Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 10:43:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 443.59 | 91.74 | 91.74 |
Net Site Energy | 443.59 | 91.74 | 91.74 |
Total Source Energy | 1346.88 | 278.56 | 278.56 |
Net Source Energy | 1346.88 | 278.56 | 278.56 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 103.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 415.76 | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 103.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 10.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 40.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 103.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 34.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 36.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.64 | 5.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 85.99 | 5.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 36.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.64 | 5.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 85.99 | 5.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 415.757 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 415.757 | 100.00 |
Total On-Site and Utility Electric Sources | 415.757 | 100.00 |
Total Electricity End Uses | 415.757 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2935.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6766 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5498 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 7.6766 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.3906 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.5498 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.5498 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-15:39 | 27-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 28-JUN-11:39 |
Heating | 0.00 | 43256.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14479.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6044.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5168.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1585.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37391.86 | 43256.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 43256.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14479.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6044.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2863.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1585.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 30.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 129.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 328.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 230.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 109.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1316.70 | 30.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 6.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 68.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 272.32 | 6.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 6.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 68.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 272.32 | 6.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.26 |
ZONE2 FINE STORAGE DIRECT AIR | 2.89 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 1.46 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 1.46 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 51895.92 |
PSZ-OFFICE HEATING COIL | 27823.76 |
PSZ-FINE STORAGE HEATING COIL | 83469.69 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 51895.92 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-FINE STORAGE | 2.89 | 2.89 | 2.89 | 2.89 | 2.89 | 2.89 | 1.00 | 1.00 | 2.89 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.26 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.89 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.26 | 1392.27 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.89 | 3096.13 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.829961 | 21599.63 | 27823.76 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.89 | 2.89 | 2.89 | 1.91 | 60427.93 | 83469.69 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.26 | 0.628758 | 0.838347 | 21599.63 | 10799.82 | 0.800320 | 0.800320 |
PSZ-FINE STORAGE COOLING COIL | 2.89 | 1.45 | 1.93 | 60427.93 | 30213.97 | 0.759410 | 0.759410 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 7.677 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.750 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1818.427 | 7.677 | 142.636 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1818.427 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10866.415 | 3.391 | 157.484 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.415 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.750 | 0.900 | 0.450 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5832 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.615 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
8 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
9 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
10 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
11 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
12 | 4 | 0.76147947E-12 | 0.16972320E-15 | -0.23941589E-14 | 0.12030052E-15 |
13 | 3 | -0.37802266E-03 | 0.40617527E-06 | -0.54770175E-04 | 0.14612398E-12 |
14 | 2 | 1.7236739 | 0.89444888E-02 | 1.1283884 | -0.72472748E-04 |
15 | 1 | -7.1497137 | 0.23277257 | -17.021073 | 0.33034766 |
16 | 0 | 5.8169840 | 0.14884880 | 16.283305 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23941589E-14 | 0.16972320E-15 | 0.76147947E-12 | 0.12030052E-15 |
85 | 3 | -0.54770175E-04 | 0.40617527E-06 | -0.37802266E-03 | 0.14612398E-12 |
86 | 2 | 1.1283884 | 0.89444888E-02 | 1.7236739 | -0.72472748E-04 |
87 | 1 | -17.021073 | 0.23277257 | -7.1497137 | 0.33034766 |
88 | 0 | 16.283305 | 0.14884880 | 5.8169840 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4637_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.4637_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.636 | 2.636 | 1.000 | 0.251 | ||
5 | SKYLIGHT_U_0.9_SHGC_0.6 | 38 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.49037E-002 | 0.16139 | 0.61562 | 0.61562 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11941 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4056E-004 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0740E-003 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2500E-004 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1443E-003 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2209E-004 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2209E-003 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5848E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1816E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5119E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5755E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1206E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1771E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3643E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7900E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7680E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.3855E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5323E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6144E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.6577E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8619E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8793E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0623E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2141E-003 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2648E-004 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0965E-003 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4951E-004 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0024E-003 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5906E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6167E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2484E-004 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0450E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8226E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1651E-003 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0824E-004 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2175E-003 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1232E-004 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4214E-003 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8535E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2695E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9692E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5676E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1664E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2577E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3662E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9029E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8834E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9222E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6649E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6132E-003 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.3702E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9293E-003 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.6126E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0188E-003 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9572E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8087E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6800E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2816E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1443E-004 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.7601E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1985E-004 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1202E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0085E-004 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7041E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.0163E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5708E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7239E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4494E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8722E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5963E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3371E-004 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.3936E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0000E-004 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.9171E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7092E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4359E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.2253E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0818E-003 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5028E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4816E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3510E-004 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1400E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2244E-003 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6017E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4566E-003 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9114E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6572E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2488E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9545E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5378E-004 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0548E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3480E-004 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5699E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3030E-004 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5863E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7796E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2088E-003 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0558E-004 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9608E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8266E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9598E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5450E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9640E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1032E-004 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.8081E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0223E-004 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1854E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5822E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1166E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3848E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7303E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0681E-004 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8985E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3825E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8137E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7470E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5420E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5769E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9795E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6895E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7927E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4175E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.3475E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2501E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4667E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7505E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1771E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2525E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8810E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.3678E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4458E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7408E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2949E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6010E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3980E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6871E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6561E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9028E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8159E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3012E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9777E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0255E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4648E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3769E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9618E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1419E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8040E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1848E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4368E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0410E-004 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3524E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7372E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9357E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1818E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0364E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2346E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9863E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0568E-004 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0921E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7347E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6616E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0254E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8535E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4592E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9279E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0568E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5270E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3747E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6604E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6859E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3690E-003 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7125E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6585E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7378E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7713E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0580E-004 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5939E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.1586E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2968E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2440E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5583E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5006E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0729E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2604E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5435E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6063E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8162E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8215E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.6875E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6379E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0165E-004 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2591E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2647E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7509E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3763E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7925E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2566E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7726E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5343E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0571E-004 