Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 10:43:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 592.97 | 122.64 | 122.64 |
Net Site Energy | 592.97 | 122.64 | 122.64 |
Total Source Energy | 1630.30 | 337.18 | 337.18 |
Net Source Energy | 1630.30 | 337.18 | 337.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 118.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 156.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 474.09 | 118.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 118.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 156.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 5.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 118.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 156.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.75 | 24.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 98.05 | 24.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.75 | 24.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 98.05 | 24.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 474.088 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 474.088 | 100.00 |
Total On-Site and Utility Electric Sources | 474.088 | 100.00 |
Total Electricity End Uses | 474.088 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 25.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2985.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.9961 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.6188 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.9961 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 9.2031 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.6188 | 46.45 | 2.5587 | |
Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 6.8172 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | 14-DEC-04:10 | - | - | - | - | - | - | - | - | - | - | 19-JUN-11:00 |
Heating | 0.00 | 124983.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13426.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9955.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5063.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1731.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 40289.59 | 124983.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 124983.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13426.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9955.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2758.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1731.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 128.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 495.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 292.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 79.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1501.44 | 128.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 102.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 310.53 | 26.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 102.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 310.53 | 26.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.34 |
ZONE2 FINE STORAGE DIRECT AIR | 3.19 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.03 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.03 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 68459.39 |
PSZ-OFFICE HEATING COIL | 28185.43 |
PSZ-FINE STORAGE HEATING COIL | 87601.92 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 68459.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-FINE STORAGE | 3.19 | 3.19 | 3.19 | 3.19 | 3.19 | 3.19 | 1.00 | 1.00 | 3.19 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.34 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.19 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.34 | 1481.67 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.19 | 3417.12 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 0.883254 | 22153.01 | 28185.43 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.19 | 3.19 | 3.19 | 2.11 | 61265.21 | 87601.92 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.34 | 0.669132 | 0.892173 | 22153.01 | 11076.50 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 3.19 | 1.60 | 2.13 | 61265.21 | 30632.60 | 0.793230 | 0.793230 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 9.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.203 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.619 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.177 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2131.000 | 8.996 | 167.154 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2131.000 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 12823.730 | 9.203 | 427.458 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12823.730 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 18007.220 | 5.619 | 260.974 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 18007.220 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3818_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3818_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.169 | 2.169 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44070E-002 | 0.31435 | 0.47919 | 0.47919 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11919 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4061E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0519E-003 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2438E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1177E-003 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2236E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2147E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5727E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2026E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5470E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6742E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1385E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3226E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4084E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7903E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7631E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3735E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5699E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7177E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6716E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0076E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.0491E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0637E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2192E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2548E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0700E-003 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5394E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7195E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6551E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6244E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2442E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0518E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7651E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1351E-003 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0948E-004 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1810E-003 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1440E-004 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4137E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7952E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3050E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9351E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6275E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1529E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3538E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3842E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8967E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8238E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9123E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6423E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6628E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4062E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0006E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6966E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0127E-003 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9011E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8041E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6567E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0041E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1727E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4102E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2406E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9774E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0040E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7108E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9807E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4328E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8307E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2899E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0196E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5234E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3393E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3923E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9389E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9517E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.1113E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4310E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7666E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1037E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5398E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4880E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3403E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2042E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3256E-003 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6392E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5939E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9779E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7387E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2548E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9448E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5442E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8041E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3457E-004 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2535E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3084E-004 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4697E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7670E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2140E-003 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0461E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7686E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6960E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7304E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5017E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8411E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0952E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8074E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0116E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1520E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4448E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0775E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3384E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7315E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0607E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9054E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3399E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8649E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6857E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5426E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5677E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0074E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6204E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6978E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4517E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3344E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2394E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4252E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7712E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1851E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1603E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7987E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3216E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3680E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6774E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2111E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5949E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3705E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6179E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6280E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1034E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8802E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5752E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0688E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0406E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4671E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2840E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8788E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1493E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3310E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1995E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1421E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0368E-004 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4089E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6674E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8401E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1974E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9578E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2600E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9091E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0543E-004 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0518E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6649E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6333E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2809E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8316E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8055E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9371E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0799E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4861E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2818E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6078E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6851E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5808E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7172E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9412E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7389E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0118E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0481E-004 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5886E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3128E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3497E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4686E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6361E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4883E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0830E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2532E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5335E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8506E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7586E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1658E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6557E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6398E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0151E-004 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2519E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1885E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7599E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2862E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8098E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1679E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7769E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4963E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0473E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9439E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4690E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1446E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6441E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0899E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4921E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3267E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8908E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8211E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3923E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1872E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5458E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3317E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4558E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2742E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8995E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7855E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3458E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5178E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2908E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3159E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8769E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8621E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8972E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3063E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2600E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5951E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1885E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0397E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8096E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1993E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9000E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0465E-003 