Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 10:43:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1105.89 | 228.72 | 228.72 |
Net Site Energy | 1105.89 | 228.72 | 228.72 |
Total Source Energy | 3007.81 | 622.07 | 622.07 |
Net Source Energy | 3007.81 | 622.07 | 622.07 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 237.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 868.47 | 237.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 237.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 50.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 237.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 50.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.38 | 49.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 179.62 | 49.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 16.38 | 49.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 179.62 | 49.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 868.473 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 868.473 | 100.00 |
Total On-Site and Utility Electric Sources | 868.473 | 100.00 |
Total Electricity End Uses | 868.473 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 54.17 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2663.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 10-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 116342.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11067.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4077.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1777.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 65217.92 | 116342.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 116342.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 11067.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4077.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1777.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 257.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 423.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2750.45 | 257.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 53.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 568.85 | 53.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 53.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 568.85 | 53.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.02 |
ZONE2 FINE STORAGE DIRECT AIR | 2.66 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.45 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.45 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 58781.82 |
PSZ-OFFICE HEATING COIL | 26945.70 |
PSZ-FINE STORAGE HEATING COIL | 86186.23 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 58781.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-FINE STORAGE | 2.66 | 2.66 | 2.66 | 2.66 | 2.66 | 2.66 | 1.00 | 1.00 | 2.66 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.02 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.66 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.02 | 1168.36 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.66 | 2908.96 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 16963.73 | 26945.70 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.66 | 2.66 | 2.66 | 2.66 | 50512.20 | 86186.23 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.02 | 0.512390 | 1.02 | 16963.73 | 8481.87 | 16963.73 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 2.66 | 1.33 | 2.66 | 50512.20 | 25066.20 | 50512.20 | 0.797230 | 0.797230 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4411 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4411 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4411 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.168 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.168 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.168 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.79006503E-12 | 0.10753925E-15 | -0.21185107E-14 | 0.11481740E-15 |
8 | 3 | -0.38759765E-03 | 0.31085009E-06 | -0.56251641E-04 | 0.15159486E-12 |
9 | 2 | 1.7463592 | 0.67751498E-02 | 1.1456386 | -0.74308999E-04 |
10 | 1 | -7.1196988 | 0.17518393 | -17.131248 | 0.33471089 |
11 | 0 | 5.6672317 | 0.11154516 | 16.279170 | |
12 | 4 | 0.79006503E-12 | 0.10753925E-15 | -0.21185107E-14 | 0.11481740E-15 |
13 | 3 | -0.38759765E-03 | 0.31085009E-06 | -0.56251641E-04 | 0.15159486E-12 |
14 | 2 | 1.7463592 | 0.67751498E-02 | 1.1456386 | -0.74308999E-04 |
15 | 1 | -7.1196988 | 0.17518393 | -17.131248 | 0.33471089 |
16 | 0 | 5.6672317 | 0.11154516 | 16.279170 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.21185107E-14 | 0.10753925E-15 | 0.79006503E-12 | 0.11481740E-15 |
85 | 3 | -0.56251641E-04 | 0.31085009E-06 | -0.38759765E-03 | 0.15159486E-12 |
86 | 2 | 1.1456386 | 0.67751498E-02 | 1.7463592 | -0.74308999E-04 |
87 | 1 | -17.131248 | 0.17518393 | -7.1196988 | 0.33471089 |
88 | 0 | 16.279170 | 0.11154516 | 5.6672317 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5016_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5016_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.852 | 2.852 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.6_SHGC_0.4 | 38 | 1 | VerySmooth | 3.411 | 3.411 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 39 | 1 | VerySmooth | 3.411 | 3.411 | 1.000 | 0.401 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.95586E-002 | 0.31435 | 0.46537 | 0.46537 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10843 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 3.310 | 0.408 | 0.402 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10270.05967 | 12324.07161 | 0.85398 | 1.02478 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 25.24733 | 8.40527E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8722.52123 | 10467.02547 | 0.24735 | 0.29682 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 34169.51162 | 41003.41394 | 2.21482 | 2.65779 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 24876.67746 | 29852.01295 | 0.59452 | 0.71342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.40696E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 48984.85367 | 58781.82440 | 1.20972 | 1.45167 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14801.10 | 1.02478 | 1.02478 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10394.45 | 0.29682 | 0.29682 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 46643.01 | 2.65779 | 2.65779 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 29289.90 | 0.71342 | 0.71342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02478 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.65779 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.45167 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.45167 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 58781.82027 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 58781.82440 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02478 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02478 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02478 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02478 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02478 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.02478 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.65779 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.65779 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.65779 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.65779 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.65779 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.65779 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.02478 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.65779 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02478 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02478 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1168.36086 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02478 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02478 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02478 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02478 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02478 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51239 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02478 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16963.73000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8481.87386 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16963.73000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16963.73000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26945.69793 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26945.69793 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.65779 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.65779 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2908.96432 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.65779 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.65779 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.65779 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.65779 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.65779 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32889 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.65779 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 50512.20000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 25066.20281 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 50512.20000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79723 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79723 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50512.20000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 86186.23153 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 86186.23153 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16168.5 | 9.78 | 9.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 48448.8 | 10.39 | 9.78 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1923849852 | 0.1800695647 | Pass | Pass | 1.5329626019 | 7.9152577500 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3676216043 | 0.3553185010 | Pass | Pass | 0.2386926164 | 0.6362427677 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.2882257263E-005 | 9.5818583798E-005 | Pass | Pass | 5.7689525690E-002 | 4.9622595811E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7392.25 | 443.96 | 0.00 | 100.12 | 147.26 | 8083.65 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.414 | 0.441 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.399 | 0.441 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.399 | 0.441 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.852 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5016_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.852 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.310 | 0.408 | 0.402 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.107 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 6.51 | 2.852 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.54 | 83.54 | 133.80 | |
