 | 18-MAR-14:00 | 0.504729E+10 | 13488.56 | 27-MAR-06:10 |
April | 0.912280E+11 | 86012.42 | 14-APR-14:00 | 0.454259E+10 | 6304.69 | 29-APR-05:49 |
May | 0.101402E+12 | 88079.29 | 18-MAY-14:00 | 0.471312E+10 | 7813.63 | 03-MAY-05:49 |
June | 0.113423E+12 | 96034.19 | 28-JUN-14:00 | 0.453729E+10 | 3907.16 | 13-JUN-05:49 |
July | 0.111696E+12 | 92975.79 | 19-JUL-13:20 | 0.468851E+10 | 3937.86 | 01-JUL-05:49 |
August | 0.114468E+12 | 93710.53 | 25-AUG-14:00 | 0.468826E+10 | 3524.61 | 24-AUG-05:49 |
September | 0.103128E+12 | 90166.67 | 08-SEP-14:50 | 0.453651E+10 | 2608.17 | 30-SEP-05:49 |
October | 0.899560E+11 | 86634.08 | 02-OCT-13:00 | 0.470544E+10 | 7980.52 | 17-OCT-05:49 |
November | 0.793612E+11 | 75557.94 | 01-NOV-14:00 | 0.462756E+10 | 10031.11 | 24-NOV-07:10 |
December | 0.814193E+11 | 68464.33 | 22-DEC-14:00 | 0.532439E+10 | 16645.75 | 07-DEC-06:10 |
Annual Sum or Average | 0.112683E+13 | 0.578460E+11 | ||||
Minimum of Months | 0.733418E+11 | 62379.62 | 0.453651E+10 | 2608.17 | ||
Maximum of Months | 0.114468E+12 | 96034.19 | 0.586173E+10 | 39840.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.131413E+11 | 0.115358E+11 | 0.00 | 0.111834E+11 | 0.00 | 0.00 | 0.127313E+10 | 0.00 | 0.00 | 0.00 | 0.209192E+10 | 0.00 |
February | 0.393028E+11 | 0.112728E+11 | 0.105871E+11 | 0.00 | 0.102507E+11 | 0.00 | 0.00 | 34208280.52 | 0.00 | 0.00 | 0.00 | 0.189426E+10 | 0.00 |
March | 0.453764E+11 | 0.115902E+11 | 0.123431E+11 | 0.00 | 0.120430E+11 | 0.00 | 0.00 | 0.178262E+10 | 0.00 | 0.00 | 0.00 | 0.209890E+10 | 0.00 |
April | 0.425433E+11 | 0.103052E+11 | 0.114862E+11 | 0.00 | 0.129583E+11 | 0.00 | 0.00 | 0.119906E+11 | 0.00 | 0.00 | 0.00 | 0.194445E+10 | 0.00 |
May | 0.441635E+11 | 0.986495E+10 | 0.119357E+11 | 0.00 | 0.155259E+11 | 0.00 | 0.00 | 0.179607E+11 | 0.00 | 0.00 | 0.00 | 0.195125E+10 | 0.00 |
June | 0.437562E+11 | 0.921992E+10 | 0.118862E+11 | 0.00 | 0.183629E+11 | 0.00 | 0.00 | 0.283435E+11 | 0.00 | 0.00 | 0.00 | 0.185467E+10 | 0.00 |
July | 0.429506E+11 | 0.964994E+10 | 0.115358E+11 | 0.00 | 0.181201E+11 | 0.00 | 0.00 | 0.275828E+11 | 0.00 | 0.00 | 0.00 | 0.185654E+10 | 0.00 |
August | 0.453764E+11 | 0.102950E+11 | 0.123357E+11 | 0.00 | 0.180189E+11 | 0.00 | 0.00 | 0.265411E+11 | 0.00 | 0.00 | 0.00 | 0.190132E+10 | 0.00 |
September | 0.425433E+11 | 0.108120E+11 | 0.114788E+11 | 0.00 | 0.155523E+11 | 0.00 | 0.00 | 0.208851E+11 | 0.00 | 0.00 | 0.00 | 0.185630E+10 | 0.00 |
October | 0.429506E+11 | 0.121226E+11 | 0.115432E+11 | 0.00 | 0.125975E+11 | 0.00 | 0.00 | 0.878359E+10 | 0.00 | 0.00 | 0.00 | 0.195860E+10 | 0.00 |
November | 0.413304E+11 | 0.125270E+11 | 0.110862E+11 | 0.00 | 0.106980E+11 | 0.00 | 0.00 | 0.176961E+10 | 0.00 | 0.00 | 0.00 | 0.194998E+10 | 0.00 |
December | 0.429506E+11 | 0.133922E+11 | 0.115358E+11 | 0.00 | 0.111452E+11 | 0.00 | 0.00 | 0.326406E+09 | 0.00 | 0.00 | 0.00 | 0.206910E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134193E+12 | 0.139290E+12 | 0.00 | 0.166456E+12 | 0.00 | 0.00 | 0.147273E+12 | 0.00 | 0.00 | 0.00 | 0.234273E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.921992E+10 | 0.105871E+11 | 0.00 | 0.102507E+11 | 0.00 | 0.00 | 34208280.52 | 0.00 | 0.00 | 0.00 | 0.185467E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.133922E+11 | 0.123431E+11 | 0.00 | 0.183629E+11 | 0.00 | 0.00 | 0.283435E+11 | 0.00 | 0.00 | 0.00 | 0.209890E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.586173E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.457333E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.504729E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.454259E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.471312E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.453729E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468851E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.468826E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453651E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.470544E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.462756E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.532439E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.578460E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.453651E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.586173E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 11250.31 | 04-JAN-14:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 11250.31 | 02-FEB-15:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 11250.31 | 01-MAR-12:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 13555.61 | 13-APR-10:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 13555.61 | 01-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 13555.61 | 01-JUN-10:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 13555.61 | 01-JUL-08:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 13555.61 | 01-AUG-11:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 13555.61 | 01-SEP-15:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 13555.61 | 04-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 11250.31 | 01-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 11250.31 | 01-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 11250.31 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 13555.61 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10631.46 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 | 1789.08 | 21-JAN-12:09 | 0.00 |
February | 1103.18 | 18-FEB-14:39 | 0.00 | 0.00 | 0.00 | 1788.70 | 02-FEB-12:20 | 0.00 |
March | 13814.90 | 19-MAR-14:30 | 0.00 | 0.00 | 0.00 | 1779.16 | 01-MAR-12:39 | 0.00 |
April | 23214.23 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 1758.05 | 01-APR-11:09 | 0.00 |
May | 26345.68 | 18-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1733.32 | 01-MAY-11:20 | 0.00 |
June | 36462.33 | 30-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1710.24 | 01-JUN-11:39 | 0.00 |
July | 32571.96 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1695.92 | 01-JUL-11:00 | 0.00 |
August | 32730.00 | 25-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1701.25 | 31-AUG-11:30 | 0.00 |
September | 28862.42 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1719.78 | 30-SEP-11:09 | 0.00 |
October | 24128.58 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1744.95 | 31-OCT-11:09 | 0.00 |
November | 14295.68 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1768.11 | 30-NOV-12:09 | 0.00 |
December | 7204.85 | 22-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1784.22 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1103.18 | 0.00 | 0.00 | 0.00 | 1695.92 | 0.00 | ||
Maximum of Months | 36462.33 | 0.00 | 0.00 | 0.00 | 1789.08 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71929.79 | 31-JAN-15:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11250.31 | 0.00 | 0.00 | 10631.46 | 0.00 |
February | 62379.62 | 18-FEB-15:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11250.31 | 0.00 | 0.00 | 1084.91 | 0.00 |
March | 73739.46 | 18-MAR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11250.31 | 0.00 | 0.00 | 12458.12 | 0.00 |
April | 86012.42 | 14-APR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 22443.25 | 0.00 |