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4891E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5541E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2691E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2866E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4737E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9387E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9915E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5702E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5900E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1816E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5613E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0807E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2567E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4528E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4291E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2389E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5481E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6405E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5108E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2505E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2142E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4481E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4336E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8360E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4298E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6161E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2023E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6559E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3948E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4994E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9975E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9790E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0128E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3718E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7451E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0837E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6556E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6480E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9750E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5670E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9944E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2399E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7233E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0601E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6029E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6804E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9810E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9042E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8047E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0521E-004 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5221E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3830E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2451E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2336E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3923E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2355E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7420E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9882E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4499E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4150E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2279E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7122E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3968E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7651E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3649E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4013E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1615E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5482E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4529E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7179E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8771E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0145E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6404E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2039E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9512E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8281E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9496E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4441E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6872E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7148E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4371E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3668E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2323E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9657E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7904E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0100E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1582E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5852E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3642E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0444E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1640E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7811E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4753E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1567E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8744E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2992E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9612E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7485E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7501E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4169E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1284E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4683E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0363E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5247E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5823E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1901E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2922E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9914E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3428E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0583E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2024E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5078E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9315E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6827E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7404E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4700E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2066E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6958E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0355E-004 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9366E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6359E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4565E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9522E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5133E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9870E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8063E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6788E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7598E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5785E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6158E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2906E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9677E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3505E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2929E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2011E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1450E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.6458E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6293E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0600E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.0173E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.8190E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7782E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8599E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.0221E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7516E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.1030E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.2671E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.1461E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8978E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.1367E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9649E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8464E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9937E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5966E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7308E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8355E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4418E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1473E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.5869E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0592E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.0227E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5977E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7441E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8361E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4084E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1467E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5869E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0592E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11149.40691 | 13379.28829 | 1.11522 | 1.33826 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.75000 | 5.69729E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8363.22430 | 10035.86915 | 0.28537 | 0.34245 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 34132.14906 | 40958.57887 | 2.66119 | 3.19343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22358.40510 | 26830.08612 | 0.64274 | 0.77128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -7.90000 | 2.34317E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 57049.50022 | 68459.40026 | 1.69471 | 2.03365 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16874.68 | 1.33826 | 1.33826 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9405.27 | 0.34245 | 0.34245 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 50268.93 | 3.19343 | 3.19343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 28677.65 | 0.77128 | 0.77128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33826 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.19343 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.03365 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.03365 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 68459.39311 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 68459.40026 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33826 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33826 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33826 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33826 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33826 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.33826 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.19343 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.19343 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.19343 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.19343 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.19343 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.19343 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.33826 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.19343 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33826 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33826 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1481.66981 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33826 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33826 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33826 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88325 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33826 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66913 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89217 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22153.01000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11076.50500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22153.01000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28185.42829 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28185.42829 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.19343 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.19343 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3417.11794 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.19343 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.19343 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.19343 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.10766 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.19343 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.59671 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.12895 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61265.21000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30632.60500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79323 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79323 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61265.21000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87601.91983 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 87601.91983 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21114.6 | 11.40 | 11.14 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 58785.9 | 11.57 | 11.31 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 9.2129474855E-002 | 0.1040349295 | Pass | Pass | 1.3095904326E-002 | 9.3932647960E-002 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2514392238 | 0.2884300339 | Pass | Pass | 0.3328317396 | 1.9601837302 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.1532361691E-002 | 3.6093956142E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11227.63 | 456.17 | 0.00 | 54.70 | 171.35 | 11909.91 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.169 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3818_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.169 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 3.832 | 0.563 | 0.561 | |||||||||||||||||
North Total or Average | 6.51 | 2.169 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 79.53 | 3.968 | 0.576 | 0.574 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.9961 | 236.88 | 2131.00 | LightsWired | LTG_SCH_OFFICE | 51.55 | 168.00 | 45.91 | 0.0000 | Y | 18.36 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 9.2031 | 1393.41 | 12823.73 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 25.90 | 0.0000 | Y | 62.35 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.6188 | 3204.84 | 18007.22 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 22.45 | 0.0000 | Y | 75.89 |
Interior Lighting Total | 6.8172 | 4835.13 | 32961.95 | 156.60 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12823.73 | 3205.93 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12823.73 | 3205.93 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18007.22 | 4501.81 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18007.22 | 4501.81 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2131.00 | 309.00 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 2131.00 | 106.55 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 94.73 | AstronomicalClock | - | 41.81 | 41.81 | 0.74 | |
EXTERIOR_LIGHTS_B | 6863.48 | AstronomicalClock | - | 83.71 | 71.14 | 91.65 | |
Exterior Lighting Total | 6958.21 | 92.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22153.01 | 17737.03 | 4415.98 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61265.21 | 48597.40 | 12667.81 | 0.79 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21114.6 | 11.40 | 11.14 | ||||
