Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 10:43:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1134.71 | 234.68 | 234.68 |
Net Site Energy | 1134.71 | 234.68 | 234.68 |
Total Source Energy | 3478.39 | 719.40 | 719.40 |
Net Source Energy | 3478.39 | 719.40 | 719.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 55.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 81.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1079.39 | 55.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 55.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 185.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 67.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 55.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 185.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 81.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 59.91 | 11.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 223.24 | 11.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 59.91 | 11.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 223.24 | 11.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1079.388 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1079.388 | 100.00 |
Total On-Site and Utility Electric Sources | 1079.388 | 100.00 |
Total Electricity End Uses | 1079.388 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 66.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3132.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 26.83 |
Skylight-Roof Ratio [%] | 0.58 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-14:50 | 16-MAR-06:10 | - | - | - | - | - | - | - | - | - | - | 24-MAY-11:09 |
Heating | 0.00 | 11645.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23557.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7486.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1673.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 81012.96 | 11645.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 11645.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23557.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5181.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1673.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 59.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 585.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 425.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 259.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 72.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3418.42 | 59.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 707.00 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 707.00 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.31 |
ZONE2 FINE STORAGE DIRECT AIR | 3.37 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.814030 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.814030 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 33275.49 |
PSZ-OFFICE HEATING COIL | 31779.92 |
PSZ-FINE STORAGE HEATING COIL | 102553.84 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-FINE STORAGE | 3.37 | 3.37 | 3.37 | 3.37 | 3.37 | 3.37 | 1.00 | 1.00 | 3.37 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.31 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.37 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.31 | 1490.02 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.37 | 3691.23 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 27423.80 | 31779.92 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.37 | 3.37 | 3.37 | 3.37 | 83747.54 | 102553.84 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.31 | 0.653453 | 1.31 | 27423.80 | 14037.34 | 27423.80 | 0.758030 | 0.758030 |
PSZ-FINE STORAGE COOLING COIL | 3.37 | 1.69 | 3.37 | 83747.54 | 41873.73 | 83747.54 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
5 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
6 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
7 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
8 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
9 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
10 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
11 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
12 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
13 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
14 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
15 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
16 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.21548121E-14 | -0.16827101E-15 | 0.71656587E-12 | 0.12539735E-15 |
85 | 3 | -0.52378714E-04 | 0.55487071E-06 | -0.36253864E-03 | 0.13752504E-12 |
86 | 2 | 1.1001971 | 0.12432070E-01 | 1.6865760 | -0.69502831E-04 |
87 | 1 | -16.840218 | 0.32704464 | -7.1998246 | 0.32320315 |
88 | 0 | 16.290177 | 0.21062598 | 6.0637144 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.4 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.733 | 0.325 | 0.251 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13218.72666 | 15862.47199 | 1.08909 | 1.30691 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.35133 | 1.71656E-002 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7120.34490 | 8544.41388 | 0.19991 | 0.23989 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70000 | 6.99286E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 43749.79997 | 52499.75996 | 2.81043 | 3.37251 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.99900 | 1.71668E-002 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 12045.03782 | 14454.04538 | 0.28516 | 0.35393 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70000 | 6.99286E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | 00:10:00 | 8.70000 | 6.99286E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20024.47 | 1.30691 | 1.30691 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7295.44 | 0.23989 | 0.23989 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 62596.29 | 3.37251 | 3.37251 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 13388.54 | 0.35393 | 0.35393 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30691 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.37251 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 33275.48708 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30691 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30691 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30691 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30691 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30691 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.30691 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.37251 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.37251 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.37251 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.37251 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.37251 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.37251 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.30691 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.37251 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30691 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30691 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1490.01593 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30691 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30691 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30691 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30691 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30691 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65345 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30691 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27423.80000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14037.34491 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27423.80000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75803 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75803 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27423.80000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31779.91668 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31779.91668 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.37251 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.37251 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3691.23440 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.37251 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.37251 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.37251 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.37251 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.37251 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.68626 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.37251 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 83747.54000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 41873.72734 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 83747.54000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 83747.54000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 102553.84416 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 102553.84416 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 26408.8 | 11.08 | 10.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 81126.1 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.1812025369E-002 | 3.4274072532E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1174389621 | 0.1799403661 | Pass | Pass | 0.7753820651 | 8.9861716153 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.5822713573E-002 | 3.6283208239E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10605.19 | 428.76 | 0.00 | -67.4 | 889.41 | 11855.95 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.233 | 0.240 | 3204.84 | 3178.02 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 44.49 | 6.201 | 0.341 | 0.342 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 37.98 | 6.096 | 0.357 | 0.358 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.82 | 83.82 | 134.25 | |
Exterior Lighting Total | 8532.22 | 134.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27423.80 | 20788.06 | 6635.74 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 83747.54 | 58713.73 | 25033.81 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 26408.8 | 11.08 | 10.44 | ||||
PSZ-FINE STORAGE COOLING COIL | 81126.1 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 33275.49 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31779.92 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 102553.84 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.31 | 1490.02 | 1140.11 | 1.00 | 1.30 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.37 | 3691.23 | 1094.51 | 1.00 | 1.22 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13218.73 | 15862.47 | 66.96 | 1.089 | 1.307 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00880 | 32.35 | 0.01717 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 43749.80 | 52499.76 | 37.68 | 2.810 | 3.373 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 26.70 | 26.69 | 0.00972 | 33.00 | 0.01717 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 33.41 | 0.01724 | 33.13 | 0.01717 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7120.34 | 8544.41 | 36.07 | 0.200 | 0.240 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00808 | 8.70 | 0.00699 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 12045.04 | 14454.05 | 10.37 | 0.285 | 0.354 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00735 | 8.70 | 0.00699 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | 00:10:00 | 10.00 | 11.01 | 0.00702 | 8.70 | 0.00699 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.31 | 1.31 | 0.24 | 0.24 | 1.3069 | 1.3069 | 1.3069 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.37 | 3.37 | 0.35 | 0.35 | 3.3725 | 3.3725 | 3.3725 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 33275.487 | 33275.487 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 33275.49 | 33275.49 | 0.814030 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.13 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 27423.800 | 20788.063 | 1.306910 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 27423.80 | 21725.37 | 1.306910 | 25.61 | 17.83 | 0.00956697 | 12.00 | 11.25 | 0.00800000 | 32.44 | 0.01716576 | 25.13 | 9.2076 | 23.90 | 0.00879596 | 47.5662 | 13212.68 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31779.917 | 31779.917 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31779.92 | 31779.92 | 1.306906 | 19.88 | 14.40 | 0.00798194 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 9.2076 | 21.10 | 0.00808224 | 51.8606 | 7120.34 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 83747.540 | 58713.725 | 3.372510 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 83747.54 | 61739.06 | 3.372510 | 28.25 | 19.42 | 0.01050131 | 12.00 | 11.25 | 0.00800000 | 33.07 | 0.01716695 | 25.29 | 10.4944 | 26.69 | 0.00971952 | 44.4414 | 43737.48 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 102553.844 | 102553.844 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 102553.84 | 102553.84 | 3.372513 | 14.84 | 11.74 | 0.00730963 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 10.4944 | 15.56 | 0.00734678 | 66.8231 | 11846.