May | 88079.29 | 18-MAY-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 24533.49 | 0.00 |
June | 96034.19 | 28-JUN-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 33014.33 | 0.00 |
July | 92975.79 | 19-JUL-13:20 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 29474.18 | 0.00 |
August | 93710.53 | 25-AUG-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 30182.89 | 0.00 |
September | 90166.67 | 08-SEP-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 26633.73 | 0.00 |
October | 86634.08 | 02-OCT-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 23112.07 | 0.00 |
November | 75557.94 | 01-NOV-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11250.31 | 0.00 | 0.00 | 14295.68 | 0.00 |
December | 68464.33 | 22-DEC-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11250.31 | 0.00 | 0.00 | 7204.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 62379.62 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11250.31 | 0.00 | 0.00 | 1084.91 | 0.00 | |
Maximum of Months | 96034.19 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13555.61 | 0.00 | 0.00 | 33014.33 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 39840.47 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9104.35 | 13-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13488.56 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6304.69 | 29-APR-05:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 7813.63 | 03-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3907.16 | 13-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3937.86 | 01-JUL-05:49 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3524.61 | 24-AUG-05:49 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2608.17 | 30-SEP-05:49 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 7980.52 | 17-OCT-05:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 10031.11 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 16645.75 | 07-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 2608.17 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 39840.47 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.59 | 1.17 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
February | 0.33 | 20.48 | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 1.00 | 20.44 | 1.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.26 | 1.00 | 26.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.08 | 5.00 | 27.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.59 | 7.00 | 26.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.82 | 6.67 | 26.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.32 | 4.83 | 25.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.27 | 1.33 | 25.00 |
November | 0.33 | 20.49 | 0.33 | 20.49 | 0.33 | 21.83 | 0.33 | 22.49 |
December | 1.50 | 20.32 | 1.50 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 4.50 | 20.16 | 4.33 | 20.25 | 47.50 | 26.08 | 26.50 | 25.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 0.00 | 19.90 |
Maximum of Months | 1.50 | 20.49 | 1.50 | 20.49 | 14.33 | 28.08 | 7.00 | 27.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 14.82 | 0.17 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.67 | 0.00 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 27.83 | 0.00 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 27.96 | 0.33 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 27.87 | 0.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 27.79 | 0.50 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 27.69 | 0.00 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.64 | 0.00 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 14.82 | 0.17 | 14.83 | 287.50 | 27.67 | 1.17 | 27.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 14.82 | 0.17 | 14.83 | 70.00 | 27.96 | 0.50 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 254.83 | 23.19 | 27.33 | 22.99 | 27.33 | 22.83 |
February | 250.00 | 23.22 | 18.00 | 23.08 | 18.00 | 22.95 |
March | 245.00 | 23.25 | 36.00 | 23.16 | 17.33 | 23.04 |
April | 63.17 | 23.69 | 110.33 | 23.82 | 0.00 | 23.82 |
May | 20.17 | 23.25 | 149.00 | 23.82 | 0.00 | 23.82 |
June | 3.17 | 22.04 | 274.83 | 23.90 | 0.00 | 23.90 |
July | 7.67 | 23.90 | 291.17 | 23.92 | 7.17 | 23.92 |
August | 6.67 | 23.70 | 315.33 | 23.91 | 5.83 | 23.91 |
September | 6.67 | 23.72 | 294.50 | 23.90 | 5.83 | 23.90 |
October | 86.50 | 23.44 | 127.67 | 23.72 | 1.00 | 23.72 |
November | 172.33 | 23.36 | 68.33 | 23.37 | 29.00 | 23.29 |
December | 292.17 | 23.14 | 56.33 | 22.82 | 56.33 | 22.59 |
Annual Sum or Average | 1408.33 | 23.26 | 1768.83 | 23.51 | 167.83 | 23.42 |
Minimum of Months | 3.17 | 22.04 | 18.00 | 22.82 | 0.00 | 22.59 |
Maximum of Months | 292.17 | 23.90 | 315.33 | 23.92 | 56.33 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.50 | 21.88 | 218.33 | 24.16 | 43.83 | 23.62 |
February | 106.00 | 22.23 | 175.17 | 24.18 | 30.17 | 23.74 |
March | 96.17 | 22.20 | 241.83 | 24.79 | 31.67 | 24.40 |
April | 158.33 | 26.34 | 264.67 | 26.56 | 138.83 | 26.59 |
May | 194.67 | 26.69 | 299.00 | 26.67 | 193.67 | 26.68 |
June | 247.17 | 26.70 | 311.83 | 26.70 | 247.17 | 26.70 |
July | 275.50 | 26.70 | 300.00 | 26.69 | 275.50 | 26.69 |
August | 296.50 | 26.71 | 324.00 | 26.70 | 296.50 | 26.70 |
September | 261.33 | 26.71 | 300.00 | 26.69 | 261.33 | 26.70 |
October | 140.00 | 25.85 | 255.33 | 26.37 | 107.33 | 26.42 |
November | 97.17 | 23.71 | 222.00 | 25.38 | 48.50 | 25.21 |
December | 145.83 | 22.08 | 169.83 | 23.10 | 63.67 | 22.50 |
Annual Sum or Average | 2125.17 | 25.50 | 3082.00 | 25.94 | 1738.17 | 25.94 |
Minimum of Months | 96.17 | 21.88 | 169.83 | 23.10 | 30.17 | 22.50 |
Maximum of Months | 296.50 | 26.71 | 324.00 | 26.70 | 296.50 | 26.70 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.64 | 149.00 | 19.90 | 149.00 | 19.53 |
February | 276.00 | 20.36 | 146.17 | 19.90 | 146.17 | 19.68 |
March | 277.83 | 21.50 | 112.33 | 21.35 | 80.50 | 20.94 |
April | 225.17 | 29.29 | 265.17 | 29.22 | 206.83 | 29.40 |
May | 304.50 | 31.01 | 312.00 | 30.96 | 304.50 | 30.98 |
June | 312.00 | 33.91 | 312.00 | 33.91 | 312.00 | 33.91 |
July | 300.00 | 33.07 | 300.00 | 33.07 | 300.00 | 33.07 |
August | 324.00 | 32.91 | 324.00 | 32.91 | 324.00 | 32.91 |
September | 300.00 | 31.65 | 300.00 | 31.65 | 300.00 | 31.65 |
October | 199.17 | 28.95 | 238.67 | 28.98 | 167.33 | 29.31 |
November | 195.83 | 22.35 | 116.33 | 22.70 | 67.17 | 22.46 |
December | 300.00 | 19.66 | 232.50 | 19.33 | 232.50 | 19.21 |
Annual Sum or Average | 3314.50 | 27.31 | 2808.17 | 27.84 | 2590.00 | 28.08 |
Minimum of Months | 195.83 | 19.66 | 112.33 | 19.33 | 67.17 | 19.21 |
Maximum of Months | 324.00 | 33.91 | 324.00 | 33.91 | 324.00 | 33.91 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.205434E+10 | 0.560473E+09 | 135.67 | 0.205434E+10 | 165.69 | 0.00 | 0.42 | 31-JAN-16:30 | 0.00 | 01-JAN-00:05 | 9358.55 | 31-JAN-16:30 | 9358.55 | 31-JAN-16:30 | 0.07 | 09-JAN-09:15 | 2726.66 | 31-JAN-16:30 | 0.00 | 01-JAN-00:05 |
February | 0.124615E+09 | 34155286.11 | 33.17 | 0.120028E+09 | 4586117.09 | 0.00 | 0.17 | 18-FEB-14:40 | 0.00 | 01-FEB-00:10 | 4059.85 | 18-FEB-14:40 | 3807.14 | 18-FEB-15:00 | 415.52 | 18-FEB-14:00 | 1103.18 | 18-FEB-14:40 | 0.00 | 01-FEB-00:10 |