PSZ-FINE STORAGE COOLING COIL | 58785.9 | 11.57 | 11.31 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 68459.39 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28185.43 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 87601.92 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.03 | 188.95 | 92.91 | 1.00 | 3.57 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1481.67 | 1107.16 | 1.00 | 1.34 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.19 | 3417.12 | 1070.05 | 1.00 | 1.26 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11149.41 | 13379.29 | 56.48 | 1.115 | 1.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 23.90 | 23.90 | 0.00818 | 33.75 | 0.00570 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34132.15 | 40958.58 | 29.39 | 2.661 | 3.193 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00806 | 35.10 | 0.00570 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 34.73 | 0.00579 | 34.97 | 0.00570 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8363.22 | 10035.87 | 42.37 | 0.285 | 0.342 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00772 | -7.90 | 0.00234 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22358.41 | 26830.09 | 19.25 | 0.643 | 0.771 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00638 | -7.90 | 0.00234 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 57049.50 | 68459.40 | 21.36 | 1.695 | 2.034 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00512 | -7.90 | 0.00234 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.34 | 1.34 | 0.34 | 0.34 | 1.3383 | 1.3383 | 1.3383 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.19 | 3.19 | 0.77 | 0.77 | 3.1934 | 3.1934 | 3.1934 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 68459.393 | 68459.393 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 68459.39 | 68459.39 | 2.033651 | 10.00 | 5.66 | 0.00512373 | 43.33 | 19.83 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 10.00 | 0.00512373 | 55.4510 | 68459.40 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22153.010 | 17737.029 | 1.338260 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 11076.50 | 11076.50 | 0.892173 | 25.78 | 14.57 | 0.00799331 | 12.00 | 9.53 | 0.00799331 | 34.11 | 0.00569784 | 15.46 | 11.4647 | 23.90 | 0.00818344 | 36.4707 | 11140.35 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28185.428 | 28185.428 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28185.43 | 28185.43 | 1.338263 | 18.84 | 11.53 | 0.00730470 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.6431 | 21.10 | 0.00771530 | 40.7932 | 8363.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 61265.210 | 48597.403 | 3.193430 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30632.60 | 30632.60 | 2.128953 | 28.88 | 15.39 | 0.00775000 | 12.00 | 9.29 | 0.00775000 | 35.10 | 0.00569938 | 15.77 | 19.9493 | 26.70 | 0.00806456 | 30.4317 | 34132.15 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 87601.920 | 87601.920 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 87601.92 | 87601.92 | 3.193427 | 12.44 | 7.53 | 0.00584469 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 13.2995 | 15.56 | 0.00638181 | 47.8824 | 22358.41 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 68459.393 | 68459.393 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.033651 | 2.01414575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 68459.39 | 68459.39 | 1.0000 | 2.01414575 | 2.033651 | 10.00 | 5.66 | 0.00512373 | 22955.5 | 43.33 | 19.83 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68459.39 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 10.00 | 0.00512373 | 10.00 | 0.00512373 | 55.4510 | 68459.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22153.010 | 17737.029 | 1.338260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6992 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.338263 | 1.32542779 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 11076.50 | 11076.50 | 1.0000 | 0.88361640 | 0.892173 | 25.78 | 14.57 | 0.00799331 | 46275.1 | 12.00 | 9.53 | 0.00799331 | 32227.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11076.50 | 34.11 | 0.00569784 | 15.46 | 0.10228463 | 11.4647 | 23.90 | 0.00818344 | 23.90 | 0.00818344 | 36.4707 | 11140.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28185.428 | 28185.428 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.338263 | 1.32542779 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 28185.43 | 28185.43 | 1.0000 | 1.32542779 | 1.338263 | 18.84 | 11.53 | 0.00730470 | 37453.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28185.43 | -7.90 | 0.00234317 | -7.90 | 0.10228463 | 7.6431 | 21.05 | 0.00771530 | 21.10 | 0.00771530 | 40.7932 | 8363.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61265.210 | 48597.403 | 3.193430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2469 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.193427 | 3.16279859 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 30632.60 | 30632.60 | 1.0000 | 2.10853432 | 2.128953 | 28.88 | 15.39 | 0.00775000 | 48815.1 | 12.00 | 9.29 | 0.00775000 | 31613.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30632.60 | 35.10 | 0.00569938 | 15.77 | 0.42471127 | 19.9493 | 26.70 | 0.00806456 | 26.70 | 0.00806456 | 30.4317 | 34132.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87601.920 | 87601.920 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.193427 | 3.16279859 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 87601.92 | 87601.92 | 1.0000 | 3.16279859 | 3.193427 | 12.44 | 7.53 | 0.00584469 | 27248.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87601.92 | -7.90 | 0.00234317 | -7.90 | 0.42471127 | 13.2995 | 15.56 | 0.00638181 | 15.56 | 0.00638181 | 47.8824 | 22358.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.34 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.19 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2659.67 | 2138.50 | 1399.50 |
ZONE2 FINE STORAGE | 3172.83 | 2855.17 | 2482.83 |
ZONE3 BULK STORAGE | 3280.33 | 3280.67 | 2967.17 |
Facility | 3446.67 | 3305.00 | 2985.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 13.83 | 0.50 | 12.33 | 0.00 |
ZONE2 FINE STORAGE | 168.83 | 62.67 | 16.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 179.50 | 63.17 | 25.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.653 | 0.425 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.625 | 0.226 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.136 | 0.000 | 0.515 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2366615.68 | 0.00 | 2366615.68 | 2293800.41 | 4660416.08 | 3225648.14 | 5680.23 | 2273.86 | 805.91 | 0.57 |
ZONE2 FINE STORAGE | 6786538.32 | 0.00 | 6786538.32 | 6671322.63 | 13457860.95 | 13393694.68 | 5655.74 | 2464.10 | 640.16 | 34.41 |
ZONE3 BULK STORAGE | 0.00 | 0.10E+09 | 0.10E+09 | 37465936.27 | 0.14E+09 | 30805497.77 | 7305.31 | 34.09 | 1420.60 | 4974.46 |
Total Facility | 9153154.00 | 0.10E+09 | 0.11E+09 | 46431059.31 | 0.16E+09 | 47424840.58 | 7976.79 | 2744.39 | 2362.76 | 4974.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1807 | 0.0000 | 0.1807 | 0.1180 | 0.2987 | 0.1023 | 556.80 | 2273.86 | 805.34 |
ZONE2 FINE STORAGE | 0.5048 | 0.0000 | 0.5048 | 0.1837 | 0.6885 | 0.4247 | 565.77 | 2464.10 | 606.13 |
ZONE3 BULK STORAGE | 0.0000 | 4.8490 | 4.8490 | 1.3221 | 6.1711 | 0.9768 | 2822.97 | 13.00 | 800.03 |
Total Facility | 0.6855 | 4.8490 | 5.5345 | 1.6238 | 7.1583 | 1.5038 | 2852.79 | 2723.30 | 1712.69 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2321374.99 | 0.00 | 2321374.99 | 3225648.14 | 7954.09 | 1.33 | 804.58 | 0.57 |
PSZ-FINE STORAGE | 6656974.73 | 0.00 | 6656974.73 | 13393694.68 | 8119.51 | 1.33 | 639.16 | 34.41 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1773 | 0.0000 | 0.1773 | 0.1023 | 2830.66 | 1.33 | 804.01 |
PSZ-FINE STORAGE | 0.4951 | 0.0000 | 0.4951 | 0.4247 | 3029.53 | 1.33 | 605.13 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2805.46 | 279.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2911.66 | 205.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1968 | 0.3321 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5651 | 0.8512 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
Electricity:Building | 301.62 | 1663.58 | 19-FEB-14:10 | 25786.98 | 21-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 50.31 | 815.73 | 05-FEB-16:10 | 3198.43 | 13-NOV-17:00 |
Electricity:SpaceType:GENERAL | 295.89 | 1663.58 | 19-FEB-14:10 | 25786.98 | 21-DEC-16:00 |
InteriorLights:Electricity | 156.60 | 1089.83 | 19-FEB-14:10 | 15674.36 | 21-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.36 | 241.98 | 05-FEB-16:10 | 1285.93 | 13-NOV-17:00 |
InteriorLights:Electricity:SpaceType:GENERAL | 156.60 | 1089.83 | 19-FEB-14:10 | 15674.36 | 21-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 156.60 | 1089.83 | 19-FEB-14:10 | 15674.36 | 21-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.36 | 241.98 | 05-FEB-16:10 | 1285.93 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 156.60 | 1089.83 | 19-FEB-14:10 | 15674.36 | 21-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 62.35 | 352.65 | 16-JAN-10:30 | 5995.09 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 62.35 | 352.65 | 16-JAN-10:30 | 5995.09 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 62.35 | 352.65 | 16-JAN-10:30 | 5995.09 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 188.96 | 495.20 | 16-JAN-09:10 | 16819.20 | 20-SEP-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 75.89 | 495.20 | 16-JAN-09:10 | 8418.38 | 02-JAN-15:20 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 75.89 | 495.20 | 16-JAN-09:10 | 8418.38 | 02-JAN-15:20 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 32.34 | 0.00 | 01-JAN-00:40 | 5387.06 | 28-JUN-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 5.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUN-13:10 |
Ventilation (simple):Fans:Electricity | 5.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUN-13:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 5.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUN-13:10 |
ElectricityPurchased:Facility | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
ElectricityNet:Plant | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
General:Cogeneration:ElectricityNet | 474.09 | 2146.58 | 19-FEB-14:10 | 40289.59 | 28-JUN-15:00 |
Electricity:HVAC | 54.85 | 0.00 | 01-JAN-00:40 | 17483.00 | 28-JUN-16:10 |
General:Fans:Electricity | 26.62 | 0.00 | 01-JAN-00:40 | 3240.61 | 17-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 28.23 | 0.00 | 01-JAN-00:10 | 14401.23 | 28-JUN-16:10 |
General:Cooling:Electricity | 28.23 | 0.00 | 01-JAN-00:10 | 14401.23 | 28-JUN-16:10 |
ExteriorLights:Electricity | 92.40 | 0.00 | 01-JAN-07:20 | 6958.21 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.40 | 0.00 | 01-JAN-07:20 | 6958.21 | 01-JAN-06:10 |
Electricity:Plant | 25.22 | 483.00 | 02-JAN-06:10 | 2363.57 | 06-FEB-13:00 |
WaterSystems:Electricity | 25.22 | 483.00 | 02-JAN-06:10 | 2363.57 | 06-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.22 | 483.00 | 02-JAN-06:10 | 2363.57 | 06-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 118.88 | 0.00 | 01-JAN-00:40 | 124983.07 | 14-DEC-04:10 |
NaturalGas:HVAC | 118.88 | 0.00 | 01-JAN-00:40 | 124983.07 | 14-DEC-04:10 |
Heating:NaturalGas | 118.88 | 0.00 | 01-JAN-00:40 | 124983.07 | 14-DEC-04:10 |
General:Heating:NaturalGas | 118.88 | 0.00 | 01-JAN-00:40 | 124983.07 | 14-DEC-04:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 397.14 | 0.00 | 01-JAN-00:40 | 195259.99 | 14-DEC-04:10 |
EnergyTransfer:Building | 200.26 | 0.00 | 01-JAN-00:40 | 98136.64 | 14-DEC-04:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 49.26 | 0.00 | 01-JAN-00:10 | 18790.40 | 06-FEB-07:10 |
Heating:EnergyTransfer | 84.35 | 0.00 | 01-JAN-00:40 | 98136.64 | 14-DEC-04:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 13.04 | 0.00 | 01-JAN-00:10 | 18790.40 | 06-FEB-07:10 |
General:Heating:EnergyTransfer | 84.35 | 0.00 | 01-JAN-00:40 | 98136.64 | 14-DEC-04:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 13.04 | 0.00 | 01-JAN-00:10 | 18790.40 | 06-FEB-07:10 |
Cooling:EnergyTransfer | 115.90 | 0.00 | 01-JAN-00:10 | 37938.74 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 36.23 | 0.00 | 01-JAN-00:10 | 12465.38 | 28-JUN-16:10 |
General:Cooling:EnergyTransfer | 115.90 | 0.00 | 01-JAN-00:10 | 37938.74 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 36.23 | 0.00 | 01-JAN-00:10 | 12465.38 | 28-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 112.18 | 0.00 | 01-JAN-00:40 | 33091.94 | 14-DEC-04:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 32.50 | 0.00 | 01-JAN-00:40 | 33091.94 | 14-DEC-04:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 32.50 | 0.00 | 01-JAN-00:40 | 33091.94 | 14-DEC-04:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 79.68 | 0.00 | 01-JAN-00:10 | 27785.13 | 22-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 79.68 | 0.00 | 01-JAN-00:10 | 27785.13 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 38.82 | 0.00 | 01-JAN-00:10 | 67593.35 | 16-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 38.82 | 0.00 | 01-JAN-00:10 | 67593.35 | 16-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 38.82 | 0.00 | 01-JAN-00:10 | 67593.35 | 16-JAN-18:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 196.88 | 0.00 | 01-JAN-00:40 | 97123.34 | 14-DEC-04:10 |
HeatingCoils:EnergyTransfer | 86.32 | 0.00 | 01-JAN-00:40 | 97123.34 | 14-DEC-04:10 |
CoolingCoils:EnergyTransfer | 110.56 | 0.00 | 01-JAN-00:10 | 47034.27 | 22-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 13.036 | -36.226 | 0.000 | 0.000 | 9.780 | 18.363 | 31.946 | 16.813 | 0.000 | 1.946 | 0.001 | 0.000 | -7.288 | 0.000 | -20.172 | -28.198 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 32.499 | -79.674 | 0.000 | 0.000 | 23.258 | 62.348 | 0.000 | 74.278 | 0.000 | 2.559 | 0.002 | 0.000 | -18.590 | 0.000 | -52.244 | -44.434 |
ZONE3 BULK STORAGE | 38.818 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 54.345 | 75.890 | 107.344 | 737.895 | 0.000 | 23.120 | 0.040 | 0.000 | -148.471 | 0.000 | -372.114 | -516.827 |
Total Facility | 38.818 | 0.000 | 45.535 | -115.900 | 0.000 | 0.000 | 87.383 | 156.601 | 139.290 | 828.986 | 0.000 | 27.625 | 0.042 | 0.000 | -174.348 | 0.000 | -444.531 | -589.459 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-MAY-07:02 | 0.00 | 0.00 | 0.00 | -26437.79 | 0.00 | 0.00 | 801.53 | 1150.83 | 1912.50 | 216.98 | 0.00 | 0.00 | 22626.92 | 0.00 | -0.00 | 0.00 | -270.98 | 0.00 |
ZONE2 FINE STORAGE | 30-JUL-13:13 | 0.00 | 0.00 | 0.00 | -53889.91 | 0.00 | 0.00 | 0.00 | 411.43 | 0.00 | 11952.27 | 0.00 | 495.33 | 41030.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUN-18:03 | 0.00 | 0.00 | 0.00 | -59847.35 | 0.00 | 0.00 | 0.00 | 1855.15 | 573.75 | 12281.62 | 0.00 | 1824.35 | 67374.46 | 0.00 | 0.00 | 0.00 | -24061.99 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-FEB-07:02 | 0.00 | 0.00 | 28686.85 | 0.00 | 0.00 | 0.00 | 261.90 | 699.39 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -623.66 | 0.00 | -9194.15 | -20786.58 |
ZONE2 FINE STORAGE | 14-DEC-04:02 | 0.00 | 0.00 | 89253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1446.62 | 0.00 | -13790.68 | -74721.12 |
ZONE3 BULK STORAGE | 16-JAN-17:55 | 67592.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 12767.92 | 0.00 | -12730.74 | 0.00 | -68620.28 | 0.00 |
Total Facility | 04-FEB-06:01 | 43982.40 | 0.00 | 115791.77 | 0.00 | 0.00 | 0.00 | 1433.82 | 2079.82 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19553.69 | 0.00 | -46293.09 | -100064.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3383 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3383 | 0.0764 | 1.0000 | Not calculated | 0.1023 | 0.0764 | ||
PSZ-FINE STORAGE | 3.1934 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.1934 | 0.1330 | 1.0000 | Not calculated | 0.4247 | 0.1330 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3383 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3383 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0764 | ||
PSZ-FINE STORAGE | 3.1934 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.1934 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1330 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3383 | 1.3383 | 1.3383 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.1934 | 3.1934 | 3.1934 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3383 | 1.3383 | 1.3383 | 1.3383 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.1934 | 3.1934 | 3.1934 | 3.1934 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3383 | 1.3383 | 1.3383 | No | 0.1023 | 0.2987 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.1934 | 3.1934 | 3.1934 | No | 0.4247 | 0.5507 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3383 | 1.3383 | 1.3383 | 1.3383 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.1934 | 3.1934 | 3.1934 | 3.1934 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 25.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 25.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 118.88 | 124983.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 28.23 | 14401.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 156.60 | 15674.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.40 | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 5.72 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 26.62 | 3240.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.22 | 2363.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 474.09 |
Natural Gas | 0.00 | 118.88 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 592.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 32.39 |
Space Heating | 0.00 |
Space Cooling | 5.84 |
Fans (All) | 6.69 |
Service Water Heating | 5.22 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 98.05 |
Subtotal | 98.05 |
Natural Gas [MJ/m2] | |
Space Heating | 24.59 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 24.59 |
Subtotal | 24.59 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.41 |
Space Heating | 20.05 |
Space Cooling | 4.76 |
Fans (All) | 5.45 |
Service Water Heating | 4.25 |
Receptacle Equipment | 23.49 |
Miscellaneous | 15.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2688. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7686.33 | 1073.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8370.83 | 389.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6433.00 | 2294.33 | 32.67 | 0.00 | 0.00 |
Min | 6433.00 | 389.17 | 0.00 | 0.00 | 0.00 |
Max | 8370.83 | 2294.33 | 32.67 | 0.00 | 0.00 |
Average | 7496.72 | 1252.39 | 10.89 | 0.00 | 0.00 |
Sum | 22490.17 | 3757.17 | 32.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32993.17 | 33.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 77504.50 | 5214.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 131431.83 | 58072.50 | 1688.67 | 0.00 | 0.00 |
Min | 32993.17 | 33.83 | 0.00 | 0.00 | 0.00 |
Max | 131431.83 | 58072.50 | 1688.67 | 0.00 | 0.00 |
Average | 80643.17 | 21106.94 | 562.89 | 0.00 | 0.00 |
Sum | 241929.50 | 63320.83 | 1688.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8142.17 | 617.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8241.50 | 518.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6916.17 | 1843.83 | 0.00 | 0.00 | 0.00 |
Min | 6916.17 | 518.50 | 0.00 | 0.00 | 0.00 |
