Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 10:43:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 704.03 | 145.61 | 145.61 |
Net Site Energy | 704.03 | 145.61 | 145.61 |
Total Source Energy | 1998.30 | 413.29 | 413.29 |
Net Source Energy | 1998.30 | 413.29 | 413.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 111.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 262.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 592.96 | 111.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 111.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 262.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 109.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 49.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 111.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 262.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 109.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 49.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.78 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 122.64 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.78 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 122.64 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 592.958 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 592.958 | 100.00 |
Total On-Site and Utility Electric Sources | 592.958 | 100.00 |
Total Electricity End Uses | 592.958 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 7.67 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2589.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 96.62 |
Skylight-Roof Ratio [%] | 2.10 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.6485 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 12.8090 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.4896 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 7.7537 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.6485 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 12.8090 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.4896 | 46.45 | 2.5587 | |
Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 7.7537 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 7.7537 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-JAN-16:49 | 19-FEB-06:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 106254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4162.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1615.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 50687.23 | 106254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 106254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4162.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1615.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 832.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 347.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 81.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1877.90 | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 172.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 388.39 | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 172.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 388.39 | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.05 |
ZONE2 FINE STORAGE DIRECT AIR | 2.65 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.83 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.83 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 73939.70 |
PSZ-OFFICE HEATING COIL | 26820.50 |
PSZ-FINE STORAGE HEATING COIL | 87174.47 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 73939.71 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-FINE STORAGE | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 1.00 | 1.00 | 2.65 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.05 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.65 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.05 | 1160.52 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.65 | 2832.01 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17433.86 | 26820.50 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.65 | 2.65 | 2.65 | 2.65 | 53676.64 | 87174.47 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.05 | 0.524097 | 1.05 | 17433.86 | 8974.95 | 17433.86 | 0.800920 | 0.800920 |
PSZ-FINE STORAGE COOLING COIL | 2.65 | 1.32 | 2.65 | 53676.64 | 26620.77 | 53676.64 | 0.771080 | 0.771080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_11 | FINESTORAGE_SKYLIGHT_17 | FINESTORAGE_SKYLIGHT_16 | FINESTORAGE_SKYLIGHT_15 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_8 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C6 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C6 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C6 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C6 | SKYLIGHT_R3C1 | SKYLIGHT_R4C6 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C6 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C6 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C6 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | SKYLIGHT_R2_C4 | SKYLIGHT_R4_C4 | SKYLIGHT_R6_C4 | SKYLIGHT_R7_C4 | SKYLIGHT_R8_C4 | SKYLIGHT_R3_C4 | SKYLIGHT_R1_C4 | SKYLIGHT_R5_C4 | SKYLIGHT_R4_C5 | SKYLIGHT_R7_C5 | SKYLIGHT_R2_C5 | SKYLIGHT_R1C5 | SKYLIGHT_R6_C5 | SKYLIGHT_R5_C5 | SKYLIGHT_R3_C5 | SKYLIGHT_R8_C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 121 | 97 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 25.27 | 11 | 23 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 71.35 | 6 | 68 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.649 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 16.722 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 12.809 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.809 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.490 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.048 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2048.656 | 8.649 | 160.695 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2048.656 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 17848.242 | 12.809 | 594.941 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17848.242 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 17593.267 | 5.490 | 254.975 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 17593.267 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3818_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3818_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE2 FINE STORAGE | 17 | 0 |
2 | ZONE3 BULK STORAGE | 48 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE2 FINE STORAGE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4950E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3081E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2947E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7457E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2795E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1357E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5725E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2024E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8077E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5294E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3215E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2139E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6359E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5254E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7630E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3734E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9357E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0039E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9460E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.4229E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8089E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0295E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2192E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2547E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3372E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1236E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1137E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1644E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1473E-004 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0345E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8630E-004 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_17 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2390E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3181E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5487E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2035E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8155E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9353E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1277E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2190E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_16 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.7788E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9233E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5838E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9262E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.7352E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0476E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5695E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4614E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_15 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5876E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2738E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0711E-004 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5197E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1492E-004 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4838E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9506E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8040E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6552E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1907E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5042E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3980E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6935E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5218E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0203E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7107E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9791E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1085E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6893E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9264E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1925E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5414E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3823E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3923E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9374E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5879E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4392E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8939E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6223E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2445E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5366E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4880E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3401E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0032E-003 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7834E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9952E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9946E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6741E-003 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2482E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0518E-003 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7636E-005 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9942E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2323E-004 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0209E-003 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3343E-004 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3325E-003 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8387E-005 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3049E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9336E-005 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2810E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8002E-005 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9931E-004 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0291E-004 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5309E-004 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8345E-005 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9122E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6407E-005 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5936E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1002E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9157E-004 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3232E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3038E-004 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6594E-004 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2547E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9447E-004 |
113 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6619E-004 |
114 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0143E-003 |
115 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4176E-004 |
116 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2658E-003 |
117 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3782E-004 |
118 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0577E-003 |
119 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7668E-004 |
120 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
121 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0706E-004 |
122 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2874E-003 |
123 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7188E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1719E-003 |
125 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6641E-005 |
126 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6835E-003 |
127 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0951E-004 |
128 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8074E-003 |
129 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0290E-004 |
130 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0543E-003 |
131 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4161E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6945E-004 |
133 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4756E-005 |
134 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7430E-003 |
135 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0605E-004 |
136 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9054E-003 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6405E-005 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7000E-005 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8423E-005 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0873E-005 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7808E-005 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4306E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6185E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6959E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2010E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8163E-005 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7214E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7192E-005 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1558E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5064E-005 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1584E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7968E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0386E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6577E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8894E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5914E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2405E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9878E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4307E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1795E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4592E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1086E-004 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1047E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3935E-004 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9663E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4533E-004 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2821E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8769E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2086E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3547E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2843E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6076E-004 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0333E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3350E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6655E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8382E-005 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4035E-005 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7230E-005 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3411E-005 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6718E-005 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6275E-005 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0613E-005 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4335E-005 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1799E-005 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8606E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2408E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6406E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4866E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0243E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5657E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2799E-005 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6059E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7051E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0245E-003 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7530E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2372E-003 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7304E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2740E-004 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0480E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5884E-004 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6503E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4211E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7273E-004 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7685E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9598E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9948E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2530E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5333E-004 