Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 10:43:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1855.55 | 383.76 | 383.76 |
Net Site Energy | 1855.55 | 383.76 | 383.76 |
Total Source Energy | 2869.54 | 593.48 | 593.48 |
Net Source Energy | 2869.54 | 593.48 | 593.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1443.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 137.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 411.97 | 1443.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1443.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 137.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1443.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 137.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 28.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 43.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.97 | 298.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 85.20 | 298.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 43.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.97 | 298.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 85.20 | 298.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 411.967 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 411.967 | 100.00 |
Total On-Site and Utility Electric Sources | 411.967 | 100.00 |
Total Electricity End Uses | 411.967 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 86.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3092.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6766 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 7.6766 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.3906 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.5498 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:00 | 18-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 395309.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10998.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9701.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4014.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1768.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 36596.57 | 395309.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 395309.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10998.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9701.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1709.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1768.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1564.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 24.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 433.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 230.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1304.70 | 1564.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 323.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 89.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 269.84 | 323.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 323.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 89.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 269.84 | 323.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.01 |
ZONE2 FINE STORAGE DIRECT AIR | 1.74 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.61 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.61 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 219034.29 |
PSZ-OFFICE HEATING COIL | 27732.44 |
PSZ-FINE STORAGE HEATING COIL | 69481.22 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 219034.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-FINE STORAGE | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.00 | 1.00 | 1.74 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.01 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.74 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.01 | 1121.41 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.74 | 1858.66 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.668494 | 19726.55 | 27732.44 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.74 | 1.74 | 1.74 | 1.15 | 43133.53 | 69481.22 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.01 | 0.506435 | 0.675247 | 19726.55 | 9863.27 | 0.786490 | 0.786490 |
PSZ-FINE STORAGE COOLING COIL | 1.74 | 0.868494 | 1.16 | 43133.53 | 21566.76 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 7.677 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.750 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1818.427 | 7.677 | 142.636 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1818.427 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10866.415 | 3.391 | 157.484 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
5 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
6 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3618_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3618_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3618_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3618_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.055 | 2.055 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63872E-002 | 0.31435 | 0.48135 | 0.48135 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11595 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2283E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9042E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9415E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3600E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3572E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1547E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1869E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0055E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6654E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6109E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6533E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9968E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3296E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0265E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2705E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6679E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4040E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9028E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5054E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9188E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4865E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3654E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3750E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3193E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1096E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0789E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6603E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0596E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8459E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4055E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5442E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6112E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9434E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9416E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.7694E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.7072E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8599E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.0221E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.7583E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.1621E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.2411E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.1715E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.8289E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.1250E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.9649E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8464E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2760E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7951E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9686E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9893E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6769E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2452E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.5869E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0592E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4594E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.8018E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0578E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9928E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4916E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2414E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5869E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0592E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9783.95162 | 11740.74195 | 0.84406 | 1.01287 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 29.85733 | 1.53626E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 13152.65998 | 15783.19198 | 0.38722 | 0.46466 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 21521.63976 | 25825.96771 | 1.44749 | 1.73699 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 47900.66227 | 57480.79472 | 1.18717 | 1.42461 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 182528.57468 | 219034.28961 | 4.67496 | 5.60995 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14628.28 | 1.01287 | 1.01287 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15741.24 | 0.46466 | 0.46466 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 31646.09 | 1.73699 | 1.73699 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 60666.07 | 1.42461 | 1.42461 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01287 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.73699 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.60995 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.60995 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 219034.28641 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 219034.28961 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01287 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01287 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01287 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01287 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01287 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.01287 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.73699 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.73699 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.73699 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.73699 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.73699 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.73699 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.01287 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.73699 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01287 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01287 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1121.40794 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01287 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01287 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01287 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66849 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01287 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50644 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67525 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19726.55000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9863.27500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78649 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78649 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19726.55000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27732.44216 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27732.44216 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.73699 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.73699 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1858.65843 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.73699 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.73699 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.73699 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14641 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.73699 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86849 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15799 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43133.53000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21566.76500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43133.53000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69481.21871 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 69481.21871 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18940.1 | 11.77 | 11.50 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 41783.4 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2358159866 | 0.2103398940 | Pass | Pass | 0.3445191064 | 1.0909534891 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5030504326 | 0.4632752837 | Pass | Pass | 0.5000243363 | 0.6652193558 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.4687040838E-005 | 6.4745390418E-005 | Pass | Pass | 2.3262026436E-002 | 2.7964645393E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8272.27 | 1096.77 | 0.00 | 82.81 | 367.86 | 9819.73 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.176 | 0.180 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.3618_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.055 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.3618_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.055 | 0.401 | 0.402 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.3618_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.055 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.3618_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.055 | 0.401 | 0.402 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.064 | 0.494 | 0.493 | |||||||||||||||||
North Total or Average | 6.51 | 2.055 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.316 | 0.517 | 0.516 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 7.6766 | 236.88 | 1818.43 | LightsWired | LTG_SCH_OFFICE | 49.99 | 168.00 | 44.77 | 0.0000 | Y | 15.28 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 33.37 | 0.0000 | Y | 58.34 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.3906 | 3204.84 | 10866.42 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 31.08 | 0.0000 | Y | 63.40 |
