Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 10:43:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1298.57 | 268.57 | 268.57 |
Net Site Energy | 1298.57 | 268.57 | 268.57 |
Total Source Energy | 4112.57 | 850.56 | 850.56 |
Net Source Energy | 4112.57 | 850.56 | 850.56 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1298.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 37.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 149.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 516.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 187.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 105.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 268.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 134.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 105.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 268.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1298.568 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1298.568 | 100.00 |
Total On-Site and Utility Electric Sources | 1298.568 | 100.00 |
Total Electricity End Uses | 1298.568 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 71.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3150.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.4109 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 15.4192 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 6.6082 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 9.3337 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.4109 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.4192 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 6.6082 | 46.45 | 2.5587 | |
Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 9.3337 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 9.3337 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 02-JAN-07:40 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 610.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48245.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 33916.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13405.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1042.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 106723.60 | 610.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 610.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48245.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 33916.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11100.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1042.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 948.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1634.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 425.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 592.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4112.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 196.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 850.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 196.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 850.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.55 |
ZONE2 FINE STORAGE DIRECT AIR | 5.01 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE HEATING COIL | 36616.26 |
PSZ-FINE STORAGE HEATING COIL | 149515.75 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.00 | 1.00 | 1.55 |
PSZ-FINE STORAGE | 5.01 | 5.01 | 5.01 | 5.01 | 5.01 | 5.01 | 1.00 | 1.00 | 5.01 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.55 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 5.01 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.55 | 1696.82 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 5.01 | 9403.73 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.55 | 32751.12 | 36616.26 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 5.01 | 5.01 | 5.01 | 5.01 | 124376.72 | 149515.75 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.55 | 0.775154 | 1.55 | 32751.12 | 16787.72 | 32751.12 | 0.755090 | 0.755090 |
PSZ-FINE STORAGE COOLING COIL | 5.01 | 2.50 | 5.01 | 124376.72 | 62188.35 | 124376.72 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.411 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.485 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.419 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.419 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 6.608 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 9.167 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2466.121 | 10.411 | 193.440 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2466.121 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 21485.263 | 15.419 | 716.175 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21485.263 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 21178.335 | 6.608 | 306.932 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 21178.335 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6762 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6762 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6762 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.380 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.380 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.380 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.74295144E-12 | -0.15622792E-15 | 0.15818062E-14 | 0.12467337E-15 |
8 | 3 | -0.37175021E-03 | 0.46723563E-06 | -0.53800768E-04 | 0.14257918E-12 |
9 | 2 | 1.7087087 | 0.10360435E-01 | 1.1170133 | -0.71269727E-04 |
10 | 1 | -7.1697731 | 0.27078767 | -16.948219 | 0.32746695 |
11 | 0 | 5.9162373 | 0.17365257 | 16.286061 | |
12 | 4 | 0.74295144E-12 | -0.15622792E-15 | 0.15818062E-14 | 0.12467337E-15 |
13 | 3 | -0.37175021E-03 | 0.46723563E-06 | -0.53800768E-04 | 0.14257918E-12 |
14 | 2 | 1.7087087 | 0.10360435E-01 | 1.1170133 | -0.71269727E-04 |
15 | 1 | -7.1697731 | 0.27078767 | -16.948219 | 0.32746695 |
16 | 0 | 5.9162373 | 0.17365257 | 16.286061 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.15818062E-14 | -0.15622792E-15 | 0.74295144E-12 | 0.12467337E-15 |
85 | 3 | -0.53800768E-04 | 0.46723563E-06 | -0.37175021E-03 | 0.14257918E-12 |
86 | 2 | 1.1170133 | 0.10360435E-01 | 1.7087087 | -0.71269727E-04 |
87 | 1 | -16.948219 | 0.27078767 | -7.1697731 | 0.32746695 |
88 | 0 | 16.286061 | 0.17365257 | 5.9162373 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.113_SHGC_SOUTH_0.25 | 34 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
2 | NONRESWINDOW_U_1.113_SHGC_NORTH_0.25 | 35 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
3 | NONRESWINDOW_U_1.113_SHGC_EAST_0.25 | 36 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
4 | NONRESWINDOW_U_1.113_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.315 | 5.826 | 1.090 | 0.251 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.35 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.356 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41449 | 0.41449 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37924 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.350 | 0.352 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 0.153 | 6.473E-004 | 9.992E-004 | 0.546 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.780 | 5.598E-004 | 3.565E-004 | 0.951 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 3.433 | 1.071E-003 | 6.996E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 15694.58398 | 18833.50078 | 1.29192 | 1.55031 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 42.31500 | 1.07810E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5200.03079 | 6240.03695 | 0.14570 | 0.17484 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 65042.53617 | 78051.04340 | 4.17388 | 5.00865 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 5686.01393 | 6823.21671 | 0.13452 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 24587.49 | 1.55031 | 1.55031 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 5042.60 | 0.17484 | 0.17484 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 97301.06 | 5.00865 | 5.00865 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 14023.03 | 0.42471 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55031 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.00865 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55031 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55031 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55031 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55031 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55031 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.55031 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.00865 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.00865 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.00865 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 5.00865 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.00865 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 5.00865 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.55031 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 5.00865 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55031 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55031 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1696.82068 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55031 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55031 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55031 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.55031 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55031 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77515 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.55031 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32751.12000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16787.72224 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32751.12000 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75509 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75509 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32751.12000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36616.26403 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 36616.26403 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.00865 |
