Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 10:43:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1869.05 | 386.56 | 386.56 |
Net Site Energy | 1869.05 | 386.56 | 386.56 |
Total Source Energy | 3073.80 | 635.72 | 635.72 |
Net Source Energy | 3073.80 | 635.72 | 635.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1366.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 204.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 503.00 | 1366.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1366.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 204.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 34.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1366.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 204.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 34.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 27.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.84 | 282.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 104.03 | 282.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.84 | 282.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 104.03 | 282.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 503.002 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 503.002 | 100.00 |
Total On-Site and Utility Electric Sources | 503.002 | 100.00 |
Total Electricity End Uses | 503.002 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 77.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3014.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.9961 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.6188 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.9961 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 9.2031 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.6188 | 46.45 | 2.5587 | |
Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 6.8172 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 18-DEC-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 300256.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10116.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14472.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1894.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 38728.21 | 300256.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 300256.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10116.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 14472.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1894.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1480.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 646.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 293.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 108.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1593.01 | 1480.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 306.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 329.47 | 306.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 306.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 329.47 | 306.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.04 |
ZONE2 FINE STORAGE DIRECT AIR | 1.86 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.76 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.76 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 147298.80 |
PSZ-OFFICE HEATING COIL | 29292.25 |
PSZ-FINE STORAGE HEATING COIL | 76550.33 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 147298.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-FINE STORAGE | 1.86 | 1.86 | 1.86 | 1.86 | 1.86 | 1.86 | 1.00 | 1.00 | 1.86 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.04 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.86 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.04 | 1154.74 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.86 | 1992.72 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 18582.98 | 29292.25 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.86 | 1.86 | 1.86 | 1.23 | 44377.37 | 76550.33 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.04 | 0.521489 | 0.695320 | 18582.98 | 9291.49 | 0.800580 | 0.800580 |
PSZ-FINE STORAGE COOLING COIL | 1.86 | 0.931134 | 1.24 | 44377.37 | 22188.69 | 0.714400 | 0.714400 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 9.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.203 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.619 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.177 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2131.000 | 8.996 | 167.154 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2131.000 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 12823.730 | 9.203 | 427.458 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12823.730 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 18007.220 | 5.619 | 260.974 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 18007.220 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1041 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.4317E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.4042E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.529 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 23.09 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 24.66 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.40943546E-08 | -0.48941433E-14 | 0.10002011E-14 | -0.40158259E-16 |
55 | 6 | 0.31272124E-05 | 0.19933103E-08 | 0.31973031E-02 | -0.26821658E-04 |
56 | 5 | -0.21335304E-03 | 0.11766416E-05 | -0.22414699 | 0.19598788E-02 |
57 | 4 | 0.48316011E-02 | 0.53476752E-04 | 4.8365802 | -0.45332602E-01 |
58 | 3 | -0.42187430E-01 | 0.42463702E-03 | -38.061149 | 0.39909293 |
59 | 2 | 0.14945981 | 0.70555311E-03 | 116.56127 | -1.4189736 |
60 | 1 | -0.21550367 | 0.21454475E-03 | -143.95282 | 2.0497880 |
61 | 0 | 0.10501452 | 0.52166033E-05 | 60.838472 | |
62 | 7 | -0.99354594E-08 | 0.85994744E-15 | -0.36446392E-14 | 0.33402613E-16 |
63 | 6 | 0.19007305E-05 | 0.85218543E-09 | 0.32020323E-02 | -0.26861330E-04 |
64 | 5 | -0.10257637E-03 | 0.49552608E-06 | -0.22441548 | 0.19622488E-02 |
65 | 4 | 0.21308868E-02 | 0.22341873E-04 | 4.8410464 | -0.45375540E-01 |
66 | 3 | -0.17974913E-01 | 0.17625076E-03 | -38.086349 | 0.39937154 |
67 | 2 | 0.62772635E-01 | 0.29099605E-03 | 116.61028 | -1.4196292 |
68 | 1 | -0.89915137E-01 | 0.87799409E-04 | -143.98166 | 2.0502620 |
69 | 0 | 0.43667207E-01 | 0.21083643E-05 | 60.838472 | |
70 | 7 | -0.10614037E-07 | 0.12466653E-14 | -0.85452615E-14 | 0.12855439E-15 |
71 | 6 | 0.18765462E-05 | 0.80237200E-09 | 0.32022472E-02 | -0.26863133E-04 |
72 | 5 | -0.98338504E-04 | 0.46542478E-06 | -0.22442766 | 0.19623563E-02 |
73 | 4 | 0.20165412E-02 | 0.20956150E-04 | 4.8412485 | -0.45377483E-01 |
74 | 3 | -0.16916006E-01 | 0.16514078E-03 | -38.087488 | 0.39938413 |
75 | 2 | 0.58934009E-01 | 0.27235831E-03 | 116.61249 | -1.4196588 |
76 | 1 | -0.84323034E-01 | 0.82076304E-04 | -143.98296 | 2.0502833 |
77 | 0 | 0.40927925E-01 | 0.19639094E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2921_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2921_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2735E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9430E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0239E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4660E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4409E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4814E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1956E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0107E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7437E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6826E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7197E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0404E-003 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3687E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0668E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3870E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6547E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3917E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9433E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1315E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5057E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4798E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1712E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1460E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2350E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0723E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0373E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6554E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0770E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8710E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4783E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.4218E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.6978E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.7704E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.9375E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.4742E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.5567E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2282E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.6976E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.9248E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 7.1645E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.3741E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.0501E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.6979E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.9298E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6319E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.3353E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 6.3068E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.5064E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.7676E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5542E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1971E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.6412E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.0513E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4676E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.5802E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.5159E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9056E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5593E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.9456E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6356E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0512E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4676E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10122.82293 | 12147.38751 | 0.86915 | 1.04298 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11622.44069 | 13946.92883 | 0.34052 | 0.40862 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 23185.43399 | 27822.52079 | 1.55189 | 1.86227 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38652.52882 | 46383.03458 | 0.95365 | 1.14438 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 122749.00896 | 147298.81075 | 3.12955 | 3.75546 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14938.77 | 1.04298 | 1.04298 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15353.48 | 0.40862 | 0.40862 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 33360.61 | 1.86227 | 1.86227 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 56201.63 | 1.14438 | 1.14438 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04298 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.86227 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.75546 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.75546 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 147298.80004 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 147298.81075 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04298 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04298 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04298 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04298 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04298 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.04298 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.86227 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.86227 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.86227 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.86227 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.86227 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.86227 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.04298 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.86227 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04298 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04298 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1154.74136 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04298 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04298 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04298 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04298 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04298 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52149 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69532 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18582.98000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9291.49000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80058 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80058 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18582.98000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29292.25171 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29292.25171 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.86227 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.86227 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1992.71524 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.86227 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.86227 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.86227 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22910 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.86227 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.93113 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24151 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44377.37000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22188.68500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71440 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71440 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44377.37000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 76550.33254 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 76550.33254 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17773.5 | 12.35 | 12.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 42930.1 | 11.99 | 11.72 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.5383634967 | 0.5203629268 | Pass | Pass | 0.9788825002 | 0.8761883271 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.0085596616 | 0.9459881627 | Pass | Pass | 0.6675209121 | 0.6518297414 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.2177160793E-005 | 1.3707571041E-004 | Pass | Pass | 2.3849767253E-002 | 2.0493306076E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7553.92 | 923.20 | 0.00 | 106.96 | 345.18 | 8929.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.102 | 0.104 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.043 | 0.043 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.040 | 0.040 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.849 | 0.521 | 0.520 | |||||||||||||||||
