Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 10:43:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1050.78 | 217.32 | 217.32 |
Net Site Energy | 1050.78 | 217.32 | 217.32 |
Total Source Energy | 3306.33 | 683.81 | 683.81 |
Net Source Energy | 3306.33 | 683.81 | 683.81 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 10.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1040.47 | 10.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 10.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 12.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 10.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 135.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 51.87 | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 215.19 | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 51.87 | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 215.19 | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1040.466 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1040.466 | 100.00 |
Total On-Site and Utility Electric Sources | 1040.466 | 100.00 |
Total Electricity End Uses | 1040.466 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 18.67 |
Time Setpoint Not Met During Occupied Cooling | 20.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2938.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:00 | 27-DEC-06:19 | - | - | - | - | - | - | - | - | - | - | 28-JUN-11:09 |
Heating | 0.00 | 40569.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12108.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1706.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87417.50 | 40569.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 40569.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9803.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1706.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 11.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 288.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 429.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3295.16 | 11.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 681.50 | 2.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 681.50 | 2.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.44 |
ZONE2 FINE STORAGE DIRECT AIR | 4.38 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.88 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.88 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 66720.52 |
PSZ-OFFICE HEATING COIL | 31402.42 |
PSZ-FINE STORAGE HEATING COIL | 121696.01 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 66720.52 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-FINE STORAGE | 4.38 | 4.38 | 4.38 | 4.38 | 4.38 | 4.38 | 1.00 | 1.00 | 4.38 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.44 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 4.38 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.44 | 1573.28 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 4.38 | 8229.92 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 1.44 | 24346.71 | 31402.42 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 4.38 | 4.38 | 4.38 | 4.38 | 89380.59 | 121696.01 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.44 | 0.718717 | 1.44 | 24346.71 | 12573.74 | 24346.71 | 0.800320 | 0.800320 |
PSZ-FINE STORAGE COOLING COIL | 4.38 | 2.19 | 4.38 | 89380.59 | 45930.58 | 89380.59 | 0.768470 | 0.768470 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6162 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6162 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6162 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.524 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.75489070E-12 | 0.18678307E-15 | -0.24646719E-14 | 0.12171915E-15 |
8 | 3 | -0.37579879E-03 | 0.42795087E-06 | -0.54426377E-04 | 0.14486322E-12 |
9 | 2 | 1.7183777 | 0.94469845E-02 | 1.1243623 | -0.72046233E-04 |
10 | 1 | -7.1567890 | 0.24622403 | -16.995305 | 0.32932838 |
11 | 0 | 5.8520676 | 0.15760904 | 16.284278 | |
12 | 4 | 0.75489070E-12 | 0.18678307E-15 | -0.24646719E-14 | 0.12171915E-15 |
13 | 3 | -0.37579879E-03 | 0.42795087E-06 | -0.54426377E-04 | 0.14486322E-12 |
14 | 2 | 1.7183777 | 0.94469845E-02 | 1.1243623 | -0.72046233E-04 |
15 | 1 | -7.1567890 | 0.24622403 | -16.995305 | 0.32932838 |
16 | 0 | 5.8520676 | 0.15760904 | 16.284278 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.24646719E-14 | 0.18678307E-15 | 0.75489070E-12 | 0.12171915E-15 |
85 | 3 | -0.54426377E-04 | 0.42795087E-06 | -0.37579879E-03 | 0.14486322E-12 |
86 | 2 | 1.1243623 | 0.94469845E-02 | 1.7183777 | -0.72046233E-04 |
87 | 1 | -16.995305 | 0.24622403 | -7.1567890 | 0.32932838 |
88 | 0 | 16.284278 | 0.15760904 | 5.8520676 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6283_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
3 | NONRESWINDOW_U_0.6283_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
4 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.572 | 3.572 | 1.000 | 0.252 | ||
5 | SKYLIGHT_U_0.65_SHGC_0.35 | 38 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.352 | ||
6 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 39 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.352 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15349 | 0.58024 | 0.58024 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.80019E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 3.575 | 0.353 | 0.351 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12627.61247 | 15153.13497 | 1.19786 | 1.43743 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 37.32000 | 6.87023E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9176.23510 | 11011.48212 | 0.29697 | 0.35637 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 49401.67688 | 59282.01226 | 3.65288 | 4.38345 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 27377.96000 | 32853.55200 | 0.74639 | 0.89567 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 55600.43714 | 66720.52457 | 1.56640 | 1.87968 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19392.29 | 1.43743 | 1.43743 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9904.39 | 0.35637 | 0.35637 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 72699.64 | 4.38345 | 4.38345 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 32226.43 | 0.89567 | 0.89567 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43743 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.38345 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.87968 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.87968 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 66720.51901 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 66720.52457 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43743 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43743 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43743 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43743 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43743 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.43743 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.38345 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.38345 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.38345 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 4.38345 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.38345 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 4.38345 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.43743 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 4.38345 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43743 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43743 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1573.27832 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43743 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43743 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43743 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.43743 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43743 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71872 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.43743 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24346.71000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12573.74295 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24346.71000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80032 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80032 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24346.71000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31402.42110 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31402.42110 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.38345 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.38345 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8229.91924 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.38345 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.38345 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.38345 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.38345 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.38345 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.19173 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.38345 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 89380.59000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 45930.58033 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 89380.59000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76847 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76847 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 89380.59000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 121696.00742 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 121696.00742 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23231.2 | 10.74 | 10.12 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 85976.5 | 10.30 | 9.70 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 5.6193262860E-002 | 3.3086555583E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 7.7586102538E-002 | 7.0500302331E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.9175413961E-002 | 3.4287959765E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11536.27 | 529.08 | 0.00 | 75.09 | 393.90 | 12534.41 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.564 | 0.616 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.537 | 0.616 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.537 | 0.616 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.572 | 0.252 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.6283_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.572 | 0.252 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.352 | 0.351 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.353 | 0.351 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.628 | 0.298 | 0.297 | |||||||||||||||||
North Total or Average | 6.51 | 3.572 | 0.252 | 0.251 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.642 | 0.309 | 0.308 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.77 | 83.77 | 134.16 | |
Exterior Lighting Total | 8532.22 | 134.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24346.71 | 19485.16 | 4861.55 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 89380.59 | 68686.30 | 20694.29 | 0.77 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23231.2 | 10.74 | 10.12 | ||||