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2721E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0093E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5513E-004 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0096E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1022E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0332E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2517E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1866E-005 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5584E-005 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7424E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4529E-005 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6839E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8555E-005 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0863E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5878E-005 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1998E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2032E-003 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1653E-004 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3203E-003 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1161E-004 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3272E-003 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3699E-004 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8906E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8192E-005 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1307E-003 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9547E-004 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2267E-003 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0826E-004 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2945E-003 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1268E-004 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8993E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7853E-004 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6563E-005 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7526E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5047E-005 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6876E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0305E-005 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1007E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7501E-005 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2167E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2245E-004 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7689E-003 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1556E-004 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0008E-003 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8328E-004 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7878E-003 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8998E-004 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0464E-003 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6642E-005 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7515E-005 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4770E-005 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6818E-005 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0670E-005 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0996E-005 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8593E-005 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2267E-005 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3685E-003 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1988E-004 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3059E-003 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0995E-004 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1897E-003 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5317E-004 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4290E-003 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2387E-004 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3250E-003 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4009E-004 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2544E-003 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9958E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1426E-003 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6693E-004 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4336E-003 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8358E-004 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4067E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0721E-003 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1802E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0119E-003 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5381E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2503E-003 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9973E-004 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9789E-003 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5756E-005 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7390E-005 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3729E-005 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6669E-005 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9338E-005 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0826E-005 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8581E-005 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2266E-005 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0584E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2288E-003 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7777E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0392E-003 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8114E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8575E-003 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9808E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9042E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8344E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0790E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4975E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6171E-005 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3675E-003 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3225E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2353E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7884E-004 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0864E-004 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4315E-004 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4986E-004 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3430E-003 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2479E-004 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3967E-003 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7649E-004 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4616E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9603E-004 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2349E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9616E-004 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5857E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3632E-004 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8769E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0145E-003 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0759E-004 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4007E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2755E-004 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9814E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4553E-004 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7331E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6870E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7146E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1661E-005 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4640E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7029E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9750E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1920E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1545E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1563E-005 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5833E-005 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4150E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7170E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2175E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6449E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6921E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0539E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7470E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2165E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6106E-005 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9859E-004 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1890E-005 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5863E-004 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6965E-005 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6273E-004 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0361E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5245E-004 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7851E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3046E-004 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4365E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0810E-004 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4801E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1577E-004 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2022E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5076E-004 |
369 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2231E-005 |
370 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6886E-005 |
371 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0462E-005 |
372 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6187E-005 |
373 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4404E-005 |
374 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0202E-005 |
375 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5844E-005 |
376 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C6 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1994E-005 |
377 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0535E-004 |
378 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7682E-005 |
379 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2668E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7385E-005 |
381 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5172E-004 |
382 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4352E-005 |
383 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6786E-004 |
384 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7579E-005 |
385 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7751E-004 |
386 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8391E-005 |
387 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4314E-004 |
388 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0906E-005 |
389 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4940E-004 |
390 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6202E-005 |
391 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2010E-004 |
392 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1431E-005 |
393 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8310E-004 |
394 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2848E-005 |
395 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9120E-004 |
396 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1589E-005 |
397 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7808E-004 |
398 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5727E-005 |
399 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0471E-004 |
400 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9420E-005 |
401 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4895E-004 |
402 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5287E-005 |
403 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2747E-004 |
404 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2362E-005 |
405 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6470E-004 |
406 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1056E-005 |
407 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9913E-004 |
408 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5683E-005 |
409 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4533E-004 |
410 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0175E-005 |
411 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2340E-004 |
412 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7089E-005 |
413 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6217E-004 |
414 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2941E-005 |
415 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8742E-004 |
416 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2973E-005 |
417 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5277E-005 |
418 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6420E-005 |
419 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1512E-005 |
420 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3777E-005 |
421 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8300E-005 |
422 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7833E-005 |
423 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0353E-004 |
424 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9347E-005 |
425 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5960E-005 |
426 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3042E-005 |
427 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8198E-005 |
428 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0944E-005 |
429 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8294E-005 |
430 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4157E-005 |
431 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6160E-005 |
432 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6261E-005 |
433 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3545E-004 |
434 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5015E-005 |
435 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3119E-004 |
436 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2833E-005 |
437 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9215E-004 |
438 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9877E-005 |
439 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8970E-004 |
440 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3044E-005 |
441 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3029E-004 |
442 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9659E-005 |
443 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4063E-004 |
444 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9171E-005 |
445 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
446 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0908E-005 |
447 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6630E-005 |
448 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6314E-005 |
449 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0770E-004 |
450 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3465E-005 |
451 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8038E-004 |
452 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0235E-005 |
453 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8901E-004 |
454 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8200E-005 |
455 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9748E-004 |
456 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5651E-005 |
457 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7116E-005 |
458 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1469E-005 |
459 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1685E-005 |
460 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0252E-005 |
461 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0053E-005 |
462 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4953E-005 |
463 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6324E-005 |
464 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4806E-005 |
465 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5168E-005 |
466 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9374E-005 |
467 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0640E-005 |
468 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8185E-005 |
469 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5125E-005 |
470 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2119E-005 |
471 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7525E-005 |
472 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3673E-005 |
473 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0046E-005 |
474 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1043E-005 |
475 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8812E-005 |
476 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0209E-005 |
477 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2925E-005 |
478 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4188E-005 |
479 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7712E-005 |
480 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3688E-005 |
481 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2060E-005 |
482 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0336E-005 |
483 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2336E-005 |
484 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9724E-005 |
485 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0738E-005 |
486 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3189E-005 |
487 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0328E-005 |
488 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2974E-005 |
489 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3999E-005 |
490 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0303E-005 |
491 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8303E-005 |
492 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9025E-005 |
493 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7647E-005 |
494 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3291E-005 |
495 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7666E-005 |
496 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4362E-005 |
497 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2373E-005 |
498 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1053E-005 |
499 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6193E-005 |
500 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9760E-005 |
501 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2188E-005 |
502 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4354E-005 |
503 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6218E-005 |
504 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4801E-005 |