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9813E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5272E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1551E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7157E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0991E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5216E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3208E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8581E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9167E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4506E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2208E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6179E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3682E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4847E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2409E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8668E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7823E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3546E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6177E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2974E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4145E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8509E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8931E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9061E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3526E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2774E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9035E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2055E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4312E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7888E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3339E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9089E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0419E-003 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5057E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6573E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2872E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3888E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4152E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9614E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9941E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6221E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6699E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1939E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6566E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0924E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2955E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4385E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4248E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2491E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6276E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7197E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6054E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3449E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2536E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3437E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4293E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8036E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4510E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8334E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2254E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9196E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3429E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6471E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9796E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0165E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4704E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7512E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1828E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5968E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6673E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9778E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6189E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9984E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2669E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7302E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0903E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5492E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6723E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9837E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9047E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9240E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0616E-004 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6626E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4783E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2299E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2191E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3879E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2457E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8593E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9934E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5892E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4287E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2139E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5741E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3924E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7331E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3601E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3080E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1611E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4895E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4275E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5848E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8861E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0100E-003 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5683E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1775E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9058E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8123E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8382E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3798E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6558E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7122E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4057E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4354E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2446E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0438E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7672E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0284E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2504E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6374E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3606E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1349E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1641E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8740E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4475E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1783E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8833E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3453E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9572E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7115E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7788E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3950E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0698E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4387E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0461E-004 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5303E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5532E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1796E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2756E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9500E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3181E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0433E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2098E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5178E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9350E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7657E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7732E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5576E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1394E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7210E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0452E-004 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9739E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5664E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5231E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9081E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5884E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8713E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7356E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6474E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8551E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5504E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6791E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2745E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0418E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3249E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2842E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2086E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2207E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.4676E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.1227E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0923E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7349E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9353E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5887E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7938E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1762E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.1790E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.7607E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.8627E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1628E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6619E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1150E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1395E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4070E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.0291E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.2067E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2669E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7455E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.4815E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3273E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2519E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0435E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.2073E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2732E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7458E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.4633E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3270E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2518E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9331E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11046.90289 | 13256.28347 | 1.04793 | 1.25752 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8164.02659 | 9796.83190 | 0.26415 | 0.31698 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32608.45010 | 39130.14012 | 2.41121 | 2.89345 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 20534.30342 | 24641.16411 | 0.55984 | 0.67181 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 43246.60070 | 51895.92084 | 1.21838 | 1.46205 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17144.36 | 1.25752 | 1.25752 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9120.87 | 0.31698 | 0.31698 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 49714.22 | 2.89345 | 2.89345 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 26483.58 | 0.67181 | 0.67181 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25752 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.89345 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.46205 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 1.46205 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 51895.91602 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 51895.92084 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25752 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25752 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25752 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25752 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25752 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.25752 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89345 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.89345 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.89345 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.89345 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.89345 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.89345 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.25752 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.89345 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25752 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25752 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1392.27010 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25752 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25752 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25752 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82996 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25752 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62876 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83835 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21599.63000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10799.81500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80032 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80032 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21599.63000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27823.76392 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27823.76392 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.89345 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.89345 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3096.12975 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.89345 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.89345 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.89345 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.90968 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.89345 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.44673 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.92897 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 60427.93000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30213.96500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75941 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75941 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 60427.93000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 83469.69205 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 83469.69205 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20623.7 | 11.49 | 11.23 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 58180.7 | 11.74 | 11.47 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.6445735524E-002 | 2.8763051129E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 5.5560589502E-002 | 4.4152624112E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.9604734106E-002 | 2.5669714262E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7128.55 | 342.93 | 0.00 | 29.80 | 208.98 | 7710.35 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.55 | 0.199 | 0.204 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.583 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.55 | 0.199 | 0.204 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.512 | 0.583 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.636 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.4637_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.636 | 0.251 | 0.251 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.636 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.4637_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.636 | 0.251 | 0.251 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.600 | 0.529 | 0.530 | |||||||||||||||||
North Total or Average | 6.51 | 2.636 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.761 | 0.552 | 0.553 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.281 | 3.464 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 7.6766 | 236.88 | 1818.43 | LightsWired | LTG_SCH_OFFICE | 49.99 | 168.00 | 45.53 | 0.0000 | Y | 15.54 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 25.13 | 0.0000 | Y | 43.93 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.3906 | 3204.84 | 10866.42 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 21.74 | 0.0000 | Y | 44.34 |
Interior Lighting Total | 4.5498 | 4835.13 | 21998.92 | 103.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.25 | 10866.42 | 2716.60 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1818.43 | 263.67 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 1818.43 | 90.92 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 93.17 | AstronomicalClock | - | 41.77 | 41.77 | 0.73 | |
EXTERIOR_LIGHTS_B | 5399.43 | AstronomicalClock | - | 83.77 | 71.17 | 72.13 | |
Exterior Lighting Total | 5492.60 | 72.86 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21599.63 | 17286.62 | 4313.01 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 60427.93 | 45889.57 | 14538.36 | 0.76 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20623.7 | 11.49 | 11.23 | ||||