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33275.487 | 33275.487 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.814030 | 0.97906550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 33275.49 | 33275.49 | 1.0000 | 0.97906550 | 0.814030 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.13 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33275.49 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27423.800 | 20788.063 | 1.306910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6245 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.306906 | 1.57186618 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 27423.80 | 21725.37 | 1.0000 | 1.57187154 | 1.306910 | 25.61 | 17.83 | 0.00956697 | 50116.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27423.80 | 32.44 | 0.01716576 | 25.13 | 0.12033486 | 9.2076 | 23.90 | 0.00879596 | 23.90 | 0.00879596 | 47.5662 | 13212.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31779.917 | 31779.917 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.306906 | 1.57186618 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 31779.92 | 31779.92 | 1.0000 | 1.57186618 | 1.306906 | 19.88 | 14.40 | 0.00798194 | 40233.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31779.92 | 8.70 | 0.00699286 | 8.70 | 0.12033486 | 9.2076 | 21.01 | 0.00808224 | 21.10 | 0.00808224 | 51.8606 | 7120.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 83747.540 | 58713.725 | 3.372510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3614 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.372513 | 4.05625312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 83747.54 | 61739.06 | 1.0000 | 4.05624909 | 3.372510 | 28.25 | 19.42 | 0.01050131 | 55201.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83747.54 | 33.07 | 0.01716695 | 25.29 | 0.35392606 | 10.4944 | 26.69 | 0.00971952 | 26.69 | 0.00971952 | 44.4414 | 43737.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 102553.844 | 102553.844 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.372513 | 4.05625312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 102553.84 | 102553.84 | 1.0000 | 4.05625312 | 3.372513 | 14.84 | 11.74 | 0.00730963 | 33393.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102553.84 | 8.70 | 0.00699286 | 8.70 | 0.35392606 | 10.4944 | 15.56 | 0.00734678 | 15.56 | 0.00734678 | 66.8231 | 11846.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3300.17 | 663.83 | 511.83 |
ZONE2 FINE STORAGE | 3516.00 | 3153.00 | 3067.33 |
ZONE3 BULK STORAGE | 3403.33 | 3234.83 | 3072.00 |
Facility | 3526.17 | 3332.83 | 3132.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 69.17 | 0.00 | 66.50 |
ZONE2 FINE STORAGE | 0.00 | 243.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 312.17 | 0.00 | 66.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.411 | 0.521 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.410 | 0.451 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.203 | 0.000 | 1.265 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1481455.19 | 0.00 | 1481455.19 | 3081126.43 | 4562581.62 | 3794880.16 | 5392.82 | 3367.18 | 0.00 | 80.00 |
ZONE2 FINE STORAGE | 4629376.31 | 0.00 | 4629376.31 | 11739418.50 | 16368794.81 | 11161412.23 | 5410.33 | 3349.67 | 0.00 | 1572.87 |
ZONE3 BULK STORAGE | 0.00 | 0.24E+09 | 0.24E+09 | 48387127.55 | 0.29E+09 | 25671248.14 | 5958.41 | 107.71 | 2693.89 | 4870.49 |
Total Facility | 6110831.51 | 0.24E+09 | 0.25E+09 | 63207672.48 | 0.31E+09 | 40627540.53 | 7070.98 | 3440.90 | 2693.89 | 4932.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1129 | 0.0000 | 0.1129 | 0.1428 | 0.2557 | 0.1203 | 268.82 | 3367.18 | 0.00 |
ZONE2 FINE STORAGE | 0.3251 | 0.0000 | 0.3251 | 0.3583 | 0.6833 | 0.3539 | 302.32 | 3333.68 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 11.7180 | 11.7180 | 1.9057 | 13.6237 | 0.8140 | 1930.03 | 52.71 | 1653.26 |
Total Facility | 0.4379 | 11.7180 | 12.1560 | 2.4068 | 14.5628 | 1.2883 | 1946.98 | 3369.90 | 1653.26 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2143044.85 | 0.00 | 2143044.85 | 3794880.16 | 5379.37 | 0.49 | 3380.14 | 78.33 |
PSZ-FINE STORAGE | 6696767.57 | 0.00 | 6696767.57 | 11161412.23 | 5386.60 | 1.35 | 3372.05 | 1570.76 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1633 | 0.0000 | 0.1633 | 0.1203 | 255.64 | 0.42 | 3379.94 |
PSZ-FINE STORAGE | 0.4702 | 0.0000 | 0.4702 | 0.3539 | 301.80 | 0.00 | 3334.20 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3604.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 4957.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1684 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5050 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1079.39 | 5771.67 | 01-JAN-07:20 | 81012.96 | 28-JUL-14:50 |
Electricity:Building | 670.25 | 5288.67 | 01-JAN-00:10 | 50600.89 | 10-APR-13:40 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 363.31 | 2117.83 | 01-JAN-00:10 | 28507.00 | 10-APR-13:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 81.85 | 0.00 | 01-JAN-00:10 | 7486.54 | 20-JUL-11:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 14.76 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
Ventilation (simple):Fans:Electricity | 14.76 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 14.76 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-APR-10:40 |
ElectricityPurchased:Facility | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
ElectricityPurchased:Plant | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
Cogeneration:ElectricityPurchased | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
General:Cogeneration:ElectricityPurchased | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
ElectricityNet:Plant | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
Cogeneration:ElectricityNet | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
General:Cogeneration:ElectricityNet | 1079.39 | 5771.67 | 19-FEB-13:10 | 81012.96 | 28-JUL-14:50 |
Electricity:HVAC | 252.09 | 0.00 | 01-JAN-00:10 | 31532.71 | 27-JUL-16:00 |
General:Fans:Electricity | 67.09 | 0.00 | 01-JAN-00:10 | 5181.25 | 02-JAN-10:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 185.00 | 0.00 | 01-JAN-00:10 | 26351.46 | 27-JUL-16:00 |
General:Cooling:Electricity | 185.00 | 0.00 | 01-JAN-00:10 | 26351.46 | 27-JUL-16:00 |
ExteriorLights:Electricity | 134.25 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.25 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 22.79 | 483.00 | 27-MAR-05:10 | 1741.24 | 18-JAN-12:10 |
WaterSystems:Electricity | 22.79 | 483.00 | 27-MAR-05:10 | 1741.24 | 18-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 22.79 | 483.00 | 27-MAR-05:10 | 1741.24 | 18-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 55.32 | 1750.00 | 27-MAR-05:10 | 11645.21 | 16-MAR-06:10 |
NaturalGas:HVAC | 55.32 | 1750.00 | 27-MAR-05:10 | 11645.21 | 16-MAR-06:10 |
Heating:NaturalGas | 55.32 | 1750.00 | 27-MAR-05:10 | 11645.21 | 16-MAR-06:10 |
General:Heating:NaturalGas | 55.32 | 1750.00 | 27-MAR-05:10 | 11645.21 | 16-MAR-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 24-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1028.03 | 0.00 | 01-JAN-00:10 | 136937.46 | 27-JUL-16:00 |
EnergyTransfer:Building | 378.76 | 0.00 | 01-JAN-00:10 | 52352.76 | 27-JUL-16:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 95.78 | 0.00 | 01-JAN-00:10 | 14364.63 | 27-JUL-16:10 |
Heating:EnergyTransfer | 0.31 | 0.00 | 01-JAN-00:10 | 5707.91 | 16-MAR-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.14 | 0.00 | 01-JAN-00:10 | 5707.91 | 16-MAR-06:10 |
General:Heating:EnergyTransfer | 0.31 | 0.00 | 01-JAN-00:10 | 5707.91 | 16-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.14 | 0.00 | 01-JAN-00:10 | 5707.91 | 16-MAR-06:10 |
Cooling:EnergyTransfer | 378.45 | 0.00 | 01-JAN-00:10 | 52352.76 | 27-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 95.64 | 0.00 | 01-JAN-00:10 | 14364.63 | 27-JUL-16:10 |
General:Cooling:EnergyTransfer | 378.45 | 0.00 | 01-JAN-00:10 | 52352.76 | 27-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 95.64 | 0.00 | 01-JAN-00:10 | 14364.63 | 27-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 282.98 | 0.00 | 01-JAN-00:10 | 39410.40 | 27-JUL-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.17 | 0.00 | 01-JAN-00:10 | 2065.93 | 06-FEB-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.17 | 0.00 | 01-JAN-00:10 | 2065.93 | 06-FEB-18:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 282.81 | 0.00 | 01-JAN-00:10 | 39410.40 | 27-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 282.81 | 0.00 | 01-JAN-00:10 | 39410.40 | 27-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 649.26 | 0.00 | 01-JAN-00:10 | 85895.49 | 16-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.09 | 0.00 | 01-JAN-00:10 | 6664.97 | 16-MAR-06:10 |
CoolingCoils:EnergyTransfer | 649.17 | 0.00 | 01-JAN-00:10 | 85895.49 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.144 | -95.632 | 0.000 | 0.000 | 9.127 | 30.293 | 31.946 | 13.228 | 0.000 | 6.217 | 19.205 | 0.000 | -6.561 | 0.000 | -7.967 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.170 | -282.801 | 0.000 | 0.000 | 17.233 | 244.699 | 0.000 | 0.000 | 0.000 | 9.820 | 48.743 | 0.000 | 0.000 | 0.000 | -37.864 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31.199 | 241.203 | 107.344 | 115.986 | 0.000 | 3.836 | 3.114 | 0.000 | -47.776 | 0.000 | -454.905 | -0.002 |
Total Facility | 0.000 | 0.000 | 0.314 | -378.433 | 0.000 | 0.000 | 57.559 | 516.195 | 139.290 | 129.214 | 0.000 | 19.872 | 71.062 | 0.000 | -54.336 | 0.000 | -500.735 | -0.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | -24554.40 | 0.00 | 0.00 | 90.38 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 25100.94 | 0.00 | -883.12 | 0.00 | -900.73 | 0.00 |
ZONE2 FINE STORAGE | 09-APR-15:23 | 0.00 | 0.00 | 0.00 | -71006.95 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 143.40 | 68715.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | -77766.69 | 0.00 | 0.00 | 576.27 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 74867.03 | 0.00 | -4185.81 | 0.00 | -954.10 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-FEB-06:03 | 0.00 | 0.00 | 15891.41 | 0.00 | 0.00 | 0.00 | 124.69 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1314.64 | 0.00 | -2153.00 | -13695.38 |
ZONE2 FINE STORAGE | 06-FEB-18:00 | 0.00 | 0.00 | 2065.98 | 0.00 | 0.00 | 0.00 | 552.63 | 12891.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3182.95 | -12326.82 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-06:03 | 0.00 | 0.00 | 15891.41 | 0.00 | 0.00 | 0.00 | 1133.76 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 50034.82 | 0.00 | -9937.77 | 0.00 | -64585.54 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3069 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.3069 | 0.0921 | 1.0000 | Not calculated | 0.1203 | 0.0921 | ||
PSZ-FINE STORAGE | 3.3725 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 3.3725 | 0.1049 | 1.0000 | Not calculated | 0.3539 | 0.1049 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3069 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.3069 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0921 | ||
PSZ-FINE STORAGE | 3.3725 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 3.3725 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.1049 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3069 | 1.3069 | 1.3069 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3725 | 3.3725 | 3.3725 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3069 | 1.3069 | 1.3069 | 1.3069 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.3725 | 3.3725 | 3.3725 | 3.3725 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3069 | 1.3069 | 1.3069 | No | 0.1203 | 0.5016 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3725 | 3.3725 | 3.3725 | No | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3069 | 1.3069 | 1.3069 | 1.3069 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.3725 | 3.3725 | 3.3725 | 3.3725 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 66.50 |