March | 0.210593E+10 | 0.581178E+09 | 129.53 | 0.209958E+10 | 6352288.25 | 0.00 | 0.43 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10017.72 | 18-MAR-16:00 | 10017.72 | 18-MAR-16:00 | 393.37 | 18-MAR-10:00 | 2889.98 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.813986E+10 | 0.236284E+10 | 249.34 | 0.813965E+10 | 204754.07 | 0.00 | 1.00 | 04-APR-05:03 | 0.00 | 01-APR-00:10 | 26647.20 | 25-APR-05:01 | 26647.20 | 25-APR-05:01 | 2047.54 | 17-APR-05:02 | 6309.52 | 25-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.111591E+11 | 0.334124E+10 | 302.19 | 0.111591E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 27192.30 | 29-MAY-19:13 | 27192.30 | 29-MAY-19:13 | 0.00 | 09-MAY-05:02 | 7210.67 | 29-MAY-19:13 | 0.00 | 01-MAY-00:10 |
June | 0.152701E+11 | 0.492147E+10 | 368.94 | 0.152490E+11 | 21065122.35 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 28366.93 | 30-JUN-05:01 | 28366.93 | 30-JUN-05:01 | 1654.82 | 17-JUN-16:55 | 8622.37 | 28-JUN-17:39 | 0.00 | 01-JUN-00:10 |
July | 0.156491E+11 | 0.477463E+10 | 351.93 | 0.143191E+11 | 0.132999E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 34684.69 | 14-JUL-05:01 | 28411.38 | 31-JUL-05:01 | 17795.78 | 14-JUL-05:06 | 8070.72 | 22-JUL-17:40 | 0.00 | 01-JUL-00:10 |
August | 0.161993E+11 | 0.492806E+10 | 354.26 | 0.147079E+11 | 0.149144E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 32814.84 | 01-AUG-05:01 | 29440.77 | 28-AUG-03:25 | 13842.60 | 04-AUG-05:45 | 8444.31 | 13-AUG-15:51 | 0.00 | 01-AUG-00:10 |
September | 0.135840E+11 | 0.399672E+10 | 305.18 | 0.122401E+11 | 0.134392E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 33152.28 | 02-SEP-05:01 | 28055.94 | 20-SEP-05:01 | 14914.78 | 05-SEP-06:00 | 7758.01 | 02-SEP-05:01 | 0.00 | 01-SEP-00:05 |
October | 0.685869E+10 | 0.196140E+10 | 218.84 | 0.658998E+10 | 0.268713E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:01 | 31614.26 | 03-OCT-05:01 | 27357.30 | 02-OCT-05:01 | 12306.51 | 03-OCT-05:08 | 7351.15 | 03-OCT-05:01 | 0.00 | 01-OCT-00:01 |
November | 0.230915E+10 | 0.629680E+09 | 125.58 | 0.225191E+10 | 57237399.50 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 27627.86 | 01-NOV-05:02 | 23444.29 | 01-NOV-05:02 | 6841.10 | 03-NOV-05:03 | 6546.58 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 |
December | 0.718122E+09 | 0.194844E+09 | 64.00 | 0.718122E+09 | 2.55 | 0.00 | 0.34 | 22-DEC-16:20 | 0.00 | 01-DEC-00:10 | 7907.86 | 22-DEC-16:30 | 7907.86 | 22-DEC-16:30 | 0.00 | 13-DEC-13:10 | 2125.50 | 22-DEC-16:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.941723E+11 | 0.282867E+11 | 2638.61 | 0.896488E+11 | 0.452352E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.124615E+09 | 34155286.11 | 33.17 | 0.120028E+09 | -0.0 | 0.00 | 0.17 | 0.00 | 4059.85 | 3807.14 | 0.00 | 1103.18 | 0.00 | |||||||
Maximum of Months | 0.161993E+11 | 0.492806E+10 | 368.94 | 0.152490E+11 | 0.149144E+10 | 0.00 | 1.00 | 0.00 | 34684.69 | 29440.77 | 17795.78 | 8622.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.233462E+10 | 0.712661E+09 | 98.17 | 0.233461E+10 | 2092.27 | 0.00 | 0.28 | 31-JAN-16:00 | 0.00 | 01-JAN-00:05 | 24819.40 | 31-JAN-16:00 | 24819.40 | 31-JAN-16:00 | 0.44 | 09-JAN-11:50 | 7999.12 | 31-JAN-16:00 | 0.00 | 01-JAN-00:05 |
February | 176161.67 | 52994.41 | 38.33 | 163773.45 | 12388.23 | 0.00 | 0.00 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 5.23 | 22-FEB-14:00 | 5.12 | 22-FEB-14:00 | 0.73 | 17-FEB-13:00 | 1.58 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.393227E+10 | 0.120144E+10 | 109.49 | 0.392840E+10 | 3868190.29 | 0.00 | 1.00 | 17-MAR-17:12 | 0.00 | 01-MAR-00:10 | 106863.74 | 17-MAR-17:12 | 106863.74 | 17-MAR-17:12 | 666.43 | 18-MAR-10:40 | 28369.22 | 18-MAR-17:11 | 0.00 | 01-MAR-00:10 |
April | 0.301378E+11 | 0.962775E+10 | 286.74 | 0.301378E+11 | 0.00 | 0.00 | 1.00 | 02-APR-10:45 | 0.00 | 01-APR-00:10 | 107032.23 | 15-APR-20:01 | 107032.23 | 15-APR-20:01 | 0.00 | 08-APR-17:43 | 31608.39 | 14-APR-17:04 | 0.00 | 01-APR-00:10 |
May | 0.441967E+11 | 0.146194E+11 | 376.96 | 0.441967E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-19:05 | 0.00 | 01-MAY-00:10 | 107955.09 | 10-MAY-23:45 | 107955.09 | 10-MAY-23:45 | 0.00 | 23-MAY-18:23 | 32353.66 | 15-MAY-17:04 | 0.00 | 01-MAY-00:10 |
June | 0.665260E+11 | 0.234221E+11 | 481.86 | 0.664548E+11 | 71206549.65 | 0.00 | 1.00 | 01-JUN-00:25 | 0.00 | 01-JUN-00:10 | 109443.14 | 18-JUN-05:31 | 109443.14 | 18-JUN-05:31 | 8603.64 | 17-JUN-17:04 | 35653.43 | 28-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.689296E+11 | 0.228082E+11 | 489.62 | 0.635533E+11 | 0.537631E+10 | 0.00 | 1.00 | 01-JUL-00:23 | 0.00 | 01-JUL-00:13 | 135733.42 | 14-JUL-01:05 | 109320.77 | 31-JUL-03:15 | 73378.50 | 14-JUL-01:05 | 34922.66 | 20-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.653417E+11 | 0.216130E+11 | 465.46 | 0.600911E+11 | 0.525056E+10 | 0.00 | 1.00 | 01-AUG-02:25 | 0.00 | 01-AUG-00:13 | 131143.81 | 09-AUG-19:51 | 109652.62 | 31-AUG-01:05 | 57868.23 | 28-AUG-17:23 | 34826.97 | 27-AUG-15:52 | 0.00 | 01-AUG-00:10 |
September | 0.527926E+11 | 0.168884E+11 | 390.31 | 0.481012E+11 | 0.469146E+10 | 0.00 | 1.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:10 | 133397.12 | 04-SEP-07:45 | 109499.25 | 17-SEP-05:05 | 69235.04 | 04-SEP-07:45 | 33684.28 | 07-SEP-17:04 | 0.00 | 01-SEP-00:05 |
October | 0.215649E+11 | 0.682219E+10 | 215.59 | 0.207323E+11 | 0.832589E+09 | 0.00 | 1.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:02 | 126356.66 | 03-OCT-02:07 | 109367.56 | 04-OCT-21:05 | 48224.43 | 03-OCT-02:07 | 32161.88 | 02-OCT-22:45 | 0.00 | 01-OCT-00:01 |
November | 0.376144E+10 | 0.113993E+10 | 90.98 | 0.370806E+10 | 53380238.62 | 0.00 | 1.00 | 01-NOV-17:11 | 0.00 | 01-NOV-00:10 | 107870.88 | 01-NOV-17:11 | 107870.88 | 01-NOV-17:11 | 2616.59 | 01-NOV-10:40 | 28392.78 | 01-NOV-17:11 | 0.00 | 01-NOV-00:10 |
December | 0.435102E+09 | 0.131562E+09 | 44.83 | 0.435100E+09 | 1163.90 | 0.00 | 0.19 | 22-DEC-15:00 | 0.00 | 01-DEC-00:10 | 16831.37 | 22-DEC-15:00 | 16831.37 | 22-DEC-15:00 | 0.28 | 13-DEC-12:30 | 5150.38 | 22-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.359953E+12 | 0.118987E+12 | 3088.34 | 0.343674E+12 | 0.162794E+11 | 0.00 | ||||||||||||||
Minimum of Months | 176161.67 | 52994.41 | 38.33 | 163773.45 | -0.0 | 0.00 | 0.00 | 0.00 | 5.23 | 5.12 | 0.00 | 1.58 | 0.00 | |||||||
Maximum of Months | 0.689296E+11 | 0.234221E+11 | 489.62 | 0.664548E+11 | 0.537631E+10 | 0.00 | 1.00 | 0.00 | 135733.42 | 109652.62 | 73378.50 | 35653.43 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 42.23 | 25.45 | 130.26 | 131.33 | 0.00 | 0.00 | 0.00 |
February | 54.34 | 26.23 | 28.11 | 79.78 | 130.53 | 0.00 | 0.00 | 0.00 |
March | 72.21 | 34.46 | 37.75 | 125.19 | 116.07 | 0.00 | 0.00 | 0.00 |
April | 110.00 | 62.46 | 47.55 | 247.91 | 79.77 | 0.00 | 0.00 | 0.00 |
May | 110.64 | 61.74 | 48.89 | 267.64 | 61.75 | 0.00 | 0.00 | 0.00 |
June | 117.51 | 68.96 | 48.55 | 327.90 | 31.43 | 0.00 | 0.00 | 0.00 |
July | 85.68 | 39.91 | 45.77 | 243.00 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 81.78 | 40.97 | 40.81 | 233.03 | 33.19 | 0.00 | 0.00 | 0.00 |
September | 71.31 | 29.92 | 41.39 | 190.71 | 43.36 | 0.00 | 0.00 | 0.00 |
