Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 10:43:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1257.53 | 260.08 | 260.08 |
Net Site Energy | 1257.53 | 260.08 | 260.08 |
Total Source Energy | 3833.75 | 792.90 | 792.90 |
Net Source Energy | 3833.75 | 792.90 | 792.90 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 71.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 217.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1186.07 | 71.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 71.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 217.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 31.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 125.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 71.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 217.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 81.99 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 245.30 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 81.99 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 245.30 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1186.071 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1186.071 | 100.00 |
Total On-Site and Utility Electric Sources | 1186.071 | 100.00 |
Total Electricity End Uses | 1186.071 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.50 |
Time Setpoint Not Met During Occupied Cooling | 58.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2760.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 26.83 |
Skylight-Roof Ratio [%] | 0.58 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-JUN-14:39 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 15-MAR-11:39 |
Heating | 0.00 | 16937.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33280.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11771.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1658.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 95006.06 | 16937.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 16937.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33280.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9466.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1658.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 77.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 687.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 496.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3756.29 | 77.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 776.87 | 16.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 776.87 | 16.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.44 |
ZONE2 FINE STORAGE DIRECT AIR | 4.20 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.814030 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.814030 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 32474.45 |
PSZ-OFFICE HEATING COIL | 34434.04 |
PSZ-FINE STORAGE HEATING COIL | 124933.89 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.000000 | 1.44 |
PSZ-FINE STORAGE | 4.20 | 4.20 | 4.20 | 4.20 | 4.20 | 4.20 | 1.00 | 1.00 | 4.20 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.44 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.20 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.44 | 1580.96 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.20 | 7885.13 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 1.44 | 29488.40 | 34434.04 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.20 | 4.20 | 4.20 | 4.20 | 100635.25 | 124933.89 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.44 | 0.722224 | 1.44 | 29488.40 | 15131.83 | 29488.40 | 0.768110 | 0.768110 |
PSZ-FINE STORAGE COOLING COIL | 4.20 | 2.10 | 4.20 | 100635.25 | 51453.48 | 100635.25 | 0.711990 | 0.711990 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
5 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
6 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
7 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
8 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
9 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
10 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
11 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
12 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
13 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
14 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
15 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
16 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.21548121E-14 | -0.16827101E-15 | 0.71656587E-12 | 0.12539735E-15 |
85 | 3 | -0.52378714E-04 | 0.55487071E-06 | -0.36253864E-03 | 0.13752504E-12 |
86 | 2 | 1.1001971 | 0.12432070E-01 | 1.6865760 | -0.69502831E-04 |
87 | 1 | -16.840218 | 0.32704464 | -7.1998246 | 0.32320315 |
88 | 0 | 16.290177 | 0.21062598 | 6.0637144 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.4 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.733 | 0.325 | 0.251 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 14261.56492 | 17113.87790 | 1.20371 | 1.44445 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6753.34244 | 8104.01092 | 0.19426 | 0.23312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6.30000 | 6.07234E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 53194.13755 | 63832.96506 | 3.49984 | 4.19981 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 11131.00769 | 13357.20922 | 0.27002 | 0.35393 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 6.30000 | 6.07234E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | 00:10:00 | 6.30000 | 6.07234E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 22774.63 | 1.44445 | 1.44445 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7308.69 | 0.23312 | 0.23312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 79183.37 | 4.19981 | 4.19981 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 14068.12 | 0.35393 | 0.35393 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44445 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.19981 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 32474.44793 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44445 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44445 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44445 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44445 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44445 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.44445 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.19981 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.19981 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.19981 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.19981 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.19981 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.19981 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.44445 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.19981 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44445 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44445 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1580.95596 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44445 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44445 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44445 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.44445 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44445 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72222 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.44445 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29488.40000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15131.82928 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29488.40000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76811 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76811 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29488.40000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34434.04406 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 34434.04406 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.19981 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.19981 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 7885.13239 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.19981 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.19981 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.19981 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.19981 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.19981 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.09990 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.19981 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 100635.25000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 51453.47807 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 100635.25000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71199 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71199 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 100635.25000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 124933.89429 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 124933.89429 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 28366.7 | 11.04 | 10.40 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 97371.4 | 10.49 | 9.88 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.2072982180E-002 | 2.7049995839E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 5.0522586661E-002 | 3.7287979110E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.8129476217E-002 | 1.8360215628E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9574.85 | 356.40 | 0.00 | -70.3 | 986.05 | 10847.05 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.233 | 0.240 | 3204.84 | 3178.02 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 44.49 | 6.201 | 0.341 | 0.342 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 37.98 | 6.096 | 0.357 | 0.358 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.75 | 83.75 | 134.14 | |
Exterior Lighting Total | 8532.22 | 134.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29488.40 | 22650.33 | 6838.07 | 0.77 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 100635.25 | 71651.29 | 28983.96 | 0.71 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 28366.7 | 11.04 | 10.40 | ||||
PSZ-FINE STORAGE COOLING COIL | 97371.4 | 10.49 | 9.88 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 32474.45 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 34434.04 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 124933.89 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.44 | 1580.96 | 1094.51 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.20 | 7885.13 | 1877.50 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14261.56 | 17113.88 | 72.25 | 1.204 | 1.444 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 23.90 | 23.90 | 0.00825 | 41.52 | 0.00916 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 53194.14 | 63832.97 | 45.81 | 3.500 | 4.200 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 26.70 | 26.70 | 0.00831 | 41.90 | 0.00916 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 0.00 | 41.39 | 0.00924 | 41.90 | 0.00916 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6753.34 | 8104.01 | 34.21 | 0.194 | 0.233 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00837 | 6.30 | 0.00607 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 11131.01 | 13357.21 | 9.59 | 0.270 | 0.354 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00761 | 6.30 | 0.00607 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | 00:10:00 | 10.00 | 10.43 | 0.00653 | 6.30 | 0.00607 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.44 | 1.44 | 0.23 | 0.23 | 1.4444 | 1.4444 | 1.4444 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.20 | 4.20 | 0.35 | 0.35 | 4.1998 | 4.1998 | 4.1998 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 32474.448 | 32474.448 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 32474.45 | 32474.45 | 0.814030 | 10.00 | 10.00 | 0.00800000 | 43.33 | 21.