Number of hours not met | 66.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 55.32 | 11645.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 185.00 | 26351.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.25 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 14.76 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.09 | 5181.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.79 | 1741.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1079.39 |
Natural Gas | 0.00 | 55.32 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1134.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 38.26 |
Fans (All) | 16.93 |
Service Water Heating | 4.71 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 223.24 |
Subtotal | 223.24 |
Natural Gas [MJ/m2] | |
Space Heating | 11.44 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.44 |
Subtotal | 11.44 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.49 |
Space Heating | 4.88 |
Space Cooling | 16.30 |
Fans (All) | 7.21 |
Service Water Heating | 2.01 |
Receptacle Equipment | 12.28 |
Miscellaneous | 11.83 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4995.50 | 3466.17 | 298.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2200.33 | 6559.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2156.50 | 3317.33 | 3286.17 | 0.00 | 0.00 |
Min | 2156.50 | 3317.33 | 0.00 | 0.00 | 0.00 |
Max | 4995.50 | 6559.67 | 3286.17 | 0.00 | 0.00 |
Average | 3117.44 | 4447.72 | 1194.83 | 0.00 | 0.00 |
Sum | 9352.33 | 13343.17 | 3584.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33026.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 12729.50 | 69989.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 31910.67 | 76294.17 | 82988.17 | 0.00 | 0.00 |
Min | 12729.50 | 0.33 | 0.00 | 0.00 | 0.00 |
Max | 33026.67 | 76294.17 | 82988.17 | 0.00 | 0.00 |
Average | 25888.94 | 48761.33 | 27662.72 | 0.00 | 0.00 |
Sum | 77666.83 | 146284.00 | 82988.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 3880.33 | 4848.33 | 31.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 1395.50 | 7364.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1314.83 | 5937.50 | 1507.67 | 0.00 | 0.00 |
Min | 1314.83 | 4848.33 | 0.00 | 0.00 | 0.00 |
Max | 3880.33 | 7364.50 | 1507.67 | 0.00 | 0.00 |
Average | 2196.89 | 6050.11 | 513.00 | 0.00 | 0.00 |
Sum | 6590.67 | 18150.33 | 1539.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 30693.33 | 2333.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 10915.50 | 71803.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 22732.00 | 119861.00 | 48600.00 | 0.00 | 0.00 |
Min | 10915.50 | 2333.67 | 0.00 | 0.00 | 0.00 |
Max | 30693.33 | 119861.00 | 48600.00 | 0.00 | 0.00 |
Average | 21446.94 | 64666.06 | 16200.00 | 0.00 | 0.00 |
Sum | 64340.83 | 193998.17 | 48600.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483087E+10 | 22228.62 | 19-JAN-06:02 | 18.30 | 16.26 | 0.632136E+09 | 769.04 | 21-JAN-16:10 | 19.32 | 14.21 |
February | 0.508466E+10 | 24471.18 | 28-FEB-06:02 | 16.88 | 13.54 | 0.581966E+09 | 770.51 | 09-FEB-08:09 | 16.88 | 13.54 |
March | 0.640049E+10 | 20965.56 | 03-MAR-06:02 | 21.10 | 16.96 | 0.682787E+09 | 769.06 | 11-MAR-16:30 | 22.50 | 16.37 |
April | 0.782567E+10 | 24555.24 | 19-APR-05:02 | 15.10 | 11.88 | 0.635060E+09 | 769.07 | 17-APR-14:20 | 15.10 | 11.88 |
May | 0.952304E+10 | 21759.08 | 08-MAY-05:01 | 23.90 | 19.12 | 0.660605E+09 | 769.07 | 22-MAY-12:09 | 33.48 | 23.09 |
June | 0.990736E+10 | 18752.78 | 17-JUN-05:01 | 25.50 | 21.57 | 0.660713E+09 | 768.97 | 23-JUN-08:20 | 27.57 | 25.14 |
July | 0.102319E+11 | 18927.77 | 06-JUL-05:01 | 23.90 | 22.23 | 0.635330E+09 | 769.10 | 27-JUL-15:39 | 34.80 | 25.19 |
August | 0.106680E+11 | 19603.41 | 30-AUG-05:01 | 24.90 | 22.92 | 0.686164E+09 | 768.97 | 24-AUG-08:09 | 24.90 | 22.92 |
September | 0.972179E+10 | 19173.31 | 05-SEP-05:01 | 23.12 | 21.64 | 0.635313E+09 | 768.97 | 19-SEP-07:40 | 27.20 | 24.31 |
October | 0.900622E+10 | 22613.36 | 18-OCT-05:01 | 24.50 | 18.64 | 0.635235E+09 | 768.97 | 10-OCT-12:30 | 24.50 | 18.64 |
November | 0.709262E+10 | 20418.21 | 07-NOV-06:01 | 20.10 | 19.76 | 0.609033E+09 | 769.05 | 14-NOV-15:39 | 23.50 | 15.78 |
December | 0.534313E+10 | 23077.51 | 02-DEC-06:01 | 20.10 | 18.90 | 0.632594E+09 | 769.04 | 13-DEC-16:00 | 20.60 | 15.54 |
Annual Sum or Average | 0.956357E+11 | 0.768694E+10 | ||||||||
Minimum of Months | 0.483087E+10 | 18752.78 | 15.10 | 11.88 | 0.581966E+09 | 768.97 | 15.10 | 11.88 | ||
Maximum of Months | 0.106680E+11 | 24555.24 | 25.50 | 22.92 | 0.686164E+09 | 770.51 | 34.80 | 25.19 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.944929E+10 | 30031.61 | 01-JAN-13:25 | 26.65 | 21.70 | 0.181892E+10 | 2246.89 | 27-JAN-11:20 | 22.07 | 15.40 |
February | 0.103324E+11 | 59443.87 | 19-FEB-15:13 | 27.20 | 21.86 | 0.167445E+10 | 2247.00 | 27-FEB-14:39 | 26.10 | 16.60 |
March | 0.145597E+11 | 57808.12 | 26-MAR-14:03 | 27.80 | 22.29 | 0.196698E+10 | 2246.97 | 11-MAR-14:20 | 27.80 | 22.29 |
April | 0.221120E+11 | 71007.73 | 09-APR-15:23 | 27.50 | 18.52 | 0.185329E+10 | 2247.06 | 17-APR-15:30 | 31.95 | 20.03 |
May | 0.296954E+11 | 63853.04 | 02-MAY-17:06 | 28.12 | 19.68 | 0.192884E+10 | 2246.81 | 10-MAY-07:10 | 26.28 | 23.33 |
June | 0.333330E+11 | 61562.71 | 11-JUN-11:43 | 31.10 | 23.34 | 0.192886E+10 | 2246.81 | 19-JUN-07:10 | 25.28 | 22.81 |
July | 0.365418E+11 | 62445.14 | 21-JUL-17:42 | 30.50 | 23.96 | 0.185457E+10 | 2246.80 | 17-JUL-08:20 | 30.50 | 23.96 |
August | 0.354136E+11 | 61473.48 | 06-AUG-12:32 | 32.93 | 25.10 | 0.200304E+10 | 2246.80 | 12-AUG-08:30 | 22.50 | 22.26 |
September | 0.333930E+11 | 61579.03 | 04-SEP-13:53 | 30.00 | 23.99 | 0.185480E+10 | 2246.81 | 27-SEP-07:10 | 23.48 | 22.19 |
October | 0.281547E+11 | 64558.84 | 15-OCT-15:23 | 29.15 | 20.93 | 0.185472E+10 | 2246.81 | 23-OCT-07:10 | 23.35 | 21.85 |
November | 0.181385E+11 | 57539.36 | 19-NOV-13:33 | 26.70 | 21.27 | 0.177235E+10 | 2246.81 | 30-NOV-08:09 | 25.68 | 24.45 |
December | 0.116894E+11 | 56235.46 | 10-DEC-16:13 | 27.93 | 22.51 | 0.182155E+10 | 2246.96 | 12-DEC-14:50 | 18.40 | 12.96 |
Annual Sum or Average | 0.282813E+12 | 0.223324E+11 | ||||||||
Minimum of Months | 0.944929E+10 | 30031.61 | 26.65 | 18.52 | 0.167445E+10 | 2246.80 | 18.40 | 12.96 | ||
Maximum of Months | 0.365418E+11 | 71007.73 | 32.93 | 25.10 | 0.200304E+10 | 2247.06 | 31.95 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.408432E+10 | 6044.41 | 02-JAN-15:09 | 28.35 | 22.91 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.376557E+10 | 6048.77 | 22-FEB-15:39 | 27.80 | 14.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.462204E+10 | 6276.28 | 30-MAR-13:09 | 26.70 | 20.09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.501109E+10 | 7442.72 | 17-APR-15:20 | 32.03 | 19.94 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.548256E+10 | 8242.61 | 22-MAY-13:30 | 34.15 | 23.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.558489E+10 | 7390.60 | 10-JUN-15:39 | 31.70 | 24.31 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 | 23.72 | 0.567104E+10 | 8801.02 | 29-JUL-15:00 | 35.60 | 24.39 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.597738E+10 | 8152.02 | 23-AUG-13:09 | 33.62 | 25.44 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 | 24.00 | 0.544142E+10 | 7566.60 | 13-SEP-14:09 | 32.12 | 24.21 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.524809E+10 | 7468.10 | 14-OCT-13:30 | 31.95 | 24.19 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.464874E+10 | 6479.33 | 03-NOV-13:50 | 29.40 | 24.41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.426445E+10 | 6344.77 | 08-DEC-14:09 | 27.70 | 22.74 |
Annual Sum or Average | 0.00 | 0.598016E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.376557E+10 | 6044.41 | 26.70 | 14.73 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.597738E+10 | 8801.02 | 35.60 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31949905.38 | 3161.45 | 25-JAN-07:20 | 9.60 |
February | 31697889.38 | 15891.43 | 04-FEB-06:03 | 5.50 |
March | 36552920.46 | 5707.91 | 16-MAR-06:10 | 6.70 |
April | 1198419.53 | 727.36 | 19-APR-06:10 | 15.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 5945206.16 | 1664.18 | 13-NOV-07:30 | 12.50 |
December | 37110639.23 | 4467.06 | 27-DEC-07:10 | 8.98 |
Annual Sum or Average | 0.144455E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 37110639.23 | 15891.43 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8036744.29 | 1497.88 | 06-JAN-07:05 | 22.88 |
February | 74813838.74 | 2065.93 | 06-FEB-18:00 | 22.20 |
March | 31226144.21 | 1556.47 | 23-MAR-06:05 | 21.70 |
April | 3410496.14 | 1310.76 | 21-APR-06:05 | 22.30 |
May | 202694.78 | 529.34 | 01-MAY-06:05 | 20.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 4742999.49 | 838.70 | 28-NOV-07:05 | 20.68 |
December | 47154293.83 | 1709.63 | 23-DEC-07:30 | 23.05 |
Annual Sum or Average | 0.169587E+09 | |||
Minimum of Months | 0.00 | 0.00 | 20.68 | |
Maximum of Months | 74813838.74 | 2065.93 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65464883.64 | 0.134415E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146006E+09 | 0.125684E+10 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168155E+09 | 0.137249E+10 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353188E+09 | 0.675052E+09 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811343E+09 | 0.386844E+09 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851925E+09 | 0.138267E+09 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928228E+09 | 0.136195E+09 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101983E+10 | 0.111933E+09 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804809E+09 | 0.135650E+09 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636324E+09 | 0.281706E+09 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352548E+09 | 0.778213E+09 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78739867.93 | 0.134955E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621656E+10 | 0.796689E+10 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65464883.64 | 0.111933E+09 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101983E+10 | 0.137249E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12556220.36 | 0.574759E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28578349.81 | 0.681527E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67795564.97 | 0.711858E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313677E+09 | 0.372601E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122917E+10 | 0.171247E+10 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165743E+10 | 0.488266E+09 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176189E+10 | 0.356719E+09 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195767E+10 | 0.346170E+09 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176812E+10 | 0.525024E+09 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847734E+09 | 0.115579E+10 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142170E+09 | 0.388173E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32886792.91 | 0.599015E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981966E+10 | 0.378638E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12556220.36 | 0.346170E+09 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195767E+10 | 0.711858E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40225086.09 | 0.213644E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112728E+09 | 0.221469E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9033921.91 | 0.280284E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4267943.93 | 0.216120E+11 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60391045.80 | 0.150500E+11 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1622538.19 | 0.753599E+10 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59761344.67 | 0.520140E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13667208.30 | 0.611188E+10 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1883014.10 | 0.657114E+10 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5718534.26 | 0.112338E+11 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276147.96 | 0.197789E+11 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28512588.26 | 0.234520E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338087E+09 | 0.188087E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276147.96 | 0.520140E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112728E+09 | 0.280284E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.16 | 02-JAN-12:10 | 5755.85 | 