505 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6062E-005 |
506 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1459E-005 |
507 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2595E-005 |
508 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0406E-005 |
509 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5331E-005 |
510 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4872E-005 |
511 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7883E-005 |
512 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4374E-005 |
513 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8032E-005 |
514 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8428E-005 |
515 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4757E-005 |
516 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7370E-005 |
517 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7393E-005 |
518 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1104E-005 |
519 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0211E-005 |
520 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8_C5 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2960E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10465.73076 | 12558.87691 | 0.87350 | 1.04819 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8459.07280 | 10150.88736 | 0.24074 | 0.28889 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 33899.58677 | 40679.50413 | 2.20552 | 2.64663 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22819.09924 | 27382.91909 | 0.54733 | 0.65680 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 61616.42454 | 73939.70945 | 1.52724 | 1.83268 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15415.86 | 1.04819 | 1.04819 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9619.62 | 0.28889 | 0.28889 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 47768.97 | 2.64663 | 2.64663 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 29157.60 | 0.65680 | 0.65680 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04819 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.64663 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.83268 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.83268 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 73939.70478 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 73939.70945 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04819 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04819 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04819 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04819 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04819 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.04819 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64663 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.64663 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.64663 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.64663 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.64663 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.64663 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.04819 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.64663 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04819 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04819 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1160.51737 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04819 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04819 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04819 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04819 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04819 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52410 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04819 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17433.86000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8974.94946 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17433.86000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80092 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80092 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17433.86000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26820.50351 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26820.50351 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.64663 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.64663 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2832.01403 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.64663 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.64663 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.64663 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.64663 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.64663 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32331 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.64663 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 53676.64000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 26620.76738 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 53676.64000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53676.64000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87174.47225 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 87174.47225 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16620.5 | 11.76 | 11.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 51621.4 | 11.66 | 10.99 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1707367506 | 0.1861139186 | Pass | Pass | 0.8049640900 | 6.5542432586 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3023879753 | 0.2821218823 | Pass | Pass | 0.7820279935 | 2.8542594850 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.1876245332E-005 | 1.4717610373E-005 | Pass | Pass | 6.3704813389E-002 | 7.0195383744E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7160.17 | 466.72 | 0.00 | 93.00 | 59.13 | 7779.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1368.14 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3133.49 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_17 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_16 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_15 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8_C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 114.28 | 3.939 | 0.573 | 0.571 | |||||||||||||||||
North Total or Average | 6.51 | 2.169 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 107.77 | 4.045 | 0.584 | 0.581 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_17 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_16 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_15 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8_C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.6485 | 236.88 | 2048.66 | LightsWired | LTG_SCH_OFFICE | 51.24 | 168.00 | 50.44 | 0.0000 | Y | 19.40 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 12.8090 | 1393.41 | 17848.24 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 40.99 | 0.0000 | Y | 137.33 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.4896 | 3204.84 | 17593.27 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 32.17 | 0.0000 | Y | 106.25 |
Interior Lighting Total | 7.7537 | 4835.13 | 37490.17 | 262.98 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17848.24 | 6603.85 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.37 | 17593.27 | 6509.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6986.42 | AstronomicalClock | - | 83.55 | 83.55 | 109.57 | |
Exterior Lighting Total | 6986.42 | 109.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17433.86 | 13963.13 | 3470.73 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 53676.64 | 41388.98 | 12287.66 | 0.77 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16620.5 | 11.76 | 11.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 51621.4 | 11.66 | 10.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 73939.70 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26820.50 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 87174.47 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.83 | 170.28 | 92.91 | 1.00 | 3.64 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1160.52 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.65 | 2832.01 | 1070.05 | 1.00 | 1.28 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10465.73 | 12558.88 | 53.02 | 0.873 | 1.048 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00831 | 28.22 | 0.00882 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33899.59 | 40679.50 | 29.19 | 2.206 | 2.647 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00839 | 29.40 | 0.00882 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 30.08 | 0.00888 | 29.40 | 0.00882 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8459.07 | 10150.89 | 42.85 | 0.241 | 0.289 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00735 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22819.10 | 27382.92 | 19.65 | 0.547 | 0.657 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00596 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 61616.42 | 73939.71 | 23.07 | 1.527 | 1.833 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00480 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.05 | 1.05 | 0.29 | 0.29 | 1.0482 | 1.0482 | 1.0482 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.65 | 2.65 | 0.66 | 0.66 | 2.6466 | 2.6466 | 2.6466 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 73939.705 | 73939.705 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 73939.70 | 73939.70 | 1.832683 | 10.00 | 6.67 | 0.00480432 | 43.33 | 21.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 10.00 | 0.00480432 | 62.3463 | 73939.71 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 17433.860 | 13963.127 | 1.048190 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 17433.86 | 16423.47 | 1.048190 | 25.25 | 16.56 | 0.00836358 | 12.00 | 11.13 | 0.00800000 | 28.36 | 0.00881983 | 18.00 | 9.7582 | 23.90 | 0.00831423 | 44.3999 | 10462.33 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26820.504 | 26820.504 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26820.50 | 26820.50 | 1.048194 | 18.55 | 12.72 | 0.00689146 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 9.7582 | 21.10 | 0.00734574 | 46.5782 | 8459.07 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 53676.640 | 41388.984 | 2.646630 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 53676.64 | 50359.43 | 2.646630 | 28.02 | 17.59 | 0.00846131 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00882150 | 18.34 | 16.0472 | 26.70 | 0.00839246 | 37.9376 | 33899.59 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 87174.472 | 87174.472 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 87174.47 | 87174.47 | 2.646625 | 12.39 | 8.54 | 0.00543639 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 16.0473 | 15.56 | 0.00596129 | 53.6431 | 22819.10 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 73939.705 | 73939.705 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.832683 | 2.17537830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 73939.70 | 73939.70 | 1.0000 | 2.17537830 | 1.832683 | 10.00 | 6.67 | 0.00480432 | 22150.7 | 43.33 | 21.98 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73939.70 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 10.00 | 0.00480432 | 10.00 | 0.00480432 | 62.3463 | 73939.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17433.860 | 13963.127 | 1.048190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3875 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.048194 | 1.24419686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 17433.86 | 16423.47 | 1.0000 | 1.24419187 | 1.048190 | 25.25 | 16.56 | 0.00836358 | 46680.0 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17433.86 | 28.36 | 0.00881983 | 18.00 | 0.10228463 | 9.7582 | 23.90 | 0.00831423 | 23.90 | 0.00831423 | 44.3999 | 10462.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26820.504 | 26820.504 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.048194 | 1.24419686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 26820.50 | 26820.50 | 1.0000 | 1.24419686 | 1.048194 | 18.55 | 12.72 | 0.00689146 | 36110.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26820.50 | -4.20 | 0.00269032 | -4.20 | 0.10228463 | 9.7582 | 21.01 | 0.00734574 | 21.10 | 0.00734574 | 46.5782 | 8459.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53676.640 | 41388.984 | 2.646630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5691 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.646625 | 3.14151967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 53676.64 | 50359.43 | 1.0000 | 3.14152542 | 2.646630 | 28.02 | 17.59 | 0.00846131 | 49752.9 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53676.64 | 29.40 | 0.00882150 | 18.34 | 0.42471127 | 16.0472 | 26.70 | 0.00839246 | 26.70 | 0.00839246 | 37.9376 | 33899.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87174.472 | 87174.472 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.646625 | 3.14151967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 87174.47 | 87174.47 | 1.0000 | 3.14151967 | 2.646625 | 12.39 | 8.54 | 0.00543639 | 26166.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87174.47 | -4.20 | 0.00269032 | -4.20 | 0.42471127 | 16.0473 | 15.56 | 0.00596129 | 15.56 | 0.00596129 | 53.6431 | 22819.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.05 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.65 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2222.33 | 2550.33 | 1476.17 |
ZONE2 FINE STORAGE | 2883.33 | 2675.33 | 2072.17 |
ZONE3 BULK STORAGE | 2904.33 | 3028.83 | 2390.17 |
Facility | 3396.83 | 3228.67 | 2589.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 9.50 | 0.00 | 6.17 | 0.00 |
ZONE2 FINE STORAGE | 82.00 | 7.33 | 2.83 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 90.17 | 7.33 | 7.67 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.808 | 0.428 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.600 | 0.226 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.137 | 0.000 | 0.051 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.30 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.05 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2907865.09 | 0.00 | 2907865.09 | 2251774.11 | 5159639.20 | 3225648.14 | 5721.06 | 1873.28 | 1165.66 | 0.00 |
ZONE2 FINE STORAGE | 6388284.48 | 0.00 | 6388284.48 | 6389014.32 | 12777298.80 | 13393694.68 | 5717.54 | 2504.25 | 538.21 | 9.87 |
ZONE3 BULK STORAGE | 0.00 | 15191358.05 | 15191358.05 | 36404708.86 | 51596066.91 | 30805497.77 | 8454.33 | 47.00 | 258.67 | 4996.00 |
Total Facility | 9296149.57 | 15191358.05 | 24487507.62 | 45045497.29 | 69533004.91 | 47424840.58 | 8605.33 | 2614.21 | 1498.99 | 4996.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2222 | 0.0000 | 0.2222 | 0.1182 | 0.3404 | 0.1023 | 597.06 | 1873.28 | 1165.66 |
ZONE2 FINE STORAGE | 0.4832 | 0.0000 | 0.4832 | 0.1829 | 0.6661 | 0.4247 | 603.25 | 2504.25 | 528.50 |
ZONE3 BULK STORAGE | 0.0000 | 0.5039 | 0.5039 | 1.3391 | 1.8431 | 0.9768 | 3471.00 | 26.83 | 138.17 |
Total Facility | 0.7054 | 0.5039 | 1.2093 | 1.6402 | 2.8496 | 1.5038 | 3481.33 | 2594.04 | 1368.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4097028.14 | 0.00 | 4097028.14 | 3225648.14 | 5717.47 | 0.17 | 3042.36 | 0.00 |
PSZ-FINE STORAGE | 9000755.02 | 0.00 | 9000755.02 | 13393694.68 | 5715.63 | 0.00 | 3044.37 | 9.87 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3130 | 0.0000 | 0.3130 | 0.1023 | 593.47 | 0.17 | 3042.36 |
PSZ-FINE STORAGE | 0.6809 | 0.0000 | 0.6809 | 0.4247 | 601.33 | 0.00 | 3034.67 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2352.36 | 693.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2714.25 | 337.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3256 | 0.5371 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.7484 | 1.3413 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 69 | 69 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 444 |
Defaulted Fields | 429 |
Fields with Defaults | 1213 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 147 |
Autocalculatable Fields | 244 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
Electricity:Building | 402.28 | 1782.47 | 20-FEB-11:40 | 41466.67 | 02-JAN-15:40 |
Electricity:Zone:ZONE1 OFFICE | 51.34 | 860.99 | 01-JAN-00:10 | 3141.26 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 402.28 | 1782.47 | 20-FEB-11:40 | 41466.67 | 02-JAN-15:40 |
InteriorLights:Electricity | 262.99 | 1208.72 | 20-FEB-11:40 | 31354.05 | 02-JAN-15:40 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 262.99 | 1208.72 | 20-FEB-11:40 | 31354.05 | 02-JAN-15:40 |
LightsWired:InteriorLights:Electricity | 262.99 | 1208.72 | 20-FEB-11:40 | 31354.05 | 02-JAN-15:40 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 19.40 | 287.24 | 01-JAN-00:10 | 1228.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 262.99 | 1208.72 | 20-FEB-11:40 | 31354.05 | 02-JAN-15:40 |
Electricity:Zone:ZONE2 FINE STORAGE | 137.33 | 464.05 | 20-FEB-11:40 | 15171.01 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 137.33 | 464.05 | 20-FEB-11:40 | 15171.01 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 137.33 | 464.05 | 20-FEB-11:40 | 15171.01 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 213.60 | 457.42 | 16-JAN-11:30 | 23154.40 | 02-JAN-15:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 106.25 | 457.42 | 16-JAN-11:30 | 14954.28 | 02-JAN-15:40 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 106.25 | 457.42 | 16-JAN-11:30 | 14954.28 | 02-JAN-15:40 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 49.53 | 0.00 | 02-JAN-18:10 | 4162.81 | 02-JAN-07:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
ElectricityPurchased:Plant | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
Cogeneration:ElectricityPurchased | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
General:Cogeneration:ElectricityPurchased | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
ElectricityNet:Plant | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
Cogeneration:ElectricityNet | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
General:Cogeneration:ElectricityNet | 592.96 | 2265.47 | 26-FEB-11:10 | 50687.23 | 18-JAN-16:50 |
Electricity:HVAC | 55.34 | 0.00 | 02-JAN-18:10 | 14670.20 | 10-AUG-15:40 |
General:Fans:Electricity | 49.53 | 0.00 | 02-JAN-18:10 | 4162.81 | 02-JAN-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.81 | 0.00 | 01-JAN-00:10 | 10677.67 | 10-AUG-15:40 |
General:Cooling:Electricity | 5.81 | 0.00 | 01-JAN-00:10 | 10677.67 | 10-AUG-15:40 |
ExteriorLights:Electricity | 109.57 | 0.00 | 01-JAN-08:10 | 6986.42 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 109.57 | 0.00 | 01-JAN-08:10 | 6986.42 | 01-JAN-00:10 |
Electricity:Plant | 25.77 | 483.00 | 22-JUN-17:20 | 2336.30 | 13-FEB-12:40 |
WaterSystems:Electricity | 25.77 | 483.00 | 22-JUN-17:20 | 2336.30 | 13-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 25.77 | 483.00 | 22-JUN-17:20 | 2336.30 | 13-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 111.07 | 0.00 | 02-JAN-18:10 | 106254.04 | 19-FEB-06:50 |