Interior Lighting Total | 4.5498 | 4835.13 | 21998.92 | 137.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 10866.42 | 1260.50 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1818.43 | 263.67 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 1818.43 | 90.92 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 42.24 | 42.24 | 0.74 | |
EXTERIOR_LIGHTS_B | 5399.43 | AstronomicalClock | - | 83.63 | 71.21 | 72.18 | |
Exterior Lighting Total | 5492.60 | 72.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19726.55 | 15514.73 | 4211.82 | 0.79 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43133.53 | 30240.06 | 12893.47 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18940.1 | 11.77 | 11.50 | ||||
PSZ-FINE STORAGE COOLING COIL | 41783.4 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 219034.29 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27732.44 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 69481.22 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.61 | 521.22 | 92.91 | 1.00 | 3.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1121.41 | 1107.16 | 1.00 | 1.40 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.74 | 1858.66 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9783.95 | 11740.74 | 49.56 | 0.844 | 1.013 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00879 | 29.86 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 21521.64 | 25825.97 | 18.53 | 1.447 | 1.737 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.69 | 0.01018 | 31.09 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.15 | 0.01543 | 31.09 | 0.01536 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13152.66 | 15783.19 | 66.63 | 0.387 | 0.465 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00718 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 47900.66 | 57480.79 | 41.25 | 1.187 | 1.425 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00576 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 182528.57 | 219034.29 | 68.34 | 4.675 | 5.610 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00484 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.01 | 1.01 | 0.46 | 0.46 | 1.0129 | 1.0129 | 1.0129 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.74 | 1.74 | 1.42 | 1.42 | 1.7370 | 1.7370 | 1.7370 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 219034.286 | 219034.286 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 219034.29 | 219034.29 | 5.609949 | 9.99 | 6.47 | 0.00484307 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00484307 | 60.8286 | 219034.29 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19726.550 | 15514.734 | 1.012870 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 9863.27 | 7986.41 | 0.675247 | 25.47 | 17.20 | 0.00945588 | 12.00 | 10.84 | 0.00800000 | 30.14 | 0.01536312 | 22.84 | 15.1477 | 23.90 | 0.00879146 | 45.3983 | 9772.42 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27732.442 | 27732.442 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27732.44 | 27732.44 | 1.012870 | 16.28 | 11.09 | 0.00648833 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 10.0985 | 21.10 | 0.00717656 | 44.0486 | 13152.66 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 43133.530 | 30240.055 | 1.736990 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21566.76 | 14752.43 | 1.157993 | 28.71 | 19.76 | 0.01145119 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 36.6765 | 26.69 | 0.01018326 | 44.4258 | 21506.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 69481.219 | 69481.219 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 69481.22 | 69481.22 | 1.736987 | 5.34 | 3.62 | 0.00443686 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 24.4510 | 15.55 | 0.00575588 | 50.1529 | 47900.66 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 219034.286 | 219034.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.609949 | 6.44333912 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 219034.29 | 219034.29 | 1.0000 | 6.44333912 | 5.609949 | 9.99 | 6.47 | 0.00484307 | 22243.8 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 219034.29 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00484307 | 9.99 | 0.00484307 | 60.8286 | 219034.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19726.550 | 15514.734 | 1.012870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4180 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.012870 | 1.16333782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 9863.27 | 7986.41 | 1.0000 | 0.77555849 | 0.675247 | 25.47 | 17.20 | 0.00945588 | 49690.8 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9863.27 | 30.14 | 0.01536312 | 22.84 | 0.10228463 | 15.1477 | 23.90 | 0.00879146 | 23.90 | 0.00879146 | 45.3983 | 9772.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27732.442 | 27732.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.012870 | 1.16333782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 27732.44 | 27732.44 | 1.0000 | 1.16333782 | 1.012870 | 16.28 | 11.09 | 0.00648833 | 32778.6 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27732.44 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 10.0985 | 21.05 | 0.00717656 | 21.10 | 0.00717656 | 44.0486 | 13152.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43133.530 | 30240.055 | 1.736990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1272 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.736987 | 1.99502679 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 21566.76 | 14752.43 | 1.0000 | 1.33001999 | 1.157993 | 28.71 | 19.76 | 0.01145119 | 58093.9 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21566.76 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 36.6765 | 26.69 | 0.01018326 | 26.69 | 0.01018326 | 44.4258 | 21506.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69481.219 | 69481.219 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.736987 | 1.99502679 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 69481.22 | 69481.22 | 1.0000 | 1.99502679 | 1.736987 | 5.34 | 3.62 | 0.00443686 | 16507.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69481.22 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 24.4510 | 15.55 | 0.00575588 | 15.55 | 0.00575588 | 50.1529 | 47900.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.01 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3012.17 | 2915.00 | 2430.83 |
ZONE2 FINE STORAGE | 3303.17 | 3211.17 | 2921.83 |
ZONE3 BULK STORAGE | 3329.00 | 3274.33 | 3037.83 |
Facility | 3470.00 | 3324.50 | 3092.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 213.83 | 0.17 | 54.33 | 0.17 |
ZONE2 FINE STORAGE | 581.83 | 1.67 | 30.17 | 0.00 |
ZONE3 BULK STORAGE | 46.50 | 0.00 | 17.50 | 0.00 |
Facility | 759.17 | 1.83 | 86.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.483 | 0.496 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.460 | 0.352 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.215 | 0.000 | 0.085 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.03 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1739392.57 | 0.00 | 1739392.57 | 2841321.04 | 4580713.60 | 3225648.14 | 5722.24 | 2523.20 | 514.56 | 0.00 |
ZONE2 FINE STORAGE | 4904490.47 | 0.00 | 4904490.47 | 9790874.37 | 14695364.84 | 13393694.68 | 5726.61 | 2821.25 | 212.14 | 2.89 |
ZONE3 BULK STORAGE | 0.00 | 23915042.02 | 23915042.02 | 56304356.95 | 80219398.97 | 30805497.77 | 6742.00 | 131.33 | 1886.67 | 5100.17 |
Total Facility | 6643883.03 | 23915042.02 | 30558925.05 | 68936552.35 | 99495477.41 | 47424840.58 | 7884.83 | 3057.26 | 2498.19 | 5100.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1329 | 0.0000 | 0.1329 | 0.1374 | 0.2703 | 0.1023 | 598.24 | 2523.20 | 514.56 |
ZONE2 FINE STORAGE | 0.3741 | 0.0000 | 0.3741 | 0.2881 | 0.6622 | 0.4247 | 605.50 | 2821.25 | 209.25 |
ZONE3 BULK STORAGE | 0.0000 | 0.8365 | 0.8365 | 2.1287 | 2.9652 | 0.9768 | 2643.67 | 53.00 | 939.33 |
Total Facility | 0.5069 | 0.8365 | 1.3435 | 2.5543 | 3.8978 | 1.5038 | 2760.83 | 2978.92 | 1548.02 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2294534.34 | 0.00 | 2294534.34 | 3225648.14 | 5721.57 | 0.00 | 3038.43 | 0.00 |
PSZ-FINE STORAGE | 6470050.91 | 0.00 | 6470050.91 | 13393694.68 | 5726.61 | 0.00 | 3033.39 | 2.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1753 | 0.0000 | 0.1753 | 0.1023 | 597.57 | 0.00 | 3038.43 |
PSZ-FINE STORAGE | 0.4935 | 0.0000 | 0.4935 | 0.4247 | 605.50 | 0.00 | 3030.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2934.34 | 109.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2998.18 | 35.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2029 | 0.3869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5893 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
Electricity:Building | 276.35 | 1814.60 | 19-MAR-14:10 | 22141.36 | 04-AUG-13:30 |
Electricity:Zone:ZONE1 OFFICE | 47.23 | 774.00 | 20-FEB-16:10 | 2976.64 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 276.32 | 1814.60 | 19-MAR-14:10 | 20603.66 | 12-DEC-16:00 |
InteriorLights:Electricity | 137.03 | 1240.85 | 19-MAR-14:10 | 10491.04 | 12-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.28 | 200.25 | 20-FEB-16:10 | 1064.14 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 137.03 | 1240.85 | 19-MAR-14:10 | 10491.04 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 137.03 | 1240.85 | 19-MAR-14:10 | 10491.04 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.28 | 200.25 | 20-FEB-16:10 | 1064.14 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 137.03 | 1240.85 | 19-MAR-14:10 | 10491.04 | 12-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 58.34 | 512.27 | 01-JAN-00:10 | 4354.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 58.34 | 512.27 | 01-JAN-00:10 | 4354.33 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 58.34 | 512.27 | 01-JAN-00:10 | 4354.33 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 170.78 | 528.33 | 01-JAN-10:20 | 14996.18 | 04-AUG-13:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 63.40 | 528.33 | 01-JAN-10:20 | 5080.05 | 02-JAN-14:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 63.40 | 528.33 | 01-JAN-10:20 | 5080.05 | 02-JAN-14:00 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 28.36 | 0.00 | 18-MAR-17:10 | 4193.25 | 04-AUG-15:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.03 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-AUG-13:30 |
Ventilation (simple):Fans:Electricity | 0.03 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-AUG-13:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.03 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-AUG-13:30 |
ElectricityPurchased:Facility | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
ElectricityPurchased:Plant | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
Cogeneration:ElectricityPurchased | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
ElectricityNet:Plant | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
Cogeneration:ElectricityNet | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
General:Cogeneration:ElectricityNet | 411.97 | 2297.60 | 19-MAR-14:10 | 36596.57 | 04-AUG-15:00 |
Electricity:HVAC | 36.04 | 0.00 | 18-MAR-17:10 | 13792.29 | 04-AUG-15:40 |
General:Fans:Electricity | 28.33 | 0.00 | 18-MAR-17:10 | 3501.29 | 18-JAN-17:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 7.71 | 0.00 | 01-JAN-00:10 | 11904.33 | 04-AUG-15:40 |
General:Cooling:Electricity | 7.71 | 0.00 | 01-JAN-00:10 | 11904.33 | 04-AUG-15:40 |
ExteriorLights:Electricity | 72.92 | 0.00 | 01-JAN-08:00 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.92 | 0.00 | 01-JAN-08:00 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 26.66 | 483.00 | 02-JAN-06:10 | 2927.48 | 16-FEB-12:50 |
WaterSystems:Electricity | 26.66 | 483.00 | 02-JAN-06:10 | 2927.48 | 16-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.66 | 483.00 | 02-JAN-06:10 | 2927.48 | 16-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1443.58 | 0.00 | 18-MAR-17:10 | 395309.93 | 18-JAN-17:10 |
NaturalGas:HVAC | 1443.58 | 0.00 | 18-MAR-17:10 | 395309.93 | 18-JAN-17:10 |
Heating:NaturalGas | 1443.58 | 0.00 | 18-MAR-17:10 | 395309.93 | 18-JAN-17:10 |
General:Heating:NaturalGas | 1443.58 | 0.00 | 18-MAR-17:10 | 395309.93 | 18-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2255.35 | 0.00 | 18-MAR-17:10 | 621142.31 | 09-DEC-07:10 |
EnergyTransfer:Building | 1107.12 | 0.00 | 18-MAR-17:10 | 311932.07 | 09-DEC-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 76.86 | 0.00 | 01-JAN-00:40 | 29171.37 | 03-FEB-07:20 |
Heating:EnergyTransfer | 1074.37 | 0.00 | 18-MAR-17:10 | 311932.07 | 09-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 61.75 | 0.00 | 01-JAN-00:40 | 29171.37 | 03-FEB-07:20 |
General:Heating:EnergyTransfer | 1074.37 | 0.00 | 18-MAR-17:10 | 311932.07 | 09-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 61.75 | 0.00 | 01-JAN-00:40 | 29171.37 | 03-FEB-07:20 |
Cooling:EnergyTransfer | 32.75 | 0.00 | 01-JAN-00:10 | 23519.90 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 15.11 | 0.00 | 01-JAN-00:10 | 9512.53 | 04-AUG-16:10 |
General:Cooling:EnergyTransfer | 32.75 | 0.00 | 01-JAN-00:10 | 23519.90 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 15.11 | 0.00 | 01-JAN-00:10 | 9512.53 | 04-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 220.18 | 0.00 | 01-JAN-00:40 | 71189.39 | 09-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 202.54 | 0.00 | 01-JAN-00:40 | 71189.39 | 09-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 202.54 | 0.00 | 01-JAN-00:40 | 71189.39 | 09-DEC-07:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 17.64 | 0.00 | 01-JAN-00:10 | 14955.75 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 17.64 | 0.00 | 01-JAN-00:10 | 14955.75 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 810.08 | 0.00 | 24-FEB-09:50 | 221491.90 | 08-DEC-17:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 810.08 | 0.00 | 24-FEB-09:50 | 221491.90 | 08-DEC-17:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 810.08 | 0.00 | 24-FEB-09:50 | 221491.90 | 08-DEC-17:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1148.23 | 0.00 | 18-MAR-17:10 | 316247.95 | 18-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1115.83 | 0.00 | 18-MAR-17:10 | 316247.95 | 18-JAN-17:10 |
CoolingCoils:EnergyTransfer | 32.40 | 0.00 | 01-JAN-00:10 | 47701.18 | 04-AUG-15:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 61.750 | -15.108 | 0.000 | 0.000 | 10.231 | 15.282 | 31.946 | 11.535 | 0.000 | 0.756 | 0.000 | 0.000 | -9.812 | 0.000 | -50.055 | -56.525 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 202.540 | -17.639 | 0.000 | 0.000 | 27.015 | 58.344 | 0.000 | 0.000 | 0.000 | 1.227 | 0.002 | 0.000 | 0.000 | 0.000 | -152.313 | -119.173 |