25-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.38 | 02-FEB-13:00 | 6086.31 | 03-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2893.24 | 13-MAR-17:00 | 7576.66 | 16-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.50 | 17-APR-17:00 | 3641.52 | 19-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.41 | 22-MAY-16:10 | 1179.73 | 01-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3456.37 | 08-JUN-16:10 | 705.39 | 18-JUN-20:00 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.48 | 27-JUL-16:10 | 638.84 | 02-JUL-15:35 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3997.91 | 16-AUG-16:10 | 857.52 | 14-AUG-03:00 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4028.59 | 18-SEP-16:10 | 636.81 | 05-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3768.55 | 03-OCT-16:10 | 979.39 | 31-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2144.00 | 03-NOV-16:10 | 5533.56 | 27-NOV-07:03 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1276.00 | 08-DEC-13:00 | 6816.21 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.16 | 636.81 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.48 | 7576.66 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.26 | 07-JAN-13:00 | 13596.99 | 24-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.92 | 02-FEB-14:00 | 15666.83 | 03-FEB-09:00 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3133.27 | 13-MAR-17:00 | 15566.07 | 15-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5108.76 | 15-APR-17:00 | 7733.37 | 18-APR-08:00 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8262.90 | 22-MAY-15:20 | 5573.09 | 10-MAY-15:10 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4314.91 | 08-JUN-16:00 | 3276.80 | 18-JUN-20:00 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7152.82 | 27-JUL-16:00 | 2621.36 | 04-JUL-03:00 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5527.07 | 16-AUG-16:00 | 4088.97 | 14-AUG-03:00 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5522.41 | 18-SEP-16:00 | 2395.48 | 19-SEP-23:10 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5443.00 | 03-OCT-15:10 | 4084.48 | 16-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.03 | 03-NOV-16:00 | 12997.18 | 11-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.95 | 10-DEC-14:57 | 13218.54 | 27-DEC-08:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.26 | 2395.48 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8262.90 | 15666.83 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3229.68 | 29-JAN-12:00 | 43363.74 | 24-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6273.96 | 08-FEB-13:10 | 48356.53 | 03-FEB-09:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.41 | 05-MAR-12:00 | 53060.11 | 15-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 985.90 | 16-APR-12:53 | 32779.20 | 18-APR-09:00 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2833.01 | 29-MAY-12:33 | 36241.20 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.79 | 11-JUN-12:52 | 26137.80 | 22-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1777.87 | 23-JUL-10:55 | 17263.22 | 14-JUL-15:00 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1262.23 | 20-AUG-10:52 | 21523.95 | 12-AUG-08:00 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 795.85 | 24-SEP-10:53 | 16038.21 | 02-SEP-12:10 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.77 | 09-OCT-10:55 | 19625.06 | 10-OCT-12:52 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.02 | 17-NOV-15:00 | 47890.91 | 11-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1931.52 | 24-DEC-11:35 | 42981.84 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 311.02 | 16038.21 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6273.96 | 53060.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22228.62 | 19-JAN-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.49 |
February | 24471.18 | 28-FEB-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.62 |
March | 20965.56 | 03-MAR-06:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.32 |
April | 24555.24 | 19-APR-05:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.73 |
May | 21759.08 | 08-MAY-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.17 |
June | 18752.78 | 17-JUN-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 |
July | 18927.77 | 06-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.02 |
August | 19603.41 | 30-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.85 |
September | 19173.31 | 05-SEP-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.12 |
October | 22613.36 | 18-OCT-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.03 |
November | 20418.21 | 07-NOV-06:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.55 |
December | 23077.51 | 02-DEC-06:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18752.78 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24555.24 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30031.61 | 01-JAN-13:25 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 |
February | 59443.87 | 19-FEB-15:13 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.47 | 0.00 |
March | 57808.12 | 26-MAR-14:03 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.85 | 0.00 |
April | 71007.73 | 09-APR-15:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.40 | 0.00 |
May | 63853.04 | 02-MAY-17:06 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.16 | 0.00 |
June | 61562.71 | 11-JUN-11:43 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.99 | 0.00 |
July | 62445.14 | 21-JUL-17:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.98 | 0.00 |
August | 61473.48 | 06-AUG-12:32 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.13 | 0.00 |
September | 61579.03 | 04-SEP-13:53 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.02 | 0.00 |
October | 64558.84 | 15-OCT-15:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.28 | 0.00 |
November | 57539.36 | 19-NOV-13:33 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.75 |
December | 56235.46 | 10-DEC-16:13 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 30031.61 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71007.73 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.99 | 96.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12171.96 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8828.45 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.60 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6870.30 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3305.38 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.54 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.83 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.97 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.49 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9497.50 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4791.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12171.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.805751E+11 | 71282.01 | 02-JAN-14:50 | 0.470765E+10 | 6733.98 | 25-JAN-07:19 |
February | 0.743932E+11 | 72501.70 | 11-FEB-14:39 | 0.426148E+10 | 7601.48 | 04-FEB-06:10 |
March | 0.862061E+11 | 71781.39 | 27-MAR-14:50 | 0.473255E+10 | 11645.21 | 16-MAR-06:10 |
April | 0.856293E+11 | 77382.51 | 14-APR-14:00 | 0.453600E+10 | 1750.00 | 01-APR-00:10 |
May | 0.947947E+11 | 78951.76 | 31-MAY-14:30 | 0.468720E+10 | 1750.00 | 01-MAY-00:10 |
June | 0.978720E+11 | 78960.38 | 08-JUN-14:00 | 0.453600E+10 | 1750.00 | 01-JUN-00:10 |
July | 0.993327E+11 | 81012.96 | 28-JUL-14:50 | 0.468720E+10 | 1750.00 | 01-JUL-00:10 |
August | 0.103327E+12 | 80576.53 | 22-AUG-13:09 | 0.468720E+10 | 1750.00 | 01-AUG-00:10 |
September | 0.971516E+11 | 80802.13 | 20-SEP-14:09 | 0.453600E+10 | 1750.00 | 01-SEP-00:10 |
October | 0.938729E+11 | 79458.66 | 03-OCT-14:30 | 0.468720E+10 | 1750.00 | 01-OCT-00:10 |
November | 0.841556E+11 | 76268.37 | 03-NOV-13:39 | 0.454020E+10 | 3954.21 | 13-NOV-07:30 |
December | 0.820786E+11 | 73992.34 | 08-DEC-14:09 | 0.472454E+10 | 8080.87 | 15-DEC-07:19 |
Annual Sum or Average | 0.107939E+13 | 0.553232E+11 | ||||
Minimum of Months | 0.743932E+11 | 71282.01 | 0.426148E+10 | 1750.00 | ||
Maximum of Months | 0.103327E+12 | 81012.96 | 0.473255E+10 | 11645.21 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.128086E+11 | 0.115358E+11 | 0.00 | 0.516091E+10 | 0.00 | 0.00 | 0.614061E+10 | 0.00 | 0.00 | 0.00 | 0.197858E+10 | 0.00 |
February | 0.393028E+11 | 0.110526E+11 | 0.105871E+11 | 0.00 | 0.476200E+10 | 0.00 | 0.00 | 0.689768E+10 | 0.00 | 0.00 | 0.00 | 0.179094E+10 | 0.00 |
March | 0.453764E+11 | 0.115390E+11 | 0.123431E+11 | 0.00 | 0.562724E+10 | 0.00 | 0.00 | 0.932342E+10 | 0.00 | 0.00 | 0.00 | 0.199698E+10 | 0.00 |
April | 0.425433E+11 | 0.104844E+11 | 0.114862E+11 | 0.00 | 0.585500E+10 | 0.00 | 0.00 | 0.133811E+11 | 0.00 | 0.00 | 0.00 | 0.187933E+10 | 0.00 |
May | 0.441635E+11 | 0.102182E+11 | 0.119357E+11 | 0.00 | 0.732378E+10 | 0.00 | 0.00 | 0.192378E+11 | 0.00 | 0.00 | 0.00 | 0.191570E+10 | 0.00 |
June | 0.437562E+11 | 0.960899E+10 | 0.118862E+11 | 0.00 | 0.861642E+10 | 0.00 | 0.00 | 0.221569E+11 | 0.00 | 0.00 | 0.00 | 0.184733E+10 | 0.00 |
July | 0.429506E+11 | 0.100185E+11 | 0.115358E+11 | 0.00 | 0.909370E+10 | 0.00 | 0.00 | 0.238704E+11 | 0.00 | 0.00 | 0.00 | 0.186364E+10 | 0.00 |
August | 0.453764E+11 | 0.105612E+11 | 0.123357E+11 | 0.00 | 0.919656E+10 | 0.00 | 0.00 | 0.239487E+11 | 0.00 | 0.00 | 0.00 | 0.190800E+10 | 0.00 |
September | 0.425433E+11 | 0.108786E+11 | 0.114788E+11 | 0.00 | 0.848955E+10 | 0.00 | 0.00 | 0.219165E+11 | 0.00 | 0.00 | 0.00 | 0.184482E+10 | 0.00 |
October | 0.429506E+11 | 0.119485E+11 | 0.115432E+11 | 0.00 | 0.713317E+10 | 0.00 | 0.00 | 0.183795E+11 | 0.00 | 0.00 | 0.00 | 0.191788E+10 | 0.00 |
November | 0.413304E+11 | 0.121942E+11 | 0.110862E+11 | 0.00 | 0.534745E+10 | 0.00 | 0.00 | 0.123171E+11 | 0.00 | 0.00 | 0.00 | 0.188019E+10 | 0.00 |
December | 0.429506E+11 | 0.129417E+11 | 0.115358E+11 | 0.00 | 0.524868E+10 | 0.00 | 0.00 | 0.743274E+10 | 0.00 | 0.00 | 0.00 | 0.196907E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134254E+12 | 0.139290E+12 | 0.00 | 0.818545E+11 | 0.00 | 0.00 | 0.185002E+12 | 0.00 | 0.00 | 0.00 | 0.227925E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.960899E+10 | 0.105871E+11 | 0.00 | 0.476200E+10 | 0.00 | 0.00 | 0.614061E+10 | 0.00 | 0.00 | 0.00 | 0.179094E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.129417E+11 | 0.123431E+11 | 0.00 | 0.919656E+10 | 0.00 | 0.00 | 0.239487E+11 | 0.00 | 0.00 | 0.00 | 0.199698E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.470765E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.426148E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.473255E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.454020E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.472454E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.553232E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.426148E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.473255E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5181.25 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5181.25 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5949.68 | 30-MAR-13:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 7486.54 | 10-APR-14:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 7486.54 | 01-MAY-10:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7486.54 | 01-JUN-10:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7486.54 | 20-JUL-11:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7486.54 | 30-AUG-16:49 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7486.54 | 29-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7486.54 | 03-OCT-13:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 7486.54 | 10-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 7486.54 | 08-DEC-14:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 5181.25 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 7486.54 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 16120.91 | 02-JAN-14:50 | 0.00 | 0.00 | 0.00 | 1741.24 | 18-JAN-12:09 | 0.00 |
February | 17362.83 | 11-FEB-14:30 | 0.00 | 0.00 | 0.00 | 1740.41 | 01-FEB-12:50 | 0.00 |
March | 17424.69 | 13-MAR-15:50 | 0.00 | 0.00 | 0.00 | 1735.31 | 01-MAR-12:09 | 0.00 |
April | 21248.79 | 15-APR-15:00 | 0.00 | 0.00 | 0.00 | 1725.04 | 01-APR-11:00 | 0.00 |
May | 23936.04 | 22-MAY-15:50 | 0.00 | 0.00 | 0.00 | 1713.51 | 01-MAY-11:20 | 0.00 |
June | 23961.42 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1702.79 | 01-JUN-11:09 | 0.00 |
July | 26351.46 | 27-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1696.85 | 01-JUL-11:00 | 0.00 |
