Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 10:43:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1350.49 | 279.31 | 279.31 |
Net Site Energy | 1350.49 | 279.31 | 279.31 |
Total Source Energy | 4129.19 | 854.00 | 854.00 |
Net Source Energy | 4129.19 | 854.00 | 854.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 287.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1279.53 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 287.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 37.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 142.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 287.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 180.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 101.29 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 264.63 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 101.29 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 264.63 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1279.530 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1279.530 | 100.00 |
Total On-Site and Utility Electric Sources | 1279.530 | 100.00 |
Total Electricity End Uses | 1279.530 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 72.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3143.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 26.83 |
Skylight-Roof Ratio [%] | 0.58 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 02-JAN-07:40 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 2931.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46274.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 33916.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12861.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 968.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 104134.66 | 2931.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 2931.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46274.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 33916.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10556.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 968.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 76.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 910.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 425.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 570.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4052.27 | 76.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 117.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 838.09 | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 117.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 838.09 | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.57 |
ZONE2 FINE STORAGE DIRECT AIR | 4.71 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.814030 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.814030 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 33299.17 |
PSZ-OFFICE HEATING COIL | 37276.68 |
PSZ-FINE STORAGE HEATING COIL | 140347.76 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
PSZ-FINE STORAGE | 4.71 | 4.71 | 4.71 | 4.71 | 4.71 | 4.71 | 1.00 | 1.00 | 4.71 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.57 | 0.120335 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.71 | 0.353926 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.57 | 1719.65 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.71 | 8836.92 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.57 | 33617.51 | 37276.68 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.71 | 4.71 | 4.71 | 4.71 | 116879.91 | 140347.76 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.57 | 0.785585 | 1.57 | 33617.51 | 17223.75 | 33617.51 | 0.750440 | 0.750440 |
PSZ-FINE STORAGE COOLING COIL | 4.71 | 2.35 | 4.71 | 116879.91 | 58439.91 | 116879.91 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.8127 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.131 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
5 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
6 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
7 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
8 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
9 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
10 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
11 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
12 | 4 | 0.71656587E-12 | -0.16827101E-15 | 0.21548121E-14 | 0.12539735E-15 |
13 | 3 | -0.36253864E-03 | 0.55487071E-06 | -0.52378714E-04 | 0.13752504E-12 |
14 | 2 | 1.6865760 | 0.12432070E-01 | 1.1001971 | -0.69502831E-04 |
15 | 1 | -7.1998246 | 0.32704464 | -16.840218 | 0.32320315 |
16 | 0 | 6.0637144 | 0.21062598 | 16.290177 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.21548121E-14 | -0.16827101E-15 | 0.71656587E-12 | 0.12539735E-15 |
85 | 3 | -0.52378714E-04 | 0.55487071E-06 | -0.36253864E-03 | 0.13752504E-12 |
86 | 2 | 1.1001971 | 0.12432070E-01 | 1.6865760 | -0.69502831E-04 |
87 | 1 | -16.840218 | 0.32704464 | -7.1998246 | 0.32320315 |
88 | 0 | 16.290177 | 0.21062598 | 6.0637144 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
3 | NONRESWINDOW_U_1.2_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
4 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
5 | SKYLIGHT_U_1.02_SHGC_0.4 | 38 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.733 | 0.325 | 0.251 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 15905.77523 | 19086.93028 | 1.30931 | 1.57117 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 42.21800 | 1.07808E-002 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5201.89331 | 6242.27198 | 0.14575 | 0.17490 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 12.74874 | 0.12033 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 61122.04635 | 73346.45562 | 3.92229 | 4.70675 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 4336.11739 | 5203.34087 | 0.10259 | 0.35393 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 30.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | 00:10:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 69.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 25286.16 | 1.57117 | 1.57117 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 5225.69 | 0.17490 | 0.17490 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 90556.16 | 4.70675 | 4.70675 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 11685.86 | 0.35393 | 0.35393 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.57117 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.70675 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 33299.17083 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.57117 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57117 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.57117 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.57117 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57117 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.57117 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.70675 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.70675 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.70675 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.70675 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.70675 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.70675 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.57117 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.70675 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57117 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12033 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57117 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1719.65315 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57117 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57117 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57117 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.57117 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57117 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78558 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.57117 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33617.51000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17223.75467 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33617.51000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75044 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75044 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33617.51000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37276.67538 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 37276.67538 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.70675 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.70675 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8836.92061 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.70675 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.70675 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.70675 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.70675 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.70675 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.35338 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.70675 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 116879.91000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 58439.90564 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 116879.91000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 116879.91000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 140347.75509 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 140347.75509 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 32397.1 | 11.10 | 10.46 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 113221.4 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.1805635761E-002 | 2.5729509810E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.9782467955E-002 | 3.6844771681E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.6991617790E-002 | 2.6458901768E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8768.40 | 334.32 | 0.00 | -111.3 | 1268.53 | 10260.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.725 | 0.813 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.233 | 0.240 | 3204.84 | 3178.02 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.680 | 0.813 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.813 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.813 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.20 | 0.00 | 2.68 | 2.68 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 44.49 | 6.201 | 0.341 | 0.342 | |||||||||||||||||
North Total or Average | 6.51 | 6.813 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 37.98 | 6.096 | 0.357 | 0.358 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.85 | 83.85 | 134.30 | |
Exterior Lighting Total | 8532.22 | 134.30 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33617.51 | 25227.92 | 8389.59 | 0.75 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 116879.91 | 81942.17 | 34937.74 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 32397.1 | 11.10 | 10.46 | ||||