47 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.00865 |
49 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 9403.73072 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.00865 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.00865 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.00865 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.00865 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.00865 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.50433 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.00865 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 124376.72000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 62188.35361 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 124376.72000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 124376.72000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 149515.75173 |
64 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
66 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 149515.75173 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 31547.0 | 11.09 | 10.45 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 120483.5 | 10.53 | 9.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.2123840653E-002 | 2.6206233268E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 5.4861691890E-002 | 4.0993983458E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.0299938421E-002 | 2.8860244988E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8742.07 | 373.03 | 0.00 | -122.5 | 1245.63 | 10238.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.582 | 0.676 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.582 | 0.676 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.113_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.315 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.113_SHGC_WEST_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 6.315 | 0.251 | 0.252 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.113_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.315 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.113_SHGC_NORTH_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 6.315 | 0.251 | 0.252 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.356 | 0.352 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.350 | 0.352 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 5.377 | 0.299 | 0.297 | |||||||||||||||||
North Total or Average | 6.51 | 6.315 | 0.251 | 0.252 | |||||||||||||||||
Non-North Total or Average | 26.02 | 5.142 | 0.311 | 0.309 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.4109 | 236.88 | 2466.12 | LightsWired | LTG_SCH_OFFICE | 66.47 | 168.00 | 65.44 | 0.0000 | Y | 30.29 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.4192 | 1393.41 | 21485.26 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 244.70 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 6.6082 | 3204.84 | 21178.33 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 241.20 |
Interior Lighting Total | 9.3337 | 4835.13 | 45129.72 | 516.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.85 | 83.85 | 134.30 | |
Exterior Lighting Total | 8532.22 | 134.30 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32751.12 | 24730.04 | 8021.08 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 124376.72 | 87198.03 | 37178.69 | 0.70 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 31547.0 | 11.09 | 10.45 | ||||
PSZ-FINE STORAGE COOLING COIL | 120483.5 | 10.53 | 9.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39959.00 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 36616.26 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 149515.75 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.55 | 1696.82 | 1094.51 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.59 | 1110.54 | 5.01 | 9403.73 | 1877.50 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 15694.58 | 18833.50 | 79.51 | 1.292 | 1.550 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 23.90 | 23.90 | 0.00834 | 42.31 | 0.01078 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 65042.54 | 78051.04 | 56.01 | 4.174 | 5.009 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00850 | 42.80 | 0.01078 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 0.00 | 42.40 | 0.01086 | 42.70 | 0.01078 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5200.03 | 6240.04 | 26.34 | 0.146 | 0.175 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00898 | 12.70 | 0.00915 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 5686.01 | 6823.22 | 4.90 | 0.135 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00877 | 12.70 | 0.00915 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 14.71 | 0.00932 | 12.70 | 0.00915 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.55 | 1.55 | 0.17 | 0.17 | 1.5503 | 1.5503 | 1.5503 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 5.01 | 5.01 | 0.42 | 0.42 | 5.0087 | 5.0087 | 5.0087 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 32751.120 | 24730.043 | 1.550310 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 32751.12 | 30253.85 | 1.550310 | 26.00 | 17.09 | 0.00850563 | 12.00 | 11.25 | 0.00800000 | 42.31 | 0.01078097 | 23.73 | 6.5977 | 23.90 | 0.00834491 | 45.1867 | 15694.58 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 36616.264 | 36616.264 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 36616.26 | 36616.26 | 1.550308 | 20.47 | 15.54 | 0.00899260 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 6.5977 | 21.10 | 0.00898124 | 57.5822 | 5200.03 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 124376.720 | 87198.031 | 5.008650 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 124376.72 | 113871.18 | 5.008650 | 29.59 | 18.46 | 0.00869566 | 12.00 | 11.25 | 0.00800000 | 42.80 | 0.01078182 | 23.86 | 8.4796 | 26.70 | 0.00850237 | 38.9692 | 65042.54 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 149515.752 | 149515.752 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 149515.75 | 149515.75 | 5.008650 | 15.32 | 13.46 | 0.00886190 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.4796 | 15.56 | 0.00883489 | 80.2189 | 5494.91 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32751.120 | 24730.043 | 1.550310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6515 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.550308 | 1.86594299 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 32751.12 | 30253.85 | 1.0000 | 1.86594534 | 1.550310 | 26.00 | 17.09 | 0.00850563 | 47813.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32751.12 | 42.31 | 0.01078097 | 23.73 | 0.10228463 | 6.5977 | 23.90 | 0.00834491 | 23.90 | 0.00834491 | 45.1867 | 15694.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36616.264 | 36616.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.550308 | 1.86594299 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 36616.26 | 36616.26 | 1.0000 | 1.86594299 | 1.550308 | 20.47 | 15.54 | 0.00899260 | 43402.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36616.26 | 12.70 | 0.00915345 | 12.70 | 0.10228463 | 6.5977 | 21.02 | 0.00898124 | 21.10 | 0.00898124 | 57.5822 | 5200.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 124376.720 | 87198.031 | 5.008650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0048 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.008650 | 6.02838660 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 124376.72 | 113871.18 | 1.0000 | 6.02838600 | 5.008650 | 29.59 | 18.46 | 0.00869566 | 51959.1 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 124376.72 | 42.80 | 0.01078182 | 23.86 | 0.42471127 | 8.4796 | 26.70 | 0.00850237 | 26.70 | 0.00850237 | 38.9692 | 65042.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 149515.752 | 149515.752 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.008650 | 6.02838660 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 149515.75 | 149515.75 | 1.0000 | 6.02838660 | 5.008650 | 15.32 | 13.46 | 0.00886190 | 37807.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 149515.75 | 12.70 | 0.00915345 | 12.70 | 0.42471127 | 8.4796 | 15.56 | 0.00883489 | 15.56 | 0.00883489 | 80.2189 | 5494.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3400.83 | 399.50 | 340.00 |