August | 24874.48 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1701.33 | 31-AUG-11:30 | 0.00 |
September | 24394.17 | 18-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1710.88 | 30-SEP-11:50 | 0.00 |
October | 22525.35 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1722.69 | 31-OCT-11:00 | 0.00 |
November | 18813.61 | 03-NOV-13:39 | 0.00 | 0.00 | 0.00 | 1733.30 | 30-NOV-12:00 | 0.00 |
December | 16546.69 | 08-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1740.00 | 30-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16120.91 | 0.00 | 0.00 | 0.00 | 1696.85 | 0.00 | ||
Maximum of Months | 26351.46 | 0.00 | 0.00 | 0.00 | 1741.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71282.01 | 02-JAN-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 5181.25 | 0.00 | 0.00 | 16120.91 | 0.00 |
February | 72501.70 | 11-FEB-14:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 5181.25 | 0.00 | 0.00 | 17341.27 | 0.00 |
March | 71781.39 | 27-MAR-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 5181.25 | 0.00 | 0.00 | 16604.45 | 0.00 |
April | 77382.51 | 14-APR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 19905.86 | 0.00 |
May | 78951.76 | 31-MAY-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 21489.60 | 0.00 |
June | 78960.38 | 08-JUN-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 21499.74 | 0.00 |
July | 81012.96 | 28-JUL-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 23557.09 | 0.00 |
August | 80576.53 | 22-AUG-13:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 23139.14 | 0.00 |
September | 80802.13 | 20-SEP-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 23336.33 | 0.00 |
October | 79458.66 | 03-OCT-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 21988.90 | 0.00 |
November | 76268.37 | 03-NOV-13:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 18813.61 | 0.00 |
December | 73992.34 | 08-DEC-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 16529.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 71282.01 | 38182.97 | 10112.62 | 0.00 | 0.00 | 5181.25 | 0.00 | 0.00 | 16120.91 | 0.00 | |
Maximum of Months | 81012.96 | 38182.97 | 10112.62 | 0.00 | 0.00 | 7486.54 | 0.00 | 0.00 | 23557.09 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 6733.98 | 25-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7601.48 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 11645.21 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1750.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1750.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1750.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1750.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 3954.21 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8080.87 | 15-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 11645.21 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.55 | 2.17 | 24.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.64 | 4.83 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.02 | 8.17 | 24.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.10 | 8.50 | 25.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.66 | 8.17 | 25.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.27 | 9.00 | 25.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.27 | 8.50 | 25.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.36 | 8.50 | 25.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.67 | 5.17 | 24.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.69 | 2.00 | 24.69 |
Annual Sum or Average | 0.00 | 0.00 | 69.17 | 25.14 | 66.50 | 25.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.66 | 9.00 | 25.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.29 | 0.00 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.41 | 0.00 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.36 | 0.00 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.48 | 0.00 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.46 | 0.00 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 27.48 | 0.00 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.59 | 0.00 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 27.52 | 0.00 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 | 27.50 | 0.00 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 27.45 | 0.00 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.37 | 0.00 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.41 | 0.00 | 27.41 |
Annual Sum or Average | 0.00 | 0.00 | 243.00 | 27.49 | 0.00 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.29 | 0.00 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.59 | 0.00 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.17 | 23.36 | 197.83 | 23.78 | 12.50 | 23.79 |
February | 52.17 | 23.49 | 212.67 | 23.81 | 21.50 | 23.81 |
March | 61.50 | 23.41 | 248.67 | 23.81 | 21.83 | 23.82 |
April | 14.50 | 24.08 | 295.67 | 23.92 | 14.50 | 23.93 |
May | 46.67 | 24.07 | 312.00 | 23.94 | 46.67 | 23.96 |
June | 72.83 | 24.06 | 312.00 | 23.96 | 72.83 | 23.98 |
July | 65.83 | 24.08 | 300.00 | 23.96 | 65.83 | 23.98 |
August | 79.67 | 24.07 | 324.00 | 23.97 | 79.67 | 23.98 |
September | 66.83 | 24.08 | 300.00 | 23.96 | 66.83 | 23.98 |
October | 55.67 | 24.05 | 300.00 | 23.95 | 55.67 | 23.96 |
November | 44.33 | 23.80 | 273.50 | 23.90 | 36.67 | 23.91 |
December | 45.67 | 23.35 | 223.83 | 23.82 | 17.33 | 23.83 |
Annual Sum or Average | 663.83 | 23.83 | 3300.17 | 23.91 | 511.83 | 23.92 |
Minimum of Months | 14.50 | 23.35 | 197.83 | 23.78 | 12.50 | 23.79 |
Maximum of Months | 79.67 | 24.08 | 324.00 | 23.97 | 79.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 158.83 | 26.07 | 264.67 | 26.38 | 133.50 | 26.44 |
February | 200.67 | 26.23 | 252.83 | 26.35 | 186.00 | 26.39 |
March | 242.00 | 26.30 | 295.17 | 26.46 | 220.67 | 26.51 |
April | 274.67 | 26.70 | 300.00 | 26.68 | 274.67 | 26.69 |
May | 311.00 | 26.71 | 312.00 | 26.71 | 311.00 | 26.71 |
June | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
July | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
August | 322.83 | 26.71 | 324.00 | 26.71 | 322.83 | 26.71 |
September | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
October | 297.00 | 26.72 | 300.00 | 26.72 | 297.00 | 26.72 |
November | 257.00 | 26.59 | 280.67 | 26.63 | 250.83 | 26.65 |
December | 177.00 | 26.21 | 274.67 | 26.41 | 158.83 | 26.46 |
Annual Sum or Average | 3153.00 | 26.58 | 3516.00 | 26.62 | 3067.33 | 26.64 |
Minimum of Months | 158.83 | 26.07 | 252.83 | 26.35 | 133.50 | 26.39 |
Maximum of Months | 322.83 | 26.72 | 324.00 | 26.72 | 322.83 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 169.17 | 25.92 | 231.00 | 26.28 | 121.00 | 26.46 |
February | 216.33 | 25.82 | 226.17 | 26.12 | 176.83 | 26.23 |
March | 247.50 | 26.81 | 270.67 | 26.97 | 209.33 | 27.14 |
April | 293.33 | 28.87 | 300.00 | 28.85 | 293.33 | 28.86 |
May | 312.00 | 29.59 | 312.00 | 29.59 | 312.00 | 29.59 |
June | 312.00 | 29.93 | 312.00 | 29.93 | 312.00 | 29.93 |
July | 300.00 | 30.68 | 300.00 | 30.68 | 300.00 | 30.68 |
August | 324.00 | 30.34 | 324.00 | 30.34 | 324.00 | 30.34 |
September | 300.00 | 30.12 | 300.00 | 30.12 | 300.00 | 30.12 |
October | 300.00 | 29.57 | 300.00 | 29.57 | 300.00 | 29.57 |
November | 253.67 | 28.59 | 282.67 | 28.47 | 250.83 | 28.53 |
December | 206.83 | 27.03 | 244.83 | 27.07 | 172.67 | 27.28 |
Annual Sum or Average | 3234.83 | 28.88 | 3403.33 | 28.88 | 3072.00 | 28.98 |
Minimum of Months | 169.17 | 25.82 | 226.17 | 26.12 | 121.00 | 26.23 |
Maximum of Months | 324.00 | 30.68 | 324.00 | 30.68 | 324.00 | 30.68 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.760573E+10 | 0.200567E+10 | 260.93 | 0.586784E+10 | 0.173789E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 34791.64 | 07-JAN-06:01 | 24110.56 | 19-JAN-06:02 | 17501.47 | 07-JAN-06:03 | 7748.72 | 07-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.822714E+10 | 0.217323E+10 | 244.93 | 0.632273E+10 | 0.190441E+10 | 0.00 | 1.00 | 02-FEB-06:02 | 0.00 | 01-FEB-00:10 | 34829.22 | 11-FEB-06:01 | 26374.23 | 28-FEB-06:02 | 17114.67 | 11-FEB-06:04 | 7754.05 | 11-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.104346E+11 | 0.273282E+10 | 292.05 | 0.779535E+10 | 0.263920E+10 | 0.00 | 1.00 | 03-MAR-06:02 | 0.00 | 01-MAR-00:10 | 35185.24 | 14-MAR-05:01 | 23518.88 | 03-MAR-06:02 | 17956.32 | 14-MAR-05:02 | 7796.69 | 14-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.127551E+11 | 0.337939E+10 | 297.04 | 0.956293E+10 | 0.319216E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 35294.39 | 13-APR-05:01 | 26588.33 | 19-APR-05:02 | 16959.64 | 13-APR-05:04 | 7839.40 | 13-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.167298E+11 | 0.447771E+10 | 313.10 | 0.117140E+11 | 0.501575E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 35690.24 | 30-MAY-05:02 | 23577.51 | 08-MAY-05:01 | 19883.04 | 27-MAY-05:03 | 7893.01 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.185373E+11 | 0.493751E+10 | 315.53 | 0.122214E+11 | 0.631597E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 35634.38 | 19-JUN-05:01 | 20553.18 | 17-JUN-05:01 | 18984.78 | 07-JUN-05:04 | 8022.81 | 08-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.189317E+11 | 0.513830E+10 | 316.83 | 0.126755E+11 | 0.625620E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 35786.75 | 24-JUL-05:01 | 20498.38 | 06-JUL-05:01 | 18294.01 | 31-JUL-05:04 | 7971.27 | 14-JUL-05:01 | 0.00 | 01-JUL-00:05 |
August | 0.200435E+11 | 0.538139E+10 | 330.67 | 0.131793E+11 | 0.686430E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 35790.14 | 14-AUG-05:01 | 21357.53 | 30-AUG-05:01 | 19058.34 | 28-AUG-05:06 | 8022.81 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.179824E+11 | 0.480819E+10 | 311.89 | 0.119693E+11 | 0.601305E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 35634.38 | 20-SEP-05:01 | 20559.04 | 05-SEP-05:01 | 19443.32 | 23-SEP-05:06 | 7998.39 | 09-SEP-05:01 | 0.00 | 01-SEP-00:05 |
October | 0.161266E+11 | 0.429331E+10 | 303.31 | 0.110951E+11 | 0.503154E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 35768.51 | 31-OCT-05:01 | 24539.86 | 18-OCT-05:01 | 21069.21 | 04-OCT-05:08 | 7967.69 | 30-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.124941E+11 | 0.328723E+10 | 276.42 | 0.873816E+10 | 0.375590E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 35421.19 | 04-NOV-05:01 | 22446.76 | 28-NOV-06:02 | 19693.46 | 30-NOV-06:05 | 7910.98 | 30-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.852713E+10 | 0.224039E+10 | 268.20 | 0.646305E+10 | 0.206408E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 35207.55 | 11-DEC-06:01 | 24425.88 | 02-DEC-06:01 | 17546.82 | 23-DEC-06:02 | 7856.30 | 09-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.168395E+12 | 0.448551E+11 | 3530.90 | 0.117605E+12 | 0.507904E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.760573E+10 | 0.200567E+10 | 244.93 | 0.586784E+10 | 0.173789E+10 | 0.00 | 1.00 | 0.00 | 34791.64 | 20498.38 | 16959.64 | 7748.72 | 0.00 | |||||||
Maximum of Months | 0.200435E+11 | 0.538139E+10 | 330.67 | 0.131793E+11 | 0.686430E+10 | 0.00 | 1.00 | 0.00 | 35790.14 | 26588.33 | 21069.21 | 8022.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.143442E+11 | 0.413494E+10 | 235.22 | 0.106514E+11 | 0.369284E+10 | 0.00 | 0.53 | 01-JAN-13:25 | 0.00 | 01-JAN-00:10 | 46535.03 | 01-JAN-13:25 | 32827.64 | 01-JAN-13:25 | 17022.41 | 01-JAN-10:03 | 13087.48 | 01-JAN-13:25 | 0.00 | 01-JAN-00:10 |
February | 0.163623E+11 | 0.472445E+10 | 220.78 | 0.122186E+11 | 0.414365E+10 | 0.00 | 1.00 | 19-FEB-14:33 | 0.00 | 01-FEB-00:10 | 95662.98 | 19-FEB-14:33 | 65963.67 | 19-FEB-15:13 | 34039.23 | 19-FEB-13:53 | 24909.48 | 19-FEB-14:33 | 0.00 | 01-FEB-00:10 |
March | 0.230463E+11 | 0.659060E+10 | 285.94 | 0.166342E+11 | 0.641209E+10 | 0.00 | 1.00 | 26-MAR-14:03 | 0.00 | 01-MAR-00:10 | 95866.51 | 26-MAR-14:03 | 64238.19 | 26-MAR-14:03 | 33305.63 | 26-MAR-13:23 | 25129.76 | 26-MAR-14:03 | 0.00 | 01-MAR-00:10 |
April | 0.345671E+11 | 0.100017E+11 | 353.77 | 0.254654E+11 | 0.910170E+10 | 0.00 | 1.00 | 01-APR-17:06 | 0.00 | 01-APR-00:10 | 105449.92 | 12-APR-05:01 | 76864.77 | 09-APR-15:23 | 51649.99 | 12-APR-05:01 | 25632.41 | 12-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.506135E+11 | 0.147601E+11 | 456.37 | 0.345572E+11 | 0.160563E+11 | 0.00 | 1.00 | 03-MAY-17:06 | 0.00 | 01-MAY-00:10 | 105292.85 | 10-MAY-05:07 | 70184.14 | 02-MAY-17:06 | 52261.22 | 10-MAY-05:07 | 26670.77 | 29-MAY-13:13 | 0.00 | 01-MAY-00:10 |
June | 0.590420E+11 | 0.172194E+11 | 524.90 | 0.387734E+11 | 0.202686E+11 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:15 | 105422.60 | 20-JUN-05:01 | 68165.65 | 11-JUN-13:43 | 51880.80 | 20-JUN-05:01 | 26034.24 | 25-JUN-14:13 | 0.00 | 01-JUN-00:10 |