NaturalGas:HVAC | 111.07 | 0.00 | 02-JAN-18:10 | 106254.04 | 19-FEB-06:50 |
Heating:NaturalGas | 111.07 | 0.00 | 02-JAN-18:10 | 106254.04 | 19-FEB-06:50 |
General:Heating:NaturalGas | 111.07 | 0.00 | 02-JAN-18:10 | 106254.04 | 19-FEB-06:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 244.94 | 0.00 | 02-JAN-18:10 | 167865.72 | 19-FEB-06:50 |
EnergyTransfer:Building | 139.72 | 0.00 | 02-JAN-18:10 | 84202.05 | 19-FEB-06:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 35.79 | 0.00 | 01-JAN-00:10 | 18119.56 | 26-DEC-07:10 |
Heating:EnergyTransfer | 83.86 | 0.00 | 02-JAN-18:10 | 84202.05 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 16.65 | 0.00 | 01-JAN-00:10 | 18119.56 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 83.86 | 0.00 | 02-JAN-18:10 | 84202.05 | 19-FEB-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 16.65 | 0.00 | 01-JAN-00:10 | 18119.56 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 55.86 | 0.00 | 01-JAN-00:10 | 31126.37 | 10-AUG-15:40 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 19.13 | 0.00 | 01-JAN-00:10 | 9893.52 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer | 55.86 | 0.00 | 01-JAN-00:10 | 31126.37 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 19.13 | 0.00 | 01-JAN-00:10 | 9893.52 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 61.79 | 0.00 | 01-JAN-00:40 | 27847.38 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.07 | 0.00 | 01-JAN-00:40 | 27847.38 | 19-FEB-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 25.07 | 0.00 | 01-JAN-00:40 | 27847.38 | 19-FEB-06:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 36.72 | 0.00 | 01-JAN-00:10 | 27826.51 | 25-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 36.72 | 0.00 | 01-JAN-00:10 | 27826.51 | 25-JUN-13:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 42.14 | 0.00 | 02-JAN-08:10 | 55195.54 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 42.14 | 0.00 | 02-JAN-08:10 | 55195.54 | 19-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 42.14 | 0.00 | 02-JAN-08:10 | 55195.54 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 105.22 | 0.00 | 02-JAN-18:10 | 83663.67 | 19-FEB-06:50 |
HeatingCoils:EnergyTransfer | 81.49 | 0.00 | 02-JAN-18:10 | 83663.67 | 19-FEB-06:50 |
CoolingCoils:EnergyTransfer | 23.74 | 0.00 | 01-JAN-00:10 | 40707.58 | 10-AUG-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 16.653 | -19.133 | 0.000 | 0.000 | 9.936 | 19.398 | 31.946 | 10.094 | 0.000 | 0.224 | 0.000 | 0.000 | -7.085 | 0.000 | -27.653 | -34.378 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 25.068 | -36.722 | 0.000 | 0.000 | 24.329 | 137.335 | 0.000 | 50.775 | 0.000 | 0.160 | 0.002 | 0.000 | -20.061 | 0.000 | -69.722 | -111.163 |
ZONE3 BULK STORAGE | 42.140 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 65.285 | 106.253 | 107.344 | 494.051 | 0.000 | 3.136 | 0.001 | 0.000 | -151.461 | 0.000 | -340.034 | -326.713 |
Total Facility | 42.140 | 0.000 | 41.721 | -55.855 | 0.000 | 0.000 | 99.550 | 262.986 | 139.290 | 554.920 | 0.000 | 3.519 | 0.003 | 0.000 | -178.607 | 0.000 | -437.410 | -472.255 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUN-07:02 | 0.00 | 0.00 | 0.00 | -21319.17 | 0.00 | 0.00 | 801.53 | 1228.76 | 1912.50 | 237.85 | 0.00 | 0.00 | 17581.02 | 0.00 | -0.00 | 0.00 | -442.50 | 0.00 |
ZONE2 FINE STORAGE | 19-JUL-18:11 | 0.00 | 0.00 | 0.00 | -57434.17 | 0.00 | 0.00 | 0.00 | 1784.82 | 0.00 | 1267.48 | 0.00 | 0.00 | 55585.63 | 0.00 | -0.00 | 0.00 | -1203.76 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUL-18:11 | 0.00 | 0.00 | 0.00 | -57434.17 | 0.00 | 0.00 | 0.00 | 3614.41 | 2623.78 | 24287.33 | 0.00 | 0.00 | 35090.57 | 0.00 | 0.00 | 0.00 | -8181.93 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-07:02 | 0.00 | 0.00 | 27158.22 | 0.00 | 0.00 | 0.00 | 260.13 | 670.24 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -463.92 | 0.00 | -6759.67 | -21821.25 |
ZONE2 FINE STORAGE | 19-FEB-06:42 | 0.00 | 0.00 | 87382.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1971.93 | 0.00 | -7872.06 | -79323.77 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 55195.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 15227.84 | 0.00 | -31493.94 | 0.00 | -40688.56 | 0.00 |
Total Facility | 19-FEB-06:42 | 54791.51 | 0.00 | 88766.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3831.39 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25463.58 | 0.00 | -49392.81 | -73106.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0482 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0482 | 0.0976 | 1.0000 | Not calculated | 0.1023 | 0.0976 | ||
PSZ-FINE STORAGE | 2.6466 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6466 | 0.1605 | 1.0000 | Not calculated | 0.4247 | 0.1605 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0482 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0482 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0976 | ||
PSZ-FINE STORAGE | 2.6466 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6466 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1605 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0482 | 1.0482 | 1.0482 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6466 | 2.6466 | 2.6466 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0482 | 1.0482 | 1.0482 | 1.0482 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6466 | 2.6466 | 2.6466 | 2.6466 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0482 | 1.0482 | 1.0482 | No | 0.1023 | 0.3541 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6466 | 2.6466 | 2.6466 | No | 0.4247 | 0.6466 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0482 | 1.0482 | 1.0482 | 1.0482 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6466 | 2.6466 | 2.6466 | 2.6466 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 7.67 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 7.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 111.07 | 106254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.81 | 10677.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 262.99 | 31354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 109.57 | 6986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 49.53 | 4162.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.77 | 2336.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 592.96 |
Natural Gas | 0.00 | 111.07 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 704.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 54.39 |
Space Heating | 0.00 |
Space Cooling | 1.20 |
Fans (All) | 10.24 |
Service Water Heating | 5.33 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 122.64 |
Subtotal | 122.64 |
Natural Gas [MJ/m2] | |
Space Heating | 22.97 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 22.97 |
Subtotal | 22.97 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 37.35 |
Space Heating | 15.78 |
Space Cooling | 0.83 |
Fans (All) | 7.04 |
Service Water Heating | 3.66 |
Receptacle Equipment | 19.78 |
Miscellaneous | 15.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2672. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8507.17 | 252.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8393.00 | 367.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8532.50 | 227.50 | 0.00 | 0.00 | 0.00 |
Min | 8393.00 | 227.50 | 0.00 | 0.00 | 0.00 |
Max | 8532.50 | 367.00 | 0.00 | 0.00 | 0.00 |
Average | 8477.56 | 282.44 | 0.00 | 0.00 | 0.00 |
Sum | 25432.67 | 847.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33026.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75107.00 | 7612.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 182198.67 | 8994.33 | 0.00 | 0.00 | 0.00 |
Min | 33026.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Max | 182198.67 | 8994.33 | 0.00 | 0.00 | 0.00 |
Average | 96777.50 | 5535.50 | 0.00 | 0.00 | 0.00 |
Sum | 290332.50 | 16606.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8495.83 | 264.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8228.33 | 531.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8409.17 | 350.83 | 0.00 | 0.00 | 0.00 |
Min | 8228.33 | 264.17 | 0.00 | 0.00 | 0.00 |
Max | 8495.83 | 531.67 | 0.00 | 0.00 | 0.00 |
Average | 8377.78 | 382.22 | 0.00 | 0.00 | 0.00 |
Sum | 25133.33 | 1146.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33023.00 | 4.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 72031.50 | 10687.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 178101.33 | 13091.67 | 0.00 | 0.00 | 0.00 |
Min | 33023.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Max | 178101.33 | 13091.67 | 0.00 | 0.00 | 0.00 |
Average | 94385.28 | 7927.72 | 0.00 | 0.00 | 0.00 |
Sum | 283155.83 | 23783.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:40
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 27573.00 | 0.00 |
Sum | 0.00 | 191193.00 | 82719.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5388352.80 | 2006.87 | 07-JAN-08:07 | -3.8 | -3.8 | 0.493780E+09 | 624.44 | 11-JAN-16:10 | 14.03 | 10.30 |
February | 16526092.78 | 1753.86 | 18-FEB-08:07 | -1.5 | -2.1 | 0.460045E+09 | 768.97 | 27-FEB-16:30 | 19.15 | 12.30 |
March | 91128388.96 | 1487.79 | 02-MAR-08:07 | 2.15 | 1.10 | 0.553947E+09 | 768.96 | 18-MAR-14:50 | 20.00 | 10.36 |
April | 0.466122E+09 | 4735.76 | 27-APR-16:00 | 27.20 | 16.90 | 0.553331E+09 | 786.46 | 29-APR-07:10 | 9.68 | 9.68 |
May | 0.182615E+10 | 18937.23 | 06-MAY-07:02 | 15.97 | 13.25 | 0.641831E+09 | 879.30 | 06-MAY-07:10 | 15.97 | 13.25 |
June | 0.308082E+10 | 21321.41 | 24-JUN-07:02 | 13.58 | 10.70 | 0.655078E+09 | 879.39 | 24-JUN-07:10 | 13.58 | 10.70 |
July | 0.461990E+10 | 20479.95 | 01-JUL-07:02 | 15.00 | 11.57 | 0.636667E+09 | 879.39 | 08-JUL-07:10 | 15.78 | 12.20 |
August | 0.513436E+10 | 20571.95 | 19-AUG-07:02 | 13.82 | 11.59 | 0.687947E+09 | 879.39 | 26-AUG-07:10 | 16.38 | 15.20 |
September | 0.309529E+10 | 21113.72 | 16-SEP-07:02 | 10.68 | 10.68 | 0.631721E+09 | 879.39 | 16-SEP-07:10 | 10.68 | 10.68 |
October | 0.680347E+09 | 4328.39 | 04-OCT-15:00 | 21.70 | 11.49 | 0.576699E+09 | 768.96 | 04-OCT-15:30 | 21.40 | 11.45 |
November | 0.100134E+09 | 2447.25 | 04-NOV-15:50 | 20.18 | 15.92 | 0.492376E+09 | 769.00 | 04-NOV-15:09 | 20.18 | 15.92 |
December | 17305697.03 | 1486.87 | 06-DEC-08:07 | 1.07 | 0.85 | 0.494286E+09 | 649.92 | 02-DEC-15:20 | 1.07 | 0.85 |
Annual Sum or Average | 0.191335E+11 | 0.687771E+10 | ||||||||
Minimum of Months | 5388352.80 | 1486.87 | -3.8 | -3.8 | 0.460045E+09 | 624.44 | 1.07 | 0.85 | ||
Maximum of Months | 0.513436E+10 | 21321.41 | 27.20 | 16.90 | 0.687947E+09 | 879.39 | 21.40 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226714E+10 | 6168.53 | 06-JAN-09:40 | -1.5 | -1.5 | 0.736136E+09 | 1184.23 | 11-JAN-16:10 | 14.03 | 10.30 |
February | 0.160173E+10 | 5386.29 | 08-FEB-09:20 | 1.13 | -0.2 | 0.734473E+09 | 1525.56 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.172375E+10 | 4547.12 | 02-MAR-09:15 | 5.17 | 3.59 | 0.993132E+09 | 1576.82 | 18-MAR-15:00 | 20.60 | 10.43 |
April | 0.136530E+10 | 4011.56 | 18-APR-08:20 | 4.60 | 3.37 | 0.111558E+10 | 2246.80 | 27-APR-14:50 | 27.02 | 17.21 |
May | 0.208295E+10 | 8047.68 | 15-MAY-16:00 | 23.90 | 12.85 | 0.154767E+10 | 2246.84 | 06-MAY-13:39 | 23.90 | 12.85 |
June | 0.315111E+10 | 55653.02 | 25-JUN-12:55 | 21.10 | 13.01 | 0.175201E+10 | 2246.85 | 28-JUN-12:39 | 23.87 | 15.64 |
July | 0.746477E+10 | 57435.13 | 19-JUL-18:11 | 22.43 | 14.50 | 0.181683E+10 | 2246.97 | 31-JUL-13:50 | 28.12 | 18.80 |
August | 0.787692E+10 | 52903.25 | 14-AUG-19:11 | 23.60 | 15.97 | 0.196464E+10 | 2246.97 | 10-AUG-13:50 | 23.60 | 15.97 |
September | 0.354424E+10 | 54823.58 | 10-SEP-14:23 | 22.50 | 14.48 | 0.169186E+10 | 2246.90 | 12-SEP-14:50 | 24.40 | 16.68 |
October | 0.169672E+10 | 4362.12 | 07-OCT-08:15 | 10.37 | 9.34 | 0.123488E+10 | 2246.79 | 04-OCT-15:30 | 10.37 | 9.34 |
November | 0.178687E+10 | 4804.12 | 13-NOV-10:00 | 1.70 | 1.46 | 0.873853E+09 | 1889.74 | 04-NOV-15:09 | 1.70 | 1.46 |
December | 0.216047E+10 | 5382.18 | 06-DEC-09:20 | 1.33 | 1.21 | 0.775778E+09 | 1206.62 | 02-DEC-14:39 | 1.33 | 1.21 |
Annual Sum or Average | 0.367220E+11 | 0.152368E+11 | ||||||||
Minimum of Months | 0.136530E+10 | 4011.56 | -1.5 | -1.5 | 0.734473E+09 | 1184.23 | 1.33 | 1.21 | ||
Maximum of Months | 0.787692E+10 | 57435.13 | 23.90 | 15.97 | 0.196464E+10 | 2246.97 | 28.12 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.735023E+09 | 1268.48 | 11-JAN-16:10 | 14.03 | 10.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.778333E+09 | 1746.98 | 27-FEB-15:00 | 19.40 | 12.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.128992E+10 | 2154.96 | 18-MAR-15:00 | 20.60 | 10.43 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.157869E+10 | 3279.17 | 29-APR-15:30 | 21.10 | 14.85 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.257541E+10 | 4207.00 | 15-MAY-15:50 | 23.80 | 12.81 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.313424E+10 | 5098.92 | 28-JUN-15:00 | 26.10 | 16.29 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.381135E+10 | 6121.77 | 31-JUL-15:00 | 28.90 | 19.18 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.441600E+10 | 6230.75 | 10-AUG-15:00 | 31.20 | 18.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.347248E+10 | 5331.46 | 15-SEP-15:00 | 23.90 | 17.57 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.198766E+10 | 3756.38 | 04-OCT-15:30 | 21.40 | 11.45 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 | 0.113012E+10 | 2405.40 | 04-NOV-15:20 | 20.73 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.806010E+09 | 1252.09 | 02-DEC-14:39 | 11.87 | 5.62 |
Annual Sum or Average | 0.00 | 0.257152E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.735023E+09 | 1252.09 | 11.87 | 5.62 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.441600E+10 | 6230.75 | 31.20 | 19.18 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417333E+10 | 27158.10 | 17-JAN-07:02 | 1.70 |
February | 0.311081E+10 | 27123.44 | 21-FEB-07:02 | 1.60 |
March | 0.190310E+10 | 27014.57 | 17-MAR-06:01 | 6.20 |
April | 0.865792E+09 | 26905.36 | 24-APR-06:01 | 4.60 |
May | 0.197293E+09 | 9938.86 | 24-MAY-07:03 | 9.08 |
June | 0.121954E+09 | 2688.95 | 14-JUN-07:03 | 10.68 |
July | 87571394.46 | 1833.75 | 24-JUL-06:07 | 17.48 |
August | 0.105847E+09 | 1799.41 | 01-AUG-06:15 | 11.33 |
September | 0.114198E+09 | 6425.92 | 28-SEP-07:03 | 9.08 |
October | 0.487524E+09 | 26868.33 | 30-OCT-06:01 | 7.20 |
November | 0.206479E+10 | 26987.83 | 24-NOV-07:02 | 1.20 |
December | 0.342113E+10 | 27116.27 | 26-DEC-07:02 | -1.6 |
Annual Sum or Average | 0.166533E+11 | |||
Minimum of Months | 87571394.46 | 1799.41 | -1.6 | |
Maximum of Months | 0.417333E+10 | 27158.10 | 17.48 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.890897E+10 | 63381.33 | 17-JAN-06:11 | 1.30 |
February | 0.608291E+10 | 87383.07 | 19-FEB-06:42 | -5.1 |
March | 0.866677E+09 | 29602.78 | 29-MAR-06:02 | 4.50 |
April | 0.365382E+09 | 20438.30 | 19-APR-06:02 | 2.48 |
May | 0.222594E+09 | 2943.01 | 10-MAY-07:00 | 8.30 |
June | 0.212441E+09 | 2938.29 | 13-JUN-07:00 | 11.70 |
July | 0.172114E+09 | 2803.64 | 28-JUL-07:00 | 15.60 |
August | 0.166699E+09 | 3034.62 | 31-AUG-07:00 | 14.00 |
September | 0.197637E+09 | 2778.39 | 27-SEP-07:00 | 8.90 |
October | 0.210370E+09 | 2692.55 | 31-OCT-07:00 | 11.10 |
November | 0.189294E+10 | 41686.82 | 24-NOV-06:01 | 2.02 |
December | 0.576971E+10 | 53829.27 | 26-DEC-04:03 | -1.0 |
Annual Sum or Average | 0.250684E+11 | |||
Minimum of Months | 0.166699E+09 | 2692.55 | -5.1 | |
Maximum of Months | 0.890897E+10 | 87383.07 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195815E+11 | 36507.47 | 15-JAN-01:53 | -1.7 |
February | 0.138931E+11 | 55196.09 | 19-FEB-07:00 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.275328E+09 | 11093.09 | 29-NOV-21:00 | 5.00 |
December | 0.839036E+10 | 28513.94 | 22-DEC-22:53 | 1.10 |
Annual Sum or Average | 0.421404E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.195815E+11 | 55196.09 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162246E+10 | 1228.76 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.147976E+10 | 1228.76 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.169071E+10 | 1228.76 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.159765E+10 | 1228.76 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.165659E+10 | 1228.76 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.163177E+10 | 1228.76 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.162246E+10 | 1228.76 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.169071E+10 | 1228.76 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.159765E+10 | 1228.76 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.162246E+10 | 1228.76 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.156352E+10 | 1228.76 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.162246E+10 | 1228.76 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.193982E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.147976E+10 | 1228.76 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.169071E+10 | 1228.76 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.149170E+11 | 15171.01 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.120694E+11 | 15171.01 | 02-FEB-09:09 | 0.00 | 0.00 |
March | 0.119074E+11 | 15171.01 | 02-MAR-09:09 | 0.00 | 0.00 |
April | 0.936331E+10 | 13386.18 | 01-APR-07:10 | 0.00 | 0.00 |
May | 0.861391E+10 | 13386.18 | 04-MAY-07:10 | 0.00 | 0.00 |
June | 0.837240E+10 | 11735.22 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 0.917643E+10 | 15171.01 | 12-JUL-08:09 | 0.00 | 0.00 |
August | 0.102171E+11 | 13386.18 | 08-AUG-07:10 | 0.00 | 0.00 |
September | 0.104589E+11 | 15171.01 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.127741E+11 | 15171.01 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 0.139914E+11 | 15171.01 | 02-NOV-08:09 | 0.00 | 0.00 |
December | 0.154737E+11 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137335E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.837240E+10 | 11735.22 | 0.00 | 0.00 | |
Maximum of Months | 0.154737E+11 | 15171.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.122267E+11 | 14954.28 | 02-JAN-15:39 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.949077E+10 | 14954.28 | 06-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.882935E+10 | 13194.95 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.699627E+10 | 10555.96 | 01-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.666488E+10 | 10555.96 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.630899E+10 | 7952.16 | 13-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.667458E+10 | 11265.56 | 12-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.729727E+10 | 10555.96 | 16-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.780417E+10 | 13194.95 | 21-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.959963E+10 | 14954.28 | 31-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.111801E+11 | 14954.28 | 03-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.131804E+11 | 14954.28 | 01-DEC-15:20 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.106253E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.630899E+10 | 7952.16 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.131804E+11 | 14954.28 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334377E+10 |
February | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282292E+10 |
March | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280777E+10 |
April | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11718108.50 | 0.232873E+10 |
May | 0.144276E+10 | 0.165659E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1229631.08 | 0.224036E+10 |
June | 0.144276E+10 | 0.163177E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9372290.04 | 0.187680E+10 |
July | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53591697.56 | 0.142385E+10 |
August | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145735E+09 | 0.133351E+10 |
September | 0.138726E+10 | 0.159765E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2091768.90 | 0.142479E+10 |
October | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232041E+10 |
November | 0.133177E+10 | 0.156352E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271575E+10 |
December | 0.138726E+10 | 0.162246E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301476E+10 |
Annual Sum or Average | 0.168137E+11 | 0.193982E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223738E+09 | 0.276534E+11 |
Minimum of Months | 0.127628E+10 | 0.147976E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133351E+10 |
Maximum of Months | 0.149825E+10 | 0.169071E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145735E+09 | 0.334377E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.149170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750827E+10 |
February | 0.300332E+10 | 0.120694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647641E+10 |
March | 0.352563E+10 | 0.119074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607689E+10 |
April | 0.326447E+10 | 0.936331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37594789.01 | 0.600775E+10 |
May | 0.339505E+10 | 0.861391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654867E+10 |
June | 0.339505E+10 | 0.837240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101992.25 | 0.602373E+10 |
July | 0.326447E+10 | 0.917643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32171264.80 | 0.512683E+10 |
August | 0.352563E+10 | 0.102171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89973626.41 | 0.465719E+10 |
September | 0.326447E+10 | 0.104589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341791E+10 |
October | 0.326447E+10 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599494E+10 |
November | 0.313390E+10 | 0.139914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571023E+10 |
December | 0.326447E+10 | 0.154737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617314E+10 |
Annual Sum or Average | 0.395654E+11 | 0.137335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159842E+09 | 0.697219E+11 |
Minimum of Months | 0.300332E+10 | 0.837240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341791E+10 |
Maximum of Months | 0.352563E+10 | 0.154737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89973626.41 | 0.750827E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.122267E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72504183.69 | 0.202109E+11 |
February | 0.690763E+10 | 0.949077E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355321E+09 | 0.172795E+11 |
March | 0.810895E+10 | 0.882935E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240585E+09 | 0.183736E+11 |
April | 0.750829E+10 | 0.699627E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114876E+10 | 0.185474E+11 |
May | 0.780862E+10 | 0.666488E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106828E+09 | 0.243106E+11 |
June | 0.780862E+10 | 0.630899E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4389361.79 | 0.227144E+11 |
July | 0.750829E+10 | 0.667458E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42830088.93 | 0.231938E+11 |
August | 0.810895E+10 | 0.729727E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194717E+09 | 0.238623E+11 |
September | 0.750829E+10 | 0.780417E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167940E+11 |
October | 0.750829E+10 | 0.959963E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219483E+11 |
November | 0.720796E+10 | 0.111801E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42083555.43 | 0.167327E+11 |
December | 0.750829E+10 | 0.131804E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22622243.90 | 0.153153E+11 |
Annual Sum or Average | 0.910005E+11 | 0.106253E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223064E+10 | 0.239283E+12 |
Minimum of Months | 0.690763E+10 | 0.630899E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153153E+11 |
Maximum of Months | 0.810895E+10 | 0.131804E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114876E+10 | 0.243106E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1228.76 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8994.50 | 06-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1228.76 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9205.11 | 13-FEB-18:00 |
March | 1680.92 | 01-MAR-08:09 | 1228.76 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8522.01 | 24-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1228.76 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.99 | 27-APR-16:10 | 7448.84 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1228.76 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.40 | 05-MAY-16:10 | 6059.94 | 18-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1228.76 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.17 | 28-JUN-17:00 | 5279.41 | 22-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1228.76 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1951.90 | 24-JUL-16:10 | 4906.95 | 12-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1228.76 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2890.64 | 10-AUG-17:00 | 5667.81 | 01-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1228.76 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.66 | 14-SEP-17:00 | 5088.74 | 06-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1228.76 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5949.52 | 31-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1228.76 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8379.11 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1228.76 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8983.32 | 26-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4906.95 | |||||
Maximum of Months | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2890.64 | 9205.11 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 15171.01 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10098.77 | 28-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 15171.01 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8753.23 | 13-FEB-08:00 |
March | 3955.50 | 01-MAR-08:09 | 15171.01 | 02-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8384.91 | 04-MAR-16:05 |
April | 3955.50 | 01-APR-07:10 | 13386.18 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2135.30 | 01-APR-16:00 | 8239.86 | 08-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 13386.18 | 04-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 9654.64 | 10-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 11735.22 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.10 | 28-JUN-17:30 | 9411.86 | 13-JUN-03:00 |
July | 3955.50 | 01-JUL-07:10 | 15171.01 | 12-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.08 | 24-JUL-15:10 | 6049.91 | 03-JUL-16:00 |
August | 3955.50 | 01-AUG-07:10 | 13386.18 | 08-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.06 | 08-AUG-17:00 | 7731.08 | 11-AUG-04:00 |
September | 3955.50 | 01-SEP-07:10 | 15171.01 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6895.39 | 26-SEP-16:00 |
October | 3955.50 | 02-OCT-07:10 | 15171.01 | 03-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7530.74 | 31-OCT-16:00 |
November | 3955.50 | 01-NOV-07:10 | 15171.01 | 02-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9886.94 | 29-NOV-16:05 |
December | 3955.50 | 01-DEC-08:09 | 15171.01 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6969.59 | 22-DEC-21:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 11735.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6049.91 | ||||
Maximum of Months | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2135.30 | 10098.77 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 14954.28 | 02-JAN-15:39 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6799.09 | 11-JAN-14:00 | 22974.05 | 14-JAN-19:57 |
February | 9097.65 | 01-FEB-08:09 | 14954.28 | 06-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5440.46 | 27-FEB-15:00 | 28936.05 | 13-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 13194.95 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9441.34 | 18-MAR-16:00 | 29970.51 | 22-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 10555.96 | 01-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27758.07 | 01-APR-16:00 | 23192.80 | 08-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 10555.96 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.18 | 04-MAY-14:00 | 32239.70 | 17-MAY-19:00 |
June | 9097.65 | 01-JUN-07:10 | 7952.16 | 13-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 835.37 | 20-JUN-17:00 | 34584.18 | 13-JUN-10:00 |
July | 9097.65 | 01-JUL-07:10 | 11265.56 | 12-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2493.02 | 23-JUL-14:00 | 24251.74 | 28-JUL-07:10 |
August | 9097.65 | 01-AUG-07:10 | 10555.96 | 16-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4013.57 | 29-AUG-18:00 | 34606.19 | 11-AUG-04:00 |
September | 9097.65 | 01-SEP-07:10 | 13194.95 | 21-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27055.39 | 26-SEP-15:50 |
October | 9097.65 | 02-OCT-07:10 | 14954.28 | 31-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 21288.51 | 31-OCT-16:00 |
November | 9097.65 | 01-NOV-07:10 | 14954.28 | 03-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992.22 | 27-NOV-03:50 | 23346.24 | 29-NOV-14:00 |
December | 9097.65 | 01-DEC-08:09 | 14954.28 | 01-DEC-15:20 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5519.92 | 14-DEC-12:00 | 29491.22 | 26-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 7952.16 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21288.51 | |||||
Maximum of Months | 9097.65 | 14954.28 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 27758.07 | 34606.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2006.87 | 07-JAN-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.39 |
February | 1753.86 | 18-FEB-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.62 |
March | 1487.79 | 02-MAR-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1766.28 |
April | 4735.76 | 27-APR-16:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 351.06 | 0.00 |
May | 18937.23 | 06-MAY-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.00 |
June | 21321.41 | 24-JUN-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.50 |
July | 20479.95 | 01-JUL-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.52 |
August | 20571.95 | 19-AUG-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.87 |
September | 21113.72 | 16-SEP-07:02 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.69 |
October | 4328.39 | 04-OCT-15:00 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
November | 2447.25 | 04-NOV-15:50 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 |
December | 1486.87 | 06-DEC-08:07 | 5042.77 | 3686.29 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1522.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1486.87 | 1680.92 | 1228.76 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21321.41 | 8404.61 | 6143.82 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 351.06 | 1766.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6168.53 | 06-JAN-09:40 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5386.29 | 08-FEB-09:20 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.94 |
March | 4547.12 | 02-MAR-09:15 | 7911.00 | 26599.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.93 |
April | 4011.56 | 18-APR-08:20 | 3955.50 | 9557.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.19 |
May | 8047.68 | 15-MAY-16:00 | 3955.50 | 8433.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.35 |
June | 55653.02 | 25-JUN-12:55 | 0.00 | 928.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.40 |
July | 57435.13 | 19-JUL-18:11 | 0.00 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.76 |
August | 52903.25 | 14-AUG-19:11 | 0.00 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.97 |
September | 54823.58 | 10-SEP-14:23 | 0.00 | 2052.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.66 |
October | 4362.12 | 07-OCT-08:15 | 7911.00 | 30342.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1770.38 |
November | 4804.12 | 13-NOV-10:00 | 3955.50 | 11428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.49 |
December | 5382.18 | 06-DEC-09:20 | 3955.50 | 15171.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4011.56 | 0.00 | 928.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57435.13 | 7911.00 | 30342.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1770.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 5277.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10444.40 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4044.27 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7898.32 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6508.74 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14528.01 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5093.36 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6899.74 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9508.44 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11358.38 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7349.27 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9192.86 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 1759.33 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4337.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4044.27 | |
Maximum of Months | 0.00 | 0.00 | 5277.98 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14528.01 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.589965E+11 | 50687.23 | 18-JAN-16:49 | 0.440371E+11 | 71594.14 | 16-JAN-08:00 |
February | 0.495030E+11 | 47259.05 | 06-FEB-15:00 | 0.310773E+11 | 106254.04 | 19-FEB-06:49 |
March | 0.509381E+11 | 43564.27 | 13-MAR-07:10 | 0.377952E+10 | 24826.37 | 24-MAR-06:10 |
April | 0.435988E+11 | 40307.59 | 01-APR-07:10 | 0.115665E+10 | 20983.50 | 19-APR-06:10 |
May | 0.424218E+11 | 35396.95 | 02-MAY-07:19 | 86144584.75 | 5360.82 | 24-MAY-07:10 |
June | 0.411742E+11 | 35390.69 | 08-JUN-07:10 | 2205906.88 | 1720.76 | 14-JUN-07:10 |
July | 0.437658E+11 | 43629.30 | 31-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.484771E+11 | 42750.58 | 10-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.465488E+11 | 43548.46 | 26-SEP-07:10 | 3268431.08 | 3753.35 | 28-SEP-07:10 |
October | 0.519829E+11 | 47130.24 | 31-OCT-08:09 | 0.538703E+09 | 13432.37 | 30-OCT-06:10 |
November | 0.549758E+11 | 50512.76 | 30-NOV-16:30 | 0.613469E+10 | 33500.36 | 29-NOV-20:00 |
December | 0.605751E+11 | 50685.86 | 26-DEC-16:40 | 0.242547E+11 | 53273.39 | 26-DEC-07:10 |
Annual Sum or Average | 0.592958E+12 | 0.111070E+12 | ||||
Minimum of Months | 0.411742E+11 | 35390.69 | 0.00 | 0.00 | ||
Maximum of Months | 0.605751E+11 | 50687.23 | 0.440371E+11 | 106254.04 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.287662E+11 | 0.119132E+11 | 0.115358E+11 | 0.00 | 0.455194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222939E+10 | 0.00 |
February | 0.230400E+11 | 0.982151E+10 | 0.105871E+11 | 0.00 | 0.402232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203204E+10 | 0.00 |
March | 0.224274E+11 | 0.958677E+10 | 0.123431E+11 | 0.00 | 0.429501E+10 | 0.00 | 0.00 | 141.19 | 0.00 | 0.00 | 0.00 | 0.228580E+10 | 0.00 |
April | 0.179572E+11 | 0.798548E+10 | 0.114862E+11 | 0.00 | 0.395371E+10 | 0.00 | 0.00 | 65591391.54 | 0.00 | 0.00 | 0.00 | 0.215061E+10 | 0.00 |
May | 0.169354E+11 | 0.709261E+10 | 0.119357E+11 | 0.00 | 0.411071E+10 | 0.00 | 0.00 | 0.156035E+09 | 0.00 | 0.00 | 0.00 | 0.219133E+10 | 0.00 |
June | 0.163132E+11 | 0.624167E+10 | 0.118862E+11 | 0.00 | 0.412269E+10 | 0.00 | 0.00 | 0.500348E+09 | 0.00 | 0.00 | 0.00 | 0.211021E+10 | 0.00 |
July | 0.174735E+11 | 0.673631E+10 | 0.115358E+11 | 0.00 | 0.402614E+10 | 0.00 | 0.00 | 0.188924E+10 | 0.00 | 0.00 | 0.00 | 0.210491E+10 | 0.00 |
August | 0.192050E+11 | 0.773397E+10 | 0.123357E+11 | 0.00 | 0.433284E+10 | 0.00 | 0.00 | 0.271644E+10 | 0.00 | 0.00 | 0.00 | 0.215311E+10 | 0.00 |
September | 0.198607E+11 | 0.871486E+10 | 0.114788E+11 | 0.00 | 0.395721E+10 | 0.00 | 0.00 | 0.471863E+09 | 0.00 | 0.00 | 0.00 | 0.206531E+10 | 0.00 |
October | 0.239962E+11 | 0.103413E+11 | 0.115432E+11 | 0.00 | 0.395261E+10 | 0.00 | 0.00 | 9106575.40 | 0.00 | 0.00 | 0.00 | 0.214059E+10 | 0.00 |
November | 0.267351E+11 | 0.111797E+11 | 0.110862E+11 | 0.00 | 0.387202E+10 | 0.00 | 0.00 | 2143713.31 | 0.00 | 0.00 | 0.00 | 0.210060E+10 | 0.00 |
December | 0.302766E+11 | 0.122192E+11 | 0.115358E+11 | 0.00 | 0.433578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220775E+10 | 0.00 |
Annual Sum or Average | 0.262986E+12 | 0.109567E+12 | 0.139290E+12 | 0.00 | 0.495330E+11 | 0.00 | 0.00 | 0.581077E+10 | 0.00 | 0.00 | 0.00 | 0.257717E+11 | 0.00 |
Minimum of Months | 0.163132E+11 | 0.624167E+10 | 0.105871E+11 | 0.00 | 0.387202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203204E+10 | 0.00 |
Maximum of Months | 0.302766E+11 | 0.122192E+11 | 0.123431E+11 | 0.00 | 0.455194E+10 | 0.00 | 0.00 | 0.271644E+10 | 0.00 | 0.00 | 0.00 | 0.228580E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.440371E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.310773E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.377952E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.115665E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 86144584.75 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2205906.88 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3268431.08 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.538703E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.613469E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242547E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111070E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.440371E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31354.05 | 02-JAN-15:39 | 6986.42 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4162.81 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31354.05 | 06-FEB-15:00 | 6986.42 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4162.81 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27809.90 | 01-MAR-16:00 | 6986.42 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3992.53 | 24-MAR-06:49 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24555.14 | 01-APR-07:10 | 6986.42 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3992.53 | 27-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 21935.14 | 01-MAY-06:10 | 6986.42 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3992.53 | 04-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 19649.42 | 08-JUN-07:10 | 6986.42 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3992.53 | 10-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 27665.32 | 12-JUL-08:09 | 6986.42 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3992.53 | 07-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24555.14 | 10-AUG-07:10 | 6986.42 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 3992.53 | 23-AUG-13:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27809.90 | 21-SEP-07:10 | 6986.42 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3992.53 | 08-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 31354.05 | 31-OCT-08:09 | 6986.42 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3992.53 | 04-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31354.05 | 03-NOV-08:09 | 6986.42 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3992.53 | 29-NOV-08:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31354.05 | 01-DEC-15:20 | 6986.42 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4162.81 | 05-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 19649.42 | 6986.42 | 10112.62 | 0.00 | 3992.53 | 0.00 | 0.00 | |||||