PSZ-FINE STORAGE COOLING COIL | 58180.7 | 11.74 | 11.47 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 51895.92 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27823.76 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 83469.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.46 | 135.84 | 92.91 | 1.00 | 3.80 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1392.27 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.89 | 3096.13 | 1070.05 | 1.00 | 1.27 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11046.90 | 13256.28 | 55.96 | 1.048 | 1.258 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.90 | 23.90 | 0.00823 | 37.15 | 0.00687 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32608.45 | 39130.14 | 28.08 | 2.411 | 2.893 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00820 | 38.10 | 0.00687 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 36.98 | 0.00696 | 37.97 | 0.00687 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8164.03 | 9796.83 | 41.36 | 0.264 | 0.317 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00789 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20534.30 | 24641.16 | 17.68 | 0.560 | 0.672 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00676 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 43246.60 | 51895.92 | 16.19 | 1.218 | 1.462 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00540 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.26 | 1.26 | 0.32 | 0.32 | 1.2575 | 1.2575 | 1.2575 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.89 | 2.89 | 0.67 | 0.67 | 2.8935 | 2.8935 | 2.8935 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 51895.916 | 51895.916 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 51895.92 | 51895.92 | 1.462051 | 10.00 | 6.39 | 0.00540363 | 43.33 | 20.46 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 10.00 | 0.00540363 | 61.6335 | 51895.92 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21599.630 | 17286.616 | 1.257520 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 10799.82 | 10618.11 | 0.838347 | 26.04 | 15.31 | 0.00811954 | 12.00 | 10.01 | 0.00800000 | 37.45 | 0.00687043 | 17.97 | 12.2008 | 23.90 | 0.00823023 | 38.6738 | 11038.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27823.764 | 27823.764 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27823.76 | 27823.76 | 1.257516 | 18.92 | 12.22 | 0.00747273 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 8.1339 | 21.10 | 0.00788571 | 43.9508 | 8164.03 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 60427.930 | 45889.574 | 2.893450 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30213.97 | 30187.00 | 1.928967 | 29.38 | 16.32 | 0.00800741 | 12.00 | 10.01 | 0.00800000 | 38.10 | 0.00687148 | 18.17 | 22.0176 | 26.70 | 0.00820283 | 32.6325 | 32608.45 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 83469.692 | 83469.692 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 83469.69 | 83469.69 | 2.893451 | 12.51 | 8.36 | 0.00618196 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 14.6784 | 15.56 | 0.00676233 | 53.4630 | 20534.30 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 51895.916 | 51895.916 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 1.462051 | 1.52686659 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 51895.92 | 51895.92 | 1.0000 | 1.52686659 | 1.462051 | 10.00 | 6.39 | 0.00540363 | 23661.5 | 43.33 | 20.46 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51895.92 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 10.00 | 0.00540363 | 10.00 | 0.00540363 | 61.6335 | 51895.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21599.630 | 17286.616 | 1.257520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9338 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.257516 | 1.31326412 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 10799.82 | 10618.11 | 1.0000 | 0.87551203 | 0.838347 | 26.04 | 15.31 | 0.00811954 | 46867.2 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10799.82 | 37.45 | 0.00687043 | 17.97 | 0.10228463 | 12.2008 | 23.90 | 0.00823023 | 23.90 | 0.00823023 | 38.6738 | 11038.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27823.764 | 27823.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.257516 | 1.31326412 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 27823.76 | 27823.76 | 1.0000 | 1.31326412 | 1.257516 | 18.92 | 12.22 | 0.00747273 | 37958.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27823.76 | -5.20 | 0.00280840 | -5.20 | 0.10228463 | 8.1339 | 21.05 | 0.00788571 | 21.10 | 0.00788571 | 43.9508 | 8164.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 60427.930 | 45889.574 | 2.893450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7254 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.893451 | 3.02172309 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 30213.97 | 30187.00 | 1.0000 | 2.01448110 | 1.928967 | 29.38 | 16.32 | 0.00800741 | 49983.1 | 12.00 | 10.01 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30213.97 | 38.10 | 0.00687148 | 18.17 | 0.42471127 | 22.0176 | 26.70 | 0.00820283 | 26.70 | 0.00820283 | 32.6325 | 32608.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 83469.692 | 83469.692 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.893451 | 3.02172309 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 83469.69 | 83469.69 | 1.0000 | 3.02172309 | 2.893451 | 12.51 | 8.36 | 0.00618196 | 28175.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83469.69 | -5.20 | 0.00280840 | -5.20 | 0.42471127 | 14.6784 | 15.56 | 0.00676233 | 15.56 | 0.00676233 | 53.4630 | 20534.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.26 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.89 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2535.83 | 1937.83 | 1103.17 |
ZONE2 FINE STORAGE | 3074.67 | 2893.67 | 2415.83 |
ZONE3 BULK STORAGE | 3165.50 | 3306.17 | 2920.83 |
Facility | 3317.17 | 3363.17 | 2935.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 4.67 | 1.17 | 4.67 | 0.00 |
ZONE2 FINE STORAGE | 42.33 | 112.83 | 6.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 45.50 | 114.00 | 9.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.625 | 0.417 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.593 | 0.220 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.135 | 0.000 | 0.804 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2258570.17 | 0.00 | 2258570.17 | 2189737.50 | 4448307.67 | 3225648.14 | 5657.51 | 2333.56 | 768.93 | 0.27 |
ZONE2 FINE STORAGE | 6412175.87 | 0.00 | 6412175.87 | 6171176.23 | 12583352.10 | 13393694.68 | 5634.74 | 2558.04 | 567.22 | 35.58 |
ZONE3 BULK STORAGE | 0.00 | 0.18E+09 | 0.18E+09 | 35183436.68 | 0.22E+09 | 30805497.77 | 6837.28 | 31.56 | 1891.17 | 4862.80 |
Total Facility | 8670746.04 | 0.18E+09 | 0.19E+09 | 43544350.41 | 0.24E+09 | 47424840.58 | 7754.93 | 2837.79 | 2831.43 | 4863.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1725 | 0.0000 | 0.1725 | 0.1154 | 0.2879 | 0.1023 | 533.77 | 2333.56 | 768.66 |
ZONE2 FINE STORAGE | 0.4768 | 0.0000 | 0.4768 | 0.1773 | 0.6541 | 0.4247 | 546.31 | 2558.04 | 531.64 |
ZONE3 BULK STORAGE | 0.0000 | 7.5308 | 7.5308 | 1.2980 | 8.8287 | 0.9768 | 2610.58 | 15.67 | 1009.75 |
Total Facility | 0.6493 | 7.5308 | 8.1801 | 1.5907 | 9.7708 | 1.5038 | 2630.93 | 2821.90 | 1920.65 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2463199.34 | 0.00 | 2463199.34 | 3225648.14 | 5657.01 | 0.17 | 3102.83 | 0.27 |
PSZ-FINE STORAGE | 6993301.62 | 0.00 | 6993301.62 | 13393694.68 | 5633.56 | 0.44 | 3125.99 | 35.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1881 | 0.0000 | 0.1881 | 0.1023 | 533.27 | 0.17 | 3102.56 |
PSZ-FINE STORAGE | 0.5200 | 0.0000 | 0.5200 | 0.4247 | 545.14 | 0.44 | 3090.42 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2842.10 | 269.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2975.92 | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2062 | 0.3649 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5933 | 0.8775 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 429 |
Defaulted Fields | 391 |
Fields with Defaults | 1171 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
Electricity:Building | 254.07 | 1328.97 | 19-MAR-15:10 | 20596.13 | 02-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 47.49 | 774.00 | 12-FEB-15:30 | 2976.64 | 17-NOV-17:00 |
Electricity:SpaceType:GENERAL | 243.10 | 1328.97 | 19-MAR-15:10 | 20596.13 | 02-DEC-16:00 |
InteriorLights:Electricity | 103.81 | 755.22 | 19-MAR-15:10 | 10483.51 | 02-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.54 | 200.25 | 12-FEB-15:30 | 1064.14 | 17-NOV-17:00 |
InteriorLights:Electricity:SpaceType:GENERAL | 103.81 | 755.22 | 19-MAR-15:10 | 10483.51 | 02-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 103.81 | 755.22 | 19-MAR-15:10 | 10483.51 | 02-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 15.54 | 200.25 | 12-FEB-15:30 | 1064.14 | 17-NOV-17:00 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 103.81 | 755.22 | 19-MAR-15:10 | 10483.51 | 02-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 43.93 | 256.14 | 08-JAN-11:10 | 4354.33 | 02-JAN-15:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 43.93 | 256.14 | 08-JAN-11:10 | 4354.33 | 02-JAN-15:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 43.93 | 256.14 | 08-JAN-11:10 | 4354.33 | 02-JAN-15:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 162.65 | 298.83 | 01-JAN-09:10 | 14240.74 | 30-SEP-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 44.34 | 298.83 | 01-JAN-09:10 | 5080.05 | 20-NOV-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 44.34 | 298.83 | 01-JAN-09:10 | 5080.05 | 20-NOV-16:00 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 34.73 | 0.00 | 01-JAN-00:10 | 5263.93 | 15-JUN-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 10.97 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-MAY-15:50 |
Ventilation (simple):Fans:Electricity | 10.97 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-MAY-15:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 10.97 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-MAY-15:50 |
ElectricityPurchased:Facility | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
ElectricityPurchased:Plant | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
Cogeneration:ElectricityPurchased | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
General:Cogeneration:ElectricityPurchased | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
ElectricityNet:Plant | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
Cogeneration:ElectricityNet | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
General:Cogeneration:ElectricityNet | 415.76 | 1811.97 | 19-MAR-15:10 | 37391.86 | 15-JUN-15:40 |
Electricity:HVAC | 64.73 | 0.00 | 01-JAN-00:10 | 17558.40 | 15-JUN-16:10 |
General:Fans:Electricity | 23.76 | 0.00 | 01-JAN-00:10 | 2958.64 | 15-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 40.97 | 0.00 | 01-JAN-00:10 | 14599.76 | 15-JUN-16:10 |
General:Cooling:Electricity | 40.97 | 0.00 | 01-JAN-00:10 | 14599.76 | 15-JUN-16:10 |
ExteriorLights:Electricity | 72.86 | 0.00 | 01-JAN-07:20 | 5492.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.86 | 0.00 | 01-JAN-07:20 | 5492.60 | 01-JAN-06:10 |
Electricity:Plant | 24.10 | 483.00 | 05-JUN-01:00 | 1943.07 | 08-FEB-13:00 |
WaterSystems:Electricity | 24.10 | 483.00 | 05-JUN-01:00 | 1943.07 | 08-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 24.10 | 483.00 | 05-JUN-01:00 | 1943.07 | 08-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 27.84 | 0.00 | 01-JAN-00:10 | 43256.88 | 27-DEC-07:10 |
NaturalGas:HVAC | 27.84 | 0.00 | 01-JAN-00:10 | 43256.88 | 27-DEC-07:10 |
Heating:NaturalGas | 27.84 | 0.00 | 01-JAN-00:10 | 43256.88 | 27-DEC-07:10 |
General:Heating:NaturalGas | 27.84 | 0.00 | 01-JAN-00:10 | 43256.88 | 27-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 336.61 | 0.00 | 01-JAN-00:10 | 87130.75 | 15-JUN-16:10 |
EnergyTransfer:Building | 159.02 | 0.00 | 01-JAN-00:10 | 38877.98 | 15-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 52.02 | 0.00 | 01-JAN-00:10 | 16924.50 | 27-DEC-07:10 |
Heating:EnergyTransfer | 19.03 | 0.00 | 01-JAN-00:10 | 33651.98 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 7.55 | 0.00 | 01-JAN-00:10 | 16924.50 | 27-DEC-07:10 |
General:Heating:EnergyTransfer | 19.03 | 0.00 | 01-JAN-00:10 | 33651.98 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 7.55 | 0.00 | 01-JAN-00:10 | 16924.50 | 27-DEC-07:10 |
Cooling:EnergyTransfer | 139.98 | 0.00 | 01-JAN-00:10 | 38877.98 | 15-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 44.47 | 0.00 | 01-JAN-00:10 | 13032.93 | 05-JUN-17:00 |
General:Cooling:EnergyTransfer | 139.98 | 0.00 | 01-JAN-00:10 | 38877.98 | 15-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 44.47 | 0.00 | 01-JAN-00:10 | 13032.93 | 05-JUN-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 106.98 | 0.00 | 01-JAN-00:10 | 27330.88 | 15-JUN-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.47 | 0.00 | 01-JAN-00:10 | 19414.11 | 27-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.47 | 0.00 | 01-JAN-00:10 | 19414.11 | 27-DEC-06:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 95.51 | 0.00 | 01-JAN-00:10 | 27330.88 | 15-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 95.51 | 0.00 | 01-JAN-00:10 | 27330.88 | 15-JUN-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.02 | 0.00 | 01-JAN-00:10 | 11440.22 | 31-DEC-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.02 | 0.00 | 01-JAN-00:10 | 11440.22 | 31-DEC-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.02 | 0.00 | 01-JAN-00:10 | 11440.22 | 31-DEC-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 177.59 | 0.00 | 01-JAN-00:10 | 48252.77 | 15-JUN-16:10 |
HeatingCoils:EnergyTransfer | 18.71 | 0.00 | 01-JAN-00:10 | 31903.59 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 158.88 | 0.00 | 01-JAN-00:10 | 48252.77 | 15-JUN-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 7.549 | -44.469 | 0.000 | 0.000 | 9.599 | 15.542 | 31.946 | 11.754 | 0.000 | 3.302 | 0.000 | 0.000 | -6.565 | 0.000 | -13.487 | -15.171 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 11.469 | -95.511 | 0.000 | 0.000 | 21.973 | 43.933 | 0.000 | 81.033 | 0.000 | 5.410 | 0.002 | 0.000 | -17.232 | 0.000 | -32.044 | -19.032 |
ZONE3 BULK STORAGE | 0.016 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 47.126 | 44.338 | 107.344 | 800.145 | 0.000 | 51.435 | 0.021 | 0.000 | -144.175 | 0.000 | -315.006 | -591.223 |
Total Facility | 0.016 | 0.000 | 19.018 | -139.980 | 0.000 | 0.000 | 78.699 | 103.813 | 139.290 | 892.932 | 0.000 | 60.148 | 0.023 | 0.000 | -167.972 | 0.000 | -360.537 | -625.425 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | -26570.70 | 0.00 | 0.00 | 801.53 | 1027.40 | 1912.50 | 0.00 | 0.00 | 0.00 | 23172.70 | 0.00 | -343.43 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 04-JUL-16:42 | 0.00 | 0.00 | 0.00 | -53268.09 | 0.00 | 0.00 | 0.00 | 384.21 | 0.00 | 2757.73 | 0.00 | 475.15 | 49651.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUL-15:53 | 0.00 | 0.00 | 0.00 | -62691.19 | 0.00 | 0.00 | 0.00 | 847.71 | 573.75 | 73598.48 | 0.00 | 6913.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19241.80 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-JAN-07:01 | 0.00 | 0.00 | 28086.89 | 0.00 | 0.00 | 0.00 | 262.14 | 580.44 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -589.52 | 0.00 | -5731.45 | -23564.75 |
ZONE2 FINE STORAGE | 27-DEC-07:02 | 0.00 | 0.00 | 57618.49 | 0.00 | 0.00 | 0.00 | 692.42 | 3073.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1764.17 | 0.00 | -3651.89 | -55968.49 |
ZONE3 BULK STORAGE | 31-DEC-07:00 | 11440.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 24843.48 | 0.00 | -9935.44 | 0.00 | -26945.77 | 0.00 |
Total Facility | 27-DEC-07:02 | 0.00 | 0.00 | 85679.83 | 0.00 | 0.00 | 0.00 | 2685.34 | 7240.01 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19697.91 | 0.00 | -27027.65 | -51885.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2575 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2575 | 0.0813 | 1.0000 | Not calculated | 0.1023 | 0.0813 | ||
PSZ-FINE STORAGE | 2.8935 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8935 | 0.1468 | 1.0000 | Not calculated | 0.4247 | 0.1468 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2575 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2575 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0813 | ||
PSZ-FINE STORAGE | 2.8935 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.8935 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1468 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2575 | 1.2575 | 1.2575 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8935 | 2.8935 | 2.8935 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2575 | 1.2575 | 1.2575 | 1.2575 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8935 | 2.8935 | 2.8935 | 2.8935 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2575 | 1.2575 | 1.2575 | No | 0.1023 | 0.3227 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8935 | 2.8935 | 2.8935 | No | 0.4247 | 0.6322 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2575 | 1.2575 | 1.2575 | 1.2575 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.8935 | 2.8935 | 2.8935 | 2.8935 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 9.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 9.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 27.84 | 43256.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 40.97 | 14599.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 103.81 | 10483.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.86 | 5492.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 10.97 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 23.76 | 2958.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.10 | 1943.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 415.76 |
Natural Gas | 0.00 | 27.84 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 443.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 21.47 |
Space Heating | 0.00 |
Space Cooling | 8.47 |
Fans (All) | 7.18 |
Service Water Heating | 4.98 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 85.99 |
Subtotal | 85.99 |
Natural Gas [MJ/m2] | |
Space Heating | 5.76 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 5.76 |
Subtotal | 5.76 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.40 |
Space Heating | 6.28 |
Space Cooling | 9.24 |
Fans (All) | 7.83 |
Service Water Heating | 5.43 |