North Total or Average | 6.51 | 1.659 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.146 | 0.539 | 0.537 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.9961 | 236.88 | 2131.00 | LightsWired | LTG_SCH_OFFICE | 51.55 | 168.00 | 46.09 | 0.0000 | Y | 18.44 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 9.2031 | 1393.41 | 12823.73 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 33.37 | 0.0000 | Y | 80.33 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.6188 | 3204.84 | 18007.22 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 31.22 | 0.0000 | Y | 105.52 |
Interior Lighting Total | 6.8172 | 4835.13 | 32961.95 | 204.29 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 18007.22 | 2088.84 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2131.00 | 309.00 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 2131.00 | 106.55 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 94.73 | AstronomicalClock | - | 42.55 | 42.55 | 0.76 | |
EXTERIOR_LIGHTS_B | 6863.48 | AstronomicalClock | - | 83.52 | 71.23 | 91.77 | |
Exterior Lighting Total | 6958.21 | 92.52 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18582.98 | 14877.16 | 3705.82 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44377.37 | 31703.19 | 12674.18 | 0.71 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17773.5 | 12.35 | 12.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 42930.1 | 11.99 | 11.72 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 147298.80 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29292.25 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 76550.33 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.76 | 348.92 | 92.91 | 1.00 | 3.26 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1154.74 | 1107.16 | 1.00 | 1.39 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.86 | 1992.72 | 1070.05 | 1.00 | 1.33 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10122.82 | 12147.39 | 51.28 | 0.869 | 1.043 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00851 | 28.36 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 23185.43 | 27822.52 | 19.97 | 1.552 | 1.862 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00923 | 29.85 | 0.01273 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 30.40 | 0.01279 | 29.98 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11622.44 | 13946.93 | 58.88 | 0.341 | 0.409 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00771 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 38652.53 | 46383.03 | 33.29 | 0.954 | 1.144 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00657 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 122749.01 | 147298.81 | 45.96 | 3.130 | 3.755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00555 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.04 | 1.04 | 0.41 | 0.41 | 1.0430 | 1.0430 | 1.0430 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.86 | 1.86 | 1.14 | 1.14 | 1.8623 | 1.8623 | 1.8623 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 147298.800 | 147298.800 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 147298.80 | 147298.80 | 3.755455 | 10.00 | 7.33 | 0.00554699 | 43.33 | 21.64 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00554699 | 69.9018 | 147298.81 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18582.980 | 14877.162 | 1.042980 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 9291.49 | 8067.02 | 0.695320 | 25.31 | 16.76 | 0.00892632 | 12.00 | 10.89 | 0.00800000 | 28.69 | 0.01272339 | 20.72 | 14.7104 | 23.90 | 0.00851284 | 44.1821 | 10109.25 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29292.252 | 29292.252 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29292.25 | 29292.25 | 1.042977 | 15.78 | 11.41 | 0.00696945 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 9.8070 | 21.10 | 0.00770733 | 47.4801 | 11622.44 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 44377.370 | 31703.193 | 1.862270 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 22188.69 | 17373.57 | 1.241513 | 28.38 | 18.65 | 0.01002758 | 12.00 | 10.89 | 0.00800000 | 30.10 | 0.01272586 | 21.13 | 34.2092 | 26.70 | 0.00922873 | 40.5061 | 23147.99 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 76550.333 | 76550.333 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 76550.33 | 76550.33 | 1.862268 | 4.55 | 4.10 | 0.00511281 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.8061 | 15.55 | 0.00656915 | 57.4134 | 38652.53 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 147298.800 | 147298.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.755455 | 4.33351314 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 147298.80 | 147298.80 | 1.0000 | 4.33351314 | 3.755455 | 10.00 | 7.33 | 0.00554699 | 24020.6 | 43.33 | 21.64 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 147298.80 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00554699 | 10.00 | 0.00554699 | 69.9018 | 147298.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18582.980 | 14877.162 | 1.042980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4336 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.042977 | 1.20351736 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 9291.49 | 8067.02 | 1.0000 | 0.80234703 | 0.695320 | 25.31 | 16.76 | 0.00892632 | 48175.1 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9291.49 | 28.69 | 0.01272339 | 20.72 | 0.10228463 | 14.7104 | 23.90 | 0.00851284 | 23.90 | 0.00851284 | 44.1821 | 10109.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29292.252 | 29292.252 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.042977 | 1.20351736 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 29292.25 | 29292.25 | 1.0000 | 1.20351736 | 1.042977 | 15.78 | 11.41 | 0.00696945 | 33489.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29292.25 | -32.70 | 0.00018338 | -32.70 | 0.10228463 | 9.8070 | 21.05 | 0.00770733 | 21.10 | 0.00770733 | 47.4801 | 11622.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44377.370 | 31703.193 | 1.862270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4808 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.862268 | 2.14891782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 22188.69 | 17373.57 | 1.0000 | 1.43261310 | 1.241513 | 28.38 | 18.65 | 0.01002758 | 54125.1 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22188.69 | 30.10 | 0.01272586 | 21.13 | 0.42471127 | 34.2092 | 26.70 | 0.00922873 | 26.70 | 0.00922873 | 40.5061 | 23147.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76550.333 | 76550.333 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.862268 | 2.14891782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 76550.33 | 76550.33 | 1.0000 | 2.14891782 | 1.862268 | 4.55 | 4.10 | 0.00511281 | 17401.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76550.33 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 22.8061 | 15.55 | 0.00656915 | 15.55 | 0.00656915 | 57.4134 | 38652.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.04 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2885.83 | 3005.00 | 2363.67 |
ZONE2 FINE STORAGE | 3156.50 | 3193.33 | 2793.83 |
ZONE3 BULK STORAGE | 3202.50 | 3305.50 | 2924.50 |
Facility | 3375.00 | 3367.67 | 3014.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 193.33 | 0.00 | 46.67 | 0.00 |
ZONE2 FINE STORAGE | 587.00 | 1.33 | 27.50 | 0.00 |
ZONE3 BULK STORAGE | 45.00 | 0.00 | 17.83 | 0.00 |
Facility | 756.00 | 1.33 | 77.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.652 | 0.447 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.461 | 0.245 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.152 | 0.000 | 0.057 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2346233.92 | 0.00 | 2346233.92 | 2325123.62 | 4671357.54 | 3225648.14 | 5720.04 | 2315.81 | 724.15 | 0.00 |
ZONE2 FINE STORAGE | 4923692.01 | 0.00 | 4923692.01 | 6606177.37 | 11529869.38 | 13393694.68 | 5727.15 | 2823.58 | 209.27 | 1.52 |
ZONE3 BULK STORAGE | 0.00 | 15949858.85 | 15949858.85 | 38498288.51 | 54448147.36 | 30805497.77 | 8272.00 | 55.83 | 432.17 | 4777.50 |
Total Facility | 7269925.93 | 15949858.85 | 23219784.79 | 47429589.50 | 70649374.28 | 47424840.58 | 8505.67 | 2973.52 | 1250.88 | 4777.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1792 | 0.0000 | 0.1792 | 0.1239 | 0.3031 | 0.1023 | 596.04 | 2315.81 | 724.15 |
ZONE2 FINE STORAGE | 0.3758 | 0.0000 | 0.3758 | 0.2003 | 0.5761 | 0.4247 | 604.67 | 2823.58 | 207.75 |
ZONE3 BULK STORAGE | 0.0000 | 0.5637 | 0.5637 | 1.5030 | 2.0667 | 0.9768 | 3366.17 | 27.83 | 242.00 |
Total Facility | 0.5550 | 0.5637 | 1.1187 | 1.8272 | 2.9459 | 1.5038 | 3381.67 | 2945.52 | 1059.20 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3124110.35 | 0.00 | 3124110.35 | 3225648.14 | 5718.04 | 0.00 | 3041.96 | 0.00 |
PSZ-FINE STORAGE | 6556347.29 | 0.00 | 6556347.29 | 13393694.68 | 5727.15 | 0.00 | 3032.85 | 1.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2387 | 0.0000 | 0.2387 | 0.1023 | 594.04 | 0.00 | 3041.96 |
PSZ-FINE STORAGE | 0.5004 | 0.0000 | 0.5004 | 0.4247 | 604.67 | 0.00 | 3031.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2699.63 | 344.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2980.44 | 52.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2553 | 0.5195 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5960 | 0.8600 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
Electricity:Building | 343.58 | 2396.55 | 02-APR-14:10 | 25798.42 | 15-NOV-16:00 |
Electricity:Zone:ZONE1 OFFICE | 50.38 | 815.73 | 19-FEB-14:30 | 3198.43 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 343.58 | 2396.55 | 02-APR-14:10 | 25798.42 | 15-NOV-16:00 |
InteriorLights:Electricity | 204.29 | 1822.80 | 02-APR-14:10 | 15685.80 | 15-NOV-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.44 | 241.98 | 19-FEB-14:30 | 1285.93 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 204.29 | 1822.80 | 02-APR-14:10 | 15685.80 | 15-NOV-16:00 |
LightsWired:InteriorLights:Electricity | 204.29 | 1822.80 | 02-APR-14:10 | 15685.80 | 15-NOV-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.44 | 241.98 | 19-FEB-14:30 | 1285.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 204.29 | 1822.80 | 02-APR-14:10 | 15685.80 | 15-NOV-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 212.86 | 875.51 | 08-JAN-11:10 | 16618.50 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 105.52 | 875.51 | 08-JAN-11:10 | 8418.38 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 105.52 | 875.51 | 08-JAN-11:10 | 8418.38 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 34.13 | 0.00 | 19-MAR-13:40 | 3318.31 | 04-JAN-08:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
ElectricityNet:Plant | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
General:Cogeneration:ElectricityNet | 503.00 | 2879.55 | 16-APR-13:30 | 38728.21 | 30-JUN-15:00 |
Electricity:HVAC | 39.39 | 0.00 | 19-MAR-13:40 | 13730.82 | 29-JUN-16:00 |
General:Fans:Electricity | 34.13 | 0.00 | 19-MAR-13:40 | 3318.31 | 04-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.25 | 0.00 | 01-JAN-00:10 | 11468.20 | 29-JUN-16:00 |
General:Cooling:Electricity | 5.25 | 0.00 | 01-JAN-00:10 | 11468.20 | 29-JUN-16:00 |
ExteriorLights:Electricity | 92.52 | 0.00 | 01-JAN-08:20 | 6958.21 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.52 | 0.00 | 01-JAN-08:20 | 6958.21 | 01-JAN-06:10 |
Electricity:Plant | 27.51 | 483.00 | 03-JAN-24:00 | 3106.67 | 25-FEB-12:20 |
WaterSystems:Electricity | 27.51 | 483.00 | 03-JAN-24:00 | 3106.67 | 25-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 27.51 | 483.00 | 03-JAN-24:00 | 3106.67 | 25-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1366.05 | 0.00 | 19-MAR-13:30 | 300256.50 | 18-DEC-17:10 |
NaturalGas:HVAC | 1366.05 | 0.00 | 19-MAR-13:30 | 300256.50 | 18-DEC-17:10 |
Heating:NaturalGas | 1366.05 | 0.00 | 19-MAR-13:30 | 300256.50 | 18-DEC-17:10 |
General:Heating:NaturalGas | 1366.05 | 0.00 | 19-MAR-13:30 | 300256.50 | 18-DEC-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2105.72 | 0.00 | 19-MAR-13:40 | 454077.60 | 18-DEC-17:10 |
EnergyTransfer:Building | 1032.01 | 0.00 | 19-MAR-13:40 | 225399.62 | 04-JAN-08:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 76.66 | 0.00 | 01-JAN-00:40 | 30506.66 | 05-JAN-07:20 |
Heating:EnergyTransfer | 998.51 | 0.00 | 19-MAR-13:40 | 225399.62 | 04-JAN-08:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 62.89 | 0.00 | 01-JAN-00:40 | 30506.66 | 05-JAN-07:20 |
General:Heating:EnergyTransfer | 998.51 | 0.00 | 19-MAR-13:40 | 225399.62 | 04-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 62.89 | 0.00 | 01-JAN-00:40 | 30506.66 | 05-JAN-07:20 |
Cooling:EnergyTransfer | 33.50 | 0.00 | 01-JAN-00:10 | 24922.91 | 30-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 13.77 | 0.00 | 01-JAN-00:10 | 10392.52 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer | 33.50 | 0.00 | 01-JAN-00:10 | 24922.91 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 13.77 | 0.00 | 01-JAN-00:10 | 10392.52 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 215.34 | 0.00 | 01-JAN-00:40 | 61225.13 | 12-FEB-22:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 195.61 | 0.00 | 01-JAN-00:40 | 61225.13 | 12-FEB-22:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 195.61 | 0.00 | 01-JAN-00:40 | 61225.13 | 12-FEB-22:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.73 | 0.00 | 01-JAN-00:10 | 16156.61 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.73 | 0.00 | 01-JAN-00:10 | 16156.61 | 30-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 740.02 | 0.00 | 13-JAN-14:00 | 148760.65 | 18-DEC-13:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 740.02 | 0.00 | 13-JAN-14:00 | 148760.65 | 18-DEC-13:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 740.02 | 0.00 | 13-JAN-14:00 | 148760.65 | 18-DEC-13:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1073.71 | 0.00 | 19-MAR-13:30 | 237626.61 | 18-DEC-17:10 |