Max | 8241.50 | 1843.83 | 0.00 | 0.00 | 0.00 |
Average | 7766.61 | 993.39 | 0.00 | 0.00 | 0.00 |
Sum | 23299.83 | 2980.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32993.50 | 33.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 76036.00 | 6683.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 142485.33 | 48707.67 | 0.00 | 0.00 | 0.00 |
Min | 32993.50 | 33.50 | 0.00 | 0.00 | 0.00 |
Max | 142485.33 | 48707.67 | 0.00 | 0.00 | 0.00 |
Average | 83838.28 | 18474.72 | 0.00 | 0.00 | 0.00 |
Sum | 251514.83 | 55424.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65706943.66 | 1717.31 | 28-JAN-08:07 | -0.6 | -3.6 | 0.497686E+09 | 687.40 | 05-JAN-16:10 | -0.6 | -3.6 |
February | 71146975.93 | 1808.24 | 11-FEB-08:07 | -1.1 | -2.6 | 0.465557E+09 | 768.97 | 13-FEB-16:00 | 20.60 | 6.59 |
March | 0.166234E+09 | 1703.74 | 18-MAR-07:07 | 1.47 | 0.32 | 0.571070E+09 | 768.96 | 08-MAR-16:49 | 1.47 | 0.32 |
April | 0.161968E+10 | 16634.56 | 29-APR-07:03 | 12.25 | 4.03 | 0.599270E+09 | 848.95 | 29-APR-07:10 | 12.25 | 4.03 |
May | 0.371101E+10 | 26437.90 | 20-MAY-07:02 | 15.37 | 5.00 | 0.653763E+09 | 879.39 | 20-MAY-07:10 | 15.37 | 5.00 |
June | 0.655243E+10 | 25713.51 | 19-JUN-07:02 | 16.38 | 6.57 | 0.664366E+09 | 879.42 | 29-JUN-07:10 | 27.57 | 17.14 |
July | 0.753708E+10 | 23656.19 | 22-JUL-06:01 | 22.15 | 12.93 | 0.640989E+09 | 879.42 | 24-JUL-07:10 | 22.88 | 15.84 |
August | 0.754182E+10 | 24254.85 | 19-AUG-06:02 | 18.77 | 12.01 | 0.691695E+09 | 879.40 | 21-AUG-07:10 | 22.38 | 15.71 |
September | 0.574178E+10 | 22569.50 | 16-SEP-07:02 | 15.47 | 11.37 | 0.638472E+09 | 879.39 | 16-SEP-07:10 | 15.47 | 11.37 |
October | 0.285373E+10 | 22328.42 | 07-OCT-07:02 | 16.88 | 11.74 | 0.609185E+09 | 879.39 | 07-OCT-07:10 | 16.88 | 11.74 |
November | 0.291236E+09 | 2195.23 | 02-NOV-15:00 | 17.20 | 9.31 | 0.505523E+09 | 768.96 | 03-NOV-15:30 | 12.50 | 2.61 |
December | 75672051.09 | 1801.03 | 30-DEC-08:07 | -0.8 | -3.8 | 0.495739E+09 | 688.06 | 02-DEC-15:50 | -0.8 | -3.8 |
Annual Sum or Average | 0.362275E+11 | 0.703331E+10 | ||||||||
Minimum of Months | 65706943.66 | 1703.74 | -1.1 | -3.8 | 0.465557E+09 | 687.40 | -0.8 | -3.8 | ||
Maximum of Months | 0.754182E+10 | 26437.90 | 22.15 | 12.93 | 0.691695E+09 | 879.42 | 27.57 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165529E+10 | 5158.68 | 20-JAN-13:20 | 0.33 | -0.3 | 0.751665E+09 | 1226.30 | 05-JAN-15:50 | 0.33 | -0.3 |
February | 0.173550E+10 | 5155.01 | 16-FEB-09:30 | 0.60 | -0.2 | 0.732713E+09 | 1520.82 | 14-FEB-15:00 | 0.60 | -0.2 |
March | 0.143994E+10 | 4940.09 | 18-MAR-07:03 | 1.47 | 0.32 | 0.101634E+10 | 1589.71 | 13-MAR-14:00 | 1.47 | 0.32 |
April | 0.156923E+10 | 4934.90 | 29-APR-12:50 | 22.62 | 9.02 | 0.137678E+10 | 2246.80 | 28-APR-13:50 | 22.62 | 9.02 |
May | 0.451101E+10 | 41346.51 | 19-MAY-17:08 | 29.90 | 12.04 | 0.174924E+10 | 2246.81 | 22-MAY-10:50 | 25.40 | 14.69 |
June | 0.142661E+11 | 52655.53 | 25-JUN-13:13 | 32.93 | 17.45 | 0.189965E+10 | 2247.00 | 28-JUN-14:20 | 37.97 | 14.19 |
July | 0.198764E+11 | 53891.03 | 30-JUL-13:13 | 31.47 | 17.58 | 0.185406E+10 | 2247.02 | 22-JUL-14:30 | 31.47 | 17.58 |
August | 0.174534E+11 | 52563.55 | 06-AUG-13:53 | 32.20 | 16.67 | 0.199939E+10 | 2246.95 | 15-AUG-10:50 | 26.60 | 18.27 |
September | 0.907706E+10 | 52937.85 | 03-SEP-13:23 | 31.95 | 16.76 | 0.182872E+10 | 2246.92 | 06-SEP-13:39 | 25.20 | 16.21 |
October | 0.365177E+10 | 41002.43 | 01-OCT-14:13 | 28.30 | 13.40 | 0.149111E+10 | 2246.87 | 02-OCT-10:00 | 23.90 | 14.77 |
November | 0.200070E+10 | 5540.16 | 04-NOV-07:03 | 0.78 | 0.12 | 0.879704E+09 | 1690.71 | 02-NOV-15:09 | 0.78 | 0.12 |
December | 0.244069E+10 | 5527.27 | 06-DEC-09:50 | -0.5 | -3.3 | 0.728313E+09 | 1189.16 | 02-DEC-15:20 | -0.5 | -3.3 |
Annual Sum or Average | 0.796771E+11 | 0.163077E+11 | ||||||||
Minimum of Months | 0.143994E+10 | 4934.90 | -0.5 | -3.3 | 0.728313E+09 | 1189.16 | -0.5 | -3.3 | ||
Maximum of Months | 0.198764E+11 | 53891.03 | 32.93 | 17.58 | 0.199939E+10 | 2247.02 | 37.97 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 | -1.2 | 0.901890E+09 | 1638.29 | 05-JAN-15:30 | 16.10 | 6.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.2 | -5.2 | 0.894002E+09 | 1909.01 | 14-FEB-16:00 | 21.10 | 7.24 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 | 0.149980E+10 | 2375.80 | 16-MAR-14:50 | 20.10 | 8.53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 | 0.240299E+10 | 4432.33 | 29-APR-15:00 | 25.60 | 10.03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 | 0.364094E+10 | 5760.20 | 19-MAY-15:00 | 30.00 | 12.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 | 0.526497E+10 | 9097.65 | 27-JUN-15:09 | 37.30 | 15.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 | 0.565606E+10 | 9097.65 | 20-JUL-14:09 | 37.02 | 15.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 | 0.576275E+10 | 8385.24 | 01-AUG-15:00 | 35.00 | 16.30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 | 0.480270E+10 | 7094.15 | 02-SEP-15:30 | 31.40 | 16.12 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 | 0.340382E+10 | 6286.53 | 06-OCT-15:20 | 27.80 | 12.63 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 | 0.153617E+10 | 3045.10 | 02-NOV-14:50 | 16.93 | 9.25 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 | 0.889571E+09 | 1705.09 | 02-DEC-15:09 | 12.02 | 3.50 |
Annual Sum or Average | 0.00 | 0.366557E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.889571E+09 | 1638.29 | 12.02 | 3.50 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.576275E+10 | 9097.65 | 37.30 | 16.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352825E+10 | 28560.97 | 17-JAN-07:02 | -3.9 |
February | 0.271588E+10 | 28686.92 | 06-FEB-07:02 | -5.4 |
March | 0.144817E+10 | 28376.62 | 31-MAR-06:01 | 3.40 |
April | 0.246758E+09 | 27749.80 | 08-APR-06:02 | 1.78 |
May | 76892696.83 | 10583.39 | 04-MAY-07:03 | 7.15 |
June | 31669729.65 | 1301.92 | 26-JUN-06:04 | 19.97 |
July | 15055645.48 | 1271.18 | 20-JUL-06:04 | 20.78 |
August | 27959944.46 | 1334.39 | 09-AUG-06:04 | 17.15 |
September | 47588506.17 | 1249.53 | 05-SEP-06:05 | 15.10 |
October | 0.256125E+09 | 28101.61 | 26-OCT-06:02 | -1.4 |
November | 0.127227E+10 | 28398.58 | 06-NOV-07:01 | 1.88 |
December | 0.336915E+10 | 28489.65 | 15-DEC-07:02 | -8.1 |
Annual Sum or Average | 0.130358E+11 | |||
Minimum of Months | 15055645.48 | 1249.53 | -8.1 | |
Maximum of Months | 0.352825E+10 | 28686.92 | 20.78 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109552E+11 | 88999.02 | 16-JAN-18:22 | -1.4 |
February | 0.736325E+10 | 88870.98 | 06-FEB-05:12 | -4.4 |
March | 0.158469E+10 | 65214.14 | 04-MAR-07:01 | -1.3 |
April | 0.202263E+09 | 2080.67 | 01-APR-16:20 | 24.40 |
May | 0.109346E+09 | 1468.13 | 11-MAY-07:00 | 11.70 |
June | 54427059.17 | 1504.84 | 28-JUN-06:03 | 22.15 |
July | 11303535.60 | 1806.83 | 24-JUL-06:03 | 22.30 |
August | 38697583.61 | 1709.09 | 22-AUG-06:03 | 20.60 |
September | 0.101149E+09 | 1417.28 | 01-SEP-07:00 | 18.90 |
October | 0.126411E+09 | 1488.65 | 31-OCT-16:10 | 23.03 |
November | 0.162298E+10 | 63072.16 | 27-NOV-06:01 | -4.4 |
December | 0.103297E+11 | 89250.62 | 14-DEC-04:02 | -1.4 |
Annual Sum or Average | 0.324994E+11 | |||
Minimum of Months | 11303535.60 | 1417.28 | -4.4 | |
Maximum of Months | 0.109552E+11 | 89250.62 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147372E+11 | 67593.62 | 16-JAN-18:00 | -1.7 |
February | 0.109127E+11 | 58559.57 | 05-FEB-02:00 | -2.8 |
March | 0.466726E+09 | 17628.98 | 04-MAR-05:55 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.127013E+11 | 67096.08 | 14-DEC-03:54 | -1.1 |
Annual Sum or Average | 0.388179E+11 | |||
Minimum of Months | 0.00 | 0.00 | -2.8 | |
Maximum of Months | 0.147372E+11 | 67593.62 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157178E+10 | 1268.23 | 04-JAN-16:00 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.141386E+10 | 1265.11 | 16-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.160014E+10 | 1254.61 | 20-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.147863E+10 | 1186.59 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.154026E+10 | 1236.42 | 22-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.152921E+10 | 1240.07 | 08-JUN-15:00 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.151192E+10 | 1237.88 | 07-JUL-15:00 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.156559E+10 | 1201.37 | 17-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.150418E+10 | 1263.63 | 08-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.155309E+10 | 1263.48 | 25-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.150831E+10 | 1285.93 | 13-NOV-16:00 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.158621E+10 | 1285.93 | 01-DEC-16:00 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.183632E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.141386E+10 | 1186.59 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.160014E+10 | 1285.93 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.573253E+10 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.507957E+10 | 5995.09 | 02-FEB-09:09 | 0.00 | 0.00 |
March | 0.543933E+10 | 5995.09 | 04-MAR-15:00 | 0.00 | 0.00 |
April | 0.467986E+10 | 5495.50 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.480981E+10 | 4995.91 | 02-MAY-08:09 | 0.00 | 0.00 |
June | 0.491806E+10 | 5495.50 | 08-JUN-08:09 | 0.00 | 0.00 |
July | 0.471271E+10 | 5289.79 | 19-JUL-07:10 | 0.00 | 0.00 |
August | 0.488494E+10 | 5495.50 | 07-AUG-08:09 | 0.00 | 0.00 |
September | 0.500107E+10 | 5995.09 | 20-SEP-08:09 | 0.00 | 0.00 |
October | 0.555729E+10 | 5995.09 | 04-OCT-08:09 | 0.00 | 0.00 |
November | 0.549909E+10 | 5995.09 | 02-NOV-14:50 | 0.00 | 0.00 |
December | 0.603422E+10 | 5995.09 | 01-DEC-15:39 | 0.00 | 0.00 |
Annual Sum or Average | 0.623485E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.467986E+10 | 4995.91 | 0.00 | 0.00 | |
Maximum of Months | 0.603422E+10 | 5995.09 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.714898E+10 | 8418.38 | 02-JAN-15:20 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.623316E+10 | 7716.84 | 04-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.660976E+10 | 7427.98 | 04-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.567408E+10 | 6189.98 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.577109E+10 | 6189.98 | 22-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.586986E+10 | 6313.78 | 08-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.569847E+10 | 6189.98 | 07-JUL-15:50 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.593894E+10 | 6189.98 | 02-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.604511E+10 | 7427.98 | 08-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.678615E+10 | 7427.98 | 04-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.672698E+10 | 8418.38 | 06-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.738710E+10 | 8418.38 | 02-DEC-15:50 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.758897E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.567408E+10 | 6189.98 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.738710E+10 | 8418.38 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.157178E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299411E+10 |
February | 0.127628E+10 | 0.141386E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259414E+10 |
March | 0.149825E+10 | 0.160014E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233231E+10 |
April | 0.138726E+10 | 0.147863E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16416238.03 | 0.155994E+10 |
May | 0.144276E+10 | 0.154026E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94757009.64 | 0.133625E+10 |
June | 0.144276E+10 | 0.152921E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545187E+09 | 0.694603E+09 |
July | 0.138726E+10 | 0.151192E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619217E+09 | 0.398491E+09 |
August | 0.149825E+10 | 0.156559E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452137E+09 | 0.593537E+09 |
September | 0.138726E+10 | 0.150418E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181664E+09 | 0.806514E+09 |
October | 0.138726E+10 | 0.155309E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36385943.84 | 0.164121E+10 |
November | 0.133177E+10 | 0.150831E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227778E+10 |
December | 0.138726E+10 | 0.158621E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294322E+10 |
Annual Sum or Average | 0.168137E+11 | 0.183632E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194576E+10 | 0.201721E+11 |
Minimum of Months | 0.127628E+10 | 0.141386E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398491E+09 |
Maximum of Months | 0.149825E+10 | 0.160014E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619217E+09 | 0.299411E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.573253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672531E+10 |
February | 0.300332E+10 | 0.507957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170020.99 | 0.627206E+10 |
March | 0.352563E+10 | 0.543933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541856.35 | 0.567308E+10 |
April | 0.326447E+10 | 0.467986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10979036.94 | 0.459802E+10 |
May | 0.339505E+10 | 0.480981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78692405.35 | 0.444671E+10 |
June | 0.339505E+10 | 0.491806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794214E+09 | 0.252214E+10 |
July | 0.326447E+10 | 0.471271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102927E+10 | 0.147366E+10 |
August | 0.352563E+10 | 0.488494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529139E+09 | 0.210768E+10 |
September | 0.326447E+10 | 0.500107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110130E+09 | 0.283659E+10 |
October | 0.326447E+10 | 0.555729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5668598.02 | 0.447042E+10 |
November | 0.313390E+10 | 0.549909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509294E+10 |
December | 0.326447E+10 | 0.603422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602556E+10 |
Annual Sum or Average | 0.395654E+11 | 0.623485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255880E+10 | 0.522442E+11 |
Minimum of Months | 0.300332E+10 | 0.467986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147366E+10 |
Maximum of Months | 0.352563E+10 | 0.603422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102927E+10 | 0.672531E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.714898E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169003E+09 | 0.218657E+11 |
February | 0.690763E+10 | 0.623316E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374779E+09 | 0.202395E+11 |
March | 0.810895E+10 | 0.660976E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103056E+10 | 0.180908E+11 |
April | 0.750829E+10 | 0.567408E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118973E+10 | 0.160593E+11 |
May | 0.780862E+10 | 0.577109E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740803E+09 | 0.199369E+11 |
June | 0.780862E+10 | 0.586986E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551945E+09 | 0.149992E+11 |
July | 0.750829E+10 | 0.569847E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269547E+09 | 0.120491E+11 |
August | 0.810895E+10 | 0.593894E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61016702.26 | 0.157226E+11 |
September | 0.750829E+10 | 0.604511E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9692454.72 | 0.178552E+11 |
October | 0.750829E+10 | 0.678615E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65303875.19 | 0.238711E+11 |
November | 0.720796E+10 | 0.672698E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11407893.42 | 0.207315E+11 |
December | 0.750829E+10 | 0.738710E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15314867.69 | 0.203110E+11 |
Annual Sum or Average | 0.910005E+11 | 0.758897E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448910E+10 | 0.221732E+12 |
Minimum of Months | 0.690763E+10 | 0.567408E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9692454.72 | 0.120491E+11 |
Maximum of Months | 0.810895E+10 | 0.738710E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118973E+10 | 0.238711E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1268.23 | 04-JAN-16:00 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10430.08 | 17-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1265.11 | 16-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9747.70 | 06-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1254.61 | 20-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7946.78 | 10-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1186.59 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 755.94 | 13-APR-17:00 | 6251.25 | 06-APR-06:04 |
May | 1680.92 | 01-MAY-07:10 | 1236.42 | 22-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.40 | 19-MAY-17:00 | 5772.78 | 04-MAY-06:03 |
June | 1680.92 | 01-JUN-07:10 | 1240.07 | 08-JUN-15:00 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4563.69 | 28-JUN-16:10 | 5063.00 | 09-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1237.88 | 07-JUL-15:00 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4364.81 | 21-JUL-17:00 | 2490.41 | 28-JUL-06:03 |
August | 1680.92 | 01-AUG-07:10 | 1201.37 | 17-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.88 | 01-AUG-16:10 | 3926.81 | 31-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1263.63 | 08-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2276.44 | 20-SEP-17:00 | 4500.84 | 27-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1263.48 | 25-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.00 | 06-OCT-16:10 | 8205.94 | 24-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1285.93 | 13-NOV-16:00 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8310.27 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1285.93 | 01-DEC-16:00 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9890.61 | 22-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1186.59 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2490.41 | |||||