Receptacle Equipment | 31.40 |
Miscellaneous | 16.43 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2607. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7030.50 | 1729.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7676.67 | 1083.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5338.50 | 3278.17 | 143.33 | 0.00 | 0.00 |
Min | 5338.50 | 1083.33 | 0.00 | 0.00 | 0.00 |
Max | 7676.67 | 3278.17 | 143.33 | 0.00 | 0.00 |
Average | 6681.89 | 2030.33 | 47.78 | 0.00 | 0.00 |
Sum | 20045.67 | 6091.00 | 143.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 32960.00 | 67.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 68802.00 | 13917.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 113131.50 | 72143.17 | 5918.33 | 0.00 | 0.00 |
Min | 32960.00 | 67.00 | 0.00 | 0.00 | 0.00 |
Max | 113131.50 | 72143.17 | 5918.33 | 0.00 | 0.00 |
Average | 71631.17 | 28709.06 | 1972.78 | 0.00 | 0.00 |
Sum | 214893.50 | 86127.17 | 5918.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7403.17 | 1356.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7401.00 | 1359.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5864.67 | 2895.33 | 0.00 | 0.00 | 0.00 |
Min | 5864.67 | 1356.83 | 0.00 | 0.00 | 0.00 |
Max | 7403.17 | 2895.33 | 0.00 | 0.00 | 0.00 |
Average | 6889.61 | 1870.39 | 0.00 | 0.00 | 0.00 |
Sum | 20668.83 | 5611.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32803.67 | 223.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 66126.50 | 16592.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 122805.67 | 68387.33 | 0.00 | 0.00 | 0.00 |
Min | 32803.67 | 223.33 | 0.00 | 0.00 | 0.00 |
Max | 122805.67 | 68387.33 | 0.00 | 0.00 | 0.00 |
Average | 73911.94 | 28401.06 | 0.00 | 0.00 | 0.00 |
Sum | 221735.83 | 85203.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101625E+09 | 1928.72 | 07-JAN-08:05 | -0.1 | -3.5 | 0.507314E+09 | 759.18 | 12-JAN-16:10 | 18.72 | 10.12 |
February | 0.118395E+09 | 2028.25 | 03-FEB-08:05 | -2.0 | -5.0 | 0.480471E+09 | 768.96 | 21-FEB-16:49 | 22.30 | 7.87 |
March | 0.456663E+09 | 2903.14 | 16-MAR-15:40 | 22.40 | 8.49 | 0.604201E+09 | 768.96 | 22-MAR-14:39 | 24.07 | 8.96 |
April | 0.289800E+10 | 21520.44 | 29-APR-07:02 | 19.27 | 12.75 | 0.624028E+09 | 879.39 | 29-APR-07:10 | 19.27 | 12.75 |
May | 0.583787E+10 | 25554.34 | 06-MAY-07:02 | 13.95 | 4.76 | 0.663383E+09 | 879.39 | 27-MAY-07:10 | 19.68 | 11.99 |
June | 0.783413E+10 | 22526.20 | 17-JUN-06:01 | 23.07 | 14.92 | 0.666496E+09 | 879.41 | 17-JUN-07:10 | 24.78 | 15.73 |
July | 0.770961E+10 | 20717.76 | 11-JUL-06:02 | 22.07 | 15.44 | 0.641294E+09 | 879.43 | 26-JUL-07:10 | 27.07 | 18.18 |
August | 0.786190E+10 | 22602.88 | 26-AUG-06:02 | 21.78 | 13.24 | 0.692204E+09 | 879.41 | 24-AUG-07:10 | 21.78 | 13.24 |
September | 0.669122E+10 | 26572.67 | 30-SEP-07:02 | 13.03 | 8.20 | 0.639876E+09 | 879.40 | 13-SEP-07:10 | 13.03 | 8.20 |
October | 0.392904E+10 | 25213.96 | 07-OCT-07:02 | 10.68 | 9.06 | 0.633108E+09 | 879.39 | 02-OCT-07:10 | 10.68 | 9.06 |
November | 0.907427E+09 | 4420.57 | 03-NOV-16:00 | 23.90 | 13.45 | 0.556019E+09 | 768.99 | 03-NOV-12:00 | 23.90 | 13.45 |
December | 0.124601E+09 | 2099.79 | 19-DEC-08:05 | -2.3 | -6.1 | 0.505858E+09 | 730.90 | 16-DEC-16:10 | -2.3 | -6.1 |
Annual Sum or Average | 0.444705E+11 | 0.721425E+10 | ||||||||
Minimum of Months | 0.101625E+09 | 1928.72 | -2.3 | -6.1 | 0.480471E+09 | 730.90 | -2.3 | -6.1 | ||
Maximum of Months | 0.786190E+10 | 26572.67 | 23.90 | 15.44 | 0.692204E+09 | 879.43 | 27.07 | 18.18 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153295E+10 | 4699.88 | 05-JAN-09:20 | 2.43 | -3.5 | 0.826577E+09 | 1408.71 | 12-JAN-15:39 | 18.90 | 10.12 |
February | 0.116968E+10 | 5036.64 | 09-FEB-09:20 | 2.57 | -1.4 | 0.835777E+09 | 1616.50 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.122130E+10 | 5377.37 | 18-MAR-07:03 | 2.15 | -2.3 | 0.117692E+10 | 1891.40 | 16-MAR-15:09 | 2.15 | -2.3 |
April | 0.208569E+10 | 37192.30 | 30-APR-10:45 | 24.53 | 12.98 | 0.160446E+10 | 2246.82 | 29-APR-10:50 | 24.53 | 12.98 |
May | 0.102316E+11 | 51951.26 | 29-MAY-13:23 | 31.70 | 16.86 | 0.189037E+10 | 2246.92 | 24-MAY-13:00 | 31.70 | 16.86 |
June | 0.205558E+11 | 52614.49 | 25-JUN-12:43 | 30.40 | 17.09 | 0.192776E+10 | 2246.95 | 15-JUN-15:39 | 30.40 | 17.09 |
July | 0.204651E+11 | 53269.78 | 04-JUL-16:42 | 28.32 | 18.59 | 0.185459E+10 | 2247.01 | 26-JUL-14:30 | 36.70 | 20.46 |
August | 0.183882E+11 | 53106.87 | 13-AUG-16:03 | 31.60 | 18.60 | 0.200055E+10 | 2246.98 | 07-AUG-15:00 | 31.60 | 18.60 |
September | 0.129738E+11 | 52438.80 | 17-SEP-14:23 | 32.50 | 16.13 | 0.184406E+10 | 2246.94 | 14-SEP-12:30 | 32.50 | 16.13 |
October | 0.374626E+10 | 49405.84 | 01-OCT-15:23 | 32.25 | 15.71 | 0.169102E+10 | 2246.94 | 04-OCT-13:09 | 29.08 | 19.06 |
November | 0.151561E+10 | 5158.02 | 16-NOV-08:62 | 4.27 | 1.91 | 0.112930E+10 | 2131.51 | 03-NOV-15:09 | 4.27 | 1.91 |
December | 0.162850E+10 | 4929.71 | 19-DEC-09:40 | 1.87 | -3.7 | 0.810745E+09 | 1286.38 | 16-DEC-15:39 | 1.87 | -3.7 |
Annual Sum or Average | 0.955145E+11 | 0.175921E+11 | ||||||||
Minimum of Months | 0.116968E+10 | 4699.88 | 1.87 | -3.7 | 0.810745E+09 | 1286.38 | 1.87 | -3.7 | ||
Maximum of Months | 0.205558E+11 | 53269.78 | 32.50 | 18.60 | 0.200055E+10 | 2247.01 | 36.70 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.143198E+10 | 2757.06 | 03-JAN-15:20 | 20.40 | 8.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.137284E+10 | 2785.55 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.217783E+10 | 3450.61 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.324400E+10 | 5697.90 | 21-APR-15:20 | 31.83 | 15.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.494186E+10 | 8171.74 | 19-MAY-14:20 | 34.80 | 17.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 | 0.615262E+10 | 9097.65 | 02-JUN-13:39 | 37.43 | 15.47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 | 0.571037E+10 | 9097.65 | 01-JUL-14:30 | 37.20 | 19.55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.594143E+10 | 9054.47 | 07-AUG-15:00 | 37.20 | 17.89 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.526072E+10 | 7952.82 | 19-SEP-14:20 | 33.70 | 16.73 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.397267E+10 | 7381.04 | 03-OCT-14:20 | 32.43 | 19.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.231962E+10 | 4367.23 | 03-NOV-15:20 | 23.50 | 13.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.134856E+10 | 2181.88 | 01-DEC-14:20 | 14.03 | 6.35 |
Annual Sum or Average | 0.00 | 0.438745E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.134856E+10 | 2181.88 | 14.03 | 6.35 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.615262E+10 | 9097.65 | 37.43 | 19.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213345E+10 | 28087.31 | 13-JAN-07:01 | 3.35 |
February | 0.150806E+10 | 28048.96 | 02-FEB-07:02 | -4.0 |
March | 0.837451E+09 | 27988.75 | 02-MAR-07:02 | -1.6 |
April | 92073163.21 | 11521.75 | 12-APR-07:03 | 7.35 |
May | 39070091.55 | 1105.20 | 31-MAY-06:04 | 23.58 |
June | 16065490.12 | 1168.43 | 22-JUN-06:04 | 21.10 |
July | 10544423.39 | 1189.58 | 05-JUL-06:04 | 18.07 |
August | 18212362.44 | 1209.86 | 23-AUG-06:04 | 20.28 |
September | 28049834.00 | 1239.62 | 20-SEP-06:04 | 18.03 |
October | 52824537.18 | 1178.01 | 05-OCT-06:05 | 19.60 |
November | 0.563560E+09 | 27907.33 | 21-NOV-07:01 | 2.57 |
December | 0.224939E+10 | 28061.83 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.754875E+10 | |||
Minimum of Months | 10544423.39 | 1105.20 | -4.3 | |
Maximum of Months | 0.224939E+10 | 28087.31 | 23.58 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318160E+10 | 55397.63 | 27-JAN-06:43 | -4.1 |
February | 0.193301E+10 | 53947.32 | 01-FEB-06:01 | -0.8 |
March | 0.786282E+09 | 54763.62 | 02-MAR-06:01 | -3.5 |
April | 0.270380E+09 | 3138.23 | 01-APR-17:00 | 28.90 |
May | 81469281.14 | 1218.37 | 01-MAY-07:00 | 15.00 |
June | 17761842.70 | 1570.32 | 08-JUN-06:03 | 25.78 |
July | 6839506.03 | 1696.58 | 27-JUL-06:03 | 23.90 |
August | 31880732.22 | 1672.12 | 05-AUG-06:03 | 23.98 |
September | 63636968.64 | 1297.17 | 23-SEP-06:03 | 21.20 |
October | 97966054.87 | 1385.88 | 13-OCT-07:00 | 14.40 |
November | 0.388803E+09 | 41019.67 | 28-NOV-05:13 | -0.0 |
December | 0.460951E+10 | 57618.48 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.114691E+11 | |||
Minimum of Months | 6839506.03 | 1218.37 | -4.3 | |
Maximum of Months | 0.460951E+10 | 57618.48 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 16060928.59 | 11440.22 | 31-DEC-07:00 | -2.8 |
Annual Sum or Average | 16060928.59 | |||
Minimum of Months | 0.00 | 0.00 | -2.8 | |
Maximum of Months | 16060928.59 | 11440.22 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132505E+10 | 1059.02 | 17-JAN-16:00 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.119919E+10 | 1047.47 | 23-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.134961E+10 | 1047.12 | 10-MAR-16:00 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.126710E+10 | 1035.45 | 20-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.130524E+10 | 1014.32 | 03-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.128798E+10 | 996.53 | 26-JUN-10:30 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.128492E+10 | 1033.68 | 07-JUL-07:30 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.134150E+10 | 1033.25 | 17-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.127432E+10 | 1029.20 | 29-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.130430E+10 | 1053.85 | 13-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.127496E+10 | 1064.14 | 17-NOV-16:00 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.132767E+10 | 1064.14 | 01-DEC-16:00 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.155418E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.119919E+10 | 996.53 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.134961E+10 | 1064.14 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.407928E+10 | 4354.33 | 02-JAN-15:09 | 0.00 | 0.00 |
February | 0.357265E+10 | 4354.33 | 01-FEB-15:00 | 0.00 | 0.00 |
March | 0.380918E+10 | 4354.33 | 17-MAR-08:09 | 0.00 | 0.00 |
April | 0.338359E+10 | 3842.06 | 01-APR-07:10 | 0.00 | 0.00 |
May | 0.339136E+10 | 3628.61 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.338643E+10 | 3628.61 | 10-JUN-08:09 | 0.00 | 0.00 |
July | 0.334572E+10 | 3991.47 | 07-JUL-08:09 | 0.00 | 0.00 |
August | 0.355232E+10 | 3991.47 | 24-AUG-08:09 | 0.00 | 0.00 |
September | 0.358531E+10 | 3991.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.375390E+10 | 3991.47 | 14-OCT-08:09 | 0.00 | 0.00 |
November | 0.394933E+10 | 4354.33 | 03-NOV-08:09 | 0.00 | 0.00 |
December | 0.412412E+10 | 4354.33 | 01-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439332E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.334572E+10 | 3628.61 | 0.00 | 0.00 | |
Maximum of Months | 0.412412E+10 | 4354.33 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.414048E+10 | 4656.71 | 02-JAN-15:30 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.356313E+10 | 4656.71 | 04-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.385540E+10 | 4108.86 | 01-MAR-16:49 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.341612E+10 | 3735.33 | 20-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.345384E+10 | 3585.92 | 03-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.339256E+10 | 2988.26 | 01-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.338001E+10 | 3386.70 | 07-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.360840E+10 | 3585.92 | 14-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.361244E+10 | 3735.33 | 01-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.379693E+10 | 4482.40 | 13-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.395612E+10 | 5080.05 | 20-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.416213E+10 | 5080.05 | 02-DEC-15:50 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.443376E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.338001E+10 | 2988.26 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.416213E+10 | 5080.05 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.132505E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214474E+10 |
February | 0.127628E+10 | 0.119919E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2345885.50 | 0.177314E+10 |
March | 0.149825E+10 | 0.134961E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3347810.39 | 0.175230E+10 |
April | 0.138726E+10 | 0.126710E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192801E+09 | 0.100779E+10 |
May | 0.144276E+10 | 0.130524E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471059E+09 | 0.595051E+09 |
June | 0.144276E+10 | 0.128798E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898037E+09 | 0.278203E+09 |
July | 0.138726E+10 | 0.128492E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688854E+09 | 0.227409E+09 |
August | 0.149825E+10 | 0.134150E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593026E+09 | 0.343968E+09 |
September | 0.138726E+10 | 0.127432E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367712E+09 | 0.426295E+09 |
October | 0.138726E+10 | 0.130430E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84857583.96 | 0.105354E+10 |
November | 0.133177E+10 | 0.127496E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174022E+10 |
December | 0.138726E+10 | 0.132767E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214419E+10 |
Annual Sum or Average | 0.168137E+11 | 0.155418E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330204E+10 | 0.134869E+11 |
Minimum of Months | 0.127628E+10 | 0.119919E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227409E+09 |
Maximum of Months | 0.149825E+10 | 0.134961E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898037E+09 | 0.214474E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.407928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1305662.93 | 0.429166E+10 |
February | 0.300332E+10 | 0.357265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39188955.92 | 0.367123E+10 |
March | 0.352563E+10 | 0.380918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33880108.73 | 0.390656E+10 |
April | 0.326447E+10 | 0.338359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307527E+09 | 0.312063E+10 |
May | 0.339505E+10 | 0.339136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822136E+09 | 0.215582E+10 |
June | 0.339505E+10 | 0.338643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169210E+10 | 0.846654E+09 |
July | 0.326447E+10 | 0.334572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122480E+10 | 0.689244E+09 |
August | 0.352563E+10 | 0.355232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960954E+09 | 0.961246E+09 |
September | 0.326447E+10 | 0.358531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259390E+09 | 0.113572E+10 |
October | 0.326447E+10 | 0.375390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69080493.14 | 0.324870E+10 |
November | 0.313390E+10 | 0.394933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31442.09 | 0.415206E+10 |
December | 0.326447E+10 | 0.412412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386490E+10 |
Annual Sum or Average | 0.395654E+11 | 0.439332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541040E+10 | 0.320444E+11 |
Minimum of Months | 0.300332E+10 | 0.334572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689244E+09 |
Maximum of Months | 0.352563E+10 | 0.412412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169210E+10 | 0.429166E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.414048E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105688E+09 | 0.167087E+11 |
February | 0.690763E+10 | 0.356313E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160155E+10 | 0.131263E+11 |
March | 0.810895E+10 | 0.385540E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188631E+10 | 0.154508E+11 |
April | 0.750829E+10 | 0.341612E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367243E+10 | 0.134207E+11 |
May | 0.780862E+10 | 0.345384E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814613E+09 | 0.130239E+11 |
June | 0.780862E+10 | 0.339256E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585422E+09 | 0.814215E+10 |
July | 0.750829E+10 | 0.338001E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311048E+09 | 0.715839E+10 |
August | 0.810895E+10 | 0.360840E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190300E+09 | 0.857820E+10 |
September | 0.750829E+10 | 0.361244E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33438085.53 | 0.888403E+10 |
October | 0.750829E+10 | 0.379693E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66401336.84 | 0.181037E+11 |
November | 0.720796E+10 | 0.395612E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44904880.81 | 0.192601E+11 |
December | 0.750829E+10 | 0.416213E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124138E+09 | 0.146646E+11 |
Annual Sum or Average | 0.910005E+11 | 0.443376E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943625E+10 | 0.156521E+12 |
Minimum of Months | 0.690763E+10 | 0.338001E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33438085.53 | 0.715839E+10 |
Maximum of Months | 0.810895E+10 | 0.416213E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367243E+10 | 0.192601E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1059.02 | 17-JAN-16:00 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 9297.55 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1047.47 | 23-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.49 | 19-FEB-14:00 | 8876.98 | 02-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1047.12 | 10-MAR-16:00 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 371.38 | 21-MAR-16:10 | 7982.36 | 02-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1035.45 | 20-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.76 | 21-APR-16:10 | 5619.16 | 12-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1014.32 | 03-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4145.26 | 19-MAY-17:00 | 4874.09 | 02-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 996.53 | 26-JUN-10:30 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5427.59 | 05-JUN-17:00 | 2932.88 | 29-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1033.68 | 07-JUL-07:30 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5260.22 | 03-JUL-17:00 | 2825.74 | 05-JUL-06:02 |