October | 72.86 | 41.58 | 31.28 | 153.79 | 101.95 | 0.00 | 0.00 | 0.00 |
November | 66.98 | 40.33 | 26.65 | 120.75 | 133.96 | 0.00 | 0.00 | 0.00 |
December | 54.46 | 31.12 | 23.34 | 90.38 | 162.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.55 | 43.39 | 37.16 | 184.64 | 87.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.34 | 26.23 | 23.34 | 79.78 | 26.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.51 | 68.96 | 48.89 | 327.90 | 162.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 42.23 | 25.45 | 130.26 | 131.33 | 0.00 | 0.00 | 0.00 |
February | 54.34 | 26.23 | 28.11 | 79.78 | 130.53 | 0.00 | 0.00 | 0.00 |
March | 72.21 | 34.46 | 37.75 | 125.19 | 116.07 | 0.00 | 0.00 | 0.00 |
April | 110.00 | 62.46 | 47.55 | 247.91 | 79.77 | 0.00 | 0.00 | 0.00 |
May | 110.64 | 61.74 | 48.89 | 267.64 | 61.75 | 0.00 | 0.00 | 0.00 |
June | 117.51 | 68.96 | 48.55 | 327.90 | 31.43 | 0.00 | 0.00 | 0.00 |
July | 85.68 | 39.91 | 45.77 | 243.00 | 26.95 | 0.00 | 0.00 | 0.00 |
August | 81.78 | 40.97 | 40.81 | 233.03 | 33.19 | 0.00 | 0.00 | 0.00 |
September | 71.31 | 29.92 | 41.39 | 190.71 | 43.36 | 0.00 | 0.00 | 0.00 |
October | 72.86 | 41.58 | 31.28 | 153.79 | 101.95 | 0.00 | 0.00 | 0.00 |
November | 66.98 | 40.33 | 26.65 | 120.75 | 133.96 | 0.00 | 0.00 | 0.00 |
December | 54.46 | 31.12 | 23.34 | 90.38 | 162.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.55 | 43.39 | 37.16 | 184.64 | 87.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.34 | 26.23 | 23.34 | 79.78 | 26.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.51 | 68.96 | 48.89 | 327.90 | 162.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.60 | 0.00 | 11.60 | 9.66 | 78.02 | 0.00 | 0.00 | 0.00 |
February | 13.22 | 0.00 | 13.22 | 5.77 | 79.11 | 0.00 | 0.00 | 0.00 |
March | 17.57 | 0.00 | 17.57 | 18.51 | 70.42 | 0.00 | 0.00 | 0.00 |
April | 21.58 | 0.39 | 21.19 | 42.76 | 45.69 | 0.00 | 0.00 | 0.00 |
May | 25.79 | 2.69 | 23.10 | 61.02 | 32.77 | 0.00 | 0.00 | 0.00 |
June | 29.90 | 6.09 | 23.81 | 99.56 | 16.67 | 0.00 | 0.00 | 0.00 |
July | 25.24 | 3.00 | 22.24 | 82.55 | 14.78 | 0.00 | 0.00 | 0.00 |
August | 20.26 | 0.70 | 19.57 | 68.51 | 18.66 | 0.00 | 0.00 | 0.00 |
September | 18.92 | 0.02 | 18.91 | 55.54 | 25.08 | 0.00 | 0.00 | 0.00 |
October | 14.63 | 0.00 | 14.63 | 23.73 | 60.69 | 0.00 | 0.00 | 0.00 |
November | 12.19 | 0.00 | 12.19 | 8.49 | 80.36 | 0.00 | 0.00 | 0.00 |
December | 10.84 | 0.00 | 10.84 | 4.91 | 97.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.50 | 1.08 | 17.42 | 40.24 | 51.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.84 | 0.00 | 10.84 | 4.91 | 14.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.90 | 6.09 | 23.81 | 99.56 | 97.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.60 | 0.00 | 11.60 | 9.66 | 78.02 | 0.00 | 0.00 | 0.00 |
February | 13.22 | 0.00 | 13.22 | 5.77 | 79.11 | 0.00 | 0.00 | 0.00 |
March | 17.57 | 0.00 | 17.57 | 18.51 | 70.42 | 0.00 | 0.00 | 0.00 |
April | 21.58 | 0.39 | 21.19 | 42.76 | 45.69 | 0.00 | 0.00 | 0.00 |
May | 25.79 | 2.69 | 23.10 | 61.02 | 32.77 | 0.00 | 0.00 | 0.00 |
June | 29.90 | 6.09 | 23.81 | 99.56 | 16.67 | 0.00 | 0.00 | 0.00 |
July | 25.24 | 3.00 | 22.24 | 82.55 | 14.78 | 0.00 | 0.00 | 0.00 |
August | 20.26 | 0.70 | 19.56 | 68.51 | 18.66 | 0.00 | 0.00 | 0.00 |
September | 18.92 | 0.02 | 18.91 | 55.54 | 25.08 | 0.00 | 0.00 | 0.00 |
October | 14.63 | 0.00 | 14.63 | 23.73 | 60.69 | 0.00 | 0.00 | 0.00 |
November | 12.19 | 0.00 | 12.19 | 8.49 | 80.36 | 0.00 | 0.00 | 0.00 |
December | 10.84 | 0.00 | 10.84 | 4.91 | 97.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.50 | 1.08 | 17.42 | 40.24 | 51.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.84 | 0.00 | 10.84 | 4.91 | 14.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.90 | 6.09 | 23.81 | 99.56 | 97.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.99 | 34.75 | 10.24 | 76.76 | 51.68 | 6.50 | 0.00 | 0.00 |
February | 43.76 | 28.13 | 15.63 | 68.42 | 44.33 | 5.17 | 0.00 | 0.00 |
March | 61.86 | 39.57 | 22.30 | 102.35 | 46.22 | 0.00 | 0.00 | 0.00 |
April | 95.61 | 73.83 | 21.78 | 164.60 | 48.65 | 0.00 | 0.00 | 0.00 |
May | 105.19 | 82.58 | 22.61 | 180.28 | 48.16 | 0.00 | 0.00 | 0.00 |
June | 110.74 | 90.52 | 20.23 | 197.81 | 36.90 | 0.00 | 0.00 | 0.00 |
July | 89.75 | 64.97 | 24.78 | 160.23 | 28.98 | 0.00 | 0.00 | 0.00 |
August | 82.75 | 61.16 | 21.59 | 148.95 | 34.70 | 0.17 | 0.00 | 0.00 |
September | 66.57 | 41.76 | 24.81 | 117.35 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 59.31 | 44.58 | 14.73 | 96.15 | 57.34 | 0.00 | 0.00 | 0.00 |
November | 44.09 | 31.92 | 12.17 | 69.55 | 55.22 | 12.00 | 0.00 | 0.00 |
December | 38.93 | 28.49 | 10.44 | 61.78 | 60.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70.42 | 51.96 | 18.45 | 120.59 | 45.72 | 23.83 | 0.00 | 0.00 |
Minimum of Months | 38.93 | 28.13 | 10.24 | 61.78 | 28.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.74 | 90.52 | 24.81 | 197.81 | 60.64 | 12.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181288E+09 | 0.113118E+09 | 68170376.46 | 0.348888E+09 | 0.351743E+09 |
February | 0.131450E+09 | 63444780.91 | 68004929.09 | 0.193003E+09 | 0.315766E+09 |
March | 0.193410E+09 | 92305875.75 | 0.101104E+09 | 0.335299E+09 | 0.310876E+09 |
April | 0.285130E+09 | 0.161887E+09 | 0.123244E+09 | 0.642572E+09 | 0.206771E+09 |
May | 0.296334E+09 | 0.165376E+09 | 0.130958E+09 | 0.716860E+09 | 0.165399E+09 |
June | 0.304582E+09 | 0.178747E+09 | 0.125836E+09 | 0.849913E+09 | 81457992.87 |
July | 0.229489E+09 | 0.106899E+09 | 0.122591E+09 | 0.650847E+09 | 72194136.97 |
August | 0.219032E+09 | 0.109722E+09 | 0.109309E+09 | 0.624145E+09 | 88883020.00 |
September | 0.184837E+09 | 77559438.27 | 0.107277E+09 | 0.494327E+09 | 0.112397E+09 |
October | 0.195142E+09 | 0.111366E+09 | 83775617.40 | 0.411902E+09 | 0.273070E+09 |
November | 0.173620E+09 | 0.104548E+09 | 69072347.18 | 0.312975E+09 | 0.347231E+09 |
December | 0.145862E+09 | 83341599.49 | 62520315.44 | 0.242082E+09 | 0.434519E+09 |
Annual Sum or Average | 0.254018E+10 | 0.136831E+10 | 0.117186E+10 | 0.582281E+10 | 0.276031E+10 |
Minimum of Months | 0.131450E+09 | 63444780.91 | 62520315.44 | 0.193003E+09 | 72194136.97 |
Maximum of Months | 0.304582E+09 | 0.178747E+09 | 0.130958E+09 | 0.849913E+09 | 0.434519E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181288E+09 | 0.113118E+09 | 68170376.46 | 0.348888E+09 | 0.351743E+09 |
February | 0.131450E+09 | 63444780.91 | 68004929.09 | 0.193003E+09 | 0.315766E+09 |
March | 0.193410E+09 | 92305875.75 | 0.101104E+09 | 0.335299E+09 | 0.310876E+09 |
April | 0.285130E+09 | 0.161887E+09 | 0.123244E+09 | 0.642572E+09 | 0.206771E+09 |
May | 0.296334E+09 | 0.165376E+09 | 0.130958E+09 | 0.716860E+09 | 0.165399E+09 |
June | 0.304582E+09 | 0.178747E+09 | 0.125836E+09 | 0.849913E+09 | 81457992.87 |
July | 0.229489E+09 | 0.106899E+09 | 0.122591E+09 | 0.650847E+09 | 72194136.97 |
August | 0.219032E+09 | 0.109722E+09 | 0.109309E+09 | 0.624145E+09 | 88883020.00 |
September | 0.184837E+09 | 77559438.27 | 0.107277E+09 | 0.494327E+09 | 0.112397E+09 |
October | 0.195142E+09 | 0.111366E+09 | 83775617.40 | 0.411902E+09 | 0.273070E+09 |
November | 0.173620E+09 | 0.104548E+09 | 69072347.18 | 0.312975E+09 | 0.347231E+09 |
