Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 10:44:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 347.76 | 71.92 | 71.92 |
Net Site Energy | 347.76 | 71.92 | 71.92 |
Total Source Energy | 1096.96 | 226.87 | 226.87 |
Net Source Energy | 1096.96 | 226.87 | 226.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 91.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 345.65 | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 91.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 91.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 23.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 31.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.68 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 71.49 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 31.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.68 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 71.49 | 0.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 345.650 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 345.650 | 100.00 |
Total On-Site and Utility Electric Sources | 345.650 | 100.00 |
Total Electricity End Uses | 345.650 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2007.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:44 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.0858 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3435 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.0858 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3435 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3435 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JAN-16:00 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 23241.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 302.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8876.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1957.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1602.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28266.55 | 23241.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 23241.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 302.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8876.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1957.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1602.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 288.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1094.67 | 2.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 59.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 226.40 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 59.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 226.40 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.977055 |
ZONE2 FINE STORAGE DIRECT AIR | 2.05 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39235.43 |
PSZ-OFFICE HEATING COIL | 24121.13 |
PSZ-FINE STORAGE HEATING COIL | 65301.61 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 27659.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.977055 | 0.977055 | 0.977055 | 0.977055 | 0.977055 | 0.977055 | 1.00 | 1.00 | 0.977055 |
PSZ-FINE STORAGE | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 1.00 | 1.000000 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.977055 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.05 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.977055 | 1081.75 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.05 | 2188.80 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.977055 | 0.977055 | 0.977055 | 0.977055 | 16774.92 | 24121.13 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.05 | 2.05 | 2.05 | 1.35 | 42752.16 | 65301.61 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.977050 | 0.488527 | 0.651367 | 16774.92 | 8387.46 | 0.800480 | 0.800480 |
PSZ-FINE STORAGE COOLING COIL | 2.05 | 1.02 | 1.36 | 42752.16 | 21376.08 | 0.759190 | 0.759190 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.086 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.160 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1441.602 | 6.086 | 113.078 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1441.602 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4232_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.405 | 2.405 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.4232_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.405 | 2.405 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.4232_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.405 | 2.405 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.4232_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.405 | 2.405 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.99101E-002 | 0.16139 | 0.62044 | 0.62044 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.99101E-002 | 0.16139 | 0.62044 | 0.62044 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.99101E-002 | 0.16139 | 0.62044 | 0.62044 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.99101E-002 | 0.16139 | 0.62044 | 0.62044 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4083E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2157E-003 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2544E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3238E-003 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2358E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3020E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5848E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1816E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5202E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4828E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1339E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3465E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4304E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.0917E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7680E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3855E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6085E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9291E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.7452E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2686E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1867E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1428E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2141E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2648E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1536E-003 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5956E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0673E-003 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7205E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7071E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2708E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0450E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8226E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3023E-003 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1188E-004 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3895E-003 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1703E-004 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5134E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9260E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2695E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9692E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6396E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3194E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6372E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5652E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2920E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9104E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9222E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6649E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3839E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3972E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6339E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6511E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5628E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9575E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8087E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6800E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9436E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1469E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3297E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2026E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9531E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0082E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0163E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4709E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7178E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3336E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8657E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4905E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3340E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0000E-004 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9079E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.6039E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4115E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0933E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0735E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4731E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3510E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1686E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0829E-003 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6211E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2747E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9129E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2826E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2488E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9545E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5494E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6852E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3565E-004 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0966E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3049E-004 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4323E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7796E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0606E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8119E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8659E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7814E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5512E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8258E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0239E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2618E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6059E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2057E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4245E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8303E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0681E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3813E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8794E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7616E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5928E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6608E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0095E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6895E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7927E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4489E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4291E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2845E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5181E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8273E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1350E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2525E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8810E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4329E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4643E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7806E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3069E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5551E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3781E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6871E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6561E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3174E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6525E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8401E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7717E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1220E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4077E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3769E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9618E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2669E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8282E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3421E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4732E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0889E-004 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3503E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7372E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9357E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0937E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9294E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1256E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8639E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0203E-004 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0293E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7347E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6616E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7722E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4435E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1363E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4336E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9861E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3296E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3747E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8813E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2678E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9542E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5290E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8418E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5114E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5939E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5245E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9314E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0019E-003 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1010E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8851E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9046E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2604E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5435E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5784E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2440E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5055E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0140E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2959E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8048E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2591E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2647E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6002E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2558E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6090E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1222E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6895E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4461E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0571E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9813E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3254E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0933E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4601E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0292E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4179E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2668E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8581E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9167E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6439E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6715E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8667E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6988E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5738E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8561E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8668E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7823E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1663E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5059E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0764E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2932E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6993E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7854E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9061E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3526E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5016E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7088E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4728E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1832E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