Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 10:43:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 551.84 | 114.13 | 114.13 |
Net Site Energy | 551.84 | 114.13 | 114.13 |
Total Source Energy | 1747.66 | 361.45 | 361.45 |
Net Source Energy | 1747.66 | 361.45 | 361.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 154.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 21.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 551.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 154.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 96.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 36.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 21.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 154.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 96.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 66.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 21.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 35.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 114.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 35.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 114.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 551.833 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 551.833 | 100.00 |
Total On-Site and Utility Electric Sources | 551.833 | 100.00 |
Total Electricity End Uses | 551.833 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 8.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2849.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6766 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 7.6766 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.3906 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.5498 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:39 | 02-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 3398.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29073.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5018.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6187.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1446.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 51839.21 | 3398.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 3398.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 29073.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5018.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3882.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1446.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 488.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 306.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 231.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1747.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 43.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 63.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 43.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.26 |
ZONE2 FINE STORAGE DIRECT AIR | 3.31 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE HEATING COIL | 30106.13 |
PSZ-FINE STORAGE HEATING COIL | 99245.95 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-FINE STORAGE | 3.31 | 3.31 | 3.31 | 3.31 | 3.31 | 3.31 | 1.00 | 1.00 | 3.31 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.26 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.31 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.26 | 1398.69 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.31 | 3539.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.833788 | 27225.54 | 30106.13 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.31 | 3.31 | 3.31 | 2.18 | 82143.83 | 99245.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.26 | 0.631658 | 0.842213 | 27225.54 | 13612.77 | 0.748400 | 0.748400 |
PSZ-FINE STORAGE COOLING COIL | 3.31 | 1.65 | 2.21 | 82143.83 | 41071.92 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 7.677 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.750 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1818.427 | 7.677 | 142.636 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1818.427 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10866.415 | 3.391 | 157.484 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2587 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2587 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.865 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.865 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.31452820E-09 | 0.26304591E-14 | 0.87829942E-15 | 0.0000000 |
2 | 1 | -5.2160429 | 0.46652437E-04 | -0.61920073E-04 | 0.60300157E-10 |
3 | 0 | 5.4747659 | 0.25867629 | 0.25878486 | |
4 | 2 | 0.31452820E-09 | 0.26304591E-14 | 0.87829942E-15 | 0.0000000 |
5 | 1 | -5.2160429 | 0.46652437E-04 | -0.61920073E-04 | 0.60300157E-10 |
6 | 0 | 5.4747659 | 0.25867629 | 0.25878486 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.504_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.504_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.16139 | 0.61064 | 0.61064 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3853E-004 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0339E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2516E-004 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3062E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1877E-004 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0675E-003 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5848E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1816E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4464E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.1090E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0913E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3123E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1942E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0578E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7680E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3855E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.4983E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9785E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6559E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0526E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2216E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8178E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2141E-003 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2648E-004 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0921E-003 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2551E-004 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9815E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2852E-004 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4786E-003 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1701E-004 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0450E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8226E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0198E-003 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.9456E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0372E-003 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0110E-004 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2584E-003 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6179E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2695E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9692E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9140E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8971E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1575E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0160E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0037E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8475E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9222E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6649E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2334E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0762E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4292E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2259E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3039E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9289E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8087E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6800E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0624E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0451E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0223E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0706E-004 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.9911E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8613E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0163E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2929E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4275E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3073E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4902E-004 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2384E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2588E-004 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0000E-004 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3309E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7386E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9464E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9678E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1033E-003 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2372E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3510E-004 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0339E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8640E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5640E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0140E-003 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8279E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8111E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2488E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9545E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4982E-004 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7635E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3403E-004 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7447E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2857E-004 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2986E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7796E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0551E-004 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9751E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.9856E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.1980E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5782E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8242E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0280E-004 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1628E-003 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.7742E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0908E-003 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3763E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5807E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0681E-004 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3476E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4933E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7878E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4210E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4083E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8297E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6895E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7927E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1649E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1672E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1615E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4442E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5412E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1639E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2525E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8810E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2902E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5417E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7822E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4393E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6220E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4535E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6871E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6561E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9584E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7163E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0897E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8455E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6992E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4174E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3769E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9618E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3780E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5222E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3435E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7764E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1628E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9993E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7372E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9357E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1903E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2435E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2428E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2349E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0447E-004 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1375E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7347E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6616E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4058E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1256E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6534E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2534E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8750E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5254E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3747E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3970E-004 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3097E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3647E-004 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5605E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4840E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4414E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5939E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8958E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5260E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3309E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8353E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5805E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1266E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2604E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5435E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1536E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0525E-004 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1956E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0534E-004 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5364E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0272E-004 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2591E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2647E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8954E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6437E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9674E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5728E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7993E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5914E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0571E-004 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9813E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0829E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2699E-004 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4165E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2327E-004 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7922E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3491E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8581E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9167E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2240E-003 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3413E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3261E-003 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7432E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3409E-003 