Maximum of Months | 1680.92 | 1285.93 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4563.69 | 10430.08 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14715.79 | 16-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 5995.09 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 14-FEB-16:10 | 11649.18 | 05-FEB-00:55 |
March | 3955.50 | 01-MAR-08:09 | 5995.09 | 04-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 | 08-MAR-16:10 | 11824.78 | 14-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 5495.50 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.05 | 01-APR-17:20 | 13630.45 | 15-APR-15:05 |
May | 3955.50 | 01-MAY-07:10 | 4995.91 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.41 | 19-MAY-15:10 | 10512.36 | 05-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 5495.50 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5374.70 | 17-JUN-16:00 | 6389.57 | 09-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 5289.79 | 19-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4840.36 | 04-JUL-15:00 | 4055.00 | 15-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 5495.50 | 07-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3094.16 | 02-AUG-17:00 | 4476.22 | 25-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 5995.09 | 20-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1481.68 | 03-SEP-14:47 | 5238.72 | 07-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 5995.09 | 04-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.05 | 01-OCT-16:00 | 13771.91 | 24-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 5995.09 | 02-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10756.25 | 26-NOV-05:47 |
December | 3955.50 | 01-DEC-08:09 | 5995.09 | 01-DEC-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15132.17 | 14-DEC-03:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4995.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.00 | ||||
Maximum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5374.70 | 15132.17 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 8418.38 | 02-JAN-15:20 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8003.25 | 24-JAN-15:00 | 47482.79 | 17-JAN-08:07 |
February | 9097.65 | 01-FEB-08:09 | 7716.84 | 04-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12207.32 | 14-FEB-17:00 | 37656.78 | 05-FEB-01:24 |
March | 9097.65 | 01-MAR-08:09 | 7427.98 | 04-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14617.09 | 08-MAR-17:00 | 38139.79 | 21-MAR-10:55 |
April | 9097.65 | 01-APR-07:10 | 6189.98 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11858.97 | 01-APR-17:00 | 55982.14 | 15-APR-12:10 |
May | 9097.65 | 01-MAY-07:10 | 6189.98 | 22-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7876.83 | 13-MAY-14:00 | 45141.31 | 05-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 6313.78 | 08-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8114.49 | 12-JUN-16:00 | 27695.78 | 09-JUN-07:10 |
July | 9097.65 | 01-JUL-07:10 | 6189.98 | 07-JUL-15:50 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3194.27 | 21-JUL-13:55 | 24495.91 | 15-JUL-19:00 |
August | 9097.65 | 01-AUG-07:10 | 6189.98 | 02-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.64 | 01-AUG-16:00 | 26708.48 | 22-AUG-21:00 |
September | 9097.65 | 01-SEP-07:10 | 7427.98 | 08-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.74 | 03-SEP-13:53 | 28800.48 | 07-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 7427.98 | 04-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7302.71 | 31-OCT-15:00 | 63216.48 | 24-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 8418.38 | 06-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.22 | 09-NOV-14:00 | 37677.31 | 03-NOV-24:00 |
December | 9097.65 | 01-DEC-08:09 | 8418.38 | 02-DEC-15:50 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3444.82 | 24-DEC-15:00 | 48908.07 | 14-DEC-03:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 6189.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.74 | 24495.91 | |||||
Maximum of Months | 9097.65 | 8418.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14617.09 | 63216.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1717.31 | 28-JAN-08:07 | 5042.77 | 3697.23 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.93 |
February | 1808.24 | 11-FEB-08:07 | 5042.77 | 3590.34 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.33 |
March | 1703.74 | 18-MAR-07:07 | 5042.77 | 3652.40 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.37 |
April | 16634.56 | 29-APR-07:03 | 6723.69 | 4655.10 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.64 |
May | 26437.90 | 20-MAY-07:02 | 8404.61 | 5754.15 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.98 |
June | 25713.51 | 19-JUN-07:02 | 8404.61 | 5940.18 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.01 |
July | 23656.19 | 22-JUL-06:01 | 2470.96 | 4519.99 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.94 |
August | 24254.85 | 19-AUG-06:02 | 2117.96 | 3981.40 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.71 |
September | 22569.50 | 16-SEP-07:02 | 8404.61 | 6005.89 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.79 |
October | 22328.42 | 07-OCT-07:02 | 8404.61 | 6170.39 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.20 |
November | 2195.23 | 02-NOV-15:00 | 1680.92 | 1054.39 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.02 |
December | 1801.03 | 30-DEC-08:07 | 5042.77 | 3738.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1703.74 | 1680.92 | 1054.39 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | |
Maximum of Months | 26437.90 | 8404.61 | 6170.39 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5158.68 | 20-JAN-13:20 | 3955.50 | 4995.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.71 |
February | 5155.01 | 16-FEB-09:30 | 3955.50 | 4995.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2708.43 |
March | 4940.09 | 18-MAR-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.92 |
April | 4934.90 | 29-APR-12:50 | 3955.50 | 2997.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.08 |
May | 41346.51 | 19-MAY-17:08 | 0.00 | 3232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1536.42 | 0.00 |
June | 52655.53 | 25-JUN-13:13 | 0.00 | 1880.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.82 | 0.00 |
July | 53891.03 | 30-JUL-13:13 | 0.00 | 1645.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.33 | 0.00 |
August | 52563.55 | 06-AUG-13:53 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.96 | 0.00 |
September | 52937.85 | 03-SEP-13:23 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.11 | 0.00 |
October | 41002.43 | 01-OCT-14:13 | 0.00 | 1234.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 | 0.00 |
November | 5540.16 | 04-NOV-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2867.47 |
December | 5527.27 | 06-DEC-09:50 | 3955.50 | 4995.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4934.90 | 0.00 | 1234.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53891.03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1536.42 | 2867.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2971.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10621.21 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 2971.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16006.09 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2973.97 |
April | 0.00 | 01-APR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4630.20 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9414.34 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9965.11 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8568.22 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7020.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8158.80 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7448.15 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3234.13 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3858.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2973.97 | |
Maximum of Months | 0.00 | 0.00 | 2971.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16006.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.403357E+11 | 29362.50 | 26-JAN-15:00 | 0.414750E+11 | 117669.59 | 16-JAN-17:00 |
February | 0.355959E+11 | 28922.57 | 16-FEB-15:00 | 0.292948E+11 | 108511.17 | 05-FEB-01:39 |
March | 0.385036E+11 | 28063.64 | 24-MAR-08:09 | 0.502295E+10 | 48660.31 | 04-MAR-06:10 |
April | 0.345584E+11 | 26489.98 | 01-APR-07:10 | 0.307991E+09 | 11271.45 | 06-APR-06:10 |
May | 0.361811E+11 | 29770.04 | 19-MAY-15:39 | 30600170.53 | 4769.29 | 05-MAY-07:10 |
June | 0.418973E+11 | 40289.59 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.450147E+11 | 40177.54 | 20-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.449198E+11 | 36532.15 | 21-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.393708E+11 | 35537.70 | 20-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.388574E+11 | 32184.11 | 06-OCT-14:00 | 0.353126E+09 | 14265.84 | 26-OCT-06:10 |
November | 0.378121E+11 | 34658.80 | 15-NOV-16:00 | 0.449251E+10 | 30145.82 | 27-NOV-07:10 |
December | 0.410414E+11 | 34839.23 | 08-DEC-16:49 | 0.379022E+11 | 124983.07 | 14-DEC-04:10 |
Annual Sum or Average | 0.474088E+12 | 0.118879E+12 | ||||
Minimum of Months | 0.345584E+11 | 26489.98 | 0.00 | 0.00 | ||
Maximum of Months | 0.450147E+11 | 40289.59 | 0.414750E+11 | 124983.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.144533E+11 | 0.945439E+10 | 0.115358E+11 | 0.00 | 0.265943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223283E+10 | 0.00 |
February | 0.127266E+11 | 0.797826E+10 | 0.105871E+11 | 0.00 | 0.226857E+10 | 0.00 | 0.00 | 68964.45 | 0.00 | 0.00 | 0.00 | 0.203529E+10 | 0.00 |
March | 0.136492E+11 | 0.802239E+10 | 0.123431E+11 | 0.00 | 0.220959E+10 | 0.00 | 0.00 | 1669464.53 | 0.00 | 0.00 | 0.00 | 0.227759E+10 | 0.00 |
April | 0.118326E+11 | 0.693333E+10 | 0.114862E+11 | 0.00 | 0.194648E+10 | 0.00 | 0.00 | 0.241441E+09 | 0.00 | 0.00 | 0.00 | 0.211835E+10 | 0.00 |
May | 0.121212E+11 | 0.646196E+10 | 0.119357E+11 | 0.00 | 0.204554E+10 | 0.00 | 0.00 | 0.148372E+10 | 0.00 | 0.00 | 0.00 | 0.213296E+10 | 0.00 |
June | 0.123171E+11 | 0.591167E+10 | 0.118862E+11 | 0.00 | 0.369675E+10 | 0.00 | 0.00 | 0.605687E+10 | 0.00 | 0.00 | 0.00 | 0.202874E+10 | 0.00 |
July | 0.119231E+11 | 0.626475E+10 | 0.115358E+11 | 0.00 | 0.465196E+10 | 0.00 | 0.00 | 0.862610E+10 | 0.00 | 0.00 | 0.00 | 0.201306E+10 | 0.00 |
August | 0.123895E+11 | 0.684506E+10 | 0.123357E+11 | 0.00 | 0.398483E+10 | 0.00 | 0.00 | 0.731094E+10 | 0.00 | 0.00 | 0.00 | 0.205377E+10 | 0.00 |
September | 0.125504E+11 | 0.741345E+10 | 0.114788E+11 | 0.00 | 0.230498E+10 | 0.00 | 0.00 | 0.363877E+10 | 0.00 | 0.00 | 0.00 | 0.198444E+10 | 0.00 |
October | 0.138965E+11 | 0.850251E+10 | 0.115432E+11 | 0.00 | 0.196161E+10 | 0.00 | 0.00 | 0.874088E+09 | 0.00 | 0.00 | 0.00 | 0.207953E+10 | 0.00 |
November | 0.137344E+11 | 0.895400E+10 | 0.110862E+11 | 0.00 | 0.196802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206949E+10 | 0.00 |
December | 0.150075E+11 | 0.965479E+10 | 0.115358E+11 | 0.00 | 0.264588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219740E+10 | 0.00 |
Annual Sum or Average | 0.156601E+12 | 0.923965E+11 | 0.139290E+12 | 0.00 | 0.323436E+11 | 0.00 | 0.00 | 0.282337E+11 | 0.00 | 0.00 | 0.00 | 0.252234E+11 | 0.00 |
Minimum of Months | 0.118326E+11 | 0.591167E+10 | 0.105871E+11 | 0.00 | 0.194648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198444E+10 | 0.00 |
Maximum of Months | 0.150075E+11 | 0.965479E+10 | 0.123431E+11 | 0.00 | 0.465196E+10 | 0.00 | 0.00 | 0.862610E+10 | 0.00 | 0.00 | 0.00 | 0.227759E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.414750E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.292948E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.502295E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.307991E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 30600170.53 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.353126E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.449251E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.379022E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118879E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.414750E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 15482.52 | 02-JAN-15:00 | 6958.21 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3240.61 | 17-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 14967.48 | 16-FEB-15:00 | 6958.21 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3118.33 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 14227.09 | 24-MAR-08:09 | 6958.21 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2707.60 | 04-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 12666.36 | 01-APR-07:10 | 6958.21 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2227.55 | 06-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 12275.37 | 22-MAY-07:10 | 6958.21 | 01-MAY-05:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2158.50 | 22-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 13041.68 | 08-JUN-08:30 | 6958.21 | 01-JUN-19:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 5387.06 | 28-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 12671.24 | 21-JUL-07:10 | 6958.21 | 01-JUL-19:19 | 10112.62 | 01-JUL-07:10 | 0.00 | 5143.66 | 22-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 12681.15 | 17-AUG-07:10 | 6958.21 | 01-AUG-05:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 4585.16 | 01-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 14227.75 | 26-SEP-08:09 | 6958.21 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4313.70 | 02-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 14242.54 | 27-OCT-08:09 | 6958.21 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3112.16 | 06-OCT-14:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 15481.88 | 28-NOV-15:00 | 6958.21 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2586.51 | 27-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 15674.36 | 21-DEC-15:00 | 6958.21 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3030.30 | 22-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 12275.37 | 6958.21 | 10112.62 | 0.00 | 2158.50 | 0.00 | 0.00 | |||||
Maximum of Months | 15674.36 | 6958.21 | 10112.62 | 0.00 | 5387.06 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2355.88 | 28-JAN-12:00 | 0.00 |
February | 60.20 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2363.57 | 06-FEB-12:00 | 0.00 |
March | 249.29 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2319.74 | 02-MAR-12:00 | 0.00 |
April | 2289.93 | 28-APR-14:39 | 0.00 | 0.00 | 0.00 | 2116.55 | 04-APR-11:30 | 0.00 |
May | 6985.79 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 | 1809.04 | 01-MAY-11:39 | 0.00 |
June | 14401.23 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1782.16 | 01-JUN-11:09 | 0.00 |
July | 14028.86 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1762.71 | 01-JUL-11:30 | 0.00 |
August | 10827.54 | 01-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1756.56 | 31-AUG-11:50 | 0.00 |
September | 8538.01 | 02-SEP-15:20 | 0.00 | 0.00 | 0.00 | 1771.07 | 30-SEP-11:09 | 0.00 |
October | 6911.41 | 01-OCT-12:00 | 0.00 | 0.00 | 0.00 | 1795.96 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1921.56 | 22-NOV-12:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2228.11 | 27-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1756.56 | 0.00 | ||
Maximum of Months | 14401.23 | 0.00 | 0.00 | 0.00 | 2363.57 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 29362.50 | 26-JAN-15:00 | 15475.29 | 10112.62 | 0.00 | 0.00 | 1959.52 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28922.57 | 16-FEB-15:00 | 14967.48 | 10112.62 | 0.00 | 0.00 | 2035.22 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28063.64 | 24-MAR-08:09 | 14227.09 | 10112.62 | 0.00 | 0.00 | 2043.24 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26489.98 | 01-APR-07:10 | 12666.36 | 10112.62 | 0.00 | 0.00 | 2066.86 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29770.04 | 19-MAY-15:39 | 9335.50 | 10112.62 | 0.00 | 0.00 | 1959.52 | 0.00 | 0.00 | 6968.56 | 0.00 |
June | 40289.59 | 28-JUN-14:00 | 9955.13 | 10112.62 | 0.00 | 0.00 | 5063.29 | 0.00 | 0.00 | 13426.57 | 0.00 |
July | 40177.54 | 20-JUL-15:00 | 10395.32 | 10112.62 | 0.00 | 0.00 | 5001.39 | 0.00 | 0.00 | 13075.52 | 0.00 |
August | 36532.15 | 21-AUG-14:00 | 9942.62 | 10112.62 | 0.00 | 0.00 | 4458.47 | 0.00 | 0.00 | 10295.15 | 0.00 |
September | 35537.70 | 20-SEP-14:00 | 12344.87 | 10112.62 | 0.00 | 0.00 | 4264.81 | 0.00 | 0.00 | 7082.60 | 0.00 |
October | 32184.11 | 06-OCT-14:00 | 12355.15 | 10112.62 | 0.00 | 0.00 | 1959.52 | 0.00 | 0.00 | 6015.09 | 0.00 |
November | 34658.80 | 15-NOV-16:00 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 1978.08 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34839.23 | 08-DEC-16:49 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 2154.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26489.98 | 9335.50 | 10112.62 | 0.00 | 0.00 | 1959.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40289.59 | 15475.29 | 10112.62 | 6958.21 | 0.00 | 5063.29 | 0.00 | 0.00 | 13426.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 117669.59 | 16-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 108511.17 | 05-FEB-01:39 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 48660.31 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 11271.45 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4769.29 | 05-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 14265.84 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 30145.82 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 124983.07 | 14-DEC-04:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 124983.07 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 16.83 | 3.50 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
February | 3.67 | 16.65 | 3.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