Maximum of Months | 31354.05 | 6986.42 | 10112.62 | 0.00 | 4162.81 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2330.82 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2336.30 | 13-FEB-12:39 | 0.00 |
March | 0.12 | 18-MAR-13:00 | 0.00 | 0.00 | 0.00 | 2320.93 | 01-MAR-12:30 | 0.00 |
April | 2721.32 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2227.76 | 01-APR-11:30 | 0.00 |
May | 2909.74 | 15-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2068.54 | 02-MAY-11:00 | 0.00 |
June | 6243.21 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 | 1842.01 | 09-JUN-11:00 | 0.00 |
July | 9923.45 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1800.18 | 01-JUL-11:09 | 0.00 |
August | 10677.67 | 10-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1794.61 | 28-AUG-11:09 | 0.00 |
September | 6226.93 | 13-SEP-17:30 | 0.00 | 0.00 | 0.00 | 1802.39 | 30-SEP-11:09 | 0.00 |
October | 850.93 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1854.30 | 17-OCT-11:00 | 0.00 |
November | 336.35 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2115.95 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2248.62 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1794.61 | 0.00 | ||
Maximum of Months | 10677.67 | 0.00 | 0.00 | 0.00 | 2336.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 50687.23 | 18-JAN-16:49 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4162.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47259.05 | 06-FEB-15:00 | 31354.05 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43564.27 | 13-MAR-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40307.59 | 01-APR-07:10 | 24555.14 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35396.95 | 02-MAY-07:19 | 19649.42 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35390.69 | 08-JUN-07:10 | 19649.42 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43629.30 | 31-JUL-15:00 | 17998.46 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 9923.45 | 0.00 |
August | 42750.58 | 10-AUG-15:50 | 16371.08 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 10672.45 | 0.00 |
September | 43548.46 | 26-SEP-07:10 | 27809.90 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47130.24 | 31-OCT-08:09 | 31354.05 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50512.76 | 30-NOV-16:30 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50685.86 | 26-DEC-16:40 | 27809.90 | 10112.62 | 6986.42 | 0.00 | 4162.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35390.69 | 16371.08 | 10112.62 | 0.00 | 0.00 | 3992.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50687.23 | 31354.05 | 10112.62 | 6986.42 | 0.00 | 4162.81 | 0.00 | 0.00 | 10672.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 71594.14 | 16-JAN-08:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 106254.04 | 19-FEB-06:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 24826.37 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 20983.50 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 5360.82 | 24-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1720.76 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3753.35 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 13432.37 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 33500.36 | 29-NOV-20:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 53273.39 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 106254.04 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 16.00 | 2.17 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
February | 3.00 | 16.20 | 1.83 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
March | 0.67 | 17.16 | 0.67 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 17.17 | 0.67 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
December | 1.17 | 16.52 | 0.83 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
Annual Sum or Average | 9.50 | 16.29 | 6.17 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 17.17 | 2.17 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.17 | 14.91 | 1.33 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
February | 26.00 | 14.86 | 1.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
March | 1.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.34 | 0.00 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.34 | 0.00 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.00 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
December | 16.33 | 14.96 | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Annual Sum or Average | 82.00 | 14.91 | 2.83 | 14.91 | 7.33 | 15.90 | 0.00 | 15.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.17 | 14.98 | 1.33 | 14.98 | 3.33 | 27.34 | 0.00 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
February | 276.00 | 20.84 | 250.33 | 20.77 | 250.33 | 20.75 |
March | 324.00 | 21.08 | 245.67 | 20.90 | 245.67 | 20.83 |
April | 288.33 | 21.79 | 112.83 | 21.40 | 112.83 | 21.18 |
May | 245.00 | 23.10 | 27.17 | 23.07 | 7.83 | 22.99 |
June | 129.33 | 23.38 | 93.17 | 23.63 | 0.00 | 23.63 |
July | 10.67 | 23.66 | 235.17 | 24.07 | 0.00 | 24.07 |
August | 7.83 | 23.36 | 275.83 | 24.08 | 0.00 | 24.08 |
September | 88.33 | 23.40 | 122.67 | 23.77 | 0.00 | 23.77 |
October | 292.83 | 22.34 | 51.33 | 22.02 | 51.33 | 21.77 |
November | 288.00 | 21.09 | 208.17 | 20.91 | 208.17 | 20.83 |
December | 300.00 | 20.74 | 300.00 | 20.74 | 300.00 | 20.74 |
Annual Sum or Average | 2550.33 | 21.61 | 2222.33 | 21.70 | 1476.17 | 21.45 |
Minimum of Months | 7.83 | 20.72 | 27.17 | 20.72 | 0.00 | 20.72 |
Maximum of Months | 324.00 | 23.66 | 300.00 | 24.08 | 300.00 | 24.08 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 16.42 | 300.00 | 16.42 | 300.00 | 16.42 |
February | 276.00 | 17.06 | 271.67 | 17.03 | 271.67 | 17.01 |
March | 324.00 | 18.32 | 307.17 | 18.23 | 307.17 | 18.20 |
April | 277.00 | 19.72 | 216.83 | 19.60 | 198.67 | 19.39 |
May | 193.17 | 22.44 | 85.67 | 23.26 | 12.33 | 23.12 |
June | 94.67 | 23.92 | 204.67 | 25.40 | 23.17 | 25.49 |
July | 126.67 | 26.58 | 282.33 | 26.45 | 121.50 | 26.51 |
August | 132.67 | 26.54 | 310.83 | 26.44 | 126.00 | 26.50 |
September | 100.50 | 24.38 | 206.67 | 25.49 | 33.67 | 25.61 |
October | 262.67 | 20.76 | 139.00 | 20.58 | 119.50 | 20.29 |
November | 288.00 | 18.19 | 258.50 | 18.00 | 258.50 | 17.94 |
December | 300.00 | 16.82 | 300.00 | 16.82 | 300.00 | 16.82 |
Annual Sum or Average | 2675.33 | 19.70 | 2883.33 | 20.33 | 2072.17 | 19.95 |
Minimum of Months | 94.67 | 16.42 | 85.67 | 16.42 | 12.33 | 16.42 |
Maximum of Months | 324.00 | 26.58 | 310.83 | 26.45 | 307.17 | 26.51 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.63 | 300.00 | 10.63 | 300.00 | 10.63 |
February | 276.00 | 11.37 | 276.00 | 11.37 | 276.00 | 11.37 |
March | 324.00 | 13.64 | 324.00 | 13.64 | 324.00 | 13.64 |
April | 300.00 | 15.73 | 296.17 | 15.70 | 296.17 | 15.68 |
May | 312.00 | 19.98 | 197.67 | 19.63 | 197.67 | 19.48 |
June | 262.17 | 21.58 | 72.17 | 21.61 | 44.17 | 21.36 |
July | 123.00 | 24.44 | 188.67 | 25.39 | 35.17 | 25.64 |
August | 91.17 | 26.97 | 290.33 | 26.40 | 71.83 | 26.65 |
September | 152.50 | 22.60 | 116.50 | 23.76 | 2.33 | 23.73 |
October | 300.00 | 17.78 | 254.83 | 17.50 | 254.83 | 17.39 |
November | 288.00 | 13.49 | 288.00 | 13.49 | 288.00 | 13.49 |
December | 300.00 | 11.10 | 300.00 | 11.10 | 300.00 | 11.10 |
Annual Sum or Average | 3028.83 | 16.12 | 2904.33 | 16.28 | 2390.17 | 15.77 |
Minimum of Months | 91.17 | 10.63 | 72.17 | 10.63 | 2.33 | 10.63 |
Maximum of Months | 324.00 | 26.97 | 324.00 | 26.40 | 324.00 | 26.65 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 565.96 | 141.19 | 0.83 | 565.96 | -0.0 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.48 | 18-MAR-14:00 | 0.48 | 18-MAR-14:00 | 0.00 | 14-MAR-15:50 | 0.12 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.242172E+09 | 59330103.08 | 21.50 | 0.230843E+09 | 11328894.94 | 0.00 | 0.43 | 27-APR-16:00 | 0.00 | 01-APR-00:10 | 6800.02 | 27-APR-16:00 | 6302.45 | 27-APR-16:00 | 500.37 | 27-APR-15:40 | 1674.97 | 27-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.598533E+09 | 0.141653E+09 | 45.85 | 0.535172E+09 | 63360460.05 | 0.00 | 1.00 | 06-MAY-07:02 | 0.00 | 01-MAY-00:10 | 16972.17 | 06-MAY-07:02 | 12671.55 | 06-MAY-07:02 | 4300.62 | 06-MAY-07:02 | 3598.03 | 06-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.128102E+10 | 0.303794E+09 | 102.18 | 0.121662E+10 | 64404376.27 | 0.00 | 1.00 | 03-JUN-07:03 | 0.00 | 01-JUN-00:10 | 16305.17 | 10-JUN-07:02 | 14060.69 | 10-JUN-07:02 | 3995.85 | 17-JUN-07:03 | 3456.50 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.340780E+10 | 0.802802E+09 | 177.26 | 0.292650E+10 | 0.481301E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18071.85 | 31-JUL-07:02 | 13588.02 | 08-JUL-07:02 | 6226.97 | 15-JUL-07:02 | 3811.75 | 31-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.463392E+10 | 0.110175E+10 | 210.89 | 0.394858E+10 | 0.685339E+09 | 0.00 | 1.00 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 | 18179.74 | 25-AUG-07:02 | 14399.36 | 09-AUG-07:02 | 7023.77 | 26-AUG-07:02 | 3831.47 | 25-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.136950E+10 | 0.320176E+09 | 86.97 | 0.112411E+10 | 0.245385E+09 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 16876.04 | 23-SEP-07:02 | 12627.40 | 09-SEP-07:02 | 6727.99 | 23-SEP-07:02 | 3578.21 | 23-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 37603422.66 | 9106572.55 | 6.83 | 37598870.69 | 4551.97 | 0.00 | 0.25 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3545.60 | 04-OCT-15:00 | 3545.60 | 04-OCT-15:00 | 7.57 | 07-OCT-15:00 | 850.93 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 8724529.50 | 2143713.31 | 3.00 | 6632963.27 | 2091566.24 | 0.00 | 0.09 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 | 1373.24 | 04-NOV-15:00 | 1057.50 | 04-NOV-15:00 | 315.74 | 04-NOV-15:00 | 336.35 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.115793E+11 | 0.274075E+10 | 655.31 | 0.100261E+11 | 0.155321E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.463392E+10 | 0.110175E+10 | 210.89 | 0.394858E+10 | 0.685339E+09 | 0.00 | 1.00 | 0.00 | 18179.74 | 14399.36 | 7023.77 | 3831.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 23134360.48 | 6261288.47 | 3.17 | 22015072.04 | 1119288.44 | 0.00 | 0.08 | 27-APR-16:00 | 0.00 | 01-APR-00:10 | 3870.00 | 27-APR-16:00 | 3655.98 | 27-APR-16:00 | 214.01 | 27-APR-16:00 | 1046.35 | 27-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 55385822.16 | 14382265.17 | 9.17 | 53395050.70 | 1990771.46 | 0.00 | 0.10 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4632.54 | 15-MAY-16:00 | 4632.54 | 15-MAY-16:00 | 370.93 | 06-MAY-13:30 | 1192.75 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.790369E+09 | 0.196554E+09 | 28.45 | 0.768289E+09 | 22080571.18 | 0.00 | 1.00 | 11-JUN-12:45 | 0.00 | 01-JUN-00:10 | 55714.68 | 22-JUN-17:51 | 54341.31 | 28-JUN-17:11 | 7186.15 | 11-JUN-12:45 | 12616.33 | 28-JUN-17:11 | 0.00 | 01-JUN-00:10 |
July | 0.435652E+10 | 0.108644E+10 | 100.14 | 0.389693E+10 | 0.459593E+09 | 0.00 | 1.00 | 07-JUL-17:25 | 0.00 | 01-JUL-00:10 | 58825.38 | 27-JUL-17:11 | 54433.18 | 23-JUL-13:05 | 16564.13 | 15-JUL-18:35 | 13219.29 | 31-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.632497E+10 | 0.161470E+10 | 117.88 | 0.566292E+10 | 0.662047E+09 | 0.00 | 1.00 | 06-AUG-13:05 | 0.00 | 01-AUG-00:10 | 57592.46 | 24-AUG-19:35 | 54406.47 | 07-AUG-17:43 | 11312.50 | 11-AUG-17:11 | 13535.81 | 10-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.605601E+09 | 0.151688E+09 | 30.85 | 0.505166E+09 | 0.100435E+09 | 0.00 | 1.00 | 10-SEP-12:55 | 0.00 | 01-SEP-00:10 | 56629.57 | 14-SEP-17:12 | 51748.95 | 10-SEP-14:23 | 8561.70 | 13-SEP-17:25 | 12489.05 | 14-SEP-17:12 | 0.00 | 01-SEP-00:10 |
October | 10.91 | 2.85 | 0.33 | 10.91 | 0.00 | 0.00 | 0.00 | 04-OCT-13:20 | 0.00 | 01-OCT-00:10 | 0.01 | 04-OCT-13:20 | 0.01 | 04-OCT-13:20 | 0.00 | 01-OCT-00:10 | 0.00 | 04-OCT-13:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.121560E+11 | 0.307002E+10 | 289.98 | 0.109087E+11 | 0.124727E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.632497E+10 | 0.161470E+10 | 117.88 | 0.566292E+10 | 0.662047E+09 | 0.00 | 1.00 | 0.00 | 58825.38 | 54433.18 | 16564.13 | 13535.81 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.37 | 11.99 | 28.38 | 21.42 | 99.55 | 0.00 | 0.00 | 0.00 |
February | 71.72 | 26.71 | 45.01 | 58.78 | 85.75 | 0.00 | 0.00 | 0.00 |
March | 101.02 | 34.13 | 66.89 | 95.77 | 70.22 | 0.00 | 0.00 | 0.00 |
April | 153.35 | 58.51 | 94.84 | 165.88 | 59.75 | 0.00 | 0.00 | 0.00 |
May | 197.81 | 80.45 | 117.36 | 220.84 | 60.86 | 0.00 | 0.00 | 0.00 |
June | 190.18 | 73.85 | 116.33 | 212.10 | 52.18 | 0.00 | 0.00 | 0.00 |
July | 235.35 | 123.89 | 111.46 | 282.35 | 52.01 | 0.00 | 0.00 | 0.00 |
August | 194.28 | 99.10 | 95.18 | 235.51 | 52.15 | 0.00 | 0.00 | 0.00 |
September | 158.80 | 76.40 | 82.40 | 179.25 | 68.55 | 0.00 | 0.00 | 0.00 |
October | 90.44 | 37.00 | 53.44 | 87.35 | 74.06 | 0.00 | 0.00 | 0.00 |
November | 45.00 | 12.82 | 32.18 | 30.27 | 80.78 | 0.00 | 0.00 | 0.00 |
December | 38.18 | 13.39 | 24.79 | 24.43 | 101.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.71 | 54.23 | 72.48 | 134.98 | 71.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.18 | 11.99 | 24.79 | 21.42 | 52.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.35 | 123.89 | 117.36 | 282.35 | 101.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.37 | 11.99 | 28.38 | 21.42 | 99.55 | 0.00 | 0.00 | 0.00 |
February | 71.72 | 26.71 | 45.01 | 58.78 | 85.75 | 0.00 | 0.00 | 0.00 |
March | 101.02 | 34.13 | 66.89 | 95.77 | 70.22 | 0.00 | 0.00 | 0.00 |
April | 153.35 | 58.51 | 94.84 | 165.88 | 59.75 | 0.00 | 0.00 | 0.00 |
May | 197.81 | 80.45 | 117.36 | 220.84 | 60.86 | 0.00 | 0.00 | 0.00 |
June | 190.18 | 73.85 | 116.33 | 212.10 | 52.18 | 0.00 | 0.00 | 0.00 |
July | 235.35 | 123.89 | 111.46 | 282.35 | 52.01 | 0.00 | 0.00 | 0.00 |
August | 194.28 | 99.10 | 95.18 | 235.51 | 52.15 | 0.00 | 0.00 | 0.00 |
September | 158.80 | 76.40 | 82.40 | 179.25 | 68.55 | 0.00 | 0.00 | 0.00 |
October | 90.44 | 37.00 | 53.44 | 87.35 | 74.06 | 0.00 | 0.00 | 0.00 |
November | 45.00 | 12.82 | 32.18 | 30.27 | 80.78 | 0.00 | 0.00 | 0.00 |
December | 38.18 | 13.39 | 24.79 | 24.43 | 101.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.71 | 54.23 | 72.48 | 134.98 | 71.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.18 | 11.99 | 24.79 | 21.42 | 52.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.35 | 123.89 | 117.36 | 282.35 | 101.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.83 | 0.00 | 13.83 | 1.52 | 60.92 | 0.00 | 0.00 | 0.00 |
February | 21.52 | 0.00 | 21.52 | 7.61 | 52.43 | 0.00 | 0.00 | 0.00 |
March | 31.71 | 0.00 | 31.71 | 18.89 | 42.11 | 0.00 | 0.00 | 0.00 |
April | 44.95 | 0.22 | 44.73 | 35.51 | 34.53 | 0.00 | 0.00 | 0.00 |
May | 57.71 | 1.69 | 56.03 | 49.36 | 34.39 | 0.00 | 0.00 | 0.00 |
June | 60.71 | 3.99 | 56.72 | 54.27 | 28.85 | 0.00 | 0.00 | 0.00 |
July | 57.75 | 4.55 | 53.21 | 55.07 | 28.66 | 0.00 | 0.00 | 0.00 |
August | 46.91 | 1.43 | 45.48 | 45.24 | 28.90 | 0.00 | 0.00 | 0.00 |
September | 36.30 | 0.02 | 36.28 | 26.81 | 40.68 | 0.00 | 0.00 | 0.00 |
October | 24.86 | 0.00 | 24.86 | 13.34 | 44.23 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 4.20 | 48.70 | 0.00 | 0.00 | 0.00 |
December | 11.75 | 0.00 | 11.75 | 1.06 | 61.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.38 | 1.00 | 34.38 | 26.18 | 42.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 1.06 | 28.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.71 | 4.55 | 56.72 | 55.07 | 61.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.83 | 0.00 | 13.83 | 1.52 | 60.92 | 0.00 | 0.00 | 0.00 |
February | 21.52 | 0.00 | 21.52 | 7.61 | 52.43 | 0.00 | 0.00 | 0.00 |
March | 31.71 | 0.00 | 31.71 | 18.89 | 42.11 | 0.00 | 0.00 | 0.00 |
April | 44.95 | 0.22 | 44.73 | 35.51 | 34.53 | 0.00 | 0.00 | 0.00 |
May | 57.71 | 1.69 | 56.03 | 49.35 | 34.39 | 0.00 | 0.00 | 0.00 |
June | 60.71 | 3.99 | 56.72 | 54.27 | 28.85 | 0.00 | 0.00 | 0.00 |
July | 57.75 | 4.55 | 53.21 | 55.07 | 28.66 | 0.00 | 0.00 | 0.00 |
August | 46.91 | 1.43 | 45.48 | 45.24 | 28.90 | 0.00 | 0.00 | 0.00 |
September | 36.30 | 0.02 | 36.28 | 26.81 | 40.68 | 0.00 | 0.00 | 0.00 |
October | 24.86 | 0.00 | 24.86 | 13.34 | 44.23 | 0.00 | 0.00 | 0.00 |
November | 15.66 | 0.00 | 15.66 | 4.20 | 48.70 | 0.00 | 0.00 | 0.00 |
December | 11.75 | 0.00 | 11.75 | 1.06 | 61.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.37 | 1.00 | 34.38 | 26.18 | 42.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 1.06 | 28.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.71 | 4.55 | 56.72 | 55.07 | 61.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 14.54 | 48.34 | 0.00 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 36.88 | 43.32 | 0.00 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 72.97 | 35.74 | 0.00 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 125.38 | 31.22 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 163.57 | 32.68 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 179.22 | 29.34 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 192.12 | 30.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 154.43 | 31.24 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 103.02 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 56.27 | 39.51 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 21.61 | 39.14 | 0.00 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 12.56 | 49.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 94.71 | 37.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 12.56 | 29.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 192.12 | 49.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.22 | 5.21 | 18.01 | 20.99 | 30.85 | 9.33 | 0.00 | 0.00 |
February | 41.44 | 14.71 | 26.73 | 44.85 | 28.25 | 32.50 | 0.00 | 0.00 |
