Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 10:43:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 555.71 | 114.93 | 114.93 |
Net Site Energy | 555.71 | 114.93 | 114.93 |
Total Source Energy | 1753.35 | 362.63 | 362.63 |
Net Source Energy | 1753.35 | 362.63 | 362.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 78.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 155.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 63.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 552.55 | 3.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 78.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 155.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 92.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 20.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 78.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 155.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 92.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 63.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 34.21 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 114.28 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 34.21 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 114.28 | 0.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 552.548 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 552.548 | 100.00 |
Total On-Site and Utility Electric Sources | 552.548 | 100.00 |
Total Electricity End Uses | 552.548 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2918.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.9961 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.6188 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.9961 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 9.2031 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.6188 | 46.45 | 2.5587 | |
Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 6.8172 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 02-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 26217.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23808.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9384.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7833.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 483.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 51621.93 | 26217.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 26217.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23808.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9384.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5528.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 483.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 248.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 492.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 292.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 201.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1749.92 | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 101.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 361.92 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 101.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 361.92 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.39 |
ZONE2 FINE STORAGE DIRECT AIR | 3.74 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 36294.69 |
PSZ-OFFICE HEATING COIL | 31384.59 |
PSZ-FINE STORAGE HEATING COIL | 107403.19 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 34052.00 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.00 | 1.39 |
PSZ-FINE STORAGE | 3.74 | 3.74 | 3.74 | 3.74 | 3.74 | 3.74 | 1.00 | 1.00 | 3.74 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.39 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.74 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.39 | 1543.36 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.74 | 6387.44 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 0.920028 | 25179.98 | 31384.59 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.74 | 3.74 | 3.74 | 2.47 | 83535.85 | 107403.19 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.39 | 0.696991 | 0.929320 | 25179.98 | 12589.99 | 0.800930 | 0.800930 |
PSZ-FINE STORAGE COOLING COIL | 3.74 | 1.87 | 2.49 | 83535.85 | 41767.93 | 0.735360 | 0.735360 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 9.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.203 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.619 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.177 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2131.000 | 8.996 | 167.154 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2131.000 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 12823.730 | 9.203 | 427.458 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12823.730 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 18007.220 | 5.619 | 260.974 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 18007.220 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.504_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.504_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4201E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.5674E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2618E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9870E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2163E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1459E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5848E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1816E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5390E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.9584E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1386E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3957E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3339E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5440E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7680E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3855E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5111E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4210E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6213E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6169E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6814E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0021E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2141E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2648E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0415E-003 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4400E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4101E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5213E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5377E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2331E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0450E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8226E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0463E-003 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0668E-004 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0715E-003 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1038E-004 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3348E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8106E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2695E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9692E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8135E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1322E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3046E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3268E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5775E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8718E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9222E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6649E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9099E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.4519E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3181E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7214E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0814E-003 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9701E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8087E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6800E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4544E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1591E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9866E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2183E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1893E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0110E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0163E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6163E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7625E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5035E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9233E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6635E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3440E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0000E-004 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9862E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8713E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5112E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4393E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1025E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5337E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3510E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1588E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3846E-003 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6223E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6669E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9533E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9855E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2488E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9545E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5465E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2694E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3579E-004 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8517E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3126E-004 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6569E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7796E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0615E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0258E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8955E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0398E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5756E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0342E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0303E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1116E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6608E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0320E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3797E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6394E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0681E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4572E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8746E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8042E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6029E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5352E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0201E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6895E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7927E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5030E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3626E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3202E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5040E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7411E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2703E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2525E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8810E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3787E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4634E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7739E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3246E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6853E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4297E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6871E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6561E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6408E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0539E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9672E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2834E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9504E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5356E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3769E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9618E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0615E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8009E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0859E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4378E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0054E-004 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3461E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7372E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9357E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3089E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2085E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3953E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1928E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1028E-004 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1763E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7347E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6616E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3894E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4503E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9335E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6661E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1393E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7817E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3747E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5507E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3026E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5490E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5742E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6578E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5981E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5939E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2214E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7866E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0462E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1829E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1747E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2696E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2604E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5435E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0020E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0606E-004 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0639E-003 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0641E-004 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0146E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0622E-004 