August | 1680.92 | 01-AUG-07:10 | 1033.25 | 17-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4636.58 | 07-AUG-16:10 | 3110.73 | 31-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1029.20 | 29-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.41 | 19-SEP-16:10 | 4866.10 | 25-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1053.85 | 13-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2453.96 | 05-OCT-16:10 | 5526.52 | 25-OCT-06:03 |
November | 1680.92 | 01-NOV-07:10 | 1064.14 | 17-NOV-16:00 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7387.82 | 28-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 1064.14 | 01-DEC-16:00 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8848.68 | 27-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 996.53 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2825.74 | |||||
Maximum of Months | 1680.92 | 1064.14 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5427.59 | 9297.55 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 4354.33 | 02-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.59 | 03-JAN-17:10 | 8478.58 | 25-JAN-23:27 |
February | 3955.50 | 01-FEB-08:09 | 4354.33 | 01-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939.12 | 20-FEB-16:00 | 12465.86 | 08-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 4354.33 | 17-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.88 | 03-MAR-16:10 | 10260.75 | 27-MAR-07:00 |
April | 3955.50 | 01-APR-07:10 | 3842.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5701.40 | 21-APR-15:10 | 12600.98 | 22-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3628.61 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.98 | 19-MAY-17:00 | 5943.07 | 01-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3628.61 | 10-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7023.16 | 05-JUN-17:00 | 5091.43 | 28-JUN-02:00 |
July | 3955.50 | 01-JUL-07:10 | 3991.47 | 07-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5589.03 | 03-JUL-17:00 | 3431.41 | 18-JUL-21:00 |
August | 3955.50 | 01-AUG-07:10 | 3991.47 | 24-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4864.08 | 26-AUG-15:10 | 4145.18 | 14-AUG-01:00 |
September | 3955.50 | 01-SEP-07:10 | 3991.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1608.02 | 18-SEP-17:00 | 3543.99 | 23-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 3991.47 | 14-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.60 | 01-OCT-15:00 | 6359.49 | 23-OCT-18:00 |
November | 3955.50 | 01-NOV-07:10 | 4354.33 | 03-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 23-NOV-16:00 | 7001.78 | 15-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 4354.33 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9800.82 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3431.41 | ||||
Maximum of Months | 3955.50 | 4354.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7023.16 | 12600.98 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4656.71 | 02-JAN-15:30 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7426.67 | 03-JAN-17:00 | 26806.65 | 05-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 4656.71 | 04-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12905.61 | 06-FEB-13:10 | 39117.47 | 09-FEB-00:55 |
March | 9097.65 | 01-MAR-08:09 | 4108.86 | 01-MAR-16:49 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21756.07 | 03-MAR-16:00 | 40726.56 | 27-MAR-07:03 |
April | 9097.65 | 01-APR-07:10 | 3735.33 | 20-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25501.28 | 01-APR-15:00 | 52393.54 | 22-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 3585.92 | 03-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10463.91 | 08-MAY-15:00 | 27580.31 | 01-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 2988.26 | 01-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3726.33 | 05-JUN-17:00 | 29594.89 | 28-JUN-02:00 |
July | 9097.65 | 01-JUL-07:10 | 3386.70 | 07-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2898.27 | 03-JUL-17:00 | 21110.18 | 08-JUL-15:00 |
August | 9097.65 | 01-AUG-07:10 | 3585.92 | 14-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2898.35 | 07-AUG-16:00 | 23903.34 | 14-AUG-01:00 |
September | 9097.65 | 01-SEP-07:10 | 3735.33 | 01-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.34 | 10-SEP-14:53 | 17050.16 | 23-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 4482.40 | 13-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3900.67 | 18-OCT-16:00 | 37595.57 | 06-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 5080.05 | 20-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2307.56 | 23-NOV-16:00 | 30494.65 | 15-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 5080.05 | 02-DEC-15:50 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4396.62 | 10-DEC-15:00 | 33203.65 | 18-DEC-08:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2988.26 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 925.34 | 17050.16 | |||||
Maximum of Months | 9097.65 | 5080.05 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 25501.28 | 52393.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1928.72 | 07-JAN-08:05 | 6723.69 | 4147.12 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.83 |
February | 2028.25 | 03-FEB-08:05 | 6723.69 | 4169.41 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.80 |
March | 2903.14 | 16-MAR-15:40 | 1680.92 | 865.35 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.02 |
April | 21520.44 | 29-APR-07:02 | 8404.61 | 4894.16 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.00 |
May | 25554.34 | 06-MAY-07:02 | 8404.61 | 4919.45 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 |
June | 22526.20 | 17-JUN-06:01 | 2470.96 | 3821.13 | 6693.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.88 |
July | 20717.76 | 11-JUL-06:02 | 2117.96 | 3306.15 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.19 |
August | 22602.88 | 26-AUG-06:02 | 1764.97 | 2801.35 | 4781.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26572.67 | 30-SEP-07:02 | 8404.61 | 5137.01 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25213.96 | 07-OCT-07:02 | 8404.61 | 5169.87 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.17 |
November | 4420.57 | 03-NOV-16:00 | 1680.92 | 878.87 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 2099.79 | 19-DEC-08:05 | 6723.69 | 4111.86 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1928.72 | 1680.92 | 865.35 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26572.67 | 8404.61 | 5169.87 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4699.88 | 05-JAN-09:20 | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2091.43 |
February | 5036.64 | 09-FEB-09:20 | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.19 |
March | 5377.37 | 18-MAR-07:03 | 15822.00 | 14087.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.78 |
April | 37192.30 | 30-APR-10:45 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 |
May | 51951.26 | 29-MAY-13:23 | 0.00 | 896.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.64 | 0.00 |
June | 52614.49 | 25-JUN-12:43 | 0.00 | 896.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.59 | 0.00 |
July | 53269.78 | 04-JUL-16:42 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.15 | 0.00 |
August | 53106.87 | 13-AUG-16:03 | 0.00 | 1536.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.82 | 0.00 |
September | 52438.80 | 17-SEP-14:23 | 0.00 | 1366.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.43 | 0.00 |
October | 49405.84 | 01-OCT-15:23 | 0.00 | 1024.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1573.77 | 0.00 |
November | 5158.02 | 16-NOV-08:62 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.03 |
December | 4929.71 | 19-DEC-09:40 | 3955.50 | 3628.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4699.88 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53269.78 | 15822.00 | 15368.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.64 | 3124.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7900.42 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12472.94 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8675.67 |
April | 0.00 | 01-APR-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3900.34 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3216.09 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7342.96 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.24 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2060.33 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7589.56 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3234.62 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10781.43 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4041.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 597.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.24 | |
Maximum of Months | 0.00 | 0.00 | 597.65 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12472.94 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.325256E+11 | 23652.62 | 26-JAN-15:00 | 0.846121E+10 | 39607.30 | 27-JAN-07:10 |
February | 0.288411E+11 | 23212.35 | 04-FEB-15:00 | 0.505178E+10 | 40032.12 | 02-FEB-07:10 |
March | 0.318426E+11 | 22768.27 | 17-MAR-08:09 | 0.193133E+10 | 31034.35 | 02-MAR-07:10 |
April | 0.299577E+11 | 25633.97 | 21-APR-15:09 | 60567799.19 | 5399.16 | 12-APR-06:10 |
May | 0.349967E+11 | 32501.91 | 19-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.412217E+11 | 37391.86 | 15-JUN-15:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.415815E+11 | 35105.16 | 26-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.414214E+11 | 35030.06 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.370946E+11 | 33185.06 | 05-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.325388E+11 | 32288.34 | 05-OCT-15:00 | 429685.09 | 716.14 | 25-OCT-07:10 |
November | 0.309839E+11 | 28425.77 | 28-NOV-16:00 | 0.128617E+10 | 26521.72 | 28-NOV-07:10 |
December | 0.327516E+11 | 28411.05 | 18-DEC-16:00 | 0.110460E+11 | 43256.88 | 27-DEC-07:10 |
Annual Sum or Average | 0.415757E+12 | 0.278375E+11 | ||||
Minimum of Months | 0.288411E+11 | 22768.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.415815E+11 | 37391.86 | 0.110460E+11 | 43256.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.954481E+10 | 0.733575E+10 | 0.115358E+11 | 0.00 | 0.196406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214521E+10 | 0.00 |
February | 0.833498E+10 | 0.622080E+10 | 0.105871E+11 | 0.00 | 0.174749E+10 | 0.00 | 0.00 | 2028683.62 | 0.00 | 0.00 | 0.00 | 0.194865E+10 | 0.00 |
March | 0.901419E+10 | 0.631083E+10 | 0.123431E+11 | 0.00 | 0.196139E+10 | 0.00 | 0.00 | 44483771.13 | 0.00 | 0.00 | 0.00 | 0.216868E+10 | 0.00 |
April | 0.806681E+10 | 0.552723E+10 | 0.114862E+11 | 0.00 | 0.178911E+10 | 0.00 | 0.00 | 0.107622E+10 | 0.00 | 0.00 | 0.00 | 0.201214E+10 | 0.00 |
May | 0.815043E+10 | 0.521341E+10 | 0.119357E+11 | 0.00 | 0.302249E+10 | 0.00 | 0.00 | 0.465359E+10 | 0.00 | 0.00 | 0.00 | 0.202101E+10 | 0.00 |
June | 0.806697E+10 | 0.479562E+10 | 0.118862E+11 | 0.00 | 0.538968E+10 | 0.00 | 0.00 | 0.916215E+10 | 0.00 | 0.00 | 0.00 | 0.192111E+10 | 0.00 |
July | 0.801064E+10 | 0.506511E+10 | 0.115358E+11 | 0.00 | 0.518537E+10 | 0.00 | 0.00 | 0.987054E+10 | 0.00 | 0.00 | 0.00 | 0.191407E+10 | 0.00 |
August | 0.850222E+10 | 0.549023E+10 | 0.123357E+11 | 0.00 | 0.470293E+10 | 0.00 | 0.00 | 0.843324E+10 | 0.00 | 0.00 | 0.00 | 0.195709E+10 | 0.00 |
September | 0.847206E+10 | 0.585020E+10 | 0.114788E+11 | 0.00 | 0.323624E+10 | 0.00 | 0.00 | 0.615570E+10 | 0.00 | 0.00 | 0.00 | 0.190160E+10 | 0.00 |
October | 0.885513E+10 | 0.665027E+10 | 0.115432E+11 | 0.00 | 0.197208E+10 | 0.00 | 0.00 | 0.151915E+10 | 0.00 | 0.00 | 0.00 | 0.199897E+10 | 0.00 |
November | 0.918040E+10 | 0.694103E+10 | 0.110862E+11 | 0.00 | 0.173379E+10 | 0.00 | 0.00 | 51661401.95 | 0.00 | 0.00 | 0.00 | 0.199074E+10 | 0.00 |
December | 0.961392E+10 | 0.746098E+10 | 0.115358E+11 | 0.00 | 0.202430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211665E+10 | 0.00 |
Annual Sum or Average | 0.103813E+12 | 0.728615E+11 | 0.139290E+12 | 0.00 | 0.347289E+11 | 0.00 | 0.00 | 0.409688E+11 | 0.00 | 0.00 | 0.00 | 0.240959E+11 | 0.00 |
Minimum of Months | 0.801064E+10 | 0.479562E+10 | 0.105871E+11 | 0.00 | 0.173379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190160E+10 | 0.00 |
Maximum of Months | 0.961392E+10 | 0.746098E+10 | 0.123431E+11 | 0.00 | 0.538968E+10 | 0.00 | 0.00 | 0.987054E+10 | 0.00 | 0.00 | 0.00 | 0.216868E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.846121E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.505178E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193133E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 60567799.19 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 429685.09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.128617E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.110460E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.278375E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.110460E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9949.10 | 26-JAN-15:00 | 5492.60 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2551.68 | 27-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9947.56 | 04-FEB-15:00 | 5492.60 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2574.50 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9180.90 | 17-MAR-08:09 | 5492.60 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2407.32 | 02-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8292.66 | 20-APR-07:10 | 5492.60 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 1962.43 | 29-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7234.88 | 03-MAY-06:10 | 5492.60 | 01-MAY-05:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4398.23 | 19-MAY-16:49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7492.94 | 26-JUN-07:10 | 5492.60 | 01-JUN-19:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 5263.93 | 15-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8406.44 | 07-JUL-08:09 | 5492.60 | 01-JUL-19:19 | 10112.62 | 01-JUL-07:10 | 0.00 | 4607.02 | 26-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8409.39 | 24-AUG-08:09 | 5492.60 | 01-AUG-05:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 4842.02 | 07-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8606.59 | 29-SEP-07:10 | 5492.60 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 4360.99 | 18-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 9378.31 | 13-OCT-07:10 | 5492.60 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4225.34 | 05-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10324.74 | 24-NOV-15:00 | 5492.60 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2318.72 | 28-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 10483.51 | 02-DEC-15:00 | 5492.60 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2632.45 | 27-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7234.88 | 5492.60 | 10112.62 | 0.00 | 1962.43 | 0.00 | 0.00 | |||||
Maximum of Months | 10483.51 | 5492.60 | 10112.62 | 0.00 | 5263.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1920.16 | 12-JAN-12:00 | 0.00 |
February | 174.39 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1943.07 | 08-FEB-12:00 | 0.00 |
March | 841.02 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 1810.33 | 01-MAR-12:00 | 0.00 |
April | 7110.55 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1790.94 | 01-APR-11:09 | 0.00 |
May | 10233.98 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1765.47 | 01-MAY-11:09 | 0.00 |
June | 14599.76 | 15-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1741.23 | 01-JUN-11:50 | 0.00 |
July | 12706.26 | 26-JUL-14:30 | 0.00 | 0.00 | 0.00 | 1724.30 | 01-JUL-11:39 | 0.00 |
August | 13270.74 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1724.49 | 31-AUG-11:39 | 0.00 |
September | 10002.39 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1741.54 | 30-SEP-11:39 | 0.00 |
October | 9064.78 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1766.42 | 31-OCT-11:50 | 0.00 |
November | 1178.78 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1791.67 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1846.11 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1724.30 | 0.00 | ||
Maximum of Months | 14599.76 | 0.00 | 0.00 | 0.00 | 1943.07 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23652.62 | 26-JAN-15:00 | 9949.10 | 10112.62 | 0.00 | 0.00 | 1813.71 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23212.35 | 04-FEB-15:00 | 9947.56 | 10112.62 | 0.00 | 0.00 | 1795.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22768.27 | 17-MAR-08:09 | 9180.90 | 10112.62 | 0.00 | 0.00 | 1811.01 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25633.97 | 21-APR-15:09 | 5018.86 | 10112.62 | 0.00 | 0.00 | 1795.36 | 0.00 | 0.00 | 7110.55 | 0.00 |
May | 32501.91 | 19-MAY-15:00 | 6352.91 | 10112.62 | 0.00 | 0.00 | 4269.82 | 0.00 | 0.00 | 10175.80 | 0.00 |
June | 37391.86 | 15-JUN-15:39 | 6044.89 | 10112.62 | 0.00 | 0.00 | 5168.88 | 0.00 | 0.00 | 14479.49 | 0.00 |
July | 35105.16 | 26-JUL-14:30 | 5986.42 | 10112.62 | 0.00 | 0.00 | 4607.02 | 0.00 | 0.00 | 12706.26 | 0.00 |
August | 35030.06 | 07-AUG-15:00 | 6352.91 | 10112.62 | 0.00 | 0.00 | 4810.79 | 0.00 | 0.00 | 13270.74 | 0.00 |
September | 33185.06 | 05-SEP-14:00 | 7521.04 | 10112.62 | 0.00 | 0.00 | 4271.97 | 0.00 | 0.00 | 9579.60 | 0.00 |
October | 32288.34 | 05-OCT-15:00 | 7750.96 | 10112.62 | 0.00 | 0.00 | 4212.81 | 0.00 | 0.00 | 8630.74 | 0.00 |
November | 28425.77 | 28-NOV-16:00 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 1831.09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28411.05 | 18-DEC-16:00 | 9388.60 | 10112.62 | 5492.60 | 0.00 | 1813.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22768.27 | 5018.86 | 10112.62 | 0.00 | 0.00 | 1795.36 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37391.86 | 9949.10 | 10112.62 | 5492.60 | 0.00 | 5168.88 | 0.00 | 0.00 | 14479.49 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 39607.30 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 40032.12 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 31034.35 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 5399.16 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 716.14 | 25-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 26521.72 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 43256.88 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 43256.88 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 17.14 | 1.50 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 1.17 | 17.09 | 1.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