Exterior Lighting Total | 8532.22 | 133.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16963.73 | 13582.18 | 3381.55 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 50512.20 | 40269.84 | 10242.36 | 0.80 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16168.5 | 9.78 | 9.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 48448.8 | 10.39 | 9.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 58781.82 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26945.70 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 86186.23 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.45 | 134.88 | 92.91 | 1.00 | 3.81 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.02 | 1168.36 | 1140.11 | 1.00 | 1.36 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.66 | 2908.96 | 1094.51 | 1.00 | 1.25 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10270.06 | 12324.07 | 52.03 | 0.854 | 1.025 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 23.90 | 23.90 | 0.00830 | 25.25 | 0.00841 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 34169.51 | 41003.41 | 29.43 | 2.215 | 2.658 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00834 | 26.40 | 0.00841 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 0.00 | 29.45 | 0.00871 | 26.32 | 0.00841 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8722.52 | 10467.03 | 44.19 | 0.247 | 0.297 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00780 | -4.30 | 0.00266 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 24876.68 | 29852.01 | 21.42 | 0.595 | 0.713 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00680 | -4.30 | 0.00266 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 48984.85 | 58781.82 | 18.34 | 1.210 | 1.452 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00588 | -4.30 | 0.00266 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.02 | 1.02 | 0.30 | 0.30 | 1.0248 | 1.0248 | 1.0248 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.66 | 2.66 | 0.71 | 0.71 | 2.6578 | 2.6578 | 2.6578 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 58781.820 | 58781.820 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 58781.82 | 58781.82 | 1.451667 | 10.00 | 7.97 | 0.00588472 | 43.33 | 22.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 10.00 | 0.00588472 | 76.5111 | 58781.82 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16963.730 | 13582.180 | 1.024780 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 16963.73 | 16089.94 | 1.024780 | 25.01 | 16.48 | 0.00831461 | 12.00 | 11.16 | 0.00800000 | 25.37 | 0.00840546 | 16.68 | 11.7425 | 23.90 | 0.00830252 | 44.5016 | 10263.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26945.698 | 26945.698 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26945.70 | 26945.70 | 1.024779 | 18.04 | 12.84 | 0.00719415 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 11.7425 | 21.10 | 0.00779774 | 49.5872 | 8722.52 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 50512.200 | 40269.841 | 2.657790 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 50512.20 | 48065.08 | 2.657790 | 27.56 | 17.38 | 0.00834627 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00840708 | 17.04 | 13.3166 | 26.70 | 0.00833693 | 37.8277 | 34169.51 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 86186.232 | 86186.232 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 86186.23 | 86186.23 | 2.657789 | 12.91 | 9.71 | 0.00625192 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 13.3166 | 15.56 | 0.00680409 | 61.3636 | 24876.68 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 58781.820 | 58781.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.451667 | 1.72947600 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 58781.82 | 58781.82 | 1.0000 | 1.72947600 | 1.451667 | 10.00 | 7.97 | 0.00588472 | 24873.9 | 43.33 | 22.02 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58781.82 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 10.00 | 0.00588472 | 10.00 | 0.00588472 | 76.5111 | 58781.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16963.730 | 13582.180 | 1.024780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2965 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.024779 | 1.22089321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | Sensible | 16963.73 | 16089.94 | 1.0000 | 1.22089421 | 1.024780 | 25.01 | 16.48 | 0.00831461 | 46311.8 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16963.73 | 25.37 | 0.00840546 | 16.68 | 0.12033486 | 11.7425 | 23.90 | 0.00830252 | 23.90 | 0.00830252 | 44.5016 | 10263.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26945.698 | 26945.698 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.024779 | 1.22089321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26945.70 | 26945.70 | 1.0000 | 1.22089321 | 1.024779 | 18.04 | 12.84 | 0.00719415 | 36356.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26945.70 | -4.30 | 0.00265759 | -4.30 | 0.12033486 | 11.7425 | 21.01 | 0.00779774 | 21.10 | 0.00779774 | 49.5872 | 8722.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 50512.200 | 40269.841 | 2.657790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3553 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.657789 | 3.16641506 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 50512.20 | 48065.08 | 1.0000 | 3.16641662 | 2.657790 | 27.56 | 17.38 | 0.00834627 | 48994.2 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50512.20 | 26.40 | 0.00840708 | 17.04 | 0.35392606 | 13.3166 | 26.70 | 0.00833693 | 26.70 | 0.00833693 | 37.8277 | 34169.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 86186.232 | 86186.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.657789 | 3.16641506 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 86186.23 | 86186.23 | 1.0000 | 3.16641506 | 2.657789 | 12.91 | 9.71 | 0.00625192 | 28761.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86186.23 | -4.30 | 0.00265759 | -4.30 | 0.35392606 | 13.3166 | 15.56 | 0.00680409 | 15.56 | 0.00680409 | 61.3636 | 24876.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.12 | 1.02 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.35 | 2.66 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1996.00 | 2922.00 | 1663.17 |
ZONE2 FINE STORAGE | 2808.50 | 2684.00 | 1978.17 |
ZONE3 BULK STORAGE | 2674.83 | 3410.00 | 2553.00 |
Facility | 3441.17 | 3511.83 | 2663.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 52.67 | 0.17 | 49.33 | 0.17 |
ZONE2 FINE STORAGE | 141.67 | 1.00 | 9.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 190.17 | 1.17 | 54.17 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.753 | 0.438 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.506 | 0.244 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.106 | 0.000 | 0.031 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.44 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.30 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2716789.93 | 0.00 | 2716789.93 | 2356288.29 | 5073078.22 | 3794880.16 | 5721.47 | 1952.14 | 1086.39 | 0.00 |
ZONE2 FINE STORAGE | 5344039.57 | 0.00 | 5344039.57 | 6952673.84 | 12296713.41 | 11161412.23 | 5728.28 | 2470.44 | 561.28 | 1.72 |
ZONE3 BULK STORAGE | 0.00 | 9256655.69 | 9256655.69 | 28128604.04 | 37385259.74 | 25671248.14 | 8581.50 | 18.17 | 160.33 | 4172.83 |
Total Facility | 8060829.49 | 9256655.69 | 17317485.19 | 37437566.18 | 54755051.37 | 40627540.53 | 8664.00 | 2505.08 | 1238.67 | 4172.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2076 | 0.0000 | 0.2076 | 0.1215 | 0.3291 | 0.1203 | 597.47 | 1952.14 | 1086.39 |
ZONE2 FINE STORAGE | 0.4075 | 0.0000 | 0.4075 | 0.1980 | 0.6055 | 0.3539 | 605.67 | 2470.44 | 559.89 |
ZONE3 BULK STORAGE | 0.0000 | 0.3089 | 0.3089 | 1.0410 | 1.3499 | 0.8140 | 3534.50 | 8.17 | 93.33 |
Total Facility | 0.6151 | 0.3089 | 0.9240 | 1.3604 | 2.2845 | 1.2883 | 3540.00 | 2495.08 | 1170.28 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3856122.70 | 0.00 | 3856122.70 | 3794880.16 | 5718.72 | 0.00 | 3041.28 | 0.00 |
PSZ-FINE STORAGE | 7585154.85 | 0.00 | 7585154.85 | 11161412.23 | 5728.11 | 0.00 | 3031.89 | 1.72 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2946 | 0.0000 | 0.2946 | 0.1203 | 594.72 | 0.00 | 3041.28 |
PSZ-FINE STORAGE | 0.5784 | 0.0000 | 0.5784 | 0.3539 | 605.67 | 0.00 | 3030.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2256.75 | 788.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2564.67 | 467.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2854 | 0.5421 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5809 | 1.3171 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 868.47 | 5771.67 | 15-JAN-10:50 | 65217.92 | 22-JUL-15:00 |
Electricity:Building | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 348.55 | 2117.83 | 01-JAN-00:10 | 26201.70 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 50.89 | 0.00 | 04-JAN-18:10 | 4212.20 | 02-JAN-07:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
General:Cogeneration:ElectricityPurchased | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
ElectricityNet:Plant | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
General:Cogeneration:ElectricityNet | 868.47 | 5771.67 | 30-APR-16:00 | 65217.92 | 22-JUL-15:00 |
Electricity:HVAC | 52.97 | 0.00 | 04-JAN-18:10 | 15145.00 | 22-JUL-15:00 |
General:Fans:Electricity | 50.89 | 0.00 | 04-JAN-18:10 | 4212.20 | 02-JAN-07:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.08 | 0.00 | 01-JAN-00:10 | 11067.68 | 22-JUL-15:00 |
General:Cooling:Electricity | 2.08 | 0.00 | 01-JAN-00:10 | 11067.68 | 22-JUL-15:00 |
ExteriorLights:Electricity | 133.80 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.80 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 26.22 | 483.00 | 04-APR-05:10 | 2432.77 | 13-FEB-12:20 |
WaterSystems:Electricity | 26.22 | 483.00 | 04-APR-05:10 | 2432.77 | 13-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 26.22 | 483.00 | 04-APR-05:10 | 2432.77 | 13-FEB-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 237.41 | 3250.00 | 23-JUL-12:50 | 116342.37 | 10-JAN-06:10 |
NaturalGas:HVAC | 237.41 | 3250.00 | 23-JUL-12:50 | 116342.37 | 10-JAN-06:10 |
Heating:NaturalGas | 237.41 | 3250.00 | 23-JUL-12:50 | 116342.37 | 10-JAN-06:10 |
General:Heating:NaturalGas | 237.41 | 3250.00 | 23-JUL-12:50 | 116342.37 | 10-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 253.86 | 0.00 | 04-JAN-18:10 | 178609.39 | 10-JAN-06:10 |
EnergyTransfer:Building | 147.31 | 0.00 | 04-JAN-18:10 | 89754.91 | 10-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 35.69 | 0.00 | 01-JAN-00:10 | 18590.62 | 10-JAN-07:10 |
Heating:EnergyTransfer | 100.21 | 0.00 | 04-JAN-18:10 | 89754.91 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 21.28 | 0.00 | 01-JAN-00:10 | 18590.62 | 10-JAN-07:10 |
General:Heating:EnergyTransfer | 100.21 | 0.00 | 04-JAN-18:10 | 89754.91 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 21.28 | 0.00 | 01-JAN-00:10 | 18590.62 | 10-JAN-07:10 |
Cooling:EnergyTransfer | 47.10 | 0.00 | 01-JAN-00:10 | 31251.71 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 14.42 | 0.00 | 01-JAN-00:10 | 8177.10 | 22-JUL-06:00 |
General:Cooling:EnergyTransfer | 47.10 | 0.00 | 01-JAN-00:10 | 31251.71 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 14.42 | 0.00 | 01-JAN-00:10 | 8177.10 | 22-JUL-06:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 69.92 | 0.00 | 01-JAN-00:40 | 31064.82 | 10-JAN-05:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 37.24 | 0.00 | 01-JAN-00:40 | 31064.82 | 10-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 37.24 | 0.00 | 01-JAN-00:40 | 31064.82 | 10-JAN-05:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 32.68 | 0.00 | 01-JAN-00:10 | 25501.79 | 20-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 32.68 | 0.00 | 01-JAN-00:10 | 25501.79 | 20-AUG-14:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 41.70 | 0.00 | 02-JAN-08:10 | 46522.43 | 30-DEC-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 41.70 | 0.00 | 02-JAN-08:10 | 46522.43 | 30-DEC-01:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 41.70 | 0.00 | 02-JAN-08:10 | 46522.43 | 30-DEC-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 106.55 | 0.00 | 04-JAN-18:10 | 88854.48 | 10-JAN-06:10 |
HeatingCoils:EnergyTransfer | 99.39 | 0.00 | 04-JAN-18:10 | 88854.48 | 10-JAN-06:10 |
CoolingCoils:EnergyTransfer | 7.16 | 0.00 | 01-JAN-00:10 | 37304.12 | 22-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 21.278 | -14.416 | 0.000 | 0.000 | 10.020 | 30.293 | 31.946 | 9.307 | 0.000 | 0.031 | 0.000 | 0.000 | -9.912 | 0.000 | -32.409 | -46.137 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 37.235 | -32.685 | 0.000 | 0.000 | 24.174 | 244.699 | 0.000 | 0.000 | 0.000 | 0.017 | 0.000 | 0.000 | 0.000 | 0.000 | -85.634 | -187.805 |
ZONE3 BULK STORAGE | 41.695 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67.737 | 241.203 | 107.344 | 64.250 | 0.000 | 0.364 | 0.000 | 0.000 | -31.487 | 0.000 | -293.803 | -197.301 |
Total Facility | 41.695 | 0.000 | 58.513 | -47.100 | 0.000 | 0.000 | 101.930 | 516.195 | 139.290 | 73.556 | 0.000 | 0.411 | 0.000 | 0.000 | -41.400 | 0.000 | -411.846 | -431.243 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-AUG-05:03 | 0.00 | 0.00 | 0.00 | -19162.43 | 0.00 | 0.00 | 93.86 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 18871.00 | 0.00 | -441.99 | 0.00 | -507.37 | 0.00 |