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7620E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8668E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7823E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7049E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9208E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7154E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7671E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9764E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9621E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9061E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3526E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9908E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5391E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8739E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2269E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3593E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6608E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9089E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8755E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9413E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7077E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7180E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5848E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0334E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9941E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6221E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2670E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3063E-004 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3837E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2188E-004 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7676E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4720E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4248E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2491E-004 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6724E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9969E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6579E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8372E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1980E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1673E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8036E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2886E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7137E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0498E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0048E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8388E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3641E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9796E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1830E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6886E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9376E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4449E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6732E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7326E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9778E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6189E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9424E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4128E-003 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6757E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2513E-003 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1923E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7663E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9837E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0166E-003 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1241E-004 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0311E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0196E-004 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3358E-003 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2384E-004 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2457E-004 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1555E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4364E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9262E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9186E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1510E-003 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8674E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3924E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7331E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3347E-004 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2431E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1432E-004 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4973E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2659E-004 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4411E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8861E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4851E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1934E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8688E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8631E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5283E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3958E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6558E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7122E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1154E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4488E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1494E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1403E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6876E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0703E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2504E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6374E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3801E-004 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2834E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2026E-004 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0701E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4583E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2362E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8833E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3453E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8209E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6293E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7328E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3542E-004 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5034E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3782E-004 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0461E-004 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5303E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4879E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1443E-004 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2411E-004 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8618E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2323E-004 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0354E-004 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2098E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5178E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8043E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8734E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8123E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7152E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1417E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7761E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0452E-004 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9739E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5516E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6997E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9560E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8652E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8591E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8048E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6474E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8551E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4822E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6943E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2451E-004 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1574E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2946E-004 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3220E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2086E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2207E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9773E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6976E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5519E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2574E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3662E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1085E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7938E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1762E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6861E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4546E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2934E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8301E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1623E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5219E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1395E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4070E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7475E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.0730E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.0950E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6621E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.4376E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.2701E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2519E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8282E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.0770E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1211E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6640E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2875E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.2677E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2518E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12789.62550 | 15347.55060 | 1.05276 | 1.26332 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 42.31500 | 1.07810E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 4565.43533 | 5478.52240 | 0.12783 | 0.15339 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 42959.60319 | 51551.52383 | 2.75661 | 3.30793 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 3645.15573 | 4374.18688 | 8.62382E-002 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 20458.51 | 1.26332 | 1.26332 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 4553.84 | 0.15339 | 0.15339 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 67073.28 | 3.30793 | 3.30793 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 14023.03 | 0.42471 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26332 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.30793 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26332 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26332 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26332 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26332 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26332 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.26332 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.30793 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.30793 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.30793 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.30793 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.30793 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.30793 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.26332 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.30793 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26332 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26332 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1398.69105 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26332 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26332 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26332 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83379 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26332 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63166 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84221 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27225.54000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13612.77000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74840 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74840 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27225.54000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30106.12620 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 30106.12620 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.30793 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.30793 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3539.64380 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.30793 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.30793 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.30793 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.18324 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.30793 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.65397 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.20529 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 82143.83000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41071.91500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 82143.83000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 99245.94873 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 99245.94873 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 26244.2 | 11.98 | 11.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 79572.6 | 11.12 | 10.87 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.4089067920E-002 | 2.0438832413E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.3849398460E-002 | 3.2853935354E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.2567557237E-002 | 2.3122361009E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5190.19 | 251.55 | 0.00 | -122.4 | 694.69 | 6014.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.250 | 0.259 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.250 | 0.259 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.865 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.504_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.865 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.865 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.504_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.865 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.647 | 0.529 | 0.530 | |||||||||||||||||
North Total or Average | 6.51 | 2.865 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.793 | 0.552 | 0.553 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 7.6766 | 236.88 | 1818.43 | LightsWired | LTG_SCH_OFFICE | 49.99 | 168.00 | 44.75 | 0.0000 | Y | 15.28 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 22.47 | 0.0000 | Y | 39.29 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.3906 | 3204.84 | 10866.42 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 20.63 | 0.0000 | Y | 42.08 |
Interior Lighting Total | 4.5498 | 4835.13 | 21998.92 | 96.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1818.43 | 263.67 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 1818.43 | 90.92 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 41.85 | 41.85 | 0.73 | |
EXTERIOR_LIGHTS_B | 5399.43 | AstronomicalClock | - | 83.85 | 71.25 | 72.22 | |
Exterior Lighting Total | 5492.60 | 72.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27225.54 | 20375.59 | 6849.95 | 0.75 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 82143.83 | 57589.40 | 24554.43 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 26244.2 | 11.98 | 11.71 | ||||