ZONE3 BULK STORAGE | 810.076 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.952 | 63.405 | 107.344 | 143.372 | 0.000 | 26.327 | 0.000 | 0.000 | -72.825 | 0.000 | -893.904 | -252.747 |
Total Facility | 810.076 | 0.000 | 264.290 | -32.747 | 0.000 | 0.000 | 106.197 | 137.030 | 139.290 | 154.907 | 0.000 | 28.310 | 0.002 | 0.000 | -82.637 | 0.000 | -1096.271 | -428.445 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 22-JUL-07:02 | 0.00 | 0.00 | 0.00 | -19535.05 | 0.00 | 0.00 | 802.09 | 941.15 | 1912.50 | 231.35 | 0.00 | 0.00 | 16251.68 | 0.00 | -0.00 | 0.00 | -603.71 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -31407.57 | 0.00 | 0.00 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 30904.11 | 0.00 | -0.00 | 0.00 | -8.81 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -31407.57 | 0.00 | 0.00 | 0.00 | 1263.96 | 2623.78 | 33748.14 | 0.00 | 73.89 | 0.00 | 0.00 | 0.00 | 0.00 | -2747.22 | -3554.97 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-FEB-06:31 | 0.00 | 0.00 | 29908.97 | 0.00 | 0.00 | 0.00 | 155.05 | 317.86 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1427.47 | 0.00 | -5288.87 | -24239.28 |
ZONE2 FINE STORAGE | 19-JAN-06:01 | 0.00 | 0.00 | 74259.06 | 0.00 | 0.00 | 0.00 | 392.96 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25148.60 | -50015.69 |
ZONE3 BULK STORAGE | 09-DEC-08:35 | 221935.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8693.74 | 4482.40 | 8200.12 | 0.00 | 0.00 | 0.00 | 55256.60 | 0.00 | -12578.16 | 0.00 | -285990.11 | 0.00 |
Total Facility | 19-JAN-06:01 | 218809.62 | 0.00 | 103788.61 | 0.00 | 0.00 | 0.00 | 1473.60 | 1427.79 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11034.98 | 0.00 | -198418.66 | -118669.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0129 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0129 | 0.1010 | 1.0000 | Not calculated | 0.1023 | 0.1010 | ||
PSZ-FINE STORAGE | 1.7370 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7370 | 0.2445 | 1.0000 | Not calculated | 0.4247 | 0.2445 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0129 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0129 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1010 | ||
PSZ-FINE STORAGE | 1.7370 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7370 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2445 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0129 | 1.0129 | 1.0129 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7370 | 1.7370 | 1.7370 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0129 | 1.0129 | 1.0129 | 1.0129 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7370 | 1.7370 | 1.7370 | 1.7370 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0129 | 1.0129 | 1.0129 | No | 0.1023 | 0.2201 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7370 | 1.7370 | 1.7370 | No | 0.4247 | 0.2981 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0129 | 1.0129 | 1.0129 | 1.0129 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7370 | 1.7370 | 1.7370 | 1.7370 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 86.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 86.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1443.58 | 395309.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7.71 | 11904.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 137.03 | 10491.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.92 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.03 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 28.33 | 3501.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.66 | 2927.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 411.97 |
Natural Gas | 0.00 | 1443.58 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1855.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 28.34 |
Space Heating | 0.00 |
Space Cooling | 1.59 |
Fans (All) | 5.87 |
Service Water Heating | 5.51 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 85.20 |
Subtotal | 85.20 |
Natural Gas [MJ/m2] | |
Space Heating | 298.56 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 298.56 |
Subtotal | 298.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.38 |
Space Heating | 77.80 |
Space Cooling | 0.42 |
Fans (All) | 1.53 |
Service Water Heating | 1.44 |
Receptacle Equipment | 7.51 |
Miscellaneous | 3.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2607. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8419.50 | 340.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8232.50 | 527.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8348.17 | 400.83 | 11.00 | 0.00 | 0.00 |
Min | 8232.50 | 340.50 | 0.00 | 0.00 | 0.00 |
Max | 8419.50 | 527.50 | 11.00 | 0.00 | 0.00 |
Average | 8333.39 | 422.94 | 3.67 | 0.00 | 0.00 |
Sum | 25000.17 | 1268.83 | 11.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33022.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 73063.50 | 9655.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 176083.17 | 14535.33 | 574.50 | 0.00 | 0.00 |
Min | 33022.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Max | 176083.17 | 14535.33 | 574.50 | 0.00 | 0.00 |
Average | 94056.33 | 8065.17 | 191.50 | 0.00 | 0.00 |
Sum | 282169.00 | 24195.50 | 574.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7741.50 | 1018.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7329.00 | 1431.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7539.83 | 1214.50 | 5.67 | 0.00 | 0.00 |
Min | 7329.00 | 1018.50 | 0.00 | 0.00 | 0.00 |
Max | 7741.50 | 1431.00 | 5.67 | 0.00 | 0.00 |
Average | 7536.78 | 1221.33 | 1.89 | 0.00 | 0.00 |
Sum | 22610.33 | 3664.00 | 5.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31901.50 | 1125.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 65542.50 | 17176.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 160108.33 | 30762.67 | 322.00 | 0.00 | 0.00 |
Min | 31901.50 | 1125.50 | 0.00 | 0.00 | 0.00 |
Max | 160108.33 | 30762.67 | 322.00 | 0.00 | 0.00 |
Average | 85850.78 | 16354.89 | 107.33 | 0.00 | 0.00 |
Sum | 257552.33 | 49064.67 | 322.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 616175.15 | 1580.28 | 13-JAN-08:05 | -1.0 | -2.0 | 0.492416E+09 | 603.25 | 06-JAN-13:09 | -1.0 | -2.0 |
February | 1590277.45 | 2148.37 | 25-FEB-08:05 | 0.10 | -0.7 | 0.452471E+09 | 603.26 | 25-FEB-08:20 | 0.20 | -0.7 |
March | 3689102.35 | 2110.98 | 09-MAR-08:05 | -1.0 | -2.0 | 0.533051E+09 | 632.33 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.153396E+09 | 3630.53 | 18-APR-15:10 | 27.75 | 20.46 | 0.507476E+09 | 768.96 | 18-APR-10:39 | 27.75 | 20.46 |
May | 0.440154E+09 | 4567.91 | 31-MAY-15:40 | 28.87 | 19.09 | 0.572722E+09 | 769.02 | 31-MAY-13:39 | 28.87 | 19.09 |
June | 0.299833E+10 | 17472.60 | 24-JUN-07:03 | 19.27 | 15.28 | 0.639661E+09 | 879.38 | 26-JUN-07:10 | 23.58 | 21.51 |
July | 0.446006E+10 | 19539.94 | 22-JUL-07:02 | 15.18 | 13.12 | 0.637242E+09 | 879.39 | 29-JUL-07:10 | 19.87 | 17.85 |
August | 0.456791E+10 | 17358.95 | 19-AUG-07:03 | 17.57 | 15.03 | 0.686122E+09 | 879.39 | 05-AUG-07:10 | 17.57 | 15.03 |
September | 0.240743E+10 | 19256.39 | 02-SEP-07:03 | 13.53 | 11.74 | 0.593732E+09 | 879.39 | 09-SEP-07:10 | 16.05 | 14.85 |
October | 49848725.89 | 2291.88 | 23-OCT-07:05 | -1.2 | -2.6 | 0.499862E+09 | 759.15 | 20-OCT-15:39 | -1.2 | -2.6 |
November | 24077526.36 | 2224.20 | 04-NOV-07:05 | 0.37 | -1.2 | 0.474783E+09 | 660.97 | 04-NOV-15:09 | 14.13 | 6.72 |
December | 1099187.87 | 2430.06 | 23-DEC-08:05 | -6.8 | -7.3 | 0.493302E+09 | 603.25 | 30-DEC-08:20 | -1.1 | -1.8 |
Annual Sum or Average | 0.151082E+11 | 0.658284E+10 | ||||||||
Minimum of Months | 616175.15 | 1580.28 | -6.8 | -7.3 | 0.452471E+09 | 603.25 | -1.2 | -2.6 | ||
Maximum of Months | 0.456791E+10 | 19539.94 | 28.87 | 20.46 | 0.686122E+09 | 879.39 | 28.87 | 21.51 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21941089.74 | 4761.07 | 13-JAN-15:45 | 3.90 | 1.90 | 0.648963E+09 | 787.43 | 19-JAN-08:39 | -28.3 | -28.5 |
February | 0.153777E+09 | 5702.79 | 25-FEB-10:15 | 1.87 | 0.60 | 0.597782E+09 | 852.75 | 24-FEB-15:30 | 1.87 | 0.60 |
March | 0.514168E+09 | 4077.41 | 27-MAR-14:00 | 6.10 | 2.67 | 0.717635E+09 | 1111.82 | 25-MAR-15:20 | 6.10 | 2.67 |
April | 0.129982E+10 | 6215.00 | 22-APR-13:40 | 2.03 | -0.4 | 0.778368E+09 | 1981.13 | 18-APR-15:30 | 2.03 | -0.4 |
May | 0.115267E+10 | 4113.09 | 02-MAY-09:40 | 5.73 | 3.10 | 0.109758E+10 | 2219.85 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.269671E+10 | 30582.23 | 29-JUN-17:12 | 29.23 | 20.38 | 0.160157E+10 | 2246.91 | 30-JUN-13:00 | 29.40 | 21.96 |
July | 0.388615E+10 | 31412.53 | 05-JUL-17:10 | 26.70 | 20.64 | 0.177234E+10 | 2246.89 | 03-JUL-14:20 | 26.70 | 20.64 |
August | 0.299234E+10 | 26361.47 | 04-AUG-17:10 | 27.93 | 23.69 | 0.188808E+10 | 2246.91 | 04-AUG-12:39 | 27.93 | 23.69 |
September | 0.238820E+10 | 12393.33 | 10-SEP-14:55 | 27.80 | 17.84 | 0.139006E+10 | 2246.87 | 07-SEP-14:00 | 27.80 | 17.84 |
October | 0.184907E+10 | 5287.58 | 23-OCT-09:40 | 3.20 | 0.70 | 0.749220E+09 | 1355.10 | 20-OCT-15:30 | 3.20 | 0.70 |
November | 0.643193E+09 | 4469.93 | 04-NOV-08:50 | 5.03 | 2.41 | 0.660737E+09 | 1161.97 | 03-NOV-14:00 | 5.03 | 2.41 |
December | 41572149.87 | 4410.84 | 02-DEC-11:35 | 4.63 | 2.51 | 0.648463E+09 | 787.56 | 09-DEC-09:30 | -22.5 | -22.7 |
Annual Sum or Average | 0.176396E+11 | 0.125508E+11 | ||||||||
Minimum of Months | 21941089.74 | 4077.41 | 1.87 | -0.4 | 0.597782E+09 | 787.43 | -28.3 | -28.5 | ||
Maximum of Months | 0.388615E+10 | 31412.53 | 29.23 | 23.69 | 0.188808E+10 | 2246.91 | 29.40 | 23.69 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.641409E+09 | 780.43 | 07-JAN-14:09 | -16.1 | -17.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.595612E+09 | 956.63 | 24-FEB-15:50 | 8.30 | 5.84 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.756846E+09 | 1554.04 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 | -2.2 | 0.104118E+10 | 3578.10 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.15 | 0.189490E+10 | 4007.82 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.328195E+10 | 6008.87 | 30-JUN-15:30 | 29.15 | 21.20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.412990E+10 | 6136.79 | 05-JUL-15:00 | 27.80 | 20.26 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.426363E+10 | 7617.58 | 04-AUG-15:00 | 33.90 | 26.33 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.298874E+10 | 5397.18 | 08-SEP-14:50 | 30.10 | 19.14 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.106287E+10 | 2167.15 | 02-OCT-15:30 | 17.45 | 14.25 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 | -0.5 | 0.759890E+09 | 1621.69 | 03-NOV-14:00 | 16.10 | 9.59 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.631723E+09 | 836.90 | 02-DEC-16:10 | 4.95 | 2.78 |
Annual Sum or Average | 0.00 | 0.220487E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.595612E+09 | 780.43 | -16.1 | -17.1 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.426363E+10 | 7617.58 | 33.90 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150121E+11 | 29698.35 | 20-JAN-06:31 | -24.4 |
February | 0.109465E+11 | 29908.82 | 01-FEB-06:31 | -31.5 |
March | 0.866720E+10 | 29334.87 | 13-MAR-06:02 | -10.5 |
April | 0.426097E+10 | 28257.05 | 03-APR-06:02 | -7.1 |
May | 0.863533E+09 | 27991.44 | 02-MAY-06:02 | 2.30 |
June | 0.132505E+09 | 27535.95 | 05-JUN-06:02 | 8.98 |
July | 34554346.18 | 938.56 | 05-JUL-06:05 | 19.60 |
August | 43443009.52 | 934.49 | 07-AUG-06:13 | 9.43 |
September | 0.458535E+09 | 27947.19 | 29-SEP-06:01 | 0.10 |
October | 0.270220E+10 | 28035.54 | 23-OCT-06:01 | -3.0 |
November | 0.699001E+10 | 28960.78 | 28-NOV-06:32 | -18.0 |
December | 0.116393E+11 | 29368.90 | 12-DEC-06:31 | -19.6 |
Annual Sum or Average | 0.617509E+11 | |||
Minimum of Months | 34554346.18 | 934.49 | -31.5 | |
Maximum of Months | 0.150121E+11 | 29908.82 | 19.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542794E+11 | 74259.06 | 19-JAN-06:01 | -27.8 |
February | 0.380647E+11 | 73023.43 | 03-FEB-06:41 | -33.9 |
March | 0.251791E+11 | 72138.43 | 05-MAR-21:22 | -15.0 |
April | 0.100261E+11 | 71399.21 | 03-APR-03:42 | -6.6 |
May | 0.100969E+10 | 56812.08 | 02-MAY-02:53 | 2.80 |
June | 0.116018E+09 | 2331.80 | 09-JUN-12:00 | 28.30 |
July | 55181961.52 | 738.31 | 20-JUL-07:00 | 20.00 |
August | 62483786.87 | 747.86 | 25-AUG-06:50 | 13.80 |
September | 0.465105E+09 | 34755.55 | 29-SEP-06:01 | 0.10 |
October | 0.582207E+10 | 69685.27 | 24-OCT-06:01 | 2.38 |
November | 0.246728E+11 | 72439.00 | 25-NOV-06:01 | -16.9 |
December | 0.427875E+11 | 72776.12 | 10-DEC-18:41 | -19.9 |
Annual Sum or Average | 0.202540E+12 | |||
Minimum of Months | 55181961.52 | 738.31 | -33.9 | |
Maximum of Months | 0.542794E+11 | 74259.06 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243914E+12 | 221074.06 | 18-JAN-13:20 | -16.3 |
February | 0.166116E+12 | 219589.07 | 01-FEB-20:57 | -28.9 |
March | 0.937199E+11 | 174695.54 | 06-MAR-08:62 | -11.8 |
April | 0.212318E+11 | 97400.37 | 02-APR-24:00 | -5.6 |
May | 0.633685E+09 | 22771.88 | 02-MAY-02:57 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.239487E+10 | 26655.35 | 24-OCT-05:53 | 2.20 |
November | 0.958376E+11 | 173044.12 | 25-NOV-11:00 | -17.2 |
December | 0.186230E+12 | 221935.46 | 09-DEC-08:35 | -22.8 |
Annual Sum or Average | 0.810077E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.243914E+12 | 221935.46 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132244E+10 | 1064.14 | 02-JAN-16:40 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.118801E+10 | 1050.48 | 11-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.132638E+10 | 1033.19 | 01-MAR-16:00 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.124945E+10 | 1035.38 | 10-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.126931E+10 | 994.92 | 25-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.123849E+10 | 1023.50 | 13-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.123467E+10 | 1024.17 | 20-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.129351E+10 | 1012.63 | 31-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.124676E+10 | 1035.74 | 21-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.128576E+10 | 1047.88 | 21-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.127727E+10 | 1064.14 | 06-NOV-16:00 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.134959E+10 | 1064.14 | 01-DEC-16:30 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.152816E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.118801E+10 | 994.92 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.134959E+10 | 1064.14 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.485298E+10 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.444173E+10 | 4354.33 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.513145E+10 | 4354.33 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.480872E+10 | 4354.33 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.499222E+10 | 4354.33 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.494796E+10 | 4354.33 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.485298E+10 | 4354.33 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.513145E+10 | 4354.33 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.480872E+10 | 4354.33 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.485298E+10 | 4354.33 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.466948E+10 | 4354.33 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.485298E+10 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.583437E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.444173E+10 | 4354.33 | 0.00 | 0.00 | |