ZONE2 FINE STORAGE | 3568.83 | 3008.17 | 2969.17 |
ZONE3 BULK STORAGE | 3488.17 | 3146.33 | 3044.17 |
Facility | 3581.50 | 3268.83 | 3150.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 120.00 | 0.00 | 70.33 |
ZONE2 FINE STORAGE | 0.00 | 577.33 | 0.00 | 11.50 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 677.17 | 0.00 | 71.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.353 | 0.493 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.497 | 0.400 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.179 | 0.000 | 2.198 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.55 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1275754.80 | 0.00 | 1275754.80 | 2685553.59 | 3961308.40 | 3225648.14 | 5390.80 | 3369.20 | 0.00 | 486.41 |
ZONE2 FINE STORAGE | 5738905.55 | 0.00 | 5738905.55 | 9501763.81 | 15240669.35 | 13393694.68 | 5404.04 | 3355.96 | 0.00 | 2018.31 |
ZONE3 BULK STORAGE | 0.00 | 0.57E+09 | 0.57E+09 | 39432196.75 | 0.61E+09 | 30805497.77 | 4203.11 | 8.08 | 4548.80 | 5105.94 |
Total Facility | 7014660.35 | 0.57E+09 | 0.58E+09 | 51619514.15 | 0.63E+09 | 47424840.58 | 6764.05 | 3395.54 | 4548.80 | 5106.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0960 | 0.0000 | 0.0960 | 0.1339 | 0.2299 | 0.1023 | 267.02 | 3368.98 | 0.00 |
ZONE2 FINE STORAGE | 0.3908 | 0.0000 | 0.3908 | 0.3144 | 0.7052 | 0.4247 | 302.33 | 3333.67 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 19.9003 | 19.9003 | 1.6442 | 21.5444 | 0.9768 | 1538.78 | 4.08 | 2093.13 |
Total Facility | 0.4868 | 19.9003 | 20.3871 | 2.0924 | 22.4795 | 1.5038 | 1640.05 | 3369.02 | 2093.13 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1848110.56 | 0.00 | 1848110.56 | 3225648.14 | 5377.78 | 1.05 | 3381.17 | 478.70 |
PSZ-FINE STORAGE | 8313613.18 | 0.00 | 8313613.18 | 13393694.68 | 5358.36 | 3.79 | 3397.85 | 2015.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1391 | 0.0000 | 0.1391 | 0.1023 | 255.72 | 0.80 | 3379.48 |
PSZ-FINE STORAGE | 0.5661 | 0.0000 | 0.5661 | 0.4247 | 301.46 | 0.18 | 3334.36 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 4011.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5445.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1432 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6001 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 383 |
Defaulted Fields | 319 |
Fields with Defaults | 1020 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1298.57 | 5771.67 | 01-JAN-07:10 | 106723.60 | 10-AUG-16:00 |
Electricity:Building | 692.77 | 5288.67 | 01-JAN-00:10 | 50600.89 | 06-FEB-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.24 | 1022.31 | 01-JAN-00:10 | 3831.41 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 655.48 | 5288.67 | 01-JAN-00:10 | 48295.59 | 02-JAN-09:10 |
InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.29 | 448.56 | 01-JAN-00:10 | 1918.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 516.19 | 4714.92 | 01-JAN-00:10 | 38182.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 244.70 | 2148.53 | 01-JAN-00:10 | 18262.47 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 385.83 | 2117.83 | 01-JAN-00:10 | 28507.00 | 06-FEB-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 241.20 | 2117.83 | 01-JAN-00:10 | 18001.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 187.11 | 0.00 | 01-JAN-00:10 | 13405.85 | 08-FEB-14:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.28 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity | 37.28 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.28 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
ElectricityPurchased:Facility | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
ElectricityNet:Plant | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1298.57 | 5771.67 | 05-FEB-11:30 | 106723.60 | 10-AUG-16:00 |
Electricity:HVAC | 449.43 | 0.00 | 01-JAN-00:10 | 59346.17 | 10-AUG-16:00 |
General:Fans:Electricity | 149.82 | 0.00 | 01-JAN-00:10 | 11100.55 | 30-NOV-10:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 299.61 | 0.00 | 01-JAN-00:10 | 48245.62 | 10-AUG-16:00 |
General:Cooling:Electricity | 299.61 | 0.00 | 01-JAN-00:10 | 48245.62 | 10-AUG-16:00 |
ExteriorLights:Electricity | 134.30 | 0.00 | 01-JAN-07:10 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 134.30 | 0.00 | 01-JAN-07:10 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 22.07 | 483.00 | 09-FEB-06:10 | 1740.30 | 12-JAN-12:10 |
WaterSystems:Electricity | 22.07 | 483.00 | 09-FEB-06:10 | 1740.30 | 12-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 22.07 | 483.00 | 09-FEB-06:10 | 1740.30 | 12-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 610.65 | 02-JAN-07:40 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 610.65 | 02-JAN-07:40 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 610.65 | 02-JAN-07:40 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 610.65 | 02-JAN-07:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1495.30 | 0.00 | 01-JAN-00:10 | 214053.21 | 10-AUG-16:00 |
EnergyTransfer:Building | 549.28 | 0.00 | 01-JAN-00:10 | 75804.27 | 09-JUN-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 119.34 | 0.00 | 01-JAN-00:10 | 19397.25 | 16-AUG-12:00 |
Heating:EnergyTransfer | 1.37 | 0.00 | 01-JAN-00:10 | 6573.29 | 02-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.11 | 0.00 | 01-JAN-00:10 | 1089.04 | 02-JAN-07:40 |
General:Heating:EnergyTransfer | 1.37 | 0.00 | 01-JAN-00:10 | 6573.29 | 02-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.11 | 0.00 | 01-JAN-00:10 | 1089.04 | 02-JAN-07:40 |
Cooling:EnergyTransfer | 547.92 | 0.00 | 01-JAN-00:10 | 75804.27 | 09-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 119.24 | 0.00 | 01-JAN-00:10 | 19397.25 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 547.92 | 0.00 | 01-JAN-00:10 | 75804.27 | 09-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 119.24 | 0.00 | 01-JAN-00:10 | 19397.25 | 16-AUG-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 429.94 | 0.00 | 01-JAN-00:10 | 65240.02 | 21-MAY-13:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.26 | 0.00 | 01-JAN-00:10 | 6573.29 | 02-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.26 | 0.00 | 01-JAN-00:10 | 6573.29 | 02-JAN-17:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 428.68 | 0.00 | 01-JAN-00:10 | 65240.02 | 21-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 428.68 | 0.00 | 01-JAN-00:10 | 65240.02 | 21-MAY-13:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 946.02 | 0.00 | 01-JAN-00:10 | 144988.82 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 391.86 | 02-JAN-07:40 |
CoolingCoils:EnergyTransfer | 946.02 | 0.00 | 01-JAN-00:10 | 144988.82 | 22-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.106 | -119.236 | 0.000 | 0.000 | 9.117 | 30.293 | 31.946 | 17.420 | 0.000 | 15.901 | 24.156 | 0.000 | -5.190 | 0.000 | -4.513 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.262 | -428.672 | 0.000 | 0.000 | 17.134 | 244.699 | 0.000 | 0.000 | 0.000 | 45.736 | 139.816 | 0.000 | 0.000 | 0.000 | -19.975 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.041 | 241.203 | 107.344 | 112.755 | 0.000 | 96.408 | 24.518 | 0.000 | -37.670 | 0.000 | -564.599 | -0.005 |
Total Facility | 0.000 | 0.000 | 1.369 | -547.908 | 0.000 | 0.000 | 46.292 | 516.195 | 139.290 | 130.175 | 0.000 | 158.045 | 188.489 | 0.000 | -42.860 | 0.000 | -589.088 | -0.007 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | -31620.34 | 0.00 | 0.00 | 72.18 | 573.18 | 573.75 | 0.00 | 0.00 | 0.00 | 31283.44 | 0.00 | -542.44 | 0.00 | -339.77 | 0.00 |
ZONE2 FINE STORAGE | 19-NOV-13:32 | 0.00 | 0.00 | 0.00 | -100149.08 | 0.00 | 0.00 | 0.00 | 2148.53 | 0.00 | 0.00 | 0.00 | 4102.57 | 93897.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -120387.36 | 0.00 | 0.00 | 359.19 | 4839.54 | 2623.78 | 12.66 | 0.00 | 2489.84 | 205143.83 | 0.00 | -2335.48 | 0.00 | -92746.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-JAN-07:10 | 0.00 | 0.00 | 1242.42 | 0.00 | 0.00 | 0.00 | 181.92 | 1046.67 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -558.26 | 0.00 | -2833.03 | -35.98 |
ZONE2 FINE STORAGE | 01-MAR-07:03 | 0.00 | 0.00 | 6602.61 | 0.00 | 0.00 | 0.00 | 390.27 | 12891.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1891.00 | -17993.04 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-MAR-07:03 | -3630.18 | 3630.18 | 6602.61 | -3630.18 | 0.00 | 0.00 | 1513.86 | 26644.83 | 3006.28 | 0.00 | 0.00 | 133.12 | 0.00 | 0.00 | -620.42 | 0.00 | -6074.27 | -27575.82 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5503 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5503 | 0.0660 | 1.0000 | Not calculated | 0.1023 | 0.0660 | ||
PSZ-FINE STORAGE | 5.0087 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.0087 | 0.0848 | 1.0000 | Not calculated | 0.4247 | 0.0848 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5503 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5503 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0660 | ||