March | 1.00 | 17.07 | 1.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.97 | 0.00 | 29.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.99 | 0.00 | 29.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 30.01 | 0.00 | 30.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 17.15 | 1.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
December | 4.17 | 16.64 | 3.50 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
Annual Sum or Average | 13.83 | 16.77 | 12.33 | 16.87 | 0.50 | 17.12 | 0.00 | 17.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 17.15 | 3.50 | 17.15 | 0.17 | 30.01 | 0.00 | 30.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.17 | 14.76 | 5.50 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
February | 36.50 | 14.74 | 3.67 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
March | 6.50 | 14.86 | 0.83 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.29 | 0.00 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.55 | 0.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.61 | 0.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.55 | 0.00 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.46 | 0.00 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.35 | 0.00 | 27.35 |
November | 9.83 | 14.89 | 0.67 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
December | 57.83 | 14.81 | 5.67 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
Annual Sum or Average | 168.83 | 14.78 | 16.33 | 14.78 | 62.67 | 18.01 | 0.00 | 18.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.17 | 14.89 | 5.67 | 14.89 | 25.00 | 27.61 | 0.00 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.79 | 295.67 | 20.78 | 295.67 | 20.78 |
February | 276.00 | 20.94 | 246.83 | 20.84 | 246.83 | 20.80 |
March | 324.00 | 21.36 | 221.33 | 21.06 | 221.33 | 20.93 |
April | 284.17 | 22.83 | 59.33 | 22.43 | 59.33 | 22.15 |
May | 128.33 | 23.32 | 60.33 | 23.44 | 6.33 | 23.35 |
June | 9.83 | 23.84 | 267.00 | 24.22 | 1.00 | 24.23 |
July | 22.67 | 26.24 | 300.00 | 24.46 | 22.67 | 24.58 |
August | 19.50 | 26.15 | 324.00 | 24.40 | 19.50 | 24.49 |
September | 3.67 | 24.87 | 278.50 | 24.18 | 3.00 | 24.19 |
October | 182.33 | 22.74 | 118.00 | 22.87 | 35.17 | 22.63 |
November | 288.00 | 21.32 | 194.00 | 21.07 | 194.00 | 20.96 |
December | 300.00 | 20.76 | 294.67 | 20.74 | 294.67 | 20.74 |
Annual Sum or Average | 2138.50 | 21.68 | 2659.67 | 22.10 | 1399.50 | 21.83 |
Minimum of Months | 3.67 | 20.76 | 59.33 | 20.74 | 1.00 | 20.74 |
Maximum of Months | 324.00 | 26.24 | 324.00 | 24.46 | 295.67 | 24.58 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 16.56 | 300.00 | 16.56 | 300.00 | 16.56 |
February | 276.00 | 17.01 | 271.67 | 16.98 | 271.67 | 16.96 |
March | 324.00 | 18.45 | 296.67 | 18.31 | 296.67 | 18.26 |
April | 229.83 | 21.46 | 134.17 | 21.51 | 91.50 | 21.08 |
May | 98.83 | 22.83 | 205.83 | 24.97 | 16.67 | 24.82 |
June | 158.17 | 26.53 | 296.67 | 26.52 | 150.00 | 26.57 |
July | 264.17 | 26.70 | 300.00 | 26.69 | 264.17 | 26.69 |
August | 270.17 | 26.69 | 324.00 | 26.66 | 270.17 | 26.67 |
September | 161.50 | 26.68 | 288.50 | 26.53 | 161.17 | 26.57 |
October | 184.50 | 21.98 | 183.67 | 22.91 | 89.17 | 22.61 |
November | 288.00 | 18.24 | 271.67 | 18.13 | 271.67 | 18.10 |
December | 300.00 | 16.33 | 300.00 | 16.33 | 300.00 | 16.33 |
Annual Sum or Average | 2855.17 | 20.95 | 3172.83 | 21.45 | 2482.83 | 21.23 |
Minimum of Months | 98.83 | 16.33 | 134.17 | 16.33 | 16.67 | 16.33 |
Maximum of Months | 324.00 | 26.70 | 324.00 | 26.69 | 300.00 | 26.69 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.69 | 300.00 | 11.69 | 300.00 | 11.69 |
February | 276.00 | 12.14 | 276.00 | 12.14 | 276.00 | 12.14 |
March | 324.00 | 14.63 | 324.00 | 14.63 | 324.00 | 14.63 |
April | 300.00 | 19.54 | 223.83 | 19.10 | 223.83 | 18.93 |
May | 169.33 | 21.90 | 176.50 | 23.09 | 60.33 | 22.67 |
June | 213.50 | 30.22 | 290.83 | 29.62 | 202.50 | 29.90 |
July | 300.00 | 30.64 | 300.00 | 30.64 | 300.00 | 30.64 |
August | 322.33 | 29.80 | 324.00 | 29.79 | 322.33 | 29.79 |
September | 232.50 | 28.70 | 300.00 | 28.39 | 232.50 | 28.48 |
October | 255.00 | 22.88 | 177.17 | 23.18 | 137.67 | 23.10 |
November | 288.00 | 15.78 | 288.00 | 15.78 | 288.00 | 15.78 |
December | 300.00 | 11.62 | 300.00 | 11.62 | 300.00 | 11.62 |
Annual Sum or Average | 3280.67 | 20.41 | 3280.33 | 20.57 | 2967.17 | 20.44 |
Minimum of Months | 169.33 | 11.62 | 176.50 | 11.62 | 60.33 | 11.62 |
Maximum of Months | 324.00 | 30.64 | 324.00 | 30.64 | 324.00 | 30.64 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 269223.38 | 68964.45 | 0.83 | 269223.38 | 0.00 | 0.00 | 0.03 | 14-FEB-16:00 | 0.00 | 01-FEB-00:03 | 235.26 | 14-FEB-16:00 | 235.26 | 14-FEB-16:00 | 0.00 | 14-FEB-16:10 | 60.20 | 14-FEB-16:00 | 0.00 | 01-FEB-00:03 |
March | 6575438.64 | 1669464.53 | 4.83 | 6575438.64 | 0.00 | 0.00 | 0.11 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 986.88 | 08-MAR-16:00 | 986.88 | 08-MAR-16:00 | 0.00 | 08-MAR-15:50 | 249.29 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.939111E+09 | 0.227910E+09 | 90.21 | 0.939111E+09 | 8.71 | 0.00 | 1.00 | 29-APR-07:03 | 0.00 | 01-APR-00:10 | 10251.69 | 29-APR-07:03 | 10251.69 | 29-APR-07:03 | 0.01 | 15-APR-07:20 | 2238.86 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.294487E+10 | 0.709802E+09 | 176.19 | 0.290881E+10 | 36062531.03 | 0.00 | 1.00 | 13-MAY-07:02 | 0.00 | 01-MAY-00:10 | 20378.67 | 27-MAY-07:02 | 20378.67 | 13-MAY-07:02 | 3963.70 | 27-MAY-07:02 | 4444.63 | 13-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.710625E+10 | 0.181484E+10 | 258.97 | 0.690991E+10 | 0.196347E+09 | 0.00 | 1.00 | 03-JUN-07:02 | 0.00 | 01-JUN-00:10 | 22515.76 | 29-JUN-06:01 | 21252.89 | 28-JUN-07:02 | 5347.13 | 08-JUN-07:03 | 5064.13 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.950856E+10 | 0.236592E+10 | 273.80 | 0.840358E+10 | 0.110497E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 23630.61 | 29-JUL-07:02 | 21242.39 | 22-JUL-07:02 | 10797.78 | 01-JUL-07:02 | 5110.08 | 29-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.922130E+10 | 0.222910E+10 | 282.21 | 0.803988E+10 | 0.118142E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23979.46 | 14-AUG-07:02 | 22085.46 | 13-AUG-15:33 | 10346.98 | 26-AUG-07:02 | 5398.97 | 13-AUG-14:43 | 0.00 | 01-AUG-00:10 |
September | 0.600535E+10 | 0.142830E+10 | 241.25 | 0.544268E+10 | 0.562671E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 22450.86 | 07-SEP-07:02 | 21312.26 | 04-SEP-16:55 | 9694.85 | 05-SEP-07:02 | 5093.62 | 04-SEP-16:55 | 0.00 | 01-SEP-00:10 |
October | 0.198839E+10 | 0.471339E+09 | 115.96 | 0.186156E+10 | 0.126831E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 20973.34 | 02-OCT-07:02 | 17185.45 | 07-OCT-07:02 | 5060.99 | 02-OCT-07:02 | 4579.39 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.377207E+11 | 0.924894E+10 | 1444.25 | 0.345124E+11 | 0.320830E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.950856E+10 | 0.236592E+10 | 282.21 | 0.840358E+10 | 0.118142E+10 | 0.00 | 1.00 | 0.00 | 23979.46 | 22085.46 | 10797.78 | 5398.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 51429822.40 | 13531128.09 | 10.17 | 51429822.40 | -0.0 | 0.00 | 0.14 | 28-APR-14:30 | 0.00 | 01-APR-00:10 | 3306.84 | 28-APR-14:30 | 3306.84 | 28-APR-14:30 | 0.00 | 28-APR-13:20 | 861.03 | 28-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.301867E+10 | 0.773913E+09 | 104.01 | 0.301495E+10 | 3712406.36 | 0.00 | 1.00 | 14-MAY-11:15 | 0.00 | 01-MAY-00:10 | 59592.87 | 28-MAY-12:15 | 58889.35 | 28-MAY-13:11 | 6892.75 | 28-MAY-11:15 | 13649.26 | 21-MAY-16:45 | 0.00 | 01-MAY-00:10 |
June | 0.157241E+11 | 0.424203E+10 | 266.85 | 0.156001E+11 | 0.124002E+09 | 0.00 | 1.00 | 03-JUN-17:30 | 0.00 | 01-JUN-00:10 | 62382.99 | 29-JUN-05:55 | 59601.14 | 29-JUN-00:31 | 9326.98 | 29-JUN-05:55 | 15626.44 | 25-JUN-15:53 | 0.00 | 01-JUN-00:10 |
July | 0.239257E+11 | 0.626018E+10 | 357.75 | 0.222064E+11 | 0.171935E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 67988.61 | 01-JUL-17:12 | 59595.13 | 23-JUL-20:35 | 28776.16 | 01-JUL-17:12 | 15885.61 | 23-JUL-13:53 | 0.00 | 01-JUL-00:10 |
August | 0.198305E+11 | 0.508184E+10 | 321.58 | 0.183868E+11 | 0.144368E+10 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:10 | 66705.15 | 13-AUG-08:45 | 59525.55 | 06-AUG-09:55 | 26232.56 | 13-AUG-08:45 | 15505.20 | 20-AUG-15:32 | 0.00 | 01-AUG-00:10 |
September | 0.870325E+10 | 0.221047E+10 | 191.68 | 0.834262E+10 | 0.360628E+09 | 0.00 | 1.00 | 01-SEP-17:10 | 0.00 | 01-SEP-00:10 | 63109.07 | 04-SEP-10:40 | 59430.58 | 03-SEP-09:25 | 15893.90 | 10-SEP-10:45 | 15012.05 | 03-SEP-14:02 | 0.00 | 01-SEP-00:10 |
October | 0.158416E+10 | 0.402750E+09 | 51.90 | 0.155943E+10 | 24733444.02 | 0.00 | 1.00 | 01-OCT-10:05 | 0.00 | 01-OCT-00:10 | 58816.51 | 01-OCT-11:35 | 58816.51 | 01-OCT-11:35 | 1130.81 | 01-OCT-10:05 | 13822.82 | 01-OCT-12:55 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.728379E+11 | 0.189847E+11 | 1303.93 | 0.691618E+11 | 0.367610E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.239257E+11 | 0.626018E+10 | 357.75 | 0.222064E+11 | 0.171935E+10 | 0.00 | 1.00 | 0.00 | 67988.61 | 59601.14 | 28776.16 | 15885.61 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.58 | 72.13 | 54.45 | 131.56 | 116.67 | 0.00 | 0.00 | 0.00 |
February | 162.51 | 93.69 | 68.82 | 178.73 | 103.51 | 0.00 | 0.00 | 0.00 |
March | 182.25 | 97.03 | 85.22 | 211.00 | 79.92 | 0.00 | 0.00 | 0.00 |
April | 232.19 | 123.40 | 108.79 | 277.26 | 62.39 | 0.00 | 0.00 | 0.00 |
May | 221.29 | 114.34 | 106.95 | 271.04 | 55.64 | 0.00 | 0.00 | 0.00 |
June | 235.90 | 131.46 | 104.44 | 317.38 | 43.67 | 0.00 | 0.00 | 0.00 |
July | 213.15 | 104.32 | 108.83 | 297.13 | 32.68 | 0.00 | 0.00 | 0.00 |
August | 217.56 | 100.45 | 117.11 | 294.69 | 36.81 | 0.00 | 0.00 | 0.00 |
September | 197.40 | 104.20 | 93.20 | 254.19 | 56.60 | 0.00 | 0.00 | 0.00 |
October | 179.82 | 111.70 | 68.12 | 211.99 | 83.34 | 0.00 | 0.00 | 0.00 |
November | 141.06 | 82.89 | 58.18 | 152.10 | 92.42 | 0.00 | 0.00 | 0.00 |
December | 122.02 | 76.45 | 45.57 | 122.66 | 120.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.00 | 100.96 | 85.04 | 226.78 | 73.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 122.02 | 72.13 | 45.57 | 122.66 | 32.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.90 | 131.46 | 117.11 | 317.38 | 120.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.58 | 72.13 | 54.45 | 131.56 | 116.67 | 0.00 | 0.00 | 0.00 |
February | 162.51 | 93.69 | 68.82 | 178.73 | 103.51 | 0.00 | 0.00 | 0.00 |
March | 182.25 | 97.03 | 85.22 | 211.00 | 79.92 | 0.00 | 0.00 | 0.00 |
April | 232.19 | 123.40 | 108.79 | 277.26 | 62.39 | 0.00 | 0.00 | 0.00 |
May | 221.29 | 114.34 | 106.95 | 271.04 | 55.64 | 0.00 | 0.00 | 0.00 |
June | 235.90 | 131.46 | 104.44 | 317.38 | 43.67 | 0.00 | 0.00 | 0.00 |
July | 213.15 | 104.32 | 108.83 | 297.13 | 32.68 | 0.00 | 0.00 | 0.00 |
August | 217.56 | 100.45 | 117.11 | 294.69 | 36.81 | 0.00 | 0.00 | 0.00 |
September | 197.40 | 104.20 | 93.20 | 254.19 | 56.60 | 0.00 | 0.00 | 0.00 |
October | 179.82 | 111.70 | 68.12 | 211.99 | 83.34 | 0.00 | 0.00 | 0.00 |
November | 141.06 | 82.89 | 58.18 | 152.10 | 92.42 | 0.00 | 0.00 | 0.00 |
December | 122.02 | 76.45 | 45.57 | 122.66 | 120.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.00 | 100.96 | 85.04 | 226.78 | 73.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 122.02 | 72.13 | 45.57 | 122.66 | 32.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.90 | 131.46 | 117.11 | 317.38 | 120.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.88 | 0.00 | 25.88 | 10.48 | 70.35 | 0.00 | 0.00 | 0.00 |
February | 32.34 | 0.00 | 32.34 | 18.13 | 62.08 | 0.00 | 0.00 | 0.00 |
March | 40.81 | 0.00 | 40.81 | 33.19 | 47.39 | 0.00 | 0.00 | 0.00 |
April | 51.87 | 0.54 | 51.33 | 46.45 | 35.84 | 0.00 | 0.00 | 0.00 |
May | 56.40 | 3.73 | 52.67 | 57.80 | 31.08 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 10.51 | 53.46 | 84.56 | 23.54 | 0.00 | 0.00 | 0.00 |
July | 58.56 | 4.76 | 53.80 | 82.23 | 18.14 | 0.00 | 0.00 | 0.00 |
August | 54.65 | 1.43 | 53.22 | 70.21 | 20.47 | 0.00 | 0.00 | 0.00 |
September | 43.57 | 0.03 | 43.54 | 47.81 | 33.10 | 0.00 | 0.00 | 0.00 |
October | 32.48 | 0.00 | 32.48 | 23.36 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 27.59 | 0.00 | 27.59 | 13.13 | 56.01 | 0.00 | 0.00 | 0.00 |
December | 22.03 | 0.00 | 22.03 | 4.64 | 73.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.55 | 1.75 | 40.80 | 41.11 | 43.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.03 | 0.00 | 22.03 | 4.64 | 18.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.96 | 10.51 | 53.80 | 84.56 | 73.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.88 | 0.00 | 25.88 | 10.48 | 70.35 | 0.00 | 0.00 | 0.00 |
February | 32.34 | 0.00 | 32.34 | 18.13 | 62.08 | 0.00 | 0.00 | 0.00 |
March | 40.81 | 0.00 | 40.81 | 33.19 | 47.39 | 0.00 | 0.00 | 0.00 |
April | 51.87 | 0.54 | 51.33 | 46.45 | 35.84 | 0.00 | 0.00 | 0.00 |
May | 56.40 | 3.73 | 52.67 | 57.80 | 31.08 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 10.50 | 53.46 | 84.56 | 23.54 | 0.00 | 0.00 | 0.00 |
July | 58.56 | 4.76 | 53.80 | 82.23 | 18.14 | 0.00 | 0.00 | 0.00 |
August | 54.65 | 1.43 | 53.22 | 70.21 | 20.47 | 0.00 | 0.00 | 0.00 |
September | 43.57 | 0.03 | 43.54 | 47.81 | 33.10 | 0.00 | 0.00 | 0.00 |
October | 32.48 | 0.00 | 32.48 | 23.36 | 49.58 | 0.00 | 0.00 | 0.00 |
November | 27.58 | 0.00 | 27.58 | 13.12 | 56.01 | 0.00 | 0.00 | 0.00 |
December | 22.03 | 0.00 | 22.03 | 4.64 | 73.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.55 | 1.75 | 40.80 | 41.11 | 43.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.03 | 0.00 | 22.03 | 4.64 | 18.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.96 | 10.50 | 53.80 | 84.56 | 73.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 79.57 | 60.88 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 113.69 | 54.26 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 154.90 | 43.46 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 211.74 | 38.89 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 232.17 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 256.24 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 255.19 | 23.03 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 235.85 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 186.32 | 35.63 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 132.73 | 47.82 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 88.96 | 49.88 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 68.47 | 62.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 168.24 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 68.47 | 23.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 256.24 | 62.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.24 | 51.48 | 23.75 | 86.74 | 47.30 | 0.00 | 0.00 | 0.00 |
February | 102.01 | 72.59 | 29.42 | 121.69 | 41.67 | 0.00 | 0.00 | 0.00 |
March | 132.36 | 91.85 | 40.51 | 162.50 | 35.19 | 0.00 | 0.00 | 0.00 |
April | 177.91 | 128.13 | 49.78 | 218.86 | 33.19 | 0.00 | 0.00 | 0.00 |
May | 193.12 | 145.70 | 47.42 | 236.53 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 204.58 | 161.31 | 43.27 | 253.79 | 32.34 | 0.00 | 0.00 | 0.00 |
July | 199.08 | 149.79 | 49.29 | 249.32 | 29.32 | 0.00 | 0.00 | 0.00 |
August | 186.69 | 134.06 | 52.62 | 231.37 | 29.86 | 0.00 | 0.00 | 0.00 |
September | 152.13 | 111.23 | 40.90 | 184.81 | 38.84 | 0.00 | 0.00 | 0.00 |
October | 115.46 | 89.76 | 25.70 | 133.58 | 48.28 | 0.00 | 0.00 | 0.00 |
November | 81.75 | 57.68 | 24.08 | 92.84 | 44.37 | 0.00 | 0.00 | 0.00 |
December | 67.05 | 50.29 | 16.75 | 75.04 | 48.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.78 | 103.79 | 36.99 | 170.81 | 38.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 67.05 | 50.29 | 16.75 | 75.04 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.58 | 161.31 | 52.62 | 253.79 | 48.79 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.339019E+09 | 0.193189E+09 | 0.145831E+09 | 0.352366E+09 | 0.312484E+09 |
February | 0.393149E+09 | 0.226664E+09 | 0.166485E+09 | 0.432373E+09 | 0.250405E+09 |
March | 0.488136E+09 | 0.259891E+09 | 0.228245E+09 | 0.565130E+09 | 0.214064E+09 |
April | 0.601833E+09 | 0.319860E+09 | 0.281973E+09 | 0.718669E+09 | 0.161722E+09 |
May | 0.592711E+09 | 0.306244E+09 | 0.286466E+09 | 0.725947E+09 | 0.149037E+09 |
June | 0.611446E+09 | 0.340732E+09 | 0.270714E+09 | 0.822637E+09 | 0.113200E+09 |
July | 0.570909E+09 | 0.279413E+09 | 0.291495E+09 | 0.795842E+09 | 87530103.83 |
August | 0.582707E+09 | 0.269043E+09 | 0.313664E+09 | 0.789291E+09 | 98595584.61 |
September | 0.511657E+09 | 0.270080E+09 | 0.241577E+09 | 0.658856E+09 | 0.146715E+09 |
October | 0.481642E+09 | 0.299184E+09 | 0.182457E+09 | 0.567781E+09 | 0.223216E+09 |
November | 0.365635E+09 | 0.214844E+09 | 0.150791E+09 | 0.394255E+09 | 0.239565E+09 |
December | 0.326828E+09 | 0.204775E+09 | 0.122053E+09 | 0.328530E+09 | 0.321659E+09 |
Annual Sum or Average | 0.586567E+10 | 0.318392E+10 | 0.268175E+10 | 0.715168E+10 | 0.231819E+10 |
Minimum of Months | 0.326828E+09 | 0.193189E+09 | 0.122053E+09 | 0.328530E+09 | 87530103.83 |
Maximum of Months | 0.611446E+09 | 0.340732E+09 | 0.313664E+09 | 0.822637E+09 | 0.321659E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.339019E+09 | 0.193189E+09 | 0.145831E+09 | 0.352366E+09 | 0.312484E+09 |
February | 0.393149E+09 | 0.226664E+09 | 0.166485E+09 | 0.432373E+09 | 0.250405E+09 |
March | 0.488136E+09 | 0.259891E+09 | 0.228245E+09 | 0.565130E+09 | 0.214064E+09 |
April | 0.601833E+09 | 0.319860E+09 | 0.281973E+09 | 0.718669E+09 | 0.161722E+09 |
May | 0.592711E+09 | 0.306244E+09 | 0.286466E+09 | 0.725947E+09 | 0.149037E+09 |
June | 0.611446E+09 | 0.340732E+09 | 0.270714E+09 | 0.822637E+09 | 0.113200E+09 |
July | 0.570909E+09 | 0.279413E+09 | 0.291495E+09 | 0.795842E+09 | 87530103.83 |
August | 0.582707E+09 | 0.269043E+09 | 0.313664E+09 | 0.789291E+09 | 98595584.61 |
September | 0.511657E+09 | 0.270080E+09 | 0.241577E+09 | 0.658856E+09 | 0.146715E+09 |
October | 0.481642E+09 | 0.299184E+09 | 0.182457E+09 | 0.567781E+09 | 0.223216E+09 |
November | 0.365635E+09 | 0.214844E+09 | 0.150791E+09 | 0.394255E+09 | 0.239565E+09 |
December | 0.326828E+09 | 0.204775E+09 | 0.122053E+09 | 0.328530E+09 | 0.321659E+09 |
Annual Sum or Average | 0.586567E+10 | 0.318392E+10 | 0.268175E+10 | 0.715168E+10 | 0.231819E+10 |