PSZ-FINE STORAGE COOLING COIL | 113221.4 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 33299.17 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 37276.68 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 140347.76 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.57 | 1719.65 | 1094.51 | 1.00 | 1.32 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.71 | 8836.92 | 1877.50 | 1.00 | 1.15 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 15905.78 | 19086.93 | 80.58 | 1.309 | 1.571 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 23.90 | 23.90 | 0.00834 | 42.22 | 0.01078 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 61122.05 | 73346.46 | 52.64 | 3.922 | 4.707 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00853 | 42.80 | 0.01078 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 0.00 | 42.26 | 0.01086 | 42.70 | 0.01078 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5201.89 | 6242.27 | 26.35 | 0.146 | 0.175 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00898 | 12.70 | 0.00915 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 4336.12 | 5203.34 | 3.73 | 0.103 | 0.354 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00884 | 12.70 | 0.00915 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | 00:10:00 | 10.00 | 15.07 | 0.00933 | 12.70 | 0.00915 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.57 | 1.57 | 0.17 | 0.17 | 1.5712 | 1.5712 | 1.5712 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.71 | 4.71 | 0.35 | 0.35 | 4.7068 | 4.7068 | 4.7068 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 33299.171 | 33299.171 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 33299.17 | 33299.17 | 0.814030 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 33617.510 | 25227.924 | 1.571170 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 33617.51 | 30982.62 | 1.571170 | 26.20 | 17.18 | 0.00852753 | 12.00 | 11.25 | 0.00800000 | 42.31 | 0.01078097 | 23.73 | 7.6589 | 23.90 | 0.00834059 | 45.1636 | 15903.26 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 37276.675 | 37276.675 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 37276.68 | 37276.68 | 1.571169 | 20.38 | 15.51 | 0.00899487 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.6589 | 21.10 | 0.00898171 | 57.5852 | 5201.89 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 116879.910 | 81942.167 | 4.706750 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 116879.91 | 106883.71 | 4.706750 | 29.44 | 18.41 | 0.00869951 | 12.00 | 11.25 | 0.00800000 | 42.80 | 0.01078182 | 23.86 | 7.5195 | 26.70 | 0.00853020 | 39.0950 | 61122.05 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 140347.755 | 140347.755 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 140347.76 | 140347.76 | 4.706754 | 15.35 | 13.55 | 0.00894250 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 7.5195 | 15.56 | 0.00892535 | 81.0290 | 4163.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33299.171 | 33299.171 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.814030 | 0.97976235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 33299.17 | 33299.17 | 1.0000 | 0.97976235 | 0.814030 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33299.17 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33617.510 | 25227.924 | 1.571170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6922 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.571169 | 1.89105118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | Sensible | 33617.51 | 30982.62 | 1.0000 | 1.89105233 | 1.571170 | 26.20 | 17.18 | 0.00852753 | 48068.8 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33617.51 | 42.31 | 0.01078097 | 23.73 | 0.12033486 | 7.6589 | 23.90 | 0.00834059 | 23.90 | 0.00834059 | 45.1636 | 15903.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37276.675 | 37276.675 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.571169 | 1.89105118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 37276.68 | 37276.68 | 1.0000 | 1.89105118 | 1.571169 | 20.38 | 15.51 | 0.00899487 | 43318.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37276.68 | 12.70 | 0.00915345 | 12.70 | 0.12033486 | 7.6589 | 21.02 | 0.00898171 | 21.10 | 0.00898171 | 57.5852 | 5201.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 116879.910 | 81942.167 | 4.706750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0120 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.706754 | 5.66502544 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 116879.91 | 106883.71 | 1.0000 | 5.66502068 | 4.706750 | 29.44 | 18.41 | 0.00869951 | 51811.1 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 116879.91 | 42.80 | 0.01078182 | 23.86 | 0.35392606 | 7.5195 | 26.70 | 0.00853020 | 26.70 | 0.00853020 | 39.0950 | 61122.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 140347.755 | 140347.755 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.706754 | 5.66502544 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 140347.76 | 140347.76 | 1.0000 | 5.66502544 | 4.706754 | 15.35 | 13.55 | 0.00894250 | 38039.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 140347.76 | 12.70 | 0.00915345 | 12.70 | 0.35392606 | 7.5195 | 15.56 | 0.00892535 | 15.56 | 0.00892535 | 81.0290 | 4163.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3408.67 | 403.83 | 350.17 |
ZONE2 FINE STORAGE | 3587.83 | 2988.17 | 2962.00 |
ZONE3 BULK STORAGE | 3500.17 | 3138.17 | 3047.50 |
Facility | 3596.00 | 3248.17 | 3143.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 120.33 | 0.00 | 70.33 |
ZONE2 FINE STORAGE | 0.00 | 579.00 | 0.00 | 11.50 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 678.83 | 0.00 | 72.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.415 | 0.493 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.414 | 0.400 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.179 | 0.000 | 2.188 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1203 | 0.120 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.3539 | 0.354 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.814 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.4743 | 1.288 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1499697.55 | 0.00 | 1499697.55 | 2685553.59 | 4185251.15 | 3794880.16 | 5392.67 | 3367.33 | 0.00 | 492.02 |
ZONE2 FINE STORAGE | 4800854.29 | 0.00 | 4800854.29 | 9501763.81 | 14302618.10 | 11161412.23 | 5404.27 | 3355.73 | 0.00 | 2051.88 |
ZONE3 BULK STORAGE | 0.00 | 0.57E+09 | 0.57E+09 | 39432196.75 | 0.61E+09 | 25671248.14 | 4069.30 | 24.72 | 4665.98 | 5105.92 |
Total Facility | 6300551.85 | 0.57E+09 | 0.57E+09 | 51619514.15 | 0.63E+09 | 40627540.53 | 6684.94 | 3397.22 | 4665.98 | 5106.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1129 | 0.0000 | 0.1129 | 0.1339 | 0.2467 | 0.1203 | 268.73 | 3367.27 | 0.00 |
ZONE2 FINE STORAGE | 0.3258 | 0.0000 | 0.3258 | 0.3144 | 0.6402 | 0.3539 | 302.29 | 3333.71 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 19.8137 | 19.8137 | 1.6442 | 21.4579 | 0.8140 | 1457.70 | 16.89 | 2161.41 |
Total Facility | 0.4387 | 19.8137 | 20.2523 | 2.0924 | 22.3448 | 1.2883 | 1560.94 | 3367.30 | 2161.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2172523.18 | 0.00 | 2172523.18 | 3794880.16 | 5380.37 | 0.83 | 3378.81 | 483.85 |
PSZ-FINE STORAGE | 6954713.79 | 0.00 | 6954713.79 | 11161412.23 | 5349.62 | 4.18 | 3406.20 | 2049.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1635 | 0.0000 | 0.1635 | 0.1203 | 258.15 | 0.53 | 3377.32 |
PSZ-FINE STORAGE | 0.4720 | 0.0000 | 0.4720 | 0.3539 | 301.35 | 0.08 | 3334.57 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 4014.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5485.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1684 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.4996 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1279.53 | 5771.67 | 01-JAN-07:10 | 104134.66 | 10-AUG-16:00 |
Electricity:Building | 692.67 | 5288.67 | 01-JAN-00:10 | 50600.89 | 06-FEB-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 385.74 | 2117.83 | 01-JAN-00:10 | 28507.00 | 06-FEB-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 180.03 | 0.00 | 01-JAN-00:10 | 12861.87 | 06-FEB-13:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.19 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity | 37.19 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.19 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
ElectricityPurchased:Facility | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
ElectricityNet:Plant | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1279.53 | 5771.67 | 05-FEB-12:10 | 104134.66 | 10-AUG-16:00 |
Electricity:HVAC | 430.49 | 0.00 | 01-JAN-00:10 | 56831.45 | 10-AUG-16:00 |
General:Fans:Electricity | 142.84 | 0.00 | 01-JAN-00:10 | 10556.57 | 04-JAN-12:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 287.65 | 0.00 | 01-JAN-00:10 | 46274.87 | 10-AUG-16:00 |
General:Cooling:Electricity | 287.65 | 0.00 | 01-JAN-00:10 | 46274.87 | 10-AUG-16:00 |
ExteriorLights:Electricity | 134.30 | 0.00 | 01-JAN-07:10 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.30 | 0.00 | 01-JAN-07:10 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 22.07 | 483.00 | 09-FEB-06:10 | 1740.29 | 11-JAN-13:00 |
WaterSystems:Electricity | 22.07 | 483.00 | 09-FEB-06:10 | 1740.29 | 11-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 22.07 | 483.00 | 09-FEB-06:10 | 1740.29 | 11-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 70.96 | 2250.00 | 09-FEB-06:10 | 2931.12 | 02-JAN-07:40 |
NaturalGas:HVAC | 70.96 | 2250.00 | 09-FEB-06:10 | 2931.12 | 02-JAN-07:40 |
Heating:NaturalGas | 70.96 | 2250.00 | 09-FEB-06:10 | 2931.12 | 02-JAN-07:40 |
General:Heating:NaturalGas | 70.96 | 2250.00 | 09-FEB-06:10 | 2931.12 | 02-JAN-07:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1439.30 | 0.00 | 01-JAN-00:10 | 205838.16 | 10-AUG-16:00 |
EnergyTransfer:Building | 529.37 | 0.00 | 01-JAN-00:10 | 72506.22 | 09-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 120.00 | 0.00 | 01-JAN-00:10 | 19490.03 | 16-AUG-12:00 |
Heating:EnergyTransfer | 1.18 | 0.00 | 01-JAN-00:10 | 6236.40 | 02-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.08 | 0.00 | 01-JAN-00:10 | 978.81 | 02-JAN-07:40 |
General:Heating:EnergyTransfer | 1.18 | 0.00 | 01-JAN-00:10 | 6236.40 | 02-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.08 | 0.00 | 01-JAN-00:10 | 978.81 | 02-JAN-07:40 |
Cooling:EnergyTransfer | 528.19 | 0.00 | 01-JAN-00:10 | 72506.22 | 09-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 119.91 | 0.00 | 01-JAN-00:10 | 19490.03 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 528.19 | 0.00 | 01-JAN-00:10 | 72506.22 | 09-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 119.91 | 0.00 | 01-JAN-00:10 | 19490.03 | 16-AUG-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 409.38 | 0.00 | 01-JAN-00:10 | 66836.18 | 21-MAY-13:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.10 | 0.00 | 01-JAN-00:10 | 6236.40 | 02-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.10 | 0.00 | 01-JAN-00:10 | 6236.40 | 02-JAN-18:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 408.28 | 0.00 | 01-JAN-00:10 | 66836.18 | 21-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 408.28 | 0.00 | 01-JAN-00:10 | 66836.18 | 21-MAY-13:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 909.93 | 0.00 | 01-JAN-00:10 | 140330.34 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 437.20 | 02-JAN-07:40 |
CoolingCoils:EnergyTransfer | 909.93 | 0.00 | 01-JAN-00:10 | 140330.34 | 22-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.083 | -119.912 | 0.000 | 0.000 | 9.117 | 30.293 | 31.946 | 17.580 | 0.000 | 15.897 | 24.831 | 0.000 | -5.307 | 0.000 | -4.527 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.098 | -408.273 | 0.000 | 0.000 | 17.123 | 244.699 | 0.000 | 0.000 | 0.000 | 45.777 | 119.969 | 0.000 | 0.000 | 0.000 | -20.392 | -0.002 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.101 | 241.203 | 107.344 | 128.478 | 0.000 | 113.223 | 0.011 | 0.000 | -59.057 | 0.000 | -542.701 | -8.590 |
Total Facility | 0.000 | 0.000 | 1.181 | -528.185 | 0.000 | 0.000 | 46.340 | 516.195 | 139.290 | 146.058 | 0.000 | 174.896 | 144.810 | 0.000 | -64.364 | 0.000 | -567.620 | -8.593 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | -32327.69 | 0.00 | 0.00 | 71.88 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 32003.75 | 0.00 | -553.76 | 0.00 | -341.10 | 0.00 |
ZONE2 FINE STORAGE | 02-APR-15:32 | 0.00 | 0.00 | 0.00 | -97580.67 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 2951.69 | 92480.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -116016.01 | 0.00 | 0.00 | 360.16 | 4839.54 | 2623.78 | 13.84 | 0.00 | 2461.66 | 200482.55 | 0.00 | -3267.73 | 0.00 | -91497.79 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-JAN-07:10 | 0.00 | 0.00 | 1152.33 | 0.00 | 0.00 | 0.00 | 181.55 | 1046.67 | 956.25 | 0.00 | 0.00 | 0.00 | 67.19 | 0.00 | -575.03 | 0.00 | -2828.96 | 0.00 |
ZONE2 FINE STORAGE | 02-JAN-18:00 | 0.00 | 0.00 | 6235.71 | 0.00 | 0.00 | 0.00 | 548.06 | 12891.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3303.14 | -16371.79 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-18:00 | -633.27 | 633.27 | 6235.71 | -633.27 | 0.00 | 0.00 | 2509.66 | 27118.32 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3102.95 | 0.00 | -10355.69 | -24778.07 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5712 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5712 | 0.0766 | 1.0000 | Not calculated | 0.1203 | 0.0766 | ||
PSZ-FINE STORAGE | 4.7068 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.7068 | 0.0752 | 1.0000 | Not calculated | 0.3539 | 0.0752 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5712 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1203 | 1.5712 | 1.0000 | 1.0000 | Not calculated | 0.1203 | 0.0766 | ||