ZONE2 FINE STORAGE | 25-JUN-16:23 | 0.00 | 0.00 | 0.00 | -52539.34 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 51039.91 | 0.00 | -0.00 | 0.00 | -649.10 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JUN-16:23 | 0.00 | 0.00 | 0.00 | -52539.34 | 0.00 | 0.00 | 0.00 | 4714.92 | 573.75 | 16142.82 | 0.00 | 0.00 | 32773.14 | 0.00 | 0.00 | 0.00 | -1665.30 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:32 | 0.00 | 0.00 | 28512.35 | 0.00 | 0.00 | 0.00 | 136.94 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -562.15 | 0.00 | -918.19 | -28315.88 |
ZONE2 FINE STORAGE | 13-FEB-06:32 | 0.00 | 0.00 | 87343.16 | 0.00 | 0.00 | 0.00 | 362.76 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3732.78 | -86121.66 |
ZONE3 BULK STORAGE | 30-DEC-00:55 | 46522.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3495.37 | 0.00 | -30435.96 | -16759.31 |
Total Facility | 10-JAN-06:01 | 43835.29 | 0.00 | 114098.61 | 0.00 | 0.00 | 0.00 | 1436.22 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4569.95 | 0.00 | -35378.59 | -126884.91 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0248 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.0248 | 0.1174 | 1.0000 | Not calculated | 0.1203 | 0.1174 | ||
PSZ-FINE STORAGE | 2.6578 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 2.6578 | 0.1332 | 1.0000 | Not calculated | 0.3539 | 0.1332 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0248 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.0248 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.1174 | ||
PSZ-FINE STORAGE | 2.6578 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 2.6578 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.1332 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0248 | 1.0248 | 1.0248 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6578 | 2.6578 | 2.6578 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0248 | 1.0248 | 1.0248 | 1.0248 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.6578 | 2.6578 | 2.6578 | 2.6578 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0248 | 1.0248 | 1.0248 | No | 0.1203 | 0.4054 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6578 | 2.6578 | 2.6578 | No | 0.3539 | 0.4961 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0248 | 1.0248 | 1.0248 | 1.0248 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.6578 | 2.6578 | 2.6578 | 2.6578 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 54.17 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 54.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 237.41 | 116342.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2.08 | 11067.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.80 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 50.89 | 4212.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.22 | 2432.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 868.47 |
Natural Gas | 0.00 | 237.41 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1105.89 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 0.43 |
Fans (All) | 10.52 |
Service Water Heating | 5.42 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 179.62 |
Subtotal | 179.62 |
Natural Gas [MJ/m2] | |
Space Heating | 49.10 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 49.10 |
Subtotal | 49.10 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 46.68 |
Space Heating | 21.47 |
Space Cooling | 0.19 |
Fans (All) | 4.60 |
Service Water Heating | 2.37 |
Receptacle Equipment | 12.60 |
Miscellaneous | 12.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8458.17 | 301.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
Min | 8458.17 | 5.33 | 0.00 | 0.00 | 0.00 |
Max | 8754.67 | 301.83 | 0.00 | 0.00 | 0.00 |
Average | 8646.89 | 113.11 | 0.00 | 0.00 | 0.00 |
Sum | 25940.67 | 339.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 75056.50 | 7662.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190906.50 | 286.50 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190906.50 | 7662.50 | 0.00 | 0.00 | 0.00 |
Average | 99663.33 | 2649.67 | 0.00 | 0.00 | 0.00 |
Sum | 298990.00 | 7949.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8323.33 | 436.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
Min | 8323.33 | 19.67 | 0.00 | 0.00 | 0.00 |
Max | 8740.33 | 436.67 | 0.00 | 0.00 | 0.00 |
Average | 8597.94 | 162.06 | 0.00 | 0.00 | 0.00 |
Sum | 25793.83 | 486.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 71819.50 | 10899.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190027.17 | 1165.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190027.17 | 10899.50 | 0.00 | 0.00 | 0.00 |
Average | 98291.22 | 4021.78 | 0.00 | 0.00 | 0.00 |
Sum | 294873.67 | 12065.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94187994.73 | 1273.48 | 21-JAN-17:00 | 4.00 | 3.53 | 0.498838E+09 | 651.62 | 19-JAN-15:00 | 4.00 | 3.53 |
February | 91269605.45 | 1148.30 | 18-FEB-17:00 | 5.00 | 3.23 | 0.458366E+09 | 655.58 | 04-FEB-15:50 | 5.00 | 3.23 |
March | 0.177269E+09 | 1024.92 | 11-MAR-14:00 | 7.00 | 4.66 | 0.543496E+09 | 726.64 | 25-MAR-13:00 | 12.00 | 9.30 |
April | 0.914699E+09 | 5302.10 | 29-APR-15:50 | 20.00 | 12.39 | 0.570182E+09 | 768.98 | 28-APR-15:09 | 20.00 | 12.39 |
May | 0.107341E+10 | 4692.02 | 22-MAY-16:00 | 23.00 | 15.28 | 0.605619E+09 | 769.01 | 22-MAY-14:39 | 23.00 | 15.28 |
June | 0.237465E+10 | 7417.42 | 13-JUN-16:00 | 26.50 | 17.70 | 0.647083E+09 | 769.04 | 12-JUN-15:00 | 26.50 | 17.70 |
July | 0.326301E+10 | 18681.53 | 22-JUL-05:03 | 16.33 | 11.78 | 0.630416E+09 | 769.04 | 26-JUL-14:50 | 19.57 | 15.15 |
August | 0.350604E+10 | 19162.90 | 15-AUG-05:03 | 14.50 | 11.07 | 0.681836E+09 | 769.04 | 19-AUG-15:09 | 20.00 | 15.22 |
September | 0.222943E+10 | 6005.83 | 13-SEP-16:00 | 23.00 | 16.22 | 0.622761E+09 | 769.04 | 13-SEP-15:09 | 23.00 | 16.22 |
October | 0.530782E+09 | 3686.88 | 07-OCT-16:00 | 18.00 | 9.66 | 0.554097E+09 | 768.96 | 07-OCT-15:50 | 18.00 | 9.66 |
November | 0.141048E+09 | 982.94 | 10-NOV-17:00 | 7.00 | 6.47 | 0.483830E+09 | 724.64 | 10-NOV-15:50 | 7.00 | 6.47 |
December | 19778260.79 | 690.31 | 02-DEC-13:30 | 9.00 | 7.93 | 0.497272E+09 | 620.93 | 02-DEC-14:30 | 9.00 | 7.93 |
Annual Sum or Average | 0.144156E+11 | 0.679380E+10 | ||||||||
Minimum of Months | 19778260.79 | 690.31 | 4.00 | 3.23 | 0.458366E+09 | 620.93 | 4.00 | 3.23 | ||
Maximum of Months | 0.350604E+10 | 19162.90 | 26.50 | 17.70 | 0.681836E+09 | 769.04 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188674E+10 | 5230.80 | 11-JAN-14:00 | -2.0 | -3.5 | 0.824721E+09 | 1365.26 | 19-JAN-15:20 | 8.67 | 7.45 |
February | 0.181277E+10 | 4231.74 | 17-FEB-09:20 | 1.67 | 1.12 | 0.795073E+09 | 1319.57 | 04-FEB-14:50 | 1.67 | 1.12 |
March | 0.193150E+10 | 4260.62 | 15-MAR-12:10 | 1.17 | 0.82 | 0.100736E+10 | 1536.79 | 25-MAR-12:30 | 13.00 | 10.05 |
April | 0.219414E+10 | 47969.63 | 30-APR-15:25 | 24.00 | 13.13 | 0.134484E+10 | 2246.79 | 27-APR-15:39 | 24.00 | 13.13 |
May | 0.224886E+10 | 8469.78 | 25-MAY-15:00 | 17.00 | 13.49 | 0.145974E+10 | 2246.82 | 22-MAY-15:09 | 17.00 | 13.49 |
June | 0.382483E+10 | 52539.80 | 25-JUN-16:23 | 23.00 | 14.48 | 0.175428E+10 | 2246.97 | 13-JUN-13:39 | 23.00 | 14.48 |
July | 0.630513E+10 | 51039.59 | 23-JUL-12:41 | 21.83 | 16.36 | 0.177256E+10 | 2246.93 | 10-JUL-15:09 | 21.83 | 16.36 |
August | 0.589764E+10 | 51003.58 | 20-AUG-14:05 | 23.00 | 14.82 | 0.193853E+10 | 2246.95 | 17-AUG-13:20 | 23.00 | 14.82 |
September | 0.241944E+10 | 12583.46 | 13-SEP-14:40 | 23.00 | 16.22 | 0.166807E+10 | 2246.90 | 13-SEP-14:50 | 23.00 | 16.22 |
October | 0.125982E+10 | 3970.93 | 06-OCT-07:10 | 3.83 | 3.69 | 0.118429E+10 | 2161.20 | 07-OCT-15:09 | 18.83 | 10.03 |
November | 0.134402E+10 | 3608.15 | 17-NOV-09:15 | 4.00 | 2.46 | 0.866697E+09 | 1534.77 | 10-NOV-14:20 | 4.00 | 2.46 |
December | 0.155950E+10 | 3922.31 | 06-DEC-09:10 | 2.33 | 1.83 | 0.775686E+09 | 1197.57 | 21-DEC-14:39 | 8.00 | 6.98 |
Annual Sum or Average | 0.326844E+11 | 0.153918E+11 | ||||||||
Minimum of Months | 0.125982E+10 | 3608.15 | -2.0 | -3.5 | 0.775686E+09 | 1197.57 | 1.67 | 1.12 | ||
Maximum of Months | 0.630513E+10 | 52539.80 | 24.00 | 16.36 | 0.193853E+10 | 2246.97 | 24.00 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.877913E+09 | 1414.01 | 19-JAN-15:39 | 8.33 | 7.46 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 5.79 | 0.841258E+09 | 1384.11 | 04-FEB-14:50 | 9.00 | 6.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 | 0.117345E+10 | 1866.15 | 25-MAR-13:20 | 13.33 | 10.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.84 | 0.188649E+10 | 3713.23 | 29-APR-15:30 | 20.00 | 12.54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.216145E+10 | 3445.00 | 23-MAY-14:39 | 18.33 | 14.52 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.39 | 0.285419E+10 | 4603.79 | 26-JUN-15:20 | 22.67 | 17.34 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.328929E+10 | 5537.97 | 22-JUL-15:30 | 29.00 | 16.79 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.367671E+10 | 4858.52 | 21-AUG-13:50 | 21.00 | 14.91 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.282652E+10 | 4289.82 | 13-SEP-15:09 | 23.00 | 16.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.83 | 0.182333E+10 | 3188.04 | 07-OCT-15:30 | 18.50 | 9.89 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.29 | 0.106748E+10 | 1885.06 | 10-NOV-14:50 | 12.00 | 8.50 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.785870E+09 | 1217.99 | 02-DEC-14:30 | 9.00 | 7.93 |
Annual Sum or Average | 0.00 | 0.232640E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.785870E+09 | 1217.99 | 8.33 | 6.50 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.367671E+10 | 5537.97 | 29.00 | 17.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409090E+10 | 28512.41 | 02-JAN-06:32 | 1.67 |
February | 0.322661E+10 | 28492.06 | 13-FEB-06:32 | -1.0 |
March | 0.300054E+10 | 27374.39 | 13-MAR-05:12 | 2.07 |
April | 0.950690E+09 | 27294.94 | 11-APR-05:42 | 5.17 |
May | 0.797184E+09 | 27252.21 | 05-MAY-05:01 | 6.00 |
June | 0.193910E+09 | 26738.93 | 08-JUN-05:02 | 6.17 |
July | 0.115462E+09 | 26242.42 | 05-JUL-05:02 | 7.33 |
August | 0.102831E+09 | 1663.93 | 30-AUG-06:15 | 10.00 |
September | 0.222372E+09 | 17459.85 | 07-SEP-05:03 | 8.83 |
October | 0.116903E+10 | 27264.61 | 23-OCT-05:01 | 3.17 |
November | 0.284205E+10 | 27433.41 | 27-NOV-06:12 | 4.00 |
December | 0.456675E+10 | 27515.49 | 26-DEC-06:12 | 1.93 |
Annual Sum or Average | 0.212783E+11 | |||
Minimum of Months | 0.102831E+09 | 1663.93 | -1.0 | |
Maximum of Months | 0.456675E+10 | 28512.41 | 10.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831908E+10 | 86815.01 | 10-JAN-06:01 | -4.0 |
February | 0.698551E+10 | 87343.01 | 13-FEB-06:32 | -1.0 |
March | 0.259560E+10 | 83350.45 | 04-MAR-06:01 | 3.00 |
April | 0.197316E+09 | 13899.09 | 01-APR-04:55 | 2.00 |
May | 0.210486E+09 | 3143.89 | 05-MAY-07:00 | 7.00 |
June | 0.202828E+09 | 3029.86 | 22-JUN-07:00 | 12.00 |
July | 0.192830E+09 | 3044.24 | 11-JUL-07:00 | 13.00 |
August | 0.211590E+09 | 2869.12 | 19-AUG-07:00 | 12.00 |
September | 0.205231E+09 | 2979.48 | 27-SEP-07:00 | 10.00 |
October | 0.280073E+09 | 35228.17 | 23-OCT-05:40 | 3.67 |
November | 0.478233E+10 | 86822.97 | 28-NOV-06:01 | 1.00 |
December | 0.130525E+11 | 86854.72 | 29-DEC-22:42 | -2.7 |
Annual Sum or Average | 0.372353E+11 | |||
Minimum of Months | 0.192830E+09 | 2869.12 | -4.0 | |
Maximum of Months | 0.130525E+11 | 87343.01 | 13.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123799E+11 | 45887.74 | 10-JAN-05:52 | -4.0 |
February | 0.558635E+10 | 29923.00 | 19-FEB-21:53 | 0.00 |
March | 0.197897E+09 | 11893.79 | 04-MAR-05:53 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.206166E+10 | 27451.01 | 29-NOV-03:55 | -1.0 |
December | 0.214692E+11 | 46523.01 | 30-DEC-00:55 | -2.0 |