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2591E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2647E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9539E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5643E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0450E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4766E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8740E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6521E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0571E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9813E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7335E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2373E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9820E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1947E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6125E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3896E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8581E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9167E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2725E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8769E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3927E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1842E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3892E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6674E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8668E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7823E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5912E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7946E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5814E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6162E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0333E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0379E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9061E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3526E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1105E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8196E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0113E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3266E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6437E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2963E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9089E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6761E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7950E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4797E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5441E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6326E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1105E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9941E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6221E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7757E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2548E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7853E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1602E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4008E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5148E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4248E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2491E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5154E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1654E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4722E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8624E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1393E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8820E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8036E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3305E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8102E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0930E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8926E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1746E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6287E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9796E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0841E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5578E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8258E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2846E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7449E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7928E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9778E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6189E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9635E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2691E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6899E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0928E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4425E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6822E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9837E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1302E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0914E-004 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8883E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8115E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2779E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2771E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2457E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6972E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1285E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4109E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5770E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1770E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8886E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3924E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7331E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3668E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3360E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1618E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5156E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3855E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6308E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8861E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5920E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1977E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9179E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8403E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7819E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4848E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6558E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7122E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4401E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4481E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2927E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0752E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8452E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0922E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2504E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6374E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3754E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1822E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1842E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9355E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5118E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2664E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8833E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3453E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0665E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7241E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8491E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4067E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9355E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4517E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0461E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5303E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5709E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1823E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2883E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0021E-004 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3104E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0733E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2098E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5178E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9588E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7914E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8344E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5969E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3712E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7755E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0452E-004 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9739E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5918E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6196E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9406E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7165E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9915E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0529E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6474E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8551E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5566E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7052E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2837E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0941E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3530E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4294E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2086E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2207E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2799E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9785E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8806E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5520E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7856E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4428E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7938E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1762E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0183E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6699E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6620E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0500E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5140E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.9591E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1395E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4070E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0196E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2207E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2733E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7579E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5424E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3378E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2519E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1066E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2242E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3118E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7597E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.4344E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3359E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2518E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12819.48835 | 15383.38602 | 1.16165 | 1.39398 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 39.64733 | 5.62931E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7480.40546 | 8976.48655 | 0.23114 | 0.27737 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 44107.06807 | 52928.48168 | 3.11534 | 3.73841 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 17238.59319 | 20686.31183 | 0.44898 | 0.53878 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 28376.66334 | 34051.99600 | 0.76373 | 0.97684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20011.15 | 1.39398 | 1.39398 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8090.73 | 0.27737 | 0.27737 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 66918.91 | 3.73841 | 3.73841 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 21491.40 | 0.53878 | 0.53878 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39398 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.73841 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 36294.68777 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 34051.99600 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39398 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39398 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39398 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39398 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39398 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.39398 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.73841 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.73841 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.73841 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.73841 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.73841 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.73841 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.39398 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.73841 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39398 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39398 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1543.35974 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39398 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39398 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39398 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92003 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39398 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69699 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92932 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25179.98000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12589.99000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80093 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80093 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25179.98000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31384.58700 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31384.58700 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.73841 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.73841 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6387.43832 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.73841 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.73841 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.73841 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.46735 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.73841 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.86920 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.49227 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 83535.85000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41767.92500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73536 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73536 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 83535.85000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 107403.19405 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 107403.19405 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 24098.0 | 11.60 | 11.34 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 80631.5 | 10.96 | 10.71 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1023276149 | 0.1118884938 | Pass | Pass | 2.9174509975E-002 | 0.1752945858 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2436412535 | 0.2849189413 | Pass | Pass | 1.8974081830 | 15.9755434373 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.5516235828E-002 | 3.4576151046E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6372.92 | 354.74 | 0.00 | 12.62 | 344.32 | 7084.65 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.865 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.865 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.865 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.865 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.647 | 0.529 | 0.530 | |||||||||||||||||
North Total or Average | 6.51 | 2.865 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.793 | 0.552 | 0.553 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.9961 | 236.88 | 2131.00 | LightsWired | LTG_SCH_OFFICE | 51.55 | 168.00 | 47.20 | 0.0000 | Y | 18.88 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 9.2031 | 1393.41 | 12823.73 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 25.54 | 0.0000 | Y | 61.48 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.6188 | 3204.84 | 18007.22 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 22.19 | 0.0000 | Y | 75.01 |
Interior Lighting Total | 6.8172 | 4835.13 | 32961.95 | 155.37 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12823.73 | 3205.93 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 12823.73 | 3205.93 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18007.22 | 4501.81 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18007.22 | 4501.81 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2131.00 | 309.00 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 2131.00 | 106.55 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 94.73 | AstronomicalClock | - | 41.79 | 41.79 | 0.74 | |
EXTERIOR_LIGHTS_B | 6863.48 | AstronomicalClock | - | 83.79 | 71.19 | 91.71 | |
Exterior Lighting Total | 6958.21 | 92.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25179.98 | 20167.40 | 5012.58 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 83535.85 | 61428.92 | 22106.93 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 24098.0 | 11.60 | 11.34 | ||||