PSZ-FINE STORAGE COOLING COIL | 79572.6 | 11.12 | 10.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39959.00 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 30106.13 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 99245.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1398.69 | 1107.16 | 1.00 | 1.35 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 3.31 | 3539.64 | 1070.05 | 1.00 | 1.25 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12789.63 | 15347.55 | 64.79 | 1.053 | 1.263 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 23.90 | 23.90 | 0.00834 | 42.31 | 0.01078 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 42959.60 | 51551.52 | 37.00 | 2.757 | 3.308 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00854 | 42.80 | 0.01078 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 0.00 | 42.04 | 0.01086 | 42.70 | 0.01078 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 4565.44 | 5478.52 | 23.13 | 0.128 | 0.153 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00907 | 12.70 | 0.00915 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 3645.16 | 4374.19 | 3.14 | 0.086 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00880 | 12.70 | 0.00915 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 15.35 | 0.00938 | 12.70 | 0.00915 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.26 | 1.26 | 0.15 | 0.15 | 1.2633 | 1.2633 | 1.2633 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.31 | 3.31 | 0.42 | 0.42 | 3.3079 | 3.3079 | 3.3079 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 27225.540 | 20375.594 | 1.263320 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 13612.77 | 12530.58 | 0.842213 | 26.30 | 17.22 | 0.00853912 | 12.00 | 11.25 | 0.00800000 | 42.41 | 0.01078115 | 23.76 | 12.1447 | 23.90 | 0.00834147 | 45.1674 | 12781.49 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 30106.126 | 30106.126 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 30106.13 | 30106.13 | 1.263316 | 20.30 | 15.55 | 0.00907413 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.0965 | 21.10 | 0.00906714 | 58.1252 | 4565.44 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 82143.830 | 57589.396 | 3.307930 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 41071.92 | 37032.02 | 2.205287 | 29.64 | 18.57 | 0.00882454 | 12.00 | 11.25 | 0.00800000 | 42.80 | 0.01078182 | 23.86 | 19.2588 | 26.70 | 0.00853622 | 39.1204 | 42959.60 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 99245.949 | 99245.949 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 99245.95 | 99245.95 | 3.307932 | 15.19 | 13.62 | 0.00907849 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.8392 | 15.56 | 0.00906745 | 82.3006 | 3460.02 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27225.540 | 20375.594 | 1.263320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7138 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.263316 | 1.52052048 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 13612.77 | 12530.58 | 1.0000 | 1.01368374 | 0.842213 | 26.30 | 17.22 | 0.00853912 | 48200.2 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13612.77 | 42.41 | 0.01078115 | 23.76 | 0.10228463 | 12.1447 | 23.90 | 0.00834147 | 23.90 | 0.00834147 | 45.1674 | 12781.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30106.126 | 30106.126 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.263316 | 1.52052048 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 30106.13 | 30106.13 | 1.0000 | 1.52052048 | 1.263316 | 20.30 | 15.55 | 0.00907413 | 43430.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30106.13 | 12.70 | 0.00915345 | 12.70 | 0.10228463 | 8.0965 | 20.97 | 0.00906714 | 21.10 | 0.00906714 | 58.1252 | 4565.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 82143.830 | 57589.396 | 3.307930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2444 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.307932 | 3.98141057 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 41071.92 | 37032.02 | 1.0000 | 2.65427196 | 2.205287 | 29.64 | 18.57 | 0.00882454 | 52334.9 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41071.92 | 42.80 | 0.01078182 | 23.86 | 0.42471127 | 19.2588 | 26.70 | 0.00853622 | 26.70 | 0.00853622 | 39.1204 | 42959.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99245.949 | 99245.949 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.307932 | 3.98141057 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 99245.95 | 99245.95 | 1.0000 | 3.98141057 | 3.307932 | 15.19 | 13.62 | 0.00907849 | 38227.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99245.95 | 12.70 | 0.00915345 | 12.70 | 0.42471127 | 12.8392 | 15.56 | 0.00906745 | 15.56 | 0.00906745 | 82.3006 | 3460.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3253.50 | 641.50 | 509.33 |
ZONE2 FINE STORAGE | 3406.83 | 2768.50 | 2607.33 |
ZONE3 BULK STORAGE | 3362.33 | 3020.00 | 2816.50 |
Facility | 3459.83 | 3092.33 | 2849.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 13.17 | 0.00 | 3.67 |
ZONE2 FINE STORAGE | 0.00 | 387.33 | 0.00 | 5.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 400.17 | 0.00 | 8.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.347 | 0.408 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.498 | 0.222 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.141 | 0.000 | 2.100 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1245653.64 | 0.00 | 1245653.64 | 1981619.38 | 3227273.02 | 3225648.14 | 5424.16 | 3335.84 | 0.00 | 204.60 |
ZONE2 FINE STORAGE | 5931364.97 | 0.00 | 5931364.97 | 5278757.67 | 11210122.64 | 13393694.68 | 5394.67 | 3365.33 | 0.00 | 1754.57 |
ZONE3 BULK STORAGE | 0.00 | 0.55E+09 | 0.55E+09 | 31127439.75 | 0.58E+09 | 30805497.77 | 4332.70 | 8.33 | 4418.97 | 5105.94 |
Total Facility | 7177018.62 | 0.55E+09 | 0.56E+09 | 38387816.80 | 0.60E+09 | 47424840.58 | 6848.27 | 3372.15 | 4418.97 | 5106.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0942 | 0.0000 | 0.0942 | 0.1106 | 0.2048 | 0.1023 | 300.16 | 3335.84 | 0.00 |
ZONE2 FINE STORAGE | 0.3914 | 0.0000 | 0.3914 | 0.1747 | 0.5660 | 0.4247 | 302.97 | 3333.03 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 19.0098 | 19.0098 | 1.2979 | 20.3077 | 0.9768 | 1625.69 | 4.33 | 2005.98 |
Total Facility | 0.4856 | 19.0098 | 19.4954 | 1.5831 | 21.0785 | 1.5038 | 1724.27 | 3335.84 | 2005.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1804518.74 | 0.00 | 1804518.74 | 3225648.14 | 5420.29 | 0.48 | 3339.23 | 202.21 |
PSZ-FINE STORAGE | 8592425.79 | 0.00 | 8592425.79 | 13393694.68 | 5297.53 | 14.46 | 3448.00 | 1754.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1365 | 0.0000 | 0.1365 | 0.1023 | 298.10 | 0.28 | 3337.62 |
PSZ-FINE STORAGE | 0.5670 | 0.0000 | 0.5670 | 0.4247 | 300.12 | 0.44 | 3335.44 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3590.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5162.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1464 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6049 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
Electricity:Building | 272.11 | 1328.97 | 19-MAR-15:20 | 21347.48 | 13-NOV-17:00 |
Electricity:Zone:ZONE1 OFFICE | 47.22 | 774.00 | 12-FEB-16:10 | 2968.85 | 15-MAR-07:10 |
Electricity:SpaceType:GENERAL | 235.94 | 1328.97 | 19-MAR-15:20 | 19742.93 | 14-MAR-08:10 |
InteriorLights:Electricity | 96.65 | 755.22 | 19-MAR-15:20 | 9630.31 | 14-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.28 | 200.25 | 12-FEB-16:10 | 1056.35 | 15-MAR-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 96.65 | 755.22 | 19-MAR-15:20 | 9630.31 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity | 96.65 | 755.22 | 19-MAR-15:20 | 9630.31 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.28 | 200.25 | 12-FEB-16:10 | 1056.35 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 96.65 | 755.22 | 19-MAR-15:20 | 9630.31 | 14-MAR-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 39.29 | 256.14 | 01-JAN-10:50 | 4354.33 | 14-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 39.29 | 256.14 | 01-JAN-10:50 | 4354.33 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 39.29 | 256.14 | 01-JAN-10:50 | 4354.33 | 14-MAR-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 185.60 | 298.83 | 01-JAN-08:50 | 14614.28 | 06-NOV-17:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 42.08 | 298.83 | 01-JAN-08:50 | 4482.40 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 42.08 | 298.83 | 01-JAN-08:50 | 4482.40 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 66.64 | 0.00 | 01-JAN-00:10 | 6289.24 | 10-AUG-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 36.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 22-APR-17:10 |
Ventilation (simple):Fans:Electricity | 36.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 22-APR-17:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 36.17 | 0.00 | 01-JAN-00:10 | 2305.29 | 22-APR-17:10 |
ElectricityPurchased:Facility | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
ElectricityPurchased:Plant | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
Cogeneration:ElectricityPurchased | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
ElectricityNet:Plant | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
Cogeneration:ElectricityNet | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
General:Cogeneration:ElectricityNet | 551.83 | 1813.90 | 12-MAR-15:30 | 51839.21 | 10-AUG-15:40 |
Electricity:HVAC | 184.86 | 0.00 | 01-JAN-00:10 | 33507.14 | 10-AUG-16:00 |
General:Fans:Electricity | 30.47 | 0.00 | 01-JAN-00:10 | 3983.94 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 154.39 | 0.00 | 01-JAN-00:10 | 29556.27 | 10-AUG-16:00 |
General:Cooling:Electricity | 154.39 | 0.00 | 01-JAN-00:10 | 29556.27 | 10-AUG-16:00 |
ExteriorLights:Electricity | 72.95 | 0.00 | 01-JAN-07:10 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.95 | 0.00 | 01-JAN-07:10 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 21.91 | 483.00 | 01-JAN-00:10 | 1738.98 | 14-JAN-12:10 |
WaterSystems:Electricity | 21.91 | 483.00 | 01-JAN-00:10 | 1738.98 | 14-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 21.91 | 483.00 | 01-JAN-00:10 | 1738.98 | 14-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 3398.38 | 02-JAN-08:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 3398.38 | 02-JAN-08:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 3398.38 | 02-JAN-08:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 3398.38 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 860.45 | 0.00 | 01-JAN-00:10 | 141361.07 | 10-AUG-16:10 |
EnergyTransfer:Building | 320.15 | 0.00 | 01-JAN-00:10 | 49019.04 | 21-JUL-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 92.57 | 0.00 | 01-JAN-00:10 | 16728.28 | 16-AUG-12:00 |
Heating:EnergyTransfer | 0.11 | 0.00 | 01-JAN-00:10 | 1955.10 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.04 | 0.00 | 01-JAN-00:10 | 1955.10 | 02-JAN-08:10 |
General:Heating:EnergyTransfer | 0.11 | 0.00 | 01-JAN-00:10 | 1955.10 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.04 | 0.00 | 01-JAN-00:10 | 1955.10 | 02-JAN-08:10 |
Cooling:EnergyTransfer | 320.04 | 0.00 | 01-JAN-00:10 | 49019.04 | 21-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 92.53 | 0.00 | 01-JAN-00:10 | 16728.28 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 320.04 | 0.00 | 01-JAN-00:10 | 49019.04 | 21-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 92.53 | 0.00 | 01-JAN-00:10 | 16728.28 | 16-AUG-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 227.58 | 0.00 | 01-JAN-00:10 | 39287.71 | 30-JUL-14:40 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.07 | 0.00 | 01-JAN-00:10 | 1060.01 | 23-JAN-12:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.07 | 0.00 | 01-JAN-00:10 | 1060.01 | 23-JAN-12:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 227.51 | 0.00 | 01-JAN-00:10 | 39287.71 | 30-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 227.51 | 0.00 | 01-JAN-00:10 | 39287.71 | 30-JUL-14:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 540.30 | 0.00 | 01-JAN-00:10 | 97325.16 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 2299.56 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 540.30 | 0.00 | 01-JAN-00:10 | 97325.16 | 22-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.038 | -92.530 | 0.000 | 0.000 | 9.065 | 15.276 | 31.946 | 13.577 | 0.000 | 12.047 | 16.751 | 0.000 | -2.904 | 0.000 | -3.267 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.068 | -227.509 | 0.000 | 0.000 | 17.535 | 39.294 | 0.000 | 73.954 | 0.000 | 25.559 | 90.357 | 0.000 | -9.654 | 0.000 | -9.603 | -0.002 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21.866 | 42.080 | 107.344 | 858.518 | 0.000 | 152.129 | 0.002 | 0.000 | -120.490 | 0.000 | -431.200 | -630.247 |
Total Facility | 0.000 | 0.000 | 0.106 | -320.039 | 0.000 | 0.000 | 48.465 | 96.650 | 139.290 | 946.049 | 0.000 | 189.735 | 107.111 | 0.000 | -133.048 | 0.000 | -444.071 | -630.250 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -25453.56 | 0.00 | 0.00 | 138.42 | 580.44 | 956.25 | 0.00 | 0.00 | 0.00 | 24918.42 | 0.00 | -230.26 | 0.00 | -909.72 | 0.00 |
ZONE2 FINE STORAGE | 15-OCT-13:23 | 0.00 | 0.00 | 0.00 | -68801.95 | 0.00 | 0.00 | 0.00 | 256.14 | 0.00 | 7505.30 | 0.00 | 2345.40 | 58695.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-MAY-12:23 | 0.00 | 0.00 | 0.00 | -73157.85 | 0.00 | 0.00 | 0.00 | 772.54 | 573.75 | 127740.73 | 0.00 | 12195.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -68125.11 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-08:63 | 0.00 | 0.00 | 5865.51 | 0.00 | 0.00 | 0.00 | 1126.80 | 1023.86 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -155.35 | 0.00 | -573.86 | -9199.45 |
ZONE2 FINE STORAGE | 16-JUN-06:03 | 0.00 | 0.00 | 2808.78 | 0.00 | 0.00 | 0.00 | 357.55 | 3073.65 | 0.00 | 154.80 | 0.00 | 132.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6527.08 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JAN-08:63 | -2295.85 | 2295.85 | 5865.51 | -2295.85 | 0.00 | 0.00 | 9744.44 | 7160.48 | 10112.62 | 8165.47 | 0.00 | 0.00 | 0.00 | 0.00 | -155.35 | 0.00 | -8517.85 | -30079.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2633 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2633 | 0.0810 | 1.0000 | Not calculated | 0.1023 | 0.0810 | ||
PSZ-FINE STORAGE | 3.3079 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.3079 | 0.1284 | 1.0000 | Not calculated | 0.4247 | 0.1284 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2633 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2633 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0810 | ||
PSZ-FINE STORAGE | 3.3079 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.3079 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1284 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2633 | 1.2633 | 1.2633 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3079 | 3.3079 | 3.3079 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2633 | 1.2633 | 1.2633 | 1.2633 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.3079 | 3.3079 | 3.3079 | 3.3079 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2633 | 1.2633 | 1.2633 | No | 0.1023 | 0.6668 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3079 | 3.3079 | 3.3079 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2633 | 1.2633 | 1.2633 | 1.2633 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.3079 | 3.3079 | 3.3079 | 3.3079 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 8.67 |
Number of hours not met | 8.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 3398.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 154.39 | 29556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 96.65 | 9630.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.95 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 36.17 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 30.47 | 3983.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 21.91 | 1738.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 551.83 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 551.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 19.99 |
Space Heating | 0.00 |
Space Cooling | 31.93 |
Fans (All) | 13.78 |
Service Water Heating | 4.53 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 114.13 |
Subtotal | 114.13 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.51 |
Space Heating | 0.00 |
Space Cooling | 27.98 |
Fans (All) | 12.08 |
Service Water Heating | 3.97 |
Receptacle Equipment | 25.24 |
Miscellaneous | 13.22 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2607. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4909.17 | 3387.67 | 463.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3407.83 | 5352.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2205.83 | 2707.17 | 1971.33 | 1844.67 | 31.00 |
Min | 2205.83 | 2707.17 | 0.00 | 0.00 | 0.00 |
Max | 4909.17 | 5352.17 | 1971.33 | 1844.67 | 31.00 |
Average | 3507.61 | 3815.67 | 811.50 | 614.89 | 10.33 |
Sum | 10522.83 | 11447.00 | 2434.50 | 1844.67 | 31.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32816.17 | 210.67 | 0.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 25975.00 | 56744.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 41111.67 | 59042.83 | 46327.00 | 43283.00 | 1428.50 |
Min | 25975.00 | 210.67 | 0.00 | 0.00 | 0.00 |
Max | 41111.67 | 59042.83 | 46327.00 | 43283.00 | 1428.50 |
Average | 33300.94 | 38665.83 | 15442.39 | 14427.67 | 476.17 |
Sum | 99902.83 | 115997.50 | 46327.17 | 43283.00 | 1428.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4088.50 | 4570.33 | 101.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2230.17 | 6529.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1641.33 | 4021.50 | 1439.17 | 1374.67 | 283.33 |
Min | 1641.33 | 4021.50 | 0.00 | 0.00 | 0.00 |
Max | 4088.50 | 6529.83 | 1439.17 | 1374.67 | 283.33 |
Average | 2653.33 | 5040.56 | 513.44 | 458.22 | 94.44 |
Sum | 7960.00 | 15121.67 | 1540.33 | 1374.67 | 283.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31034.17 | 1992.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 18070.00 | 64649.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 28351.17 | 92546.67 | 31853.17 | 29015.83 | 9426.17 |
Min | 18070.00 | 1992.83 | 0.00 | 0.00 | 0.00 |
Max | 31034.17 | 92546.67 | 31853.17 | 29015.83 | 9426.17 |
Average | 25818.44 | 53062.83 | 10617.72 | 9671.94 | 3142.06 |
Sum | 77455.33 | 159188.50 | 31853.17 | 29015.83 | 9426.17 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307546E+10 | 12759.20 | 30-JAN-08:63 | 20.33 | 17.75 | 0.630645E+09 | 826.02 | 30-JAN-08:09 | 20.33 | 17.75 |
February | 0.384249E+10 | 23557.12 | 11-FEB-08:62 | 20.00 | 14.46 | 0.584292E+09 | 879.39 | 09-FEB-08:09 | 20.00 | 14.46 |
March | 0.569868E+10 | 25453.97 | 28-MAR-06:02 | 24.00 | 14.40 | 0.688839E+09 | 879.41 | 02-MAR-08:09 | 24.00 | 14.40 |
April | 0.677939E+10 | 25114.69 | 25-APR-06:02 | 23.17 | 13.26 | 0.640288E+09 | 879.42 | 29-APR-07:10 | 27.25 | 16.62 |
May | 0.942726E+10 | 25187.95 | 05-MAY-06:01 | 25.92 | 15.74 | 0.667310E+09 | 879.42 | 08-MAY-07:10 | 27.75 | 16.25 |
June | 0.102662E+11 | 22492.52 | 16-JUN-06:01 | 29.00 | 20.06 | 0.667338E+09 | 879.45 | 12-JUN-07:10 | 29.00 | 20.06 |
July | 0.109579E+11 | 23102.49 | 03-JUL-05:02 | 28.83 | 16.82 | 0.641740E+09 | 879.47 | 17-JUL-07:10 | 31.50 | 26.90 |
August | 0.120925E+11 | 20381.30 | 07-AUG-05:02 | 32.82 | 23.16 | 0.693196E+09 | 879.46 | 21-AUG-07:10 | 30.17 | 28.35 |
September | 0.100798E+11 | 20133.17 | 26-SEP-07:02 | 27.00 | 17.98 | 0.641698E+09 | 879.47 | 07-SEP-07:10 | 27.00 | 17.98 |
October | 0.883630E+10 | 24854.25 | 20-OCT-06:01 | 23.82 | 15.96 | 0.641683E+09 | 879.39 | 07-OCT-07:10 | 23.82 | 15.96 |
November | 0.680691E+10 | 23104.68 | 18-NOV-07:02 | 20.75 | 15.04 | 0.615158E+09 | 879.39 | 03-NOV-07:10 | 20.75 | 15.04 |
December | 0.466860E+10 | 21635.73 | 02-DEC-08:62 | 19.50 | 15.43 | 0.636815E+09 | 879.39 | 09-DEC-08:09 | 19.33 | 17.80 |
Annual Sum or Average | 0.925315E+11 | 0.774900E+10 | ||||||||