Annual Sum or Average | 0.416951E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.214692E+11 | 46523.01 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281367E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277157E+10 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270754E+10 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222213E+10 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4355.34 | 0.342254E+10 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7890085.18 | 0.272662E+10 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17054415.62 | 0.234244E+10 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5556155.92 | 0.208125E+10 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212838E+10 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249146E+10 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300740E+10 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369359E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30505012.06 | 0.324086E+11 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208125E+10 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17054415.62 | 0.369359E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387959E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543765E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377850E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487044E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114275E+11 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185666.78 | 0.101478E+11 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15787945.25 | 0.941526E+10 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631440.58 | 0.793381E+10 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724011E+10 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577975E+10 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651330E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921045E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16605052.61 | 0.856342E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377850E+10 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15787945.25 | 0.114275E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16707006.72 | 0.888219E+10 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118687E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866028E+10 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22839635.95 | 0.126614E+11 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53081095.53 | 0.306929E+11 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77985510.31 | 0.271783E+11 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60345149.39 | 0.275980E+11 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14838754.42 | 0.238536E+11 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2619486.95 | 0.205658E+11 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158345E+11 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19724759.75 | 0.141861E+11 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6843410.01 | 0.185164E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274985E+09 | 0.220498E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866028E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77985510.31 | 0.306929E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 11785.18 | 10-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9547.45 | 24-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9222.43 | 31-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 7307.38 | 11-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 22-MAY-15:00 | 8488.74 | 01-MAY-16:03 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1294.62 | 13-JUN-17:00 | 6692.07 | 08-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1994.26 | 21-JUL-17:00 | 5172.26 | 05-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.79 | 14-AUG-17:00 | 5163.49 | 24-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6529.39 | 20-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7928.53 | 04-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10324.53 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10659.23 | 28-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5163.49 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1994.26 | 11785.18 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 12927.04 | 10-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 10224.32 | 01-FEB-16:05 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 13035.69 | 31-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 11242.78 | 24-APR-15:05 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 20953.02 | 01-MAY-15:03 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.78 | 13-JUN-17:00 | 15004.15 | 07-JUN-15:03 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.36 | 22-JUL-15:10 | 9993.72 | 30-JUL-19:00 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.88 | 14-AUG-17:27 | 13356.40 | 22-AUG-16:00 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 15546.27 | 29-SEP-15:05 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12686.46 | 20-OCT-15:05 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12827.90 | 18-NOV-16:05 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 18987.54 | 02-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9993.72 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.36 | 20953.02 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.94 | 29-JAN-06:00 | 31530.05 | 10-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 19614.65 | 01-FEB-16:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 30604.66 | 31-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.18 | 30-APR-19:00 | 22914.82 | 24-APR-12:05 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3547.09 | 22-MAY-15:00 | 50350.69 | 01-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3910.72 | 13-JUN-16:00 | 33622.54 | 07-JUN-15:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2715.76 | 22-JUL-19:00 | 28268.55 | 01-JUL-12:10 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2256.12 | 14-AUG-18:00 | 31683.63 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.55 | 24-SEP-16:00 | 27369.60 | 19-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 24213.95 | 01-OCT-24:00 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4940.03 | 24-NOV-12:00 | 21960.87 | 03-NOV-07:10 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4273.94 | 23-DEC-11:00 | 28970.67 | 02-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19614.65 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4940.03 | 50350.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1273.48 | 21-JAN-17:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1148.30 | 18-FEB-17:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.17 |
March | 1024.92 | 11-MAR-14:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5302.10 | 29-APR-15:50 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 |
May | 4692.02 | 22-MAY-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.81 |
June | 7417.42 | 13-JUN-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 400.52 | 0.00 |
July | 18681.53 | 22-JUL-05:03 | 739.61 | 2292.70 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.19 |
August | 19162.90 | 15-AUG-05:03 | 554.70 | 1719.53 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.37 |
September | 6005.83 | 13-SEP-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.79 |
October | 3686.88 | 07-OCT-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 982.94 | 10-NOV-17:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.11 |
December | 690.31 | 02-DEC-13:30 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 690.31 | 554.70 | 1719.53 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19162.90 | 1680.92 | 2292.70 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.52 | 811.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5230.80 | 11-JAN-14:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.37 |
February | 4231.74 | 17-FEB-09:20 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4260.62 | 15-MAR-12:10 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47969.63 | 30-APR-15:25 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.49 |
May | 8469.78 | 25-MAY-15:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.64 |
June | 52539.80 | 25-JUN-16:23 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.10 |
July | 51039.59 | 23-JUL-12:41 | 0.00 | 19336.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.59 |
August | 51003.58 | 20-AUG-14:05 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.94 |
September | 12583.46 | 13-SEP-14:40 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.45 |
October | 3970.93 | 06-OCT-07:10 | 3955.50 | 16113.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3608.15 | 17-NOV-09:15 | 7911.00 | 36524.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.69 |
December | 3922.31 | 06-DEC-09:10 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3608.15 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52539.80 | 7911.00 | 36524.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 6353.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3957.55 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4043.46 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4950.37 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9691.95 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11507.50 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20232.20 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9439.85 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11367.48 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16163.24 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6995.65 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3191.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 6353.50 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20232.20 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.758565E+11 | 58425.58 | 07-JAN-08:09 | 0.424225E+11 | 116342.37 | 10-JAN-06:10 |
February | 0.680559E+11 | 54282.21 | 11-FEB-13:00 | 0.299172E+11 | 73164.91 | 24-FEB-06:10 |
March | 0.762341E+11 | 54273.93 | 02-MAR-13:39 | 0.175144E+11 | 54358.79 | 04-MAR-06:10 |
April | 0.699878E+11 | 55074.81 | 29-APR-14:00 | 0.977895E+10 | 22797.30 | 01-APR-05:10 |
May | 0.711719E+11 | 56955.85 | 22-MAY-14:00 | 0.976081E+10 | 17334.21 | 05-MAY-05:10 |
June | 0.699845E+11 | 62700.14 | 13-JUN-14:00 | 0.855745E+10 | 11395.60 | 08-JUN-05:10 |
July | 0.697207E+11 | 65217.92 | 22-JUL-14:00 | 0.874056E+10 | 9934.63 | 05-JUL-05:10 |
August | 0.742461E+11 | 60555.43 | 14-AUG-14:30 | 0.870480E+10 | 3250.00 | 01-AUG-00:10 |
September | 0.709773E+11 | 58545.68 | 13-SEP-14:00 | 0.860128E+10 | 10021.39 | 05-SEP-06:10 |
October | 0.733855E+11 | 54308.83 | 07-OCT-14:00 | 0.104621E+11 | 25752.39 | 23-OCT-05:10 |
November | 0.723600E+11 | 58253.42 | 30-NOV-16:30 | 0.222560E+11 | 81068.67 | 28-NOV-06:10 |
December | 0.764928E+11 | 58424.49 | 27-DEC-08:09 | 0.606976E+11 | 102938.13 | 28-DEC-06:49 |
Annual Sum or Average | 0.868473E+12 | 0.237414E+12 | ||||
Minimum of Months | 0.680559E+11 | 54273.93 | 0.855745E+10 | 3250.00 | ||
Maximum of Months | 0.764928E+11 | 65217.92 | 0.606976E+11 | 116342.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.146259E+11 | 0.115358E+11 | 0.00 | 0.449493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224919E+10 | 0.00 |
February | 0.393028E+11 | 0.120355E+11 | 0.105871E+11 | 0.00 | 0.407992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205058E+10 | 0.00 |
March | 0.453764E+11 | 0.117130E+11 | 0.123431E+11 | 0.00 | 0.448962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231197E+10 | 0.00 |
April | 0.425433E+11 | 0.970625E+10 | 0.114862E+11 | 0.00 | 0.405040E+10 | 0.00 | 0.00 | 21075416.70 | 0.00 | 0.00 | 0.00 | 0.218058E+10 | 0.00 |
May | 0.441635E+11 | 0.860048E+10 | 0.119357E+11 | 0.00 | 0.420823E+10 | 0.00 | 0.00 | 28746864.77 | 0.00 | 0.00 | 0.00 | 0.223518E+10 | 0.00 |
June | 0.437562E+11 | 0.756125E+10 | 0.118862E+11 | 0.00 | 0.420363E+10 | 0.00 | 0.00 | 0.417215E+09 | 0.00 | 0.00 | 0.00 | 0.216010E+10 | 0.00 |
July | 0.429506E+11 | 0.814998E+10 | 0.115358E+11 | 0.00 | 0.405343E+10 | 0.00 | 0.00 | 0.872342E+09 | 0.00 | 0.00 | 0.00 | 0.215851E+10 | 0.00 |
August | 0.453764E+11 | 0.939397E+10 | 0.123357E+11 | 0.00 | 0.436254E+10 | 0.00 | 0.00 | 0.567621E+09 | 0.00 | 0.00 | 0.00 | 0.220986E+10 | 0.00 |
September | 0.425433E+11 | 0.106277E+11 | 0.114788E+11 | 0.00 | 0.403728E+10 | 0.00 | 0.00 | 0.176391E+09 | 0.00 | 0.00 | 0.00 | 0.211380E+10 | 0.00 |
October | 0.429506E+11 | 0.126550E+11 | 0.115432E+11 | 0.00 | 0.405389E+10 | 0.00 | 0.00 | 241416.64 | 0.00 | 0.00 | 0.00 | 0.218254E+10 | 0.00 |
November | 0.413304E+11 | 0.137096E+11 | 0.110862E+11 | 0.00 | 0.410178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213201E+10 | 0.00 |