PSZ-FINE STORAGE COOLING COIL | 80631.5 | 10.96 | 10.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 36294.69 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31384.59 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 107403.19 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.39 | 1543.36 | 1107.16 | 1.00 | 1.33 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.74 | 6387.44 | 1708.60 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12819.49 | 15383.39 | 64.94 | 1.162 | 1.394 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 23.90 | 23.90 | 0.00807 | 39.65 | 0.00563 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 44107.07 | 52928.48 | 37.98 | 3.115 | 3.738 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00784 | 40.67 | 0.00563 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 39.58 | 0.00572 | 40.67 | 0.00563 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7480.41 | 8976.49 | 37.89 | 0.231 | 0.277 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00772 | 0.50 | 0.00432 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 17238.59 | 20686.31 | 14.85 | 0.449 | 0.539 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00654 | 0.50 | 0.00432 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 28376.66 | 34052.00 | 10.63 | 0.764 | 0.977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00561 | 0.50 | 0.00432 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.39 | 1.39 | 0.28 | 0.28 | 1.3940 | 1.3940 | 1.3940 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.74 | 3.74 | 0.54 | 0.54 | 3.7384 | 3.7384 | 3.7384 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 36294.688 | 36294.688 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 36294.69 | 36294.69 | 0.976836 | 10.00 | 6.98 | 0.00561002 | 43.33 | 21.00 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 10.00 | 0.00561002 | 66.9566 | 34052.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25179.980 | 20167.401 | 1.393980 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 12589.99 | 12589.99 | 0.929320 | 26.08 | 15.61 | 0.00789439 | 12.00 | 10.31 | 0.00789439 | 40.00 | 0.00562986 | 18.33 | 11.0064 | 23.90 | 0.00807392 | 39.7227 | 12805.40 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31384.587 | 31384.587 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 31384.59 | 31384.59 | 1.393982 | 19.50 | 12.87 | 0.00746731 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.3376 | 21.10 | 0.00771688 | 45.0353 | 7480.41 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 83535.850 | 61428.923 | 3.738410 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 41767.93 | 41767.93 | 2.492273 | 29.84 | 16.63 | 0.00759245 | 12.00 | 10.00 | 0.00759245 | 40.80 | 0.00563111 | 18.58 | 17.0411 | 26.70 | 0.00784397 | 32.6808 | 44085.20 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 107403.194 | 107403.194 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 107403.19 | 107403.19 | 3.738409 | 13.85 | 9.44 | 0.00628864 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 11.3608 | 15.56 | 0.00654153 | 54.1559 | 17238.59 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 36294.688 | 36294.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.06787139 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 36294.69 | 36294.69 | 1.0000 | 1.06787139 | 0.976836 | 10.00 | 6.98 | 0.00561002 | 24182.1 | 43.33 | 21.00 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36294.69 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 10.00 | 0.00561002 | 10.00 | 0.00561002 | 66.9566 | 34052.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25179.980 | 20167.401 | 1.393980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5153 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.393982 | 1.52389344 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | Sensible | 12589.99 | 12589.99 | 1.0000 | 1.01592725 | 0.929320 | 26.08 | 15.61 | 0.00789439 | 46328.1 | 12.00 | 10.31 | 0.00789439 | 31977.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12589.99 | 40.00 | 0.00562986 | 18.33 | 0.10228463 | 11.0064 | 23.90 | 0.00807392 | 23.90 | 0.00807392 | 39.7227 | 12805.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31384.587 | 31384.587 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.393982 | 1.52389344 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 31384.59 | 31384.59 | 1.0000 | 1.52389344 | 1.393982 | 19.50 | 12.87 | 0.00746731 | 38545.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31384.59 | 0.50 | 0.00431558 | 0.50 | 0.10228463 | 7.3376 | 21.01 | 0.00771688 | 21.10 | 0.00771688 | 45.0353 | 7480.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 83535.850 | 61428.923 | 3.738410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9540 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.738409 | 4.08680657 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 41767.93 | 41767.93 | 1.0000 | 2.72453879 | 2.492273 | 29.84 | 16.63 | 0.00759245 | 49390.9 | 12.00 | 10.00 | 0.00759245 | 31215.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41767.93 | 40.80 | 0.00563111 | 18.58 | 0.42471127 | 17.0411 | 26.70 | 0.00784397 | 26.70 | 0.00784397 | 32.6808 | 44085.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 107403.194 | 107403.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.738409 | 4.08680657 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 107403.19 | 107403.19 | 1.0000 | 4.08680657 | 3.738409 | 13.85 | 9.44 | 0.00628864 | 29803.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 107403.19 | 0.50 | 0.00431558 | 0.50 | 0.42471127 | 11.3608 | 15.56 | 0.00654153 | 15.56 | 0.00654153 | 54.1559 | 17238.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.39 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 3.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1915.17 | 1660.00 | 433.83 |
ZONE2 FINE STORAGE | 2675.00 | 2580.17 | 1767.33 |
ZONE3 BULK STORAGE | 3084.00 | 3393.33 | 2912.83 |
Facility | 3246.33 | 3478.67 | 2918.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.17 | 9.83 | 0.17 | 0.00 |
ZONE2 FINE STORAGE | 2.67 | 205.17 | 0.17 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.83 | 211.33 | 0.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.642 | 0.481 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.591 | 0.360 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.150 | 0.000 | 1.371 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.57 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2316080.19 | 0.00 | 2316080.19 | 2774240.53 | 5090320.72 | 3225648.14 | 5655.24 | 2313.01 | 791.75 | 0.41 |
ZONE2 FINE STORAGE | 6421784.56 | 0.00 | 6421784.56 | 9791994.30 | 16213778.86 | 13393694.68 | 5612.28 | 2748.03 | 399.69 | 37.38 |
ZONE3 BULK STORAGE | 0.00 | 0.33E+09 | 0.33E+09 | 38699785.83 | 0.37E+09 | 30805497.77 | 6174.55 | 9.32 | 2576.13 | 5116.00 |
Total Facility | 8737864.75 | 0.33E+09 | 0.34E+09 | 51266020.66 | 0.39E+09 | 47424840.58 | 7450.66 | 2944.63 | 3547.09 | 5116.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1769 | 0.0000 | 0.1769 | 0.1325 | 0.3094 | 0.1023 | 531.65 | 2313.01 | 791.34 |
ZONE2 FINE STORAGE | 0.4729 | 0.0000 | 0.4729 | 0.2883 | 0.7612 | 0.4247 | 525.66 | 2748.03 | 362.31 |
ZONE3 BULK STORAGE | 0.0000 | 12.7596 | 12.7596 | 1.4276 | 14.1872 | 0.9768 | 2291.82 | 5.94 | 1338.24 |
Total Facility | 0.6498 | 12.7596 | 13.4094 | 1.8483 | 15.2577 | 1.5038 | 2326.66 | 2941.25 | 2282.88 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2767868.20 | 0.00 | 2767868.20 | 3225648.14 | 5654.45 | 0.00 | 3105.55 | 0.41 |
PSZ-FINE STORAGE | 7674512.78 | 0.00 | 7674512.78 | 13393694.68 | 5610.22 | 0.03 | 3149.75 | 37.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2114 | 0.0000 | 0.2114 | 0.1023 | 530.86 | 0.00 | 3105.14 |
PSZ-FINE STORAGE | 0.5652 | 0.0000 | 0.5652 | 0.4247 | 523.60 | 0.03 | 3112.37 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2737.15 | 372.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3035.08 | 122.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2236 | 0.4217 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6376 | 1.1811 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
Electricity:Building | 315.31 | 1663.58 | 09-APR-15:10 | 25607.78 | 06-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 50.83 | 815.73 | 12-MAR-16:10 | 3198.43 | 28-NOV-16:30 |
Electricity:SpaceType:GENERAL | 294.66 | 1663.58 | 09-APR-15:10 | 25607.78 | 06-DEC-16:00 |
InteriorLights:Electricity | 155.37 | 1089.83 | 09-APR-15:10 | 15495.16 | 06-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.88 | 241.98 | 12-MAR-16:10 | 1285.93 | 28-NOV-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 155.37 | 1089.83 | 09-APR-15:10 | 15495.16 | 06-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 155.37 | 1089.83 | 09-APR-15:10 | 15495.16 | 06-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.88 | 241.98 | 12-MAR-16:10 | 1285.93 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 155.37 | 1089.83 | 09-APR-15:10 | 15495.16 | 06-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 61.48 | 352.65 | 08-JAN-11:20 | 5995.09 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 61.48 | 352.65 | 08-JAN-11:20 | 5995.09 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 61.48 | 352.65 | 08-JAN-11:20 | 5995.09 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 203.00 | 495.20 | 01-JAN-10:10 | 16819.20 | 14-OCT-14:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 75.01 | 495.20 | 01-JAN-10:10 | 8418.38 | 04-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 75.01 | 495.20 | 01-JAN-10:10 | 8418.38 | 04-DEC-16:00 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 63.53 | 0.00 | 01-JAN-00:10 | 8216.50 | 30-JUN-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 20.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-APR-12:10 |
Ventilation (simple):Fans:Electricity | 20.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-APR-12:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 20.65 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-APR-12:10 |
ElectricityPurchased:Facility | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
ElectricityNet:Plant | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
General:Cogeneration:ElectricityNet | 552.55 | 2146.58 | 09-APR-15:10 | 51621.93 | 29-JUN-16:00 |
Electricity:HVAC | 121.34 | 0.00 | 01-JAN-00:10 | 30989.23 | 30-JUN-16:10 |
General:Fans:Electricity | 42.88 | 0.00 | 01-JAN-00:10 | 5911.21 | 30-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 78.46 | 0.00 | 01-JAN-00:10 | 25078.03 | 30-JUN-16:10 |
General:Cooling:Electricity | 78.46 | 0.00 | 01-JAN-00:10 | 25078.03 | 30-JUN-16:10 |
ExteriorLights:Electricity | 92.46 | 0.00 | 01-JAN-07:30 | 6958.21 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 92.46 | 0.00 | 01-JAN-07:30 | 6958.21 | 01-JAN-06:10 |
Electricity:Plant | 23.44 | 483.00 | 15-APR-18:40 | 1789.33 | 26-JAN-12:40 |
WaterSystems:Electricity | 23.44 | 483.00 | 15-APR-18:40 | 1789.33 | 26-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 23.44 | 483.00 | 15-APR-18:40 | 1789.33 | 26-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3.16 | 0.00 | 01-JAN-00:10 | 26217.24 | 02-JAN-07:10 |
NaturalGas:HVAC | 3.16 | 0.00 | 01-JAN-00:10 | 26217.24 | 02-JAN-07:10 |
Heating:NaturalGas | 3.16 | 0.00 | 01-JAN-00:10 | 26217.24 | 02-JAN-07:10 |
General:Heating:NaturalGas | 3.16 | 0.00 | 01-JAN-00:10 | 26217.24 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 484.33 | 0.00 | 01-JAN-00:10 | 131775.98 | 30-JUN-16:10 |
EnergyTransfer:Building | 217.37 | 0.00 | 01-JAN-00:10 | 58658.05 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 63.70 | 0.00 | 01-JAN-00:10 | 16951.10 | 30-JUN-16:10 |
Heating:EnergyTransfer | 7.75 | 0.00 | 01-JAN-00:10 | 21759.78 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.01 | 0.00 | 01-JAN-00:10 | 13262.44 | 07-DEC-07:10 |
General:Heating:EnergyTransfer | 7.75 | 0.00 | 01-JAN-00:10 | 21759.78 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.01 | 0.00 | 01-JAN-00:10 | 13262.44 | 07-DEC-07:10 |
Cooling:EnergyTransfer | 209.62 | 0.00 | 01-JAN-00:10 | 58658.05 | 30-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 61.69 | 0.00 | 01-JAN-00:10 | 16951.10 | 30-JUN-16:10 |
General:Cooling:EnergyTransfer | 209.62 | 0.00 | 01-JAN-00:10 | 58658.05 | 30-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 61.69 | 0.00 | 01-JAN-00:10 | 16951.10 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 153.67 | 0.00 | 01-JAN-00:10 | 43366.67 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 5.74 | 0.00 | 01-JAN-00:10 | 17339.69 | 01-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 5.74 | 0.00 | 01-JAN-00:10 | 17339.69 | 01-JAN-07:40 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 147.93 | 0.00 | 01-JAN-00:10 | 43366.67 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 147.93 | 0.00 | 01-JAN-00:10 | 43366.67 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 266.95 | 0.00 | 01-JAN-00:10 | 73117.93 | 30-JUN-16:10 |
HeatingCoils:EnergyTransfer | 2.13 | 0.00 | 01-JAN-00:10 | 18757.85 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 264.83 | 0.00 | 01-JAN-00:10 | 73117.93 | 30-JUN-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.013 | -61.690 | 0.000 | 0.000 | 9.292 | 18.880 | 31.946 | 13.061 | 0.000 | 8.210 | 0.000 | 0.000 | -6.053 | 0.000 | -12.276 | -3.382 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 5.739 | -147.924 | 0.000 | 0.000 | 19.943 | 61.480 | 0.000 | 81.005 | 0.000 | 21.760 | 14.160 | 0.000 | -16.040 | 0.000 | -40.123 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.130 | 75.013 | 107.344 | 818.165 | 0.000 | 134.491 | 0.012 | 0.000 | -149.799 | 0.000 | -416.062 | -606.281 |
Total Facility | 0.000 | 0.000 | 7.752 | -209.614 | 0.000 | 0.000 | 66.364 | 155.373 | 139.290 | 912.231 | 0.000 | 164.461 | 14.172 | 0.000 | -171.892 | 0.000 | -468.460 | -609.664 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 21-OCT-07:02 | 0.00 | 0.00 | 0.00 | -29442.39 | 0.00 | 0.00 | 801.53 | 1254.87 | 1912.50 | 0.00 | 0.00 | 0.00 | 26471.45 | 0.00 | -327.33 | 0.00 | -670.63 | 0.00 |
ZONE2 FINE STORAGE | 24-SEP-13:32 | 0.00 | 0.00 | 0.00 | -70373.62 | 0.00 | 0.00 | 0.00 | 352.65 | 0.00 | 8313.23 | 0.00 | 3078.87 | 58628.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-AUG-15:52 | 0.00 | 0.00 | 0.00 | -80512.52 | 0.00 | 0.00 | 0.00 | 1351.84 | 573.75 | 89468.50 | 0.00 | 57152.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -68034.16 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-DEC-07:01 | 0.00 | 0.00 | 31434.97 | 0.00 | 0.00 | 0.00 | 267.00 | 701.42 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -587.55 | 0.00 | -5342.59 | -27429.50 |
ZONE2 FINE STORAGE | 01-JAN-07:33 | 0.00 | 0.00 | 52019.20 | 0.00 | 0.00 | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1380.53 | 0.00 | -5712.19 | -45631.79 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-07:02 | 0.00 | 0.00 | 62111.67 | 0.00 | 0.00 | 0.00 | 2595.22 | 10875.63 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14212.68 | 0.00 | -16777.21 | -47598.91 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3940 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3940 | 0.0734 | 1.0000 | Not calculated | 0.1023 | 0.0734 | ||
PSZ-FINE STORAGE | 3.7384 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.7384 | 0.1136 | 1.0000 | Not calculated | 0.4247 | 0.1136 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3940 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.3940 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0734 | ||
PSZ-FINE STORAGE | 3.7384 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.7384 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1136 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3940 | 1.3940 | 1.3940 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7384 | 3.7384 | 3.7384 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3940 | 1.3940 | 1.3940 | 1.3940 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.7384 | 3.7384 | 3.7384 | 3.7384 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3940 | 1.3940 | 1.3940 | No | 0.1023 | 0.3688 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7384 | 3.7384 | 3.7384 | No | 0.4247 | 0.7883 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3940 | 1.3940 | 1.3940 | 1.3940 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.7384 | 3.7384 | 3.7384 | 3.7384 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 3.16 | 26217.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 78.46 | 25078.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 155.37 | 15495.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 92.46 | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 20.65 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 42.88 | 5911.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.44 | 1789.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 552.55 |
Natural Gas | 0.00 | 3.16 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 555.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 32.13 |
Space Heating | 0.00 |
Space Cooling | 16.23 |
Fans (All) | 13.14 |
Service Water Heating | 4.85 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 114.28 |
Subtotal | 114.28 |
Natural Gas [MJ/m2] | |
Space Heating | 0.65 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.65 |
Subtotal | 0.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 27.96 |
Space Heating | 0.57 |
Space Cooling | 14.12 |
Fans (All) | 11.43 |
Service Water Heating | 4.22 |
Receptacle Equipment | 25.07 |
Miscellaneous | 16.64 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2688. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 6909.67 | 1850.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7813.83 | 946.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 4605.50 | 3454.17 | 700.00 | 0.33 | 0.00 |
Min | 4605.50 | 946.17 | 0.00 | 0.00 | 0.00 |
Max | 7813.83 | 3454.17 | 700.00 | 0.33 | 0.00 |
Average | 6443.00 | 2083.56 | 233.33 | 0.11 | 0.00 |
Sum | 19329.00 | 6250.67 | 700.00 | 0.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32965.83 | 61.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 72253.00 | 10466.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 94573.83 | 69818.17 | 26785.83 | 15.17 | 0.00 |
Min | 32965.83 | 61.17 | 0.00 | 0.00 | 0.00 |
Max | 94573.83 | 69818.17 | 26785.83 | 15.17 | 0.00 |
Average | 66597.56 | 26781.78 | 8928.61 | 5.06 | 0.00 |
Sum | 199792.67 | 80345.33 | 26785.83 | 15.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7591.67 | 1168.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7636.83 | 1123.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6030.83 | 2709.33 | 19.83 | 0.00 | 0.00 |
Min | 6030.83 | 1123.17 | 0.00 | 0.00 | 0.00 |
Max | 7636.83 | 2709.33 | 19.83 | 0.00 | 0.00 |
Average | 7086.44 | 1666.94 | 6.61 | 0.00 | 0.00 |
Sum | 21259.33 | 5000.83 | 19.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32784.50 | 242.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70202.50 | 12516.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 122141.17 | 68018.17 | 1033.67 | 0.00 | 0.00 |
Min | 32784.50 | 242.50 | 0.00 | 0.00 | 0.00 |
Max | 122141.17 | 68018.17 | 1033.67 | 0.00 | 0.00 |
Average | 75042.72 | 26925.72 | 344.56 | 0.00 | 0.00 |
Sum | 225128.17 | 80777.17 | 1033.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:57
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128853E+10 | 4891.50 | 31-JAN-16:40 | 29.00 | 10.73 | 0.598865E+09 | 768.96 | 06-JAN-13:09 | 29.00 | 10.73 |
February | 0.460277E+09 | 2870.65 | 01-FEB-16:00 | 16.00 | 7.03 | 0.527207E+09 | 768.98 | 18-FEB-14:30 | 22.00 | 14.16 |
March | 0.149454E+10 | 5496.44 | 18-MAR-16:00 | 27.20 | 11.10 | 0.649979E+09 | 768.99 | 18-MAR-10:09 | 27.20 | 11.10 |
April | 0.561164E+10 | 24947.71 | 29-APR-07:02 | 20.67 | 7.94 | 0.635797E+09 | 879.39 | 29-APR-07:10 | 20.67 | 7.94 |
May | 0.750167E+10 | 27124.70 | 13-MAY-07:02 | 18.50 | 10.28 | 0.665319E+09 | 879.39 | 13-MAY-07:10 | 18.50 | 10.28 |
June | 0.992622E+10 | 26325.63 | 12-JUN-06:02 | 21.53 | 11.06 | 0.666832E+09 | 879.40 | 30-JUN-07:10 | 29.33 | 19.12 |