PSZ-FINE STORAGE COOLING COIL | 85976.5 | 10.30 | 9.70 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 66720.52 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31402.42 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 121696.01 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.88 | 174.64 | 92.91 | 1.00 | 3.62 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.44 | 1573.28 | 1094.51 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.38 | 8229.92 | 1877.50 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12627.61 | 15153.13 | 63.97 | 1.198 | 1.437 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 23.90 | 23.90 | 0.00817 | 37.32 | 0.00687 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 49401.68 | 59282.01 | 42.54 | 3.653 | 4.383 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 26.70 | 26.70 | 0.00807 | 38.10 | 0.00687 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 37.36 | 0.00696 | 37.97 | 0.00687 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9176.24 | 11011.48 | 46.49 | 0.297 | 0.356 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00768 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27377.96 | 32853.55 | 23.58 | 0.746 | 0.896 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00646 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 55600.44 | 66720.52 | 20.82 | 1.566 | 1.880 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00552 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.44 | 1.44 | 0.36 | 0.36 | 1.4374 | 1.4374 | 1.4374 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.38 | 4.38 | 0.90 | 0.90 | 4.3835 | 4.3835 | 4.3835 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 66720.519 | 66720.519 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 66720.52 | 66720.52 | 1.879683 | 10.00 | 6.52 | 0.00551904 | 43.33 | 20.46 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 10.00 | 0.00551904 | 62.9395 | 66720.52 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 24346.710 | 19485.159 | 1.437430 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24346.71 | 24070.25 | 1.437430 | 25.89 | 15.23 | 0.00807955 | 12.00 | 10.01 | 0.00800000 | 37.45 | 0.00687043 | 17.97 | 7.1158 | 23.90 | 0.00817224 | 38.4045 | 12619.49 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31402.421 | 31402.421 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 31402.42 | 31402.42 | 1.437433 | 19.18 | 12.19 | 0.00733261 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.1158 | 21.10 | 0.00767920 | 42.8157 | 9176.24 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 89380.590 | 68686.302 | 4.383450 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 89380.59 | 89380.59 | 4.383450 | 29.57 | 16.34 | 0.00795716 | 12.00 | 9.97 | 0.00795716 | 38.10 | 0.00687148 | 18.17 | 9.6890 | 26.70 | 0.00807364 | 32.1245 | 49401.68 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 121696.007 | 121696.007 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 121696.01 | 121696.01 | 4.383451 | 13.54 | 8.73 | 0.00610508 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 9.6890 | 15.56 | 0.00645876 | 51.0932 | 27377.96 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 66720.519 | 66720.519 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.879683 | 1.96301309 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 66720.52 | 66720.52 | 1.0000 | 1.96301309 | 1.879683 | 10.00 | 6.52 | 0.00551904 | 23951.9 | 43.33 | 20.46 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66720.52 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 10.00 | 0.00551904 | 10.00 | 0.00551904 | 62.9395 | 66720.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24346.710 | 19485.159 | 1.437430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8595 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.437433 | 1.50115690 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 24346.71 | 24070.25 | 1.0000 | 1.50115376 | 1.437430 | 25.89 | 15.23 | 0.00807955 | 46612.3 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24346.71 | 37.45 | 0.00687043 | 17.97 | 0.10228463 | 7.1158 | 23.90 | 0.00817224 | 23.90 | 0.00817224 | 38.4045 | 12619.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31402.421 | 31402.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.437433 | 1.50115690 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 31402.42 | 31402.42 | 1.0000 | 1.50115690 | 1.437433 | 19.18 | 12.19 | 0.00733261 | 37875.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31402.42 | -5.20 | 0.00280840 | -5.20 | 0.10228463 | 7.1158 | 21.05 | 0.00767920 | 21.10 | 0.00767920 | 42.8157 | 9176.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 89380.590 | 68686.302 | 4.383450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6320 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.383451 | 4.57777655 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 89380.59 | 89380.59 | 1.0000 | 4.57777593 | 4.383450 | 29.57 | 16.34 | 0.00795716 | 50048.2 | 12.00 | 9.97 | 0.00795716 | 32136.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89380.59 | 38.10 | 0.00687148 | 18.17 | 0.42471127 | 9.6890 | 26.70 | 0.00807364 | 26.70 | 0.00807364 | 32.1245 | 49401.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 121696.007 | 121696.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 4.383451 | 4.57777655 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 121696.01 | 121696.01 | 1.0000 | 4.57777655 | 4.383451 | 13.54 | 8.73 | 0.00610508 | 29032.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 121696.01 | -5.20 | 0.00280840 | -5.20 | 0.42471127 | 9.6890 | 15.56 | 0.00645876 | 15.56 | 0.00645876 | 51.0932 | 27377.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.44 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 4.38 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2060.67 | 1765.67 | 572.00 |
ZONE2 FINE STORAGE | 2767.83 | 2602.00 | 1877.83 |
ZONE3 BULK STORAGE | 3189.00 | 3262.83 | 2900.00 |
Facility | 3514.00 | 3338.17 | 2938.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 17.83 | 23.17 | 17.83 | 20.50 |
ZONE2 FINE STORAGE | 8.83 | 157.83 | 1.67 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 25.83 | 181.00 | 18.67 | 20.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 1.106 | 0.503 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1.233 | 0.398 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.171 | 0.000 | 0.908 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 3992912.70 | 0.00 | 3992912.70 | 3012676.23 | 7005588.93 | 3225648.14 | 5589.36 | 1875.98 | 1294.66 | 0.46 |
ZONE2 FINE STORAGE | 13444642.00 | 0.00 | 13444642.00 | 11108117.21 | 24552759.21 | 13393694.68 | 5562.45 | 2009.61 | 1187.93 | 52.06 |
ZONE3 BULK STORAGE | 0.00 | 0.20E+09 | 0.20E+09 | 44570327.94 | 0.25E+09 | 30805497.77 | 6712.23 | 30.41 | 2017.36 | 4863.75 |
Total Facility | 17437554.71 | 0.20E+09 | 0.22E+09 | 58691121.38 | 0.28E+09 | 47424840.58 | 7667.12 | 2336.42 | 3455.54 | 4865.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.3049 | 0.0000 | 0.3049 | 0.1390 | 0.4440 | 0.1023 | 465.82 | 1875.98 | 1294.20 |
ZONE2 FINE STORAGE | 0.9842 | 0.0000 | 0.9842 | 0.3191 | 1.3033 | 0.4247 | 490.52 | 2009.61 | 1135.87 |
ZONE3 BULK STORAGE | 0.0000 | 8.5011 | 8.5011 | 1.6443 | 10.1454 | 0.9768 | 2521.31 | 14.92 | 1099.77 |
Total Facility | 1.2891 | 8.5011 | 9.7903 | 2.1024 | 11.8927 | 1.5038 | 2543.12 | 2320.92 | 2493.80 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4354785.45 | 0.00 | 4354785.45 | 3225648.14 | 5588.45 | 0.17 | 3171.39 | 0.46 |
PSZ-FINE STORAGE | 14663113.32 | 0.00 | 14663113.32 | 13393694.68 | 5562.12 | 0.25 | 3197.63 | 52.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3326 | 0.0000 | 0.3326 | 0.1023 | 464.91 | 0.17 | 3170.93 |
PSZ-FINE STORAGE | 1.0734 | 0.0000 | 1.0734 | 0.4247 | 490.18 | 0.25 | 3145.57 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2488.00 | 690.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2694.44 | 506.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3530 | 0.4800 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 1.1549 | 1.6841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1040.47 | 5771.67 | 01-JAN-07:30 | 87417.50 | 15-JUN-15:00 |
Electricity:Building | 667.62 | 5288.67 | 01-JAN-00:10 | 50600.89 | 21-APR-14:10 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 360.68 | 2117.83 | 01-JAN-00:10 | 28507.00 | 21-APR-14:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 135.60 | 0.00 | 01-JAN-00:10 | 12108.49 | 11-MAY-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.13 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-MAY-14:50 |
Ventilation (simple):Fans:Electricity | 12.13 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-MAY-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.13 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-MAY-14:50 |
ElectricityPurchased:Facility | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
ElectricityPurchased:Plant | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
ElectricityNet:Plant | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
Cogeneration:ElectricityNet | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1040.47 | 5771.67 | 07-MAY-11:10 | 87417.50 | 15-JUN-15:00 |
Electricity:HVAC | 214.43 | 0.00 | 01-JAN-00:10 | 37048.18 | 15-JUN-15:10 |
General:Fans:Electricity | 123.46 | 0.00 | 01-JAN-00:10 | 9803.20 | 02-JAN-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 90.97 | 0.00 | 01-JAN-00:10 | 27244.98 | 15-JUN-15:10 |
General:Cooling:Electricity | 90.97 | 0.00 | 01-JAN-00:10 | 27244.98 | 15-JUN-15:10 |
ExteriorLights:Electricity | 134.16 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.16 | 0.00 | 01-JAN-07:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 24.26 | 483.00 | 04-JAN-06:10 | 1973.40 | 27-JAN-12:30 |
WaterSystems:Electricity | 24.26 | 483.00 | 04-JAN-06:10 | 1973.40 | 27-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 24.26 | 483.00 | 04-JAN-06:10 | 1973.40 | 27-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 10.31 | 0.00 | 01-JAN-00:10 | 40569.19 | 27-DEC-06:20 |
NaturalGas:HVAC | 10.31 | 0.00 | 01-JAN-00:10 | 40569.19 | 27-DEC-06:20 |
Heating:NaturalGas | 10.31 | 0.00 | 01-JAN-00:10 | 40569.19 | 27-DEC-06:20 |
General:Heating:NaturalGas | 10.31 | 0.00 | 01-JAN-00:10 | 40569.19 | 27-DEC-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 572.27 | 0.00 | 01-JAN-00:10 | 134483.29 | 15-JUN-15:10 |
EnergyTransfer:Building | 265.68 | 0.00 | 01-JAN-00:10 | 58985.80 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 64.12 | 0.00 | 01-JAN-00:10 | 16504.26 | 27-DEC-07:10 |
Heating:EnergyTransfer | 24.55 | 0.00 | 01-JAN-00:10 | 30050.03 | 27-DEC-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 6.42 | 0.00 | 01-JAN-00:10 | 16504.26 | 27-DEC-07:10 |
General:Heating:EnergyTransfer | 24.55 | 0.00 | 01-JAN-00:10 | 30050.03 | 27-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 6.42 | 0.00 | 01-JAN-00:10 | 16504.26 | 27-DEC-07:10 |
Cooling:EnergyTransfer | 241.13 | 0.00 | 01-JAN-00:10 | 58985.80 | 15-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 57.70 | 0.00 | 01-JAN-00:10 | 15246.69 | 05-JUN-17:00 |
General:Cooling:EnergyTransfer | 241.13 | 0.00 | 01-JAN-00:10 | 58985.80 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 57.70 | 0.00 | 01-JAN-00:10 | 15246.69 | 05-JUN-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 201.56 | 0.00 | 01-JAN-00:10 | 46101.58 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.13 | 0.00 | 01-JAN-00:10 | 18056.24 | 26-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.13 | 0.00 | 01-JAN-00:10 | 18056.24 | 26-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 183.43 | 0.00 | 01-JAN-00:10 | 46101.58 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 183.43 | 0.00 | 01-JAN-00:10 | 46101.58 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 306.59 | 0.00 | 01-JAN-00:10 | 75497.49 | 15-JUN-15:10 |
HeatingCoils:EnergyTransfer | 6.99 | 0.00 | 01-JAN-00:10 | 29023.34 | 28-JAN-06:10 |
CoolingCoils:EnergyTransfer | 299.61 | 0.00 | 01-JAN-00:10 | 75497.49 | 15-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 6.420 | -57.695 | 0.000 | 0.000 | 9.355 | 30.293 | 31.946 | 11.536 | 0.000 | 4.102 | 0.000 | 0.000 | -9.246 | 0.000 | -19.974 | -6.736 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 18.133 | -183.421 | 0.000 | 0.000 | 19.189 | 244.699 | 0.000 | 0.000 | 0.000 | 9.569 | 0.000 | 0.000 | 0.000 | 0.000 | -71.343 | -36.825 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44.840 | 241.203 | 107.344 | 117.716 | 0.000 | 30.104 | 0.004 | 0.000 | -40.341 | 0.000 | -438.687 | -62.178 |
Total Facility | 0.000 | 0.000 | 24.552 | -241.116 | 0.000 | 0.000 | 73.385 | 516.195 | 139.290 | 129.252 | 0.000 | 43.775 | 0.004 | 0.000 | -49.587 | 0.000 | -530.005 | -105.740 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -32542.27 | 0.00 | 0.00 | 87.26 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 32567.34 | 0.00 | -846.71 | 0.00 | -412.55 | 0.00 |
ZONE2 FINE STORAGE | 24-SEP-13:01 | 0.00 | 0.00 | 0.00 | -86948.50 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 85906.26 | 0.00 | -0.00 | 0.00 | -1106.28 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 | -100382.59 | 0.00 | 0.00 | 575.98 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 103260.64 | 0.00 | -2587.16 | 0.00 | -8330.19 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-DEC-06:01 | 0.00 | 0.00 | 31653.37 | 0.00 | 0.00 | 0.00 | 146.90 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -794.50 | 0.00 | -2321.96 | -29830.74 |
ZONE2 FINE STORAGE | 28-JAN-06:01 | 0.00 | 0.00 | 88635.13 | 0.00 | 0.00 | 0.00 | 362.37 | 2148.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10213.84 | -80932.19 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-JAN-06:01 | 0.00 | 0.00 | 120204.71 | 0.00 | 0.00 | 0.00 | 1415.77 | 4839.54 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5554.50 | 0.00 | -46103.94 | -77425.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.4374 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.4374 | 0.0712 | 1.0000 | Not calculated | 0.1023 | 0.0712 | ||