March | 0.50 | 17.14 | 0.50 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.96 | 0.00 | 29.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 29.97 | 0.00 | 29.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30.03 | 0.00 | 30.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.96 | 0.00 | 29.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 17.08 | 1.50 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
Annual Sum or Average | 4.67 | 17.11 | 4.67 | 17.11 | 1.17 | 18.54 | 0.00 | 18.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 17.14 | 1.50 | 17.14 | 0.50 | 30.03 | 0.00 | 30.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 14.91 | 1.67 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
February | 6.83 | 14.90 | 1.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 1.83 | 14.93 | 0.33 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.33 | 0.00 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.49 | 0.00 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.57 | 0.00 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.56 | 0.00 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.54 | 0.00 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.49 | 0.00 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.40 | 0.00 | 27.40 |
November | 0.83 | 14.95 | 0.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 19.67 | 14.90 | 2.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 42.33 | 14.91 | 6.00 | 14.90 | 112.83 | 23.75 | 0.00 | 23.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 | 14.89 |
Maximum of Months | 19.67 | 14.95 | 2.50 | 14.95 | 33.67 | 27.57 | 0.00 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.96 | 262.50 | 20.86 | 262.50 | 20.82 |
February | 276.00 | 21.25 | 203.17 | 21.01 | 203.17 | 20.92 |
March | 324.00 | 22.00 | 150.67 | 21.54 | 150.67 | 21.30 |
April | 217.17 | 23.38 | 37.00 | 23.30 | 12.67 | 23.17 |
May | 42.17 | 23.82 | 192.83 | 24.17 | 0.00 | 24.17 |
June | 4.00 | 27.76 | 298.50 | 24.38 | 4.00 | 24.42 |
July | 63.17 | 25.66 | 300.00 | 24.58 | 63.17 | 24.74 |
August | 30.83 | 26.37 | 324.00 | 24.50 | 30.83 | 24.65 |
September | 18.67 | 25.47 | 288.67 | 24.34 | 18.67 | 24.40 |
October | 87.33 | 23.61 | 125.50 | 23.89 | 4.50 | 23.92 |
November | 274.50 | 22.34 | 90.83 | 21.90 | 90.83 | 21.63 |
December | 300.00 | 20.93 | 262.17 | 20.84 | 262.17 | 20.80 |
Annual Sum or Average | 1937.83 | 22.12 | 2535.83 | 22.55 | 1103.17 | 22.30 |
Minimum of Months | 4.00 | 20.93 | 37.00 | 20.84 | 0.00 | 20.80 |
Maximum of Months | 324.00 | 27.76 | 324.00 | 24.58 | 262.50 | 24.74 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 17.34 | 300.00 | 17.34 | 300.00 | 17.34 |
February | 276.00 | 18.14 | 261.17 | 18.03 | 261.17 | 18.00 |
March | 324.00 | 19.94 | 210.50 | 19.43 | 210.50 | 19.21 |
April | 144.83 | 22.74 | 146.83 | 24.12 | 24.00 | 23.87 |
May | 128.83 | 26.25 | 277.67 | 26.45 | 110.00 | 26.51 |
June | 233.83 | 26.70 | 312.00 | 26.69 | 233.83 | 26.69 |
July | 289.67 | 26.71 | 300.00 | 26.71 | 289.67 | 26.71 |
August | 289.50 | 26.69 | 324.00 | 26.68 | 289.50 | 26.68 |
September | 214.17 | 26.70 | 295.00 | 26.63 | 214.17 | 26.65 |
October | 123.83 | 24.36 | 204.50 | 25.51 | 48.83 | 25.64 |
November | 269.00 | 20.39 | 143.00 | 19.86 | 134.17 | 19.51 |
December | 300.00 | 17.16 | 300.00 | 17.16 | 300.00 | 17.16 |
Annual Sum or Average | 2893.67 | 22.26 | 3074.67 | 22.68 | 2415.83 | 22.54 |
Minimum of Months | 123.83 | 17.16 | 143.00 | 17.16 | 24.00 | 17.16 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.71 | 300.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 14.90 | 300.00 | 14.90 | 300.00 | 14.90 |
February | 276.00 | 15.20 | 276.00 | 15.20 | 276.00 | 15.20 |
March | 324.00 | 17.86 | 324.00 | 17.86 | 324.00 | 17.86 |
April | 238.67 | 22.10 | 95.00 | 22.26 | 55.00 | 21.92 |
May | 216.50 | 28.75 | 261.33 | 28.72 | 188.83 | 28.95 |
June | 312.00 | 31.32 | 312.00 | 31.32 | 312.00 | 31.32 |
July | 300.00 | 30.83 | 300.00 | 30.83 | 300.00 | 30.83 |
August | 324.00 | 30.26 | 324.00 | 30.26 | 324.00 | 30.26 |
September | 292.00 | 29.64 | 300.00 | 29.60 | 292.00 | 29.61 |
October | 136.83 | 25.52 | 182.00 | 26.22 | 57.83 | 26.61 |
November | 286.17 | 19.56 | 191.17 | 19.06 | 191.17 | 18.84 |
December | 300.00 | 14.43 | 300.00 | 14.43 | 300.00 | 14.43 |
Annual Sum or Average | 3306.17 | 23.24 | 3165.50 | 23.39 | 2920.83 | 23.36 |
Minimum of Months | 136.83 | 14.43 | 95.00 | 14.43 | 55.00 | 14.43 |
Maximum of Months | 324.00 | 31.32 | 324.00 | 31.32 | 324.00 | 31.32 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 7964057.56 | 2028683.62 | 6.67 | 7964057.56 | -0.0 | 0.00 | 0.08 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 687.02 | 21-FEB-16:00 | 687.02 | 21-FEB-16:00 | 0.00 | 21-FEB-16:10 | 174.39 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.178930E+09 | 44483771.13 | 37.67 | 0.178930E+09 | 0.00 | 0.00 | 0.38 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 3396.45 | 21-MAR-16:00 | 3396.45 | 21-MAR-16:00 | 0.00 | 14-MAR-15:00 | 841.02 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.256377E+10 | 0.640247E+09 | 171.41 | 0.254846E+10 | 15317056.10 | 0.00 | 1.00 | 20-APR-07:03 | 0.00 | 01-APR-00:10 | 20395.63 | 29-APR-07:02 | 18507.86 | 29-APR-07:02 | 1887.77 | 29-APR-07:02 | 4453.07 | 29-APR-07:02 | 0.00 | 01-APR-00:10 |
May | 0.644094E+10 | 0.159110E+10 | 256.24 | 0.621666E+10 | 0.224280E+09 | 0.00 | 1.00 | 06-MAY-07:02 | 0.00 | 01-MAY-00:10 | 22146.93 | 23-MAY-07:02 | 20542.25 | 30-MAY-06:02 | 6944.94 | 24-MAY-07:03 | 4816.25 | 23-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.947170E+10 | 0.245921E+10 | 284.13 | 0.898834E+10 | 0.483362E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 22533.94 | 19-JUN-07:02 | 21227.68 | 03-JUN-06:02 | 8676.00 | 28-JUN-07:02 | 4934.68 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.108211E+11 | 0.265974E+10 | 280.15 | 0.878503E+10 | 0.203611E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:10 | 26268.66 | 21-JUL-07:02 | 21566.02 | 03-JUL-06:02 | 15917.42 | 21-JUL-07:02 | 5482.41 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.101550E+11 | 0.248064E+10 | 295.56 | 0.862875E+10 | 0.152630E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 25275.37 | 03-AUG-07:02 | 20840.11 | 24-AUG-06:01 | 11673.23 | 03-AUG-07:04 | 5345.02 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.837256E+10 | 0.200908E+10 | 258.98 | 0.719552E+10 | 0.117705E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 24337.18 | 23-SEP-07:02 | 21510.29 | 04-SEP-17:13 | 11903.81 | 14-SEP-07:02 | 5378.08 | 03-SEP-15:18 | 0.00 | 01-SEP-00:10 |
October | 0.337040E+10 | 0.802370E+09 | 178.78 | 0.299299E+10 | 0.377405E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 23021.19 | 04-OCT-07:02 | 19857.37 | 02-OCT-06:02 | 9242.98 | 04-OCT-07:02 | 4979.01 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.211302E+09 | 51661401.95 | 32.50 | 0.207988E+09 | 3313314.70 | 0.00 | 0.53 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 4973.76 | 03-NOV-16:00 | 4973.76 | 03-NOV-16:00 | 257.72 | 03-NOV-13:00 | 1178.78 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.515938E+11 | 0.127406E+11 | 1802.09 | 0.457506E+11 | 0.584313E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.108211E+11 | 0.265974E+10 | 295.56 | 0.898834E+10 | 0.203611E+10 | 0.00 | 1.00 | 0.00 | 26268.66 | 21566.02 | 15917.42 | 5482.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.158882E+10 | 0.435976E+09 | 73.56 | 0.158690E+10 | 1921925.99 | 0.00 | 1.00 | 21-APR-17:10 | 0.00 | 01-APR-00:10 | 57443.34 | 30-APR-10:45 | 57443.34 | 30-APR-10:45 | 242.79 | 29-APR-10:40 | 13293.05 | 30-APR-11:41 | 0.00 | 01-APR-00:10 |
May | 0.114692E+11 | 0.306248E+10 | 258.81 | 0.111425E+11 | 0.326635E+09 | 0.00 | 1.00 | 07-MAY-12:35 | 0.00 | 01-MAY-00:10 | 64454.96 | 28-MAY-09:15 | 58505.35 | 18-MAY-19:15 | 17336.07 | 28-MAY-09:15 | 14945.42 | 19-MAY-17:06 | 0.00 | 01-MAY-00:10 |
June | 0.245145E+11 | 0.670294E+10 | 400.10 | 0.236421E+11 | 0.872394E+09 | 0.00 | 1.00 | 01-JUN-14:50 | 0.00 | 01-JUN-00:10 | 66757.27 | 19-JUN-18:03 | 58456.41 | 25-JUN-21:25 | 23487.40 | 19-JUN-18:03 | 15627.14 | 18-JUN-15:43 | 0.00 | 01-JUN-00:10 |
July | 0.277767E+11 | 0.721080E+10 | 416.10 | 0.232247E+11 | 0.455200E+10 | 0.00 | 1.00 | 01-JUL-14:00 | 0.00 | 01-JUL-00:10 | 71591.97 | 21-JUL-21:05 | 57618.56 | 04-JUL-16:42 | 35531.55 | 21-JUL-21:05 | 16012.98 | 02-JUL-15:32 | 0.00 | 01-JUL-00:10 |
August | 0.228965E+11 | 0.595260E+10 | 375.82 | 0.201963E+11 | 0.270019E+10 | 0.00 | 1.00 | 01-AUG-00:41 | 0.00 | 01-AUG-00:15 | 68546.83 | 01-AUG-21:15 | 58403.83 | 10-AUG-23:51 | 31322.46 | 01-AUG-21:15 | 15593.06 | 06-AUG-15:13 | 0.00 | 01-AUG-00:10 |
September | 0.162597E+11 | 0.414662E+10 | 279.49 | 0.140863E+11 | 0.217340E+10 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 67276.77 | 03-SEP-08:52 | 58281.68 | 10-SEP-19:55 | 27886.01 | 03-SEP-07:55 | 14955.75 | 04-SEP-12:43 | 0.00 | 01-SEP-00:10 |
October | 0.278343E+10 | 0.716782E+09 | 77.57 | 0.242913E+10 | 0.354307E+09 | 0.00 | 1.00 | 01-OCT-09:55 | 0.00 | 01-OCT-00:10 | 63066.10 | 08-OCT-14:05 | 58069.83 | 22-OCT-12:15 | 13918.77 | 05-OCT-19:35 | 14591.12 | 01-OCT-14:43 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.107289E+12 | 0.282282E+11 | 1881.45 | 0.963079E+11 | 0.109809E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.277767E+11 | 0.721080E+10 | 416.10 | 0.236421E+11 | 0.455200E+10 | 0.00 | 1.00 | 0.00 | 71591.97 | 58505.35 | 35531.55 | 16012.98 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.77 | 39.33 | 30.44 | 85.32 | 99.02 | 0.00 | 0.00 | 0.00 |
February | 78.52 | 41.66 | 36.86 | 102.55 | 87.52 | 0.00 | 0.00 | 0.00 |
March | 107.12 | 57.40 | 49.71 | 149.39 | 78.39 | 0.00 | 0.00 | 0.00 |
April | 122.98 | 66.33 | 56.65 | 187.68 | 57.99 | 0.00 | 0.00 | 0.00 |
May | 132.45 | 70.77 | 61.67 | 218.43 | 44.20 | 0.00 | 0.00 | 0.00 |
June | 129.25 | 69.46 | 59.79 | 237.01 | 27.29 | 0.00 | 0.00 | 0.00 |
July | 114.79 | 57.10 | 57.69 | 209.43 | 24.35 | 0.00 | 0.00 | 0.00 |
August | 110.91 | 56.45 | 54.46 | 195.26 | 31.84 | 0.00 | 0.00 | 0.00 |
September | 113.74 | 63.45 | 50.29 | 191.07 | 54.87 | 0.00 | 0.00 | 0.00 |
October | 97.68 | 56.99 | 40.69 | 144.07 | 74.81 | 0.00 | 0.00 | 0.00 |
November | 81.45 | 49.39 | 32.06 | 104.58 | 99.80 | 0.00 | 0.00 | 0.00 |
December | 66.09 | 35.90 | 30.19 | 76.20 | 113.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.15 | 55.39 | 46.76 | 158.64 | 65.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.09 | 35.90 | 30.19 | 76.20 | 24.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.45 | 70.77 | 61.67 | 237.01 | 113.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.77 | 39.33 | 30.44 | 85.32 | 99.02 | 0.00 | 0.00 | 0.00 |
February | 78.52 | 41.66 | 36.86 | 102.55 | 87.52 | 0.00 | 0.00 | 0.00 |
March | 107.12 | 57.40 | 49.71 | 149.39 | 78.39 | 0.00 | 0.00 | 0.00 |
April | 122.98 | 66.33 | 56.65 | 187.68 | 57.99 | 0.00 | 0.00 | 0.00 |
May | 132.45 | 70.77 | 61.67 | 218.43 | 44.20 | 0.00 | 0.00 | 0.00 |
June | 129.25 | 69.46 | 59.79 | 237.01 | 27.29 | 0.00 | 0.00 | 0.00 |
July | 114.79 | 57.10 | 57.69 | 209.43 | 24.35 | 0.00 | 0.00 | 0.00 |
August | 110.91 | 56.45 | 54.46 | 195.26 | 31.84 | 0.00 | 0.00 | 0.00 |
September | 113.74 | 63.45 | 50.29 | 191.07 | 54.87 | 0.00 | 0.00 | 0.00 |
October | 97.68 | 56.99 | 40.69 | 144.07 | 74.81 | 0.00 | 0.00 | 0.00 |
November | 81.45 | 49.39 | 32.06 | 104.58 | 99.80 | 0.00 | 0.00 | 0.00 |
December | 66.09 | 35.90 | 30.19 | 76.20 | 113.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.15 | 55.39 | 46.76 | 158.64 | 65.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.09 | 35.90 | 30.19 | 76.20 | 24.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.45 | 70.77 | 61.67 | 237.01 | 113.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.43 | 0.00 | 14.43 | 5.44 | 60.51 | 0.00 | 0.00 | 0.00 |
February | 17.62 | 0.00 | 17.62 | 11.50 | 52.87 | 0.00 | 0.00 | 0.00 |
March | 23.07 | 0.00 | 23.07 | 19.89 | 47.01 | 0.00 | 0.00 | 0.00 |
April | 26.72 | 0.29 | 26.43 | 30.61 | 33.56 | 0.00 | 0.00 | 0.00 |
May | 31.63 | 2.33 | 29.30 | 47.44 | 24.18 | 0.00 | 0.00 | 0.00 |
June | 33.51 | 4.06 | 29.45 | 65.29 | 15.05 | 0.00 | 0.00 | 0.00 |
July | 30.91 | 2.88 | 28.02 | 58.92 | 13.47 | 0.00 | 0.00 | 0.00 |
August | 26.33 | 0.68 | 25.65 | 45.53 | 17.81 | 0.00 | 0.00 | 0.00 |
September | 22.86 | 0.02 | 22.84 | 34.21 | 32.06 | 0.00 | 0.00 | 0.00 |
October | 18.96 | 0.00 | 18.96 | 17.31 | 44.80 | 0.00 | 0.00 | 0.00 |
November | 15.31 | 0.00 | 15.31 | 5.94 | 61.25 | 0.00 | 0.00 | 0.00 |
December | 14.32 | 0.00 | 14.32 | 3.74 | 69.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.00 | 0.86 | 22.14 | 28.90 | 39.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.32 | 0.00 | 14.32 | 3.74 | 13.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.51 | 4.06 | 29.45 | 65.29 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.43 | 0.00 | 14.43 | 5.44 | 60.51 | 0.00 | 0.00 | 0.00 |
February | 17.62 | 0.00 | 17.62 | 11.50 | 52.87 | 0.00 | 0.00 | 0.00 |
March | 23.07 | 0.00 | 23.06 | 19.89 | 47.01 | 0.00 | 0.00 | 0.00 |
April | 26.72 | 0.29 | 26.43 | 30.61 | 33.56 | 0.00 | 0.00 | 0.00 |
May | 31.63 | 2.33 | 29.30 | 47.44 | 24.18 | 0.00 | 0.00 | 0.00 |
June | 33.51 | 4.06 | 29.45 | 65.29 | 15.05 | 0.00 | 0.00 | 0.00 |
July | 30.91 | 2.88 | 28.02 | 58.91 | 13.47 | 0.00 | 0.00 | 0.00 |
August | 26.33 | 0.68 | 25.65 | 45.53 | 17.81 | 0.00 | 0.00 | 0.00 |
September | 22.86 | 0.02 | 22.84 | 34.21 | 32.06 | 0.00 | 0.00 | 0.00 |
October | 18.96 | 0.00 | 18.96 | 17.31 | 44.80 | 0.00 | 0.00 | 0.00 |
November | 15.30 | 0.00 | 15.30 | 5.94 | 61.24 | 0.00 | 0.00 | 0.00 |
December | 14.32 | 0.00 | 14.32 | 3.73 | 69.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.00 | 0.86 | 22.14 | 28.90 | 39.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.32 | 0.00 | 14.32 | 3.73 | 13.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.51 | 4.06 | 29.45 | 65.29 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 96.11 | 50.11 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 126.28 | 47.13 | 0.00 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 180.90 | 44.55 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 229.90 | 38.49 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 259.60 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 284.12 | 23.55 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 247.77 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 228.43 | 23.42 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 205.66 | 34.75 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 146.70 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 108.67 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 85.80 | 58.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.54 | 39.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 85.80 | 18.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 284.12 | 58.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.85 | 57.42 | 24.43 | 100.44 | 44.20 | 0.00 | 0.00 | 0.00 |
February | 104.72 | 74.05 | 30.66 | 132.26 | 39.72 | 5.50 | 0.00 | 0.00 |
March | 146.20 | 103.18 | 43.01 | 186.30 | 40.29 | 0.00 | 0.00 | 0.00 |
April | 181.85 | 134.80 | 47.05 | 235.05 | 35.27 | 0.00 | 0.00 | 0.00 |
May | 200.50 | 148.91 | 51.59 | 258.03 | 36.76 | 0.00 | 0.00 | 0.00 |
June | 211.71 | 164.07 | 47.64 | 275.81 | 31.95 | 0.00 | 0.00 | 0.00 |
July | 183.23 | 132.00 | 51.24 | 240.58 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 171.33 | 123.48 | 47.86 | 222.27 | 30.95 | 0.00 | 0.00 | 0.00 |
September | 156.86 | 117.24 | 39.62 | 201.24 | 41.61 | 0.00 | 0.00 | 0.00 |
October | 118.34 | 85.91 | 32.43 | 147.09 | 45.12 | 0.00 | 0.00 | 0.00 |
November | 92.77 | 68.87 | 23.90 | 111.14 | 51.06 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 50.57 | 25.34 | 90.49 | 50.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.91 | 105.12 | 38.79 | 183.56 | 39.43 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 50.57 | 23.90 | 90.49 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.71 | 164.07 | 51.59 | 275.81 | 51.06 | 5.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186862E+09 | 0.105330E+09 | 81531223.12 | 0.228516E+09 | 0.265222E+09 |
February | 0.189951E+09 | 0.100776E+09 | 89174474.56 | 0.248100E+09 | 0.211718E+09 |
March | 0.286902E+09 | 0.153748E+09 | 0.133155E+09 | 0.400128E+09 | 0.209958E+09 |
April | 0.318756E+09 | 0.171921E+09 | 0.146835E+09 | 0.486472E+09 | 0.150302E+09 |
May | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.585052E+09 | 0.118391E+09 |
June | 0.335014E+09 | 0.180051E+09 | 0.154963E+09 | 0.614341E+09 | 70734318.04 |
July | 0.307442E+09 | 0.152935E+09 | 0.154508E+09 | 0.560944E+09 | 65206764.26 |
August | 0.297050E+09 | 0.151193E+09 | 0.145858E+09 | 0.522978E+09 | 85278065.80 |
September | 0.294810E+09 | 0.164463E+09 | 0.130346E+09 | 0.495248E+09 | 0.142227E+09 |
October | 0.261623E+09 | 0.152639E+09 | 0.108984E+09 | 0.385882E+09 | 0.200370E+09 |
November | 0.211128E+09 | 0.128023E+09 | 83105568.41 | 0.271067E+09 | 0.258690E+09 |
December | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.204100E+09 | 0.303079E+09 |
Annual Sum or Average | 0.322130E+10 | 0.174679E+10 | 0.147451E+10 | 0.500283E+10 | 0.208117E+10 |
Minimum of Months | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.204100E+09 | 65206764.26 |
Maximum of Months | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.614341E+09 | 0.303079E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186862E+09 | 0.105330E+09 | 81531223.12 | 0.228516E+09 | 0.265222E+09 |
February | 0.189951E+09 | 0.100776E+09 | 89174474.56 | 0.248100E+09 | 0.211718E+09 |
March | 0.286902E+09 | 0.153748E+09 | 0.133155E+09 | 0.400128E+09 | 0.209958E+09 |
April | 0.318756E+09 | 0.171921E+09 | 0.146835E+09 | 0.486472E+09 | 0.150302E+09 |
May | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.585052E+09 | 0.118391E+09 |