Minimum of Months | 0.307546E+10 | 12759.20 | 19.50 | 13.26 | 0.584292E+09 | 826.02 | 19.33 | 14.40 | ||
Maximum of Months | 0.120925E+11 | 25453.97 | 32.82 | 23.16 | 0.693196E+09 | 879.47 | 31.50 | 28.35 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.972170E+09 | 3792.04 | 09-JAN-08:10 | 12.17 | 12.17 | 0.163056E+10 | 2246.82 | 28-JAN-14:00 | 26.00 | 18.37 |
February | 0.213122E+10 | 24960.34 | 05-FEB-14:55 | 32.00 | 19.39 | 0.161600E+10 | 2246.89 | 06-FEB-14:30 | 32.25 | 17.25 |
March | 0.618148E+10 | 59787.03 | 26-MAR-13:43 | 33.33 | 18.37 | 0.195477E+10 | 2246.90 | 21-MAR-12:39 | 33.33 | 18.37 |
April | 0.131554E+11 | 62090.64 | 02-APR-13:43 | 33.73 | 18.49 | 0.184573E+10 | 2246.94 | 11-APR-15:20 | 29.33 | 19.80 |
May | 0.271870E+11 | 66811.24 | 14-MAY-16:23 | 34.00 | 20.91 | 0.192894E+10 | 2247.03 | 30-MAY-15:30 | 38.75 | 25.65 |
June | 0.317531E+11 | 64659.19 | 20-JUN-17:42 | 37.17 | 19.79 | 0.192890E+10 | 2247.04 | 12-JUN-12:50 | 37.17 | 19.79 |
July | 0.386440E+11 | 61270.27 | 03-JUL-17:05 | 40.83 | 20.49 | 0.185470E+10 | 2247.05 | 31-JUL-12:30 | 40.95 | 26.01 |
August | 0.405366E+11 | 58630.69 | 02-AUG-00:23 | 36.40 | 23.11 | 0.200313E+10 | 2247.05 | 17-AUG-12:30 | 43.50 | 24.36 |
September | 0.307645E+11 | 59118.07 | 04-SEP-10:23 | 38.00 | 23.07 | 0.185476E+10 | 2247.06 | 05-SEP-14:20 | 39.67 | 25.10 |
October | 0.222636E+11 | 68803.55 | 15-OCT-13:23 | 35.10 | 19.49 | 0.185482E+10 | 2246.97 | 16-OCT-12:00 | 32.90 | 25.19 |
November | 0.108839E+11 | 59480.80 | 05-NOV-12:03 | 33.90 | 17.83 | 0.177549E+10 | 2246.95 | 04-NOV-14:50 | 33.90 | 17.83 |
December | 0.303971E+10 | 25292.14 | 03-DEC-13:05 | 29.33 | 18.32 | 0.178285E+10 | 2246.82 | 30-DEC-15:30 | 24.50 | 13.81 |
Annual Sum or Average | 0.227513E+12 | 0.220307E+11 | ||||||||
Minimum of Months | 0.972170E+09 | 3792.04 | 12.17 | 12.17 | 0.161600E+10 | 2246.82 | 24.50 | 13.81 | ||
Maximum of Months | 0.405366E+11 | 68803.55 | 40.83 | 23.11 | 0.200313E+10 | 2247.06 | 43.50 | 26.01 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.344167E+10 | 4938.73 | 28-JAN-14:50 | 26.33 | 17.65 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.364522E+10 | 5894.31 | 08-FEB-14:39 | 29.00 | 19.99 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.496533E+10 | 8930.33 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.554745E+10 | 9097.65 | 24-APR-12:50 | 37.33 | 17.85 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 | 23.56 | 0.691521E+10 | 9097.65 | 04-MAY-10:20 | 38.03 | 18.31 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.720341E+10 | 9097.65 | 01-JUN-09:09 | 37.48 | 21.75 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.722850E+10 | 9097.65 | 01-JUL-09:50 | 37.25 | 26.05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.785625E+10 | 9097.65 | 01-AUG-08:00 | 37.00 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.683145E+10 | 9097.65 | 01-SEP-10:20 | 36.27 | 25.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.608193E+10 | 9097.65 | 02-OCT-12:00 | 36.70 | 19.32 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 | 21.17 | 0.506010E+10 | 7694.81 | 01-NOV-14:20 | 32.67 | 26.20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.435806E+10 | 6274.51 | 01-DEC-14:30 | 28.00 | 18.25 |
Annual Sum or Average | 0.00 | 0.691346E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.344167E+10 | 4938.73 | 26.33 | 17.65 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.785625E+10 | 9097.65 | 38.03 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2438404.04 | 5865.30 | 02-JAN-08:63 | 13.50 |
February | 1836428.25 | 570.27 | 09-FEB-07:07 | 22.42 |
March | 4016754.06 | 989.52 | 02-MAR-07:05 | 27.67 |
April | 4818352.51 | 1069.76 | 29-APR-06:04 | 25.25 |
May | 5985102.15 | 1164.07 | 13-MAY-06:05 | 28.10 |
June | 3843319.89 | 1423.45 | 17-JUN-06:05 | 29.03 |
July | 811599.04 | 1653.86 | 22-JUL-06:05 | 31.25 |
August | 298697.16 | 1274.11 | 26-AUG-06:07 | 29.97 |
September | 3096907.59 | 1138.50 | 09-SEP-06:07 | 28.90 |
October | 5633694.83 | 1015.66 | 03-OCT-06:05 | 26.87 |
November | 4040440.29 | 825.94 | 25-NOV-07:05 | 24.70 |
December | 1621463.17 | 841.74 | 12-DEC-07:05 | 23.17 |
Annual Sum or Average | 38441162.97 | |||
Minimum of Months | 298697.16 | 570.27 | 13.50 | |
Maximum of Months | 5985102.15 | 5865.30 | 31.25 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38848959.28 | 1060.01 | 23-JAN-12:50 | 26.67 |
February | 7797227.40 | 946.86 | 04-FEB-10:30 | 26.50 |
March | 9267875.74 | 1964.09 | 02-MAR-07:03 | 27.67 |
April | 493663.89 | 1119.43 | 29-APR-06:03 | 25.25 |
May | 2829372.56 | 2500.46 | 31-MAY-06:02 | 27.83 |
June | 2432072.86 | 2808.75 | 16-JUN-06:03 | 29.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 2223932.75 | 2018.36 | 21-SEP-06:03 | 27.08 |
October | 1756734.93 | 2130.09 | 05-OCT-06:02 | 26.92 |
November | 405868.02 | 769.86 | 20-NOV-07:02 | 25.25 |
December | 1904596.10 | 464.60 | 23-DEC-17:40 | 24.40 |
Annual Sum or Average | 67960303.52 | |||
Minimum of Months | 0.00 | 0.00 | 24.40 | |
Maximum of Months | 38848959.28 | 2808.75 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130601E+10 | 1041.96 | 09-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.117471E+10 | 1039.57 | 09-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.133380E+10 | 1056.35 | 15-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.125604E+10 | 1044.29 | 18-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.129034E+10 | 1002.27 | 23-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.126121E+10 | 1005.92 | 08-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.125996E+10 | 1034.96 | 20-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.131414E+10 | 1019.96 | 29-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.124874E+10 | 1026.10 | 06-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.127787E+10 | 1035.10 | 31-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.124365E+10 | 1035.95 | 29-NOV-08:09 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.130996E+10 | 1050.37 | 15-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.152764E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.117471E+10 | 1002.27 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.133380E+10 | 1056.35 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.352040E+10 | 3842.06 | 02-JAN-16:49 | 0.00 | 0.00 |
February | 0.308976E+10 | 3842.06 | 09-FEB-16:49 | 0.00 | 0.00 |
March | 0.344105E+10 | 4354.33 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.313645E+10 | 3842.06 | 18-APR-07:10 | 0.00 | 0.00 |
May | 0.320497E+10 | 3521.89 | 03-MAY-07:10 | 0.00 | 0.00 |
June | 0.314996E+10 | 3265.75 | 02-JUN-08:09 | 0.00 | 0.00 |
July | 0.311798E+10 | 3521.89 | 03-JUL-07:10 | 0.00 | 0.00 |
August | 0.328972E+10 | 3521.89 | 01-AUG-07:10 | 0.00 | 0.00 |
September | 0.314585E+10 | 3521.89 | 01-SEP-07:10 | 0.00 | 0.00 |
October | 0.330081E+10 | 3842.06 | 11-OCT-07:10 | 0.00 | 0.00 |
November | 0.331986E+10 | 3842.06 | 01-NOV-07:10 | 0.00 | 0.00 |
December | 0.357693E+10 | 3991.47 | 09-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392938E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.308976E+10 | 3265.75 | 0.00 | 0.00 | |
Maximum of Months | 0.357693E+10 | 4354.33 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.372359E+10 | 4108.86 | 02-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.330303E+10 | 3735.33 | 06-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.370555E+10 | 4482.40 | 14-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.337659E+10 | 3735.33 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.341917E+10 | 3585.92 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.335954E+10 | 3585.92 | 08-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.334420E+10 | 3735.33 | 20-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.355596E+10 | 3585.92 | 01-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.340414E+10 | 3585.92 | 01-SEP-06:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.354849E+10 | 3735.33 | 11-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.354356E+10 | 4482.40 | 29-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.379619E+10 | 4482.40 | 07-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.420800E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.330303E+10 | 3585.92 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.379619E+10 | 4482.40 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.130601E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9559633.89 | 0.809890E+09 |
February | 0.127628E+10 | 0.117471E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103714E+09 | 0.667490E+09 |
March | 0.149825E+10 | 0.133380E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361110E+09 | 0.468238E+09 |
April | 0.138726E+10 | 0.125604E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701471E+09 | 0.250498E+09 |
May | 0.144276E+10 | 0.129034E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149072E+10 | 60196515.90 |
June | 0.144276E+10 | 0.126121E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181208E+10 | 16469270.23 |
July | 0.138726E+10 | 0.125996E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204329E+10 | 78358.63 |
August | 0.149825E+10 | 0.131414E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228965E+10 | 22498.85 |
September | 0.138726E+10 | 0.124874E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156509E+10 | 16201804.83 |
October | 0.138726E+10 | 0.127787E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107079E+10 | 86076452.99 |
November | 0.133177E+10 | 0.124365E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519208E+09 | 0.290857E+09 |
December | 0.138726E+10 | 0.130996E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80411446.83 | 0.600969E+09 |
Annual Sum or Average | 0.168137E+11 | 0.152764E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120471E+11 | 0.326699E+10 |
Minimum of Months | 0.127628E+10 | 0.117471E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9559633.89 | 22498.85 |
Maximum of Months | 0.149825E+10 | 0.133380E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228965E+10 | 0.809890E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.352040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2093848.91 | 0.208616E+10 |
February | 0.300332E+10 | 0.308976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101766E+09 | 0.231485E+10 |
March | 0.352563E+10 | 0.344105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382972E+09 | 0.153249E+10 |
April | 0.326447E+10 | 0.313645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104790E+10 | 0.720773E+09 |
May | 0.339505E+10 | 0.320497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307715E+10 | 0.104592E+09 |
June | 0.339505E+10 | 0.314996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405141E+10 | 25878304.24 |
July | 0.326447E+10 | 0.311798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532099E+10 | 0.00 |
August | 0.352563E+10 | 0.328972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538794E+10 | 0.00 |
September | 0.326447E+10 | 0.314585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360354E+10 | 21511467.42 |
October | 0.326447E+10 | 0.330081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200328E+10 | 0.188773E+09 |
November | 0.313390E+10 | 0.331986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554493E+09 | 0.748296E+09 |
December | 0.326447E+10 | 0.357693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25490563.47 | 0.185996E+10 |
Annual Sum or Average | 0.395654E+11 | 0.392938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255590E+11 | 0.960329E+10 |
Minimum of Months | 0.300332E+10 | 0.308976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2093848.91 | 0.00 |
Maximum of Months | 0.352563E+10 | 0.357693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538794E+10 | 0.231485E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.372359E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128733E+09 | 0.902319E+10 |
February | 0.690763E+10 | 0.330303E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583367E+09 | 0.116271E+11 |
March | 0.810895E+10 | 0.370555E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108574E+10 | 0.993603E+10 |
April | 0.750829E+10 | 0.337659E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356980E+09 | 0.723861E+10 |
May | 0.780862E+10 | 0.341917E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101912E+10 | 0.198945E+10 |
June | 0.780862E+10 | 0.335954E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108843E+10 | 0.166945E+10 |
July | 0.750829E+10 | 0.334420E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100636E+10 | 0.121143E+10 |
August | 0.810895E+10 | 0.355596E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823909E+09 | 0.136200E+10 |
September | 0.750829E+10 | 0.340414E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685750E+09 | 0.153658E+10 |
October | 0.750829E+10 | 0.354849E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365653E+09 | 0.299425E+10 |
November | 0.720796E+10 | 0.354356E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39700706.29 | 0.720392E+10 |
December | 0.750829E+10 | 0.379619E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32378314.95 | 0.120192E+11 |
Annual Sum or Average | 0.910005E+11 | 0.420800E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721612E+10 | 0.678113E+11 |
Minimum of Months | 0.690763E+10 | 0.330303E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32378314.95 | 0.121143E+10 |
Maximum of Months | 0.810895E+10 | 0.379619E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108843E+10 | 0.120192E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1041.96 | 09-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.14 | 23-JAN-13:00 | 4527.64 | 19-JAN-07:03 |
February | 1680.92 | 01-FEB-08:09 | 1039.57 | 09-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2631.65 | 07-FEB-13:00 | 4043.66 | 13-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1056.35 | 15-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5181.75 | 27-MAR-11:10 | 3588.27 | 16-MAR-06:05 |
April | 1680.92 | 01-APR-07:10 | 1044.29 | 18-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6122.05 | 28-APR-12:00 | 3290.80 | 05-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 1002.27 | 23-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5926.05 | 09-MAY-12:00 | 2414.92 | 01-MAY-06:02 |
June | 1680.92 | 01-JUN-07:10 | 1005.92 | 08-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7538.28 | 09-JUN-16:10 | 1244.23 | 07-JUN-06:01 |
July | 1680.92 | 01-JUL-07:10 | 1034.96 | 20-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7526.63 | 21-JUL-17:00 | 21.32 | 03-JUL-05:45 |
August | 1680.92 | 01-AUG-07:10 | 1019.96 | 29-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7803.01 | 16-AUG-12:00 | 4.53 | 31-AUG-04:00 |
September | 1680.92 | 01-SEP-07:10 | 1026.10 | 06-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142.70 | 05-SEP-16:10 | 1580.44 | 25-SEP-06:01 |
October | 1680.92 | 02-OCT-07:10 | 1035.10 | 31-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5317.28 | 19-OCT-16:10 | 1856.97 | 30-OCT-06:01 |
November | 1680.92 | 01-NOV-07:10 | 1035.95 | 29-NOV-08:09 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.35 | 01-NOV-16:10 | 3432.21 | 22-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1050.37 | 15-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1558.20 | 01-DEC-13:00 | 3948.13 | 26-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1002.27 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.14 | 4.53 | |||||
Maximum of Months | 1680.92 | 1056.35 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 7803.01 | 4527.64 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3842.06 | 02-JAN-16:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.35 | 29-JAN-12:00 | 3784.90 | 19-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 3842.06 | 09-FEB-16:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.97 | 05-FEB-15:00 | 4608.14 | 10-FEB-16:10 |
March | 3955.50 | 01-MAR-08:09 | 4354.33 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5261.29 | 01-MAR-16:10 | 3210.55 | 25-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 3842.06 | 18-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.36 | 28-APR-15:10 | 2280.88 | 04-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3521.89 | 03-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19566.44 | 21-MAY-12:51 | 1308.37 | 01-MAY-07:06 |
June | 3955.50 | 01-JUN-07:10 | 3265.75 | 02-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10184.04 | 09-JUN-15:40 | 901.67 | 07-JUN-06:00 |
July | 3955.50 | 01-JUL-07:10 | 3521.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10207.61 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 3955.50 | 01-AUG-07:10 | 3521.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8722.89 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 3955.50 | 01-SEP-07:10 | 3521.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7470.15 | 02-SEP-16:00 | 591.64 | 25-SEP-05:10 |
October | 3955.50 | 02-OCT-07:10 | 3842.06 | 11-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7954.05 | 19-OCT-15:10 | 1697.29 | 21-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 3842.06 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2937.76 | 01-NOV-15:10 | 2208.38 | 22-NOV-07:05 |
December | 3955.50 | 01-DEC-08:09 | 3991.47 | 09-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.30 | 10-DEC-13:00 | 3116.64 | 16-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3265.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.35 | 0.00 | ||||
Maximum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19566.44 | 4608.14 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4108.86 | 02-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6270.76 | 23-JAN-13:10 | 18267.07 | 19-JAN-09:10 |