July | 0.939640E+10 | 29220.26 | 01-JUL-06:01 | 18.83 | 6.96 | 0.641356E+09 | 879.44 | 10-JUL-07:10 | 27.50 | 18.00 |
August | 0.966315E+10 | 26686.82 | 23-AUG-06:02 | 22.00 | 12.48 | 0.692690E+09 | 879.44 | 28-AUG-07:10 | 29.17 | 20.16 |
September | 0.827912E+10 | 26638.54 | 30-SEP-06:02 | 20.45 | 12.06 | 0.640966E+09 | 879.39 | 20-SEP-07:10 | 20.45 | 12.06 |
October | 0.512247E+10 | 29441.84 | 21-OCT-07:02 | 15.67 | 8.64 | 0.632999E+09 | 879.39 | 03-OCT-07:10 | 15.67 | 8.64 |
November | 0.227358E+10 | 7189.37 | 01-NOV-16:00 | 28.00 | 15.72 | 0.594801E+09 | 792.34 | 01-NOV-07:10 | 28.00 | 15.72 |
December | 0.674074E+09 | 3518.57 | 22-DEC-16:30 | 24.50 | 9.81 | 0.574896E+09 | 768.96 | 21-DEC-13:09 | 24.50 | 9.81 |
Annual Sum or Average | 0.616917E+11 | 0.752171E+10 | ||||||||
Minimum of Months | 0.460277E+09 | 2870.65 | 15.67 | 6.96 | 0.527207E+09 | 768.96 | 15.67 | 7.94 | ||
Maximum of Months | 0.992622E+10 | 29441.84 | 29.00 | 15.72 | 0.692690E+09 | 879.44 | 29.33 | 20.16 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218400E+09 | 2741.98 | 12-JAN-08:63 | 6.67 | 5.50 | 0.133729E+10 | 2240.07 | 31-JAN-16:00 | 29.00 | 10.73 |
February | 0.451791E+09 | 3602.98 | 01-FEB-08:63 | 5.67 | 3.96 | 0.107146E+10 | 1873.63 | 01-FEB-16:10 | 15.83 | 6.96 |
March | 0.366336E+09 | 3720.93 | 18-MAR-15:30 | 27.20 | 11.82 | 0.147303E+10 | 2246.80 | 23-MAR-13:50 | 25.42 | 11.73 |
April | 0.951144E+10 | 64278.34 | 14-APR-17:42 | 34.17 | 14.14 | 0.180506E+10 | 2296.36 | 01-APR-14:30 | 34.17 | 14.14 |
May | 0.179595E+11 | 65827.05 | 21-MAY-17:12 | 31.67 | 13.28 | 0.192313E+10 | 2246.80 | 20-MAY-07:10 | 31.67 | 13.28 |
June | 0.322393E+11 | 68495.15 | 17-JUN-19:42 | 34.50 | 18.60 | 0.192851E+10 | 2247.14 | 29-JUN-15:00 | 41.00 | 18.42 |
July | 0.304414E+11 | 69337.75 | 30-JUL-11:02 | 34.33 | 19.08 | 0.185427E+10 | 2247.12 | 22-JUL-15:50 | 34.33 | 19.08 |
August | 0.273485E+11 | 69613.70 | 21-AUG-17:42 | 33.18 | 17.49 | 0.200268E+10 | 2247.07 | 15-AUG-15:50 | 33.18 | 17.49 |
September | 0.206299E+11 | 70373.53 | 24-SEP-13:32 | 33.10 | 18.95 | 0.185325E+10 | 2246.97 | 05-SEP-12:39 | 33.10 | 18.95 |
October | 0.765882E+10 | 64173.47 | 04-OCT-17:05 | 33.83 | 17.44 | 0.174105E+10 | 2246.95 | 03-OCT-12:09 | 33.83 | 17.44 |
November | 0.649662E+09 | 7478.05 | 01-NOV-15:20 | 28.67 | 16.04 | 0.147013E+10 | 2246.87 | 01-NOV-15:09 | 28.67 | 16.04 |
December | 0.454914E+09 | 4403.04 | 05-DEC-08:63 | 2.83 | -2.3 | 0.116290E+10 | 1984.54 | 01-DEC-15:39 | 2.83 | -2.3 |
Annual Sum or Average | 0.147930E+12 | 0.196228E+11 | ||||||||
Minimum of Months | 0.218400E+09 | 2741.98 | 2.83 | -2.3 | 0.107146E+10 | 1873.63 | 2.83 | -2.3 | ||
Maximum of Months | 0.322393E+11 | 70373.53 | 34.50 | 19.08 | 0.200268E+10 | 2296.36 | 41.00 | 19.08 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 | 1.81 | 0.235626E+10 | 3943.33 | 31-JAN-15:00 | 29.00 | 10.73 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.208564E+10 | 3501.61 | 01-FEB-15:20 | 15.33 | 6.93 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.285429E+10 | 4462.54 | 23-MAR-14:50 | 25.08 | 11.24 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.463399E+10 | 8171.85 | 14-APR-15:00 | 35.00 | 14.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.592188E+10 | 8946.09 | 31-MAY-15:00 | 37.00 | 13.71 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 | 11.09 | 0.689571E+10 | 9097.65 | 01-JUN-13:30 | 37.00 | 17.19 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.641573E+10 | 9097.65 | 01-JUL-12:50 | 36.67 | 13.99 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.689131E+10 | 9097.65 | 01-AUG-15:39 | 36.67 | 20.72 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 | 16.66 | 0.596818E+10 | 9097.65 | 01-SEP-14:30 | 36.90 | 21.80 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 | 0.465978E+10 | 8492.95 | 06-OCT-15:39 | 35.00 | 14.89 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.299070E+10 | 5101.35 | 01-NOV-15:50 | 28.17 | 15.80 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.219744E+10 | 3595.24 | 01-DEC-15:39 | 23.20 | 10.01 |
Annual Sum or Average | 0.00 | 0.538709E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.208564E+10 | 3501.61 | 15.33 | 6.93 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.689571E+10 | 9097.65 | 37.00 | 21.80 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401539E+09 | 31189.21 | 04-JAN-07:01 | 7.17 |
February | 0.371296E+09 | 31183.28 | 09-FEB-07:01 | 6.17 |
March | 0.346488E+09 | 31279.33 | 27-MAR-06:01 | 1.97 |
April | 54026113.51 | 1297.23 | 15-APR-06:04 | 20.33 |
May | 28673390.65 | 1439.62 | 08-MAY-06:04 | 20.50 |
June | 12381779.30 | 1393.67 | 07-JUN-06:04 | 22.50 |
July | 6423421.42 | 1241.47 | 27-JUL-06:04 | 22.17 |
August | 10814682.32 | 1338.59 | 25-AUG-06:03 | 21.67 |
September | 17818839.02 | 1392.11 | 21-SEP-06:04 | 20.18 |
October | 55111354.75 | 10156.71 | 25-OCT-07:03 | 5.50 |
November | 0.125632E+09 | 13118.22 | 24-NOV-07:03 | 4.50 |
December | 0.582549E+09 | 31435.14 | 19-DEC-07:01 | 4.00 |
Annual Sum or Average | 0.201275E+10 | |||
Minimum of Months | 6423421.42 | 1241.47 | 1.97 | |
Maximum of Months | 0.582549E+09 | 31435.14 | 22.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181283E+10 | 52019.06 | 01-JAN-07:33 | 0.83 |
February | 0.470641E+09 | 2566.77 | 06-FEB-07:50 | 9.00 |
March | 0.107293E+10 | 3870.03 | 15-MAR-16:20 | 28.10 |
April | 0.280069E+09 | 4282.65 | 01-APR-12:50 | 30.83 |
May | 0.144563E+09 | 2350.38 | 08-MAY-06:02 | 20.50 |
June | 9994652.38 | 3062.19 | 09-JUN-06:03 | 25.50 |
July | 11758406.73 | 3132.66 | 10-JUL-06:02 | 25.33 |
August | 11925977.29 | 3099.98 | 14-AUG-06:03 | 26.33 |
September | 72018728.66 | 3072.40 | 25-SEP-06:03 | 23.30 |
October | 0.255068E+09 | 2982.42 | 02-OCT-06:03 | 25.00 |
November | 0.637656E+09 | 2752.61 | 10-NOV-14:00 | 27.00 |
December | 0.959799E+09 | 28772.43 | 07-DEC-07:02 | 1.33 |
Annual Sum or Average | 0.573926E+10 | |||
Minimum of Months | 9994652.38 | 2350.38 | 0.83 | |
Maximum of Months | 0.181283E+10 | 52019.06 | 30.83 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160039E+10 | 1275.79 | 20-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.145702E+10 | 1274.33 | 11-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.163846E+10 | 1268.04 | 21-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.153516E+10 | 1253.22 | 29-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.159011E+10 | 1230.15 | 26-MAY-08:30 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.157177E+10 | 1218.58 | 12-JUN-09:30 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.156712E+10 | 1234.12 | 27-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.164311E+10 | 1268.34 | 04-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.154253E+10 | 1259.54 | 29-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.159003E+10 | 1270.53 | 27-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.153713E+10 | 1285.93 | 28-NOV-16:30 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.160750E+10 | 1285.93 | 01-DEC-16:30 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.188803E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.145702E+10 | 1218.58 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.164311E+10 | 1285.93 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.580397E+10 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.492217E+10 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.521517E+10 | 5995.09 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.471678E+10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.478202E+10 | 5289.79 | 01-MAY-07:10 | 0.00 | 0.00 |
June | 0.491460E+10 | 5289.79 | 02-JUN-07:10 | 0.00 | 0.00 |
July | 0.472533E+10 | 5495.50 | 11-JUL-08:09 | 0.00 | 0.00 |
August | 0.511175E+10 | 5495.50 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.473064E+10 | 5495.50 | 05-SEP-08:09 | 0.00 | 0.00 |
October | 0.537882E+10 | 5995.09 | 05-OCT-08:09 | 0.00 | 0.00 |
November | 0.544427E+10 | 5995.09 | 02-NOV-08:09 | 0.00 | 0.00 |
December | 0.573417E+10 | 5995.09 | 01-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.614797E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.471678E+10 | 5289.79 | 0.00 | 0.00 | |
Maximum of Months | 0.580397E+10 | 5995.09 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.709379E+10 | 7427.98 | 02-JAN-08:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.604519E+10 | 7427.98 | 01-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.639059E+10 | 7427.98 | 13-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.579860E+10 | 6189.98 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.586053E+10 | 6189.98 | 01-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.577887E+10 | 6189.98 | 08-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.573017E+10 | 6189.98 | 01-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.616921E+10 | 6808.98 | 04-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.584797E+10 | 6189.98 | 05-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.655475E+10 | 7716.84 | 31-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.658570E+10 | 7716.84 | 28-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.715733E+10 | 8418.38 | 04-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.750127E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.573017E+10 | 6189.98 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.715733E+10 | 8418.38 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.160039E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23369050.65 | 0.160086E+10 |
February | 0.127628E+10 | 0.145702E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169404E+10 |
March | 0.149825E+10 | 0.163846E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65841158.76 | 0.182990E+10 |
April | 0.138726E+10 | 0.153516E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607778E+09 | 0.787947E+09 |
May | 0.144276E+10 | 0.159011E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109024E+10 | 0.521713E+09 |
June | 0.144276E+10 | 0.157177E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193686E+10 | 0.185596E+09 |
July | 0.138726E+10 | 0.156712E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155859E+10 | 0.178655E+09 |
August | 0.149825E+10 | 0.164311E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141816E+10 | 0.257969E+09 |
September | 0.138726E+10 | 0.154253E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102687E+10 | 0.422155E+09 |
October | 0.138726E+10 | 0.159003E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431766E+09 | 0.120667E+10 |
November | 0.133177E+10 | 0.153713E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46901547.10 | 0.168469E+10 |
December | 0.138726E+10 | 0.160750E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3592408.60 | 0.190581E+10 |
Annual Sum or Average | 0.168137E+11 | 0.188803E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820997E+10 | 0.122760E+11 |
Minimum of Months | 0.127628E+10 | 0.145702E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178655E+09 |
Maximum of Months | 0.149825E+10 | 0.164311E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193686E+10 | 0.190581E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.580397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41817400.13 | 0.517116E+10 |
February | 0.300332E+10 | 0.492217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451157E+10 |
March | 0.352563E+10 | 0.521517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55672736.97 | 0.599774E+10 |
April | 0.326447E+10 | 0.471678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125802E+10 | 0.306745E+10 |
May | 0.339505E+10 | 0.478202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278543E+10 | 0.197230E+10 |
June | 0.339505E+10 | 0.491460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589965E+10 | 0.619658E+09 |
July | 0.326447E+10 | 0.472533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497767E+10 | 0.573171E+09 |
August | 0.352563E+10 | 0.511175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340229E+10 | 0.927616E+09 |
September | 0.326447E+10 | 0.473064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248721E+10 | 0.156885E+10 |
October | 0.326447E+10 | 0.537882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794564E+09 | 0.462481E+10 |
November | 0.313390E+10 | 0.544427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34711081.02 | 0.594903E+10 |
December | 0.326447E+10 | 0.573417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22799110.62 | 0.513935E+10 |
Annual Sum or Average | 0.395654E+11 | 0.614797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217598E+11 | 0.401227E+11 |
Minimum of Months | 0.300332E+10 | 0.471678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573171E+09 |
Maximum of Months | 0.352563E+10 | 0.580397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589965E+10 | 0.599774E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.709379E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238892E+10 | 0.125066E+11 |
February | 0.690763E+10 | 0.604519E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42981019.75 | 0.141506E+11 |
March | 0.810895E+10 | 0.639059E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140884E+10 | 0.176377E+11 |
April | 0.750829E+10 | 0.579860E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241975E+10 | 0.129938E+11 |
May | 0.780862E+10 | 0.586053E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550342E+09 | 0.111256E+11 |
June | 0.780862E+10 | 0.577887E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167305E+10 | 0.486872E+10 |
July | 0.750829E+10 | 0.573017E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123102E+10 | 0.562253E+10 |
August | 0.810895E+10 | 0.616921E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939588E+09 | 0.741265E+10 |
September | 0.750829E+10 | 0.584797E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553450E+09 | 0.104872E+11 |
October | 0.750829E+10 | 0.655475E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349486E+09 | 0.214745E+11 |
November | 0.720796E+10 | 0.658570E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540161E+09 | 0.193612E+11 |
December | 0.750829E+10 | 0.715733E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643472E+09 | 0.155303E+11 |
Annual Sum or Average | 0.910005E+11 | 0.750127E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127411E+11 | 0.153171E+12 |
Minimum of Months | 0.690763E+10 | 0.573017E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42981019.75 | 0.486872E+10 |
Maximum of Months | 0.810895E+10 | 0.715733E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241975E+10 | 0.214745E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1275.79 | 20-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.40 | 31-JAN-17:10 | 6027.81 | 12-JAN-07:07 |
February | 1680.92 | 01-FEB-08:09 | 1274.33 | 11-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6382.46 | 01-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1268.04 | 21-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1905.26 | 16-MAR-16:10 | 7917.41 | 27-MAR-06:04 |
April | 1680.92 | 01-APR-07:10 | 1253.22 | 29-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4270.80 | 10-APR-16:10 | 5570.46 | 21-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1230.15 | 26-MAY-08:30 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5522.72 | 18-MAY-16:10 | 4466.50 | 01-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1218.58 | 12-JUN-09:30 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.48 | 30-JUN-16:10 | 2540.98 | 21-JUN-06:03 |
July | 1680.92 | 01-JUL-07:10 | 1234.12 | 27-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7499.70 | 20-JUL-17:00 | 1655.61 | 27-JUL-06:02 |
August | 1680.92 | 01-AUG-07:10 | 1268.34 | 04-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7290.60 | 25-AUG-17:00 | 2445.03 | 24-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1259.54 | 29-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6063.06 | 08-SEP-16:10 | 3461.20 | 22-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1270.53 | 27-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4624.40 | 04-OCT-17:00 | 6830.85 | 25-OCT-06:03 |
November | 1680.92 | 01-NOV-07:10 | 1285.93 | 28-NOV-16:30 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.28 | 01-NOV-16:10 | 6297.93 | 24-NOV-07:30 |
December | 1680.92 | 01-DEC-08:09 | 1285.93 | 01-DEC-16:30 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.16 | 21-DEC-15:00 | 7996.98 | 14-DEC-07:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1218.58 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1655.61 | |||||
Maximum of Months | 1680.92 | 1285.93 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.48 | 7996.98 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1219.98 | 16-JAN-12:00 | 7782.65 | 01-JAN-01:37 |
February | 3955.50 | 01-FEB-08:09 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9508.79 | 02-FEB-17:03 |
March | 3955.50 | 01-MAR-08:09 | 5995.09 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1752.18 | 15-MAR-15:10 | 8906.40 | 28-MAR-06:10 |
April | 3955.50 | 01-APR-07:10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6721.45 | 10-APR-16:00 | 7159.50 | 21-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 5289.79 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9306.01 | 10-MAY-16:00 | 4998.41 | 23-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 5289.79 | 02-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17953.20 | 30-JUN-16:00 | 3376.59 | 13-JUN-06:10 |
July | 3955.50 | 01-JUL-07:10 | 5495.50 | 11-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18136.19 | 22-JUL-16:00 | 4470.94 | 26-JUL-23:51 |
August | 3955.50 | 01-AUG-07:10 | 5495.50 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12616.18 | 12-AUG-16:00 | 9229.23 | 28-AUG-17:00 |
September | 3955.50 | 01-SEP-07:10 | 5495.50 | 05-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10606.40 | 01-SEP-16:00 | 5134.63 | 15-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 5995.09 | 05-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6816.64 | 10-OCT-15:10 | 9965.28 | 22-OCT-14:00 |