June | 0.335014E+09 | 0.180051E+09 | 0.154963E+09 | 0.614341E+09 | 70734318.04 |
July | 0.307442E+09 | 0.152935E+09 | 0.154508E+09 | 0.560944E+09 | 65206764.26 |
August | 0.297050E+09 | 0.151193E+09 | 0.145858E+09 | 0.522978E+09 | 85278065.80 |
September | 0.294810E+09 | 0.164463E+09 | 0.130346E+09 | 0.495248E+09 | 0.142227E+09 |
October | 0.261623E+09 | 0.152639E+09 | 0.108984E+09 | 0.385882E+09 | 0.200370E+09 |
November | 0.211128E+09 | 0.128023E+09 | 83105568.41 | 0.271067E+09 | 0.258690E+09 |
December | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.204100E+09 | 0.303079E+09 |
Annual Sum or Average | 0.322130E+10 | 0.174679E+10 | 0.147451E+10 | 0.500283E+10 | 0.208117E+10 |
Minimum of Months | 0.177016E+09 | 96155759.73 | 80860322.06 | 0.204100E+09 | 65206764.26 |
Maximum of Months | 0.354743E+09 | 0.189558E+09 | 0.165186E+09 | 0.614341E+09 | 0.303079E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38650826.57 | 0.00 | 38650826.57 | 14570459.82 | 0.162074E+09 |
February | 42629329.24 | 0.00 | 42629329.24 | 27830685.38 | 0.127911E+09 |
March | 61785000.29 | 6925.16 | 61778075.14 | 53285551.23 | 0.125900E+09 |
April | 69251959.12 | 748395.50 | 68503563.62 | 79337741.03 | 86987608.01 |
May | 84714655.88 | 6242423.55 | 78472232.32 | 0.127061E+09 | 64774796.76 |
June | 86858169.44 | 10533716.25 | 76324453.19 | 0.169236E+09 | 39002223.93 |
July | 82784501.55 | 7722763.83 | 75061737.72 | 0.157798E+09 | 36087770.37 |
August | 70531133.29 | 1817921.11 | 68713212.18 | 0.121942E+09 | 47704943.31 |
September | 59249700.15 | 55765.71 | 59193934.44 | 88663100.29 | 83096651.24 |
October | 50778777.08 | 0.00 | 50778777.08 | 46355077.72 | 0.119997E+09 |
November | 39671081.77 | 0.00 | 39671081.77 | 15387335.06 | 0.158747E+09 |
December | 38351488.79 | 0.00 | 38351488.79 | 10004013.25 | 0.186319E+09 |
Annual Sum or Average | 0.725257E+09 | 27127911.12 | 0.698129E+09 | 0.911470E+09 | 0.123860E+10 |
Minimum of Months | 38351488.79 | 0.00 | 38351488.79 | 10004013.25 | 36087770.37 |
Maximum of Months | 86858169.44 | 10533716.25 | 78472232.32 | 0.169236E+09 | 0.186319E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38649788.77 | 0.00 | 38649788.77 | 14569703.49 | 0.162073E+09 |
February | 42628207.63 | 0.00 | 42628207.63 | 27829812.42 | 0.127910E+09 |
March | 61783405.35 | 6924.83 | 61776480.52 | 53283986.24 | 0.125899E+09 |
April | 69250255.87 | 748360.42 | 68501895.45 | 79336179.09 | 86986681.20 |
May | 84712419.12 | 6242130.96 | 78470288.15 | 0.127058E+09 | 64773751.15 |
June | 86855859.48 | 10533222.52 | 76322636.95 | 0.169233E+09 | 39001404.58 |
July | 82782208.32 | 7722401.86 | 75059806.46 | 0.157795E+09 | 36087118.77 |
August | 70529311.95 | 1817835.90 | 68711476.05 | 0.121939E+09 | 47704238.28 |
September | 59248266.05 | 55763.10 | 59192502.95 | 88661635.90 | 83095683.86 |
October | 50777470.78 | 0.00 | 50777470.78 | 46353816.39 | 0.119996E+09 |
November | 39670069.84 | 0.00 | 39670069.84 | 15386757.22 | 0.158746E+09 |
December | 38350424.67 | 0.00 | 38350424.67 | 10003445.49 | 0.186318E+09 |
Annual Sum or Average | 0.725238E+09 | 27126639.59 | 0.698111E+09 | 0.911451E+09 | 0.123859E+10 |
Minimum of Months | 38350424.67 | 0.00 | 38350424.67 | 10003445.49 | 36087118.77 |
Maximum of Months | 86855859.48 | 10533222.52 | 78470288.15 | 0.169233E+09 | 0.186318E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.257425E+09 | 0.134220E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.305503E+09 | 0.114028E+09 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.484524E+09 | 0.119325E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.595906E+09 | 99757597.64 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.695321E+09 | 89746200.41 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.736432E+09 | 61048290.77 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.663633E+09 | 50411083.16 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.611818E+09 | 62734753.36 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.533077E+09 | 90069123.71 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.392926E+09 | 0.116785E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.281663E+09 | 0.137240E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.229817E+09 | 0.155469E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578805E+10 | 0.123084E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.229817E+09 | 50411083.16 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.736432E+09 | 0.155469E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219228E+09 | 0.153802E+09 | 65425845.84 | 0.269017E+09 | 0.118391E+09 |
February | 0.253331E+09 | 0.179152E+09 | 74179744.18 | 0.319954E+09 | 96100490.40 |
March | 0.391572E+09 | 0.276365E+09 | 0.115207E+09 | 0.498977E+09 | 0.107908E+09 |
April | 0.471359E+09 | 0.349404E+09 | 0.121954E+09 | 0.609238E+09 | 91414058.27 |
May | 0.537017E+09 | 0.398842E+09 | 0.138175E+09 | 0.691107E+09 | 98449843.69 |
June | 0.548758E+09 | 0.425273E+09 | 0.123485E+09 | 0.714890E+09 | 82809754.52 |
July | 0.490771E+09 | 0.353538E+09 | 0.137233E+09 | 0.644373E+09 | 69544667.08 |
August | 0.458900E+09 | 0.330722E+09 | 0.128178E+09 | 0.595316E+09 | 82891402.21 |
September | 0.406583E+09 | 0.303882E+09 | 0.102701E+09 | 0.521617E+09 | 0.107845E+09 |
October | 0.316956E+09 | 0.230089E+09 | 86867005.25 | 0.393959E+09 | 0.120849E+09 |
November | 0.240460E+09 | 0.178509E+09 | 61950592.78 | 0.288078E+09 | 0.132344E+09 |
December | 0.203328E+09 | 0.135460E+09 | 67868227.27 | 0.242373E+09 | 0.134882E+09 |
Annual Sum or Average | 0.453826E+10 | 0.331504E+10 | 0.122322E+10 | 0.578890E+10 | 0.124343E+10 |
Minimum of Months | 0.203328E+09 | 0.135460E+09 | 61950592.78 | 0.242373E+09 | 69544667.08 |
Maximum of Months | 0.548758E+09 | 0.425273E+09 | 0.138175E+09 | 0.714890E+09 | 0.134882E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.91 | 314.46 | 168.39 | 78.65 | 89.74 | 0.00 | 0.00 |
February | 224.84 | 277.50 | 192.28 | 83.31 | 108.96 | 0.00 | 0.00 |
March | 336.25 | 248.47 | 260.37 | 114.81 | 145.56 | 0.00 | 0.00 |
April | 435.57 | 182.08 | 299.39 | 133.23 | 166.16 | 0.00 | 0.00 |
May | 530.34 | 135.37 | 328.15 | 146.21 | 181.94 | 0.00 | 0.00 |
June | 603.32 | 83.38 | 325.52 | 147.06 | 178.46 | 0.00 | 0.00 |
July | 535.40 | 74.35 | 291.39 | 119.97 | 171.42 | 0.00 | 0.00 |
August | 481.01 | 98.74 | 274.48 | 114.26 | 160.22 | 0.00 | 0.00 |
September | 450.21 | 173.52 | 273.19 | 126.94 | 146.25 | 0.00 | 0.00 |
October | 320.95 | 237.41 | 233.27 | 113.98 | 119.30 | 0.00 | 0.00 |
November | 216.28 | 317.35 | 193.52 | 98.78 | 94.73 | 0.00 | 0.00 |
December | 154.21 | 359.78 | 160.82 | 71.80 | 89.02 | 0.00 | 0.00 |
Annual Sum or Average | 372.72 | 208.18 | 250.29 | 112.50 | 137.79 | 0.00 | 0.00 |
Minimum of Months | 154.21 | 74.35 | 160.82 | 71.80 | 89.02 | 0.00 | 0.00 |
Maximum of Months | 603.32 | 359.78 | 328.15 | 147.06 | 181.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1345.56 | 701.57 | 1145.91 | 803.92 | 341.98 | 0.00 | 0.00 |
February | 1767.95 | 659.89 | 1466.04 | 1036.76 | 429.28 | 0.00 | 0.00 |
March | 2532.61 | 623.71 | 2046.75 | 1444.56 | 602.19 | 0.00 | 0.00 |
April | 3218.63 | 538.81 | 2545.92 | 1887.22 | 658.70 | 0.00 | 0.00 |
May | 3634.44 | 469.10 | 2806.99 | 2084.75 | 722.24 | 0.00 | 0.00 |
June | 3977.64 | 329.74 | 2963.97 | 2297.00 | 666.97 | 0.00 | 0.00 |
July | 3468.81 | 263.50 | 2565.26 | 1847.95 | 717.32 | 0.00 | 0.00 |
August | 3197.97 | 327.91 | 2398.67 | 1728.68 | 669.98 | 0.00 | 0.00 |
September | 2879.27 | 486.48 | 2196.05 | 1641.34 | 554.71 | 0.00 | 0.00 |
October | 2053.83 | 610.44 | 1656.73 | 1202.67 | 454.05 | 0.00 | 0.00 |
November | 1521.33 | 741.27 | 1298.78 | 964.17 | 334.61 | 0.00 | 0.00 |
December | 1201.25 | 812.64 | 1062.80 | 708.05 | 354.75 | 0.00 | 0.00 |
Annual Sum or Average | 2569.53 | 546.41 | 2014.70 | 1471.67 | 543.03 | 0.00 | 0.00 |
Minimum of Months | 1201.25 | 263.50 | 1062.80 | 708.05 | 334.61 | 0.00 | 0.00 |
Maximum of Months | 3977.64 | 812.64 | 2963.97 | 2297.00 | 722.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12557.07 | 6111.97 | 2619.21 | 1837.54 | 781.67 | 0.00 | 0.00 |
February | 16528.36 | 5113.47 | 3350.94 | 2369.73 | 981.21 | 0.00 | 0.00 |
March | 24930.83 | 4249.14 | 4678.28 | 3301.86 | 1376.42 | 0.00 | 0.00 |
April | 30140.87 | 3401.12 | 5819.24 | 4313.64 | 1505.61 | 0.00 | 0.00 |
May | 35781.97 | 3812.81 | 6415.98 | 4765.14 | 1650.84 | 0.00 | 0.00 |
June | 48943.69 | 5072.69 | 6774.79 | 5250.28 | 1524.50 | 0.00 | 0.00 |
July | 41086.85 | 4149.70 | 5863.46 | 4223.88 | 1639.58 | 0.00 | 0.00 |
August | 36695.18 | 4565.39 | 5482.67 | 3951.28 | 1531.39 | 0.00 | 0.00 |
September | 31491.79 | 4930.53 | 5019.54 | 3751.63 | 1267.91 | 0.00 | 0.00 |
October | 17951.62 | 4669.03 | 3786.81 | 2748.97 | 1037.84 | 0.00 | 0.00 |
November | 15055.65 | 5414.62 | 2968.64 | 2203.82 | 764.82 | 0.00 | 0.00 |
December | 11311.39 | 7419.49 | 2429.25 | 1618.39 | 810.85 | 0.00 | 0.00 |
Annual Sum or Average | 26908.27 | 4909.73 | 4605.04 | 3363.81 | 1241.22 | 0.00 | 0.00 |
Minimum of Months | 11311.39 | 3401.12 | 2429.25 | 1618.39 | 764.82 | 0.00 | 0.00 |
Maximum of Months | 48943.69 | 7419.49 | 6774.79 | 5250.28 | 1650.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473826E+09 | 0.842245E+09 | 0.451024E+09 | 0.210661E+09 | 0.240363E+09 | 0.00 | 0.00 |
February | 0.543929E+09 | 0.671324E+09 | 0.465159E+09 | 0.201552E+09 | 0.263606E+09 | 0.00 | 0.00 |
March | 0.900616E+09 | 0.665506E+09 | 0.697373E+09 | 0.307509E+09 | 0.389864E+09 | 0.00 | 0.00 |
April | 0.112900E+10 | 0.471957E+09 | 0.776014E+09 | 0.345338E+09 | 0.430675E+09 | 0.00 | 0.00 |
May | 0.142047E+10 | 0.362574E+09 | 0.878914E+09 | 0.391600E+09 | 0.487314E+09 | 0.00 | 0.00 |
June | 0.156380E+10 | 0.216125E+09 | 0.843742E+09 | 0.381168E+09 | 0.462574E+09 | 0.00 | 0.00 |
July | 0.143402E+10 | 0.199129E+09 | 0.780452E+09 | 0.321315E+09 | 0.459137E+09 | 0.00 | 0.00 |
August | 0.128833E+10 | 0.264458E+09 | 0.735161E+09 | 0.306021E+09 | 0.429140E+09 | 0.00 | 0.00 |
September | 0.116695E+10 | 0.449775E+09 | 0.708117E+09 | 0.329038E+09 | 0.379079E+09 | 0.00 | 0.00 |
October | 0.859620E+09 | 0.635879E+09 | 0.624803E+09 | 0.305279E+09 | 0.319524E+09 | 0.00 | 0.00 |
November | 0.560600E+09 | 0.822565E+09 | 0.501598E+09 | 0.256046E+09 | 0.245552E+09 | 0.00 | 0.00 |
December | 0.413041E+09 | 0.963627E+09 | 0.430734E+09 | 0.192312E+09 | 0.238423E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.117542E+11 | 0.656516E+10 | 0.789309E+10 | 0.354784E+10 | 0.434525E+10 | 0.00 | 0.00 |
Minimum of Months | 0.413041E+09 | 0.199129E+09 | 0.430734E+09 | 0.192312E+09 | 0.238423E+09 | 0.00 | 0.00 |
Maximum of Months | 0.156380E+10 | 0.963627E+09 | 0.878914E+09 | 0.391600E+09 | 0.487314E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.360395E+10 | 0.187908E+10 | 0.306919E+10 | 0.215323E+10 | 0.915962E+09 | 0.00 | 0.00 |
February | 0.427704E+10 | 0.159640E+10 | 0.354664E+10 | 0.250812E+10 | 0.103852E+10 | 0.00 | 0.00 |
March | 0.678333E+10 | 0.167055E+10 | 0.548201E+10 | 0.386912E+10 | 0.161289E+10 | 0.00 | 0.00 |
April | 0.834269E+10 | 0.139661E+10 | 0.659902E+10 | 0.489166E+10 | 0.170736E+10 | 0.00 | 0.00 |
May | 0.973449E+10 | 0.125645E+10 | 0.751824E+10 | 0.558379E+10 | 0.193445E+10 | 0.00 | 0.00 |
June | 0.103100E+11 | 0.854676E+09 | 0.768261E+10 | 0.595382E+10 | 0.172879E+10 | 0.00 | 0.00 |
July | 0.929087E+10 | 0.705755E+09 | 0.687080E+10 | 0.494954E+10 | 0.192126E+10 | 0.00 | 0.00 |
August | 0.856545E+10 | 0.878287E+09 | 0.642459E+10 | 0.463011E+10 | 0.179449E+10 | 0.00 | 0.00 |
September | 0.746308E+10 | 0.126097E+10 | 0.569216E+10 | 0.425435E+10 | 0.143781E+10 | 0.00 | 0.00 |
October | 0.550097E+10 | 0.163499E+10 | 0.443738E+10 | 0.322124E+10 | 0.121614E+10 | 0.00 | 0.00 |
November | 0.394329E+10 | 0.192136E+10 | 0.336644E+10 | 0.249913E+10 | 0.867308E+09 | 0.00 | 0.00 |
December | 0.321744E+10 | 0.217657E+10 | 0.284659E+10 | 0.189644E+10 | 0.950155E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810326E+11 | 0.172317E+11 | 0.635357E+11 | 0.464105E+11 | 0.171251E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321744E+10 | 0.705755E+09 | 0.284659E+10 | 0.189644E+10 | 0.867308E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103100E+11 | 0.217657E+10 | 0.768261E+10 | 0.595382E+10 | 0.193445E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336329E+11 | 0.163703E+11 | 0.701530E+10 | 0.492167E+10 | 0.209363E+10 | 0.00 | 0.00 |
February | 0.399854E+11 | 0.123705E+11 | 0.810660E+10 | 0.573285E+10 | 0.237375E+10 | 0.00 | 0.00 |
March | 0.667747E+11 | 0.113809E+11 | 0.125303E+11 | 0.884369E+10 | 0.368661E+10 | 0.00 | 0.00 |
April | 0.781251E+11 | 0.881570E+10 | 0.150835E+11 | 0.111809E+11 | 0.390254E+10 | 0.00 | 0.00 |
May | 0.958384E+11 | 0.102122E+11 | 0.171846E+11 | 0.127630E+11 | 0.442161E+10 | 0.00 | 0.00 |
June | 0.126862E+12 | 0.131484E+11 | 0.175602E+11 | 0.136087E+11 | 0.395151E+10 | 0.00 | 0.00 |
July | 0.110047E+12 | 0.111146E+11 | 0.157047E+11 | 0.113132E+11 | 0.439145E+10 | 0.00 | 0.00 |
August | 0.982844E+11 | 0.122280E+11 | 0.146848E+11 | 0.105831E+11 | 0.410168E+10 | 0.00 | 0.00 |
September | 0.816267E+11 | 0.127799E+11 | 0.130107E+11 | 0.972422E+10 | 0.328643E+10 | 0.00 | 0.00 |
October | 0.480816E+11 | 0.125055E+11 | 0.101426E+11 | 0.736283E+10 | 0.277974E+10 | 0.00 | 0.00 |
November | 0.390243E+11 | 0.140347E+11 | 0.769472E+10 | 0.571230E+10 | 0.198242E+10 | 0.00 | 0.00 |
December | 0.302964E+11 | 0.198724E+11 | 0.650649E+10 | 0.433471E+10 | 0.217178E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.848579E+12 | 0.154833E+12 | 0.145224E+12 | 0.106081E+12 | 0.391432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.302964E+11 | 0.881570E+10 | 0.650649E+10 | 0.433471E+10 | 0.198242E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126862E+12 | 0.198724E+11 | 0.175602E+11 | 0.136087E+11 | 0.442161E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.851940E+09 | -782872706.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69066842.7 | 59.00 | 0.00 | 0.00 |
February | 0.780125E+09 | -718605585.2 | 0.00 | 0.00 | 672.00 | 0.00 | -61519197.3 | 59.00 | 0.00 | 0.00 |
March | 0.874752E+09 | -808969323.5 | 0.00 | 0.00 | 744.00 | 0.00 | -65782686.6 | 58.99 | 0.00 | 0.00 |
April | 0.760021E+09 | -701669857.8 | 0.00 | 0.00 | 720.00 | 0.00 | -58351465.5 | 58.99 | 0.00 | 0.00 |
May | 0.727378E+09 | -670065874.9 | 0.00 | 0.00 | 744.00 | 0.00 | -57312067.7 | 58.99 | 0.00 | 0.00 |
June | 0.668950E+09 | -614635011.2 | 0.00 | 0.00 | 720.00 | 0.00 | -54315418.3 | 59.00 | 0.00 | 0.00 |
July | 0.620492E+09 | -564848279.4 | 0.00 | 0.00 | 744.00 | 0.00 | -55643220.9 | 58.99 | 0.00 | 0.00 |
August | 0.663369E+09 | -607197960.3 | 0.00 | 0.00 | 744.00 | 0.00 | -56171136.3 | 59.00 | 0.00 | 0.00 |
September | 0.649267E+09 | -594563407.3 | 0.00 | 0.00 | 720.00 | 0.00 | -54704031.9 | 59.00 | 0.00 | 0.00 |
October | 0.705407E+09 | -646578327.2 | 0.00 | 0.00 | 744.00 | 0.00 | -58828253.3 | 58.99 | 0.00 | 0.00 |
November | 0.738730E+09 | -676116833.8 | 0.00 | 0.00 | 720.00 | 0.00 | -62612670.4 | 58.99 | 0.00 | 0.00 |
December | 0.822611E+09 | -753476027.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69134597.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.886304E+10 | -0.813960E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -723441588.5 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.620492E+09 | -808969323.5 | 0.00 | 0.00 | 672.00 | 0.00 | -69134597.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.874752E+09 | -564848279.4 | 0.00 | 0.00 | 744.00 | 0.00 | -54315418.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.79 | 0.50 | 08-JAN-11:09 | 1315.87 | 0.00 | 0.00 | 68.33 | 167.53 | 0.00 | 0.00 | 27.50 |
February | 268.33 | 0.77 | 0.50 | 07-FEB-12:09 | 232.68 | 0.00 | 0.00 | 65.17 | 197.00 | 0.00 | 0.00 | 47.17 |
March | 351.83 | 0.73 | 0.50 | 02-MAR-10:39 | 287.81 | 0.00 | 0.00 | 121.17 | 235.93 | 0.00 | 0.00 | 92.17 |
April | 373.83 | 0.71 | 0.50 | 01-APR-10:09 | 300.31 | 0.00 | 0.00 | 161.83 | 246.07 | 0.00 | 0.00 | 109.00 |
May | 408.83 | 0.69 | 0.50 | 01-MAY-09:50 | 1428.19 | 0.00 | 0.00 | 210.67 | 2323.31 | 0.00 | 0.00 | 136.00 |
June | 398.00 | 0.70 | 0.50 | 01-JUN-10:09 | 5411.01 | 0.00 | 0.00 | 204.83 | 231.81 | 0.00 | 0.00 | 107.67 |
July | 400.17 | 0.70 | 0.50 | 01-JUL-10:39 | 2334.74 | 0.00 | 0.00 | 212.67 | 251.11 | 0.00 | 0.00 | 135.17 |
August | 377.83 | 0.69 | 0.50 | 01-AUG-10:30 | 924.80 | 0.00 | 0.00 | 190.83 | 255.46 | 0.00 | 0.00 | 129.33 |
September | 365.83 | 0.74 | 0.50 | 02-SEP-09:00 | 271.80 | 0.00 | 0.00 | 116.00 | 226.19 | 0.00 | 0.00 | 94.83 |
October | 318.83 | 0.74 | 0.50 | 02-OCT-09:20 | 245.02 | 0.00 | 0.00 | 75.67 | 1775.02 | 0.00 | 0.00 | 78.17 |
November | 295.83 | 0.82 | 0.50 | 02-NOV-09:00 | 182.73 | 0.00 | 0.00 | 32.50 | 155.01 | 0.00 | 0.00 | 16.17 |
December | 289.50 | 0.80 | 0.50 | 01-DEC-10:00 | 195.37 | 0.00 | 0.00 | 45.83 | 166.06 | 0.00 | 0.00 | 24.50 |
Annual Sum or Average | 4125.67 | 0.74 | 1199.71 | 0.00 | 0.00 | 1505.50 | 546.81 | 0.00 | 0.00 | 997.67 | ||
Minimum of Months | 268.33 | 0.69 | 0.50 | 182.73 | 0.00 | 0.00 | 32.50 | 155.01 | 0.00 | 0.00 | 16.17 | |
Maximum of Months | 408.83 | 0.82 | 0.50 | 5411.01 | 0.00 | 0.00 | 212.67 | 2323.31 | 0.00 | 0.00 | 136.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.65 | 0.50 | 01-JAN-09:09 | 230.45 | 12.86 | 0.00 | 156.83 | 1555.81 | 20.61 | 67.83 | 139.00 |
February | 268.33 | 0.63 | 0.50 | 01-FEB-10:09 | 1883.91 | 15.79 | 31.33 | 181.50 | 573.20 | 18.93 | 64.50 | 151.00 |
March | 351.83 | 0.62 | 0.50 | 01-MAR-08:30 | 438.01 | 14.21 | 3.67 | 243.17 | 277.96 | 18.12 | 90.33 | 210.17 |
April | 373.83 | 0.60 | 0.50 | 01-APR-07:00 | 2336.37 | 14.50 | 5.67 | 277.00 | 4302.57 | 20.28 | 118.33 | 242.83 |
May | 408.83 | 0.59 | 0.50 | 01-MAY-06:00 | 367.78 | 14.72 | 2.50 | 313.33 | 2486.11 | 18.83 | 127.33 | 276.17 |
June | 398.00 | 0.59 | 0.50 | 01-JUN-07:10 | 349.52 | 14.64 | 3.00 | 309.17 | 298.12 | 18.78 | 116.00 | 270.00 |
July | 400.17 | 0.60 | 0.50 | 01-JUL-07:10 | 369.42 | 14.67 | 5.00 | 311.33 | 316.61 | 18.77 | 122.33 | 271.50 |
August | 377.83 | 0.59 | 0.50 | 01-AUG-07:19 | 2066.54 | 14.83 | 4.83 | 291.00 | 2127.28 | 18.93 | 118.17 | 255.33 |
September | 365.83 | 0.63 | 0.50 | 01-SEP-08:39 | 316.19 | 13.71 | 2.83 | 238.67 | 265.93 | 17.78 | 75.00 | 202.33 |