PSZ-FINE STORAGE | 5.0087 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.0087 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0848 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5503 | 1.5503 | 1.5503 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0087 | 5.0087 | 5.0087 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5503 | 1.5503 | 1.5503 | 1.5503 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.0087 | 5.0087 | 5.0087 | 5.0087 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5503 | 1.5503 | 1.5503 | No | 0.1023 | 0.5850 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0087 | 5.0087 | 5.0087 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5503 | 1.5503 | 1.5503 | 1.5503 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.0087 | 5.0087 | 5.0087 | 5.0087 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 71.83 |
Number of hours not met | 71.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 610.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 299.61 | 48245.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 516.19 | 38182.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 134.30 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 37.28 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 149.82 | 11100.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.07 | 1740.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 1298.57 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1298.57 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.76 |
Space Heating | 0.00 |
Space Cooling | 61.96 |
Fans (All) | 38.70 |
Service Water Heating | 4.57 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 268.57 |
Subtotal | 268.57 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 39.75 |
Space Heating | 0.00 |
Space Cooling | 23.07 |
Fans (All) | 14.41 |
Service Water Heating | 1.70 |
Receptacle Equipment | 10.73 |
Miscellaneous | 10.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3466. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 4919.67 | 3109.00 | 731.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3279.67 | 5480.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1753.33 | 3125.83 | 1963.50 | 1876.33 | 41.00 |
Min | 1753.33 | 3109.00 | 0.00 | 0.00 | 0.00 |
Max | 4919.67 | 5480.33 | 1963.50 | 1876.33 | 41.00 |
Average | 3317.56 | 3905.06 | 898.28 | 625.44 | 13.67 |
Sum | 9952.67 | 11715.17 | 2694.83 | 1876.33 | 41.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33021.33 | 5.50 | 0.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 29084.50 | 53634.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 23788.67 | 74621.83 | 46594.33 | 44169.50 | 2018.67 |
Min | 23788.67 | 5.50 | 0.00 | 0.00 | 0.00 |
Max | 33021.33 | 74621.83 | 46594.33 | 44169.50 | 2018.67 |
Average | 28631.50 | 42753.94 | 15531.50 | 14723.17 | 672.89 |
Sum | 85894.50 | 128261.83 | 46594.50 | 44169.50 | 2018.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4168.50 | 4344.00 | 247.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2371.67 | 6388.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1282.33 | 4337.50 | 1424.50 | 1402.67 | 313.00 |
Min | 1282.33 | 4337.50 | 0.00 | 0.00 | 0.00 |
Max | 4168.50 | 6388.33 | 1424.50 | 1402.67 | 313.00 |
Average | 2607.50 | 5023.28 | 557.33 | 467.56 | 104.33 |
Sum | 7822.50 | 15069.83 | 1672.00 | 1402.67 | 313.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31726.17 | 1300.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 25539.50 | 57179.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 17069.33 | 101931.83 | 31610.67 | 29865.17 | 10716.00 |
Min | 17069.33 | 1300.83 | 0.00 | 0.00 | 0.00 |
Max | 31726.17 | 101931.83 | 31610.67 | 29865.17 | 10716.00 |
Average | 24778.33 | 53470.72 | 10536.89 | 9955.06 | 3572.00 |
Sum | 74335.00 | 160412.17 | 31610.67 | 29865.17 | 10716.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458772E+10 | 25628.88 | 31-JAN-06:02 | 15.90 | 14.14 | 0.633053E+09 | 769.04 | 28-JAN-15:50 | 15.90 | 14.14 |
February | 0.519538E+10 | 25719.50 | 10-FEB-06:02 | 19.82 | 12.70 | 0.583484E+09 | 769.05 | 23-FEB-16:10 | 26.25 | 17.96 |
March | 0.751244E+10 | 31620.87 | 27-MAR-05:01 | 21.92 | 13.45 | 0.685720E+09 | 769.07 | 21-MAR-15:20 | 21.92 | 13.45 |
April | 0.867225E+10 | 31418.09 | 25-APR-05:01 | 23.83 | 13.00 | 0.635116E+09 | 769.11 | 28-APR-15:50 | 34.42 | 21.78 |
May | 0.119829E+11 | 30985.33 | 05-MAY-05:01 | 26.00 | 15.80 | 0.660791E+09 | 769.11 | 22-MAY-15:00 | 35.60 | 24.38 |
June | 0.131227E+11 | 27531.28 | 16-JUN-05:01 | 28.17 | 20.46 | 0.660904E+09 | 769.12 | 26-JUN-15:00 | 36.70 | 27.07 |
July | 0.142024E+11 | 29916.12 | 03-JUL-05:01 | 28.83 | 16.82 | 0.635614E+09 | 769.13 | 20-JUL-15:00 | 38.10 | 27.03 |
August | 0.156385E+11 | 25552.32 | 06-AUG-15:31 | 40.40 | 25.42 | 0.686595E+09 | 769.13 | 29-AUG-15:00 | 37.00 | 29.07 |
September | 0.127214E+11 | 24091.34 | 05-SEP-05:01 | 30.17 | 24.66 | 0.635517E+09 | 769.13 | 12-SEP-15:00 | 37.70 | 27.44 |
October | 0.110075E+11 | 29565.86 | 20-OCT-05:01 | 23.17 | 16.23 | 0.635384E+09 | 769.10 | 03-OCT-13:09 | 23.17 | 16.23 |
November | 0.847150E+10 | 28474.02 | 18-NOV-06:01 | 20.08 | 16.00 | 0.609769E+09 | 769.09 | 06-NOV-15:09 | 20.08 | 16.00 |
December | 0.612295E+10 | 28169.12 | 13-DEC-06:02 | 15.02 | 12.69 | 0.634770E+09 | 769.07 | 01-DEC-15:20 | 15.02 | 12.69 |
Annual Sum or Average | 0.119238E+12 | 0.769672E+10 | ||||||||
Minimum of Months | 0.458772E+10 | 24091.34 | 15.02 | 12.69 | 0.583484E+09 | 769.04 | 15.02 | 12.69 | ||
Maximum of Months | 0.156385E+11 | 31620.87 | 40.40 | 25.42 | 0.686595E+09 | 769.13 | 38.10 | 29.07 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.778546E+10 | 21786.02 | 22-JAN-14:35 | 26.00 | 16.51 | 0.182954E+10 | 2246.95 | 28-JAN-15:30 | 25.25 | 17.93 |
February | 0.111574E+11 | 63398.33 | 05-FEB-12:53 | 31.10 | 19.64 | 0.169589E+10 | 2267.22 | 13-FEB-09:30 | 17.70 | 13.29 |
March | 0.199305E+11 | 99619.98 | 26-MAR-15:53 | 31.80 | 18.54 | 0.199878E+10 | 2247.04 | 21-MAR-13:30 | 31.80 | 18.54 |
April | 0.293120E+11 | 100032.38 | 02-APR-11:32 | 33.80 | 18.27 | 0.185361E+10 | 2247.13 | 29-APR-13:20 | 35.73 | 21.50 |
May | 0.483267E+11 | 98215.14 | 04-MAY-18:23 | 35.00 | 18.70 | 0.192889E+10 | 2247.17 | 22-MAY-14:30 | 37.25 | 23.36 |
June | 0.539616E+11 | 96281.31 | 15-JUN-17:04 | 37.67 | 20.98 | 0.192892E+10 | 2247.18 | 03-JUN-14:09 | 37.67 | 20.98 |
July | 0.620177E+11 | 94405.38 | 21-JUL-23:03 | 37.50 | 23.50 | 0.185496E+10 | 2247.25 | 11-JUL-15:39 | 37.50 | 23.50 |
August | 0.651606E+11 | 93075.14 | 06-AUG-07:42 | 35.82 | 22.90 | 0.200341E+10 | 2247.24 | 17-AUG-15:39 | 39.80 | 25.84 |
September | 0.519389E+11 | 91598.04 | 04-SEP-08:23 | 34.55 | 21.42 | 0.185474E+10 | 2247.19 | 05-SEP-14:30 | 39.50 | 25.12 |
October | 0.410286E+11 | 100145.55 | 29-OCT-11:02 | 33.28 | 15.98 | 0.185479E+10 | 2247.14 | 04-OCT-15:50 | 33.28 | 15.98 |
November | 0.250669E+11 | 100153.71 | 19-NOV-13:32 | 31.00 | 17.39 | 0.177966E+10 | 2247.00 | 13-NOV-13:20 | 31.00 | 17.39 |
December | 0.129914E+11 | 61695.00 | 03-DEC-13:13 | 28.87 | 18.94 | 0.184783E+10 | 2247.02 | 01-DEC-13:30 | 28.87 | 18.94 |
Annual Sum or Average | 0.428678E+12 | 0.224310E+11 | ||||||||
Minimum of Months | 0.778546E+10 | 21786.02 | 26.00 | 15.98 | 0.169589E+10 | 2246.95 | 17.70 | 13.29 | ||
Maximum of Months | 0.651606E+11 | 100153.71 | 37.67 | 23.50 | 0.200341E+10 | 2267.22 | 39.80 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.379518E+10 | 5606.69 | 28-JAN-14:39 | 26.67 | 16.87 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.402515E+10 | 7206.70 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.537657E+10 | 9097.65 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.562643E+10 | 9097.65 | 24-APR-12:20 | 37.13 | 17.91 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.697759E+10 | 9097.65 | 04-MAY-10:09 | 37.72 | 18.25 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.725378E+10 | 9097.65 | 01-JUN-08:00 | 37.00 | 22.08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.725634E+10 | 9097.65 | 01-JUL-09:39 | 36.80 | 26.55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.788006E+10 | 9097.65 | 01-AUG-08:00 | 37.00 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.688427E+10 | 9097.65 | 01-SEP-10:09 | 36.08 | 24.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.615963E+10 | 9097.65 | 02-OCT-12:30 | 36.35 | 19.25 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.511966E+10 | 7829.40 | 01-NOV-14:20 | 32.67 | 26.20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.460470E+10 | 6339.61 | 02-DEC-14:00 | 27.00 | 19.71 |
Annual Sum or Average | 0.00 | 0.709594E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.379518E+10 | 5606.69 | 26.67 | 16.87 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.788006E+10 | 9097.65 | 37.72 | 26.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46592417.65 | 1242.50 | 25-JAN-07:10 | 17.42 |
February | 28515792.11 | 1124.49 | 14-FEB-07:15 | 13.67 |
March | 12353629.47 | 1129.93 | 17-MAR-06:10 | 16.83 |
April | 107957.70 | 359.86 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 18534919.93 | 1089.14 | 29-DEC-07:10 | 15.33 |