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 29488.400 | 22650.335 | 1.444450 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 29488.40 | 28048.71 | 1.444450 | 26.29 | 16.78 | 0.00832791 | 12.00 | 11.03 | 0.00800000 | 41.61 | 0.00915725 | 22.16 | 8.3308 | 23.90 | 0.00825250 | 43.5845 | 14253.48 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 34434.044 | 34434.044 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 34434.04 | 34434.04 | 1.444448 | 19.79 | 14.31 | 0.00817628 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 8.3309 | 21.10 | 0.00836748 | 52.3726 | 6753.34 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 100635.250 | 71651.292 | 4.199810 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 100635.25 | 95894.12 | 4.199810 | 29.56 | 17.92 | 0.00837954 | 12.00 | 11.03 | 0.00800000 | 42.00 | 0.00915790 | 22.26 | 8.4272 | 26.70 | 0.00830790 | 37.1431 | 53183.37 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 124933.894 | 124933.894 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 124933.89 | 124933.89 | 4.199809 | 14.78 | 11.72 | 0.00753621 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 8.4272 | 15.56 | 0.00767093 | 68.0549 | 10921.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 32474.448 | 32474.448 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.814030 | 0.95549651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 32474.45 | 32474.45 | 1.0000 | 0.95549651 | 0.814030 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 21.85 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32474.45 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29488.400 | 22650.335 | 1.444450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3212 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.444448 | 1.69547172 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | Sensible | 29488.40 | 28048.71 | 1.0000 | 1.69547441 | 1.444450 | 26.29 | 16.78 | 0.00832791 | 47651.0 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29488.40 | 41.61 | 0.00915725 | 22.16 | 0.12033486 | 8.3308 | 23.90 | 0.00825250 | 23.90 | 0.00825250 | 43.5845 | 14253.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34434.044 | 34434.044 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.444448 | 1.69547172 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 34434.04 | 34434.04 | 1.0000 | 1.69547172 | 1.444448 | 19.79 | 14.31 | 0.00817628 | 40633.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34434.04 | 6.30 | 0.00607234 | 6.30 | 0.12033486 | 8.3309 | 21.01 | 0.00836748 | 21.10 | 0.00836748 | 52.3726 | 6753.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 100635.250 | 71651.292 | 4.199810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4172 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.199809 | 4.92967466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | Sensible | 100635.25 | 95894.12 | 1.0000 | 4.92967591 | 4.199810 | 29.56 | 17.92 | 0.00837954 | 51115.9 | 12.00 | 11.03 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100635.25 | 42.00 | 0.00915790 | 22.26 | 0.35392606 | 8.4272 | 26.70 | 0.00830790 | 26.70 | 0.00830790 | 37.1431 | 53183.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 124933.894 | 124933.894 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.199809 | 4.92967466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 124933.89 | 124933.89 | 1.0000 | 4.92967466 | 4.199809 | 14.78 | 11.72 | 0.00753621 | 33905.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 124933.89 | 6.30 | 0.00607234 | 6.30 | 0.35392606 | 8.4272 | 15.56 | 0.00767093 | 15.56 | 0.00767093 | 68.0549 | 10921.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2808.50 | 793.83 | 380.00 |
ZONE2 FINE STORAGE | 3399.67 | 2578.17 | 2392.17 |
ZONE3 BULK STORAGE | 3081.50 | 3202.00 | 2729.33 |
Facility | 3473.33 | 3296.67 | 2760.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.50 | 81.00 | 0.50 | 58.00 |
ZONE2 FINE STORAGE | 0.00 | 425.67 | 0.00 | 7.17 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.50 | 494.00 | 0.50 | 58.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.414 | 0.393 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.44 | 30.00 | 2953.02 | 0.414 | 0.187 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.087 | 0.000 | 1.942 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.44 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.44 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.57 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1485411.84 | 0.00 | 1485411.84 | 1786839.17 | 3272251.01 | 3794880.16 | 5398.05 | 3361.95 | 0.00 | 274.26 |
ZONE2 FINE STORAGE | 4697247.15 | 0.00 | 4697247.15 | 4051620.53 | 8748867.68 | 11161412.23 | 5411.20 | 3348.80 | 0.00 | 1837.26 |
ZONE3 BULK STORAGE | 0.00 | 0.48E+09 | 0.48E+09 | 17587623.02 | 0.50E+09 | 25671248.14 | 4964.90 | 1.83 | 3793.27 | 3978.77 |
Total Facility | 6182658.99 | 0.48E+09 | 0.48E+09 | 23426082.72 | 0.51E+09 | 40627540.53 | 7009.54 | 3378.42 | 3793.27 | 4125.88 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1125 | 0.0000 | 0.1125 | 0.1067 | 0.2192 | 0.1203 | 274.14 | 3361.86 | 0.00 |
ZONE2 FINE STORAGE | 0.3255 | 0.0000 | 0.3255 | 0.1472 | 0.4727 | 0.3539 | 302.67 | 3333.33 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 17.6195 | 17.6195 | 0.8039 | 18.4234 | 0.8140 | 1808.79 | 0.83 | 1826.37 |
Total Facility | 0.4380 | 17.6195 | 18.0576 | 1.0578 | 19.1154 | 1.2883 | 1885.54 | 3361.86 | 1826.37 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2046559.30 | 0.00 | 2046559.30 | 3794880.16 | 5387.76 | 0.26 | 3371.98 | 269.80 |
PSZ-FINE STORAGE | 6471737.04 | 0.00 | 6471737.04 | 11161412.23 | 5375.06 | 4.46 | 3380.48 | 1834.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1550 | 0.0000 | 0.1550 | 0.1203 | 264.74 | 0.17 | 3371.09 |
PSZ-FINE STORAGE | 0.4485 | 0.0000 | 0.4485 | 0.3539 | 301.79 | 0.10 | 3334.11 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3769.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5261.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1611 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.4760 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1186.07 | 5771.67 | 01-JAN-07:20 | 95006.06 | 06-JUN-14:40 |
Electricity:Building | 686.88 | 5288.67 | 01-JAN-00:10 | 50600.89 | 07-MAR-13:30 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 379.94 | 2117.83 | 01-JAN-00:10 | 28507.00 | 07-MAR-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 156.72 | 0.00 | 01-JAN-00:10 | 11771.38 | 07-MAR-15:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 31.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity | 31.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 31.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 30-JUN-05:10 |
ElectricityPurchased:Facility | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
ElectricityPurchased:Plant | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
Cogeneration:ElectricityPurchased | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
General:Cogeneration:ElectricityPurchased | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
ElectricityNet:Plant | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
Cogeneration:ElectricityNet | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
General:Cogeneration:ElectricityNet | 1186.07 | 5771.67 | 05-MAR-13:50 | 95006.06 | 06-JUN-14:40 |
Electricity:HVAC | 342.34 | 0.00 | 01-JAN-00:10 | 45938.38 | 06-JUN-15:10 |
General:Fans:Electricity | 125.32 | 0.00 | 01-JAN-00:10 | 9466.09 | 07-JAN-12:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 217.02 | 0.00 | 01-JAN-00:10 | 36472.29 | 06-JUN-15:10 |
General:Cooling:Electricity | 217.02 | 0.00 | 01-JAN-00:10 | 36472.29 | 06-JUN-15:10 |
ExteriorLights:Electricity | 134.14 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.14 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 22.71 | 483.00 | 11-MAR-06:10 | 1770.91 | 20-JAN-12:40 |
WaterSystems:Electricity | 22.71 | 483.00 | 11-MAR-06:10 | 1770.91 | 20-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 22.71 | 483.00 | 11-MAR-06:10 | 1770.91 | 20-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 71.46 | 2250.00 | 11-MAR-06:10 | 16937.42 | 02-JAN-06:10 |
NaturalGas:HVAC | 71.46 | 2250.00 | 11-MAR-06:10 | 16937.42 | 02-JAN-06:10 |
Heating:NaturalGas | 71.46 | 2250.00 | 11-MAR-06:10 | 16937.42 | 02-JAN-06:10 |
General:Heating:NaturalGas | 71.46 | 2250.00 | 11-MAR-06:10 | 16937.42 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-MAR-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1130.18 | 0.00 | 01-JAN-00:10 | 166824.53 | 06-JUN-15:10 |
EnergyTransfer:Building | 431.93 | 0.00 | 01-JAN-00:10 | 73526.56 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 100.19 | 0.00 | 01-JAN-00:10 | 19806.93 | 06-JUN-16:10 |
Heating:EnergyTransfer | 2.87 | 0.00 | 01-JAN-00:10 | 10837.35 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.44 | 0.00 | 01-JAN-00:10 | 10646.97 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 2.87 | 0.00 | 01-JAN-00:10 | 10837.35 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.44 | 0.00 | 01-JAN-00:10 | 10646.97 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 429.06 | 0.00 | 01-JAN-00:10 | 73526.56 | 06-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 99.75 | 0.00 | 01-JAN-00:10 | 19806.93 | 06-JUN-16:10 |
General:Cooling:EnergyTransfer | 429.06 | 0.00 | 01-JAN-00:10 | 73526.56 | 06-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 99.75 | 0.00 | 01-JAN-00:10 | 19806.93 | 06-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 331.74 | 0.00 | 01-JAN-00:10 | 57025.28 | 06-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.43 | 0.00 | 01-JAN-00:10 | 5926.00 | 03-JAN-17:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.43 | 0.00 | 01-JAN-00:10 | 5926.00 | 03-JAN-17:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 329.31 | 0.00 | 01-JAN-00:10 | 57025.28 | 06-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 329.31 | 0.00 | 01-JAN-00:10 | 57025.28 | 06-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 698.25 | 0.00 | 01-JAN-00:10 | 99224.69 | 17-JUL-17:00 |
HeatingCoils:EnergyTransfer | 0.34 | 0.00 | 01-JAN-00:10 | 11212.37 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 697.91 | 0.00 | 01-JAN-00:10 | 99224.69 | 17-JUL-17:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.443 | -99.745 | 0.000 | 0.000 | 9.142 | 30.293 | 31.946 | 15.365 | 0.000 | 9.070 | 16.354 | 0.000 | -8.122 | 0.000 | -4.746 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.429 | -329.305 | 0.000 | 0.000 | 17.317 | 244.699 | 0.000 | 0.000 | 0.000 | 15.371 | 61.497 | 0.000 | 0.000 | 0.000 | -12.007 | -0.004 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.160 | 241.203 | 107.344 | 121.342 | 0.000 | 85.933 | 0.001 | 0.000 | -63.737 | 0.000 | -443.605 | -74.640 |
Total Facility | 0.000 | 0.000 | 2.872 | -429.050 | 0.000 | 0.000 | 52.620 | 516.195 | 139.290 | 136.707 | 0.000 | 110.374 | 77.852 | 0.000 | -71.859 | 0.000 | -460.358 | -74.644 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | -28801.24 | 0.00 | 0.00 | 73.37 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 28594.03 | 0.00 | -630.02 | 0.00 | -383.06 | 0.00 |
ZONE2 FINE STORAGE | 22-OCT-13:23 | 0.00 | 0.00 | 0.00 | -86268.16 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 473.91 | 83645.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-MAY-05:01 | 0.00 | 0.00 | 0.00 | -106526.91 | 0.00 | 0.00 | 357.85 | 4839.54 | 2623.78 | 86.60 | 0.00 | 888.57 | 149937.96 | 0.00 | -2594.17 | 0.00 | -49613.22 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:01 | 0.00 | 0.00 | 32941.52 | 0.00 | 0.00 | 0.00 | 137.82 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -827.12 | 0.00 | -627.88 | -32771.26 |
ZONE2 FINE STORAGE | 03-JAN-17:20 | 0.00 | 0.00 | 5925.83 | 0.00 | 0.00 | 0.00 | 603.05 | 12891.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1146.85 | -18273.18 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-06:01 | 0.00 | 0.00 | 32941.52 | 0.00 | 0.00 | 0.00 | 1232.93 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7603.15 | 0.00 | -627.88 | -33406.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.4444 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.4444 | 0.0833 | 1.0000 | Not calculated | 0.1203 | 0.0833 | ||
PSZ-FINE STORAGE | 4.1998 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.1998 | 0.0843 | 1.0000 | Not calculated | 0.3539 | 0.0843 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.4444 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.4444 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0833 | ||