March | 70.63 | 30.62 | 40.01 | 81.04 | 25.51 | 5.33 | 0.00 | 0.00 |
April | 111.25 | 56.48 | 54.78 | 134.72 | 22.79 | 0.00 | 0.00 | 0.00 |
May | 143.63 | 73.44 | 70.20 | 172.02 | 26.01 | 0.00 | 0.00 | 0.00 |
June | 156.84 | 91.20 | 65.65 | 187.43 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 163.67 | 107.36 | 56.32 | 196.73 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 83.68 | 48.35 | 156.50 | 30.45 | 0.00 | 0.00 | 0.00 |
September | 93.93 | 52.38 | 41.55 | 106.08 | 36.61 | 0.00 | 0.00 | 0.00 |
October | 56.30 | 26.89 | 29.41 | 61.48 | 31.74 | 0.00 | 0.00 | 0.00 |
November | 27.73 | 7.42 | 20.30 | 27.19 | 26.97 | 15.83 | 0.00 | 0.00 |
December | 20.27 | 5.60 | 14.67 | 18.35 | 31.23 | 27.67 | 0.00 | 0.00 |
Annual Sum or Average | 87.00 | 46.45 | 40.56 | 100.93 | 28.46 | 90.67 | 0.00 | 0.00 |
Minimum of Months | 20.27 | 5.21 | 14.67 | 18.35 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.67 | 107.36 | 70.20 | 196.73 | 36.61 | 32.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108122E+09 | 32103306.91 | 76018307.89 | 57375825.97 | 0.266639E+09 |
February | 0.173500E+09 | 64623203.54 | 0.108876E+09 | 0.142212E+09 | 0.207439E+09 |
March | 0.270578E+09 | 91417062.02 | 0.179161E+09 | 0.256500E+09 | 0.188080E+09 |
April | 0.397495E+09 | 0.151668E+09 | 0.245827E+09 | 0.429954E+09 | 0.154863E+09 |
May | 0.529808E+09 | 0.215475E+09 | 0.314334E+09 | 0.591491E+09 | 0.163006E+09 |
June | 0.492944E+09 | 0.191424E+09 | 0.301520E+09 | 0.549763E+09 | 0.135248E+09 |
July | 0.630362E+09 | 0.331837E+09 | 0.298526E+09 | 0.756233E+09 | 0.139297E+09 |
August | 0.520365E+09 | 0.265426E+09 | 0.254938E+09 | 0.630778E+09 | 0.139688E+09 |
September | 0.411615E+09 | 0.198025E+09 | 0.213591E+09 | 0.464605E+09 | 0.177670E+09 |
October | 0.242222E+09 | 99092833.58 | 0.143129E+09 | 0.233966E+09 | 0.198359E+09 |
November | 0.116637E+09 | 33225367.21 | 83411214.22 | 78447299.15 | 0.209380E+09 |
December | 0.102253E+09 | 35867605.16 | 66385120.44 | 65431912.27 | 0.271469E+09 |
Annual Sum or Average | 0.399590E+10 | 0.171018E+10 | 0.228572E+10 | 0.425676E+10 | 0.225114E+10 |
Minimum of Months | 0.102253E+09 | 32103306.91 | 66385120.44 | 57375825.97 | 0.135248E+09 |
Maximum of Months | 0.630362E+09 | 0.331837E+09 | 0.314334E+09 | 0.756233E+09 | 0.271469E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108122E+09 | 32103306.91 | 76018307.89 | 57375825.97 | 0.266639E+09 |
February | 0.173500E+09 | 64623203.54 | 0.108876E+09 | 0.142212E+09 | 0.207439E+09 |
March | 0.270578E+09 | 91417062.02 | 0.179161E+09 | 0.256500E+09 | 0.188080E+09 |
April | 0.397495E+09 | 0.151668E+09 | 0.245827E+09 | 0.429954E+09 | 0.154863E+09 |
May | 0.529808E+09 | 0.215475E+09 | 0.314334E+09 | 0.591491E+09 | 0.163006E+09 |
June | 0.492944E+09 | 0.191424E+09 | 0.301520E+09 | 0.549763E+09 | 0.135248E+09 |
July | 0.630362E+09 | 0.331837E+09 | 0.298526E+09 | 0.756233E+09 | 0.139297E+09 |
August | 0.520365E+09 | 0.265426E+09 | 0.254938E+09 | 0.630778E+09 | 0.139688E+09 |
September | 0.411615E+09 | 0.198025E+09 | 0.213591E+09 | 0.464605E+09 | 0.177670E+09 |
October | 0.242222E+09 | 99092833.58 | 0.143129E+09 | 0.233966E+09 | 0.198359E+09 |
November | 0.116637E+09 | 33225367.21 | 83411214.22 | 78447299.15 | 0.209380E+09 |
December | 0.102253E+09 | 35867605.16 | 66385120.44 | 65431912.27 | 0.271469E+09 |
Annual Sum or Average | 0.399590E+10 | 0.171018E+10 | 0.228572E+10 | 0.425676E+10 | 0.225114E+10 |
Minimum of Months | 0.102253E+09 | 32103306.91 | 66385120.44 | 57375825.97 | 0.135248E+09 |
Maximum of Months | 0.630362E+09 | 0.331837E+09 | 0.314334E+09 | 0.756233E+09 | 0.271469E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37047291.95 | 0.00 | 37047291.95 | 4060415.40 | 0.163161E+09 |
February | 52067903.54 | 0.00 | 52067903.54 | 18400070.93 | 0.126833E+09 |
March | 84945400.62 | 1694.17 | 84943706.44 | 50586301.49 | 0.112780E+09 |
April | 0.116505E+09 | 564349.27 | 0.115940E+09 | 92053604.14 | 89498891.95 |
May | 0.154582E+09 | 4519910.97 | 0.150062E+09 | 0.132193E+09 | 92102904.81 |
June | 0.157369E+09 | 10354948.37 | 0.147015E+09 | 0.140670E+09 | 74782043.60 |
July | 0.154687E+09 | 12174915.22 | 0.142512E+09 | 0.147512E+09 | 76760778.59 |
August | 0.125656E+09 | 3832074.87 | 0.121824E+09 | 0.121174E+09 | 77395556.37 |
September | 94098771.83 | 60912.38 | 94037859.45 | 69482211.42 | 0.105432E+09 |
October | 66587274.63 | 0.00 | 66587274.63 | 35731215.80 | 0.118468E+09 |
November | 40590374.91 | 0.00 | 40590374.91 | 10886464.58 | 0.126233E+09 |
December | 31480644.54 | 0.00 | 31480644.54 | 2839367.05 | 0.163554E+09 |
Annual Sum or Average | 0.111562E+10 | 31508805.24 | 0.108411E+10 | 0.825590E+09 | 0.132700E+10 |
Minimum of Months | 31480644.54 | 0.00 | 31480644.54 | 2839367.05 | 74782043.60 |
Maximum of Months | 0.157369E+09 | 12174915.22 | 0.150062E+09 | 0.147512E+09 | 0.163554E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37045994.81 | 0.00 | 37045994.81 | 4059837.44 | 0.163161E+09 |
February | 52066167.00 | 0.00 | 52066167.00 | 18398554.78 | 0.126833E+09 |
March | 84942643.14 | 1694.10 | 84940949.04 | 50583473.02 | 0.112780E+09 |
April | 0.116501E+09 | 564322.82 | 0.115937E+09 | 92049496.45 | 89498703.66 |
May | 0.154578E+09 | 4519699.11 | 0.150058E+09 | 0.132187E+09 | 92102728.71 |
June | 0.157365E+09 | 10354463.02 | 0.147010E+09 | 0.140664E+09 | 74781878.53 |
July | 0.154683E+09 | 12174344.56 | 0.142508E+09 | 0.147507E+09 | 76760570.11 |
August | 0.125652E+09 | 3831895.25 | 0.121820E+09 | 0.121170E+09 | 77395228.52 |
September | 94095927.95 | 60909.52 | 94035018.43 | 69479094.76 | 0.105432E+09 |
October | 66585148.86 | 0.00 | 66585148.86 | 35729071.76 | 0.118467E+09 |
November | 40588964.18 | 0.00 | 40588964.18 | 10885401.58 | 0.126233E+09 |
December | 31479558.13 | 0.00 | 31479558.13 | 2838954.42 | 0.163554E+09 |
Annual Sum or Average | 0.111558E+10 | 31507328.38 | 0.108408E+10 | 0.825552E+09 | 0.132700E+10 |
Minimum of Months | 31479558.13 | 0.00 | 31479558.13 | 2838954.42 | 74781878.53 |
Maximum of Months | 0.157365E+09 | 12174344.56 | 0.150058E+09 | 0.147507E+09 | 0.163554E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_17
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_16
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_15
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 38937919.18 | 0.129473E+09 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 89215398.86 | 0.104789E+09 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.195440E+09 | 95737452.24 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.324974E+09 | 80917465.55 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.438098E+09 | 87541290.32 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.464535E+09 | 76060131.47 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.514585E+09 | 80967920.96 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.413619E+09 | 83676065.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.267030E+09 | 0.101401E+09 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.150700E+09 | 0.105815E+09 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 56019307.36 | 0.101439E+09 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 33639806.92 | 0.132213E+09 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.298679E+10 | 0.118003E+10 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 33639806.92 | 76060131.47 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.514585E+09 | 0.132213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C6
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C4
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8_C5
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62192068.95 | 13958828.96 | 48233239.99 | 56230738.97 | 82616094.90 |
February | 0.100254E+09 | 35577293.77 | 64677083.55 | 0.108497E+09 | 68330948.78 |
March | 0.189182E+09 | 82007905.78 | 0.107174E+09 | 0.217047E+09 | 68316724.31 |
April | 0.288365E+09 | 0.146384E+09 | 0.141981E+09 | 0.349187E+09 | 59083481.93 |
May | 0.384701E+09 | 0.196689E+09 | 0.188012E+09 | 0.460732E+09 | 69663318.59 |
June | 0.406537E+09 | 0.236383E+09 | 0.170153E+09 | 0.485816E+09 | 61431511.70 |
July | 0.438386E+09 | 0.287547E+09 | 0.150839E+09 | 0.526915E+09 | 72936451.71 |
August | 0.353641E+09 | 0.224141E+09 | 0.129500E+09 | 0.419159E+09 | 81552867.42 |
September | 0.243467E+09 | 0.135765E+09 | 0.107702E+09 | 0.274961E+09 | 94895860.89 |
October | 0.150797E+09 | 72023332.59 | 78773668.65 | 0.164660E+09 | 85005372.59 |
November | 71870075.69 | 19245249.25 | 52624826.44 | 70472931.69 | 69912178.54 |
December | 54304200.85 | 15003838.47 | 39300362.38 | 49141092.01 | 83635170.54 |
Annual Sum or Average | 0.274370E+10 | 0.146473E+10 | 0.127897E+10 | 0.318282E+10 | 0.897380E+09 |
Minimum of Months | 54304200.85 | 13958828.96 | 39300362.38 | 49141092.01 | 59083481.93 |
Maximum of Months | 0.438386E+09 | 0.287547E+09 | 0.188012E+09 | 0.526915E+09 | 94895860.89 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.57 | 316.63 | 108.40 | 23.97 | 84.43 | 0.00 | 0.00 |
February | 129.66 | 273.23 | 186.48 | 53.43 | 133.06 | 0.00 | 0.00 |
March | 227.39 | 222.74 | 265.47 | 68.26 | 197.21 | 0.00 | 0.00 |
April | 402.03 | 187.80 | 396.60 | 117.46 | 279.14 | 0.00 | 0.00 |
May | 538.82 | 188.93 | 511.04 | 164.27 | 346.77 | 0.00 | 0.00 |
June | 530.02 | 159.34 | 501.78 | 155.69 | 346.09 | 0.00 | 0.00 |
July | 672.16 | 158.66 | 586.21 | 256.88 | 329.33 | 0.00 | 0.00 |
August | 560.33 | 160.94 | 482.39 | 201.06 | 281.33 | 0.00 | 0.00 |
September | 410.75 | 217.09 | 390.21 | 152.84 | 237.37 | 0.00 | 0.00 |
October | 199.40 | 234.59 | 230.59 | 73.99 | 156.60 | 0.00 | 0.00 |
November | 66.76 | 256.79 | 121.32 | 25.64 | 95.68 | 0.00 | 0.00 |
December | 47.69 | 321.55 | 99.86 | 26.78 | 73.08 | 0.00 | 0.00 |
Annual Sum or Average | 320.07 | 224.67 | 324.17 | 110.46 | 213.71 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 158.66 | 99.86 | 23.97 | 73.08 | 0.00 | 0.00 |
Maximum of Months | 672.16 | 321.55 | 586.21 | 256.88 | 346.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 247.14 | 821.77 | 394.74 | 88.60 | 306.14 | 0.00 | 0.00 |
February | 626.93 | 736.36 | 704.50 | 250.01 | 454.49 | 0.00 | 0.00 |
March | 1240.47 | 607.65 | 1200.75 | 520.51 | 680.24 | 0.00 | 0.00 |
April | 2131.39 | 530.71 | 1891.28 | 960.08 | 931.20 | 0.00 | 0.00 |
May | 2780.64 | 555.63 | 2441.73 | 1248.40 | 1193.33 | 0.00 | 0.00 |
June | 3046.72 | 498.85 | 2666.33 | 1550.35 | 1115.97 | 0.00 | 0.00 |
July | 3266.11 | 513.91 | 2782.47 | 1825.08 | 957.39 | 0.00 | 0.00 |
August | 2625.27 | 531.10 | 2244.59 | 1422.64 | 821.94 | 0.00 | 0.00 |
September | 1751.36 | 665.06 | 1596.81 | 890.43 | 706.38 | 0.00 | 0.00 |
October | 956.51 | 671.62 | 957.12 | 457.14 | 499.98 | 0.00 | 0.00 |
November | 367.41 | 665.30 | 471.37 | 126.22 | 345.15 | 0.00 | 0.00 |
December | 213.51 | 839.16 | 344.67 | 95.23 | 249.44 | 0.00 | 0.00 |
Annual Sum or Average | 1610.08 | 636.11 | 1479.03 | 789.58 | 689.45 | 0.00 | 0.00 |
Minimum of Months | 213.51 | 498.85 | 344.67 | 88.60 | 249.44 | 0.00 | 0.00 |
Maximum of Months | 3266.11 | 839.16 | 2782.47 | 1825.08 | 1193.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3233.95 | 7950.34 | 1114.55 | 250.16 | 864.39 | 0.00 | 0.00 |
February | 7160.25 | 7021.02 | 1989.17 | 705.90 | 1283.28 | 0.00 | 0.00 |
March | 12181.43 | 4365.28 | 3390.35 | 1469.68 | 1920.68 | 0.00 | 0.00 |
April | 21564.37 | 3386.79 | 5340.09 | 2710.81 | 2629.28 | 0.00 | 0.00 |
May | 27573.39 | 3771.00 | 6894.28 | 3524.89 | 3369.39 | 0.00 | 0.00 |
June | 29834.59 | 3420.57 | 7528.45 | 4377.47 | 3150.98 | 0.00 | 0.00 |
July | 33317.84 | 4015.63 | 7856.38 | 5153.17 | 2703.21 | 0.00 | 0.00 |
August | 25599.01 | 4566.66 | 6337.65 | 4016.87 | 2320.78 | 0.00 | 0.00 |
September | 15929.70 | 5506.35 | 4508.65 | 2514.16 | 1994.49 | 0.00 | 0.00 |
October | 10123.85 | 4868.41 | 2702.46 | 1290.74 | 1411.71 | 0.00 | 0.00 |
November | 4103.88 | 5155.81 | 1330.93 | 356.39 | 974.53 | 0.00 | 0.00 |
December | 2771.59 | 7233.43 | 973.19 | 268.89 | 704.31 | 0.00 | 0.00 |
Annual Sum or Average | 16170.67 | 5097.45 | 4176.10 | 2229.41 | 1946.68 | 0.00 | 0.00 |
Minimum of Months | 2771.59 | 3386.79 | 973.19 | 250.16 | 704.31 | 0.00 | 0.00 |
Maximum of Months | 33317.84 | 7950.34 | 7856.38 | 5153.17 | 3369.39 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111330E+09 | 0.848058E+09 | 0.290337E+09 | 64206613.83 | 0.226130E+09 | 0.00 | 0.00 |
February | 0.313667E+09 | 0.660989E+09 | 0.451133E+09 | 0.129246E+09 | 0.321887E+09 | 0.00 | 0.00 |
March | 0.609034E+09 | 0.596583E+09 | 0.711045E+09 | 0.182838E+09 | 0.528207E+09 | 0.00 | 0.00 |
April | 0.104206E+10 | 0.486777E+09 | 0.102799E+10 | 0.304464E+09 | 0.723531E+09 | 0.00 | 0.00 |
May | 0.144317E+10 | 0.506024E+09 | 0.136878E+10 | 0.439989E+09 | 0.928788E+09 | 0.00 | 0.00 |
June | 0.137381E+10 | 0.413010E+09 | 0.130062E+10 | 0.403557E+09 | 0.897065E+09 | 0.00 | 0.00 |
July | 0.180032E+10 | 0.424949E+09 | 0.157009E+10 | 0.688022E+09 | 0.882072E+09 | 0.00 | 0.00 |
August | 0.150080E+10 | 0.431064E+09 | 0.129204E+10 | 0.538517E+09 | 0.753520E+09 | 0.00 | 0.00 |
September | 0.106465E+10 | 0.562685E+09 | 0.101143E+10 | 0.396171E+09 | 0.615254E+09 | 0.00 | 0.00 |
October | 0.534066E+09 | 0.628327E+09 | 0.617616E+09 | 0.198186E+09 | 0.419431E+09 | 0.00 | 0.00 |
November | 0.173047E+09 | 0.665607E+09 | 0.314453E+09 | 66450734.41 | 0.248002E+09 | 0.00 | 0.00 |
December | 0.127730E+09 | 0.861235E+09 | 0.267466E+09 | 71735210.31 | 0.195730E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100937E+11 | 0.708531E+10 | 0.102230E+11 | 0.348338E+10 | 0.673962E+10 | 0.00 | 0.00 |
Minimum of Months | 0.111330E+09 | 0.413010E+09 | 0.267466E+09 | 64206613.83 | 0.195730E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180032E+10 | 0.861235E+09 | 0.157009E+10 | 0.688022E+09 | 0.928788E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.661945E+09 | 0.220104E+10 | 0.105727E+10 | 0.237300E+09 | 0.819965E+09 | 0.00 | 0.00 |
February | 0.151666E+10 | 0.178141E+10 | 0.170432E+10 | 0.604814E+09 | 0.109951E+10 | 0.00 | 0.00 |
March | 0.332248E+10 | 0.162754E+10 | 0.321609E+10 | 0.139413E+10 | 0.182195E+10 | 0.00 | 0.00 |
April | 0.552455E+10 | 0.137560E+10 | 0.490220E+10 | 0.248853E+10 | 0.241368E+10 | 0.00 | 0.00 |
May | 0.744767E+10 | 0.148820E+10 | 0.653992E+10 | 0.334371E+10 | 0.319621E+10 | 0.00 | 0.00 |
June | 0.789709E+10 | 0.129302E+10 | 0.691112E+10 | 0.401852E+10 | 0.289260E+10 | 0.00 | 0.00 |
July | 0.874795E+10 | 0.137645E+10 | 0.745256E+10 | 0.488830E+10 | 0.256426E+10 | 0.00 | 0.00 |
August | 0.703152E+10 | 0.142249E+10 | 0.601190E+10 | 0.381040E+10 | 0.220149E+10 | 0.00 | 0.00 |
September | 0.453951E+10 | 0.172382E+10 | 0.413894E+10 | 0.230800E+10 | 0.183094E+10 | 0.00 | 0.00 |
October | 0.256191E+10 | 0.179886E+10 | 0.256355E+10 | 0.122440E+10 | 0.133915E+10 | 0.00 | 0.00 |
November | 0.952328E+09 | 0.172446E+10 | 0.122179E+10 | 0.327169E+09 | 0.894622E+09 | 0.00 | 0.00 |
December | 0.571877E+09 | 0.224762E+10 | 0.923171E+09 | 0.255065E+09 | 0.668106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.507755E+11 | 0.200605E+11 | 0.466428E+11 | 0.249003E+11 | 0.217425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.571877E+09 | 0.129302E+10 | 0.923171E+09 | 0.237300E+09 | 0.668106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.874795E+10 | 0.224762E+10 | 0.745256E+10 | 0.488830E+10 | 0.319621E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866180E+10 | 0.212942E+11 | 0.298522E+10 | 0.670024E+09 | 0.231520E+10 | 0.00 | 0.00 |
February | 0.173221E+11 | 0.169853E+11 | 0.481221E+10 | 0.170771E+10 | 0.310450E+10 | 0.00 | 0.00 |
March | 0.326268E+11 | 0.116920E+11 | 0.908072E+10 | 0.393638E+10 | 0.514434E+10 | 0.00 | 0.00 |
April | 0.558948E+11 | 0.877856E+10 | 0.138415E+11 | 0.702643E+10 | 0.681509E+10 | 0.00 | 0.00 |
May | 0.738526E+11 | 0.101002E+11 | 0.184657E+11 | 0.944107E+10 | 0.902458E+10 | 0.00 | 0.00 |
June | 0.773313E+11 | 0.886611E+10 | 0.195138E+11 | 0.113464E+11 | 0.816735E+10 | 0.00 | 0.00 |
July | 0.892385E+11 | 0.107555E+11 | 0.210425E+11 | 0.138023E+11 | 0.724027E+10 | 0.00 | 0.00 |
August | 0.685644E+11 | 0.122313E+11 | 0.169748E+11 | 0.107588E+11 | 0.621598E+10 | 0.00 | 0.00 |
September | 0.412898E+11 | 0.142725E+11 | 0.116864E+11 | 0.651670E+10 | 0.516972E+10 | 0.00 | 0.00 |
October | 0.271157E+11 | 0.130395E+11 | 0.723826E+10 | 0.345712E+10 | 0.378114E+10 | 0.00 | 0.00 |
November | 0.106373E+11 | 0.133639E+11 | 0.344976E+10 | 0.923772E+09 | 0.252599E+10 | 0.00 | 0.00 |
December | 0.742342E+10 | 0.193740E+11 | 0.260660E+10 | 0.720184E+09 | 0.188642E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.509958E+12 | 0.160753E+12 | 0.131697E+12 | 0.703068E+11 | 0.613906E+11 | 0.00 | 0.00 |
Minimum of Months | 0.742342E+10 | 0.877856E+10 | 0.260660E+10 | 0.670024E+09 | 0.188642E+10 | 0.00 | 0.00 |
Maximum of Months | 0.892385E+11 | 0.212942E+11 | 0.210425E+11 | 0.138023E+11 | 0.902458E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.936208E+09 | -848749069.2 | 0.00 | 0.00 | 744.00 | 0.00 | -87459276.9 | 58.99 | 0.00 | 0.00 |
February | 0.863382E+09 | -785126571.5 | 0.00 | 0.00 | 672.00 | 0.00 | -78255876.6 | 58.99 | 0.00 | 0.00 |
March | 0.991795E+09 | -907205747.9 | 0.00 | 0.00 | 744.00 | 0.00 | -84588965.3 | 59.00 | 0.00 | 0.00 |
April | 0.898706E+09 | -819655958.6 | 0.00 | 0.00 | 720.00 | 0.00 | -79050285.8 | 58.99 | 0.00 | 0.00 |
May | 0.897269E+09 | -820648259.6 | 0.00 | 0.00 | 744.00 | 0.00 | -76621014.9 | 58.99 | 0.00 | 0.00 |
June | 0.858532E+09 | -786767864.2 | 0.00 | 0.00 | 720.00 | 0.00 | -71764073.2 | 58.99 | 0.00 | 0.00 |
July | 0.811305E+09 | -739279156.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72026166.6 | 58.99 | 0.00 | 0.00 |
August | 0.859334E+09 | -787240978.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72093095.9 | 59.00 | 0.00 | 0.00 |
September | 0.812974E+09 | -741737441.8 | 0.00 | 0.00 | 720.00 | 0.00 | -71236090.1 | 59.00 | 0.00 | 0.00 |
October | 0.846966E+09 | -767149655.4 | 0.00 | 0.00 | 744.00 | 0.00 | -79816282.4 | 58.99 | 0.00 | 0.00 |
November | 0.848365E+09 | -766212313.0 | 0.00 | 0.00 | 720.00 | 0.00 | -82152446.2 | 59.00 | 0.00 | 0.00 |
December | 0.914103E+09 | -827209324.7 | 0.00 | 0.00 | 744.00 | 0.00 | -86893949.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.105389E+11 | -0.959698E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -941957523.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.811305E+09 | -907205747.9 | 0.00 | 0.00 | 672.00 | 0.00 | -87459276.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.991795E+09 | -739279156.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71236090.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.82 | 0.38 | 22-JAN-12:20 | 150.09 | 0.00 | 0.00 | 1.50 | 111.48 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.71 | 0.26 | 10-FEB-11:30 | 193.86 | 0.00 | 0.00 | 42.17 | 455.30 | 0.00 | 0.00 | 27.17 |
March | 247.00 | 0.60 | 0.26 | 04-MAR-11:00 | 274.51 | 0.00 | 0.00 | 108.83 | 305.89 | 0.00 | 0.00 | 61.83 |
April | 379.50 | 0.56 | 0.26 | 01-APR-10:39 | 320.01 | 0.00 | 0.00 | 178.17 | 243.43 | 0.00 | 0.00 | 126.33 |
May | 427.83 | 0.53 | 0.26 | 01-MAY-09:30 | 385.44 | 0.00 | 0.00 | 235.00 | 290.40 | 0.00 | 0.00 | 173.83 |