Maximum of Months | 0.513145E+10 | 4354.33 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.545906E+10 | 5080.05 | 02-JAN-13:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.494157E+10 | 5080.05 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.554231E+10 | 5080.05 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.513337E+10 | 4883.62 | 10-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.528017E+10 | 4687.19 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.521652E+10 | 4687.19 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.513015E+10 | 4687.19 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.544347E+10 | 4883.62 | 29-AUG-08:20 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.516755E+10 | 4883.62 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.534011E+10 | 5080.05 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.520368E+10 | 5080.05 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.554691E+10 | 5080.05 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.634049E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.494157E+10 | 4687.19 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.554691E+10 | 5080.05 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.132244E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988854E+10 |
February | 0.127628E+10 | 0.118801E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734619E+10 |
March | 0.149825E+10 | 0.132638E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 547367.78 | 0.605959E+10 |
April | 0.138726E+10 | 0.124945E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49556618.37 | 0.345693E+10 |
May | 0.144276E+10 | 0.126931E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46841009.16 | 0.170369E+10 |
June | 0.144276E+10 | 0.123849E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189911E+09 | 0.113458E+10 |
July | 0.138726E+10 | 0.123467E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140684E+09 | 0.821809E+09 |
August | 0.149825E+10 | 0.129351E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206305E+09 | 0.111030E+10 |
September | 0.138726E+10 | 0.124676E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121740E+09 | 0.182137E+10 |
October | 0.138726E+10 | 0.128576E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309375E+10 |
November | 0.133177E+10 | 0.127727E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558760E+10 |
December | 0.138726E+10 | 0.134959E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803023E+10 |
Annual Sum or Average | 0.168137E+11 | 0.152816E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755584E+09 | 0.500546E+11 |
Minimum of Months | 0.127628E+10 | 0.118801E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821809E+09 |
Maximum of Months | 0.149825E+10 | 0.134959E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206305E+09 | 0.988854E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309989E+11 |
February | 0.300332E+10 | 0.444173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227026E+11 |
March | 0.352563E+10 | 0.513145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14276404.48 | 0.176408E+11 |
April | 0.326447E+10 | 0.480872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348535E+09 | 0.926473E+10 |
May | 0.339505E+10 | 0.499222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153868E+09 | 0.410535E+10 |
June | 0.339505E+10 | 0.494796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371945E+09 | 0.344692E+10 |
July | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87279843.28 | 0.318733E+10 |
August | 0.352563E+10 | 0.513145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130794E+09 | 0.430527E+10 |
September | 0.326447E+10 | 0.480872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103048E+09 | 0.536538E+10 |
October | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17406633.23 | 0.781354E+10 |
November | 0.313390E+10 | 0.466948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177199E+11 |
December | 0.326447E+10 | 0.485298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257618E+11 |
Annual Sum or Average | 0.395654E+11 | 0.583437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122715E+10 | 0.152313E+12 |
Minimum of Months | 0.300332E+10 | 0.444173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318733E+10 |
Maximum of Months | 0.352563E+10 | 0.513145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371945E+09 | 0.309989E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.545906E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141600E+12 |
February | 0.690763E+10 | 0.494157E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987157E+11 |
March | 0.810895E+10 | 0.554231E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141800E+10 | 0.663671E+11 |
April | 0.750829E+10 | 0.513337E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597390E+10 | 0.307346E+11 |
May | 0.780862E+10 | 0.528017E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425077E+10 | 0.122397E+11 |
June | 0.780862E+10 | 0.521652E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299567E+10 | 0.135510E+11 |
July | 0.750829E+10 | 0.513015E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332041E+09 | 0.169229E+11 |
August | 0.810895E+10 | 0.544347E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485726E+09 | 0.207206E+11 |
September | 0.750829E+10 | 0.516755E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103100E+10 | 0.255378E+11 |
October | 0.750829E+10 | 0.534011E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150753E+10 | 0.235719E+11 |
November | 0.720796E+10 | 0.520368E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276234E+09 | 0.686615E+11 |
December | 0.750829E+10 | 0.554691E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110839E+12 |
Annual Sum or Average | 0.910005E+11 | 0.634049E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182709E+11 | 0.629462E+12 |
Minimum of Months | 0.690763E+10 | 0.494157E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122397E+11 |
Maximum of Months | 0.810895E+10 | 0.554691E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597390E+10 | 0.141600E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1064.14 | 02-JAN-16:40 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 24120.18 | 19-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1050.48 | 11-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 26134.77 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1033.19 | 01-MAR-16:00 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 | 19-MAR-14:00 | 18397.60 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 1035.38 | 10-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.72 | 18-APR-12:00 | 13321.82 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 994.92 | 25-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1998.67 | 31-MAY-17:00 | 8207.95 | 02-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1023.50 | 13-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3037.11 | 26-JUN-16:10 | 5716.11 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1024.17 | 20-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2491.23 | 25-JUL-16:10 | 4417.85 | 24-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1012.63 | 31-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3619.87 | 04-AUG-16:10 | 5862.59 | 07-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1035.74 | 21-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.23 | 06-SEP-16:10 | 8513.65 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1047.88 | 21-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 9766.53 | 23-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1064.14 | 06-NOV-16:00 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 16628.76 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1064.14 | 01-DEC-16:30 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 24145.56 | 08-DEC-17:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 994.92 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4417.85 | |||||
Maximum of Months | 1680.92 | 1064.14 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3619.87 | 26134.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4354.33 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 51766.64 | 18-JAN-17:55 |
February | 3955.50 | 01-FEB-08:09 | 4354.33 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 33244.30 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 4354.33 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.49 | 19-MAR-16:00 | 32673.63 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 4354.33 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6920.12 | 15-APR-15:10 | 20410.75 | 25-APR-06:01 |
May | 3955.50 | 01-MAY-07:10 | 4354.33 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3572.39 | 05-MAY-15:10 | 8908.79 | 02-MAY-02:57 |
June | 3955.50 | 01-JUN-07:10 | 4354.33 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4202.12 | 11-JUN-15:00 | 7864.08 | 02-JUN-05:00 |
July | 3955.50 | 01-JUL-07:10 | 4354.33 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.13 | 25-JUL-16:00 | 5070.85 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 4354.33 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.70 | 04-AUG-16:20 | 6061.65 | 30-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 4354.33 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.91 | 06-SEP-15:40 | 7997.61 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 4354.33 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1393.87 | 20-OCT-15:10 | 14077.70 | 24-OCT-06:03 |
November | 3955.50 | 01-NOV-07:10 | 4354.33 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 29671.83 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 4354.33 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 55002.30 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5070.85 | ||||
Maximum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6920.12 | 55002.30 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 5080.05 | 02-JAN-13:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 186390.04 | 18-JAN-13:10 |
February | 9097.65 | 01-FEB-08:09 | 5080.05 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 137022.96 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 5080.05 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24684.60 | 25-MAR-15:00 | 124914.74 | 06-MAR-08:05 |
April | 9097.65 | 01-APR-07:10 | 4883.62 | 10-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55060.53 | 15-APR-15:00 | 59362.67 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 4687.19 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38149.60 | 04-MAY-14:00 | 30895.69 | 13-MAY-12:55 |
June | 9097.65 | 01-JUN-07:10 | 4687.19 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28258.67 | 11-JUN-15:00 | 32263.05 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 4687.19 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8996.13 | 25-JUL-16:00 | 33226.01 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 4883.62 | 29-AUG-08:20 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7348.90 | 21-AUG-13:00 | 27891.35 | 06-AUG-06:00 |
September | 9097.65 | 01-SEP-07:10 | 4883.62 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14198.56 | 06-SEP-14:00 | 34881.88 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 5080.05 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21987.80 | 20-OCT-15:00 | 34512.69 | 24-OCT-07:05 |
November | 9097.65 | 01-NOV-07:10 | 5080.05 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11512.72 | 20-NOV-10:00 | 134635.28 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 5080.05 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 218485.03 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 4687.19 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27891.35 | |||||
Maximum of Months | 9097.65 | 5080.05 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 55060.53 | 218485.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1580.28 | 13-JAN-08:05 | 6723.69 | 4175.83 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2670.27 |
February | 2148.37 | 25-FEB-08:05 | 6723.69 | 3998.62 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.06 |
March | 2110.98 | 09-MAR-08:05 | 6723.69 | 3946.49 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.88 |
April | 3630.53 | 18-APR-15:10 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 826.09 | 0.00 |
May | 4567.91 | 31-MAY-15:40 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 638.08 | 0.00 |
June | 17472.60 | 24-JUN-07:03 | 6723.69 | 3688.87 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.91 |
July | 19539.94 | 22-JUL-07:02 | 8404.61 | 4705.75 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.71 |
August | 17358.95 | 19-AUG-07:03 | 6723.69 | 3910.57 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.90 |
September | 19256.39 | 02-SEP-07:03 | 6723.69 | 3862.99 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.09 |
October | 2291.88 | 23-OCT-07:05 | 6723.69 | 4118.74 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2492.03 |
November | 2224.20 | 04-NOV-07:05 | 6723.69 | 4162.07 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.39 |
December | 2430.06 | 23-DEC-08:05 | 6723.69 | 4232.56 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1580.28 | 1680.92 | 856.64 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19539.94 | 8404.61 | 4705.75 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 826.09 | 2670.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4761.07 | 13-JAN-15:45 | 7911.00 | 8708.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.08 |
February | 5702.79 | 25-FEB-10:15 | 7911.00 | 8708.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.97 |
March | 4077.41 | 27-MAR-14:00 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2121.43 |
April | 6215.00 | 22-APR-13:40 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.52 |