February | 9097.65 | 01-FEB-08:09 | 3735.33 | 06-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10501.85 | 05-FEB-14:55 | 19225.61 | 10-FEB-16:00 |
March | 9097.65 | 01-MAR-08:09 | 4482.40 | 14-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26503.04 | 01-MAR-13:10 | 38393.00 | 25-MAR-08:50 |
April | 9097.65 | 01-APR-07:10 | 3735.33 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4135.92 | 25-APR-07:53 | 13961.61 | 04-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 3585.92 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8641.90 | 21-MAY-12:51 | 10081.26 | 01-MAY-07:40 |
June | 9097.65 | 01-JUN-07:10 | 3585.92 | 08-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6330.86 | 09-JUN-15:00 | 7275.44 | 07-JUN-05:50 |
July | 9097.65 | 01-JUL-07:10 | 3735.33 | 20-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6389.46 | 15-JUL-09:55 | 3393.45 | 16-JUL-16:52 |
August | 9097.65 | 01-AUG-07:10 | 3585.92 | 01-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7752.58 | 16-AUG-10:55 | 5000.00 | 10-AUG-20:53 |
September | 9097.65 | 01-SEP-07:10 | 3585.92 | 01-SEP-06:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3995.85 | 26-SEP-11:00 | 6126.18 | 23-SEP-07:02 |
October | 9097.65 | 02-OCT-07:10 | 3735.33 | 11-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4323.93 | 19-OCT-14:00 | 11362.34 | 21-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 4482.40 | 29-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 942.84 | 13-NOV-15:00 | 10772.95 | 22-NOV-06:00 |
December | 9097.65 | 01-DEC-08:09 | 4482.40 | 07-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2464.30 | 10-DEC-12:00 | 31967.95 | 15-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3585.92 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 942.84 | 3393.45 | |||||
Maximum of Months | 9097.65 | 4482.40 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 26503.04 | 38393.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12759.20 | 30-JAN-08:63 | 5042.77 | 3112.94 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.89 |
February | 23557.12 | 11-FEB-08:62 | 8404.61 | 5098.67 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.67 |
March | 25453.97 | 28-MAR-06:02 | 2117.96 | 3482.65 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 909.72 |
April | 25114.69 | 25-APR-06:02 | 1764.97 | 2855.05 | 4781.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.24 |
May | 25187.95 | 05-MAY-06:01 | 2470.96 | 3971.81 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.49 |
June | 22492.52 | 16-JUN-06:01 | 2470.96 | 3948.60 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 597.45 | 0.00 |
July | 23102.49 | 03-JUL-05:02 | 924.51 | 1589.31 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 | 0.00 |
August | 20381.30 | 07-AUG-05:02 | 924.51 | 1589.31 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 304.43 | 0.00 |
September | 20133.17 | 26-SEP-07:02 | 8404.61 | 5115.77 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 116.47 | 0.00 |
October | 24854.25 | 20-OCT-06:01 | 2470.96 | 4063.09 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1186.19 |
November | 23104.68 | 18-NOV-07:02 | 1764.97 | 2836.03 | 4781.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.15 |
December | 21635.73 | 02-DEC-08:62 | 8404.61 | 5079.64 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12759.20 | 924.51 | 1589.31 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25453.97 | 8404.61 | 5115.77 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 597.45 | 1186.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3792.04 | 09-JAN-08:10 | 11866.50 | 11526.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892.34 |
February | 24960.34 | 05-FEB-14:55 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2565.26 | 0.00 |
March | 59787.03 | 26-MAR-13:43 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.15 | 0.00 |
April | 62090.64 | 02-APR-13:43 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2222.15 | 0.00 |
May | 66811.24 | 14-MAY-16:23 | 0.00 | 1195.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2696.64 | 0.00 |
June | 64659.19 | 20-JUN-17:42 | 0.00 | 1878.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3948.39 | 0.00 |
July | 61270.27 | 03-JUL-17:05 | 0.00 | 2305.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3583.56 | 0.00 |
August | 58630.69 | 02-AUG-00:23 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2751.90 | 0.00 |
September | 59118.07 | 04-SEP-10:23 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3385.07 | 0.00 |
October | 68803.55 | 15-OCT-13:23 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2345.40 | 0.00 |
November | 59480.80 | 05-NOV-12:03 | 0.00 | 768.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.53 | 0.00 |
December | 25292.14 | 03-DEC-13:05 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3792.04 | 0.00 | 512.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68803.55 | 11866.50 | 11526.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3948.39 | 892.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1516.91 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4160.42 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2525.48 |
April | 0.00 | 01-APR-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3148.68 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.77 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.07 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.01 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.31 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.32 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2007.08 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6140.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | |
Maximum of Months | 0.00 | 0.00 | 1195.31 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6140.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.320540E+11 | 24124.33 | 30-JAN-08:09 | 3050040.21 | 3398.38 | 02-JAN-08:09 |
February | 0.297445E+11 | 27986.68 | 07-FEB-16:49 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.358717E+11 | 33270.53 | 27-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.388541E+11 | 36510.08 | 28-APR-12:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.512583E+11 | 42155.52 | 31-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.563818E+11 | 46489.11 | 09-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.628864E+11 | 47523.66 | 14-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.668765E+11 | 51839.21 | 10-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.566297E+11 | 44007.50 | 08-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.488332E+11 | 38930.46 | 07-OCT-13:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.385367E+11 | 36489.56 | 01-NOV-15:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.339060E+11 | 28636.21 | 05-DEC-16:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.551833E+12 | 3050040.21 | ||||
Minimum of Months | 0.297445E+11 | 24124.33 | 0.00 | 0.00 | ||
Maximum of Months | 0.668765E+11 | 51839.21 | 3050040.21 | 3398.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.855000E+10 | 0.704244E+10 | 0.115358E+11 | 0.00 | 0.195571E+10 | 0.00 | 0.00 | 0.100799E+10 | 0.00 | 0.00 | 0.00 | 0.196213E+10 | 0.00 |
February | 0.756750E+10 | 0.606921E+10 | 0.105871E+11 | 0.00 | 0.180497E+10 | 0.00 | 0.00 | 0.195068E+10 | 0.00 | 0.00 | 0.00 | 0.176504E+10 | 0.00 |
March | 0.848040E+10 | 0.629435E+10 | 0.123431E+11 | 0.00 | 0.247319E+10 | 0.00 | 0.00 | 0.433794E+10 | 0.00 | 0.00 | 0.00 | 0.194278E+10 | 0.00 |
April | 0.776908E+10 | 0.563928E+10 | 0.114862E+11 | 0.00 | 0.395584E+10 | 0.00 | 0.00 | 0.820415E+10 | 0.00 | 0.00 | 0.00 | 0.179958E+10 | 0.00 |
May | 0.791448E+10 | 0.546387E+10 | 0.119357E+11 | 0.00 | 0.766327E+10 | 0.00 | 0.00 | 0.164747E+11 | 0.00 | 0.00 | 0.00 | 0.180624E+10 | 0.00 |
June | 0.777071E+10 | 0.511859E+10 | 0.118862E+11 | 0.00 | 0.872760E+10 | 0.00 | 0.00 | 0.211593E+11 | 0.00 | 0.00 | 0.00 | 0.171936E+10 | 0.00 |
July | 0.772214E+10 | 0.535182E+10 | 0.115358E+11 | 0.00 | 0.972114E+10 | 0.00 | 0.00 | 0.268198E+11 | 0.00 | 0.00 | 0.00 | 0.173577E+10 | 0.00 |
August | 0.815982E+10 | 0.566490E+10 | 0.123357E+11 | 0.00 | 0.999542E+10 | 0.00 | 0.00 | 0.289368E+11 | 0.00 | 0.00 | 0.00 | 0.178382E+10 | 0.00 |
September | 0.779873E+10 | 0.589304E+10 | 0.114788E+11 | 0.00 | 0.852546E+10 | 0.00 | 0.00 | 0.211802E+11 | 0.00 | 0.00 | 0.00 | 0.175345E+10 | 0.00 |
October | 0.812717E+10 | 0.653822E+10 | 0.115432E+11 | 0.00 | 0.651905E+10 | 0.00 | 0.00 | 0.142515E+11 | 0.00 | 0.00 | 0.00 | 0.185413E+10 | 0.00 |
November | 0.810707E+10 | 0.671364E+10 | 0.110862E+11 | 0.00 | 0.332911E+10 | 0.00 | 0.00 | 0.745716E+10 | 0.00 | 0.00 | 0.00 | 0.184350E+10 | 0.00 |
December | 0.868308E+10 | 0.715779E+10 | 0.115358E+11 | 0.00 | 0.196897E+10 | 0.00 | 0.00 | 0.261183E+10 | 0.00 | 0.00 | 0.00 | 0.194854E+10 | 0.00 |
Annual Sum or Average | 0.966502E+11 | 0.729471E+11 | 0.139290E+12 | 0.00 | 0.666397E+11 | 0.00 | 0.00 | 0.154392E+12 | 0.00 | 0.00 | 0.00 | 0.219143E+11 | 0.00 |
Minimum of Months | 0.756750E+10 | 0.511859E+10 | 0.105871E+11 | 0.00 | 0.180497E+10 | 0.00 | 0.00 | 0.100799E+10 | 0.00 | 0.00 | 0.00 | 0.171936E+10 | 0.00 |
Maximum of Months | 0.868308E+10 | 0.715779E+10 | 0.123431E+11 | 0.00 | 0.999542E+10 | 0.00 | 0.00 | 0.289368E+11 | 0.00 | 0.00 | 0.00 | 0.196213E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 3050040.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3050040.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 3050040.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8929.07 | 04-JAN-16:00 | 5492.60 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2092.06 | 30-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8616.96 | 09-FEB-16:00 | 5492.60 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2203.07 | 09-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9630.31 | 14-MAR-08:09 | 5492.60 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4501.50 | 27-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8621.68 | 18-APR-07:10 | 5492.60 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4732.03 | 28-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7504.18 | 10-MAY-07:10 | 5492.60 | 01-MAY-05:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 5029.81 | 31-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7234.73 | 08-JUN-06:10 | 5492.60 | 01-JUN-05:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 5678.82 | 09-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8292.18 | 20-JUL-07:10 | 5492.60 | 01-JUL-05:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 5779.01 | 14-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7530.11 | 29-AUG-07:10 | 5492.60 | 01-AUG-05:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6289.24 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7906.84 | 26-SEP-07:10 | 5492.60 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 5294.05 | 06-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8612.49 | 31-OCT-07:10 | 5492.60 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4745.34 | 05-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9355.59 | 29-NOV-16:00 | 5492.60 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4607.50 | 01-NOV-11:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9374.83 | 15-DEC-08:09 | 5492.60 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4280.63 | 01-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7234.73 | 5492.60 | 10112.62 | 0.00 | 2092.06 | 0.00 | 0.00 | |||||
Maximum of Months | 9630.31 | 5492.60 | 10112.62 | 0.00 | 6289.24 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3218.61 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 1738.98 | 14-JAN-12:09 | 0.00 |
February | 8147.13 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 1736.18 | 01-FEB-12:39 | 0.00 |
March | 12378.55 | 27-MAR-11:39 | 0.00 | 0.00 | 0.00 | 1723.97 | 01-MAR-12:30 | 0.00 |
April | 16794.98 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 1702.81 | 01-APR-11:30 | 0.00 |
May | 20254.29 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1680.46 | 01-MAY-11:39 | 0.00 |
June | 24567.34 | 09-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1661.94 | 01-JUN-11:39 | 0.00 |
July | 25308.65 | 14-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1653.11 | 31-JUL-11:50 | 0.00 |
August | 29556.27 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1664.77 | 31-AUG-11:30 | 0.00 |
September | 22027.89 | 08-SEP-15:30 | 0.00 | 0.00 | 0.00 | 1684.08 | 30-SEP-11:39 | 0.00 |
October | 17438.43 | 07-OCT-15:39 | 0.00 | 0.00 | 0.00 | 1707.01 | 31-OCT-11:30 | 0.00 |
November | 14282.19 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 1726.57 | 30-NOV-12:50 | 0.00 |
December | 7320.20 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 1737.67 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3218.61 | 0.00 | 0.00 | 0.00 | 1653.11 | 0.00 | ||
Maximum of Months | 29556.27 | 0.00 | 0.00 | 0.00 | 1738.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 24124.33 | 30-JAN-08:09 | 8294.86 | 10112.62 | 0.00 | 0.00 | 2092.06 | 0.00 | 0.00 | 2014.76 | 0.00 |
February | 27986.68 | 07-FEB-16:49 | 7452.44 | 10112.62 | 0.00 | 0.00 | 1975.33 | 0.00 | 0.00 | 6859.65 | 0.00 |
March | 33270.53 | 27-MAR-12:09 | 5662.80 | 10112.62 | 0.00 | 0.00 | 4280.63 | 0.00 | 0.00 | 11531.76 | 0.00 |
April | 36510.08 | 28-APR-12:20 | 5665.90 | 10112.62 | 0.00 | 0.00 | 4333.34 | 0.00 | 0.00 | 14735.47 | 0.00 |
May | 42155.52 | 31-MAY-15:00 | 5339.03 | 10112.62 | 0.00 | 0.00 | 4970.15 | 0.00 | 0.00 | 20166.34 | 0.00 |
June | 46489.11 | 09-JUN-15:20 | 5018.86 | 10112.62 | 0.00 | 0.00 | 5531.85 | 0.00 | 0.00 | 24259.50 | 0.00 |
July | 47523.66 | 14-JUL-15:00 | 5395.12 | 10112.62 | 0.00 | 0.00 | 5620.63 | 0.00 | 0.00 | 24831.01 | 0.00 |
August | 51839.21 | 10-AUG-15:39 | 5018.86 | 10112.62 | 0.00 | 0.00 | 6187.87 | 0.00 | 0.00 | 29073.00 | 0.00 |
September | 44007.50 | 08-SEP-15:00 | 5339.03 | 10112.62 | 0.00 | 0.00 | 5229.46 | 0.00 | 0.00 | 21757.15 | 0.00 |
October | 38930.46 | 07-OCT-13:39 | 5593.35 | 10112.62 | 0.00 | 0.00 | 4447.12 | 0.00 | 0.00 | 17129.67 | 0.00 |
November | 36489.56 | 01-NOV-15:50 | 6371.21 | 10112.62 | 0.00 | 0.00 | 4410.67 | 0.00 | 0.00 | 14015.43 | 0.00 |
December | 28636.21 | 05-DEC-16:49 | 8872.77 | 10112.62 | 0.00 | 0.00 | 1975.33 | 0.00 | 0.00 | 6090.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 24124.33 | 5018.86 | 10112.62 | 0.00 | 0.00 | 1975.33 | 0.00 | 0.00 | 2014.76 | 0.00 | |
Maximum of Months | 51839.21 | 8872.77 | 10112.62 | 0.00 | 0.00 | 6187.87 | 0.00 | 0.00 | 29073.00 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3398.38 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3398.38 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 30.00 | 0.00 | 30.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 29.97 | 0.00 | 29.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.77 | 0.83 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.92 | 2.00 | 27.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 29.22 | 0.67 | 28.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 29.61 | 0.17 | 29.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 30.08 | 0.00 | 30.08 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.17 | 28.71 | 3.67 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 30.08 | 2.00 | 30.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.39 | 0.00 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.46 | 0.00 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.57 | 0.17 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 27.58 | 0.33 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 93.00 | 27.61 | 1.50 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 96.33 | 27.58 | 2.50 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.57 | 0.17 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.50 | 0.33 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.38 | 0.00 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 387.33 | 27.57 | 5.00 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 96.33 | 27.61 | 2.50 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.33 | 23.41 | 96.33 | 23.69 | 0.00 | 23.69 |
February | 29.00 | 23.92 | 194.00 | 24.05 | 8.00 | 24.11 |
March | 10.17 | 24.57 | 279.17 | 24.19 | 5.50 | 24.22 |
April | 23.67 | 26.49 | 300.00 | 24.44 | 23.67 | 24.58 |
May | 43.50 | 26.81 | 312.00 | 24.68 | 43.50 | 24.91 |
June | 66.00 | 26.05 | 312.00 | 24.68 | 66.00 | 24.88 |
July | 89.33 | 25.49 | 300.00 | 24.64 | 89.33 | 24.80 |
August | 101.00 | 25.47 | 324.00 | 24.65 | 101.00 | 24.80 |
September | 75.50 | 25.80 | 300.00 | 24.67 | 75.50 | 24.86 |
October | 55.17 | 26.34 | 300.00 | 24.69 | 55.17 | 24.91 |
November | 32.50 | 26.39 | 288.00 | 24.53 | 32.50 | 24.70 |
December | 17.33 | 24.39 | 248.00 | 24.13 | 9.17 | 24.18 |
Annual Sum or Average | 641.50 | 25.39 | 3253.50 | 24.48 | 509.33 | 24.65 |
Minimum of Months | 10.17 | 23.41 | 96.33 | 23.69 | 0.00 | 23.69 |
Maximum of Months | 101.00 | 26.81 | 324.00 | 24.69 | 101.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.83 | 23.31 | 171.83 | 24.80 | 22.17 | 24.89 |
February | 94.00 | 25.16 | 223.83 | 25.92 | 58.33 | 25.99 |
March | 138.33 | 26.39 | 306.83 | 26.36 | 129.83 | 26.41 |
April | 240.00 | 26.64 | 300.00 | 26.60 | 240.00 | 26.61 |
May | 287.50 | 26.71 | 312.00 | 26.71 | 287.50 | 26.71 |
June | 309.67 | 26.71 | 312.00 | 26.71 | 309.67 | 26.71 |
July | 298.17 | 26.71 | 300.00 | 26.71 | 298.17 | 26.71 |
August | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
September | 298.67 | 26.71 | 300.00 | 26.71 | 298.67 | 26.71 |
October | 284.00 | 26.72 | 300.00 | 26.72 | 284.00 | 26.72 |
November | 244.00 | 26.67 | 288.00 | 26.64 | 244.00 | 26.65 |
December | 131.33 | 25.93 | 268.33 | 26.14 | 111.00 | 26.19 |