PSZ-FINE STORAGE | 4.1998 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.1998 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.0843 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4444 | 1.4444 | 1.4444 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.1998 | 4.1998 | 4.1998 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.4444 | 1.4444 | 1.4444 | 1.4444 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.1998 | 4.1998 | 4.1998 | 4.1998 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4444 | 1.4444 | 1.4444 | No | 0.1203 | 0.5162 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.1998 | 4.1998 | 4.1998 | No | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.4444 | 1.4444 | 1.4444 | 1.4444 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.1998 | 4.1998 | 4.1998 | 4.1998 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.50 |
Number of hours cooling loads not met | 58.50 |
Number of hours not met | 59.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 71.46 | 16937.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 217.02 | 36472.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.14 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 31.40 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 125.32 | 9466.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.71 | 1770.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1186.07 |
Natural Gas | 0.00 | 71.46 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1257.53 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 44.88 |
Fans (All) | 32.41 |
Service Water Heating | 4.70 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 245.30 |
Subtotal | 245.30 |
Natural Gas [MJ/m2] | |
Space Heating | 14.78 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 14.78 |
Subtotal | 14.78 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 41.05 |
Space Heating | 5.68 |
Space Cooling | 17.26 |
Fans (All) | 12.46 |
Service Water Heating | 1.81 |
Receptacle Equipment | 11.08 |
Miscellaneous | 10.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5571.83 | 2916.17 | 272.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5177.33 | 3582.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2479.00 | 2723.67 | 2630.17 | 927.17 | 0.00 |
Min | 2479.00 | 2723.67 | 0.00 | 0.00 | 0.00 |
Max | 5571.83 | 3582.67 | 2630.17 | 927.17 | 0.00 |
Average | 4409.39 | 3074.17 | 967.39 | 309.06 | 0.00 |
Sum | 13228.17 | 9222.50 | 2902.17 | 927.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33025.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 44980.00 | 37739.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 44685.50 | 61159.00 | 56875.67 | 28472.83 | 0.00 |
Min | 33025.17 | 1.83 | 0.00 | 0.00 | 0.00 |
Max | 44980.00 | 61159.00 | 56875.67 | 28472.83 | 0.00 |
Average | 40896.89 | 32966.61 | 18958.56 | 9490.94 | 0.00 |
Sum | 122690.67 | 98899.83 | 56875.67 | 28472.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 5437.17 | 3273.00 | 49.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4936.50 | 3823.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2583.00 | 3272.67 | 2214.00 | 677.17 | 13.17 |
Min | 2583.00 | 3272.67 | 0.00 | 0.00 | 0.00 |
Max | 5437.17 | 3823.50 | 2214.00 | 677.17 | 13.17 |
Average | 4318.89 | 3456.39 | 754.61 | 225.72 | 4.39 |
Sum | 12956.67 | 10369.17 | 2263.83 | 677.17 | 13.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31766.33 | 1260.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 42200.00 | 40519.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 45789.00 | 75121.00 | 49600.50 | 20040.50 | 642.00 |
Min | 31766.33 | 1260.67 | 0.00 | 0.00 | 0.00 |
Max | 45789.00 | 75121.00 | 49600.50 | 20040.50 | 642.00 |
Average | 39918.44 | 38966.89 | 16533.50 | 6680.17 | 214.00 |
Sum | 119755.33 | 116900.67 | 49600.50 | 20040.50 | 642.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237793E+10 | 5506.77 | 14-JAN-16:00 | 21.30 | 15.07 | 0.619860E+09 | 769.02 | 07-JAN-16:00 | 21.30 | 15.07 |
February | 0.349321E+10 | 23360.75 | 25-FEB-06:02 | 17.60 | 15.67 | 0.578871E+09 | 769.04 | 28-FEB-14:39 | 24.97 | 15.58 |
March | 0.696837E+10 | 28219.88 | 29-MAR-05:01 | 21.18 | 17.34 | 0.685318E+09 | 769.08 | 10-MAR-15:00 | 21.18 | 17.34 |
April | 0.977042E+10 | 28674.21 | 14-APR-05:01 | 23.07 | 17.76 | 0.635246E+09 | 769.10 | 18-APR-12:09 | 35.22 | 23.17 |
May | 0.124592E+11 | 28335.21 | 09-MAY-05:01 | 26.97 | 19.07 | 0.660869E+09 | 769.10 | 17-MAY-12:09 | 37.18 | 25.45 |
June | 0.127211E+11 | 27139.59 | 05-JUN-05:01 | 30.05 | 20.36 | 0.660963E+09 | 769.11 | 29-JUN-12:09 | 36.47 | 26.15 |
July | 0.116986E+11 | 23319.76 | 07-JUL-05:01 | 31.52 | 25.91 | 0.635516E+09 | 769.11 | 05-JUL-12:39 | 31.52 | 25.91 |
August | 0.117740E+11 | 22023.34 | 07-AUG-05:01 | 29.53 | 24.79 | 0.686308E+09 | 769.11 | 08-AUG-15:00 | 36.80 | 26.65 |
September | 0.102017E+11 | 25867.83 | 27-SEP-05:01 | 23.08 | 20.68 | 0.635394E+09 | 769.10 | 25-SEP-14:30 | 23.08 | 20.68 |
October | 0.889429E+10 | 28800.15 | 25-OCT-05:01 | 19.02 | 16.53 | 0.635215E+09 | 769.09 | 10-OCT-15:30 | 19.02 | 16.53 |
November | 0.598122E+10 | 27767.60 | 02-NOV-05:01 | 16.55 | 13.37 | 0.608994E+09 | 769.25 | 15-NOV-08:09 | 16.78 | 12.85 |
December | 0.340680E+10 | 7113.68 | 02-DEC-15:20 | 23.50 | 13.33 | 0.628689E+09 | 769.04 | 27-DEC-15:39 | 22.53 | 15.09 |
Annual Sum or Average | 0.997467E+11 | 0.767124E+10 | ||||||||
Minimum of Months | 0.237793E+10 | 5506.77 | 16.55 | 13.33 | 0.578871E+09 | 769.02 | 16.78 | 12.85 | ||
Maximum of Months | 0.127211E+11 | 28800.15 | 31.52 | 25.91 | 0.686308E+09 | 769.25 | 37.18 | 26.65 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222471E+10 | 9795.87 | 12-JAN-15:00 | 23.60 | 14.20 | 0.172586E+10 | 2246.90 | 12-JAN-15:39 | 23.40 | 14.39 |
February | 0.611726E+10 | 20474.89 | 20-FEB-14:55 | 26.30 | 14.02 | 0.166386E+10 | 2246.97 | 22-FEB-15:50 | 26.60 | 16.00 |
March | 0.190330E+11 | 83562.76 | 12-MAR-14:43 | 31.45 | 19.56 | 0.199711E+10 | 2247.07 | 11-MAR-14:50 | 31.45 | 19.56 |
April | 0.358699E+11 | 82785.84 | 23-APR-15:02 | 31.73 | 19.58 | 0.185467E+10 | 2247.14 | 18-APR-14:50 | 31.73 | 19.58 |
May | 0.480796E+11 | 81096.56 | 28-MAY-09:02 | 34.52 | 19.77 | 0.192896E+10 | 2247.17 | 25-MAY-15:39 | 34.52 | 19.77 |
June | 0.483591E+11 | 79688.70 | 12-JUN-05:01 | 34.12 | 19.12 | 0.192900E+10 | 2247.17 | 13-JUN-14:20 | 39.23 | 26.24 |
July | 0.443437E+11 | 76496.06 | 07-JUL-05:01 | 31.52 | 25.91 | 0.185479E+10 | 2247.16 | 03-JUL-15:00 | 31.52 | 25.91 |
August | 0.412214E+11 | 71602.11 | 09-AUG-05:01 | 29.90 | 25.20 | 0.200308E+10 | 2246.80 | 22-AUG-13:30 | 29.90 | 27.13 |
September | 0.346043E+11 | 76713.73 | 26-SEP-17:42 | 33.40 | 22.35 | 0.185464E+10 | 2247.14 | 27-SEP-14:50 | 35.75 | 22.73 |
October | 0.284913E+11 | 86269.58 | 22-OCT-13:23 | 30.25 | 17.91 | 0.185443E+10 | 2247.13 | 03-OCT-15:30 | 30.25 | 17.91 |
November | 0.152849E+11 | 60633.21 | 11-NOV-13:23 | 28.60 | 16.87 | 0.177418E+10 | 2247.02 | 07-NOV-15:50 | 28.60 | 16.87 |
December | 0.568183E+10 | 19786.25 | 03-DEC-14:40 | 23.90 | 14.21 | 0.180739E+10 | 2246.94 | 04-DEC-15:50 | 22.28 | 14.51 |
Annual Sum or Average | 0.329311E+12 | 0.222480E+11 | ||||||||
Minimum of Months | 0.222471E+10 | 9795.87 | 23.60 | 14.02 | 0.166386E+10 | 2246.80 | 22.28 | 14.39 | ||
Maximum of Months | 0.483591E+11 | 86269.58 | 34.52 | 25.91 | 0.200308E+10 | 2247.17 | 39.23 | 27.13 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.296488E+10 | 4312.02 | 26-JAN-14:50 | 21.75 | 13.69 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.333908E+10 | 5582.62 | 24-FEB-15:50 | 26.32 | 17.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.535760E+10 | 8508.74 | 28-MAR-15:30 | 35.55 | 18.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.616430E+10 | 9097.65 | 13-APR-15:39 | 36.70 | 19.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.709019E+10 | 9097.65 | 01-MAY-09:30 | 36.80 | 21.56 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.712941E+10 | 9097.65 | 01-JUN-15:50 | 35.98 | 21.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.632839E+10 | 9097.65 | 01-JUL-10:30 | 36.45 | 27.25 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.647249E+10 | 9097.65 | 05-AUG-14:20 | 36.03 | 26.92 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.580639E+10 | 9051.01 | 26-SEP-15:20 | 36.00 | 22.61 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 | 21.85 | 0.552936E+10 | 9097.65 | 02-OCT-13:39 | 36.33 | 21.10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.474324E+10 | 6765.36 | 04-NOV-14:20 | 30.27 | 17.30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.391545E+10 | 6052.64 | 01-DEC-15:09 | 23.22 | 13.42 |
Annual Sum or Average | 0.00 | 0.648408E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.296488E+10 | 4312.02 | 21.75 | 13.42 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.712941E+10 | 9097.65 | 36.80 | 27.25 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291570E+09 | 32942.13 | 02-JAN-06:01 | 6.45 |
February | 64200078.83 | 4224.38 | 02-FEB-07:10 | 7.12 |
March | 14567687.71 | 871.84 | 06-MAR-07:10 | 16.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 13049044.03 | 772.01 | 28-NOV-07:15 | 15.43 |
December | 59682942.08 | 5036.96 | 21-DEC-07:10 | 5.68 |
Annual Sum or Average | 0.443070E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.68 | |
Maximum of Months | 0.291570E+09 | 32942.13 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117590E+10 | 5926.00 | 03-JAN-17:20 | 18.10 |
February | 0.473703E+09 | 4830.72 | 09-FEB-17:20 | 17.63 |
March | 0.158139E+09 | 4207.29 | 27-MAR-06:20 | 20.30 |
April | 2721268.13 | 3310.18 | 10-APR-06:05 | 18.85 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 4581912.78 | 4607.37 | 03-OCT-06:04 | 23.67 |
November | 0.113779E+09 | 3039.98 | 28-NOV-07:30 | 15.50 |
December | 0.499914E+09 | 5401.11 | 29-DEC-17:20 | 18.17 |
Annual Sum or Average | 0.242874E+10 | |||
Minimum of Months | 0.00 | 0.00 | 15.50 | |
Maximum of Months | 0.117590E+10 | 5926.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131640E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26512045.29 | 0.960544E+09 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360333E+09 | 0.556222E+09 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112673E+10 | 82290280.00 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185908E+10 | 27402820.33 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171823E+10 | 11760508.58 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131605E+10 | 17806826.98 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112236E+10 | 23489066.32 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824877E+09 | 38722369.76 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553318E+09 | 0.144344E+09 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161879E+09 | 0.454279E+09 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374328.41 | 0.111249E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906974E+10 | 0.474576E+10 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11760508.58 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185908E+10 | 0.131640E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279169E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163618.77 | 0.316712E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330575E+09 | 0.200022E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203311E+10 | 0.247150E+09 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389269E+10 | 88711823.92 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286728E+10 | 42845099.89 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299320E+10 | 23536329.57 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167407E+10 | 39150476.50 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102719E+10 | 0.102102E+09 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508286E+09 | 0.270356E+09 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44274113.37 | 0.772384E+09 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246201E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153708E+11 | 0.120073E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23536329.57 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389269E+10 | 0.316712E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3055455.22 | 0.787328E+10 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12032079.02 | 0.100466E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83743378.55 | 0.993093E+10 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542067E+09 | 0.234067E+10 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929696E+09 | 0.203480E+10 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437069E+09 | 0.137083E+10 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148580E+09 | 0.187260E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81946637.89 | 0.176191E+10 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82300479.05 | 0.192810E+10 