July | 0.631226E+11 | 0.187321E+11 | 557.06 | 0.425984E+11 | 0.205243E+11 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:15 | 102019.28 | 13-JUL-05:07 | 69087.63 | 29-JUL-17:42 | 43992.35 | 13-JUL-05:07 | 26382.50 | 30-JUL-14:43 | 0.00 | 01-JUL-00:05 |
August | 0.632021E+11 | 0.185673E+11 | 556.99 | 0.413892E+11 | 0.218129E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:15 | 105334.93 | 12-AUG-05:01 | 68494.04 | 06-AUG-12:32 | 50681.71 | 12-AUG-05:01 | 26648.24 | 20-AUG-11:43 | 0.00 | 01-AUG-00:10 |
September | 0.584622E+11 | 0.171084E+11 | 516.89 | 0.387486E+11 | 0.197136E+11 | 0.00 | 1.00 | 01-SEP-05:06 | 0.00 | 01-SEP-00:15 | 100498.10 | 29-SEP-05:08 | 67410.95 | 04-SEP-13:53 | 42534.14 | 18-SEP-19:03 | 26202.76 | 18-SEP-18:23 | 0.00 | 01-SEP-00:05 |
October | 0.484102E+11 | 0.140862E+11 | 468.35 | 0.327878E+11 | 0.156224E+11 | 0.00 | 1.00 | 01-OCT-12:03 | 0.00 | 01-OCT-00:15 | 107047.70 | 04-OCT-05:08 | 70287.45 | 15-OCT-15:23 | 57623.79 | 04-OCT-05:08 | 26322.62 | 01-OCT-13:23 | 0.00 | 01-OCT-00:10 |
November | 0.314731E+11 | 0.902987E+10 | 327.63 | 0.212530E+11 | 0.102201E+11 | 0.00 | 1.00 | 05-NOV-13:23 | 0.00 | 01-NOV-00:10 | 101495.00 | 23-NOV-12:03 | 63576.65 | 19-NOV-13:33 | 44656.00 | 23-NOV-12:03 | 25767.31 | 23-NOV-12:03 | 0.00 | 01-NOV-00:10 |
December | 0.181342E+11 | 0.519234E+10 | 257.22 | 0.131331E+11 | 0.500105E+10 | 0.00 | 1.00 | 10-DEC-12:13 | 0.00 | 01-DEC-00:10 | 98575.67 | 10-DEC-12:13 | 62899.95 | 10-DEC-16:13 | 39292.65 | 10-DEC-11:33 | 25585.96 | 10-DEC-12:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.480780E+12 | 0.140147E+12 | 4761.12 | 0.328210E+12 | 0.152569E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.143442E+11 | 0.413494E+10 | 220.78 | 0.106514E+11 | 0.369284E+10 | 0.00 | 0.53 | 0.00 | 46535.03 | 32827.64 | 17022.41 | 13087.48 | 0.00 | |||||||
Maximum of Months | 0.632021E+11 | 0.187321E+11 | 557.06 | 0.425984E+11 | 0.218129E+11 | 0.00 | 1.00 | 0.00 | 107047.70 | 76864.77 | 57623.79 | 26670.77 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.62 | 19.41 | 25.21 | 89.45 | 127.31 | 0.83 | 0.00 | 0.00 |
February | 55.47 | 25.16 | 30.32 | 132.51 | 101.46 | 0.00 | 0.00 | 0.00 |
March | 68.80 | 31.30 | 37.50 | 164.40 | 88.40 | 0.00 | 0.00 | 0.00 |
April | 75.20 | 34.47 | 40.74 | 202.76 | 66.18 | 0.00 | 0.00 | 0.00 |
May | 69.11 | 26.55 | 42.56 | 209.43 | 42.26 | 0.00 | 0.00 | 0.00 |
June | 58.69 | 16.48 | 42.21 | 189.64 | 26.23 | 0.00 | 0.00 | 0.00 |
July | 65.57 | 20.33 | 45.24 | 221.59 | 33.46 | 0.00 | 0.00 | 0.00 |
August | 65.27 | 21.18 | 44.09 | 203.65 | 32.64 | 2.00 | 0.00 | 0.00 |
September | 55.71 | 16.42 | 39.28 | 182.14 | 34.99 | 0.00 | 0.00 | 0.00 |
October | 55.38 | 21.57 | 33.81 | 162.72 | 52.29 | 2.50 | 0.00 | 0.00 |
November | 45.82 | 16.86 | 28.96 | 119.22 | 74.75 | 0.00 | 0.00 | 0.00 |
December | 46.08 | 20.74 | 25.34 | 100.62 | 109.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 22.53 | 36.30 | 165.02 | 65.70 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 44.62 | 16.42 | 25.21 | 89.45 | 26.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.20 | 34.47 | 45.24 | 221.59 | 127.31 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.62 | 19.41 | 25.21 | 89.45 | 127.31 | 0.83 | 0.00 | 0.00 |
February | 55.47 | 25.16 | 30.32 | 132.51 | 101.46 | 0.00 | 0.00 | 0.00 |
March | 68.80 | 31.30 | 37.50 | 164.40 | 88.40 | 0.00 | 0.00 | 0.00 |
April | 75.20 | 34.47 | 40.74 | 202.76 | 66.18 | 0.00 | 0.00 | 0.00 |
May | 69.11 | 26.55 | 42.56 | 209.43 | 42.26 | 0.00 | 0.00 | 0.00 |
June | 58.69 | 16.48 | 42.21 | 189.64 | 26.23 | 0.00 | 0.00 | 0.00 |
July | 65.57 | 20.33 | 45.24 | 221.59 | 33.46 | 0.00 | 0.00 | 0.00 |
August | 65.27 | 21.18 | 44.09 | 203.65 | 32.64 | 2.00 | 0.00 | 0.00 |
September | 55.71 | 16.42 | 39.28 | 182.14 | 34.99 | 0.00 | 0.00 | 0.00 |
October | 55.38 | 21.57 | 33.81 | 162.72 | 52.29 | 2.50 | 0.00 | 0.00 |
November | 45.82 | 16.86 | 28.96 | 119.22 | 74.75 | 0.00 | 0.00 | 0.00 |
December | 46.08 | 20.74 | 25.34 | 100.62 | 109.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.84 | 22.53 | 36.30 | 165.02 | 65.70 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 44.62 | 16.42 | 25.21 | 89.45 | 26.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.20 | 34.47 | 45.24 | 221.59 | 127.31 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.94 | 0.00 | 11.94 | 13.47 | 77.84 | 0.83 | 0.00 | 0.00 |
February | 14.13 | 0.00 | 14.13 | 23.32 | 61.72 | 0.00 | 0.00 | 0.00 |
March | 16.86 | 0.00 | 16.85 | 28.14 | 54.35 | 0.00 | 0.00 | 0.00 |
April | 18.99 | 0.17 | 18.82 | 42.58 | 39.83 | 0.00 | 0.00 | 0.00 |
May | 21.84 | 1.22 | 20.62 | 65.24 | 24.06 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 2.13 | 21.39 | 76.71 | 14.50 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 1.48 | 22.17 | 83.58 | 19.15 | 0.00 | 0.00 | 0.00 |
August | 20.81 | 0.35 | 20.46 | 66.39 | 18.87 | 2.00 | 0.00 | 0.00 |
September | 18.31 | 0.01 | 18.30 | 61.31 | 20.26 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 43.49 | 31.03 | 2.50 | 0.00 | 0.00 |
November | 13.33 | 0.00 | 13.33 | 28.20 | 44.44 | 0.00 | 0.00 | 0.00 |
December | 11.81 | 0.00 | 11.81 | 15.77 | 67.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.56 | 0.45 | 17.11 | 45.80 | 39.40 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 11.81 | 0.00 | 11.81 | 13.47 | 14.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.65 | 2.13 | 22.17 | 83.58 | 77.84 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.94 | 0.00 | 11.94 | 13.47 | 77.83 | 0.83 | 0.00 | 0.00 |
February | 14.13 | 0.00 | 14.13 | 23.32 | 61.72 | 0.00 | 0.00 | 0.00 |
March | 16.86 | 0.00 | 16.85 | 28.14 | 54.35 | 0.00 | 0.00 | 0.00 |
April | 18.99 | 0.17 | 18.82 | 42.58 | 39.83 | 0.00 | 0.00 | 0.00 |
May | 21.84 | 1.22 | 20.62 | 65.24 | 24.06 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 2.13 | 21.38 | 76.71 | 14.50 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 1.48 | 22.17 | 83.58 | 19.14 | 0.00 | 0.00 | 0.00 |
August | 20.81 | 0.35 | 20.46 | 66.39 | 18.87 | 2.00 | 0.00 | 0.00 |
September | 18.31 | 0.01 | 18.30 | 61.31 | 20.26 | 0.00 | 0.00 | 0.00 |
October | 15.33 | 0.00 | 15.33 | 43.49 | 31.03 | 2.50 | 0.00 | 0.00 |
November | 13.33 | 0.00 | 13.33 | 28.20 | 44.44 | 0.00 | 0.00 | 0.00 |
December | 11.81 | 0.00 | 11.81 | 15.77 | 67.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.56 | 0.45 | 17.11 | 45.80 | 39.40 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 11.81 | 0.00 | 11.81 | 13.47 | 14.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.65 | 2.13 | 22.17 | 83.58 | 77.83 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.32 | 26.13 | 17.19 | 66.31 | 56.80 | 33.83 | 0.00 | 0.00 |
February | 52.95 | 32.22 | 20.73 | 87.82 | 45.96 | 9.67 | 0.00 | 0.00 |
March | 66.02 | 40.18 | 25.84 | 108.88 | 42.27 | 4.00 | 0.00 | 0.00 |
April | 76.87 | 47.70 | 29.17 | 129.88 | 41.18 | 5.00 | 0.00 | 0.00 |
May | 75.89 | 42.63 | 33.26 | 132.54 | 31.95 | 0.00 | 0.00 | 0.00 |
June | 72.16 | 35.98 | 36.17 | 127.35 | 26.82 | 5.17 | 0.00 | 0.00 |
July | 78.58 | 41.09 | 37.48 | 141.53 | 29.35 | 0.17 | 0.00 | 0.00 |
August | 71.47 | 35.33 | 36.15 | 120.26 | 30.08 | 7.00 | 0.00 | 0.00 |
September | 63.01 | 30.66 | 32.36 | 111.51 | 30.81 | 6.50 | 0.00 | 0.00 |
October | 55.42 | 30.95 | 24.48 | 92.22 | 41.25 | 10.83 | 0.00 | 0.00 |
November | 44.25 | 23.01 | 21.24 | 71.47 | 45.07 | 14.50 | 0.00 | 0.00 |
December | 39.72 | 21.83 | 17.88 | 61.70 | 50.12 | 25.50 | 0.00 | 0.00 |
Annual Sum or Average | 61.68 | 33.99 | 27.70 | 104.36 | 39.29 | 122.17 | 0.00 | 0.00 |
Minimum of Months | 39.72 | 21.83 | 17.19 | 61.70 | 26.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.58 | 47.70 | 37.48 | 141.53 | 56.80 | 33.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119514E+09 | 51989820.64 | 67524471.88 | 0.239575E+09 | 0.340995E+09 |
February | 0.134200E+09 | 60857118.44 | 73342704.95 | 0.320572E+09 | 0.245455E+09 |
March | 0.184282E+09 | 83838571.27 | 0.100443E+09 | 0.440335E+09 | 0.236761E+09 |
April | 0.194930E+09 | 89339790.75 | 0.105590E+09 | 0.525561E+09 | 0.171550E+09 |
May | 0.185102E+09 | 71103770.22 | 0.113998E+09 | 0.560940E+09 | 0.113193E+09 |
June | 0.152126E+09 | 42716516.55 | 0.109409E+09 | 0.491556E+09 | 68000599.55 |
July | 0.175613E+09 | 54447372.73 | 0.121165E+09 | 0.593515E+09 | 89608591.15 |
August | 0.174829E+09 | 56727446.87 | 0.118102E+09 | 0.545463E+09 | 87435255.98 |
September | 0.144390E+09 | 42573599.93 | 0.101816E+09 | 0.472107E+09 | 90705129.07 |
October | 0.148334E+09 | 57777091.23 | 90557215.98 | 0.435823E+09 | 0.140049E+09 |
November | 0.118770E+09 | 43696238.03 | 75073278.39 | 0.309023E+09 | 0.193754E+09 |
December | 0.123420E+09 | 55560149.66 | 67860092.45 | 0.269499E+09 | 0.294377E+09 |
Annual Sum or Average | 0.185551E+10 | 0.710627E+09 | 0.114488E+10 | 0.520397E+10 | 0.207188E+10 |
Minimum of Months | 0.118770E+09 | 42573599.93 | 67524471.88 | 0.239575E+09 | 68000599.55 |
Maximum of Months | 0.194930E+09 | 89339790.75 | 0.121165E+09 | 0.593515E+09 | 0.340995E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119514E+09 | 51989820.64 | 67524471.88 | 0.239575E+09 | 0.340995E+09 |
February | 0.134200E+09 | 60857118.44 | 73342704.95 | 0.320572E+09 | 0.245455E+09 |
March | 0.184282E+09 | 83838571.27 | 0.100443E+09 | 0.440335E+09 | 0.236761E+09 |
April | 0.194930E+09 | 89339790.75 | 0.105590E+09 | 0.525561E+09 | 0.171550E+09 |
May | 0.185102E+09 | 71103770.22 | 0.113998E+09 | 0.560940E+09 | 0.113193E+09 |
June | 0.152126E+09 | 42716516.55 | 0.109409E+09 | 0.491556E+09 | 68000599.55 |
July | 0.175613E+09 | 54447372.73 | 0.121165E+09 | 0.593515E+09 | 89608591.15 |
August | 0.174829E+09 | 56727446.87 | 0.118102E+09 | 0.545463E+09 | 87435255.98 |
September | 0.144390E+09 | 42573599.93 | 0.101816E+09 | 0.472107E+09 | 90705129.07 |
October | 0.148334E+09 | 57777091.23 | 90557215.98 | 0.435823E+09 | 0.140049E+09 |
November | 0.118770E+09 | 43696238.03 | 75073278.39 | 0.309023E+09 | 0.193754E+09 |
December | 0.123420E+09 | 55560149.66 | 67860092.45 | 0.269499E+09 | 0.294377E+09 |
Annual Sum or Average | 0.185551E+10 | 0.710627E+09 | 0.114488E+10 | 0.520397E+10 | 0.207188E+10 |
Minimum of Months | 0.118770E+09 | 42573599.93 | 67524471.88 | 0.239575E+09 | 68000599.55 |
Maximum of Months | 0.194930E+09 | 89339790.75 | 0.121165E+09 | 0.593515E+09 | 0.340995E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31970577.54 | 0.00 | 31970577.54 | 36075086.16 | 0.208474E+09 |
February | 34180133.89 | 0.00 | 34180133.89 | 56416943.40 | 0.149309E+09 |
March | 45149631.54 | 6085.77 | 45143545.78 | 75366610.25 | 0.145566E+09 |
April | 49225591.75 | 448589.94 | 48777001.81 | 0.110371E+09 | 0.103244E+09 |
May | 58488871.22 | 3271850.94 | 55217020.28 | 0.174746E+09 | 64434242.12 |
June | 60941883.82 | 5510456.11 | 55431427.71 | 0.198839E+09 | 37591808.33 |
July | 63350739.75 | 3962798.65 | 59387941.09 | 0.223872E+09 | 51277970.82 |
August | 55728085.89 | 935564.41 | 54792521.48 | 0.177830E+09 | 50534087.41 |
September | 47458565.99 | 17908.27 | 47440657.72 | 0.158913E+09 | 52516375.79 |
October | 41059420.72 | 0.00 | 41059420.72 | 0.116489E+09 | 83105007.20 |
November | 34549726.50 | 0.00 | 34549726.50 | 73086320.17 | 0.115200E+09 |
December | 31622888.14 | 0.00 | 31622888.14 | 42226964.95 | 0.181290E+09 |
Annual Sum or Average | 0.553726E+09 | 14153254.09 | 0.539573E+09 | 0.144423E+10 | 0.124254E+10 |
Minimum of Months | 31622888.14 | 0.00 | 31622888.14 | 36075086.16 | 37591808.33 |
Maximum of Months | 63350739.75 | 5510456.11 | 59387941.09 | 0.223872E+09 | 0.208474E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31969646.60 | 0.00 | 31969646.60 | 36073802.04 | 0.208472E+09 |
February | 34179156.05 | 0.00 | 34179156.05 | 56415319.63 | 0.149308E+09 |
March | 45148353.52 | 6085.48 | 45142268.04 | 75364240.06 | 0.145565E+09 |
April | 49224220.79 | 448568.91 | 48775651.88 | 0.110368E+09 | 0.103243E+09 |
May | 58487079.46 | 3271697.58 | 55215381.88 | 0.174741E+09 | 64433088.98 |
June | 60939905.25 | 5510197.83 | 55429707.41 | 0.198834E+09 | 37590740.54 |
July | 63348754.24 | 3962612.91 | 59386141.33 | 0.223867E+09 | 51276758.15 |
August | 55726373.33 | 935520.56 | 54790852.77 | 0.177826E+09 | 50533024.28 |
September | 47457114.51 | 17907.43 | 47439207.08 | 0.158910E+09 | 52515215.62 |
October | 41058204.21 | 0.00 | 41058204.21 | 0.116487E+09 | 83103475.61 |
November | 34548666.66 | 0.00 | 34548666.66 | 73084286.28 | 0.115199E+09 |
December | 31621931.21 | 0.00 | 31621931.21 | 42225393.07 | 0.181289E+09 |
Annual Sum or Average | 0.553709E+09 | 14152590.71 | 0.539557E+09 | 0.144420E+10 | 0.124253E+10 |