December | 0.145862E+09 | 83341599.49 | 62520315.44 | 0.242082E+09 | 0.434519E+09 |
Annual Sum or Average | 0.254018E+10 | 0.136831E+10 | 0.117186E+10 | 0.582281E+10 | 0.276031E+10 |
Minimum of Months | 0.131450E+09 | 63444780.91 | 62520315.44 | 0.193003E+09 | 72194136.97 |
Maximum of Months | 0.304582E+09 | 0.178747E+09 | 0.130958E+09 | 0.849913E+09 | 0.434519E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31069929.10 | 0.00 | 31069929.10 | 25866465.26 | 0.208966E+09 |
February | 31977233.33 | 0.00 | 31977233.33 | 13956732.93 | 0.191377E+09 |
March | 47067343.67 | 8893.91 | 47058449.76 | 49570561.61 | 0.188624E+09 |
April | 55936042.68 | 1015900.50 | 54920142.18 | 0.110829E+09 | 0.118429E+09 |
May | 69067257.25 | 7202951.39 | 61864305.86 | 0.163429E+09 | 87780513.41 |
June | 77509988.04 | 15784066.75 | 61725921.29 | 0.258052E+09 | 43214574.61 |
July | 67603695.08 | 8027795.28 | 59575899.80 | 0.221109E+09 | 39593535.39 |
August | 54277189.57 | 1873753.87 | 52403435.70 | 0.183496E+09 | 49991914.66 |
September | 49053075.55 | 45373.51 | 49007702.04 | 0.143971E+09 | 65001593.49 |
October | 39183319.34 | 0.00 | 39183319.34 | 63548354.96 | 0.162560E+09 |
November | 31593765.24 | 0.00 | 31593765.24 | 21995798.54 | 0.208302E+09 |
December | 29022163.57 | 0.00 | 29022163.57 | 13151898.47 | 0.261640E+09 |
Annual Sum or Average | 0.583361E+09 | 33958735.22 | 0.549402E+09 | 0.126898E+10 | 0.162548E+10 |
Minimum of Months | 29022163.57 | 0.00 | 29022163.57 | 13151898.47 | 39593535.39 |
Maximum of Months | 77509988.04 | 15784066.75 | 61864305.86 | 0.258052E+09 | 0.261640E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31069169.72 | 0.00 | 31069169.72 | 25866010.81 | 0.208964E+09 |
February | 31976337.70 | 0.00 | 31976337.70 | 13955879.47 | 0.191377E+09 |
March | 47066024.86 | 8893.50 | 47057131.37 | 49568897.01 | 0.188623E+09 |
April | 55934735.75 | 1015852.89 | 54918882.86 | 0.110828E+09 | 0.118428E+09 |
May | 69065487.18 | 7202613.78 | 61862873.40 | 0.163427E+09 | 87778801.18 |
June | 77507850.35 | 15783326.93 | 61724523.42 | 0.258049E+09 | 43213311.97 |
July | 67601785.51 | 8027419.01 | 59574366.50 | 0.221106E+09 | 39592665.75 |
August | 54275807.02 | 1873666.04 | 52402140.97 | 0.183494E+09 | 49990724.29 |
September | 49051698.69 | 45371.38 | 49006327.31 | 0.143969E+09 | 65000430.33 |
October | 39182357.41 | 0.00 | 39182357.41 | 63547549.82 | 0.162558E+09 |
November | 31592945.98 | 0.00 | 31592945.98 | 21995189.87 | 0.208301E+09 |
December | 29021414.92 | 0.00 | 29021414.92 | 13151501.66 | 0.261638E+09 |
Annual Sum or Average | 0.583346E+09 | 33957143.53 | 0.549388E+09 | 0.126896E+10 | 0.162546E+10 |
Minimum of Months | 29021414.92 | 0.00 | 29021414.92 | 13151501.66 | 39592665.75 |
Maximum of Months | 77507850.35 | 15783326.93 | 61862873.40 | 0.258049E+09 | 0.261638E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120503E+09 | 93070402.79 | 27432671.35 | 0.205603E+09 | 0.138422E+09 |
February | 0.105861E+09 | 68040446.25 | 37820444.82 | 0.165514E+09 | 0.107234E+09 |
March | 0.165699E+09 | 0.105979E+09 | 59720193.65 | 0.274131E+09 | 0.123807E+09 |
April | 0.247817E+09 | 0.191368E+09 | 56448929.09 | 0.426642E+09 | 0.126113E+09 |
May | 0.281741E+09 | 0.221183E+09 | 60557656.87 | 0.482852E+09 | 0.128987E+09 |
June | 0.287047E+09 | 0.234616E+09 | 52430929.83 | 0.512711E+09 | 95647881.71 |
July | 0.240384E+09 | 0.174005E+09 | 66379635.37 | 0.429171E+09 | 77622995.33 |
August | 0.221632E+09 | 0.163818E+09 | 57813779.68 | 0.398957E+09 | 92949517.07 |
September | 0.172547E+09 | 0.108246E+09 | 64300810.03 | 0.304163E+09 | 92055418.99 |
October | 0.158855E+09 | 0.119404E+09 | 39450645.40 | 0.257531E+09 | 0.153590E+09 |
November | 0.114276E+09 | 82734680.43 | 31541015.51 | 0.180276E+09 | 0.143124E+09 |
December | 0.104267E+09 | 76298919.46 | 27967974.08 | 0.165474E+09 | 0.162419E+09 |
Annual Sum or Average | 0.222063E+10 | 0.163876E+10 | 0.581865E+09 | 0.380303E+10 | 0.144197E+10 |
Minimum of Months | 0.104267E+09 | 68040446.25 | 27432671.35 | 0.165474E+09 | 77622995.33 |
Maximum of Months | 0.287047E+09 | 0.234616E+09 | 66379635.37 | 0.512711E+09 | 0.162419E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.70 | 415.56 | 158.57 | 84.47 | 74.10 | 0.00 | 0.00 |
February | 165.93 | 414.10 | 135.11 | 52.45 | 82.66 | 0.00 | 0.00 |
March | 282.11 | 367.71 | 179.57 | 68.93 | 110.63 | 0.00 | 0.00 |
April | 580.75 | 250.35 | 263.17 | 125.70 | 137.47 | 0.00 | 0.00 |
May | 654.26 | 185.99 | 272.85 | 128.87 | 143.98 | 0.00 | 0.00 |
June | 851.42 | 92.71 | 294.82 | 150.10 | 144.72 | 0.00 | 0.00 |
July | 649.21 | 81.58 | 221.84 | 85.82 | 136.03 | 0.00 | 0.00 |
August | 602.23 | 102.85 | 204.08 | 83.33 | 120.75 | 0.00 | 0.00 |
September | 492.46 | 136.83 | 180.47 | 59.88 | 120.59 | 0.00 | 0.00 |
October | 352.35 | 322.61 | 174.97 | 83.16 | 91.81 | 0.00 | 0.00 |
November | 253.40 | 423.59 | 158.34 | 80.67 | 77.67 | 0.00 | 0.00 |
December | 184.62 | 513.87 | 130.59 | 62.23 | 68.36 | 0.00 | 0.00 |
Annual Sum or Average | 446.67 | 275.05 | 198.09 | 88.93 | 109.16 | 0.00 | 0.00 |
Minimum of Months | 165.93 | 81.58 | 130.59 | 52.45 | 68.36 | 0.00 | 0.00 |
Maximum of Months | 851.42 | 513.87 | 294.82 | 150.10 | 144.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2466.04 | 1845.05 | 449.91 | 347.49 | 102.42 | 0.00 | 0.00 |
February | 2203.85 | 1566.79 | 437.59 | 281.25 | 156.33 | 0.00 | 0.00 |
March | 3327.98 | 1561.24 | 618.65 | 395.68 | 222.97 | 0.00 | 0.00 |
April | 6861.65 | 1962.18 | 956.08 | 738.30 | 217.78 | 0.00 | 0.00 |
May | 7958.04 | 2456.54 | 1051.90 | 825.80 | 226.10 | 0.00 | 0.00 |
June | 8524.18 | 2911.75 | 1107.43 | 905.15 | 202.28 | 0.00 | 0.00 |
July | 7668.56 | 2299.68 | 897.49 | 649.66 | 247.83 | 0.00 | 0.00 |
August | 6797.05 | 2607.33 | 827.48 | 611.63 | 215.85 | 0.00 | 0.00 |
September | 5073.31 | 2326.95 | 665.69 | 417.62 | 248.07 | 0.00 | 0.00 |
October | 3728.91 | 2332.49 | 593.09 | 445.80 | 147.29 | 0.00 | 0.00 |
November | 2243.14 | 1862.14 | 440.88 | 319.19 | 121.69 | 0.00 | 0.00 |
December | 2005.16 | 2181.18 | 389.29 | 284.87 | 104.42 | 0.00 | 0.00 |
Annual Sum or Average | 4918.58 | 2163.15 | 704.16 | 519.65 | 184.51 | 0.00 | 0.00 |
Minimum of Months | 2005.16 | 1561.24 | 389.29 | 281.25 | 102.42 | 0.00 | 0.00 |
Maximum of Months | 8524.18 | 2911.75 | 1107.43 | 905.15 | 248.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.741115E+09 | 0.111302E+10 | 0.424716E+09 | 0.226236E+09 | 0.198480E+09 | 0.00 | 0.00 |
February | 0.401425E+09 | 0.100179E+10 | 0.326853E+09 | 0.126890E+09 | 0.199963E+09 | 0.00 | 0.00 |
March | 0.755610E+09 | 0.984871E+09 | 0.480954E+09 | 0.184630E+09 | 0.296324E+09 | 0.00 | 0.00 |
April | 0.150531E+10 | 0.648908E+09 | 0.682132E+09 | 0.325805E+09 | 0.356327E+09 | 0.00 | 0.00 |
May | 0.175238E+10 | 0.498156E+09 | 0.730801E+09 | 0.345158E+09 | 0.385643E+09 | 0.00 | 0.00 |
June | 0.220689E+10 | 0.240306E+09 | 0.764183E+09 | 0.389061E+09 | 0.375122E+09 | 0.00 | 0.00 |
July | 0.173884E+10 | 0.218508E+09 | 0.594184E+09 | 0.229853E+09 | 0.364331E+09 | 0.00 | 0.00 |
August | 0.161301E+10 | 0.275477E+09 | 0.546616E+09 | 0.223192E+09 | 0.323424E+09 | 0.00 | 0.00 |
September | 0.127645E+10 | 0.354655E+09 | 0.467779E+09 | 0.155210E+09 | 0.312569E+09 | 0.00 | 0.00 |