PSZ-FINE STORAGE | 4.3835 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 4.3835 | 0.0969 | 1.0000 | Not calculated | 0.4247 | 0.0969 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.4374 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.4374 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0712 | ||
PSZ-FINE STORAGE | 4.3835 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 4.3835 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0969 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4374 | 1.4374 | 1.4374 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3835 | 4.3835 | 4.3835 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.4374 | 1.4374 | 1.4374 | 1.4374 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 4.3835 | 4.3835 | 4.3835 | 4.3835 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4374 | 1.4374 | 1.4374 | No | 0.1023 | 0.2870 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3835 | 4.3835 | 4.3835 | No | 0.4247 | 0.4742 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.4374 | 1.4374 | 1.4374 | 1.4374 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 4.3835 | 4.3835 | 4.3835 | 4.3835 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 18.67 |
Number of hours cooling loads not met | 20.50 |
Number of hours not met | 39.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 10.31 | 40569.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 90.97 | 27244.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.16 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 12.13 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 123.46 | 9803.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.26 | 1973.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1040.47 |
Natural Gas | 0.00 | 10.31 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1050.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 18.81 |
Fans (All) | 28.04 |
Service Water Heating | 5.02 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 215.19 |
Subtotal | 215.19 |
Natural Gas [MJ/m2] | |
Space Heating | 2.13 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 2.13 |
Subtotal | 2.13 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 49.13 |
Space Heating | 0.98 |
Space Cooling | 8.66 |
Fans (All) | 12.90 |
Service Water Heating | 2.31 |
Receptacle Equipment | 13.26 |
Miscellaneous | 12.77 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7025.83 | 1734.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7677.33 | 1082.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5239.00 | 3339.17 | 181.83 | 0.00 | 0.00 |
Min | 5239.00 | 1082.67 | 0.00 | 0.00 | 0.00 |
Max | 7677.33 | 3339.17 | 181.83 | 0.00 | 0.00 |
Average | 6647.39 | 2052.00 | 60.61 | 0.00 | 0.00 |
Sum | 19942.17 | 6156.00 | 181.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70184.00 | 12535.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 108504.33 | 74921.83 | 7766.83 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 108504.33 | 74921.83 | 7766.83 | 0.00 | 0.00 |
Average | 70571.78 | 29152.28 | 2588.94 | 0.00 | 0.00 |
Sum | 211715.33 | 87456.83 | 7766.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7396.17 | 1363.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7396.17 | 1363.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5807.33 | 2952.67 | 0.00 | 0.00 | 0.00 |
Min | 5807.33 | 1363.83 | 0.00 | 0.00 | 0.00 |
Max | 7396.17 | 2952.67 | 0.00 | 0.00 | 0.00 |
Average | 6866.56 | 1893.44 | 0.00 | 0.00 | 0.00 |
Sum | 20599.67 | 5680.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32853.00 | 174.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 67572.50 | 15146.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 120494.83 | 70698.17 | 0.00 | 0.00 | 0.00 |
Min | 32853.00 | 174.00 | 0.00 | 0.00 | 0.00 |
Max | 120494.83 | 70698.17 | 0.00 | 0.00 | 0.00 |
Average | 73640.11 | 28672.89 | 0.00 | 0.00 | 0.00 |
Sum | 220920.33 | 86018.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257964E+09 | 3179.65 | 12-JAN-15:30 | 18.90 | 10.10 | 0.565676E+09 | 768.97 | 31-JAN-16:40 | 15.60 | 5.14 |
February | 0.554882E+09 | 3842.40 | 23-FEB-14:30 | 21.65 | 7.41 | 0.538297E+09 | 768.97 | 06-FEB-13:09 | 21.65 | 7.41 |
March | 0.159159E+10 | 5175.16 | 14-MAR-16:00 | 24.40 | 10.33 | 0.657445E+09 | 768.96 | 06-MAR-16:10 | 24.40 | 10.33 |
April | 0.425623E+10 | 29247.29 | 28-APR-05:02 | 14.22 | 8.86 | 0.630624E+09 | 769.03 | 29-APR-08:00 | 22.20 | 14.12 |
May | 0.725737E+10 | 32229.99 | 17-MAY-05:01 | 14.08 | 5.19 | 0.659732E+09 | 769.07 | 24-MAY-15:09 | 28.58 | 18.02 |
June | 0.953764E+10 | 31593.58 | 13-JUN-05:01 | 15.18 | 4.59 | 0.660248E+09 | 769.07 | 19-JUN-08:50 | 26.83 | 17.78 |
July | 0.935951E+10 | 24808.85 | 11-JUL-05:01 | 21.70 | 15.06 | 0.635046E+09 | 769.09 | 17-JUL-15:00 | 30.60 | 21.38 |
August | 0.953203E+10 | 27555.61 | 23-AUG-05:01 | 20.00 | 11.78 | 0.685736E+09 | 769.08 | 03-AUG-12:09 | 20.00 | 11.78 |
September | 0.804725E+10 | 32545.32 | 30-SEP-05:02 | 9.72 | 6.50 | 0.634902E+09 | 769.07 | 06-SEP-12:09 | 9.72 | 6.50 |
October | 0.514953E+10 | 29796.85 | 20-OCT-05:03 | 11.60 | 7.28 | 0.633265E+09 | 769.07 | 04-OCT-13:50 | 11.60 | 7.28 |
November | 0.181767E+10 | 6529.17 | 03-NOV-16:00 | 23.90 | 13.45 | 0.588417E+09 | 769.01 | 03-NOV-12:00 | 23.90 | 13.45 |
December | 0.334717E+09 | 3284.52 | 16-DEC-16:00 | 15.00 | 4.18 | 0.569287E+09 | 768.97 | 01-DEC-16:19 | 15.00 | 4.18 |
Annual Sum or Average | 0.576964E+11 | 0.745868E+10 | ||||||||
Minimum of Months | 0.257964E+09 | 3179.65 | 9.72 | 4.18 | 0.538297E+09 | 768.96 | 9.72 | 4.18 | ||
Maximum of Months | 0.953764E+10 | 32545.32 | 24.40 | 15.06 | 0.685736E+09 | 769.09 | 30.60 | 21.38 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10596696.82 | 1643.41 | 27-JAN-09:10 | -1.2 | -5.7 | 0.127422E+10 | 2246.80 | 12-JAN-15:39 | -1.2 | -5.7 |
February | 55971752.71 | 4247.74 | 22-FEB-14:00 | 21.70 | 7.92 | 0.131016E+10 | 2246.80 | 21-FEB-15:50 | 21.70 | 7.92 |
March | 0.777298E+09 | 9971.08 | 16-MAR-15:00 | 22.80 | 8.72 | 0.174613E+10 | 2246.81 | 30-MAR-13:09 | 17.98 | 6.08 |
April | 0.102000E+11 | 85827.80 | 23-APR-14:51 | 22.20 | 8.25 | 0.180883E+10 | 2246.90 | 29-APR-09:30 | 23.05 | 14.28 |
May | 0.238511E+11 | 79817.36 | 20-MAY-21:21 | 24.70 | 10.95 | 0.192095E+10 | 2246.99 | 23-MAY-14:20 | 27.43 | 16.86 |
June | 0.371168E+11 | 81409.21 | 26-JUN-23:51 | 24.40 | 15.32 | 0.192820E+10 | 2247.06 | 28-JUN-14:20 | 27.40 | 17.31 |
July | 0.365982E+11 | 77953.32 | 16-JUL-01:21 | 26.10 | 15.85 | 0.185455E+10 | 2247.09 | 27-JUL-12:20 | 32.97 | 20.77 |
August | 0.345215E+11 | 80067.82 | 23-AUG-01:18 | 23.67 | 12.39 | 0.200228E+10 | 2247.10 | 02-AUG-14:09 | 23.67 | 12.39 |
September | 0.267407E+11 | 86963.28 | 24-SEP-13:01 | 22.98 | 12.49 | 0.185261E+10 | 2247.09 | 09-SEP-13:50 | 22.98 | 12.49 |
October | 0.121957E+11 | 86841.71 | 01-OCT-09:11 | 22.93 | 13.06 | 0.182739E+10 | 2247.10 | 04-OCT-14:30 | 30.00 | 19.20 |
November | 0.132864E+10 | 15231.58 | 03-NOV-15:00 | 23.30 | 13.57 | 0.157258E+10 | 2246.85 | 03-NOV-13:30 | 23.30 | 13.57 |
December | 32254442.39 | 1483.71 | 22-DEC-08:45 | 0.22 | -2.7 | 0.127809E+10 | 2129.95 | 16-DEC-15:39 | 0.22 | -2.7 |
Annual Sum or Average | 0.183429E+12 | 0.203760E+11 | ||||||||
Minimum of Months | 10596696.82 | 1483.71 | -1.2 | -5.7 | 0.127422E+10 | 2129.95 | -1.2 | -5.7 | ||
Maximum of Months | 0.371168E+11 | 86963.28 | 26.10 | 15.85 | 0.200228E+10 | 2247.10 | 32.97 | 20.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.158637E+10 | 2917.26 | 03-JAN-15:20 | 20.40 | 8.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.161565E+10 | 3293.72 | 23-FEB-14:39 | 21.47 | 7.31 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.251060E+10 | 3982.41 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.366019E+10 | 6972.50 | 21-APR-14:00 | 32.20 | 15.49 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.518541E+10 | 8392.58 | 19-MAY-14:20 | 34.80 | 17.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 | 11.56 | 0.622303E+10 | 9097.65 | 02-JUN-13:09 | 36.88 | 15.22 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 | 17.07 | 0.577842E+10 | 9097.65 | 01-JUL-13:50 | 37.02 | 19.85 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 | 18.12 | 0.600989E+10 | 9097.65 | 07-AUG-15:50 | 36.83 | 18.06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.531602E+10 | 8104.29 | 19-SEP-14:20 | 33.70 | 16.73 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.420193E+10 | 7533.98 | 03-OCT-14:20 | 32.43 | 19.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.252950E+10 | 4876.34 | 03-NOV-15:20 | 23.50 | 13.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.154309E+10 | 2505.68 | 16-DEC-15:39 | 15.00 | 4.18 |
Annual Sum or Average | 0.00 | 0.461601E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.154309E+10 | 2505.68 | 15.00 | 4.18 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.622303E+10 | 9097.65 | 37.02 | 19.85 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179118E+10 | 31609.12 | 27-JAN-06:01 | -3.1 |
February | 0.120501E+10 | 31616.36 | 02-FEB-06:01 | -3.5 |
March | 0.787894E+09 | 31621.60 | 02-MAR-06:01 | -3.5 |
April | 0.155801E+09 | 17404.28 | 11-APR-05:03 | 4.90 |
May | 36397647.17 | 5707.45 | 27-MAY-05:50 | 16.23 |
June | 5264175.31 | 1513.58 | 01-JUN-05:50 | 18.98 |
July | 2669125.25 | 1967.97 | 14-JUL-06:05 | 21.88 |
August | 6375592.36 | 2243.60 | 28-AUG-06:05 | 20.37 |
September | 11222748.32 | 1706.91 | 25-SEP-06:07 | 10.55 |
October | 98469421.35 | 2248.33 | 19-OCT-05:50 | 17.88 |
November | 0.571540E+09 | 31604.12 | 28-NOV-06:01 | 1.02 |
December | 0.174791E+10 | 31653.41 | 26-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.641973E+10 | |||
Minimum of Months | 2669125.25 | 1513.58 | -3.5 | |
Maximum of Months | 0.179118E+10 | 31653.41 | 21.88 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383504E+10 | 88635.15 | 28-JAN-06:01 | -3.3 |
February | 0.338818E+10 | 52354.75 | 03-FEB-06:01 | -3.7 |
March | 0.269143E+10 | 37556.42 | 02-MAR-06:01 | -3.5 |
April | 0.926338E+09 | 8316.79 | 04-APR-06:25 | 11.95 |
May | 0.301966E+09 | 8215.08 | 01-MAY-06:25 | 14.70 |
June | 12879667.57 | 7230.64 | 01-JUN-06:02 | 19.37 |
July | 5244908.17 | 6954.23 | 05-JUL-06:03 | 18.07 |
August | 18098260.60 | 7586.49 | 17-AUG-06:13 | 17.40 |
September | 0.110819E+09 | 8058.15 | 25-SEP-06:25 | 11.65 |
October | 0.730987E+09 | 8354.45 | 13-OCT-06:25 | 14.40 |
November | 0.206023E+10 | 20835.77 | 28-NOV-05:05 | -0.3 |
December | 0.405153E+10 | 64580.99 | 30-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.181328E+11 | |||
Minimum of Months | 5244908.17 | 6954.23 | -3.7 | |
Maximum of Months | 0.405153E+10 | 88635.15 | 19.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319231E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273746E+10 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3534968.25 | 0.279187E+10 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246151E+09 | 0.156179E+10 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608686E+09 | 0.858164E+09 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113868E+10 | 0.346374E+09 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857305E+09 | 0.288629E+09 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730081E+09 | 0.422141E+09 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418621E+09 | 0.545631E+09 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99278779.25 | 0.151966E+10 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262354E+10 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308676E+10 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410234E+10 | 0.199743E+11 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288629E+09 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113868E+10 | 0.319231E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984606E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914224E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105477E+11 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420021E+09 | 0.680499E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149349E+10 | 0.408351E+10 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306885E+10 | 0.144995E+10 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222212E+10 | 0.117986E+10 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175122E+10 | 0.168211E+10 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478471E+09 | 0.203411E+10 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134587E+09 | 0.636719E+10 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942835E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877739E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956876E+10 | 0.713435E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117986E+10 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306885E+10 | 0.105477E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48194222.97 | 0.231241E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999415E+09 | 