HeatingCoils:EnergyTransfer | 1049.92 | 0.00 | 19-MAR-13:30 | 237626.61 | 18-DEC-17:10 |
CoolingCoils:EnergyTransfer | 23.80 | 0.00 | 01-JAN-00:10 | 46105.38 | 30-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 62.889 | -13.765 | 0.000 | 0.000 | 10.195 | 18.438 | 31.946 | 12.330 | 0.000 | 0.434 | 0.000 | 0.000 | -9.525 | 0.000 | -48.101 | -64.842 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 195.606 | -19.734 | 0.000 | 0.000 | 27.241 | 80.328 | 0.000 | 0.000 | 0.000 | 0.536 | 0.001 | 0.000 | 0.000 | 0.000 | -120.583 | -163.396 |
ZONE3 BULK STORAGE | 740.015 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 70.058 | 105.521 | 107.344 | 121.989 | 0.000 | 12.328 | 0.000 | 0.000 | -88.510 | 0.000 | -740.283 | -328.462 |
Total Facility | 740.015 | 0.000 | 258.496 | -33.498 | 0.000 | 0.000 | 107.495 | 204.288 | 139.290 | 134.319 | 0.000 | 13.298 | 0.002 | 0.000 | -98.036 | 0.000 | -908.966 | -556.700 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 08-JUL-07:02 | 0.00 | 0.00 | 0.00 | -21269.87 | 0.00 | 0.00 | 801.53 | 1232.35 | 1912.50 | 0.00 | 0.00 | 0.00 | 18015.14 | 0.00 | -110.09 | 0.00 | -581.56 | 0.00 |
ZONE2 FINE STORAGE | 24-JUL-17:08 | 0.00 | 0.00 | 0.00 | -35802.86 | 0.00 | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 471.45 | 34626.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:08 | 0.00 | 0.00 | 0.00 | -35802.86 | 0.00 | 0.00 | 0.00 | 1899.39 | 2623.78 | 33370.12 | 0.00 | 745.03 | 0.00 | 0.00 | 0.00 | 0.00 | -88.06 | -2747.41 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-DEC-06:31 | 0.00 | 0.00 | 31297.73 | 0.00 | 0.00 | 0.00 | 153.41 | 384.11 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1126.83 | 0.00 | -4910.07 | -26372.10 |
ZONE2 FINE STORAGE | 05-JAN-06:41 | 0.00 | 0.00 | 80215.57 | 0.00 | 0.00 | 0.00 | 383.52 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11964.35 | -69340.05 |
ZONE3 BULK STORAGE | 18-DEC-13:30 | 148758.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8451.73 | 7767.35 | 8200.12 | 0.00 | 0.00 | 0.00 | 7542.01 | 0.00 | -2811.30 | 0.00 | -177908.49 | 0.00 |
Total Facility | 16-DEC-06:01 | 147642.11 | 0.00 | 106570.39 | 0.00 | 0.00 | 0.00 | 1462.81 | 2079.82 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7371.66 | 0.00 | -158232.46 | -94774.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0430 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0430 | 0.0981 | 1.0000 | Not calculated | 0.1023 | 0.0981 | ||
PSZ-FINE STORAGE | 1.8623 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.8623 | 0.2281 | 1.0000 | Not calculated | 0.4247 | 0.2281 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0430 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0430 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0981 | ||
PSZ-FINE STORAGE | 1.8623 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.8623 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2281 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0430 | 1.0430 | 1.0430 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8623 | 1.8623 | 1.8623 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0430 | 1.0430 | 1.0430 | 1.0430 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8623 | 1.8623 | 1.8623 | 1.8623 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0430 | 1.0430 | 1.0430 | No | 0.1023 | 0.2503 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8623 | 1.8623 | 1.8623 | No | 0.4247 | 0.3711 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0430 | 1.0430 | 1.0430 | 1.0430 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8623 | 1.8623 | 1.8623 | 1.8623 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 77.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 77.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1366.05 | 300256.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.25 | 11468.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 204.29 | 15685.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.52 | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 34.13 | 3318.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.51 | 3106.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 503.00 |
Natural Gas | 0.00 | 1366.05 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1869.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 42.25 |
Space Heating | 0.00 |
Space Cooling | 1.09 |
Fans (All) | 7.06 |
Service Water Heating | 5.69 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 104.03 |
Subtotal | 104.03 |
Natural Gas [MJ/m2] | |
Space Heating | 282.53 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 282.53 |
Subtotal | 282.53 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.93 |
Space Heating | 73.09 |
Space Cooling | 0.28 |
Fans (All) | 1.83 |
Service Water Heating | 1.47 |
Receptacle Equipment | 7.45 |
Miscellaneous | 4.95 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2688. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8433.00 | 327.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8336.67 | 423.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8457.00 | 301.67 | 1.33 | 0.00 | 0.00 |
Min | 8336.67 | 301.67 | 0.00 | 0.00 | 0.00 |
Max | 8457.00 | 423.33 | 1.33 | 0.00 | 0.00 |
Average | 8408.89 | 350.67 | 0.44 | 0.00 | 0.00 |
Sum | 25226.67 | 1052.00 | 1.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33022.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 74984.50 | 7734.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 180443.67 | 10665.17 | 84.17 | 0.00 | 0.00 |
Min | 33022.50 | 4.50 | 0.00 | 0.00 | 0.00 |
Max | 180443.67 | 10665.17 | 84.17 | 0.00 | 0.00 |
Average | 96150.22 | 6134.72 | 28.06 | 0.00 | 0.00 |
Sum | 288450.67 | 18404.17 | 84.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7981.50 | 778.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7724.33 | 1035.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7887.83 | 872.17 | 0.00 | 0.00 | 0.00 |
Min | 7724.33 | 778.50 | 0.00 | 0.00 | 0.00 |
Max | 7981.50 | 1035.67 | 0.00 | 0.00 | 0.00 |
Average | 7864.56 | 895.44 | 0.00 | 0.00 | 0.00 |
Sum | 23593.67 | 2686.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31999.17 | 1027.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 69539.50 | 13179.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 167860.17 | 23332.83 | 0.00 | 0.00 | 0.00 |
Min | 31999.17 | 1027.83 | 0.00 | 0.00 | 0.00 |
Max | 167860.17 | 23332.83 | 0.00 | 0.00 | 0.00 |
Average | 89799.61 | 12513.39 | 0.00 | 0.00 | 0.00 |
Sum | 269398.83 | 37540.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70964.72 | 354.82 | 21-JAN-08:07 | -22.1 | -22.3 | 0.492388E+09 | 603.25 | 03-JAN-15:09 | -22.1 | -22.3 |
February | 103639.01 | 518.20 | 11-FEB-08:07 | -15.5 | -15.9 | 0.453884E+09 | 603.25 | 02-FEB-14:09 | -15.5 | -15.9 |
March | 366935.49 | 780.33 | 25-MAR-07:07 | -3.2 | -3.7 | 0.532924E+09 | 603.25 | 01-MAR-16:49 | -3.2 | -3.7 |
April | 5448943.50 | 1680.92 | 13-APR-07:07 | -1.8 | -3.5 | 0.500327E+09 | 752.31 | 13-APR-15:00 | 20.00 | 8.11 |
May | 0.996833E+09 | 19038.19 | 27-MAY-07:02 | 17.20 | 13.08 | 0.600012E+09 | 879.36 | 27-MAY-07:10 | 17.20 | 13.08 |
June | 0.285305E+10 | 15431.39 | 24-JUN-07:02 | 17.30 | 16.96 | 0.653942E+09 | 879.39 | 30-JUN-07:10 | 26.02 | 21.73 |
July | 0.477508E+10 | 21272.08 | 08-JUL-07:02 | 13.40 | 11.20 | 0.638053E+09 | 879.39 | 22-JUL-07:10 | 21.78 | 20.21 |
August | 0.392463E+10 | 19945.42 | 05-AUG-07:02 | 15.78 | 12.69 | 0.685625E+09 | 879.39 | 26-AUG-07:10 | 17.57 | 15.27 |
September | 0.117047E+10 | 20995.67 | 02-SEP-07:02 | 13.17 | 11.14 | 0.589086E+09 | 879.39 | 02-SEP-07:10 | 13.17 | 11.14 |
October | 37481450.68 | 1945.53 | 25-OCT-07:07 | -3.2 | -3.4 | 0.504427E+09 | 768.97 | 19-OCT-15:50 | -3.2 | -3.4 |
November | 1551256.50 | 1606.12 | 18-NOV-08:07 | -0.7 | -1.8 | 0.474303E+09 | 655.57 | 01-NOV-15:00 | -0.7 | -1.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.493228E+09 | 603.25 | 01-DEC-11:30 | -19.4 | -19.9 |
Annual Sum or Average | 0.137651E+11 | 0.661820E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -22.1 | -22.3 | 0.453884E+09 | 603.25 | -22.1 | -22.3 | ||
Maximum of Months | 0.477508E+10 | 21272.08 | 17.30 | 16.96 | 0.685625E+09 | 879.39 | 26.02 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 822802.95 | 238.17 | 17-JAN-13:10 | -3.6 | -4.9 | 0.649055E+09 | 787.42 | 27-JAN-11:39 | -17.6 | -18.3 |
February | 0.221411E+09 | 4512.97 | 08-FEB-14:10 | 5.00 | -0.5 | 0.597266E+09 | 799.43 | 08-FEB-14:30 | 5.00 | -0.5 |
March | 0.780118E+09 | 7085.03 | 23-MAR-13:30 | -0.6 | -4.5 | 0.702978E+09 | 916.17 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.153856E+10 | 5444.88 | 27-APR-15:50 | 3.03 | -1.1 | 0.724473E+09 | 1304.07 | 13-APR-15:00 | 3.03 | -1.1 |
May | 0.173465E+10 | 5973.70 | 20-MAY-08:20 | 6.87 | 3.69 | 0.121051E+10 | 2246.80 | 25-MAY-15:30 | 29.00 | 19.65 |
June | 0.256770E+10 | 31246.90 | 30-JUN-17:08 | 30.92 | 21.22 | 0.159916E+10 | 2246.93 | 30-JUN-14:30 | 30.92 | 21.22 |
July | 0.453044E+10 | 35805.72 | 24-JUL-17:08 | 28.80 | 19.14 | 0.179509E+10 | 2246.91 | 29-JUL-15:09 | 30.10 | 21.16 |
August | 0.292054E+10 | 22409.29 | 08-AUG-17:25 | 28.85 | 22.75 | 0.181266E+10 | 2246.84 | 04-AUG-15:09 | 28.85 | 22.75 |
September | 0.261742E+10 | 7874.36 | 06-SEP-07:03 | 4.05 | 3.63 | 0.120933E+10 | 2246.81 | 01-SEP-10:00 | 4.05 | 3.63 |
October | 0.217435E+10 | 6625.29 | 04-OCT-07:03 | 0.37 | 0.10 | 0.740085E+09 | 1377.42 | 21-OCT-15:09 | 20.00 | 11.21 |
November | 0.647608E+09 | 7621.49 | 04-NOV-09:45 | -2.3 | -3.7 | 0.634197E+09 | 1081.57 | 01-NOV-15:09 | -2.3 | -3.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.649126E+09 | 787.42 | 29-DEC-11:00 | -12.8 | -13.6 |
Annual Sum or Average | 0.197336E+11 | 0.123239E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -8.8 | -9.9 | 0.597266E+09 | 787.42 | -17.6 | -18.3 | ||
Maximum of Months | 0.453044E+10 | 35805.72 | 30.92 | 22.75 | 0.181266E+10 | 2246.93 | 30.92 | 22.75 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.632795E+09 | 841.38 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.595348E+09 | 900.37 | 11-FEB-15:09 | -6.1 | -8.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.713522E+09 | 1068.06 | 23-MAR-14:20 | 0.20 | -4.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 | 0.849339E+09 | 1790.33 | 18-APR-13:00 | 17.80 | 10.49 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 | -1.4 | 0.193439E+10 | 3880.17 | 25-MAY-15:30 | 29.00 | 19.65 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.321490E+10 | 6195.25 | 30-JUN-15:30 | 31.95 | 24.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.422834E+10 | 6213.30 | 24-JUL-15:20 | 29.23 | 19.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.395797E+10 | 5551.41 | 08-AUG-15:00 | 30.60 | 22.99 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.246993E+10 | 5203.07 | 01-SEP-15:00 | 26.10 | 17.64 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.104627E+10 | 2187.01 | 02-OCT-13:39 | 10.37 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.659846E+09 | 1408.41 | 01-NOV-14:30 | 18.05 | 13.35 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.639357E+09 | 794.91 | 02-DEC-15:30 | -17.9 | -18.6 |
Annual Sum or Average | 0.00 | 0.209420E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.595348E+09 | 794.91 | -17.9 | -18.6 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.422834E+10 | 6213.30 | 31.95 | 24.59 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143319E+11 | 31270.15 | 25-JAN-06:31 | -25.2 |
February | 0.108311E+11 | 31264.64 | 01-FEB-06:31 | -22.8 |
March | 0.920871E+10 | 30484.26 | 14-MAR-05:32 | -13.7 |
April | 0.441983E+10 | 29666.23 | 04-APR-06:02 | -9.2 |
May | 0.838424E+09 | 29413.24 | 01-MAY-06:02 | -3.5 |
June | 0.115735E+09 | 8820.55 | 02-JUN-07:03 | 10.18 |
July | 81388328.03 | 1706.00 | 24-JUL-06:07 | 18.68 |
August | 0.116146E+09 | 1760.08 | 25-AUG-06:15 | 9.80 |
September | 0.432270E+09 | 29075.59 | 28-SEP-06:02 | 6.70 |
October | 0.296819E+10 | 29612.78 | 30-OCT-06:02 | -9.4 |
November | 0.660834E+10 | 30076.55 | 29-NOV-06:42 | -19.2 |
December | 0.129384E+11 | 31297.65 | 20-DEC-06:31 | -29.0 |
Annual Sum or Average | 0.628904E+11 | |||
Minimum of Months | 81388328.03 | 1706.00 | -29.0 | |
Maximum of Months | 0.143319E+11 | 31297.65 | 18.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489077E+11 | 80215.53 | 05-JAN-06:41 | -32.3 |
February | 0.358380E+11 | 79925.03 | 24-FEB-02:61 | -18.4 |
March | 0.256994E+11 | 79091.21 | 06-MAR-04:02 | -17.4 |
April | 0.105132E+11 | 77413.00 | 04-APR-18:23 | -6.4 |
May | 0.700791E+09 | 48006.60 | 01-MAY-04:03 | -2.9 |
June | 80714025.33 | 1317.71 | 06-JUN-13:00 | 25.60 |
July | 56028933.66 | 770.43 | 24-JUL-06:25 | 19.45 |
August | 63836982.29 | 864.83 | 31-AUG-07:00 | 17.20 |
September | 68741190.92 | 844.25 | 23-SEP-07:00 | 3.90 |
October | 0.553831E+10 | 65001.96 | 31-OCT-21:03 | -1.9 |
November | 0.215628E+11 | 79100.67 | 25-NOV-02:62 | -15.7 |
December | 0.465772E+11 | 79951.22 | 20-DEC-01:21 | -27.8 |
Annual Sum or Average | 0.195607E+12 | |||
Minimum of Months | 56028933.66 | 770.43 | -32.3 | |
Maximum of Months | 0.489077E+11 | 80215.53 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200282E+12 | 148578.36 | 04-JAN-10:00 | -28.9 |
February | 0.149097E+12 | 148421.41 | 12-FEB-23:00 | -17.2 |
March | 0.947203E+11 | 123643.31 | 15-MAR-04:53 | -22.2 |
April | 0.266841E+11 | 77570.89 | 04-APR-18:54 | -7.2 |
May | 0.152925E+09 | 12826.76 | 01-MAY-03:57 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.321285E+10 | 37684.92 | 31-OCT-20:57 | -2.2 |
November | 0.756857E+11 | 104558.76 | 25-NOV-02:00 | -15.6 |
December | 0.190181E+12 | 148760.65 | 18-DEC-13:30 | -22.8 |