December | 0.429506E+11 | 0.150201E+11 | 0.115358E+11 | 0.00 | 0.475320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223305E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.133799E+12 | 0.139290E+12 | 0.00 | 0.508889E+11 | 0.00 | 0.00 | 0.208363E+10 | 0.00 | 0.00 | 0.00 | 0.262174E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.756125E+10 | 0.105871E+11 | 0.00 | 0.403728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205058E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.150201E+11 | 0.123431E+11 | 0.00 | 0.475320E+10 | 0.00 | 0.00 | 0.872342E+09 | 0.00 | 0.00 | 0.00 | 0.231197E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.424225E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.299172E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.175144E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.977895E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.976081E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.855745E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.874056E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.870480E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.860128E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104621E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.222560E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.606976E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237414E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.855745E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.606976E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4212.20 | 02-JAN-07:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4212.20 | 13-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4077.33 | 07-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4077.33 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4077.33 | 22-MAY-14:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4077.33 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 4077.33 | 10-JUL-08:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 4077.33 | 05-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4077.33 | 12-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4077.33 | 02-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4212.20 | 27-NOV-07:49 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4212.20 | 04-DEC-07:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 4077.33 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 4212.20 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2425.80 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2432.77 | 13-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2424.57 | 02-MAR-12:00 | 0.00 |
April | 6267.63 | 30-APR-15:30 | 0.00 | 0.00 | 0.00 | 2367.01 | 01-APR-11:09 | 0.00 |
May | 2790.02 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2257.75 | 03-MAY-11:30 | 0.00 |
June | 8855.74 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2129.12 | 02-JUN-11:09 | 0.00 |
July | 11067.68 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 2005.20 | 06-JUL-11:00 | 0.00 |
August | 7068.04 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1949.36 | 02-AUG-11:00 | 0.00 |
September | 4395.02 | 13-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2017.88 | 30-SEP-11:00 | 0.00 |
October | 153.01 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2126.51 | 28-OCT-11:39 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2240.26 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2365.82 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1949.36 | 0.00 | ||
Maximum of Months | 11067.68 | 0.00 | 0.00 | 0.00 | 2432.77 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58425.58 | 07-JAN-08:09 | 33916.61 | 10112.62 | 8532.22 | 0.00 | 4212.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54282.21 | 11-FEB-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54273.93 | 02-MAR-13:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55074.81 | 29-APR-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 901.66 | 0.00 |
May | 56955.85 | 22-MAY-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 2790.02 | 0.00 |
June | 62700.14 | 13-JUN-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 8810.08 | 0.00 |
July | 65217.92 | 22-JUL-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 11067.68 | 0.00 |
August | 60555.43 | 14-AUG-14:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 6406.84 | 0.00 |
September | 58545.68 | 13-SEP-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 4395.02 | 0.00 |
October | 54308.83 | 07-OCT-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 153.01 | 0.00 |
November | 58253.42 | 30-NOV-16:30 | 33916.61 | 10112.62 | 8532.22 | 0.00 | 4077.33 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58424.49 | 27-DEC-08:09 | 33916.61 | 10112.62 | 8532.22 | 0.00 | 4212.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 54273.93 | 33916.61 | 10112.62 | 0.00 | 0.00 | 4077.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65217.92 | 38182.97 | 10112.62 | 8532.22 | 0.00 | 4212.20 | 0.00 | 0.00 | 11067.68 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 116342.37 | 10-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 73164.91 | 24-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 54358.79 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 22797.30 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 17334.21 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 11395.60 | 08-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 9934.63 | 05-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10021.39 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 25752.39 | 23-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 81068.67 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 102938.13 | 28-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 3250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 116342.37 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 19.29 | 8.50 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
February | 8.00 | 19.62 | 7.67 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
March | 8.50 | 20.05 | 8.50 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
April | 2.67 | 20.32 | 2.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
May | 2.33 | 20.40 | 2.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
June | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
July | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
September | 0.17 | 20.40 | 0.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
October | 3.00 | 20.30 | 3.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
November | 8.00 | 19.59 | 7.50 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
December | 10.17 | 18.85 | 8.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Annual Sum or Average | 52.67 | 19.59 | 49.33 | 19.74 | 0.17 | 19.75 | 0.17 | 19.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 0.00 | 19.15 |
Maximum of Months | 10.17 | 20.53 | 8.67 | 20.53 | 0.17 | 24.48 | 0.17 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.33 | 14.77 | 2.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
February | 26.17 | 14.87 | 1.33 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
March | 5.33 | 14.97 | 0.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.00 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.00 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
November | 20.67 | 14.84 | 1.17 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
December | 58.00 | 14.76 | 4.33 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
Annual Sum or Average | 141.67 | 14.80 | 9.00 | 14.80 | 1.00 | 14.88 | 0.00 | 14.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.00 | 14.97 | 4.33 | 14.97 | 0.67 | 27.35 | 0.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.09 | 292.83 | 21.08 | 292.83 | 21.08 |
February | 276.00 | 21.08 | 272.17 | 21.08 | 272.17 | 21.07 |
March | 324.00 | 21.18 | 297.17 | 21.14 | 297.17 | 21.12 |
April | 292.17 | 22.34 | 97.83 | 22.04 | 97.83 | 21.86 |
May | 288.67 | 22.48 | 52.83 | 22.30 | 48.67 | 22.14 |
June | 174.83 | 23.08 | 54.67 | 23.23 | 4.00 | 23.19 |
July | 98.00 | 23.28 | 126.17 | 23.62 | 0.67 | 23.61 |
August | 90.17 | 23.29 | 125.00 | 23.64 | 0.00 | 23.64 |
September | 190.17 | 23.14 | 27.83 | 23.23 | 0.33 | 23.23 |
October | 300.00 | 22.09 | 101.83 | 21.84 | 101.83 | 21.69 |
November | 288.00 | 21.18 | 247.67 | 21.13 | 247.67 | 21.11 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 2922.00 | 21.86 | 1996.00 | 21.74 | 1663.17 | 21.57 |
Minimum of Months | 90.17 | 21.05 | 27.83 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 324.00 | 23.29 | 300.00 | 23.64 | 300.00 | 23.64 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 17.30 | 300.00 | 17.30 | 300.00 | 17.30 |
February | 276.00 | 17.68 | 276.00 | 17.68 | 276.00 | 17.68 |
March | 324.00 | 18.35 | 319.33 | 18.32 | 319.33 | 18.31 |
April | 249.00 | 21.21 | 145.50 | 21.12 | 108.17 | 20.69 |
May | 238.67 | 21.50 | 124.67 | 21.78 | 67.50 | 21.34 |
June | 116.00 | 23.04 | 202.83 | 24.86 | 25.50 | 24.76 |
July | 116.50 | 24.90 | 234.00 | 25.85 | 68.50 | 25.91 |
August | 84.83 | 24.41 | 256.17 | 26.00 | 32.83 | 26.06 |
September | 101.83 | 22.25 | 185.67 | 24.43 | 18.83 | 24.14 |
October | 289.17 | 20.49 | 182.33 | 19.99 | 179.50 | 19.74 |
November | 288.00 | 18.05 | 282.00 | 18.01 | 282.00 | 18.00 |
December | 300.00 | 16.80 | 300.00 | 16.80 | 300.00 | 16.80 |
Annual Sum or Average | 2684.00 | 19.56 | 2808.50 | 20.18 | 1978.17 | 19.71 |
Minimum of Months | 84.83 | 16.80 | 124.67 | 16.80 | 18.83 | 16.80 |
Maximum of Months | 324.00 | 24.90 | 319.33 | 26.00 | 319.33 | 26.06 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.57 | 300.00 | 11.57 | 300.00 | 11.57 |
February | 276.00 | 11.79 | 276.00 | 11.79 | 276.00 | 11.79 |
March | 324.00 | 12.91 | 324.00 | 12.91 | 324.00 | 12.91 |
April | 300.00 | 17.16 | 279.67 | 17.00 | 279.67 | 16.95 |
May | 312.00 | 18.13 | 276.83 | 17.95 | 276.83 | 17.88 |
June | 302.50 | 20.86 | 113.33 | 20.38 | 109.00 | 20.07 |
July | 203.67 | 22.06 | 85.00 | 22.62 | 22.00 | 22.39 |
August | 203.83 | 22.74 | 54.50 | 23.26 | 0.00 | 23.26 |
September | 300.00 | 21.32 | 77.50 | 20.89 | 77.50 | 20.60 |
October | 300.00 | 16.94 | 300.00 | 16.94 | 300.00 | 16.94 |
November | 288.00 | 13.07 | 288.00 | 13.07 | 288.00 | 13.07 |
December | 300.00 | 10.95 | 300.00 | 10.95 | 300.00 | 10.95 |
Annual Sum or Average | 3410.00 | 16.33 | 2674.83 | 15.68 | 2553.00 | 15.28 |
Minimum of Months | 203.67 | 10.95 | 54.50 | 10.95 | 0.00 | 10.95 |
Maximum of Months | 324.00 | 22.74 | 324.00 | 23.26 | 324.00 | 23.26 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 57278781.70 | 17314840.25 | 10.17 | 56480720.97 | 798060.74 | 0.00 | 0.22 | 29-APR-15:50 | 0.00 | 01-APR-00:10 | 3080.90 | 29-APR-15:50 | 3080.90 | 29-APR-15:50 | 191.06 | 28-APR-15:00 | 923.52 | 29-APR-15:50 | 0.00 | 01-APR-00:10 |
May | 89212294.93 | 26517868.08 | 13.33 | 78393268.45 | 10819026.48 | 0.00 | 0.40 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 6267.66 | 22-MAY-15:00 | 5684.07 | 22-MAY-15:00 | 583.59 | 22-MAY-15:00 | 1822.81 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.667551E+09 | 0.195391E+09 | 51.00 | 0.553111E+09 | 0.114441E+09 | 0.00 | 0.62 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 10085.18 | 13-JUN-16:00 | 8961.10 | 13-JUN-16:00 | 2333.09 | 26-JUN-16:00 | 2945.88 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.126526E+10 | 0.376135E+09 | 93.44 | 0.109306E+10 | 0.172204E+09 | 0.00 | 1.00 | 18-JUL-05:03 | 0.00 | 01-JUL-00:10 | 16938.12 | 18-JUL-05:03 | 14173.46 | 22-JUL-05:55 | 6831.46 | 24-JUL-05:03 | 4457.03 | 18-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.125248E+10 | 0.371823E+09 | 137.31 | 0.102913E+10 | 0.223354E+09 | 0.00 | 1.00 | 15-AUG-05:03 | 0.00 | 01-AUG-00:10 | 15605.02 | 15-AUG-05:03 | 13413.09 | 15-AUG-05:03 | 2191.93 | 15-AUG-05:03 | 4108.16 | 15-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 0.500508E+09 | 0.148644E+09 | 57.83 | 0.437803E+09 | 62705141.00 | 0.00 | 0.47 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 | 7457.02 | 13-SEP-16:00 | 6384.71 | 13-SEP-16:00 | 1328.35 | 12-SEP-14:00 | 2140.04 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 782319.43 | 241416.64 | 1.83 | 782316.07 | 3.37 | 0.00 | 0.04 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 496.80 | 07-OCT-15:00 | 496.80 | 07-OCT-15:00 | 0.00 | 11-OCT-10:30 | 153.01 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.383308E+10 | 0.113607E+10 | 364.92 | 0.324875E+10 | 0.584321E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.126526E+10 | 0.376135E+09 | 137.31 | 0.109306E+10 | 0.223354E+09 | 0.00 | 1.00 | 0.00 | 16938.12 | 14173.46 | 6831.46 | 4457.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 14926808.40 | 3760576.44 | 0.08 | 14926808.40 | 0.00 | 0.00 | 1.00 | 30-APR-15:25 | 0.00 | 01-APR-00:10 | 49756.03 | 30-APR-15:25 | 49756.03 | 30-APR-15:25 | 0.00 | 30-APR-15:25 | 12535.25 | 30-APR-15:25 | 0.00 | 01-APR-00:10 |