October | 0.943728E+09 | 0.864087E+09 | 0.468649E+09 | 0.222732E+09 | 0.245917E+09 | 0.00 | 0.00 |
November | 0.656817E+09 | 0.109794E+10 | 0.410427E+09 | 0.209095E+09 | 0.201331E+09 | 0.00 | 0.00 |
December | 0.494496E+09 | 0.137634E+10 | 0.349767E+09 | 0.166683E+09 | 0.183084E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140861E+11 | 0.867407E+10 | 0.624706E+10 | 0.280454E+10 | 0.344252E+10 | 0.00 | 0.00 |
Minimum of Months | 0.401425E+09 | 0.218508E+09 | 0.326853E+09 | 0.126890E+09 | 0.183084E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220689E+10 | 0.137634E+10 | 0.764183E+09 | 0.389061E+09 | 0.385643E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.660504E+10 | 0.494178E+10 | 0.120503E+10 | 0.930704E+09 | 0.274327E+09 | 0.00 | 0.00 |
February | 0.533155E+10 | 0.379037E+10 | 0.105861E+10 | 0.680404E+09 | 0.378204E+09 | 0.00 | 0.00 |
March | 0.891365E+10 | 0.418161E+10 | 0.165699E+10 | 0.105979E+10 | 0.597202E+09 | 0.00 | 0.00 |
April | 0.177854E+11 | 0.508596E+10 | 0.247817E+10 | 0.191368E+10 | 0.564489E+09 | 0.00 | 0.00 |
May | 0.213148E+11 | 0.657961E+10 | 0.281741E+10 | 0.221183E+10 | 0.605577E+09 | 0.00 | 0.00 |
June | 0.220947E+11 | 0.754726E+10 | 0.287047E+10 | 0.234616E+10 | 0.524309E+09 | 0.00 | 0.00 |
July | 0.205395E+11 | 0.615946E+10 | 0.240384E+10 | 0.174005E+10 | 0.663796E+09 | 0.00 | 0.00 |
August | 0.182052E+11 | 0.698347E+10 | 0.221632E+10 | 0.163818E+10 | 0.578138E+09 | 0.00 | 0.00 |
September | 0.131500E+11 | 0.603145E+10 | 0.172547E+10 | 0.108246E+10 | 0.643008E+09 | 0.00 | 0.00 |
October | 0.998751E+10 | 0.624733E+10 | 0.158855E+10 | 0.119404E+10 | 0.394506E+09 | 0.00 | 0.00 |
November | 0.581423E+10 | 0.482668E+10 | 0.114276E+10 | 0.827347E+09 | 0.315410E+09 | 0.00 | 0.00 |
December | 0.537061E+10 | 0.584208E+10 | 0.104267E+10 | 0.762989E+09 | 0.279680E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155112E+12 | 0.682171E+11 | 0.222063E+11 | 0.163876E+11 | 0.581865E+10 | 0.00 | 0.00 |
Minimum of Months | 0.533155E+10 | 0.379037E+10 | 0.104267E+10 | 0.680404E+09 | 0.274327E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220947E+11 | 0.754726E+10 | 0.287047E+10 | 0.234616E+10 | 0.663796E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.798354E+09 | -720553791.6 | 0.00 | 0.00 | 744.00 | 0.00 | -77800050.2 | 58.99 | 0.00 | 0.00 |
February | 0.726034E+09 | -655400687.9 | 0.00 | 0.00 | 672.00 | 0.00 | -70632874.0 | 58.99 | 0.00 | 0.00 |
March | 0.805086E+09 | -728584250.0 | 0.00 | 0.00 | 744.00 | 0.00 | -76501536.9 | 58.99 | 0.00 | 0.00 |
April | 0.692055E+09 | -623094873.7 | 0.00 | 0.00 | 720.00 | 0.00 | -68960126.6 | 58.99 | 0.00 | 0.00 |
May | 0.657889E+09 | -587765956.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70123271.0 | 58.99 | 0.00 | 0.00 |
June | 0.602282E+09 | -535588399.8 | 0.00 | 0.00 | 720.00 | 0.00 | -66693205.4 | 58.99 | 0.00 | 0.00 |
July | 0.562655E+09 | -494118578.6 | 0.00 | 0.00 | 744.00 | 0.00 | -68536374.7 | 58.99 | 0.00 | 0.00 |
August | 0.607813E+09 | -538559901.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69253226.6 | 58.99 | 0.00 | 0.00 |
September | 0.604168E+09 | -537057341.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67110261.7 | 58.99 | 0.00 | 0.00 |
October | 0.664721E+09 | -592650291.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72070465.3 | 58.99 | 0.00 | 0.00 |
November | 0.697922E+09 | -624742730.0 | 0.00 | 0.00 | 720.00 | 0.00 | -73178957.8 | 58.99 | 0.00 | 0.00 |
December | 0.775637E+09 | -697060474.4 | 0.00 | 0.00 | 744.00 | 0.00 | -78576108.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.819461E+10 | -0.733518E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -859436458.7 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.562655E+09 | -728584250.0 | 0.00 | 0.00 | 672.00 | 0.00 | -78576108.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.805086E+09 | -494118578.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66693205.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278561E+09 | 35300.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225165E+09 | 35300.89 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239282E+09 | 35300.89 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4350399.43 | 6081.08 | 29-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17380818.06 | 8212.87 | 03-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 844872.04 | 2816.24 | 13-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 857136.28 | 2857.12 | 01-JUL-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 692592.83 | 2308.64 | 24-AUG-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 332121.29 | 1107.07 | 30-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12067144.20 | 8452.46 | 17-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 60352251.96 | 25519.80 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429561E+09 | 35300.89 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 332121.29 | 1107.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.429561E+09 | 35300.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.501900E+09 | 64610.85 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.501900E+09 | 64610.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.205434E+10 | 0.205434E+10 | 9358.55 | 31-JAN-16:30 | 9358.55 | 0.00 |
February | 0.00 | 0.00 | 0.124615E+09 | 0.120028E+09 | 4059.85 | 18-FEB-14:40 | 3770.63 | 0.00 |
March | 0.00 | 0.00 | 0.210593E+10 | 0.209958E+10 | 10017.72 | 18-MAR-16:00 | 10017.72 | 0.00 |
April | 0.00 | 0.00 | 0.813986E+10 | 0.813965E+10 | 26647.20 | 25-APR-05:01 | 26647.20 | 0.00 |
May | 0.00 | 0.00 | 0.111591E+11 | 0.111591E+11 | 27192.30 | 29-MAY-19:13 | 27192.30 | 0.00 |
June | 0.00 | 0.00 | 0.152701E+11 | 0.152490E+11 | 28366.93 | 30-JUN-05:01 | 28366.93 | 0.00 |
July | 0.00 | 0.00 | 0.156491E+11 | 0.143191E+11 | 34684.69 | 14-JUL-05:01 | 17331.27 | 0.00 |
August | 0.00 | 0.00 | 0.161993E+11 | 0.147079E+11 | 32814.84 | 01-AUG-05:01 | 20647.97 | 0.00 |
September | 0.00 | 0.00 | 0.135840E+11 | 0.122401E+11 | 33152.28 | 02-SEP-05:01 | 20878.72 | 0.00 |
October | 0.00 | 0.00 | 0.685869E+10 | 0.658998E+10 | 31614.26 | 03-OCT-05:01 | 20042.45 | 0.00 |
November | 0.00 | 0.00 | 0.230915E+10 | 0.225191E+10 | 27627.86 | 01-NOV-05:02 | 23444.29 | 0.00 |
December | 0.00 | 0.00 | 0.718122E+09 | 0.718122E+09 | 7907.86 | 22-DEC-16:30 | 7907.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.941723E+11 | 0.896488E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.124615E+09 | 0.120028E+09 | 4059.85 | 3770.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161993E+11 | 0.152490E+11 | 34684.69 | 28366.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.233462E+10 | 0.233461E+10 | 24819.40 | 31-JAN-16:00 | 24819.40 | 0.00 |
February | 0.00 | 0.00 | 176161.67 | 163773.45 | 5.23 | 22-FEB-14:00 | 5.12 | 0.00 |
March | 0.00 | 0.00 | 0.393227E+10 | 0.392840E+10 | 106863.74 | 17-MAR-17:12 | 106863.74 | 0.00 |
April | 0.00 | 0.00 | 0.301378E+11 | 0.301378E+11 | 107032.23 | 15-APR-20:01 | 107032.23 | 0.00 |
May | 0.00 | 0.00 | 0.441967E+11 | 0.441967E+11 | 107955.09 | 10-MAY-23:45 | 107955.09 | 0.00 |
June | 0.00 | 0.00 | 0.665260E+11 | 0.664548E+11 | 109443.14 | 18-JUN-05:31 | 109443.14 | 0.00 |