PSZ-FINE STORAGE | 4.7068 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.3539 | 4.7068 | 1.0000 | 1.0000 | Not calculated | 0.3539 | 0.0752 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5712 | 1.5712 | 1.5712 | No | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7068 | 4.7068 | 4.7068 | No | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5712 | 1.5712 | 1.5712 | 1.5712 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.7068 | 4.7068 | 4.7068 | 4.7068 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5712 | 1.5712 | 1.5712 | No | 0.1203 | 0.6880 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7068 | 4.7068 | 4.7068 | No | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5712 | 1.5712 | 1.5712 | 1.5712 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 4.7068 | 4.7068 | 4.7068 | 4.7068 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 72.33 |
Number of hours not met | 72.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 70.96 | 2931.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 287.65 | 46274.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.30 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 37.19 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 142.84 | 10556.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.07 | 1740.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1279.53 |
Natural Gas | 0.00 | 70.96 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1350.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 59.49 |
Fans (All) | 37.23 |
Service Water Heating | 4.57 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 264.63 |
Subtotal | 264.63 |
Natural Gas [MJ/m2] | |
Space Heating | 14.68 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 14.68 |
Subtotal | 14.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.22 |
Space Heating | 5.25 |
Space Cooling | 21.30 |
Fans (All) | 13.33 |
Service Water Heating | 1.63 |
Receptacle Equipment | 10.31 |
Miscellaneous | 9.94 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4909.50 | 3129.67 | 720.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3207.33 | 5552.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1729.50 | 3160.67 | 1962.67 | 1868.33 | 38.83 |
Min | 1729.50 | 3129.67 | 0.00 | 0.00 | 0.00 |
Max | 4909.50 | 5552.67 | 1962.67 | 1868.33 | 38.83 |
Average | 3282.11 | 3947.67 | 894.50 | 622.78 | 12.94 |
Sum | 9846.33 | 11843.00 | 2683.50 | 1868.33 | 38.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33020.67 | 6.00 | 0.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 29035.00 | 53684.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 23604.67 | 75334.83 | 46392.00 | 43946.33 | 1915.17 |
Min | 23604.67 | 6.00 | 0.00 | 0.00 | 0.00 |
Max | 33020.67 | 75334.83 | 46392.00 | 43946.33 | 1915.17 |
Average | 28553.44 | 43008.28 | 15464.11 | 14648.78 | 638.39 |
Sum | 85660.33 | 129024.83 | 46392.33 | 43946.33 | 1915.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4152.83 | 4360.67 | 246.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2304.50 | 6455.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1257.50 | 4372.67 | 1431.00 | 1398.67 | 300.17 |
Min | 1257.50 | 4360.67 | 0.00 | 0.00 | 0.00 |
Max | 4152.83 | 6455.50 | 1431.00 | 1398.67 | 300.17 |
Average | 2571.61 | 5062.94 | 559.17 | 466.22 | 100.06 |
Sum | 7714.83 | 15188.83 | 1677.50 | 1398.67 | 300.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31640.00 | 1387.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 25443.00 | 57276.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 16864.67 | 102612.17 | 31686.00 | 29764.50 | 10265.67 |
Min | 16864.67 | 1387.00 | 0.00 | 0.00 | 0.00 |
Max | 31640.00 | 102612.17 | 31686.00 | 29764.50 | 10265.67 |
Average | 24649.22 | 53758.39 | 10562.00 | 9921.50 | 3421.89 |
Sum | 73947.67 | 161275.17 | 31686.00 | 29764.50 | 10265.67 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466731E+10 | 26260.49 | 31-JAN-06:02 | 15.90 | 14.14 | 0.633031E+09 | 769.05 | 23-JAN-14:00 | 15.90 | 14.14 |
February | 0.524962E+10 | 25964.43 | 10-FEB-06:02 | 19.82 | 12.70 | 0.583450E+09 | 769.05 | 06-FEB-13:39 | 19.82 | 12.70 |
March | 0.755409E+10 | 32328.43 | 27-MAR-05:01 | 21.92 | 13.45 | 0.685702E+09 | 774.39 | 13-MAR-07:10 | 21.92 | 13.45 |
April | 0.869782E+10 | 32261.43 | 26-APR-05:01 | 23.17 | 12.12 | 0.635113E+09 | 769.10 | 29-APR-15:50 | 35.33 | 22.33 |
May | 0.120397E+11 | 31716.91 | 10-MAY-05:01 | 28.00 | 15.72 | 0.660788E+09 | 769.12 | 22-MAY-15:00 | 35.60 | 24.38 |
June | 0.131839E+11 | 27999.93 | 16-JUN-05:01 | 28.17 | 20.46 | 0.660901E+09 | 769.12 | 26-JUN-15:50 | 37.08 | 26.81 |
July | 0.142632E+11 | 30694.61 | 03-JUL-05:01 | 28.83 | 16.82 | 0.635687E+09 | 769.12 | 06-JUL-15:00 | 38.20 | 29.44 |
August | 0.156725E+11 | 25880.50 | 07-AUG-05:01 | 32.82 | 23.16 | 0.686672E+09 | 769.13 | 04-AUG-15:50 | 32.82 | 23.16 |
September | 0.127912E+11 | 24550.46 | 05-SEP-05:01 | 30.17 | 24.66 | 0.635514E+09 | 769.13 | 06-SEP-15:00 | 37.60 | 27.36 |
October | 0.110392E+11 | 30211.06 | 20-OCT-05:01 | 23.17 | 16.23 | 0.635385E+09 | 769.10 | 11-OCT-15:00 | 23.17 | 16.23 |
November | 0.853643E+10 | 29130.30 | 18-NOV-06:01 | 20.08 | 16.00 | 0.609772E+09 | 769.09 | 06-NOV-14:00 | 20.08 | 16.00 |
December | 0.621893E+10 | 28808.84 | 13-DEC-06:02 | 15.02 | 12.69 | 0.634768E+09 | 769.07 | 01-DEC-14:20 | 15.02 | 12.69 |
Annual Sum or Average | 0.119914E+12 | 0.769678E+10 | ||||||||
Minimum of Months | 0.466731E+10 | 24550.46 | 15.02 | 12.12 | 0.583450E+09 | 769.05 | 15.02 | 12.69 | ||
Maximum of Months | 0.156725E+11 | 32328.43 | 32.82 | 24.66 | 0.686672E+09 | 774.39 | 38.20 | 29.44 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.776115E+10 | 21845.97 | 29-JAN-12:00 | 27.00 | 18.66 | 0.183520E+10 | 2246.91 | 19-JAN-13:50 | 27.00 | 18.66 |
February | 0.107322E+11 | 62960.67 | 05-FEB-13:33 | 31.43 | 19.44 | 0.169811E+10 | 2246.97 | 23-FEB-15:20 | 27.30 | 17.53 |
March | 0.188730E+11 | 96651.80 | 26-MAR-15:23 | 32.20 | 18.57 | 0.199976E+10 | 2247.03 | 21-MAR-13:30 | 32.20 | 18.57 |
April | 0.274961E+11 | 97583.63 | 02-APR-15:32 | 31.27 | 18.46 | 0.185395E+10 | 2247.10 | 27-APR-15:39 | 35.93 | 22.50 |
May | 0.454107E+11 | 93066.61 | 04-MAY-18:23 | 35.00 | 18.70 | 0.192891E+10 | 2247.15 | 22-MAY-14:20 | 37.33 | 23.24 |
June | 0.506422E+11 | 91044.04 | 15-JUN-17:04 | 37.67 | 20.98 | 0.192892E+10 | 2247.16 | 02-JUN-13:30 | 37.67 | 20.98 |
July | 0.583638E+11 | 93763.43 | 04-JUL-09:02 | 34.72 | 21.09 | 0.185495E+10 | 2247.23 | 11-JUL-15:39 | 39.73 | 25.59 |
August | 0.616866E+11 | 87846.12 | 06-AUG-07:42 | 35.82 | 22.90 | 0.200341E+10 | 2247.22 | 17-AUG-15:39 | 39.80 | 25.84 |
September | 0.495381E+11 | 86232.17 | 04-SEP-08:23 | 34.55 | 21.42 | 0.185476E+10 | 2247.19 | 05-SEP-15:30 | 39.05 | 25.34 |
October | 0.397042E+11 | 95369.58 | 29-OCT-16:03 | 31.83 | 20.03 | 0.185468E+10 | 2247.13 | 04-OCT-15:00 | 31.83 | 20.03 |
November | 0.248992E+11 | 97008.96 | 19-NOV-14:02 | 30.83 | 17.93 | 0.178007E+10 | 2247.07 | 06-NOV-14:09 | 30.83 | 17.93 |
December | 0.131713E+11 | 57420.56 | 03-DEC-13:03 | 29.33 | 18.32 | 0.184990E+10 | 2247.01 | 01-DEC-13:30 | 29.33 | 18.32 |
Annual Sum or Average | 0.408278E+12 | 0.224426E+11 | ||||||||
Minimum of Months | 0.776115E+10 | 21845.97 | 27.00 | 17.93 | 0.169811E+10 | 2246.91 | 27.00 | 17.53 | ||
Maximum of Months | 0.616866E+11 | 97583.63 | 37.67 | 22.90 | 0.200341E+10 | 2247.23 | 39.80 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.381812E+10 | 5589.25 | 28-JAN-14:39 | 26.67 | 16.87 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.401841E+10 | 7181.05 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.534839E+10 | 9097.65 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.561357E+10 | 9097.65 | 24-APR-12:30 | 37.20 | 17.89 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.696011E+10 | 9097.65 | 04-MAY-10:09 | 37.72 | 18.25 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.724110E+10 | 9097.65 | 01-JUN-09:09 | 37.48 | 21.75 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.725003E+10 | 9097.65 | 01-JUL-09:39 | 36.80 | 26.55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.787528E+10 | 9097.65 | 01-AUG-08:00 | 37.00 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.687341E+10 | 9097.65 | 01-SEP-10:09 | 36.08 | 24.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.614418E+10 | 9097.65 | 02-OCT-12:39 | 36.47 | 19.28 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.511794E+10 | 7804.64 | 01-NOV-14:20 | 32.67 | 26.20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.463920E+10 | 6341.53 | 02-DEC-14:50 | 27.00 | 19.63 |
Annual Sum or Average | 0.00 | 0.708997E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.381812E+10 | 5589.25 | 26.67 | 16.87 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.787528E+10 | 9097.65 | 37.72 | 26.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36129977.49 | 1152.40 | 25-JAN-07:10 | 17.42 |
February | 22768670.80 | 1001.97 | 14-FEB-07:15 | 13.67 |
March | 10411578.57 | 1019.79 | 17-MAR-06:10 | 16.83 |
April | 104693.02 | 348.98 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 14000842.92 | 975.92 | 22-DEC-07:10 | 15.17 |
Annual Sum or Average | 83415762.80 | |||
Minimum of Months | 0.00 | 0.00 | 13.67 | |
Maximum of Months | 36129977.49 | 1152.40 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506149E+09 | 6236.40 | 02-JAN-18:00 | 20.00 |
February | 0.270728E+09 | 5526.07 | 15-FEB-07:50 | 21.57 |
March | 0.120261E+09 | 5681.60 | 01-MAR-07:05 | 24.17 |
April | 18616381.69 | 4673.17 | 06-APR-06:05 | 21.22 |
May | 370990.55 | 3709.91 | 03-MAY-06:03 | 22.12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 441571.07 | 3679.76 | 25-SEP-06:04 | 23.23 |
October | 298004.58 | 1986.70 | 18-OCT-06:05 | 25.07 |
November | 7511209.34 | 4384.61 | 29-NOV-07:05 | 20.67 |
December | 0.173167E+09 | 6155.00 | 27-DEC-07:13 | 20.93 |
Annual Sum or Average | 0.109754E+10 | |||
Minimum of Months | 0.00 | 0.00 | 20.00 | |
Maximum of Months | 0.506149E+09 | 6236.40 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11678939.38 | 0.118251E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123874E+09 | 0.984924E+09 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453568E+09 | 0.649688E+09 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887610E+09 | 0.313303E+09 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194165E+10 | 58178981.12 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241388E+10 | 21462236.76 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278426E+10 | 402702.89 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308085E+10 | 222689.35 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209576E+10 | 22187214.63 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137798E+10 | 91235211.49 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628299E+09 | 0.354839E+09 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97157950.84 | 0.848237E+09 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158966E+11 | 0.452719E+10 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11678939.38 | 222689.35 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308085E+10 | 0.118251E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2634997.76 | 0.497930E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179271E+09 | 0.489204E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684381E+09 | 0.318085E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188144E+10 | 0.138313E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551224E+10 | 0.184442E+09 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725849E+10 | 44492105.34 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952586E+10 | 0.00 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964947E+10 | 0.00 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645131E+10 | 36422625.06 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358923E+10 | 0.326854E+09 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996607E+09 | 0.142923E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46170941.21 | 0.393494E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457771E+11 | 0.203917E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2634997.76 | 0.00 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964947E+10 | 0.497930E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30513468.71 | 0.153131E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291033E+09 | 0.186869E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547023E+09 | 0.159277E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289498E+09 | 0.962544E+10 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968124E+09 | 0.272992E+10 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100612E+10 | 0.238523E+10 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950002E+09 | 0.180732E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742000E+09 | 0.209185E+10 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578703E+09 | 0.225087E+10 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265245E+09 | 0.405215E+10 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19457095.96 | 0.963129E+10 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14032589.82 | 0.178449E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570175E+10 | 0.102347E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14032589.82 | 0.180732E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100612E+10 | 0.186869E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.80 | 23-JAN-13:00 | 5061.69 | 19-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2816.31 | 07-FEB-13:00 | 4345.40 | 13-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5653.76 | 27-MAR-11:10 | 3699.20 | 06-MAR-07:05 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6328.07 | 28-APR-12:00 | 3009.70 | 05-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6573.13 | 10-MAY-16:10 | 1380.97 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9144.85 | 09-JUN-16:10 | 462.93 | 07-JUN-05:01 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8928.87 | 21-JUL-17:00 | 33.90 | 03-JUL-04:40 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8538.21 | 16-AUG-12:00 | 33.26 | 27-AUG-06:00 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7147.77 | 05-SEP-16:10 | 504.29 | 25-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6641.20 | 19-OCT-16:10 | 735.83 | 30-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.12 | 01-NOV-16:10 | 2982.37 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1629.26 | 01-DEC-13:00 | 3893.63 | 18-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.80 | 33.26 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 9144.85 | 5061.69 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.27 | 23-JAN-14:00 | 9201.37 | 19-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4651.36 | 05-FEB-14:57 | 9347.07 | 10-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9470.32 | 01-MAR-16:10 | 7065.33 | 25-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13007.83 | 28-APR-15:10 | 4811.11 | 05-APR-06:40 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34966.61 | 21-MAY-12:51 | 2355.08 | 01-MAY-07:10 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18328.78 | 09-JUN-15:40 | 1590.72 | 07-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18373.69 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15698.62 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13446.28 | 02-SEP-16:00 | 1100.39 | 25-SEP-05:09 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14317.30 | 19-OCT-15:10 | 3068.00 | 21-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5287.95 | 01-NOV-15:10 | 4471.21 | 22-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.44 | 10-DEC-12:57 | 8487.21 | 16-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.27 | 0.00 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34966.61 | 9347.07 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3152.99 | 23-JAN-13:10 | 25815.13 | 19-JAN-09:30 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9369.21 | 05-FEB-14:53 | 29981.94 | 10-FEB-16:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19579.78 | 01-MAR-11:00 | 57555.05 | 25-MAR-08:50 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4471.46 | 25-APR-07:53 | 18024.42 | 04-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9817.15 | 21-MAY-12:51 | 12868.53 | 01-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6941.58 | 09-JUN-15:00 | 9484.17 | 07-JUN-06:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7016.84 | 15-JUL-09:55 | 4442.72 | 16-JUL-16:52 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8813.05 | 16-AUG-10:55 | 6950.74 | 10-AUG-20:52 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4338.50 | 26-SEP-11:00 | 7778.52 | 27-SEP-06:00 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4341.96 | 19-OCT-14:00 | 14842.17 | 21-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.40 | 05-NOV-10:53 | 13738.98 | 22-NOV-06:01 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2001.77 | 10-DEC-12:00 | 45667.07 | 15-DEC-11:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.40 | 4442.72 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19579.78 | 57555.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26260.49 | 31-JAN-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.55 |
February | 25964.43 | 10-FEB-06:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.40 |
March | 32328.43 | 27-MAR-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.10 |
April | 32261.43 | 26-APR-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.80 |
May | 31716.91 | 10-MAY-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 27999.93 | 16-JUN-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 |
July | 30694.61 | 03-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 |
August | 25880.50 | 07-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 341.15 | 0.00 |
September | 24550.46 | 05-SEP-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 0.00 |
October | 30211.06 | 20-OCT-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.33 |
November | 29130.30 | 18-NOV-06:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.06 |
December | 28808.84 | 13-DEC-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24550.46 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32328.43 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 341.15 | 954.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21845.97 | 29-JAN-12:00 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.69 | 0.00 |
February | 62960.67 | 05-FEB-13:33 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.52 | 0.00 |
March | 96651.80 | 26-MAR-15:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3296.91 | 0.00 |
April | 97583.63 | 02-APR-15:32 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2951.69 | 0.00 |
May | 93066.61 | 04-MAY-18:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4875.56 | 0.00 |
June | 91044.04 | 15-JUN-17:04 | 0.00 | 15039.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.65 | 0.00 |
July | 93763.43 | 04-JUL-09:02 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1919.19 | 0.00 |
August | 87846.12 | 06-AUG-07:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.79 | 0.00 |
September | 86232.17 | 04-SEP-08:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3951.72 | 0.00 |
October | 95369.58 | 29-OCT-16:03 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3529.29 | 0.00 |
November | 97008.96 | 19-NOV-14:02 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4152.46 | 0.00 |
December | 57420.56 | 03-DEC-13:03 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 21845.97 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.69 | 0.00 | |
Maximum of Months | 97583.63 | 0.00 | 15039.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.65 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1934.87 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6116.06 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4757.01 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4143.77 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2293.57 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.88 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.98 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.83 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843.09 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2717.16 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8141.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 | |
Maximum of Months | 0.00 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8141.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.860657E+11 | 72569.69 | 23-JAN-13:50 | 0.602748E+10 | 2931.12 | 02-JAN-07:40 |
February | 0.805089E+11 | 80705.83 | 07-FEB-13:50 | 0.544320E+10 | 2250.00 | 01-FEB-00:10 |
March | 0.959498E+11 | 84897.24 | 27-MAR-12:09 | 0.602640E+10 | 2250.00 | 01-MAR-00:10 |
April | 0.972834E+11 | 89388.54 | 28-APR-12:09 | 0.583200E+10 | 2250.00 | 01-APR-00:10 |
May | 0.115350E+12 | 93517.76 | 31-MAY-14:39 | 0.602640E+10 | 2250.00 | 01-MAY-00:10 |
June | 0.121792E+12 | 98691.19 | 09-JUN-14:09 | 0.583200E+10 | 2250.00 | 01-JUN-00:10 |
July | 0.128967E+12 | 100865.31 | 14-JUL-13:50 | 0.602640E+10 | 2250.00 | 01-JUL-00:10 |
August | 0.136925E+12 | 104134.66 | 10-AUG-15:00 | 0.602640E+10 | 2250.00 | 01-AUG-00:10 |
September | 0.120785E+12 | 95737.76 | 08-SEP-14:50 | 0.583200E+10 | 2250.00 | 01-SEP-00:10 |
October | 0.110975E+12 | 91650.03 | 07-OCT-13:00 | 0.602640E+10 | 2250.00 | 01-OCT-00:10 |
November | 0.953052E+11 | 88027.56 | 01-NOV-13:00 | 0.583200E+10 | 2250.00 | 01-NOV-00:10 |
December | 0.896230E+11 | 77971.02 | 06-DEC-13:30 | 0.602640E+10 | 2250.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.127953E+13 | 0.709571E+11 | ||||
Minimum of Months | 0.805089E+11 | 72569.69 | 0.544320E+10 | 2250.00 | ||
Maximum of Months | 0.136925E+12 | 104134.66 | 0.602748E+10 | 2931.12 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.127215E+11 | 0.115358E+11 | 0.00 | 0.104721E+11 | 0.00 | 0.00 | 0.641000E+10 | 0.00 | 0.00 | 0.00 | 0.197561E+10 | 0.00 |
February | 0.393028E+11 | 0.110373E+11 | 0.105871E+11 | 0.00 | 0.973307E+10 | 0.00 | 0.00 | 0.807076E+10 | 0.00 | 0.00 | 0.00 | 0.177785E+10 | 0.00 |
March | 0.453764E+11 | 0.115595E+11 | 0.123431E+11 | 0.00 | 0.120771E+11 | 0.00 | 0.00 | 0.126377E+11 | 0.00 | 0.00 | 0.00 | 0.195605E+10 | 0.00 |
April | 0.425433E+11 | 0.104844E+11 | 0.114862E+11 | 0.00 | 0.131766E+11 | 0.00 | 0.00 | 0.177797E+11 | 0.00 | 0.00 | 0.00 | 0.181317E+10 | 0.00 |
May | 0.441635E+11 | 0.102694E+11 | 0.119357E+11 | 0.00 | 0.177817E+11 | 0.00 | 0.00 | 0.293802E+11 | 0.00 | 0.00 | 0.00 | 0.181912E+10 | 0.00 |
June | 0.437562E+11 | 0.967554E+10 | 0.118862E+11 | 0.00 | 0.189079E+11 | 0.00 | 0.00 | 0.358342E+11 | 0.00 | 0.00 | 0.00 | 0.173211E+10 | 0.00 |
July | 0.429506E+11 | 0.100953E+11 | 0.115358E+11 | 0.00 | 0.198080E+11 | 0.00 | 0.00 | 0.428282E+11 | 0.00 | 0.00 | 0.00 | 0.174887E+10 | 0.00 |
August | 0.453764E+11 | 0.105817E+11 | 0.123357E+11 | 0.00 | 0.206095E+11 | 0.00 | 0.00 | 0.462239E+11 | 0.00 | 0.00 | 0.00 | 0.179785E+10 | 0.00 |
September | 0.425433E+11 | 0.108786E+11 | 0.114788E+11 | 0.00 | 0.184643E+11 | 0.00 | 0.00 | 0.356545E+11 | 0.00 | 0.00 | 0.00 | 0.176599E+10 | 0.00 |
October | 0.429506E+11 | 0.119383E+11 | 0.115432E+11 | 0.00 | 0.162526E+11 | 0.00 | 0.00 | 0.264222E+11 | 0.00 | 0.00 | 0.00 | 0.186767E+10 | 0.00 |
November | 0.413304E+11 | 0.121533E+11 | 0.110862E+11 | 0.00 | 0.121484E+11 | 0.00 | 0.00 | 0.167305E+11 | 0.00 | 0.00 | 0.00 | 0.185632E+10 | 0.00 |
December | 0.429506E+11 | 0.129007E+11 | 0.115358E+11 | 0.00 | 0.105998E+11 | 0.00 | 0.00 | 0.967393E+10 | 0.00 | 0.00 | 0.00 | 0.196215E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134295E+12 | 0.139290E+12 | 0.00 | 0.180031E+12 | 0.00 | 0.00 | 0.287646E+12 | 0.00 | 0.00 | 0.00 | 0.220728E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.967554E+10 | 0.105871E+11 | 0.00 | 0.973307E+10 | 0.00 | 0.00 | 0.641000E+10 | 0.00 | 0.00 | 0.00 | 0.173211E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.129007E+11 | 0.123431E+11 | 0.00 | 0.206095E+11 | 0.00 | 0.00 | 0.462239E+11 | 0.00 | 0.00 | 0.00 | 0.197561E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.602748E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.544320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.709571E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.544320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.602748E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 10556.57 | 04-JAN-12:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 12861.87 | 06-FEB-13:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 12861.87 | 01-MAR-11:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 12861.87 | 01-APR-10:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 12861.87 | 01-MAY-09:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12861.87 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12861.87 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12861.87 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12861.87 | 01-SEP-06:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 12861.87 | 02-OCT-07:49 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 12861.87 | 01-NOV-09:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 12861.87 | 01-DEC-12:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 10556.57 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 12861.87 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12006.48 | 23-JAN-13:50 | 0.00 | 0.00 | 0.00 | 1740.29 | 11-JAN-12:00 | 0.00 |