May | 4113.09 | 02-MAY-09:40 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2261.00 |
June | 30582.23 | 29-JUN-17:12 | 0.00 | 2049.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.03 | 0.00 |
July | 31412.53 | 05-JUL-17:10 | 0.00 | 2049.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
August | 26361.47 | 04-AUG-17:10 | 0.00 | 2049.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.78 | 0.00 |
September | 12393.33 | 10-SEP-14:55 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.75 | 0.00 |
October | 5287.58 | 23-OCT-09:40 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.14 |
November | 4469.93 | 04-NOV-08:50 | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.25 |
December | 4410.84 | 02-DEC-11:35 | 7911.00 | 8708.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3318.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4077.41 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31412.53 | 7911.00 | 8708.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.78 | 3318.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2390.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24532.35 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 3585.92 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60205.96 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 3585.92 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62313.18 |
April | 0.00 | 01-APR-00:03 | 0.00 | 1792.96 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11316.08 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5663.68 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6871.13 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7136.50 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8534.27 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10696.28 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11633.58 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7674.04 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 2390.61 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25208.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5663.68 | |
Maximum of Months | 0.00 | 0.00 | 3585.92 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62313.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.379864E+11 | 29852.39 | 18-JAN-16:00 | 0.417057E+12 | 395309.93 | 18-JAN-17:10 |
February | 0.335573E+11 | 25488.44 | 02-FEB-15:09 | 0.287950E+12 | 362208.43 | 01-FEB-20:00 |
March | 0.364387E+11 | 24772.28 | 01-MAR-15:50 | 0.173251E+12 | 315003.42 | 06-MAR-08:09 |
April | 0.322696E+11 | 24716.53 | 18-APR-14:39 | 0.505143E+11 | 170974.03 | 02-APR-23:49 |
May | 0.318456E+11 | 24505.58 | 31-MAY-14:00 | 0.323953E+10 | 53754.55 | 02-MAY-02:00 |
June | 0.325116E+11 | 30300.72 | 30-JUN-14:00 | 0.164534E+09 | 10302.54 | 05-JUN-06:10 |
July | 0.332365E+11 | 31563.00 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.351957E+11 | 36596.57 | 04-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.326583E+11 | 28382.76 | 08-SEP-14:20 | 0.142942E+10 | 29588.97 | 29-SEP-06:10 |
October | 0.336396E+11 | 23958.07 | 24-OCT-08:09 | 0.170283E+11 | 76800.04 | 24-OCT-06:10 |
November | 0.347842E+11 | 29424.78 | 25-NOV-16:49 | 0.171103E+12 | 289773.81 | 25-NOV-16:10 |
December | 0.378439E+11 | 29891.05 | 08-DEC-16:00 | 0.321843E+12 | 395309.93 | 08-DEC-17:10 |
Annual Sum or Average | 0.411967E+12 | 0.144358E+13 | ||||
Minimum of Months | 0.318456E+11 | 23958.07 | 0.00 | 0.00 | ||
Maximum of Months | 0.379864E+11 | 36596.57 | 0.417057E+12 | 395309.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.116345E+11 | 0.796190E+10 | 0.115358E+11 | 0.00 | 0.451245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234179E+10 | 0.00 |
February | 0.105713E+11 | 0.655365E+10 | 0.105871E+11 | 0.00 | 0.369647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214876E+10 | 0.00 |
March | 0.120001E+11 | 0.637344E+10 | 0.123431E+11 | 0.00 | 0.329788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242419E+10 | 0.00 |
April | 0.111915E+11 | 0.526359E+10 | 0.114862E+11 | 0.00 | 0.201789E+10 | 0.00 | 0.00 | 45096879.06 | 0.00 | 0.00 | 0.00 | 0.226532E+10 | 0.00 |
May | 0.115417E+11 | 0.469714E+10 | 0.119357E+11 | 0.00 | 0.129301E+10 | 0.00 | 0.00 | 92671572.43 | 0.00 | 0.00 | 0.00 | 0.228538E+10 | 0.00 |
June | 0.114030E+11 | 0.419605E+10 | 0.118862E+11 | 0.00 | 0.124830E+10 | 0.00 | 0.00 | 0.160638E+10 | 0.00 | 0.00 | 0.00 | 0.217169E+10 | 0.00 |
July | 0.112178E+11 | 0.446582E+10 | 0.115358E+11 | 0.00 | 0.121520E+10 | 0.00 | 0.00 | 0.266554E+10 | 0.00 | 0.00 | 0.00 | 0.213633E+10 | 0.00 |
August | 0.118684E+11 | 0.509147E+10 | 0.123357E+11 | 0.00 | 0.133057E+10 | 0.00 | 0.00 | 0.239687E+10 | 0.00 | 0.00 | 0.00 | 0.217264E+10 | 0.00 |
September | 0.112230E+11 | 0.576451E+10 | 0.114788E+11 | 0.00 | 0.120435E+10 | 0.00 | 0.00 | 0.902288E+09 | 0.00 | 0.00 | 0.00 | 0.208528E+10 | 0.00 |
October | 0.114789E+11 | 0.689085E+10 | 0.115432E+11 | 0.00 | 0.154955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217719E+10 | 0.00 |
November | 0.111504E+11 | 0.747491E+10 | 0.110862E+11 | 0.00 | 0.291605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215658E+10 | 0.00 |
December | 0.117495E+11 | 0.818271E+10 | 0.115358E+11 | 0.00 | 0.408227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229369E+10 | 0.00 |
Annual Sum or Average | 0.137030E+12 | 0.729161E+11 | 0.139290E+12 | 0.00 | 0.283640E+11 | 0.00 | 0.00 | 0.770885E+10 | 0.00 | 0.00 | 0.00 | 0.266588E+11 | 0.00 |
Minimum of Months | 0.105713E+11 | 0.419605E+10 | 0.105871E+11 | 0.00 | 0.120435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208528E+10 | 0.00 |
Maximum of Months | 0.120001E+11 | 0.818271E+10 | 0.123431E+11 | 0.00 | 0.451245E+10 | 0.00 | 0.00 | 0.266554E+10 | 0.00 | 0.00 | 0.00 | 0.242419E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.417057E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.287950E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.173251E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.505143E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.323953E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.164534E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.142942E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.170283E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.171103E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.321843E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144358E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.417057E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 10479.81 | 17-JAN-15:00 | 5492.60 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3501.29 | 18-JAN-17:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 10445.02 | 08-FEB-09:09 | 5492.60 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3501.29 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 10439.74 | 13-MAR-08:09 | 5492.60 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3133.16 | 06-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 10254.65 | 10-APR-08:09 | 5492.60 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2714.49 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 10032.57 | 15-MAY-08:30 | 5492.60 | 01-MAY-19:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2245.88 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 10042.80 | 05-JUN-08:09 | 5492.60 | 01-JUN-19:40 | 10112.62 | 01-JUN-07:10 | 0.00 | 1520.23 | 26-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 10049.26 | 20-JUL-08:09 | 5492.60 | 01-JUL-19:00 | 10112.62 | 01-JUL-07:10 | 0.00 | 1479.16 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 10212.44 | 29-AUG-08:20 | 5492.60 | 01-AUG-19:40 | 10112.62 | 01-AUG-07:10 | 0.00 | 4193.25 | 04-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 10264.83 | 21-SEP-08:30 | 5492.60 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 1654.82 | 29-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 10442.21 | 30-OCT-08:09 | 5492.60 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2409.03 | 24-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10480.92 | 27-NOV-15:00 | 5492.60 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2953.48 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10491.04 | 12-DEC-15:00 | 5492.60 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3501.29 | 08-DEC-17:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 10032.57 | 5492.60 | 10112.62 | 0.00 | 1479.16 | 0.00 | 0.00 | |||||
Maximum of Months | 10491.04 | 5492.60 | 10112.62 | 0.00 | 4193.25 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2896.23 | 28-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2927.48 | 16-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2922.67 | 01-MAR-12:20 | 0.00 |
April | 1588.47 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 2809.58 | 04-APR-11:00 | 0.00 |
May | 1759.13 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2615.25 | 02-MAY-11:39 | 0.00 |
June | 7714.07 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2335.64 | 01-JUN-11:00 | 0.00 |
July | 8666.38 | 03-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1973.37 | 10-JUL-11:00 | 0.00 |
August | 11904.33 | 04-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1837.82 | 01-AUG-11:00 | 0.00 |
September | 5885.50 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1834.40 | 21-SEP-11:00 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2240.78 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2528.94 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2754.06 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1834.40 | 0.00 | ||
Maximum of Months | 11904.33 | 0.00 | 0.00 | 0.00 | 2927.48 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 29852.39 | 18-JAN-16:00 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 3229.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25488.44 | 02-FEB-15:09 | 10312.36 | 10112.62 | 0.00 | 0.00 | 2623.61 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24772.28 | 01-MAR-15:50 | 10027.67 | 10112.62 | 0.00 | 0.00 | 2175.31 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24716.53 | 18-APR-14:39 | 9701.73 | 10112.62 | 0.00 | 0.00 | 1192.03 | 0.00 | 0.00 | 1483.68 | 0.00 |
May | 24505.58 | 31-MAY-14:00 | 9701.73 | 10112.62 | 0.00 | 0.00 | 1192.03 | 0.00 | 0.00 | 1692.56 | 0.00 |
June | 30300.72 | 30-JUN-14:00 | 9701.73 | 10112.62 | 0.00 | 0.00 | 1259.86 | 0.00 | 0.00 | 7442.89 | 0.00 |
July | 31563.00 | 03-JUL-14:00 | 9701.73 | 10112.62 | 0.00 | 0.00 | 1364.76 | 0.00 | 0.00 | 8601.91 | 0.00 |
August | 36596.57 | 04-AUG-14:00 | 9701.73 | 10112.62 | 0.00 | 0.00 | 4014.63 | 0.00 | 0.00 | 10998.64 | 0.00 |
September | 28382.76 | 08-SEP-14:20 | 9701.73 | 10112.62 | 0.00 | 0.00 | 1192.03 | 0.00 | 0.00 | 5607.26 | 0.00 |
October | 23958.07 | 24-OCT-08:09 | 10236.93 | 10112.62 | 0.00 | 0.00 | 1929.52 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29424.78 | 25-NOV-16:49 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 2812.09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29891.05 | 08-DEC-16:00 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 3275.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23958.07 | 9388.60 | 10112.62 | 0.00 | 0.00 | 1192.03 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36596.57 | 10312.36 | 10112.62 | 5492.60 | 0.00 | 4014.63 | 0.00 | 0.00 | 10998.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 395309.93 | 18-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 362208.43 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 315003.42 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 170974.03 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 53754.55 | 02-MAY-02:00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10302.54 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 29588.97 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 76800.04 | 24-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 289773.81 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 395309.93 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 395309.93 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.50 | 15.48 | 17.17 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
February | 48.67 | 15.69 | 15.17 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
March | 21.67 | 15.31 | 5.67 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
April | 6.50 | 15.69 | 3.00 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
May | 1.17 | 16.27 | 0.83 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
September | 0.17 | 17.20 | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
October | 1.67 | 17.12 | 1.67 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
November | 21.67 | 15.16 | 3.50 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
December | 34.83 | 15.25 | 7.17 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
Annual Sum or Average | 213.83 | 15.47 | 54.33 | 15.89 | 0.17 | 15.90 | 0.17 | 15.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.50 | 17.20 | 17.17 | 17.20 | 0.17 | 24.57 | 0.17 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.83 | 13.93 | 6.33 | 13.93 | 0.00 | 13.93 | 0.00 | 13.93 |
February | 103.83 | 14.17 | 4.17 | 14.17 | 0.00 | 14.17 | 0.00 | 14.17 |
March | 86.50 | 14.45 | 4.67 | 14.45 | 0.00 | 14.45 | 0.00 | 14.45 |
April | 43.00 | 14.71 | 3.00 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
May | 2.83 | 14.86 | 0.17 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.29 | 0.00 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
September | 0.83 | 14.96 | 0.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
October | 20.00 | 14.91 | 2.17 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
November | 78.17 | 14.34 | 3.00 | 14.34 | 0.00 | 14.34 | 0.00 | 14.34 |
December | 121.83 | 14.18 | 6.50 | 14.18 | 0.00 | 14.18 | 0.00 | 14.18 |
Annual Sum or Average | 581.83 | 14.26 | 30.17 | 14.26 | 1.67 | 14.29 | 0.00 | 14.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 0.00 | 13.93 |
Maximum of Months | 124.83 | 14.96 | 6.50 | 14.97 | 1.00 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.33 | 8.78 | 4.67 | 8.75 | 0.00 | 8.75 | 0.00 | 8.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23.17 | 7.73 | 12.83 | 7.57 | 0.00 | 7.57 | 0.00 | 7.57 |
Annual Sum or Average | 46.50 | 8.25 | 17.50 | 8.09 | 0.00 | 8.09 | 0.00 | 8.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.33 | 8.78 | 12.83 | 8.75 | 0.00 | 8.75 | 0.00 | 8.75 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.64 | 300.00 | 20.64 | 300.00 | 20.64 |
February | 276.00 | 20.62 | 276.00 | 20.62 | 276.00 | 20.62 |
March | 324.00 | 20.70 | 324.00 | 20.70 | 324.00 | 20.70 |
April | 299.00 | 20.98 | 265.83 | 20.89 | 265.83 | 20.86 |
May | 305.17 | 21.80 | 125.67 | 21.52 | 125.00 | 21.37 |