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43346870.41 | 0.209970E+10 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454562E+10 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2913606.07 | 0.891358E+10 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236675E+10 | 0.547186E+11 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137083E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929696E+09 | 0.100466E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6014.76 | 31-JAN-07:20 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 933.59 | 22-FEB-13:00 | 5063.58 | 02-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.24 | 27-MAR-16:10 | 3747.52 | 03-MAR-07:05 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7088.60 | 27-APR-16:10 | 1956.94 | 10-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.01 | 05-MAY-16:10 | 403.92 | 15-MAY-05:01 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8343.91 | 06-JUN-16:10 | 277.76 | 18-JUN-01:35 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5668.44 | 06-JUL-16:10 | 270.45 | 26-JUL-05:01 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5095.63 | 07-AUG-16:10 | 294.86 | 16-AUG-05:01 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4315.13 | 27-SEP-16:10 | 333.63 | 19-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.02 | 03-OCT-16:10 | 2794.48 | 31-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.46 | 09-NOV-13:00 | 4772.26 | 27-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 | 28-DEC-14:00 | 5801.19 | 21-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.45 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.01 | 6014.76 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7005.48 | 31-JAN-08:40 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 | 22-FEB-15:00 | 9271.73 | 18-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4337.05 | 27-MAR-15:10 | 10445.90 | 24-MAR-24:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12687.18 | 15-APR-15:10 | 2995.44 | 22-APR-18:00 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13994.70 | 05-MAY-15:10 | 1320.21 | 15-MAY-03:40 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14246.64 | 06-JUN-15:10 | 1288.56 | 18-JUN-04:27 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7170.44 | 20-JUL-15:10 | 1065.53 | 19-JUL-02:30 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4567.38 | 07-AUG-15:10 | 1126.30 | 15-AUG-23:40 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4943.50 | 22-SEP-15:10 | 979.11 | 08-SEP-20:40 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5686.23 | 03-OCT-15:10 | 2033.61 | 12-OCT-03:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.98 | 03-NOV-15:10 | 3113.51 | 30-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9335.31 | 29-DEC-17:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979.11 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14246.64 | 10445.90 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 551.09 | 08-JAN-15:00 | 20613.69 | 31-JAN-08:70 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1350.54 | 19-FEB-15:00 | 25970.50 | 18-FEB-08:10 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2459.79 | 26-MAR-15:00 | 39134.36 | 24-MAR-23:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5749.87 | 15-APR-14:00 | 14566.01 | 22-APR-17:40 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5147.39 | 27-MAY-15:00 | 11064.47 | 24-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4296.96 | 06-JUN-15:00 | 15303.14 | 24-JUN-10:05 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.97 | 02-JUL-12:52 | 8955.15 | 18-JUL-11:00 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 897.67 | 06-AUG-13:55 | 7558.24 | 10-AUG-15:55 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.99 | 29-SEP-13:00 | 5359.81 | 08-SEP-21:00 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1212.52 | 03-OCT-14:00 | 9827.78 | 23-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13545.35 | 02-NOV-10:10 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 477.17 | 24-DEC-14:00 | 20132.38 | 29-DEC-17:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5359.81 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5749.87 | 39134.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5506.77 | 14-JAN-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 |
February | 23360.75 | 25-FEB-06:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.05 |
March | 28219.88 | 29-MAR-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.69 |
April | 28674.21 | 14-APR-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.41 |
May | 28335.21 | 09-MAY-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.11 |
June | 27139.59 | 05-JUN-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 45.84 | 0.00 |
July | 23319.76 | 07-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 116.03 | 0.00 |
August | 22023.34 | 07-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 0.00 |
September | 25867.83 | 27-SEP-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.71 |
October | 28800.15 | 25-OCT-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.06 |
November | 27767.60 | 02-NOV-05:01 | 1479.21 | 4585.41 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.39 |
December | 7113.68 | 02-DEC-15:20 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5506.77 | 924.51 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28800.15 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 116.03 | 593.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9795.87 | 12-JAN-15:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.71 |
February | 20474.89 | 20-FEB-14:55 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 |
March | 83562.76 | 12-MAR-14:43 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.89 | 0.00 |
April | 82785.84 | 23-APR-15:02 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.49 | 0.00 |
May | 81096.56 | 28-MAY-09:02 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2141.88 | 0.00 |
June | 79688.70 | 12-JUN-05:01 | 4351.05 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.37 | 0.00 |
July | 76496.06 | 07-JUL-05:01 | 4351.05 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.32 | 0.00 |
August | 71602.11 | 09-AUG-05:01 | 4351.05 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.75 | 0.00 |
September | 76713.73 | 26-SEP-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 996.28 | 0.00 |
October | 86269.58 | 22-OCT-13:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.91 | 0.00 |
November | 60633.21 | 11-NOV-13:23 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.10 | 0.00 |
December | 19786.25 | 03-DEC-14:40 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 9795.87 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86269.58 | 4351.05 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2141.88 | 727.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.10 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.61 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.22 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.73 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 4235.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2349.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 4235.67 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2349.63 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.811238E+11 | 66396.61 | 13-JAN-15:09 | 0.643697E+10 | 16937.42 | 02-JAN-06:10 |
February | 0.760461E+11 | 70904.36 | 22-FEB-14:00 | 0.549859E+10 | 7084.49 | 02-FEB-07:40 |
March | 0.938456E+11 | 81728.38 | 28-MAR-14:00 | 0.602640E+10 | 2250.00 | 01-MAR-00:10 |
April | 0.101008E+12 | 88987.25 | 27-APR-14:00 | 0.583200E+10 | 2250.00 | 01-APR-00:10 |
May | 0.115892E+12 | 93913.43 | 03-MAY-14:00 | 0.602640E+10 | 2250.00 | 01-MAY-00:10 |
June | 0.116590E+12 | 95006.06 | 06-JUN-14:39 | 0.583200E+10 | 2250.00 | 01-JUN-00:10 |
July | 0.115099E+12 | 92366.76 | 06-JUL-14:20 | 0.602640E+10 | 2250.00 | 01-JUL-00:10 |
August | 0.116536E+12 | 90681.09 | 07-AUG-14:00 | 0.602640E+10 | 2250.00 | 01-AUG-00:10 |
September | 0.104369E+12 | 87472.23 | 22-SEP-14:50 | 0.583200E+10 | 2250.00 | 01-SEP-00:10 |
October | 0.973494E+11 | 86090.26 | 03-OCT-14:30 | 0.602640E+10 | 2250.00 | 01-OCT-00:10 |
November | 0.851346E+11 | 77557.04 | 04-NOV-14:20 | 0.583200E+10 | 2250.00 | 01-NOV-00:10 |
December | 0.830767E+11 | 68900.34 | 02-DEC-14:30 | 0.606870E+10 | 8131.94 | 21-DEC-07:40 |
Annual Sum or Average | 0.118607E+13 | 0.714643E+11 | ||||
Minimum of Months | 0.760461E+11 | 66396.61 | 0.549859E+10 | 2250.00 | ||
Maximum of Months | 0.116590E+12 | 95006.06 | 0.643697E+10 | 16937.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.128905E+11 | 0.115358E+11 | 0.00 | 0.937339E+10 | 0.00 | 0.00 | 0.232317E+10 | 0.00 | 0.00 | 0.00 | 0.205037E+10 | 0.00 |
February | 0.393028E+11 | 0.111550E+11 | 0.105871E+11 | 0.00 | 0.863145E+10 | 0.00 | 0.00 | 0.452225E+10 | 0.00 | 0.00 | 0.00 | 0.184743E+10 | 0.00 |
March | 0.453764E+11 | 0.115595E+11 | 0.123431E+11 | 0.00 | 0.110607E+11 | 0.00 | 0.00 | 0.114736E+11 | 0.00 | 0.00 | 0.00 | 0.203234E+10 | 0.00 |
April | 0.425433E+11 | 0.104127E+11 | 0.114862E+11 | 0.00 | 0.141029E+11 | 0.00 | 0.00 | 0.205881E+11 | 0.00 | 0.00 | 0.00 | 0.187502E+10 | 0.00 |
May | 0.441635E+11 | 0.100800E+11 | 0.119357E+11 | 0.00 | 0.173600E+11 | 0.00 | 0.00 | 0.304794E+11 | 0.00 | 0.00 | 0.00 | 0.187292E+10 | 0.00 |
June | 0.437562E+11 | 0.938885E+10 | 0.118862E+11 | 0.00 | 0.173951E+11 | 0.00 | 0.00 | 0.323890E+11 | 0.00 | 0.00 | 0.00 | 0.177511E+10 | 0.00 |
July | 0.429506E+11 | 0.990079E+10 | 0.115358E+11 | 0.00 | 0.171856E+11 | 0.00 | 0.00 | 0.317440E+11 | 0.00 | 0.00 | 0.00 | 0.178265E+10 | 0.00 |
August | 0.453764E+11 | 0.104486E+11 | 0.123357E+11 | 0.00 | 0.167093E+11 | 0.00 | 0.00 | 0.298354E+11 | 0.00 | 0.00 | 0.00 | 0.183031E+10 | 0.00 |
September | 0.425433E+11 | 0.108530E+11 | 0.114788E+11 | 0.00 | 0.139100E+11 | 0.00 | 0.00 | 0.237839E+11 | 0.00 | 0.00 | 0.00 | 0.180010E+10 | 0.00 |
October | 0.429506E+11 | 0.120202E+11 | 0.115432E+11 | 0.00 | 0.121582E+11 | 0.00 | 0.00 | 0.167674E+11 | 0.00 | 0.00 | 0.00 | 0.190979E+10 | 0.00 |
November | 0.413304E+11 | 0.123018E+11 | 0.110862E+11 | 0.00 | 0.945234E+10 | 0.00 | 0.00 | 0.905530E+10 | 0.00 | 0.00 | 0.00 | 0.190859E+10 | 0.00 |
December | 0.429506E+11 | 0.131311E+11 | 0.115358E+11 | 0.00 | 0.937617E+10 | 0.00 | 0.00 | 0.405450E+10 | 0.00 | 0.00 | 0.00 | 0.202853E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134142E+12 | 0.139290E+12 | 0.00 | 0.156715E+12 | 0.00 | 0.00 | 0.217016E+12 | 0.00 | 0.00 | 0.00 | 0.227132E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.938885E+10 | 0.105871E+11 | 0.00 | 0.863145E+10 | 0.00 | 0.00 | 0.232317E+10 | 0.00 | 0.00 | 0.00 | 0.177511E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.131311E+11 | 0.123431E+11 | 0.00 | 0.173951E+11 | 0.00 | 0.00 | 0.323890E+11 | 0.00 | 0.00 | 0.00 | 0.205037E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.643697E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.549859E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.606870E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.714643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.549859E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.643697E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 9466.09 | 07-JAN-11:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 9466.09 | 04-FEB-16:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 11771.38 | 07-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 11771.38 | 01-APR-09:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 11771.38 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 11771.38 | 01-JUN-06:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 11771.38 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 11771.38 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 11771.38 | 01-SEP-06:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 11771.38 | 02-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 11771.38 | 01-NOV-12:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 9466.09 | 01-DEC-09:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 9466.09 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 11771.38 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6917.00 | 13-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1770.91 | 20-JAN-12:39 | 0.00 |
February | 11444.25 | 22-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1769.07 | 01-FEB-12:30 | 0.00 |