0.195444E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831645E+09 | 0.236194E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219638E+10 | 0.204147E+11 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271870E+09 | 0.193797E+11 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438035E+09 | 0.105464E+11 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211394E+09 | 0.933442E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115005E+09 | 0.110735E+11 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12579040.55 | 0.113812E+11 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26408591.63 | 0.244960E+11 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10327599.20 | 0.263877E+11 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28871536.38 | 0.207264E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519012E+10 | 0.220028E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10327599.20 | 0.933442E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219638E+10 | 0.263877E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10742.07 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 10441.58 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 431.60 | 21-MAR-16:10 | 9517.86 | 27-MAR-06:55 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4200.56 | 21-APR-16:10 | 6467.16 | 11-APR-06:03 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5042.90 | 19-MAY-17:00 | 5424.71 | 02-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6602.52 | 05-JUN-17:00 | 2506.04 | 29-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6186.92 | 03-JUL-17:00 | 2324.87 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5301.17 | 07-AUG-16:10 | 2745.70 | 31-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3291.06 | 18-SEP-17:00 | 4863.34 | 25-SEP-06:03 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2834.05 | 05-OCT-16:10 | 6027.86 | 25-OCT-06:05 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8747.55 | 28-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10183.00 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2324.87 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 6602.52 | 10742.07 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 17803.80 | 25-JAN-16:03 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 29019.38 | 08-FEB-17:55 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 22033.17 | 27-MAR-06:55 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10262.49 | 21-APR-15:10 | 23832.45 | 22-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8861.35 | 19-MAY-17:00 | 13107.99 | 01-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12642.52 | 05-JUN-17:00 | 8827.53 | 28-JUN-02:00 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10060.25 | 03-JUL-17:00 | 6130.19 | 18-JUL-21:00 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8755.39 | 26-AUG-15:10 | 7109.52 | 14-AUG-01:00 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2894.43 | 18-SEP-17:00 | 6454.94 | 23-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3460.33 | 01-OCT-14:52 | 12531.56 | 06-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17325.56 | 15-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18146.75 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6130.19 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12642.52 | 29019.38 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6775.72 | 03-JAN-17:00 | 33649.72 | 05-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11480.31 | 06-FEB-13:10 | 50739.12 | 09-FEB-01:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18307.23 | 03-MAR-16:00 | 53784.07 | 27-MAR-07:10 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23519.83 | 01-APR-15:00 | 69943.33 | 22-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6286.89 | 08-MAY-13:00 | 39610.24 | 01-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3816.02 | 05-JUN-17:00 | 36945.65 | 28-JUN-02:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.06 | 02-JUL-21:42 | 27500.88 | 08-JUL-14:52 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2760.63 | 07-AUG-16:00 | 29672.84 | 14-AUG-01:00 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.81 | 10-SEP-14:53 | 21989.64 | 23-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.68 | 01-OCT-14:52 | 47908.94 | 06-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1652.65 | 23-NOV-16:00 | 41249.63 | 15-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129.58 | 10-DEC-15:00 | 43407.66 | 18-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.81 | 21989.64 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23519.83 | 69943.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3179.65 | 12-JAN-15:30 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.13 |
February | 3842.40 | 23-FEB-14:30 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.46 |
March | 5175.16 | 14-MAR-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 | 0.00 |
April | 29247.29 | 28-APR-05:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.91 |
May | 32229.99 | 17-MAY-05:01 | 1479.21 | 4585.41 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.46 |
June | 31593.58 | 13-JUN-05:01 | 1664.11 | 5158.58 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.11 |
July | 24808.85 | 11-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.48 |
August | 27555.61 | 23-AUG-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.84 |
September | 32545.32 | 30-SEP-05:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.55 |
October | 29796.85 | 20-OCT-05:03 | 739.61 | 2292.70 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.29 |
November | 6529.17 | 03-NOV-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
December | 3284.52 | 16-DEC-16:00 | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3179.65 | 739.61 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32545.32 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 | 1133.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1643.41 | 27-JAN-09:10 | 7911.00 | 36524.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3996.03 |
February | 4247.74 | 22-FEB-14:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9971.08 | 16-MAR-15:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2304.91 |
April | 85827.80 | 23-APR-14:51 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79817.36 | 20-MAY-21:21 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.48 |
June | 81409.21 | 26-JUN-23:51 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.47 |
July | 77953.32 | 16-JUL-01:21 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.35 |
August | 80067.82 | 23-AUG-01:18 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.05 |
September | 86963.28 | 24-SEP-13:01 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.28 |
October | 86841.71 | 01-OCT-09:11 | 0.00 | 21485.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15231.58 | 03-NOV-15:00 | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1483.71 | 22-DEC-08:45 | 7911.00 | 32227.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1483.71 | 0.00 | 10742.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86963.28 | 7911.00 | 36524.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3996.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9399.18 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17134.54 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12131.43 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5491.49 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5034.51 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 8471.33 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9585.05 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.50 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 4235.67 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2545.25 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9607.38 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4060.96 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14081.37 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5491.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.50 | |
Maximum of Months | 0.00 | 0.00 | 8471.33 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17134.54 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.796028E+11 | 59877.42 | 30-JAN-13:09 | 0.306125E+10 | 39169.49 | 28-JAN-06:10 |
February | 0.721336E+11 | 60951.70 | 21-FEB-15:50 | 0.180777E+10 | 34097.20 | 02-FEB-06:10 |
March | 0.822634E+11 | 64603.90 | 22-MAR-13:09 | 0.881908E+09 | 29002.52 | 02-MAR-06:10 |
April | 0.807445E+11 | 78639.55 | 21-APR-14:39 | 58818532.57 | 6140.93 | 13-APR-06:10 |
May | 0.914966E+11 | 82447.11 | 19-MAY-13:00 | 5038643.06 | 3960.07 | 27-MAY-05:49 |
June | 0.100387E+12 | 87417.50 | 15-JUN-14:00 | 922972.63 | 1072.64 | 01-JUN-05:49 |
July | 0.100547E+12 | 85913.05 | 26-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.101818E+12 | 84019.91 | 04-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.921104E+11 | 81614.73 | 01-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.830990E+11 | 80625.17 | 03-OCT-14:09 | 945142.13 | 1575.24 | 19-OCT-05:49 |
November | 0.764579E+11 | 65253.80 | 03-NOV-14:50 | 0.633866E+09 | 24728.34 | 28-NOV-06:10 |
December | 0.798063E+11 | 63969.42 | 18-DEC-16:00 | 0.386110E+10 | 40569.19 | 27-DEC-06:19 |
Annual Sum or Average | 0.104047E+13 | 0.103116E+11 | ||||
Minimum of Months | 0.721336E+11 | 59877.42 | 0.00 | 0.00 | ||
Maximum of Months | 0.101818E+12 | 87417.50 | 0.386110E+10 | 40569.19 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.131772E+11 | 0.115358E+11 | 0.00 | 0.978014E+10 | 0.00 | 0.00 | 310.79 | 0.00 | 0.00 | 0.00 | 0.215910E+10 | 0.00 |
February | 0.393028E+11 | 0.112728E+11 | 0.105871E+11 | 0.00 | 0.896933E+10 | 0.00 | 0.00 | 40795920.34 | 0.00 | 0.00 | 0.00 | 0.196082E+10 | 0.00 |
March | 0.453764E+11 | 0.115850E+11 | 0.123431E+11 | 0.00 | 0.104944E+11 | 0.00 | 0.00 | 0.282978E+09 | 0.00 | 0.00 | 0.00 | 0.218145E+10 | 0.00 |
April | 0.425433E+11 | 0.103103E+11 | 0.114862E+11 | 0.00 | 0.991695E+10 | 0.00 | 0.00 | 0.446303E+10 | 0.00 | 0.00 | 0.00 | 0.202471E+10 | 0.00 |
May | 0.441635E+11 | 0.988031E+10 | 0.119357E+11 | 0.00 | 0.121221E+11 | 0.00 | 0.00 | 0.113601E+11 | 0.00 | 0.00 | 0.00 | 0.203482E+10 | 0.00 |
June | 0.437562E+11 | 0.917384E+10 | 0.118862E+11 | 0.00 | 0.146194E+11 | 0.00 | 0.00 | 0.190167E+11 | 0.00 | 0.00 | 0.00 | 0.193447E+10 | 0.00 |
July | 0.429506E+11 | 0.964994E+10 | 0.115358E+11 | 0.00 | 0.143053E+11 | 0.00 | 0.00 | 0.201777E+11 | 0.00 | 0.00 | 0.00 | 0.192778E+10 | 0.00 |
August | 0.453764E+11 | 0.103103E+11 | 0.123357E+11 | 0.00 | 0.142413E+11 | 0.00 | 0.00 | 0.175834E+11 | 0.00 | 0.00 | 0.00 | 0.197078E+10 | 0.00 |
September | 0.425433E+11 | 0.108120E+11 | 0.114788E+11 | 0.00 | 0.119202E+11 | 0.00 | 0.00 | 0.134415E+11 | 0.00 | 0.00 | 0.00 | 0.191448E+10 | 0.00 |
October | 0.429506E+11 | 0.121123E+11 | 0.115432E+11 | 0.00 | 0.100819E+11 | 0.00 | 0.00 | 0.439759E+10 | 0.00 | 0.00 | 0.00 | 0.201333E+10 | 0.00 |
November | 0.413304E+11 | 0.125065E+11 | 0.110862E+11 | 0.00 | 0.932709E+10 | 0.00 | 0.00 | 0.204080E+09 | 0.00 | 0.00 | 0.00 | 0.200357E+10 | 0.00 |
December | 0.429506E+11 | 0.133717E+11 | 0.115358E+11 | 0.00 | 0.981789E+10 | 0.00 | 0.00 | 378.25 | 0.00 | 0.00 | 0.00 | 0.213028E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134162E+12 | 0.139290E+12 | 0.00 | 0.135596E+12 | 0.00 | 0.00 | 0.909679E+11 | 0.00 | 0.00 | 0.00 | 0.242556E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.917384E+10 | 0.105871E+11 | 0.00 | 0.896933E+10 | 0.00 | 0.00 | 310.79 | 0.00 | 0.00 | 0.00 | 0.191448E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.133717E+11 | 0.123431E+11 | 0.00 | 0.146194E+11 | 0.00 | 0.00 | 0.201777E+11 | 0.00 | 0.00 | 0.00 | 0.218145E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.306125E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.180777E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.881908E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 58818532.57 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 5038643.06 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 922972.63 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 945142.13 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.633866E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.386110E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103116E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.386110E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 9803.20 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 9803.20 | 01-FEB-07:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 9803.20 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 12108.49 | 21-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 12108.49 | 11-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 12108.49 | 01-JUN-09:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 12108.49 | 07-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 12108.49 | 01-AUG-08:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 12108.49 | 20-SEP-12:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 12108.49 | 04-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 9803.20 | 01-NOV-08:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 9803.20 | 01-DEC-07:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 9803.20 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 12108.49 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.13 | 03-JAN-13:20 | 0.00 | 0.00 | 0.00 | 1973.40 | 27-JAN-12:30 | 0.00 |