February | 17859.70 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 1737.44 | 01-FEB-12:00 | 0.00 |
March | 23006.10 | 27-MAR-11:30 | 0.00 | 0.00 | 0.00 | 1725.33 | 01-MAR-12:00 | 0.00 |
April | 28597.86 | 28-APR-15:09 | 0.00 | 0.00 | 0.00 | 1704.18 | 01-APR-11:39 | 0.00 |
May | 33785.57 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1681.90 | 01-MAY-11:50 | 0.00 |
June | 39927.48 | 09-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1663.03 | 01-JUN-11:20 | 0.00 |
July | 41233.47 | 14-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1654.39 | 31-JUL-11:20 | 0.00 |
August | 46274.87 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1665.97 | 31-AUG-11:30 | 0.00 |
September | 36345.40 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1685.16 | 30-SEP-11:00 | 0.00 |
October | 30275.67 | 07-OCT-15:50 | 0.00 | 0.00 | 0.00 | 1708.33 | 31-OCT-11:30 | 0.00 |
November | 25725.23 | 01-NOV-15:39 | 0.00 | 0.00 | 0.00 | 1727.92 | 30-NOV-12:20 | 0.00 |
December | 16292.63 | 06-DEC-13:50 | 0.00 | 0.00 | 0.00 | 1739.09 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12006.48 | 0.00 | 0.00 | 0.00 | 1654.39 | 0.00 | ||
Maximum of Months | 46274.87 | 0.00 | 0.00 | 0.00 | 1740.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72569.69 | 23-JAN-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 10556.57 | 0.00 | 0.00 | 12006.48 | 0.00 |
February | 80705.83 | 07-FEB-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 17840.60 | 0.00 |
March | 84897.24 | 27-MAR-12:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 22055.78 | 0.00 |
April | 89388.54 | 28-APR-12:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 26567.22 | 0.00 |
May | 93517.76 | 31-MAY-14:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 30714.23 | 0.00 |
June | 98691.19 | 09-JUN-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 35891.14 | 0.00 |
July | 100865.31 | 14-JUL-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 38397.65 | 0.00 |
August | 104134.66 | 10-AUG-15:00 | 33916.61 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 46274.87 | 0.00 |
September | 95737.76 | 08-SEP-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 32928.12 | 0.00 |
October | 91650.03 | 07-OCT-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 28843.63 | 0.00 |
November | 88027.56 | 01-NOV-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 25207.95 | 0.00 |
December | 77971.02 | 06-DEC-13:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11709.22 | 0.00 | 0.00 | 16262.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 72569.69 | 33916.61 | 10112.62 | 0.00 | 0.00 | 10556.57 | 0.00 | 0.00 | 12006.48 | 0.00 | |
Maximum of Months | 104134.66 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12861.87 | 0.00 | 0.00 | 46274.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2931.12 | 02-JAN-07:40 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2250.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2250.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2250.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2250.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2250.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2250.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2250.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2250.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 2250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2931.12 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.10 | 1.67 | 24.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.64 | 4.17 | 24.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.78 | 8.50 | 26.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.12 | 9.00 | 26.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 28.32 | 10.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 28.23 | 11.67 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.56 | 8.83 | 26.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.95 | 8.33 | 25.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.84 | 5.83 | 24.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.55 | 1.33 | 24.55 |
Annual Sum or Average | 0.00 | 0.00 | 120.33 | 27.26 | 70.33 | 26.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 28.32 | 11.67 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.45 | 0.00 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.41 | 0.00 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.54 | 0.00 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 27.68 | 0.17 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 84.83 | 27.67 | 0.83 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 114.83 | 27.82 | 4.00 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 | 27.84 | 4.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 90.17 | 27.67 | 2.00 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.60 | 0.00 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.45 | 0.00 | 27.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.35 | 0.00 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 579.00 | 27.70 | 11.50 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 114.83 | 27.84 | 4.50 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.33 | 23.33 | 174.83 | 23.80 | 0.00 | 23.80 |
February | 12.17 | 23.40 | 228.83 | 23.88 | 0.50 | 23.88 |
March | 3.17 | 23.76 | 293.17 | 23.91 | 0.67 | 23.91 |
April | 3.17 | 24.11 | 300.00 | 23.92 | 3.17 | 23.92 |
May | 17.83 | 24.19 | 312.00 | 23.95 | 17.83 | 23.96 |
June | 48.83 | 24.15 | 312.00 | 23.97 | 48.83 | 24.00 |
July | 85.00 | 24.12 | 300.00 | 24.00 | 85.00 | 24.02 |
August | 93.50 | 24.17 | 324.00 | 24.02 | 93.50 | 24.05 |
September | 61.00 | 24.15 | 300.00 | 23.98 | 61.00 | 24.01 |
October | 30.50 | 24.13 | 300.00 | 23.95 | 30.50 | 23.97 |
November | 8.50 | 24.10 | 288.00 | 23.92 | 8.50 | 23.93 |
December | 1.83 | 23.61 | 275.83 | 23.91 | 0.67 | 23.91 |
Annual Sum or Average | 403.83 | 24.04 | 3408.67 | 23.94 | 350.17 | 23.96 |
Minimum of Months | 1.83 | 23.33 | 174.83 | 23.80 | 0.00 | 23.80 |
Maximum of Months | 93.50 | 24.19 | 324.00 | 24.02 | 93.50 | 24.05 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.00 | 25.98 | 269.50 | 26.42 | 71.17 | 26.47 |
February | 152.33 | 26.55 | 266.50 | 26.55 | 146.50 | 26.58 |
March | 217.83 | 26.68 | 320.83 | 26.65 | 217.33 | 26.66 |
April | 252.83 | 26.69 | 300.00 | 26.69 | 252.83 | 26.69 |
May | 298.67 | 26.71 | 312.00 | 26.71 | 298.67 | 26.71 |
June | 311.50 | 26.71 | 312.00 | 26.71 | 311.50 | 26.71 |
July | 299.50 | 26.71 | 300.00 | 26.71 | 299.50 | 26.71 |
August | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
September | 299.83 | 26.71 | 300.00 | 26.71 | 299.83 | 26.71 |
October | 291.67 | 26.71 | 300.00 | 26.71 | 291.67 | 26.71 |
November | 265.17 | 26.71 | 288.00 | 26.70 | 265.17 | 26.70 |
December | 184.83 | 26.66 | 295.00 | 26.61 | 183.83 | 26.63 |
Annual Sum or Average | 2988.17 | 26.67 | 3587.83 | 26.67 | 2962.00 | 26.68 |
Minimum of Months | 90.00 | 25.98 | 266.50 | 26.42 | 71.17 | 26.47 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.00 | 23.67 | 179.00 | 25.10 | 17.50 | 25.18 |
February | 123.17 | 27.77 | 262.17 | 27.17 | 119.00 | 27.34 |
March | 263.50 | 29.05 | 324.00 | 28.77 | 263.50 | 28.86 |
April | 300.00 | 30.45 | 300.00 | 30.45 | 300.00 | 30.45 |
May | 312.00 | 33.47 | 312.00 | 33.47 | 312.00 | 33.47 |
June | 312.00 | 34.71 | 312.00 | 34.71 | 312.00 | 34.71 |
July | 300.00 | 36.33 | 300.00 | 36.33 | 300.00 | 36.33 |
August | 324.00 | 36.65 | 324.00 | 36.65 | 324.00 | 36.65 |
September | 300.00 | 34.13 | 300.00 | 34.13 | 300.00 | 34.13 |
October | 300.00 | 31.85 | 300.00 | 31.85 | 300.00 | 31.85 |
November | 288.00 | 29.73 | 288.00 | 29.73 | 288.00 | 29.73 |
December | 211.50 | 28.26 | 299.00 | 27.90 | 211.50 | 28.01 |
Annual Sum or Average | 3138.17 | 32.20 | 3500.17 | 31.90 | 3047.50 | 32.08 |
Minimum of Months | 104.00 | 23.67 | 179.00 | 25.10 | 17.50 | 25.18 |
Maximum of Months | 324.00 | 36.65 | 324.00 | 36.65 | 324.00 | 36.65 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.690933E+10 | 0.184482E+10 | 261.46 | 0.588401E+10 | 0.102532E+10 | 0.00 | 1.00 | 23-JAN-06:02 | 0.00 | 01-JAN-00:10 | 38978.87 | 30-JAN-06:01 | 29317.82 | 25-JAN-06:02 | 12932.28 | 30-JAN-06:02 | 8973.85 | 30-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.797614E+10 | 0.214964E+10 | 250.80 | 0.663843E+10 | 0.133772E+10 | 0.00 | 1.00 | 04-FEB-06:02 | 0.00 | 01-FEB-00:10 | 40095.32 | 09-FEB-06:01 | 29072.54 | 10-FEB-06:02 | 14823.56 | 09-FEB-06:03 | 9148.06 | 09-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.111013E+11 | 0.306890E+10 | 309.43 | 0.955723E+10 | 0.154408E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 40634.62 | 29-MAR-05:01 | 34863.82 | 27-MAR-05:01 | 16406.72 | 29-MAR-05:03 | 9227.65 | 29-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.131894E+11 | 0.379588E+10 | 303.01 | 0.111260E+11 | 0.206341E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 40966.82 | 20-APR-05:01 | 34985.63 | 26-APR-05:01 | 17038.56 | 12-APR-05:03 | 9275.19 | 20-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.186141E+11 | 0.567654E+10 | 350.38 | 0.154040E+11 | 0.321008E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 43489.58 | 25-MAY-05:02 | 34953.51 | 10-MAY-05:01 | 23901.87 | 24-MAY-05:04 | 9848.06 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.224926E+11 | 0.686264E+10 | 359.74 | 0.168424E+11 | 0.565017E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 43166.20 | 08-JUN-05:01 | 30979.85 | 16-JUN-05:01 | 25140.85 | 27-JUN-05:07 | 10131.07 | 29-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.257571E+11 | 0.793632E+10 | 430.22 | 0.181655E+11 | 0.759162E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 41968.30 | 06-JUL-05:06 | 33850.67 | 03-JUL-05:01 | 25672.41 | 06-JUL-05:08 | 10209.02 | 14-JUL-05:11 | 0.00 | 01-JUL-00:10 |
August | 0.286988E+11 | 0.882412E+10 | 457.04 | 0.199092E+11 | 0.878962E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 41968.30 | 31-AUG-05:01 | 29982.32 | 13-AUG-14:51 | 25376.35 | 08-AUG-05:09 | 10766.66 | 13-AUG-14:11 | 0.00 | 01-AUG-00:10 |
September | 0.227911E+11 | 0.678325E+10 | 360.78 | 0.162138E+11 | 0.657732E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 43873.42 | 25-SEP-05:02 | 27515.03 | 05-SEP-05:01 | 25201.72 | 12-SEP-05:08 | 9951.28 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.182205E+11 | 0.525628E+10 | 331.18 | 0.139085E+11 | 0.431201E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 43458.47 | 17-OCT-05:01 | 32751.20 | 20-OCT-05:01 | 24734.45 | 07-OCT-05:05 | 9752.74 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.136758E+11 | 0.378578E+10 | 289.14 | 0.107191E+11 | 0.295676E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 42948.43 | 03-NOV-05:01 | 31214.69 | 18-NOV-06:01 | 19654.76 | 03-NOV-05:05 | 9535.50 | 03-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.951918E+10 | 0.254274E+10 | 280.83 | 0.777078E+10 | 0.174839E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 40061.05 | 06-DEC-06:01 | 31352.79 | 13-DEC-06:02 | 15673.11 | 06-DEC-06:02 | 9142.91 | 06-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.198945E+12 | 0.585269E+11 | 3984.01 | 0.152139E+12 | 0.468065E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.690933E+10 | 0.184482E+10 | 250.80 | 0.588401E+10 | 0.102532E+10 | 0.00 | 1.00 | 0.00 | 38978.87 | 27515.03 | 12932.28 | 8973.85 | 0.00 | |||||||
Maximum of Months | 0.286988E+11 | 0.882412E+10 | 457.04 | 0.199092E+11 | 0.878962E+10 | 0.00 | 1.00 | 0.00 | 43873.42 | 34985.63 | 25672.41 | 10766.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.156977E+11 | 0.456517E+10 | 243.08 | 0.133572E+11 | 0.234058E+10 | 0.00 | 0.28 | 29-JAN-12:00 | 0.00 | 01-JAN-00:10 | 32584.81 | 29-JAN-12:00 | 28509.31 | 28-JAN-14:00 | 8262.67 | 29-JAN-15:25 | 9637.23 | 29-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 0.201033E+11 | 0.592113E+10 | 245.07 | 0.168896E+11 | 0.321364E+10 | 0.00 | 0.71 | 05-FEB-13:33 | 0.00 | 01-FEB-00:10 | 80548.05 | 05-FEB-13:33 | 73613.10 | 05-FEB-13:33 | 12473.60 | 07-FEB-18:10 | 24484.83 | 05-FEB-13:33 | 0.00 | 01-FEB-00:10 |
March | 0.316548E+11 | 0.956882E+10 | 339.64 | 0.275235E+11 | 0.413125E+10 | 0.00 | 1.00 | 26-MAR-12:43 | 0.00 | 01-MAR-00:10 | 113320.83 | 26-MAR-15:23 | 113320.83 | 26-MAR-15:23 | 17209.33 | 31-MAR-17:08 | 34810.81 | 26-MAR-12:43 | 0.00 | 01-MAR-00:10 |