May | 7630715.63 | 2228996.69 | 1.33 | 7079328.88 | 551386.75 | 0.00 | 0.07 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3319.27 | 22-MAY-15:00 | 3097.25 | 22-MAY-15:00 | 222.02 | 22-MAY-15:00 | 967.21 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.786774E+09 | 0.221824E+09 | 22.90 | 0.687308E+09 | 99466237.47 | 0.00 | 1.00 | 13-JUN-17:11 | 0.00 | 01-JUN-00:10 | 53114.04 | 13-JUN-17:51 | 50988.78 | 25-JUN-15:05 | 5278.86 | 13-JUN-18:00 | 13615.40 | 13-JUN-17:11 | 0.00 | 01-JUN-00:10 |
July | 0.173387E+10 | 0.496207E+09 | 43.45 | 0.164865E+10 | 85221115.97 | 0.00 | 1.00 | 21-JUL-17:11 | 0.00 | 01-JUL-00:10 | 53537.11 | 23-JUL-15:51 | 51556.33 | 21-JUL-17:27 | 12474.25 | 23-JUL-17:15 | 13520.58 | 21-JUL-17:11 | 0.00 | 01-JUL-00:10 |
August | 0.684371E+09 | 0.195799E+09 | 35.31 | 0.608973E+09 | 75398030.20 | 0.00 | 1.00 | 14-AUG-17:23 | 0.00 | 01-AUG-00:10 | 50864.08 | 20-AUG-15:25 | 50864.08 | 20-AUG-15:25 | 2472.15 | 17-AUG-14:20 | 13303.06 | 14-AUG-17:23 | 0.00 | 01-AUG-00:10 |
September | 96143655.49 | 27747064.68 | 9.50 | 83311600.02 | 12832055.47 | 0.00 | 0.18 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 | 8176.12 | 13-SEP-14:30 | 7110.82 | 13-SEP-14:40 | 1065.43 | 13-SEP-14:30 | 2338.60 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.332372E+10 | 0.947567E+09 | 112.58 | 0.305025E+10 | 0.273469E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.173387E+10 | 0.496207E+09 | 43.45 | 0.164865E+10 | 99466237.47 | 0.00 | 1.00 | 0.00 | 53537.11 | 51556.33 | 12474.25 | 13615.40 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.33 | 15.46 | 31.87 | 30.06 | 131.45 | 0.00 | 0.00 | 0.00 |
February | 83.73 | 35.57 | 48.17 | 68.22 | 123.59 | 0.00 | 0.00 | 0.00 |
March | 75.46 | 14.51 | 60.96 | 48.49 | 99.77 | 0.00 | 0.00 | 0.00 |
April | 177.57 | 70.35 | 107.22 | 183.08 | 92.02 | 0.00 | 0.00 | 0.00 |
May | 208.27 | 84.44 | 123.83 | 210.90 | 79.43 | 0.00 | 0.00 | 0.00 |
June | 225.34 | 92.98 | 132.36 | 241.23 | 69.50 | 0.00 | 0.00 | 0.00 |
July | 229.51 | 101.25 | 128.26 | 255.09 | 67.95 | 0.00 | 0.00 | 0.00 |
August | 192.62 | 83.31 | 109.31 | 215.02 | 75.97 | 0.00 | 0.00 | 0.00 |
September | 155.91 | 70.47 | 85.44 | 168.22 | 91.29 | 0.00 | 0.00 | 0.00 |
October | 82.79 | 29.87 | 52.92 | 71.83 | 104.13 | 0.00 | 0.00 | 0.00 |
November | 44.81 | 13.19 | 31.62 | 28.28 | 117.43 | 0.00 | 0.00 | 0.00 |
December | 25.17 | 5.24 | 19.93 | 9.43 | 148.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.18 | 51.40 | 77.77 | 127.67 | 99.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.17 | 5.24 | 19.93 | 9.43 | 67.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.51 | 101.25 | 132.36 | 255.09 | 148.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.33 | 15.46 | 31.87 | 30.06 | 131.45 | 0.00 | 0.00 | 0.00 |
February | 83.73 | 35.57 | 48.17 | 68.22 | 123.59 | 0.00 | 0.00 | 0.00 |
March | 75.46 | 14.51 | 60.96 | 48.49 | 99.77 | 0.00 | 0.00 | 0.00 |
April | 177.57 | 70.35 | 107.22 | 183.08 | 92.02 | 0.00 | 0.00 | 0.00 |
May | 208.27 | 84.44 | 123.83 | 210.90 | 79.43 | 0.00 | 0.00 | 0.00 |
June | 225.34 | 92.98 | 132.36 | 241.23 | 69.50 | 0.00 | 0.00 | 0.00 |
July | 229.51 | 101.25 | 128.26 | 255.09 | 67.95 | 0.00 | 0.00 | 0.00 |
August | 192.62 | 83.31 | 109.31 | 215.02 | 75.97 | 0.00 | 0.00 | 0.00 |
September | 155.91 | 70.47 | 85.44 | 168.22 | 91.29 | 0.00 | 0.00 | 0.00 |
October | 82.79 | 29.87 | 52.92 | 71.83 | 104.13 | 0.00 | 0.00 | 0.00 |
November | 44.81 | 13.19 | 31.62 | 28.28 | 117.43 | 0.00 | 0.00 | 0.00 |
December | 25.17 | 5.24 | 19.93 | 9.43 | 148.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129.18 | 51.40 | 77.77 | 127.67 | 99.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.17 | 5.24 | 19.93 | 9.43 | 67.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.51 | 101.25 | 132.36 | 255.09 | 148.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.81 | 0.00 | 13.81 | 1.34 | 80.90 | 0.00 | 0.00 | 0.00 |
February | 21.57 | 0.00 | 21.57 | 3.51 | 75.05 | 0.00 | 0.00 | 0.00 |
March | 29.85 | 0.00 | 29.85 | 10.87 | 60.58 | 0.00 | 0.00 | 0.00 |
April | 48.67 | 0.26 | 48.40 | 30.02 | 53.94 | 0.00 | 0.00 | 0.00 |
May | 61.02 | 3.16 | 57.87 | 37.46 | 43.77 | 0.00 | 0.00 | 0.00 |
June | 66.99 | 4.10 | 62.89 | 50.36 | 38.40 | 0.00 | 0.00 | 0.00 |
July | 63.68 | 3.60 | 60.08 | 49.80 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 50.31 | 0.97 | 49.34 | 37.68 | 43.00 | 0.00 | 0.00 | 0.00 |
September | 38.14 | 0.02 | 38.12 | 24.70 | 54.31 | 0.00 | 0.00 | 0.00 |
October | 24.43 | 0.00 | 24.43 | 9.37 | 62.02 | 0.00 | 0.00 | 0.00 |
November | 14.68 | 0.00 | 14.68 | 1.77 | 70.22 | 0.00 | 0.00 | 0.00 |
December | 9.99 | 0.00 | 9.99 | 0.12 | 87.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 1.02 | 35.98 | 21.50 | 58.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.99 | 0.00 | 9.99 | 0.12 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.99 | 4.10 | 62.89 | 50.36 | 87.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.81 | 0.00 | 13.81 | 1.34 | 80.90 | 0.00 | 0.00 | 0.00 |
February | 21.57 | 0.00 | 21.57 | 3.51 | 75.05 | 0.00 | 0.00 | 0.00 |
March | 29.85 | 0.00 | 29.85 | 10.87 | 60.58 | 0.00 | 0.00 | 0.00 |
April | 48.67 | 0.26 | 48.40 | 30.02 | 53.94 | 0.00 | 0.00 | 0.00 |
May | 61.02 | 3.16 | 57.87 | 37.45 | 43.77 | 0.00 | 0.00 | 0.00 |
June | 66.98 | 4.10 | 62.89 | 50.36 | 38.40 | 0.00 | 0.00 | 0.00 |
July | 63.68 | 3.60 | 60.08 | 49.80 | 37.33 | 0.00 | 0.00 | 0.00 |
August | 50.31 | 0.97 | 49.34 | 37.67 | 43.00 | 0.00 | 0.00 | 0.00 |
September | 38.14 | 0.02 | 38.12 | 24.69 | 54.31 | 0.00 | 0.00 | 0.00 |
October | 24.42 | 0.00 | 24.42 | 9.37 | 62.02 | 0.00 | 0.00 | 0.00 |
November | 14.68 | 0.00 | 14.68 | 1.77 | 70.22 | 0.00 | 0.00 | 0.00 |
December | 9.99 | 0.00 | 9.99 | 0.12 | 87.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 1.02 | 35.98 | 21.50 | 58.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.99 | 0.00 | 9.99 | 0.12 | 37.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.98 | 4.10 | 62.89 | 50.36 | 87.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.23 | 3.42 | 10.81 | 12.48 | 29.65 | 89.17 | 0.00 | 0.00 |
February | 25.11 | 8.36 | 16.75 | 25.14 | 28.67 | 7.83 | 0.00 | 0.00 |
March | 32.39 | 6.02 | 26.37 | 33.12 | 23.24 | 6.50 | 0.00 | 0.00 |
April | 79.13 | 42.37 | 36.76 | 93.83 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 95.46 | 53.03 | 42.42 | 109.74 | 23.95 | 0.00 | 0.00 | 0.00 |
June | 101.77 | 55.24 | 46.54 | 119.00 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 103.23 | 60.43 | 42.80 | 120.57 | 23.31 | 0.00 | 0.00 | 0.00 |
August | 88.67 | 53.69 | 34.98 | 103.17 | 28.20 | 0.00 | 0.00 | 0.00 |
September | 64.32 | 38.04 | 26.28 | 73.83 | 31.87 | 0.00 | 0.00 | 0.00 |
October | 32.64 | 13.93 | 18.71 | 33.16 | 31.00 | 14.33 | 0.00 | 0.00 |
November | 15.73 | 4.16 | 11.58 | 13.46 | 27.28 | 16.17 | 0.00 | 0.00 |
December | 9.93 | 2.09 | 7.85 | 6.84 | 31.21 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 55.36 | 28.49 | 26.87 | 62.19 | 27.16 | 135.67 | 0.00 | 0.00 |
Minimum of Months | 9.93 | 2.09 | 7.85 | 6.84 | 21.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.23 | 60.43 | 46.54 | 120.57 | 31.87 | 89.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126781E+09 | 41421035.00 | 85359724.23 | 80516195.48 | 0.352066E+09 |
February | 0.202565E+09 | 86042013.35 | 0.116523E+09 | 0.165047E+09 | 0.298989E+09 |
March | 0.202120E+09 | 38851759.88 | 0.163269E+09 | 0.129864E+09 | 0.267235E+09 |
April | 0.460258E+09 | 0.182350E+09 | 0.277908E+09 | 0.474544E+09 | 0.238519E+09 |
May | 0.557831E+09 | 0.226153E+09 | 0.331678E+09 | 0.564863E+09 | 0.212744E+09 |
June | 0.584093E+09 | 0.241003E+09 | 0.343090E+09 | 0.625271E+09 | 0.180132E+09 |
July | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.683236E+09 | 0.181989E+09 |
August | 0.515907E+09 | 0.223125E+09 | 0.292783E+09 | 0.575907E+09 | 0.203465E+09 |
September | 0.404128E+09 | 0.182659E+09 | 0.221469E+09 | 0.436020E+09 | 0.236627E+09 |
October | 0.221745E+09 | 79998991.38 | 0.141746E+09 | 0.192382E+09 | 0.278902E+09 |
November | 0.116157E+09 | 34196504.77 | 81960929.17 | 73310461.55 | 0.304370E+09 |
December | 67413167.84 | 14032114.69 | 53381053.14 | 25248752.12 | 0.396733E+09 |
Annual Sum or Average | 0.407371E+10 | 0.162102E+10 | 0.245269E+10 | 0.402621E+10 | 0.315177E+10 |
Minimum of Months | 67413167.84 | 14032114.69 | 53381053.14 | 25248752.12 | 0.180132E+09 |
Maximum of Months | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.683236E+09 | 0.396733E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126781E+09 | 41421035.00 | 85359724.23 | 80516195.48 | 0.352066E+09 |
February | 0.202565E+09 | 86042013.35 | 0.116523E+09 | 0.165047E+09 | 0.298989E+09 |
March | 0.202120E+09 | 38851759.88 | 0.163269E+09 | 0.129864E+09 | 0.267235E+09 |
April | 0.460258E+09 | 0.182350E+09 | 0.277908E+09 | 0.474544E+09 | 0.238519E+09 |
May | 0.557831E+09 | 0.226153E+09 | 0.331678E+09 | 0.564863E+09 | 0.212744E+09 |
June | 0.584093E+09 | 0.241003E+09 | 0.343090E+09 | 0.625271E+09 | 0.180132E+09 |
July | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.683236E+09 | 0.181989E+09 |
August | 0.515907E+09 | 0.223125E+09 | 0.292783E+09 | 0.575907E+09 | 0.203465E+09 |
September | 0.404128E+09 | 0.182659E+09 | 0.221469E+09 | 0.436020E+09 | 0.236627E+09 |
October | 0.221745E+09 | 79998991.38 | 0.141746E+09 | 0.192382E+09 | 0.278902E+09 |
November | 0.116157E+09 | 34196504.77 | 81960929.17 | 73310461.55 | 0.304370E+09 |
December | 67413167.84 | 14032114.69 | 53381053.14 | 25248752.12 | 0.396733E+09 |
Annual Sum or Average | 0.407371E+10 | 0.162102E+10 | 0.245269E+10 | 0.402621E+10 | 0.315177E+10 |
Minimum of Months | 67413167.84 | 14032114.69 | 53381053.14 | 25248752.12 | 0.180132E+09 |
Maximum of Months | 0.614712E+09 | 0.271188E+09 | 0.343524E+09 | 0.683236E+09 | 0.396733E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36996128.09 | 0.00 | 36996128.09 | 3589133.80 | 0.216682E+09 |
February | 52180276.64 | 0.00 | 52180276.64 | 8497667.88 | 0.181571E+09 |
March | 79953231.58 | 1133.24 | 79952098.34 | 29105775.39 | 0.162266E+09 |
April | 0.126147E+09 | 682750.86 | 0.125465E+09 | 77813141.10 | 0.139813E+09 |
May | 0.163449E+09 | 8457423.59 | 0.154992E+09 | 0.100320E+09 | 0.117231E+09 |
June | 0.173628E+09 | 10620006.69 | 0.163008E+09 | 0.130527E+09 | 99536379.59 |
July | 0.170570E+09 | 9645341.69 | 0.160924E+09 | 0.133384E+09 | 99991680.29 |
August | 0.134754E+09 | 2610657.95 | 0.132144E+09 | 0.100910E+09 | 0.115160E+09 |
September | 98871495.97 | 59436.37 | 98812059.59 | 64011511.93 | 0.140776E+09 |
October | 65420331.74 | 0.00 | 65420331.74 | 25087227.58 | 0.166117E+09 |
November | 38039882.33 | 0.00 | 38039882.33 | 4589782.81 | 0.181998E+09 |
December | 26768561.36 | 0.00 | 26768561.36 | 327865.13 | 0.234336E+09 |
Annual Sum or Average | 0.116678E+10 | 32076750.38 | 0.113470E+10 | 0.678163E+09 | 0.185548E+10 |
Minimum of Months | 26768561.36 | 0.00 | 26768561.36 | 327865.13 | 99536379.59 |
Maximum of Months | 0.173628E+09 | 10620006.69 | 0.163008E+09 | 0.133384E+09 | 0.234336E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36994860.08 | 0.00 | 36994860.08 | 3588671.13 | 0.216682E+09 |
February | 52178534.12 | 0.00 | 52178534.12 | 8496580.42 | 0.181571E+09 |
March | 79950383.50 | 1133.19 | 79949250.31 | 29103139.45 | 0.162267E+09 |
April | 0.126144E+09 | 682718.86 | 0.125461E+09 | 77809009.62 | 0.139813E+09 |
May | 0.163444E+09 | 8457027.18 | 0.154987E+09 | 0.100314E+09 | 0.117230E+09 |
June | 0.173622E+09 | 10619508.92 | 0.163003E+09 | 0.130520E+09 | 99536166.67 |
July | 0.170564E+09 | 9644889.59 | 0.160919E+09 | 0.133378E+09 | 99991340.30 |
August | 0.134750E+09 | 2610535.58 | 0.132140E+09 | 0.100906E+09 | 0.115160E+09 |
September | 98868606.10 | 59433.59 | 98809172.51 | 64008621.96 | 0.140775E+09 |
October | 65418197.57 | 0.00 | 65418197.57 | 25085419.52 | 0.166116E+09 |
November | 38038575.26 | 0.00 | 38038575.26 | 4589081.19 | 0.181998E+09 |
December | 26767629.89 | 0.00 | 26767629.89 | 327766.66 | 0.234336E+09 |