Annual Sum or Average | 2768.50 | 26.45 | 3406.83 | 26.50 | 2607.33 | 26.55 |
Minimum of Months | 94.00 | 23.31 | 171.83 | 24.80 | 22.17 | 24.89 |
Maximum of Months | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.50 | 23.06 | 95.83 | 23.70 | 13.33 | 23.76 |
February | 76.50 | 25.56 | 225.83 | 25.81 | 49.67 | 25.94 |
March | 168.00 | 28.76 | 319.33 | 27.96 | 168.00 | 28.17 |
April | 300.00 | 30.26 | 300.00 | 30.26 | 300.00 | 30.26 |
May | 312.00 | 33.31 | 312.00 | 33.31 | 312.00 | 33.31 |
June | 312.00 | 34.52 | 312.00 | 34.52 | 312.00 | 34.52 |
July | 300.00 | 36.15 | 300.00 | 36.15 | 300.00 | 36.15 |
August | 324.00 | 36.47 | 324.00 | 36.47 | 324.00 | 36.47 |
September | 300.00 | 33.95 | 300.00 | 33.95 | 300.00 | 33.95 |
October | 300.00 | 31.69 | 300.00 | 31.69 | 300.00 | 31.69 |
November | 288.00 | 29.57 | 288.00 | 29.57 | 288.00 | 29.57 |
December | 151.00 | 27.86 | 285.33 | 27.24 | 149.50 | 27.41 |
Annual Sum or Average | 3020.00 | 31.94 | 3362.33 | 31.69 | 2816.50 | 31.97 |
Minimum of Months | 76.50 | 23.06 | 95.83 | 23.70 | 13.33 | 23.76 |
Maximum of Months | 324.00 | 36.47 | 324.00 | 36.47 | 324.00 | 36.47 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.401602E+10 | 0.966263E+09 | 239.78 | 0.325061E+10 | 0.765406E+09 | 0.00 | 1.00 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 21714.06 | 30-JAN-08:63 | 14052.91 | 30-JAN-08:63 | 7661.15 | 30-JAN-08:63 | 4644.11 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.524624E+10 | 0.126037E+10 | 228.57 | 0.421273E+10 | 0.103351E+10 | 0.00 | 1.00 | 04-FEB-08:63 | 0.00 | 01-FEB-00:10 | 31906.67 | 09-FEB-08:62 | 25945.59 | 11-FEB-08:62 | 12599.56 | 07-FEB-08:62 | 6744.17 | 09-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.768100E+10 | 0.187588E+10 | 275.67 | 0.642392E+10 | 0.125708E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:10 | 32281.00 | 29-MAR-07:02 | 28145.87 | 28-MAR-06:02 | 13878.76 | 29-MAR-07:02 | 6797.65 | 29-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.954556E+10 | 0.239991E+10 | 265.68 | 0.791455E+10 | 0.163102E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:10 | 32875.26 | 10-APR-06:02 | 28039.48 | 25-APR-06:02 | 13303.52 | 12-APR-07:02 | 6879.20 | 10-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.138639E+11 | 0.368480E+10 | 310.55 | 0.113517E+11 | 0.251223E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:05 | 34894.01 | 25-MAY-06:01 | 27783.43 | 05-MAY-06:01 | 17475.74 | 24-MAY-06:03 | 7281.63 | 30-MAY-05:02 | 0.00 | 01-MAY-00:05 |
June | 0.168326E+11 | 0.450544E+10 | 317.51 | 0.125158E+11 | 0.431675E+10 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 35291.08 | 08-JUN-06:03 | 25219.66 | 16-JUN-06:01 | 18919.78 | 08-JUN-07:02 | 7560.95 | 09-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.194199E+11 | 0.528015E+10 | 341.58 | 0.135209E+11 | 0.589904E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 33988.51 | 06-JUL-05:03 | 26278.74 | 03-JUL-05:02 | 19385.82 | 20-JUL-06:15 | 7729.60 | 19-JUL-17:00 | 0.00 | 01-JUL-00:10 |
August | 0.216883E+11 | 0.590664E+10 | 358.20 | 0.149151E+11 | 0.677323E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 33988.51 | 31-AUG-05:03 | 23798.88 | 07-AUG-05:02 | 19656.42 | 08-AUG-06:15 | 8016.45 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.173088E+11 | 0.452064E+10 | 318.97 | 0.121840E+11 | 0.512471E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 35478.54 | 25-SEP-06:01 | 22816.44 | 26-SEP-07:02 | 19282.46 | 12-SEP-06:05 | 7423.44 | 07-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.138053E+11 | 0.345313E+10 | 296.24 | 0.103710E+11 | 0.343423E+10 | 0.00 | 1.00 | 01-OCT-12:52 | 0.00 | 01-OCT-00:10 | 35336.44 | 07-OCT-06:01 | 27201.92 | 20-OCT-06:01 | 18237.45 | 07-OCT-06:04 | 7282.27 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.101504E+11 | 0.244152E+10 | 257.78 | 0.776962E+10 | 0.238075E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:05 | 34370.11 | 03-NOV-06:01 | 25465.06 | 18-NOV-07:02 | 15241.77 | 03-NOV-06:03 | 7066.25 | 03-NOV-06:01 | 0.00 | 01-NOV-00:05 |
December | 0.648061E+10 | 0.153467E+10 | 251.80 | 0.509448E+10 | 0.138613E+10 | 0.00 | 1.00 | 01-DEC-08:63 | 0.00 | 01-DEC-00:10 | 31812.83 | 05-DEC-08:62 | 23713.05 | 02-DEC-08:62 | 12897.42 | 05-DEC-08:62 | 6730.51 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.146039E+12 | 0.378294E+11 | 3462.32 | 0.109524E+12 | 0.365141E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.401602E+10 | 0.966263E+09 | 228.57 | 0.325061E+10 | 0.765406E+09 | 0.00 | 1.00 | 0.00 | 21714.06 | 14052.91 | 7661.15 | 4644.11 | 0.00 | |||||||
Maximum of Months | 0.216883E+11 | 0.590664E+10 | 358.20 | 0.149151E+11 | 0.677323E+10 | 0.00 | 1.00 | 0.00 | 35478.54 | 28145.87 | 19656.42 | 8016.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.144438E+09 | 41723214.66 | 17.33 | 0.117529E+09 | 26908958.47 | 0.00 | 0.15 | 28-JAN-14:00 | 0.00 | 01-JAN-00:10 | 5007.90 | 28-JAN-14:00 | 5007.90 | 28-JAN-14:00 | 1138.41 | 30-JAN-13:10 | 1521.79 | 28-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.238703E+10 | 0.690306E+09 | 111.08 | 0.182990E+10 | 0.557126E+09 | 0.00 | 0.81 | 05-FEB-14:55 | 0.00 | 01-FEB-00:10 | 31895.77 | 05-FEB-14:55 | 28342.79 | 05-FEB-14:55 | 6207.68 | 07-FEB-16:10 | 9241.08 | 05-FEB-14:55 | 0.00 | 01-FEB-00:10 |
March | 0.844129E+10 | 0.246205E+10 | 227.41 | 0.687025E+10 | 0.157105E+10 | 0.00 | 1.00 | 23-MAR-17:10 | 0.00 | 01-MAR-00:10 | 68765.09 | 26-MAR-13:43 | 68539.31 | 26-MAR-13:43 | 12720.46 | 29-MAR-17:10 | 19958.22 | 26-MAR-13:43 | 0.00 | 01-MAR-00:10 |
April | 0.197215E+11 | 0.580424E+10 | 324.51 | 0.158840E+11 | 0.383748E+10 | 0.00 | 1.00 | 01-APR-17:10 | 0.00 | 01-APR-00:10 | 92167.68 | 30-APR-16:53 | 72532.16 | 30-APR-12:53 | 31945.20 | 30-APR-17:33 | 24458.85 | 30-APR-10:53 | 0.00 | 01-APR-00:10 |
May | 0.424225E+11 | 0.127899E+11 | 522.68 | 0.336710E+11 | 0.875151E+10 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:10 | 94068.62 | 24-MAY-17:43 | 76323.72 | 10-MAY-17:06 | 35791.10 | 24-MAY-17:43 | 26336.35 | 31-MAY-18:23 | 0.00 | 01-MAY-00:05 |
June | 0.560843E+11 | 0.166539E+11 | 563.00 | 0.396307E+11 | 0.164537E+11 | 0.00 | 1.00 | 01-JUN-15:10 | 0.00 | 01-JUN-00:15 | 94729.62 | 26-JUN-19:03 | 75366.30 | 15-JUN-17:05 | 38903.18 | 26-JUN-19:03 | 26433.00 | 09-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.717737E+11 | 0.215396E+11 | 601.78 | 0.486406E+11 | 0.231331E+11 | 0.00 | 1.00 | 01-JUL-11:50 | 0.00 | 01-JUL-00:15 | 95609.29 | 26-JUL-19:43 | 74968.84 | 30-JUL-13:42 | 41943.48 | 26-JUL-19:43 | 26991.75 | 30-JUL-11:02 | 0.00 | 01-JUL-00:10 |
August | 0.769172E+11 | 0.230302E+11 | 611.19 | 0.511649E+11 | 0.257523E+11 | 0.00 | 1.00 | 01-AUG-04:25 | 0.00 | 01-AUG-00:13 | 98144.35 | 08-AUG-21:03 | 72395.05 | 06-AUG-11:02 | 47168.05 | 22-AUG-17:07 | 27519.11 | 10-AUG-17:42 | 0.00 | 01-AUG-00:10 |
September | 0.573305E+11 | 0.166595E+11 | 557.70 | 0.380823E+11 | 0.192483E+11 | 0.00 | 1.00 | 01-SEP-01:05 | 0.00 | 01-SEP-00:13 | 97793.70 | 08-SEP-18:23 | 73574.08 | 04-SEP-12:23 | 45996.08 | 08-SEP-18:23 | 26310.56 | 04-SEP-14:22 | 0.00 | 01-SEP-00:10 |
October | 0.374734E+11 | 0.107983E+11 | 489.78 | 0.269411E+11 | 0.105324E+11 | 0.00 | 1.00 | 01-OCT-08:25 | 0.00 | 01-OCT-00:15 | 95814.03 | 07-OCT-17:06 | 77799.90 | 15-OCT-13:23 | 42166.67 | 07-OCT-17:06 | 25282.60 | 07-OCT-17:06 | 0.00 | 01-OCT-00:10 |
November | 0.177133E+11 | 0.501564E+10 | 304.48 | 0.128492E+11 | 0.486409E+10 | 0.00 | 1.00 | 01-NOV-17:08 | 0.00 | 01-NOV-00:10 | 80102.51 | 02-NOV-17:10 | 68515.55 | 05-NOV-12:03 | 28164.03 | 02-NOV-17:10 | 20907.79 | 02-NOV-17:10 | 0.00 | 01-NOV-00:05 |
December | 0.385098E+10 | 0.107717E+10 | 149.42 | 0.272825E+10 | 0.112273E+10 | 0.00 | 0.84 | 03-DEC-13:05 | 0.00 | 01-DEC-00:10 | 35343.83 | 03-DEC-13:05 | 28017.20 | 03-DEC-13:05 | 9012.13 | 03-DEC-11:50 | 9561.56 | 03-DEC-13:05 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.394260E+12 | 0.116563E+12 | 4480.37 | 0.278410E+12 | 0.115851E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.144438E+09 | 41723214.66 | 17.33 | 0.117529E+09 | 26908958.47 | 0.00 | 0.15 | 0.00 | 5007.90 | 5007.90 | 1138.41 | 1521.79 | 0.00 | |||||||
Maximum of Months | 0.769172E+11 | 0.230302E+11 | 611.19 | 0.511649E+11 | 0.257523E+11 | 0.00 | 1.00 | 0.00 | 98144.35 | 77799.90 | 47168.05 | 27519.11 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.48 | 17.12 | 42.36 | 80.82 | 63.60 | 0.00 | 0.00 | 0.00 |
February | 67.83 | 19.41 | 48.42 | 98.76 | 57.35 | 0.00 | 0.00 | 0.00 |
March | 80.28 | 23.83 | 56.45 | 130.08 | 46.97 | 0.00 | 0.00 | 0.00 |
April | 87.51 | 24.52 | 63.00 | 160.19 | 34.05 | 0.00 | 0.00 | 0.00 |
May | 95.22 | 28.43 | 66.79 | 204.47 | 12.38 | 0.00 | 0.00 | 0.00 |
June | 98.56 | 31.13 | 67.44 | 221.17 | 5.37 | 0.00 | 0.00 | 0.00 |
July | 90.44 | 25.89 | 64.55 | 227.40 | 0.75 | 0.00 | 0.00 | 0.00 |
August | 92.60 | 28.08 | 64.52 | 232.74 | 0.49 | 0.00 | 0.00 | 0.00 |
September | 88.22 | 27.73 | 60.48 | 196.09 | 7.52 | 0.00 | 0.00 | 0.00 |
October | 78.41 | 25.33 | 53.08 | 155.80 | 20.98 | 0.00 | 0.00 | 0.00 |
November | 67.49 | 22.10 | 45.39 | 115.88 | 42.14 | 0.00 | 0.00 | 0.00 |
December | 56.46 | 17.10 | 39.36 | 81.07 | 60.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.25 | 24.24 | 56.02 | 159.04 | 29.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.46 | 17.10 | 39.36 | 80.82 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.56 | 31.13 | 67.44 | 232.74 | 63.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.48 | 17.12 | 42.36 | 80.82 | 63.60 | 0.00 | 0.00 | 0.00 |
February | 67.83 | 19.41 | 48.42 | 98.76 | 57.35 | 0.00 | 0.00 | 0.00 |
March | 80.28 | 23.83 | 56.45 | 130.08 | 46.97 | 0.00 | 0.00 | 0.00 |
April | 87.51 | 24.52 | 63.00 | 160.19 | 34.05 | 0.00 | 0.00 | 0.00 |
May | 95.22 | 28.43 | 66.79 | 204.47 | 12.38 | 0.00 | 0.00 | 0.00 |
June | 98.56 | 31.13 | 67.44 | 221.17 | 5.37 | 0.00 | 0.00 | 0.00 |
July | 90.44 | 25.89 | 64.55 | 227.40 | 0.75 | 0.00 | 0.00 | 0.00 |
August | 92.60 | 28.08 | 64.52 | 232.74 | 0.49 | 0.00 | 0.00 | 0.00 |
September | 88.22 | 27.73 | 60.48 | 196.09 | 7.52 | 0.00 | 0.00 | 0.00 |
October | 78.41 | 25.33 | 53.08 | 155.80 | 20.98 | 0.00 | 0.00 | 0.00 |
November | 67.49 | 22.10 | 45.39 | 115.88 | 42.14 | 0.00 | 0.00 | 0.00 |
December | 56.46 | 17.10 | 39.36 | 81.07 | 60.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.25 | 24.24 | 56.02 | 159.04 | 29.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.46 | 17.10 | 39.36 | 80.82 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.56 | 31.13 | 67.44 | 232.74 | 63.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 0.00 | 19.49 | 20.71 | 37.60 | 0.00 | 0.00 | 0.00 |
February | 22.34 | 0.00 | 22.34 | 27.33 | 33.92 | 0.00 | 0.00 | 0.00 |
March | 25.67 | 0.00 | 25.67 | 38.46 | 27.55 | 0.00 | 0.00 | 0.00 |
April | 28.96 | 0.08 | 28.88 | 54.05 | 19.54 | 0.00 | 0.00 | 0.00 |
May | 32.63 | 1.03 | 31.60 | 78.39 | 6.74 | 0.00 | 0.00 | 0.00 |
June | 34.78 | 1.88 | 32.90 | 89.21 | 3.11 | 0.00 | 0.00 | 0.00 |
July | 31.97 | 0.91 | 31.06 | 96.11 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 29.85 | 0.32 | 29.53 | 93.12 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 27.12 | 0.01 | 27.11 | 70.85 | 4.20 | 0.00 | 0.00 | 0.00 |
October | 24.03 | 0.00 | 24.03 | 51.91 | 12.01 | 0.00 | 0.00 | 0.00 |
November | 20.63 | 0.00 | 20.63 | 33.86 | 24.47 | 0.00 | 0.00 | 0.00 |
December | 18.19 | 0.00 | 18.19 | 21.08 | 35.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.32 | 0.35 | 25.97 | 56.43 | 17.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.19 | 0.00 | 18.19 | 20.71 | 0.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.78 | 1.88 | 32.90 | 96.11 | 37.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 0.00 | 19.49 | 20.71 | 37.60 | 0.00 | 0.00 | 0.00 |
February | 22.34 | 0.00 | 22.34 | 27.33 | 33.92 | 0.00 | 0.00 | 0.00 |
March | 25.67 | 0.00 | 25.66 | 38.46 | 27.55 | 0.00 | 0.00 | 0.00 |
April | 28.96 | 0.08 | 28.88 | 54.05 | 19.54 | 0.00 | 0.00 | 0.00 |
May | 32.63 | 1.03 | 31.60 | 78.39 | 6.74 | 0.00 | 0.00 | 0.00 |
June | 34.78 | 1.88 | 32.90 | 89.20 | 3.11 | 0.00 | 0.00 | 0.00 |
July | 31.97 | 0.91 | 31.06 | 96.11 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 29.85 | 0.32 | 29.53 | 93.12 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 27.12 | 0.01 | 27.11 | 70.85 | 4.20 | 0.00 | 0.00 | 0.00 |
October | 24.03 | 0.00 | 24.03 | 51.91 | 12.01 | 0.00 | 0.00 | 0.00 |
November | 20.63 | 0.00 | 20.63 | 33.86 | 24.47 | 0.00 | 0.00 | 0.00 |
December | 18.19 | 0.00 | 18.19 | 21.08 | 35.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.32 | 0.35 | 25.97 | 56.43 | 17.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.19 | 0.00 | 18.19 | 20.71 | 0.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.78 | 1.88 | 32.90 | 96.11 | 37.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 96.71 | 36.38 | 5.17 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 119.72 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.79 | 31.03 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 184.43 | 26.06 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 219.27 | 14.45 | 0.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 230.97 | 10.99 | 0.00 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 230.94 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 220.80 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 192.20 | 12.18 | 0.00 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 155.66 | 20.85 | 0.00 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 116.67 | 31.34 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 90.02 | 36.55 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 167.50 | 21.87 | 13.00 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 90.02 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 230.97 | 36.55 | 7.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.96 | 30.65 | 49.31 | 99.25 | 34.62 | 10.33 | 0.00 | 0.00 |
February | 96.95 | 39.62 | 57.33 | 121.27 | 33.69 | 0.00 | 0.00 | 0.00 |
March | 117.25 | 49.22 | 68.03 | 149.05 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 138.22 | 61.27 | 76.95 | 178.84 | 32.73 | 0.00 | 0.00 | 0.00 |
May | 156.83 | 76.26 | 80.57 | 207.38 | 24.76 | 1.00 | 0.00 | 0.00 |
June | 163.48 | 83.14 | 80.34 | 215.92 | 23.94 | 3.17 | 0.00 | 0.00 |
July | 158.58 | 80.46 | 78.12 | 211.33 | 21.55 | 0.00 | 0.00 | 0.00 |
August | 151.06 | 74.23 | 76.83 | 200.42 | 22.39 | 3.00 | 0.00 | 0.00 |
September | 135.57 | 65.05 | 70.52 | 179.12 | 25.80 | 6.83 | 0.00 | 0.00 |
October | 114.06 | 53.57 | 60.49 | 148.03 | 30.70 | 24.17 | 0.00 | 0.00 |
November | 90.62 | 39.64 | 50.99 | 112.81 | 38.26 | 0.00 | 0.00 | 0.00 |
December | 74.29 | 28.87 | 45.42 | 89.46 | 39.34 | 7.67 | 0.00 | 0.00 |
Annual Sum or Average | 123.19 | 56.91 | 66.28 | 159.59 | 30.08 | 56.17 | 0.00 | 0.00 |
Minimum of Months | 74.29 | 28.87 | 45.42 | 89.46 | 21.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.48 | 83.14 | 80.57 | 215.92 | 39.34 | 24.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159322E+09 | 45856831.24 | 0.113465E+09 | 0.216457E+09 | 0.170343E+09 |
February | 0.164098E+09 | 46952797.52 | 0.117146E+09 | 0.238931E+09 | 0.138732E+09 |
March | 0.215009E+09 | 63814222.80 | 0.151194E+09 | 0.348400E+09 | 0.125792E+09 |
April | 0.226838E+09 | 63544997.13 | 0.163293E+09 | 0.415208E+09 | 88249991.73 |
May | 0.255038E+09 | 76145680.82 | 0.178893E+09 | 0.547652E+09 | 33146091.95 |
June | 0.255478E+09 | 80679905.96 | 0.174798E+09 | 0.573267E+09 | 13913268.01 |
July | 0.242234E+09 | 69348224.93 | 0.172886E+09 | 0.609080E+09 | 2002167.27 |
August | 0.248012E+09 | 75204280.32 | 0.172808E+09 | 0.623373E+09 | 1319664.34 |
September | 0.228660E+09 | 71885489.79 | 0.156774E+09 | 0.508271E+09 | 19496734.78 |
October | 0.210015E+09 | 67843113.60 | 0.142172E+09 | 0.417286E+09 | 56198532.79 |
November | 0.174928E+09 | 57279143.02 | 0.117648E+09 | 0.300371E+09 | 0.109222E+09 |
December | 0.151234E+09 | 45810012.52 | 0.105424E+09 | 0.217138E+09 | 0.162880E+09 |
Annual Sum or Average | 0.253087E+10 | 0.764365E+09 | 0.176650E+10 | 0.501543E+10 | 0.921295E+09 |
Minimum of Months | 0.151234E+09 | 45810012.52 | 0.105424E+09 | 0.216457E+09 | 1319664.34 |
Maximum of Months | 0.255478E+09 | 80679905.96 | 0.178893E+09 | 0.623373E+09 | 0.170343E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159322E+09 | 45856831.24 | 0.113465E+09 | 0.216457E+09 | 0.170343E+09 |
February | 0.164098E+09 | 46952797.52 | 0.117146E+09 | 0.238931E+09 | 0.138732E+09 |
March | 0.215009E+09 | 63814222.80 | 0.151194E+09 | 0.348400E+09 | 0.125792E+09 |
April | 0.226838E+09 | 63544997.13 | 0.163293E+09 | 0.415208E+09 | 88249991.73 |
May | 0.255038E+09 | 76145680.82 | 0.178893E+09 | 0.547652E+09 | 33146091.95 |
June | 0.255478E+09 | 80679905.96 | 0.174798E+09 | 0.573267E+09 | 13913268.01 |
July | 0.242234E+09 | 69348224.93 | 0.172886E+09 | 0.609080E+09 | 2002167.27 |
August | 0.248012E+09 | 75204280.32 | 0.172808E+09 | 0.623373E+09 | 1319664.34 |
September | 0.228660E+09 | 71885489.79 | 0.156774E+09 | 0.508271E+09 | 19496734.78 |
October | 0.210015E+09 | 67843113.60 | 0.142172E+09 | 0.417286E+09 | 56198532.79 |
November | 0.174928E+09 | 57279143.02 | 0.117648E+09 | 0.300371E+09 | 0.109222E+09 |
December | 0.151234E+09 | 45810012.52 | 0.105424E+09 | 0.217138E+09 | 0.162880E+09 |
Annual Sum or Average | 0.253087E+10 | 0.764365E+09 | 0.176650E+10 | 0.501543E+10 | 0.921295E+09 |
Minimum of Months | 0.151234E+09 | 45810012.52 | 0.105424E+09 | 0.216457E+09 | 1319664.34 |
Maximum of Months | 0.255478E+09 | 80679905.96 | 0.178893E+09 | 0.623373E+09 | 0.170343E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52201214.34 | 0.00 | 52201214.34 | 55477754.54 | 0.100700E+09 |
February | 54046823.17 | 0.00 | 54046823.17 | 66122554.00 | 82056283.17 |
March | 68744926.07 | 2982.89 | 68741943.18 | 0.103024E+09 | 73789167.94 |
April | 75064922.18 | 216550.64 | 74848371.54 | 0.140109E+09 | 50636952.46 |