Annual Sum or Average | 0.740016E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.200282E+12 | 148760.65 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160262E+10 | 1285.93 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.141816E+10 | 1267.14 | 02-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.161010E+10 | 1263.92 | 13-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.150235E+10 | 1256.05 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.151438E+10 | 1194.96 | 19-MAY-08:30 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.149286E+10 | 1234.99 | 30-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.148585E+10 | 1232.35 | 08-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.156891E+10 | 1255.54 | 31-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.150419E+10 | 1257.46 | 19-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.156561E+10 | 1284.61 | 31-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.154930E+10 | 1285.93 | 06-NOV-16:49 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.162396E+10 | 1285.93 | 01-DEC-16:19 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.184383E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.141816E+10 | 1194.96 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.162396E+10 | 1285.93 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.668164E+10 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.611542E+10 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.706504E+10 | 5995.09 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.662070E+10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.687334E+10 | 5995.09 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.681240E+10 | 5995.09 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.668164E+10 | 5995.09 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.706504E+10 | 5995.09 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.662070E+10 | 5995.09 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.668164E+10 | 5995.09 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.642900E+10 | 5995.09 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.668164E+10 | 5995.09 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.803282E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.611542E+10 | 5995.09 | 0.00 | 0.00 | |
Maximum of Months | 0.706504E+10 | 5995.09 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910070E+10 | 8418.38 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.818919E+10 | 8418.38 | 01-FEB-15:20 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.931349E+10 | 8418.38 | 06-MAR-15:50 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.861283E+10 | 8092.87 | 04-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.876975E+10 | 8092.87 | 06-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.866050E+10 | 7767.35 | 09-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.850788E+10 | 7767.35 | 05-JUL-09:30 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.905070E+10 | 8092.87 | 15-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.863094E+10 | 8092.87 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.887007E+10 | 8418.38 | 17-OCT-14:20 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.870225E+10 | 8418.38 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.911273E+10 | 8418.38 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.105521E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.818919E+10 | 7767.35 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.931349E+10 | 8418.38 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.160262E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881887E+10 |
February | 0.127628E+10 | 0.141816E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695789E+10 |
March | 0.149825E+10 | 0.161010E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587535E+10 |
April | 0.138726E+10 | 0.150235E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11224659.71 | 0.360736E+10 |
May | 0.144276E+10 | 0.151438E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60874535.52 | 0.168065E+10 |
June | 0.144276E+10 | 0.149286E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143086E+09 | 0.100326E+10 |
July | 0.138726E+10 | 0.148585E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141529E+09 | 0.829702E+09 |
August | 0.149825E+10 | 0.156891E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73731817.26 | 0.124175E+10 |
September | 0.138726E+10 | 0.150419E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3215070.20 | 0.198484E+10 |
October | 0.138726E+10 | 0.156561E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303790E+10 |
November | 0.133177E+10 | 0.154930E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489622E+10 |
December | 0.138726E+10 | 0.162396E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816712E+10 |
Annual Sum or Average | 0.168137E+11 | 0.184383E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433661E+09 | 0.481009E+11 |
Minimum of Months | 0.127628E+10 | 0.141816E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829702E+09 |
Maximum of Months | 0.149825E+10 | 0.162396E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143086E+09 | 0.881887E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217386E+11 |
February | 0.300332E+10 | 0.611542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181112E+11 |
March | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127951E+11 |
April | 0.326447E+10 | 0.662070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96990601.79 | 0.899460E+10 |
May | 0.339505E+10 | 0.687334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117157E+09 | 0.388995E+10 |
June | 0.339505E+10 | 0.681240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161802E+09 | 0.273667E+10 |
July | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117764E+09 | 0.273223E+10 |
August | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33279293.94 | 0.357648E+10 |
September | 0.326447E+10 | 0.662070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3800406.51 | 0.480172E+10 |
October | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5638943.87 | 0.614748E+10 |
November | 0.313390E+10 | 0.642900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130112E+11 |
December | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220476E+11 |
Annual Sum or Average | 0.395654E+11 | 0.803282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536432E+09 | 0.120583E+12 |
Minimum of Months | 0.300332E+10 | 0.611542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273223E+10 |
Maximum of Months | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161802E+09 | 0.220476E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.910070E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101874E+12 |
February | 0.690763E+10 | 0.818919E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824256E+11 |
March | 0.810895E+10 | 0.931349E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1738261.12 | 0.550879E+11 |
April | 0.750829E+10 | 0.861283E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200026E+10 | 0.304714E+11 |
May | 0.780862E+10 | 0.876975E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358168E+10 | 0.128360E+11 |
June | 0.780862E+10 | 0.866050E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144032E+10 | 0.102992E+11 |
July | 0.750829E+10 | 0.850788E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229297E+09 | 0.150626E+11 |
August | 0.810895E+10 | 0.905070E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281453E+09 | 0.184584E+11 |
September | 0.750829E+10 | 0.863094E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135902E+09 | 0.234318E+11 |
October | 0.750829E+10 | 0.887007E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839809E+09 | 0.219674E+11 |
November | 0.720796E+10 | 0.870225E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292421E+09 | 0.500680E+11 |
December | 0.750829E+10 | 0.911273E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996333E+11 |
Annual Sum or Average | 0.910005E+11 | 0.105521E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880288E+10 | 0.521616E+12 |
Minimum of Months | 0.690763E+10 | 0.818919E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102992E+11 |
Maximum of Months | 0.810895E+10 | 0.931349E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358168E+10 | 0.101874E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1285.93 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 24343.77 | 05-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1267.14 | 02-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23523.54 | 14-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1263.92 | 13-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19847.60 | 15-MAR-06:20 |
April | 1680.92 | 01-APR-07:10 | 1256.05 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.53 | 23-APR-16:00 | 12836.70 | 04-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1194.96 | 19-MAY-08:30 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.34 | 25-MAY-16:10 | 8697.23 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1234.99 | 30-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.89 | 29-JUN-16:10 | 4488.18 | 09-JUN-11:05 |
July | 1680.92 | 01-JUL-07:10 | 1232.35 | 08-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2141.00 | 28-JUL-16:10 | 4762.35 | 27-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1255.54 | 31-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2758.11 | 08-AUG-16:10 | 5550.92 | 17-AUG-16:03 |
September | 1680.92 | 01-SEP-07:10 | 1257.46 | 19-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 712.57 | 01-SEP-16:10 | 7456.33 | 06-SEP-06:03 |
October | 1680.92 | 02-OCT-07:10 | 1284.61 | 31-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12547.46 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1285.93 | 06-NOV-16:49 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16402.29 | 29-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1285.93 | 01-DEC-16:19 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 23510.58 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1194.96 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4488.18 | |||||
Maximum of Months | 1680.92 | 1285.93 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.89 | 24343.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 26759.87 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 32644.15 | 12-FEB-23:00 |
March | 3955.50 | 01-MAR-08:09 | 5995.09 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19931.54 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4679.77 | 23-APR-16:00 | 16287.34 | 26-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 5995.09 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2295.02 | 10-MAY-15:10 | 7692.22 | 20-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 5995.09 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.65 | 29-JUN-16:00 | 7046.79 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 5995.09 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.42 | 15-JUL-15:10 | 5056.59 | 08-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 5995.09 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2305.49 | 08-AUG-16:00 | 9331.87 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 5995.09 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.89 | 24-SEP-15:00 | 7897.94 | 20-SEP-06:10 |
October | 3955.50 | 02-OCT-07:10 | 5995.09 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.19 | 19-OCT-15:10 | 10713.64 | 31-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 5995.09 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15882.26 | 22-NOV-01:50 |
December | 3955.50 | 01-DEC-08:09 | 5995.09 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 32861.77 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5056.59 | ||||
Maximum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4679.77 | 32861.77 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 8418.38 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 154029.76 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 8418.38 | 01-FEB-15:20 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 120669.04 | 12-FEB-22:55 |
March | 9097.65 | 01-MAR-08:09 | 8418.38 | 06-MAR-15:50 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 696.62 | 26-MAR-16:00 | 77070.24 | 14-MAR-15:50 |
April | 9097.65 | 01-APR-07:10 | 8092.87 | 04-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34599.90 | 23-APR-16:00 | 53593.80 | 26-APR-15:00 |
May | 9097.65 | 01-MAY-07:10 | 8092.87 | 06-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22492.77 | 10-MAY-15:00 | 25790.79 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 7767.35 | 09-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16249.17 | 29-JUN-16:00 | 34630.79 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 7767.35 | 05-JUL-09:30 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9466.77 | 15-JUL-14:00 | 39369.01 | 03-JUL-11:00 |
August | 9097.65 | 01-AUG-07:10 | 8092.87 | 15-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8448.08 | 08-AUG-16:00 | 52323.68 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 8092.87 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5940.26 | 24-SEP-15:00 | 30451.42 | 20-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 8418.38 | 17-OCT-14:20 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19512.38 | 19-OCT-15:00 | 36508.14 | 05-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 8418.38 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.67 | 01-NOV-14:00 | 64879.46 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 8418.38 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 138678.09 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 7767.35 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25790.79 | |||||
Maximum of Months | 9097.65 | 8418.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 34599.90 | 154029.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 354.82 | 21-JAN-08:07 | 5042.77 | 3784.51 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.63 |
February | 518.20 | 11-FEB-08:07 | 5042.77 | 3741.14 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.09 |
March | 780.33 | 25-MAR-07:07 | 5042.77 | 3746.34 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.58 |
April | 1680.92 | 13-APR-07:07 | 5042.77 | 3521.85 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.09 |
May | 19038.19 | 27-MAY-07:02 | 8404.61 | 5387.96 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.00 |
June | 15431.39 | 24-JUN-07:02 | 8404.61 | 6084.88 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.16 |
July | 21272.08 | 08-JUL-07:02 | 8404.61 | 6161.75 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.56 |
August | 19945.42 | 05-AUG-07:02 | 8404.61 | 5703.41 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 |
September | 20995.67 | 02-SEP-07:02 | 8404.61 | 5987.04 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 |
October | 1945.53 | 25-OCT-07:07 | 5042.77 | 3771.53 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.98 |
November | 1606.12 | 18-NOV-08:07 | 5042.77 | 3769.45 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.37 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1202.40 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1407.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1202.40 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 | |
Maximum of Months | 21272.08 | 8404.61 | 6161.75 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 238.17 | 17-JAN-13:10 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.12 |
February | 4512.97 | 08-FEB-14:10 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.45 |