9748E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2542E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9089E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3669E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5793E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1335E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3046E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2400E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8527E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9941E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6221E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5409E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1494E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5028E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0438E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1714E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3801E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4248E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2491E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7230E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3135E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7208E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8829E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3561E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8689E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8036E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6100E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7489E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4037E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8171E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5652E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5798E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9796E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9725E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4370E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7008E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1427E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4867E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5783E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9778E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6189E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0592E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2591E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7973E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0818E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7018E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6691E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9837E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7216E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0450E-004 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4397E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2842E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1906E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1770E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2457E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0347E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8911E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7802E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3142E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2622E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3325E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3924E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7331E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3720E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3366E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1778E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5102E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4940E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6128E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8861E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5924E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1876E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9344E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8109E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9620E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3131E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6558E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7122E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4903E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4791E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3020E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0702E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7539E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9904E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2504E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6374E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3643E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1355E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1610E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8663E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4044E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1180E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8833E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3453E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9665E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7269E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8189E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4065E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3076E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4484E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0461E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5303E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5601E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1948E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2837E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0034E-004 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3469E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0273E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2098E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5178E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0338E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7818E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8237E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5654E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9997E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6853E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0452E-004 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9739E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5891E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5325E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9160E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5647E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8133E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5191E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6474E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8551E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5692E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7317E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2863E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0667E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3168E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1916E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2086E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2207E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7627E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.3590E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4277E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.0232E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1486E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7868E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7938E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1762E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4413E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9387E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.1830E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3667E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.8630E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3423E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1395E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4070E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1005E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2271E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3095E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7609E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.4521E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3365E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2519E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0396E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2247E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2823E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7596E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.5265E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3378E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2518E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9712.67971 | 11655.21565 | 0.81421 | 0.97705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 30.64733 | 8.23245E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7058.47590 | 8470.17108 | 0.20168 | 0.24202 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 26085.72829 | 31302.87395 | 1.70460 | 2.04552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 14109.27483 | 16931.12979 | 0.33994 | 0.42471 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 23049.25692 | 27659.10830 | 0.57385 | 0.97684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14634.75 | 0.97705 | 0.97705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7547.77 | 0.24202 | 0.24202 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 38025.65 | 2.04552 | 2.04552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 18257.59 | 0.42471 | 0.42471 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97705 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.04552 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39235.42941 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 27659.10830 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97705 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97705 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97705 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97705 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97705 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.97705 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.04552 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.04552 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.04552 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04552 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.04552 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.04552 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.97705 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.04552 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97705 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97705 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1081.75452 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97705 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97705 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97705 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97705 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97705 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48853 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65137 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16774.92000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8387.46000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80048 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80048 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16774.92000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24121.13291 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24121.13291 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.04552 |
45 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.04552 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2188.79799 |
47 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.04552 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.04552 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.04552 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35004 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.04552 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02276 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36368 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42752.16000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21376.08000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75919 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75919 |
58 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42752.16000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65301.61251 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 65301.61251 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16016.7 | 12.25 | 11.97 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 41163.5 | 11.74 | 11.48 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.1875593804E-002 | 1.6913382349E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 3.2628794239E-002 | 3.0849572008E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.0291583691E-002 | 1.9503244646E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7608.64 | 312.49 | 0.00 | 56.60 | 47.43 | 8025.21 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.4232_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.405 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.4232_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.405 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.4232_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.405 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.4232_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.405 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.553 | 0.529 | 0.530 | |||||||||||||||||
North Total or Average | 6.51 | 2.405 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.729 | 0.552 | 0.553 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.393 | 1.760 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.0858 | 236.88 | 1441.60 | LightsWired | LTG_SCH_OFFICE | 47.92 | 168.00 | 39.84 | 0.0000 | Y | 10.78 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 23.01 | 0.0000 | Y | 40.24 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 20.80 | 0.0000 | Y | 39.99 |
Interior Lighting Total | 4.3435 | 4835.13 | 21001.18 | 91.01 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1441.60 | 418.06 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1441.60 | 144.16 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 42.14 | 42.14 | 0.74 | |
EXTERIOR_LIGHTS_B | 4307.58 | AstronomicalClock | - | 83.75 | 62.95 | 50.90 | |
EXTERIOR_LIGHTS_C | 1091.85 | AstronomicalClock | - | 83.75 | 48.95 | 10.03 | |
Exterior Lighting Total | 5492.60 | 61.67 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16774.92 | 13427.99 | 3346.93 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42752.16 | 32457.01 | 10295.15 | 0.76 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16016.7 | 12.25 | 11.97 | ||||