March | 20007.82 | 29-MAR-15:09 | 0.00 | 0.00 | 0.00 | 1756.14 | 01-MAR-12:39 | 0.00 |
April | 29669.46 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 1731.41 | 01-APR-11:09 | 0.00 |
May | 35099.34 | 05-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1704.37 | 01-MAY-11:39 | 0.00 |
June | 36472.29 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1680.50 | 01-JUN-11:39 | 0.00 |
July | 31636.30 | 01-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1666.93 | 01-JUL-11:00 | 0.00 |
August | 29982.95 | 07-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1677.42 | 31-AUG-11:50 | 0.00 |
September | 26585.18 | 22-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1699.36 | 30-SEP-11:30 | 0.00 |
October | 24987.75 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1727.29 | 31-OCT-11:00 | 0.00 |
November | 15818.18 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 1752.16 | 30-NOV-12:09 | 0.00 |
December | 9444.81 | 02-DEC-14:30 | 0.00 | 0.00 | 0.00 | 1768.05 | 30-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6917.00 | 0.00 | 0.00 | 0.00 | 1666.93 | 0.00 | ||
Maximum of Months | 36472.29 | 0.00 | 0.00 | 0.00 | 1770.91 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66396.61 | 13-JAN-15:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9466.09 | 0.00 | 0.00 | 6897.40 | 0.00 |
February | 70904.36 | 22-FEB-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9466.09 | 0.00 | 0.00 | 11444.25 | 0.00 |
March | 81728.38 | 28-MAR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 19954.07 | 0.00 |
April | 88987.25 | 27-APR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 27236.01 | 0.00 |
May | 93913.43 | 03-MAY-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 32166.95 | 0.00 |
June | 95006.06 | 06-JUN-14:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 33280.89 | 0.00 |
July | 92366.76 | 06-JUL-14:20 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 30651.66 | 0.00 |
August | 90681.09 | 07-AUG-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 28964.56 | 0.00 |
September | 87472.23 | 22-SEP-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 25733.99 | 0.00 |
October | 86090.26 | 03-OCT-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 24344.01 | 0.00 |
November | 77557.04 | 04-NOV-14:20 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 15786.63 | 0.00 |
December | 68900.34 | 02-DEC-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9466.09 | 0.00 | 0.00 | 9444.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 66396.61 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9466.09 | 0.00 | 0.00 | 6897.40 | 0.00 | |
Maximum of Months | 95006.06 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11771.38 | 0.00 | 0.00 | 33280.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 16937.42 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7084.49 | 02-FEB-07:40 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2250.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2250.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2250.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2250.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2250.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2250.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8131.94 | 21-DEC-07:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 2250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 16937.42 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.36 | 0.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.56 | 1.33 | 24.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.79 | 6.17 | 25.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.19 | 8.67 | 26.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.03 | 9.00 | 26.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.38 | 9.50 | 26.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.32 | 9.00 | 25.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.74 | 8.17 | 25.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 25.23 | 6.00 | 24.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.36 | 0.50 | 20.36 | 81.00 | 26.49 | 58.00 | 25.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.36 | 0.50 | 20.36 | 16.33 | 27.38 | 9.50 | 26.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.47 | 0.00 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 27.64 | 0.00 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 27.71 | 1.50 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 81.33 | 27.71 | 2.33 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 27.66 | 2.17 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 27.53 | 1.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 27.52 | 0.00 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.58 | 0.00 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.44 | 0.00 | 27.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 425.67 | 27.63 | 7.17 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 27.71 | 2.33 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.00 | 23.07 | 16.50 | 23.02 | 9.00 | 22.94 |
February | 88.17 | 23.14 | 90.33 | 23.52 | 0.00 | 23.52 |
March | 15.33 | 23.58 | 260.33 | 23.89 | 0.00 | 23.89 |
April | 0.00 | 0.00 | 297.83 | 23.92 | 0.00 | 23.92 |
May | 14.17 | 24.20 | 312.00 | 23.95 | 14.17 | 23.96 |
June | 50.83 | 24.11 | 312.00 | 23.97 | 50.83 | 23.99 |
July | 105.83 | 24.05 | 300.00 | 23.98 | 105.83 | 23.99 |
August | 129.00 | 24.03 | 324.00 | 23.97 | 129.00 | 23.98 |
September | 68.00 | 24.04 | 300.00 | 23.96 | 68.00 | 23.97 |
October | 3.17 | 24.01 | 300.00 | 23.92 | 3.17 | 23.92 |
November | 12.67 | 23.49 | 230.17 | 23.88 | 0.00 | 23.88 |
December | 115.67 | 23.22 | 65.33 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 793.83 | 23.58 | 2808.50 | 23.85 | 380.00 | 23.86 |
Minimum of Months | 0.00 | 0.00 | 16.50 | 23.02 | 0.00 | 22.94 |
Maximum of Months | 191.00 | 24.20 | 324.00 | 23.98 | 129.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 94.00 | 22.33 | 205.33 | 24.96 | 12.33 | 24.73 |
February | 66.33 | 24.35 | 221.50 | 26.09 | 23.67 | 26.14 |
March | 195.00 | 26.64 | 314.67 | 26.63 | 191.33 | 26.65 |
April | 243.50 | 26.70 | 300.00 | 26.71 | 243.50 | 26.71 |
May | 308.33 | 26.71 | 312.00 | 26.71 | 308.33 | 26.71 |
June | 309.83 | 26.71 | 312.00 | 26.71 | 309.83 | 26.71 |
July | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
August | 322.83 | 26.71 | 324.00 | 26.71 | 322.83 | 26.71 |
September | 289.33 | 26.71 | 300.00 | 26.71 | 289.33 | 26.71 |
October | 236.00 | 26.70 | 300.00 | 26.70 | 236.00 | 26.70 |
November | 155.83 | 26.63 | 276.50 | 26.61 | 152.00 | 26.63 |
December | 57.17 | 23.35 | 233.67 | 25.99 | 3.00 | 26.00 |
Annual Sum or Average | 2578.17 | 26.40 | 3399.67 | 26.54 | 2392.17 | 26.58 |
Minimum of Months | 57.17 | 22.33 | 205.33 | 24.96 | 3.00 | 24.73 |
Maximum of Months | 322.83 | 26.71 | 324.00 | 26.71 | 322.83 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.85 | 59.33 | 21.45 | 59.33 | 21.17 |
February | 139.00 | 22.88 | 103.50 | 24.22 | 4.67 | 24.24 |
March | 245.00 | 29.24 | 313.00 | 28.95 | 238.67 | 29.08 |
April | 300.00 | 32.14 | 300.00 | 32.14 | 300.00 | 32.14 |
May | 312.00 | 34.77 | 312.00 | 34.77 | 312.00 | 34.77 |
June | 312.00 | 34.95 | 312.00 | 34.95 | 312.00 | 34.95 |
July | 300.00 | 32.69 | 300.00 | 32.69 | 300.00 | 32.69 |
August | 324.00 | 31.54 | 324.00 | 31.54 | 324.00 | 31.54 |
September | 300.00 | 31.05 | 300.00 | 31.05 | 300.00 | 31.05 |
October | 300.00 | 30.29 | 300.00 | 30.29 | 300.00 | 30.29 |
November | 247.33 | 28.90 | 288.00 | 28.71 | 247.33 | 28.77 |
December | 122.67 | 24.43 | 169.67 | 25.62 | 31.33 | 25.87 |
Annual Sum or Average | 3202.00 | 30.25 | 3081.50 | 30.59 | 2729.33 | 30.89 |
Minimum of Months | 122.67 | 21.85 | 59.33 | 21.45 | 4.67 | 21.17 |
Maximum of Months | 324.00 | 34.95 | 324.00 | 34.95 | 324.00 | 34.95 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.307940E+10 | 0.833053E+09 | 212.33 | 0.287851E+10 | 0.200887E+09 | 0.00 | 0.29 | 14-JAN-15:50 | 0.00 | 01-JAN-00:10 | 7602.46 | 14-JAN-15:50 | 6974.79 | 12-JAN-15:40 | 1247.92 | 17-JAN-14:10 | 2022.90 | 14-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.477413E+10 | 0.128559E+10 | 221.89 | 0.435566E+10 | 0.418471E+09 | 0.00 | 1.00 | 25-FEB-06:02 | 0.00 | 01-FEB-00:10 | 31298.08 | 25-FEB-06:02 | 25924.18 | 25-FEB-06:02 | 5373.90 | 25-FEB-06:02 | 7353.95 | 25-FEB-06:02 | 0.00 | 01-FEB-00:10 |
March | 0.963998E+10 | 0.267949E+10 | 303.40 | 0.877385E+10 | 0.866127E+09 | 0.00 | 1.00 | 06-MAR-06:02 | 0.00 | 01-MAR-00:10 | 33149.26 | 11-MAR-06:01 | 30262.69 | 29-MAR-05:01 | 7707.88 | 11-MAR-06:03 | 7696.68 | 11-MAR-06:01 | 0.00 | 01-MAR-00:10 |
April | 0.134738E+11 | 0.407169E+10 | 313.57 | 0.124665E+11 | 0.100726E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 33564.36 | 03-APR-05:01 | 30970.82 | 14-APR-05:01 | 8289.92 | 03-APR-05:04 | 8027.44 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.189002E+11 | 0.592593E+10 | 365.04 | 0.159288E+11 | 0.297142E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 37513.14 | 24-MAY-05:01 | 30968.06 | 09-MAY-05:01 | 17604.50 | 24-MAY-05:05 | 9153.54 | 29-MAY-15:31 | 0.00 | 01-MAY-00:10 |
June | 0.209594E+11 | 0.641340E+10 | 367.55 | 0.161928E+11 | 0.476665E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 37523.62 | 24-JUN-05:01 | 30164.19 | 13-JUN-05:01 | 21416.89 | 26-JUN-05:07 | 9536.42 | 11-JUN-16:11 | 0.00 | 01-JUN-00:10 |
July | 0.219751E+11 | 0.625150E+10 | 365.66 | 0.146804E+11 | 0.729470E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 37793.38 | 19-JUL-05:01 | 26224.26 | 07-JUL-05:01 | 22138.63 | 20-JUL-05:08 | 9532.43 | 02-JUL-15:31 | 0.00 | 01-JUL-00:10 |
August | 0.227450E+11 | 0.629202E+10 | 349.54 | 0.147200E+11 | 0.802497E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 38311.67 | 16-AUG-05:01 | 24560.82 | 07-AUG-05:01 | 21474.44 | 19-AUG-05:07 | 8694.12 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.183634E+11 | 0.509366E+10 | 311.89 | 0.127574E+11 | 0.560600E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 38153.37 | 09-SEP-05:02 | 27863.04 | 27-SEP-05:01 | 22146.42 | 11-SEP-05:06 | 8546.95 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.129989E+11 | 0.365581E+10 | 309.13 | 0.110463E+11 | 0.195258E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:05 | 35844.47 | 12-OCT-05:01 | 30546.11 | 25-OCT-05:01 | 14538.83 | 12-OCT-05:04 | 8123.10 | 12-OCT-05:01 | 0.00 | 01-OCT-00:05 |
November | 0.802940E+10 | 0.219008E+10 | 265.11 | 0.738457E+10 | 0.644829E+09 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 31779.12 | 09-NOV-06:01 | 29595.60 | 02-NOV-05:01 | 5289.48 | 09-NOV-06:02 | 7446.99 | 09-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.432950E+10 | 0.116517E+10 | 237.06 | 0.406741E+10 | 0.262084E+09 | 0.00 | 0.34 | 02-DEC-15:10 | 0.00 | 01-DEC-00:10 | 8746.80 | 02-DEC-15:10 | 8670.06 | 02-DEC-15:00 | 927.67 | 29-DEC-16:00 | 2314.44 | 02-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.159268E+12 | 0.458574E+11 | 3622.19 | 0.125252E+12 | 0.340160E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.307940E+10 | 0.833053E+09 | 212.33 | 0.287851E+10 | 0.200887E+09 | 0.00 | 0.29 | 0.00 | 7602.46 | 6974.79 | 927.67 | 2022.90 | 0.00 | |||||||
Maximum of Months | 0.227450E+11 | 0.641340E+10 | 367.55 | 0.161928E+11 | 0.802497E+10 | 0.00 | 1.00 | 0.00 | 38311.67 | 30970.82 | 22146.42 | 9536.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.505600E+10 | 0.149012E+10 | 155.33 | 0.469780E+10 | 0.358196E+09 | 0.00 | 0.19 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 17120.97 | 12-JAN-15:00 | 16368.02 | 12-JAN-15:00 | 2366.90 | 18-JAN-14:40 | 4998.84 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.110362E+11 | 0.323665E+10 | 199.42 | 0.100764E+11 | 0.959805E+09 | 0.00 | 0.32 | 22-FEB-14:40 | 0.00 | 01-FEB-00:10 | 28701.91 | 22-FEB-14:40 | 27196.00 | 22-FEB-14:40 | 5206.94 | 25-FEB-16:00 | 8668.38 | 22-FEB-14:40 | 0.00 | 01-FEB-00:10 |
March | 0.289708E+11 | 0.879415E+10 | 335.18 | 0.265752E+11 | 0.239563E+10 | 0.00 | 1.00 | 12-MAR-13:23 | 0.00 | 01-MAR-00:10 | 100501.19 | 12-MAR-16:03 | 97043.16 | 12-MAR-14:43 | 7883.71 | 10-MAR-18:08 | 29108.30 | 12-MAR-15:23 | 0.00 | 01-MAR-00:10 |
April | 0.500082E+11 | 0.165164E+11 | 488.40 | 0.470919E+11 | 0.291632E+10 | 0.00 | 1.00 | 01-APR-17:06 | 0.00 | 01-APR-00:10 | 104298.70 | 02-APR-12:13 | 96945.05 | 05-APR-17:42 | 13226.45 | 02-APR-12:13 | 32440.15 | 16-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.717347E+11 | 0.245535E+11 | 579.34 | 0.626761E+11 | 0.905863E+10 | 0.00 | 1.00 | 01-MAY-17:04 | 0.00 | 01-MAY-00:25 | 112710.04 | 24-MAY-05:07 | 96075.12 | 28-MAY-09:02 | 48234.63 | 24-MAY-05:07 | 33769.28 | 07-MAY-15:02 | 0.00 | 01-MAY-00:10 |