Annual Sum or Average | 0.116674E+10 | 32075246.90 | 0.113467E+10 | 0.678126E+09 | 0.185548E+10 |
Minimum of Months | 26767629.89 | 0.00 | 26767629.89 | 327766.66 | 99536166.67 |
Maximum of Months | 0.173622E+09 | 10619508.92 | 0.163003E+09 | 0.133378E+09 | 0.234336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38122911.18 | 9158667.57 | 28964243.61 | 33415641.85 | 79423151.81 |
February | 60737526.01 | 20217935.88 | 40519590.13 | 60815846.66 | 69349271.56 |
March | 86755048.50 | 16125708.18 | 70629340.32 | 88702766.82 | 62255369.62 |
April | 0.205113E+09 | 0.109832E+09 | 95281336.97 | 0.243199E+09 | 68615082.95 |
May | 0.255667E+09 | 0.142038E+09 | 0.113630E+09 | 0.293939E+09 | 64158317.10 |
June | 0.263795E+09 | 0.143169E+09 | 0.120625E+09 | 0.308449E+09 | 54959245.96 |
July | 0.276496E+09 | 0.161866E+09 | 0.114630E+09 | 0.322944E+09 | 62432897.90 |
August | 0.237507E+09 | 0.143807E+09 | 93699903.42 | 0.276321E+09 | 75527992.66 |
September | 0.166718E+09 | 98596545.09 | 68121653.13 | 0.191368E+09 | 82616954.27 |
October | 87415581.68 | 37308257.86 | 50107323.82 | 88826610.09 | 83026418.89 |
November | 40779815.95 | 10775198.78 | 30004617.17 | 34898075.21 | 70708083.45 |
December | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 83580814.63 |
Annual Sum or Average | 0.174572E+10 | 0.898480E+09 | 0.847237E+09 | 0.196120E+10 | 0.856654E+09 |
Minimum of Months | 26608974.51 | 5585236.76 | 21023737.75 | 18315746.00 | 54959245.96 |
Maximum of Months | 0.276496E+09 | 0.161866E+09 | 0.120625E+09 | 0.322944E+09 | 83580814.63 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 56.34 | 418.23 | 122.29 | 30.93 | 91.36 | 0.00 | 0.00 |
February | 138.47 | 392.28 | 210.60 | 71.13 | 139.47 | 0.00 | 0.00 |
March | 115.42 | 317.43 | 210.63 | 29.01 | 181.62 | 0.00 | 0.00 |
April | 423.80 | 289.52 | 452.47 | 141.23 | 311.24 | 0.00 | 0.00 |
May | 493.76 | 243.46 | 538.59 | 175.19 | 363.40 | 0.00 | 0.00 |
June | 579.84 | 212.46 | 584.66 | 194.15 | 390.51 | 0.00 | 0.00 |
July | 606.55 | 207.33 | 586.38 | 209.70 | 376.68 | 0.00 | 0.00 |
August | 503.84 | 236.38 | 485.86 | 168.56 | 317.30 | 0.00 | 0.00 |
September | 383.17 | 288.55 | 388.12 | 140.99 | 247.13 | 0.00 | 0.00 |
October | 159.78 | 329.69 | 214.43 | 59.74 | 154.69 | 0.00 | 0.00 |
November | 56.96 | 372.14 | 118.98 | 26.39 | 92.59 | 0.00 | 0.00 |
December | 16.72 | 468.85 | 70.33 | 10.48 | 59.85 | 0.00 | 0.00 |
Annual Sum or Average | 295.11 | 314.32 | 332.35 | 104.84 | 227.51 | 0.00 | 0.00 |
Minimum of Months | 16.72 | 207.33 | 70.33 | 10.48 | 59.85 | 0.00 | 0.00 |
Maximum of Months | 606.55 | 468.85 | 586.38 | 209.70 | 390.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 393.46 | 1511.12 | 142.33 | 34.19 | 108.14 | 0.00 | 0.00 |
February | 780.79 | 1526.94 | 251.06 | 83.57 | 167.49 | 0.00 | 0.00 |
March | 1024.48 | 1004.74 | 323.91 | 60.21 | 263.70 | 0.00 | 0.00 |
April | 3341.78 | 885.07 | 791.33 | 423.74 | 367.60 | 0.00 | 0.00 |
May | 3977.99 | 767.35 | 954.55 | 530.31 | 424.24 | 0.00 | 0.00 |
June | 4160.54 | 640.90 | 1017.73 | 552.35 | 465.38 | 0.00 | 0.00 |
July | 4042.33 | 705.85 | 1032.32 | 604.34 | 427.98 | 0.00 | 0.00 |
August | 3279.73 | 863.00 | 886.75 | 536.91 | 349.84 | 0.00 | 0.00 |
September | 2354.67 | 1012.71 | 643.20 | 380.39 | 262.82 | 0.00 | 0.00 |
October | 1184.52 | 1092.20 | 326.37 | 139.29 | 187.08 | 0.00 | 0.00 |
November | 418.57 | 1279.24 | 157.33 | 41.57 | 115.76 | 0.00 | 0.00 |
December | 222.69 | 1757.57 | 99.35 | 20.85 | 78.49 | 0.00 | 0.00 |
Annual Sum or Average | 2104.14 | 1085.06 | 553.56 | 284.91 | 268.66 | 0.00 | 0.00 |
Minimum of Months | 222.69 | 640.90 | 99.35 | 20.85 | 78.49 | 0.00 | 0.00 |
Maximum of Months | 4160.54 | 1757.57 | 1032.32 | 604.34 | 465.38 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150894E+09 | 0.112018E+10 | 0.327553E+09 | 82842070.00 | 0.244710E+09 | 0.00 | 0.00 |
February | 0.334981E+09 | 0.949013E+09 | 0.509489E+09 | 0.172084E+09 | 0.337405E+09 | 0.00 | 0.00 |
March | 0.309133E+09 | 0.850198E+09 | 0.564145E+09 | 77705786.18 | 0.486439E+09 | 0.00 | 0.00 |
April | 0.109849E+10 | 0.750439E+09 | 0.117281E+10 | 0.366066E+09 | 0.806741E+09 | 0.00 | 0.00 |
May | 0.132248E+10 | 0.652071E+09 | 0.144256E+10 | 0.469220E+09 | 0.973335E+09 | 0.00 | 0.00 |
June | 0.150295E+10 | 0.550700E+09 | 0.151544E+10 | 0.503246E+09 | 0.101219E+10 | 0.00 | 0.00 |
July | 0.162457E+10 | 0.555301E+09 | 0.157056E+10 | 0.561666E+09 | 0.100889E+10 | 0.00 | 0.00 |
August | 0.134950E+10 | 0.633114E+09 | 0.130132E+10 | 0.451470E+09 | 0.849849E+09 | 0.00 | 0.00 |
September | 0.993174E+09 | 0.747918E+09 | 0.100600E+10 | 0.365437E+09 | 0.640559E+09 | 0.00 | 0.00 |
October | 0.427953E+09 | 0.883052E+09 | 0.574329E+09 | 0.159998E+09 | 0.414331E+09 | 0.00 | 0.00 |
November | 0.147640E+09 | 0.964576E+09 | 0.308393E+09 | 68393009.55 | 0.240000E+09 | 0.00 | 0.00 |
December | 44791642.50 | 0.125578E+10 | 0.188363E+09 | 28064229.39 | 0.160298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.930656E+10 | 0.991234E+10 | 0.104809E+11 | 0.330619E+10 | 0.717475E+10 | 0.00 | 0.00 |
Minimum of Months | 44791642.50 | 0.550700E+09 | 0.188363E+09 | 28064229.39 | 0.160298E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162457E+10 | 0.125578E+10 | 0.157056E+10 | 0.561666E+09 | 0.101219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105385E+10 | 0.404740E+10 | 0.381229E+09 | 91586675.66 | 0.289642E+09 | 0.00 | 0.00 |
February | 0.188889E+10 | 0.369399E+10 | 0.607375E+09 | 0.202179E+09 | 0.405196E+09 | 0.00 | 0.00 |
March | 0.274398E+10 | 0.269109E+10 | 0.867550E+09 | 0.161257E+09 | 0.706293E+09 | 0.00 | 0.00 |
April | 0.866189E+10 | 0.229410E+10 | 0.205113E+10 | 0.109832E+10 | 0.952813E+09 | 0.00 | 0.00 |
May | 0.106546E+11 | 0.205528E+10 | 0.255667E+10 | 0.142038E+10 | 0.113630E+10 | 0.00 | 0.00 |
June | 0.107841E+11 | 0.166121E+10 | 0.263795E+10 | 0.143169E+10 | 0.120625E+10 | 0.00 | 0.00 |
July | 0.108270E+11 | 0.189054E+10 | 0.276496E+10 | 0.161866E+10 | 0.114630E+10 | 0.00 | 0.00 |
August | 0.878442E+10 | 0.231145E+10 | 0.237507E+10 | 0.143807E+10 | 0.936999E+09 | 0.00 | 0.00 |
September | 0.610331E+10 | 0.262494E+10 | 0.166718E+10 | 0.985965E+09 | 0.681217E+09 | 0.00 | 0.00 |
October | 0.317262E+10 | 0.292534E+10 | 0.874156E+09 | 0.373083E+09 | 0.501073E+09 | 0.00 | 0.00 |
November | 0.108495E+10 | 0.331579E+10 | 0.407798E+09 | 0.107752E+09 | 0.300046E+09 | 0.00 | 0.00 |
December | 0.596447E+09 | 0.470747E+10 | 0.266090E+09 | 55852367.64 | 0.210237E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.663561E+11 | 0.342186E+11 | 0.174572E+11 | 0.898480E+10 | 0.847237E+10 | 0.00 | 0.00 |
Minimum of Months | 0.596447E+09 | 0.166121E+10 | 0.266090E+09 | 55852367.64 | 0.210237E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108270E+11 | 0.470747E+10 | 0.276496E+10 | 0.161866E+10 | 0.120625E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.955806E+09 | -869202479.0 | 0.00 | 0.00 | 744.00 | 0.00 | -86603023.0 | 58.99 | 0.00 | 0.00 |
February | 0.882121E+09 | -803825040.0 | 0.00 | 0.00 | 672.00 | 0.00 | -78296257.3 | 58.99 | 0.00 | 0.00 |
March | 0.101834E+10 | -933153569.3 | 0.00 | 0.00 | 744.00 | 0.00 | -85189832.7 | 58.99 | 0.00 | 0.00 |
April | 0.928516E+09 | -850509829.4 | 0.00 | 0.00 | 720.00 | 0.00 | -78006528.4 | 58.99 | 0.00 | 0.00 |
May | 0.941037E+09 | -860905586.3 | 0.00 | 0.00 | 744.00 | 0.00 | -80131143.7 | 58.99 | 0.00 | 0.00 |
June | 0.908375E+09 | -834456339.9 | 0.00 | 0.00 | 720.00 | 0.00 | -73919008.1 | 58.99 | 0.00 | 0.00 |
July | 0.864568E+09 | -789598379.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74969149.3 | 58.99 | 0.00 | 0.00 |
August | 0.916053E+09 | -841418934.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74633998.1 | 58.99 | 0.00 | 0.00 |
September | 0.862159E+09 | -788056634.5 | 0.00 | 0.00 | 720.00 | 0.00 | -74102808.7 | 58.99 | 0.00 | 0.00 |
October | 0.888759E+09 | -806688167.3 | 0.00 | 0.00 | 744.00 | 0.00 | -82071176.4 | 58.99 | 0.00 | 0.00 |
November | 0.879682E+09 | -796620002.6 | 0.00 | 0.00 | 720.00 | 0.00 | -83062237.3 | 58.99 | 0.00 | 0.00 |
December | 0.939193E+09 | -851914297.4 | 0.00 | 0.00 | 744.00 | 0.00 | -87278585.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.109846E+11 | -0.100263E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -958263748.4 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.862159E+09 | -933153569.3 | 0.00 | 0.00 | 672.00 | 0.00 | -87278585.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.101834E+10 | -788056634.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73919008.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488010E+10 | 26945.70 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384632E+10 | 26945.70 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349425E+10 | 26945.70 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.913775E+09 | 26945.70 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.716507E+09 | 26945.70 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88917596.74 | 26945.70 | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24156362.72 | 26687.23 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117188E+09 | 17510.12 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112892E+10 | 26945.70 | 03-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324073E+10 | 26945.70 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539470E+10 | 26945.70 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.539470E+10 | 26945.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.810328E+10 | 86186.23 | 08-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.659381E+10 | 86186.23 | 13-FEB-06:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230201E+10 | 82686.15 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8299716.81 | 13598.26 | 01-APR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65001168.82 | 34575.82 | 23-OCT-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449720E+10 | 86186.23 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127135E+11 | 86186.23 | 25-DEC-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127135E+11 | 86186.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122591E+11 | 45752.89 | 10-JAN-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.551298E+10 | 29788.13 | 19-FEB-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190274E+09 | 11759.02 | 04-MAR-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203371E+10 | 27316.14 | 29-NOV-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212655E+11 | 46388.13 | 30-DEC-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212655E+11 | 46388.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 57278781.70 | 56480720.97 | 3080.90 | 29-APR-15:50 | 3080.90 | 0.00 |
May | 0.00 | 0.00 | 89212294.93 | 78393268.45 | 6267.66 | 22-MAY-15:00 | 5684.07 | 0.00 |
June | 0.00 | 0.00 | 0.667551E+09 | 0.553111E+09 | 10085.18 | 13-JUN-16:00 | 8961.10 | 0.00 |
July | 0.00 | 0.00 | 0.126526E+10 | 0.109306E+10 | 16938.12 | 18-JUL-05:03 | 11088.46 | 0.00 |
August | 0.00 | 0.00 | 0.125248E+10 | 0.102913E+10 | 15605.02 | 15-AUG-05:03 | 13413.09 | 0.00 |
September | 0.00 | 0.00 | 0.500508E+09 | 0.437803E+09 | 7457.02 | 13-SEP-16:00 | 6384.71 | 0.00 |
October | 0.00 | 0.00 | 782319.43 | 782316.07 | 496.80 | 07-OCT-15:00 | 496.80 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.383308E+10 | 0.324875E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126526E+10 | 0.109306E+10 | 16938.12 | 13413.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 14926808.40 | 14926808.40 | 49756.03 | 30-APR-15:25 | 49756.03 | 0.00 |
May | 0.00 | 0.00 | 7630715.63 | 7079328.88 | 3319.27 | 22-MAY-15:00 | 3097.25 | 0.00 |
June | 0.00 | 0.00 | 0.786774E+09 | 0.687308E+09 | 53114.04 | 13-JUN-17:51 | 47892.60 | 0.00 |
July | 0.00 | 0.00 | 0.173387E+10 | 0.164865E+10 | 53537.11 | 23-JUL-15:51 | 42432.63 | 0.00 |
August | 0.00 | 0.00 | 0.684371E+09 | 0.608973E+09 | 50864.08 | 20-AUG-15:25 | 50864.08 | 0.00 |
September | 0.00 | 0.00 | 96143655.49 | 83311600.02 | 8176.12 | 13-SEP-14:30 | 7110.69 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.332372E+10 | 0.305025E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.173387E+10 | 0.164865E+10 | 53537.11 | 50864.08 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120635E+09 | 0.03 | 134.88 | 01-JAN-00:03 | 0.08 |
February | 72448146.78 | 0.02 | 134.88 | 04-FEB-02:70 | 0.08 |