April | 0.445767E+11 | 0.139838E+11 | 419.99 | 0.378490E+11 | 0.672768E+10 | 0.00 | 1.00 | 02-APR-13:32 | 0.00 | 01-APR-00:10 | 133680.44 | 30-APR-16:23 | 114071.70 | 02-APR-15:32 | 46039.81 | 30-APR-16:23 | 36797.85 | 30-APR-11:02 | 0.00 | 01-APR-00:10 |
May | 0.715999E+11 | 0.237037E+11 | 567.55 | 0.599438E+11 | 0.116561E+11 | 0.00 | 1.00 | 03-MAY-17:42 | 0.00 | 01-MAY-00:15 | 134094.25 | 24-MAY-17:42 | 112087.61 | 07-MAY-15:22 | 47439.13 | 29-MAY-14:23 | 39351.01 | 31-MAY-17:42 | 0.00 | 01-MAY-00:10 |
June | 0.877596E+11 | 0.289715E+11 | 575.35 | 0.665050E+11 | 0.212546E+11 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:13 | 139983.47 | 09-JUN-05:01 | 108963.32 | 20-JUN-17:42 | 63147.08 | 09-JUN-05:01 | 39402.75 | 11-JUN-13:42 | 0.00 | 01-JUN-00:10 |
July | 0.104156E+12 | 0.348919E+11 | 597.86 | 0.759257E+11 | 0.282302E+11 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:13 | 140962.21 | 18-JUL-05:01 | 111562.00 | 04-JUL-09:02 | 63037.48 | 18-JUL-05:01 | 40530.17 | 30-JUL-13:02 | 0.00 | 01-JUL-00:10 |
August | 0.111866E+12 | 0.373998E+11 | 607.07 | 0.803001E+11 | 0.315659E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:12 | 144621.48 | 08-AUG-05:01 | 105294.12 | 06-AUG-07:42 | 73081.79 | 08-AUG-05:01 | 41085.30 | 10-AUG-17:42 | 0.00 | 01-AUG-00:10 |
September | 0.892675E+11 | 0.288713E+11 | 572.51 | 0.647260E+11 | 0.245415E+11 | 0.00 | 1.00 | 01-SEP-17:04 | 0.00 | 01-SEP-00:13 | 139179.37 | 10-SEP-17:42 | 105925.21 | 04-SEP-12:22 | 61789.43 | 10-SEP-17:42 | 39524.45 | 04-SEP-14:22 | 0.00 | 01-SEP-00:10 |
October | 0.671359E+11 | 0.211660E+11 | 555.99 | 0.523239E+11 | 0.148120E+11 | 0.00 | 1.00 | 02-OCT-17:05 | 0.00 | 01-OCT-00:15 | 134289.98 | 07-OCT-17:06 | 111780.78 | 29-OCT-16:03 | 55334.13 | 18-OCT-05:07 | 37568.37 | 07-OCT-17:06 | 0.00 | 01-OCT-00:10 |
November | 0.427123E+11 | 0.129447E+11 | 398.23 | 0.342667E+11 | 0.844562E+10 | 0.00 | 1.00 | 05-NOV-11:43 | 0.00 | 01-NOV-00:15 | 123396.48 | 03-NOV-05:01 | 113162.96 | 19-NOV-14:02 | 47884.37 | 03-NOV-05:01 | 34846.74 | 05-NOV-15:43 | 0.00 | 01-NOV-00:10 |
December | 0.244533E+11 | 0.713119E+10 | 285.61 | 0.201138E+11 | 0.433945E+10 | 0.00 | 0.65 | 03-DEC-13:03 | 0.00 | 01-DEC-00:10 | 75071.52 | 03-DEC-13:03 | 66321.41 | 03-DEC-13:03 | 15402.86 | 03-DEC-15:03 | 22082.63 | 03-DEC-13:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.710983E+12 | 0.229119E+12 | 5407.95 | 0.549724E+12 | 0.161259E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.156977E+11 | 0.456517E+10 | 243.08 | 0.133572E+11 | 0.234058E+10 | 0.00 | 0.28 | 0.00 | 32584.81 | 28509.31 | 8262.67 | 9637.23 | 0.00 | |||||||
Maximum of Months | 0.111866E+12 | 0.373998E+11 | 607.07 | 0.803001E+11 | 0.315659E+11 | 0.00 | 1.00 | 0.00 | 144621.48 | 114071.70 | 73081.79 | 41085.30 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.12 | 12.48 | 30.64 | 79.09 | 122.38 | 0.00 | 0.00 | 0.00 |
February | 49.17 | 14.14 | 35.02 | 104.33 | 106.46 | 0.00 | 0.00 | 0.00 |
March | 58.02 | 17.19 | 40.83 | 148.23 | 85.31 | 0.00 | 0.00 | 0.00 |
April | 63.18 | 17.61 | 45.57 | 197.31 | 59.77 | 0.00 | 0.00 | 0.00 |
May | 68.87 | 20.56 | 48.31 | 271.95 | 22.25 | 0.00 | 0.00 | 0.00 |
June | 71.29 | 22.52 | 48.78 | 299.19 | 10.19 | 0.00 | 0.00 | 0.00 |
July | 65.54 | 18.85 | 46.69 | 320.03 | 1.54 | 0.00 | 0.00 | 0.00 |
August | 66.90 | 20.23 | 46.67 | 328.13 | 1.00 | 0.00 | 0.00 | 0.00 |
September | 63.74 | 20.00 | 43.75 | 264.25 | 13.43 | 0.00 | 0.00 | 0.00 |
October | 56.72 | 18.32 | 38.39 | 201.59 | 36.41 | 0.00 | 0.00 | 0.00 |
November | 48.88 | 16.05 | 32.83 | 139.78 | 73.22 | 0.00 | 0.00 | 0.00 |
December | 40.99 | 12.52 | 28.47 | 85.87 | 111.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.07 | 17.55 | 40.52 | 203.89 | 53.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.99 | 12.48 | 28.47 | 79.09 | 1.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.29 | 22.52 | 48.78 | 328.13 | 122.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.12 | 12.48 | 30.64 | 79.09 | 122.38 | 0.00 | 0.00 | 0.00 |
February | 49.17 | 14.14 | 35.02 | 104.33 | 106.46 | 0.00 | 0.00 | 0.00 |
March | 58.02 | 17.19 | 40.83 | 148.23 | 85.31 | 0.00 | 0.00 | 0.00 |
April | 63.18 | 17.61 | 45.57 | 197.31 | 59.77 | 0.00 | 0.00 | 0.00 |
May | 68.87 | 20.56 | 48.31 | 271.95 | 22.25 | 0.00 | 0.00 | 0.00 |
June | 71.29 | 22.52 | 48.78 | 299.19 | 10.19 | 0.00 | 0.00 | 0.00 |
July | 65.54 | 18.85 | 46.69 | 320.03 | 1.54 | 0.00 | 0.00 | 0.00 |
August | 66.90 | 20.23 | 46.67 | 328.13 | 1.00 | 0.00 | 0.00 | 0.00 |
September | 63.74 | 20.00 | 43.75 | 264.25 | 13.43 | 0.00 | 0.00 | 0.00 |
October | 56.72 | 18.32 | 38.39 | 201.59 | 36.41 | 0.00 | 0.00 | 0.00 |
November | 48.88 | 16.05 | 32.83 | 139.78 | 73.22 | 0.00 | 0.00 | 0.00 |
December | 40.99 | 12.52 | 28.47 | 85.87 | 111.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.07 | 17.55 | 40.52 | 203.89 | 53.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.99 | 12.48 | 28.47 | 79.09 | 1.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.29 | 22.52 | 48.78 | 328.13 | 122.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.10 | 0.00 | 14.10 | 16.89 | 73.21 | 0.00 | 0.00 | 0.00 |
February | 16.16 | 0.00 | 16.16 | 26.23 | 63.75 | 0.00 | 0.00 | 0.00 |
March | 18.57 | 0.00 | 18.56 | 42.59 | 50.46 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 0.10 | 20.89 | 68.13 | 34.48 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 1.04 | 22.85 | 108.93 | 12.23 | 0.00 | 0.00 | 0.00 |
June | 25.65 | 1.85 | 23.79 | 126.53 | 5.97 | 0.00 | 0.00 | 0.00 |
July | 23.41 | 0.94 | 22.47 | 141.91 | 0.89 | 0.00 | 0.00 | 0.00 |
August | 21.70 | 0.35 | 21.36 | 139.03 | 0.50 | 0.00 | 0.00 | 0.00 |
September | 19.62 | 0.01 | 19.61 | 100.61 | 7.56 | 0.00 | 0.00 | 0.00 |
October | 17.38 | 0.00 | 17.38 | 69.79 | 20.94 | 0.00 | 0.00 | 0.00 |
November | 14.92 | 0.00 | 14.92 | 41.06 | 42.72 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 19.74 | 66.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.14 | 0.36 | 18.78 | 75.42 | 31.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 16.89 | 0.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.65 | 1.85 | 23.79 | 141.91 | 73.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.10 | 0.00 | 14.10 | 16.89 | 73.21 | 0.00 | 0.00 | 0.00 |
February | 16.16 | 0.00 | 16.16 | 26.23 | 63.75 | 0.00 | 0.00 | 0.00 |
March | 18.56 | 0.00 | 18.56 | 42.59 | 50.45 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 0.10 | 20.89 | 68.13 | 34.48 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 1.04 | 22.85 | 108.93 | 12.23 | 0.00 | 0.00 | 0.00 |
June | 25.64 | 1.85 | 23.79 | 126.53 | 5.97 | 0.00 | 0.00 | 0.00 |
July | 23.40 | 0.94 | 22.47 | 141.91 | 0.89 | 0.00 | 0.00 | 0.00 |
August | 21.70 | 0.35 | 21.36 | 139.03 | 0.50 | 0.00 | 0.00 | 0.00 |
September | 19.62 | 0.01 | 19.61 | 100.61 | 7.56 | 0.00 | 0.00 | 0.00 |
October | 17.38 | 0.00 | 17.38 | 69.79 | 20.94 | 0.00 | 0.00 | 0.00 |
November | 14.92 | 0.00 | 14.92 | 41.06 | 42.72 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 19.74 | 66.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.14 | 0.36 | 18.78 | 75.42 | 31.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 16.89 | 0.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.64 | 1.85 | 23.79 | 141.91 | 73.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.45 | 15.51 | 24.95 | 61.41 | 54.79 | 8.00 | 0.00 | 0.00 |
February | 49.05 | 20.04 | 29.00 | 75.97 | 53.32 | 0.00 | 0.00 | 0.00 |
March | 59.31 | 24.90 | 34.42 | 95.48 | 52.38 | 0.00 | 0.00 | 0.00 |
April | 69.91 | 30.98 | 38.93 | 118.72 | 47.52 | 2.00 | 0.00 | 0.00 |
May | 79.30 | 38.54 | 40.76 | 140.09 | 34.28 | 2.00 | 0.00 | 0.00 |
June | 82.65 | 42.01 | 40.64 | 145.81 | 32.82 | 8.17 | 0.00 | 0.00 |
July | 80.18 | 40.65 | 39.52 | 143.69 | 29.32 | 2.33 | 0.00 | 0.00 |
August | 76.39 | 37.52 | 38.87 | 135.61 | 30.22 | 3.67 | 0.00 | 0.00 |
September | 68.58 | 32.90 | 35.67 | 120.65 | 35.13 | 20.33 | 0.00 | 0.00 |
October | 57.70 | 27.10 | 30.60 | 98.32 | 42.87 | 32.00 | 0.00 | 0.00 |
November | 45.85 | 20.05 | 25.79 | 72.57 | 55.86 | 0.00 | 0.00 | 0.00 |
December | 37.59 | 14.61 | 22.98 | 54.64 | 60.54 | 6.17 | 0.00 | 0.00 |
Annual Sum or Average | 62.31 | 28.78 | 33.53 | 105.39 | 44.03 | 84.67 | 0.00 | 0.00 |
Minimum of Months | 37.59 | 14.61 | 22.98 | 54.64 | 29.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.65 | 42.01 | 40.76 | 145.81 | 60.54 | 32.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115499E+09 | 33430114.87 | 82069350.32 | 0.211829E+09 | 0.327793E+09 |
February | 0.118943E+09 | 34211376.74 | 84731438.60 | 0.252387E+09 | 0.257552E+09 |
March | 0.155399E+09 | 46040397.02 | 0.109359E+09 | 0.397032E+09 | 0.228497E+09 |
April | 0.163755E+09 | 45644833.27 | 0.118110E+09 | 0.511430E+09 | 0.154927E+09 |
May | 0.184463E+09 | 55070047.26 | 0.129393E+09 | 0.728393E+09 | 59597119.83 |
June | 0.184790E+09 | 58358977.90 | 0.126431E+09 | 0.775498E+09 | 26410157.60 |
July | 0.175542E+09 | 50493352.68 | 0.125049E+09 | 0.857161E+09 | 4134281.33 |
August | 0.179188E+09 | 54196184.91 | 0.124992E+09 | 0.878872E+09 | 2681766.68 |
September | 0.165224E+09 | 51829243.54 | 0.113395E+09 | 0.684933E+09 | 34820544.14 |
October | 0.151910E+09 | 49076778.40 | 0.102833E+09 | 0.539940E+09 | 97517514.54 |
November | 0.126705E+09 | 41610043.46 | 85095231.67 | 0.362315E+09 | 0.189796E+09 |
December | 0.109780E+09 | 33526329.08 | 76253413.23 | 0.229991E+09 | 0.297608E+09 |
Annual Sum or Average | 0.183120E+10 | 0.553488E+09 | 0.127771E+10 | 0.642978E+10 | 0.168133E+10 |
Minimum of Months | 0.109780E+09 | 33430114.87 | 76253413.23 | 0.211829E+09 | 2681766.68 |
Maximum of Months | 0.184790E+09 | 58358977.90 | 0.129393E+09 | 0.878872E+09 | 0.327793E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115499E+09 | 33430114.87 | 82069350.32 | 0.211829E+09 | 0.327793E+09 |
February | 0.118943E+09 | 34211376.74 | 84731438.60 | 0.252387E+09 | 0.257552E+09 |
March | 0.155399E+09 | 46040397.02 | 0.109359E+09 | 0.397032E+09 | 0.228497E+09 |
April | 0.163755E+09 | 45644833.27 | 0.118110E+09 | 0.511430E+09 | 0.154927E+09 |
May | 0.184463E+09 | 55070047.26 | 0.129393E+09 | 0.728393E+09 | 59597119.83 |
June | 0.184790E+09 | 58358977.90 | 0.126431E+09 | 0.775498E+09 | 26410157.60 |
July | 0.175542E+09 | 50493352.68 | 0.125049E+09 | 0.857161E+09 | 4134281.33 |
August | 0.179188E+09 | 54196184.91 | 0.124992E+09 | 0.878872E+09 | 2681766.68 |
September | 0.165224E+09 | 51829243.54 | 0.113395E+09 | 0.684933E+09 | 34820544.14 |
October | 0.151910E+09 | 49076778.40 | 0.102833E+09 | 0.539940E+09 | 97517514.54 |
November | 0.126705E+09 | 41610043.46 | 85095231.67 | 0.362315E+09 | 0.189796E+09 |
December | 0.109780E+09 | 33526329.08 | 76253413.23 | 0.229991E+09 | 0.297608E+09 |
Annual Sum or Average | 0.183120E+10 | 0.553488E+09 | 0.127771E+10 | 0.642978E+10 | 0.168133E+10 |
Minimum of Months | 0.109780E+09 | 33430114.87 | 76253413.23 | 0.211829E+09 | 2681766.68 |
Maximum of Months | 0.184790E+09 | 58358977.90 | 0.129393E+09 | 0.878872E+09 | 0.327793E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37757180.39 | 0.00 | 37757180.39 | 45237018.74 | 0.196074E+09 |
February | 39092110.75 | 0.00 | 39092110.75 | 63448930.86 | 0.154221E+09 |
March | 49725459.30 | 4356.41 | 49721102.89 | 0.114067E+09 | 0.135140E+09 |
April | 54391648.46 | 253761.02 | 54137887.44 | 0.176592E+09 | 89363420.81 |
May | 63986555.05 | 2775915.28 | 61210639.76 | 0.291762E+09 | 32760798.68 |
June | 66473330.18 | 4799522.49 | 61673807.69 | 0.327962E+09 | 15464436.13 |
July | 62688753.09 | 2515175.01 | 60173578.08 | 0.380090E+09 | 2380007.13 |
August | 58130145.26 | 927816.44 | 57202328.83 | 0.372388E+09 | 1341221.16 |
September | 50851213.01 | 23723.51 | 50827489.50 | 0.260789E+09 | 19591518.66 |
October | 46560892.55 | 0.00 | 46560892.55 | 0.186918E+09 | 56094227.16 |
November | 38682121.08 | 0.00 | 38682121.08 | 0.106426E+09 | 0.110731E+09 |
December | 35241442.63 | 0.00 | 35241442.63 | 52884531.98 | 0.177545E+09 |
Annual Sum or Average | 0.603581E+09 | 11300270.16 | 0.592281E+09 | 0.237856E+10 | 0.990707E+09 |
Minimum of Months | 35241442.63 | 0.00 | 35241442.63 | 45237018.74 | 1341221.16 |
Maximum of Months | 66473330.18 | 4799522.49 | 61673807.69 | 0.380090E+09 | 0.196074E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37755941.24 | 0.00 | 37755941.24 | 45234939.59 | 0.196073E+09 |
February | 39090851.70 | 0.00 | 39090851.70 | 63446691.21 | 0.154220E+09 |
March | 49723882.49 | 4356.21 | 49719526.28 | 0.114064E+09 | 0.135138E+09 |
April | 54389956.29 | 253749.12 | 54136207.16 | 0.176589E+09 | 89361741.85 |
May | 63984550.27 | 2775785.17 | 61208765.09 | 0.291759E+09 | 32759576.13 |
June | 66471214.63 | 4799297.53 | 61671917.10 | 0.327958E+09 | 15463521.75 |