June | 375.17 | 0.54 | 0.26 | 01-JUN-09:00 | 352.20 | 0.00 | 0.00 | 231.83 | 1145.16 | 0.00 | 0.00 | 172.83 |
July | 471.00 | 0.61 | 0.26 | 01-JUL-11:39 | 303.62 | 0.00 | 0.00 | 181.83 | 232.46 | 0.00 | 0.00 | 134.00 |
August | 366.67 | 0.61 | 0.26 | 01-AUG-08:30 | 422.04 | 0.00 | 0.00 | 161.00 | 216.40 | 0.00 | 0.00 | 97.00 |
September | 301.17 | 0.57 | 0.26 | 01-SEP-11:50 | 1254.30 | 0.00 | 0.00 | 137.00 | 221.52 | 0.00 | 0.00 | 72.67 |
October | 245.33 | 0.69 | 0.26 | 01-OCT-11:00 | 209.66 | 0.00 | 0.00 | 51.67 | 165.86 | 0.00 | 0.00 | 19.00 |
November | 242.67 | 0.79 | 0.38 | 01-NOV-12:20 | 164.96 | 0.00 | 0.00 | 3.00 | 122.02 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.85 | 0.38 | 10-DEC-12:20 | 129.51 | 0.00 | 0.00 | 0.50 | 100.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.63 | 366.19 | 0.00 | 0.00 | 1332.50 | 325.39 | 0.00 | 0.00 | 884.67 | ||
Minimum of Months | 160.33 | 0.53 | 0.26 | 129.51 | 0.00 | 0.00 | 0.50 | 100.91 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.85 | 0.38 | 1254.30 | 0.00 | 0.00 | 235.00 | 1145.16 | 0.00 | 0.00 | 173.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.60 | 0.26 | 02-JAN-11:20 | 171.84 | 14.85 | 0.33 | 76.50 | 141.46 | 15.43 | 0.83 | 36.00 |
February | 259.50 | 0.51 | 0.26 | 01-FEB-11:20 | 224.56 | 16.52 | 18.17 | 128.50 | 184.55 | 17.17 | 31.00 | 96.33 |
March | 247.00 | 0.44 | 0.26 | 01-MAR-09:50 | 853.19 | 19.04 | 69.50 | 225.33 | 821.40 | 19.02 | 80.00 | 188.67 |
April | 379.50 | 0.41 | 0.26 | 01-APR-08:09 | 649.89 | 19.24 | 124.67 | 279.83 | 617.29 | 19.50 | 137.50 | 241.17 |
May | 427.83 | 0.39 | 0.26 | 01-MAY-07:30 | 1365.46 | 20.24 | 148.00 | 329.00 | 369.13 | 19.74 | 163.50 | 289.00 |
June | 375.17 | 0.40 | 0.26 | 01-JUN-07:19 | 417.87 | 18.95 | 131.50 | 330.50 | 628.12 | 21.00 | 152.50 | 301.83 |
July | 471.00 | 0.46 | 0.26 | 01-JUL-06:30 | 356.06 | 17.23 | 97.83 | 306.33 | 1200.23 | 19.66 | 137.67 | 273.17 |
August | 366.67 | 0.44 | 0.26 | 01-AUG-06:30 | 331.72 | 18.04 | 102.17 | 291.17 | 620.83 | 19.45 | 127.33 | 252.00 |
September | 301.17 | 0.41 | 0.26 | 01-SEP-07:00 | 334.20 | 18.53 | 75.50 | 247.33 | 269.41 | 19.33 | 91.33 | 202.33 |
October | 245.33 | 0.49 | 0.26 | 01-OCT-08:39 | 248.37 | 16.94 | 39.50 | 181.17 | 611.94 | 19.24 | 63.33 | 147.00 |
November | 242.67 | 0.55 | 0.26 | 01-NOV-10:30 | 188.91 | 15.55 | 2.17 | 96.50 | 155.81 | 16.13 | 5.83 | 57.17 |
December | 160.33 | 0.65 | 0.26 | 01-DEC-10:20 | 152.85 | 14.96 | 0.00 | 40.67 | 124.95 | 15.64 | 0.00 | 12.83 |
Annual Sum or Average | 3714.00 | 0.46 | 489.70 | 17.83 | 809.33 | 2532.83 | 536.97 | 18.82 | 990.83 | 2097.50 | ||
Minimum of Months | 160.33 | 0.39 | 0.26 | 152.85 | 14.85 | 0.00 | 40.67 | 124.95 | 15.43 | 0.00 | 12.83 | |
Maximum of Months | 471.00 | 0.65 | 0.26 | 1365.46 | 20.24 | 148.00 | 330.50 | 1200.23 | 21.00 | 163.50 | 301.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.474395E+10 | 26820.50 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345204E+10 | 26820.50 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198483E+10 | 26820.50 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783616E+09 | 26820.50 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57569931.27 | 11385.07 | 24-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1449153.40 | 3408.83 | 14-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2215921.48 | 7725.37 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363202E+09 | 26820.50 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225855E+10 | 26820.50 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388057E+10 | 26820.50 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.474395E+10 | 26820.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.870058E+10 | 62713.69 | 17-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598125E+10 | 87174.47 | 19-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.565197E+09 | 28262.92 | 29-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3623378.15 | 18692.38 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164387E+10 | 40909.75 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552365E+10 | 53358.08 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.870058E+10 | 87174.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193204E+11 | 36337.24 | 15-JAN-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137338E+11 | 55025.83 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.264792E+09 | 10922.82 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822375E+10 | 28343.73 | 22-DEC-22:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193204E+11 | 55025.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 565.96 | 565.96 | 0.48 | 18-MAR-14:00 | 0.48 | 0.00 |
April | 0.00 | 0.00 | 0.242172E+09 | 0.230843E+09 | 6800.02 | 27-APR-16:00 | 6302.45 | 0.00 |
May | 0.00 | 0.00 | 0.598533E+09 | 0.535172E+09 | 16972.17 | 06-MAY-07:02 | 12671.55 | 0.00 |
June | 0.00 | 0.00 | 0.128102E+10 | 0.121662E+10 | 16305.17 | 10-JUN-07:02 | 14060.69 | 0.00 |
July | 0.00 | 0.00 | 0.340780E+10 | 0.292650E+10 | 18071.85 | 31-JUL-07:02 | 13168.66 | 0.00 |
August | 0.00 | 0.00 | 0.463392E+10 | 0.394858E+10 | 18179.74 | 25-AUG-07:02 | 12398.74 | 0.00 |
September | 0.00 | 0.00 | 0.136950E+10 | 0.112411E+10 | 16876.04 | 23-SEP-07:02 | 10148.05 | 0.00 |
October | 0.00 | 0.00 | 37603422.66 | 37598870.69 | 3545.60 | 04-OCT-15:00 | 3545.60 | 0.00 |
November | 0.00 | 0.00 | 8724529.50 | 6632963.27 | 1373.24 | 04-NOV-15:00 | 1057.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115793E+11 | 0.100261E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.463392E+10 | 0.394858E+10 | 18179.74 | 14060.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 23134360.48 | 22015072.04 | 3870.00 | 27-APR-16:00 | 3655.98 | 0.00 |
May | 0.00 | 0.00 | 55385822.16 | 53395050.70 | 4632.54 | 15-MAY-16:00 | 4632.54 | 0.00 |
June | 0.00 | 0.00 | 0.790369E+09 | 0.768289E+09 | 55714.68 | 22-JUN-17:51 | 50389.55 | 0.00 |
July | 0.00 | 0.00 | 0.435652E+10 | 0.389693E+10 | 58825.38 | 27-JUL-17:11 | 46191.45 | 0.00 |
August | 0.00 | 0.00 | 0.632497E+10 | 0.566292E+10 | 57592.46 | 24-AUG-19:35 | 47117.93 | 0.00 |
September | 0.00 | 0.00 | 0.605601E+09 | 0.505166E+09 | 56629.57 | 14-SEP-17:12 | 48732.32 | 0.00 |
October | 0.00 | 0.00 | 10.91 | 10.91 | 0.01 | 04-OCT-13:20 | 0.01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121560E+11 | 0.109087E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.632497E+10 | 0.566292E+10 | 58825.38 | 50389.55 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.260172E+09 | 0.04 | 170.28 | 01-JAN-00:03 | 0.08 |
February | 0.158656E+09 | 0.03 | 170.28 | 01-FEB-00:10 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 10505994.32 | 0.00 | 170.28 | 29-NOV-18:30 | 0.08 |
December | 0.166133E+09 | 0.03 | 170.28 | 01-DEC-05:40 | 0.08 |
Annual Sum or Average | 0.595467E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260172E+09 | 0.04 | 170.28 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116898E+10 | 0.39 | 1160.52 | 05-JAN-13:50 | 0.92 |
February | 0.107246E+10 | 0.39 | 1160.52 | 02-FEB-14:20 | 0.92 |
March | 0.124557E+10 | 0.38 | 1160.52 | 03-MAR-10:00 | 0.92 |
April | 0.115001E+10 | 0.35 | 1160.52 | 06-APR-12:00 | 0.92 |
May | 0.119487E+10 | 0.35 | 1160.52 | 03-MAY-07:00 | 0.92 |
June | 0.119487E+10 | 0.36 | 1160.52 | 01-JUN-16:50 | 0.92 |
July | 0.114891E+10 | 0.34 | 1160.52 | 13-JUL-11:40 | 0.91 |
August | 0.124083E+10 | 0.36 | 1160.52 | 01-AUG-16:50 | 0.92 |
September | 0.114891E+10 | 0.35 | 1160.52 | 02-SEP-11:00 | 0.91 |
October | 0.114891E+10 | 0.34 | 1160.52 | 16-OCT-07:50 | 0.92 |
November | 0.110764E+10 | 0.35 | 1160.52 | 07-NOV-07:40 | 0.92 |
December | 0.116004E+10 | 0.36 | 1160.52 | 01-DEC-16:10 | 0.92 |
Annual Sum or Average | 0.139820E+11 | 0.36 | |||
Minimum of Months | 0.107246E+10 | 0.34 | 1160.52 | 0.91 | |
Maximum of Months | 0.124557E+10 | 0.39 | 1160.52 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.312279E+10 | 0.67 | 2832.01 | 02-JAN-07:05 | 0.89 |
February | 0.279120E+10 | 0.57 | 2832.01 | 04-FEB-07:01 | 0.89 |
March | 0.304943E+10 | 0.39 | 2832.01 | 06-MAR-07:02 | 0.89 |
April | 0.280369E+10 | 0.34 | 2832.01 | 01-APR-06:01 | 0.89 |
May | 0.291584E+10 | 0.34 | 2832.01 | 04-MAY-14:30 | 0.89 |
June | 0.292782E+10 | 0.35 | 2832.01 | 10-JUN-13:10 | 0.89 |
July | 0.287723E+10 | 0.34 | 2832.01 | 07-JUL-12:20 | 0.88 |
August | 0.309202E+10 | 0.37 | 2832.01 | 23-AUG-13:20 | 0.88 |
September | 0.280830E+10 | 0.34 | 2832.01 | 08-SEP-14:50 | 0.89 |
October | 0.280369E+10 | 0.33 | 2832.01 | 04-OCT-13:20 | 0.89 |
November | 0.275388E+10 | 0.42 | 2832.01 | 20-NOV-07:01 | 0.89 |
December | 0.300961E+10 | 0.60 | 2832.01 | 02-DEC-07:01 | 0.89 |
Annual Sum or Average | 0.349555E+11 | 0.42 | |||
Minimum of Months | 0.275388E+10 | 0.33 | 2832.01 | 0.88 | |
Maximum of Months | 0.312279E+10 | 0.67 | 2832.01 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.116898E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107246E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124557E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120934E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.133652E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.149866E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.195171E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.234257E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.146909E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115802E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110978E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116004E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.167228E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107246E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.234257E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.312279E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.279120E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.304943E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.280996E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.293022E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.312437E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.396366E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.470672E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.295999E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.280369E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.275388E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.300961E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.380255E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.275388E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.470672E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116898E+10 | 0.00 | 0.474395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107246E+10 | 0.00 | 0.345204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124557E+10 | 565.96 | 0.198483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115001E+10 | 0.242172E+09 | 0.783616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119487E+10 | 0.598533E+09 | 57569931.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119487E+10 | 0.128102E+10 | 1449153.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114891E+10 | 0.340780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124083E+10 | 0.463392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114891E+10 | 0.136950E+10 | 2215921.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114891E+10 | 37603422.66 | 0.363202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110764E+10 | 8724529.50 | 0.225855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116004E+10 | 0.00 | 0.388057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139820E+11 | 0.115793E+11 | 0.175280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124557E+10 | 0.463392E+10 | 0.474395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.312279E+10 | 0.00 | 0.870058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279120E+10 | 0.00 | 0.598125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304943E+10 | 0.00 | 0.565197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280369E+10 | 23134360.48 | 3623378.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291584E+10 | 55385822.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.292782E+10 | 0.790369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287723E+10 | 0.435652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.309202E+10 | 0.632497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280830E+10 | 0.605601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280369E+10 | 10.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275388E+10 | 0.00 | 0.164387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300961E+10 | 0.00 | 0.552365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349555E+11 | 0.121560E+11 | 0.224182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312279E+10 | 0.632497E+10 | 0.870058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124557E+10 | 0.00 | 0.00 | 0.00 | 141.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115001E+10 | 0.00 | 0.00 | 0.00 | 59330103.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119487E+10 | 0.00 | 0.00 | 0.00 | 0.141653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119487E+10 | 0.00 | 0.00 | 0.00 | 0.303794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114891E+10 | 0.00 | 0.00 | 0.00 | 0.802802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124083E+10 | 0.00 | 0.00 | 0.00 | 0.110175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114891E+10 | 0.00 | 0.00 | 0.00 | 0.320176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114891E+10 | 0.00 | 0.00 | 0.00 | 9106572.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110764E+10 | 0.00 | 0.00 | 0.00 | 2143713.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139820E+11 | 0.00 | 0.00 | 0.00 | 0.274075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124557E+10 | 0.00 | 0.00 | 0.00 | 0.110175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.312279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280369E+10 | 0.00 | 0.00 | 0.00 | 6261288.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291584E+10 | 0.00 | 0.00 | 0.00 | 14382265.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.292782E+10 | 0.00 | 0.00 | 0.00 | 0.196554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287723E+10 | 0.00 | 0.00 | 0.00 | 0.108644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.309202E+10 | 0.00 | 0.00 | 0.00 | 0.161470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280830E+10 | 0.00 | 0.00 | 0.00 | 0.151688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280369E+10 | 0.00 | 0.00 | 0.00 | 2.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349555E+11 | 0.00 | 0.00 | 0.00 | 0.307002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312279E+10 | 0.00 | 0.00 | 0.00 | 0.161470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 30873091.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188940E+10 | 0.00 | 0.00 | 0.12 |
February | 0.239996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135987E+10 | 0.00 | 0.00 | 0.13 |
March | 0.747969E+09 | 0.00 | 0.00 | 6833.43 | 0.00 | 0.856483E+09 | 29670156.91 | 0.00 | 0.14 |
April | 0.900996E+09 | 5218495.46 | 0.00 | 440876.91 | 0.00 | 0.256216E+09 | 0.381113E+09 | 0.00 | 0.18 |
May | 0.365068E+09 | 10094341.82 | 0.00 | 2822949.95 | 0.00 | 8122271.13 | 0.234780E+10 | 0.00 | 0.40 |
June | 0.116029E+09 | 5611614.99 | 0.00 | 5086373.54 | 0.00 | 740270.65 | 0.330956E+10 | 0.00 | 0.62 |
July | 7853675.96 | 69597978.65 | 0.00 | 6415576.98 | 0.00 | 0.00 | 0.293957E+10 | 0.00 | 0.71 |
August | 9991186.96 | 0.160114E+09 | 0.00 | 5619442.49 | 0.00 | 0.00 | 0.254017E+10 | 0.00 | 0.65 |
September | 0.112813E+09 | 18471123.27 | 0.00 | 4815403.51 | 0.00 | 580697.98 | 0.321373E+10 | 0.00 | 0.60 |
October | 0.844631E+09 | 0.00 | 0.00 | 909423.48 | 0.00 | 0.106163E+09 | 0.101160E+10 | 0.00 | 0.21 |
November | 0.484521E+09 | 0.00 | 0.00 | 52580.95 | 0.00 | 0.101654E+10 | 65640370.47 | 0.00 | 0.14 |
December | 0.116761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170566E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.397750E+10 | 0.269108E+09 | 0.00 | 26169461.25 | 0.00 | 0.719977E+10 | 0.158388E+11 | 0.00 | 0.34 |
Minimum of Months | 7853675.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.900996E+09 | 0.160114E+09 | 0.00 | 6415576.98 | 0.00 | 0.188940E+10 | 0.330956E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.520149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241652E+09 | 0.00 | 0.00 | 0.17 |
February | 0.433727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244980E+09 | 0.00 | 0.00 | 0.18 |
March | 0.490908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
April | 0.428680E+10 | 0.00 | 0.00 | 567.30 | 3666318.87 | 0.00 | 635515.88 | 0.00 | 0.19 |
May | 0.483144E+10 | 0.00 | 0.00 | 498299.54 | 0.00 | 0.00 | 0.699952E+09 | 0.00 | 0.22 |
June | 0.367890E+10 | 33812.83 | 0.00 | 3043013.22 | 0.00 | 0.00 | 0.264481E+10 | 0.00 | 0.31 |
July | 0.130918E+10 | 44202676.90 | 0.00 | 9614520.30 | 0.00 | 0.00 | 0.606104E+10 | 0.00 | 0.47 |
August | 0.134655E+10 | 0.145935E+09 | 0.00 | 8033313.41 | 0.00 | 0.00 | 0.501264E+10 | 0.00 | 0.45 |
September | 0.349394E+10 | 0.00 | 0.00 | 3502674.12 | 0.00 | 0.00 | 0.325275E+10 | 0.00 | 0.31 |
October | 0.485394E+10 | 0.00 | 0.00 | 26451.92 | 0.00 | 0.00 | 70548523.21 | 0.00 | 0.18 |
November | 0.461082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33309241.20 | 0.00 | 0.00 | 0.17 |
December | 0.517994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68848489.83 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.480393E+11 | 0.190172E+09 | 0.00 | 24718839.82 | 3666318.87 | 0.588790E+09 | 0.177424E+11 | 0.00 | 0.25 |
Minimum of Months | 0.130918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.520149E+10 | 0.145935E+09 | 0.00 | 9614520.30 | 3666318.87 | 0.244980E+09 | 0.606104E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:40
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.842204E+11 | 0.410585E+11 | 0.00 | 0.736341E+10 | 0.112712E+11 |
February | 0.237050E+12 | 0.347463E+11 | 0.00 | 0.618212E+10 | 0.791017E+10 |
March | 0.491330E+12 | 0.366389E+11 | 0.00 | 0.654321E+10 | 0.122950E+10 |
April | 0.803894E+12 | 0.352040E+11 | 0.00 | 0.581731E+10 | 0.700309E+09 |
May | 0.108970E+13 | 0.462917E+11 | 0.00 | 0.824561E+10 | 0.838529E+09 |
June | 0.111009E+13 | 0.437817E+11 | 0.00 | 0.975307E+10 | 0.257250E+10 |
July | 0.119436E+13 | 0.434376E+11 | 0.00 | 0.102326E+11 | 0.965356E+10 |
August | 0.938940E+12 | 0.441931E+11 | 0.00 | 0.862653E+10 | 0.136753E+11 |
September | 0.655713E+12 | 0.325814E+11 | 0.00 | 0.100637E+11 | 0.244801E+10 |
October | 0.380325E+12 | 0.424060E+11 | 0.00 | 0.688782E+10 | 0.222211E+09 |
November | 0.122748E+12 | 0.340062E+11 | 0.00 | 0.621088E+10 | 0.197834E+10 |
December | 0.517936E+11 | 0.323740E+11 | 0.00 | 0.707121E+10 | 0.662675E+10 |
Annual Sum or Average | 0.716017E+13 | 0.466719E+12 | 0.00 | 0.929974E+11 | 0.591264E+11 |
Minimum of Months | 0.517936E+11 | 0.323740E+11 | 0.00 | 0.581731E+10 | 0.222211E+09 |
Maximum of Months | 0.119436E+13 | 0.462917E+11 | 0.00 | 0.102326E+11 | 0.136753E+11 |