February | 1095.70 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1962.48 | 09-FEB-12:20 | 0.00 |
March | 4813.39 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 1884.02 | 01-MAR-12:20 | 0.00 |
April | 18206.20 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1792.43 | 01-APR-11:09 | 0.00 |
May | 21075.64 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1767.39 | 01-MAY-11:39 | 0.00 |
June | 27244.98 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1742.58 | 01-JUN-11:30 | 0.00 |
July | 23815.09 | 26-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1725.43 | 01-JUL-11:20 | 0.00 |
August | 24665.24 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1725.66 | 31-AUG-11:00 | 0.00 |
September | 19690.96 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1742.81 | 30-SEP-11:20 | 0.00 |
October | 18683.15 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1767.43 | 31-OCT-11:09 | 0.00 |
November | 5571.51 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1792.43 | 29-NOV-12:30 | 0.00 |
December | 0.45 | 29-DEC-16:40 | 0.00 | 0.00 | 0.00 | 1811.80 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.13 | 0.00 | 0.00 | 0.00 | 1725.43 | 0.00 | ||
Maximum of Months | 27244.98 | 0.00 | 0.00 | 0.00 | 1973.40 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 59877.42 | 30-JAN-13:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9803.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60951.70 | 21-FEB-15:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9803.20 | 0.00 | 0.00 | 1078.81 | 0.00 |
March | 64603.90 | 22-MAR-13:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9803.20 | 0.00 | 0.00 | 4778.93 | 0.00 |
April | 78639.55 | 21-APR-14:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 16494.03 | 0.00 |
May | 82447.11 | 19-MAY-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 20349.87 | 0.00 |
June | 87417.50 | 15-JUN-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 25307.33 | 0.00 |
July | 85913.05 | 26-JUL-14:20 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 23815.09 | 0.00 |
August | 84019.91 | 04-AUG-14:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 21922.08 | 0.00 |
September | 81614.73 | 01-SEP-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 19511.29 | 0.00 |
October | 80625.17 | 03-OCT-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 12108.49 | 0.00 | 0.00 | 18505.38 | 0.00 |
November | 65253.80 | 03-NOV-14:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 9803.20 | 0.00 | 0.00 | 5418.35 | 0.00 |
December | 63969.42 | 18-DEC-16:00 | 33916.61 | 10112.62 | 8532.22 | 0.00 | 9803.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 59877.42 | 33916.61 | 10112.62 | 0.00 | 0.00 | 9803.20 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87417.50 | 38182.97 | 10112.62 | 8532.22 | 0.00 | 12108.49 | 0.00 | 0.00 | 25307.33 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 39169.49 | 28-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 34097.20 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 29002.52 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6140.93 | 13-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3960.07 | 27-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1072.64 | 01-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1575.24 | 19-OCT-05:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 24728.34 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 40569.19 | 27-DEC-06:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 40569.19 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 19.96 | 5.17 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
February | 3.83 | 20.09 | 3.83 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
March | 2.17 | 20.31 | 2.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
April | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.17 | 1.33 | 24.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.89 | 4.17 | 24.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.27 | 5.83 | 25.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.96 | 5.00 | 25.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.84 | 3.50 | 24.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.67 | 24.56 |
November | 1.50 | 20.27 | 1.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
December | 4.83 | 19.96 | 4.83 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
Annual Sum or Average | 17.83 | 20.07 | 17.83 | 20.07 | 23.17 | 22.13 | 20.50 | 22.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 0.00 | 19.96 |
Maximum of Months | 5.17 | 20.54 | 5.17 | 20.54 | 6.50 | 25.96 | 5.83 | 25.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 14.89 | 0.67 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 1.33 | 14.95 | 0.33 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.47 | 0.00 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.68 | 0.00 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 27.74 | 0.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 27.70 | 0.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 27.69 | 0.00 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.64 | 0.00 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.52 | 0.00 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.33 | 14.87 | 0.67 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
Annual Sum or Average | 8.83 | 14.89 | 1.67 | 14.87 | 157.83 | 26.89 | 0.00 | 26.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 14.95 | 0.67 | 14.95 | 46.00 | 27.74 | 0.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 22.29 | 137.50 | 21.94 | 137.50 | 21.76 |
February | 276.00 | 22.65 | 90.33 | 22.29 | 90.33 | 22.06 |
March | 323.33 | 23.11 | 66.50 | 22.78 | 66.50 | 22.54 |
April | 146.17 | 23.51 | 50.17 | 23.52 | 6.67 | 23.44 |
May | 33.00 | 23.49 | 183.67 | 23.84 | 0.00 | 23.84 |
June | 1.50 | 22.13 | 285.00 | 23.90 | 0.00 | 23.90 |
July | 48.83 | 23.91 | 300.00 | 23.90 | 48.83 | 23.90 |
August | 20.33 | 23.86 | 322.00 | 23.90 | 19.83 | 23.90 |
September | 21.00 | 23.88 | 279.67 | 23.90 | 20.50 | 23.90 |
October | 53.33 | 23.49 | 156.83 | 23.80 | 5.00 | 23.80 |
November | 242.17 | 23.08 | 54.50 | 22.83 | 42.33 | 22.62 |
December | 300.00 | 22.34 | 134.50 | 21.98 | 134.50 | 21.78 |
Annual Sum or Average | 1765.67 | 22.85 | 2060.67 | 23.08 | 572.00 | 22.89 |
Minimum of Months | 1.50 | 22.13 | 50.17 | 21.94 | 0.00 | 21.76 |
Maximum of Months | 323.33 | 23.91 | 322.00 | 23.90 | 137.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.17 | 21.11 | 138.83 | 20.38 | 135.33 | 19.96 |
February | 233.50 | 21.85 | 104.83 | 21.32 | 87.17 | 20.80 |
March | 160.50 | 21.95 | 187.67 | 23.14 | 64.67 | 22.56 |
April | 86.00 | 24.54 | 237.17 | 26.00 | 40.17 | 25.98 |
May | 179.17 | 26.55 | 294.83 | 26.60 | 170.17 | 26.63 |
June | 259.33 | 26.70 | 312.00 | 26.69 | 259.33 | 26.69 |
July | 291.83 | 26.71 | 300.00 | 26.71 | 291.83 | 26.71 |
August | 299.00 | 26.70 | 324.00 | 26.69 | 299.00 | 26.69 |
September | 249.00 | 26.69 | 296.67 | 26.67 | 248.33 | 26.68 |
October | 124.83 | 25.93 | 260.33 | 26.38 | 95.83 | 26.44 |
November | 131.67 | 21.92 | 172.50 | 23.46 | 47.00 | 22.92 |
December | 295.00 | 21.21 | 139.00 | 20.42 | 139.00 | 20.01 |
Annual Sum or Average | 2602.00 | 24.36 | 2767.83 | 24.85 | 1877.83 | 24.82 |
Minimum of Months | 86.00 | 21.11 | 104.83 | 20.38 | 40.17 | 19.96 |
Maximum of Months | 299.00 | 26.71 | 324.00 | 26.71 | 299.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.65 | 300.00 | 15.65 | 300.00 | 15.65 |
February | 276.00 | 16.46 | 276.00 | 16.46 | 276.00 | 16.46 |
March | 324.00 | 19.14 | 277.83 | 18.91 | 277.83 | 18.82 |
April | 190.50 | 23.26 | 111.17 | 24.08 | 49.83 | 24.08 |
May | 230.50 | 29.40 | 287.50 | 29.19 | 216.83 | 29.36 |
June | 312.00 | 31.50 | 312.00 | 31.50 | 312.00 | 31.50 |
July | 300.00 | 31.01 | 300.00 | 31.01 | 300.00 | 31.01 |
August | 324.00 | 30.41 | 324.00 | 30.41 | 324.00 | 30.41 |
September | 288.67 | 29.80 | 300.00 | 29.75 | 288.67 | 29.77 |
October | 140.00 | 26.44 | 223.67 | 26.85 | 84.33 | 27.18 |
November | 277.17 | 20.21 | 176.83 | 19.74 | 170.50 | 19.47 |
December | 300.00 | 15.40 | 300.00 | 15.40 | 300.00 | 15.40 |
Annual Sum or Average | 3262.83 | 23.95 | 3189.00 | 24.13 | 2900.00 | 24.12 |
Minimum of Months | 140.00 | 15.40 | 111.17 | 15.40 | 49.83 | 15.40 |
Maximum of Months | 324.00 | 31.50 | 324.00 | 31.50 | 324.00 | 31.50 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1115.67 | 310.79 | 3.42 | 1115.67 | -0.0 | 0.00 | 0.00 | 03-JAN-13:20 | 0.00 | 01-JAN-00:10 | 0.47 | 03-JAN-13:20 | 0.47 | 03-JAN-13:20 | 0.00 | 19-JAN-14:10 | 0.13 | 03-JAN-13:20 | 0.00 | 01-JAN-00:10 |
February | 0.149648E+09 | 40780375.04 | 30.67 | 0.149648E+09 | 0.00 | 0.00 | 0.21 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 4059.20 | 21-FEB-16:00 | 4059.20 | 21-FEB-16:00 | 0.00 | 21-FEB-16:20 | 1095.70 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.725314E+09 | 0.196314E+09 | 74.64 | 0.725314E+09 | 0.97 | 0.00 | 0.34 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 6802.22 | 14-MAR-16:00 | 6802.22 | 14-MAR-16:00 | 0.00 | 11-MAR-09:15 | 1829.88 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.395471E+10 | 0.110208E+10 | 175.27 | 0.393924E+10 | 15465874.76 | 0.00 | 1.00 | 20-APR-05:02 | 0.00 | 01-APR-00:10 | 22682.84 | 29-APR-05:01 | 22396.67 | 20-APR-05:02 | 3158.04 | 29-APR-05:45 | 5374.41 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.842834E+10 | 0.237656E+10 | 273.19 | 0.817244E+10 | 0.255901E+09 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 24407.17 | 23-MAY-05:01 | 23067.48 | 31-MAY-05:01 | 8832.09 | 25-MAY-05:02 | 5774.70 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.121135E+11 | 0.358379E+10 | 311.46 | 0.115374E+11 | 0.576103E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:03 | 25379.27 | 28-JUN-05:01 | 23762.91 | 17-JUN-05:01 | 9955.20 | 28-JUN-05:03 | 6012.31 | 05-JUN-17:00 | 0.00 | 01-JUN-00:03 |
July | 0.139546E+11 | 0.391748E+10 | 311.19 | 0.113226E+11 | 0.263205E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 29102.88 | 21-JUL-05:01 | 24439.00 | 03-JUL-05:01 | 17273.90 | 21-JUL-05:06 | 6728.89 | 16-JUL-14:35 | 0.00 | 01-JUL-00:05 |
August | 0.128651E+11 | 0.360247E+10 | 321.18 | 0.110197E+11 | 0.184545E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:05 | 28118.78 | 03-AUG-05:01 | 23876.31 | 07-AUG-05:01 | 13772.17 | 02-AUG-05:09 | 6481.10 | 03-AUG-05:01 | 0.00 | 01-AUG-00:05 |
September | 0.104373E+11 | 0.288058E+10 | 275.58 | 0.902397E+10 | 0.141328E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 27428.37 | 22-SEP-05:01 | 24875.90 | 04-SEP-16:45 | 13834.26 | 22-SEP-05:05 | 6680.38 | 03-SEP-13:23 | 0.00 | 01-SEP-00:10 |
October | 0.451045E+10 | 0.121324E+10 | 179.92 | 0.405557E+10 | 0.454884E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 25686.18 | 04-OCT-05:02 | 23524.87 | 02-OCT-05:01 | 11369.87 | 04-OCT-05:03 | 6041.15 | 04-OCT-05:02 | 0.00 | 01-OCT-00:10 |
November | 0.454704E+09 | 0.122471E+09 | 54.22 | 0.450891E+09 | 3812980.98 | 0.00 | 0.39 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 8098.80 | 03-NOV-16:00 | 8098.80 | 03-NOV-16:00 | 349.22 | 03-NOV-12:50 | 2128.62 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 1357.87 | 378.25 | 2.58 | 1357.87 | -0.0 | 0.00 | 0.00 | 29-DEC-16:40 | 0.00 | 01-DEC-00:10 | 1.62 | 29-DEC-16:40 | 1.62 | 29-DEC-16:40 | 0.00 | 12-DEC-15:40 | 0.45 | 29-DEC-16:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.675937E+11 | 0.190358E+11 | 2013.32 | 0.603967E+11 | 0.719695E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1115.67 | 310.79 | 2.58 | 1115.67 | -0.0 | 0.00 | 0.00 | 0.00 | 0.47 | 0.47 | 0.00 | 0.13 | 0.00 | |||||||
Maximum of Months | 0.139546E+11 | 0.391748E+10 | 321.18 | 0.115374E+11 | 0.263205E+10 | 0.00 | 1.00 | 0.00 | 29102.88 | 24875.90 | 17273.90 | 6728.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 51555.29 | 15545.30 | 6.83 | 51555.29 | 0.00 | 0.00 | 0.00 | 23-FEB-13:00 | 0.00 | 01-FEB-00:10 | 5.80 | 23-FEB-12:50 | 5.80 | 23-FEB-12:50 | 0.00 | 23-FEB-13:10 | 1.75 | 23-FEB-12:50 | 0.00 | 01-FEB-00:10 |