July | 62686814.52 | 2515057.12 | 60171757.40 | 0.380087E+09 | 2379730.33 |
August | 58128378.47 | 927772.95 | 57200605.52 | 0.372386E+09 | 1341036.72 |
September | 50849669.28 | 23722.39 | 50825946.88 | 0.260787E+09 | 19590540.85 |
October | 46559448.55 | 0.00 | 46559448.55 | 0.186916E+09 | 56092419.68 |
November | 38680887.14 | 0.00 | 38680887.14 | 0.106424E+09 | 0.110729E+09 |
December | 35240285.69 | 0.00 | 35240285.69 | 52882586.71 | 0.177543E+09 |
Annual Sum or Average | 0.603562E+09 | 11299740.50 | 0.592262E+09 | 0.237853E+10 | 0.990692E+09 |
Minimum of Months | 35240285.69 | 0.00 | 35240285.69 | 45234939.59 | 1341036.72 |
Maximum of Months | 66471214.63 | 4799297.53 | 61671917.10 | 0.380087E+09 | 0.196073E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108353E+09 | 41536984.76 | 66816085.92 | 0.164482E+09 | 0.146741E+09 |
February | 0.118651E+09 | 48489204.99 | 70161876.04 | 0.183785E+09 | 0.128996E+09 |
March | 0.158865E+09 | 66683171.47 | 92182130.45 | 0.255730E+09 | 0.140303E+09 |
April | 0.181210E+09 | 80312888.98 | 0.100897E+09 | 0.307723E+09 | 0.123164E+09 |
May | 0.212402E+09 | 0.103231E+09 | 0.109171E+09 | 0.375206E+09 | 91817757.84 |
June | 0.214234E+09 | 0.108887E+09 | 0.105346E+09 | 0.377946E+09 | 85069856.81 |
July | 0.214744E+09 | 0.108889E+09 | 0.105855E+09 | 0.384860E+09 | 78536429.41 |
August | 0.204604E+09 | 0.100505E+09 | 0.104099E+09 | 0.363205E+09 | 80948731.07 |
September | 0.177758E+09 | 85289166.94 | 92469315.66 | 0.312731E+09 | 91058186.89 |
October | 0.154542E+09 | 72582102.93 | 81959435.78 | 0.263349E+09 | 0.114818E+09 |
November | 0.118839E+09 | 51978803.71 | 66860136.24 | 0.188091E+09 | 0.144789E+09 |
December | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 0.162140E+09 |
Annual Sum or Average | 0.196487E+10 | 0.907511E+09 | 0.105736E+10 | 0.332344E+10 | 0.138838E+10 |
Minimum of Months | 0.100671E+09 | 39125538.77 | 61545088.40 | 0.146335E+09 | 78536429.41 |
Maximum of Months | 0.214744E+09 | 0.108889E+09 | 0.109171E+09 | 0.384860E+09 | 0.162140E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 187.34 | 386.56 | 114.44 | 24.96 | 89.48 | 0.00 | 0.00 |
February | 257.95 | 337.27 | 130.65 | 28.28 | 102.37 | 0.00 | 0.00 |
March | 379.82 | 269.71 | 153.17 | 34.38 | 118.79 | 0.00 | 0.00 |
April | 530.50 | 188.11 | 168.32 | 35.42 | 132.91 | 0.00 | 0.00 |
May | 761.28 | 68.48 | 185.52 | 43.19 | 142.33 | 0.00 | 0.00 |
June | 851.13 | 32.01 | 193.88 | 48.73 | 145.14 | 0.00 | 0.00 |
July | 923.81 | 4.80 | 177.89 | 39.58 | 138.31 | 0.00 | 0.00 |
August | 934.31 | 2.99 | 177.21 | 41.16 | 136.05 | 0.00 | 0.00 |
September | 729.67 | 41.93 | 166.72 | 40.01 | 126.71 | 0.00 | 0.00 |
October | 542.73 | 114.68 | 148.20 | 36.65 | 111.55 | 0.00 | 0.00 |
November | 361.21 | 231.42 | 127.61 | 32.11 | 95.51 | 0.00 | 0.00 |
December | 208.58 | 352.16 | 108.29 | 25.03 | 83.25 | 0.00 | 0.00 |
Annual Sum or Average | 557.46 | 168.30 | 154.41 | 35.82 | 118.59 | 0.00 | 0.00 |
Minimum of Months | 187.34 | 2.99 | 108.29 | 24.96 | 83.25 | 0.00 | 0.00 |
Maximum of Months | 934.31 | 386.56 | 193.88 | 48.73 | 145.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1922.19 | 1829.71 | 404.54 | 155.08 | 249.46 | 0.00 | 0.00 |
February | 2478.66 | 1813.79 | 490.46 | 200.43 | 290.02 | 0.00 | 0.00 |
March | 3445.25 | 1923.40 | 593.14 | 248.97 | 344.17 | 0.00 | 0.00 |
April | 5083.10 | 2119.43 | 699.11 | 309.85 | 389.26 | 0.00 | 0.00 |
May | 6800.89 | 2140.36 | 793.02 | 385.42 | 407.60 | 0.00 | 0.00 |
June | 6704.32 | 2084.29 | 826.52 | 420.09 | 406.43 | 0.00 | 0.00 |
July | 7204.52 | 2051.69 | 801.76 | 406.55 | 395.22 | 0.00 | 0.00 |
August | 6158.88 | 2190.02 | 763.91 | 375.24 | 388.66 | 0.00 | 0.00 |
September | 5523.46 | 2285.46 | 685.80 | 329.05 | 356.75 | 0.00 | 0.00 |
October | 4175.18 | 2636.15 | 576.99 | 270.99 | 306.00 | 0.00 | 0.00 |
November | 2938.78 | 2478.53 | 458.48 | 200.54 | 257.95 | 0.00 | 0.00 |
December | 1879.09 | 2116.48 | 375.86 | 146.08 | 229.78 | 0.00 | 0.00 |
Annual Sum or Average | 4537.15 | 2140.66 | 623.06 | 287.77 | 335.29 | 0.00 | 0.00 |
Minimum of Months | 1879.09 | 1813.79 | 375.86 | 146.08 | 229.78 | 0.00 | 0.00 |
Maximum of Months | 7204.52 | 2636.15 | 826.52 | 420.09 | 407.60 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501765E+09 | 0.103537E+10 | 0.306512E+09 | 66860229.73 | 0.239652E+09 | 0.00 | 0.00 |
February | 0.624042E+09 | 0.815919E+09 | 0.316069E+09 | 68422753.48 | 0.247646E+09 | 0.00 | 0.00 |
March | 0.101731E+10 | 0.722387E+09 | 0.410248E+09 | 92089506.66 | 0.318159E+09 | 0.00 | 0.00 |
April | 0.137505E+10 | 0.487588E+09 | 0.436291E+09 | 91797176.69 | 0.344494E+09 | 0.00 | 0.00 |
May | 0.203902E+10 | 0.183429E+09 | 0.496898E+09 | 0.115692E+09 | 0.381206E+09 | 0.00 | 0.00 |
June | 0.220613E+10 | 82960507.94 | 0.502525E+09 | 0.126317E+09 | 0.376209E+09 | 0.00 | 0.00 |
July | 0.247433E+10 | 12854168.12 | 0.476459E+09 | 0.106017E+09 | 0.370442E+09 | 0.00 | 0.00 |
August | 0.250247E+10 | 7995511.21 | 0.474635E+09 | 0.110248E+09 | 0.364387E+09 | 0.00 | 0.00 |
September | 0.189131E+10 | 0.108687E+09 | 0.432149E+09 | 0.103706E+09 | 0.328443E+09 | 0.00 | 0.00 |
October | 0.145365E+10 | 0.307160E+09 | 0.396941E+09 | 98153556.79 | 0.298787E+09 | 0.00 | 0.00 |
November | 0.936268E+09 | 0.599840E+09 | 0.330774E+09 | 83220086.91 | 0.247553E+09 | 0.00 | 0.00 |
December | 0.558667E+09 | 0.943222E+09 | 0.290041E+09 | 67052658.16 | 0.222989E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175800E+11 | 0.530741E+10 | 0.486954E+10 | 0.112958E+10 | 0.373997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.501765E+09 | 7995511.21 | 0.290041E+09 | 66860229.73 | 0.222989E+09 | 0.00 | 0.00 |
Maximum of Months | 0.250247E+10 | 0.103537E+10 | 0.502525E+09 | 0.126317E+09 | 0.381206E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.514840E+10 | 0.490070E+10 | 0.108353E+10 | 0.415370E+09 | 0.668161E+09 | 0.00 | 0.00 |
February | 0.599638E+10 | 0.438793E+10 | 0.118651E+10 | 0.484892E+09 | 0.701619E+09 | 0.00 | 0.00 |
March | 0.922777E+10 | 0.515164E+10 | 0.158865E+10 | 0.666832E+09 | 0.921821E+09 | 0.00 | 0.00 |
April | 0.131754E+11 | 0.549356E+10 | 0.181210E+10 | 0.803129E+09 | 0.100897E+10 | 0.00 | 0.00 |
May | 0.182155E+11 | 0.573275E+10 | 0.212402E+10 | 0.103231E+10 | 0.109171E+10 | 0.00 | 0.00 |
June | 0.173776E+11 | 0.540247E+10 | 0.214234E+10 | 0.108887E+10 | 0.105346E+10 | 0.00 | 0.00 |
July | 0.192966E+11 | 0.549525E+10 | 0.214744E+10 | 0.108889E+10 | 0.105855E+10 | 0.00 | 0.00 |
August | 0.164959E+11 | 0.586575E+10 | 0.204604E+10 | 0.100505E+10 | 0.104099E+10 | 0.00 | 0.00 |
September | 0.143168E+11 | 0.592391E+10 | 0.177758E+10 | 0.852892E+09 | 0.924693E+09 | 0.00 | 0.00 |
October | 0.111828E+11 | 0.706067E+10 | 0.154542E+10 | 0.725821E+09 | 0.819594E+09 | 0.00 | 0.00 |
November | 0.761731E+10 | 0.642435E+10 | 0.118839E+10 | 0.519788E+09 | 0.668601E+09 | 0.00 | 0.00 |
December | 0.503296E+10 | 0.566878E+10 | 0.100671E+10 | 0.391255E+09 | 0.615451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143083E+12 | 0.675078E+11 | 0.196487E+11 | 0.907511E+10 | 0.105736E+11 | 0.00 | 0.00 |
Minimum of Months | 0.503296E+10 | 0.438793E+10 | 0.100671E+10 | 0.391255E+09 | 0.615451E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192966E+11 | 0.706067E+10 | 0.214744E+10 | 0.108889E+10 | 0.109171E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.682083E+09 | -608896211.6 | 0.00 | 0.00 | 744.00 | 0.00 | -73186844.7 | 58.99 | 0.00 | 0.00 |
February | 0.609227E+09 | -543788992.1 | 0.00 | 0.00 | 672.00 | 0.00 | -65437577.6 | 58.99 | 0.00 | 0.00 |
March | 0.662249E+09 | -590760274.1 | 0.00 | 0.00 | 744.00 | 0.00 | -71488967.6 | 58.99 | 0.00 | 0.00 |
April | 0.560971E+09 | -493210578.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67760431.6 | 58.99 | 0.00 | 0.00 |
May | 0.525341E+09 | -456668485.0 | 0.00 | 0.00 | 744.00 | 0.00 | -68672786.7 | 59.00 | 0.00 | 0.00 |
June | 0.480146E+09 | -413920279.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66225978.7 | 58.99 | 0.00 | 0.00 |
July | 0.455480E+09 | -387614282.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67865948.9 | 58.99 | 0.00 | 0.00 |
August | 0.503561E+09 | -435319637.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68241463.7 | 58.98 | 0.00 | 0.00 |
September | 0.514208E+09 | -448226283.3 | 0.00 | 0.00 | 720.00 | 0.00 | -65981657.3 | 58.99 | 0.00 | 0.00 |
October | 0.573687E+09 | -505123923.8 | 0.00 | 0.00 | 744.00 | 0.00 | -68563338.1 | 58.99 | 0.00 | 0.00 |
November | 0.604278E+09 | -536757200.5 | 0.00 | 0.00 | 720.00 | 0.00 | -67521057.8 | 58.99 | 0.00 | 0.00 |
December | 0.668541E+09 | -596895100.9 | 0.00 | 0.00 | 744.00 | 0.00 | -71645816.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.683977E+10 | -0.601718E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -822591869.7 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.455480E+09 | -608896211.6 | 0.00 | 0.00 | 672.00 | 0.00 | -73186844.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.682083E+09 | -387614282.3 | 0.00 | 0.00 | 744.00 | 0.00 | -65437577.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 695504.77 | 437.20 | 02-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695504.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 695504.77 | 437.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.690933E+10 | 0.588401E+10 | 38978.87 | 30-JAN-06:01 | 26376.31 | 0.00 |
February | 0.00 | 0.00 | 0.797614E+10 | 0.663843E+10 | 40095.32 | 09-FEB-06:01 | 25854.28 | 0.00 |
March | 0.00 | 0.00 | 0.111013E+11 | 0.955723E+10 | 40634.62 | 29-MAR-05:01 | 24713.85 | 0.00 |
April | 0.00 | 0.00 | 0.131894E+11 | 0.111260E+11 | 40966.82 | 20-APR-05:01 | 24489.82 | 0.00 |
May | 0.00 | 0.00 | 0.186141E+11 | 0.154040E+11 | 43489.58 | 25-MAY-05:02 | 21222.94 | 0.00 |
June | 0.00 | 0.00 | 0.224926E+11 | 0.168424E+11 | 43166.20 | 08-JUN-05:01 | 19657.91 | 0.00 |
July | 0.00 | 0.00 | 0.257571E+11 | 0.181655E+11 | 41968.30 | 06-JUL-05:06 | 16414.53 | 0.00 |
August | 0.00 | 0.00 | 0.286988E+11 | 0.199092E+11 | 41968.30 | 31-AUG-05:01 | 19122.12 | 0.00 |
September | 0.00 | 0.00 | 0.227911E+11 | 0.162138E+11 | 43873.42 | 25-SEP-05:02 | 21523.81 | 0.00 |
October | 0.00 | 0.00 | 0.182205E+11 | 0.139085E+11 | 43458.47 | 17-OCT-05:01 | 21736.06 | 0.00 |
November | 0.00 | 0.00 | 0.136758E+11 | 0.107191E+11 | 42948.43 | 03-NOV-05:01 | 23789.70 | 0.00 |
December | 0.00 | 0.00 | 0.951918E+10 | 0.777078E+10 | 40061.05 | 06-DEC-06:01 | 24618.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198945E+12 | 0.152139E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.690933E+10 | 0.588401E+10 | 38978.87 | 16414.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.286988E+11 | 0.199092E+11 | 43873.42 | 26376.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.156977E+11 | 0.133572E+11 | 32584.81 | 29-JAN-12:00 | 25206.59 | 0.00 |
February | 0.00 | 0.00 | 0.201033E+11 | 0.168896E+11 | 80548.05 | 05-FEB-13:33 | 73613.10 | 0.00 |
March | 0.00 | 0.00 | 0.316548E+11 | 0.275235E+11 | 113320.83 | 26-MAR-15:23 | 113320.83 | 0.00 |
April | 0.00 | 0.00 | 0.445767E+11 | 0.378490E+11 | 133680.44 | 30-APR-16:23 | 87640.63 | 0.00 |
May | 0.00 | 0.00 | 0.715999E+11 | 0.599438E+11 | 134094.25 | 24-MAY-17:42 | 87159.52 | 0.00 |
June | 0.00 | 0.00 | 0.877596E+11 | 0.665050E+11 | 139983.47 | 09-JUN-05:01 | 76836.39 | 0.00 |
July | 0.00 | 0.00 | 0.104156E+12 | 0.759257E+11 | 140962.21 | 18-JUL-05:01 | 77924.73 | 0.00 |
August | 0.00 | 0.00 | 0.111866E+12 | 0.803001E+11 | 144621.48 | 08-AUG-05:01 | 71539.69 | 0.00 |
September | 0.00 | 0.00 | 0.892675E+11 | 0.647260E+11 | 139179.37 | 10-SEP-17:42 | 77389.94 | 0.00 |
October | 0.00 | 0.00 | 0.671359E+11 | 0.523239E+11 | 134289.98 | 07-OCT-17:06 | 82599.12 | 0.00 |
November | 0.00 | 0.00 | 0.427123E+11 | 0.342667E+11 | 123396.48 | 03-NOV-05:01 | 75512.10 | 0.00 |
December | 0.00 | 0.00 | 0.244533E+11 | 0.201138E+11 | 75071.52 | 03-DEC-13:03 | 66321.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.710983E+12 | 0.549724E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.156977E+11 | 0.133572E+11 | 32584.81 | 25206.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111866E+12 | 0.803001E+11 | 144621.48 | 113320.83 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170813E+10 | 0.34 | 1719.65 | 02-JAN-08:00 | 0.89 |
February | 0.157657E+10 | 0.35 | 1719.65 | 01-FEB-08:40 | 0.89 |
March | 0.185938E+10 | 0.38 | 1719.65 | 08-MAR-16:50 | 0.89 |
April | 0.173603E+10 | 0.38 | 1719.65 | 03-APR-10:50 | 0.89 |
May | 0.185091E+10 | 0.43 | 1719.65 | 01-MAY-10:40 | 0.89 |
June | 0.187818E+10 | 0.45 | 1719.65 | 03-JUN-09:07 | 0.89 |
July | 0.187777E+10 | 0.54 | 1719.65 | 01-JUL-16:00 | 0.89 |