June | 0.770844E+11 | 0.259756E+11 | 573.45 | 0.630761E+11 | 0.140083E+11 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:15 | 111876.50 | 23-JUN-05:01 | 94041.47 | 04-JUN-11:42 | 40342.09 | 17-JUN-23:03 | 34401.12 | 11-JUN-15:42 | 0.00 | 01-JUN-00:10 |
July | 0.812523E+11 | 0.254925E+11 | 586.67 | 0.575794E+11 | 0.236729E+11 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:13 | 117648.53 | 03-JUL-05:01 | 90328.43 | 04-JUL-17:02 | 46256.58 | 12-JUL-05:01 | 34020.85 | 02-JUL-15:42 | 0.00 | 01-JUL-00:10 |
August | 0.769888E+11 | 0.235434E+11 | 591.19 | 0.538303E+11 | 0.231585E+11 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:13 | 116350.11 | 31-AUG-05:01 | 84389.86 | 01-AUG-17:42 | 46222.91 | 31-AUG-05:01 | 32689.79 | 27-AUG-13:43 | 0.00 | 01-AUG-00:10 |
September | 0.610575E+11 | 0.186903E+11 | 545.80 | 0.454152E+11 | 0.156423E+11 | 0.00 | 1.00 | 01-SEP-17:05 | 0.00 | 01-SEP-00:15 | 112692.88 | 06-SEP-05:07 | 90871.99 | 26-SEP-17:42 | 47537.21 | 09-SEP-05:01 | 32068.19 | 17-SEP-17:42 | 0.00 | 01-SEP-00:10 |
October | 0.425114E+11 | 0.131116E+11 | 443.13 | 0.375126E+11 | 0.499879E+10 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:15 | 100497.13 | 22-OCT-12:43 | 99436.03 | 22-OCT-13:23 | 15914.02 | 11-OCT-17:10 | 30728.63 | 01-OCT-14:32 | 0.00 | 01-OCT-00:05 |
November | 0.230714E+11 | 0.686522E+10 | 281.43 | 0.213304E+11 | 0.174102E+10 | 0.00 | 0.74 | 11-NOV-13:23 | 0.00 | 01-NOV-00:10 | 71265.46 | 11-NOV-13:23 | 69664.48 | 11-NOV-13:23 | 4781.45 | 09-NOV-10:10 | 20632.44 | 11-NOV-13:23 | 0.00 | 01-NOV-00:10 |
December | 0.986981E+10 | 0.288932E+10 | 211.33 | 0.917699E+10 | 0.692826E+09 | 0.00 | 0.27 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 24778.86 | 02-DEC-14:30 | 24538.36 | 02-DEC-14:20 | 2368.07 | 16-DEC-14:50 | 7165.76 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.538642E+12 | 0.171159E+12 | 4990.68 | 0.439038E+12 | 0.996032E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.505600E+10 | 0.149012E+10 | 155.33 | 0.469780E+10 | 0.358196E+09 | 0.00 | 0.19 | 0.00 | 17120.97 | 16368.02 | 2366.90 | 4998.84 | 0.00 | |||||||
Maximum of Months | 0.812523E+11 | 0.259756E+11 | 591.19 | 0.630761E+11 | 0.236729E+11 | 0.00 | 1.00 | 0.00 | 117648.53 | 99436.03 | 48234.63 | 34401.12 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.55 | 17.46 | 27.09 | 72.63 | 182.93 | 5.33 | 0.00 | 0.00 |
February | 50.78 | 18.78 | 32.00 | 102.37 | 151.81 | 0.00 | 0.00 | 0.00 |
March | 65.91 | 26.43 | 39.47 | 174.77 | 98.04 | 0.00 | 0.00 | 0.00 |
April | 79.60 | 37.17 | 42.43 | 281.08 | 42.96 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 32.07 | 43.56 | 316.39 | 14.37 | 0.00 | 0.00 | 0.00 |
June | 71.46 | 28.01 | 43.45 | 314.53 | 12.10 | 0.00 | 0.00 | 0.00 |
July | 52.75 | 10.27 | 42.47 | 224.64 | 6.61 | 0.00 | 0.00 | 0.00 |
August | 48.30 | 8.47 | 39.84 | 192.75 | 13.67 | 0.00 | 0.00 | 0.00 |
September | 53.29 | 15.72 | 37.58 | 181.80 | 32.60 | 0.00 | 0.00 | 0.00 |
October | 55.67 | 22.31 | 33.36 | 174.04 | 86.38 | 0.00 | 0.00 | 0.00 |
November | 50.56 | 21.80 | 28.76 | 122.80 | 147.31 | 0.00 | 0.00 | 0.00 |
December | 43.23 | 16.70 | 26.54 | 71.43 | 190.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.63 | 21.24 | 36.40 | 186.02 | 81.30 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 43.23 | 8.47 | 26.54 | 71.43 | 6.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.60 | 37.17 | 43.56 | 316.39 | 190.76 | 5.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.55 | 17.46 | 27.09 | 72.63 | 182.93 | 5.33 | 0.00 | 0.00 |
February | 50.78 | 18.78 | 32.00 | 102.37 | 151.81 | 0.00 | 0.00 | 0.00 |
March | 65.91 | 26.43 | 39.47 | 174.77 | 98.04 | 0.00 | 0.00 | 0.00 |
April | 79.60 | 37.17 | 42.43 | 281.08 | 42.96 | 0.00 | 0.00 | 0.00 |
May | 75.63 | 32.07 | 43.56 | 316.39 | 14.37 | 0.00 | 0.00 | 0.00 |
June | 71.46 | 28.01 | 43.45 | 314.53 | 12.10 | 0.00 | 0.00 | 0.00 |
July | 52.75 | 10.27 | 42.47 | 224.64 | 6.61 | 0.00 | 0.00 | 0.00 |
August | 48.30 | 8.47 | 39.84 | 192.75 | 13.67 | 0.00 | 0.00 | 0.00 |
September | 53.29 | 15.72 | 37.58 | 181.80 | 32.60 | 0.00 | 0.00 | 0.00 |
October | 55.67 | 22.31 | 33.36 | 174.04 | 86.38 | 0.00 | 0.00 | 0.00 |
November | 50.56 | 21.80 | 28.76 | 122.80 | 147.31 | 0.00 | 0.00 | 0.00 |
December | 43.23 | 16.70 | 26.54 | 71.43 | 190.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.63 | 21.24 | 36.40 | 186.02 | 81.30 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 43.23 | 8.47 | 26.54 | 71.43 | 6.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.60 | 37.17 | 43.56 | 316.39 | 190.76 | 5.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.34 | 0.00 | 12.34 | 5.69 | 110.78 | 5.50 | 0.00 | 0.00 |
February | 14.63 | 0.00 | 14.63 | 16.22 | 90.47 | 0.00 | 0.00 | 0.00 |
March | 17.64 | 0.00 | 17.63 | 39.59 | 58.11 | 0.00 | 0.00 | 0.00 |
April | 19.23 | 0.15 | 19.08 | 78.72 | 24.83 | 0.00 | 0.00 | 0.00 |
May | 21.55 | 0.94 | 20.60 | 113.14 | 8.31 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 1.08 | 21.12 | 121.15 | 7.12 | 0.00 | 0.00 | 0.00 |
July | 21.82 | 0.51 | 21.30 | 102.49 | 3.77 | 0.00 | 0.00 | 0.00 |
August | 19.98 | 0.16 | 19.82 | 85.84 | 7.90 | 0.00 | 0.00 | 0.00 |
September | 17.70 | 0.00 | 17.70 | 63.40 | 18.94 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 46.51 | 50.21 | 0.00 | 0.00 | 0.00 |
November | 12.99 | 0.00 | 12.99 | 20.56 | 86.82 | 0.00 | 0.00 | 0.00 |
December | 12.04 | 0.00 | 12.04 | 6.53 | 116.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.30 | 0.24 | 17.06 | 58.53 | 48.42 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 12.04 | 0.00 | 12.04 | 5.69 | 3.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 1.08 | 21.30 | 121.15 | 116.10 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.34 | 0.00 | 12.34 | 5.69 | 110.78 | 5.50 | 0.00 | 0.00 |
February | 14.63 | 0.00 | 14.63 | 16.22 | 90.47 | 0.00 | 0.00 | 0.00 |
March | 17.64 | 0.00 | 17.63 | 39.59 | 58.11 | 0.00 | 0.00 | 0.00 |
April | 19.23 | 0.15 | 19.08 | 78.72 | 24.83 | 0.00 | 0.00 | 0.00 |
May | 21.55 | 0.94 | 20.60 | 113.14 | 8.31 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 1.08 | 21.12 | 121.15 | 7.12 | 0.00 | 0.00 | 0.00 |
July | 21.82 | 0.51 | 21.30 | 102.49 | 3.77 | 0.00 | 0.00 | 0.00 |
August | 19.98 | 0.16 | 19.82 | 85.84 | 7.90 | 0.00 | 0.00 | 0.00 |
September | 17.70 | 0.00 | 17.70 | 63.40 | 18.94 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 46.51 | 50.21 | 0.00 | 0.00 | 0.00 |
November | 12.99 | 0.00 | 12.99 | 20.56 | 86.82 | 0.00 | 0.00 | 0.00 |
December | 12.04 | 0.00 | 12.04 | 6.53 | 116.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.30 | 0.24 | 17.06 | 58.53 | 48.42 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 12.04 | 0.00 | 12.04 | 5.69 | 3.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 1.08 | 21.30 | 121.15 | 116.10 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.88 | 21.84 | 19.03 | 59.63 | 72.99 | 110.83 | 0.00 | 0.00 |
February | 51.38 | 28.56 | 22.82 | 80.31 | 65.26 | 0.17 | 0.00 | 0.00 |
March | 69.16 | 41.30 | 27.86 | 113.21 | 58.53 | 0.00 | 0.00 | 0.00 |
April | 88.74 | 61.93 | 26.81 | 156.09 | 45.20 | 0.00 | 0.00 | 0.00 |
May | 94.05 | 64.80 | 29.25 | 166.10 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 88.01 | 55.78 | 32.23 | 156.67 | 32.58 | 8.00 | 0.00 | 0.00 |
July | 61.86 | 22.08 | 39.78 | 111.05 | 21.10 | 4.00 | 0.00 | 0.00 |
August | 53.51 | 15.21 | 38.30 | 97.71 | 21.37 | 32.17 | 0.00 | 0.00 |
September | 54.84 | 23.10 | 31.74 | 92.49 | 32.60 | 35.50 | 0.00 | 0.00 |
October | 61.53 | 38.96 | 22.57 | 103.94 | 60.25 | 0.00 | 0.00 | 0.00 |
November | 51.23 | 33.64 | 17.59 | 77.87 | 83.58 | 0.00 | 0.00 | 0.00 |
December | 39.70 | 21.39 | 18.30 | 53.86 | 89.04 | 13.33 | 0.00 | 0.00 |
Annual Sum or Average | 62.92 | 35.69 | 27.23 | 105.79 | 51.32 | 204.00 | 0.00 | 0.00 |
Minimum of Months | 39.70 | 15.21 | 17.59 | 53.86 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.05 | 64.80 | 39.78 | 166.10 | 89.04 | 110.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119317E+09 | 46759457.72 | 72557141.67 | 0.194525E+09 | 0.489955E+09 |
February | 0.122855E+09 | 45442081.83 | 77412949.57 | 0.247655E+09 | 0.367247E+09 |
March | 0.176528E+09 | 70797959.45 | 0.105730E+09 | 0.468099E+09 | 0.262586E+09 |
April | 0.206321E+09 | 96346432.54 | 0.109975E+09 | 0.728550E+09 | 0.111343E+09 |
May | 0.202569E+09 | 85904051.13 | 0.116665E+09 | 0.847411E+09 | 38496213.12 |
June | 0.185226E+09 | 72601842.11 | 0.112624E+09 | 0.815272E+09 | 31361622.03 |
July | 0.141281E+09 | 27519299.37 | 0.113762E+09 | 0.601674E+09 | 17709362.63 |
August | 0.129377E+09 | 22677496.91 | 0.106699E+09 | 0.516272E+09 | 36618684.18 |
September | 0.138138E+09 | 40736732.51 | 97401692.02 | 0.471233E+09 | 84495703.52 |
October | 0.149107E+09 | 59764424.93 | 89342775.44 | 0.466150E+09 | 0.231372E+09 |
November | 0.131059E+09 | 56505357.95 | 74553833.02 | 0.318299E+09 | 0.381826E+09 |
December | 0.115794E+09 | 44717288.20 | 71077153.99 | 0.191323E+09 | 0.510931E+09 |
Annual Sum or Average | 0.181757E+10 | 0.669772E+09 | 0.114780E+10 | 0.586646E+10 | 0.256394E+10 |
Minimum of Months | 0.115794E+09 | 22677496.91 | 71077153.99 | 0.191323E+09 | 17709362.63 |
Maximum of Months | 0.206321E+09 | 96346432.54 | 0.116665E+09 | 0.847411E+09 | 0.510931E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119317E+09 | 46759457.72 | 72557141.67 | 0.194525E+09 | 0.489955E+09 |
February | 0.122855E+09 | 45442081.83 | 77412949.57 | 0.247655E+09 | 0.367247E+09 |
March | 0.176528E+09 | 70797959.45 | 0.105730E+09 | 0.468099E+09 | 0.262586E+09 |
April | 0.206321E+09 | 96346432.54 | 0.109975E+09 | 0.728550E+09 | 0.111343E+09 |
May | 0.202569E+09 | 85904051.13 | 0.116665E+09 | 0.847411E+09 | 38496213.12 |
June | 0.185226E+09 | 72601842.11 | 0.112624E+09 | 0.815272E+09 | 31361622.03 |
July | 0.141281E+09 | 27519299.37 | 0.113762E+09 | 0.601674E+09 | 17709362.63 |
August | 0.129377E+09 | 22677496.91 | 0.106699E+09 | 0.516272E+09 | 36618684.18 |
September | 0.138138E+09 | 40736732.51 | 97401692.02 | 0.471233E+09 | 84495703.52 |
October | 0.149107E+09 | 59764424.93 | 89342775.44 | 0.466150E+09 | 0.231372E+09 |
November | 0.131059E+09 | 56505357.95 | 74553833.02 | 0.318299E+09 | 0.381826E+09 |
December | 0.115794E+09 | 44717288.20 | 71077153.99 | 0.191323E+09 | 0.510931E+09 |
Annual Sum or Average | 0.181757E+10 | 0.669772E+09 | 0.114780E+10 | 0.586646E+10 | 0.256394E+10 |
Minimum of Months | 0.115794E+09 | 22677496.91 | 71077153.99 | 0.191323E+09 | 17709362.63 |
Maximum of Months | 0.206321E+09 | 96346432.54 | 0.116665E+09 | 0.847411E+09 | 0.510931E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33046738.31 | 0.00 | 33046738.31 | 15236274.76 | 0.296703E+09 |
February | 35395458.44 | 0.00 | 35395458.44 | 39246864.09 | 0.218866E+09 |
March | 47238227.42 | 9028.93 | 47229198.49 | 0.106049E+09 | 0.155635E+09 |
April | 49856391.18 | 398203.59 | 49458187.59 | 0.204035E+09 | 64370751.52 |
May | 57712664.30 | 2524546.39 | 55188117.91 | 0.303029E+09 | 22248835.40 |
June | 57553981.12 | 2798877.76 | 54755103.37 | 0.314013E+09 | 18449425.54 |
July | 58431371.17 | 1377771.14 | 57053600.03 | 0.274522E+09 | 10093953.09 |
August | 53515662.64 | 427659.85 | 53088002.79 | 0.229906E+09 | 21157052.33 |
September | 45888126.03 | 10822.86 | 45877303.17 | 0.164338E+09 | 49086660.73 |
October | 41070187.91 | 0.00 | 41070187.91 | 0.124581E+09 | 0.134495E+09 |
November | 33664697.58 | 0.00 | 33664697.58 | 53290044.07 | 0.225039E+09 |
December | 32237683.47 | 0.00 | 32237683.47 | 17503115.18 | 0.310975E+09 |
Annual Sum or Average | 0.545611E+09 | 7546910.52 | 0.538064E+09 | 0.184575E+10 | 0.152712E+10 |
Minimum of Months | 32237683.47 | 0.00 | 32237683.47 | 15236274.76 | 10093953.09 |
Maximum of Months | 58431371.17 | 2798877.76 | 57053600.03 | 0.314013E+09 | 0.310975E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33045727.07 | 0.00 | 33045727.07 | 15235278.82 | 0.296702E+09 |
February | 35394403.61 | 0.00 | 35394403.61 | 39245442.36 | 0.218865E+09 |
March | 47236881.95 | 9028.51 | 47227853.45 | 0.106046E+09 | 0.155633E+09 |
April | 49855121.52 | 398184.93 | 49456936.59 | 0.204034E+09 | 64369092.65 |
May | 57711111.73 | 2524428.06 | 55186683.67 | 0.303027E+09 | 22247840.86 |
June | 57552329.92 | 2798746.57 | 54753583.35 | 0.314010E+09 | 18448967.41 |
July | 58429416.44 | 1377706.56 | 57051709.88 | 0.274518E+09 | 10093479.53 |