PSZ-FINE STORAGE COOLING COIL | 41163.5 | 11.74 | 11.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39235.43 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24121.13 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 65301.61 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1081.75 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.05 | 2188.80 | 1070.05 | 1.00 | 1.31 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9712.68 | 11655.22 | 49.20 | 0.814 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 23.90 | 23.90 | 0.00831 | 30.65 | 0.00823 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 26085.73 | 31302.87 | 22.46 | 1.705 | 2.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00840 | 31.30 | 0.00823 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 31.47 | 0.00830 | 31.30 | 0.00823 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7058.48 | 8470.17 | 35.76 | 0.202 | 0.242 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00785 | 3.80 | 0.00506 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 14109.27 | 16931.13 | 12.15 | 0.340 | 0.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00681 | 3.80 | 0.00506 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 23049.26 | 27659.11 | 8.63 | 0.574 | 0.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00581 | 3.80 | 0.00506 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.98 | 0.98 | 0.24 | 0.24 | 0.9771 | 0.9771 | 0.9771 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.05 | 2.05 | 0.42 | 0.42 | 2.0455 | 2.0455 | 2.0455 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39235.429 | 39235.429 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 39235.43 | 39235.43 | 0.976836 | 10.00 | 7.82 | 0.00581076 | 43.33 | 21.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00581076 | 74.9469 | 27659.11 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16774.920 | 13427.988 | 0.977050 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 8387.46 | 7988.09 | 0.651367 | 25.54 | 16.57 | 0.00830248 | 12.00 | 11.09 | 0.00800000 | 30.77 | 0.00823264 | 18.27 | 15.7031 | 23.90 | 0.00831065 | 44.1859 | 9708.92 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24121.133 | 24121.133 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 24121.13 | 24121.13 | 0.977055 | 19.21 | 13.58 | 0.00756024 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.4687 | 21.10 | 0.00785277 | 49.5299 | 7058.48 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 42752.160 | 32457.012 | 2.045520 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 21376.08 | 20339.33 | 1.363680 | 28.54 | 17.65 | 0.00836888 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00823349 | 18.45 | 31.1445 | 26.70 | 0.00840436 | 37.8233 | 26084.12 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 65301.613 | 65301.613 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 65301.61 | 65301.61 | 2.045515 | 13.12 | 9.94 | 0.00643934 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.7630 | 15.56 | 0.00680120 | 60.8392 | 13864.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39235.429 | 39235.429 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.15440386 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 39235.43 | 39235.43 | 1.0000 | 1.15440386 | 0.976836 | 10.00 | 7.82 | 0.00581076 | 24688.2 | 43.33 | 21.93 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39235.43 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00581076 | 10.00 | 0.00581076 | 74.9469 | 27659.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16774.920 | 13427.988 | 0.977050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2739 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.977055 | 1.15466226 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | Sensible | 8387.46 | 7988.09 | 1.0000 | 0.76977123 | 0.651367 | 25.54 | 16.57 | 0.00830248 | 46818.1 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8387.46 | 30.77 | 0.00823264 | 18.27 | 0.10228460 | 15.7031 | 23.90 | 0.00831065 | 23.90 | 0.00831065 | 44.1859 | 9708.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24121.133 | 24121.133 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.977055 | 1.15466226 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 24121.13 | 24121.13 | 1.0000 | 1.15466226 | 0.977055 | 19.21 | 13.58 | 0.00756024 | 38481.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24121.13 | 3.80 | 0.00505843 | 3.80 | 0.10228460 | 10.4687 | 21.01 | 0.00785277 | 21.10 | 0.00785277 | 49.5299 | 7058.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42752.160 | 32457.012 | 2.045520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3973 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.045515 | 2.41734626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 21376.08 | 20339.33 | 1.0000 | 1.61156793 | 1.363680 | 28.54 | 17.65 | 0.00836888 | 50053.9 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21376.08 | 31.30 | 0.00823349 | 18.45 | 0.42471127 | 31.1445 | 26.70 | 0.00840436 | 26.70 | 0.00840436 | 37.8233 | 26084.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65301.613 | 65301.613 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.045515 | 2.41734626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 65301.61 | 65301.61 | 1.0000 | 2.41734626 | 2.045515 | 13.12 | 9.94 | 0.00643934 | 29441.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65301.61 | 3.80 | 0.00505843 | 3.80 | 0.42471127 | 20.7630 | 15.56 | 0.00680120 | 15.56 | 0.00680120 | 60.8392 | 13864.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 0.98 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
ZONE1 OFFICE | ZONE1_OFFICE_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
ZONE2 FINE STORAGE | ZONE2_FINE_STORAGE_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1586.50 | 2100.50 | 426.33 |
ZONE2 FINE STORAGE | 2233.00 | 2650.33 | 1395.17 |
ZONE3 BULK STORAGE | 2478.33 | 2915.83 | 1908.67 |
Facility | 2815.17 | 3059.17 | 2007.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.33 | 0.00 | 0.33 | 0.00 |
ZONE2 FINE STORAGE | 0.33 | 3.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 3.17 | 0.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.48 | 12.75 | 1010.76 | 1.140 | 0.399 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.31 | 30.00 | 2953.02 | 0.539 | 0.178 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.30 | 69.00 | 35277.63 | 0.000 | 0.115 | 0.000 | 0.043 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.48 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.31 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.30 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.48 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.072 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.31 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.30 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.09 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.474 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 4085700.05 | 0.00 | 4085700.05 | 1849054.15 | 5934754.20 | 2577844.23 | 5717.75 | 1156.16 | 1886.09 | 0.00 |
ZONE2 FINE STORAGE | 5685399.11 | 0.00 | 5685399.11 | 4130661.33 | 9816060.43 | 13393694.68 | 5714.79 | 2414.00 | 631.21 | 17.37 |
ZONE3 BULK STORAGE | 0.00 | 10269953.54 | 10269953.54 | 25131564.63 | 35401518.17 | 30805497.77 | 8700.17 | 6.67 | 53.17 | 4402.83 |
Total Facility | 9771099.16 | 10269953.54 | 20041052.69 | 31111280.11 | 51152332.80 | 46777036.68 | 8713.83 | 2563.25 | 2078.71 | 4404.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.3121 | 0.0000 | 0.3121 | 0.1096 | 0.4217 | 0.0952 | 593.75 | 1156.16 | 1886.09 |
ZONE2 FINE STORAGE | 0.4305 | 0.0000 | 0.4305 | 0.1429 | 0.5733 | 0.4247 | 606.00 | 2414.00 | 616.00 |
ZONE3 BULK STORAGE | 0.0000 | 0.4130 | 0.4130 | 1.1039 | 1.5169 | 0.9768 | 3587.50 | 5.33 | 43.17 |
Total Facility | 0.7426 | 0.4130 | 1.1556 | 1.3564 | 2.5120 | 1.4967 | 3589.83 | 2561.92 | 2053.51 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 5706092.00 | 0.00 | 5706092.00 | 2577844.23 | 5715.83 | 0.00 | 3044.17 | 0.00 |
PSZ-FINE STORAGE | 7940232.95 | 0.00 | 7940232.95 | 13393694.68 | 5714.38 | 0.00 | 3045.62 | 17.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.4359 | 0.0000 | 0.4359 | 0.0952 | 591.83 | 0.00 | 3044.17 |
PSZ-FINE STORAGE | 0.6012 | 0.0000 | 0.6012 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 1041.45 | 849.89 | 0.00 | 0.00 | 0.00 | 1155.16 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 459.21 | 200.69 | 0.00 | 0.00 | 0.00 | 2387.64 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.9556 | 0.5112 | 0.0000 | 0.0000 | 0.0000 | 0.1352 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.3203 | 0.9228 | 0.0000 | 0.0000 | 0.0000 | 0.5933 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 430 |
Defaulted Fields | 389 |
Fields with Defaults | 1172 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
Electricity:Building | 227.52 | 1123.07 | 12-MAR-14:30 | 18912.07 | 02-JAN-16:50 |
Electricity:Zone:ZONE1 OFFICE | 39.95 | 585.18 | 19-FEB-15:50 | 2643.62 | 02-JAN-16:50 |
Electricity:SpaceType:GENERAL | 227.52 | 1123.07 | 12-MAR-14:30 | 18912.07 | 02-JAN-16:50 |
InteriorLights:Electricity | 91.01 | 653.19 | 12-MAR-14:30 | 8876.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.78 | 115.30 | 19-FEB-15:50 | 808.57 | 02-JAN-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 91.01 | 653.19 | 12-MAR-14:30 | 8876.89 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 91.01 | 653.19 | 12-MAR-14:30 | 8876.89 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.78 | 115.30 | 19-FEB-15:50 | 808.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 91.01 | 653.19 | 12-MAR-14:30 | 8876.89 | 02-JAN-16:50 |
Electricity:Zone:ZONE2 FINE STORAGE | 40.24 | 256.14 | 01-JAN-11:50 | 4030.92 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 40.24 | 256.14 | 01-JAN-11:50 | 4030.92 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 40.24 | 256.14 | 01-JAN-11:50 | 4030.92 | 18-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 147.34 | 281.75 | 01-JAN-08:50 | 12426.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 39.99 | 281.75 | 01-JAN-08:50 | 4226.27 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 39.99 | 281.75 | 01-JAN-08:50 | 4226.27 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 23.58 | 0.00 | 01-JAN-00:10 | 2061.61 | 09-JAN-07:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
ElectricityPurchased:Plant | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
Cogeneration:ElectricityPurchased | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
General:Cogeneration:ElectricityPurchased | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
ElectricityNet:Plant | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
Cogeneration:ElectricityNet | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
General:Cogeneration:ElectricityNet | 345.65 | 1606.07 | 12-MAR-14:30 | 28266.55 | 14-JAN-17:00 |
Electricity:HVAC | 31.93 | 0.00 | 01-JAN-00:10 | 9831.98 | 16-OCT-11:10 |
General:Fans:Electricity | 23.58 | 0.00 | 01-JAN-00:10 | 2061.61 | 09-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.36 | 0.00 | 01-JAN-00:10 | 7874.71 | 16-OCT-11:10 |
General:Cooling:Electricity | 8.36 | 0.00 | 01-JAN-00:10 | 7874.71 | 16-OCT-11:10 |
ExteriorLights:Electricity | 61.67 | 0.00 | 01-JAN-07:00 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.67 | 0.00 | 01-JAN-07:00 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 24.52 | 483.00 | 01-JAN-00:10 | 1797.90 | 30-JAN-12:20 |
WaterSystems:Electricity | 24.52 | 483.00 | 01-JAN-00:10 | 1797.90 | 30-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 24.52 | 483.00 | 01-JAN-00:10 | 1797.90 | 30-JAN-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2.11 | 0.00 | 01-JAN-00:10 | 23241.87 | 09-JAN-07:10 |
NaturalGas:HVAC | 2.11 | 0.00 | 01-JAN-00:10 | 23241.87 | 09-JAN-07:10 |
Heating:NaturalGas | 2.11 | 0.00 | 01-JAN-00:10 | 23241.87 | 09-JAN-07:10 |
General:Heating:NaturalGas | 2.11 | 0.00 | 01-JAN-00:10 | 23241.87 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 101.36 | 0.00 | 01-JAN-00:10 | 48091.17 | 31-JUL-14:20 |
EnergyTransfer:Building | 61.50 | 0.00 | 01-JAN-00:10 | 20004.78 | 16-OCT-12:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 28.14 | 0.00 | 01-JAN-00:10 | 13064.54 | 03-JAN-07:10 |
Heating:EnergyTransfer | 4.77 | 0.00 | 01-JAN-00:10 | 18796.15 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.27 | 0.00 | 01-JAN-00:10 | 13064.54 | 03-JAN-07:10 |
General:Heating:EnergyTransfer | 4.77 | 0.00 | 01-JAN-00:10 | 18796.15 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.27 | 0.00 | 01-JAN-00:10 | 13064.54 | 03-JAN-07:10 |
Cooling:EnergyTransfer | 56.73 | 0.00 | 01-JAN-00:10 | 20004.78 | 16-OCT-12:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 24.88 | 0.00 | 01-JAN-00:10 | 9714.94 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer | 56.73 | 0.00 | 01-JAN-00:10 | 20004.78 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 24.88 | 0.00 | 01-JAN-00:10 | 9714.94 | 16-OCT-11:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 33.36 | 0.00 | 01-JAN-00:10 | 14251.44 | 23-JUL-14:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.50 | 0.00 | 01-JAN-00:10 | 10703.22 | 03-JAN-03:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.50 | 0.00 | 01-JAN-00:10 | 10703.22 | 03-JAN-03:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 31.85 | 0.00 | 01-JAN-00:10 | 14251.44 | 23-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 31.85 | 0.00 | 01-JAN-00:10 | 14251.44 | 23-JUL-14:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 39.86 | 0.00 | 01-JAN-00:10 | 29486.50 | 17-AUG-14:00 |
HeatingCoils:EnergyTransfer | 1.45 | 0.00 | 01-JAN-00:10 | 17363.26 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 38.41 | 0.00 | 01-JAN-00:10 | 29486.50 | 17-AUG-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 3.265 | -24.878 | 0.000 | 0.000 | 9.352 | 10.781 | 29.165 | 10.147 | 0.000 | 0.231 | 0.000 | 0.000 | -6.200 | 0.000 | -13.643 | -18.219 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.504 | -31.854 | 0.000 | 0.000 | 21.678 | 40.239 | 0.000 | 73.665 | 0.000 | 0.258 | 0.002 | 0.000 | -16.500 | 0.000 | -31.491 | -57.499 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 51.550 | 39.994 | 107.344 | 646.590 | 0.000 | 5.384 | 0.030 | 0.000 | -114.662 | 0.000 | -227.545 | -508.655 |
Total Facility | 0.000 | 0.000 | 4.769 | -56.732 | 0.000 | 0.000 | 82.579 | 91.014 | 136.508 | 730.401 | 0.000 | 5.874 | 0.032 | 0.000 | -137.362 | 0.000 | -272.679 | -584.372 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 29-APR-07:03 | 0.00 | 0.00 | 0.00 | -18797.43 | 0.00 | 0.00 | 817.68 | 707.08 | 1835.05 | 0.00 | 0.00 | 0.00 | 15563.55 | 0.00 | -74.76 | 0.00 | -51.18 | 0.00 |
ZONE2 FINE STORAGE | 04-JUL-17:12 | 0.00 | 0.00 | 0.00 | -28684.70 | 0.00 | 0.00 | 0.00 | 390.24 | 0.00 | 1764.11 | 0.00 | 0.00 | 27105.75 | 0.00 | -0.00 | 0.00 | -575.41 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JUL-17:12 | 0.00 | 0.00 | 0.00 | -28684.70 | 0.00 | 0.00 | 0.00 | 837.56 | 469.88 | 23913.15 | 0.00 | 0.00 | 8361.51 | 0.00 | 0.00 | 0.00 | -4897.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-JAN-07:01 | 0.00 | 0.00 | 24376.06 | 0.00 | 0.00 | 0.00 | 266.07 | 429.41 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -344.50 | 0.00 | -4113.81 | -21530.75 |
ZONE2 FINE STORAGE | 03-JAN-06:10 | 0.00 | 0.00 | 34867.38 | 0.00 | 0.00 | 0.00 | 353.09 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1297.59 | 0.00 | -1414.18 | -33020.97 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-JAN-07:02 | 0.00 | 0.00 | 55979.57 | 0.00 | 0.00 | 0.00 | 2510.06 | 6573.61 | 2967.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14273.32 | 0.00 | -24021.80 | -29735.68 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9771 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9771 | 0.1047 | 1.0000 | Not calculated | 0.1023 | 0.1047 | ||
PSZ-FINE STORAGE | 2.0455 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.0455 | 0.2076 | 1.0000 | Not calculated | 0.4247 | 0.2076 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9771 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9771 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1047 | ||
PSZ-FINE STORAGE | 2.0455 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.0455 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2076 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.002360 | 12.7487 | 0.000305 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.002360 | 12.75 | 0.000305 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9771 | 0.9771 | 0.9771 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0455 | 2.0455 | 2.0455 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9771 | 0.9771 | 0.9771 | 0.9771 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.0455 | 2.0455 | 2.0455 | 2.0455 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9771 | 0.9771 | 0.9771 | No | 0.1023 | 0.4226 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0455 | 2.0455 | 2.0455 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9771 | 0.9771 | 0.9771 | 0.9771 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.0455 | 2.0455 | 2.0455 | 2.0455 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2.11 | 23241.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.36 | 7874.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 91.01 | 8876.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.67 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 23.58 | 2061.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.52 | 1797.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 345.65 |
Natural Gas | 0.00 | 2.11 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 347.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 18.82 |
Space Heating | 0.00 |
Space Cooling | 1.73 |
Fans (All) | 4.88 |
Service Water Heating | 5.07 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 71.49 |
Subtotal | 71.49 |
Natural Gas [MJ/m2] | |
Space Heating | 0.44 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.44 |
Subtotal | 0.44 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.17 |
Space Heating | 0.61 |
Space Cooling | 2.40 |
Fans (All) | 6.78 |
Service Water Heating | 7.05 |
Receptacle Equipment | 39.25 |
Miscellaneous | 17.73 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2499. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8479.33 | 280.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7944.00 | 816.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7681.00 | 1079.00 | 0.00 | 0.00 | 0.00 |
Min | 7681.00 | 280.67 | 0.00 | 0.00 | 0.00 |
Max | 8479.33 | 1079.00 | 0.00 | 0.00 | 0.00 |
Average | 8034.78 | 725.22 | 0.00 | 0.00 | 0.00 |
Sum | 24104.33 | 2175.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 65422.50 | 17296.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 152503.50 | 38689.50 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 152503.50 | 38689.50 | 0.00 | 0.00 | 0.00 |
Average | 83651.00 | 18662.00 | 0.00 | 0.00 | 0.00 |
Sum | 250953.00 | 55986.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7409.50 | 1350.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6656.00 | 2104.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6650.67 | 2109.33 | 0.00 | 0.00 | 0.00 |
Min | 6650.67 | 1350.50 | 0.00 | 0.00 | 0.00 |
Max | 7409.50 | 2109.33 | 0.00 | 0.00 | 0.00 |
Average | 6905.39 | 1854.61 | 0.00 | 0.00 | 0.00 |
Sum | 20716.17 | 5563.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32387.17 | 639.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 55884.00 | 26835.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 136573.00 | 54620.00 | 0.00 | 0.00 | 0.00 |
Min | 32387.17 | 639.83 | 0.00 | 0.00 | 0.00 |