June | 169.00 | 22.97 | 162.17 | 23.33 | 66.33 | 23.33 |
July | 74.17 | 24.32 | 274.83 | 24.15 | 67.50 | 24.20 |
August | 114.00 | 24.04 | 279.00 | 24.03 | 97.00 | 24.07 |
September | 165.67 | 22.08 | 159.17 | 22.38 | 63.67 | 22.11 |
October | 300.00 | 20.84 | 269.17 | 20.77 | 269.17 | 20.74 |
November | 288.00 | 20.73 | 276.33 | 20.71 | 276.33 | 20.71 |
December | 300.00 | 20.69 | 300.00 | 20.69 | 300.00 | 20.69 |
Annual Sum or Average | 2915.00 | 21.28 | 3012.17 | 21.44 | 2430.83 | 21.31 |
Minimum of Months | 74.17 | 20.62 | 125.67 | 20.62 | 63.67 | 20.62 |
Maximum of Months | 324.00 | 24.32 | 324.00 | 24.15 | 324.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.70 | 324.00 | 15.70 | 324.00 | 15.70 |
April | 300.00 | 16.85 | 285.00 | 16.72 | 285.00 | 16.68 |
May | 310.50 | 19.61 | 224.00 | 19.37 | 222.50 | 19.26 |
June | 230.17 | 23.40 | 226.67 | 23.98 | 154.17 | 24.00 |
July | 214.83 | 26.10 | 282.50 | 26.09 | 203.33 | 26.14 |
August | 185.17 | 25.66 | 285.50 | 25.86 | 161.67 | 25.90 |
September | 182.50 | 20.55 | 211.50 | 21.63 | 107.17 | 21.13 |
October | 300.00 | 16.57 | 300.00 | 16.57 | 300.00 | 16.57 |
November | 288.00 | 15.95 | 288.00 | 15.95 | 288.00 | 15.95 |
December | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
Annual Sum or Average | 3211.17 | 18.34 | 3303.17 | 18.62 | 2921.83 | 18.42 |
Minimum of Months | 182.50 | 15.52 | 211.50 | 15.52 | 107.17 | 15.52 |
Maximum of Months | 324.00 | 26.10 | 324.00 | 26.09 | 324.00 | 26.14 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.98 | 300.00 | 9.98 | 300.00 | 9.98 |
February | 276.00 | 10.02 | 276.00 | 10.02 | 276.00 | 10.02 |
March | 324.00 | 10.39 | 324.00 | 10.39 | 324.00 | 10.39 |
April | 300.00 | 12.46 | 300.00 | 12.46 | 300.00 | 12.46 |
May | 312.00 | 16.87 | 302.33 | 16.78 | 302.33 | 16.75 |
June | 273.83 | 22.19 | 200.67 | 22.27 | 186.50 | 22.24 |
July | 200.50 | 26.47 | 280.83 | 26.33 | 190.50 | 26.42 |
August | 193.00 | 25.47 | 273.00 | 25.68 | 159.50 | 25.75 |
September | 207.00 | 20.15 | 184.17 | 20.68 | 111.00 | 20.17 |
October | 300.00 | 12.77 | 300.00 | 12.77 | 300.00 | 12.77 |
November | 288.00 | 11.00 | 288.00 | 11.00 | 288.00 | 11.00 |
December | 300.00 | 9.89 | 300.00 | 9.89 | 300.00 | 9.89 |
Annual Sum or Average | 3274.33 | 14.83 | 3329.00 | 15.03 | 3037.83 | 14.78 |
Minimum of Months | 193.00 | 9.89 | 184.17 | 9.89 | 111.00 | 9.89 |
Maximum of Months | 324.00 | 26.47 | 324.00 | 26.33 | 324.00 | 26.42 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.180277E+09 | 45096879.06 | 12.83 | 0.121157E+09 | 59120331.53 | 0.00 | 0.66 | 18-APR-15:10 | 0.00 | 01-APR-00:03 | 6545.69 | 18-APR-15:10 | 4537.45 | 18-APR-15:10 | 2101.22 | 18-APR-12:00 | 1588.47 | 18-APR-15:10 | 0.00 | 01-APR-00:03 |
May | 0.372718E+09 | 92671572.43 | 28.67 | 0.276340E+09 | 96378434.86 | 0.00 | 0.74 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 | 7027.05 | 31-MAY-17:00 | 5681.15 | 31-MAY-15:10 | 1597.87 | 31-MAY-11:10 | 1759.13 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 |
June | 0.382300E+10 | 0.897069E+09 | 176.06 | 0.272421E+10 | 0.109879E+10 | 0.00 | 1.00 | 13-JUN-15:20 | 0.00 | 01-JUN-00:10 | 24116.76 | 26-JUN-07:02 | 14836.13 | 24-JUN-07:03 | 12771.88 | 26-JUN-07:02 | 5023.38 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.627245E+10 | 0.143205E+10 | 240.67 | 0.422690E+10 | 0.204554E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 23218.46 | 20-JUL-07:03 | 13543.41 | 01-JUL-07:02 | 13591.71 | 20-JUL-07:03 | 4901.01 | 20-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.631131E+10 | 0.146212E+10 | 259.87 | 0.427447E+10 | 0.203684E+10 | 0.00 | 1.00 | 01-AUG-07:05 | 0.00 | 01-AUG-00:10 | 25680.11 | 04-AUG-07:03 | 13314.26 | 19-AUG-07:03 | 16870.24 | 04-AUG-07:03 | 5220.63 | 04-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.234220E+10 | 0.564619E+09 | 121.59 | 0.197243E+10 | 0.369768E+09 | 0.00 | 1.00 | 02-SEP-07:03 | 0.00 | 01-SEP-00:10 | 21706.67 | 11-SEP-07:03 | 12548.09 | 11-SEP-07:03 | 9158.58 | 11-SEP-07:03 | 4665.66 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.193019E+11 | 0.449362E+10 | 839.69 | 0.135955E+11 | 0.570644E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.631131E+10 | 0.146212E+10 | 259.87 | 0.427447E+10 | 0.204554E+10 | 0.00 | 1.00 | 0.00 | 25680.11 | 14836.13 | 16870.24 | 5220.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.286355E+10 | 0.709306E+09 | 72.01 | 0.184894E+10 | 0.101461E+10 | 0.00 | 1.00 | 18-JUN-15:25 | 0.00 | 01-JUN-00:10 | 48071.20 | 29-JUN-19:35 | 32925.47 | 29-JUN-17:12 | 16609.52 | 29-JUN-19:35 | 10856.52 | 28-JUN-18:05 | 0.00 | 01-JUN-00:10 |
July | 0.512607E+10 | 0.123350E+10 | 139.33 | 0.309755E+10 | 0.202852E+10 | 0.00 | 1.00 | 01-JUL-17:15 | 0.00 | 01-JUL-00:10 | 53037.96 | 03-JUL-20:05 | 34126.05 | 05-JUL-17:10 | 27762.98 | 03-JUL-20:05 | 11478.76 | 03-JUL-20:05 | 0.00 | 01-JUL-00:10 |
August | 0.382979E+10 | 0.934755E+09 | 114.04 | 0.226749E+10 | 0.156231E+10 | 0.00 | 1.00 | 01-AUG-17:15 | 0.00 | 01-AUG-00:10 | 54177.90 | 03-AUG-19:05 | 28884.75 | 04-AUG-17:10 | 30009.54 | 03-AUG-19:05 | 11661.08 | 03-AUG-19:05 | 0.00 | 01-AUG-00:10 |
September | 0.128071E+10 | 0.337669E+09 | 56.58 | 0.100138E+10 | 0.279327E+09 | 0.00 | 0.78 | 10-SEP-14:55 | 0.00 | 01-SEP-00:10 | 17006.85 | 10-SEP-14:55 | 13462.33 | 10-SEP-14:55 | 3632.40 | 11-SEP-15:10 | 4140.32 | 10-SEP-14:55 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.131001E+11 | 0.321523E+10 | 381.96 | 0.821536E+10 | 0.488476E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.512607E+10 | 0.123350E+10 | 139.33 | 0.309755E+10 | 0.202852E+10 | 0.00 | 1.00 | 0.00 | 54177.90 | 34126.05 | 30009.54 | 11661.08 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 34.96 | 222.41 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 72.68 | 171.60 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 105.83 | 102.63 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 199.97 | 66.32 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 221.90 | 38.27 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 269.99 | 35.14 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 292.03 | 37.71 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 256.00 | 43.36 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 194.00 | 62.50 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 118.03 | 75.39 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 48.01 | 127.53 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 31.10 | 198.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 154.11 | 98.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 31.10 | 35.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 292.03 | 222.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 34.96 | 222.41 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 72.68 | 171.60 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 105.83 | 102.63 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 199.97 | 66.32 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 221.90 | 38.27 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 269.99 | 35.14 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 292.03 | 37.71 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 256.00 | 43.36 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 194.00 | 62.50 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 118.03 | 75.39 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 48.01 | 127.53 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 31.10 | 198.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 154.11 | 98.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 31.10 | 35.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 292.03 | 222.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.20 | 141.75 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 2.42 | 109.96 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 16.25 | 63.71 | 0.00 | 0.00 | 0.00 |
April | 42.75 | 0.29 | 42.45 | 30.69 | 39.42 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 59.54 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 76.38 | 19.47 | 0.00 | 0.00 | 0.00 |
July | 60.94 | 4.09 | 56.85 | 70.64 | 21.01 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 59.04 | 24.36 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 37.37 | 37.04 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 18.96 | 45.54 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 5.34 | 78.85 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.10 | 123.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 31.58 | 60.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.10 | 19.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 76.38 | 141.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.20 | 141.75 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 2.42 | 109.96 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 16.25 | 63.71 | 0.00 | 0.00 | 0.00 |
April | 42.74 | 0.29 | 42.45 | 30.69 | 39.42 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 59.54 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 76.38 | 19.47 | 0.00 | 0.00 | 0.00 |
July | 60.93 | 4.09 | 56.85 | 70.64 | 21.01 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 59.04 | 24.36 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 37.37 | 37.04 | 0.00 | 0.00 | 0.00 |
October | 29.09 | 0.00 | 29.09 | 18.95 | 45.54 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 5.34 | 78.85 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.10 | 123.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 31.58 | 60.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.10 | 19.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 76.38 | 141.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.34 | 17.42 | 22.92 | 24.17 | 89.48 | 0.00 | 0.00 | 0.00 |
February | 55.42 | 27.61 | 27.82 | 46.06 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 87.48 | 41.88 | 45.60 | 95.73 | 39.21 | 10.00 | 0.00 | 0.00 |
April | 118.88 | 71.52 | 47.36 | 142.97 | 25.33 | 37.33 | 0.00 | 0.00 |
May | 142.85 | 80.38 | 62.47 | 181.53 | 17.68 | 44.83 | 0.00 | 0.00 |
June | 162.42 | 95.11 | 67.31 | 203.83 | 19.91 | 27.33 | 0.00 | 0.00 |
July | 163.68 | 100.80 | 62.87 | 200.36 | 25.64 | 16.00 | 0.00 | 0.00 |
August | 136.28 | 77.69 | 58.58 | 169.02 | 26.34 | 19.83 | 0.00 | 0.00 |
September | 105.84 | 61.48 | 44.36 | 125.81 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 67.07 | 33.19 | 33.88 | 78.76 | 31.13 | 6.33 | 0.00 | 0.00 |
November | 39.90 | 14.66 | 25.24 | 36.89 | 48.36 | 0.00 | 0.00 | 0.00 |
December | 27.29 | 13.27 | 14.02 | 16.46 | 75.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.83 | 53.04 | 42.79 | 110.47 | 41.88 | 161.67 | 0.00 | 0.00 |
Minimum of Months | 27.29 | 13.27 | 14.02 | 16.46 | 17.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.68 | 100.80 | 67.31 | 203.83 | 89.48 | 44.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 93645756.08 | 0.595707E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.175819E+09 | 0.415142E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.283465E+09 | 0.274896E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.518335E+09 | 0.171905E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.594337E+09 | 0.102492E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.699814E+09 | 91088429.10 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.782184E+09 | 0.101004E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.685675E+09 | 0.116134E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.502852E+09 | 0.162012E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.316119E+09 | 0.201915E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.124453E+09 | 0.330549E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 83294038.24 | 0.531392E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.485999E+10 | 0.309424E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 83294038.24 | 91088429.10 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.782184E+09 | 0.595707E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 93645756.08 | 0.595707E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.175819E+09 | 0.415142E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.283465E+09 | 0.274896E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.518335E+09 | 0.171905E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.594337E+09 | 0.102492E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.699814E+09 | 91088429.10 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.782184E+09 | 0.101004E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.685675E+09 | 0.116134E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.502852E+09 | 0.162012E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.316119E+09 | 0.201915E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.124453E+09 | 0.330549E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 83294038.24 | 0.531392E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.485999E+10 | 0.309424E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 83294038.24 | 91088429.10 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.782184E+09 | 0.595707E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52073982.96 | 0.00 | 52073982.96 | 543414.64 | 0.379654E+09 |
February | 59630661.61 | 0.00 | 59630661.61 | 5865375.72 | 0.266017E+09 |
March | 98960829.24 | 2684.40 | 98958144.85 | 43525295.27 | 0.170634E+09 |
April | 0.110796E+09 | 754006.91 | 0.110042E+09 | 79553973.79 | 0.102188E+09 |
May | 0.149190E+09 | 5777377.20 | 0.143413E+09 | 0.159468E+09 | 56997321.38 |
June | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.197974E+09 | 50459490.50 |
July | 0.163211E+09 | 10950639.71 | 0.152260E+09 | 0.189205E+09 | 56286504.80 |
August | 0.137186E+09 | 2858059.88 | 0.134328E+09 | 0.158131E+09 | 65247840.10 |
September | 0.101528E+09 | 67832.33 | 0.101460E+09 | 96859791.08 | 96003133.74 |
October | 77929157.78 | 0.00 | 77929157.78 | 50770611.76 | 0.121964E+09 |
November | 52753737.13 | 0.00 | 52753737.13 | 13831999.60 | 0.204390E+09 |
December | 35359907.87 | 0.00 | 35359907.87 | 255880.15 | 0.330219E+09 |
Annual Sum or Average | 0.120698E+10 | 35619645.52 | 0.117136E+10 | 0.995984E+09 | 0.190006E+10 |
Minimum of Months | 35359907.87 | 0.00 | 35359907.87 | 255880.15 | 50459490.50 |
Maximum of Months | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.197974E+09 | 0.379654E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52072306.59 | 0.00 | 52072306.59 | 543283.63 | 0.379655E+09 |
February | 59628805.47 | 0.00 | 59628805.47 | 5864709.82 | 0.266018E+09 |
March | 98957687.10 | 2684.27 | 98955002.83 | 43522403.92 | 0.170634E+09 |
April | 0.110793E+09 | 753971.57 | 0.110039E+09 | 79550817.49 | 0.102188E+09 |