March | 7085.03 | 23-MAR-13:30 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5444.88 | 27-APR-15:50 | 3955.50 | 5289.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.77 |
May | 5973.70 | 20-MAY-08:20 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2542.35 |
June | 31246.90 | 30-JUN-17:08 | 0.00 | 3526.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.73 | 0.00 |
July | 35805.72 | 24-JUL-17:08 | 0.00 | 3526.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.45 | 0.00 |
August | 22409.29 | 08-AUG-17:25 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.03 | 0.00 |
September | 7874.36 | 06-SEP-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.12 |
October | 6625.29 | 04-OCT-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3138.77 |
November | 7621.49 | 04-NOV-09:45 | 7911.00 | 11990.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.32 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8441.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35805.72 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.73 | 8441.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 6932.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38081.41 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 5942.38 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60689.62 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 2971.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16084.62 |
April | 0.00 | 01-APR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11249.81 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1980.79 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.59 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7914.26 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4983.92 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8599.48 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4595.96 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6107.68 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11241.46 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 3961.59 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31457.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.59 | |
Maximum of Months | 0.00 | 0.00 | 6932.78 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60689.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.461953E+11 | 36067.55 | 04-JAN-08:09 | 0.358854E+12 | 299594.00 | 04-JAN-17:30 |
February | 0.407278E+11 | 30913.43 | 13-FEB-15:39 | 0.266255E+12 | 282345.32 | 13-FEB-07:10 |
March | 0.446450E+11 | 30553.46 | 06-MAR-13:20 | 0.180305E+12 | 223650.63 | 15-MAR-05:10 |
April | 0.397002E+11 | 29902.16 | 04-APR-14:30 | 0.580858E+11 | 135581.23 | 04-APR-18:30 |
May | 0.393403E+11 | 31428.55 | 25-MAY-14:39 | 0.176199E+10 | 36253.84 | 01-MAY-04:10 |
June | 0.393731E+11 | 38728.21 | 30-JUN-14:00 | 7170573.75 | 4823.79 | 02-JUN-07:10 |
July | 0.400821E+11 | 36629.12 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.417046E+11 | 34934.13 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.397093E+11 | 32875.98 | 01-SEP-14:00 | 0.475563E+09 | 12513.99 | 28-SEP-06:10 |
October | 0.420250E+11 | 29948.33 | 30-OCT-08:20 | 0.185151E+11 | 78175.55 | 31-OCT-16:00 |
November | 0.430640E+11 | 35443.80 | 28-NOV-16:49 | 0.142520E+12 | 184131.97 | 25-NOV-02:09 |
December | 0.464354E+11 | 35741.51 | 19-DEC-16:49 | 0.339268E+12 | 300256.50 | 18-DEC-17:10 |
Annual Sum or Average | 0.503002E+12 | 0.136605E+13 | ||||
Minimum of Months | 0.393403E+11 | 29902.16 | 0.00 | 0.00 | ||
Maximum of Months | 0.464354E+11 | 38728.21 | 0.358854E+12 | 300256.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.173850E+11 | 0.105273E+11 | 0.115358E+11 | 0.00 | 0.434495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240229E+10 | 0.00 |
February | 0.157228E+11 | 0.852935E+10 | 0.105871E+11 | 0.00 | 0.368186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220663E+10 | 0.00 |
March | 0.179886E+11 | 0.811424E+10 | 0.123431E+11 | 0.00 | 0.370192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249716E+10 | 0.00 |
April | 0.167359E+11 | 0.651584E+10 | 0.114862E+11 | 0.00 | 0.262117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234112E+10 | 0.00 |
May | 0.171575E+11 | 0.563205E+10 | 0.119357E+11 | 0.00 | 0.202840E+10 | 0.00 | 0.00 | 0.220384E+09 | 0.00 | 0.00 | 0.00 | 0.236629E+10 | 0.00 |
June | 0.169658E+11 | 0.488712E+10 | 0.118862E+11 | 0.00 | 0.202074E+10 | 0.00 | 0.00 | 0.135787E+10 | 0.00 | 0.00 | 0.00 | 0.225547E+10 | 0.00 |
July | 0.166754E+11 | 0.528404E+10 | 0.115358E+11 | 0.00 | 0.195150E+10 | 0.00 | 0.00 | 0.241828E+10 | 0.00 | 0.00 | 0.00 | 0.221718E+10 | 0.00 |
August | 0.176846E+11 | 0.620153E+10 | 0.123357E+11 | 0.00 | 0.208744E+10 | 0.00 | 0.00 | 0.113993E+10 | 0.00 | 0.00 | 0.00 | 0.225540E+10 | 0.00 |
September | 0.167558E+11 | 0.726733E+10 | 0.114788E+11 | 0.00 | 0.193231E+10 | 0.00 | 0.00 | 0.117021E+09 | 0.00 | 0.00 | 0.00 | 0.215798E+10 | 0.00 |
October | 0.171173E+11 | 0.889495E+10 | 0.115432E+11 | 0.00 | 0.222524E+10 | 0.00 | 0.00 | 42.75 | 0.00 | 0.00 | 0.00 | 0.224436E+10 | 0.00 |
November | 0.166805E+11 | 0.982238E+10 | 0.110862E+11 | 0.00 | 0.325836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221652E+10 | 0.00 |
December | 0.174183E+11 | 0.108488E+11 | 0.115358E+11 | 0.00 | 0.427875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235375E+10 | 0.00 |
Annual Sum or Average | 0.204288E+12 | 0.925250E+11 | 0.139290E+12 | 0.00 | 0.341326E+11 | 0.00 | 0.00 | 0.525349E+10 | 0.00 | 0.00 | 0.00 | 0.275142E+11 | 0.00 |
Minimum of Months | 0.157228E+11 | 0.488712E+10 | 0.105871E+11 | 0.00 | 0.193231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215798E+10 | 0.00 |
Maximum of Months | 0.179886E+11 | 0.108488E+11 | 0.123431E+11 | 0.00 | 0.434495E+10 | 0.00 | 0.00 | 0.241828E+10 | 0.00 | 0.00 | 0.00 | 0.249716E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.358854E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.266255E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180305E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.580858E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.176199E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7170573.75 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.475563E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.185151E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.142520E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.339268E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136605E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.358854E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 15671.73 | 11-JAN-15:00 | 6958.21 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3318.31 | 04-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15619.86 | 10-FEB-09:09 | 6958.21 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3119.85 | 13-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15619.64 | 17-MAR-08:09 | 6958.21 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2994.64 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 15278.26 | 22-APR-08:09 | 6958.21 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2733.83 | 04-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 15262.09 | 06-MAY-08:09 | 6958.21 | 01-MAY-19:30 | 10112.62 | 01-MAY-07:10 | 0.00 | 2073.55 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 14974.03 | 10-JUN-08:09 | 6958.21 | 01-JUN-19:00 | 10112.62 | 01-JUN-07:10 | 0.00 | 2262.62 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 14963.11 | 22-JUL-08:30 | 6958.21 | 01-JUL-20:19 | 10112.62 | 01-JUL-07:10 | 0.00 | 1951.83 | 01-JUL-10:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 15324.30 | 31-AUG-08:09 | 6958.21 | 01-AUG-19:49 | 10112.62 | 01-AUG-07:10 | 0.00 | 1951.83 | 04-AUG-13:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 15312.47 | 19-SEP-08:09 | 6958.21 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 1951.83 | 01-SEP-16:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15658.61 | 26-OCT-08:09 | 6958.21 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2669.34 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 15685.80 | 15-NOV-15:00 | 6958.21 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2907.17 | 25-NOV-08:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 15683.11 | 13-DEC-15:00 | 6958.21 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3254.05 | 18-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 14963.11 | 6958.21 | 10112.62 | 0.00 | 1951.83 | 0.00 | 0.00 | |||||
Maximum of Months | 15685.80 | 6958.21 | 10112.62 | 0.00 | 3318.31 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3069.61 | 30-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3106.67 | 25-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3102.55 | 06-MAR-12:30 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3029.59 | 04-APR-11:30 | 0.00 |
May | 2831.49 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2881.20 | 02-MAY-11:50 | 0.00 |
June | 11468.20 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2653.11 | 01-JUN-11:09 | 0.00 |
July | 8432.39 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2400.68 | 03-JUL-11:30 | 0.00 |
August | 7318.40 | 08-AUG-15:39 | 0.00 | 0.00 | 0.00 | 2227.82 | 01-AUG-11:50 | 0.00 |
September | 4221.50 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2260.06 | 27-SEP-11:00 | 0.00 |
October | 0.03 | 21-OCT-14:20 | 0.00 | 0.00 | 0.00 | 2456.70 | 27-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2720.41 | 29-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2931.36 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2227.82 | 0.00 | ||
Maximum of Months | 11468.20 | 0.00 | 0.00 | 0.00 | 3106.67 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 36067.55 | 04-JAN-08:09 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 3318.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30913.43 | 13-FEB-15:39 | 15466.66 | 10112.62 | 0.00 | 0.00 | 2721.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30553.46 | 06-MAR-13:20 | 15196.10 | 10112.62 | 0.00 | 0.00 | 2584.56 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29902.16 | 04-APR-14:30 | 14797.62 | 10112.62 | 0.00 | 0.00 | 2413.81 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31428.55 | 25-MAY-14:39 | 14808.34 | 10112.62 | 0.00 | 0.00 | 1951.83 | 0.00 | 0.00 | 2337.17 | 0.00 |
June | 38728.21 | 30-JUN-14:00 | 14472.11 | 10112.62 | 0.00 | 0.00 | 2132.48 | 0.00 | 0.00 | 10116.68 | 0.00 |
July | 36629.12 | 15-JUL-14:30 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1951.83 | 0.00 | 0.00 | 8288.49 | 0.00 |
August | 34934.13 | 08-AUG-14:00 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1951.83 | 0.00 | 0.00 | 6750.66 | 0.00 |
September | 32875.98 | 01-SEP-14:00 | 14797.62 | 10112.62 | 0.00 | 0.00 | 1951.83 | 0.00 | 0.00 | 4221.50 | 0.00 |
October | 29948.33 | 30-OCT-08:20 | 15622.33 | 10112.62 | 0.00 | 0.00 | 2520.31 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35443.80 | 28-NOV-16:49 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 2743.45 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35741.51 | 19-DEC-16:49 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 3037.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29902.16 | 14003.70 | 10112.62 | 0.00 | 0.00 | 1951.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38728.21 | 15622.33 | 10112.62 | 6958.21 | 0.00 | 3318.31 | 0.00 | 0.00 | 10116.68 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 299594.00 | 04-JAN-17:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 282345.32 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 223650.63 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 135581.23 | 04-APR-18:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 36253.84 | 01-MAY-04:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4823.79 | 02-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 12513.99 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 78175.55 | 31-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 184131.97 | 25-NOV-02:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 300256.50 | 18-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 300256.50 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.17 | 15.58 | 16.33 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
February | 41.67 | 15.31 | 7.17 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
March | 16.83 | 15.58 | 6.17 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
April | 4.00 | 16.11 | 2.50 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
May | 0.17 | 17.02 | 0.17 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 17.07 | 1.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
November | 7.67 | 15.89 | 3.50 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
December | 58.67 | 15.30 | 9.67 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
Annual Sum or Average | 193.33 | 15.47 | 46.67 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.17 | 17.07 | 16.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.83 | 13.98 | 4.50 | 13.98 | 0.00 | 13.98 | 0.00 | 13.98 |
February | 102.67 | 14.20 | 4.17 | 14.20 | 0.00 | 14.20 | 0.00 | 14.20 |
March | 97.50 | 14.52 | 5.50 | 14.51 | 0.00 | 14.51 | 0.00 | 14.51 |
April | 49.67 | 14.75 | 3.17 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
May | 1.33 | 14.95 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.27 | 0.00 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13.83 | 14.91 | 0.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
November | 90.00 | 14.58 | 4.50 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
December | 116.17 | 14.04 | 4.67 | 14.04 | 0.00 | 14.04 | 0.00 | 14.04 |
Annual Sum or Average | 587.00 | 14.30 | 27.50 | 14.30 | 1.33 | 14.33 | 0.00 | 14.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.17 | 14.95 | 5.50 | 14.96 | 0.67 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.83 | 8.38 | 12.00 | 8.19 | 0.00 | 8.19 | 0.00 | 8.19 |
February | 3.83 | 8.87 | 0.00 | 8.87 | 0.00 | 8.87 | 0.00 | 8.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.33 | 8.50 | 5.83 | 8.38 | 0.00 | 8.38 | 0.00 | 8.38 |
Annual Sum or Average | 45.00 | 8.46 | 17.83 | 8.29 | 0.00 | 8.29 | 0.00 | 8.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.83 | 8.87 | 12.00 | 8.87 | 0.00 | 8.87 | 0.00 | 8.87 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.63 | 300.00 | 20.63 | 300.00 | 20.63 |
February | 276.00 | 20.69 | 276.00 | 20.69 | 276.00 | 20.69 |
March | 324.00 | 20.70 | 324.00 | 20.70 | 324.00 | 20.70 |
April | 300.00 | 20.85 | 284.17 | 20.80 | 284.17 | 20.78 |
May | 270.33 | 22.19 | 121.50 | 21.84 | 105.00 | 21.58 |
June | 229.17 | 23.58 | 125.33 | 23.73 | 63.83 | 23.77 |
July | 51.17 | 24.39 | 283.67 | 24.17 | 49.00 | 24.21 |
August | 96.67 | 23.76 | 246.83 | 23.97 | 55.83 | 23.98 |