November | 3955.50 | 01-NOV-07:10 | 5995.09 | 02-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1361.39 | 19-NOV-15:00 | 9433.31 | 24-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 5995.09 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.67 | 25-DEC-16:00 | 8853.68 | 07-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 5289.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3376.59 | ||||
Maximum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18136.19 | 9965.28 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 7427.98 | 02-JAN-08:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23789.95 | 06-JAN-13:10 | 18583.40 | 11-JAN-08:10 |
February | 9097.65 | 01-FEB-08:09 | 7427.98 | 01-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.54 | 18-FEB-14:00 | 27536.59 | 02-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 7427.98 | 13-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17382.74 | 15-MAR-13:00 | 27908.40 | 27-MAR-07:10 |
April | 9097.65 | 01-APR-07:10 | 6189.98 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22291.61 | 01-APR-15:00 | 24365.71 | 26-APR-21:00 |
May | 9097.65 | 01-MAY-07:10 | 6189.98 | 01-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4883.69 | 20-MAY-14:00 | 21199.72 | 23-MAY-05:00 |
June | 9097.65 | 01-JUN-07:10 | 6189.98 | 08-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6734.41 | 02-JUN-15:00 | 14624.85 | 13-JUN-06:00 |
July | 9097.65 | 01-JUL-07:10 | 6189.98 | 01-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5592.93 | 17-JUL-15:00 | 27628.54 | 17-JUL-19:52 |
August | 9097.65 | 01-AUG-07:10 | 6808.98 | 04-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4747.93 | 25-AUG-16:00 | 35556.59 | 28-AUG-17:00 |
September | 9097.65 | 01-SEP-07:10 | 6189.98 | 05-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4188.35 | 17-SEP-11:43 | 22699.51 | 03-SEP-05:00 |
October | 9097.65 | 02-OCT-07:10 | 7716.84 | 31-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5150.86 | 14-OCT-13:40 | 45936.54 | 07-OCT-15:00 |
November | 9097.65 | 01-NOV-07:10 | 7716.84 | 28-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8495.83 | 19-NOV-15:00 | 38370.34 | 22-NOV-12:00 |
December | 9097.65 | 01-DEC-08:09 | 8418.38 | 04-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8892.24 | 21-DEC-14:00 | 27061.09 | 07-DEC-08:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 6189.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.54 | 14624.85 | |||||
Maximum of Months | 9097.65 | 8418.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23789.95 | 45936.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4891.50 | 31-JAN-16:40 | 1680.92 | 1047.51 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 478.61 | 0.00 |
February | 2870.65 | 01-FEB-16:00 | 1680.92 | 1058.40 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.06 |
March | 5496.44 | 18-MAR-16:00 | 1680.92 | 1092.88 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 116.85 | 0.00 |
April | 24947.71 | 29-APR-07:02 | 8404.61 | 6266.09 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.19 |
May | 27124.70 | 13-MAY-07:02 | 8404.61 | 6083.42 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.15 |
June | 26325.63 | 12-JUN-06:02 | 2117.96 | 4045.81 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.20 |
July | 29220.26 | 01-JUL-06:01 | 2470.96 | 4762.94 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.83 |
August | 26686.82 | 23-AUG-06:02 | 2117.96 | 4147.35 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.74 |
September | 26638.54 | 30-SEP-06:02 | 1764.97 | 3507.09 | 4781.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.21 |
October | 29441.84 | 21-OCT-07:02 | 8404.61 | 6274.37 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.63 |
November | 7189.37 | 01-NOV-16:00 | 1680.92 | 1056.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 672.09 | 0.00 |
December | 3518.57 | 22-DEC-16:30 | 1680.92 | 1057.50 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2870.65 | 1680.92 | 1047.51 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29441.84 | 8404.61 | 6274.37 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 672.09 | 1749.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2741.98 | 12-JAN-08:63 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5313.07 |
February | 3602.98 | 01-FEB-08:63 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7398.01 |
March | 3720.93 | 18-MAR-15:30 | 3955.50 | 4408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.29 | 0.00 |
April | 64278.34 | 14-APR-17:42 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4378.99 | 0.00 |
May | 65827.05 | 21-MAY-17:12 | 0.00 | 2351.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4056.07 | 0.00 |
June | 68495.15 | 17-JUN-19:42 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6192.04 | 0.00 |
July | 69337.75 | 30-JUL-11:02 | 0.00 | 1645.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.99 | 0.00 |
August | 69613.70 | 21-AUG-17:42 | 0.00 | 2821.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3103.00 | 0.00 |
September | 70373.53 | 24-SEP-13:32 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3078.87 | 0.00 |
October | 64173.47 | 04-OCT-17:05 | 0.00 | 4231.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5112.60 | 0.00 |
November | 7478.05 | 01-NOV-15:20 | 3955.50 | 4408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.74 | 0.00 |
December | 4403.04 | 05-DEC-08:63 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2741.98 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70373.53 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6192.04 | 7398.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 1980.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12886.65 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8508.02 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6316.58 |
April | 0.00 | 01-APR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4886.16 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8235.70 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 2971.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3110.53 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.79 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.27 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 1980.79 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2682.49 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4165.33 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4569.39 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8038.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.27 | |
Maximum of Months | 0.00 | 0.00 | 2971.19 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12886.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.408267E+11 | 29978.41 | 05-JAN-15:00 | 0.117363E+10 | 26217.24 | 02-JAN-07:10 |
February | 0.357032E+11 | 29212.03 | 03-FEB-09:09 | 0.482421E+09 | 12859.72 | 09-FEB-07:10 |
March | 0.394248E+11 | 29509.40 | 18-MAR-15:39 | 0.413440E+09 | 15857.54 | 27-MAR-06:10 |
April | 0.416905E+11 | 38206.67 | 14-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.482830E+11 | 41851.81 | 31-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.576407E+11 | 51621.93 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.568731E+11 | 49153.44 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.576163E+11 | 47665.99 | 25-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.509351E+11 | 43623.90 | 08-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.438223E+11 | 42322.27 | 06-OCT-15:20 | 8065280.88 | 4297.36 | 25-OCT-07:10 |
November | 0.389106E+11 | 32481.68 | 01-NOV-14:00 | 0.102927E+09 | 9007.69 | 24-NOV-07:10 |
December | 0.408219E+11 | 30624.94 | 01-DEC-15:00 | 0.982539E+09 | 23895.98 | 07-DEC-07:10 |
Annual Sum or Average | 0.552548E+12 | 0.316302E+10 | ||||
Minimum of Months | 0.357032E+11 | 29212.03 | 0.00 | 0.00 | ||
Maximum of Months | 0.576407E+11 | 51621.93 | 0.117363E+10 | 26217.24 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.144982E+11 | 0.927487E+10 | 0.115358E+11 | 0.00 | 0.317783E+10 | 0.00 | 0.00 | 0.246241E+09 | 0.00 | 0.00 | 0.00 | 0.209386E+10 | 0.00 |
February | 0.124244E+11 | 0.789058E+10 | 0.105871E+11 | 0.00 | 0.289895E+10 | 0.00 | 0.00 | 5167450.36 | 0.00 | 0.00 | 0.00 | 0.189702E+10 | 0.00 |
March | 0.132442E+11 | 0.800987E+10 | 0.123431E+11 | 0.00 | 0.340012E+10 | 0.00 | 0.00 | 0.326547E+09 | 0.00 | 0.00 | 0.00 | 0.210098E+10 | 0.00 |
April | 0.120505E+11 | 0.700848E+10 | 0.114862E+11 | 0.00 | 0.410074E+10 | 0.00 | 0.00 | 0.510012E+10 | 0.00 | 0.00 | 0.00 | 0.194439E+10 | 0.00 |
May | 0.122327E+11 | 0.660292E+10 | 0.119357E+11 | 0.00 | 0.645642E+10 | 0.00 | 0.00 | 0.910394E+10 | 0.00 | 0.00 | 0.00 | 0.195136E+10 | 0.00 |
June | 0.122652E+11 | 0.612340E+10 | 0.118862E+11 | 0.00 | 0.913054E+10 | 0.00 | 0.00 | 0.163810E+11 | 0.00 | 0.00 | 0.00 | 0.185440E+10 | 0.00 |
July | 0.120226E+11 | 0.642757E+10 | 0.115358E+11 | 0.00 | 0.894281E+10 | 0.00 | 0.00 | 0.160884E+11 | 0.00 | 0.00 | 0.00 | 0.185599E+10 | 0.00 |
August | 0.129241E+11 | 0.695361E+10 | 0.123357E+11 | 0.00 | 0.839303E+10 | 0.00 | 0.00 | 0.151081E+11 | 0.00 | 0.00 | 0.00 | 0.190174E+10 | 0.00 |
September | 0.121211E+11 | 0.742180E+10 | 0.114788E+11 | 0.00 | 0.666915E+10 | 0.00 | 0.00 | 0.113888E+11 | 0.00 | 0.00 | 0.00 | 0.185544E+10 | 0.00 |
October | 0.135236E+11 | 0.844406E+10 | 0.115432E+11 | 0.00 | 0.418374E+10 | 0.00 | 0.00 | 0.416880E+10 | 0.00 | 0.00 | 0.00 | 0.195892E+10 | 0.00 |
November | 0.135671E+11 | 0.882040E+10 | 0.110862E+11 | 0.00 | 0.301699E+10 | 0.00 | 0.00 | 0.469098E+09 | 0.00 | 0.00 | 0.00 | 0.195077E+10 | 0.00 |
December | 0.144990E+11 | 0.947944E+10 | 0.115358E+11 | 0.00 | 0.316309E+10 | 0.00 | 0.00 | 72523442.27 | 0.00 | 0.00 | 0.00 | 0.207208E+10 | 0.00 |
Annual Sum or Average | 0.155373E+12 | 0.924570E+11 | 0.139290E+12 | 0.00 | 0.635334E+11 | 0.00 | 0.00 | 0.784587E+11 | 0.00 | 0.00 | 0.00 | 0.234369E+11 | 0.00 |
Minimum of Months | 0.120226E+11 | 0.612340E+10 | 0.105871E+11 | 0.00 | 0.289895E+10 | 0.00 | 0.00 | 5167450.36 | 0.00 | 0.00 | 0.00 | 0.185440E+10 | 0.00 |
Maximum of Months | 0.144990E+11 | 0.947944E+10 | 0.123431E+11 | 0.00 | 0.913054E+10 | 0.00 | 0.00 | 0.163810E+11 | 0.00 | 0.00 | 0.00 | 0.210098E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.117363E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.482421E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.413440E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 8065280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.102927E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.982539E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.316302E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.117363E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 14274.95 | 20-JAN-09:09 | 6958.21 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3763.12 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 14268.72 | 03-FEB-09:09 | 6958.21 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3452.53 | 09-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 14257.05 | 14-MAR-08:30 | 6958.21 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3524.23 | 27-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 12833.47 | 01-APR-08:09 | 6958.21 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5735.30 | 14-APR-16:49 | 0.00 | 0.00 | 01-APR-00:10 |
May | 12702.42 | 06-MAY-07:10 | 6958.21 | 01-MAY-05:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 5952.49 | 31-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 12697.22 | 08-JUN-07:10 | 6958.21 | 01-JUN-05:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 8216.50 | 30-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 12713.89 | 27-JUL-07:10 | 6958.21 | 01-JUL-05:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7448.45 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 13367.11 | 04-AUG-07:10 | 6958.21 | 01-AUG-05:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7136.26 | 25-AUG-16:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 12739.31 | 29-SEP-07:10 | 6958.21 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6109.44 | 08-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 14966.11 | 31-OCT-08:09 | 6958.21 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 5764.86 | 06-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14789.82 | 28-NOV-15:00 | 6958.21 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3356.77 | 24-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 15495.16 | 06-DEC-15:00 | 6958.21 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3707.86 | 07-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 12697.22 | 6958.21 | 10112.62 | 0.00 | 3356.77 | 0.00 | 0.00 | |||||
Maximum of Months | 15495.16 | 6958.21 | 10112.62 | 0.00 | 8216.50 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1587.76 | 31-JAN-16:40 | 0.00 | 0.00 | 0.00 | 1789.33 | 26-JAN-12:39 | 0.00 |
February | 331.32 | 18-FEB-15:09 | 0.00 | 0.00 | 0.00 | 1788.96 | 02-FEB-12:20 | 0.00 |
March | 3544.00 | 18-MAR-15:39 | 0.00 | 0.00 | 0.00 | 1778.79 | 01-MAR-12:09 | 0.00 |
April | 12662.07 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 1758.09 | 01-APR-11:50 | 0.00 |
May | 15180.04 | 18-MAY-15:30 | 0.00 | 0.00 | 0.00 | 1733.41 | 01-MAY-11:50 | 0.00 |
June | 25078.03 | 30-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1710.17 | 01-JUN-11:30 | 0.00 |
July | 21707.83 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1695.92 | 01-JUL-11:50 | 0.00 |
August | 21354.43 | 25-AUG-16:40 | 0.00 | 0.00 | 0.00 | 1701.38 | 31-AUG-11:39 | 0.00 |
September | 17583.34 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1719.83 | 30-SEP-11:30 | 0.00 |
October | 13973.74 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1744.80 | 31-OCT-11:30 | 0.00 |
November | 5658.37 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 1768.51 | 30-NOV-12:30 | 0.00 |
December | 1027.13 | 22-DEC-16:30 | 0.00 | 0.00 | 0.00 | 1784.72 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 331.32 | 0.00 | 0.00 | 0.00 | 1695.92 | 0.00 | ||
Maximum of Months | 25078.03 | 0.00 | 0.00 | 0.00 | 1789.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 29978.41 | 05-JAN-15:00 | 14130.81 | 10112.62 | 0.00 | 0.00 | 3172.32 | 0.00 | 0.00 | 811.75 | 0.00 |
February | 29212.03 | 03-FEB-09:09 | 14268.72 | 10112.62 | 0.00 | 0.00 | 3172.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29509.40 | 18-MAR-15:39 | 11084.65 | 10112.62 | 0.00 | 0.00 | 3172.32 | 0.00 | 0.00 | 3544.00 | 0.00 |
April | 38206.67 | 14-APR-15:00 | 9347.43 | 10112.62 | 0.00 | 0.00 | 5601.55 | 0.00 | 0.00 | 12662.07 | 0.00 |
May | 41851.81 | 31-MAY-15:00 | 9346.37 | 10112.62 | 0.00 | 0.00 | 5768.47 | 0.00 | 0.00 | 15043.13 | 0.00 |
June | 51621.93 | 29-JUN-15:00 | 9384.36 | 10112.62 | 0.00 | 0.00 | 7833.80 | 0.00 | 0.00 | 23808.14 | 0.00 |
July | 49153.44 | 22-JUL-15:00 | 9401.54 | 10112.62 | 0.00 | 0.00 | 7448.45 | 0.00 | 0.00 | 21707.83 | 0.00 |
August | 47665.99 | 25-AUG-15:00 | 9350.69 | 10112.62 | 0.00 | 0.00 | 6970.15 | 0.00 | 0.00 | 20749.52 | 0.00 |
September | 43623.90 | 08-SEP-15:00 | 9335.50 | 10112.62 | 0.00 | 0.00 | 6109.44 | 0.00 | 0.00 | 17583.34 | 0.00 |
October | 42322.27 | 06-OCT-15:20 | 11088.76 | 10112.62 | 0.00 | 0.00 | 5667.54 | 0.00 | 0.00 | 13868.71 | 0.00 |
November | 32481.68 | 01-NOV-14:00 | 12416.82 | 10112.62 | 0.00 | 0.00 | 3172.32 | 0.00 | 0.00 | 5546.07 | 0.00 |
December | 30624.94 | 01-DEC-15:00 | 14784.18 | 10112.62 | 0.00 | 0.00 | 3172.32 | 0.00 | 0.00 | 819.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29212.03 | 9335.50 | 10112.62 | 0.00 | 0.00 | 3172.32 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51621.93 | 14784.18 | 10112.62 | 0.00 | 0.00 | 7833.80 | 0.00 | 0.00 | 23808.14 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 26217.24 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 12859.72 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 15857.54 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 4297.36 | 25-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 9007.69 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 23895.98 | 07-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 26217.24 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.16 | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30.04 | 0.00 | 30.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 30.02 | 0.00 | 30.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 30.04 | 0.00 | 30.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 30.06 | 0.00 | 30.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.16 | 0.17 | 17.16 | 9.83 | 29.62 | 0.00 | 29.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.16 | 0.17 | 17.16 | 3.50 | 30.06 | 0.00 | 30.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.48 | 0.00 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.58 | 0.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 27.78 | 0.00 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 27.70 | 0.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 27.67 | 0.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.56 | 0.00 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.44 | 0.00 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 14.99 | 0.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 2.67 | 14.87 | 0.17 | 14.88 | 205.17 | 27.49 | 0.00 | 27.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 14.99 | 0.17 | 14.99 | 53.00 | 27.78 | 0.00 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.80 | 68.67 | 22.35 | 68.67 | 22.03 |
February | 276.00 | 22.24 | 64.67 | 21.83 | 64.67 | 21.55 |
March | 304.33 | 22.82 | 52.17 | 22.42 | 52.17 | 22.12 |
April | 68.33 | 23.74 | 72.50 | 23.94 | 1.33 | 23.91 |
May | 0.17 | 23.90 | 148.00 | 24.44 | 0.00 | 24.44 |
June | 4.33 | 27.96 | 300.50 | 24.41 | 4.33 | 24.46 |
July | 28.67 | 26.73 | 295.00 | 24.57 | 28.67 | 24.74 |
August | 33.00 | 26.84 | 321.67 | 24.59 | 33.00 | 24.78 |