May | 0.149186E+09 | 5777106.41 | 0.143409E+09 | 0.159462E+09 | 56996963.99 |
June | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.197967E+09 | 50459081.87 |
July | 0.163206E+09 | 10950126.44 | 0.152256E+09 | 0.189199E+09 | 56285965.16 |
August | 0.137182E+09 | 2857925.91 | 0.134324E+09 | 0.158126E+09 | 65247420.32 |
September | 0.101525E+09 | 67829.15 | 0.101457E+09 | 96856519.62 | 96002580.79 |
October | 77926706.53 | 0.00 | 77926706.53 | 50768054.92 | 0.121964E+09 |
November | 52751976.39 | 0.00 | 52751976.39 | 13830949.89 | 0.204390E+09 |
December | 35358789.52 | 0.00 | 35358789.52 | 255815.57 | 0.330219E+09 |
Annual Sum or Average | 0.120695E+10 | 35617975.98 | 0.117133E+10 | 0.995946E+09 | 0.190006E+10 |
Minimum of Months | 35358789.52 | 0.00 | 35358789.52 | 255815.57 | 50459081.87 |
Maximum of Months | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.197967E+09 | 0.379655E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108036E+09 | 46645566.98 | 61390854.53 | 64725936.89 | 0.239665E+09 |
February | 0.134079E+09 | 66783377.90 | 67295249.39 | 0.111436E+09 | 0.166293E+09 |
March | 0.234300E+09 | 0.112176E+09 | 0.122123E+09 | 0.256401E+09 | 0.105025E+09 |
April | 0.308145E+09 | 0.185382E+09 | 0.122763E+09 | 0.370577E+09 | 65664979.88 |
May | 0.382604E+09 | 0.215288E+09 | 0.167317E+09 | 0.486199E+09 | 47362281.50 |
June | 0.420987E+09 | 0.246514E+09 | 0.174474E+09 | 0.528328E+09 | 51595773.52 |
July | 0.438388E+09 | 0.269993E+09 | 0.168396E+09 | 0.536645E+09 | 68681991.59 |
August | 0.365005E+09 | 0.208093E+09 | 0.156911E+09 | 0.452690E+09 | 70539309.41 |
September | 0.274331E+09 | 0.159356E+09 | 0.114975E+09 | 0.326101E+09 | 95017773.63 |
October | 0.179630E+09 | 88896729.45 | 90733049.82 | 0.210948E+09 | 83385710.99 |
November | 0.103431E+09 | 38002514.34 | 65428206.71 | 95613086.80 | 0.125345E+09 |
December | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 0.202299E+09 |
Annual Sum or Average | 0.302204E+10 | 0.167268E+10 | 0.134936E+10 | 0.348375E+10 | 0.132087E+10 |
Minimum of Months | 73101035.17 | 35550117.56 | 37550917.61 | 44088187.39 | 47362281.50 |
Maximum of Months | 0.438388E+09 | 0.269993E+09 | 0.174474E+09 | 0.536645E+09 | 0.239665E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 54.24 | 712.23 | 180.96 | 57.63 | 123.32 | 0.00 | 0.00 |
February | 133.54 | 546.46 | 255.97 | 101.37 | 154.59 | 0.00 | 0.00 |
March | 238.38 | 326.89 | 322.05 | 92.44 | 229.60 | 0.00 | 0.00 |
April | 459.60 | 209.76 | 447.24 | 179.34 | 267.90 | 0.00 | 0.00 |
May | 561.32 | 117.53 | 474.13 | 149.24 | 324.90 | 0.00 | 0.00 |
June | 690.45 | 106.94 | 554.88 | 195.56 | 359.32 | 0.00 | 0.00 |
July | 723.72 | 115.82 | 579.13 | 225.48 | 353.65 | 0.00 | 0.00 |
August | 629.38 | 134.74 | 500.96 | 184.40 | 316.56 | 0.00 | 0.00 |
September | 461.37 | 197.72 | 401.73 | 153.36 | 248.36 | 0.00 | 0.00 |
October | 271.30 | 239.19 | 284.54 | 100.90 | 183.64 | 0.00 | 0.00 |
November | 100.44 | 406.50 | 176.10 | 50.29 | 125.81 | 0.00 | 0.00 |
December | 51.17 | 632.16 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Annual Sum or Average | 365.78 | 311.13 | 359.51 | 128.36 | 231.15 | 0.00 | 0.00 |
Minimum of Months | 51.17 | 106.94 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 723.72 | 712.23 | 579.13 | 225.48 | 359.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1484.36 | 8535.56 | 403.36 | 174.15 | 229.21 | 0.00 | 0.00 |
February | 2546.13 | 6390.66 | 554.23 | 276.06 | 278.17 | 0.00 | 0.00 |
March | 4668.34 | 3067.00 | 874.78 | 418.82 | 455.96 | 0.00 | 0.00 |
April | 5941.47 | 1434.19 | 1188.83 | 715.21 | 473.62 | 0.00 | 0.00 |
May | 7252.82 | 581.41 | 1428.48 | 803.79 | 624.69 | 0.00 | 0.00 |
June | 8410.57 | 599.52 | 1624.18 | 951.06 | 673.12 | 0.00 | 0.00 |
July | 8093.35 | 774.84 | 1636.75 | 1008.04 | 628.72 | 0.00 | 0.00 |
August | 6804.77 | 794.02 | 1362.77 | 776.93 | 585.84 | 0.00 | 0.00 |
September | 4904.60 | 1200.61 | 1058.38 | 614.80 | 443.58 | 0.00 | 0.00 |
October | 3108.15 | 1571.10 | 670.66 | 331.90 | 338.76 | 0.00 | 0.00 |
November | 1708.67 | 3902.70 | 399.04 | 146.61 | 252.42 | 0.00 | 0.00 |
December | 894.40 | 6434.34 | 272.93 | 132.73 | 140.20 | 0.00 | 0.00 |
Annual Sum or Average | 4662.31 | 2924.81 | 958.28 | 530.40 | 427.88 | 0.00 | 0.00 |
Minimum of Months | 894.40 | 581.41 | 272.93 | 132.73 | 140.20 | 0.00 | 0.00 |
Maximum of Months | 8410.57 | 8535.56 | 1636.75 | 1008.04 | 673.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145283E+09 | 0.190763E+10 | 0.484677E+09 | 0.154367E+09 | 0.330310E+09 | 0.00 | 0.00 |
February | 0.323048E+09 | 0.132200E+10 | 0.619234E+09 | 0.245241E+09 | 0.373992E+09 | 0.00 | 0.00 |
March | 0.638468E+09 | 0.875552E+09 | 0.862567E+09 | 0.247600E+09 | 0.614966E+09 | 0.00 | 0.00 |
April | 0.119128E+10 | 0.543690E+09 | 0.115925E+10 | 0.464862E+09 | 0.694385E+09 | 0.00 | 0.00 |
May | 0.150343E+10 | 0.314800E+09 | 0.126992E+10 | 0.399715E+09 | 0.870204E+09 | 0.00 | 0.00 |
June | 0.178965E+10 | 0.277177E+09 | 0.143825E+10 | 0.506899E+09 | 0.931352E+09 | 0.00 | 0.00 |
July | 0.193840E+10 | 0.310210E+09 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
August | 0.168573E+10 | 0.360886E+09 | 0.134177E+10 | 0.493892E+09 | 0.847878E+09 | 0.00 | 0.00 |
September | 0.119588E+10 | 0.512487E+09 | 0.104128E+10 | 0.397522E+09 | 0.643756E+09 | 0.00 | 0.00 |
October | 0.726655E+09 | 0.640636E+09 | 0.762111E+09 | 0.270243E+09 | 0.491868E+09 | 0.00 | 0.00 |
November | 0.260341E+09 | 0.105365E+10 | 0.456463E+09 | 0.130355E+09 | 0.326108E+09 | 0.00 | 0.00 |
December | 0.137045E+09 | 0.169317E+10 | 0.350817E+09 | 0.133214E+09 | 0.217603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115352E+11 | 0.981188E+10 | 0.113375E+11 | 0.404784E+10 | 0.728963E+10 | 0.00 | 0.00 |
Minimum of Months | 0.137045E+09 | 0.277177E+09 | 0.350817E+09 | 0.130355E+09 | 0.217603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193840E+10 | 0.190763E+10 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397571E+10 | 0.228616E+11 | 0.108036E+10 | 0.466456E+09 | 0.613909E+09 | 0.00 | 0.00 |
February | 0.615961E+10 | 0.154603E+11 | 0.134079E+10 | 0.667834E+09 | 0.672952E+09 | 0.00 | 0.00 |
March | 0.125037E+11 | 0.821466E+10 | 0.234300E+10 | 0.112176E+10 | 0.122123E+10 | 0.00 | 0.00 |
April | 0.154003E+11 | 0.371742E+10 | 0.308145E+10 | 0.185382E+10 | 0.122763E+10 | 0.00 | 0.00 |
May | 0.194260E+11 | 0.155724E+10 | 0.382604E+10 | 0.215288E+10 | 0.167317E+10 | 0.00 | 0.00 |
June | 0.218002E+11 | 0.155396E+10 | 0.420987E+10 | 0.246514E+10 | 0.174474E+10 | 0.00 | 0.00 |
July | 0.216772E+11 | 0.207532E+10 | 0.438388E+10 | 0.269993E+10 | 0.168396E+10 | 0.00 | 0.00 |
August | 0.182259E+11 | 0.212671E+10 | 0.365005E+10 | 0.208093E+10 | 0.156911E+10 | 0.00 | 0.00 |
September | 0.127127E+11 | 0.311199E+10 | 0.274331E+10 | 0.159356E+10 | 0.114975E+10 | 0.00 | 0.00 |
October | 0.832488E+10 | 0.420804E+10 | 0.179630E+10 | 0.888967E+09 | 0.907330E+09 | 0.00 | 0.00 |
November | 0.442888E+10 | 0.101158E+11 | 0.103431E+10 | 0.380025E+09 | 0.654282E+09 | 0.00 | 0.00 |
December | 0.239556E+10 | 0.172337E+11 | 0.731010E+09 | 0.355501E+09 | 0.375509E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.147031E+12 | 0.922368E+11 | 0.302204E+11 | 0.167268E+11 | 0.134936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239556E+10 | 0.155396E+10 | 0.731010E+09 | 0.355501E+09 | 0.375509E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218002E+11 | 0.228616E+11 | 0.438388E+10 | 0.269993E+10 | 0.174474E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104853E+10 | -977139592.7 | 0.00 | 0.00 | 744.00 | 0.00 | -71395001.2 | 59.00 | 0.00 | 0.00 |
February | 0.980044E+09 | -915643941.8 | 0.00 | 0.00 | 672.00 | 0.00 | -64400052.9 | 59.00 | 0.00 | 0.00 |
March | 0.113016E+10 | -0.105946E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -70699611.3 | 59.00 | 0.00 | 0.00 |
April | 0.101342E+10 | -946397950.8 | 0.00 | 0.00 | 720.00 | 0.00 | -67020034.8 | 59.00 | 0.00 | 0.00 |
May | 0.992060E+09 | -926240024.5 | 0.00 | 0.00 | 744.00 | 0.00 | -65819611.8 | 58.99 | 0.00 | 0.00 |
June | 0.919146E+09 | -860527430.7 | 0.00 | 0.00 | 720.00 | 0.00 | -58618659.9 | 58.98 | 0.00 | 0.00 |
July | 0.842636E+09 | -784686214.6 | 0.00 | 0.00 | 744.00 | 0.00 | -57949775.6 | 59.00 | 0.00 | 0.00 |
August | 0.879194E+09 | -820485643.8 | 0.00 | 0.00 | 744.00 | 0.00 | -58708341.1 | 59.00 | 0.00 | 0.00 |
September | 0.832989E+09 | -773207260.5 | 0.00 | 0.00 | 720.00 | 0.00 | -59781866.5 | 58.99 | 0.00 | 0.00 |
October | 0.883631E+09 | -814144402.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69486832.9 | 58.99 | 0.00 | 0.00 |
November | 0.904338E+09 | -835949612.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68388554.9 | 58.99 | 0.00 | 0.00 |
December | 0.100046E+10 | -929154881.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71309974.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114266E+11 | -0.106430E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -783578317.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.832989E+09 | -0.105946E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -71395001.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.113016E+10 | -773207260.5 | 0.00 | 0.00 | 744.00 | 0.00 | -57949775.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.95 | 0.88 | 01-JAN-10:20 | 133.19 | 9.59 | 0.00 | 39.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.94 | 0.88 | 03-FEB-10:00 | 143.06 | 9.70 | 0.00 | 73.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.92 | 0.88 | 01-MAR-08:50 | 234.69 | 12.22 | 0.00 | 179.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.91 | 0.88 | 02-APR-14:39 | 261.70 | 12.20 | 0.00 | 220.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.91 | 0.88 | 01-MAY-07:19 | 871.08 | 12.98 | 0.00 | 280.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.91 | 0.88 | 01-JUN-07:30 | 2170.42 | 13.29 | 0.00 | 295.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.91 | 0.88 | 01-JUL-07:40 | 1999.60 | 14.01 | 20.00 | 293.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.91 | 0.88 | 01-AUG-08:20 | 1203.33 | 13.41 | 14.67 | 270.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.92 | 0.88 | 01-SEP-07:30 | 231.97 | 12.10 | 0.00 | 189.83 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.93 | 0.88 | 02-OCT-09:09 | 177.52 | 10.75 | 0.00 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.94 | 0.88 | 01-NOV-09:50 | 152.10 | 10.22 | 0.00 | 65.17 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.97 | 0.88 | 13-DEC-11:30 | 86.58 | 7.45 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.92 | 779.45 | 11.94 | 34.67 | 2016.33 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.91 | 0.88 | 86.58 | 7.45 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.97 | 0.88 | 2170.42 | 14.01 | 20.00 | 295.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.89 | 0.82 | 24-JAN-14:39 | 336.14 | 23.96 | 118.17 | 29.83 | 121.26 | 21.07 | 103.50 | 0.00 |
February | 226.83 | 0.89 | 0.80 | 20-FEB-16:10 | 615.57 | 24.87 | 137.50 | 53.33 | 141.64 | 21.31 | 131.83 | 1.67 |
March | 334.33 | 0.87 | 0.80 | 03-MAR-16:10 | 385.10 | 23.52 | 198.33 | 88.83 | 281.96 | 23.89 | 216.83 | 37.17 |
April | 285.17 | 0.86 | 0.80 | 03-APR-14:09 | 454.48 | 22.96 | 164.00 | 108.50 | 445.15 | 23.84 | 219.67 | 76.67 |
May | 428.67 | 0.87 | 0.80 | 01-MAY-13:50 | 312.65 | 21.57 | 223.17 | 118.00 | 296.14 | 22.67 | 291.33 | 70.50 |
June | 400.67 | 0.85 | 0.80 | 01-JUN-16:19 | 366.60 | 22.08 | 246.00 | 163.17 | 444.92 | 23.36 | 309.17 | 96.33 |
July | 414.00 | 0.85 | 0.80 | 01-JUL-13:39 | 372.15 | 22.35 | 246.00 | 171.83 | 492.91 | 23.58 | 326.17 | 121.67 |
August | 410.83 | 0.86 | 0.80 | 01-AUG-14:30 | 371.76 | 22.15 | 240.50 | 145.33 | 386.49 | 23.15 | 284.83 | 97.33 |
September | 326.50 | 0.87 | 0.80 | 01-SEP-14:30 | 532.04 | 24.63 | 197.17 | 105.17 | 454.55 | 25.15 | 244.33 | 69.83 |
October | 325.17 | 0.88 | 0.80 | 01-OCT-14:50 | 426.92 | 24.31 | 188.50 | 69.17 | 176.40 | 23.22 | 195.17 | 19.33 |
November | 254.83 | 0.91 | 0.82 | 03-NOV-15:30 | 249.30 | 22.45 | 120.83 | 19.50 | 110.36 | 20.70 | 108.33 | 0.00 |
December | 186.17 | 0.92 | 0.83 | 02-DEC-14:30 | 208.20 | 22.07 | 68.00 | 13.17 | 88.36 | 19.40 | 34.83 | 0.00 |
Annual Sum or Average | 3807.33 | 0.87 | 386.76 | 22.96 | 2148.17 | 1085.83 | 314.58 | 22.88 | 2466.00 | 590.50 | ||
Minimum of Months | 186.17 | 0.85 | 0.80 | 208.20 | 21.57 | 68.00 | 13.17 | 88.36 | 19.40 | 34.83 | 0.00 | |
Maximum of Months | 428.67 | 0.92 | 0.83 | 615.57 | 24.87 | 246.00 | 171.83 | 492.91 | 25.15 | 326.17 | 121.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177061E+11 | 27732.44 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129760E+11 | 27732.44 | 01-FEB-01:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101675E+11 | 27732.44 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510645E+10 | 27732.44 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.923495E+09 | 27732.44 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110356E+09 | 27732.44 | 05-JUN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.540274E+09 | 27732.44 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336451E+10 | 27732.44 | 02-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.828424E+10 | 27732.44 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138199E+11 | 27732.44 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.729988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177061E+11 | 27732.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.648264E+11 | 69481.22 | 01-JAN-00:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.456635E+11 | 69481.22 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300025E+11 | 69481.22 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117531E+11 | 69481.22 | 01-APR-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.764950E+09 | 56561.47 | 02-MAY-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.420419E+09 | 34166.62 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624240E+10 | 69481.22 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286980E+11 | 69481.22 | 10-NOV-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509701E+11 | 69481.22 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648264E+11 | 69481.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242513E+12 | 219034.29 | 18-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164879E+12 | 219034.29 | 01-FEB-20:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926481E+11 | 174175.47 | 06-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207982E+11 | 96879.19 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609660E+09 | 22251.03 | 02-MAY-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226300E+10 | 26134.15 | 24-OCT-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.949371E+11 | 172523.00 | 25-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184845E+12 | 219034.29 | 08-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.803493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242513E+12 | 219034.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.180277E+09 | 0.121157E+09 | 6545.69 | 18-APR-15:10 | 4537.45 | 0.00 |