September | 269.67 | 22.57 | 80.00 | 22.41 | 61.50 | 22.23 |
October | 300.00 | 20.93 | 259.33 | 20.82 | 259.33 | 20.77 |
November | 288.00 | 20.73 | 285.00 | 20.72 | 285.00 | 20.72 |
December | 300.00 | 20.68 | 300.00 | 20.68 | 300.00 | 20.68 |
Annual Sum or Average | 3005.00 | 21.41 | 2885.83 | 21.46 | 2363.67 | 21.31 |
Minimum of Months | 51.17 | 20.63 | 80.00 | 20.63 | 49.00 | 20.63 |
Maximum of Months | 324.00 | 24.39 | 324.00 | 24.17 | 324.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.56 | 324.00 | 15.56 | 324.00 | 15.56 |
April | 300.00 | 16.33 | 300.00 | 16.33 | 300.00 | 16.33 |
May | 271.17 | 19.89 | 207.33 | 19.80 | 177.67 | 19.49 |
June | 241.67 | 23.59 | 158.67 | 24.23 | 111.00 | 24.39 |
July | 146.67 | 26.43 | 286.00 | 26.29 | 142.50 | 26.34 |
August | 179.50 | 25.05 | 253.00 | 25.48 | 128.17 | 25.60 |
September | 266.33 | 20.62 | 163.50 | 20.44 | 146.50 | 20.20 |
October | 300.00 | 16.50 | 300.00 | 16.50 | 300.00 | 16.50 |
November | 288.00 | 15.66 | 288.00 | 15.66 | 288.00 | 15.66 |
December | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
Annual Sum or Average | 3193.33 | 18.15 | 3156.50 | 18.33 | 2793.83 | 18.09 |
Minimum of Months | 146.67 | 15.53 | 158.67 | 15.53 | 111.00 | 15.53 |
Maximum of Months | 324.00 | 26.43 | 324.00 | 26.29 | 324.00 | 26.34 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.90 | 300.00 | 9.90 | 300.00 | 9.90 |
February | 276.00 | 10.02 | 276.00 | 10.02 | 276.00 | 10.02 |
March | 324.00 | 10.12 | 324.00 | 10.12 | 324.00 | 10.12 |
April | 300.00 | 11.38 | 300.00 | 11.38 | 300.00 | 11.38 |
May | 312.00 | 16.95 | 264.50 | 16.55 | 264.50 | 16.40 |
June | 295.67 | 22.18 | 170.67 | 22.34 | 158.50 | 22.36 |
July | 150.67 | 27.13 | 278.50 | 26.78 | 146.17 | 26.90 |
August | 169.83 | 24.12 | 215.17 | 24.80 | 91.00 | 24.93 |
September | 289.33 | 19.69 | 185.67 | 19.29 | 176.33 | 19.03 |
October | 300.00 | 12.68 | 300.00 | 12.68 | 300.00 | 12.68 |
November | 288.00 | 10.29 | 288.00 | 10.29 | 288.00 | 10.29 |
December | 300.00 | 9.96 | 300.00 | 9.96 | 300.00 | 9.96 |
Annual Sum or Average | 3305.50 | 14.49 | 3202.50 | 14.53 | 2924.50 | 14.21 |
Minimum of Months | 150.67 | 9.90 | 170.67 | 9.90 | 91.00 | 9.90 |
Maximum of Months | 324.00 | 27.13 | 324.00 | 26.78 | 324.00 | 26.90 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.999631E+09 | 0.212595E+09 | 72.21 | 0.884018E+09 | 0.115614E+09 | 0.00 | 1.00 | 26-MAY-07:03 | 0.00 | 01-MAY-00:05 | 18200.81 | 27-MAY-07:02 | 14052.17 | 27-MAY-07:02 | 4619.45 | 26-MAY-07:03 | 3665.03 | 27-MAY-07:02 | 0.00 | 01-MAY-00:05 |
June | 0.331478E+10 | 0.691192E+09 | 163.33 | 0.255966E+10 | 0.755115E+09 | 0.00 | 1.00 | 24-JUN-07:02 | 0.00 | 01-JUN-00:10 | 22641.82 | 30-JUN-06:02 | 12907.70 | 30-JUN-07:02 | 9843.08 | 24-JUN-07:02 | 4473.98 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.587375E+10 | 0.118141E+10 | 226.02 | 0.440845E+10 | 0.146530E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 21859.53 | 22-JUL-07:02 | 13213.01 | 08-JUL-07:02 | 11781.73 | 05-JUL-07:04 | 4258.24 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.376081E+10 | 0.759608E+09 | 187.59 | 0.277016E+10 | 0.990649E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 20746.28 | 30-AUG-07:03 | 13817.05 | 05-AUG-07:02 | 10674.79 | 30-AUG-07:03 | 4100.87 | 30-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.398904E+09 | 81827245.47 | 39.70 | 0.339465E+09 | 59439547.96 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17348.72 | 02-SEP-07:02 | 12649.59 | 02-SEP-07:02 | 4699.13 | 02-SEP-07:02 | 3493.87 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 190.52 | 42.75 | 0.67 | 190.52 | 0.00 | 0.00 | 0.00 | 21-OCT-14:20 | 0.00 | 01-OCT-00:10 | 0.15 | 21-OCT-14:20 | 0.15 | 21-OCT-14:20 | 0.00 | 21-OCT-14:20 | 0.03 | 21-OCT-14:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.143479E+11 | 0.292663E+10 | 689.51 | 0.109618E+11 | 0.338611E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.587375E+10 | 0.118141E+10 | 226.02 | 0.440845E+10 | 0.146530E+10 | 0.00 | 1.00 | 0.00 | 22641.82 | 14052.17 | 11781.73 | 4473.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 28723662.02 | 7788890.08 | 3.17 | 20418449.85 | 8305212.17 | 0.00 | 0.18 | 25-MAY-16:00 | 0.00 | 01-MAY-00:05 | 3841.48 | 25-MAY-16:00 | 2746.86 | 25-MAY-16:00 | 1094.62 | 25-MAY-16:00 | 1038.14 | 25-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 0.268969E+10 | 0.666678E+09 | 56.33 | 0.174802E+10 | 0.941665E+09 | 0.00 | 1.00 | 28-JUN-17:12 | 0.00 | 01-JUN-00:10 | 50516.85 | 28-JUN-19:05 | 35196.17 | 30-JUN-19:23 | 18565.68 | 28-JUN-19:05 | 12047.28 | 29-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.506197E+10 | 0.123687E+10 | 143.31 | 0.327860E+10 | 0.178337E+10 | 0.00 | 1.00 | 02-JUL-14:55 | 0.00 | 01-JUL-00:10 | 54659.69 | 23-JUL-09:35 | 38742.07 | 24-JUL-17:08 | 28449.17 | 23-JUL-09:35 | 11862.75 | 03-JUL-18:05 | 0.00 | 01-JUL-00:10 |
August | 0.152841E+10 | 0.380324E+09 | 64.85 | 0.973298E+09 | 0.555116E+09 | 0.00 | 1.00 | 08-AUG-17:25 | 0.00 | 01-AUG-00:10 | 50589.38 | 09-AUG-17:23 | 32040.63 | 09-AUG-17:23 | 18548.74 | 09-AUG-17:23 | 11348.02 | 09-AUG-17:23 | 0.00 | 01-AUG-00:10 |
September | 0.140542E+09 | 35193309.82 | 6.33 | 0.101983E+09 | 38559483.64 | 0.00 | 0.45 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 9565.70 | 01-SEP-15:00 | 7300.61 | 01-SEP-15:00 | 2425.79 | 01-SEP-14:00 | 2391.07 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.944934E+10 | 0.232685E+10 | 273.98 | 0.612233E+10 | 0.332701E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.506197E+10 | 0.123687E+10 | 143.31 | 0.327860E+10 | 0.178337E+10 | 0.00 | 1.00 | 0.00 | 54659.69 | 38742.07 | 28449.17 | 12047.28 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.59 | 31.51 | 43.09 | 37.68 | 206.85 | 0.00 | 0.00 | 0.00 |
February | 120.51 | 55.11 | 65.40 | 90.11 | 161.00 | 0.00 | 0.00 | 0.00 |
March | 158.37 | 81.13 | 77.25 | 139.72 | 120.42 | 0.00 | 0.00 | 0.00 |
April | 201.75 | 102.06 | 99.69 | 213.31 | 68.15 | 0.00 | 0.00 | 0.00 |
May | 248.41 | 118.54 | 129.87 | 293.27 | 40.32 | 0.00 | 0.00 | 0.00 |
June | 239.42 | 103.48 | 135.94 | 289.93 | 32.48 | 0.00 | 0.00 | 0.00 |
July | 256.09 | 119.26 | 136.83 | 311.77 | 37.05 | 0.00 | 0.00 | 0.00 |
August | 209.73 | 94.90 | 114.83 | 250.00 | 41.07 | 0.00 | 0.00 | 0.00 |
September | 164.26 | 73.59 | 90.68 | 181.80 | 53.95 | 0.00 | 0.00 | 0.00 |
October | 104.03 | 41.80 | 62.23 | 99.05 | 71.21 | 0.00 | 0.00 | 0.00 |
November | 63.53 | 21.69 | 41.84 | 40.42 | 114.46 | 0.00 | 0.00 | 0.00 |
December | 56.13 | 19.58 | 36.55 | 21.58 | 199.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.28 | 71.99 | 86.29 | 164.47 | 95.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.13 | 19.58 | 36.55 | 21.58 | 32.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 256.09 | 119.26 | 136.83 | 311.77 | 206.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.59 | 31.51 | 43.09 | 37.68 | 206.85 | 0.00 | 0.00 | 0.00 |
February | 120.51 | 55.11 | 65.40 | 90.11 | 161.00 | 0.00 | 0.00 | 0.00 |
March | 158.37 | 81.13 | 77.25 | 139.72 | 120.42 | 0.00 | 0.00 | 0.00 |
April | 201.75 | 102.06 | 99.69 | 213.31 | 68.15 | 0.00 | 0.00 | 0.00 |
May | 248.41 | 118.54 | 129.87 | 293.27 | 40.32 | 0.00 | 0.00 | 0.00 |
June | 239.42 | 103.48 | 135.94 | 289.93 | 32.48 | 0.00 | 0.00 | 0.00 |
July | 256.09 | 119.26 | 136.83 | 311.77 | 37.05 | 0.00 | 0.00 | 0.00 |
August | 209.73 | 94.90 | 114.83 | 250.00 | 41.07 | 0.00 | 0.00 | 0.00 |
September | 164.26 | 73.59 | 90.68 | 181.80 | 53.95 | 0.00 | 0.00 | 0.00 |
October | 104.03 | 41.80 | 62.23 | 99.05 | 71.21 | 0.00 | 0.00 | 0.00 |
November | 63.53 | 21.69 | 41.84 | 40.42 | 114.46 | 0.00 | 0.00 | 0.00 |
December | 56.13 | 19.58 | 36.55 | 21.58 | 199.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.28 | 71.99 | 86.29 | 164.47 | 95.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.13 | 19.58 | 36.55 | 21.58 | 32.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 256.09 | 119.26 | 136.83 | 311.77 | 206.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 0.00 | 19.41 | 0.72 | 132.08 | 0.00 | 0.00 | 0.00 |
February | 29.82 | 0.00 | 29.82 | 5.11 | 100.78 | 0.00 | 0.00 | 0.00 |
March | 36.69 | 0.00 | 36.69 | 11.34 | 74.03 | 0.00 | 0.00 | 0.00 |
April | 48.21 | 0.48 | 47.73 | 33.47 | 39.77 | 0.00 | 0.00 | 0.00 |
May | 67.76 | 3.71 | 64.05 | 69.68 | 22.27 | 0.00 | 0.00 | 0.00 |
June | 75.56 | 8.36 | 67.20 | 85.82 | 18.01 | 0.00 | 0.00 | 0.00 |
July | 72.10 | 6.17 | 65.93 | 80.64 | 20.51 | 0.00 | 0.00 | 0.00 |
August | 54.98 | 1.13 | 53.85 | 56.94 | 23.37 | 0.00 | 0.00 | 0.00 |
September | 42.72 | 0.03 | 42.69 | 36.66 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 29.63 | 0.00 | 29.63 | 17.45 | 42.66 | 0.00 | 0.00 | 0.00 |
November | 19.62 | 0.00 | 19.62 | 3.74 | 70.45 | 0.00 | 0.00 | 0.00 |
December | 16.45 | 0.00 | 16.45 | 0.21 | 126.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.81 | 1.66 | 41.15 | 33.64 | 58.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.45 | 0.00 | 16.45 | 0.21 | 18.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.56 | 8.36 | 67.20 | 85.82 | 132.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.41 | 0.00 | 19.41 | 0.72 | 132.08 | 0.00 | 0.00 | 0.00 |
February | 29.82 | 0.00 | 29.82 | 5.11 | 100.78 | 0.00 | 0.00 | 0.00 |
March | 36.69 | 0.00 | 36.69 | 11.33 | 74.03 | 0.00 | 0.00 | 0.00 |
April | 48.21 | 0.48 | 47.72 | 33.47 | 39.77 | 0.00 | 0.00 | 0.00 |
May | 67.76 | 3.71 | 64.05 | 69.67 | 22.27 | 0.00 | 0.00 | 0.00 |
June | 75.55 | 8.36 | 67.20 | 85.82 | 18.01 | 0.00 | 0.00 | 0.00 |
July | 72.10 | 6.17 | 65.93 | 80.64 | 20.51 | 0.00 | 0.00 | 0.00 |
August | 54.98 | 1.13 | 53.85 | 56.94 | 23.37 | 0.00 | 0.00 | 0.00 |
September | 42.72 | 0.03 | 42.69 | 36.66 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 29.63 | 0.00 | 29.63 | 17.44 | 42.66 | 0.00 | 0.00 | 0.00 |
November | 19.62 | 0.00 | 19.62 | 3.74 | 70.45 | 0.00 | 0.00 | 0.00 |
December | 16.45 | 0.00 | 16.45 | 0.21 | 126.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.81 | 1.66 | 41.14 | 33.64 | 58.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.45 | 0.00 | 16.45 | 0.21 | 18.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.55 | 8.36 | 67.20 | 85.82 | 132.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.19 | 10.89 | 20.30 | 11.72 | 107.97 | 0.00 | 0.00 | 0.00 |
February | 55.28 | 25.44 | 29.85 | 43.53 | 84.23 | 0.00 | 0.00 | 0.00 |
March | 79.66 | 45.06 | 34.60 | 77.66 | 59.64 | 0.00 | 0.00 | 0.00 |
April | 116.10 | 73.12 | 42.98 | 136.09 | 33.74 | 2.00 | 0.00 | 0.00 |
May | 142.39 | 79.96 | 62.44 | 178.75 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 150.26 | 86.55 | 63.71 | 186.80 | 21.64 | 15.83 | 0.00 | 0.00 |
July | 153.60 | 91.53 | 62.07 | 184.98 | 29.07 | 2.33 | 0.00 | 0.00 |
August | 122.39 | 69.04 | 53.35 | 146.02 | 28.37 | 4.83 | 0.00 | 0.00 |
September | 88.93 | 46.04 | 42.89 | 101.86 | 32.95 | 4.83 | 0.00 | 0.00 |
October | 51.09 | 19.51 | 31.58 | 54.81 | 34.67 | 13.33 | 0.00 | 0.00 |
November | 30.51 | 9.34 | 21.17 | 23.34 | 54.58 | 12.67 | 0.00 | 0.00 |
December | 24.22 | 6.16 | 18.06 | 6.02 | 101.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.30 | 46.99 | 40.31 | 96.22 | 50.78 | 55.83 | 0.00 | 0.00 |
Minimum of Months | 24.22 | 6.16 | 18.06 | 6.02 | 21.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.60 | 91.53 | 63.71 | 186.80 | 107.97 | 15.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199794E+09 | 84389883.00 | 0.115404E+09 | 0.100917E+09 | 0.554017E+09 |
February | 0.291548E+09 | 0.133331E+09 | 0.158217E+09 | 0.217997E+09 | 0.389497E+09 |
March | 0.424186E+09 | 0.217289E+09 | 0.206898E+09 | 0.374235E+09 | 0.322532E+09 |
April | 0.522928E+09 | 0.264542E+09 | 0.258386E+09 | 0.552906E+09 | 0.176652E+09 |
May | 0.665338E+09 | 0.317502E+09 | 0.347836E+09 | 0.785495E+09 | 0.108000E+09 |
June | 0.620566E+09 | 0.268209E+09 | 0.352357E+09 | 0.751487E+09 | 84180524.60 |
July | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.835051E+09 | 99240894.28 |
August | 0.561744E+09 | 0.254174E+09 | 0.307570E+09 | 0.669597E+09 | 0.110008E+09 |
September | 0.425772E+09 | 0.190738E+09 | 0.235033E+09 | 0.471214E+09 | 0.139840E+09 |
October | 0.278640E+09 | 0.111969E+09 | 0.166671E+09 | 0.265307E+09 | 0.190733E+09 |
November | 0.164664E+09 | 56212558.91 | 0.108451E+09 | 0.104772E+09 | 0.296680E+09 |
December | 0.150340E+09 | 52445171.42 | 97894864.64 | 57811990.15 | 0.533923E+09 |
Annual Sum or Average | 0.499142E+10 | 0.227021E+10 | 0.272121E+10 | 0.518679E+10 | 0.300530E+10 |
Minimum of Months | 0.150340E+09 | 52445171.42 | 97894864.64 | 57811990.15 | 84180524.60 |
Maximum of Months | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.835051E+09 | 0.554017E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199794E+09 | 84389883.00 | 0.115404E+09 | 0.100917E+09 | 0.554017E+09 |
February | 0.291548E+09 | 0.133331E+09 | 0.158217E+09 | 0.217997E+09 | 0.389497E+09 |
March | 0.424186E+09 | 0.217289E+09 | 0.206898E+09 | 0.374235E+09 | 0.322532E+09 |
April | 0.522928E+09 | 0.264542E+09 | 0.258386E+09 | 0.552906E+09 | 0.176652E+09 |
May | 0.665338E+09 | 0.317502E+09 | 0.347836E+09 | 0.785495E+09 | 0.108000E+09 |
June | 0.620566E+09 | 0.268209E+09 | 0.352357E+09 | 0.751487E+09 | 84180524.60 |
July | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.835051E+09 | 99240894.28 |
August | 0.561744E+09 | 0.254174E+09 | 0.307570E+09 | 0.669597E+09 | 0.110008E+09 |
September | 0.425772E+09 | 0.190738E+09 | 0.235033E+09 | 0.471214E+09 | 0.139840E+09 |
October | 0.278640E+09 | 0.111969E+09 | 0.166671E+09 | 0.265307E+09 | 0.190733E+09 |
November | 0.164664E+09 | 56212558.91 | 0.108451E+09 | 0.104772E+09 | 0.296680E+09 |
December | 0.150340E+09 | 52445171.42 | 97894864.64 | 57811990.15 | 0.533923E+09 |
Annual Sum or Average | 0.499142E+10 | 0.227021E+10 | 0.272121E+10 | 0.518679E+10 | 0.300530E+10 |
Minimum of Months | 0.150340E+09 | 52445171.42 | 97894864.64 | 57811990.15 | 84180524.60 |
Maximum of Months | 0.685903E+09 | 0.319413E+09 | 0.366490E+09 | 0.835051E+09 | 0.554017E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51990863.87 | 0.00 | 51990863.87 | 1926934.63 | 0.353774E+09 |
February | 72133446.97 | 0.00 | 72133446.97 | 12365900.37 | 0.243809E+09 |
March | 98282822.99 | 7352.79 | 98275470.20 | 30361018.13 | 0.198289E+09 |
April | 0.124960E+09 | 1256703.87 | 0.123703E+09 | 86756750.78 | 0.103084E+09 |
May | 0.181487E+09 | 9924750.11 | 0.171562E+09 | 0.186621E+09 | 59658591.14 |
June | 0.195840E+09 | 21660897.00 | 0.174180E+09 | 0.222451E+09 | 46692409.29 |
July | 0.193117E+09 | 16529927.81 | 0.176587E+09 | 0.215997E+09 | 54925024.90 |
August | 0.147270E+09 | 3037828.54 | 0.144233E+09 | 0.152519E+09 | 62584452.92 |
September | 0.110730E+09 | 82776.70 | 0.110647E+09 | 95030584.47 | 82608903.16 |
October | 79364750.39 | 0.00 | 79364750.39 | 46726249.81 | 0.114254E+09 |