March | 7606954.26 | 0.00 | 134.88 | 03-MAR-23:20 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 27757290.53 | 0.01 | 134.88 | 19-NOV-07:20 | 0.08 |
December | 0.202624E+09 | 0.04 | 134.88 | 01-DEC-00:40 | 0.08 |
Annual Sum or Average | 0.431072E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202624E+09 | 0.04 | 134.88 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119650E+10 | 0.41 | 1168.36 | 02-JAN-07:40 | 0.95 |
February | 0.109754E+10 | 0.39 | 1168.36 | 01-FEB-07:20 | 0.94 |
March | 0.127970E+10 | 0.40 | 1168.36 | 01-MAR-09:10 | 0.94 |
April | 0.116934E+10 | 0.38 | 1168.36 | 01-APR-08:20 | 0.94 |
May | 0.121316E+10 | 0.38 | 1168.36 | 01-MAY-06:10 | 0.94 |
June | 0.120400E+10 | 0.38 | 1168.36 | 01-JUN-06:05 | 0.94 |
July | 0.115860E+10 | 0.35 | 1168.36 | 03-JUL-06:05 | 0.94 |
August | 0.124991E+10 | 0.37 | 1168.36 | 01-AUG-13:10 | 0.94 |
September | 0.115741E+10 | 0.36 | 1168.36 | 01-SEP-07:35 | 0.94 |
October | 0.117142E+10 | 0.37 | 1168.36 | 02-OCT-06:10 | 0.94 |
November | 0.113973E+10 | 0.38 | 1168.36 | 01-NOV-06:05 | 0.94 |
December | 0.120305E+10 | 0.41 | 1168.36 | 01-DEC-08:70 | 0.94 |
Annual Sum or Average | 0.142404E+11 | 0.38 | |||
Minimum of Months | 0.109754E+10 | 0.35 | 1168.36 | 0.94 | |
Maximum of Months | 0.127970E+10 | 0.41 | 1168.36 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.317780E+10 | 0.60 | 2908.96 | 02-JAN-08:00 | 0.91 |
February | 0.290993E+10 | 0.65 | 2908.96 | 07-FEB-08:70 | 0.90 |
March | 0.320231E+10 | 0.48 | 2908.96 | 07-MAR-07:10 | 0.91 |
April | 0.288106E+10 | 0.35 | 2908.96 | 01-APR-06:05 | 0.91 |
May | 0.299507E+10 | 0.35 | 2908.96 | 22-MAY-14:20 | 0.90 |
June | 0.299964E+10 | 0.36 | 2908.96 | 20-JUN-14:30 | 0.90 |
July | 0.289483E+10 | 0.34 | 2908.96 | 10-JUL-09:00 | 0.90 |
August | 0.311263E+10 | 0.36 | 2908.96 | 05-AUG-14:10 | 0.90 |
September | 0.287987E+10 | 0.34 | 2908.96 | 12-SEP-14:30 | 0.90 |
October | 0.288248E+10 | 0.34 | 2908.96 | 02-OCT-06:05 | 0.91 |
November | 0.293429E+10 | 0.50 | 2908.96 | 02-NOV-06:05 | 0.90 |
December | 0.334753E+10 | 0.72 | 2908.96 | 02-DEC-17:50 | 0.90 |
Annual Sum or Average | 0.362174E+11 | 0.45 | |||
Minimum of Months | 0.287987E+10 | 0.34 | 2908.96 | 0.90 | |
Maximum of Months | 0.334753E+10 | 0.72 | 2908.96 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119650E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109754E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127970E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118665E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.123968E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139939E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.153473E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.162173E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130605E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117166E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113973E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120305E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.153764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109754E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.162173E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.317780E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.290993E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.320231E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.288482E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.299730E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.322146E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.339104E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.330843E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.290762E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.288248E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.293429E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.334753E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.371650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.288248E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.339104E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119650E+10 | 0.00 | 0.488010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109754E+10 | 0.00 | 0.384632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127970E+10 | 0.00 | 0.349425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116934E+10 | 57278781.70 | 0.913775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121316E+10 | 89212294.93 | 0.716507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120400E+10 | 0.667551E+09 | 88917596.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115860E+10 | 0.126526E+10 | 24156362.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124991E+10 | 0.125248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115741E+10 | 0.500508E+09 | 0.117188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117142E+10 | 782319.43 | 0.112892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113973E+10 | 0.00 | 0.324073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120305E+10 | 0.00 | 0.539470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142404E+11 | 0.383308E+10 | 0.238456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127970E+10 | 0.126526E+10 | 0.539470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.317780E+10 | 0.00 | 0.810328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290993E+10 | 0.00 | 0.659381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320231E+10 | 0.00 | 0.230201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288106E+10 | 14926808.40 | 8299716.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299507E+10 | 7630715.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299964E+10 | 0.786774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289483E+10 | 0.173387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311263E+10 | 0.684371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287987E+10 | 96143655.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288248E+10 | 0.00 | 65001168.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293429E+10 | 0.00 | 0.449720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334753E+10 | 0.00 | 0.127135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362174E+11 | 0.332372E+10 | 0.342831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.334753E+10 | 0.173387E+10 | 0.127135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116934E+10 | 0.00 | 0.00 | 0.00 | 17314840.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121316E+10 | 0.00 | 0.00 | 0.00 | 26517868.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120400E+10 | 0.00 | 0.00 | 0.00 | 0.195391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115860E+10 | 0.00 | 0.00 | 0.00 | 0.376135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124991E+10 | 0.00 | 0.00 | 0.00 | 0.371823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115741E+10 | 0.00 | 0.00 | 0.00 | 0.148644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117142E+10 | 0.00 | 0.00 | 0.00 | 241416.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142404E+11 | 0.00 | 0.00 | 0.00 | 0.113607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127970E+10 | 0.00 | 0.00 | 0.00 | 0.376135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.317780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288106E+10 | 0.00 | 0.00 | 0.00 | 3760576.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299507E+10 | 0.00 | 0.00 | 0.00 | 2228996.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299964E+10 | 0.00 | 0.00 | 0.00 | 0.221824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289483E+10 | 0.00 | 0.00 | 0.00 | 0.496207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311263E+10 | 0.00 | 0.00 | 0.00 | 0.195799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287987E+10 | 0.00 | 0.00 | 0.00 | 27747064.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362174E+11 | 0.00 | 0.00 | 0.00 | 0.947567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.334753E+10 | 0.00 | 0.00 | 0.00 | 0.496207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.413427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187596E+10 | 0.00 | 0.00 | 0.15 |
February | 0.423418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156473E+10 | 0.00 | 0.00 | 0.15 |
March | 0.796743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138543E+10 | 0.00 | 0.00 | 0.16 |
April | 0.108402E+10 | 122256.59 | 0.00 | 981040.61 | 0.00 | 0.187294E+09 | 0.989720E+09 | 0.00 | 0.24 |
May | 0.100392E+10 | 0.00 | 0.00 | 1282897.06 | 0.00 | 0.135735E+09 | 0.124560E+10 | 0.00 | 0.26 |
June | 0.307837E+09 | 9869889.94 | 0.00 | 3641832.72 | 0.00 | 7948898.02 | 0.291832E+10 | 0.00 | 0.47 |
July | 65613758.89 | 15575441.04 | 0.00 | 4889801.07 | 0.00 | 0.00 | 0.351017E+10 | 0.00 | 0.58 |
August | 38494069.95 | 139196.99 | 0.00 | 5955617.91 | 0.00 | 0.00 | 0.388482E+10 | 0.00 | 0.76 |
September | 0.229800E+09 | 0.00 | 0.00 | 3726933.23 | 0.00 | 0.00 | 0.293552E+10 | 0.00 | 0.52 |
October | 0.110235E+10 | 0.00 | 0.00 | 431721.69 | 0.00 | 0.260358E+09 | 0.538115E+09 | 0.00 | 0.18 |
November | 0.613417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124721E+10 | 0.00 | 0.00 | 0.14 |
December | 0.110676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212767E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.618972E+10 | 25706784.56 | 0.00 | 20909844.30 | 0.00 | 0.879234E+10 | 0.160223E+11 | 0.00 | 0.31 |
Minimum of Months | 38494069.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.110235E+10 | 15575441.04 | 0.00 | 5955617.91 | 0.00 | 0.212767E+10 | 0.388482E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.488934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327029E+09 | 0.00 | 0.00 | 0.14 |
February | 0.454034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11668888.87 | 0.00 | 0.00 | 0.15 |
March | 0.524238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19353163.18 | 0.00 | 0.00 | 0.16 |
April | 0.469354E+10 | 0.00 | 0.00 | 638041.12 | 320229.73 | 0.00 | 0.748275E+09 | 0.00 | 0.17 |
May | 0.468149E+10 | 0.00 | 0.00 | 734202.65 | 0.00 | 0.00 | 0.800912E+09 | 0.00 | 0.17 |
June | 0.306501E+10 | 0.00 | 0.00 | 4354723.04 | 0.00 | 0.00 | 0.352281E+10 | 0.00 | 0.27 |
July | 0.143400E+10 | 0.00 | 0.00 | 9466303.99 | 0.00 | 0.00 | 0.689728E+10 | 0.00 | 0.36 |
August | 0.103151E+10 | 0.00 | 0.00 | 9182196.01 | 0.00 | 0.00 | 0.819937E+10 | 0.00 | 0.42 |
September | 0.293595E+10 | 0.00 | 0.00 | 2444857.76 | 0.00 | 0.00 | 0.273133E+10 | 0.00 | 0.24 |
October | 0.433581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
November | 0.413110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112593E+09 | 0.00 | 0.00 | 0.14 |
December | 0.429910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436910E+09 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.452796E+11 | 0.00 | 0.00 | 26820324.57 | 320229.73 | 0.907554E+09 | 0.229000E+11 | 0.00 | 0.21 |
Minimum of Months | 0.103151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.524238E+10 | 0.00 | 0.00 | 9466303.99 | 320229.73 | 0.436910E+09 | 0.819937E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.154845E+12 | 0.197887E+11 | 0.00 | 0.750576E+10 | 0.171788E+11 |
February | 0.263841E+12 | 0.256478E+11 | 0.00 | 0.654016E+10 | 0.139640E+11 |
March | 0.341334E+12 | 0.200744E+11 | 0.00 | 0.744391E+10 | 0.115278E+11 |
April | 0.960466E+12 | 0.261951E+11 | 0.00 | 0.770402E+10 | 0.895016E+10 |
May | 0.114735E+13 | 0.584871E+11 | 0.00 | 0.786968E+10 | 0.916989E+10 |
June | 0.116919E+13 | 0.525875E+11 | 0.00 | 0.982076E+10 | 0.103401E+11 |
July | 0.119920E+13 | 0.524868E+11 | 0.00 | 0.119110E+11 | 0.125879E+11 |
August | 0.993861E+12 | 0.459499E+11 | 0.00 | 0.131698E+11 | 0.112093E+11 |
September | 0.723045E+12 | 0.406840E+11 | 0.00 | 0.883877E+10 | 0.925714E+10 |
October | 0.323510E+12 | 0.321675E+11 | 0.00 | 0.623707E+10 | 0.926918E+10 |
November | 0.102197E+12 | 0.303125E+11 | 0.00 | 0.610432E+10 | 0.124844E+11 |
December | 0.134147E+11 | 0.395795E+11 | 0.00 | 0.697435E+10 | 0.213239E+11 |
Annual Sum or Average | 0.739225E+13 | 0.443961E+12 | 0.00 | 0.100120E+12 | 0.147263E+12 |
Minimum of Months | 0.134147E+11 | 0.197887E+11 | 0.00 | 0.610432E+10 | 0.895016E+10 |
Maximum of Months | 0.119920E+13 | 0.584871E+11 | 0.00 | 0.131698E+11 | 0.213239E+11 |