Minimum of Months | 0.326828E+09 | 0.193189E+09 | 0.122053E+09 | 0.328530E+09 | 87530103.83 |
Maximum of Months | 0.611446E+09 | 0.340732E+09 | 0.313664E+09 | 0.822637E+09 | 0.321659E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69315124.01 | 0.00 | 69315124.01 | 28060432.94 | 0.188435E+09 |
February | 78248492.49 | 0.00 | 78248492.49 | 43867350.50 | 0.150177E+09 |
March | 0.109306E+09 | 10660.23 | 0.109295E+09 | 88890217.52 | 0.126925E+09 |
April | 0.134447E+09 | 1403813.24 | 0.133044E+09 | 0.120403E+09 | 92891370.07 |
May | 0.151062E+09 | 9987259.40 | 0.141075E+09 | 0.154819E+09 | 83245234.73 |
June | 0.165795E+09 | 27229216.57 | 0.138565E+09 | 0.219175E+09 | 61008785.17 |
July | 0.156842E+09 | 12738363.15 | 0.144103E+09 | 0.220254E+09 | 48584920.45 |
August | 0.146373E+09 | 3818289.96 | 0.142554E+09 | 0.188050E+09 | 54821885.81 |
September | 0.112925E+09 | 67928.89 | 0.112857E+09 | 0.123915E+09 | 85805437.21 |
October | 87002362.43 | 0.00 | 87002362.43 | 62571536.83 | 0.132801E+09 |
November | 71502183.35 | 0.00 | 71502183.35 | 34020310.92 | 0.145184E+09 |
December | 58997644.33 | 0.00 | 58997644.33 | 12432672.96 | 0.197278E+09 |
Annual Sum or Average | 0.134182E+10 | 55255531.44 | 0.128656E+10 | 0.129646E+10 | 0.136716E+10 |
Minimum of Months | 58997644.33 | 0.00 | 58997644.33 | 12432672.96 | 48584920.45 |
Maximum of Months | 0.165795E+09 | 27229216.57 | 0.144103E+09 | 0.220254E+09 | 0.197278E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69313236.53 | 0.00 | 69313236.53 | 28058896.51 | 0.188434E+09 |
February | 78246449.14 | 0.00 | 78246449.14 | 43865534.58 | 0.150176E+09 |
March | 0.109303E+09 | 10659.73 | 0.109293E+09 | 88887225.29 | 0.126925E+09 |
April | 0.134444E+09 | 1403747.44 | 0.133040E+09 | 0.120400E+09 | 92890741.46 |
May | 0.151058E+09 | 9986791.28 | 0.141071E+09 | 0.154814E+09 | 83244458.99 |
June | 0.165790E+09 | 27227940.30 | 0.138562E+09 | 0.219169E+09 | 61008063.84 |
July | 0.156837E+09 | 12737766.08 | 0.144100E+09 | 0.220249E+09 | 48584278.01 |
August | 0.146369E+09 | 3818111.00 | 0.142551E+09 | 0.188046E+09 | 54821285.77 |
September | 0.112922E+09 | 67925.71 | 0.112854E+09 | 0.123911E+09 | 85804770.02 |
October | 87000278.73 | 0.00 | 87000278.73 | 62569697.34 | 0.132801E+09 |
November | 71500277.21 | 0.00 | 71500277.21 | 34018667.97 | 0.145184E+09 |
December | 58996151.47 | 0.00 | 58996151.47 | 12431784.74 | 0.197277E+09 |
Annual Sum or Average | 0.134178E+10 | 55252941.54 | 0.128653E+10 | 0.129642E+10 | 0.136715E+10 |
Minimum of Months | 58996151.47 | 0.00 | 58996151.47 | 12431784.74 | 48584278.01 |
Maximum of Months | 0.165790E+09 | 27227940.30 | 0.144100E+09 | 0.220249E+09 | 0.197277E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.213125E+09 | 0.163068E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.275050E+09 | 0.131256E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.414893E+09 | 0.116400E+09 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.548842E+09 | 0.100795E+09 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.621841E+09 | 95702013.24 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.664181E+09 | 76062719.20 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.683509E+09 | 61684580.62 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.631693E+09 | 65395065.00 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.482945E+09 | 92344096.65 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.355508E+09 | 0.128071E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.230595E+09 | 0.129299E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 0.167754E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.530556E+10 | 0.132783E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.183377E+09 | 61684580.62 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.683509E+09 | 0.167754E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201516E+09 | 0.137892E+09 | 63624122.30 | 0.232325E+09 | 0.126700E+09 |
February | 0.246777E+09 | 0.175611E+09 | 71166156.16 | 0.294389E+09 | 0.100799E+09 |
March | 0.354509E+09 | 0.246002E+09 | 0.108507E+09 | 0.435246E+09 | 94242105.56 |
April | 0.461130E+09 | 0.332113E+09 | 0.129017E+09 | 0.567290E+09 | 86035007.90 |
May | 0.517252E+09 | 0.390242E+09 | 0.127010E+09 | 0.633522E+09 | 88651460.90 |
June | 0.530260E+09 | 0.418104E+09 | 0.112156E+09 | 0.657836E+09 | 83835639.40 |
July | 0.533210E+09 | 0.401186E+09 | 0.132025E+09 | 0.667766E+09 | 78532289.80 |
August | 0.500022E+09 | 0.359078E+09 | 0.140944E+09 | 0.619705E+09 | 79973210.63 |
September | 0.394311E+09 | 0.288304E+09 | 0.106008E+09 | 0.479023E+09 | 0.100674E+09 |
October | 0.309251E+09 | 0.240406E+09 | 68844739.91 | 0.357783E+09 | 0.129311E+09 |
November | 0.211903E+09 | 0.149495E+09 | 62407473.89 | 0.240639E+09 | 0.115003E+09 |
December | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 0.130671E+09 |
Annual Sum or Average | 0.443972E+10 | 0.327314E+10 | 0.116658E+10 | 0.538652E+10 | 0.121443E+10 |
Minimum of Months | 0.179582E+09 | 0.134707E+09 | 44874882.89 | 0.200990E+09 | 78532289.80 |
Maximum of Months | 0.533210E+09 | 0.418104E+09 | 0.140944E+09 | 0.667766E+09 | 0.130671E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 280.50 | 370.47 | 304.91 | 144.26 | 160.65 | 0.00 | 0.00 |
February | 390.85 | 328.30 | 389.71 | 187.39 | 202.33 | 0.00 | 0.00 |
March | 486.85 | 253.11 | 446.12 | 194.07 | 252.05 | 0.00 | 0.00 |
April | 646.07 | 195.10 | 568.12 | 247.89 | 320.23 | 0.00 | 0.00 |
May | 655.75 | 171.52 | 555.38 | 236.13 | 319.25 | 0.00 | 0.00 |
June | 798.88 | 129.44 | 599.72 | 283.92 | 315.80 | 0.00 | 0.00 |
July | 756.88 | 99.79 | 543.42 | 218.15 | 325.27 | 0.00 | 0.00 |
August | 728.42 | 113.18 | 544.41 | 203.75 | 340.66 | 0.00 | 0.00 |
September | 603.62 | 179.05 | 481.93 | 208.45 | 273.48 | 0.00 | 0.00 |
October | 468.78 | 263.93 | 424.61 | 223.41 | 201.21 | 0.00 | 0.00 |
November | 326.95 | 293.37 | 337.30 | 165.77 | 171.52 | 0.00 | 0.00 |
December | 248.19 | 381.09 | 288.10 | 152.91 | 135.19 | 0.00 | 0.00 |
Annual Sum or Average | 533.14 | 231.09 | 457.09 | 205.43 | 251.67 | 0.00 | 0.00 |
Minimum of Months | 248.19 | 99.79 | 288.10 | 144.26 | 135.19 | 0.00 | 0.00 |
Maximum of Months | 798.88 | 381.09 | 599.72 | 283.92 | 340.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1114.01 | 852.36 | 1053.33 | 720.76 | 332.56 | 0.00 | 0.00 |
February | 1591.72 | 759.58 | 1428.11 | 1016.27 | 411.84 | 0.00 | 0.00 |
March | 2168.65 | 608.42 | 1853.02 | 1285.86 | 567.16 | 0.00 | 0.00 |
April | 2964.42 | 544.42 | 2490.67 | 1793.82 | 696.85 | 0.00 | 0.00 |
May | 3250.36 | 500.23 | 2703.68 | 2039.80 | 663.88 | 0.00 | 0.00 |
June | 3587.40 | 410.83 | 2864.06 | 2258.28 | 605.78 | 0.00 | 0.00 |
July | 3572.70 | 322.43 | 2787.09 | 2097.00 | 690.09 | 0.00 | 0.00 |
August | 3301.86 | 341.82 | 2613.62 | 1876.90 | 736.72 | 0.00 | 0.00 |
September | 2608.50 | 498.77 | 2129.77 | 1557.20 | 572.57 | 0.00 | 0.00 |
October | 1858.24 | 669.43 | 1616.45 | 1256.60 | 359.85 | 0.00 | 0.00 |
November | 1245.50 | 698.37 | 1144.54 | 807.46 | 337.08 | 0.00 | 0.00 |
December | 958.51 | 876.85 | 938.67 | 704.11 | 234.56 | 0.00 | 0.00 |
Annual Sum or Average | 2355.33 | 589.47 | 1970.96 | 1453.07 | 517.89 | 0.00 | 0.00 |
Minimum of Months | 958.51 | 322.43 | 938.67 | 704.11 | 234.56 | 0.00 | 0.00 |
Maximum of Months | 3587.40 | 876.85 | 2864.06 | 2258.28 | 736.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10994.87 | 8927.96 | 2407.60 | 1647.46 | 760.14 | 0.00 | 0.00 |
February | 15709.54 | 7317.09 | 3264.25 | 2322.90 | 941.35 | 0.00 | 0.00 |
March | 21932.65 | 4203.49 | 4235.47 | 2939.10 | 1296.38 | 0.00 | 0.00 |
April | 29333.94 | 3219.94 | 5692.97 | 4100.17 | 1592.80 | 0.00 | 0.00 |
May | 31323.61 | 3192.20 | 6179.83 | 4662.39 | 1517.44 | 0.00 | 0.00 |
June | 40015.40 | 3996.92 | 6546.42 | 5161.78 | 1384.64 | 0.00 | 0.00 |
July | 44616.14 | 4204.95 | 6370.49 | 4793.14 | 1577.35 | 0.00 | 0.00 |
August | 38513.40 | 3807.84 | 5973.98 | 4290.06 | 1683.92 | 0.00 | 0.00 |
September | 25190.27 | 4006.96 | 4868.04 | 3559.31 | 1308.74 | 0.00 | 0.00 |
October | 17412.00 | 4989.30 | 3694.75 | 2872.23 | 822.52 | 0.00 | 0.00 |
November | 12460.20 | 5391.03 | 2616.08 | 1845.62 | 770.46 | 0.00 | 0.00 |
December | 9570.29 | 8876.39 | 2145.54 | 1609.40 | 536.14 | 0.00 | 0.00 |
Annual Sum or Average | 24808.53 | 5171.48 | 4505.05 | 3321.30 | 1183.75 | 0.00 | 0.00 |
Minimum of Months | 9570.29 | 3192.20 | 2145.54 | 1609.40 | 536.14 | 0.00 | 0.00 |
Maximum of Months | 44616.14 | 8927.96 | 6546.42 | 5161.78 | 1683.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.751293E+09 | 0.992277E+09 | 0.816667E+09 | 0.386377E+09 | 0.430290E+09 | 0.00 | 0.00 |
February | 0.945547E+09 | 0.794233E+09 | 0.942793E+09 | 0.453327E+09 | 0.489465E+09 | 0.00 | 0.00 |
March | 0.130398E+10 | 0.677918E+09 | 0.119488E+10 | 0.519803E+09 | 0.675078E+09 | 0.00 | 0.00 |
April | 0.167461E+10 | 0.505699E+09 | 0.147256E+10 | 0.642528E+09 | 0.830029E+09 | 0.00 | 0.00 |
May | 0.175636E+10 | 0.459394E+09 | 0.148754E+10 | 0.632463E+09 | 0.855079E+09 | 0.00 | 0.00 |
June | 0.207070E+10 | 0.335497E+09 | 0.155448E+10 | 0.735921E+09 | 0.818556E+09 | 0.00 | 0.00 |
July | 0.202724E+10 | 0.267277E+09 | 0.145550E+10 | 0.584303E+09 | 0.871193E+09 | 0.00 | 0.00 |
August | 0.195100E+10 | 0.303152E+09 | 0.145816E+10 | 0.545723E+09 | 0.912433E+09 | 0.00 | 0.00 |
September | 0.156459E+10 | 0.464092E+09 | 0.124916E+10 | 0.540296E+09 | 0.708866E+09 | 0.00 | 0.00 |
October | 0.125557E+10 | 0.706904E+09 | 0.113729E+10 | 0.598369E+09 | 0.538917E+09 | 0.00 | 0.00 |
November | 0.847463E+09 | 0.760413E+09 | 0.874273E+09 | 0.429688E+09 | 0.444585E+09 | 0.00 | 0.00 |
December | 0.664751E+09 | 0.102070E+10 | 0.771650E+09 | 0.409550E+09 | 0.362100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168131E+11 | 0.728756E+10 | 0.144149E+11 | 0.647835E+10 | 0.793659E+10 | 0.00 | 0.00 |
Minimum of Months | 0.664751E+09 | 0.267277E+09 | 0.771650E+09 | 0.386377E+09 | 0.362100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.207070E+10 | 0.102070E+10 | 0.155448E+10 | 0.735921E+09 | 0.912433E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298375E+10 | 0.228296E+10 | 0.282123E+10 | 0.193049E+10 | 0.890738E+09 | 0.00 | 0.00 |
February | 0.385070E+10 | 0.183758E+10 | 0.345488E+10 | 0.245855E+10 | 0.996326E+09 | 0.00 | 0.00 |
March | 0.580851E+10 | 0.162959E+10 | 0.496313E+10 | 0.344403E+10 | 0.151909E+10 | 0.00 | 0.00 |
April | 0.768378E+10 | 0.141113E+10 | 0.645583E+10 | 0.464959E+10 | 0.180624E+10 | 0.00 | 0.00 |
May | 0.870577E+10 | 0.133983E+10 | 0.724153E+10 | 0.546339E+10 | 0.177814E+10 | 0.00 | 0.00 |
June | 0.929853E+10 | 0.106488E+10 | 0.742364E+10 | 0.585346E+10 | 0.157019E+10 | 0.00 | 0.00 |
July | 0.956913E+10 | 0.863584E+09 | 0.746494E+10 | 0.561660E+10 | 0.184834E+10 | 0.00 | 0.00 |
August | 0.884370E+10 | 0.915531E+09 | 0.700031E+10 | 0.502709E+10 | 0.197322E+10 | 0.00 | 0.00 |
September | 0.676123E+10 | 0.129282E+10 | 0.552036E+10 | 0.403626E+10 | 0.148411E+10 | 0.00 | 0.00 |
October | 0.497711E+10 | 0.179299E+10 | 0.432951E+10 | 0.336568E+10 | 0.963826E+09 | 0.00 | 0.00 |
November | 0.322833E+10 | 0.181018E+10 | 0.296664E+10 | 0.209293E+10 | 0.873705E+09 | 0.00 | 0.00 |
December | 0.256728E+10 | 0.234855E+10 | 0.251415E+10 | 0.188590E+10 | 0.628248E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.742778E+11 | 0.185896E+11 | 0.621561E+11 | 0.458240E+11 | 0.163322E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256728E+10 | 0.863584E+09 | 0.251415E+10 | 0.188590E+10 | 0.628248E+09 | 0.00 | 0.00 |
Maximum of Months | 0.956913E+10 | 0.234855E+10 | 0.746494E+10 | 0.585346E+10 | 0.197322E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294487E+11 | 0.239126E+11 | 0.644853E+10 | 0.441255E+10 | 0.203597E+10 | 0.00 | 0.00 |
February | 0.380045E+11 | 0.177015E+11 | 0.789687E+10 | 0.561955E+10 | 0.227732E+10 | 0.00 | 0.00 |
March | 0.587444E+11 | 0.112586E+11 | 0.113443E+11 | 0.787208E+10 | 0.347221E+10 | 0.00 | 0.00 |
April | 0.760336E+11 | 0.834609E+10 | 0.147562E+11 | 0.106276E+11 | 0.412854E+10 | 0.00 | 0.00 |
May | 0.838972E+11 | 0.854998E+10 | 0.165521E+11 | 0.124877E+11 | 0.406432E+10 | 0.00 | 0.00 |
June | 0.103720E+12 | 0.103600E+11 | 0.169683E+11 | 0.133793E+11 | 0.358900E+10 | 0.00 | 0.00 |
July | 0.119500E+12 | 0.112625E+11 | 0.170627E+11 | 0.128379E+11 | 0.422479E+10 | 0.00 | 0.00 |
August | 0.103154E+12 | 0.101989E+11 | 0.160007E+11 | 0.114905E+11 | 0.451022E+10 | 0.00 | 0.00 |
September | 0.652932E+11 | 0.103860E+11 | 0.126180E+11 | 0.922573E+10 | 0.339224E+10 | 0.00 | 0.00 |
October | 0.466363E+11 | 0.133633E+11 | 0.989602E+10 | 0.769299E+10 | 0.220303E+10 | 0.00 | 0.00 |
November | 0.322968E+11 | 0.139735E+11 | 0.678088E+10 | 0.478384E+10 | 0.199704E+10 | 0.00 | 0.00 |
December | 0.256331E+11 | 0.237745E+11 | 0.574662E+10 | 0.431062E+10 | 0.143600E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.782362E+12 | 0.163088E+12 | 0.142071E+12 | 0.104741E+12 | 0.373307E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256331E+11 | 0.834609E+10 | 0.574662E+10 | 0.431062E+10 | 0.143600E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119500E+12 | 0.239126E+11 | 0.170627E+11 | 0.133793E+11 | 0.451022E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.939446E+09 | -852341093.2 | 0.00 | 0.00 | 744.00 | 0.00 | -87104747.3 | 58.99 | 0.00 | 0.00 |
February | 0.867000E+09 | -789006722.3 | 0.00 | 0.00 | 672.00 | 0.00 | -77993477.1 | 58.99 | 0.00 | 0.00 |
March | 0.983222E+09 | -899296858.3 | 0.00 | 0.00 | 744.00 | 0.00 | -83924752.1 | 58.99 | 0.00 | 0.00 |
April | 0.866773E+09 | -791273247.0 | 0.00 | 0.00 | 720.00 | 0.00 | -75499337.4 | 58.99 | 0.00 | 0.00 |
May | 0.839124E+09 | -765532888.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73590742.2 | 59.00 | 0.00 | 0.00 |
June | 0.776568E+09 | -708002015.5 | 0.00 | 0.00 | 720.00 | 0.00 | -68566059.3 | 58.99 | 0.00 | 0.00 |
July | 0.719042E+09 | -649624688.8 | 0.00 | 0.00 | 744.00 | 0.00 | -69417699.2 | 58.99 | 0.00 | 0.00 |
August | 0.760204E+09 | -690143104.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70060803.7 | 59.00 | 0.00 | 0.00 |
September | 0.732558E+09 | -663845887.6 | 0.00 | 0.00 | 720.00 | 0.00 | -68712049.3 | 58.99 | 0.00 | 0.00 |
October | 0.785955E+09 | -710471253.5 | 0.00 | 0.00 | 744.00 | 0.00 | -75483730.7 | 58.99 | 0.00 | 0.00 |
November | 0.817010E+09 | -735515504.2 | 0.00 | 0.00 | 720.00 | 0.00 | -81494923.2 | 59.00 | 0.00 | 0.00 |
December | 0.904148E+09 | -817175847.9 | 0.00 | 0.00 | 744.00 | 0.00 | -86971740.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999105E+10 | -0.907223E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -918820062.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.719042E+09 | -899296858.3 | 0.00 | 0.00 | 672.00 | 0.00 | -87104747.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.983222E+09 | -649624688.8 | 0.00 | 0.00 | 744.00 | 0.00 | -68566059.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.83 | 0.50 | 04-JAN-11:09 | 175.50 | 0.00 | 0.00 | 50.00 | 145.57 | 0.00 | 0.00 | 23.83 |
February | 282.00 | 0.79 | 0.50 | 01-FEB-11:50 | 212.18 | 0.00 | 0.00 | 59.17 | 179.48 | 0.00 | 0.00 | 43.67 |
March | 351.33 | 0.75 | 0.50 | 01-MAR-10:09 | 269.25 | 0.00 | 0.00 | 106.17 | 216.88 | 0.00 | 0.00 | 79.83 |
April | 381.83 | 0.71 | 0.50 | 01-APR-10:00 | 297.52 | 0.00 | 0.00 | 165.17 | 242.47 | 0.00 | 0.00 | 119.33 |
May | 378.00 | 0.71 | 0.50 | 01-MAY-10:09 | 302.10 | 0.00 | 0.00 | 174.50 | 3771.16 | 0.00 | 0.00 | 114.50 |
June | 412.83 | 0.75 | 0.50 | 01-JUN-08:30 | 1932.67 | 0.00 | 0.00 | 138.33 | 3328.97 | 0.00 | 0.00 | 102.67 |
July | 395.33 | 0.71 | 0.50 | 01-JUL-08:30 | 1529.28 | 0.00 | 0.00 | 172.83 | 1137.99 | 0.00 | 0.00 | 116.33 |
August | 408.83 | 0.71 | 0.50 | 01-AUG-09:30 | 317.75 | 0.00 | 0.00 | 179.50 | 752.33 | 0.00 | 0.00 | 134.17 |
September | 359.33 | 0.74 | 0.50 | 01-SEP-13:00 | 1365.73 | 0.00 | 0.00 | 121.33 | 218.99 | 0.00 | 0.00 | 73.67 |
October | 329.00 | 0.81 | 0.50 | 01-OCT-13:20 | 726.56 | 0.00 | 0.00 | 66.00 | 162.41 | 0.00 | 0.00 | 41.17 |
November | 284.17 | 0.83 | 0.50 | 02-NOV-10:09 | 178.53 | 0.00 | 0.00 | 38.50 | 151.16 | 0.00 | 0.00 | 20.00 |
December | 265.67 | 0.88 | 0.50 | 01-DEC-11:20 | 136.51 | 0.00 | 0.00 | 10.33 | 117.68 | 0.00 | 0.00 | 2.33 |
Annual Sum or Average | 4149.83 | 0.76 | 670.94 | 0.00 | 0.00 | 1281.83 | 970.38 | 0.00 | 0.00 | 871.50 | ||
Minimum of Months | 265.67 | 0.71 | 0.50 | 136.51 | 0.00 | 0.00 | 10.33 | 117.68 | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 412.83 | 0.88 | 0.50 | 1932.67 | 0.00 | 0.00 | 179.50 | 3771.16 | 0.00 | 0.00 | 134.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.71 | 0.50 | 02-JAN-11:00 | 636.21 | 11.81 | 0.00 | 119.00 | 170.32 | 15.52 | 22.67 | 84.17 |
February | 282.00 | 0.67 | 0.50 | 01-FEB-08:50 | 639.82 | 12.71 | 0.00 | 149.33 | 207.42 | 16.44 | 46.17 | 109.67 |
March | 351.33 | 0.64 | 0.50 | 01-MAR-07:00 | 305.80 | 13.60 | 0.67 | 215.83 | 258.33 | 17.43 | 65.33 | 178.33 |
April | 381.83 | 0.61 | 0.50 | 01-APR-08:50 | 349.14 | 14.63 | 1.50 | 274.00 | 1734.95 | 20.32 | 124.83 | 243.33 |
May | 378.00 | 0.60 | 0.50 | 01-MAY-06:49 | 2385.50 | 14.38 | 2.33 | 301.83 | 2799.35 | 18.35 | 107.67 | 263.83 |
June | 412.83 | 0.63 | 0.50 | 01-JUN-06:40 | 303.44 | 13.14 | 5.67 | 263.00 | 262.43 | 17.09 | 65.50 | 225.00 |
July | 395.33 | 0.60 | 0.50 | 01-JUL-07:10 | 1599.85 | 14.13 | 8.83 | 292.33 | 1620.39 | 18.07 | 94.17 | 253.83 |
August | 408.83 | 0.60 | 0.50 | 01-AUG-06:00 | 2560.73 | 14.61 | 5.33 | 303.00 | 2453.00 | 20.07 | 106.67 | 267.50 |
September | 359.33 | 0.63 | 0.50 | 01-SEP-08:20 | 310.07 | 13.52 | 1.83 | 237.50 | 259.68 | 17.39 | 78.67 | 199.17 |
October | 329.00 | 0.69 | 0.50 | 01-OCT-09:00 | 221.05 | 11.84 | 0.00 | 163.67 | 186.49 | 15.75 | 27.17 | 122.17 |
November | 284.17 | 0.69 | 0.50 | 01-NOV-10:50 | 209.91 | 12.43 | 0.00 | 132.83 | 175.79 | 16.23 | 28.00 | 94.50 |
December | 265.67 | 0.73 | 0.50 | 01-DEC-08:50 | 3259.30 | 10.77 | 0.00 | 118.83 | 2038.48 | 14.36 | 16.00 | 76.00 |
Annual Sum or Average | 4149.83 | 0.64 | 1067.28 | 13.27 | 26.17 | 2571.17 | 1064.91 | 17.45 | 782.83 | 2117.50 | ||
Minimum of Months | 265.67 | 0.60 | 0.50 | 209.91 | 10.77 | 0.00 | 118.83 | 170.32 | 14.36 | 16.00 | 76.00 | |