September | 22.17 | 26.75 | 300.00 | 24.49 | 22.17 | 24.63 |
October | 100.33 | 23.58 | 119.33 | 23.92 | 5.67 | 23.97 |
November | 222.67 | 23.20 | 56.00 | 23.09 | 36.50 | 22.96 |
December | 300.00 | 22.27 | 116.67 | 21.78 | 116.67 | 21.51 |
Annual Sum or Average | 1660.00 | 22.97 | 1915.17 | 23.33 | 433.83 | 23.17 |
Minimum of Months | 0.17 | 22.24 | 52.17 | 21.78 | 0.00 | 21.51 |
Maximum of Months | 304.33 | 27.96 | 321.67 | 24.59 | 116.67 | 24.78 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.67 | 21.68 | 110.00 | 20.99 | 107.67 | 20.58 |
February | 276.00 | 20.63 | 131.50 | 20.12 | 131.50 | 19.86 |
March | 267.17 | 21.56 | 122.17 | 21.55 | 79.33 | 21.10 |
April | 64.50 | 24.98 | 239.83 | 26.22 | 32.50 | 26.21 |
May | 76.67 | 26.67 | 296.00 | 26.64 | 75.67 | 26.65 |
June | 212.50 | 26.70 | 312.00 | 26.70 | 212.50 | 26.70 |
July | 268.83 | 26.71 | 300.00 | 26.70 | 268.83 | 26.70 |
August | 291.00 | 26.71 | 324.00 | 26.70 | 291.00 | 26.70 |
September | 250.00 | 26.70 | 300.00 | 26.69 | 250.00 | 26.69 |
October | 126.50 | 24.82 | 212.00 | 25.83 | 69.17 | 25.92 |
November | 175.33 | 22.44 | 136.00 | 23.14 | 57.67 | 22.82 |
December | 300.00 | 20.50 | 191.50 | 19.96 | 191.50 | 19.72 |
Annual Sum or Average | 2580.17 | 23.85 | 2675.00 | 24.46 | 1767.33 | 24.42 |
Minimum of Months | 64.50 | 20.50 | 110.00 | 19.96 | 32.50 | 19.72 |
Maximum of Months | 300.00 | 26.71 | 324.00 | 26.70 | 291.00 | 26.70 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 19.30 | 244.17 | 19.02 | 244.17 | 18.91 |
February | 276.00 | 19.06 | 257.83 | 18.99 | 257.83 | 18.97 |
March | 324.00 | 20.58 | 185.83 | 20.12 | 185.83 | 19.91 |
April | 199.67 | 28.08 | 239.50 | 28.25 | 159.00 | 28.52 |
May | 304.00 | 30.80 | 312.00 | 30.76 | 304.00 | 30.77 |
June | 312.00 | 33.60 | 312.00 | 33.60 | 312.00 | 33.60 |
July | 300.00 | 32.79 | 300.00 | 32.79 | 300.00 | 32.79 |
August | 324.00 | 32.64 | 324.00 | 32.64 | 324.00 | 32.64 |
September | 300.00 | 31.44 | 300.00 | 31.44 | 300.00 | 31.44 |
October | 195.33 | 28.51 | 219.00 | 28.73 | 151.50 | 29.10 |
November | 258.33 | 22.12 | 99.67 | 21.91 | 84.50 | 21.65 |
December | 300.00 | 18.68 | 290.00 | 18.62 | 290.00 | 18.61 |
Annual Sum or Average | 3393.33 | 26.49 | 3084.00 | 26.78 | 2912.83 | 26.89 |
Minimum of Months | 195.33 | 18.68 | 99.67 | 18.62 | 84.50 | 18.61 |
Maximum of Months | 324.00 | 33.60 | 324.00 | 33.60 | 324.00 | 33.60 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.987994E+09 | 0.246241E+09 | 109.00 | 0.987994E+09 | 0.00 | 0.00 | 0.59 | 31-JAN-16:40 | 0.00 | 01-JAN-00:05 | 6081.47 | 31-JAN-16:40 | 6081.47 | 31-JAN-16:40 | 0.00 | 26-JAN-15:00 | 1587.76 | 31-JAN-16:40 | 0.00 | 01-JAN-00:05 |
February | 20390666.55 | 5167450.36 | 8.75 | 19265380.29 | 1125286.26 | 0.00 | 0.13 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 1312.75 | 18-FEB-15:10 | 1255.63 | 22-FEB-16:00 | 133.26 | 18-FEB-14:20 | 331.32 | 18-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.112342E+10 | 0.282132E+09 | 103.25 | 0.111845E+10 | 4971226.95 | 0.00 | 0.60 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 | 6481.60 | 18-MAR-16:00 | 6481.60 | 18-MAR-16:00 | 303.75 | 18-MAR-10:00 | 1654.10 | 16-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.610028E+10 | 0.155909E+10 | 240.64 | 0.610024E+10 | 36395.22 | 0.00 | 1.00 | 05-APR-16:10 | 0.00 | 01-APR-00:10 | 24060.84 | 25-APR-07:02 | 24060.84 | 25-APR-07:02 | 120.22 | 17-APR-07:05 | 5279.03 | 25-APR-07:02 | 0.00 | 01-APR-00:10 |
May | 0.864428E+10 | 0.226592E+10 | 276.17 | 0.864428E+10 | -0.0 | 0.00 | 1.00 | 02-MAY-07:02 | 0.00 | 01-MAY-00:10 | 23995.24 | 31-MAY-07:02 | 23995.24 | 31-MAY-07:02 | 0.00 | 25-MAY-07:02 | 5789.44 | 21-MAY-18:45 | 0.00 | 01-MAY-00:10 |
June | 0.118939E+11 | 0.339173E+10 | 327.79 | 0.118704E+11 | 23455594.32 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:03 | 25324.58 | 30-JUN-05:55 | 25324.58 | 30-JUN-05:55 | 1545.76 | 17-JUN-16:55 | 6482.88 | 30-JUN-16:10 | 0.00 | 01-JUN-00:03 |
July | 0.122335E+11 | 0.327520E+10 | 316.54 | 0.111127E+11 | 0.112084E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:10 | 30389.39 | 14-JUL-06:01 | 25389.16 | 31-JUL-06:01 | 14314.55 | 14-JUL-06:03 | 6436.64 | 23-JUL-17:33 | 0.00 | 01-JUL-00:10 |
August | 0.126413E+11 | 0.337097E+10 | 317.12 | 0.113872E+11 | 0.125403E+10 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 29117.09 | 01-AUG-05:03 | 25639.16 | 28-AUG-06:02 | 13050.39 | 04-AUG-07:02 | 6297.16 | 06-AUG-18:15 | 0.00 | 01-AUG-00:10 |
September | 0.106406E+11 | 0.273516E+10 | 278.22 | 0.954189E+10 | 0.109869E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29892.36 | 05-SEP-07:02 | 25079.97 | 20-SEP-06:01 | 15443.72 | 05-SEP-07:02 | 6409.06 | 02-SEP-05:55 | 0.00 | 01-SEP-00:05 |
October | 0.528148E+10 | 0.132847E+10 | 208.99 | 0.504942E+10 | 0.232053E+09 | 0.00 | 1.00 | 02-OCT-05:03 | 0.00 | 01-OCT-00:10 | 28498.27 | 03-OCT-07:02 | 24418.02 | 07-OCT-06:02 | 10773.52 | 03-OCT-07:02 | 6084.33 | 03-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.148277E+10 | 0.365115E+09 | 118.67 | 0.143472E+10 | 48051171.62 | 0.00 | 0.75 | 01-NOV-15:50 | 0.00 | 01-NOV-00:10 | 8632.80 | 01-NOV-16:00 | 8269.82 | 01-NOV-16:00 | 1122.87 | 14-NOV-16:00 | 2136.43 | 01-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 0.292008E+09 | 72523442.27 | 41.83 | 0.292008E+09 | -0.0 | 0.00 | 0.40 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 4202.49 | 22-DEC-16:30 | 4202.49 | 22-DEC-16:30 | 0.00 | 21-DEC-16:30 | 1027.13 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.713419E+11 | 0.188977E+11 | 2346.98 | 0.675586E+11 | 0.378325E+10 | 0.00 | ||||||||||||||
Minimum of Months | 20390666.55 | 5167450.36 | 8.75 | 19265380.29 | -0.0 | 0.00 | 0.13 | 0.00 | 1312.75 | 1255.63 | 0.00 | 331.32 | 0.00 | |||||||
Maximum of Months | 0.126413E+11 | 0.339173E+10 | 327.79 | 0.118704E+11 | 0.125403E+10 | 0.00 | 1.00 | 0.00 | 30389.39 | 25639.16 | 15443.72 | 6482.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.146903E+09 | 44414329.30 | 15.17 | 0.146879E+09 | 24669.34 | 0.00 | 0.19 | 18-MAR-15:30 | 0.00 | 01-MAR-00:10 | 6508.92 | 18-MAR-15:30 | 6508.92 | 18-MAR-15:30 | 19.07 | 17-MAR-12:50 | 1944.59 | 18-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 0.116495E+11 | 0.354103E+10 | 235.08 | 0.116491E+11 | 364225.37 | 0.00 | 1.00 | 03-APR-17:10 | 0.00 | 01-APR-00:10 | 79971.50 | 16-APR-15:55 | 79971.50 | 16-APR-15:55 | 125.84 | 15-APR-08:30 | 22472.51 | 14-APR-17:42 | 0.00 | 01-APR-00:10 |
May | 0.220827E+11 | 0.683802E+10 | 350.47 | 0.220827E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:10 | 79944.00 | 10-MAY-22:45 | 79944.00 | 10-MAY-22:45 | 0.00 | 05-MAY-21:55 | 23148.80 | 15-MAY-17:05 | 0.00 | 01-MAY-00:10 |
June | 0.400871E+11 | 0.129893E+11 | 475.77 | 0.399875E+11 | 99571254.30 | 0.00 | 1.00 | 01-JUN-15:20 | 0.00 | 01-JUN-00:03 | 82417.59 | 18-JUN-06:05 | 81622.86 | 18-JUN-04:35 | 9614.91 | 17-JUN-17:05 | 25375.87 | 17-JUN-17:42 | 0.00 | 01-JUN-00:03 |
July | 0.420789E+11 | 0.128132E+11 | 487.27 | 0.376915E+11 | 0.438740E+10 | 0.00 | 1.00 | 01-JUL-00:25 | 0.00 | 01-JUL-00:15 | 102352.01 | 14-JUL-01:22 | 80365.23 | 08-JUL-05:15 | 57732.32 | 14-JUL-01:22 | 24899.58 | 20-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.384646E+11 | 0.117372E+11 | 459.84 | 0.343164E+11 | 0.414829E+10 | 0.00 | 1.00 | 01-AUG-02:25 | 0.00 | 01-AUG-00:15 | 99025.97 | 09-AUG-21:21 | 81257.41 | 31-AUG-03:15 | 44601.93 | 09-AUG-20:10 | 24896.60 | 13-AUG-13:52 | 0.00 | 01-AUG-00:10 |
September | 0.291354E+11 | 0.865363E+10 | 375.36 | 0.256500E+11 | 0.348542E+10 | 0.00 | 1.00 | 01-SEP-00:25 | 0.00 | 01-SEP-00:05 | 101413.88 | 04-SEP-08:15 | 81479.68 | 26-SEP-21:15 | 54069.31 | 04-SEP-08:15 | 24157.66 | 07-SEP-17:04 | 0.00 | 01-SEP-00:05 |
October | 0.948811E+10 | 0.284034E+10 | 173.10 | 0.891921E+10 | 0.568896E+09 | 0.00 | 1.00 | 01-OCT-08:15 | 0.00 | 01-OCT-00:10 | 93551.63 | 02-OCT-23:15 | 80914.53 | 09-OCT-10:35 | 31301.65 | 02-OCT-23:15 | 23063.80 | 02-OCT-22:41 | 0.00 | 01-OCT-00:10 |
November | 0.350449E+09 | 0.103983E+09 | 21.17 | 0.332658E+09 | 17791420.34 | 0.00 | 0.32 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 11874.11 | 01-NOV-15:10 | 10996.86 | 01-NOV-15:10 | 1033.98 | 01-NOV-14:20 | 3533.48 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.193484E+12 | 0.595610E+11 | 2593.22 | 0.180776E+12 | 0.127078E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.420789E+11 | 0.129893E+11 | 487.27 | 0.399875E+11 | 0.438740E+10 | 0.00 | 1.00 | 0.00 | 102352.01 | 81622.86 | 57732.32 | 25375.87 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.62 | 51.52 | 31.11 | 126.13 | 90.29 | 0.00 | 0.00 | 0.00 |
February | 66.41 | 32.05 | 34.35 | 84.11 | 81.86 | 0.00 | 0.00 | 0.00 |
March | 88.58 | 42.45 | 46.13 | 126.94 | 77.28 | 0.00 | 0.00 | 0.00 |
April | 135.14 | 77.03 | 58.11 | 229.05 | 58.39 | 0.00 | 0.00 | 0.00 |
May | 135.73 | 75.97 | 59.75 | 242.74 | 46.57 | 0.00 | 0.00 | 0.00 |
June | 144.25 | 84.92 | 59.33 | 290.50 | 23.48 | 0.00 | 0.00 | 0.00 |
July | 104.92 | 48.98 | 55.94 | 214.97 | 19.67 | 0.00 | 0.00 | 0.00 |
August | 100.24 | 50.36 | 49.88 | 205.42 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 87.31 | 36.73 | 50.58 | 169.74 | 32.61 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 50.98 | 38.23 | 142.91 | 75.67 | 0.00 | 0.00 | 0.00 |
November | 81.86 | 49.29 | 32.57 | 117.18 | 94.98 | 0.00 | 0.00 | 0.00 |
December | 66.19 | 37.67 | 28.53 | 91.12 | 110.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.65 | 53.24 | 45.41 | 170.43 | 61.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.19 | 32.05 | 28.53 | 84.11 | 19.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.25 | 84.92 | 59.75 | 290.50 | 110.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.62 | 51.52 | 31.11 | 126.13 | 90.29 | 0.00 | 0.00 | 0.00 |
February | 66.41 | 32.05 | 34.35 | 84.11 | 81.86 | 0.00 | 0.00 | 0.00 |
March | 88.58 | 42.45 | 46.13 | 126.94 | 77.28 | 0.00 | 0.00 | 0.00 |
April | 135.14 | 77.03 | 58.11 | 229.05 | 58.39 | 0.00 | 0.00 | 0.00 |
May | 135.73 | 75.97 | 59.75 | 242.74 | 46.57 | 0.00 | 0.00 | 0.00 |
June | 144.25 | 84.92 | 59.33 | 290.50 | 23.48 | 0.00 | 0.00 | 0.00 |
July | 104.92 | 48.98 | 55.94 | 214.97 | 19.67 | 0.00 | 0.00 | 0.00 |
August | 100.24 | 50.36 | 49.88 | 205.42 | 24.42 | 0.00 | 0.00 | 0.00 |
September | 87.31 | 36.73 | 50.58 | 169.74 | 32.61 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 50.98 | 38.23 | 142.91 | 75.67 | 0.00 | 0.00 | 0.00 |
November | 81.86 | 49.29 | 32.57 | 117.18 | 94.98 | 0.00 | 0.00 | 0.00 |
December | 66.19 | 37.67 | 28.53 | 91.12 | 110.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.65 | 53.24 | 45.41 | 170.43 | 61.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.19 | 32.05 | 28.53 | 84.11 | 19.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.25 | 84.92 | 59.75 | 290.50 | 110.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.18 | 0.00 | 14.18 | 12.92 | 53.18 | 0.00 | 0.00 | 0.00 |
February | 16.15 | 0.00 | 16.15 | 10.17 | 48.86 | 0.00 | 0.00 | 0.00 |
March | 21.47 | 0.00 | 21.47 | 22.50 | 46.25 | 0.00 | 0.00 | 0.00 |
April | 26.24 | 0.35 | 25.89 | 40.55 | 33.36 | 0.00 | 0.00 | 0.00 |
May | 30.90 | 2.68 | 28.23 | 55.20 | 24.60 | 0.00 | 0.00 | 0.00 |
June | 35.45 | 6.34 | 29.10 | 85.36 | 12.27 | 0.00 | 0.00 | 0.00 |
July | 30.25 | 3.07 | 27.18 | 71.38 | 10.62 | 0.00 | 0.00 | 0.00 |
August | 24.57 | 0.66 | 23.91 | 59.14 | 13.65 | 0.00 | 0.00 | 0.00 |
September | 23.12 | 0.01 | 23.11 | 49.10 | 18.86 | 0.00 | 0.00 | 0.00 |
October | 17.88 | 0.00 | 17.88 | 23.14 | 44.77 | 0.00 | 0.00 | 0.00 |
November | 14.90 | 0.00 | 14.90 | 10.79 | 56.38 | 0.00 | 0.00 | 0.00 |
December | 13.24 | 0.00 | 13.24 | 8.15 | 65.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.39 | 1.10 | 21.29 | 37.49 | 35.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.24 | 0.00 | 13.24 | 8.15 | 10.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.45 | 6.34 | 29.10 | 85.36 | 65.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.18 | 0.00 | 14.18 | 12.92 | 53.18 | 0.00 | 0.00 | 0.00 |
February | 16.15 | 0.00 | 16.15 | 10.17 | 48.86 | 0.00 | 0.00 | 0.00 |
March | 21.47 | 0.00 | 21.47 | 22.49 | 46.25 | 0.00 | 0.00 | 0.00 |
April | 26.24 | 0.35 | 25.89 | 40.55 | 33.36 | 0.00 | 0.00 | 0.00 |
May | 30.90 | 2.68 | 28.23 | 55.20 | 24.60 | 0.00 | 0.00 | 0.00 |
June | 35.45 | 6.34 | 29.10 | 85.36 | 12.27 | 0.00 | 0.00 | 0.00 |
July | 30.25 | 3.07 | 27.18 | 71.38 | 10.62 | 0.00 | 0.00 | 0.00 |
August | 24.57 | 0.66 | 23.91 | 59.14 | 13.65 | 0.00 | 0.00 | 0.00 |
September | 23.12 | 0.01 | 23.11 | 49.10 | 18.86 | 0.00 | 0.00 | 0.00 |
October | 17.88 | 0.00 | 17.88 | 23.14 | 44.77 | 0.00 | 0.00 | 0.00 |
November | 14.90 | 0.00 | 14.90 | 10.79 | 56.38 | 0.00 | 0.00 | 0.00 |
December | 13.24 | 0.00 | 13.24 | 8.15 | 65.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.39 | 1.09 | 21.29 | 37.49 | 35.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.24 | 0.00 | 13.24 | 8.15 | 10.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.45 | 6.34 | 29.10 | 85.36 | 65.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 111.70 | 50.07 | 0.00 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 104.39 | 39.49 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 152.81 | 40.74 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 247.21 | 38.88 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 275.18 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 303.23 | 21.90 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 246.76 | 15.75 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 227.78 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 180.58 | 22.92 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 149.24 | 45.35 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 105.70 | 49.70 | 0.17 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 92.82 | 56.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 183.48 | 36.33 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 92.82 | 15.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 303.23 | 56.41 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.89 | 68.64 | 20.25 | 116.71 | 44.08 | 6.67 | 0.00 | 0.00 |
February | 86.48 | 55.58 | 30.90 | 107.61 | 37.01 | 0.83 | 0.00 | 0.00 |
March | 122.29 | 78.21 | 44.07 | 157.14 | 38.02 | 0.00 | 0.00 | 0.00 |
April | 189.00 | 145.95 | 43.05 | 246.60 | 41.40 | 0.00 | 0.00 | 0.00 |
May | 208.01 | 163.32 | 44.69 | 268.17 | 43.03 | 0.00 | 0.00 | 0.00 |
June | 219.04 | 179.06 | 39.98 | 290.01 | 32.75 | 0.00 | 0.00 | 0.00 |
July | 177.50 | 128.51 | 48.99 | 235.01 | 25.43 | 0.00 | 0.00 | 0.00 |
August | 163.60 | 120.93 | 42.67 | 217.56 | 30.49 | 0.00 | 0.00 | 0.00 |
September | 131.59 | 82.55 | 49.04 | 173.01 | 31.53 | 0.00 | 0.00 | 0.00 |
October | 117.23 | 88.11 | 29.12 | 146.41 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 87.11 | 63.06 | 24.05 | 108.28 | 48.05 | 9.83 | 0.00 | 0.00 |
December | 76.90 | 56.26 | 20.64 | 96.08 | 53.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.21 | 102.73 | 36.47 | 180.55 | 39.72 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 76.90 | 55.58 | 20.25 | 96.08 | 25.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.04 | 179.06 | 49.04 | 290.01 | 53.10 | 9.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221300E+09 | 0.137988E+09 | 83311683.76 | 0.337828E+09 | 0.241842E+09 |
February | 0.160649E+09 | 77539787.01 | 83109488.92 | 0.203487E+09 | 0.198045E+09 |
March | 0.237253E+09 | 0.113692E+09 | 0.123560E+09 | 0.339994E+09 | 0.206990E+09 |
April | 0.350270E+09 | 0.199653E+09 | 0.150618E+09 | 0.593688E+09 | 0.151351E+09 |
May | 0.363529E+09 | 0.203484E+09 | 0.160045E+09 | 0.650159E+09 | 0.124735E+09 |
June | 0.373901E+09 | 0.220116E+09 | 0.153785E+09 | 0.752969E+09 | 60848061.15 |
July | 0.281007E+09 | 0.131188E+09 | 0.149819E+09 | 0.575777E+09 | 52680599.46 |
August | 0.268479E+09 | 0.134891E+09 | 0.133588E+09 | 0.550195E+09 | 65396431.54 |
September | 0.226305E+09 | 95200585.37 | 0.131105E+09 | 0.439974E+09 | 84532363.97 |
October | 0.238915E+09 | 0.136532E+09 | 0.102383E+09 | 0.382758E+09 | 0.202683E+09 |
November | 0.212181E+09 | 0.127767E+09 | 84413991.00 | 0.303737E+09 | 0.246185E+09 |
December | 0.177291E+09 | 0.100884E+09 | 76406688.93 | 0.244066E+09 | 0.294629E+09 |
Annual Sum or Average | 0.311108E+10 | 0.167894E+10 | 0.143214E+10 | 0.537463E+10 | 0.192992E+10 |
Minimum of Months | 0.160649E+09 | 77539787.01 | 76406688.93 | 0.203487E+09 | 52680599.46 |
Maximum of Months | 0.373901E+09 | 0.220116E+09 | 0.160045E+09 | 0.752969E+09 | 0.294629E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221300E+09 | 0.137988E+09 | 83311683.76 | 0.337828E+09 | 0.241842E+09 |
February | 0.160649E+09 | 77539787.01 | 83109488.92 | 0.203487E+09 | 0.198045E+09 |
March | 0.237253E+09 | 0.113692E+09 | 0.123560E+09 | 0.339994E+09 | 0.206990E+09 |
April | 0.350270E+09 | 0.199653E+09 | 0.150618E+09 | 0.593688E+09 | 0.151351E+09 |
May | 0.363529E+09 | 0.203484E+09 | 0.160045E+09 | 0.650159E+09 | 0.124735E+09 |
June | 0.373901E+09 | 0.220116E+09 | 0.153785E+09 | 0.752969E+09 | 60848061.15 |
July | 0.281007E+09 | 0.131188E+09 | 0.149819E+09 | 0.575777E+09 | 52680599.46 |
August | 0.268479E+09 | 0.134891E+09 | 0.133588E+09 | 0.550195E+09 | 65396431.54 |
September | 0.226305E+09 | 95200585.37 | 0.131105E+09 | 0.439974E+09 | 84532363.97 |
October | 0.238915E+09 | 0.136532E+09 | 0.102383E+09 | 0.382758E+09 | 0.202683E+09 |
November | 0.212181E+09 | 0.127767E+09 | 84413991.00 | 0.303737E+09 | 0.246185E+09 |
December | 0.177291E+09 | 0.100884E+09 | 76406688.93 | 0.244066E+09 | 0.294629E+09 |
Annual Sum or Average | 0.311108E+10 | 0.167894E+10 | 0.143214E+10 | 0.537463E+10 | 0.192992E+10 |
Minimum of Months | 0.160649E+09 | 77539787.01 | 76406688.93 | 0.203487E+09 | 52680599.46 |
Maximum of Months | 0.373901E+09 | 0.220116E+09 | 0.160045E+09 | 0.752969E+09 | 0.294629E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37970864.21 | 0.00 | 37970864.21 | 34605377.84 | 0.142440E+09 |
February | 39079689.59 | 0.00 | 39079689.59 | 24608929.01 | 0.118194E+09 |