Max | 136573.00 | 54620.00 | 0.00 | 0.00 | 0.00 |
Average | 74948.06 | 27364.94 | 0.00 | 0.00 | 0.00 |
Sum | 224844.17 | 82094.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:44:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338623E+09 | 2479.51 | 21-JAN-15:00 | 14.00 | 11.21 | 0.580294E+09 | 775.25 | 17-JAN-11:30 | 14.00 | 11.21 |
February | 0.254233E+09 | 2499.64 | 03-FEB-15:20 | 22.33 | 9.30 | 0.533588E+09 | 768.97 | 01-FEB-13:39 | 22.33 | 9.30 |
March | 0.343871E+09 | 3261.20 | 23-MAR-15:50 | 21.17 | 17.23 | 0.623451E+09 | 769.01 | 23-MAR-15:09 | 21.17 | 17.23 |
April | 0.160016E+10 | 18800.10 | 29-APR-07:03 | 14.33 | 11.79 | 0.622196E+09 | 863.25 | 29-APR-07:10 | 14.33 | 11.79 |
May | 0.212397E+10 | 16355.60 | 06-MAY-07:03 | 14.83 | 14.24 | 0.654384E+09 | 855.28 | 06-MAY-07:10 | 14.83 | 14.24 |
June | 0.322632E+10 | 17010.21 | 03-JUN-07:02 | 17.17 | 14.02 | 0.661516E+09 | 879.39 | 24-JUN-07:10 | 18.17 | 14.44 |
July | 0.453293E+10 | 16715.72 | 08-JUL-07:02 | 17.00 | 14.51 | 0.640392E+09 | 879.39 | 22-JUL-07:10 | 19.33 | 17.20 |
August | 0.472947E+10 | 15251.65 | 26-AUG-07:02 | 16.17 | 16.07 | 0.691081E+09 | 879.39 | 19-AUG-07:10 | 16.17 | 16.07 |
September | 0.340900E+10 | 18343.41 | 02-SEP-07:02 | 16.17 | 12.63 | 0.637525E+09 | 879.39 | 30-SEP-07:10 | 23.92 | 14.07 |
October | 0.306475E+10 | 18390.99 | 07-OCT-07:02 | 17.00 | 12.30 | 0.634428E+09 | 879.39 | 04-OCT-07:10 | 17.00 | 12.30 |
November | 0.808929E+09 | 2871.28 | 04-NOV-15:00 | 16.70 | 10.78 | 0.588881E+09 | 768.98 | 10-NOV-13:30 | 20.50 | 16.08 |
December | 0.445307E+09 | 2756.74 | 05-DEC-15:10 | 24.67 | 13.10 | 0.594359E+09 | 772.53 | 19-DEC-10:09 | 23.33 | 10.05 |
Annual Sum or Average | 0.248776E+11 | 0.746209E+10 | ||||||||
Minimum of Months | 0.254233E+09 | 2479.51 | 14.00 | 9.30 | 0.533588E+09 | 768.97 | 14.00 | 9.30 | ||
Maximum of Months | 0.472947E+10 | 18800.10 | 24.67 | 17.23 | 0.691081E+09 | 879.39 | 23.92 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117790E+10 | 4091.62 | 28-JAN-08:70 | 8.67 | 6.43 | 0.112989E+10 | 1839.84 | 18-JAN-14:20 | 8.67 | 6.43 |
February | 0.138707E+10 | 3469.74 | 09-FEB-08:63 | 9.40 | 7.65 | 0.103661E+10 | 1830.61 | 03-FEB-15:09 | 9.40 | 7.65 |
March | 0.183102E+10 | 4814.09 | 29-MAR-15:00 | 8.00 | 6.48 | 0.121751E+10 | 1986.09 | 23-MAR-14:00 | 8.00 | 6.48 |
April | 0.178156E+10 | 3996.41 | 11-APR-07:05 | 12.33 | 12.24 | 0.146219E+10 | 2246.82 | 26-APR-14:09 | 25.50 | 16.68 |
May | 0.211426E+10 | 5026.15 | 04-MAY-12:30 | 23.50 | 16.62 | 0.160353E+10 | 2246.84 | 04-MAY-12:30 | 23.50 | 16.62 |
June | 0.303211E+10 | 26037.85 | 25-JUN-15:45 | 21.00 | 16.52 | 0.177167E+10 | 2246.87 | 24-JUN-13:09 | 21.00 | 16.52 |
July | 0.637024E+10 | 28686.52 | 04-JUL-17:12 | 18.67 | 15.17 | 0.183050E+10 | 2246.91 | 24-JUL-14:50 | 26.17 | 20.02 |
August | 0.625490E+10 | 25805.15 | 20-AUG-16:22 | 21.40 | 17.21 | 0.196915E+10 | 2246.90 | 19-AUG-13:39 | 21.40 | 17.21 |
September | 0.292671E+10 | 23781.90 | 10-SEP-14:25 | 22.50 | 17.91 | 0.174619E+10 | 2246.86 | 11-SEP-13:50 | 23.00 | 17.26 |
October | 0.224891E+10 | 22426.74 | 15-OCT-13:35 | 31.33 | 15.44 | 0.168365E+10 | 2246.85 | 18-OCT-13:00 | 22.00 | 18.09 |
November | 0.147435E+10 | 4535.37 | 01-NOV-07:05 | 11.17 | 11.08 | 0.124836E+10 | 1908.35 | 18-NOV-14:20 | 25.33 | 14.85 |
December | 0.125519E+10 | 4582.00 | 01-DEC-08:63 | 9.33 | 9.16 | 0.118862E+10 | 1881.64 | 05-DEC-15:20 | 24.33 | 12.97 |
Annual Sum or Average | 0.318542E+11 | 0.178879E+11 | ||||||||
Minimum of Months | 0.117790E+10 | 3469.74 | 8.00 | 6.43 | 0.103661E+10 | 1830.61 | 8.00 | 6.43 | ||
Maximum of Months | 0.637024E+10 | 28686.52 | 31.33 | 17.91 | 0.196915E+10 | 2246.91 | 26.17 | 20.02 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.222134E+10 | 3401.07 | 24-JAN-15:50 | 24.17 | 15.12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.209842E+10 | 3530.54 | 03-FEB-14:00 | 23.00 | 8.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.241184E+10 | 3696.51 | 23-MAR-14:50 | 22.17 | 17.39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.291112E+10 | 4492.87 | 26-APR-14:09 | 25.50 | 16.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.337411E+10 | 4817.81 | 04-MAY-12:00 | 23.00 | 16.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.386826E+10 | 5546.08 | 30-JUN-15:30 | 22.85 | 17.86 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.456279E+10 | 6246.44 | 31-JUL-13:39 | 27.33 | 20.96 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.500943E+10 | 6216.54 | 19-AUG-14:20 | 26.67 | 19.73 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.405059E+10 | 5999.02 | 30-SEP-14:30 | 32.00 | 17.36 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.385751E+10 | 5900.25 | 16-OCT-12:00 | 34.10 | 16.81 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.265737E+10 | 4082.82 | 01-NOV-14:30 | 17.00 | 13.18 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.242782E+10 | 3634.70 | 05-DEC-15:20 | 24.33 | 12.97 |
Annual Sum or Average | 0.00 | 0.394506E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.209842E+10 | 3401.07 | 17.00 | 8.84 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.500943E+10 | 6246.44 | 34.10 | 20.96 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.717358E+09 | 24376.80 | 13-JAN-07:01 | 8.17 |
February | 0.415412E+09 | 24068.91 | 28-FEB-07:02 | 11.33 |
March | 0.585153E+09 | 24374.68 | 31-MAR-06:01 | 8.00 |
April | 0.188528E+09 | 24128.93 | 01-APR-06:01 | 7.67 |
May | 0.145822E+09 | 7826.64 | 15-MAY-07:03 | 13.50 |
June | 0.120928E+09 | 1415.00 | 29-JUN-06:20 | 15.33 |
July | 90220130.19 | 1489.39 | 24-JUL-06:10 | 16.17 |
August | 0.104524E+09 | 1482.58 | 28-AUG-06:15 | 14.00 |
September | 0.104225E+09 | 1415.98 | 15-SEP-06:10 | 14.00 |
October | 0.116149E+09 | 1597.12 | 19-OCT-06:15 | 11.67 |
November | 0.238859E+09 | 13051.95 | 24-NOV-07:03 | 8.75 |
December | 0.437989E+09 | 24294.67 | 15-DEC-07:01 | 6.50 |
Annual Sum or Average | 0.326517E+10 | |||
Minimum of Months | 90220130.19 | 1415.00 | 6.50 | |
Maximum of Months | 0.717358E+09 | 24376.80 | 16.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369257E+09 | 34867.48 | 03-JAN-06:10 | 4.67 |
February | 87634858.37 | 1953.16 | 01-FEB-12:00 | 26.00 |
March | 0.106715E+09 | 12204.38 | 30-MAR-06:02 | 5.58 |
April | 0.102332E+09 | 1783.55 | 01-APR-12:00 | 24.00 |
May | 64057190.10 | 936.18 | 25-MAY-07:00 | 14.00 |
June | 63866896.80 | 909.77 | 06-JUN-07:00 | 17.00 |
July | 61350878.41 | 838.35 | 24-JUL-07:00 | 17.00 |
August | 66580457.45 | 852.88 | 21-AUG-07:00 | 17.00 |
September | 71973346.50 | 1943.91 | 29-SEP-08:00 | 29.00 |
October | 0.124845E+09 | 3063.45 | 14-OCT-09:10 | 31.33 |
November | 0.128289E+09 | 1758.11 | 18-NOV-13:00 | 26.00 |
December | 0.257158E+09 | 2531.69 | 16-DEC-13:00 | 26.00 |
Annual Sum or Average | 0.150406E+10 | |||
Minimum of Months | 61350878.41 | 838.35 | 4.67 | |
Maximum of Months | 0.369257E+09 | 34867.48 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.943561E+09 | 808.57 | 02-JAN-16:49 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.835334E+09 | 794.16 | 27-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.935433E+09 | 772.32 | 16-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.868577E+09 | 759.70 | 15-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.889506E+09 | 756.73 | 09-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.872859E+09 | 748.92 | 09-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.867008E+09 | 738.54 | 12-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.914253E+09 | 757.97 | 21-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.877018E+09 | 777.25 | 18-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.930878E+09 | 778.27 | 24-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.897028E+09 | 808.57 | 06-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.949365E+09 | 808.57 | 01-DEC-16:40 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.107808E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.835334E+09 | 738.54 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.949365E+09 | 808.57 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.378763E+10 | 3983.13 | 21-JAN-15:00 | 0.00 | 0.00 |
February | 0.314225E+10 | 3645.77 | 27-FEB-16:00 | 0.00 | 0.00 |
March | 0.343185E+10 | 3458.31 | 01-MAR-16:00 | 0.00 | 0.00 |
April | 0.311090E+10 | 3332.55 | 03-APR-07:10 | 0.00 | 0.00 |
May | 0.310855E+10 | 3215.43 | 09-MAY-08:09 | 0.00 | 0.00 |
June | 0.308352E+10 | 3043.12 | 14-JUN-07:10 | 0.00 | 0.00 |
July | 0.307524E+10 | 3148.89 | 19-JUL-07:10 | 0.00 | 0.00 |
August | 0.330602E+10 | 3329.29 | 31-AUG-07:10 | 0.00 | 0.00 |
September | 0.320914E+10 | 3578.81 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.356869E+10 | 3785.80 | 30-OCT-08:09 | 0.00 | 0.00 |
November | 0.353926E+10 | 4020.11 | 25-NOV-15:00 | 0.00 | 0.00 |
December | 0.387611E+10 | 4030.92 | 18-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402392E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.307524E+10 | 3043.12 | 0.00 | 0.00 | |
Maximum of Months | 0.387611E+10 | 4030.92 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.368401E+10 | 4226.27 | 02-JAN-16:49 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.313856E+10 | 3839.06 | 27-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.345292E+10 | 3475.61 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.312504E+10 | 2993.88 | 05-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.315997E+10 | 2725.06 | 09-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.311705E+10 | 2715.91 | 16-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.308797E+10 | 2719.87 | 12-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.330127E+10 | 2941.74 | 29-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.320705E+10 | 3257.24 | 18-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.348672E+10 | 3737.22 | 30-OCT-15:00 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.348373E+10 | 4226.27 | 06-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.374981E+10 | 4226.27 | 01-DEC-16:40 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.399941E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.308797E+10 | 2715.91 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.374981E+10 | 4226.27 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.943561E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5004012.40 | 0.128502E+10 |
February | 0.127628E+10 | 0.835334E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457897.94 | 0.135816E+10 |
March | 0.149825E+10 | 0.935433E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50349.77 | 0.171569E+10 |
April | 0.138726E+10 | 0.868577E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5636524.03 | 0.118297E+10 |
May | 0.144276E+10 | 0.889506E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66788.14 | 0.133639E+10 |
June | 0.144276E+10 | 0.872859E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244073.78 | 0.973588E+09 |
July | 0.138726E+10 | 0.867008E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30878812.88 | 0.701716E+09 |
August | 0.149825E+10 | 0.914253E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32597305.09 | 0.801261E+09 |
September | 0.138726E+10 | 0.877018E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49917887.99 | 0.849812E+09 |
October | 0.138726E+10 | 0.930878E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95598354.14 | 0.906014E+09 |
November | 0.133177E+10 | 0.897028E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2500055.74 | 0.128543E+10 |
December | 0.138726E+10 | 0.949365E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5758176.74 | 0.124711E+10 |
Annual Sum or Average | 0.168137E+11 | 0.107808E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230710E+09 | 0.136431E+11 |
Minimum of Months | 0.127628E+10 | 0.835334E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50349.77 | 0.701716E+09 |
Maximum of Months | 0.149825E+10 | 0.949365E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95598354.14 | 0.171569E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.378763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27282647.05 | 0.224189E+10 |
February | 0.300332E+10 | 0.314225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2365586.18 | 0.281600E+10 |
March | 0.352563E+10 | 0.343185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371439.17 | 0.343280E+10 |
April | 0.326447E+10 | 0.311090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9544632.45 | 0.277055E+10 |
May | 0.339505E+10 | 0.310855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350725E+10 |
June | 0.339505E+10 | 0.308352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251618E+10 |
July | 0.326447E+10 | 0.307524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3407871.76 | 0.210067E+10 |
August | 0.352563E+10 | 0.330602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2089210.72 | 0.241386E+10 |
September | 0.326447E+10 | 0.320914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47089991.02 | 0.212268E+10 |
October | 0.326447E+10 | 0.356869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121744E+09 | 0.255930E+10 |
November | 0.313390E+10 | 0.353926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13932921.67 | 0.258489E+10 |
December | 0.326447E+10 | 0.387611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29514032.04 | 0.242453E+10 |
Annual Sum or Average | 0.395654E+11 | 0.402392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258342E+09 | 0.314906E+11 |
Minimum of Months | 0.300332E+10 | 0.307524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210067E+10 |
Maximum of Months | 0.352563E+10 | 0.387611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121744E+09 | 0.350725E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.368401E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702027E+09 | 0.974849E+10 |
February | 0.690763E+10 | 0.313856E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119249E+09 | 0.127649E+11 |
March | 0.810895E+10 | 0.345292E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187937E+09 | 0.154874E+11 |
April | 0.750829E+10 | 0.312504E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327371E+09 | 0.121271E+11 |
May | 0.780862E+10 | 0.315997E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167876E+11 |
June | 0.780862E+10 | 0.311705E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127647E+11 |
July | 0.750829E+10 | 0.308797E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139578E+11 |
August | 0.810895E+10 | 0.330127E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161922E+11 |
September | 0.750829E+10 | 0.320705E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342495E+09 | 0.123108E+11 |
October | 0.750829E+10 | 0.348672E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103278E+10 | 0.139752E+11 |
November | 0.720796E+10 | 0.348373E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330431E+09 | 0.129572E+11 |
December | 0.750829E+10 | 0.374981E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850818E+09 | 0.112161E+11 |
Annual Sum or Average | 0.910005E+11 | 0.399941E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389311E+10 | 0.160289E+12 |
Minimum of Months | 0.690763E+10 | 0.308797E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974849E+10 |
Maximum of Months | 0.810895E+10 | 0.374981E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103278E+10 | 0.167876E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 808.57 | 02-JAN-16:49 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 746.58 | 18-JAN-13:00 | 6669.29 | 09-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 794.16 | 27-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 638.63 | 01-FEB-12:10 | 5132.23 | 10-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 772.32 | 16-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 12-MAR-10:00 | 6228.28 | 30-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 759.70 | 15-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 754.99 | 26-APR-11:10 | 4852.32 | 17-APR-16:03 |
May | 1680.92 | 01-MAY-07:10 | 756.73 | 09-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 03-MAY-12:00 | 4339.40 | 12-MAY-16:05 |
June | 1680.92 | 01-JUN-07:10 | 748.92 | 09-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.41 | 29-JUN-11:10 | 3645.66 | 05-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 738.54 | 12-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.21 | 19-JUL-12:00 | 3691.58 | 17-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 757.97 | 21-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.99 | 18-AUG-12:00 | 3962.57 | 28-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 777.25 | 18-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4197.54 | 29-SEP-12:00 | 3873.14 | 20-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 778.27 | 24-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4614.22 | 16-OCT-11:10 | 4879.34 | 19-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 808.57 | 06-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.56 | 19-NOV-13:00 | 4888.44 | 30-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 808.57 | 01-DEC-16:40 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 751.24 | 19-DEC-13:00 | 5791.84 | 22-DEC-07:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 738.54 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 3645.66 | |||||
Maximum of Months | 1680.92 | 808.57 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4614.22 | 6669.29 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3983.13 | 21-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.05 | 15-JAN-10:00 | 4247.42 | 27-JAN-05:00 |