March | 0.288868E+09 | 86663791.43 | 42.83 | 0.288868E+09 | -0.0 | 0.00 | 0.15 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 10665.87 | 22-MAR-13:00 | 10665.87 | 22-MAR-13:00 | 0.00 | 14-MAR-15:20 | 3215.30 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.109252E+11 | 0.336095E+10 | 164.92 | 0.109151E+11 | 10112358.18 | 0.00 | 1.00 | 02-APR-14:05 | 0.00 | 01-APR-00:10 | 86671.56 | 30-APR-10:45 | 86671.56 | 30-APR-10:45 | 1275.14 | 30-APR-09:55 | 23098.33 | 30-APR-11:50 | 0.00 | 01-APR-00:10 |
May | 0.288952E+11 | 0.898353E+10 | 305.02 | 0.283343E+11 | 0.560943E+09 | 0.00 | 1.00 | 05-MAY-17:11 | 0.00 | 01-MAY-00:10 | 95791.34 | 28-MAY-08:25 | 89197.98 | 28-MAY-17:53 | 24786.56 | 28-MAY-08:25 | 25879.13 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
June | 0.474940E+11 | 0.154330E+11 | 416.62 | 0.462347E+11 | 0.125928E+10 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:03 | 100010.76 | 19-JUN-18:04 | 89171.46 | 20-JUN-21:05 | 31902.26 | 19-JUN-18:04 | 27095.94 | 18-JUN-16:02 | 0.00 | 01-JUN-00:03 |
July | 0.528178E+11 | 0.162602E+11 | 424.88 | 0.453553E+11 | 0.746252E+10 | 0.00 | 1.00 | 01-JUL-01:55 | 0.00 | 01-JUL-00:15 | 107903.21 | 20-JUL-21:45 | 88063.04 | 03-JUL-05:55 | 61264.31 | 20-JUL-21:45 | 27902.99 | 02-JUL-15:52 | 0.00 | 01-JUL-00:05 |
August | 0.454279E+11 | 0.139809E+11 | 395.65 | 0.411215E+11 | 0.430643E+10 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:15 | 103564.39 | 01-AUG-23:52 | 88836.18 | 24-AUG-02:41 | 44833.47 | 01-AUG-21:35 | 27124.63 | 06-AUG-15:22 | 0.00 | 01-AUG-00:05 |
September | 0.351316E+11 | 0.105610E+11 | 300.32 | 0.316135E+11 | 0.351813E+10 | 0.00 | 1.00 | 01-SEP-17:42 | 0.00 | 01-SEP-00:10 | 100901.24 | 23-SEP-00:25 | 88799.35 | 08-SEP-17:43 | 41678.57 | 23-SEP-00:25 | 25764.91 | 04-SEP-13:13 | 0.00 | 01-SEP-00:10 |
October | 0.107561E+11 | 0.318435E+10 | 154.23 | 0.993812E+10 | 0.817977E+09 | 0.00 | 1.00 | 01-OCT-09:11 | 0.00 | 01-OCT-00:10 | 99663.68 | 03-OCT-17:12 | 87499.82 | 22-OCT-14:33 | 32610.23 | 03-OCT-17:12 | 25316.93 | 03-OCT-18:05 | 0.00 | 01-OCT-00:10 |
November | 0.275054E+09 | 81609046.86 | 19.08 | 0.273204E+09 | 1849926.11 | 0.00 | 0.16 | 03-NOV-15:00 | 0.00 | 01-NOV-00:10 | 12361.71 | 03-NOV-15:00 | 12361.71 | 03-NOV-15:00 | 369.67 | 03-NOV-13:10 | 3639.20 | 03-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.232012E+12 | 0.719321E+11 | 2230.39 | 0.214075E+12 | 0.179372E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.528178E+11 | 0.162602E+11 | 424.88 | 0.462347E+11 | 0.746252E+10 | 0.00 | 1.00 | 0.00 | 107903.21 | 89197.98 | 61264.31 | 27902.99 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.00 | 37.79 | 29.22 | 77.01 | 143.31 | 0.00 | 0.00 | 0.00 |
February | 75.39 | 40.01 | 35.38 | 92.53 | 131.09 | 0.00 | 0.00 | 0.00 |
March | 102.73 | 55.01 | 47.72 | 137.84 | 117.61 | 0.00 | 0.00 | 0.00 |
April | 117.93 | 63.55 | 54.38 | 184.86 | 81.49 | 0.00 | 0.00 | 0.00 |
May | 127.03 | 67.83 | 59.20 | 223.17 | 57.73 | 0.00 | 0.00 | 0.00 |
June | 124.00 | 66.61 | 57.39 | 248.86 | 35.11 | 0.00 | 0.00 | 0.00 |
July | 110.12 | 54.75 | 55.37 | 219.92 | 31.32 | 0.00 | 0.00 | 0.00 |
August | 106.39 | 54.11 | 52.27 | 203.42 | 41.14 | 0.00 | 0.00 | 0.00 |
September | 109.07 | 60.80 | 48.27 | 197.28 | 69.73 | 0.00 | 0.00 | 0.00 |
October | 93.70 | 54.65 | 39.06 | 142.94 | 99.27 | 0.00 | 0.00 | 0.00 |
November | 78.20 | 47.42 | 30.78 | 97.62 | 142.90 | 0.00 | 0.00 | 0.00 |
December | 63.49 | 34.51 | 28.98 | 67.60 | 163.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.00 | 53.12 | 44.88 | 158.02 | 92.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.49 | 34.51 | 28.98 | 67.60 | 31.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.03 | 67.83 | 59.20 | 248.86 | 163.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.00 | 37.79 | 29.22 | 77.01 | 143.31 | 0.00 | 0.00 | 0.00 |
February | 75.39 | 40.01 | 35.38 | 92.53 | 131.09 | 0.00 | 0.00 | 0.00 |
March | 102.73 | 55.01 | 47.72 | 137.84 | 117.61 | 0.00 | 0.00 | 0.00 |
April | 117.93 | 63.55 | 54.38 | 184.86 | 81.49 | 0.00 | 0.00 | 0.00 |
May | 127.03 | 67.83 | 59.20 | 223.17 | 57.73 | 0.00 | 0.00 | 0.00 |
June | 124.00 | 66.61 | 57.39 | 248.86 | 35.11 | 0.00 | 0.00 | 0.00 |
July | 110.12 | 54.75 | 55.37 | 219.92 | 31.32 | 0.00 | 0.00 | 0.00 |
August | 106.39 | 54.11 | 52.27 | 203.42 | 41.14 | 0.00 | 0.00 | 0.00 |
September | 109.07 | 60.80 | 48.27 | 197.28 | 69.73 | 0.00 | 0.00 | 0.00 |
October | 93.70 | 54.65 | 39.06 | 142.94 | 99.27 | 0.00 | 0.00 | 0.00 |
November | 78.20 | 47.42 | 30.78 | 97.62 | 142.90 | 0.00 | 0.00 | 0.00 |
December | 63.49 | 34.51 | 28.98 | 67.60 | 163.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.00 | 53.12 | 44.88 | 158.02 | 92.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.49 | 34.51 | 28.98 | 67.60 | 31.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.03 | 67.83 | 59.20 | 248.86 | 163.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.85 | 0.00 | 13.85 | 2.21 | 89.92 | 0.00 | 0.00 | 0.00 |
February | 16.91 | 0.00 | 16.91 | 6.46 | 80.89 | 0.00 | 0.00 | 0.00 |
March | 22.14 | 0.00 | 22.14 | 13.08 | 72.10 | 0.00 | 0.00 | 0.00 |
April | 25.67 | 0.30 | 25.37 | 26.74 | 47.94 | 0.00 | 0.00 | 0.00 |
May | 30.48 | 2.36 | 28.12 | 46.88 | 31.61 | 0.00 | 0.00 | 0.00 |
June | 32.34 | 4.08 | 28.26 | 68.83 | 19.49 | 0.00 | 0.00 | 0.00 |
July | 29.80 | 2.90 | 26.90 | 62.05 | 17.52 | 0.00 | 0.00 | 0.00 |
August | 25.32 | 0.69 | 24.62 | 47.06 | 23.22 | 0.00 | 0.00 | 0.00 |
September | 21.94 | 0.02 | 21.92 | 34.47 | 40.92 | 0.00 | 0.00 | 0.00 |
October | 18.20 | 0.00 | 18.20 | 14.56 | 60.20 | 0.00 | 0.00 | 0.00 |
November | 14.69 | 0.00 | 14.69 | 2.49 | 89.89 | 0.00 | 0.00 | 0.00 |
December | 13.74 | 0.00 | 13.74 | 1.11 | 103.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.12 | 0.87 | 21.25 | 27.27 | 56.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.74 | 0.00 | 13.74 | 1.11 | 17.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.34 | 4.08 | 28.26 | 68.83 | 103.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.85 | 0.00 | 13.85 | 2.21 | 89.92 | 0.00 | 0.00 | 0.00 |
February | 16.91 | 0.00 | 16.91 | 6.46 | 80.89 | 0.00 | 0.00 | 0.00 |
March | 22.14 | 0.00 | 22.14 | 13.08 | 72.10 | 0.00 | 0.00 | 0.00 |
April | 25.67 | 0.30 | 25.37 | 26.74 | 47.94 | 0.00 | 0.00 | 0.00 |
May | 30.48 | 2.36 | 28.12 | 46.88 | 31.61 | 0.00 | 0.00 | 0.00 |
June | 32.34 | 4.08 | 28.26 | 68.83 | 19.49 | 0.00 | 0.00 | 0.00 |
July | 29.79 | 2.90 | 26.90 | 62.05 | 17.52 | 0.00 | 0.00 | 0.00 |
August | 25.32 | 0.69 | 24.62 | 47.06 | 23.22 | 0.00 | 0.00 | 0.00 |
September | 21.94 | 0.02 | 21.92 | 34.47 | 40.92 | 0.00 | 0.00 | 0.00 |
October | 18.20 | 0.00 | 18.20 | 14.56 | 60.20 | 0.00 | 0.00 | 0.00 |
November | 14.69 | 0.00 | 14.69 | 2.49 | 89.89 | 0.00 | 0.00 | 0.00 |
December | 13.74 | 0.00 | 13.74 | 1.11 | 103.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.12 | 0.87 | 21.25 | 27.27 | 56.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.74 | 0.00 | 13.74 | 1.11 | 17.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.34 | 4.08 | 28.26 | 68.83 | 103.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.62 | 28.25 | 12.37 | 52.33 | 37.15 | 0.00 | 0.00 | 0.00 |
February | 52.76 | 37.23 | 15.53 | 70.15 | 34.91 | 0.00 | 0.00 | 0.00 |
March | 74.58 | 52.80 | 21.79 | 100.93 | 35.18 | 0.00 | 0.00 | 0.00 |
April | 93.33 | 69.50 | 23.83 | 128.73 | 30.99 | 0.00 | 0.00 | 0.00 |
May | 103.15 | 77.02 | 26.13 | 142.61 | 30.86 | 0.00 | 0.00 | 0.00 |
June | 109.16 | 85.04 | 24.13 | 154.10 | 25.94 | 0.00 | 0.00 | 0.00 |
July | 94.33 | 68.38 | 25.95 | 134.51 | 21.19 | 0.00 | 0.00 | 0.00 |
August | 88.10 | 63.87 | 24.24 | 123.64 | 25.08 | 0.00 | 0.00 | 0.00 |
September | 80.26 | 60.19 | 20.07 | 111.10 | 33.92 | 0.00 | 0.00 | 0.00 |
October | 59.93 | 43.51 | 16.43 | 79.01 | 37.35 | 0.00 | 0.00 | 0.00 |
November | 46.25 | 34.15 | 12.11 | 57.66 | 42.89 | 0.00 | 0.00 | 0.00 |
December | 37.45 | 24.62 | 12.83 | 45.80 | 42.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.40 | 53.75 | 19.65 | 100.15 | 33.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.45 | 24.62 | 12.11 | 45.80 | 21.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.16 | 85.04 | 26.13 | 154.10 | 42.96 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179463E+09 | 0.101204E+09 | 78259173.43 | 0.206273E+09 | 0.383832E+09 |
February | 0.182386E+09 | 96789877.26 | 85595682.28 | 0.223851E+09 | 0.317144E+09 |
March | 0.275156E+09 | 0.147345E+09 | 0.127811E+09 | 0.369199E+09 | 0.314997E+09 |
April | 0.305676E+09 | 0.164734E+09 | 0.140942E+09 | 0.479149E+09 | 0.211229E+09 |
May | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.597747E+09 | 0.154612E+09 |
June | 0.321406E+09 | 0.172662E+09 | 0.148744E+09 | 0.645039E+09 | 91016977.70 |
July | 0.294955E+09 | 0.146648E+09 | 0.148307E+09 | 0.589030E+09 | 83875467.56 |
August | 0.284942E+09 | 0.144939E+09 | 0.140004E+09 | 0.544837E+09 | 0.110196E+09 |
September | 0.282710E+09 | 0.157595E+09 | 0.125115E+09 | 0.511338E+09 | 0.180740E+09 |
October | 0.250972E+09 | 0.146361E+09 | 0.104610E+09 | 0.382845E+09 | 0.265884E+09 |
November | 0.202684E+09 | 0.122913E+09 | 79770336.35 | 0.253020E+09 | 0.370394E+09 |
December | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.181064E+09 | 0.438279E+09 |
Annual Sum or Average | 0.309063E+10 | 0.167530E+10 | 0.141533E+10 | 0.498339E+10 | 0.292220E+10 |
Minimum of Months | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.181064E+09 | 83875467.56 |
Maximum of Months | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.645039E+09 | 0.438279E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179463E+09 | 0.101204E+09 | 78259173.43 | 0.206273E+09 | 0.383832E+09 |
February | 0.182386E+09 | 96789877.26 | 85595682.28 | 0.223851E+09 | 0.317144E+09 |
March | 0.275156E+09 | 0.147345E+09 | 0.127811E+09 | 0.369199E+09 | 0.314997E+09 |
April | 0.305676E+09 | 0.164734E+09 | 0.140942E+09 | 0.479149E+09 | 0.211229E+09 |
May | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.597747E+09 | 0.154612E+09 |
June | 0.321406E+09 | 0.172662E+09 | 0.148744E+09 | 0.645039E+09 | 91016977.70 |
July | 0.294955E+09 | 0.146648E+09 | 0.148307E+09 | 0.589030E+09 | 83875467.56 |
August | 0.284942E+09 | 0.144939E+09 | 0.140004E+09 | 0.544837E+09 | 0.110196E+09 |
September | 0.282710E+09 | 0.157595E+09 | 0.125115E+09 | 0.511338E+09 | 0.180740E+09 |
October | 0.250972E+09 | 0.146361E+09 | 0.104610E+09 | 0.382845E+09 | 0.265884E+09 |
November | 0.202684E+09 | 0.122913E+09 | 79770336.35 | 0.253020E+09 | 0.370394E+09 |
December | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.181064E+09 | 0.438279E+09 |
Annual Sum or Average | 0.309063E+10 | 0.167530E+10 | 0.141533E+10 | 0.498339E+10 | 0.292220E+10 |
Minimum of Months | 0.170052E+09 | 92436426.13 | 77615197.29 | 0.181064E+09 | 83875467.56 |
Maximum of Months | 0.340226E+09 | 0.181670E+09 | 0.158556E+09 | 0.645039E+09 | 0.438279E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37099673.28 | 0.00 | 37099673.28 | 5914681.64 | 0.240834E+09 |
February | 40918508.79 | 0.00 | 40918508.79 | 15638276.85 | 0.195698E+09 |
March | 59306438.91 | 7670.77 | 59298768.14 | 35032542.55 | 0.193103E+09 |
April | 66535406.92 | 781060.78 | 65754346.14 | 69309378.60 | 0.124258E+09 |
May | 81639584.07 | 6316636.56 | 75322947.50 | 0.125554E+09 | 84669668.40 |
June | 83832858.99 | 10571494.93 | 73261364.06 | 0.178409E+09 | 50526120.44 |
July | 79803954.64 | 7754630.16 | 72049324.48 | 0.166199E+09 | 46920633.89 |
August | 67814502.26 | 1858921.28 | 65955580.98 | 0.126057E+09 | 62187590.12 |
September | 56878671.07 | 60335.66 | 56818335.41 | 89338454.86 | 0.106060E+09 |
October | 48740899.13 | 0.00 | 48740899.13 | 39000849.02 | 0.161238E+09 |
November | 38078983.12 | 0.00 | 38078983.12 | 6459689.40 | 0.232983E+09 |
December | 36812348.67 | 0.00 | 36812348.67 | 2962376.11 | 0.277690E+09 |
Annual Sum or Average | 0.697462E+09 | 27350750.15 | 0.670111E+09 | 0.859875E+09 | 0.177617E+10 |
Minimum of Months | 36812348.67 | 0.00 | 36812348.67 | 2962376.11 | 46920633.89 |
Maximum of Months | 83832858.99 | 10571494.93 | 75322947.50 | 0.178409E+09 | 0.277690E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37098677.13 | 0.00 | 37098677.13 | 5914188.54 | 0.240833E+09 |
February | 40917432.20 | 0.00 | 40917432.20 | 15637672.95 | 0.195697E+09 |
March | 59304907.93 | 7670.41 | 59297237.52 | 35031249.23 | 0.193101E+09 |
April | 66533769.09 | 781024.17 | 65752744.91 | 69308056.04 | 0.124257E+09 |
May | 81637421.85 | 6316340.50 | 75321081.36 | 0.125551E+09 | 84668399.69 |
June | 83830620.15 | 10570999.43 | 73259620.71 | 0.178406E+09 | 50525050.18 |
July | 79801737.42 | 7754266.69 | 72047470.73 | 0.166196E+09 | 46919793.13 |
August | 67812748.68 | 1858834.15 | 65953914.53 | 0.126055E+09 | 62186687.42 |
September | 56877294.21 | 60332.84 | 56816961.37 | 89337124.56 | 0.106059E+09 |
October | 48739645.26 | 0.00 | 48739645.26 | 38999748.22 | 0.161237E+09 |