Annual Sum or Average | 0.106105E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.67 | |
Maximum of Months | 46592417.65 | 1242.50 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549493E+09 | 6573.29 | 02-JAN-17:50 | 20.17 |
February | 0.292661E+09 | 6276.84 | 15-FEB-08:00 | 23.20 |
March | 0.163898E+09 | 6602.48 | 01-MAR-07:03 | 24.17 |
April | 28153946.99 | 4766.55 | 06-APR-06:05 | 21.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 14095.16 | 93.97 | 07-JUN-06:05 | 24.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 255286.05 | 2127.38 | 27-OCT-06:04 | 23.93 |
November | 12750768.26 | 4439.99 | 29-NOV-07:05 | 20.67 |
December | 0.215268E+09 | 6380.87 | 27-DEC-07:13 | 20.93 |
Annual Sum or Average | 0.126249E+10 | |||
Minimum of Months | 0.00 | 0.00 | 20.17 | |
Maximum of Months | 0.549493E+09 | 6602.48 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253372E+10 | 1918.91 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.231087E+10 | 1918.91 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.264030E+10 | 1918.91 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.249496E+10 | 1918.91 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.258701E+10 | 1918.91 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.254825E+10 | 1918.91 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.253372E+10 | 1918.91 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.264030E+10 | 1918.91 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.249496E+10 | 1918.91 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.253372E+10 | 1918.91 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.244167E+10 | 1918.91 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.253372E+10 | 1918.91 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.302932E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.231087E+10 | 1918.91 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.264030E+10 | 1918.91 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.203538E+11 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.186290E+11 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.215218E+11 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.201682E+11 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.209378E+11 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.207522E+11 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.203538E+11 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.215218E+11 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.201682E+11 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.203538E+11 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.195842E+11 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.203538E+11 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.244699E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.186290E+11 | 18262.47 | 0.00 | 0.00 | |
Maximum of Months | 0.215218E+11 | 18262.47 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.200631E+11 | 18001.58 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.183629E+11 | 18001.58 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.212143E+11 | 18001.58 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.198801E+11 | 18001.58 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.206387E+11 | 18001.58 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.204557E+11 | 18001.58 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.200631E+11 | 18001.58 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.212143E+11 | 18001.58 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.198801E+11 | 18001.58 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.200631E+11 | 18001.58 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.193045E+11 | 18001.58 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.200631E+11 | 18001.58 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.241203E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.183629E+11 | 18001.58 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.212143E+11 | 18001.58 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11678690.09 | 0.117697E+10 |
February | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124133E+09 | 0.983335E+09 |
March | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453860E+09 | 0.649162E+09 |
April | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887779E+09 | 0.313538E+09 |
May | 0.144276E+10 | 0.258701E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194245E+10 | 58315240.10 |
June | 0.144276E+10 | 0.254825E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241355E+10 | 21454245.91 |
July | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278523E+10 | 413301.12 |
August | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308188E+10 | 219038.86 |
September | 0.138726E+10 | 0.249496E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209601E+10 | 22067507.14 |
October | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137867E+10 | 91086152.24 |
November | 0.133177E+10 | 0.244167E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628768E+09 | 0.353119E+09 |
December | 0.138726E+10 | 0.253372E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97193862.73 | 0.843736E+09 |
Annual Sum or Average | 0.168137E+11 | 0.302932E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159012E+11 | 0.451342E+10 |
Minimum of Months | 0.127628E+10 | 0.231087E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11678690.09 | 219038.86 |
Maximum of Months | 0.149825E+10 | 0.264030E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308188E+10 | 0.117697E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2798466.06 | 0.484968E+10 |
February | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178946E+09 | 0.479393E+10 |
March | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684674E+09 | 0.313144E+10 |
April | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187821E+10 | 0.136779E+10 |
May | 0.339505E+10 | 0.209378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550469E+10 | 0.184200E+09 |
June | 0.339505E+10 | 0.207522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725194E+10 | 44464680.39 |
July | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951575E+10 | 0.00 |
August | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964265E+10 | 0.00 |
September | 0.326447E+10 | 0.201682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644647E+10 | 36441345.39 |
October | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358782E+10 | 0.330557E+09 |
November | 0.313390E+10 | 0.195842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996170E+09 | 0.140957E+10 |
December | 0.326447E+10 | 0.203538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46052355.12 | 0.382727E+10 |
Annual Sum or Average | 0.395654E+11 | 0.244699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457362E+11 | 0.199753E+11 |
Minimum of Months | 0.300332E+10 | 0.186290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2798466.06 | 0.00 |
Maximum of Months | 0.352563E+10 | 0.215218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964265E+10 | 0.484968E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28285856.97 | 0.149225E+11 |
February | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278493E+09 | 0.186400E+11 |
March | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488240E+09 | 0.161394E+11 |
April | 0.750829E+10 | 0.198801E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241088E+09 | 0.971449E+10 |
May | 0.780862E+10 | 0.206387E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810985E+09 | 0.285578E+10 |
June | 0.780862E+10 | 0.204557E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829149E+09 | 0.254363E+10 |
July | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783360E+09 | 0.197985E+10 |
August | 0.810895E+10 | 0.212143E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625305E+09 | 0.227947E+10 |
September | 0.750829E+10 | 0.198801E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478180E+09 | 0.236349E+10 |
October | 0.750829E+10 | 0.200631E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224390E+09 | 0.413856E+10 |
November | 0.720796E+10 | 0.193045E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15447294.86 | 0.953554E+10 |
December | 0.750829E+10 | 0.200631E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13781475.20 | 0.173581E+11 |
Annual Sum or Average | 0.910005E+11 | 0.241203E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481670E+10 | 0.102471E+12 |
Minimum of Months | 0.690763E+10 | 0.183629E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13781475.20 | 0.197985E+10 |
Maximum of Months | 0.810895E+10 | 0.212143E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829149E+09 | 0.186400E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1918.91 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.71 | 23-JAN-13:00 | 5048.81 | 19-JAN-07:05 |
February | 1680.92 | 01-FEB-08:09 | 1918.91 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2816.31 | 07-FEB-13:00 | 4346.08 | 13-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1918.91 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5653.76 | 27-MAR-11:10 | 3697.81 | 06-MAR-07:05 |