March | 57517097.34 | 6505.67 | 57510591.67 | 60252351.31 | 0.123880E+09 |
April | 68019221.58 | 900778.72 | 67118442.86 | 0.105102E+09 | 86475589.27 |
May | 82773834.44 | 7168861.23 | 75604973.21 | 0.147856E+09 | 65900168.24 |
June | 91877693.53 | 16441841.46 | 75435852.07 | 0.221245E+09 | 31798180.61 |
July | 81022562.70 | 8214272.92 | 72808289.78 | 0.191195E+09 | 28451929.39 |
August | 65806993.89 | 1764242.64 | 64042751.26 | 0.158389E+09 | 36560270.93 |
September | 59928443.16 | 35651.21 | 59892791.95 | 0.127261E+09 | 48885607.34 |
October | 47886317.76 | 0.00 | 47886317.76 | 61974357.90 | 0.119908E+09 |
November | 38611049.47 | 0.00 | 38611049.47 | 27972461.61 | 0.146136E+09 |
December | 35468269.93 | 0.00 | 35468269.93 | 21817084.02 | 0.174767E+09 |
Annual Sum or Average | 0.705962E+09 | 34532153.84 | 0.671430E+09 | 0.118228E+10 | 0.112340E+10 |
Minimum of Months | 35468269.93 | 0.00 | 35468269.93 | 21817084.02 | 28451929.39 |
Maximum of Months | 91877693.53 | 16441841.46 | 75604973.21 | 0.221245E+09 | 0.174767E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37969936.17 | 0.00 | 37969936.17 | 34604791.62 | 0.142438E+09 |
February | 39078595.02 | 0.00 | 39078595.02 | 24607855.20 | 0.118194E+09 |
March | 57515485.81 | 6505.36 | 57508980.45 | 60250573.43 | 0.123879E+09 |
April | 68017640.33 | 900736.50 | 67116903.84 | 0.105101E+09 | 86474336.59 |
May | 82771747.80 | 7168525.21 | 75603222.59 | 0.147854E+09 | 65898878.82 |
June | 91875214.53 | 16441070.81 | 75434143.73 | 0.221242E+09 | 31797265.74 |
July | 81020303.82 | 8213887.91 | 72806415.92 | 0.191192E+09 | 28451298.78 |
August | 65805328.90 | 1764159.94 | 64041168.96 | 0.158388E+09 | 36559457.65 |
September | 59926761.42 | 35649.54 | 59891111.87 | 0.127259E+09 | 48884735.69 |
October | 47885142.18 | 0.00 | 47885142.18 | 61973422.16 | 0.119906E+09 |
November | 38610048.25 | 0.00 | 38610048.25 | 27971700.67 | 0.146135E+09 |
December | 35467354.99 | 0.00 | 35467354.99 | 21816553.18 | 0.174765E+09 |
Annual Sum or Average | 0.705944E+09 | 34530535.27 | 0.671413E+09 | 0.118226E+10 | 0.112338E+10 |
Minimum of Months | 35467354.99 | 0.00 | 35467354.99 | 21816553.18 | 28451298.78 |
Maximum of Months | 91875214.53 | 16441070.81 | 75603222.59 | 0.221242E+09 | 0.174765E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.299173E+09 | 0.134096E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.252536E+09 | 95539119.86 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.409298E+09 | 0.109121E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.640761E+09 | 0.100776E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.737031E+09 | 93305157.56 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.785960E+09 | 56755082.78 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.660913E+09 | 42174370.93 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.610075E+09 | 53148037.95 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.468060E+09 | 59414578.47 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.399727E+09 | 0.121456E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.273963E+09 | 0.128824E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.248607E+09 | 0.151086E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.578611E+10 | 0.114569E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.248607E+09 | 42174370.93 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.785960E+09 | 0.151086E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238071E+09 | 0.183845E+09 | 54226147.05 | 0.312603E+09 | 0.118053E+09 |
February | 0.209219E+09 | 0.134459E+09 | 74759653.42 | 0.260334E+09 | 89537529.04 |
March | 0.327528E+09 | 0.209480E+09 | 0.118049E+09 | 0.420880E+09 | 0.101830E+09 |
April | 0.489877E+09 | 0.378295E+09 | 0.111583E+09 | 0.639196E+09 | 0.107298E+09 |
May | 0.557143E+09 | 0.437438E+09 | 0.119704E+09 | 0.718270E+09 | 0.115240E+09 |
June | 0.567752E+09 | 0.464112E+09 | 0.103640E+09 | 0.751693E+09 | 84894258.77 |
July | 0.475404E+09 | 0.344192E+09 | 0.131213E+09 | 0.629444E+09 | 68122617.17 |
August | 0.438182E+09 | 0.323902E+09 | 0.114280E+09 | 0.582720E+09 | 81661034.62 |
September | 0.341071E+09 | 0.213968E+09 | 0.127103E+09 | 0.448445E+09 | 81734178.07 |
October | 0.313984E+09 | 0.236001E+09 | 77982070.05 | 0.392145E+09 | 0.137630E+09 |
November | 0.225793E+09 | 0.163446E+09 | 62347108.81 | 0.280664E+09 | 0.124548E+09 |
December | 0.205975E+09 | 0.150690E+09 | 55284279.68 | 0.257344E+09 | 0.142213E+09 |
Annual Sum or Average | 0.439000E+10 | 0.323983E+10 | 0.115017E+10 | 0.569374E+10 | 0.125276E+10 |
Minimum of Months | 0.205975E+09 | 0.134459E+09 | 54226147.05 | 0.257344E+09 | 68122617.17 |
Maximum of Months | 0.567752E+09 | 0.464112E+09 | 0.131213E+09 | 0.751693E+09 | 0.142213E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.73 | 285.58 | 193.60 | 103.04 | 90.56 | 0.00 | 0.00 |
February | 186.47 | 259.34 | 165.12 | 64.10 | 101.02 | 0.00 | 0.00 |
March | 296.40 | 244.60 | 220.11 | 84.90 | 135.21 | 0.00 | 0.00 |
April | 538.92 | 183.24 | 322.75 | 154.75 | 168.01 | 0.00 | 0.00 |
May | 593.27 | 139.73 | 333.26 | 157.30 | 175.96 | 0.00 | 0.00 |
June | 748.71 | 68.48 | 359.40 | 182.53 | 176.87 | 0.00 | 0.00 |
July | 571.11 | 58.99 | 270.33 | 104.09 | 166.24 | 0.00 | 0.00 |
August | 528.38 | 75.40 | 249.62 | 102.04 | 147.57 | 0.00 | 0.00 |
September | 437.65 | 102.91 | 220.86 | 73.48 | 147.37 | 0.00 | 0.00 |
October | 330.69 | 239.49 | 214.16 | 101.95 | 112.21 | 0.00 | 0.00 |
November | 253.61 | 300.38 | 193.51 | 98.59 | 94.93 | 0.00 | 0.00 |
December | 196.16 | 348.13 | 158.87 | 75.33 | 83.54 | 0.00 | 0.00 |
Annual Sum or Average | 414.15 | 191.95 | 242.07 | 108.67 | 133.41 | 0.00 | 0.00 |
Minimum of Months | 186.47 | 58.99 | 158.87 | 64.10 | 83.54 | 0.00 | 0.00 |
Maximum of Months | 748.71 | 348.13 | 359.40 | 182.53 | 176.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1563.78 | 700.92 | 1244.40 | 960.96 | 283.44 | 0.00 | 0.00 |
February | 1461.43 | 552.89 | 1210.76 | 778.12 | 432.64 | 0.00 | 0.00 |
March | 2139.40 | 570.38 | 1711.99 | 1094.95 | 617.04 | 0.00 | 0.00 |
April | 3460.90 | 544.31 | 2645.94 | 2043.26 | 602.68 | 0.00 | 0.00 |
May | 3852.46 | 487.71 | 2912.19 | 2286.49 | 625.69 | 0.00 | 0.00 |
June | 4245.16 | 306.55 | 3066.56 | 2506.78 | 559.78 | 0.00 | 0.00 |
July | 3454.60 | 220.45 | 2484.94 | 1799.09 | 685.85 | 0.00 | 0.00 |
August | 3188.86 | 277.80 | 2290.38 | 1693.04 | 597.34 | 0.00 | 0.00 |
September | 2528.10 | 320.91 | 1842.20 | 1155.69 | 686.52 | 0.00 | 0.00 |
October | 2089.38 | 634.85 | 1641.19 | 1233.58 | 407.61 | 0.00 | 0.00 |
November | 1479.74 | 695.81 | 1219.56 | 882.81 | 336.75 | 0.00 | 0.00 |
December | 1299.47 | 789.73 | 1076.63 | 787.66 | 288.97 | 0.00 | 0.00 |
Annual Sum or Average | 2568.67 | 508.62 | 1948.88 | 1438.28 | 510.60 | 0.00 | 0.00 |
Minimum of Months | 1299.47 | 220.45 | 1076.63 | 778.12 | 283.44 | 0.00 | 0.00 |
Maximum of Months | 4245.16 | 789.73 | 3066.56 | 2506.78 | 686.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14952.91 | 4675.66 | 2844.33 | 2196.47 | 647.86 | 0.00 | 0.00 |
February | 15756.53 | 3802.98 | 2767.44 | 1778.56 | 988.88 | 0.00 | 0.00 |
March | 21090.97 | 3782.74 | 3913.12 | 2502.74 | 1410.38 | 0.00 | 0.00 |
April | 32462.27 | 4209.41 | 6047.87 | 4670.30 | 1377.56 | 0.00 | 0.00 |
May | 41670.62 | 5516.28 | 6656.43 | 5226.27 | 1430.16 | 0.00 | 0.00 |
June | 52254.80 | 6904.23 | 7009.29 | 5729.78 | 1279.51 | 0.00 | 0.00 |
July | 42084.80 | 5534.34 | 5679.86 | 4112.21 | 1567.65 | 0.00 | 0.00 |
August | 37208.40 | 6050.54 | 5235.15 | 3869.80 | 1365.36 | 0.00 | 0.00 |
September | 27642.52 | 5132.83 | 4210.75 | 2641.57 | 1569.18 | 0.00 | 0.00 |
October | 19743.49 | 5891.80 | 3751.30 | 2819.61 | 931.69 | 0.00 | 0.00 |
November | 14210.00 | 4848.81 | 2787.57 | 2017.85 | 769.72 | 0.00 | 0.00 |
December | 13121.03 | 5727.31 | 2460.87 | 1800.36 | 660.51 | 0.00 | 0.00 |
Annual Sum or Average | 27737.83 | 5183.23 | 4454.59 | 3287.50 | 1167.09 | 0.00 | 0.00 |
Minimum of Months | 13121.03 | 3782.74 | 2460.87 | 1778.56 | 647.86 | 0.00 | 0.00 |
Maximum of Months | 52254.80 | 6904.23 | 7009.29 | 5729.78 | 1569.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.741205E+09 | 0.764901E+09 | 0.518541E+09 | 0.275977E+09 | 0.242564E+09 | 0.00 | 0.00 |
February | 0.451120E+09 | 0.627407E+09 | 0.399457E+09 | 0.155080E+09 | 0.244377E+09 | 0.00 | 0.00 |
March | 0.793888E+09 | 0.655137E+09 | 0.589538E+09 | 0.227397E+09 | 0.362140E+09 | 0.00 | 0.00 |
April | 0.139689E+10 | 0.474959E+09 | 0.836578E+09 | 0.401107E+09 | 0.435470E+09 | 0.00 | 0.00 |
May | 0.158903E+10 | 0.374266E+09 | 0.892604E+09 | 0.421305E+09 | 0.471299E+09 | 0.00 | 0.00 |
June | 0.194064E+10 | 0.177511E+09 | 0.931554E+09 | 0.473115E+09 | 0.458440E+09 | 0.00 | 0.00 |
July | 0.152967E+10 | 0.157991E+09 | 0.724058E+09 | 0.278805E+09 | 0.445253E+09 | 0.00 | 0.00 |
August | 0.141521E+10 | 0.201956E+09 | 0.668571E+09 | 0.273311E+09 | 0.395259E+09 | 0.00 | 0.00 |
September | 0.113438E+10 | 0.266751E+09 | 0.572466E+09 | 0.190472E+09 | 0.381994E+09 | 0.00 | 0.00 |
October | 0.885722E+09 | 0.641439E+09 | 0.573601E+09 | 0.273064E+09 | 0.300537E+09 | 0.00 | 0.00 |
November | 0.657369E+09 | 0.778591E+09 | 0.501583E+09 | 0.255534E+09 | 0.246049E+09 | 0.00 | 0.00 |
December | 0.525398E+09 | 0.932422E+09 | 0.425517E+09 | 0.201768E+09 | 0.223749E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.130605E+11 | 0.605333E+10 | 0.763407E+10 | 0.342693E+10 | 0.420713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.451120E+09 | 0.157991E+09 | 0.399457E+09 | 0.155080E+09 | 0.223749E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194064E+10 | 0.932422E+09 | 0.931554E+09 | 0.473115E+09 | 0.471299E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.418843E+10 | 0.187735E+10 | 0.333299E+10 | 0.257382E+10 | 0.759166E+09 | 0.00 | 0.00 |
February | 0.353550E+10 | 0.133755E+10 | 0.292906E+10 | 0.188243E+10 | 0.104664E+10 | 0.00 | 0.00 |
March | 0.573017E+10 | 0.152770E+10 | 0.458540E+10 | 0.293271E+10 | 0.165268E+10 | 0.00 | 0.00 |
April | 0.897066E+10 | 0.141086E+10 | 0.685828E+10 | 0.529612E+10 | 0.156216E+10 | 0.00 | 0.00 |
May | 0.103184E+11 | 0.130627E+10 | 0.780000E+10 | 0.612414E+10 | 0.167586E+10 | 0.00 | 0.00 |
June | 0.110034E+11 | 0.794571E+09 | 0.794853E+10 | 0.649757E+10 | 0.145096E+10 | 0.00 | 0.00 |
July | 0.925279E+10 | 0.590441E+09 | 0.665566E+10 | 0.481868E+10 | 0.183698E+10 | 0.00 | 0.00 |
August | 0.854105E+10 | 0.744073E+09 | 0.613455E+10 | 0.453463E+10 | 0.159993E+10 | 0.00 | 0.00 |
September | 0.655284E+10 | 0.831804E+09 | 0.477499E+10 | 0.299555E+10 | 0.177945E+10 | 0.00 | 0.00 |
October | 0.559618E+10 | 0.170038E+10 | 0.439577E+10 | 0.330402E+10 | 0.109175E+10 | 0.00 | 0.00 |
November | 0.383548E+10 | 0.180353E+10 | 0.316110E+10 | 0.228824E+10 | 0.872860E+09 | 0.00 | 0.00 |
December | 0.348050E+10 | 0.211520E+10 | 0.288364E+10 | 0.210966E+10 | 0.773980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810055E+11 | 0.160397E+11 | 0.614600E+11 | 0.453576E+11 | 0.161024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.348050E+10 | 0.590441E+09 | 0.288364E+10 | 0.188243E+10 | 0.759166E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110034E+11 | 0.211520E+10 | 0.794853E+10 | 0.649757E+10 | 0.183698E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.400499E+11 | 0.125233E+11 | 0.761826E+10 | 0.588303E+10 | 0.173524E+10 | 0.00 | 0.00 |
February | 0.381182E+11 | 0.920018E+10 | 0.669500E+10 | 0.430269E+10 | 0.239231E+10 | 0.00 | 0.00 |
March | 0.564901E+11 | 0.101317E+11 | 0.104809E+11 | 0.670335E+10 | 0.377756E+10 | 0.00 | 0.00 |
April | 0.841422E+11 | 0.109108E+11 | 0.156761E+11 | 0.121054E+11 | 0.357064E+10 | 0.00 | 0.00 |
May | 0.111611E+12 | 0.147748E+11 | 0.178286E+11 | 0.139980E+11 | 0.383054E+10 | 0.00 | 0.00 |
June | 0.135444E+12 | 0.178958E+11 | 0.181681E+11 | 0.148516E+11 | 0.331649E+10 | 0.00 | 0.00 |
July | 0.112720E+12 | 0.148232E+11 | 0.152129E+11 | 0.110141E+11 | 0.419880E+10 | 0.00 | 0.00 |
August | 0.996590E+11 | 0.162058E+11 | 0.140218E+11 | 0.103649E+11 | 0.365697E+10 | 0.00 | 0.00 |
September | 0.716494E+11 | 0.133043E+11 | 0.109143E+11 | 0.684696E+10 | 0.406731E+10 | 0.00 | 0.00 |
October | 0.528810E+11 | 0.157806E+11 | 0.100475E+11 | 0.755205E+10 | 0.249543E+10 | 0.00 | 0.00 |
November | 0.368323E+11 | 0.125681E+11 | 0.722538E+10 | 0.523027E+10 | 0.199511E+10 | 0.00 | 0.00 |
December | 0.351434E+11 | 0.153400E+11 | 0.659119E+10 | 0.482209E+10 | 0.176910E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.874740E+12 | 0.163458E+12 | 0.140480E+12 | 0.103674E+12 | 0.368055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.351434E+11 | 0.920018E+10 | 0.659119E+10 | 0.430269E+10 | 0.173524E+10 | 0.00 | 0.00 |
Maximum of Months | 0.135444E+12 | 0.178958E+11 | 0.181681E+11 | 0.148516E+11 | 0.419880E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.800118E+09 | -720550932.5 | 0.00 | 0.00 | 744.00 | 0.00 | -79567063.9 | 58.99 | 0.00 | 0.00 |
February | 0.728675E+09 | -655401715.0 | 0.00 | 0.00 | 672.00 | 0.00 | -73273234.9 | 58.99 | 0.00 | 0.00 |
March | 0.807048E+09 | -728585378.7 | 0.00 | 0.00 | 744.00 | 0.00 | -78462768.3 | 58.99 | 0.00 | 0.00 |
April | 0.692404E+09 | -623093490.1 | 0.00 | 0.00 | 720.00 | 0.00 | -69310257.8 | 58.99 | 0.00 | 0.00 |
May | 0.657803E+09 | -587761730.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70040795.6 | 58.99 | 0.00 | 0.00 |
June | 0.602055E+09 | -535584391.8 | 0.00 | 0.00 | 720.00 | 0.00 | -66470500.3 | 58.99 | 0.00 | 0.00 |
July | 0.562500E+09 | -494118888.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68381408.8 | 58.99 | 0.00 | 0.00 |
August | 0.607598E+09 | -538543826.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69053950.0 | 58.99 | 0.00 | 0.00 |
September | 0.603995E+09 | -537058287.8 | 0.00 | 0.00 | 720.00 | 0.00 | -66936664.7 | 58.99 | 0.00 | 0.00 |
October | 0.664873E+09 | -592658709.1 | 0.00 | 0.00 | 744.00 | 0.00 | -72214540.0 | 58.99 | 0.00 | 0.00 |
November | 0.698866E+09 | -624741527.2 | 0.00 | 0.00 | 720.00 | 0.00 | -74124920.7 | 58.99 | 0.00 | 0.00 |
December | 0.778114E+09 | -697066728.6 | 0.00 | 0.00 | 744.00 | 0.00 | -81047053.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.820405E+10 | -0.733517E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -868883158.5 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.562500E+09 | -728585378.7 | 0.00 | 0.00 | 672.00 | 0.00 | -81047053.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.807048E+09 | -494118888.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66470500.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.84 | 0.50 | 06-JAN-11:39 | 163.32 | 0.00 | 0.00 | 21.50 | 141.71 | 0.00 | 0.00 | 13.33 |
February | 241.00 | 0.76 | 0.50 | 05-FEB-11:00 | 233.45 | 0.00 | 0.00 | 66.83 | 1704.55 | 0.00 | 0.00 | 57.67 |
March | 344.33 | 0.73 | 0.50 | 02-MAR-10:30 | 277.62 | 0.00 | 0.00 | 136.50 | 226.42 | 0.00 | 0.00 | 100.17 |
April | 380.33 | 0.71 | 0.50 | 02-APR-11:50 | 279.72 | 0.00 | 0.00 | 153.00 | 1924.75 | 0.00 | 0.00 | 131.17 |
May | 403.17 | 0.70 | 0.50 | 01-MAY-10:20 | 1218.77 | 0.00 | 0.00 | 190.50 | 1965.50 | 0.00 | 0.00 | 136.50 |
June | 418.17 | 0.74 | 0.50 | 01-JUN-10:39 | 2886.66 | 0.00 | 0.00 | 177.67 | 196.42 | 0.00 | 0.00 | 60.50 |
July | 399.50 | 0.71 | 0.50 | 01-JUL-10:00 | 2070.53 | 0.00 | 0.00 | 192.33 | 235.79 | 0.00 | 0.00 | 117.50 |
August | 361.83 | 0.71 | 0.50 | 01-AUG-10:09 | 735.57 | 0.00 | 0.00 | 142.50 | 1755.99 | 0.00 | 0.00 | 115.33 |
September | 350.17 | 0.70 | 0.50 | 01-SEP-09:30 | 309.09 | 0.00 | 0.00 | 168.17 | 250.18 | 0.00 | 0.00 | 126.83 |
October | 348.00 | 0.78 | 0.50 | 01-OCT-09:00 | 213.80 | 0.00 | 0.00 | 76.33 | 1628.13 | 0.00 | 0.00 | 81.00 |
November | 288.50 | 0.82 | 0.50 | 01-NOV-11:09 | 186.28 | 0.00 | 0.00 | 37.50 | 157.53 | 0.00 | 0.00 | 21.50 |
December | 290.67 | 0.82 | 0.50 | 02-DEC-11:09 | 1625.73 | 0.00 | 0.00 | 64.00 | 144.22 | 0.00 | 0.00 | 13.67 |
Annual Sum or Average | 4135.50 | 0.75 | 921.19 | 0.00 | 0.00 | 1426.83 | 873.03 | 0.00 | 0.00 | 975.17 | ||
Minimum of Months | 241.00 | 0.70 | 0.50 | 163.32 | 0.00 | 0.00 | 21.50 | 141.71 | 0.00 | 0.00 | 13.33 | |
Maximum of Months | 418.17 | 0.84 | 0.50 | 2886.66 | 0.00 | 0.00 | 192.33 | 1965.50 | 0.00 | 0.00 | 136.50 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.70 | 0.50 | 01-JAN-10:09 | 192.53 | 11.77 | 0.00 | 132.33 | 158.82 | 15.63 | 14.00 | 81.00 |
February | 241.00 | 0.65 | 0.50 | 01-FEB-12:00 | 1562.31 | 13.29 | 0.00 | 167.67 | 222.88 | 17.12 | 40.00 | 125.33 |
March | 344.33 | 0.62 | 0.50 | 01-MAR-08:09 | 319.80 | 14.20 | 0.50 | 246.00 | 267.72 | 18.13 | 92.50 | 215.33 |
April | 380.33 | 0.61 | 0.50 | 01-APR-08:50 | 2454.92 | 14.13 | 2.00 | 276.17 | 2643.77 | 18.35 | 99.50 | 229.50 |
May | 403.17 | 0.60 | 0.50 | 01-MAY-07:49 | 334.03 | 14.39 | 0.33 | 306.83 | 2694.91 | 18.66 | 110.33 | 251.67 |
June | 418.17 | 0.61 | 0.50 | 01-JUN-07:40 | 293.77 | 13.60 | 0.00 | 297.67 | 248.23 | 17.76 | 84.67 | 241.67 |
July | 399.50 | 0.60 | 0.50 | 01-JUL-08:30 | 345.92 | 14.50 | 2.00 | 298.67 | 296.10 | 18.52 | 96.83 | 260.00 |
August | 361.83 | 0.60 | 0.50 | 01-AUG-08:20 | 2193.08 | 14.48 | 1.17 | 280.67 | 291.05 | 18.66 | 101.83 | 235.33 |
September | 350.17 | 0.60 | 0.50 | 01-SEP-07:30 | 357.83 | 14.77 | 3.33 | 266.00 | 298.92 | 18.68 | 106.50 | 231.00 |
October | 348.00 | 0.66 | 0.50 | 01-OCT-07:49 | 1163.56 | 15.44 | 37.67 | 209.33 | 209.57 | 16.71 | 60.17 | 149.33 |
November | 288.50 | 0.68 | 0.50 | 01-NOV-08:20 | 854.23 | 12.35 | 0.00 | 162.83 | 180.22 | 16.25 | 25.83 | 97.17 |
December | 290.67 | 0.70 | 0.50 | 01-DEC-09:30 | 426.17 | 12.12 | 0.00 | 128.00 | 163.43 | 15.94 | 17.00 | 77.17 |
Annual Sum or Average | 4135.50 | 0.63 | 863.20 | 13.85 | 47.00 | 2772.17 | 699.22 | 17.64 | 849.17 | 2194.50 | ||
Minimum of Months | 241.00 | 0.60 | 0.50 | 192.53 | 11.77 | 0.00 | 128.00 | 158.82 | 15.63 | 14.00 | 77.17 | |
Maximum of Months | 418.17 | 0.70 | 0.50 | 2454.92 | 15.44 | 37.67 | 306.83 | 2694.91 | 18.68 | 110.33 | 260.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.92 | 0.80 | 26-JAN-16:30 | 280.78 | 21.67 | 106.83 | 42.67 | 98.37 | 18.91 | 74.33 | 0.00 |