May | 87386460.65 | 2759650.78 | 84626809.87 | 0.209959E+09 | 18042118.86 |
June | 90149479.98 | 4882316.99 | 85267162.99 | 0.231221E+09 | 8060617.69 |
July | 85632023.61 | 2439004.03 | 83193019.57 | 0.257433E+09 | 1160532.36 |
August | 79948054.55 | 862937.57 | 79085116.97 | 0.249425E+09 | 681603.05 |
September | 70289075.30 | 17496.58 | 70271578.72 | 0.183654E+09 | 10895784.78 |
October | 64372792.32 | 0.00 | 64372792.32 | 0.139044E+09 | 32172509.75 |
November | 53479991.70 | 0.00 | 53479991.70 | 87769455.56 | 63428371.03 |
December | 48723079.47 | 0.00 | 48723079.47 | 56450163.95 | 95839275.15 |
Annual Sum or Average | 0.830039E+09 | 11180939.48 | 0.818858E+09 | 0.177969E+10 | 0.537463E+09 |
Minimum of Months | 48723079.47 | 0.00 | 48723079.47 | 55477754.54 | 681603.05 |
Maximum of Months | 90149479.98 | 4882316.99 | 85267162.99 | 0.257433E+09 | 0.100700E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52199501.16 | 0.00 | 52199501.16 | 55475631.17 | 0.100699E+09 |
February | 54045082.48 | 0.00 | 54045082.48 | 66120328.53 | 82055403.14 |
March | 68742746.19 | 2982.75 | 68739763.45 | 0.103022E+09 | 73788109.52 |
April | 75062588.96 | 216540.49 | 74846048.48 | 0.140106E+09 | 50635945.54 |
May | 87383739.48 | 2759521.43 | 84624218.05 | 0.209956E+09 | 18041422.74 |
June | 90146637.29 | 4882088.15 | 85264549.15 | 0.231218E+09 | 8060118.55 |
July | 85629392.10 | 2438889.72 | 83190502.39 | 0.257430E+09 | 1160390.15 |
August | 79945631.54 | 862897.12 | 79082734.42 | 0.249422E+09 | 681506.46 |
September | 70286941.73 | 17495.76 | 70269445.97 | 0.183652E+09 | 10895221.18 |
October | 64370795.92 | 0.00 | 64370795.92 | 0.139042E+09 | 32171473.49 |
November | 53478285.71 | 0.00 | 53478285.71 | 87767420.43 | 63427198.24 |
December | 48721479.94 | 0.00 | 48721479.94 | 56448186.67 | 95838147.22 |
Annual Sum or Average | 0.830013E+09 | 11180415.41 | 0.818832E+09 | 0.177966E+10 | 0.537454E+09 |
Minimum of Months | 48721479.94 | 0.00 | 48721479.94 | 55475631.17 | 681506.46 |
Maximum of Months | 90146637.29 | 4882088.15 | 85264549.15 | 0.257430E+09 | 0.100699E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.259026E+09 | 97447271.79 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.289634E+09 | 81786428.41 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.401197E+09 | 83115825.40 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.478042E+09 | 67538913.17 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.587294E+09 | 38698203.25 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.598680E+09 | 28496802.04 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.618541E+09 | 13555568.06 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.591382E+09 | 12376826.26 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.498173E+09 | 31558280.83 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.416923E+09 | 55854082.85 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.302407E+09 | 81238657.46 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 97907538.61 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.528241E+10 | 0.689574E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.241109E+09 | 12376826.26 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.618541E+09 | 97907538.61 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214164E+09 | 82088627.75 | 0.132075E+09 | 0.265829E+09 | 92738823.61 |
February | 0.234541E+09 | 95851933.36 | 0.138689E+09 | 0.293375E+09 | 81507163.87 |
March | 0.314037E+09 | 0.131821E+09 | 0.182216E+09 | 0.399215E+09 | 89697130.36 |
April | 0.358265E+09 | 0.158822E+09 | 0.199443E+09 | 0.463549E+09 | 84835623.29 |
May | 0.420063E+09 | 0.204266E+09 | 0.215797E+09 | 0.555449E+09 | 66329689.08 |
June | 0.423737E+09 | 0.215499E+09 | 0.208238E+09 | 0.559661E+09 | 62045118.52 |
July | 0.424752E+09 | 0.215509E+09 | 0.209243E+09 | 0.566022E+09 | 57708926.58 |
August | 0.404593E+09 | 0.198820E+09 | 0.205773E+09 | 0.536798E+09 | 59958543.88 |
September | 0.351400E+09 | 0.168616E+09 | 0.182784E+09 | 0.464276E+09 | 66868879.37 |
October | 0.305485E+09 | 0.143476E+09 | 0.162009E+09 | 0.396493E+09 | 82238583.61 |
November | 0.234899E+09 | 0.102737E+09 | 0.132162E+09 | 0.292413E+09 | 99178316.76 |
December | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 0.105375E+09 |
Annual Sum or Average | 0.388491E+10 | 0.179482E+10 | 0.209009E+10 | 0.503270E+10 | 0.948481E+09 |
Minimum of Months | 0.198973E+09 | 77316722.52 | 0.121656E+09 | 0.239616E+09 | 57708926.58 |
Maximum of Months | 0.424752E+09 | 0.215509E+09 | 0.215797E+09 | 0.566022E+09 | 0.105375E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 201.61 | 200.94 | 157.95 | 34.24 | 123.70 | 0.00 | 0.00 |
February | 251.00 | 181.33 | 180.34 | 38.82 | 141.53 | 0.00 | 0.00 |
March | 336.41 | 148.36 | 211.88 | 47.65 | 164.23 | 0.00 | 0.00 |
April | 428.34 | 107.02 | 232.95 | 49.20 | 183.75 | 0.00 | 0.00 |
May | 565.34 | 37.85 | 255.69 | 58.92 | 196.77 | 0.00 | 0.00 |
June | 620.48 | 16.69 | 266.69 | 66.02 | 200.67 | 0.00 | 0.00 |
July | 647.01 | 2.33 | 244.82 | 53.60 | 191.22 | 0.00 | 0.00 |
August | 651.71 | 1.47 | 244.89 | 56.80 | 188.09 | 0.00 | 0.00 |
September | 533.88 | 23.44 | 230.67 | 55.48 | 175.19 | 0.00 | 0.00 |
October | 415.40 | 65.97 | 204.89 | 50.66 | 154.23 | 0.00 | 0.00 |
November | 299.35 | 133.08 | 176.24 | 44.20 | 132.04 | 0.00 | 0.00 |
December | 203.45 | 192.35 | 149.31 | 34.21 | 115.10 | 0.00 | 0.00 |
Annual Sum or Average | 430.52 | 92.09 | 213.15 | 49.18 | 163.96 | 0.00 | 0.00 |
Minimum of Months | 201.61 | 1.47 | 149.31 | 34.21 | 115.10 | 0.00 | 0.00 |
Maximum of Months | 651.71 | 200.94 | 266.69 | 66.02 | 200.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1353.93 | 509.36 | 1119.44 | 429.08 | 690.36 | 0.00 | 0.00 |
February | 1676.12 | 473.30 | 1357.30 | 554.70 | 802.60 | 0.00 | 0.00 |
March | 2097.06 | 434.45 | 1641.47 | 689.03 | 952.45 | 0.00 | 0.00 |
April | 2582.02 | 364.79 | 1935.07 | 857.83 | 1077.24 | 0.00 | 0.00 |
May | 3069.78 | 202.28 | 2195.67 | 1067.70 | 1127.97 | 0.00 | 0.00 |
June | 3233.61 | 153.92 | 2288.70 | 1163.96 | 1124.74 | 0.00 | 0.00 |
July | 3233.11 | 70.85 | 2220.18 | 1126.47 | 1093.71 | 0.00 | 0.00 |
August | 3091.16 | 64.69 | 2114.81 | 1039.23 | 1075.58 | 0.00 | 0.00 |
September | 2690.75 | 170.45 | 1897.99 | 910.73 | 987.26 | 0.00 | 0.00 |
October | 2179.26 | 291.95 | 1596.77 | 749.95 | 846.82 | 0.00 | 0.00 |
November | 1633.37 | 438.79 | 1268.75 | 554.91 | 713.84 | 0.00 | 0.00 |
December | 1260.28 | 511.76 | 1040.03 | 404.13 | 635.90 | 0.00 | 0.00 |
Annual Sum or Average | 2345.06 | 306.13 | 1724.66 | 796.79 | 927.87 | 0.00 | 0.00 |
Minimum of Months | 1260.28 | 64.69 | 1040.03 | 404.13 | 635.90 | 0.00 | 0.00 |
Maximum of Months | 3233.61 | 511.76 | 2288.70 | 1163.96 | 1127.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12218.80 | 3567.46 | 2558.71 | 980.75 | 1577.96 | 0.00 | 0.00 |
February | 14915.24 | 3466.82 | 3102.39 | 1267.88 | 1834.51 | 0.00 | 0.00 |
March | 20679.12 | 3511.65 | 3751.94 | 1574.92 | 2177.02 | 0.00 | 0.00 |
April | 28872.77 | 3871.70 | 4423.02 | 1960.76 | 2462.26 | 0.00 | 0.00 |
May | 42684.47 | 4311.11 | 5018.68 | 2440.45 | 2578.22 | 0.00 | 0.00 |
June | 45928.57 | 4242.67 | 5231.32 | 2660.48 | 2570.84 | 0.00 | 0.00 |
July | 50101.50 | 4069.08 | 5074.70 | 2574.78 | 2499.92 | 0.00 | 0.00 |
August | 46806.27 | 4400.94 | 4833.85 | 2375.39 | 2458.46 | 0.00 | 0.00 |
September | 37549.25 | 4798.06 | 4338.27 | 2081.67 | 2256.59 | 0.00 | 0.00 |
October | 26694.82 | 5410.14 | 3649.76 | 1714.17 | 1935.59 | 0.00 | 0.00 |
November | 16262.37 | 4457.87 | 2899.99 | 1268.36 | 1631.63 | 0.00 | 0.00 |
December | 10648.47 | 4113.10 | 2377.21 | 923.74 | 1453.48 | 0.00 | 0.00 |
Annual Sum or Average | 29536.58 | 4189.23 | 3942.07 | 1821.23 | 2120.84 | 0.00 | 0.00 |
Minimum of Months | 10648.47 | 3466.82 | 2377.21 | 923.74 | 1453.48 | 0.00 | 0.00 |
Maximum of Months | 50101.50 | 5410.14 | 5231.32 | 2660.48 | 2578.22 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.539992E+09 | 0.538209E+09 | 0.423044E+09 | 91713662.48 | 0.331331E+09 | 0.00 | 0.00 |
February | 0.607210E+09 | 0.438681E+09 | 0.436289E+09 | 93905595.05 | 0.342383E+09 | 0.00 | 0.00 |
March | 0.901042E+09 | 0.397357E+09 | 0.567505E+09 | 0.127634E+09 | 0.439871E+09 | 0.00 | 0.00 |
April | 0.111026E+10 | 0.277399E+09 | 0.603803E+09 | 0.127523E+09 | 0.476280E+09 | 0.00 | 0.00 |
May | 0.151421E+10 | 0.101365E+09 | 0.684847E+09 | 0.157811E+09 | 0.527036E+09 | 0.00 | 0.00 |
June | 0.160830E+10 | 43271153.65 | 0.691252E+09 | 0.171124E+09 | 0.520128E+09 | 0.00 | 0.00 |
July | 0.173295E+10 | 6251415.45 | 0.655730E+09 | 0.143574E+09 | 0.512155E+09 | 0.00 | 0.00 |
August | 0.174554E+10 | 3949147.04 | 0.655918E+09 | 0.152134E+09 | 0.503783E+09 | 0.00 | 0.00 |
September | 0.138382E+10 | 60751094.63 | 0.597895E+09 | 0.143806E+09 | 0.454089E+09 | 0.00 | 0.00 |
October | 0.111262E+10 | 0.176702E+09 | 0.548774E+09 | 0.135686E+09 | 0.413088E+09 | 0.00 | 0.00 |
November | 0.775917E+09 | 0.344938E+09 | 0.456813E+09 | 0.114558E+09 | 0.342255E+09 | 0.00 | 0.00 |
December | 0.544924E+09 | 0.515188E+09 | 0.399913E+09 | 91620025.04 | 0.308293E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135768E+11 | 0.290406E+10 | 0.672178E+10 | 0.155109E+10 | 0.517069E+10 | 0.00 | 0.00 |
Minimum of Months | 0.539992E+09 | 3949147.04 | 0.399913E+09 | 91620025.04 | 0.308293E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174554E+10 | 0.538209E+09 | 0.691252E+09 | 0.171124E+09 | 0.527036E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.362637E+10 | 0.136426E+10 | 0.299830E+10 | 0.114924E+10 | 0.184905E+10 | 0.00 | 0.00 |
February | 0.405488E+10 | 0.114501E+10 | 0.328357E+10 | 0.134193E+10 | 0.194165E+10 | 0.00 | 0.00 |
March | 0.561676E+10 | 0.116362E+10 | 0.439652E+10 | 0.184549E+10 | 0.255103E+10 | 0.00 | 0.00 |
April | 0.669259E+10 | 0.945545E+09 | 0.501570E+10 | 0.222350E+10 | 0.279220E+10 | 0.00 | 0.00 |
May | 0.822211E+10 | 0.541775E+09 | 0.588088E+10 | 0.285972E+10 | 0.302116E+10 | 0.00 | 0.00 |
June | 0.838152E+10 | 0.398955E+09 | 0.593232E+10 | 0.301698E+10 | 0.291533E+10 | 0.00 | 0.00 |
July | 0.865957E+10 | 0.189778E+09 | 0.594653E+10 | 0.301713E+10 | 0.292940E+10 | 0.00 | 0.00 |
August | 0.827935E+10 | 0.173276E+09 | 0.566430E+10 | 0.278348E+10 | 0.288083E+10 | 0.00 | 0.00 |
September | 0.697443E+10 | 0.441816E+09 | 0.491959E+10 | 0.236062E+10 | 0.255898E+10 | 0.00 | 0.00 |
October | 0.583692E+10 | 0.781957E+09 | 0.427679E+10 | 0.200866E+10 | 0.226813E+10 | 0.00 | 0.00 |
November | 0.423370E+10 | 0.113734E+10 | 0.328859E+10 | 0.143832E+10 | 0.185027E+10 | 0.00 | 0.00 |
December | 0.337552E+10 | 0.137071E+10 | 0.278562E+10 | 0.108243E+10 | 0.170319E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.739537E+11 | 0.965404E+10 | 0.543887E+11 | 0.251275E+11 | 0.292612E+11 | 0.00 | 0.00 |
Minimum of Months | 0.337552E+10 | 0.173276E+09 | 0.278562E+10 | 0.108243E+10 | 0.170319E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865957E+10 | 0.137071E+10 | 0.594653E+10 | 0.301713E+10 | 0.302116E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327268E+11 | 0.955509E+10 | 0.685325E+10 | 0.262684E+10 | 0.422641E+10 | 0.00 | 0.00 |
February | 0.360829E+11 | 0.838693E+10 | 0.750531E+10 | 0.306726E+10 | 0.443805E+10 | 0.00 | 0.00 |
March | 0.553870E+11 | 0.940560E+10 | 0.100492E+11 | 0.421827E+10 | 0.583092E+10 | 0.00 | 0.00 |
April | 0.748382E+11 | 0.100354E+11 | 0.114645E+11 | 0.508229E+10 | 0.638218E+10 | 0.00 | 0.00 |
May | 0.114326E+12 | 0.115469E+11 | 0.134420E+11 | 0.653651E+10 | 0.690551E+10 | 0.00 | 0.00 |
June | 0.119047E+12 | 0.109970E+11 | 0.135596E+11 | 0.689596E+10 | 0.666362E+10 | 0.00 | 0.00 |
July | 0.134192E+12 | 0.108986E+11 | 0.135921E+11 | 0.689629E+10 | 0.669577E+10 | 0.00 | 0.00 |
August | 0.125366E+12 | 0.117875E+11 | 0.129470E+11 | 0.636224E+10 | 0.658474E+10 | 0.00 | 0.00 |
September | 0.973277E+11 | 0.124366E+11 | 0.112448E+11 | 0.539570E+10 | 0.584909E+10 | 0.00 | 0.00 |
October | 0.714994E+11 | 0.144905E+11 | 0.977552E+10 | 0.459122E+10 | 0.518429E+10 | 0.00 | 0.00 |
November | 0.421521E+11 | 0.115548E+11 | 0.751678E+10 | 0.328758E+10 | 0.422920E+10 | 0.00 | 0.00 |
December | 0.285209E+11 | 0.110165E+11 | 0.636713E+10 | 0.247414E+10 | 0.389300E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.931466E+12 | 0.132111E+12 | 0.124317E+12 | 0.574343E+11 | 0.668828E+11 | 0.00 | 0.00 |
Minimum of Months | 0.285209E+11 | 0.838693E+10 | 0.636713E+10 | 0.247414E+10 | 0.389300E+10 | 0.00 | 0.00 |
Maximum of Months | 0.134192E+12 | 0.144905E+11 | 0.135921E+11 | 0.689629E+10 | 0.690551E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.668642E+09 | -608906280.2 | 0.00 | 0.00 | 744.00 | 0.00 | -59735492.3 | 58.99 | 0.00 | 0.00 |
February | 0.596806E+09 | -543778924.7 | 0.00 | 0.00 | 672.00 | 0.00 | -53027439.5 | 58.99 | 0.00 | 0.00 |
March | 0.648568E+09 | -590749769.8 | 0.00 | 0.00 | 744.00 | 0.00 | -57817786.2 | 59.00 | 0.00 | 0.00 |
April | 0.547871E+09 | -493197862.0 | 0.00 | 0.00 | 720.00 | 0.00 | -54673335.9 | 58.99 | 0.00 | 0.00 |
May | 0.512092E+09 | -456693936.3 | 0.00 | 0.00 | 744.00 | 0.00 | -55397658.6 | 58.99 | 0.00 | 0.00 |
June | 0.467336E+09 | -413953746.7 | 0.00 | 0.00 | 720.00 | 0.00 | -53381980.8 | 58.98 | 0.00 | 0.00 |
July | 0.442191E+09 | -387627642.2 | 0.00 | 0.00 | 744.00 | 0.00 | -54563362.3 | 58.99 | 0.00 | 0.00 |
August | 0.490096E+09 | -435322132.4 | 0.00 | 0.00 | 744.00 | 0.00 | -54773539.7 | 58.98 | 0.00 | 0.00 |
September | 0.501416E+09 | -448221546.7 | 0.00 | 0.00 | 720.00 | 0.00 | -53194065.6 | 58.99 | 0.00 | 0.00 |
October | 0.560394E+09 | -505119689.3 | 0.00 | 0.00 | 744.00 | 0.00 | -55274500.2 | 58.99 | 0.00 | 0.00 |
November | 0.591139E+09 | -536771401.6 | 0.00 | 0.00 | 720.00 | 0.00 | -54367921.9 | 58.98 | 0.00 | 0.00 |
December | 0.654932E+09 | -596897712.2 | 0.00 | 0.00 | 744.00 | 0.00 | -58033819.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.668148E+10 | -0.601724E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -664240902.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.442191E+09 | -608906280.2 | 0.00 | 0.00 | 672.00 | 0.00 | -59735492.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.668642E+09 | -387627642.2 | 0.00 | 0.00 | 744.00 | 0.00 | -53027439.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.68 | 0.50 | 01-JAN-10:50 | 321.49 | 0.00 | 0.00 | 169.83 | 595.07 | 0.00 | 0.00 | 134.00 |
February | 308.33 | 0.66 | 0.50 | 01-FEB-10:20 | 369.62 | 0.00 | 0.00 | 177.83 | 674.77 | 0.00 | 0.00 | 145.00 |
March | 357.50 | 0.65 | 0.50 | 01-MAR-09:00 | 429.37 | 0.00 | 0.00 | 226.17 | 342.82 | 0.00 | 0.00 | 185.33 |
April | 375.00 | 0.65 | 0.50 | 01-APR-09:39 | 473.17 | 0.00 | 0.00 | 243.33 | 904.29 | 0.00 | 0.00 | 195.67 |
May | 405.33 | 0.65 | 0.50 | 01-MAY-09:20 | 1216.80 | 0.00 | 0.00 | 265.67 | 341.09 | 0.00 | 0.00 | 199.33 |
June | 403.50 | 0.65 | 0.50 | 01-JUN-09:30 | 513.93 | 0.00 | 0.00 | 267.67 | 324.43 | 0.00 | 0.00 | 191.67 |
July | 405.00 | 0.64 | 0.50 | 01-JUL-09:20 | 930.33 | 0.00 | 0.00 | 272.17 | 340.76 | 0.00 | 0.00 | 204.50 |
August | 395.83 | 0.64 | 0.50 | 01-AUG-09:30 | 1374.57 | 0.00 | 0.00 | 265.17 | 379.95 | 0.00 | 0.00 | 208.67 |
September | 358.83 | 0.64 | 0.50 | 01-SEP-09:20 | 472.61 | 0.00 | 0.00 | 239.00 | 378.99 | 0.00 | 0.00 | 196.17 |
October | 351.17 | 0.65 | 0.50 | 01-OCT-09:09 | 401.98 | 0.00 | 0.00 | 216.17 | 472.50 | 0.00 | 0.00 | 179.67 |
November | 318.83 | 0.67 | 0.50 | 01-NOV-09:30 | 345.66 | 0.00 | 0.00 | 176.67 | 841.21 | 0.00 | 0.00 | 146.67 |
December | 319.00 | 0.69 | 0.50 | 01-DEC-10:09 | 305.54 | 0.00 | 0.00 | 160.17 | 251.81 | 0.00 | 0.00 | 122.50 |
Annual Sum or Average | 4323.33 | 0.65 | 622.04 | 0.00 | 0.00 | 2679.83 | 479.06 | 0.00 | 0.00 | 2109.17 | ||
Minimum of Months | 308.33 | 0.64 | 0.50 | 305.54 | 0.00 | 0.00 | 160.17 | 251.81 | 0.00 | 0.00 | 122.50 | |
Maximum of Months | 405.33 | 0.69 | 0.50 | 1374.57 | 0.00 | 0.00 | 272.17 | 904.29 | 0.00 | 0.00 | 208.67 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.60 | 0.50 | 01-JAN-08:50 | 915.36 | 16.20 | 20.17 | 240.67 | 485.44 | 20.99 | 128.17 | 226.67 |
February | 308.33 | 0.59 | 0.50 | 01-FEB-08:39 | 1105.32 | 16.50 | 16.50 | 235.50 | 345.30 | 19.26 | 113.67 | 213.00 |
March | 357.50 | 0.58 | 0.50 | 01-MAR-08:30 | 1151.10 | 16.05 | 6.00 | 282.83 | 977.95 | 19.60 | 131.67 | 258.83 |
April | 375.00 | 0.58 | 0.50 | 01-APR-07:40 | 1115.57 | 16.05 | 19.83 | 299.00 | 969.23 | 19.56 | 138.17 | 276.00 |
May | 405.33 | 0.57 | 0.50 | 01-MAY-07:10 | 517.81 | 16.11 | 27.50 | 327.00 | 447.79 | 19.71 | 148.33 | 303.33 |
June | 403.50 | 0.58 | 0.50 | 01-JUN-07:10 | 526.42 | 16.10 | 39.83 | 324.67 | 454.49 | 19.81 | 147.17 | 300.50 |
July | 405.00 | 0.57 | 0.50 | 01-JUL-06:00 | 535.81 | 16.15 | 39.17 | 329.33 | 495.33 | 21.41 | 165.50 | 314.33 |
August | 395.83 | 0.58 | 0.50 | 01-AUG-07:19 | 693.06 | 16.32 | 45.17 | 321.17 | 612.24 | 19.91 | 151.67 | 297.33 |
September | 358.83 | 0.57 | 0.50 | 01-SEP-07:30 | 1580.02 | 16.47 | 31.67 | 292.00 | 1393.37 | 20.17 | 146.83 | 269.67 |
October | 351.17 | 0.58 | 0.50 | 01-OCT-07:40 | 456.15 | 16.12 | 9.33 | 276.17 | 381.72 | 19.86 | 142.00 | 250.83 |
November | 318.83 | 0.59 | 0.50 | 01-NOV-07:49 | 394.81 | 15.98 | 0.00 | 243.00 | 852.09 | 19.68 | 123.17 | 217.50 |
December | 319.00 | 0.61 | 0.50 | 01-DEC-08:30 | 349.39 | 15.15 | 0.00 | 231.33 | 539.53 | 18.67 | 102.17 | 205.00 |
Annual Sum or Average | 4323.33 | 0.58 | 774.00 | 16.11 | 255.17 | 3402.67 | 662.21 | 19.91 | 1638.50 | 3133.00 | ||
Minimum of Months | 308.33 | 0.57 | 0.50 | 349.39 | 15.15 | 0.00 | 231.33 | 345.30 | 18.67 | 102.17 | 205.00 | |
Maximum of Months | 405.33 | 0.61 | 0.50 | 1580.02 | 16.50 | 45.17 | 329.33 | 1393.37 | 21.41 | 165.50 | 314.33 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.90 | 0.82 | 29-JAN-15:30 | 226.28 | 22.63 | 171.67 | 25.67 | 112.75 | 20.41 | 153.33 | 0.00 |