November | 38078011.80 | 0.00 | 38078011.80 | 6459391.68 | 0.232982E+09 |
December | 36811327.25 | 0.00 | 36811327.25 | 2962084.00 | 0.277689E+09 |
Annual Sum or Average | 0.697444E+09 | 27349468.18 | 0.670094E+09 | 0.859858E+09 | 0.177615E+10 |
Minimum of Months | 36811327.25 | 0.00 | 36811327.25 | 2962084.00 | 46919793.13 |
Maximum of Months | 83830620.15 | 10570999.43 | 75321081.36 | 0.178406E+09 | 0.277689E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108801E+09 | 75664407.04 | 33136590.38 | 0.140162E+09 | 99510987.30 |
February | 0.127629E+09 | 90058621.95 | 37570225.74 | 0.169714E+09 | 84463407.38 |
March | 0.199761E+09 | 0.141411E+09 | 58349352.67 | 0.270332E+09 | 94236054.87 |
April | 0.241905E+09 | 0.180139E+09 | 61766888.14 | 0.333664E+09 | 80314874.80 |
May | 0.276271E+09 | 0.206289E+09 | 69982390.15 | 0.381957E+09 | 82668003.80 |
June | 0.282954E+09 | 0.220412E+09 | 62541977.75 | 0.399430E+09 | 67231606.43 |
July | 0.252658E+09 | 0.183153E+09 | 69505062.30 | 0.360281E+09 | 56763368.19 |
August | 0.235977E+09 | 0.171059E+09 | 64918845.14 | 0.331169E+09 | 67171968.31 |
September | 0.208037E+09 | 0.156021E+09 | 52015562.86 | 0.287979E+09 | 87933456.95 |
October | 0.160525E+09 | 0.116529E+09 | 43996013.10 | 0.211609E+09 | 0.100041E+09 |
November | 0.119881E+09 | 88504822.72 | 31376459.72 | 0.149450E+09 | 0.111175E+09 |
December | 0.100305E+09 | 65931212.33 | 34373596.82 | 0.122670E+09 | 0.115054E+09 |
Annual Sum or Average | 0.231470E+10 | 0.169517E+10 | 0.619533E+09 | 0.315842E+10 | 0.104656E+10 |
Minimum of Months | 0.100305E+09 | 65931212.33 | 31376459.72 | 0.122670E+09 | 56763368.19 |
Maximum of Months | 0.282954E+09 | 0.220412E+09 | 69982390.15 | 0.399430E+09 | 0.115054E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.33 | 456.33 | 161.71 | 75.57 | 86.14 | 0.00 | 0.00 |
February | 190.21 | 416.19 | 184.61 | 80.02 | 104.59 | 0.00 | 0.00 |
March | 295.80 | 373.36 | 249.75 | 110.03 | 139.72 | 0.00 | 0.00 |
April | 421.04 | 256.71 | 287.20 | 127.71 | 159.49 | 0.00 | 0.00 |
May | 538.63 | 177.20 | 315.01 | 140.37 | 174.64 | 0.00 | 0.00 |
June | 633.89 | 107.73 | 312.68 | 141.38 | 171.30 | 0.00 | 0.00 |
July | 562.47 | 96.19 | 279.84 | 115.29 | 164.54 | 0.00 | 0.00 |
August | 500.43 | 128.18 | 263.41 | 109.62 | 153.79 | 0.00 | 0.00 |
September | 462.87 | 220.68 | 262.03 | 121.65 | 140.38 | 0.00 | 0.00 |
October | 311.79 | 315.73 | 223.80 | 109.29 | 114.51 | 0.00 | 0.00 |
November | 190.41 | 455.76 | 185.77 | 94.84 | 90.93 | 0.00 | 0.00 |
December | 124.66 | 521.87 | 154.47 | 69.02 | 85.44 | 0.00 | 0.00 |
Annual Sum or Average | 365.80 | 293.19 | 240.24 | 107.98 | 132.26 | 0.00 | 0.00 |
Minimum of Months | 124.66 | 96.19 | 154.47 | 69.02 | 85.44 | 0.00 | 0.00 |
Maximum of Months | 633.89 | 521.87 | 315.01 | 141.38 | 174.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1870.60 | 1474.10 | 406.22 | 282.50 | 123.72 | 0.00 | 0.00 |
February | 2499.95 | 1352.31 | 527.57 | 372.27 | 155.30 | 0.00 | 0.00 |
March | 3381.81 | 1233.56 | 745.82 | 527.97 | 217.85 | 0.00 | 0.00 |
April | 4572.42 | 1006.23 | 933.28 | 694.98 | 238.30 | 0.00 | 0.00 |
May | 6105.82 | 1262.32 | 1031.48 | 770.19 | 261.28 | 0.00 | 0.00 |
June | 7008.65 | 1648.00 | 1091.64 | 850.35 | 241.29 | 0.00 | 0.00 |
July | 6211.66 | 1401.74 | 943.32 | 683.82 | 259.50 | 0.00 | 0.00 |
August | 5603.33 | 1534.47 | 881.04 | 638.66 | 242.38 | 0.00 | 0.00 |
September | 5297.62 | 1676.89 | 802.61 | 601.93 | 200.68 | 0.00 | 0.00 |
October | 3015.60 | 1341.08 | 599.33 | 435.07 | 164.26 | 0.00 | 0.00 |
November | 1898.38 | 1466.15 | 462.50 | 341.45 | 121.05 | 0.00 | 0.00 |
December | 1661.72 | 1736.63 | 374.50 | 246.16 | 128.34 | 0.00 | 0.00 |
Annual Sum or Average | 4100.49 | 1428.18 | 733.99 | 537.54 | 196.45 | 0.00 | 0.00 |
Minimum of Months | 1661.72 | 1006.23 | 374.50 | 246.16 | 121.05 | 0.00 | 0.00 |
Maximum of Months | 7008.65 | 1736.63 | 1091.64 | 850.35 | 261.28 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397282E+09 | 0.122224E+10 | 0.433125E+09 | 0.202408E+09 | 0.230717E+09 | 0.00 | 0.00 |
February | 0.460154E+09 | 0.100686E+10 | 0.446607E+09 | 0.193580E+09 | 0.253027E+09 | 0.00 | 0.00 |
March | 0.792274E+09 | 0.100001E+10 | 0.668923E+09 | 0.294705E+09 | 0.374218E+09 | 0.00 | 0.00 |
April | 0.109135E+10 | 0.665403E+09 | 0.744422E+09 | 0.331031E+09 | 0.413391E+09 | 0.00 | 0.00 |
May | 0.144266E+10 | 0.474621E+09 | 0.843730E+09 | 0.375973E+09 | 0.467757E+09 | 0.00 | 0.00 |
June | 0.164303E+10 | 0.279224E+09 | 0.810475E+09 | 0.366466E+09 | 0.444009E+09 | 0.00 | 0.00 |
July | 0.150651E+10 | 0.257646E+09 | 0.749516E+09 | 0.308805E+09 | 0.440711E+09 | 0.00 | 0.00 |
August | 0.134035E+10 | 0.343327E+09 | 0.705512E+09 | 0.293595E+09 | 0.411917E+09 | 0.00 | 0.00 |
September | 0.119976E+10 | 0.572006E+09 | 0.679176E+09 | 0.315310E+09 | 0.363865E+09 | 0.00 | 0.00 |
October | 0.835091E+09 | 0.845643E+09 | 0.599424E+09 | 0.292723E+09 | 0.306701E+09 | 0.00 | 0.00 |
November | 0.493542E+09 | 0.118134E+10 | 0.481524E+09 | 0.245827E+09 | 0.235698E+09 | 0.00 | 0.00 |
December | 0.333893E+09 | 0.139778E+10 | 0.413727E+09 | 0.184873E+09 | 0.228854E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115359E+11 | 0.924609E+10 | 0.757616E+10 | 0.340530E+10 | 0.417087E+10 | 0.00 | 0.00 |
Minimum of Months | 0.333893E+09 | 0.257646E+09 | 0.413727E+09 | 0.184873E+09 | 0.228854E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164303E+10 | 0.139778E+10 | 0.843730E+09 | 0.375973E+09 | 0.467757E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501020E+10 | 0.394823E+10 | 0.108801E+10 | 0.756644E+09 | 0.331366E+09 | 0.00 | 0.00 |
February | 0.604787E+10 | 0.327152E+10 | 0.127629E+10 | 0.900586E+09 | 0.375702E+09 | 0.00 | 0.00 |
March | 0.905784E+10 | 0.330397E+10 | 0.199761E+10 | 0.141411E+10 | 0.583494E+09 | 0.00 | 0.00 |
April | 0.118517E+11 | 0.260814E+10 | 0.241905E+10 | 0.180139E+10 | 0.617669E+09 | 0.00 | 0.00 |
May | 0.163538E+11 | 0.338101E+10 | 0.276271E+10 | 0.206289E+10 | 0.699824E+09 | 0.00 | 0.00 |
June | 0.181664E+11 | 0.427162E+10 | 0.282954E+10 | 0.220412E+10 | 0.625420E+09 | 0.00 | 0.00 |
July | 0.166373E+11 | 0.375442E+10 | 0.252658E+10 | 0.183153E+10 | 0.695051E+09 | 0.00 | 0.00 |
August | 0.150080E+11 | 0.410993E+10 | 0.235977E+10 | 0.171059E+10 | 0.649188E+09 | 0.00 | 0.00 |
September | 0.137314E+11 | 0.434650E+10 | 0.208037E+10 | 0.156021E+10 | 0.520156E+09 | 0.00 | 0.00 |
October | 0.807698E+10 | 0.359194E+10 | 0.160525E+10 | 0.116529E+10 | 0.439960E+09 | 0.00 | 0.00 |
November | 0.492060E+10 | 0.380027E+10 | 0.119881E+10 | 0.885048E+09 | 0.313765E+09 | 0.00 | 0.00 |
December | 0.445076E+10 | 0.465140E+10 | 0.100305E+10 | 0.659312E+09 | 0.343736E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129313E+12 | 0.450389E+11 | 0.231470E+11 | 0.169517E+11 | 0.619533E+10 | 0.00 | 0.00 |
Minimum of Months | 0.445076E+10 | 0.260814E+10 | 0.100305E+10 | 0.659312E+09 | 0.313765E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181664E+11 | 0.465140E+10 | 0.282954E+10 | 0.220412E+10 | 0.699824E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.865859E+09 | -782878346.3 | 0.00 | 0.00 | 744.00 | 0.00 | -82980216.9 | 59.00 | 0.00 | 0.00 |
February | 0.791968E+09 | -718606079.9 | 0.00 | 0.00 | 672.00 | 0.00 | -73362183.7 | 59.00 | 0.00 | 0.00 |
March | 0.887610E+09 | -808968791.9 | 0.00 | 0.00 | 744.00 | 0.00 | -78640905.7 | 58.99 | 0.00 | 0.00 |
April | 0.772985E+09 | -701667555.5 | 0.00 | 0.00 | 720.00 | 0.00 | -71317748.7 | 58.99 | 0.00 | 0.00 |
May | 0.741170E+09 | -670056045.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71113871.7 | 58.99 | 0.00 | 0.00 |
June | 0.682175E+09 | -614653639.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67521206.0 | 58.99 | 0.00 | 0.00 |
July | 0.634061E+09 | -564859186.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69201377.7 | 58.99 | 0.00 | 0.00 |
August | 0.677051E+09 | -607216212.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69834859.2 | 58.99 | 0.00 | 0.00 |
September | 0.662553E+09 | -594569552.0 | 0.00 | 0.00 | 720.00 | 0.00 | -67983662.1 | 58.99 | 0.00 | 0.00 |
October | 0.719206E+09 | -646569798.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72636155.3 | 58.99 | 0.00 | 0.00 |
November | 0.751736E+09 | -676115490.4 | 0.00 | 0.00 | 720.00 | 0.00 | -75620842.8 | 58.99 | 0.00 | 0.00 |
December | 0.836177E+09 | -753476524.0 | 0.00 | 0.00 | 744.00 | 0.00 | -82700153.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.902255E+10 | -0.813964E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -882913183.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.634061E+09 | -808968791.9 | 0.00 | 0.00 | 672.00 | 0.00 | -82980216.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.887610E+09 | -564859186.6 | 0.00 | 0.00 | 744.00 | 0.00 | -67521206.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149826E+10 | 31402.42 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.961206E+09 | 31402.42 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.565870E+09 | 31402.42 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38743851.65 | 17455.09 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3333458.22 | 5282.05 | 27-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 596106.94 | 1388.15 | 01-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 614759.16 | 2049.20 | 19-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379012E+09 | 31402.42 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154287E+10 | 31402.42 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154287E+10 | 31402.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581009E+09 | 85284.82 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269722E+09 | 49516.65 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30521796.68 | 35215.20 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48129533.06 | 19583.86 | 28-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106915E+10 | 61414.43 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106915E+10 | 85284.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1115.67 | 1115.67 | 0.47 | 03-JAN-13:20 | 0.47 | 0.00 |
February | 0.00 | 0.00 | 0.149648E+09 | 0.149648E+09 | 4059.20 | 21-FEB-16:00 | 4059.20 | 0.00 |
March | 0.00 | 0.00 | 0.725314E+09 | 0.725314E+09 | 6802.22 | 14-MAR-16:00 | 6802.22 | 0.00 |
April | 0.00 | 0.00 | 0.395471E+10 | 0.393924E+10 | 22682.84 | 29-APR-05:01 | 20158.75 | 0.00 |
May | 0.00 | 0.00 | 0.842834E+10 | 0.817244E+10 | 24407.17 | 23-MAY-05:01 | 19339.97 | 0.00 |
June | 0.00 | 0.00 | 0.121135E+11 | 0.115374E+11 | 25379.27 | 28-JUN-05:01 | 15515.56 | 0.00 |
July | 0.00 | 0.00 | 0.139546E+11 | 0.113226E+11 | 29102.88 | 21-JUL-05:01 | 12049.62 | 0.00 |
August | 0.00 | 0.00 | 0.128651E+11 | 0.110197E+11 | 28118.78 | 03-AUG-05:01 | 15775.21 | 0.00 |
September | 0.00 | 0.00 | 0.104373E+11 | 0.902397E+10 | 27428.37 | 22-SEP-05:01 | 14239.05 | 0.00 |
October | 0.00 | 0.00 | 0.451045E+10 | 0.405557E+10 | 25686.18 | 04-OCT-05:02 | 14391.86 | 0.00 |
November | 0.00 | 0.00 | 0.454704E+09 | 0.450891E+09 | 8098.80 | 03-NOV-16:00 | 8098.80 | 0.00 |
December | 0.00 | 0.00 | 1357.87 | 1357.87 | 1.62 | 29-DEC-16:40 | 1.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.675937E+11 | 0.603967E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1115.67 | 1115.67 | 0.47 | 0.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139546E+11 | 0.115374E+11 | 29102.88 | 20158.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 51555.29 | 51555.29 | 5.80 | 23-FEB-12:50 | 5.80 | 0.00 |
March | 0.00 | 0.00 | 0.288868E+09 | 0.288868E+09 | 10665.87 | 22-MAR-13:00 | 10665.87 | 0.00 |
April | 0.00 | 0.00 | 0.109252E+11 | 0.109151E+11 | 86671.56 | 30-APR-10:45 | 86671.56 | 0.00 |
May | 0.00 | 0.00 | 0.288952E+11 | 0.283343E+11 | 95791.34 | 28-MAY-08:25 | 71004.79 | 0.00 |
June | 0.00 | 0.00 | 0.474940E+11 | 0.462347E+11 | 100010.76 | 19-JUN-18:04 | 68108.50 | 0.00 |
July | 0.00 | 0.00 | 0.528178E+11 | 0.453553E+11 | 107903.21 | 20-JUL-21:45 | 46638.90 | 0.00 |
August | 0.00 | 0.00 | 0.454279E+11 | 0.411215E+11 | 103564.39 | 01-AUG-23:52 | 59108.85 | 0.00 |
September | 0.00 | 0.00 | 0.351316E+11 | 0.316135E+11 | 100901.24 | 23-SEP-00:25 | 59222.67 | 0.00 |
October | 0.00 | 0.00 | 0.107561E+11 | 0.993812E+10 | 99663.68 | 03-OCT-17:12 | 67053.45 | 0.00 |
November | 0.00 | 0.00 | 0.275054E+09 | 0.273204E+09 | 12361.71 | 03-NOV-15:00 | 12361.71 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232012E+12 | 0.214075E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.528178E+11 | 0.462347E+11 | 107903.21 | 86671.56 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158506E+10 | 0.41 | 1573.28 | 05-JAN-10:00 | 1.04 |
February | 0.145148E+10 | 0.41 | 1573.28 | 23-FEB-15:20 | 1.04 |
March | 0.169247E+10 | 0.43 | 1573.28 | 03-MAR-08:00 | 1.04 |
April | 0.156206E+10 | 0.40 | 1573.28 | 11-APR-06:17 | 1.04 |