November | 50854377.39 | 0.00 | 50854377.39 | 9685647.95 | 0.182607E+09 |
December | 44050793.27 | 0.00 | 44050793.27 | 550546.77 | 0.337611E+09 |
Annual Sum or Average | 0.135008E+10 | 52500236.82 | 0.129758E+10 | 0.106099E+10 | 0.183990E+10 |
Minimum of Months | 44050793.27 | 0.00 | 44050793.27 | 550546.77 | 46692409.29 |
Maximum of Months | 0.195840E+09 | 21660897.00 | 0.176587E+09 | 0.222451E+09 | 0.353774E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51989147.24 | 0.00 | 51989147.24 | 1926589.86 | 0.353775E+09 |
February | 72131177.34 | 0.00 | 72131177.34 | 12364619.62 | 0.243809E+09 |
March | 98279861.15 | 7352.45 | 98272508.70 | 30358728.00 | 0.198289E+09 |
April | 0.124957E+09 | 1256644.97 | 0.123700E+09 | 86753016.20 | 0.103083E+09 |
May | 0.181481E+09 | 9924284.92 | 0.171557E+09 | 0.186614E+09 | 59658183.49 |
June | 0.195834E+09 | 21659881.72 | 0.174174E+09 | 0.222443E+09 | 46692063.57 |
July | 0.193111E+09 | 16529153.03 | 0.176582E+09 | 0.215990E+09 | 54924605.26 |
August | 0.147266E+09 | 3037686.16 | 0.144228E+09 | 0.152514E+09 | 62584117.59 |
September | 0.110726E+09 | 82772.82 | 0.110644E+09 | 95026668.51 | 82608647.79 |
October | 79362103.55 | 0.00 | 79362103.55 | 46723489.43 | 0.114254E+09 |
November | 50852644.70 | 0.00 | 50852644.70 | 9684664.50 | 0.182607E+09 |
December | 44049291.06 | 0.00 | 44049291.06 | 550409.27 | 0.337612E+09 |
Annual Sum or Average | 0.135004E+10 | 52497776.06 | 0.129754E+10 | 0.106095E+10 | 0.183990E+10 |
Minimum of Months | 44049291.06 | 0.00 | 44049291.06 | 550409.27 | 46692063.57 |
Maximum of Months | 0.195834E+09 | 21659881.72 | 0.176582E+09 | 0.222443E+09 | 0.353775E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83552590.32 | 29179118.55 | 54373471.77 | 31380659.48 | 0.289179E+09 |
February | 0.133743E+09 | 61538591.07 | 72204020.66 | 0.105302E+09 | 0.203764E+09 |
March | 0.213374E+09 | 0.120694E+09 | 92679939.19 | 0.208008E+09 | 0.159753E+09 |
April | 0.300928E+09 | 0.189517E+09 | 0.111411E+09 | 0.352758E+09 | 87461813.16 |
May | 0.381386E+09 | 0.214153E+09 | 0.167233E+09 | 0.478759E+09 | 59820501.88 |
June | 0.389469E+09 | 0.224334E+09 | 0.165134E+09 | 0.484180E+09 | 56097522.02 |
July | 0.411403E+09 | 0.245148E+09 | 0.166255E+09 | 0.495441E+09 | 77874200.27 |
August | 0.327809E+09 | 0.184913E+09 | 0.142897E+09 | 0.391090E+09 | 75988283.12 |
September | 0.230515E+09 | 0.119336E+09 | 0.111180E+09 | 0.264025E+09 | 85407489.96 |
October | 0.136848E+09 | 52265865.98 | 84582064.19 | 0.146807E+09 | 92851551.67 |
November | 79085815.53 | 24220210.60 | 54865604.93 | 60499796.14 | 0.141461E+09 |
December | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 0.271791E+09 |
Annual Sum or Average | 0.275297E+10 | 0.148179E+10 | 0.127118E+10 | 0.303438E+10 | 0.160145E+10 |
Minimum of Months | 64857997.03 | 16494405.55 | 48363591.48 | 16131636.48 | 56097522.02 |
Maximum of Months | 0.411403E+09 | 0.245148E+09 | 0.167233E+09 | 0.495441E+09 | 0.289179E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.97 | 661.03 | 188.01 | 63.02 | 125.00 | 0.00 | 0.00 |
February | 179.34 | 512.46 | 300.66 | 110.23 | 190.43 | 0.00 | 0.00 |
March | 295.98 | 382.77 | 390.13 | 162.26 | 227.88 | 0.00 | 0.00 |
April | 492.50 | 214.78 | 499.91 | 205.09 | 294.82 | 0.00 | 0.00 |
May | 723.43 | 122.74 | 632.33 | 244.49 | 387.84 | 0.00 | 0.00 |
June | 749.29 | 98.78 | 629.94 | 223.66 | 406.28 | 0.00 | 0.00 |
July | 782.37 | 112.65 | 656.37 | 250.85 | 405.52 | 0.00 | 0.00 |
August | 613.25 | 128.25 | 529.43 | 192.06 | 337.37 | 0.00 | 0.00 |
September | 436.13 | 170.86 | 413.97 | 147.24 | 266.73 | 0.00 | 0.00 |
October | 231.42 | 226.16 | 267.33 | 83.61 | 183.72 | 0.00 | 0.00 |
November | 83.08 | 364.59 | 166.29 | 43.37 | 122.92 | 0.00 | 0.00 |
December | 31.02 | 638.23 | 145.15 | 39.16 | 105.99 | 0.00 | 0.00 |
Annual Sum or Average | 390.99 | 302.04 | 402.17 | 147.31 | 254.87 | 0.00 | 0.00 |
Minimum of Months | 31.02 | 98.78 | 145.15 | 39.16 | 105.99 | 0.00 | 0.00 |
Maximum of Months | 782.37 | 661.03 | 656.37 | 250.85 | 406.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 663.44 | 9892.46 | 311.95 | 108.94 | 203.01 | 0.00 | 0.00 |
February | 2370.93 | 7404.65 | 552.84 | 254.38 | 298.46 | 0.00 | 0.00 |
March | 3731.71 | 4505.91 | 796.65 | 450.62 | 346.03 | 0.00 | 0.00 |
April | 5855.48 | 1928.12 | 1160.99 | 731.16 | 429.83 | 0.00 | 0.00 |
May | 7355.40 | 713.18 | 1423.93 | 799.55 | 624.38 | 0.00 | 0.00 |
June | 7516.03 | 654.16 | 1502.58 | 865.49 | 637.09 | 0.00 | 0.00 |
July | 6886.58 | 877.48 | 1536.00 | 915.28 | 620.72 | 0.00 | 0.00 |
August | 5300.98 | 854.73 | 1223.90 | 690.38 | 533.51 | 0.00 | 0.00 |
September | 4055.03 | 1011.07 | 889.33 | 460.40 | 428.93 | 0.00 | 0.00 |
October | 2217.19 | 1590.00 | 510.93 | 195.14 | 315.79 | 0.00 | 0.00 |
November | 1129.26 | 3764.71 | 305.12 | 93.44 | 211.67 | 0.00 | 0.00 |
December | 342.55 | 9429.02 | 242.15 | 61.58 | 180.57 | 0.00 | 0.00 |
Annual Sum or Average | 3957.52 | 3539.23 | 872.96 | 469.87 | 403.09 | 0.00 | 0.00 |
Minimum of Months | 342.55 | 654.16 | 242.15 | 61.58 | 180.57 | 0.00 | 0.00 |
Maximum of Months | 7516.03 | 9892.46 | 1536.00 | 915.28 | 637.09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160620E+09 | 0.177051E+10 | 0.503569E+09 | 0.168780E+09 | 0.334789E+09 | 0.00 | 0.00 |
February | 0.433854E+09 | 0.123974E+10 | 0.727361E+09 | 0.266662E+09 | 0.460699E+09 | 0.00 | 0.00 |
March | 0.792765E+09 | 0.102522E+10 | 0.104494E+10 | 0.434592E+09 | 0.610343E+09 | 0.00 | 0.00 |
April | 0.127657E+10 | 0.556717E+09 | 0.129577E+10 | 0.531597E+09 | 0.764175E+09 | 0.00 | 0.00 |
May | 0.193765E+10 | 0.328739E+09 | 0.169364E+10 | 0.654852E+09 | 0.103879E+10 | 0.00 | 0.00 |
June | 0.194216E+10 | 0.256037E+09 | 0.163281E+10 | 0.579739E+09 | 0.105307E+10 | 0.00 | 0.00 |
July | 0.209549E+10 | 0.301734E+09 | 0.175803E+10 | 0.671885E+09 | 0.108615E+10 | 0.00 | 0.00 |
August | 0.164253E+10 | 0.343494E+09 | 0.141802E+10 | 0.514423E+09 | 0.903601E+09 | 0.00 | 0.00 |
September | 0.113045E+10 | 0.442859E+09 | 0.107300E+10 | 0.381643E+09 | 0.691357E+09 | 0.00 | 0.00 |
October | 0.619844E+09 | 0.605755E+09 | 0.716006E+09 | 0.223937E+09 | 0.492069E+09 | 0.00 | 0.00 |
November | 0.215350E+09 | 0.945010E+09 | 0.431034E+09 | 0.112425E+09 | 0.318609E+09 | 0.00 | 0.00 |
December | 83097050.14 | 0.170944E+10 | 0.388780E+09 | 0.104890E+09 | 0.283890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123304E+11 | 0.952526E+10 | 0.126830E+11 | 0.464542E+10 | 0.803754E+10 | 0.00 | 0.00 |
Minimum of Months | 83097050.14 | 0.256037E+09 | 0.388780E+09 | 0.104890E+09 | 0.283890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.209549E+10 | 0.177051E+10 | 0.175803E+10 | 0.671885E+09 | 0.108615E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177695E+10 | 0.264960E+11 | 0.835526E+09 | 0.291791E+09 | 0.543735E+09 | 0.00 | 0.00 |
February | 0.573575E+10 | 0.179133E+11 | 0.133743E+10 | 0.615386E+09 | 0.722040E+09 | 0.00 | 0.00 |
March | 0.999500E+10 | 0.120686E+11 | 0.213374E+10 | 0.120694E+10 | 0.926799E+09 | 0.00 | 0.00 |
April | 0.151774E+11 | 0.499768E+10 | 0.300928E+10 | 0.189517E+10 | 0.111411E+10 | 0.00 | 0.00 |
May | 0.197007E+11 | 0.191019E+10 | 0.381386E+10 | 0.214153E+10 | 0.167233E+10 | 0.00 | 0.00 |
June | 0.194815E+11 | 0.169560E+10 | 0.389469E+10 | 0.224334E+10 | 0.165134E+10 | 0.00 | 0.00 |
July | 0.184450E+11 | 0.235024E+10 | 0.411403E+10 | 0.245148E+10 | 0.166255E+10 | 0.00 | 0.00 |
August | 0.141981E+11 | 0.228930E+10 | 0.327809E+10 | 0.184913E+10 | 0.142897E+10 | 0.00 | 0.00 |
September | 0.105106E+11 | 0.262069E+10 | 0.230515E+10 | 0.119336E+10 | 0.111180E+10 | 0.00 | 0.00 |
October | 0.593852E+10 | 0.425865E+10 | 0.136848E+10 | 0.522659E+09 | 0.845821E+09 | 0.00 | 0.00 |
November | 0.292704E+10 | 0.975814E+10 | 0.790858E+09 | 0.242202E+09 | 0.548656E+09 | 0.00 | 0.00 |
December | 0.917495E+09 | 0.252547E+11 | 0.648580E+09 | 0.164944E+09 | 0.483636E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.124804E+12 | 0.111613E+12 | 0.275297E+11 | 0.148179E+11 | 0.127118E+11 | 0.00 | 0.00 |
Minimum of Months | 0.917495E+09 | 0.169560E+10 | 0.648580E+09 | 0.164944E+09 | 0.483636E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197007E+11 | 0.264960E+11 | 0.411403E+10 | 0.245148E+10 | 0.167233E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.110858E+10 | -0.102007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88512289.3 | 58.99 | 0.00 | 0.00 |
February | 0.103811E+10 | -958353455.6 | 0.00 | 0.00 | 672.00 | 0.00 | -79758650.7 | 59.00 | 0.00 | 0.00 |
March | 0.120355E+10 | -0.111573E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87816719.2 | 59.00 | 0.00 | 0.00 |
April | 0.108918E+10 | -0.100534E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83842319.0 | 58.99 | 0.00 | 0.00 |
May | 0.107275E+10 | -993228018.5 | 0.00 | 0.00 | 744.00 | 0.00 | -79524193.5 | 58.99 | 0.00 | 0.00 |
June | 0.100320E+10 | -930606748.5 | 0.00 | 0.00 | 720.00 | 0.00 | -72588885.6 | 58.99 | 0.00 | 0.00 |
July | 0.923508E+09 | -852033467.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71474418.5 | 58.99 | 0.00 | 0.00 |
August | 0.961799E+09 | -888790568.1 | 0.00 | 0.00 | 744.00 | 0.00 | -73008166.1 | 58.99 | 0.00 | 0.00 |
September | 0.905931E+09 | -830480148.4 | 0.00 | 0.00 | 720.00 | 0.00 | -75451113.8 | 58.99 | 0.00 | 0.00 |
October | 0.950571E+09 | -864899289.3 | 0.00 | 0.00 | 744.00 | 0.00 | -85671218.6 | 58.99 | 0.00 | 0.00 |
November | 0.964667E+09 | -879476409.9 | 0.00 | 0.00 | 720.00 | 0.00 | -85190972.5 | 58.99 | 0.00 | 0.00 |
December | 0.105995E+10 | -971527750.5 | 0.00 | 0.00 | 744.00 | 0.00 | -88418651.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.122818E+11 | -0.113105E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -971257598.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.905931E+09 | -0.111573E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88512289.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.120355E+10 | -830480148.4 | 0.00 | 0.00 | 744.00 | 0.00 | -71474418.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.95 | 0.88 | 08-JAN-11:09 | 124.63 | 8.94 | 0.00 | 45.50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.94 | 0.88 | 02-FEB-10:00 | 155.16 | 10.22 | 0.00 | 74.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.94 | 0.88 | 02-MAR-10:39 | 167.91 | 10.50 | 0.00 | 112.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.93 | 0.88 | 01-APR-10:39 | 197.93 | 11.03 | 0.00 | 158.67 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.91 | 0.88 | 01-MAY-11:20 | 967.09 | 12.57 | 0.00 | 271.67 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.91 | 0.88 | 01-JUN-07:49 | 406.70 | 12.90 | 1.83 | 284.83 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.91 | 0.88 | 01-JUL-07:49 | 1053.52 | 14.06 | 27.67 | 291.50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.91 | 0.88 | 01-AUG-07:49 | 284.79 | 12.71 | 0.00 | 247.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.92 | 0.88 | 01-SEP-14:30 | 213.22 | 11.58 | 0.00 | 161.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.93 | 0.88 | 01-OCT-09:20 | 173.99 | 10.58 | 0.00 | 110.83 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.95 | 0.88 | 01-NOV-09:39 | 130.29 | 9.33 | 0.00 | 39.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.95 | 0.88 | 01-DEC-11:30 | 120.81 | 8.84 | 0.00 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.93 | 390.16 | 11.43 | 29.50 | 1819.83 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.33 | 0.91 | 0.88 | 120.81 | 8.84 | 0.00 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.95 | 0.88 | 1053.52 | 14.06 | 27.67 | 291.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.90 | 0.82 | 31-JAN-15:09 | 277.14 | 23.21 | 135.50 | 20.00 | 113.11 | 20.87 | 109.17 | 0.00 |
February | 265.33 | 0.88 | 0.80 | 06-FEB-15:30 | 560.82 | 25.23 | 172.17 | 68.00 | 155.64 | 21.97 | 163.83 | 2.33 |
March | 254.17 | 0.87 | 0.80 | 02-MAR-14:30 | 580.37 | 24.67 | 181.83 | 89.50 | 491.40 | 25.32 | 205.00 | 47.33 |
April | 296.33 | 0.87 | 0.80 | 01-APR-12:30 | 419.21 | 22.72 | 197.33 | 107.17 | 451.96 | 23.97 | 242.00 | 71.83 |
May | 437.50 | 0.85 | 0.80 | 01-MAY-14:30 | 353.96 | 22.09 | 263.50 | 187.00 | 473.32 | 23.18 | 310.33 | 96.33 |
June | 401.83 | 0.85 | 0.80 | 01-JUN-14:50 | 385.65 | 22.29 | 258.17 | 182.83 | 468.66 | 23.49 | 321.50 | 100.83 |
July | 409.17 | 0.85 | 0.80 | 01-JUL-13:30 | 401.62 | 22.62 | 259.83 | 198.50 | 546.12 | 23.77 | 334.00 | 118.50 |
August | 352.83 | 0.85 | 0.80 | 01-AUG-13:30 | 395.93 | 22.90 | 231.50 | 159.67 | 448.21 | 23.84 | 286.00 | 94.83 |
September | 344.17 | 0.87 | 0.80 | 01-SEP-14:20 | 503.05 | 23.99 | 213.83 | 113.50 | 426.54 | 24.45 | 240.50 | 57.67 |
October | 299.00 | 0.89 | 0.80 | 01-OCT-13:00 | 357.04 | 23.46 | 172.67 | 55.17 | 151.45 | 22.14 | 172.67 | 6.00 |
November | 255.50 | 0.91 | 0.82 | 09-NOV-14:39 | 203.50 | 21.57 | 111.33 | 10.67 | 103.43 | 20.39 | 103.67 | 0.00 |
December | 226.33 | 0.92 | 0.83 | 16-DEC-14:30 | 176.08 | 20.36 | 87.33 | 0.00 | 97.80 | 20.40 | 84.17 | 0.00 |
Annual Sum or Average | 3785.50 | 0.87 | 389.26 | 22.90 | 2285.00 | 1192.00 | 355.38 | 22.99 | 2572.83 | 595.67 | ||
Minimum of Months | 226.33 | 0.85 | 0.80 | 176.08 | 20.36 | 87.33 | 0.00 | 97.80 | 20.39 | 84.17 | 0.00 | |
Maximum of Months | 437.50 | 0.92 | 0.83 | 580.37 | 25.23 | 263.50 | 198.50 | 546.12 | 25.32 | 334.00 | 118.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170819E+11 | 29292.25 | 01-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127346E+11 | 29292.25 | 01-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108444E+11 | 29292.25 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484721E+10 | 29292.25 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.685771E+09 | 29292.25 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4767931.06 | 10056.61 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318073E+09 | 29292.25 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330444E+10 | 29292.25 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.760355E+10 | 29292.25 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153787E+11 | 29292.25 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.728035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170819E+11 | 29292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.612499E+11 | 76550.33 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444740E+11 | 76550.33 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329294E+11 | 76550.33 | 01-MAR-18:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124114E+11 | 76550.33 | 01-APR-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.383230E+09 | 47655.83 | 01-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.658006E+10 | 64943.63 | 31-OCT-21:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262022E+11 | 76550.33 | 07-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.576638E+11 | 76550.33 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.612499E+11 | 76550.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199353E+12 | 147298.80 | 03-JAN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148281E+12 | 147298.80 | 01-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938870E+11 | 123294.39 | 15-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263041E+11 | 77221.96 | 04-APR-18:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145411E+09 | 12477.84 | 01-MAY-03:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307788E+10 | 37336.01 | 31-OCT-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.749241E+11 | 104209.84 | 25-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189246E+12 | 147298.80 | 16-DEC-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199353E+12 | 147298.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.999631E+09 | 0.884018E+09 | 18200.81 | 27-MAY-07:02 | 14052.17 | 0.00 |