April | 1680.92 | 01-APR-07:10 | 1918.91 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6328.07 | 28-APR-12:00 | 3009.72 | 05-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1918.91 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6573.12 | 10-MAY-16:10 | 1380.97 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1918.91 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9144.88 | 09-JUN-16:10 | 463.10 | 07-JUN-05:01 |
July | 1680.92 | 01-JUL-07:10 | 1918.91 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8928.89 | 21-JUL-17:00 | 34.70 | 03-JUL-04:30 |
August | 1680.92 | 01-AUG-07:10 | 1918.91 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8538.25 | 16-AUG-12:00 | 32.38 | 27-AUG-06:00 |
September | 1680.92 | 01-SEP-07:10 | 1918.91 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7147.81 | 05-SEP-16:10 | 506.88 | 25-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 1918.91 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6641.20 | 19-OCT-16:10 | 735.83 | 30-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1918.91 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.12 | 01-NOV-16:10 | 2982.37 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1918.91 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1629.29 | 01-DEC-13:00 | 3889.58 | 18-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.71 | 32.38 | |||||
Maximum of Months | 1680.92 | 1918.91 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 9144.88 | 5048.81 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 18262.47 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.27 | 23-JAN-14:00 | 8974.65 | 19-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 18262.47 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4651.68 | 05-FEB-14:57 | 9347.06 | 10-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 18262.47 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9470.32 | 01-MAR-16:10 | 7065.34 | 25-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 18262.47 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13007.83 | 28-APR-15:10 | 4797.04 | 05-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 18262.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34850.15 | 21-MAY-12:51 | 2355.09 | 01-MAY-07:10 |
June | 3955.50 | 01-JUN-07:10 | 18262.47 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18328.67 | 09-JUN-15:40 | 1624.33 | 07-JUN-06:03 |
July | 3955.50 | 01-JUL-07:10 | 18262.47 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18373.70 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 3955.50 | 01-AUG-07:10 | 18262.47 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15698.44 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 3955.50 | 01-SEP-07:10 | 18262.47 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13446.28 | 02-SEP-16:00 | 1089.70 | 25-SEP-05:10 |
October | 3955.50 | 02-OCT-07:10 | 18262.47 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14317.30 | 19-OCT-15:10 | 3068.00 | 21-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 18262.47 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5287.95 | 01-NOV-15:10 | 4369.38 | 22-NOV-07:20 |
December | 3955.50 | 01-DEC-08:09 | 18262.47 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1868.68 | 10-DEC-12:57 | 8307.49 | 16-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.27 | 0.00 | ||||
Maximum of Months | 3955.50 | 18262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34850.15 | 9347.06 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 18001.58 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3034.24 | 23-JAN-13:10 | 25266.19 | 19-JAN-09:30 |
February | 9097.65 | 01-FEB-08:09 | 18001.58 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9140.14 | 05-FEB-14:53 | 30476.29 | 10-FEB-16:00 |
March | 9097.65 | 01-MAR-08:09 | 18001.58 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19030.08 | 01-MAR-11:00 | 57600.10 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 18001.58 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4754.77 | 25-APR-07:53 | 17983.59 | 04-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 18001.58 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8590.68 | 31-MAY-17:55 | 12901.50 | 01-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 18001.58 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6262.27 | 09-JUN-15:00 | 9653.47 | 07-JUN-06:00 |
July | 9097.65 | 01-JUL-07:10 | 18001.58 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6559.16 | 15-JUL-09:55 | 4755.32 | 16-JUL-16:51 |
August | 9097.65 | 01-AUG-07:10 | 18001.58 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10111.94 | 16-AUG-10:43 | 7051.16 | 10-AUG-20:52 |
September | 9097.65 | 01-SEP-07:10 | 18001.58 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4068.74 | 26-SEP-11:00 | 7755.05 | 23-SEP-07:05 |
October | 9097.65 | 02-OCT-07:10 | 18001.58 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5743.03 | 19-OCT-09:53 | 15163.91 | 21-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 18001.58 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.83 | 05-NOV-10:45 | 13477.67 | 22-NOV-06:01 |
December | 9097.65 | 01-DEC-08:09 | 18001.58 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.05 | 10-DEC-12:00 | 45115.45 | 15-DEC-11:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.83 | 4755.32 | |||||
Maximum of Months | 9097.65 | 18001.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19030.08 | 57600.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25628.88 | 31-JAN-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.37 |
February | 25719.50 | 10-FEB-06:02 | 924.51 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.25 |
March | 31620.87 | 27-MAR-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.77 |
April | 31418.09 | 25-APR-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.82 |
May | 30985.33 | 05-MAY-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.24 |
June | 27531.28 | 16-JUN-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 |
July | 29916.12 | 03-JUL-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 |
August | 25552.32 | 06-AUG-15:31 | 0.00 | 3588.50 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.61 | 0.00 |
September | 24091.34 | 05-SEP-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 | 0.00 |
October | 29565.86 | 20-OCT-05:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.85 |
November | 28474.02 | 18-NOV-06:01 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.67 |
December | 28169.12 | 13-DEC-06:02 | 1109.41 | 3439.05 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24091.34 | 0.00 | 2865.88 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31620.87 | 1849.01 | 5731.76 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.61 | 954.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21786.02 | 22-JAN-14:35 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.41 |
February | 63398.33 | 05-FEB-12:53 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3536.00 | 0.00 |
March | 99619.98 | 26-MAR-15:53 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2958.91 | 0.00 |
April | 100032.38 | 02-APR-11:32 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2036.88 | 0.00 |
May | 98215.14 | 04-MAY-18:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4906.02 | 0.00 |
June | 96281.31 | 15-JUN-17:04 | 0.00 | 15039.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6393.65 | 0.00 |
July | 94405.38 | 21-JUL-23:03 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2176.18 | 0.00 |
August | 93075.14 | 06-AUG-07:42 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.83 | 0.00 |
September | 91598.04 | 04-SEP-08:23 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3944.44 | 0.00 |
October | 100145.55 | 29-OCT-11:02 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2814.21 | 0.00 |
November | 100153.71 | 19-NOV-13:32 | 0.00 | 8594.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4102.57 | 0.00 |
December | 61695.00 | 03-DEC-13:13 | 0.00 | 6445.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 21786.02 | 0.00 | 4297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100153.71 | 0.00 | 15039.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6393.65 | 194.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.96 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5969.47 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4704.85 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2090.16 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.16 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.72 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1761.18 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.73 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2376.89 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7896.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 2117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 | |