February | 3955.50 | 01-FEB-08:09 | 3645.77 | 27-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.49 | 01-FEB-12:00 | 4154.29 | 25-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 3458.31 | 01-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.46 | 12-MAR-10:00 | 6135.78 | 28-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 3332.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 02-APR-13:00 | 7000.11 | 17-APR-16:55 |
May | 3955.50 | 01-MAY-07:10 | 3215.43 | 09-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 6035.06 | 12-MAY-16:00 |
June | 3955.50 | 01-JUN-07:10 | 3043.12 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 3375.70 | 12-JUN-16:00 |
July | 3955.50 | 01-JUL-07:10 | 3148.89 | 19-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.77 | 31-JUL-13:00 | 4000.95 | 20-JUL-18:00 |
August | 3955.50 | 01-AUG-07:10 | 3329.29 | 31-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.84 | 17-AUG-14:00 | 3017.67 | 21-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 3578.81 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.71 | 29-SEP-15:10 | 3691.48 | 02-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 3785.80 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2171.04 | 14-OCT-15:10 | 3899.70 | 07-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 4020.11 | 25-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.13 | 19-NOV-13:00 | 4280.11 | 30-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 4030.92 | 18-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.02 | 25-DEC-12:00 | 4234.58 | 13-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3043.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3017.67 | ||||
Maximum of Months | 3955.50 | 4030.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.71 | 7000.11 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4226.27 | 02-JAN-16:49 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9178.17 | 14-JAN-13:10 | 19028.89 | 27-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 3839.06 | 27-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7283.41 | 01-FEB-12:00 | 22089.48 | 25-FEB-13:10 |
March | 9097.65 | 01-MAR-08:09 | 3475.61 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6555.62 | 11-MAR-13:10 | 27911.46 | 28-MAR-08:00 |
April | 9097.65 | 01-APR-07:10 | 2993.88 | 05-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8956.38 | 01-APR-12:10 | 28378.29 | 17-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 2725.06 | 09-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 27935.06 | 12-MAY-16:00 |
June | 9097.65 | 01-JUN-07:10 | 2715.91 | 16-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 14593.26 | 12-JUN-16:00 |
July | 9097.65 | 01-JUL-07:10 | 2719.87 | 12-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 20383.02 | 20-JUL-09:00 |
August | 9097.65 | 01-AUG-07:10 | 2941.74 | 29-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 14870.35 | 22-AUG-16:00 |
September | 9097.65 | 01-SEP-07:10 | 3257.24 | 18-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12617.02 | 29-SEP-12:10 | 18208.22 | 02-SEP-15:00 |
October | 9097.65 | 02-OCT-07:10 | 3737.22 | 30-OCT-15:00 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20491.77 | 16-OCT-10:00 | 20884.82 | 07-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 4226.27 | 06-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6865.00 | 27-NOV-12:00 | 17937.65 | 01-NOV-08:00 |
December | 9097.65 | 01-DEC-08:09 | 4226.27 | 01-DEC-16:40 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15261.91 | 18-DEC-11:00 | 20342.97 | 12-DEC-13:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2715.91 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14593.26 | |||||
Maximum of Months | 9097.65 | 4226.27 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 20491.77 | 28378.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2479.51 | 21-JAN-15:00 | 1680.92 | 587.49 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.96 |
February | 2499.64 | 03-FEB-15:20 | 1680.92 | 515.51 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.90 |
March | 3261.20 | 23-MAR-15:50 | 1680.92 | 493.23 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.33 |
April | 18800.10 | 29-APR-07:03 | 6723.69 | 2828.31 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.18 |
May | 16355.60 | 06-MAY-07:03 | 6723.69 | 2790.81 | 7340.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.45 |
June | 17010.21 | 03-JUN-07:02 | 8404.61 | 3294.62 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.29 |
July | 16715.72 | 08-JUL-07:02 | 8404.61 | 3356.89 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.50 |
August | 15251.65 | 26-AUG-07:02 | 8404.61 | 3601.99 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.35 |
September | 18343.41 | 02-SEP-07:02 | 8404.61 | 3700.28 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.94 |
October | 18390.99 | 07-OCT-07:02 | 8404.61 | 3692.90 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.11 |
November | 2871.28 | 04-NOV-15:00 | 1680.92 | 518.96 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.24 |
December | 2756.74 | 05-DEC-15:10 | 1680.92 | 520.83 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2479.51 | 1680.92 | 493.23 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18800.10 | 8404.61 | 3700.28 | 9175.27 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 | 654.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4091.62 | 28-JAN-08:70 | 3955.50 | 3457.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1878.20 |
February | 3469.74 | 09-FEB-08:63 | 11866.50 | 9915.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1715.35 |
March | 4814.09 | 29-MAR-15:00 | 3955.50 | 2177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.42 |
April | 3996.41 | 11-APR-07:05 | 7911.00 | 5892.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.52 |
May | 5026.15 | 04-MAY-12:30 | 3955.50 | 2177.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.84 |
June | 26037.85 | 25-JUN-15:45 | 0.00 | 600.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.40 |
July | 28686.52 | 04-JUL-17:12 | 0.00 | 1951.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.41 |
August | 25805.15 | 20-AUG-16:22 | 0.00 | 1862.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.25 |
September | 23781.90 | 10-SEP-14:25 | 0.00 | 579.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.37 |
October | 22426.74 | 15-OCT-13:35 | 0.00 | 698.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1524.56 | 0.00 |
November | 4535.37 | 01-NOV-07:05 | 7911.00 | 6636.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3203.28 |
December | 4582.00 | 01-DEC-08:63 | 11866.50 | 8917.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3469.74 | 0.00 | 579.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28686.52 | 11866.50 | 9915.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1524.56 | 3203.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7483.27 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6185.28 |
April | 0.00 | 01-APR-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8936.92 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5562.48 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4493.90 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3560.61 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5246.49 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5729.14 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8687.72 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6830.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 563.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 563.50 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8936.92 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.301966E+11 | 28266.55 | 14-JAN-16:00 | 0.822859E+09 | 23241.87 | 09-JAN-07:10 |
February | 0.265590E+11 | 21864.82 | 25-FEB-16:00 | 0.304865E+09 | 10781.77 | 10-FEB-07:10 |
March | 0.295403E+11 | 21021.57 | 01-MAR-16:00 | 0.552803E+09 | 17548.84 | 30-MAR-06:10 |
April | 0.270579E+11 | 21058.03 | 26-APR-12:00 | 40265361.80 | 8074.90 | 01-APR-06:10 |
May | 0.274051E+11 | 20931.19 | 04-MAY-12:09 | 2632520.43 | 4121.59 | 15-MAY-07:10 |
June | 0.275038E+11 | 22853.27 | 29-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.289252E+11 | 25411.47 | 31-JUL-13:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.309147E+11 | 25489.81 | 17-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.283328E+11 | 26092.71 | 29-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.300032E+11 | 26200.35 | 16-OCT-12:20 | 215655.76 | 359.43 | 30-OCT-07:10 |
November | 0.287183E+11 | 27962.00 | 30-NOV-16:49 | 84713711.84 | 6455.95 | 24-NOV-07:10 |
December | 0.304934E+11 | 28091.54 | 05-DEC-16:00 | 0.303366E+09 | 13124.13 | 15-DEC-07:10 |
Annual Sum or Average | 0.345650E+12 | 0.211172E+10 | ||||
Minimum of Months | 0.265590E+11 | 20931.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.309147E+11 | 28266.55 | 0.822859E+09 | 23241.87 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.841520E+10 | 0.639532E+10 | 0.112984E+11 | 0.00 | 0.194299E+10 | 0.00 | 0.00 | 43397749.47 | 0.00 | 0.00 | 0.00 | 0.210129E+10 | 0.00 |
February | 0.711614E+10 | 0.536405E+10 | 0.103734E+11 | 0.00 | 0.178268E+10 | 0.00 | 0.00 | 12256000.23 | 0.00 | 0.00 | 0.00 | 0.191053E+10 | 0.00 |
March | 0.782021E+10 | 0.534074E+10 | 0.121089E+11 | 0.00 | 0.209309E+10 | 0.00 | 0.00 | 29085186.19 | 0.00 | 0.00 | 0.00 | 0.214828E+10 | 0.00 |
April | 0.710452E+10 | 0.458174E+10 | 0.112578E+11 | 0.00 | 0.193770E+10 | 0.00 | 0.00 | 0.146165E+09 | 0.00 | 0.00 | 0.00 | 0.202999E+10 | 0.00 |
May | 0.715803E+10 | 0.427063E+10 | 0.117000E+11 | 0.00 | 0.201521E+10 | 0.00 | 0.00 | 0.179136E+09 | 0.00 | 0.00 | 0.00 | 0.208217E+10 | 0.00 |
June | 0.707343E+10 | 0.392101E+10 | 0.116594E+11 | 0.00 | 0.201941E+10 | 0.00 | 0.00 | 0.812555E+09 | 0.00 | 0.00 | 0.00 | 0.201800E+10 | 0.00 |
July | 0.703021E+10 | 0.410898E+10 | 0.112984E+11 | 0.00 | 0.198163E+10 | 0.00 | 0.00 | 0.248048E+10 | 0.00 | 0.00 | 0.00 | 0.202553E+10 | 0.00 |
August | 0.752154E+10 | 0.450037E+10 | 0.121016E+11 | 0.00 | 0.212174E+10 | 0.00 | 0.00 | 0.259419E+10 | 0.00 | 0.00 | 0.00 | 0.207528E+10 | 0.00 |
September | 0.729320E+10 | 0.491789E+10 | 0.112504E+11 | 0.00 | 0.193824E+10 | 0.00 | 0.00 | 0.943514E+09 | 0.00 | 0.00 | 0.00 | 0.198955E+10 | 0.00 |
October | 0.798629E+10 | 0.569007E+10 | 0.113057E+11 | 0.00 | 0.194477E+10 | 0.00 | 0.00 | 0.102518E+10 | 0.00 | 0.00 | 0.00 | 0.205116E+10 | 0.00 |
November | 0.792002E+10 | 0.603838E+10 | 0.108562E+11 | 0.00 | 0.186019E+10 | 0.00 | 0.00 | 42523395.05 | 0.00 | 0.00 | 0.00 | 0.200098E+10 | 0.00 |
December | 0.857528E+10 | 0.654032E+10 | 0.112984E+11 | 0.00 | 0.193770E+10 | 0.00 | 0.00 | 50516506.42 | 0.00 | 0.00 | 0.00 | 0.209126E+10 | 0.00 |
Annual Sum or Average | 0.910141E+11 | 0.616695E+11 | 0.136508E+12 | 0.00 | 0.235754E+11 | 0.00 | 0.00 | 0.835901E+10 | 0.00 | 0.00 | 0.00 | 0.245240E+11 | 0.00 |
Minimum of Months | 0.703021E+10 | 0.392101E+10 | 0.103734E+11 | 0.00 | 0.178268E+10 | 0.00 | 0.00 | 12256000.23 | 0.00 | 0.00 | 0.00 | 0.191053E+10 | 0.00 |
Maximum of Months | 0.857528E+10 | 0.654032E+10 | 0.121089E+11 | 0.00 | 0.212174E+10 | 0.00 | 0.00 | 0.259419E+10 | 0.00 | 0.00 | 0.00 | 0.214828E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.822859E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.304865E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.552803E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 40265361.80 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2632520.43 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 215655.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 84713711.84 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.303366E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211172E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.822859E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8876.89 | 02-JAN-16:49 | 5492.60 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2061.61 | 09-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8278.99 | 27-FEB-16:00 | 5492.60 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 1957.27 | 01-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7427.14 | 01-MAR-16:00 | 5492.60 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 1995.57 | 30-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 6856.76 | 21-APR-15:00 | 5492.60 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 1957.27 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6546.30 | 09-MAY-07:10 | 5492.60 | 01-MAY-18:30 | 10035.17 | 01-MAY-07:10 | 0.00 | 1957.27 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6130.54 | 16-JUN-08:09 | 5492.60 | 01-JUN-18:49 | 10035.17 | 01-JUN-07:10 | 0.00 | 1957.27 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6234.64 | 19-JUL-08:09 | 5492.60 | 01-JUL-18:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 1957.27 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 6849.63 | 31-AUG-07:10 | 5492.60 | 01-AUG-18:49 | 10035.17 | 01-AUG-07:10 | 0.00 | 1957.27 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7532.59 | 21-SEP-08:09 | 5492.60 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1957.27 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8023.33 | 30-OCT-14:00 | 5492.60 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1957.27 | 02-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8876.89 | 06-NOV-16:00 | 5492.60 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 1957.27 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8876.89 | 01-DEC-16:40 | 5492.60 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 1957.27 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6130.54 | 5492.60 | 10035.17 | 0.00 | 1957.27 | 0.00 | 0.00 | |||||
Maximum of Months | 8876.89 | 5492.60 | 10035.17 | 0.00 | 2061.61 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 757.52 | 24-JAN-15:30 | 0.00 | 0.00 | 0.00 | 1797.90 | 30-JAN-12:20 | 0.00 |
February | 625.60 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 1797.77 | 13-FEB-12:39 | 0.00 |
March | 862.70 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 1796.16 | 02-MAR-12:20 | 0.00 |
April | 2148.31 | 26-APR-13:09 | 0.00 | 0.00 | 0.00 | 1790.30 | 01-APR-11:50 | 0.00 |
May | 2021.09 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 1781.85 | 01-MAY-11:09 | 0.00 |
June | 5090.62 | 30-JUN-17:30 | 0.00 | 0.00 | 0.00 | 1773.73 | 02-JUN-11:09 | 0.00 |
July | 6526.14 | 31-JUL-13:09 | 0.00 | 0.00 | 0.00 | 1767.76 | 01-JUL-11:09 | 0.00 |
August | 6638.33 | 17-AUG-13:00 | 0.00 | 0.00 | 0.00 | 1767.14 | 31-AUG-11:50 | 0.00 |
September | 7375.85 | 29-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1772.59 | 30-SEP-11:20 | 0.00 |
October | 7874.71 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 1780.33 | 30-OCT-11:00 | 0.00 |
November | 851.45 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1787.85 | 30-NOV-12:09 | 0.00 |
December | 843.35 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1794.95 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 625.60 | 0.00 | 0.00 | 0.00 | 1767.14 | 0.00 | ||
Maximum of Months | 7874.71 | 0.00 | 0.00 | 0.00 | 1797.90 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28266.55 | 14-JAN-16:00 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 1957.27 | 0.00 | 0.00 | 302.45 | 0.00 |
February | 21864.82 | 25-FEB-16:00 | 8270.20 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21021.57 | 01-MAR-16:00 | 7427.14 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21058.03 | 26-APR-12:00 | 5206.70 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 2110.89 | 0.00 |
May | 20931.19 | 04-MAY-12:09 | 5171.89 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 2021.09 | 0.00 |
June | 22853.27 | 29-JUN-13:09 | 5193.48 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 3963.39 | 0.00 |
July | 25411.47 | 31-JUL-13:20 | 5195.48 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 6521.64 | 0.00 |
August | 25489.81 | 17-AUG-14:09 | 5149.66 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 6614.63 | 0.00 |
September | 26092.71 | 29-SEP-12:00 | 5174.95 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 7186.81 | 0.00 |
October | 26200.35 | 16-OCT-12:20 | 5420.64 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 7045.02 | 0.00 |
November | 27962.00 | 30-NOV-16:49 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 1957.27 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28091.54 | 05-DEC-16:00 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 1957.27 | 0.00 | 0.00 | 129.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20931.19 | 5149.66 | 10035.17 | 0.00 | 0.00 | 1957.27 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28266.55 | 8876.89 | 10035.17 | 5492.60 | 0.00 | 1957.27 | 0.00 | 0.00 | 7186.81 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 23241.87 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 10781.77 | 10-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 17548.84 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 8074.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4121.59 | 15-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 359.43 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 6455.95 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 13124.13 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 23241.87 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.20 | 0.33 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.20 | 0.33 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.20 | 0.33 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.29 | 0.00 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.29 | 0.00 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 14.96 | 0.00 | 14.96 | 3.17 | 26.12 | 0.00 | 26.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 14.96 | 0.00 | 14.96 | 1.33 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.35 | 91.67 | 21.89 | 91.67 | 21.61 |