February | 308.33 | 0.89 | 0.80 | 10-FEB-16:10 | 268.23 | 22.90 | 162.33 | 40.33 | 172.52 | 22.30 | 161.67 | 21.50 |
March | 357.50 | 0.89 | 0.80 | 01-MAR-16:10 | 294.45 | 22.62 | 175.50 | 67.50 | 212.24 | 23.16 | 195.17 | 29.67 |
April | 375.00 | 0.89 | 0.80 | 01-APR-15:20 | 241.62 | 20.15 | 147.00 | 56.17 | 169.93 | 21.18 | 186.83 | 20.67 |
May | 405.33 | 0.88 | 0.80 | 01-MAY-14:00 | 257.80 | 20.02 | 147.17 | 73.67 | 180.81 | 21.28 | 187.83 | 27.00 |
June | 403.50 | 0.87 | 0.80 | 01-JUN-15:09 | 274.27 | 20.03 | 152.00 | 87.33 | 195.83 | 21.31 | 202.00 | 38.83 |
July | 405.00 | 0.88 | 0.80 | 01-JUL-14:50 | 270.84 | 19.94 | 155.00 | 83.33 | 182.58 | 21.10 | 207.83 | 34.67 |
August | 395.83 | 0.88 | 0.80 | 01-AUG-15:09 | 269.07 | 20.33 | 164.17 | 85.33 | 197.01 | 21.63 | 216.00 | 46.83 |
September | 358.83 | 0.88 | 0.80 | 01-SEP-14:50 | 286.39 | 21.83 | 178.00 | 88.17 | 242.33 | 23.68 | 208.50 | 45.67 |
October | 351.17 | 0.88 | 0.80 | 01-OCT-15:09 | 274.92 | 23.29 | 194.17 | 76.00 | 182.89 | 23.65 | 206.67 | 29.00 |
November | 318.83 | 0.89 | 0.80 | 01-NOV-16:10 | 286.54 | 23.89 | 180.50 | 37.17 | 139.12 | 22.46 | 175.33 | 8.00 |
December | 319.00 | 0.91 | 0.83 | 05-DEC-14:39 | 226.28 | 22.71 | 168.67 | 21.17 | 110.08 | 20.40 | 148.67 | 0.00 |
Annual Sum or Average | 4323.33 | 0.89 | 265.15 | 21.57 | 1996.17 | 741.83 | 176.79 | 21.87 | 2249.83 | 301.83 | ||
Minimum of Months | 308.33 | 0.87 | 0.80 | 226.28 | 19.94 | 147.00 | 21.17 | 110.08 | 20.40 | 148.67 | 0.00 | |
Maximum of Months | 405.33 | 0.91 | 0.83 | 294.45 | 23.89 | 194.17 | 88.17 | 242.33 | 23.68 | 216.00 | 46.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2044646.17 | 6898.68 | 02-JAN-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2044646.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2044646.17 | 6898.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.401602E+10 | 0.325061E+10 | 21714.06 | 30-JAN-08:63 | 14052.91 | 0.00 |
February | 0.00 | 0.00 | 0.524624E+10 | 0.421273E+10 | 31906.67 | 09-FEB-08:62 | 19685.31 | 0.00 |
March | 0.00 | 0.00 | 0.768100E+10 | 0.642392E+10 | 32281.00 | 29-MAR-07:02 | 18402.23 | 0.00 |
April | 0.00 | 0.00 | 0.954556E+10 | 0.791455E+10 | 32875.26 | 10-APR-06:02 | 20338.40 | 0.00 |
May | 0.00 | 0.00 | 0.138639E+11 | 0.113517E+11 | 34894.01 | 25-MAY-06:01 | 18355.43 | 0.00 |
June | 0.00 | 0.00 | 0.168326E+11 | 0.125158E+11 | 35291.08 | 08-JUN-06:03 | 16595.66 | 0.00 |
July | 0.00 | 0.00 | 0.194199E+11 | 0.135209E+11 | 33988.51 | 06-JUL-05:03 | 15237.55 | 0.00 |
August | 0.00 | 0.00 | 0.216883E+11 | 0.149151E+11 | 33988.51 | 31-AUG-05:03 | 16335.42 | 0.00 |
September | 0.00 | 0.00 | 0.173088E+11 | 0.121840E+11 | 35478.54 | 25-SEP-06:01 | 17903.80 | 0.00 |
October | 0.00 | 0.00 | 0.138053E+11 | 0.103710E+11 | 35336.44 | 07-OCT-06:01 | 17372.06 | 0.00 |
November | 0.00 | 0.00 | 0.101504E+11 | 0.776962E+10 | 34370.11 | 03-NOV-06:01 | 19281.49 | 0.00 |
December | 0.00 | 0.00 | 0.648061E+10 | 0.509448E+10 | 31812.83 | 05-DEC-08:62 | 18915.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146039E+12 | 0.109524E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.401602E+10 | 0.325061E+10 | 21714.06 | 14052.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216883E+11 | 0.149151E+11 | 35478.54 | 20338.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144438E+09 | 0.117529E+09 | 5007.90 | 28-JAN-14:00 | 5007.90 | 0.00 |
February | 0.00 | 0.00 | 0.238703E+10 | 0.182990E+10 | 31895.77 | 05-FEB-14:55 | 28342.79 | 0.00 |
March | 0.00 | 0.00 | 0.844129E+10 | 0.687025E+10 | 68765.09 | 26-MAR-13:43 | 68539.31 | 0.00 |
April | 0.00 | 0.00 | 0.197215E+11 | 0.158840E+11 | 92167.68 | 30-APR-16:53 | 61061.12 | 0.00 |
May | 0.00 | 0.00 | 0.424225E+11 | 0.336710E+11 | 94068.62 | 24-MAY-17:43 | 58277.51 | 0.00 |
June | 0.00 | 0.00 | 0.560843E+11 | 0.396307E+11 | 94729.62 | 26-JUN-19:03 | 55826.44 | 0.00 |
July | 0.00 | 0.00 | 0.717737E+11 | 0.486406E+11 | 95609.29 | 26-JUL-19:43 | 53665.81 | 0.00 |
August | 0.00 | 0.00 | 0.769172E+11 | 0.511649E+11 | 98144.35 | 08-AUG-21:03 | 51538.36 | 0.00 |
September | 0.00 | 0.00 | 0.573305E+11 | 0.380823E+11 | 97793.70 | 08-SEP-18:23 | 51797.63 | 0.00 |
October | 0.00 | 0.00 | 0.374734E+11 | 0.269411E+11 | 95814.03 | 07-OCT-17:06 | 53647.35 | 0.00 |
November | 0.00 | 0.00 | 0.177133E+11 | 0.128492E+11 | 80102.51 | 02-NOV-17:10 | 51938.48 | 0.00 |
December | 0.00 | 0.00 | 0.385098E+10 | 0.272825E+10 | 35343.83 | 03-DEC-13:05 | 28017.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.394260E+12 | 0.278410E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.144438E+09 | 0.117529E+09 | 5007.90 | 5007.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.769172E+11 | 0.511649E+11 | 98144.35 | 68539.31 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.554009E+09 | 0.20 | 909.67 | 30-JAN-08:63 | 0.73 |
February | 0.510364E+09 | 0.21 | 1398.69 | 06-FEB-08:62 | 0.90 |
March | 0.601001E+09 | 0.22 | 1398.69 | 01-MAR-08:62 | 0.90 |
April | 0.565811E+09 | 0.21 | 1398.69 | 01-APR-07:02 | 0.90 |
May | 0.675530E+09 | 0.25 | 1398.69 | 01-MAY-06:02 | 0.89 |
June | 0.787760E+09 | 0.28 | 1398.69 | 01-JUN-06:02 | 0.90 |
July | 0.908302E+09 | 0.31 | 1398.69 | 01-JUL-06:02 | 0.89 |
August | 0.102054E+10 | 0.34 | 1398.69 | 01-AUG-05:02 | 0.89 |
September | 0.791211E+09 | 0.29 | 1398.69 | 01-SEP-05:03 | 0.89 |
October | 0.635848E+09 | 0.23 | 1398.69 | 02-OCT-05:03 | 0.88 |
November | 0.544703E+09 | 0.20 | 1398.69 | 01-NOV-06:02 | 0.89 |
December | 0.555127E+09 | 0.20 | 1398.69 | 02-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.815020E+10 | 0.25 | |||
Minimum of Months | 0.510364E+09 | 0.20 | 909.67 | 0.73 | |
Maximum of Months | 0.102054E+10 | 0.34 | 1398.69 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140170E+10 | 0.19 | 1415.86 | 23-JAN-13:50 | 0.53 |
February | 0.129461E+10 | 0.20 | 1415.86 | 03-FEB-12:20 | 0.52 |
March | 0.154075E+10 | 0.22 | 3023.86 | 26-MAR-13:43 | 0.81 |
April | 0.155690E+10 | 0.27 | 3539.64 | 30-APR-10:53 | 0.87 |
May | 0.198909E+10 | 0.39 | 3539.64 | 04-MAY-17:06 | 0.87 |
June | 0.220262E+10 | 0.44 | 3539.64 | 01-JUN-17:05 | 0.87 |
July | 0.263834E+10 | 0.47 | 3539.64 | 01-JUL-17:06 | 0.86 |
August | 0.280039E+10 | 0.48 | 3539.64 | 01-AUG-17:05 | 0.87 |
September | 0.219965E+10 | 0.43 | 3539.64 | 01-SEP-17:05 | 0.86 |
October | 0.183322E+10 | 0.37 | 3539.64 | 01-OCT-10:23 | 0.86 |
November | 0.145000E+10 | 0.24 | 3040.12 | 05-NOV-12:03 | 0.81 |
December | 0.141038E+10 | 0.20 | 1415.86 | 09-DEC-15:20 | 0.53 |
Annual Sum or Average | 0.223177E+11 | 0.33 | |||
Minimum of Months | 0.129461E+10 | 0.19 | 1415.86 | 0.52 | |
Maximum of Months | 0.280039E+10 | 0.48 | 3539.64 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152027E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177073E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.247688E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.296572E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.436033E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.529320E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.618845E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.692718E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.531185E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.408898E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.298622E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.208979E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.459796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152027E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.692718E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144342E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.198491E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.400281E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.736114E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147790E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.188565E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.241780E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.258306E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.188592E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.126315E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.646564E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.248755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138880E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144342E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.258306E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.554009E+09 | 0.401602E+10 | 2044646.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510364E+09 | 0.524624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601001E+09 | 0.768100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.565811E+09 | 0.954556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675530E+09 | 0.138639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.787760E+09 | 0.168326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.908302E+09 | 0.194199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102054E+10 | 0.216883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.791211E+09 | 0.173088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.635848E+09 | 0.138053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544703E+09 | 0.101504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555127E+09 | 0.648061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815020E+10 | 0.146039E+12 | 2044646.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.510364E+09 | 0.401602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102054E+10 | 0.216883E+11 | 2044646.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140170E+10 | 0.144438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129461E+10 | 0.238703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154075E+10 | 0.844129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155690E+10 | 0.197215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198909E+10 | 0.424225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220262E+10 | 0.560843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.263834E+10 | 0.717737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.280039E+10 | 0.769172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.219965E+10 | 0.573305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183322E+10 | 0.374734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145000E+10 | 0.177133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141038E+10 | 0.385098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223177E+11 | 0.394260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129461E+10 | 0.144438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.280039E+10 | 0.769172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.554009E+09 | 0.00 | 0.00 | 0.00 | 0.966263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510364E+09 | 0.00 | 0.00 | 0.00 | 0.126037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601001E+09 | 0.00 | 0.00 | 0.00 | 0.187588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.565811E+09 | 0.00 | 0.00 | 0.00 | 0.239991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675530E+09 | 0.00 | 0.00 | 0.00 | 0.368480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.787760E+09 | 0.00 | 0.00 | 0.00 | 0.450544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.908302E+09 | 0.00 | 0.00 | 0.00 | 0.528015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102054E+10 | 0.00 | 0.00 | 0.00 | 0.590664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.791211E+09 | 0.00 | 0.00 | 0.00 | 0.452064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.635848E+09 | 0.00 | 0.00 | 0.00 | 0.345313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544703E+09 | 0.00 | 0.00 | 0.00 | 0.244152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555127E+09 | 0.00 | 0.00 | 0.00 | 0.153467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815020E+10 | 0.00 | 0.00 | 0.00 | 0.378294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.510364E+09 | 0.00 | 0.00 | 0.00 | 0.966263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102054E+10 | 0.00 | 0.00 | 0.00 | 0.590664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140170E+10 | 0.00 | 0.00 | 0.00 | 41723214.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 0.690306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154075E+10 | 0.00 | 0.00 | 0.00 | 0.246205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155690E+10 | 0.00 | 0.00 | 0.00 | 0.580424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198909E+10 | 0.00 | 0.00 | 0.00 | 0.127899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220262E+10 | 0.00 | 0.00 | 0.00 | 0.166539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.263834E+10 | 0.00 | 0.00 | 0.00 | 0.215396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.280039E+10 | 0.00 | 0.00 | 0.00 | 0.230302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.219965E+10 | 0.00 | 0.00 | 0.00 | 0.166595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183322E+10 | 0.00 | 0.00 | 0.00 | 0.107983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145000E+10 | 0.00 | 0.00 | 0.00 | 0.501564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141038E+10 | 0.00 | 0.00 | 0.00 | 0.107717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223177E+11 | 0.00 | 0.00 | 0.00 | 0.116563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 41723214.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.280039E+10 | 0.00 | 0.00 | 0.00 | 0.230302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140637E+09 | 0.109612E+09 | 0.00 | 2860148.64 | 0.00 | 347868.74 | 0.273900E+09 | 0.00 | 0.14 |
February | 87584010.52 | 0.256231E+09 | 0.00 | 2787483.64 | 0.00 | 0.00 | 0.130383E+09 | 0.00 | 0.14 |
March | 70040318.95 | 0.541112E+09 | 0.00 | 2525751.54 | 88501.54 | 0.00 | 96429526.29 | 0.00 | 0.15 |
April | 34231626.70 | 0.104294E+10 | 0.00 | 2339487.20 | 1012055.54 | 0.00 | 54093045.94 | 0.00 | 0.14 |
May | 3126553.20 | 0.194896E+10 | 0.00 | 2350098.05 | 1695898.95 | 0.00 | 16151271.45 | 0.00 | 0.15 |
June | 630888.71 | 0.292024E+10 | 0.00 | 724248.34 | 4326591.04 | 0.00 | 4758711.56 | 0.00 | 0.15 |
July | 68364.55 | 0.385900E+10 | 0.00 | 374725.25 | 2107727.54 | 0.00 | 2049169.11 | 0.00 | 0.15 |
August | 0.00 | 0.434096E+10 | 0.00 | 178110.08 | 683103.67 | 0.00 | 163672.05 | 0.00 | 0.16 |
September | 390795.04 | 0.318892E+10 | 0.00 | 759719.39 | 2953714.76 | 0.00 | 3525812.70 | 0.00 | 0.15 |
October | 1161591.76 | 0.205881E+10 | 0.00 | 1413499.91 | 6268474.08 | 0.00 | 15362716.66 | 0.00 | 0.14 |
November | 16938239.25 | 0.122985E+10 | 0.00 | 1622989.95 | 1110271.77 | 0.00 | 18343025.86 | 0.00 | 0.14 |
December | 85226808.61 | 0.416963E+09 | 0.00 | 2572117.33 | 0.00 | 0.00 | 0.110810E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.440037E+09 | 0.219136E+11 | 0.00 | 20508379.32 | 20246338.91 | 347868.74 | 0.725970E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.109612E+09 | 0.00 | 178110.08 | 0.00 | 0.00 | 163672.05 | 0.00 | 0.14 |
Maximum of Months | 0.140637E+09 | 0.434096E+10 | 0.00 | 2860148.64 | 6268474.08 | 347868.74 | 0.273900E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295907E+10 | 12570045.84 | 0.00 | 141460.53 | 6880672.61 | 0.00 | 0.163798E+09 | 0.00 | 0.20 |
February | 0.166566E+10 | 0.178017E+09 | 0.00 | 1397586.36 | 0.00 | 0.00 | 0.813203E+09 | 0.00 | 0.20 |
March | 0.104056E+10 | 0.794970E+09 | 0.00 | 3319970.97 | 559441.73 | 0.00 | 0.875798E+09 | 0.00 | 0.22 |
April | 0.448773E+09 | 0.253367E+10 | 0.00 | 3118784.83 | 1749056.73 | 0.00 | 0.452401E+09 | 0.00 | 0.22 |
May | 8478744.88 | 0.771026E+10 | 0.00 | 2028220.79 | 6222295.05 | 0.00 | 85309497.71 | 0.00 | 0.25 |
June | 431302.91 | 0.129916E+11 | 0.00 | 298498.71 | 7830140.01 | 0.00 | 9212124.87 | 0.00 | 0.28 |
July | 0.00 | 0.191891E+11 | 0.00 | 241324.19 | 0.00 | 0.00 | 841960.53 | 0.00 | 0.29 |
August | 0.00 | 0.211908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 250307.63 | 0.143424E+11 | 0.00 | 209800.65 | 9530110.82 | 0.00 | 3485199.31 | 0.00 | 0.27 |
October | 3556712.59 | 0.731769E+10 | 0.00 | 1686533.93 | 12585033.29 | 0.00 | 99541921.32 | 0.00 | 0.24 |
November | 0.218573E+09 | 0.253296E+10 | 0.00 | 2628842.15 | 627085.10 | 0.00 | 0.192954E+09 | 0.00 | 0.21 |
December | 0.160009E+10 | 0.275041E+09 | 0.00 | 2242824.69 | 27560.17 | 0.00 | 0.778945E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.794543E+10 | 0.890690E+11 | 0.00 | 17313847.80 | 46011395.52 | 0.00 | 0.347549E+10 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 12570045.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.295907E+10 | 0.211908E+11 | 0.00 | 3319970.97 | 12585033.29 | 0.00 | 0.875798E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.307161E+12 | 0.192568E+11 | 0.00 | 0.101408E+11 | 0.516945E+10 |
February | 0.353871E+12 | 0.220328E+11 | 0.00 | 0.765498E+10 | 0.958395E+10 |
March | 0.456000E+12 | 0.151598E+11 | 0.00 | 0.498962E+10 | 0.204602E+11 |
April | 0.500168E+12 | 0.134464E+11 | 0.00 | -0.207900E+10 | 0.374712E+11 |
May | 0.548742E+12 | 0.203607E+11 | 0.00 | -0.147341E+11 | 0.727611E+11 |
June | 0.536548E+12 | 0.235964E+11 | 0.00 | -0.237898E+11 | 0.940762E+11 |
July | 0.546546E+12 | 0.134727E+11 | 0.00 | -0.329010E+11 | 0.118013E+12 |
August | 0.531032E+12 | 0.274272E+11 | 0.00 | -0.353379E+11 | 0.127542E+12 |
September | 0.455938E+12 | 0.279108E+11 | 0.00 | -0.259425E+11 | 0.958194E+11 |
October | 0.382564E+12 | 0.243875E+11 | 0.00 | -0.155000E+11 | 0.655301E+11 |
November | 0.295608E+12 | 0.204303E+11 | 0.00 | -0.278137E+10 | 0.353208E+11 |
December | 0.276011E+12 | 0.240671E+11 | 0.00 | 0.786253E+10 | 0.129434E+11 |
Annual Sum or Average | 0.519019E+13 | 0.251548E+12 | 0.00 | -0.122418E+12 | 0.694692E+12 |
Minimum of Months | 0.276011E+12 | 0.134464E+11 | 0.00 | -0.353379E+11 | 0.516945E+10 |