July | 0.00 | 0.00 | 0.689296E+11 | 0.635533E+11 | 135733.42 | 14-JUL-01:05 | 62354.92 | 0.00 |
August | 0.00 | 0.00 | 0.653417E+11 | 0.600911E+11 | 131143.81 | 09-AUG-19:51 | 76159.87 | 0.00 |
September | 0.00 | 0.00 | 0.527926E+11 | 0.481012E+11 | 133397.12 | 04-SEP-07:45 | 64162.07 | 0.00 |
October | 0.00 | 0.00 | 0.215649E+11 | 0.207323E+11 | 126356.66 | 03-OCT-02:07 | 78132.22 | 0.00 |
November | 0.00 | 0.00 | 0.376144E+10 | 0.370806E+10 | 107870.88 | 01-NOV-17:11 | 107870.88 | 0.00 |
December | 0.00 | 0.00 | 0.435102E+09 | 0.435100E+09 | 16831.37 | 22-DEC-15:00 | 16831.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.359953E+12 | 0.343674E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 176161.67 | 163773.45 | 5.23 | 5.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.689296E+11 | 0.664548E+11 | 135733.42 | 109443.14 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170143E+10 | 0.38 | 1713.30 | 03-JAN-08:15 | 0.99 |
February | 0.156437E+10 | 0.38 | 1713.30 | 01-FEB-07:05 | 0.99 |
March | 0.183574E+10 | 0.40 | 1713.30 | 01-MAR-13:20 | 0.98 |
April | 0.171800E+10 | 0.40 | 1713.30 | 01-APR-16:20 | 0.99 |
May | 0.181903E+10 | 0.43 | 1713.30 | 01-MAY-08:55 | 0.99 |
June | 0.186267E+10 | 0.52 | 1713.30 | 01-JUN-06:40 | 0.99 |
July | 0.179346E+10 | 0.48 | 1713.30 | 03-JUL-16:30 | 0.99 |
August | 0.191288E+10 | 0.48 | 1713.30 | 04-AUG-08:18 | 0.97 |
September | 0.175291E+10 | 0.43 | 1713.30 | 12-SEP-14:40 | 0.98 |
October | 0.172061E+10 | 0.39 | 1713.30 | 04-OCT-06:15 | 0.98 |
November | 0.163011E+10 | 0.36 | 1713.30 | 01-NOV-12:30 | 0.98 |
December | 0.170351E+10 | 0.38 | 1713.30 | 01-DEC-07:10 | 0.99 |
Annual Sum or Average | 0.210147E+11 | 0.42 | |||
Minimum of Months | 0.156437E+10 | 0.36 | 1713.30 | 0.97 | |
Maximum of Months | 0.191288E+10 | 0.52 | 1713.30 | 0.99 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.948200E+10 | 0.66 | 9537.01 | 04-JAN-14:10 | 1.70 |
February | 0.868631E+10 | 0.64 | 9537.01 | 02-FEB-15:50 | 1.70 |
March | 0.102073E+11 | 0.68 | 9537.01 | 01-MAR-13:00 | 1.69 |
April | 0.100347E+11 | 0.83 | 9537.01 | 01-APR-13:30 | 1.70 |
May | 0.108456E+11 | 0.95 | 9537.01 | 01-MAY-11:30 | 1.70 |
June | 0.118209E+11 | 1.20 | 9537.01 | 01-JUN-06:05 | 1.69 |
July | 0.116311E+11 | 1.17 | 9537.01 | 01-JUL-07:37 | 1.70 |
August | 0.118781E+11 | 1.11 | 9537.01 | 01-AUG-06:10 | 1.67 |
September | 0.107128E+11 | 0.99 | 9537.01 | 05-SEP-10:30 | 1.67 |
October | 0.984337E+10 | 0.74 | 9537.01 | 04-OCT-06:50 | 1.67 |
November | 0.906789E+10 | 0.62 | 9537.01 | 01-NOV-13:50 | 1.68 |
December | 0.944164E+10 | 0.63 | 9537.01 | 01-DEC-13:00 | 1.70 |
Annual Sum or Average | 0.123652E+12 | 0.85 | |||
Minimum of Months | 0.868631E+10 | 0.62 | 9537.01 | 1.67 | |
Maximum of Months | 0.118781E+11 | 1.20 | 9537.01 | 1.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.226190E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159853E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241692E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.408084E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.516027E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.678414E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.656809E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.684094E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.574962E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.368201E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.225979E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189836E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.493014E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159853E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.684094E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101947E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.868636E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.114087E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.196624E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.254650E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.352430E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.344393E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.334911E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.276012E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.166656E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.102078E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.957320E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.242638E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.868636E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.352430E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170143E+10 | 0.205434E+10 | 0.278561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156437E+10 | 0.124615E+09 | 0.225165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183574E+10 | 0.210593E+10 | 0.239282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171800E+10 | 0.813986E+10 | 4350399.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181903E+10 | 0.111591E+11 | 17380818.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186267E+10 | 0.152701E+11 | 844872.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179346E+10 | 0.156491E+11 | 857136.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191288E+10 | 0.161993E+11 | 692592.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175291E+10 | 0.135840E+11 | 332121.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172061E+10 | 0.685869E+10 | 12067144.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163011E+10 | 0.230915E+10 | 60352251.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170351E+10 | 0.718122E+09 | 0.429561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210147E+11 | 0.941723E+11 | 0.126945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156437E+10 | 0.124615E+09 | 332121.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191288E+10 | 0.161993E+11 | 0.429561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.948200E+10 | 0.233462E+10 | 0.501900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.868631E+10 | 176161.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102073E+11 | 0.393227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100347E+11 | 0.301378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108456E+11 | 0.441967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118209E+11 | 0.665260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116311E+11 | 0.689296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118781E+11 | 0.653417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107128E+11 | 0.527926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.984337E+10 | 0.215649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.906789E+10 | 0.376144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944164E+10 | 0.435102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123652E+12 | 0.359953E+12 | 0.501900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.868631E+10 | 176161.