February | 276.00 | 22.35 | 63.50 | 21.94 | 63.50 | 21.66 |
March | 314.33 | 22.26 | 73.00 | 21.86 | 71.67 | 21.57 |
April | 211.83 | 23.17 | 42.17 | 23.21 | 7.33 | 23.12 |
May | 164.33 | 23.36 | 56.50 | 23.53 | 1.33 | 23.51 |
June | 50.50 | 23.50 | 184.67 | 24.02 | 1.33 | 24.01 |
July | 22.83 | 25.24 | 300.00 | 24.32 | 22.83 | 24.38 |
August | 37.50 | 24.86 | 324.00 | 24.28 | 37.50 | 24.34 |
September | 23.33 | 23.87 | 247.50 | 24.10 | 14.83 | 24.10 |
October | 116.67 | 23.70 | 111.00 | 23.97 | 21.83 | 24.04 |
November | 283.17 | 23.04 | 29.17 | 22.78 | 29.17 | 22.56 |
December | 300.00 | 22.63 | 63.33 | 22.22 | 63.33 | 21.92 |
Annual Sum or Average | 2100.50 | 22.83 | 1586.50 | 23.06 | 426.33 | 22.88 |
Minimum of Months | 22.83 | 22.26 | 29.17 | 21.86 | 1.33 | 21.57 |
Maximum of Months | 314.33 | 25.24 | 324.00 | 24.32 | 91.67 | 24.38 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.23 | 165.17 | 19.71 | 165.17 | 19.47 |
February | 276.00 | 20.31 | 135.67 | 19.84 | 135.67 | 19.60 |
March | 309.33 | 20.12 | 159.83 | 19.76 | 150.00 | 19.50 |
April | 181.33 | 22.11 | 108.00 | 23.04 | 13.17 | 22.86 |
May | 139.50 | 22.53 | 141.67 | 23.95 | 2.83 | 23.91 |
June | 118.50 | 25.32 | 243.33 | 25.72 | 74.33 | 25.88 |
July | 229.33 | 26.63 | 300.00 | 26.51 | 229.33 | 26.55 |
August | 260.00 | 26.54 | 324.00 | 26.43 | 260.00 | 26.47 |
September | 123.33 | 25.97 | 267.33 | 25.94 | 112.67 | 26.00 |
October | 130.17 | 24.41 | 197.17 | 25.38 | 61.17 | 25.51 |
November | 282.83 | 21.82 | 59.33 | 21.44 | 59.33 | 21.18 |
December | 300.00 | 20.80 | 131.50 | 20.31 | 131.50 | 20.05 |
Annual Sum or Average | 2650.33 | 22.58 | 2233.00 | 23.21 | 1395.17 | 23.15 |
Minimum of Months | 118.50 | 20.12 | 59.33 | 19.71 | 2.83 | 19.47 |
Maximum of Months | 309.33 | 26.63 | 324.00 | 26.51 | 260.00 | 26.55 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 18.78 | 259.00 | 18.63 | 259.00 | 18.57 |
February | 276.00 | 19.11 | 252.00 | 19.02 | 252.00 | 18.99 |
March | 324.00 | 18.89 | 285.50 | 18.74 | 285.50 | 18.68 |
April | 282.50 | 21.53 | 53.83 | 21.23 | 50.00 | 20.98 |
May | 256.67 | 22.62 | 36.33 | 22.86 | 3.00 | 22.83 |
June | 140.33 | 24.20 | 165.17 | 25.07 | 40.17 | 25.29 |
July | 247.67 | 27.76 | 300.00 | 27.60 | 247.67 | 27.65 |
August | 286.83 | 27.87 | 324.00 | 27.77 | 286.83 | 27.80 |
September | 82.83 | 26.25 | 285.67 | 25.99 | 78.00 | 26.07 |
October | 131.00 | 24.63 | 168.83 | 25.48 | 58.50 | 25.66 |
November | 288.00 | 21.12 | 99.17 | 20.80 | 99.17 | 20.60 |
December | 300.00 | 19.70 | 248.83 | 19.56 | 248.83 | 19.51 |
Annual Sum or Average | 2915.83 | 22.15 | 2478.33 | 22.52 | 1908.67 | 22.42 |
Minimum of Months | 82.83 | 18.78 | 36.33 | 18.63 | 3.00 | 18.57 |
Maximum of Months | 324.00 | 27.87 | 324.00 | 27.77 | 286.83 | 27.80 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.200254E+09 | 43397749.47 | 33.75 | 0.195174E+09 | 5080167.54 | 0.00 | 0.43 | 24-JAN-15:30 | 0.00 | 01-JAN-00:10 | 3580.60 | 24-JAN-15:30 | 3487.38 | 18-JAN-14:20 | 432.19 | 17-JAN-14:00 | 757.52 | 24-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 56612359.20 | 12256000.23 | 14.83 | 56558881.30 | 53477.90 | 0.00 | 0.37 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2844.60 | 01-FEB-12:10 | 2844.60 | 01-FEB-12:10 | 68.15 | 01-FEB-13:30 | 625.60 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.135874E+09 | 29085186.19 | 24.00 | 0.117474E+09 | 18400104.90 | 0.00 | 0.47 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4175.99 | 23-MAR-14:00 | 3256.64 | 23-MAR-14:00 | 1050.37 | 23-MAR-15:00 | 862.70 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.671359E+09 | 0.140956E+09 | 77.29 | 0.561012E+09 | 0.110347E+09 | 0.00 | 1.00 | 29-APR-07:03 | 0.00 | 01-APR-00:10 | 15771.02 | 29-APR-07:03 | 12138.87 | 29-APR-07:03 | 3632.16 | 29-APR-07:03 | 3176.84 | 29-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.804474E+09 | 0.168859E+09 | 102.29 | 0.690094E+09 | 0.114379E+09 | 0.00 | 1.00 | 06-MAY-07:03 | 0.00 | 01-MAY-00:10 | 16891.28 | 06-MAY-07:03 | 9977.25 | 06-MAY-07:03 | 6914.02 | 06-MAY-07:03 | 3395.38 | 06-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.281554E+10 | 0.566664E+09 | 180.10 | 0.215389E+10 | 0.661645E+09 | 0.00 | 1.00 | 03-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17994.17 | 30-JUN-07:03 | 12591.29 | 24-JUN-07:02 | 7658.68 | 30-JUN-07:03 | 3586.84 | 30-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.575580E+10 | 0.112970E+10 | 235.82 | 0.417736E+10 | 0.157844E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18547.46 | 19-JUL-07:02 | 12571.35 | 10-JUL-07:03 | 9223.98 | 20-JUL-07:03 | 3674.49 | 19-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.632036E+10 | 0.123444E+10 | 252.75 | 0.450482E+10 | 0.181554E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 18987.44 | 19-AUG-07:02 | 11213.68 | 01-AUG-07:03 | 9726.91 | 18-AUG-07:03 | 3740.28 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.318307E+10 | 0.659923E+09 | 188.68 | 0.243384E+10 | 0.749230E+09 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18193.18 | 09-SEP-07:02 | 16681.66 | 29-SEP-07:03 | 8424.67 | 23-SEP-07:02 | 3619.00 | 09-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.311495E+10 | 0.653660E+09 | 184.94 | 0.262380E+10 | 0.491144E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 18984.02 | 05-OCT-07:02 | 16085.42 | 14-OCT-07:03 | 9162.08 | 05-OCT-07:04 | 3739.78 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.197477E+09 | 42523395.05 | 38.00 | 0.196081E+09 | 1395648.86 | 0.00 | 0.48 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3957.31 | 18-NOV-14:10 | 3957.31 | 18-NOV-14:10 | 314.35 | 10-NOV-13:10 | 851.45 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.233205E+09 | 50516506.42 | 43.50 | 0.232571E+09 | 634607.45 | 0.00 | 0.49 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 3970.55 | 05-DEC-15:00 | 3970.55 | 05-DEC-15:00 | 212.73 | 07-DEC-14:00 | 843.35 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.234890E+11 | 0.473198E+10 | 1375.95 | 0.179427E+11 | 0.554629E+10 | 0.00 | ||||||||||||||
Minimum of Months | 56612359.20 | 12256000.23 | 14.83 | 56558881.30 | 53477.90 | 0.00 | 0.37 | 0.00 | 2844.60 | 2844.60 | 68.15 | 625.60 | 0.00 | |||||||
Maximum of Months | 0.632036E+10 | 0.123444E+10 | 252.75 | 0.450482E+10 | 0.181554E+10 | 0.00 | 1.00 | 0.00 | 18987.44 | 16681.66 | 9726.91 | 3740.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 19676113.72 | 5209587.63 | 2.33 | 17381996.20 | 2294117.52 | 0.00 | 0.16 | 26-APR-13:10 | 0.00 | 01-APR-00:10 | 3109.43 | 26-APR-13:10 | 2764.41 | 26-APR-13:20 | 420.34 | 26-APR-13:10 | 824.26 | 26-APR-13:10 | 0.00 | 01-APR-00:10 |
May | 40130138.95 | 10277413.81 | 6.17 | 33794340.30 | 6335798.66 | 0.00 | 0.16 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 | 3032.59 | 04-MAY-12:10 | 2664.89 | 03-MAY-13:00 | 552.47 | 04-MAY-12:20 | 769.86 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 |
June | 0.101021E+10 | 0.245891E+09 | 60.27 | 0.690634E+09 | 0.319579E+09 | 0.00 | 1.00 | 25-JUN-11:15 | 0.00 | 01-JUN-00:10 | 47779.21 | 29-JUN-17:42 | 35470.10 | 25-JUN-12:42 | 18352.88 | 29-JUN-17:42 | 10415.73 | 29-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.571378E+10 | 0.135078E+10 | 182.70 | 0.385281E+10 | 0.186097E+10 | 0.00 | 1.00 | 02-JUL-10:15 | 0.00 | 01-JUL-00:10 | 49393.89 | 18-JUL-17:25 | 34820.14 | 09-JUL-14:55 | 20440.98 | 24-JUL-17:45 | 10863.35 | 23-JUL-10:53 | 0.00 | 01-JUL-00:10 |
August | 0.571102E+10 | 0.135975E+10 | 192.63 | 0.374855E+10 | 0.196247E+10 | 0.00 | 1.00 | 03-AUG-17:25 | 0.00 | 01-AUG-00:10 | 49324.98 | 13-AUG-10:15 | 34501.98 | 19-AUG-17:25 | 22394.83 | 18-AUG-17:55 | 10853.50 | 06-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 0.105079E+10 | 0.283591E+09 | 49.08 | 0.961285E+09 | 89508806.66 | 0.00 | 1.00 | 10-SEP-13:35 | 0.00 | 01-SEP-00:10 | 47537.17 | 10-SEP-13:35 | 31501.53 | 10-SEP-14:25 | 16664.49 | 10-SEP-13:35 | 10375.48 | 10-SEP-13:35 | 0.00 | 01-SEP-00:10 |
October | 0.137609E+10 | 0.371522E+09 | 53.08 | 0.126287E+10 | 0.113221E+09 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 49272.76 | 01-OCT-12:15 | 31410.36 | 01-OCT-12:15 | 19707.12 | 01-OCT-15:25 | 10873.19 | 01-OCT-12:15 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.149217E+11 | 0.362702E+10 | 546.27 | 0.105673E+11 | 0.435437E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.571378E+10 | 0.135975E+10 | 192.63 | 0.385281E+10 | 0.196247E+10 | 0.00 | 1.00 | 0.00 | 49393.89 | 35470.10 | 22394.83 | 10873.19 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.41 | 32.49 | 31.93 | 89.35 | 72.33 | 0.00 | 0.00 | 0.00 |
February | 76.77 | 35.42 | 41.35 | 101.38 | 64.59 | 0.00 | 0.00 | 0.00 |
March | 87.97 | 38.91 | 49.07 | 117.70 | 67.10 | 0.00 | 0.00 | 0.00 |
April | 121.11 | 62.93 | 58.18 | 172.62 | 62.65 | 0.00 | 0.00 | 0.00 |
May | 119.00 | 54.83 | 64.17 | 162.79 | 60.51 | 0.00 | 0.00 | 0.00 |
June | 126.35 | 63.19 | 63.16 | 179.19 | 51.17 | 0.00 | 0.00 | 0.00 |
July | 133.76 | 71.59 | 62.17 | 196.12 | 51.09 | 0.00 | 0.00 | 0.00 |
August | 125.30 | 67.83 | 57.47 | 186.77 | 53.02 | 0.00 | 0.00 | 0.00 |
September | 107.28 | 57.35 | 49.94 | 156.38 | 57.44 | 0.00 | 0.00 | 0.00 |
October | 82.11 | 44.85 | 37.26 | 123.17 | 61.85 | 0.00 | 0.00 | 0.00 |
November | 74.04 | 38.67 | 35.37 | 101.40 | 72.00 | 0.00 | 0.00 | 0.00 |
December | 65.28 | 34.91 | 30.37 | 90.66 | 75.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.70 | 50.31 | 48.39 | 139.97 | 62.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.41 | 32.49 | 30.37 | 89.35 | 51.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.76 | 71.59 | 64.17 | 196.12 | 75.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.41 | 32.49 | 31.93 | 89.35 | 72.33 | 0.00 | 0.00 | 0.00 |
February | 76.77 | 35.42 | 41.35 | 101.38 | 64.59 | 0.00 | 0.00 | 0.00 |
March | 87.97 | 38.91 | 49.07 | 117.70 | 67.10 | 0.00 | 0.00 | 0.00 |
April | 121.11 | 62.93 | 58.18 | 172.62 | 62.65 | 0.00 | 0.00 | 0.00 |
May | 119.00 | 54.83 | 64.17 | 162.79 | 60.51 | 0.00 | 0.00 | 0.00 |
June | 126.35 | 63.19 | 63.16 | 179.19 | 51.17 | 0.00 | 0.00 | 0.00 |
July | 133.76 | 71.59 | 62.17 | 196.12 | 51.09 | 0.00 | 0.00 | 0.00 |
August | 125.30 | 67.83 | 57.47 | 186.77 | 53.02 | 0.00 | 0.00 | 0.00 |
September | 107.28 | 57.35 | 49.94 | 156.38 | 57.44 | 0.00 | 0.00 | 0.00 |
October | 82.11 | 44.85 | 37.26 | 123.17 | 61.85 | 0.00 | 0.00 | 0.00 |
November | 74.04 | 38.67 | 35.37 | 101.40 | 72.00 | 0.00 | 0.00 | 0.00 |
December | 65.28 | 34.91 | 30.37 | 90.66 | 75.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.70 | 50.31 | 48.39 | 139.97 | 62.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.41 | 32.49 | 30.37 | 89.35 | 51.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.76 | 71.59 | 64.17 | 196.12 | 75.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.63 | 0.00 | 14.63 | 12.34 | 43.23 | 0.00 | 0.00 | 0.00 |
February | 18.36 | 0.00 | 18.36 | 14.63 | 38.78 | 0.00 | 0.00 | 0.00 |
March | 22.50 | 0.00 | 22.50 | 20.19 | 40.19 | 0.00 | 0.00 | 0.00 |
April | 25.99 | 0.15 | 25.84 | 23.82 | 36.73 | 0.00 | 0.00 | 0.00 |
May | 31.35 | 1.63 | 29.72 | 29.63 | 34.07 | 0.00 | 0.00 | 0.00 |
June | 33.15 | 3.20 | 29.95 | 35.18 | 28.80 | 0.00 | 0.00 | 0.00 |
July | 31.39 | 2.59 | 28.80 | 34.18 | 29.06 | 0.00 | 0.00 | 0.00 |
August | 26.20 | 0.61 | 25.59 | 27.61 | 30.60 | 0.00 | 0.00 | 0.00 |
September | 22.10 | 0.01 | 22.09 | 22.12 | 34.70 | 0.00 | 0.00 | 0.00 |
October | 17.52 | 0.00 | 17.52 | 19.60 | 36.96 | 0.00 | 0.00 | 0.00 |
November | 15.87 | 0.00 | 15.87 | 12.45 | 43.39 | 0.00 | 0.00 | 0.00 |
December | 13.62 | 0.00 | 13.62 | 10.61 | 45.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.74 | 0.69 | 22.06 | 21.90 | 36.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.62 | 0.00 | 13.62 | 10.61 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.15 | 3.20 | 29.95 | 35.18 | 45.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.63 | 0.00 | 14.63 | 12.34 | 43.23 | 0.00 | 0.00 | 0.00 |
February | 18.36 | 0.00 | 18.36 | 14.63 | 38.78 | 0.00 | 0.00 | 0.00 |
March | 22.50 | 0.00 | 22.50 | 20.19 | 40.19 | 0.00 | 0.00 | 0.00 |
April | 25.99 | 0.15 | 25.84 | 23.82 | 36.73 | 0.00 | 0.00 | 0.00 |
May | 31.35 | 1.63 | 29.72 | 29.63 | 34.07 | 0.00 | 0.00 | 0.00 |
June | 33.15 | 3.20 | 29.95 | 35.17 | 28.80 | 0.00 | 0.00 | 0.00 |
July | 31.39 | 2.59 | 28.80 | 34.18 | 29.06 | 0.00 | 0.00 | 0.00 |
August | 26.20 | 0.61 | 25.59 | 27.61 | 30.60 | 0.00 | 0.00 | 0.00 |
September | 22.10 | 0.01 | 22.09 | 22.12 | 34.70 | 0.00 | 0.00 | 0.00 |
October | 17.52 | 0.00 | 17.52 | 19.60 | 36.96 | 0.00 | 0.00 | 0.00 |
November | 15.87 | 0.00 | 15.87 | 12.45 | 43.39 | 0.00 | 0.00 | 0.00 |
December | 13.62 | 0.00 | 13.62 | 10.61 | 45.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.74 | 0.69 | 22.06 | 21.90 | 36.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.62 | 0.00 | 13.62 | 10.61 | 28.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.15 | 3.20 | 29.95 | 35.17 | 45.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 97.78 | 43.35 | 16.50 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 108.35 | 37.43 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 143.87 | 37.24 | 25.00 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 217.50 | 36.41 | 0.00 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 213.54 | 34.72 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 228.79 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.89 | 31.44 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 235.23 | 32.99 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 179.49 | 35.23 | 0.17 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.02 | 39.36 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 102.24 | 43.80 | 8.33 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 89.78 | 46.67 | 9.83 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 166.85 | 37.37 | 64.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 89.78 | 29.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.89 | 46.67 | 25.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.97 | 52.12 | 26.85 | 100.75 | 40.59 | 13.83 | 0.00 | 0.00 |
February | 89.79 | 50.54 | 39.25 | 111.38 | 35.19 | 4.83 | 0.00 | 0.00 |
March | 116.06 | 65.62 | 50.44 | 147.88 | 34.18 | 44.17 | 0.00 | 0.00 |
April | 173.39 | 125.15 | 48.24 | 222.70 | 33.04 | 6.67 | 0.00 | 0.00 |
May | 173.00 | 110.14 | 62.86 | 217.55 | 32.89 | 0.00 | 0.00 | 0.00 |
June | 183.45 | 125.20 | 58.25 | 232.47 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 201.04 | 149.63 | 51.41 | 252.83 | 33.29 | 0.00 | 0.00 | 0.00 |
August | 186.36 | 142.05 | 44.31 | 234.27 | 35.86 | 0.00 | 0.00 | 0.00 |
September | 143.71 | 101.67 | 42.03 | 180.66 | 36.11 | 0.67 | 0.00 | 0.00 |
October | 103.19 | 71.18 | 32.00 | 129.94 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 84.13 | 53.98 | 30.15 | 104.13 | 43.10 | 2.17 | 0.00 | 0.00 |
December | 73.69 | 50.23 | 23.46 | 92.13 | 44.91 | 7.33 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 91.69 | 42.44 | 169.19 | 36.49 | 79.67 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 50.23 | 23.46 | 92.13 | 28.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.04 | 149.63 | 62.86 | 252.83 | 44.91 | 44.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172520E+09 | 87008483.01 | 85511893.36 | 0.239303E+09 | 0.193736E+09 |
February | 0.185716E+09 | 85688879.95 | 0.100027E+09 | 0.245269E+09 | 0.156259E+09 |
March | 0.235631E+09 | 0.104204E+09 | 0.131426E+09 | 0.315251E+09 | 0.179724E+09 |
April | 0.313911E+09 | 0.163121E+09 | 0.150790E+09 | 0.447438E+09 | 0.162386E+09 |
May | 0.318735E+09 | 0.146851E+09 | 0.171884E+09 | 0.436019E+09 | 0.162062E+09 |
June | 0.327495E+09 | 0.163791E+09 | 0.163703E+09 | 0.464471E+09 | 0.132629E+09 |
July | 0.358267E+09 | 0.191752E+09 | 0.166515E+09 | 0.525301E+09 | 0.136843E+09 |
August | 0.335603E+09 | 0.181687E+09 | 0.153916E+09 | 0.500251E+09 | 0.142002E+09 |
September | 0.278082E+09 | 0.148640E+09 | 0.129443E+09 | 0.405344E+09 | 0.148892E+09 |
October | 0.219931E+09 | 0.120139E+09 | 99791852.06 | 0.329901E+09 | 0.165660E+09 |
November | 0.191911E+09 | 0.100220E+09 | 91690786.11 | 0.262833E+09 | 0.186629E+09 |
December | 0.174848E+09 | 93503618.68 | 81344281.86 | 0.242826E+09 | 0.203269E+09 |
Annual Sum or Average | 0.311265E+10 | 0.158661E+10 | 0.152604E+10 | 0.441421E+10 | 0.197009E+10 |
Minimum of Months | 0.172520E+09 | 85688879.95 | 81344281.86 | 0.239303E+09 | 0.132629E+09 |
Maximum of Months | 0.358267E+09 | 0.191752E+09 | 0.171884E+09 | 0.525301E+09 | 0.203269E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172520E+09 | 87008483.01 | 85511893.36 | 0.239303E+09 | 0.193736E+09 |
February | 0.185716E+09 | 85688879.95 | 0.100027E+09 | 0.245269E+09 | 0.156259E+09 |
March | 0.235631E+09 | 0.104204E+09 | 0.131426E+09 | 0.315251E+09 | 0.179724E+09 |
April | 0.313911E+09 | 0.163121E+09 | 0.150790E+09 | 0.447438E+09 | 0.162386E+09 |
May | 0.318735E+09 | 0.146851E+09 | 0.171884E+09 | 0.436019E+09 | 0.162062E+09 |
June | 0.327495E+09 | 0.163791E+09 | 0.163703E+09 | 0.464471E+09 | 0.132629E+09 |
July | 0.358267E+09 | 0.191752E+09 | 0.166515E+09 | 0.525301E+09 | 0.136843E+09 |
August | 0.335603E+09 | 0.181687E+09 | 0.153916E+09 | 0.500251E+09 | 0.142002E+09 |
September | 0.278082E+09 | 0.148640E+09 | 0.129443E+09 | 0.405344E+09 | 0.148892E+09 |
October | 0.219931E+09 | 0.120139E+09 | 99791852.06 | 0.329901E+09 | 0.165660E+09 |
November | 0.191911E+09 | 0.100220E+09 | 91690786.11 | 0.262833E+09 | 0.186629E+09 |
December | 0.174848E+09 | 93503618.68 | 81344281.86 | 0.242826E+09 | 0.203269E+09 |
Annual Sum or Average | 0.311265E+10 | 0.158661E+10 | 0.152604E+10 | 0.441421E+10 | 0.197009E+10 |
Minimum of Months | 0.172520E+09 | 85688879.95 | 81344281.86 | 0.239303E+09 | 0.132629E+09 |