August | 53513838.26 | 427639.80 | 53086198.46 | 0.229901E+09 | 21156280.16 |
September | 45886653.77 | 10822.35 | 45875831.42 | 0.164335E+09 | 49085390.34 |
October | 41069040.85 | 0.00 | 41069040.85 | 0.124580E+09 | 0.134493E+09 |
November | 33663765.90 | 0.00 | 33663765.90 | 53289018.44 | 0.225037E+09 |
December | 32236700.80 | 0.00 | 32236700.80 | 17502124.54 | 0.310974E+09 |
Annual Sum or Average | 0.545595E+09 | 7546556.78 | 0.538048E+09 | 0.184572E+10 | 0.152710E+10 |
Minimum of Months | 32236700.80 | 0.00 | 32236700.80 | 15235278.82 | 10093479.53 |
Maximum of Months | 58429416.44 | 2798746.57 | 57051709.88 | 0.314010E+09 | 0.310974E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109491E+09 | 58509164.48 | 50982236.62 | 0.159701E+09 | 0.195504E+09 |
February | 0.124308E+09 | 69099796.32 | 55208465.40 | 0.194292E+09 | 0.157867E+09 |
March | 0.185237E+09 | 0.110611E+09 | 74625920.77 | 0.303227E+09 | 0.156767E+09 |
April | 0.230003E+09 | 0.160515E+09 | 69487914.51 | 0.404591E+09 | 0.117166E+09 |
May | 0.251901E+09 | 0.173564E+09 | 78336568.04 | 0.444882E+09 | 91896263.50 |
June | 0.228118E+09 | 0.144586E+09 | 83532324.81 | 0.406086E+09 | 84453187.26 |
July | 0.165676E+09 | 59132212.10 | 0.106544E+09 | 0.297448E+09 | 56525075.00 |
August | 0.143325E+09 | 40732733.09 | 0.102592E+09 | 0.261705E+09 | 57228728.77 |
September | 0.142150E+09 | 59871508.26 | 82278762.32 | 0.239724E+09 | 84501354.97 |
October | 0.164804E+09 | 0.104353E+09 | 60450628.30 | 0.278402E+09 | 0.161366E+09 |
November | 0.132799E+09 | 87195557.94 | 45603275.20 | 0.201833E+09 | 0.216633E+09 |
December | 0.106320E+09 | 57293233.77 | 49026783.63 | 0.144267E+09 | 0.238493E+09 |
Annual Sum or Average | 0.198413E+10 | 0.112546E+10 | 0.858669E+09 | 0.333616E+10 | 0.161840E+10 |
Minimum of Months | 0.106320E+09 | 40732733.09 | 45603275.20 | 0.144267E+09 | 56525075.00 |
Maximum of Months | 0.251901E+09 | 0.173564E+09 | 0.106544E+09 | 0.444882E+09 | 0.238493E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.64 | 580.41 | 113.77 | 34.92 | 78.86 | 0.00 | 0.00 |
February | 234.15 | 481.52 | 130.83 | 37.57 | 93.26 | 0.00 | 0.00 |
March | 427.39 | 310.96 | 167.09 | 52.87 | 114.22 | 0.00 | 0.00 |
April | 719.46 | 135.45 | 197.67 | 74.65 | 123.02 | 0.00 | 0.00 |
May | 858.74 | 45.05 | 194.36 | 66.03 | 128.32 | 0.00 | 0.00 |
June | 871.24 | 38.31 | 187.33 | 58.18 | 129.15 | 0.00 | 0.00 |
July | 654.24 | 20.74 | 149.13 | 21.58 | 127.55 | 0.00 | 0.00 |
August | 557.14 | 43.10 | 136.57 | 17.25 | 119.31 | 0.00 | 0.00 |
September | 490.36 | 103.03 | 142.00 | 31.44 | 110.55 | 0.00 | 0.00 |
October | 440.97 | 273.06 | 142.01 | 44.63 | 97.38 | 0.00 | 0.00 |
November | 284.67 | 466.21 | 127.10 | 43.60 | 83.50 | 0.00 | 0.00 |
December | 147.41 | 605.21 | 110.54 | 33.39 | 77.15 | 0.00 | 0.00 |
Annual Sum or Average | 487.21 | 257.55 | 149.87 | 42.96 | 106.92 | 0.00 | 0.00 |
Minimum of Months | 147.41 | 20.74 | 110.54 | 17.25 | 77.15 | 0.00 | 0.00 |
Maximum of Months | 871.24 | 605.21 | 197.67 | 74.65 | 129.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1828.00 | 2416.79 | 408.79 | 218.45 | 190.35 | 0.00 | 0.00 |
February | 2508.76 | 2107.78 | 513.84 | 285.63 | 228.21 | 0.00 | 0.00 |
March | 4173.37 | 2100.75 | 691.59 | 412.97 | 278.62 | 0.00 | 0.00 |
April | 6546.50 | 2530.27 | 887.36 | 619.27 | 268.09 | 0.00 | 0.00 |
May | 7318.56 | 2194.33 | 940.49 | 648.02 | 292.48 | 0.00 | 0.00 |
June | 6382.19 | 2143.03 | 880.09 | 557.82 | 322.27 | 0.00 | 0.00 |
July | 4917.77 | 1337.19 | 618.56 | 220.77 | 397.79 | 0.00 | 0.00 |
August | 3950.97 | 1322.17 | 535.11 | 152.08 | 383.04 | 0.00 | 0.00 |
September | 3533.79 | 2001.16 | 548.42 | 230.99 | 317.43 | 0.00 | 0.00 |
October | 4529.95 | 2975.09 | 615.31 | 389.61 | 225.70 | 0.00 | 0.00 |
November | 3074.99 | 2921.26 | 512.34 | 336.40 | 175.94 | 0.00 | 0.00 |
December | 1668.02 | 2892.03 | 396.95 | 213.91 | 183.05 | 0.00 | 0.00 |
Annual Sum or Average | 4209.19 | 2244.60 | 629.16 | 356.88 | 272.28 | 0.00 | 0.00 |
Minimum of Months | 1668.02 | 1322.17 | 396.95 | 152.08 | 175.94 | 0.00 | 0.00 |
Maximum of Months | 7318.56 | 2975.09 | 940.49 | 648.02 | 397.79 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.400784E+09 | 0.155458E+10 | 0.304726E+09 | 93518915.45 | 0.211207E+09 | 0.00 | 0.00 |
February | 0.566463E+09 | 0.116489E+10 | 0.316500E+09 | 90884163.66 | 0.225616E+09 | 0.00 | 0.00 |
March | 0.114472E+10 | 0.832869E+09 | 0.447530E+09 | 0.141614E+09 | 0.305916E+09 | 0.00 | 0.00 |
April | 0.186484E+10 | 0.351095E+09 | 0.512354E+09 | 0.193489E+09 | 0.318864E+09 | 0.00 | 0.00 |
May | 0.230006E+10 | 0.120670E+09 | 0.520561E+09 | 0.176857E+09 | 0.343704E+09 | 0.00 | 0.00 |
June | 0.225825E+10 | 99300526.34 | 0.485558E+09 | 0.150801E+09 | 0.334757E+09 | 0.00 | 0.00 |
July | 0.175233E+10 | 55547001.67 | 0.399424E+09 | 57794076.44 | 0.341630E+09 | 0.00 | 0.00 |
August | 0.149225E+10 | 0.115448E+09 | 0.365783E+09 | 46210293.47 | 0.319572E+09 | 0.00 | 0.00 |
September | 0.127102E+10 | 0.267048E+09 | 0.368052E+09 | 81495110.23 | 0.286557E+09 | 0.00 | 0.00 |
October | 0.118110E+10 | 0.731371E+09 | 0.380354E+09 | 0.119529E+09 | 0.260825E+09 | 0.00 | 0.00 |
November | 0.737875E+09 | 0.120843E+10 | 0.329447E+09 | 0.113011E+09 | 0.216436E+09 | 0.00 | 0.00 |
December | 0.394830E+09 | 0.162099E+10 | 0.296063E+09 | 89434576.39 | 0.206629E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153645E+11 | 0.812223E+10 | 0.472635E+10 | 0.135464E+10 | 0.337171E+10 | 0.00 | 0.00 |
Minimum of Months | 0.394830E+09 | 55547001.67 | 0.296063E+09 | 46210293.47 | 0.206629E+09 | 0.00 | 0.00 |
Maximum of Months | 0.230006E+10 | 0.162099E+10 | 0.520561E+09 | 0.193489E+09 | 0.343704E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.489612E+10 | 0.647314E+10 | 0.109491E+10 | 0.585092E+09 | 0.509822E+09 | 0.00 | 0.00 |
February | 0.606920E+10 | 0.509913E+10 | 0.124308E+10 | 0.690998E+09 | 0.552085E+09 | 0.00 | 0.00 |
March | 0.111780E+11 | 0.562666E+10 | 0.185237E+10 | 0.110611E+10 | 0.746259E+09 | 0.00 | 0.00 |
April | 0.169685E+11 | 0.655846E+10 | 0.230003E+10 | 0.160515E+10 | 0.694879E+09 | 0.00 | 0.00 |
May | 0.196020E+11 | 0.587731E+10 | 0.251901E+10 | 0.173564E+10 | 0.783366E+09 | 0.00 | 0.00 |
June | 0.165426E+11 | 0.555472E+10 | 0.228118E+10 | 0.144586E+10 | 0.835323E+09 | 0.00 | 0.00 |
July | 0.131718E+11 | 0.358154E+10 | 0.165676E+10 | 0.591322E+09 | 0.106544E+10 | 0.00 | 0.00 |
August | 0.105823E+11 | 0.354130E+10 | 0.143325E+10 | 0.407327E+09 | 0.102592E+10 | 0.00 | 0.00 |
September | 0.915958E+10 | 0.518700E+10 | 0.142150E+10 | 0.598715E+09 | 0.822788E+09 | 0.00 | 0.00 |
October | 0.121330E+11 | 0.796847E+10 | 0.164804E+10 | 0.104353E+10 | 0.604506E+09 | 0.00 | 0.00 |
November | 0.797037E+10 | 0.757191E+10 | 0.132799E+10 | 0.871956E+09 | 0.456033E+09 | 0.00 | 0.00 |
December | 0.446763E+10 | 0.774602E+10 | 0.106320E+10 | 0.572932E+09 | 0.490268E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132741E+12 | 0.707856E+11 | 0.198413E+11 | 0.112546E+11 | 0.858669E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446763E+10 | 0.354130E+10 | 0.106320E+10 | 0.407327E+09 | 0.456033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196020E+11 | 0.796847E+10 | 0.251901E+10 | 0.173564E+10 | 0.106544E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.756826E+09 | -679989202.3 | 0.00 | 0.00 | 744.00 | 0.00 | -76836729.4 | 58.99 | 0.00 | 0.00 |
February | 0.678724E+09 | -611538373.2 | 0.00 | 0.00 | 672.00 | 0.00 | -67185981.7 | 58.99 | 0.00 | 0.00 |
March | 0.738558E+09 | -666820135.1 | 0.00 | 0.00 | 744.00 | 0.00 | -71737932.5 | 58.99 | 0.00 | 0.00 |
April | 0.623118E+09 | -556032477.8 | 0.00 | 0.00 | 720.00 | 0.00 | -67085584.3 | 58.99 | 0.00 | 0.00 |
May | 0.579446E+09 | -510932745.6 | 0.00 | 0.00 | 744.00 | 0.00 | -68513567.1 | 58.99 | 0.00 | 0.00 |
June | 0.522794E+09 | -456445833.0 | 0.00 | 0.00 | 720.00 | 0.00 | -66347688.7 | 58.99 | 0.00 | 0.00 |
July | 0.488871E+09 | -420672416.8 | 0.00 | 0.00 | 744.00 | 0.00 | -68198540.7 | 58.99 | 0.00 | 0.00 |
August | 0.536556E+09 | -467792035.8 | 0.00 | 0.00 | 744.00 | 0.00 | -68763632.2 | 58.98 | 0.00 | 0.00 |
September | 0.548113E+09 | -481518596.3 | 0.00 | 0.00 | 720.00 | 0.00 | -66594278.3 | 58.98 | 0.00 | 0.00 |
October | 0.616223E+09 | -546566819.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69656470.5 | 58.98 | 0.00 | 0.00 |
November | 0.656300E+09 | -586876064.5 | 0.00 | 0.00 | 720.00 | 0.00 | -69423597.8 | 58.99 | 0.00 | 0.00 |
December | 0.734680E+09 | -659816316.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74863719.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.748021E+10 | -0.664500E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -835207722.8 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.488871E+09 | -679989202.3 | 0.00 | 0.00 | 672.00 | 0.00 | -76836729.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.756826E+09 | -420672416.8 | 0.00 | 0.00 | 744.00 | 0.00 | -66347688.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274604E+09 | 34434.04 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36053644.36 | 4457.77 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27643678.52 | 5463.22 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274604E+09 | 34434.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.307940E+10 | 0.287851E+10 | 7602.46 | 14-JAN-15:50 | 6715.84 | 0.00 |
February | 0.00 | 0.00 | 0.477413E+10 | 0.435566E+10 | 31298.08 | 25-FEB-06:02 | 25924.18 | 0.00 |
March | 0.00 | 0.00 | 0.963998E+10 | 0.877385E+10 | 33149.26 | 11-MAR-06:01 | 26428.80 | 0.00 |
April | 0.00 | 0.00 | 0.134738E+11 | 0.124665E+11 | 33564.36 | 03-APR-05:01 | 26893.94 | 0.00 |
May | 0.00 | 0.00 | 0.189002E+11 | 0.159288E+11 | 37513.14 | 24-MAY-05:01 | 20385.66 | 0.00 |
June | 0.00 | 0.00 | 0.209594E+11 | 0.161928E+11 | 37523.62 | 24-JUN-05:01 | 20789.48 | 0.00 |
July | 0.00 | 0.00 | 0.219751E+11 | 0.146804E+11 | 37793.38 | 19-JUL-05:01 | 17241.66 | 0.00 |
August | 0.00 | 0.00 | 0.227450E+11 | 0.147200E+11 | 38311.67 | 16-AUG-05:01 | 19280.03 | 0.00 |
September | 0.00 | 0.00 | 0.183634E+11 | 0.127574E+11 | 38153.37 | 09-SEP-05:02 | 18489.76 | 0.00 |
October | 0.00 | 0.00 | 0.129989E+11 | 0.110463E+11 | 35844.47 | 12-OCT-05:01 | 22083.33 | 0.00 |
November | 0.00 | 0.00 | 0.802940E+10 | 0.738457E+10 | 31779.12 | 09-NOV-06:01 | 27039.79 | 0.00 |
December | 0.00 | 0.00 | 0.432950E+10 | 0.406741E+10 | 8746.80 | 02-DEC-15:10 | 8659.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159268E+12 | 0.125252E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.307940E+10 | 0.287851E+10 | 7602.46 | 6715.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.227450E+11 | 0.161928E+11 | 38311.67 | 27039.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.505600E+10 | 0.469780E+10 | 17120.97 | 12-JAN-15:00 | 16368.02 | 0.00 |
February | 0.00 | 0.00 | 0.110362E+11 | 0.100764E+11 | 28701.91 | 22-FEB-14:40 | 27196.00 | 0.00 |
March | 0.00 | 0.00 | 0.289708E+11 | 0.265752E+11 | 100501.19 | 12-MAR-16:03 | 96309.76 | 0.00 |
April | 0.00 | 0.00 | 0.500082E+11 | 0.470919E+11 | 104298.70 | 02-APR-12:13 | 91072.26 | 0.00 |
May | 0.00 | 0.00 | 0.717347E+11 | 0.626761E+11 | 112710.04 | 24-MAY-05:07 | 64475.42 | 0.00 |
June | 0.00 | 0.00 | 0.770844E+11 | 0.630761E+11 | 111876.50 | 23-JUN-05:01 | 78971.94 | 0.00 |
July | 0.00 | 0.00 | 0.812523E+11 | 0.575794E+11 | 117648.53 | 03-JUL-05:01 | 73217.64 | 0.00 |
August | 0.00 | 0.00 | 0.769888E+11 | 0.538303E+11 | 116350.11 | 31-AUG-05:01 | 70127.20 | 0.00 |
September | 0.00 | 0.00 | 0.610575E+11 | 0.454152E+11 | 112692.88 | 06-SEP-05:07 | 66808.50 | 0.00 |
October | 0.00 | 0.00 | 0.425114E+11 | 0.375126E+11 | 100497.13 | 22-OCT-12:43 | 99149.20 | 0.00 |
November | 0.00 | 0.00 | 0.230714E+11 | 0.213304E+11 | 71265.46 | 11-NOV-13:23 | 69664.48 | 0.00 |
December | 0.00 | 0.00 | 0.986981E+10 | 0.917699E+10 | 24778.86 | 02-DEC-14:30 | 24538.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.538642E+12 | 0.439038E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.505600E+10 | 0.469780E+10 | 17120.97 | 16368.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.812523E+11 | 0.630761E+11 | 117648.53 | 99149.20 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156711E+10 | 0.34 | 1580.96 | 03-JAN-08:30 | 0.92 |
February | 0.144119E+10 | 0.35 | 1580.96 | 01-FEB-07:30 | 0.92 |
March | 0.170561E+10 | 0.38 | 1580.96 | 01-MAR-15:50 | 0.92 |
April | 0.160657E+10 | 0.40 | 1580.96 | 01-APR-06:30 | 0.91 |
May | 0.171948E+10 | 0.46 | 1580.96 | 01-MAY-07:30 | 0.91 |
June | 0.172837E+10 | 0.48 | 1580.96 | 01-JUN-06:05 | 0.91 |