October | 318.83 | 0.62 | 0.50 | 01-OCT-08:30 | 1283.13 | 13.62 | 0.17 | 232.67 | 239.51 | 17.61 | 77.67 | 174.83 |
November | 295.83 | 0.68 | 0.50 | 01-NOV-12:39 | 214.86 | 12.52 | 0.00 | 157.00 | 181.55 | 16.45 | 38.17 | 116.50 |
December | 289.50 | 0.66 | 0.50 | 01-DEC-08:00 | 230.67 | 13.17 | 0.00 | 161.17 | 1452.34 | 19.93 | 72.50 | 133.00 |
Annual Sum or Average | 4125.67 | 0.62 | 841.09 | 14.16 | 59.00 | 2872.83 | 1212.91 | 18.74 | 1088.17 | 2442.67 | ||
Minimum of Months | 268.33 | 0.59 | 0.50 | 214.86 | 12.52 | 0.00 | 156.83 | 181.55 | 16.45 | 38.17 | 116.50 | |
Maximum of Months | 408.83 | 0.68 | 0.50 | 2336.37 | 15.79 | 31.33 | 313.33 | 4302.57 | 20.61 | 127.33 | 276.17 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.91 | 0.82 | 20-JAN-15:30 | 383.03 | 23.57 | 107.33 | 40.00 | 99.88 | 19.84 | 60.67 | 0.00 |
February | 268.33 | 0.91 | 0.80 | 10-FEB-16:10 | 282.47 | 22.67 | 102.00 | 30.50 | 172.31 | 21.89 | 87.50 | 12.00 |
March | 351.83 | 0.90 | 0.80 | 01-MAR-16:10 | 404.11 | 22.64 | 134.50 | 63.83 | 350.71 | 23.22 | 143.00 | 41.50 |
April | 373.83 | 0.89 | 0.80 | 01-APR-15:09 | 285.38 | 20.94 | 124.00 | 46.00 | 462.83 | 22.05 | 151.83 | 59.83 |
May | 408.83 | 0.89 | 0.80 | 01-MAY-15:20 | 228.41 | 20.22 | 120.83 | 34.50 | 250.81 | 21.73 | 169.67 | 59.17 |
June | 398.00 | 0.89 | 0.80 | 01-JUN-16:10 | 224.37 | 20.13 | 103.33 | 21.50 | 262.13 | 21.63 | 159.00 | 46.33 |
July | 400.17 | 0.89 | 0.80 | 01-JUL-15:09 | 221.98 | 20.08 | 108.83 | 24.50 | 242.74 | 21.57 | 176.00 | 45.00 |
August | 377.83 | 0.89 | 0.80 | 01-AUG-15:20 | 220.17 | 20.20 | 115.50 | 28.83 | 229.05 | 21.65 | 155.67 | 42.17 |
September | 365.83 | 0.90 | 0.80 | 01-SEP-16:10 | 273.77 | 21.05 | 140.00 | 45.00 | 329.31 | 23.12 | 161.17 | 49.00 |
October | 318.83 | 0.90 | 0.80 | 01-OCT-15:09 | 552.49 | 24.08 | 125.33 | 56.17 | 193.83 | 22.86 | 122.50 | 23.00 |
November | 295.83 | 0.92 | 0.80 | 02-NOV-15:20 | 382.40 | 22.86 | 99.33 | 41.17 | 95.43 | 19.56 | 58.33 | 0.00 |
December | 289.50 | 0.92 | 0.82 | 05-DEC-15:39 | 328.66 | 22.98 | 108.17 | 34.67 | 91.99 | 19.50 | 58.50 | 0.00 |
Annual Sum or Average | 4125.67 | 0.90 | 307.82 | 21.61 | 1389.17 | 466.67 | 241.89 | 21.64 | 1503.83 | 378.00 | ||
Minimum of Months | 268.33 | 0.89 | 0.80 | 220.17 | 20.08 | 99.33 | 21.50 | 91.99 | 19.50 | 58.33 | 0.00 | |
Maximum of Months | 408.83 | 0.92 | 0.82 | 552.49 | 24.08 | 140.00 | 63.83 | 462.83 | 23.22 | 176.00 | 59.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246106E+10 | 27823.76 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166613E+10 | 27823.76 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.856579E+09 | 27823.76 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40244580.90 | 13044.28 | 12-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 278438.42 | 1392.19 | 25-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585366E+09 | 27823.76 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263324E+10 | 27823.76 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263324E+10 | 27823.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320965E+10 | 55022.33 | 27-JAN-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173570E+10 | 53382.05 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449960E+09 | 54180.61 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277698E+09 | 40464.88 | 28-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.477615E+10 | 57462.90 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477615E+10 | 57462.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15676525.32 | 11304.44 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15676525.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15676525.32 | 11304.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7964057.56 | 7964057.56 | 687.02 | 21-FEB-16:00 | 687.02 | 0.00 |
March | 0.00 | 0.00 | 0.178930E+09 | 0.178930E+09 | 3396.45 | 21-MAR-16:00 | 3396.45 | 0.00 |
April | 0.00 | 0.00 | 0.256377E+10 | 0.254846E+10 | 20395.63 | 29-APR-07:02 | 18507.86 | 0.00 |
May | 0.00 | 0.00 | 0.644094E+10 | 0.621666E+10 | 22146.93 | 23-MAY-07:02 | 17337.20 | 0.00 |
June | 0.00 | 0.00 | 0.947170E+10 | 0.898834E+10 | 22533.94 | 19-JUN-07:02 | 18564.90 | 0.00 |
July | 0.00 | 0.00 | 0.108211E+11 | 0.878503E+10 | 26268.66 | 21-JUL-07:02 | 10351.24 | 0.00 |
August | 0.00 | 0.00 | 0.101550E+11 | 0.862875E+10 | 25275.37 | 03-AUG-07:02 | 13604.53 | 0.00 |
September | 0.00 | 0.00 | 0.837256E+10 | 0.719552E+10 | 24337.18 | 23-SEP-07:02 | 13549.31 | 0.00 |
October | 0.00 | 0.00 | 0.337040E+10 | 0.299299E+10 | 23021.19 | 04-OCT-07:02 | 13778.21 | 0.00 |
November | 0.00 | 0.00 | 0.211302E+09 | 0.207988E+09 | 4973.76 | 03-NOV-16:00 | 4973.76 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.515938E+11 | 0.457506E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108211E+11 | 0.898834E+10 | 26268.66 | 18564.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.158882E+10 | 0.158690E+10 | 57443.34 | 30-APR-10:45 | 57443.34 | 0.00 |
May | 0.00 | 0.00 | 0.114692E+11 | 0.111425E+11 | 64454.96 | 28-MAY-09:15 | 47118.89 | 0.00 |
June | 0.00 | 0.00 | 0.245145E+11 | 0.236421E+11 | 66757.27 | 19-JUN-18:03 | 43269.87 | 0.00 |
July | 0.00 | 0.00 | 0.277767E+11 | 0.232247E+11 | 71591.97 | 21-JUL-21:05 | 36060.41 | 0.00 |
August | 0.00 | 0.00 | 0.228965E+11 | 0.201963E+11 | 68546.83 | 01-AUG-21:15 | 37224.37 | 0.00 |
September | 0.00 | 0.00 | 0.162597E+11 | 0.140863E+11 | 67276.77 | 03-SEP-08:52 | 42722.53 | 0.00 |
October | 0.00 | 0.00 | 0.278343E+10 | 0.242913E+10 | 63066.10 | 08-OCT-14:05 | 50622.03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107289E+12 | 0.963079E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.277767E+11 | 0.236421E+11 | 71591.97 | 57443.34 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 380351.56 | 0.00 | 135.84 | 31-DEC-06:47 | 0.09 |
Annual Sum or Average | 380351.56 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 380351.56 | 0.00 | 135.84 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.628821E+09 | 0.27 | 1392.27 | 02-JAN-07:02 | 1.05 |
February | 0.559530E+09 | 0.26 | 1392.27 | 01-FEB-06:01 | 1.05 |
March | 0.621793E+09 | 0.26 | 1392.27 | 01-MAR-06:02 | 1.05 |
April | 0.552649E+09 | 0.24 | 1392.27 | 29-APR-07:02 | 1.04 |
May | 0.583926E+09 | 0.25 | 1392.27 | 09-MAY-07:02 | 1.05 |
June | 0.662120E+09 | 0.28 | 1392.27 | 01-JUN-07:02 | 1.05 |
July | 0.652251E+09 | 0.27 | 1392.27 | 01-JUL-06:01 | 1.04 |
August | 0.663260E+09 | 0.28 | 1392.27 | 01-AUG-06:01 | 1.03 |
September | 0.580790E+09 | 0.25 | 1392.27 | 01-SEP-07:02 | 1.03 |
October | 0.554576E+09 | 0.23 | 1392.27 | 02-OCT-06:02 | 1.04 |
November | 0.547242E+09 | 0.24 | 1392.27 | 20-NOV-07:01 | 1.05 |
December | 0.633980E+09 | 0.27 | 1392.27 | 01-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.724094E+10 | 0.26 | |||
Minimum of Months | 0.547242E+09 | 0.23 | 1392.27 | 1.03 | |
Maximum of Months | 0.663260E+09 | 0.28 | 1392.27 | 1.05 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133524E+10 | 0.35 | 2091.41 | 07-JAN-07:02 | 0.84 |
February | 0.118796E+10 | 0.30 | 2395.75 | 02-FEB-07:02 | 0.90 |
March | 0.133960E+10 | 0.26 | 2009.71 | 02-MAR-06:01 | 1.02 |
April | 0.123646E+10 | 0.24 | 1343.74 | 21-APR-17:10 | 0.64 |
May | 0.140699E+10 | 0.29 | 3096.13 | 14-MAY-14:13 | 1.01 |
June | 0.161245E+10 | 0.37 | 3096.13 | 01-JUN-17:05 | 1.01 |
July | 0.160930E+10 | 0.36 | 3096.13 | 01-JUL-17:06 | 1.00 |
August | 0.160190E+10 | 0.35 | 3096.13 | 01-AUG-17:06 | 1.00 |
September | 0.136681E+10 | 0.28 | 3096.13 | 03-SEP-12:03 | 1.00 |
October | 0.124564E+10 | 0.23 | 3096.13 | 01-OCT-14:43 | 1.01 |
November | 0.118655E+10 | 0.24 | 1732.64 | 29-NOV-07:02 | 0.75 |
December | 0.138994E+10 | 0.40 | 2517.33 | 27-DEC-07:02 | 0.92 |
Annual Sum or Average | 0.165188E+11 | 0.31 | |||
Minimum of Months | 0.118655E+10 | 0.23 | 1343.74 | 0.64 | |
Maximum of Months | 0.161245E+10 | 0.40 | 3096.13 | 1.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.628821E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.561559E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.666277E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119290E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.217503E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.312133E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.331199E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.314390E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.258987E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.135695E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.598903E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.633980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.199815E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.561559E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.331199E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133524E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.118796E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133960E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167244E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.446948E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.831539E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.882010E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.755450E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.551343E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.196242E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118655E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.138994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.447470E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118655E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.882010E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.628821E+09 | 0.00 | 0.246106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.559530E+09 | 7964057.56 | 0.166613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.621793E+09 | 0.178930E+09 | 0.856579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552649E+09 | 0.256377E+10 | 40244580.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583926E+09 | 0.644094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.662120E+09 | 0.947170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.652251E+09 | 0.108132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.663260E+09 | 0.101530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.580790E+09 | 0.836985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.554576E+09 | 0.337040E+10 | 278438.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.547242E+09 | 0.211302E+09 | 0.585366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633980E+09 | 0.00 | 0.263324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724094E+10 | 0.515811E+11 | 0.824290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.663260E+09 | 0.108132E+11 | 0.263324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133524E+10 | 0.00 | 0.320965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118796E+10 | 0.00 | 0.173570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133960E+10 | 0.00 | 0.449960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123646E+10 | 0.157965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140699E+10 | 0.112863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161245E+10 | 0.240419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160930E+10 | 0.270243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160190E+10 | 0.222689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136681E+10 | 0.157286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124564E+10 | 0.272398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118655E+10 | 0.00 | 0.277698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138994E+10 | 0.00 | 0.477615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165188E+11 | 0.104654E+12 | 0.104492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161245E+10 | 0.270243E+11 | 0.477615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.628821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.559530E+09 | 0.00 | 0.00 | 0.00 | 2028683.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.621793E+09 | 0.00 | 0.00 | 0.00 | 44483771.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552649E+09 | 0.00 | 0.00 | 0.00 | 0.640247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583926E+09 | 0.00 | 0.00 | 0.00 | 0.159110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.662120E+09 | 0.00 | 0.00 | 0.00 | 0.245921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.652251E+09 | 0.00 | 0.00 | 0.00 | 0.265974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.663260E+09 | 0.00 | 0.00 | 0.00 | 0.248064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.580790E+09 | 0.00 | 0.00 | 0.00 | 0.200908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.554576E+09 | 0.00 | 0.00 | 0.00 | 0.802370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.547242E+09 | 0.00 | 0.00 | 0.00 | 51661401.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724094E+10 | 0.00 | 0.00 | 0.00 | 0.127406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.663260E+09 | 0.00 | 0.00 | 0.00 | 0.265974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123646E+10 | 0.00 | 0.00 | 0.00 | 0.435976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140699E+10 | 0.00 | 0.00 | 0.00 | 0.306248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161245E+10 | 0.00 | 0.00 | 0.00 | 0.670294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160930E+10 | 0.00 | 0.00 | 0.00 | 0.721080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160190E+10 | 0.00 | 0.00 | 0.00 | 0.595260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136681E+10 | 0.00 | 0.00 | 0.00 | 0.414662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124564E+10 | 0.00 | 0.00 | 0.00 | 0.716782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165188E+11 | 0.00 | 0.00 | 0.00 | 0.282282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161245E+10 | 0.00 | 0.00 | 0.00 | 0.721080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834546E+09 | 0.00 | 0.00 | 0.12 |
February | 0.464929E+09 | 0.00 | 0.00 | 36145.16 | 0.00 | 0.517729E+09 | 65141659.69 | 0.00 | 0.15 |
March | 0.625339E+09 | 0.00 | 0.00 | 452319.18 | 0.00 | 0.204001E+09 | 0.393131E+09 | 0.00 | 0.23 |
April | 0.127330E+09 | 44877558.04 | 0.00 | 3119531.44 | 0.00 | 1334139.58 | 0.109891E+10 | 0.00 | 0.35 |
May | 5377585.79 | 0.238601E+09 | 0.00 | 3552895.45 | 0.00 | 0.00 | 0.593237E+09 | 0.00 | 0.31 |
June | 970830.10 | 0.586614E+09 | 0.00 | 3014548.12 | 0.00 | 0.00 | 0.137562E+09 | 0.00 | 0.24 |
July | 4139.95 | 0.124176E+10 | 0.00 | 1849688.53 | 116589.95 | 0.00 | 36796456.75 | 0.00 | 0.24 |
August | 1830549.00 | 0.754236E+09 | 0.00 | 3414517.65 | 242108.17 | 0.00 | 0.154603E+09 | 0.00 | 0.31 |
September | 2843062.27 | 0.617563E+09 | 0.00 | 3232360.38 | 97977.14 | 0.00 | 0.304933E+09 | 0.00 | 0.29 |
October | 44246296.73 | 0.129578E+09 | 0.00 | 4720821.68 | 0.00 | 280604.46 | 0.177367E+10 | 0.00 | 0.48 |
November | 0.453173E+09 | 0.00 | 0.00 | 1208873.43 | 0.00 | 0.165694E+09 | 0.945539E+09 | 0.00 | 0.27 |
December | 0.491951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869423E+09 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.264485E+10 | 0.361323E+10 | 0.00 | 24601701.00 | 456675.27 | 0.259301E+10 | 0.550353E+10 | 0.00 | 0.26 |
Minimum of Months | 4139.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.625339E+09 | 0.124176E+10 | 0.00 | 4720821.68 | 242108.17 | 0.869423E+09 | 0.177367E+10 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.314469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190113E+09 | 0.00 | 0.00 | 0.17 |
February | 0.257870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76154954.48 | 0.00 | 0.00 | 0.18 |
March | 0.275376E+10 | 0.00 | 0.00 | 0.00 | 2553559.99 | 28407262.71 | 0.00 | 0.00 | 0.19 |
April | 0.198600E+10 | 42810799.42 | 0.00 | 1209644.81 | 14055737.24 | 0.00 | 0.348152E+09 | 0.00 | 0.21 |
May | 0.498502E+09 | 0.297940E+09 | 0.00 | 6145499.70 | 92554.71 | 0.00 | 0.131659E+10 | 0.00 | 0.30 |
June | 22463672.26 | 0.119568E+10 | 0.00 | 9168488.02 | 0.00 | 0.00 | 0.109127E+10 | 0.00 | 0.33 |
July | 1661509.32 | 0.221124E+10 | 0.00 | 5070856.33 | 4037.45 | 0.00 | 0.747639E+09 | 0.00 | 0.33 |
August | 78680107.47 | 0.121937E+10 | 0.00 | 8425752.49 | 0.00 | 0.00 | 0.154429E+10 | 0.00 | 0.36 |
September | 0.179984E+09 | 0.724894E+09 | 0.00 | 8693605.06 | 0.00 | 0.00 | 0.146506E+10 | 0.00 | 0.34 |
October | 0.211846E+10 | 0.116594E+09 | 0.00 | 2416688.72 | 0.00 | 0.00 | 0.154605E+10 | 0.00 | 0.27 |
November | 0.312137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16473035.31 | 0.00 | 0.00 | 0.17 |
December | 0.336196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283362E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.198462E+11 | 0.580852E+10 | 0.00 | 41130535.13 | 16705889.40 | 0.594510E+09 | 0.805906E+10 | 0.00 | 0.25 |
Minimum of Months | 1661509.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.336196E+10 | 0.221124E+10 | 0.00 | 9168488.02 | 14055737.24 | 0.283362E+09 | 0.154605E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.401825E+12 | 0.324837E+11 | 0.00 | 0.459620E+10 | 0.279050E+10 |
February | 0.414940E+12 | 0.235351E+11 | 0.00 | 0.370269E+10 | 0.165994E+10 |
March | 0.644805E+12 | 0.282115E+11 | 0.00 | 0.400254E+10 | 0.848209E+09 |
April | 0.707685E+12 | 0.214175E+11 | 0.00 | 0.346431E+10 | 0.524914E+10 |
May | 0.769441E+12 | 0.237487E+11 | 0.00 | 0.188502E+10 | 0.225637E+11 |
June | 0.770972E+12 | 0.285609E+11 | 0.00 | -516329937.5 | 0.431483E+11 |
July | 0.756412E+12 | 0.260856E+11 | 0.00 | -0.270253E+10 | 0.484683E+11 |
August | 0.700734E+12 | 0.311595E+11 | 0.00 | -196813938.2 | 0.414848E+11 |
September | 0.648695E+12 | 0.284085E+11 | 0.00 | 0.618465E+09 | 0.307880E+11 |
October | 0.561923E+12 | 0.341956E+11 | 0.00 | 0.523940E+10 | 0.767313E+10 |
November | 0.421060E+12 | 0.360655E+11 | 0.00 | 0.470346E+10 | 0.686069E+09 |
December | 0.330064E+12 | 0.290619E+11 | 0.00 | 0.500669E+10 | 0.362090E+10 |
Annual Sum or Average | 0.712855E+13 | 0.342934E+12 | 0.00 | 0.298031E+11 | 0.208981E+12 |
Minimum of Months | 0.330064E+12 | 0.214175E+11 | 0.00 | -0.270253E+10 | 0.686069E+09 |
Maximum of Months | 0.770972E+12 | 0.360655E+11 | 0.00 | 0.523940E+10 | 0.484683E+11 |