Maximum of Months | 0.358267E+09 | 0.191752E+09 | 0.171884E+09 | 0.525301E+09 | 0.203269E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39180440.36 | 0.00 | 39180440.36 | 33057978.15 | 0.115788E+09 |
February | 44422348.44 | 0.00 | 44422348.44 | 35383017.59 | 93826457.91 |
March | 60275496.02 | 1891.92 | 60273604.10 | 54079517.38 | 0.107657E+09 |
April | 67377058.44 | 401407.28 | 66975651.16 | 61737334.64 | 95197460.77 |
May | 83958900.97 | 4364064.65 | 79594836.32 | 79356106.95 | 91244492.19 |
June | 85915259.84 | 8287439.62 | 77627820.23 | 91174451.93 | 74656007.78 |
July | 84079046.43 | 6931707.61 | 77147338.82 | 91556891.49 | 77847691.41 |
August | 70175901.41 | 1637363.10 | 68538538.31 | 73947155.81 | 81948544.34 |
September | 57278866.92 | 20196.66 | 57258670.27 | 57325095.53 | 89952131.67 |
October | 46938181.22 | 0.00 | 46938181.22 | 52488045.47 | 99004210.83 |
November | 41128196.19 | 0.00 | 41128196.19 | 32280675.39 | 0.112455E+09 |
December | 36473657.13 | 0.00 | 36473657.13 | 28406676.27 | 0.121999E+09 |
Annual Sum or Average | 0.717203E+09 | 21644070.83 | 0.695559E+09 | 0.690793E+09 | 0.116158E+10 |
Minimum of Months | 36473657.13 | 0.00 | 36473657.13 | 28406676.27 | 74656007.78 |
Maximum of Months | 85915259.84 | 8287439.62 | 79594836.32 | 91556891.49 | 0.121999E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39179352.82 | 0.00 | 39179352.82 | 33056901.01 | 0.115787E+09 |
February | 44421026.75 | 0.00 | 44421026.75 | 35381468.63 | 93825839.30 |
March | 60273709.52 | 1891.83 | 60271817.69 | 54077208.60 | 0.107656E+09 |
April | 67375371.63 | 401388.47 | 66973983.16 | 61735457.05 | 95197050.56 |
May | 83956469.13 | 4363860.10 | 79592609.03 | 79352715.13 | 91244116.74 |
June | 85912769.02 | 8287051.17 | 77625717.85 | 91170839.31 | 74655738.99 |
July | 84076837.05 | 6931382.71 | 77145454.34 | 91553878.57 | 77847287.14 |
August | 70174221.71 | 1637286.35 | 68536935.35 | 73945251.88 | 81948121.34 |
September | 57277403.05 | 20195.71 | 57257207.34 | 57323391.29 | 89951570.81 |
October | 46936925.77 | 0.00 | 46936925.77 | 52486699.65 | 99003363.43 |
November | 41127040.51 | 0.00 | 41127040.51 | 32279483.72 | 0.112454E+09 |
December | 36472664.03 | 0.00 | 36472664.03 | 28405837.23 | 0.121998E+09 |
Annual Sum or Average | 0.717184E+09 | 21643056.35 | 0.695541E+09 | 0.690769E+09 | 0.116157E+10 |
Minimum of Months | 36472664.03 | 0.00 | 36472664.03 | 28405837.23 | 74655738.99 |
Maximum of Months | 85912769.02 | 8287051.17 | 79592609.03 | 91553878.57 | 0.121998E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.261894E+09 | 0.116102E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.262129E+09 | 90546903.43 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.385353E+09 | 99734250.63 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.563772E+09 | 94383505.65 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.571935E+09 | 92989495.62 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.593032E+09 | 76991010.91 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677338E+09 | 84203811.58 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.630028E+09 | 88364799.40 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.465238E+09 | 91303827.12 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.345556E+09 | 0.105417E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.265017E+09 | 0.113537E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.240461E+09 | 0.125006E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.526175E+10 | 0.117858E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.240461E+09 | 76991010.91 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677338E+09 | 0.125006E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211517E+09 | 0.139600E+09 | 71916697.35 | 0.269855E+09 | 0.108722E+09 |
February | 0.217217E+09 | 0.122263E+09 | 94954173.61 | 0.269458E+09 | 85120531.08 |
March | 0.310856E+09 | 0.175765E+09 | 0.135091E+09 | 0.396078E+09 | 91548633.50 |
April | 0.449426E+09 | 0.324386E+09 | 0.125040E+09 | 0.577239E+09 | 85627539.11 |
May | 0.463373E+09 | 0.295012E+09 | 0.168362E+09 | 0.582678E+09 | 88096916.29 |
June | 0.475502E+09 | 0.324514E+09 | 0.150988E+09 | 0.602558E+09 | 72863497.07 |
July | 0.538472E+09 | 0.400770E+09 | 0.137702E+09 | 0.677171E+09 | 89167208.62 |
August | 0.499156E+09 | 0.380478E+09 | 0.118679E+09 | 0.627482E+09 | 96043764.37 |
September | 0.372487E+09 | 0.263538E+09 | 0.108950E+09 | 0.468268E+09 | 93598364.77 |
October | 0.276374E+09 | 0.190655E+09 | 85718368.22 | 0.348022E+09 | 0.107981E+09 |
November | 0.218068E+09 | 0.139920E+09 | 78148097.78 | 0.269910E+09 | 0.111715E+09 |
December | 0.197367E+09 | 0.134537E+09 | 62830658.66 | 0.246763E+09 | 0.120277E+09 |
Annual Sum or Average | 0.422982E+10 | 0.289144E+10 | 0.133838E+10 | 0.533548E+10 | 0.115076E+10 |
Minimum of Months | 0.197367E+09 | 0.122263E+09 | 62830658.66 | 0.246763E+09 | 72863497.07 |
Maximum of Months | 0.538472E+09 | 0.400770E+09 | 0.168362E+09 | 0.677171E+09 | 0.120277E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 201.20 | 228.95 | 158.08 | 64.97 | 93.11 | 0.00 | 0.00 |
February | 229.83 | 204.56 | 190.26 | 70.84 | 119.42 | 0.00 | 0.00 |
March | 273.57 | 212.38 | 220.96 | 77.81 | 143.14 | 0.00 | 0.00 |
April | 391.50 | 197.38 | 294.20 | 126.17 | 168.03 | 0.00 | 0.00 |
May | 383.17 | 187.48 | 300.70 | 112.91 | 187.78 | 0.00 | 0.00 |
June | 427.11 | 158.31 | 318.99 | 132.78 | 186.21 | 0.00 | 0.00 |
July | 458.97 | 158.67 | 330.31 | 148.36 | 181.95 | 0.00 | 0.00 |
August | 427.66 | 166.12 | 303.00 | 136.89 | 166.11 | 0.00 | 0.00 |
September | 354.50 | 181.79 | 258.77 | 114.71 | 144.06 | 0.00 | 0.00 |
October | 283.58 | 195.68 | 199.27 | 89.71 | 109.56 | 0.00 | 0.00 |
November | 224.78 | 227.84 | 179.81 | 77.33 | 102.48 | 0.00 | 0.00 |
December | 199.94 | 240.29 | 157.80 | 69.82 | 87.98 | 0.00 | 0.00 |
Annual Sum or Average | 321.76 | 196.61 | 242.89 | 101.99 | 140.89 | 0.00 | 0.00 |
Minimum of Months | 199.94 | 158.31 | 157.80 | 64.97 | 87.98 | 0.00 | 0.00 |
Maximum of Months | 458.97 | 240.29 | 330.31 | 148.36 | 187.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1368.92 | 606.87 | 1105.60 | 729.69 | 375.91 | 0.00 | 0.00 |
February | 1516.95 | 524.00 | 1257.04 | 707.54 | 549.50 | 0.00 | 0.00 |
March | 2014.24 | 521.31 | 1624.85 | 918.72 | 706.12 | 0.00 | 0.00 |
April | 3045.07 | 509.79 | 2427.46 | 1752.09 | 675.37 | 0.00 | 0.00 |
May | 2989.50 | 486.06 | 2422.05 | 1542.03 | 880.03 | 0.00 | 0.00 |
June | 3203.11 | 415.85 | 2568.30 | 1752.78 | 815.52 | 0.00 | 0.00 |
July | 3540.44 | 440.13 | 2814.59 | 2094.83 | 719.77 | 0.00 | 0.00 |
August | 3293.16 | 461.88 | 2609.09 | 1988.76 | 620.33 | 0.00 | 0.00 |
September | 2512.86 | 493.15 | 2011.89 | 1423.43 | 588.46 | 0.00 | 0.00 |
October | 1806.22 | 551.01 | 1444.60 | 996.55 | 448.05 | 0.00 | 0.00 |
November | 1431.42 | 613.24 | 1177.84 | 755.74 | 422.10 | 0.00 | 0.00 |
December | 1256.89 | 653.41 | 1031.64 | 703.22 | 328.42 | 0.00 | 0.00 |
Annual Sum or Average | 2335.89 | 523.22 | 1877.77 | 1283.62 | 594.16 | 0.00 | 0.00 |
Minimum of Months | 1256.89 | 415.85 | 1031.64 | 703.22 | 328.42 | 0.00 | 0.00 |
Maximum of Months | 3540.44 | 653.41 | 2814.59 | 2094.83 | 880.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13194.51 | 4492.80 | 2527.08 | 1667.86 | 859.22 | 0.00 | 0.00 |
February | 14733.10 | 3712.99 | 2873.24 | 1617.23 | 1256.01 | 0.00 | 0.00 |
March | 20127.67 | 3441.58 | 3713.93 | 2099.94 | 1613.99 | 0.00 | 0.00 |
April | 28213.43 | 3179.98 | 5548.47 | 4004.77 | 1543.70 | 0.00 | 0.00 |
May | 27026.52 | 3157.45 | 5536.12 | 3524.63 | 2011.49 | 0.00 | 0.00 |
June | 27725.05 | 2698.35 | 5870.39 | 4006.35 | 1864.05 | 0.00 | 0.00 |
July | 30985.60 | 3209.57 | 6433.35 | 4788.17 | 1645.18 | 0.00 | 0.00 |
August | 27206.00 | 3460.76 | 5963.64 | 4545.73 | 1417.91 | 0.00 | 0.00 |
September | 20653.74 | 3482.97 | 4598.61 | 3253.55 | 1345.06 | 0.00 | 0.00 |
October | 16063.86 | 3938.31 | 3301.95 | 2277.84 | 1024.11 | 0.00 | 0.00 |
November | 13598.24 | 4497.42 | 2692.20 | 1727.40 | 964.79 | 0.00 | 0.00 |
December | 12212.17 | 4835.97 | 2358.03 | 1607.37 | 750.66 | 0.00 | 0.00 |
Annual Sum or Average | 21012.46 | 3677.68 | 4292.05 | 2933.98 | 1358.07 | 0.00 | 0.00 |
Minimum of Months | 12212.17 | 2698.35 | 2358.03 | 1607.37 | 750.66 | 0.00 | 0.00 |
Maximum of Months | 30985.60 | 4835.97 | 6433.35 | 4788.17 | 2011.49 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.538894E+09 | 0.613219E+09 | 0.423401E+09 | 0.174017E+09 | 0.249384E+09 | 0.00 | 0.00 |
February | 0.555993E+09 | 0.494860E+09 | 0.460275E+09 | 0.171378E+09 | 0.288898E+09 | 0.00 | 0.00 |
March | 0.732727E+09 | 0.568829E+09 | 0.591811E+09 | 0.208412E+09 | 0.383398E+09 | 0.00 | 0.00 |
April | 0.101478E+10 | 0.511598E+09 | 0.762575E+09 | 0.327045E+09 | 0.435530E+09 | 0.00 | 0.00 |
May | 0.102628E+10 | 0.502145E+09 | 0.805385E+09 | 0.302430E+09 | 0.502955E+09 | 0.00 | 0.00 |
June | 0.110707E+10 | 0.410347E+09 | 0.826817E+09 | 0.344157E+09 | 0.482660E+09 | 0.00 | 0.00 |
July | 0.122932E+10 | 0.424987E+09 | 0.884690E+09 | 0.397366E+09 | 0.487323E+09 | 0.00 | 0.00 |
August | 0.114544E+10 | 0.444948E+09 | 0.811556E+09 | 0.366648E+09 | 0.444908E+09 | 0.00 | 0.00 |
September | 0.918852E+09 | 0.471205E+09 | 0.670721E+09 | 0.297320E+09 | 0.373401E+09 | 0.00 | 0.00 |
October | 0.759551E+09 | 0.524102E+09 | 0.533737E+09 | 0.240278E+09 | 0.293459E+09 | 0.00 | 0.00 |
November | 0.582632E+09 | 0.590574E+09 | 0.466077E+09 | 0.200440E+09 | 0.265637E+09 | 0.00 | 0.00 |
December | 0.535529E+09 | 0.643601E+09 | 0.422642E+09 | 0.187007E+09 | 0.235635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101471E+11 | 0.620041E+10 | 0.765969E+10 | 0.321650E+10 | 0.444319E+10 | 0.00 | 0.00 |
Minimum of Months | 0.535529E+09 | 0.410347E+09 | 0.422642E+09 | 0.171378E+09 | 0.235635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122932E+10 | 0.643601E+09 | 0.884690E+09 | 0.397366E+09 | 0.502955E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366652E+10 | 0.162543E+10 | 0.296123E+10 | 0.195440E+10 | 0.100683E+10 | 0.00 | 0.00 |
February | 0.366980E+10 | 0.126766E+10 | 0.304104E+10 | 0.171168E+10 | 0.132936E+10 | 0.00 | 0.00 |
March | 0.539494E+10 | 0.139628E+10 | 0.435199E+10 | 0.246071E+10 | 0.189128E+10 | 0.00 | 0.00 |
April | 0.789281E+10 | 0.132137E+10 | 0.629197E+10 | 0.454141E+10 | 0.175056E+10 | 0.00 | 0.00 |
May | 0.800708E+10 | 0.130185E+10 | 0.648723E+10 | 0.413016E+10 | 0.235706E+10 | 0.00 | 0.00 |
June | 0.830245E+10 | 0.107787E+10 | 0.665703E+10 | 0.454320E+10 | 0.211383E+10 | 0.00 | 0.00 |
July | 0.948273E+10 | 0.117885E+10 | 0.753860E+10 | 0.561078E+10 | 0.192782E+10 | 0.00 | 0.00 |
August | 0.882039E+10 | 0.123711E+10 | 0.698819E+10 | 0.532669E+10 | 0.166150E+10 | 0.00 | 0.00 |
September | 0.651333E+10 | 0.127825E+10 | 0.521482E+10 | 0.368953E+10 | 0.152529E+10 | 0.00 | 0.00 |
October | 0.483778E+10 | 0.147583E+10 | 0.386923E+10 | 0.266917E+10 | 0.120006E+10 | 0.00 | 0.00 |
November | 0.371024E+10 | 0.158952E+10 | 0.305295E+10 | 0.195888E+10 | 0.109407E+10 | 0.00 | 0.00 |
December | 0.336646E+10 | 0.175008E+10 | 0.276314E+10 | 0.188351E+10 | 0.879629E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.736645E+11 | 0.165001E+11 | 0.592174E+11 | 0.404801E+11 | 0.187373E+11 | 0.00 | 0.00 |
Minimum of Months | 0.336646E+10 | 0.107787E+10 | 0.276314E+10 | 0.171168E+10 | 0.879629E+09 | 0.00 | 0.00 |
Maximum of Months | 0.948273E+10 | 0.175008E+10 | 0.753860E+10 | 0.561078E+10 | 0.235706E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.353402E+11 | 0.120335E+11 | 0.676853E+10 | 0.446720E+10 | 0.230133E+10 | 0.00 | 0.00 |
February | 0.356423E+11 | 0.898245E+10 | 0.695095E+10 | 0.391241E+10 | 0.303853E+10 | 0.00 | 0.00 |
March | 0.539100E+11 | 0.921794E+10 | 0.994740E+10 | 0.562448E+10 | 0.432292E+10 | 0.00 | 0.00 |
April | 0.731292E+11 | 0.824250E+10 | 0.143816E+11 | 0.103804E+11 | 0.400128E+10 | 0.00 | 0.00 |
May | 0.723878E+11 | 0.845691E+10 | 0.148279E+11 | 0.944037E+10 | 0.538758E+10 | 0.00 | 0.00 |
June | 0.718633E+11 | 0.699411E+10 | 0.152161E+11 | 0.103845E+11 | 0.483161E+10 | 0.00 | 0.00 |
July | 0.829918E+11 | 0.859652E+10 | 0.172311E+11 | 0.128246E+11 | 0.440645E+10 | 0.00 | 0.00 |
August | 0.728685E+11 | 0.926930E+10 | 0.159730E+11 | 0.121753E+11 | 0.379772E+10 | 0.00 | 0.00 |
September | 0.535345E+11 | 0.902785E+10 | 0.119196E+11 | 0.843320E+10 | 0.348638E+10 | 0.00 | 0.00 |
October | 0.430254E+11 | 0.105484E+11 | 0.884395E+10 | 0.610097E+10 | 0.274299E+10 | 0.00 | 0.00 |
November | 0.352466E+11 | 0.116573E+11 | 0.697817E+10 | 0.447743E+10 | 0.250074E+10 | 0.00 | 0.00 |
December | 0.327091E+11 | 0.129527E+11 | 0.631575E+10 | 0.430517E+10 | 0.201058E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662649E+12 | 0.115979E+12 | 0.135354E+12 | 0.925260E+11 | 0.428281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327091E+11 | 0.699411E+10 | 0.631575E+10 | 0.391241E+10 | 0.201058E+10 | 0.00 | 0.00 |
Maximum of Months | 0.829918E+11 | 0.129527E+11 | 0.172311E+11 | 0.128246E+11 | 0.538758E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.808109E+09 | -742382962.8 | 0.00 | 0.00 | 744.00 | 0.00 | -65725685.4 | 58.99 | 0.00 | 0.00 |
February | 0.741870E+09 | -682787411.3 | 0.00 | 0.00 | 672.00 | 0.00 | -59082759.7 | 59.01 | 0.00 | 0.00 |
March | 0.854496E+09 | -789296983.1 | 0.00 | 0.00 | 744.00 | 0.00 | -65199329.3 | 58.99 | 0.00 | 0.00 |
April | 0.777922E+09 | -718028442.9 | 0.00 | 0.00 | 720.00 | 0.00 | -59893888.8 | 58.99 | 0.00 | 0.00 |
May | 0.788543E+09 | -727628517.3 | 0.00 | 0.00 | 744.00 | 0.00 | -60914088.4 | 58.99 | 0.00 | 0.00 |
June | 0.765727E+09 | -708293937.5 | 0.00 | 0.00 | 720.00 | 0.00 | -57433090.8 | 58.99 | 0.00 | 0.00 |
July | 0.732055E+09 | -674436176.5 | 0.00 | 0.00 | 744.00 | 0.00 | -57618580.7 | 58.98 | 0.00 | 0.00 |
August | 0.781355E+09 | -723282880.7 | 0.00 | 0.00 | 744.00 | 0.00 | -58072393.2 | 58.99 | 0.00 | 0.00 |
September | 0.737650E+09 | -680588561.2 | 0.00 | 0.00 | 720.00 | 0.00 | -57061903.7 | 58.99 | 0.00 | 0.00 |
October | 0.757246E+09 | -697621330.4 | 0.00 | 0.00 | 744.00 | 0.00 | -59624846.8 | 58.99 | 0.00 | 0.00 |
November | 0.749124E+09 | -687579630.9 | 0.00 | 0.00 | 720.00 | 0.00 | -61544639.2 | 59.00 | 0.00 | 0.00 |
December | 0.797054E+09 | -732052440.1 | 0.00 | 0.00 | 744.00 | 0.00 | -65001106.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929115E+10 | -0.856398E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -727172312.7 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.732055E+09 | -789296983.1 | 0.00 | 0.00 | 672.00 | 0.00 | -65725685.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.854496E+09 | -674436176.5 | 0.00 | 0.00 | 744.00 | 0.00 | -57061903.7 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.72 | 0.50 | 01-JAN-11:50 | 206.13 | 0.00 | 0.00 | 46.83 | 174.99 | 0.00 | 0.00 | 27.67 |
February | 279.67 | 0.66 | 0.50 | 01-FEB-10:50 | 271.92 | 0.00 | 0.00 | 94.50 | 1032.71 | 0.00 | 0.00 | 81.83 |
March | 338.17 | 0.64 | 0.50 | 01-MAR-10:00 | 1322.48 | 0.00 | 0.00 | 177.67 | 349.77 | 0.00 | 0.00 | 113.33 |
April | 358.33 | 0.63 | 0.50 | 01-APR-09:00 | 318.06 | 0.00 | 0.00 | 182.50 | 259.28 | 0.00 | 0.00 | 132.00 |
May | 393.83 | 0.62 | 0.50 | 01-MAY-09:09 | 386.52 | 0.00 | 0.00 | 236.33 | 2897.47 | 0.00 | 0.00 | 164.83 |
June | 381.00 | 0.62 | 0.50 | 01-JUN-09:30 | 2480.19 | 0.00 | 0.00 | 221.83 | 1053.01 | 0.00 | 0.00 | 142.17 |
July | 408.67 | 0.63 | 0.50 | 01-JUL-09:09 | 336.93 | 0.00 | 0.00 | 216.33 | 3521.25 | 0.00 | 0.00 | 138.50 |
August | 390.67 | 0.64 | 0.50 | 01-AUG-09:09 | 300.46 | 0.00 | 0.00 | 188.33 | 1095.15 | 0.00 | 0.00 | 129.50 |
September | 328.83 | 0.63 | 0.50 | 01-SEP-09:00 | 300.54 | 0.00 | 0.00 | 145.50 | 246.63 | 0.00 | 0.00 | 100.00 |
October | 296.17 | 0.70 | 0.50 | 01-OCT-09:39 | 2129.17 | 0.00 | 0.00 | 98.83 | 195.18 | 0.00 | 0.00 | 48.83 |
November | 300.00 | 0.71 | 0.50 | 01-NOV-09:30 | 218.90 | 0.00 | 0.00 | 62.67 | 185.43 | 0.00 | 0.00 | 45.50 |
December | 297.00 | 0.75 | 0.50 | 01-DEC-10:20 | 179.19 | 0.00 | 0.00 | 29.83 | 153.46 | 0.00 | 0.00 | 16.00 |
Annual Sum or Average | 4065.67 | 0.66 | 712.86 | 0.00 | 0.00 | 1701.17 | 1033.19 | 0.00 | 0.00 | 1140.17 | ||
Minimum of Months | 279.67 | 0.62 | 0.50 | 179.19 | 0.00 | 0.00 | 29.83 | 153.46 | 0.00 | 0.00 | 16.00 | |
Maximum of Months | 408.67 | 0.75 | 0.50 | 2480.19 | 0.00 | 0.00 | 236.33 | 3521.25 | 0.00 | 0.00 | 164.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.60 | 0.50 | 01-JAN-08:50 | 242.67 | 13.61 | 0.00 | 181.00 | 199.57 | 17.48 | 40.00 | 127.67 |
February | 279.67 | 0.58 | 0.50 | 01-FEB-08:39 | 313.39 | 14.66 | 0.00 | 203.00 | 1274.52 | 18.48 | 62.83 | 166.50 |
March | 338.17 | 0.57 | 0.50 | 01-MAR-08:30 | 374.43 | 15.10 | 0.00 | 267.67 | 422.99 | 18.92 | 105.67 | 230.50 |
April | 358.33 | 0.56 | 0.50 | 01-APR-07:30 | 2194.00 | 16.44 | 38.83 | 292.17 | 310.38 | 19.05 | 106.17 | 242.17 |
May | 393.83 | 0.55 | 0.50 | 01-MAY-06:30 | 422.65 | 15.38 | 8.83 | 331.67 | 358.29 | 19.26 | 121.50 | 281.50 |
June | 381.00 | 0.56 | 0.50 | 01-JUN-06:30 | 398.49 | 14.95 | 2.50 | 325.67 | 333.98 | 18.79 | 100.33 | 274.00 |
July | 408.67 | 0.56 | 0.50 | 01-JUL-06:30 | 373.25 | 14.70 | 2.67 | 332.33 | 313.32 | 18.67 | 120.67 | 274.50 |
August | 390.67 | 0.56 | 0.50 | 01-AUG-06:00 | 2364.87 | 16.07 | 36.67 | 306.83 | 291.19 | 18.63 | 109.67 | 249.17 |
September | 328.83 | 0.56 | 0.50 | 01-SEP-06:49 | 347.31 | 14.45 | 1.00 | 266.67 | 286.62 | 18.37 | 75.67 | 214.00 |
October | 296.17 | 0.60 | 0.50 | 01-OCT-09:39 | 3575.22 | 15.41 | 36.17 | 205.50 | 1348.78 | 19.18 | 67.83 | 167.67 |
November | 300.00 | 0.61 | 0.50 | 01-NOV-07:40 | 255.50 | 13.35 | 0.00 | 186.50 | 209.69 | 17.13 | 41.83 | 134.17 |
December | 297.00 | 0.62 | 0.50 | 01-DEC-08:09 | 211.22 | 12.81 | 0.00 | 158.00 | 172.91 | 16.64 | 13.00 | 96.50 |
Annual Sum or Average | 4065.67 | 0.58 | 929.43 | 14.82 | 126.67 | 3057.00 | 439.63 | 18.44 | 965.17 | 2458.33 | ||