Maximum of Months | 412.83 | 0.73 | 0.50 | 3259.30 | 14.63 | 8.83 | 303.00 | 2799.35 | 20.32 | 124.83 | 267.50 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.89 | 0.80 | 10-JAN-15:20 | 583.74 | 24.10 | 146.50 | 59.17 | 131.36 | 20.81 | 121.00 | 0.33 |
February | 282.00 | 0.88 | 0.80 | 01-FEB-14:09 | 636.55 | 24.62 | 153.67 | 86.67 | 292.27 | 23.40 | 158.50 | 31.00 |
March | 351.33 | 0.88 | 0.80 | 01-MAR-16:10 | 553.34 | 23.70 | 185.83 | 113.17 | 472.82 | 24.25 | 201.33 | 55.83 |
April | 381.83 | 0.86 | 0.80 | 01-APR-14:09 | 473.10 | 22.87 | 224.50 | 133.50 | 738.90 | 23.91 | 283.83 | 92.00 |
May | 378.00 | 0.86 | 0.80 | 01-MAY-14:00 | 329.57 | 21.83 | 180.83 | 113.33 | 357.83 | 23.17 | 279.83 | 88.00 |
June | 412.83 | 0.87 | 0.80 | 01-JUN-13:39 | 289.73 | 20.79 | 147.17 | 118.00 | 423.83 | 22.16 | 203.33 | 83.50 |
July | 395.33 | 0.87 | 0.80 | 01-JUL-13:30 | 324.05 | 21.46 | 186.50 | 145.33 | 367.17 | 22.72 | 241.00 | 87.67 |
August | 408.83 | 0.86 | 0.80 | 01-AUG-14:50 | 351.94 | 22.01 | 218.17 | 156.50 | 357.14 | 23.34 | 269.17 | 115.17 |
September | 359.33 | 0.87 | 0.80 | 01-SEP-13:00 | 412.83 | 22.69 | 178.83 | 119.00 | 440.29 | 24.52 | 212.67 | 80.17 |
October | 329.00 | 0.88 | 0.80 | 01-OCT-13:39 | 774.12 | 24.41 | 161.67 | 90.83 | 274.38 | 23.31 | 163.17 | 40.33 |
November | 284.17 | 0.89 | 0.80 | 01-NOV-14:30 | 529.19 | 24.64 | 150.83 | 67.50 | 146.39 | 21.53 | 132.33 | 3.33 |
December | 265.67 | 0.90 | 0.80 | 11-DEC-15:09 | 472.56 | 24.14 | 125.17 | 49.00 | 119.54 | 20.20 | 80.33 | 0.00 |
Annual Sum or Average | 4149.83 | 0.87 | 464.04 | 22.94 | 2059.67 | 1252.00 | 359.90 | 22.87 | 2346.50 | 677.33 | ||
Minimum of Months | 265.67 | 0.86 | 0.80 | 289.73 | 20.79 | 125.17 | 49.00 | 119.54 | 20.20 | 80.33 | 0.00 | |
Maximum of Months | 412.83 | 0.90 | 0.80 | 774.12 | 24.64 | 224.50 | 156.50 | 738.90 | 24.52 | 283.83 | 115.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412213E+10 | 28185.43 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317151E+10 | 28185.43 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159540E+10 | 28185.43 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207895E+09 | 28185.43 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20233140.91 | 12028.27 | 04-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237737E+09 | 28185.43 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146804E+10 | 28185.43 | 06-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413689E+10 | 28185.43 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413689E+10 | 28185.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116277E+11 | 87601.92 | 16-JAN-18:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752149E+10 | 87601.92 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139499E+10 | 64713.36 | 04-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154437E+10 | 62400.94 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109003E+11 | 87601.92 | 14-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116277E+11 | 87601.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145752E+11 | 67404.68 | 16-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108115E+11 | 58370.60 | 05-FEB-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.456747E+09 | 17440.03 | 04-MAR-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125269E+11 | 66907.14 | 14-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145752E+11 | 67404.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 269223.38 | 269223.38 | 235.26 | 14-FEB-16:00 | 235.26 | 0.00 |
March | 0.00 | 0.00 | 6575438.64 | 6575438.64 | 986.88 | 08-MAR-16:00 | 986.88 | 0.00 |
April | 0.00 | 0.00 | 0.939111E+09 | 0.939111E+09 | 10251.69 | 29-APR-07:03 | 10251.69 | 0.00 |
May | 0.00 | 0.00 | 0.294487E+10 | 0.290881E+10 | 20378.67 | 27-MAY-07:02 | 16414.98 | 0.00 |
June | 0.00 | 0.00 | 0.710625E+10 | 0.690991E+10 | 22515.76 | 29-JUN-06:01 | 20245.20 | 0.00 |
July | 0.00 | 0.00 | 0.950856E+10 | 0.840358E+10 | 23630.61 | 29-JUL-07:02 | 15167.50 | 0.00 |
August | 0.00 | 0.00 | 0.922130E+10 | 0.803988E+10 | 23979.46 | 14-AUG-07:02 | 13648.20 | 0.00 |
September | 0.00 | 0.00 | 0.600535E+10 | 0.544268E+10 | 22450.86 | 07-SEP-07:02 | 15316.49 | 0.00 |
October | 0.00 | 0.00 | 0.198839E+10 | 0.186156E+10 | 20973.34 | 02-OCT-07:02 | 15912.36 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.377207E+11 | 0.345124E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.950856E+10 | 0.840358E+10 | 23979.46 | 20245.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 51429822.40 | 51429822.40 | 3306.84 | 28-APR-14:30 | 3306.84 | 0.00 |
May | 0.00 | 0.00 | 0.301867E+10 | 0.301495E+10 | 59592.87 | 28-MAY-12:15 | 56452.34 | 0.00 |
June | 0.00 | 0.00 | 0.157241E+11 | 0.156001E+11 | 62382.99 | 29-JUN-05:55 | 53056.01 | 0.00 |
July | 0.00 | 0.00 | 0.239257E+11 | 0.222064E+11 | 67988.61 | 01-JUL-17:12 | 39212.45 | 0.00 |
August | 0.00 | 0.00 | 0.198305E+11 | 0.183868E+11 | 66705.15 | 13-AUG-08:45 | 40472.58 | 0.00 |
September | 0.00 | 0.00 | 0.870325E+10 | 0.834262E+10 | 63109.07 | 04-SEP-10:40 | 50995.46 | 0.00 |
October | 0.00 | 0.00 | 0.158416E+10 | 0.155943E+10 | 58816.51 | 01-OCT-11:35 | 58816.51 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.728379E+11 | 0.691618E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.239257E+11 | 0.222064E+11 | 67988.61 | 58816.51 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161176E+09 | 0.03 | 188.95 | 08-JAN-06:10 | 0.09 |
February | 0.100989E+09 | 0.02 | 188.95 | 01-FEB-00:03 | 0.09 |
March | 9938633.11 | 0.00 | 188.95 | 03-MAR-23:30 | 0.09 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.173380E+09 | 0.03 | 188.95 | 06-DEC-06:40 | 0.09 |
Annual Sum or Average | 0.445483E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173380E+09 | 0.03 | 188.95 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.725016E+09 | 0.33 | 1481.67 | 02-JAN-06:01 | 1.11 |
February | 0.646768E+09 | 0.32 | 1481.67 | 01-FEB-06:01 | 1.11 |
March | 0.686003E+09 | 0.29 | 1481.67 | 01-MAR-07:02 | 1.11 |
April | 0.593300E+09 | 0.26 | 1481.67 | 01-APR-06:02 | 1.11 |
May | 0.611379E+09 | 0.26 | 1481.67 | 13-MAY-07:02 | 1.10 |
June | 0.654692E+09 | 0.28 | 1481.67 | 03-JUN-07:02 | 1.09 |
July | 0.650044E+09 | 0.27 | 1481.67 | 01-JUL-06:02 | 1.09 |
August | 0.668222E+09 | 0.28 | 1481.67 | 01-AUG-06:02 | 1.09 |
September | 0.588911E+09 | 0.25 | 1481.67 | 01-SEP-07:02 | 1.09 |
October | 0.594453E+09 | 0.25 | 1481.67 | 02-OCT-07:02 | 1.09 |
November | 0.611240E+09 | 0.27 | 1481.67 | 06-NOV-07:01 | 1.11 |
December | 0.723385E+09 | 0.30 | 1481.67 | 01-DEC-07:01 | 1.11 |
Annual Sum or Average | 0.775341E+10 | 0.28 | |||
Minimum of Months | 0.588911E+09 | 0.25 | 1481.67 | 1.09 | |
Maximum of Months | 0.725016E+09 | 0.33 | 1481.67 | 1.11 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177324E+10 | 0.59 | 3417.12 | 16-JAN-18:22 | 1.07 |
February | 0.152082E+10 | 0.51 | 3417.12 | 04-FEB-06:01 | 1.07 |
March | 0.151365E+10 | 0.32 | 2881.42 | 04-MAR-07:01 | 0.99 |
April | 0.135318E+10 | 0.25 | 1366.85 | 28-APR-16:00 | 0.65 |
May | 0.143417E+10 | 0.26 | 2740.27 | 19-MAY-17:08 | 0.96 |
June | 0.160179E+10 | 0.32 | 3417.12 | 13-JUN-17:05 | 1.07 |
July | 0.166710E+10 | 0.33 | 3417.12 | 02-JUL-13:13 | 1.06 |
August | 0.167179E+10 | 0.32 | 3417.12 | 01-AUG-17:05 | 1.06 |
September | 0.141622E+10 | 0.27 | 3417.12 | 03-SEP-13:23 | 1.06 |
October | 0.136277E+10 | 0.24 | 2513.73 | 01-OCT-14:13 | 0.92 |
November | 0.135678E+10 | 0.31 | 2434.09 | 27-NOV-06:01 | 1.07 |
December | 0.174911E+10 | 0.59 | 3417.12 | 14-DEC-04:02 | 1.07 |
Annual Sum or Average | 0.184206E+11 | 0.36 | |||
Minimum of Months | 0.135318E+10 | 0.24 | 1366.85 | 0.65 | |
Maximum of Months | 0.177324E+10 | 0.59 | 3417.12 | 1.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.725016E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.646837E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.687672E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.821210E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132118E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.246953E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.301596E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.289732E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.201721E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106579E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.611240E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.723385E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.611240E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.301596E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177324E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152082E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151365E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136671E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.220808E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.584382E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.792728E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.675363E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.362669E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176552E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135678E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.174911E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.374053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135678E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.792728E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.725016E+09 | 0.00 | 0.412213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646768E+09 | 269223.38 | 0.317151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686003E+09 | 6575438.64 | 0.159540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.593300E+09 | 0.939111E+09 | 0.207895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.611379E+09 | 0.294487E+10 | 20233140.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.654692E+09 | 0.710285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.650044E+09 | 0.950856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668222E+09 | 0.921190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.588911E+09 | 0.600307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594453E+09 | 0.198839E+10 | 0.237737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611240E+09 | 0.00 | 0.146804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723385E+09 | 0.00 | 0.413689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775341E+10 | 0.377056E+11 | 0.149598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.588911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725016E+09 | 0.950856E+10 | 0.413689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177324E+10 | 0.00 | 0.116277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152082E+10 | 0.00 | 0.752149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151365E+10 | 0.00 | 0.139499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135318E+10 | 51429822.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143417E+10 | 0.286899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160179E+10 | 0.153384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166710E+10 | 0.231273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167179E+10 | 0.191668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141622E+10 | 0.834885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136277E+10 | 0.154050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135678E+10 | 0.00 | 0.154437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174911E+10 | 0.00 | 0.109003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184206E+11 | 0.704423E+11 | 0.329888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177324E+10 | 0.231273E+11 | 0.116277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.725016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646768E+09 | 0.00 | 0.00 | 0.00 | 68964.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686003E+09 | 0.00 | 0.00 | 0.00 | 1669464.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.593300E+09 | 0.00 | 0.00 | 0.00 | 0.227910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.611379E+09 | 0.00 | 0.00 | 0.00 | 0.709802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.654692E+09 | 0.00 | 0.00 | 0.00 | 0.181484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.650044E+09 | 0.00 | 0.00 | 0.00 | 0.236592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668222E+09 | 0.00 | 0.00 | 0.00 | 0.222910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.588911E+09 | 0.00 | 0.00 | 0.00 | 0.142830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594453E+09 | 0.00 | 0.00 | 0.00 | 0.471339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775341E+10 | 0.00 | 0.00 | 0.00 | 0.924894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.588911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.725016E+09 | 0.00 | 0.00 | 0.00 | 0.236592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135318E+10 | 0.00 | 0.00 | 0.00 | 13531128.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143417E+10 | 0.00 | 0.00 | 0.00 | 0.773913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160179E+10 | 0.00 | 0.00 | 0.00 | 0.424203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166710E+10 | 0.00 | 0.00 | 0.00 | 0.626018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167179E+10 | 0.00 | 0.00 | 0.00 | 0.508184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141622E+10 | 0.00 | 0.00 | 0.00 | 0.221047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136277E+10 | 0.00 | 0.00 | 0.00 | 0.402750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184206E+11 | 0.00 | 0.00 | 0.00 | 0.189847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177324E+10 | 0.00 | 0.00 | 0.00 | 0.626018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129033E+10 | 0.00 | 0.00 | 0.12 |
February | 0.287490E+09 | 0.00 | 0.00 | 13790.66 | 0.00 | 0.105482E+10 | 29923447.55 | 0.00 | 0.13 |
March | 0.620827E+09 | 0.00 | 0.00 | 56131.16 | 0.00 | 0.512969E+09 | 0.120429E+09 | 0.00 | 0.15 |
April | 0.414426E+09 | 244006.62 | 0.00 | 2400085.12 | 0.00 | 32532445.75 | 0.117299E+10 | 0.00 | 0.34 |
May | 0.110676E+09 | 8938534.31 | 0.00 | 5362825.52 | 0.00 | 2463776.00 | 0.168361E+10 | 0.00 | 0.44 |
June | 8439260.02 | 0.225074E+09 | 0.00 | 4929414.80 | 674690.27 | 0.00 | 0.786553E+09 | 0.00 | 0.36 |
July | 657357.98 | 0.665909E+09 | 0.00 | 2813136.20 | 2472.13 | 0.00 | 0.125119E+09 | 0.00 | 0.27 |
August | 1108702.26 | 0.497349E+09 | 0.00 | 3990139.38 | 5094.50 | 0.00 | 0.343554E+09 | 0.00 | 0.36 |
September | 1520237.96 | 0.104635E+09 | 0.00 | 5684199.31 | 0.00 | 0.00 | 0.957253E+09 | 0.00 | 0.43 |
October | 0.325873E+09 | 11814231.73 | 0.00 | 3980950.47 | 0.00 | 61460504.55 | 0.155259E+10 | 0.00 | 0.39 |
November | 0.742089E+09 | 0.00 | 0.00 | 65616.67 | 0.00 | 0.486924E+09 | 77743711.06 | 0.00 | 0.13 |
December | 0.294028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148551E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.309091E+10 | 0.151396E+10 | 0.00 | 29296289.31 | 682256.90 | 0.492701E+10 | 0.684977E+10 | 0.00 | 0.27 |
Minimum of Months | 657357.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.742089E+09 | 0.665909E+09 | 0.00 | 5684199.31 | 674690.27 | 0.148551E+10 | 0.168361E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.349999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907847E+09 | 0.00 | 0.00 | 0.17 |
February | 0.339581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394074E+09 | 0.00 | 0.00 | 0.18 |
March | 0.327609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25863773.95 | 0.00 | 0.00 | 0.19 |
April | 0.311175E+10 | 0.00 | 0.00 | 236634.43 | 0.00 | 0.00 | 0.337433E+09 | 0.00 | 0.21 |
May | 0.204291E+10 | 1639905.08 | 0.00 | 5128410.95 | 273787.73 | 0.00 | 0.225348E+10 | 0.00 | 0.32 |
June | 0.528294E+09 | 0.320239E+09 | 0.00 | 10755043.09 | 211572.37 | 0.00 | 0.191122E+10 | 0.00 | 0.34 |
July | 661811.75 | 0.765167E+09 | 0.00 | 11265055.30 | 0.00 | 0.00 | 0.137570E+10 | 0.00 | 0.36 |
August | 85356897.29 | 0.346714E+09 | 0.00 | 15814712.09 | 0.00 | 0.00 | 0.246194E+10 | 0.00 | 0.42 |
September | 0.519947E+09 | 16603772.67 | 0.00 | 12963805.18 | 0.00 | 0.00 | 0.317319E+10 | 0.00 | 0.40 |
October | 0.323185E+10 | 19192.08 | 0.00 | 3126581.70 | 0.00 | 0.00 | 0.124778E+10 | 0.00 | 0.26 |
November | 0.373561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36945097.86 | 0.00 | 0.00 | 0.17 |
December | 0.437665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767283E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.278049E+11 | 0.145038E+10 | 0.00 | 59290242.74 | 485360.11 | 0.213201E+10 | 0.127607E+11 | 0.00 | 0.27 |
Minimum of Months | 661811.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.437665E+10 | 0.765167E+09 | 0.00 | 15814712.09 | 273787.73 | 0.907847E+09 | 0.317319E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.550737E+12 | 0.425669E+11 | 0.00 | 0.598194E+10 | 0.111501E+11 |
February | 0.687107E+12 | 0.385603E+11 | 0.00 | 0.516213E+10 | 0.779067E+10 |
March | 0.923968E+12 | 0.345538E+11 | 0.00 | 0.455624E+10 | 0.158405E+10 |
April | 0.117299E+13 | 0.305703E+11 | 0.00 | 0.507152E+10 | 0.133208E+10 |
May | 0.127040E+13 | 0.371523E+11 | 0.00 | 0.609293E+10 | 0.745762E+10 |
June | 0.122468E+13 | 0.299996E+11 | 0.00 | 0.270831E+10 | 0.288873E+11 |
July | 0.126167E+13 | 0.405425E+11 | 0.00 | 84825045.66 | 0.420604E+11 |
August | 0.123410E+13 | 0.443027E+11 | 0.00 | 0.207239E+10 | 0.363628E+11 |
September | 0.993455E+12 | 0.352200E+11 | 0.00 | 0.455312E+10 | 0.183474E+11 |
October | 0.799544E+12 | 0.441434E+11 | 0.00 | 0.641482E+10 | 0.456202E+10 |
November | 0.595697E+12 | 0.389895E+11 | 0.00 | 0.507938E+10 | 0.148010E+10 |
December | 0.513290E+12 | 0.395643E+11 | 0.00 | 0.692347E+10 | 0.103381E+11 |
Annual Sum or Average | 0.112276E+14 | 0.456165E+12 | 0.00 | 0.547011E+11 | 0.171352E+12 |
Minimum of Months | 0.513290E+12 | 0.299996E+11 | 0.00 | 84825045.66 | 0.133208E+10 |
Maximum of Months | 0.127040E+13 | 0.443027E+11 | 0.00 | 0.692347E+10 | 0.420604E+11 |