Maximum of Months | 0.00 | 0.00 | 2117.83 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7896.14 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.866064E+11 | 73569.83 | 23-JAN-13:30 | 978170.36 | 610.65 | 02-JAN-07:40 |
February | 0.811981E+11 | 82064.98 | 07-FEB-13:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.970219E+11 | 86844.89 | 27-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.987490E+11 | 91873.95 | 28-APR-12:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.117459E+12 | 95985.22 | 31-MAY-14:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.124320E+12 | 101424.18 | 09-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.131882E+12 | 103836.48 | 14-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.139867E+12 | 106723.60 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.122927E+12 | 98174.49 | 06-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.112378E+12 | 93853.86 | 07-OCT-13:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.960284E+11 | 89750.17 | 01-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.901308E+11 | 80107.26 | 04-DEC-13:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.129857E+13 | 978170.36 | ||||
Minimum of Months | 0.811981E+11 | 73569.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.139867E+12 | 106723.60 | 978170.36 | 610.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.429506E+11 | 0.127215E+11 | 0.115358E+11 | 0.00 | 0.110128E+11 | 0.00 | 0.00 | 0.641010E+10 | 0.00 | 0.00 | 0.00 | 0.197554E+10 | 0.00 |
February | 0.393028E+11 | 0.110373E+11 | 0.105871E+11 | 0.00 | 0.102406E+11 | 0.00 | 0.00 | 0.825224E+10 | 0.00 | 0.00 | 0.00 | 0.177802E+10 | 0.00 |
March | 0.453764E+11 | 0.115595E+11 | 0.123431E+11 | 0.00 | 0.126941E+11 | 0.00 | 0.00 | 0.130928E+11 | 0.00 | 0.00 | 0.00 | 0.195606E+10 | 0.00 |
April | 0.425433E+11 | 0.104844E+11 | 0.114862E+11 | 0.00 | 0.137852E+11 | 0.00 | 0.00 | 0.186368E+11 | 0.00 | 0.00 | 0.00 | 0.181318E+10 | 0.00 |
May | 0.441635E+11 | 0.102694E+11 | 0.119357E+11 | 0.00 | 0.184032E+11 | 0.00 | 0.00 | 0.308685E+11 | 0.00 | 0.00 | 0.00 | 0.181911E+10 | 0.00 |
June | 0.437562E+11 | 0.967554E+10 | 0.118862E+11 | 0.00 | 0.195666E+11 | 0.00 | 0.00 | 0.377032E+11 | 0.00 | 0.00 | 0.00 | 0.173211E+10 | 0.00 |
July | 0.429506E+11 | 0.100953E+11 | 0.115358E+11 | 0.00 | 0.204860E+11 | 0.00 | 0.00 | 0.450653E+11 | 0.00 | 0.00 | 0.00 | 0.174887E+10 | 0.00 |
August | 0.453764E+11 | 0.105817E+11 | 0.123357E+11 | 0.00 | 0.213092E+11 | 0.00 | 0.00 | 0.484665E+11 | 0.00 | 0.00 | 0.00 | 0.179786E+10 | 0.00 |
September | 0.425433E+11 | 0.108786E+11 | 0.114788E+11 | 0.00 | 0.190700E+11 | 0.00 | 0.00 | 0.371904E+11 | 0.00 | 0.00 | 0.00 | 0.176600E+10 | 0.00 |
October | 0.429506E+11 | 0.119383E+11 | 0.115432E+11 | 0.00 | 0.167871E+11 | 0.00 | 0.00 | 0.272911E+11 | 0.00 | 0.00 | 0.00 | 0.186767E+10 | 0.00 |
November | 0.413304E+11 | 0.121533E+11 | 0.110862E+11 | 0.00 | 0.126236E+11 | 0.00 | 0.00 | 0.169785E+11 | 0.00 | 0.00 | 0.00 | 0.185632E+10 | 0.00 |
December | 0.429506E+11 | 0.129007E+11 | 0.115358E+11 | 0.00 | 0.111280E+11 | 0.00 | 0.00 | 0.965334E+10 | 0.00 | 0.00 | 0.00 | 0.196225E+10 | 0.00 |
Annual Sum or Average | 0.516195E+12 | 0.134295E+12 | 0.139290E+12 | 0.00 | 0.187106E+12 | 0.00 | 0.00 | 0.299609E+12 | 0.00 | 0.00 | 0.00 | 0.220730E+11 | 0.00 |
Minimum of Months | 0.393028E+11 | 0.967554E+10 | 0.105871E+11 | 0.00 | 0.102406E+11 | 0.00 | 0.00 | 0.641010E+10 | 0.00 | 0.00 | 0.00 | 0.173211E+10 | 0.00 |
Maximum of Months | 0.453764E+11 | 0.129007E+11 | 0.123431E+11 | 0.00 | 0.213092E+11 | 0.00 | 0.00 | 0.484665E+11 | 0.00 | 0.00 | 0.00 | 0.197554E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 978170.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 978170.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 978170.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38182.97 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 11100.55 | 02-JAN-10:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38182.97 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 13405.85 | 08-FEB-14:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38182.97 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 13405.85 | 01-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38182.97 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 13405.85 | 01-APR-09:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38182.97 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 13405.85 | 12-MAY-13:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38182.97 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 13405.85 | 05-JUN-14:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38182.97 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 13405.85 | 06-JUL-10:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38182.97 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 13405.85 | 11-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38182.97 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 13405.85 | 01-SEP-08:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38182.97 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 13405.85 | 05-OCT-11:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38182.97 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 13405.85 | 08-NOV-13:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38182.97 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 13405.85 | 01-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 11100.55 | 0.00 | 0.00 | |||||
Maximum of Months | 38182.97 | 8532.22 | 10112.62 | 0.00 | 13405.85 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12493.76 | 23-JAN-13:39 | 0.00 | 0.00 | 0.00 | 1740.30 | 12-JAN-12:09 | 0.00 |
February | 18707.33 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 1737.44 | 01-FEB-12:09 | 0.00 |
March | 24380.07 | 27-MAR-11:30 | 0.00 | 0.00 | 0.00 | 1725.35 | 01-MAR-12:00 | 0.00 |
April | 30180.10 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 1704.18 | 01-APR-11:39 | 0.00 |
May | 35407.83 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1681.88 | 01-MAY-11:50 | 0.00 |
June | 41822.81 | 09-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1663.04 | 01-JUN-11:20 | 0.00 |
July | 42883.14 | 14-JUL-15:39 | 0.00 | 0.00 | 0.00 | 1654.39 | 31-JUL-11:20 | 0.00 |
August | 48245.62 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1665.97 | 31-AUG-11:30 | 0.00 |
September | 37787.65 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1685.16 | 30-SEP-11:00 | 0.00 |
October | 31484.40 | 07-OCT-15:50 | 0.00 | 0.00 | 0.00 | 1708.34 | 31-OCT-11:30 | 0.00 |
November | 26559.34 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 | 1727.99 | 30-NOV-12:20 | 0.00 |
December | 16885.82 | 06-DEC-13:39 | 0.00 | 0.00 | 0.00 | 1739.10 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12493.76 | 0.00 | 0.00 | 0.00 | 1654.39 | 0.00 | ||
Maximum of Months | 48245.62 | 0.00 | 0.00 | 0.00 | 1740.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 73569.83 | 23-JAN-13:30 | 38182.97 | 10112.62 | 0.00 | 0.00 | 11100.55 | 0.00 | 0.00 | 12463.06 | 0.00 |
February | 82064.98 | 07-FEB-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 18655.71 | 0.00 |
March | 86844.89 | 27-MAR-12:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 23459.45 | 0.00 |
April | 91873.95 | 28-APR-12:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 28508.66 | 0.00 |
May | 95985.22 | 31-MAY-14:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 32637.71 | 0.00 |
June | 101424.18 | 09-JUN-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 38080.16 | 0.00 |
July | 103836.48 | 14-JUL-13:50 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 40693.64 | 0.00 |
August | 106723.60 | 10-AUG-15:00 | 33916.61 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 48245.62 | 0.00 |
September | 98174.49 | 06-SEP-14:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 34821.89 | 0.00 |
October | 93853.86 | 07-OCT-13:39 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 30503.61 | 0.00 |
November | 89750.17 | 01-NOV-13:00 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 26386.56 | 0.00 |
December | 80107.26 | 04-DEC-13:09 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 16703.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 73569.83 | 33916.61 | 10112.62 | 0.00 | 0.00 | 11100.55 | 0.00 | 0.00 | 12463.06 | 0.00 | |