Minimum of Months | 279.67 | 0.55 | 0.50 | 211.22 | 12.81 | 0.00 | 158.00 | 172.91 | 16.64 | 13.00 | 96.50 | |
Maximum of Months | 408.67 | 0.62 | 0.50 | 3575.22 | 16.44 | 38.83 | 332.33 | 1348.78 | 19.26 | 121.50 | 281.50 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.83 | 0.64 | 30-JAN-15:50 | 302.56 | 22.49 | 111.67 | 36.67 | 101.04 | 19.88 | 86.17 | 0.00 |
February | 279.67 | 0.80 | 0.61 | 07-FEB-15:30 | 318.38 | 22.82 | 126.17 | 45.83 | 155.82 | 22.17 | 125.00 | 12.83 |
March | 338.17 | 0.79 | 0.61 | 01-MAR-15:20 | 269.57 | 21.99 | 144.00 | 54.67 | 219.48 | 23.05 | 156.50 | 36.00 |
April | 358.33 | 0.78 | 0.61 | 01-APR-14:39 | 237.92 | 20.51 | 131.17 | 64.67 | 339.06 | 22.14 | 155.17 | 63.50 |
May | 393.83 | 0.77 | 0.61 | 01-MAY-15:09 | 240.48 | 20.29 | 132.67 | 59.33 | 298.93 | 21.65 | 183.17 | 68.00 |
June | 381.00 | 0.77 | 0.61 | 01-JUN-14:00 | 242.86 | 20.22 | 130.67 | 60.00 | 232.52 | 21.81 | 168.83 | 71.83 |
July | 408.67 | 0.77 | 0.61 | 01-JUL-15:30 | 240.79 | 20.24 | 144.33 | 60.00 | 238.42 | 21.83 | 191.50 | 78.83 |
August | 390.67 | 0.78 | 0.61 | 01-AUG-15:09 | 230.02 | 20.23 | 141.50 | 60.17 | 342.94 | 21.70 | 175.00 | 72.50 |
September | 328.83 | 0.78 | 0.61 | 01-SEP-15:09 | 254.87 | 21.83 | 142.67 | 59.00 | 258.92 | 23.75 | 162.00 | 49.67 |
October | 296.17 | 0.81 | 0.61 | 01-OCT-15:20 | 354.69 | 22.66 | 110.67 | 40.33 | 258.04 | 22.49 | 103.00 | 25.83 |
November | 300.00 | 0.82 | 0.61 | 03-NOV-15:30 | 271.52 | 22.60 | 132.33 | 37.67 | 108.95 | 19.82 | 106.00 | 0.00 |
December | 297.00 | 0.84 | 0.64 | 02-DEC-15:30 | 247.30 | 22.25 | 114.17 | 30.67 | 95.10 | 19.44 | 82.50 | 0.00 |
Annual Sum or Average | 4065.67 | 0.79 | 264.03 | 21.37 | 1562.00 | 609.00 | 228.54 | 21.69 | 1694.83 | 479.00 | ||
Minimum of Months | 279.67 | 0.77 | 0.61 | 230.02 | 20.22 | 110.67 | 30.67 | 95.10 | 19.44 | 82.50 | 0.00 | |
Maximum of Months | 408.67 | 0.84 | 0.64 | 354.69 | 22.82 | 144.33 | 64.67 | 342.94 | 23.75 | 191.50 | 78.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.449469E+09 | 24121.13 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209278E+09 | 24121.13 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377493E+09 | 24121.13 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27753842.07 | 24121.13 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1826400.04 | 8620.48 | 15-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 139013.97 | 695.07 | 30-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57266484.25 | 12945.75 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209201E+09 | 24121.13 | 13-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.449469E+09 | 24121.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115332E+09 | 34396.39 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1142545.91 | 11425.46 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115332E+09 | 34396.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200254E+09 | 0.195174E+09 | 3580.60 | 24-JAN-15:30 | 3486.82 | 0.00 |
February | 0.00 | 0.00 | 56612359.20 | 56558881.30 | 2844.60 | 01-FEB-12:10 | 2844.60 | 0.00 |
March | 0.00 | 0.00 | 0.135874E+09 | 0.117474E+09 | 4175.99 | 23-MAR-14:00 | 3256.64 | 0.00 |
April | 0.00 | 0.00 | 0.671359E+09 | 0.561012E+09 | 15771.02 | 29-APR-07:03 | 12138.87 | 0.00 |
May | 0.00 | 0.00 | 0.804474E+09 | 0.690094E+09 | 16891.28 | 06-MAY-07:03 | 9977.25 | 0.00 |
June | 0.00 | 0.00 | 0.281554E+10 | 0.215389E+10 | 17994.17 | 30-JUN-07:03 | 10335.50 | 0.00 |
July | 0.00 | 0.00 | 0.575580E+10 | 0.417736E+10 | 18547.46 | 19-JUL-07:02 | 10237.69 | 0.00 |
August | 0.00 | 0.00 | 0.632036E+10 | 0.450482E+10 | 18987.44 | 19-AUG-07:02 | 10097.11 | 0.00 |
September | 0.00 | 0.00 | 0.318307E+10 | 0.243384E+10 | 18193.18 | 09-SEP-07:02 | 10826.61 | 0.00 |
October | 0.00 | 0.00 | 0.311495E+10 | 0.262380E+10 | 18984.02 | 05-OCT-07:02 | 9842.75 | 0.00 |
November | 0.00 | 0.00 | 0.197477E+09 | 0.196081E+09 | 3957.31 | 18-NOV-14:10 | 3957.31 | 0.00 |
December | 0.00 | 0.00 | 0.233205E+09 | 0.232571E+09 | 3970.55 | 05-DEC-15:00 | 3970.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234890E+11 | 0.179427E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 56612359.20 | 56558881.30 | 2844.60 | 2844.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.632036E+10 | 0.450482E+10 | 18987.44 | 12138.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 19676113.72 | 17381996.20 | 3109.43 | 26-APR-13:10 | 2689.09 | 0.00 |
May | 0.00 | 0.00 | 40130138.95 | 33794340.30 | 3032.59 | 04-MAY-12:10 | 2483.08 | 0.00 |
June | 0.00 | 0.00 | 0.101021E+10 | 0.690634E+09 | 47779.21 | 29-JUN-17:42 | 29426.34 | 0.00 |
July | 0.00 | 0.00 | 0.571378E+10 | 0.385281E+10 | 49393.89 | 18-JUL-17:25 | 29978.85 | 0.00 |
August | 0.00 | 0.00 | 0.571102E+10 | 0.374855E+10 | 49324.98 | 13-AUG-10:15 | 30194.83 | 0.00 |
September | 0.00 | 0.00 | 0.105079E+10 | 0.961285E+09 | 47537.17 | 10-SEP-13:35 | 30872.68 | 0.00 |
October | 0.00 | 0.00 | 0.137609E+10 | 0.126287E+10 | 49272.76 | 01-OCT-12:15 | 31410.36 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149217E+11 | 0.105673E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.571378E+10 | 0.385281E+10 | 49393.89 | 31410.36 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107252E+10 | 0.34 | 1081.75 | 02-JAN-07:20 | 0.92 |
February | 0.985262E+09 | 0.35 | 1081.75 | 27-FEB-17:30 | 0.92 |
March | 0.115696E+10 | 0.37 | 1081.75 | 01-MAR-07:08 | 0.92 |
April | 0.107094E+10 | 0.35 | 1081.75 | 01-APR-06:20 | 0.92 |
May | 0.111377E+10 | 0.35 | 1081.75 | 03-MAY-08:30 | 0.92 |
June | 0.111377E+10 | 0.36 | 1081.75 | 28-JUN-16:50 | 0.91 |
July | 0.107094E+10 | 0.34 | 1081.75 | 13-JUL-07:40 | 0.92 |
August | 0.115661E+10 | 0.36 | 1081.75 | 18-AUG-14:40 | 0.91 |
September | 0.107094E+10 | 0.35 | 1081.75 | 01-SEP-07:10 | 0.92 |
October | 0.107094E+10 | 0.34 | 1081.75 | 02-OCT-09:40 | 0.91 |
November | 0.102810E+10 | 0.34 | 1081.75 | 22-NOV-10:10 | 0.92 |
December | 0.107094E+10 | 0.34 | 1081.75 | 01-DEC-08:00 | 0.92 |
Annual Sum or Average | 0.129817E+11 | 0.35 | |||
Minimum of Months | 0.985262E+09 | 0.34 | 1081.75 | 0.91 | |
Maximum of Months | 0.115696E+10 | 0.37 | 1081.75 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.870468E+09 | 0.20 | 1501.51 | 09-JAN-07:02 | 0.75 |
February | 0.797423E+09 | 0.20 | 875.52 | 01-FEB-07:10 | 0.54 |
March | 0.936128E+09 | 0.21 | 1105.30 | 30-MAR-06:02 | 0.63 |
April | 0.866764E+09 | 0.21 | 875.52 | 26-APR-13:00 | 0.54 |
May | 0.901435E+09 | 0.21 | 875.52 | 04-MAY-11:50 | 0.54 |
June | 0.905636E+09 | 0.21 | 875.52 | 23-JUN-13:40 | 0.54 |
July | 0.910688E+09 | 0.21 | 1652.92 | 30-JUL-14:40 | 0.77 |
August | 0.965131E+09 | 0.22 | 1404.52 | 20-AUG-12:10 | 0.71 |
September | 0.867302E+09 | 0.20 | 875.52 | 07-SEP-15:10 | 0.53 |
October | 0.873838E+09 | 0.20 | 1394.30 | 01-OCT-11:33 | 0.71 |
November | 0.832093E+09 | 0.20 | 875.52 | 01-NOV-06:05 | 0.54 |
December | 0.866764E+09 | 0.20 | 875.52 | 01-DEC-07:05 | 0.54 |
Annual Sum or Average | 0.105937E+11 | 0.21 | |||
Minimum of Months | 0.797423E+09 | 0.20 | 875.52 | 0.53 | |
Maximum of Months | 0.965131E+09 | 0.22 | 1652.92 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111592E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.997518E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118605E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121189E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.128263E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.168044E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.220064E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.239105E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.173086E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.172460E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107062E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177137E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.997518E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.239105E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.870468E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.797423E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.936128E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.871974E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.911712E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.115153E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226147E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.232488E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115089E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124536E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.832093E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.866764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142207E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.797423E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232488E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107252E+10 | 0.200254E+09 | 0.449469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.985262E+09 | 56612359.20 | 0.209278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115696E+10 | 0.135874E+09 | 0.377493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107094E+10 | 0.671359E+09 | 27753842.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111377E+10 | 0.804474E+09 | 1826400.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111377E+10 | 0.281554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107094E+10 | 0.575580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115661E+10 | 0.632036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107094E+10 | 0.318307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107094E+10 | 0.311495E+10 | 139013.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102810E+10 | 0.197477E+09 | 57266484.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107094E+10 | 0.233205E+09 | 0.209201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129817E+11 | 0.234890E+11 | 0.133243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985262E+09 | 56612359.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115696E+10 | 0.632036E+10 | 0.449469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.870468E+09 | 0.00 | 0.115332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936128E+09 | 0.00 | 1142545.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866764E+09 | 19676113.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.901435E+09 | 40130138.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905636E+09 | 0.969338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.910688E+09 | 0.535798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.965131E+09 | 0.547894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.867302E+09 | 0.104115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.873838E+09 | 0.134448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.832093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.866764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105937E+11 | 0.142517E+11 | 0.116475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.797423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.965131E+09 | 0.547894E+10 | 0.115332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107252E+10 | 0.00 | 0.00 | 0.00 | 43397749.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.985262E+09 | 0.00 | 0.00 | 0.00 | 12256000.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115696E+10 | 0.00 | 0.00 | 0.00 | 29085186.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 0.140956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111377E+10 | 0.00 | 0.00 | 0.00 | 0.168859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111377E+10 | 0.00 | 0.00 | 0.00 | 0.566664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 0.112970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115661E+10 | 0.00 | 0.00 | 0.00 | 0.123444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 0.659923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 0.653660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102810E+10 | 0.00 | 0.00 | 0.00 | 42523395.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107094E+10 | 0.00 | 0.00 | 0.00 | 50516506.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129817E+11 | 0.00 | 0.00 | 0.00 | 0.473198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985262E+09 | 0.00 | 0.00 | 0.00 | 12256000.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115696E+10 | 0.00 | 0.00 | 0.00 | 0.123444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.870468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866764E+09 | 0.00 | 0.00 | 0.00 | 5209587.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.901435E+09 | 0.00 | 0.00 | 0.00 | 10277413.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905636E+09 | 0.00 | 0.00 | 0.00 | 0.245891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.910688E+09 | 0.00 | 0.00 | 0.00 | 0.135078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.965131E+09 | 0.00 | 0.00 | 0.00 | 0.135975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.867302E+09 | 0.00 | 0.00 | 0.00 | 0.283591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.873838E+09 | 0.00 | 0.00 | 0.00 | 0.371522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.832093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.866764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105937E+11 | 0.00 | 0.00 | 0.00 | 0.362702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.797423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.965131E+09 | 0.00 | 0.00 | 0.00 | 0.135975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489394E+09 | 2029601.89 | 0.00 | 497029.36 | 74818.19 | 0.112275E+09 | 0.594884E+09 | 0.00 | 0.22 |
February | 0.622609E+09 | 3034011.74 | 0.00 | 361874.35 | 0.00 | 35206898.35 | 0.503995E+09 | 0.00 | 0.20 |
March | 0.742022E+09 | 0.00 | 0.00 | 505179.24 | 0.00 | 88459147.53 | 0.585448E+09 | 0.00 | 0.23 |
April | 0.206740E+09 | 3294057.38 | 0.00 | 2539919.91 | 0.00 | 3672577.34 | 0.208541E+10 | 0.00 | 0.51 |
May | 0.125772E+09 | 4764805.06 | 0.00 | 3480467.47 | 0.00 | 156215.74 | 0.265771E+10 | 0.00 | 0.59 |
June | 41043321.73 | 88251454.20 | 0.00 | 4529379.44 | 63162.19 | 0.00 | 0.208089E+10 | 0.00 | 0.75 |
July | 4816262.83 | 0.432500E+09 | 0.00 | 4017121.45 | 2541245.03 | 0.00 | 0.984336E+09 | 0.00 | 0.65 |
August | 5829093.74 | 0.539934E+09 | 0.00 | 3279260.00 | 1075104.06 | 0.00 | 0.882671E+09 | 0.00 | 0.68 |
September | 36482121.74 | 0.100418E+09 | 0.00 | 4466057.73 | 410813.66 | 0.00 | 0.185609E+10 | 0.00 | 0.69 |
October | 56281981.61 | 0.220362E+09 | 0.00 | 3255688.57 | 421622.90 | 221339.77 | 0.152848E+10 | 0.00 | 0.55 |
November | 0.313269E+09 | 1211569.24 | 0.00 | 1291513.78 | 0.00 | 3443432.41 | 0.144322E+10 | 0.00 | 0.33 |
December | 0.504891E+09 | 1513604.80 | 0.00 | 656423.75 | 0.00 | 28550446.41 | 0.747494E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.314915E+10 | 0.139731E+10 | 0.00 | 28879915.05 | 4586766.04 | 0.271985E+09 | 0.159506E+11 | 0.00 | 0.47 |
Minimum of Months | 4816262.83 | 0.00 | 0.00 | 361874.35 | 0.00 | 0.00 | 0.503995E+09 | 0.00 | 0.20 |
Maximum of Months | 0.742022E+09 | 0.539934E+09 | 0.00 | 4529379.44 | 2541245.03 | 0.112275E+09 | 0.265771E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237378E+10 | 0.00 | 0.00 | 0.00 | 38256732.39 | 0.00 | 0.00 | 0.00 | 0.18 |
February | 0.253250E+10 | 0.00 | 0.00 | 0.00 | 7029134.02 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.325972E+10 | 0.00 | 0.00 | 0.00 | 1946768.62 | 0.00 | 0.00 | 0.00 | 0.19 |
April | 0.331641E+10 | 0.00 | 0.00 | 49323.74 | 2189315.75 | 0.00 | 80264222.14 | 0.00 | 0.19 |
May | 0.354235E+10 | 0.00 | 0.00 | 305065.43 | 757668.08 | 0.00 | 0.325307E+09 | 0.00 | 0.19 |
June | 0.239433E+10 | 0.00 | 0.00 | 3070125.95 | 0.00 | 0.00 | 0.178659E+10 | 0.00 | 0.26 |
July | 0.609928E+09 | 0.155456E+09 | 0.00 | 8556695.81 | 0.00 | 0.00 | 0.328255E+10 | 0.00 | 0.35 |
August | 0.729458E+09 | 0.138160E+09 | 0.00 | 8281264.21 | 0.00 | 0.00 | 0.306053E+10 | 0.00 | 0.37 |
September | 0.211611E+10 | 94774645.38 | 0.00 | 2072952.37 | 0.00 | 0.00 | 0.187579E+10 | 0.00 | 0.24 |
October | 0.218821E+10 | 0.184512E+09 | 0.00 | 908685.17 | 24287044.94 | 0.00 | 0.608065E+09 | 0.00 | 0.20 |
November | 0.283148E+10 | 0.00 | 0.00 | 0.00 | 1862850.94 | 0.00 | 0.00 | 0.00 | 0.18 |
December | 0.231708E+10 | 0.00 | 0.00 | 0.00 | 25035913.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.282113E+11 | 0.572902E+09 | 0.00 | 23244112.68 | 0.101365E+09 | 0.00 | 0.110191E+11 | 0.00 | 0.23 |
Minimum of Months | 0.609928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.354235E+10 | 0.184512E+09 | 0.00 | 8556695.81 | 38256732.39 | 0.00 | 0.328255E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:44:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.369612E+12 | 0.192902E+11 | 0.00 | 0.353047E+10 | 0.501710E+09 |
February | 0.428602E+12 | 0.251283E+11 | 0.00 | 0.368461E+10 | 0.164456E+09 |
March | 0.608017E+12 | 0.300910E+11 | 0.00 | 0.467421E+10 | 0.339126E+09 |
April | 0.815443E+12 | 0.238604E+11 | 0.00 | 0.568960E+10 | 0.849712E+09 |
May | 0.854097E+12 | 0.326954E+11 | 0.00 | 0.664956E+10 | 0.102455E+10 |
June | 0.854670E+12 | 0.255263E+11 | 0.00 | 0.622213E+10 | 0.463831E+10 |
July | 0.930649E+12 | 0.266834E+11 | 0.00 | 0.431827E+10 | 0.139501E+11 |
August | 0.864109E+12 | 0.309883E+11 | 0.00 | 0.401371E+10 | 0.146256E+11 |
September | 0.678889E+12 | 0.246927E+11 | 0.00 | 0.569540E+10 | 0.517738E+10 |
October | 0.472997E+12 | 0.261759E+11 | 0.00 | 0.395584E+10 | 0.551629E+10 |
November | 0.399862E+12 | 0.257294E+11 | 0.00 | 0.458963E+10 | 0.267447E+09 |
December | 0.331692E+12 | 0.216293E+11 | 0.00 | 0.357212E+10 | 0.377887E+09 |
Annual Sum or Average | 0.760864E+13 | 0.312491E+12 | 0.00 | 0.565955E+11 | 0.474325E+11 |