June | 0.00 | 0.00 | 0.331478E+10 | 0.255966E+10 | 22641.82 | 30-JUN-06:02 | 12888.37 | 0.00 |
July | 0.00 | 0.00 | 0.587375E+10 | 0.440845E+10 | 21859.53 | 22-JUL-07:02 | 10753.41 | 0.00 |
August | 0.00 | 0.00 | 0.376081E+10 | 0.277016E+10 | 20746.28 | 30-AUG-07:03 | 10071.49 | 0.00 |
September | 0.00 | 0.00 | 0.398904E+09 | 0.339465E+09 | 17348.72 | 02-SEP-07:02 | 12649.59 | 0.00 |
October | 0.00 | 0.00 | 190.52 | 190.52 | 0.15 | 21-OCT-14:20 | 0.15 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143479E+11 | 0.109618E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.587375E+10 | 0.440845E+10 | 22641.82 | 14052.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 28723662.02 | 20418449.85 | 3841.48 | 25-MAY-16:00 | 2746.86 | 0.00 |
June | 0.00 | 0.00 | 0.268969E+10 | 0.174802E+10 | 50516.85 | 28-JUN-19:05 | 31951.17 | 0.00 |
July | 0.00 | 0.00 | 0.506197E+10 | 0.327860E+10 | 54659.69 | 23-JUL-09:35 | 26210.52 | 0.00 |
August | 0.00 | 0.00 | 0.152841E+10 | 0.973298E+09 | 50589.38 | 09-AUG-17:23 | 32040.63 | 0.00 |
September | 0.00 | 0.00 | 0.140542E+09 | 0.101983E+09 | 9565.70 | 01-SEP-15:00 | 7300.61 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.944934E+10 | 0.612233E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.506197E+10 | 0.327860E+10 | 54659.69 | 32040.63 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.928060E+09 | 0.08 | 348.92 | 01-JAN-00:01 | 0.08 |
February | 0.815219E+09 | 0.08 | 348.92 | 01-FEB-00:02 | 0.08 |
March | 0.831866E+09 | 0.07 | 348.92 | 01-MAR-00:03 | 0.08 |
April | 0.378893E+09 | 0.03 | 348.92 | 01-APR-00:10 | 0.08 |
May | 7501802.08 | 0.00 | 348.92 | 01-MAY-00:20 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.134300E+09 | 0.01 | 348.92 | 12-OCT-01:55 | 0.08 |
November | 0.760850E+09 | 0.07 | 348.92 | 01-NOV-00:10 | 0.08 |
December | 0.932247E+09 | 0.08 | 348.92 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.478894E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.932247E+09 | 0.08 | 348.92 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132125E+10 | 0.76 | 1154.74 | 02-JAN-13:20 | 0.95 |
February | 0.117882E+10 | 0.71 | 1154.74 | 01-FEB-07:15 | 0.95 |
March | 0.130782E+10 | 0.59 | 1154.74 | 01-MAR-10:00 | 0.95 |
April | 0.116929E+10 | 0.44 | 1154.74 | 01-APR-06:50 | 0.95 |
May | 0.119091E+10 | 0.37 | 1154.74 | 01-MAY-12:50 | 0.95 |
June | 0.118892E+10 | 0.37 | 1154.74 | 02-JUN-06:30 | 0.95 |
July | 0.114319E+10 | 0.35 | 1154.74 | 05-JUL-09:50 | 0.93 |
August | 0.123465E+10 | 0.37 | 1154.74 | 01-AUG-11:00 | 0.94 |
September | 0.114319E+10 | 0.36 | 1154.74 | 02-SEP-06:20 | 0.94 |
October | 0.114970E+10 | 0.36 | 1154.74 | 02-OCT-06:50 | 0.94 |
November | 0.115251E+10 | 0.52 | 1154.74 | 01-NOV-08:40 | 0.94 |
December | 0.131150E+10 | 0.73 | 1154.74 | 01-DEC-07:17 | 0.95 |
Annual Sum or Average | 0.144918E+11 | 0.49 | |||
Minimum of Months | 0.114319E+10 | 0.35 | 1154.74 | 0.93 | |
Maximum of Months | 0.132125E+10 | 0.76 | 1154.74 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209564E+10 | 0.68 | 1992.72 | 01-JAN-00:04 | 0.92 |
February | 0.168782E+10 | 0.65 | 1992.72 | 01-FEB-00:02 | 0.92 |
March | 0.156223E+10 | 0.60 | 1992.72 | 01-MAR-18:42 | 0.92 |
April | 0.107299E+10 | 0.45 | 1992.72 | 01-APR-19:03 | 0.92 |
May | 0.829982E+09 | 0.22 | 1247.89 | 01-MAY-06:02 | 0.73 |
June | 0.831816E+09 | 0.22 | 1992.72 | 29-JUN-17:08 | 0.90 |
July | 0.808307E+09 | 0.21 | 1992.72 | 24-JUL-17:08 | 0.91 |
August | 0.852788E+09 | 0.22 | 1508.27 | 08-AUG-17:25 | 0.79 |
September | 0.789115E+09 | 0.21 | 797.09 | 01-SEP-16:40 | 0.55 |
October | 0.941242E+09 | 0.38 | 1690.58 | 31-OCT-21:03 | 0.92 |
November | 0.134500E+10 | 0.59 | 1992.72 | 07-NOV-04:03 | 0.92 |
December | 0.203500E+10 | 0.67 | 1992.72 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.148519E+11 | 0.42 | |||
Minimum of Months | 0.789115E+09 | 0.21 | 797.09 | 0.55 | |
Maximum of Months | 0.209564E+10 | 0.68 | 1992.72 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132125E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117882E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.130782E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116929E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.140351E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.188011E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.232461E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.199426E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.122502E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114970E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115251E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131150E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174184E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232461E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.209564E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168782E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.156223E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107299E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.837771E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.149849E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204517E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.123311E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.824309E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.941242E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.134500E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.203500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171788E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.824309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.209564E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132125E+10 | 0.00 | 0.170819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117882E+10 | 0.00 | 0.127346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130782E+10 | 0.00 | 0.108444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116929E+10 | 0.00 | 0.484721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119091E+10 | 0.999631E+09 | 0.685771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118892E+10 | 0.331478E+10 | 4767931.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114319E+10 | 0.587375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123465E+10 | 0.376081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114319E+10 | 0.398904E+09 | 0.318073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114970E+10 | 190.52 | 0.330444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115251E+10 | 0.00 | 0.760355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131150E+10 | 0.00 | 0.153787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144918E+11 | 0.143479E+11 | 0.728035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132125E+10 | 0.587375E+10 | 0.170819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.209564E+10 | 0.00 | 0.612499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168782E+10 | 0.00 | 0.444740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156223E+10 | 0.00 | 0.329294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107299E+10 | 0.00 | 0.124114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.829982E+09 | 28723662.02 | 0.383230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.831816E+09 | 0.267720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808307E+09 | 0.498423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.852788E+09 | 0.152497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.789115E+09 | 0.140542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941242E+09 | 0.00 | 0.658006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134500E+10 | 0.00 | 0.262022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203500E+10 | 0.00 | 0.576638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148519E+11 | 0.935567E+10 | 0.241894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.789115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209564E+10 | 0.498423E+10 | 0.612499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119091E+10 | 0.00 | 0.00 | 0.00 | 0.212595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118892E+10 | 0.00 | 0.00 | 0.00 | 0.691192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114319E+10 | 0.00 | 0.00 | 0.00 | 0.118141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123465E+10 | 0.00 | 0.00 | 0.00 | 0.759608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114319E+10 | 0.00 | 0.00 | 0.00 | 81827245.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114970E+10 | 0.00 | 0.00 | 0.00 | 42.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144918E+11 | 0.00 | 0.00 | 0.00 | 0.292663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132125E+10 | 0.00 | 0.00 | 0.00 | 0.118141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.209564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.829982E+09 | 0.00 | 0.00 | 0.00 | 7788890.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.831816E+09 | 0.00 | 0.00 | 0.00 | 0.666678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808307E+09 | 0.00 | 0.00 | 0.00 | 0.123687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.852788E+09 | 0.00 | 0.00 | 0.00 | 0.380324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.789115E+09 | 0.00 | 0.00 | 0.00 | 35193309.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148519E+11 | 0.00 | 0.00 | 0.00 | 0.232685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.789115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209564E+10 | 0.00 | 0.00 | 0.00 | 0.123687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1096854.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421701E+10 | 0.00 | 0.00 | 0.12 |
February | 884397.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321878E+10 | 0.00 | 0.00 | 0.13 |
March | 2796731.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312145E+10 | 0.00 | 0.00 | 0.13 |
April | 0.154296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163188E+10 | 0.00 | 0.00 | 0.13 |
May | 0.489123E+09 | 35830242.21 | 0.00 | 891331.13 | 0.00 | 0.229434E+09 | 0.645385E+09 | 0.00 | 0.27 |
June | 0.110287E+09 | 0.333648E+09 | 0.00 | 2597072.57 | 0.00 | 656795.05 | 0.162069E+10 | 0.00 | 0.55 |
July | 4980576.46 | 0.597737E+09 | 0.00 | 4016610.46 | 0.00 | 0.00 | 0.148630E+10 | 0.00 | 0.54 |
August | 38505650.54 | 0.255393E+09 | 0.00 | 4378933.16 | 0.00 | 0.00 | 0.229564E+10 | 0.00 | 0.66 |
September | 0.595973E+09 | 8686190.38 | 0.00 | 1599133.73 | 0.00 | 0.105598E+09 | 0.146347E+10 | 0.00 | 0.34 |
October | 0.313260E+09 | 0.00 | 0.00 | 2487.44 | 0.00 | 0.137860E+10 | 16209516.98 | 0.00 | 0.13 |
November | 13853855.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230579E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390275E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.172506E+10 | 0.123129E+10 | 0.00 | 13485568.48 | 0.00 | 0.201120E+11 | 0.752769E+10 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.595973E+09 | 0.597737E+09 | 0.00 | 4378933.16 | 0.00 | 0.421701E+10 | 0.229564E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76470647.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145403E+11 | 0.00 | 0.00 | 0.17 |
February | 0.760829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991885E+10 | 0.00 | 0.00 | 0.17 |
March | 0.226409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756315E+10 | 0.00 | 0.00 | 0.19 |
April | 0.308211E+10 | 0.00 | 0.00 | 0.00 | 777974.92 | 0.176559E+10 | 0.00 | 0.00 | 0.18 |
May | 0.275980E+10 | 0.00 | 0.00 | 4250.05 | 22963243.85 | 11172208.03 | 860487.60 | 0.00 | 0.18 |
June | 0.228012E+10 | 0.518191E+09 | 0.00 | 357800.78 | 98646.13 | 0.00 | 0.194311E+09 | 0.00 | 0.21 |
July | 0.118657E+10 | 0.591551E+09 | 0.00 | 2603917.71 | 0.00 | 0.00 | 0.155342E+10 | 0.00 | 0.25 |
August | 0.261925E+10 | 0.132335E+09 | 0.00 | 1318197.55 | 0.00 | 0.00 | 0.935464E+09 | 0.00 | 0.24 |
September | 0.379921E+10 | 0.00 | 0.00 | 220800.08 | 0.00 | 0.00 | 93902722.06 | 0.00 | 0.19 |
October | 0.375729E+10 | 0.00 | 0.00 | 0.00 | 1938927.76 | 0.759084E+09 | 0.00 | 0.00 | 0.17 |
November | 0.194694E+10 | 0.00 | 0.00 | 0.00 | 47884.95 | 0.493014E+10 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132782E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.245327E+11 | 0.124208E+10 | 0.00 | 4504966.18 | 25826677.61 | 0.527665E+11 | 0.277796E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.379921E+10 | 0.591551E+09 | 0.00 | 2603917.71 | 22963243.85 | 0.145403E+11 | 0.155342E+10 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.236843E+12 | 0.176448E+12 | 0.00 | 0.188349E+11 | 0.811669E+11 |
February | 0.423803E+12 | 0.143008E+12 | 0.00 | 0.138993E+11 | 0.607659E+11 |
March | 0.649127E+12 | 0.980408E+11 | 0.00 | 0.129515E+11 | 0.426438E+11 |
April | 0.851312E+12 | 0.545171E+11 | 0.00 | 0.663311E+10 | 0.145231E+11 |
May | 0.103542E+13 | 0.210405E+11 | 0.00 | 0.407787E+10 | 0.179631E+10 |
June | 0.106367E+13 | 0.185346E+11 | 0.00 | 0.335708E+10 | 0.736474E+10 |
July | 0.110253E+13 | 0.287402E+11 | 0.00 | 0.304861E+10 | 0.133540E+11 |
August | 0.918169E+12 | 0.341590E+11 | 0.00 | 0.550684E+10 | 0.642916E+10 |
September | 0.657673E+12 | 0.436471E+11 | 0.00 | 0.605129E+10 | 0.813957E+09 |
October | 0.338407E+12 | 0.415598E+11 | 0.00 | 0.622250E+10 | 0.555273E+10 |
November | 0.140412E+12 | 0.900444E+11 | 0.00 | 0.919667E+10 | 0.337905E+11 |
December | 0.136558E+12 | 0.173461E+12 | 0.00 | 0.171809E+11 | 0.769802E+11 |
Annual Sum or Average | 0.755392E+13 | 0.923200E+12 | 0.00 | 0.106961E+12 | 0.345181E+12 |
Minimum of Months | 0.136558E+12 | 0.185346E+11 | 0.00 | 0.304861E+10 | 0.813957E+09 |
Maximum of Months | 0.110253E+13 | 0.176448E+12 | 0.00 | 0.188349E+11 | 0.811669E+11 |