Minimum of Months | 31621931.21 | 0.00 | 31621931.21 | 36073802.04 | 37590740.54 |
Maximum of Months | 63348754.24 | 5510197.83 | 59386141.33 | 0.223867E+09 | 0.208472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116033E+09 | 69977640.37 | 46054945.05 | 0.177608E+09 | 0.152137E+09 |
February | 0.128104E+09 | 77944018.99 | 50159547.37 | 0.212445E+09 | 0.111193E+09 |
March | 0.176838E+09 | 0.107630E+09 | 69207893.29 | 0.291614E+09 | 0.113229E+09 |
April | 0.199247E+09 | 0.123636E+09 | 75610734.55 | 0.336638E+09 | 0.106737E+09 |
May | 0.203276E+09 | 0.114185E+09 | 89091028.71 | 0.354989E+09 | 85587878.48 |
June | 0.187030E+09 | 93272595.63 | 93757038.58 | 0.330087E+09 | 69522734.13 |
July | 0.210459E+09 | 0.110068E+09 | 0.100391E+09 | 0.379065E+09 | 78617256.81 |
August | 0.191434E+09 | 94615582.86 | 96818565.71 | 0.322102E+09 | 80567981.40 |
September | 0.163334E+09 | 79461652.69 | 83872664.47 | 0.289040E+09 | 79860285.35 |
October | 0.148440E+09 | 82883925.06 | 65555944.74 | 0.246994E+09 | 0.110484E+09 |
November | 0.114702E+09 | 59651294.82 | 55050430.40 | 0.185247E+09 | 0.116821E+09 |
December | 0.106374E+09 | 58482741.07 | 47891290.64 | 0.165265E+09 | 0.134240E+09 |
Annual Sum or Average | 0.194527E+10 | 0.107181E+10 | 0.873461E+09 | 0.329109E+10 | 0.123900E+10 |
Minimum of Months | 0.106374E+09 | 58482741.07 | 46054945.05 | 0.165265E+09 | 69522734.13 |
Maximum of Months | 0.210459E+09 | 0.123636E+09 | 0.100391E+09 | 0.379065E+09 | 0.152137E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 200.05 | 404.52 | 113.12 | 38.82 | 74.29 | 0.00 | 0.00 |
February | 308.59 | 323.29 | 139.20 | 50.31 | 88.89 | 0.00 | 0.00 |
March | 380.52 | 280.92 | 171.32 | 62.61 | 108.71 | 0.00 | 0.00 |
April | 488.34 | 209.69 | 188.39 | 69.28 | 119.11 | 0.00 | 0.00 |
May | 548.40 | 131.69 | 181.89 | 55.54 | 126.35 | 0.00 | 0.00 |
June | 531.42 | 80.19 | 164.40 | 37.21 | 127.19 | 0.00 | 0.00 |
July | 609.68 | 104.53 | 178.44 | 43.62 | 134.82 | 0.00 | 0.00 |
August | 539.82 | 102.75 | 172.16 | 43.06 | 129.10 | 0.00 | 0.00 |
September | 486.75 | 110.36 | 148.03 | 32.86 | 115.17 | 0.00 | 0.00 |
October | 411.60 | 165.81 | 141.42 | 43.14 | 98.28 | 0.00 | 0.00 |
November | 293.60 | 237.15 | 118.30 | 33.72 | 84.59 | 0.00 | 0.00 |
December | 227.95 | 350.37 | 115.77 | 41.49 | 74.29 | 0.00 | 0.00 |
Annual Sum or Average | 419.46 | 208.03 | 152.79 | 45.97 | 106.83 | 0.00 | 0.00 |
Minimum of Months | 200.05 | 80.19 | 113.12 | 32.86 | 74.29 | 0.00 | 0.00 |
Maximum of Months | 609.68 | 404.52 | 188.39 | 69.28 | 134.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2150.69 | 1878.01 | 433.22 | 261.27 | 171.95 | 0.00 | 0.00 |
February | 2883.19 | 1524.50 | 529.53 | 322.19 | 207.34 | 0.00 | 0.00 |
March | 3550.19 | 1422.17 | 660.24 | 401.84 | 258.39 | 0.00 | 0.00 |
April | 5113.77 | 1552.03 | 768.70 | 476.99 | 291.71 | 0.00 | 0.00 |
May | 4984.46 | 1475.74 | 758.94 | 426.32 | 332.63 | 0.00 | 0.00 |
June | 4903.58 | 1503.17 | 721.56 | 359.85 | 361.72 | 0.00 | 0.00 |
July | 5949.76 | 1743.85 | 785.76 | 410.95 | 374.82 | 0.00 | 0.00 |
August | 4600.10 | 1717.08 | 714.73 | 353.25 | 361.48 | 0.00 | 0.00 |
September | 4642.32 | 1672.43 | 630.15 | 306.57 | 323.58 | 0.00 | 0.00 |
October | 3614.97 | 1998.76 | 554.21 | 309.45 | 244.76 | 0.00 | 0.00 |
November | 2645.90 | 1719.54 | 442.52 | 230.14 | 212.39 | 0.00 | 0.00 |
December | 2218.39 | 1703.13 | 397.16 | 218.35 | 178.81 | 0.00 | 0.00 |
Annual Sum or Average | 3942.53 | 1660.83 | 616.84 | 339.87 | 276.97 | 0.00 | 0.00 |
Minimum of Months | 2150.69 | 1422.17 | 397.16 | 218.35 | 171.95 | 0.00 | 0.00 |
Maximum of Months | 5949.76 | 1998.76 | 785.76 | 476.99 | 374.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.535820E+09 | 0.108346E+10 | 0.302969E+09 | 0.103980E+09 | 0.198989E+09 | 0.00 | 0.00 |
February | 0.746547E+09 | 0.782098E+09 | 0.336759E+09 | 0.121714E+09 | 0.215045E+09 | 0.00 | 0.00 |
March | 0.101917E+10 | 0.752426E+09 | 0.458862E+09 | 0.167689E+09 | 0.291173E+09 | 0.00 | 0.00 |
April | 0.126578E+10 | 0.543507E+09 | 0.488310E+09 | 0.179577E+09 | 0.308733E+09 | 0.00 | 0.00 |
May | 0.146883E+10 | 0.352719E+09 | 0.487179E+09 | 0.148751E+09 | 0.338428E+09 | 0.00 | 0.00 |
June | 0.137745E+10 | 0.207850E+09 | 0.426133E+09 | 96453687.04 | 0.329679E+09 | 0.00 | 0.00 |
July | 0.163298E+10 | 0.279980E+09 | 0.477925E+09 | 0.116820E+09 | 0.361105E+09 | 0.00 | 0.00 |
August | 0.144585E+10 | 0.275205E+09 | 0.461113E+09 | 0.115326E+09 | 0.345787E+09 | 0.00 | 0.00 |
September | 0.126165E+10 | 0.286058E+09 | 0.383696E+09 | 85183015.56 | 0.298513E+09 | 0.00 | 0.00 |
October | 0.110242E+10 | 0.444103E+09 | 0.378786E+09 | 0.115554E+09 | 0.263232E+09 | 0.00 | 0.00 |
November | 0.761013E+09 | 0.614704E+09 | 0.306637E+09 | 87392476.06 | 0.219245E+09 | 0.00 | 0.00 |
December | 0.610554E+09 | 0.938437E+09 | 0.310085E+09 | 0.111120E+09 | 0.198965E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132281E+11 | 0.656054E+10 | 0.481845E+10 | 0.144956E+10 | 0.336889E+10 | 0.00 | 0.00 |
Minimum of Months | 0.535820E+09 | 0.207850E+09 | 0.302969E+09 | 85183015.56 | 0.198965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163298E+10 | 0.108346E+10 | 0.488310E+09 | 0.179577E+09 | 0.361105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.576041E+10 | 0.503005E+10 | 0.116033E+10 | 0.699776E+09 | 0.460549E+09 | 0.00 | 0.00 |
February | 0.697501E+10 | 0.368806E+10 | 0.128104E+10 | 0.779440E+09 | 0.501595E+09 | 0.00 | 0.00 |
March | 0.950883E+10 | 0.380913E+10 | 0.176838E+10 | 0.107630E+10 | 0.692079E+09 | 0.00 | 0.00 |
April | 0.132549E+11 | 0.402287E+10 | 0.199247E+10 | 0.123636E+10 | 0.756107E+09 | 0.00 | 0.00 |
May | 0.133504E+11 | 0.395263E+10 | 0.203276E+10 | 0.114185E+10 | 0.890910E+09 | 0.00 | 0.00 |
June | 0.127101E+11 | 0.389621E+10 | 0.187030E+10 | 0.932726E+09 | 0.937570E+09 | 0.00 | 0.00 |
July | 0.159358E+11 | 0.467072E+10 | 0.210459E+10 | 0.110068E+10 | 0.100391E+10 | 0.00 | 0.00 |
August | 0.123209E+11 | 0.459903E+10 | 0.191434E+10 | 0.946156E+09 | 0.968186E+09 | 0.00 | 0.00 |
September | 0.120329E+11 | 0.433493E+10 | 0.163334E+10 | 0.794617E+09 | 0.838727E+09 | 0.00 | 0.00 |
October | 0.968234E+10 | 0.535349E+10 | 0.148440E+10 | 0.828839E+09 | 0.655559E+09 | 0.00 | 0.00 |
November | 0.685818E+10 | 0.445705E+10 | 0.114702E+10 | 0.596513E+09 | 0.550504E+09 | 0.00 | 0.00 |
December | 0.594174E+10 | 0.456167E+10 | 0.106374E+10 | 0.584827E+09 | 0.478913E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.124331E+12 | 0.523759E+11 | 0.194527E+11 | 0.107181E+11 | 0.873461E+10 | 0.00 | 0.00 |
Minimum of Months | 0.576041E+10 | 0.368806E+10 | 0.106374E+10 | 0.584827E+09 | 0.460549E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159358E+11 | 0.535349E+10 | 0.210459E+10 | 0.123636E+10 | 0.100391E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.684818E+09 | -611934894.9 | 0.00 | 0.00 | 744.00 | 0.00 | -72883430.6 | 58.99 | 0.00 | 0.00 |
February | 0.622859E+09 | -556836662.4 | 0.00 | 0.00 | 672.00 | 0.00 | -66022259.1 | 58.99 | 0.00 | 0.00 |
March | 0.702972E+09 | -630605531.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72366863.1 | 58.99 | 0.00 | 0.00 |
April | 0.627188E+09 | -558834429.5 | 0.00 | 0.00 | 720.00 | 0.00 | -68353506.4 | 58.99 | 0.00 | 0.00 |
May | 0.622038E+09 | -552235297.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69802988.9 | 58.98 | 0.00 | 0.00 |
June | 0.595170E+09 | -527950925.2 | 0.00 | 0.00 | 720.00 | 0.00 | -67218643.1 | 58.99 | 0.00 | 0.00 |
July | 0.570135E+09 | -501273068.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68862370.1 | 58.99 | 0.00 | 0.00 |
August | 0.614178E+09 | -544838736.8 | 0.00 | 0.00 | 744.00 | 0.00 | -69339329.6 | 58.98 | 0.00 | 0.00 |
September | 0.592897E+09 | -525948059.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66949222.7 | 58.99 | 0.00 | 0.00 |
October | 0.623904E+09 | -554354528.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69549753.3 | 58.99 | 0.00 | 0.00 |
November | 0.627901E+09 | -559010090.8 | 0.00 | 0.00 | 720.00 | 0.00 | -68891128.8 | 58.99 | 0.00 | 0.00 |
December | 0.675395E+09 | -603011803.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72382917.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.755946E+10 | -0.672683E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -832622413.0 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.570135E+09 | -630605531.7 | 0.00 | 0.00 | 672.00 | 0.00 | -72883430.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.702972E+09 | -501273068.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66022259.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13333944.94 | 3271.84 | 25-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18462785.09 | 16980.81 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29913793.88 | 6664.97 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2711708.77 | 1426.53 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24555047.77 | 4674.82 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88977280.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29913793.88 | 16980.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.760573E+10 | 0.586784E+10 | 34791.64 | 07-JAN-06:01 | 17303.22 | 0.00 |
February | 0.00 | 0.00 | 0.822714E+10 | 0.632273E+10 | 34829.22 | 11-FEB-06:01 | 17755.58 | 0.00 |
March | 0.00 | 0.00 | 0.104346E+11 | 0.779535E+10 | 35185.24 | 14-MAR-05:01 | 17242.15 | 0.00 |
April | 0.00 | 0.00 | 0.127551E+11 | 0.956293E+10 | 35294.39 | 13-APR-05:01 | 18448.30 | 0.00 |
May | 0.00 | 0.00 | 0.167298E+11 | 0.117140E+11 | 35690.24 | 30-MAY-05:02 | 17157.61 | 0.00 |
June | 0.00 | 0.00 | 0.185373E+11 | 0.122214E+11 | 35634.38 | 19-JUN-05:01 | 17329.70 | 0.00 |
July | 0.00 | 0.00 | 0.189317E+11 | 0.126755E+11 | 35786.75 | 24-JUL-05:01 | 18631.98 | 0.00 |
August | 0.00 | 0.00 | 0.200435E+11 | 0.131793E+11 | 35790.14 | 14-AUG-05:01 | 17602.13 | 0.00 |
September | 0.00 | 0.00 | 0.179824E+11 | 0.119693E+11 | 35634.38 | 20-SEP-05:01 | 17662.84 | 0.00 |
October | 0.00 | 0.00 | 0.161266E+11 | 0.110951E+11 | 35768.51 | 31-OCT-05:01 | 17155.36 | 0.00 |
November | 0.00 | 0.00 | 0.124941E+11 | 0.873816E+10 | 35421.19 | 04-NOV-05:01 | 16570.32 | 0.00 |
December | 0.00 | 0.00 | 0.852713E+10 | 0.646305E+10 | 35207.55 | 11-DEC-06:01 | 18403.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168395E+12 | 0.117605E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.760573E+10 | 0.586784E+10 | 34791.64 | 16570.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200435E+11 | 0.131793E+11 | 35790.14 | 18631.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143442E+11 | 0.106514E+11 | 46535.03 | 01-JAN-13:25 | 32827.64 | 0.00 |
February | 0.00 | 0.00 | 0.163623E+11 | 0.122186E+11 | 95662.98 | 19-FEB-14:33 | 64701.46 | 0.00 |
March | 0.00 | 0.00 | 0.230463E+11 | 0.166342E+11 | 95866.51 | 26-MAR-14:03 | 64238.19 | 0.00 |
April | 0.00 | 0.00 | 0.345671E+11 | 0.254654E+11 | 105449.92 | 12-APR-05:01 | 53799.93 | 0.00 |
May | 0.00 | 0.00 | 0.506135E+11 | 0.345572E+11 | 105292.85 | 10-MAY-05:07 | 53031.63 | 0.00 |
June | 0.00 | 0.00 | 0.590420E+11 | 0.387734E+11 | 105422.60 | 20-JUN-05:01 | 53541.80 | 0.00 |
July | 0.00 | 0.00 | 0.631226E+11 | 0.425984E+11 | 102019.28 | 13-JUL-05:07 | 58026.93 | 0.00 |
August | 0.00 | 0.00 | 0.632021E+11 | 0.413892E+11 | 105334.93 | 12-AUG-05:01 | 54653.22 | 0.00 |
September | 0.00 | 0.00 | 0.584622E+11 | 0.387486E+11 | 100498.10 | 29-SEP-05:08 | 60033.56 | 0.00 |
October | 0.00 | 0.00 | 0.484102E+11 | 0.327878E+11 | 107047.70 | 04-OCT-05:08 | 49423.91 | 0.00 |
November | 0.00 | 0.00 | 0.314731E+11 | 0.212530E+11 | 101495.00 | 23-NOV-12:03 | 56839.00 | 0.00 |
December | 0.00 | 0.00 | 0.181342E+11 | 0.131331E+11 | 98575.67 | 10-DEC-12:13 | 59828.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.480780E+12 | 0.328210E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.143442E+11 | 0.106514E+11 | 46535.03 | 32827.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.632021E+11 | 0.425984E+11 | 107047.70 | 64701.46 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148560E+10 | 0.35 | 1490.02 | 04-JAN-08:30 | 0.92 |
February | 0.136780E+10 | 0.36 | 1490.02 | 01-FEB-07:05 | 0.93 |
March | 0.161113E+10 | 0.39 | 1490.02 | 01-MAR-08:10 | 0.93 |
April | 0.150726E+10 | 0.39 | 1490.02 | 01-APR-06:40 | 0.92 |
May | 0.158399E+10 | 0.39 | 1490.02 | 01-MAY-06:15 | 0.92 |
June | 0.159727E+10 | 0.41 | 1490.02 | 08-JUN-16:40 | 0.92 |
July | 0.154737E+10 | 0.40 | 1490.02 | 12-JUL-12:10 | 0.92 |
August | 0.166475E+10 | 0.41 | 1490.02 | 02-AUG-14:50 | 0.92 |
September | 0.154204E+10 | 0.41 | 1490.02 | 01-SEP-15:20 | 0.92 |