February | 241.00 | 0.91 | 0.80 | 02-FEB-16:30 | 341.76 | 21.80 | 94.17 | 33.67 | 113.22 | 19.55 | 82.50 | 3.00 |
March | 344.33 | 0.90 | 0.80 | 02-MAR-16:10 | 305.36 | 21.96 | 137.67 | 43.33 | 268.27 | 23.38 | 158.17 | 38.67 |
April | 380.33 | 0.89 | 0.80 | 01-APR-15:20 | 224.19 | 20.20 | 136.00 | 64.17 | 281.42 | 22.16 | 161.00 | 65.83 |
May | 403.17 | 0.89 | 0.80 | 01-MAY-16:10 | 220.34 | 19.99 | 117.33 | 46.00 | 312.51 | 21.37 | 157.83 | 63.67 |
June | 418.17 | 0.90 | 0.80 | 01-JUN-16:10 | 207.60 | 19.46 | 99.83 | 23.33 | 382.71 | 21.03 | 160.83 | 56.67 |
July | 399.50 | 0.90 | 0.80 | 01-JUL-17:19 | 207.69 | 19.58 | 102.00 | 26.83 | 288.83 | 20.96 | 157.83 | 49.17 |
August | 361.83 | 0.90 | 0.80 | 01-AUG-15:50 | 198.04 | 19.64 | 92.67 | 25.00 | 232.46 | 20.86 | 127.00 | 41.67 |
September | 350.17 | 0.90 | 0.80 | 01-SEP-16:10 | 251.69 | 21.08 | 133.33 | 39.83 | 201.56 | 21.86 | 150.67 | 31.50 |
October | 348.00 | 0.91 | 0.80 | 01-OCT-16:10 | 324.37 | 22.24 | 126.17 | 42.67 | 204.23 | 22.10 | 119.17 | 28.33 |
November | 288.50 | 0.91 | 0.80 | 04-NOV-16:10 | 552.61 | 23.31 | 101.83 | 53.83 | 107.20 | 19.49 | 79.50 | 0.00 |
December | 290.67 | 0.92 | 0.82 | 13-DEC-16:19 | 425.96 | 22.53 | 96.33 | 46.50 | 92.28 | 19.01 | 67.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.91 | 283.96 | 20.97 | 1344.17 | 487.83 | 227.81 | 21.01 | 1495.83 | 378.50 | ||
Minimum of Months | 241.00 | 0.89 | 0.80 | 198.04 | 19.46 | 92.67 | 23.33 | 92.28 | 18.91 | 67.00 | 0.00 | |
Maximum of Months | 418.17 | 0.92 | 0.82 | 552.61 | 23.31 | 137.67 | 64.17 | 382.71 | 23.38 | 161.00 | 65.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324595E+09 | 31384.59 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325335E+09 | 31384.59 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.280646E+09 | 31384.59 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5450415.52 | 12057.90 | 25-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68350193.14 | 13088.43 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557637E+09 | 31384.59 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.557637E+09 | 31384.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.463034E+09 | 50484.99 | 01-JAN-07:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103687E+09 | 26640.74 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.566721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.463034E+09 | 50484.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.987994E+09 | 0.987994E+09 | 6081.47 | 31-JAN-16:40 | 6081.47 | 0.00 |
February | 0.00 | 0.00 | 20390666.55 | 19265380.29 | 1312.75 | 18-FEB-15:10 | 1214.64 | 0.00 |
March | 0.00 | 0.00 | 0.112342E+10 | 0.111845E+10 | 6481.60 | 18-MAR-16:00 | 6481.60 | 0.00 |
April | 0.00 | 0.00 | 0.610028E+10 | 0.610024E+10 | 24060.84 | 25-APR-07:02 | 24060.84 | 0.00 |
May | 0.00 | 0.00 | 0.864428E+10 | 0.864428E+10 | 23995.24 | 31-MAY-07:02 | 23995.24 | 0.00 |
June | 0.00 | 0.00 | 0.118939E+11 | 0.118704E+11 | 25324.58 | 30-JUN-05:55 | 25324.58 | 0.00 |
July | 0.00 | 0.00 | 0.122335E+11 | 0.111127E+11 | 30389.39 | 14-JUL-06:01 | 16137.91 | 0.00 |
August | 0.00 | 0.00 | 0.126413E+11 | 0.113872E+11 | 29117.09 | 01-AUG-05:03 | 17869.41 | 0.00 |
September | 0.00 | 0.00 | 0.106406E+11 | 0.954189E+10 | 29892.36 | 05-SEP-07:02 | 14448.64 | 0.00 |
October | 0.00 | 0.00 | 0.528148E+10 | 0.504942E+10 | 28498.27 | 03-OCT-07:02 | 17724.75 | 0.00 |
November | 0.00 | 0.00 | 0.148277E+10 | 0.143472E+10 | 8632.80 | 01-NOV-16:00 | 8269.82 | 0.00 |
December | 0.00 | 0.00 | 0.292008E+09 | 0.292008E+09 | 4202.49 | 22-DEC-16:30 | 4202.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.713419E+11 | 0.675586E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 20390666.55 | 19265380.29 | 1312.75 | 1214.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126413E+11 | 0.118704E+11 | 30389.39 | 25324.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.146903E+09 | 0.146879E+09 | 6508.92 | 18-MAR-15:30 | 6508.92 | 0.00 |
April | 0.00 | 0.00 | 0.116495E+11 | 0.116491E+11 | 79971.50 | 16-APR-15:55 | 79971.50 | 0.00 |
May | 0.00 | 0.00 | 0.220827E+11 | 0.220827E+11 | 79944.00 | 10-MAY-22:45 | 79944.00 | 0.00 |
June | 0.00 | 0.00 | 0.400871E+11 | 0.399875E+11 | 82417.59 | 18-JUN-06:05 | 79923.85 | 0.00 |
July | 0.00 | 0.00 | 0.420789E+11 | 0.376915E+11 | 102352.01 | 14-JUL-01:22 | 44619.68 | 0.00 |
August | 0.00 | 0.00 | 0.384646E+11 | 0.343164E+11 | 99025.97 | 09-AUG-21:21 | 55166.71 | 0.00 |
September | 0.00 | 0.00 | 0.291354E+11 | 0.256500E+11 | 101413.88 | 04-SEP-08:15 | 47344.57 | 0.00 |
October | 0.00 | 0.00 | 0.948811E+10 | 0.891921E+10 | 93551.63 | 02-OCT-23:15 | 62249.98 | 0.00 |
November | 0.00 | 0.00 | 0.350449E+09 | 0.332658E+09 | 11874.11 | 01-NOV-15:10 | 10996.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193484E+12 | 0.180776E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.420789E+11 | 0.399875E+11 | 102352.01 | 79971.50 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.621288E+09 | 0.23 | 1543.36 | 02-JAN-06:01 | 1.00 |
February | 0.571876E+09 | 0.23 | 1543.36 | 06-FEB-07:02 | 0.99 |
March | 0.668345E+09 | 0.24 | 1543.36 | 27-MAR-06:01 | 1.00 |
April | 0.617038E+09 | 0.23 | 1543.36 | 15-APR-07:02 | 1.00 |
May | 0.672653E+09 | 0.25 | 1543.36 | 02-MAY-07:02 | 1.00 |
June | 0.811993E+09 | 0.31 | 1543.36 | 01-JUN-06:02 | 1.00 |
July | 0.741716E+09 | 0.28 | 1543.36 | 01-JUL-06:01 | 1.00 |
August | 0.776505E+09 | 0.28 | 1543.36 | 01-AUG-06:02 | 0.98 |
September | 0.670871E+09 | 0.25 | 1543.36 | 01-SEP-06:02 | 0.98 |
October | 0.622973E+09 | 0.23 | 1543.36 | 02-OCT-06:01 | 0.99 |
November | 0.588740E+09 | 0.22 | 1003.52 | 24-NOV-07:03 | 0.81 |
December | 0.627886E+09 | 0.23 | 1543.36 | 05-DEC-07:02 | 1.00 |
Annual Sum or Average | 0.799188E+10 | 0.25 | |||
Minimum of Months | 0.571876E+09 | 0.22 | 1003.52 | 0.81 | |
Maximum of Months | 0.811993E+09 | 0.31 | 1543.36 | 1.00 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.255655E+10 | 0.37 | 3581.66 | 02-JAN-07:02 | 1.15 |
February | 0.232707E+10 | 0.35 | 2554.98 | 01-FEB-07:10 | 0.93 |
March | 0.273178E+10 | 0.37 | 2554.98 | 16-MAR-15:20 | 0.93 |
April | 0.269813E+10 | 0.42 | 6387.44 | 14-APR-17:42 | 1.54 |
May | 0.306137E+10 | 0.51 | 6387.44 | 06-MAY-17:06 | 1.55 |
June | 0.371446E+10 | 0.66 | 6387.44 | 01-JUN-17:05 | 1.54 |
July | 0.360868E+10 | 0.65 | 6387.44 | 01-JUL-17:05 | 1.55 |
August | 0.351277E+10 | 0.61 | 6387.44 | 01-AUG-17:05 | 1.53 |
September | 0.304939E+10 | 0.53 | 6387.44 | 05-SEP-17:05 | 1.53 |
October | 0.266926E+10 | 0.40 | 5945.44 | 05-OCT-17:05 | 1.49 |
November | 0.242825E+10 | 0.34 | 2554.98 | 09-NOV-16:40 | 0.94 |
December | 0.253521E+10 | 0.35 | 3505.60 | 07-DEC-07:02 | 1.14 |
Annual Sum or Average | 0.348929E+11 | 0.47 | |||
Minimum of Months | 0.232707E+10 | 0.34 | 2554.98 | 0.93 | |
Maximum of Months | 0.371446E+10 | 0.66 | 6387.44 | 1.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.867529E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.577043E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.950477E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.217613E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.293857E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.420372E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.401691E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.414748E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.340603E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.195144E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.953855E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.700409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268896E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.577043E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.420372E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.255655E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.232707E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.277619E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.623916E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.989940E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167037E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164219E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.152499E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.117030E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.550960E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.253223E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.253521E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.944540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.232707E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.167037E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.621288E+09 | 0.987994E+09 | 0.324595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571876E+09 | 20390666.55 | 0.325335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668345E+09 | 0.112342E+10 | 0.280646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617038E+09 | 0.610028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.672653E+09 | 0.864187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.811993E+09 | 0.118781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.741716E+09 | 0.121961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.776505E+09 | 0.126234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.670871E+09 | 0.106216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.622973E+09 | 0.527970E+10 | 5450415.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.588740E+09 | 0.148277E+10 | 68350193.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627886E+09 | 0.292008E+09 | 0.557637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.799188E+10 | 0.712476E+11 | 0.156201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.571876E+09 | 20390666.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811993E+09 | 0.126234E+11 | 0.557637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.255655E+10 | 0.00 | 0.463034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273178E+10 | 0.146903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269813E+10 | 0.114787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306137E+10 | 0.218671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371446E+10 | 0.395709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.360868E+10 | 0.409818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.351277E+10 | 0.374126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304939E+10 | 0.282528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266926E+10 | 0.928319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242825E+10 | 0.350449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253521E+10 | 0.00 | 0.103687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348929E+11 | 0.189344E+12 | 0.566721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.232707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371446E+10 | 0.409818E+11 | 0.463034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.621288E+09 | 0.00 | 0.00 | 0.00 | 0.246241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571876E+09 | 0.00 | 0.00 | 0.00 | 5167450.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668345E+09 | 0.00 | 0.00 | 0.00 | 0.282132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617038E+09 | 0.00 | 0.00 | 0.00 | 0.155909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.672653E+09 | 0.00 | 0.00 | 0.00 | 0.226592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.811993E+09 | 0.00 | 0.00 | 0.00 | 0.339173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.741716E+09 | 0.00 | 0.00 | 0.00 | 0.327520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.776505E+09 | 0.00 | 0.00 | 0.00 | 0.337097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.670871E+09 | 0.00 | 0.00 | 0.00 | 0.273516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.622973E+09 | 0.00 | 0.00 | 0.00 | 0.132847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.588740E+09 | 0.00 | 0.00 | 0.00 | 0.365115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627886E+09 | 0.00 | 0.00 | 0.00 | 72523442.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.799188E+10 | 0.00 | 0.00 | 0.00 | 0.188977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.571876E+09 | 0.00 | 0.00 | 0.00 | 5167450.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811993E+09 | 0.00 | 0.00 | 0.00 | 0.339173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.255655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273178E+10 | 0.00 | 0.00 | 0.00 | 44414329.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269813E+10 | 0.00 | 0.00 | 0.00 | 0.354103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306137E+10 | 0.00 | 0.00 | 0.00 | 0.683802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371446E+10 | 0.00 | 0.00 | 0.00 | 0.129893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.360868E+10 | 0.00 | 0.00 | 0.00 | 0.128132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.351277E+10 | 0.00 | 0.00 | 0.00 | 0.117372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304939E+10 | 0.00 | 0.00 | 0.00 | 0.865363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266926E+10 | 0.00 | 0.00 | 0.00 | 0.284034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242825E+10 | 0.00 | 0.00 | 0.00 | 0.103983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348929E+11 | 0.00 | 0.00 | 0.00 | 0.595610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.232707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371446E+10 | 0.00 | 0.00 | 0.00 | 0.129893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289858E+09 | 2061120.19 | 0.00 | 1837085.41 | 0.00 | 34308803.50 | 0.933054E+09 | 0.00 | 0.34 |
February | 0.627440E+09 | 0.00 | 0.00 | 471067.65 | 0.00 | 46442918.17 | 0.596681E+09 | 0.00 | 0.20 |
March | 0.359623E+09 | 11993353.91 | 0.00 | 1819733.18 | 0.00 | 21726175.48 | 0.100127E+10 | 0.00 | 0.34 |
April | 8952930.48 | 0.182118E+09 | 0.00 | 3562981.15 | 0.00 | 0.00 | 0.631356E+09 | 0.00 | 0.29 |
May | 2440977.29 | 0.371844E+09 | 0.00 | 3870347.10 | 0.00 | 0.00 | 0.237619E+09 | 0.00 | 0.21 |
June | 634334.98 | 0.882247E+09 | 0.00 | 1522568.28 | 489523.36 | 0.00 | 52012174.31 | 0.00 | 0.18 |
July | 72440.09 | 0.113693E+10 | 0.00 | 1395205.44 | 340903.16 | 0.00 | 41754709.44 | 0.00 | 0.17 |
August | 354291.70 | 0.124296E+10 | 0.00 | 1889077.21 | 702094.96 | 0.00 | 68474660.78 | 0.00 | 0.20 |
September | 2212568.09 | 0.856912E+09 | 0.00 | 2411288.37 | 136890.54 | 0.00 | 0.111404E+09 | 0.00 | 0.22 |
October | 54902102.43 | 0.225586E+09 | 0.00 | 4001891.09 | 143277.37 | 956722.24 | 0.110377E+10 | 0.00 | 0.37 |
November | 0.157416E+09 | 10798615.33 | 0.00 | 3067298.97 | 0.00 | 6362742.65 | 0.163557E+10 | 0.00 | 0.42 |
December | 0.545111E+09 | 0.00 | 0.00 | 867406.78 | 98574.82 | 0.103932E+09 | 0.640822E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.204902E+10 | 0.492345E+10 | 0.00 | 26715950.63 | 1911264.22 | 0.213730E+09 | 0.705379E+10 | 0.00 | 0.27 |
Minimum of Months | 72440.09 | 0.00 | 0.00 | 471067.65 | 0.00 | 0.00 | 41754709.44 | 0.00 | 0.17 |
Maximum of Months | 0.627440E+09 | 0.124296E+10 | 0.00 | 4001891.09 | 702094.96 | 0.103932E+09 | 0.163557E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217307E+10 | 0.00 | 0.00 | 0.00 | 453554.71 | 4914332.29 | 0.00 | 0.00 | 0.18 |
February | 0.295864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.255552E+10 | 398655.61 | 0.00 | 68957.47 | 6652418.13 | 0.00 | 95308282.54 | 0.00 | 0.20 |
April | 0.466994E+09 | 0.287709E+09 | 0.00 | 5756811.08 | 3323072.90 | 0.00 | 0.157617E+10 | 0.00 | 0.32 |
May | 84310744.37 | 0.813861E+09 | 0.00 | 6917857.47 | 0.00 | 0.00 | 0.122602E+10 | 0.00 | 0.30 |
June | 2332684.32 | 0.257517E+10 | 0.00 | 4224875.85 | 0.00 | 0.00 | 0.372791E+09 | 0.00 | 0.27 |
July | 340370.00 | 0.336396E+10 | 0.00 | 2316181.71 | 2455032.74 | 0.00 | 0.212657E+09 | 0.00 | 0.27 |
August | 5749999.22 | 0.351829E+10 | 0.00 | 2736930.32 | 517362.98 | 0.00 | 0.440477E+09 | 0.00 | 0.32 |
September | 38962094.10 | 0.211504E+10 | 0.00 | 4525367.06 | 0.00 | 0.00 | 0.787571E+09 | 0.00 | 0.33 |
October | 0.140292E+10 | 0.411028E+09 | 0.00 | 4142178.88 | 9944.65 | 0.00 | 0.122895E+10 | 0.00 | 0.30 |
November | 0.281755E+10 | 0.00 | 0.00 | 320707.78 | 0.00 | 0.00 | 0.208370E+09 | 0.00 | 0.20 |
December | 0.270415E+10 | 0.00 | 0.00 | 0.00 | 7535604.10 | 3459711.18 | 0.00 | 0.00 | 0.18 |
Annual Sum or Average | 0.152105E+11 | 0.130855E+11 | 0.00 | 31009867.61 | 20946990.22 | 8374043.47 | 0.614831E+10 | 0.00 | 0.25 |
Minimum of Months | 340370.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.295864E+10 | 0.351829E+10 | 0.00 | 6917857.47 | 7535604.10 | 4914332.29 | 0.157617E+10 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:57
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.376096E+12 | 0.235703E+11 | 0.00 | 0.343453E+10 | 0.162024E+10 |
February | 0.396053E+12 | 0.273479E+11 | 0.00 | 0.422967E+10 | 0.182643E+09 |
March | 0.531911E+12 | 0.334136E+11 | 0.00 | 0.401629E+10 | 0.172967E+10 |
April | 0.690520E+12 | 0.175061E+11 | 0.00 | 0.221934E+10 | 0.228499E+11 |
May | 0.702579E+12 | 0.235704E+11 | 0.00 | 0.371036E+09 | 0.398309E+11 |
June | 0.735626E+12 | 0.256783E+11 | 0.00 | -0.302439E+10 | 0.683620E+11 |
July | 0.673425E+12 | 0.366118E+11 | 0.00 | -0.424780E+10 | 0.704008E+11 |
August | 0.606350E+12 | 0.331757E+11 | 0.00 | -0.426352E+10 | 0.662140E+11 |
September | 0.513260E+12 | 0.280834E+11 | 0.00 | -0.208471E+10 | 0.511648E+11 |
October | 0.463589E+12 | 0.393702E+11 | 0.00 | 0.316315E+10 | 0.189410E+11 |
November | 0.385843E+12 | 0.365225E+11 | 0.00 | 0.481786E+10 | 0.233690E+10 |
December | 0.297666E+12 | 0.298945E+11 | 0.00 | 0.399071E+10 | 0.685746E+09 |
Annual Sum or Average | 0.637292E+13 | 0.354745E+12 | 0.00 | 0.126222E+11 | 0.344319E+12 |
Minimum of Months | 0.297666E+12 | 0.175061E+11 | 0.00 | -0.426352E+10 | 0.182643E+09 |
Maximum of Months | 0.735626E+12 | 0.393702E+11 | 0.00 | 0.481786E+10 | 0.704008E+11 |