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118781E+11 | 0.689296E+11 | 0.501900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170143E+10 | 0.00 | 0.00 | 0.00 | 0.560473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156437E+10 | 0.00 | 0.00 | 0.00 | 34155286.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183574E+10 | 0.00 | 0.00 | 0.00 | 0.581178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171800E+10 | 0.00 | 0.00 | 0.00 | 0.236284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181903E+10 | 0.00 | 0.00 | 0.00 | 0.334124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186267E+10 | 0.00 | 0.00 | 0.00 | 0.492147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179346E+10 | 0.00 | 0.00 | 0.00 | 0.477463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191288E+10 | 0.00 | 0.00 | 0.00 | 0.492806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175291E+10 | 0.00 | 0.00 | 0.00 | 0.399672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172061E+10 | 0.00 | 0.00 | 0.00 | 0.196140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163011E+10 | 0.00 | 0.00 | 0.00 | 0.629680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170351E+10 | 0.00 | 0.00 | 0.00 | 0.194844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210147E+11 | 0.00 | 0.00 | 0.00 | 0.282867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156437E+10 | 0.00 | 0.00 | 0.00 | 34155286.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191288E+10 | 0.00 | 0.00 | 0.00 | 0.492806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.948200E+10 | 0.00 | 0.00 | 0.00 | 0.712661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.868631E+10 | 0.00 | 0.00 | 0.00 | 52994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102073E+11 | 0.00 | 0.00 | 0.00 | 0.120144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100347E+11 | 0.00 | 0.00 | 0.00 | 0.962775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108456E+11 | 0.00 | 0.00 | 0.00 | 0.146194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118209E+11 | 0.00 | 0.00 | 0.00 | 0.234221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116311E+11 | 0.00 | 0.00 | 0.00 | 0.228082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118781E+11 | 0.00 | 0.00 | 0.00 | 0.216130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107128E+11 | 0.00 | 0.00 | 0.00 | 0.168884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.984337E+10 | 0.00 | 0.00 | 0.00 | 0.682219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.906789E+10 | 0.00 | 0.00 | 0.00 | 0.113993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944164E+10 | 0.00 | 0.00 | 0.00 | 0.131562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123652E+12 | 0.00 | 0.00 | 0.00 | 0.118987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.868631E+10 | 0.00 | 0.00 | 0.00 | 52994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118781E+11 | 0.00 | 0.00 | 0.00 | 0.234221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192441E+09 | 3664659.72 | 0.00 | 4072225.19 | 0.00 | 14422637.85 | 0.231263E+10 | 0.00 | 0.72 |
February | 0.339340E+09 | 0.00 | 0.00 | 2495153.65 | 0.00 | 0.00 | 0.284910E+10 | 0.00 | 0.55 |
March | 0.197037E+09 | 18908710.92 | 0.00 | 4158171.46 | 0.00 | 6062814.18 | 0.284954E+10 | 0.00 | 0.75 |
April | 24268608.55 | 0.253137E+09 | 0.00 | 5282907.95 | 0.00 | 0.00 | 0.114449E+10 | 0.00 | 0.48 |
May | 2394782.91 | 0.475522E+09 | 0.00 | 6138086.11 | 0.00 | 0.00 | 0.616675E+09 | 0.00 | 0.38 |
June | 723518.37 | 0.107804E+10 | 0.00 | 5556365.73 | 0.00 | 0.00 | 85967993.07 | 0.00 | 0.22 |
July | 0.00 | 0.138841E+10 | 0.00 | 4262751.73 | 0.00 | 0.00 | 40356080.96 | 0.00 | 0.19 |
August | 121354.32 | 0.151837E+10 | 0.00 | 5864404.62 | 177656.39 | 0.00 | 58255177.73 | 0.00 | 0.25 |
September | 0.00 | 0.109089E+10 | 0.00 | 6114688.40 | 62370.49 | 0.00 | 0.208847E+09 | 0.00 | 0.33 |
October | 38931342.72 | 0.290926E+09 | 0.00 | 6168982.40 | 123304.17 | 0.00 | 0.190660E+10 | 0.00 | 0.63 |
November | 97473387.10 | 17121551.19 | 0.00 | 4785395.53 | 0.00 | 2325141.28 | 0.301123E+10 | 0.00 | 0.76 |
December | 0.420853E+09 | 0.00 | 0.00 | 3006729.91 | 0.00 | 18538151.00 | 0.254465E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.131359E+10 | 0.613499E+10 | 0.00 | 57905862.67 | 363331.05 | 41348744.30 | 0.176283E+11 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2495153.65 | 0.00 | 0.00 | 40356080.96 | 0.00 | 0.19 |
Maximum of Months | 0.420853E+09 | 0.151837E+10 | 0.00 | 6168982.40 | 177656.39 | 18538151.00 | 0.301123E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212273E+10 | 116668.91 | 0.00 | 5046744.28 | 0.00 | 0.00 | 0.665478E+10 | 0.00 | 0.68 |
February | 0.350822E+10 | 0.00 | 0.00 | 1537468.72 | 0.00 | 0.00 | 0.390161E+10 | 0.00 | 0.31 |
March | 0.252837E+10 | 1060458.00 | 0.00 | 6748501.49 | 0.00 | 0.00 | 0.685135E+10 | 0.00 | 0.67 |
April | 0.333722E+09 | 0.290776E+09 | 0.00 | 19662152.05 | 0.00 | 0.00 | 0.515568E+10 | 0.00 | 0.67 |
May | 0.111949E+09 | 0.693067E+09 | 0.00 | 16586840.37 | 0.00 | 0.00 | 0.333347E+10 | 0.00 | 0.55 |
June | 2137466.05 | 0.213870E+10 | 0.00 | 6756688.28 | 0.00 | 0.00 | 0.928932E+09 | 0.00 | 0.36 |
July | 0.00 | 0.358114E+10 | 0.00 | 3538163.41 | 9229734.27 | 0.00 | 0.486551E+09 | 0.00 | 0.37 |
August | 2541005.80 | 0.368126E+10 | 0.00 | 4610307.58 | 3241484.35 | 0.00 | 0.101590E+10 | 0.00 | 0.47 |
September | 31481267.84 | 0.241419E+10 | 0.00 | 8777897.80 | 3045051.54 | 0.00 | 0.208316E+10 | 0.00 | 0.57 |
October | 0.585340E+09 | 0.430409E+09 | 0.00 | 15114687.41 | 0.00 | 0.00 | 0.754137E+10 | 0.00 | 0.77 |
November | 0.141407E+10 | 901682.74 | 0.00 | 8883798.57 | 0.00 | 0.00 | 0.906634E+10 | 0.00 | 0.76 |
December | 0.367152E+10 | 0.00 | 0.00 | 1767921.94 | 0.00 | 0.00 | 0.343237E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.143121E+11 | 0.132316E+11 | 0.00 | 99031171.89 | 15516270.16 | 0.00 | 0.504515E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1537468.72 | 0.00 | 0.00 | 0.486551E+09 | 0.00 | 0.31 |
Maximum of Months | 0.367152E+10 | 0.368126E+10 | 0.00 | 19662152.05 | 9229734.27 | 0.00 | 0.906634E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.617903E+12 | 0.300560E+11 | 0.00 | 0.113023E+11 | 0.107389E+11 |
February | 0.619583E+12 | 0.336837E+11 | 0.00 | 0.106023E+11 | 0.450716E+10 |
March | 0.863998E+12 | 0.430830E+11 | 0.00 | 0.124233E+11 | 0.126288E+11 |
April | 0.114500E+13 | 0.304501E+11 | 0.00 | 0.617260E+10 | 0.548065E+11 |
May | 0.120355E+13 | 0.408113E+11 | 0.00 | 0.291101E+10 | 0.780122E+11 |
June | 0.123273E+13 | 0.504196E+11 | 0.00 | -0.218104E+10 | 0.114676E+12 |
July | 0.109502E+13 | 0.590253E+11 | 0.00 | -0.444174E+10 | 0.116849E+12 |
August | 0.992147E+12 | 0.554710E+11 | 0.00 | -0.411105E+10 | 0.112770E+12 |
September | 0.824167E+12 | 0.450528E+11 | 0.00 | -0.112947E+10 | 0.917979E+11 |
October | 0.764287E+12 | 0.458829E+11 | 0.00 | 0.942712E+10 | 0.419006E+11 |
November | 0.618312E+12 | 0.406871E+11 | 0.00 | 0.135854E+11 | 0.124074E+11 |
December | 0.508646E+12 | 0.343233E+11 | 0.00 | 0.100927E+11 | 0.637446E+10 |
Annual Sum or Average | 0.104853E+14 | 0.508946E+12 | 0.00 | 0.646535E+11 | 0.657469E+12 |
Minimum of Months | 0.508646E+12 | 0.300560E+11 | 0.00 | -0.444174E+10 | 0.450716E+10 |
Maximum of Months | 0.123273E+13 | 0.590253E+11 | 0.00 | 0.135854E+11 | 0.116849E+12 |