May | 0.165002E+10 | 0.42 | 1573.28 | 05-MAY-09:40 | 1.04 |
June | 0.166888E+10 | 0.46 | 1573.28 | 10-JUN-06:20 | 1.03 |
July | 0.162164E+10 | 0.44 | 1573.28 | 01-JUL-06:30 | 1.03 |
August | 0.174320E+10 | 0.46 | 1573.28 | 10-AUG-06:15 | 1.02 |
September | 0.160529E+10 | 0.42 | 1573.28 | 12-SEP-06:03 | 1.03 |
October | 0.156774E+10 | 0.39 | 1573.28 | 10-OCT-11:30 | 1.03 |
November | 0.150145E+10 | 0.39 | 1573.28 | 15-NOV-07:40 | 1.04 |
December | 0.158334E+10 | 0.41 | 1573.28 | 12-DEC-08:30 | 1.04 |
Annual Sum or Average | 0.192326E+11 | 0.42 | |||
Minimum of Months | 0.145148E+10 | 0.39 | 1573.28 | 1.02 | |
Maximum of Months | 0.174320E+10 | 0.46 | 1573.28 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.819507E+10 | 0.72 | 8229.92 | 02-JAN-07:05 | 1.77 |
February | 0.751786E+10 | 0.70 | 8229.92 | 23-FEB-13:00 | 1.78 |
March | 0.880195E+10 | 0.71 | 8229.92 | 08-MAR-11:40 | 1.77 |
April | 0.829450E+10 | 0.73 | 8229.92 | 12-APR-11:50 | 1.78 |
May | 0.907867E+10 | 0.88 | 8229.92 | 02-MAY-16:40 | 1.78 |
June | 0.968204E+10 | 1.08 | 8229.92 | 01-JUN-11:10 | 1.78 |
July | 0.958037E+10 | 1.05 | 8229.92 | 06-JUL-10:00 | 1.75 |
August | 0.988522E+10 | 1.02 | 8229.92 | 01-AUG-06:20 | 1.75 |
September | 0.882585E+10 | 0.84 | 8229.92 | 01-SEP-12:20 | 1.75 |
October | 0.830984E+10 | 0.69 | 8229.92 | 04-OCT-14:50 | 1.76 |
November | 0.782564E+10 | 0.66 | 8229.92 | 03-NOV-12:50 | 1.76 |
December | 0.823456E+10 | 0.76 | 8229.92 | 26-DEC-07:30 | 1.78 |
Annual Sum or Average | 0.104232E+12 | 0.82 | |||
Minimum of Months | 0.751786E+10 | 0.66 | 8229.92 | 1.75 | |
Maximum of Months | 0.988522E+10 | 1.08 | 8229.92 | 1.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158506E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149226E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.188878E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.266414E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.402658E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.525266E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.553912E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.534568E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.448587E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.278098E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162392E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158334E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.382684E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.553912E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.819507E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.751787E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.888861E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116554E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.180622E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.251150E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.258406E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.238661E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.193868E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114942E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.790725E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.823456E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176164E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.751787E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.258406E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158506E+10 | 1115.67 | 0.149826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145148E+10 | 0.149648E+09 | 0.961206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169247E+10 | 0.725314E+09 | 0.565870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156206E+10 | 0.395471E+10 | 38743851.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165002E+10 | 0.842834E+10 | 3333458.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166888E+10 | 0.121135E+11 | 596106.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162164E+10 | 0.139546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174320E+10 | 0.128651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160529E+10 | 0.104373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156774E+10 | 0.451045E+10 | 614759.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150145E+10 | 0.454704E+09 | 0.379012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158334E+10 | 1357.87 | 0.154287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192326E+11 | 0.675937E+11 | 0.499051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145148E+10 | 1115.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174320E+10 | 0.139546E+11 | 0.154287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.819507E+10 | 0.00 | 0.581009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751786E+10 | 51555.29 | 0.269722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.880195E+10 | 0.288868E+09 | 30521796.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829450E+10 | 0.109252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.907867E+10 | 0.288952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.968204E+10 | 0.474940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.958037E+10 | 0.528178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.988522E+10 | 0.454279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882585E+10 | 0.351316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.830984E+10 | 0.107561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.782564E+10 | 0.275054E+09 | 48129533.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.823456E+10 | 0.00 | 0.106915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104232E+12 | 0.232012E+12 | 0.199853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.988522E+10 | 0.528178E+11 | 0.106915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158506E+10 | 0.00 | 0.00 | 0.00 | 310.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145148E+10 | 0.00 | 0.00 | 0.00 | 40780375.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169247E+10 | 0.00 | 0.00 | 0.00 | 0.196314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156206E+10 | 0.00 | 0.00 | 0.00 | 0.110208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165002E+10 | 0.00 | 0.00 | 0.00 | 0.237656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166888E+10 | 0.00 | 0.00 | 0.00 | 0.358379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162164E+10 | 0.00 | 0.00 | 0.00 | 0.391748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174320E+10 | 0.00 | 0.00 | 0.00 | 0.360247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160529E+10 | 0.00 | 0.00 | 0.00 | 0.288058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156774E+10 | 0.00 | 0.00 | 0.00 | 0.121324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150145E+10 | 0.00 | 0.00 | 0.00 | 0.122471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158334E+10 | 0.00 | 0.00 | 0.00 | 378.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192326E+11 | 0.00 | 0.00 | 0.00 | 0.190358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145148E+10 | 0.00 | 0.00 | 0.00 | 310.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174320E+10 | 0.00 | 0.00 | 0.00 | 0.391748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.819507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751786E+10 | 0.00 | 0.00 | 0.00 | 15545.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.880195E+10 | 0.00 | 0.00 | 0.00 | 86663791.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829450E+10 | 0.00 | 0.00 | 0.00 | 0.336095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.907867E+10 | 0.00 | 0.00 | 0.00 | 0.898353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.968204E+10 | 0.00 | 0.00 | 0.00 | 0.154330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.958037E+10 | 0.00 | 0.00 | 0.00 | 0.162602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.988522E+10 | 0.00 | 0.00 | 0.00 | 0.139809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882585E+10 | 0.00 | 0.00 | 0.00 | 0.105610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.830984E+10 | 0.00 | 0.00 | 0.00 | 0.318435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.782564E+10 | 0.00 | 0.00 | 0.00 | 81609046.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.823456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104232E+12 | 0.00 | 0.00 | 0.00 | 0.719321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.988522E+10 | 0.00 | 0.00 | 0.00 | 0.162602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.753239E+09 | 0.00 | 0.00 | 391852.45 | 0.00 | 0.336024E+09 | 0.693788E+09 | 0.00 | 0.19 |
February | 0.571501E+09 | 0.00 | 0.00 | 904608.45 | 0.00 | 0.159770E+09 | 0.119578E+10 | 0.00 | 0.34 |
March | 0.414955E+09 | 25872.24 | 0.00 | 2643260.36 | 0.00 | 53821896.31 | 0.229521E+10 | 0.00 | 0.59 |
April | 71760079.28 | 57421549.02 | 0.00 | 4517938.56 | 0.00 | 0.00 | 0.207644E+10 | 0.00 | 0.61 |
May | 12810399.71 | 0.264880E+09 | 0.00 | 6023063.31 | 0.00 | 0.00 | 0.107458E+10 | 0.00 | 0.51 |
June | 508820.67 | 0.613947E+09 | 0.00 | 7254946.88 | 325583.45 | 0.00 | 0.262001E+09 | 0.00 | 0.35 |
July | 0.00 | 0.152845E+10 | 0.00 | 4746632.36 | 0.00 | 0.00 | 35746990.37 | 0.00 | 0.35 |
August | 121276.45 | 0.854052E+09 | 0.00 | 8493444.04 | 738675.48 | 0.00 | 0.424769E+09 | 0.00 | 0.49 |
September | 6699721.36 | 0.653221E+09 | 0.00 | 7793794.99 | 37898.04 | 0.00 | 0.708012E+09 | 0.00 | 0.50 |
October | 13488718.92 | 0.146360E+09 | 0.00 | 6782753.73 | 0.00 | 0.00 | 0.292346E+10 | 0.00 | 0.82 |
November | 0.335450E+09 | 0.00 | 0.00 | 3063729.95 | 0.00 | 43047898.84 | 0.264748E+10 | 0.00 | 0.57 |
December | 0.737665E+09 | 0.00 | 0.00 | 497729.60 | 0.00 | 0.370262E+09 | 0.861754E+09 | 0.00 | 0.19 |
Annual Sum or Average | 0.291820E+10 | 0.411836E+10 | 0.00 | 53113754.68 | 1102156.97 | 0.962925E+09 | 0.151990E+11 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 391852.45 | 0.00 | 0.00 | 35746990.37 | 0.00 | 0.19 |
Maximum of Months | 0.753239E+09 | 0.152845E+10 | 0.00 | 8493444.04 | 738675.48 | 0.370262E+09 | 0.292346E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.525024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5310342.01 | 0.00 | 0.00 | 0.18 |
February | 0.468922E+10 | 0.00 | 0.00 | 74434.80 | 0.00 | 0.00 | 0.259423E+09 | 0.00 | 0.21 |
March | 0.451608E+10 | 0.00 | 0.00 | 1286232.23 | 0.00 | 0.00 | 0.284766E+10 | 0.00 | 0.39 |
April | 0.102279E+10 | 75944748.72 | 0.00 | 12605007.22 | 0.00 | 0.00 | 0.673307E+10 | 0.00 | 0.69 |
May | 0.162331E+09 | 0.470428E+09 | 0.00 | 17038815.99 | 0.00 | 0.00 | 0.537252E+10 | 0.00 | 0.73 |
June | 10330851.87 | 0.135005E+10 | 0.00 | 19041386.79 | 0.00 | 0.00 | 0.271759E+10 | 0.00 | 0.62 |
July | 2101075.32 | 0.323641E+10 | 0.00 | 8935904.96 | 0.00 | 0.00 | 0.150414E+10 | 0.00 | 0.64 |
August | 14463420.40 | 0.162432E+10 | 0.00 | 19361111.14 | 527242.85 | 0.00 | 0.408188E+10 | 0.00 | 0.77 |
September | 56256205.63 | 0.119694E+10 | 0.00 | 21317068.40 | 0.00 | 0.00 | 0.449842E+10 | 0.00 | 0.75 |
October | 0.632011E+09 | 0.205621E+09 | 0.00 | 14663085.28 | 0.00 | 0.00 | 0.104930E+11 | 0.00 | 0.88 |
November | 0.374860E+10 | 0.00 | 0.00 | 2201263.37 | 0.00 | 0.00 | 0.378925E+10 | 0.00 | 0.35 |
December | 0.563943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19377568.91 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.257438E+11 | 0.815971E+10 | 0.00 | 0.116524E+09 | 527242.85 | 24687910.93 | 0.422970E+11 | 0.00 | 0.53 |
Minimum of Months | 2101075.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.563943E+10 | 0.323641E+10 | 0.00 | 21317068.40 | 527242.85 | 19377568.91 | 0.104930E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.639457E+12 | 0.466654E+11 | 0.00 | 0.703899E+10 | 0.981985E+09 |
February | 0.678048E+12 | 0.388878E+11 | 0.00 | 0.687667E+10 | 0.767341E+09 |
March | 0.104799E+13 | 0.473202E+11 | 0.00 | 0.101316E+11 | 0.158268E+10 |
April | 0.116683E+13 | 0.356334E+11 | 0.00 | 0.979954E+10 | 0.193630E+11 |
May | 0.128001E+13 | 0.401493E+11 | 0.00 | 0.593329E+10 | 0.486854E+11 |
June | 0.127041E+13 | 0.475333E+11 | 0.00 | 0.105802E+10 | 0.786245E+11 |
July | 0.120678E+13 | 0.431804E+11 | 0.00 | -0.323910E+10 | 0.869501E+11 |
August | 0.112183E+13 | 0.491272E+11 | 0.00 | 0.204668E+10 | 0.758764E+11 |
September | 0.102509E+13 | 0.422244E+11 | 0.00 | 0.349453E+10 | 0.590104E+11 |
October | 0.879005E+12 | 0.458396E+11 | 0.00 | 0.137535E+11 | 0.196645E+11 |
November | 0.673378E+12 | 0.502895E+11 | 0.00 | 0.105691E+11 | 0.114056E+10 |
December | 0.547435E+12 | 0.422278E+11 | 0.00 | 0.762899E+10 | 0.124908E+10 |
Annual Sum or Average | 0.115363E+14 | 0.529078E+12 | 0.00 | 0.750918E+11 | 0.393896E+12 |
Minimum of Months | 0.547435E+12 | 0.356334E+11 | 0.00 | -0.323910E+10 | 0.767341E+09 |
Maximum of Months | 0.128001E+13 | 0.502895E+11 | 0.00 | 0.137535E+11 | 0.869501E+11 |