October | 0.152813E+10 | 0.38 | 1490.02 | 16-OCT-06:30 | 0.92 |
November | 0.144510E+10 | 0.36 | 1490.02 | 01-NOV-07:20 | 0.92 |
December | 0.149119E+10 | 0.36 | 1490.02 | 04-DEC-07:20 | 0.93 |
Annual Sum or Average | 0.183716E+11 | 0.38 | |||
Minimum of Months | 0.136780E+10 | 0.35 | 1490.02 | 0.92 | |
Maximum of Months | 0.166475E+10 | 0.41 | 1490.02 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.367531E+10 | 0.34 | 3691.23 | 02-JAN-10:00 | 0.89 |
February | 0.339419E+10 | 0.35 | 3691.23 | 01-FEB-10:20 | 0.89 |
March | 0.401519E+10 | 0.39 | 3691.23 | 01-MAR-09:15 | 0.89 |
April | 0.387344E+10 | 0.46 | 3691.23 | 01-APR-07:00 | 0.88 |
May | 0.426618E+10 | 0.57 | 3691.23 | 01-MAY-06:15 | 0.88 |
June | 0.446710E+10 | 0.69 | 3691.23 | 01-JUN-07:35 | 0.88 |
July | 0.446081E+10 | 0.71 | 3691.23 | 01-JUL-07:30 | 0.88 |
August | 0.467627E+10 | 0.71 | 3691.23 | 01-AUG-09:10 | 0.88 |
September | 0.435138E+10 | 0.68 | 3691.23 | 01-SEP-06:50 | 0.88 |
October | 0.413463E+10 | 0.59 | 3691.23 | 02-OCT-07:10 | 0.88 |
November | 0.367564E+10 | 0.43 | 3691.23 | 01-NOV-08:70 | 0.88 |
December | 0.372787E+10 | 0.37 | 3691.23 | 01-DEC-07:30 | 0.89 |
Annual Sum or Average | 0.487180E+11 | 0.52 | |||
Minimum of Months | 0.339419E+10 | 0.34 | 3691.23 | 0.88 | |
Maximum of Months | 0.467627E+10 | 0.71 | 3691.23 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.349127E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.354103E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.434395E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.488665E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.606170E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.653478E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.668567E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.704614E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.635023E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.582144E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.473233E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.373158E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.632268E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.349127E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.704614E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.781025E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.811864E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106058E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138751E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.190262E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.216865E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.231929E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.232435E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.214597E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.182208E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127055E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.892021E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188865E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.781025E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232435E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148560E+10 | 0.760573E+10 | 13333944.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136780E+10 | 0.822714E+10 | 18462785.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161113E+10 | 0.104346E+11 | 29913793.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150726E+10 | 0.127551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158399E+10 | 0.167298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159727E+10 | 0.185373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154737E+10 | 0.189317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166475E+10 | 0.200435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154204E+10 | 0.179824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152813E+10 | 0.161266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144510E+10 | 0.124941E+11 | 2711708.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149119E+10 | 0.852713E+10 | 24555047.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183716E+11 | 0.168395E+12 | 88977280.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136780E+10 | 0.760573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166475E+10 | 0.200435E+11 | 29913793.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.367531E+10 | 0.143442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339419E+10 | 0.163623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401519E+10 | 0.230463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387344E+10 | 0.345671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.426618E+10 | 0.506135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446710E+10 | 0.590420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.446081E+10 | 0.631226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467627E+10 | 0.632021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.435138E+10 | 0.584622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.413463E+10 | 0.484102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367564E+10 | 0.314731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372787E+10 | 0.181342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487180E+11 | 0.480780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339419E+10 | 0.143442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.467627E+10 | 0.632021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148560E+10 | 0.00 | 0.00 | 0.00 | 0.200567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136780E+10 | 0.00 | 0.00 | 0.00 | 0.217323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161113E+10 | 0.00 | 0.00 | 0.00 | 0.273282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150726E+10 | 0.00 | 0.00 | 0.00 | 0.337939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158399E+10 | 0.00 | 0.00 | 0.00 | 0.447771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159727E+10 | 0.00 | 0.00 | 0.00 | 0.493751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154737E+10 | 0.00 | 0.00 | 0.00 | 0.513830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166475E+10 | 0.00 | 0.00 | 0.00 | 0.538139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154204E+10 | 0.00 | 0.00 | 0.00 | 0.480819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152813E+10 | 0.00 | 0.00 | 0.00 | 0.429331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144510E+10 | 0.00 | 0.00 | 0.00 | 0.328723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149119E+10 | 0.00 | 0.00 | 0.00 | 0.224039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183716E+11 | 0.00 | 0.00 | 0.00 | 0.448551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136780E+10 | 0.00 | 0.00 | 0.00 | 0.200567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166475E+10 | 0.00 | 0.00 | 0.00 | 0.538139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.367531E+10 | 0.00 | 0.00 | 0.00 | 0.413494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339419E+10 | 0.00 | 0.00 | 0.00 | 0.472445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401519E+10 | 0.00 | 0.00 | 0.00 | 0.659060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387344E+10 | 0.00 | 0.00 | 0.00 | 0.100017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.426618E+10 | 0.00 | 0.00 | 0.00 | 0.147601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446710E+10 | 0.00 | 0.00 | 0.00 | 0.172194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.446081E+10 | 0.00 | 0.00 | 0.00 | 0.187321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467627E+10 | 0.00 | 0.00 | 0.00 | 0.185673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.435138E+10 | 0.00 | 0.00 | 0.00 | 0.171084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.413463E+10 | 0.00 | 0.00 | 0.00 | 0.140862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367564E+10 | 0.00 | 0.00 | 0.00 | 0.902987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372787E+10 | 0.00 | 0.00 | 0.00 | 0.519234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487180E+11 | 0.00 | 0.00 | 0.00 | 0.140147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339419E+10 | 0.00 | 0.00 | 0.00 | 0.413494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.467627E+10 | 0.00 | 0.00 | 0.00 | 0.187321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 99901567.13 | 0.543606E+09 | 0.00 | 3662723.10 | 0.00 | 11503836.01 | 0.352162E+09 | 0.00 | 0.16 |
February | 69334921.28 | 0.637957E+09 | 0.00 | 2496516.21 | 0.00 | 11782559.81 | 0.147802E+09 | 0.00 | 0.17 |
March | 79457428.78 | 0.862235E+09 | 0.00 | 3529028.39 | 0.00 | 20452334.72 | 0.231962E+09 | 0.00 | 0.18 |
April | 3448956.72 | 0.134426E+10 | 0.00 | 3098945.87 | 0.00 | 0.00 | 39456106.65 | 0.00 | 0.17 |
May | 0.00 | 0.229547E+10 | 0.00 | 2036432.52 | 0.00 | 0.00 | 334641.14 | 0.00 | 0.17 |
June | 0.00 | 0.303996E+10 | 0.00 | 608330.81 | 0.00 | 0.00 | 16813.25 | 0.00 | 0.18 |
July | 0.00 | 0.337826E+10 | 0.00 | 153146.17 | 0.00 | 0.00 | 24925.54 | 0.00 | 0.17 |
August | 0.00 | 0.342988E+10 | 0.00 | 450847.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.300916E+10 | 0.00 | 751615.18 | 0.00 | 0.00 | 125680.76 | 0.00 | 0.18 |
October | 0.00 | 0.237687E+10 | 0.00 | 1204039.50 | 0.00 | 0.00 | 263247.28 | 0.00 | 0.17 |
November | 13211542.02 | 0.160882E+10 | 0.00 | 2752107.33 | 0.00 | 3553490.28 | 21373063.74 | 0.00 | 0.16 |
December | 89460605.52 | 0.701143E+09 | 0.00 | 4021803.91 | 0.00 | 14585711.72 | 0.300095E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.354815E+09 | 0.232276E+11 | 0.00 | 24765536.54 | 0.00 | 61877932.54 | 0.109362E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.543606E+09 | 0.00 | 153146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 99901567.13 | 0.342988E+10 | 0.00 | 4021803.91 | 0.00 | 20452334.72 | 0.352162E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.775728E+09 | 0.684529E+09 | 0.00 | 6932878.45 | 0.00 | 0.00 | 0.138046E+10 | 0.00 | 0.17 |
February | 0.586934E+09 | 0.755121E+09 | 0.00 | 6961301.07 | 0.00 | 0.00 | 0.628281E+09 | 0.00 | 0.17 |
March | 0.674755E+09 | 0.121168E+10 | 0.00 | 6979646.22 | 0.00 | 0.00 | 0.880987E+09 | 0.00 | 0.18 |
April | 56836027.87 | 0.249564E+10 | 0.00 | 5162839.58 | 0.00 | 0.00 | 0.317929E+09 | 0.00 | 0.18 |
May | 1827589.44 | 0.508721E+10 | 0.00 | 660761.48 | 0.00 | 0.00 | 28028481.26 | 0.00 | 0.19 |
June | 0.00 | 0.789536E+10 | 0.00 | 61217.80 | 0.00 | 0.00 | 2279725.37 | 0.00 | 0.21 |
July | 0.00 | 0.937053E+10 | 0.00 | 29643.98 | 0.00 | 0.00 | 135400.65 | 0.00 | 0.20 |
August | 0.00 | 0.907811E+10 | 0.00 | 34442.59 | 0.00 | 0.00 | 383522.54 | 0.00 | 0.21 |
September | 0.00 | 0.788726E+10 | 0.00 | 86258.34 | 0.00 | 0.00 | 2634642.54 | 0.00 | 0.20 |
October | 0.00 | 0.555029E+10 | 0.00 | 771947.93 | 0.00 | 0.00 | 35689357.86 | 0.00 | 0.19 |
November | 0.111303E+09 | 0.321760E+10 | 0.00 | 2930021.93 | 0.00 | 0.00 | 0.281755E+09 | 0.00 | 0.17 |
December | 0.752179E+09 | 0.113571E+10 | 0.00 | 6014447.61 | 0.00 | 0.00 | 0.121190E+10 | 0.00 | 0.17 |
Annual Sum or Average | 0.295956E+10 | 0.543690E+11 | 0.00 | 36625406.97 | 0.00 | 0.00 | 0.477046E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.684529E+09 | 0.00 | 29643.98 | 0.00 | 0.00 | 135400.65 | 0.00 | 0.17 |
Maximum of Months | 0.775728E+09 | 0.937053E+10 | 0.00 | 6979646.22 | 0.00 | 0.00 | 0.138046E+10 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.653204E+12 | 0.388430E+11 | 0.00 | 0.757576E+10 | 0.327838E+11 |
February | 0.712081E+12 | 0.386925E+11 | 0.00 | 0.446364E+10 | 0.357301E+11 |
March | 0.984819E+12 | 0.458173E+11 | 0.00 | 0.356770E+10 | 0.475069E+11 |
April | 0.108315E+13 | 0.379011E+11 | 0.00 | -0.178835E+10 | 0.652392E+11 |
May | 0.106752E+13 | 0.297276E+11 | 0.00 | -0.858641E+10 | 0.912683E+11 |
June | 0.973669E+12 | 0.317203E+11 | 0.00 | -0.148684E+11 | 0.104272E+12 |
July | 0.106934E+13 | 0.357119E+11 | 0.00 | -0.174744E+11 | 0.110612E+12 |
August | 0.111119E+13 | 0.329974E+11 | 0.00 | -0.171010E+11 | 0.111881E+12 |
September | 0.866513E+12 | 0.318108E+11 | 0.00 | -0.149670E+11 | 0.102897E+12 |
October | 0.833862E+12 | 0.302510E+11 | 0.00 | -0.104949E+11 | 0.876035E+11 |
November | 0.621944E+12 | 0.336928E+11 | 0.00 | -0.273588E+10 | 0.608217E+11 |
December | 0.627903E+12 | 0.415906E+11 | 0.00 | 0.498808E+10 | 0.387940E+11 |
Annual Sum or Average | 0.106052E+14 | 0.428756E+12 | 0.00 | -0.674210E+11 | 0.889410E+12 |
Minimum of Months | 0.621944E+12 | 0.297276E+11 | 0.00 | -0.174744E+11 | 0.327838E+11 |
Maximum of Months | 0.111119E+13 | 0.458173E+11 | 0.00 | 0.757576E+10 | 0.111881E+12 |