May | 0.00 | 0.00 | 0.372718E+09 | 0.276340E+09 | 7027.05 | 31-MAY-17:00 | 5598.61 | 0.00 |
June | 0.00 | 0.00 | 0.382300E+10 | 0.272421E+10 | 24116.76 | 26-JUN-07:02 | 11344.88 | 0.00 |
July | 0.00 | 0.00 | 0.627245E+10 | 0.422690E+10 | 23218.46 | 20-JUL-07:03 | 9626.75 | 0.00 |
August | 0.00 | 0.00 | 0.631131E+10 | 0.427447E+10 | 25680.11 | 04-AUG-07:03 | 8809.87 | 0.00 |
September | 0.00 | 0.00 | 0.234220E+10 | 0.197243E+10 | 21706.67 | 11-SEP-07:03 | 12548.09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193019E+11 | 0.135955E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.631131E+10 | 0.427447E+10 | 25680.11 | 12548.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.286355E+10 | 0.184894E+10 | 48071.20 | 29-JUN-19:35 | 31461.68 | 0.00 |
July | 0.00 | 0.00 | 0.512607E+10 | 0.309755E+10 | 53037.96 | 03-JUL-20:05 | 25274.99 | 0.00 |
August | 0.00 | 0.00 | 0.382979E+10 | 0.226749E+10 | 54177.90 | 03-AUG-19:05 | 24168.36 | 0.00 |
September | 0.00 | 0.00 | 0.128071E+10 | 0.100138E+10 | 17006.85 | 10-SEP-14:55 | 13462.33 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131001E+11 | 0.821536E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.512607E+10 | 0.309755E+10 | 54177.90 | 31461.68 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139604E+10 | 0.08 | 521.22 | 01-JAN-00:03 | 0.08 |
February | 0.123688E+10 | 0.08 | 521.22 | 01-FEB-00:02 | 0.08 |
March | 0.107054E+10 | 0.06 | 521.22 | 01-MAR-00:02 | 0.08 |
April | 0.432608E+09 | 0.03 | 521.22 | 01-APR-00:03 | 0.08 |
May | 23767761.18 | 0.00 | 521.22 | 01-MAY-20:00 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.131478E+09 | 0.01 | 521.22 | 15-OCT-22:00 | 0.08 |
November | 0.899214E+09 | 0.05 | 521.22 | 09-NOV-22:40 | 0.08 |
December | 0.138760E+10 | 0.08 | 521.22 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.657813E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139604E+10 | 0.08 | 521.22 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.947580E+09 | 0.64 | 1121.41 | 02-JAN-06:01 | 0.95 |
February | 0.770528E+09 | 0.56 | 1121.41 | 01-FEB-01:11 | 0.96 |
March | 0.754761E+09 | 0.46 | 1121.41 | 01-MAR-06:01 | 0.96 |
April | 0.577169E+09 | 0.31 | 1121.41 | 01-APR-05:11 | 0.95 |
May | 0.485106E+09 | 0.23 | 1121.41 | 01-MAY-05:01 | 0.95 |
June | 0.470920E+09 | 0.23 | 1121.41 | 05-JUN-06:02 | 0.95 |
July | 0.452935E+09 | 0.21 | 1121.41 | 01-JUL-07:02 | 0.94 |
August | 0.495690E+09 | 0.23 | 1121.41 | 03-AUG-06:03 | 0.93 |
September | 0.457978E+09 | 0.22 | 1121.41 | 09-SEP-07:02 | 0.94 |
October | 0.528784E+09 | 0.25 | 1121.41 | 02-OCT-06:01 | 0.95 |
November | 0.654273E+09 | 0.42 | 1121.41 | 01-NOV-06:02 | 0.95 |
December | 0.829390E+09 | 0.57 | 1121.41 | 01-DEC-06:01 | 0.95 |
Annual Sum or Average | 0.742511E+10 | 0.36 | |||
Minimum of Months | 0.452935E+09 | 0.21 | 1121.41 | 0.93 | |
Maximum of Months | 0.947580E+09 | 0.64 | 1121.41 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216883E+10 | 0.69 | 1858.66 | 01-JAN-00:08 | 0.92 |
February | 0.168907E+10 | 0.66 | 1858.66 | 01-FEB-00:02 | 0.93 |
March | 0.147258E+10 | 0.58 | 1858.66 | 01-MAR-00:02 | 0.93 |
April | 0.100811E+10 | 0.43 | 1858.66 | 01-APR-19:03 | 0.92 |
May | 0.784133E+09 | 0.23 | 1513.05 | 02-MAY-02:53 | 0.92 |
June | 0.777377E+09 | 0.23 | 1770.22 | 29-JUN-17:12 | 0.89 |
July | 0.762268E+09 | 0.22 | 1858.66 | 03-JUL-17:10 | 0.90 |
August | 0.802033E+09 | 0.22 | 1858.66 | 03-AUG-17:12 | 0.90 |
September | 0.746377E+09 | 0.23 | 1291.85 | 29-SEP-06:01 | 0.77 |
October | 0.889288E+09 | 0.40 | 1858.66 | 24-OCT-06:01 | 0.92 |
November | 0.136257E+10 | 0.54 | 1858.66 | 10-NOV-02:62 | 0.92 |
December | 0.186528E+10 | 0.67 | 1858.66 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.143279E+11 | 0.42 | |||
Minimum of Months | 0.746377E+09 | 0.22 | 1291.85 | 0.77 | |
Maximum of Months | 0.216883E+10 | 0.69 | 1858.66 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.947580E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.770528E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.754761E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.622266E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.577778E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136799E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188498E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.195781E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.102260E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.528784E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.654273E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.829390E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.119187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.528784E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.195781E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.216883E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168907E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147258E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.100811E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.784133E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148668E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.199577E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.173679E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.108405E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.889288E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.136257E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.186528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.175431E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.784133E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.216883E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.947580E+09 | 0.00 | 0.177061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.770528E+09 | 0.00 | 0.129760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754761E+09 | 0.00 | 0.101675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.577169E+09 | 0.180277E+09 | 0.510645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485106E+09 | 0.372718E+09 | 0.923495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.470920E+09 | 0.382300E+10 | 0.110356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452935E+09 | 0.627245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.495690E+09 | 0.631131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457978E+09 | 0.234220E+10 | 0.540274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.528784E+09 | 0.00 | 0.336451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.654273E+09 | 0.00 | 0.828424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.829390E+09 | 0.00 | 0.138199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742511E+10 | 0.193019E+11 | 0.729988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.452935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.947580E+09 | 0.631131E+10 | 0.177061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.216883E+10 | 0.00 | 0.648264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168907E+10 | 0.00 | 0.456635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147258E+10 | 0.00 | 0.300025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100811E+10 | 0.00 | 0.117531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.784133E+09 | 0.00 | 0.764950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.777377E+09 | 0.284653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.762268E+09 | 0.499965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802033E+09 | 0.381282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746377E+09 | 0.128071E+10 | 0.420419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.889288E+09 | 0.00 | 0.624240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136257E+10 | 0.00 | 0.286980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186528E+10 | 0.00 | 0.509701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143279E+11 | 0.129397E+11 | 0.239341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216883E+10 | 0.499965E+10 | 0.648264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.947580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.770528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.577169E+09 | 0.00 | 0.00 | 0.00 | 45096879.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485106E+09 | 0.00 | 0.00 | 0.00 | 92671572.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.470920E+09 | 0.00 | 0.00 | 0.00 | 0.897069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452935E+09 | 0.00 | 0.00 | 0.00 | 0.143205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.495690E+09 | 0.00 | 0.00 | 0.00 | 0.146212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457978E+09 | 0.00 | 0.00 | 0.00 | 0.564619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.528784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.654273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.829390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742511E+10 | 0.00 | 0.00 | 0.00 | 0.449362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.452935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.947580E+09 | 0.00 | 0.00 | 0.00 | 0.146212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.216883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.784133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.777377E+09 | 0.00 | 0.00 | 0.00 | 0.709306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.762268E+09 | 0.00 | 0.00 | 0.00 | 0.123350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802033E+09 | 0.00 | 0.00 | 0.00 | 0.934755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746377E+09 | 0.00 | 0.00 | 0.00 | 0.337669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.889288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143279E+11 | 0.00 | 0.00 | 0.00 | 0.321523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216883E+10 | 0.00 | 0.00 | 0.00 | 0.123350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1812747.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377569E+10 | 0.00 | 0.00 | 0.12 |
February | 3323394.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293573E+10 | 0.00 | 0.00 | 0.13 |
March | 13516569.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238911E+10 | 0.00 | 0.00 | 0.13 |
April | 0.168651E+09 | 25416698.04 | 51160.11 | 21542.43 | 6201306.99 | 0.144226E+10 | 28095120.35 | 520.18 | 0.13 |
May | 0.567812E+09 | 33487192.93 | 0.00 | 123817.05 | 336119.62 | 0.233003E+09 | 94178185.98 | 0.00 | 0.15 |
June | 0.218235E+09 | 0.459099E+09 | 0.00 | 1866442.76 | 3219.61 | 23154337.25 | 0.672032E+09 | 0.00 | 0.32 |
July | 8341508.94 | 0.760455E+09 | 0.00 | 2484000.12 | 0.00 | 0.00 | 0.575708E+09 | 0.00 | 0.36 |
August | 7525282.63 | 0.748651E+09 | 0.00 | 2661899.73 | 13363.28 | 0.00 | 0.660673E+09 | 0.00 | 0.41 |
September | 0.291411E+09 | 0.153895E+09 | 0.00 | 1825624.82 | 0.00 | 0.200939E+09 | 0.787992E+09 | 0.00 | 0.27 |
October | 0.197860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122565E+10 | 0.00 | 0.00 | 0.12 |
November | 88717788.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205267E+10 | 0.00 | 0.00 | 0.12 |
December | 3769241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315740E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.157098E+10 | 0.218100E+10 | 51160.11 | 8983326.91 | 6554009.50 | 0.174356E+11 | 0.281868E+10 | 520.18 | 0.20 |
Minimum of Months | 1812747.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.567812E+09 | 0.760455E+09 | 51160.11 | 2661899.73 | 6201306.99 | 0.377569E+10 | 0.787992E+09 | 520.18 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126204E+11 | 0.00 | 0.00 | 0.17 |
February | 0.487318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903696E+10 | 0.00 | 0.00 | 0.18 |
March | 0.122231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570687E+10 | 0.00 | 0.00 | 0.19 |
April | 0.249621E+10 | 0.00 | 0.00 | 0.00 | 0.113675E+09 | 0.191478E+10 | 0.00 | 0.00 | 0.18 |
May | 0.207974E+10 | 0.00 | 0.00 | 0.00 | 46019066.43 | 47165909.51 | 0.00 | 0.00 | 0.18 |
June | 0.206833E+10 | 0.403474E+09 | 0.00 | 269251.31 | 13215824.09 | 0.00 | 0.149338E+09 | 0.00 | 0.21 |
July | 0.123409E+10 | 0.682565E+09 | 0.00 | 1791590.15 | 326311.98 | 0.00 | 0.903374E+09 | 0.00 | 0.24 |
August | 0.147268E+10 | 0.646341E+09 | 0.00 | 1334619.73 | 1610228.01 | 0.00 | 0.762274E+09 | 0.00 | 0.24 |
September | 0.259447E+10 | 0.118545E+09 | 0.00 | 526893.79 | 1479008.38 | 36231422.42 | 0.289997E+09 | 0.00 | 0.19 |
October | 0.305450E+10 | 0.00 | 0.00 | 0.00 | 6302278.99 | 0.418056E+09 | 0.00 | 0.00 | 0.17 |
November | 0.135032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491253E+10 | 0.00 | 0.00 | 0.17 |
December | 0.244412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995039E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.184560E+11 | 0.185092E+10 | 0.00 | 3922354.99 | 0.182628E+09 | 0.446434E+11 | 0.210498E+10 | 0.00 | 0.19 |
Minimum of Months | 0.151559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.305450E+10 | 0.682565E+09 | 0.00 | 1791590.15 | 0.113675E+09 | 0.126204E+11 | 0.903374E+09 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.337001E+12 | 0.243813E+12 | 0.00 | 0.165495E+11 | 0.920094E+11 |
February | 0.417676E+12 | 0.171305E+12 | 0.00 | 0.124633E+11 | 0.644318E+11 |
March | 0.715713E+12 | 0.117552E+12 | 0.00 | 0.933182E+10 | 0.404327E+11 |
April | 0.888262E+12 | 0.492202E+11 | 0.00 | 0.590466E+10 | 0.130819E+11 |
May | 0.106429E+13 | 0.192595E+11 | 0.00 | 0.294218E+10 | 0.140682E+10 |
June | 0.112704E+13 | 0.220759E+11 | 0.00 | 0.225743E+10 | 0.834710E+10 |
July | 0.115455E+13 | 0.307350E+11 | 0.00 | 0.127522E+10 | 0.140641E+11 |
August | 0.998961E+12 | 0.373316E+11 | 0.00 | 0.151053E+10 | 0.125380E+11 |
September | 0.687317E+12 | 0.466312E+11 | 0.00 | 0.392948E+10 | 0.499392E+10 |
October | 0.477068E+12 | 0.442032E+11 | 0.00 | 0.488977E+10 | 0.515837E+10 |
November | 0.248399E+12 | 0.121995E+12 | 0.00 | 0.840424E+10 | 0.391839E+11 |
December | 0.155991E+12 | 0.192644E+12 | 0.00 | 0.133560E+11 | 0.722079E+11 |
Annual Sum or Average | 0.827227E+13 | 0.109677E+13 | 0.00 | 0.828141E+11 | 0.367856E+12 |
Minimum of Months | 0.155991E+12 | 0.192595E+11 | 0.00 | 0.127522E+10 | 0.140682E+10 |
Maximum of Months | 0.115455E+13 | 0.243813E+12 | 0.00 | 0.165495E+11 | 0.920094E+11 |