August | 0.202470E+10 | 0.57 | 1719.65 | 04-AUG-11:50 | 0.89 |
September | 0.182510E+10 | 0.46 | 1719.65 | 09-SEP-06:40 | 0.88 |
October | 0.177513E+10 | 0.40 | 1719.65 | 06-OCT-17:00 | 0.88 |
November | 0.166922E+10 | 0.36 | 1719.65 | 04-NOV-07:10 | 0.89 |
December | 0.171887E+10 | 0.35 | 1719.65 | 01-DEC-07:50 | 0.89 |
Annual Sum or Average | 0.215000E+11 | 0.42 | |||
Minimum of Months | 0.157657E+10 | 0.34 | 1719.65 | 0.88 | |
Maximum of Months | 0.202470E+10 | 0.57 | 1719.65 | 0.89 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.876397E+10 | 0.58 | 8836.92 | 04-JAN-12:30 | 1.53 |
February | 0.809679E+10 | 0.61 | 8836.92 | 02-FEB-10:30 | 1.52 |
March | 0.964097E+10 | 0.73 | 8836.92 | 18-MAR-14:10 | 1.53 |
April | 0.941812E+10 | 0.94 | 8836.92 | 01-APR-06:10 | 1.52 |
May | 0.108494E+11 | 1.24 | 8836.92 | 30-MAY-06:10 | 1.51 |
June | 0.112679E+11 | 1.30 | 8836.92 | 01-JUN-06:10 | 1.52 |
July | 0.117557E+11 | 1.30 | 8836.92 | 01-JUL-06:10 | 1.51 |
August | 0.124103E+11 | 1.32 | 8836.92 | 01-AUG-06:10 | 1.51 |
September | 0.110642E+11 | 1.29 | 8836.92 | 01-SEP-06:20 | 1.52 |
October | 0.102966E+11 | 1.22 | 8836.92 | 14-OCT-07:20 | 1.53 |
November | 0.894602E+10 | 0.89 | 8836.92 | 02-NOV-08:00 | 1.52 |
December | 0.883207E+10 | 0.62 | 8836.92 | 01-DEC-07:15 | 1.53 |
Annual Sum or Average | 0.121342E+12 | 1.00 | |||
Minimum of Months | 0.809679E+10 | 0.58 | 8836.92 | 1.51 | |
Maximum of Months | 0.124103E+11 | 1.32 | 8836.92 | 1.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.355296E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.372621E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.492828E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.553191E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.752745E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.874082E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.981409E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.108488E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.860835E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.703140E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.545500E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.426160E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.800269E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.355296E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.108488E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133291E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140179E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192098E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.234019E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.345531E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.402394E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.466476E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.498101E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.399355E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.314626E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.218907E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159633E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.350461E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133291E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.498101E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170813E+10 | 0.690933E+10 | 695504.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157657E+10 | 0.797614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185938E+10 | 0.111013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173603E+10 | 0.131894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185091E+10 | 0.186141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187818E+10 | 0.224926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187777E+10 | 0.257571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202470E+10 | 0.286988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182510E+10 | 0.227911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177513E+10 | 0.182205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166922E+10 | 0.136758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171887E+10 | 0.951918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215000E+11 | 0.198945E+12 | 695504.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157657E+10 | 0.690933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202470E+10 | 0.286988E+11 | 695504.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.876397E+10 | 0.156977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.809679E+10 | 0.201033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.964097E+10 | 0.316548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.941812E+10 | 0.445767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108494E+11 | 0.715999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112679E+11 | 0.877596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117557E+11 | 0.104156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124103E+11 | 0.111866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110642E+11 | 0.892675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102966E+11 | 0.671359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.894602E+10 | 0.427123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883207E+10 | 0.244533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121342E+12 | 0.710983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.809679E+10 | 0.156977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124103E+11 | 0.111866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170813E+10 | 0.00 | 0.00 | 0.00 | 0.184482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157657E+10 | 0.00 | 0.00 | 0.00 | 0.214964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185938E+10 | 0.00 | 0.00 | 0.00 | 0.306890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173603E+10 | 0.00 | 0.00 | 0.00 | 0.379588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185091E+10 | 0.00 | 0.00 | 0.00 | 0.567654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187818E+10 | 0.00 | 0.00 | 0.00 | 0.686264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187777E+10 | 0.00 | 0.00 | 0.00 | 0.793632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202470E+10 | 0.00 | 0.00 | 0.00 | 0.882412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182510E+10 | 0.00 | 0.00 | 0.00 | 0.678325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177513E+10 | 0.00 | 0.00 | 0.00 | 0.525628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166922E+10 | 0.00 | 0.00 | 0.00 | 0.378578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171887E+10 | 0.00 | 0.00 | 0.00 | 0.254274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215000E+11 | 0.00 | 0.00 | 0.00 | 0.585269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157657E+10 | 0.00 | 0.00 | 0.00 | 0.184482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202470E+10 | 0.00 | 0.00 | 0.00 | 0.882412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.876397E+10 | 0.00 | 0.00 | 0.00 | 0.456517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.809679E+10 | 0.00 | 0.00 | 0.00 | 0.592113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.964097E+10 | 0.00 | 0.00 | 0.00 | 0.956882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.941812E+10 | 0.00 | 0.00 | 0.00 | 0.139838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108494E+11 | 0.00 | 0.00 | 0.00 | 0.237037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112679E+11 | 0.00 | 0.00 | 0.00 | 0.289715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117557E+11 | 0.00 | 0.00 | 0.00 | 0.348919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124103E+11 | 0.00 | 0.00 | 0.00 | 0.373998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110642E+11 | 0.00 | 0.00 | 0.00 | 0.288713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.211660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.894602E+10 | 0.00 | 0.00 | 0.00 | 0.129447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883207E+10 | 0.00 | 0.00 | 0.00 | 0.713119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121342E+12 | 0.00 | 0.00 | 0.00 | 0.229119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.809679E+10 | 0.00 | 0.00 | 0.00 | 0.456517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124103E+11 | 0.00 | 0.00 | 0.00 | 0.373998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 97760587.58 | 0.171436E+09 | 0.00 | 4524018.16 | 0.00 | 3224644.45 | 0.341162E+09 | 0.00 | 0.16 |
February | 57409437.66 | 0.335705E+09 | 0.00 | 4060097.01 | 0.00 | 0.00 | 0.155720E+09 | 0.00 | 0.17 |
March | 22144830.29 | 0.675691E+09 | 0.00 | 4921531.98 | 0.00 | 0.00 | 0.132042E+09 | 0.00 | 0.18 |
April | 263738.91 | 0.126959E+10 | 0.00 | 5485295.05 | 0.00 | 0.00 | 59247657.58 | 0.00 | 0.17 |
May | 0.00 | 0.240939E+10 | 0.00 | 3913746.87 | 0.00 | 0.00 | 5436082.24 | 0.00 | 0.18 |
June | 0.00 | 0.361675E+10 | 0.00 | 1882527.01 | 0.00 | 0.00 | 1861568.02 | 0.00 | 0.19 |
July | 0.00 | 0.478895E+10 | 0.00 | 1220047.60 | 0.00 | 0.00 | 584713.95 | 0.00 | 0.18 |
August | 0.00 | 0.538721E+10 | 0.00 | 153218.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.393021E+10 | 0.00 | 2004422.23 | 0.00 | 0.00 | 1857037.38 | 0.00 | 0.18 |
October | 0.00 | 0.254170E+10 | 0.00 | 2072631.26 | 0.00 | 0.00 | 7359684.49 | 0.00 | 0.17 |
November | 0.00 | 0.150079E+10 | 0.00 | 4017969.56 | 0.00 | 0.00 | 14597681.77 | 0.00 | 0.16 |
December | 36393210.35 | 0.522927E+09 | 0.00 | 4665476.49 | 0.00 | 0.00 | 0.143015E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.213972E+09 | 0.271503E+11 | 0.00 | 38920981.26 | 0.00 | 3224644.45 | 0.862884E+09 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.171436E+09 | 0.00 | 153218.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 97760587.58 | 0.538721E+10 | 0.00 | 5485295.05 | 0.00 | 3224644.45 | 0.341162E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.847714E+09 | 0.113566E+09 | 0.00 | 10017765.12 | 0.00 | 0.00 | 0.148815E+10 | 0.00 | 0.16 |
February | 0.429736E+09 | 0.391286E+09 | 0.00 | 9575160.24 | 0.00 | 0.00 | 0.993519E+09 | 0.00 | 0.17 |
March | 0.230029E+09 | 0.112334E+10 | 0.00 | 11585632.12 | 0.00 | 0.00 | 0.861727E+09 | 0.00 | 0.18 |
April | 31091743.81 | 0.271105E+10 | 0.00 | 6603901.64 | 0.00 | 0.00 | 0.465509E+09 | 0.00 | 0.18 |
May | 237777.33 | 0.667593E+10 | 0.00 | 2057572.40 | 0.00 | 0.00 | 44747861.57 | 0.00 | 0.20 |
June | 0.00 | 0.107696E+11 | 0.00 | 364097.39 | 0.00 | 0.00 | 4322080.22 | 0.00 | 0.22 |
July | 0.00 | 0.152436E+11 | 0.00 | 377960.27 | 0.00 | 0.00 | 614057.99 | 0.00 | 0.22 |
August | 0.00 | 0.169437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.119765E+11 | 0.00 | 55712.88 | 332420.81 | 0.00 | 172003.95 | 0.00 | 0.21 |
October | 0.00 | 0.686170E+10 | 0.00 | 2470212.85 | 483785.96 | 0.00 | 52183816.51 | 0.00 | 0.19 |
November | 10604576.77 | 0.322036E+10 | 0.00 | 3334376.64 | 0.00 | 0.00 | 0.171411E+09 | 0.00 | 0.17 |
December | 0.309708E+09 | 0.782773E+09 | 0.00 | 10754503.53 | 0.00 | 0.00 | 0.970377E+09 | 0.00 | 0.17 |
Annual Sum or Average | 0.185912E+10 | 0.768134E+11 | 0.00 | 57196895.08 | 816206.77 | 0.00 | 0.505273E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.113566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.847714E+09 | 0.169437E+11 | 0.00 | 11585632.12 | 483785.96 | 0.00 | 0.148815E+10 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.515770E+12 | 0.295961E+11 | 0.00 | 0.921224E+10 | 0.350425E+11 |
February | 0.582770E+12 | 0.325066E+11 | 0.00 | 0.604889E+10 | 0.415934E+11 |
March | 0.757845E+12 | 0.258024E+11 | 0.00 | 0.332519E+10 | 0.614202E+11 |
April | 0.835828E+12 | 0.241809E+11 | 0.00 | -0.277148E+10 | 0.813777E+11 |
May | 0.930222E+12 | 0.295450E+11 | 0.00 | -0.128194E+11 | 0.125621E+12 |
June | 0.919565E+12 | 0.280542E+11 | 0.00 | -0.206655E+11 | 0.151918E+12 |
July | 0.926534E+12 | 0.102503E+11 | 0.00 | -0.281952E+11 | 0.178768E+12 |
August | 0.894995E+12 | 0.247698E+11 | 0.00 | -0.305841E+11 | 0.192815E+12 |
September | 0.772094E+12 | 0.314685E+11 | 0.00 | -0.226412E+11 | 0.153545E+12 |
October | 0.656484E+12 | 0.350787E+11 | 0.00 | -0.136694E+11 | 0.117805E+12 |
November | 0.510249E+12 | 0.300329E+11 | 0.00 | -0.393828E+10 | 0.789506E+11 |
December | 0.466041E+12 | 0.330386E+11 | 0.00 | 0.537802E+10 | 0.496728E+11 |
Annual Sum or Average | 0.876840E+13 | 0.334324E+12 | 0.00 | -0.111320E+12 | 0.126853E+13 |
Minimum of Months | 0.466041E+12 | 0.102503E+11 | 0.00 | -0.305841E+11 | 0.350425E+11 |
Maximum of Months | 0.930222E+12 | 0.350787E+11 | 0.00 | 0.921224E+10 | 0.192815E+12 |