July | 0.168570E+10 | 0.46 | 1580.96 | 01-JUL-06:10 | 0.91 |
August | 0.178671E+10 | 0.43 | 1580.96 | 01-AUG-06:20 | 0.91 |
September | 0.163298E+10 | 0.40 | 1580.96 | 01-SEP-06:30 | 0.90 |
October | 0.160459E+10 | 0.38 | 1580.96 | 02-OCT-06:05 | 0.91 |
November | 0.151432E+10 | 0.35 | 1580.96 | 14-NOV-07:30 | 0.91 |
December | 0.156515E+10 | 0.34 | 1580.96 | 02-DEC-10:30 | 0.92 |
Annual Sum or Average | 0.195578E+11 | 0.40 | |||
Minimum of Months | 0.144119E+10 | 0.34 | 1580.96 | 0.90 | |
Maximum of Months | 0.178671E+10 | 0.48 | 1580.96 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.780628E+10 | 0.58 | 7885.13 | 07-JAN-12:00 | 1.57 |
February | 0.719027E+10 | 0.60 | 7885.13 | 04-FEB-16:40 | 1.57 |
March | 0.864373E+10 | 0.75 | 7885.13 | 31-MAR-06:40 | 1.56 |
April | 0.886086E+10 | 1.13 | 7885.13 | 01-APR-06:50 | 1.57 |
May | 0.999831E+10 | 1.30 | 7885.13 | 01-MAY-07:40 | 1.57 |
June | 0.100918E+11 | 1.33 | 7885.13 | 01-JUN-06:10 | 1.56 |
July | 0.100084E+11 | 1.31 | 7885.13 | 01-JUL-06:20 | 1.56 |
August | 0.101648E+11 | 1.32 | 7885.13 | 01-AUG-06:10 | 1.55 |
September | 0.908984E+10 | 1.27 | 7885.13 | 28-SEP-06:10 | 1.57 |
October | 0.848163E+10 | 0.99 | 7885.13 | 28-OCT-07:51 | 1.57 |
November | 0.761512E+10 | 0.66 | 7885.13 | 22-NOV-08:20 | 1.57 |
December | 0.781102E+10 | 0.59 | 7885.13 | 01-DEC-09:30 | 1.57 |
Annual Sum or Average | 0.105762E+12 | 0.99 | |||
Minimum of Months | 0.719027E+10 | 0.58 | 7885.13 | 1.55 | |
Maximum of Months | 0.101648E+11 | 1.33 | 7885.13 | 1.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.240017E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.272678E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.438510E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.567826E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.764540E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.814177E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.793720E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.807873E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.672665E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.526040E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.370441E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.273032E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.654152E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.240017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.814177E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.929640E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104269E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.174379E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.253773E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.345518E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.360674E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.355008E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.337081E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.277801E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.215933E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144803E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.107003E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.276921E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.929640E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.360674E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156711E+10 | 0.307940E+10 | 0.274604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144119E+10 | 0.477413E+10 | 36053644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170561E+10 | 0.963998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160657E+10 | 0.134738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171948E+10 | 0.189002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172837E+10 | 0.209594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168570E+10 | 0.219751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178671E+10 | 0.227450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163298E+10 | 0.183634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160459E+10 | 0.129989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151432E+10 | 0.802940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156515E+10 | 0.432950E+10 | 27643678.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195578E+11 | 0.159268E+12 | 0.338301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144119E+10 | 0.307940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178671E+10 | 0.227450E+11 | 0.274604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.780628E+10 | 0.505600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719027E+10 | 0.110362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.864373E+10 | 0.289708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.886086E+10 | 0.500082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.999831E+10 | 0.717347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100918E+11 | 0.770844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100084E+11 | 0.812523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101648E+11 | 0.769888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.908984E+10 | 0.610575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848163E+10 | 0.425114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.761512E+10 | 0.230714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.781102E+10 | 0.986981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105762E+12 | 0.538642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.719027E+10 | 0.505600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101648E+11 | 0.812523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156711E+10 | 0.00 | 0.00 | 0.00 | 0.833053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144119E+10 | 0.00 | 0.00 | 0.00 | 0.128559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170561E+10 | 0.00 | 0.00 | 0.00 | 0.267949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160657E+10 | 0.00 | 0.00 | 0.00 | 0.407169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171948E+10 | 0.00 | 0.00 | 0.00 | 0.592593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172837E+10 | 0.00 | 0.00 | 0.00 | 0.641340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168570E+10 | 0.00 | 0.00 | 0.00 | 0.625150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178671E+10 | 0.00 | 0.00 | 0.00 | 0.629202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163298E+10 | 0.00 | 0.00 | 0.00 | 0.509366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160459E+10 | 0.00 | 0.00 | 0.00 | 0.365581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151432E+10 | 0.00 | 0.00 | 0.00 | 0.219008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156515E+10 | 0.00 | 0.00 | 0.00 | 0.116517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195578E+11 | 0.00 | 0.00 | 0.00 | 0.458574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144119E+10 | 0.00 | 0.00 | 0.00 | 0.833053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178671E+10 | 0.00 | 0.00 | 0.00 | 0.641340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.780628E+10 | 0.00 | 0.00 | 0.00 | 0.149012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719027E+10 | 0.00 | 0.00 | 0.00 | 0.323665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.864373E+10 | 0.00 | 0.00 | 0.00 | 0.879415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.886086E+10 | 0.00 | 0.00 | 0.00 | 0.165164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.999831E+10 | 0.00 | 0.00 | 0.00 | 0.245535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100918E+11 | 0.00 | 0.00 | 0.00 | 0.259756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100084E+11 | 0.00 | 0.00 | 0.00 | 0.254925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101648E+11 | 0.00 | 0.00 | 0.00 | 0.235434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.908984E+10 | 0.00 | 0.00 | 0.00 | 0.186903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848163E+10 | 0.00 | 0.00 | 0.00 | 0.131116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.761512E+10 | 0.00 | 0.00 | 0.00 | 0.686522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.781102E+10 | 0.00 | 0.00 | 0.00 | 0.288932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105762E+12 | 0.00 | 0.00 | 0.00 | 0.171159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.719027E+10 | 0.00 | 0.00 | 0.00 | 0.149012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101648E+11 | 0.00 | 0.00 | 0.00 | 0.259756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302779E+09 | 0.00 | 0.00 | 3898029.67 | 0.00 | 0.133686E+09 | 0.805815E+09 | 0.00 | 0.16 |
February | 0.146173E+09 | 30871340.52 | 0.00 | 4666626.29 | 0.00 | 32523416.05 | 0.483240E+09 | 0.00 | 0.17 |
March | 35543921.97 | 0.413447E+09 | 0.00 | 6308126.62 | 0.00 | 0.00 | 0.208764E+09 | 0.00 | 0.18 |
April | 0.00 | 0.124127E+10 | 0.00 | 1385993.77 | 0.00 | 0.00 | 7754424.24 | 0.00 | 0.17 |
May | 0.00 | 0.277814E+10 | 0.00 | 244616.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.376239E+10 | 0.00 | 60961.57 | 0.00 | 0.00 | 15192.47 | 0.00 | 0.19 |
July | 0.00 | 0.443583E+10 | 0.00 | 14113.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.471787E+10 | 0.00 | 8938.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.345997E+10 | 0.00 | 25355.56 | 0.00 | 0.00 | 909.93 | 0.00 | 0.18 |
October | 0.00 | 0.124487E+10 | 0.00 | 3321197.41 | 0.00 | 0.00 | 29008255.94 | 0.00 | 0.17 |
November | 52562208.65 | 0.222287E+09 | 0.00 | 5640648.71 | 0.00 | 0.00 | 0.276480E+09 | 0.00 | 0.16 |
December | 0.210120E+09 | 138133.59 | 0.00 | 5715400.52 | 0.00 | 28629494.81 | 0.819436E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.747178E+09 | 0.223071E+11 | 0.00 | 31290009.92 | 0.00 | 0.194839E+09 | 0.263051E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8938.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.302779E+09 | 0.471787E+10 | 0.00 | 6308126.62 | 0.00 | 0.133686E+09 | 0.819436E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290479E+10 | 0.00 | 0.00 | 3706549.69 | 0.00 | 0.00 | 0.193221E+10 | 0.00 | 0.16 |
February | 0.123030E+10 | 5958235.78 | 0.00 | 9895316.56 | 0.00 | 0.00 | 0.177558E+10 | 0.00 | 0.17 |
March | 0.274702E+09 | 0.699754E+09 | 0.00 | 16290438.16 | 60230.46 | 0.00 | 0.120030E+10 | 0.00 | 0.18 |
April | 1608023.14 | 0.298886E+10 | 0.00 | 5746558.50 | 0.00 | 0.00 | 0.103560E+09 | 0.00 | 0.19 |
May | 0.00 | 0.802876E+10 | 0.00 | 72595.68 | 0.00 | 0.00 | 153737.69 | 0.00 | 0.21 |
June | 0.00 | 0.116711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.138440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.144093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.101606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
October | 5077212.47 | 0.299214E+10 | 0.00 | 4523248.60 | 184856.12 | 0.00 | 0.181281E+09 | 0.00 | 0.18 |
November | 0.327622E+09 | 0.242609E+09 | 0.00 | 18252672.92 | 0.00 | 0.00 | 0.133667E+10 | 0.00 | 0.17 |
December | 0.159172E+10 | 0.00 | 0.00 | 9523483.72 | 0.00 | 0.00 | 0.275804E+10 | 0.00 | 0.16 |
Annual Sum or Average | 0.633582E+10 | 0.650430E+11 | 0.00 | 68010863.83 | 245086.58 | 0.00 | 0.928779E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.290479E+10 | 0.144093E+11 | 0.00 | 18252672.92 | 184856.12 | 0.00 | 0.275804E+10 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.548086E+12 | 0.183079E+11 | 0.00 | 0.175528E+11 | 0.166196E+11 |
February | 0.631251E+12 | 0.207037E+11 | 0.00 | 0.108242E+11 | 0.257951E+11 |
March | 0.908787E+12 | 0.218981E+11 | 0.00 | 0.384052E+10 | 0.561108E+11 |
April | 0.105335E+13 | 0.291206E+11 | 0.00 | -0.598717E+10 | 0.899021E+11 |
May | 0.115443E+13 | 0.374895E+11 | 0.00 | -0.155313E+11 | 0.127141E+12 |
June | 0.105625E+13 | 0.410980E+11 | 0.00 | -0.226000E+11 | 0.136265E+12 |
July | 0.839999E+12 | 0.392011E+11 | 0.00 | -0.268522E+11 | 0.140998E+12 |
August | 0.713992E+12 | 0.428866E+11 | 0.00 | -0.281926E+11 | 0.135596E+12 |
September | 0.756621E+12 | 0.345572E+11 | 0.00 | -0.215267E+11 | 0.109037E+12 |
October | 0.762303E+12 | 0.325840E+11 | 0.00 | -0.583738E+10 | 0.783041E+11 |
November | 0.637565E+12 | 0.184364E+11 | 0.00 | 0.723704E+10 | 0.459881E+11 |
December | 0.512213E+12 | 0.201218E+11 | 0.00 | 0.167595E+11 | 0.242949E+11 |
Annual Sum or Average | 0.957485E+13 | 0.356405E+12 | 0.00 | -0.703133E+11 | 0.986051E+12 |
Minimum of Months | 0.512213E+12 | 0.183079E+11 | 0.00 | -0.281926E+11 | 0.166196E+11 |
Maximum of Months | 0.115443E+13 | 0.428866E+11 | 0.00 | 0.175528E+11 | 0.140998E+12 |