Maximum of Months | 106723.60 | 38182.97 | 10112.62 | 0.00 | 0.00 | 13405.85 | 0.00 | 0.00 | 48245.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 610.65 | 02-JAN-07:40 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 610.65 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.10 | 1.67 | 24.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.21 | 4.17 | 24.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.68 | 8.67 | 26.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.17 | 9.00 | 26.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 28.32 | 9.83 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 28.09 | 11.83 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.47 | 9.00 | 26.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.14 | 8.33 | 25.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.69 | 5.83 | 24.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.53 | 1.17 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 120.00 | 27.23 | 70.33 | 26.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 28.32 | 11.83 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.00 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 0.00 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.45 | 0.00 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.60 | 0.00 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 27.72 | 0.33 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 27.71 | 0.67 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 114.67 | 27.87 | 4.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 | 27.87 | 4.50 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 89.33 | 27.70 | 2.00 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 27.62 | 0.00 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.49 | 0.00 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.36 | 0.00 | 27.36 |
Annual Sum or Average | 0.00 | 0.00 | 577.33 | 27.74 | 11.50 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.00 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 114.67 | 27.87 | 4.50 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.33 | 23.36 | 171.33 | 23.80 | 0.00 | 23.80 |
February | 12.67 | 23.45 | 227.33 | 23.88 | 0.67 | 23.88 |
March | 3.83 | 23.81 | 292.67 | 23.91 | 0.83 | 23.91 |
April | 3.00 | 24.13 | 300.00 | 23.92 | 3.00 | 23.92 |
May | 18.00 | 24.22 | 312.00 | 23.95 | 18.00 | 23.96 |
June | 47.33 | 24.17 | 312.00 | 23.98 | 47.33 | 24.00 |
July | 80.67 | 24.12 | 300.00 | 24.00 | 80.67 | 24.02 |
August | 90.17 | 24.16 | 324.00 | 24.01 | 90.17 | 24.04 |
September | 60.00 | 24.16 | 300.00 | 23.99 | 60.00 | 24.01 |
October | 30.00 | 24.15 | 300.00 | 23.95 | 30.00 | 23.97 |
November | 8.67 | 24.10 | 288.00 | 23.92 | 8.67 | 23.93 |
December | 3.83 | 23.68 | 273.50 | 23.90 | 0.67 | 23.90 |
Annual Sum or Average | 399.50 | 24.04 | 3400.83 | 23.94 | 340.00 | 23.96 |
Minimum of Months | 3.00 | 23.36 | 171.33 | 23.80 | 0.00 | 23.80 |
Maximum of Months | 90.17 | 24.22 | 324.00 | 24.01 | 90.17 | 24.04 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.17 | 25.77 | 262.17 | 26.35 | 76.50 | 26.41 |
February | 161.50 | 26.52 | 258.67 | 26.55 | 154.50 | 26.58 |
March | 224.17 | 26.67 | 320.00 | 26.63 | 223.17 | 26.64 |
April | 254.00 | 26.69 | 300.00 | 26.68 | 254.00 | 26.68 |
May | 297.00 | 26.71 | 312.00 | 26.71 | 297.00 | 26.71 |
June | 311.17 | 26.71 | 312.00 | 26.71 | 311.17 | 26.71 |
July | 299.33 | 26.71 | 300.00 | 26.71 | 299.33 | 26.71 |
August | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
September | 299.33 | 26.71 | 300.00 | 26.71 | 299.33 | 26.71 |
October | 290.00 | 26.71 | 300.00 | 26.71 | 290.00 | 26.71 |
November | 260.83 | 26.70 | 288.00 | 26.69 | 260.83 | 26.69 |
December | 182.67 | 26.62 | 292.00 | 26.58 | 179.33 | 26.60 |
Annual Sum or Average | 3008.17 | 26.66 | 3568.83 | 26.66 | 2969.17 | 26.67 |
Minimum of Months | 104.17 | 25.77 | 258.67 | 26.35 | 76.50 | 26.41 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.83 | 23.57 | 174.00 | 24.98 | 18.83 | 25.08 |
February | 129.33 | 27.73 | 259.17 | 27.19 | 123.17 | 27.37 |
March | 264.50 | 29.13 | 324.00 | 28.84 | 264.50 | 28.93 |
April | 300.00 | 30.48 | 300.00 | 30.48 | 300.00 | 30.48 |
May | 312.00 | 33.55 | 312.00 | 33.55 | 312.00 | 33.55 |
June | 312.00 | 34.79 | 312.00 | 34.79 | 312.00 | 34.79 |
July | 300.00 | 36.42 | 300.00 | 36.42 | 300.00 | 36.42 |
August | 324.00 | 36.73 | 324.00 | 36.73 | 324.00 | 36.73 |
September | 300.00 | 34.19 | 300.00 | 34.19 | 300.00 | 34.19 |
October | 300.00 | 31.89 | 300.00 | 31.89 | 300.00 | 31.89 |
November | 288.00 | 29.72 | 288.00 | 29.72 | 288.00 | 29.72 |
December | 201.67 | 28.23 | 295.00 | 27.83 | 201.67 | 27.95 |
Annual Sum or Average | 3146.33 | 32.22 | 3488.17 | 31.94 | 3044.17 | 32.13 |
Minimum of Months | 114.83 | 23.57 | 174.00 | 24.98 | 18.83 | 25.08 |
Maximum of Months | 324.00 | 36.73 | 324.00 | 36.73 | 324.00 | 36.73 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.681864E+10 | 0.181995E+10 | 261.75 | 0.583929E+10 | 0.979352E+09 | 0.00 | 1.00 | 23-JAN-06:02 | 0.00 | 01-JAN-00:10 | 37994.43 | 30-JAN-06:01 | 28807.15 | 25-JAN-06:02 | 12541.44 | 30-JAN-06:02 | 8745.83 | 30-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.786487E+10 | 0.211839E+10 | 250.54 | 0.658220E+10 | 0.128267E+10 | 0.00 | 1.00 | 04-FEB-06:02 | 0.00 | 01-FEB-00:10 | 39076.28 | 09-FEB-06:01 | 28911.09 | 10-FEB-06:02 | 14338.89 | 09-FEB-06:03 | 8914.45 | 09-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.109434E+11 | 0.302292E+10 | 310.66 | 0.946696E+10 | 0.147640E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 39613.35 | 29-MAR-05:01 | 34211.68 | 27-MAR-05:01 | 15809.60 | 29-MAR-05:03 | 8993.59 | 29-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.129484E+11 | 0.372419E+10 | 302.92 | 0.109755E+11 | 0.197284E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 39971.34 | 20-APR-05:01 | 34216.76 | 25-APR-05:01 | 16480.42 | 12-APR-05:03 | 9044.66 | 20-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.181607E+11 | 0.553816E+10 | 349.60 | 0.150980E+11 | 0.306274E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 42368.76 | 25-MAY-05:02 | 34073.59 | 10-MAY-05:01 | 23225.79 | 24-MAY-05:04 | 9590.49 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.218739E+11 | 0.667912E+10 | 358.91 | 0.164941E+11 | 0.537979E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 42053.72 | 08-JUN-05:01 | 30472.52 | 16-JUN-05:01 | 24519.89 | 27-JUN-05:08 | 9869.97 | 29-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.250105E+11 | 0.771601E+10 | 428.15 | 0.177851E+11 | 0.722539E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 40886.69 | 06-JUL-05:06 | 33008.79 | 03-JUL-05:01 | 24829.86 | 06-JUL-05:08 | 10536.92 | 16-JUL-13:31 | 0.00 | 01-JUL-00:10 |
August | 0.278992E+11 | 0.859114E+10 | 454.74 | 0.195314E+11 | 0.836784E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 40886.69 | 31-AUG-05:11 | 30077.22 | 06-AUG-15:31 | 24965.47 | 09-AUG-05:09 | 10527.57 | 06-AUG-14:51 | 0.00 | 01-AUG-00:10 |
September | 0.221428E+11 | 0.659650E+10 | 361.12 | 0.158860E+11 | 0.625684E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 42742.71 | 25-SEP-05:01 | 26983.46 | 05-SEP-05:01 | 24468.16 | 23-SEP-05:06 | 9694.82 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.178006E+11 | 0.513737E+10 | 331.34 | 0.136950E+11 | 0.410567E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 42338.46 | 17-OCT-05:01 | 32139.34 | 20-OCT-05:01 | 23988.62 | 07-OCT-05:05 | 9501.40 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.133734E+11 | 0.370208E+10 | 290.16 | 0.105565E+11 | 0.281690E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 41831.23 | 03-NOV-05:01 | 30650.57 | 18-NOV-06:01 | 18983.41 | 03-NOV-05:05 | 9288.50 | 03-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.933411E+10 | 0.249285E+10 | 280.77 | 0.767079E+10 | 0.166333E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 39068.33 | 06-DEC-06:01 | 30848.64 | 13-DEC-06:02 | 15161.21 | 06-DEC-06:02 | 8913.25 | 06-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.194170E+12 | 0.571387E+11 | 3980.65 | 0.149581E+12 | 0.445897E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.681864E+10 | 0.181995E+10 | 250.54 | 0.583929E+10 | 0.979352E+09 | 0.00 | 1.00 | 0.00 | 37994.43 | 26983.46 | 12541.44 | 8745.83 | 0.00 | |||||||
Maximum of Months | 0.278992E+11 | 0.859114E+10 | 454.74 | 0.195314E+11 | 0.836784E+10 | 0.00 | 1.00 | 0.00 | 42742.71 | 34216.76 | 24965.47 | 10536.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.157689E+11 | 0.459015E+10 | 237.72 | 0.133996E+11 | 0.236930E+10 | 0.00 | 0.28 | 28-JAN-14:00 | 0.00 | 01-JAN-00:10 | 33200.91 | 29-JAN-15:15 | 29983.95 | 28-JAN-14:00 | 8891.41 | 29-JAN-15:15 | 9576.19 | 23-JAN-13:40 | 0.00 | 01-JAN-00:10 |
February | 0.208063E+11 | 0.613385E+10 | 243.37 | 0.174935E+11 | 0.331288E+10 | 0.00 | 0.68 | 05-FEB-12:53 | 0.00 | 01-FEB-00:10 | 80728.02 | 05-FEB-12:53 | 74142.70 | 05-FEB-12:53 | 12336.08 | 07-FEB-16:35 | 24548.75 | 05-FEB-12:53 | 0.00 | 01-FEB-00:10 |
March | 0.332902E+11 | 0.100698E+11 | 334.32 | 0.289702E+11 | 0.431997E+10 | 0.00 | 1.00 | 26-MAR-12:32 | 0.00 | 01-MAR-00:10 | 117791.61 | 26-MAR-12:32 | 117791.61 | 26-MAR-12:32 | 18586.80 | 28-MAR-17:08 | 37015.02 | 26-MAR-12:32 | 0.00 | 01-MAR-00:10 |
April | 0.475027E+11 | 0.149126E+11 | 412.76 | 0.404140E+11 | 0.708869E+10 | 0.00 | 1.00 | 02-APR-11:32 | 0.00 | 01-APR-00:10 | 138469.87 | 09-APR-13:02 | 118994.59 | 02-APR-11:32 | 37645.07 | 30-APR-15:53 | 39205.76 | 30-APR-12:32 | 0.00 | 01-APR-00:10 |
May | 0.765049E+11 | 0.253304E+11 | 566.64 | 0.642026E+11 | 0.123023E+11 | 0.00 | 1.00 | 03-MAY-17:42 | 0.00 | 01-MAY-00:25 | 142870.38 | 24-MAY-17:42 | 119905.39 | 07-MAY-15:22 | 49775.84 | 24-MAY-17:42 | 41897.55 | 31-MAY-17:42 | 0.00 | 01-MAY-00:10 |
June | 0.939794E+11 | 0.310241E+11 | 574.54 | 0.713802E+11 | 0.225993E+11 | 0.00 | 1.00 | 01-JUN-17:04 | 0.00 | 01-JUN-00:13 | 149096.69 | 09-JUN-05:01 | 115406.66 | 20-JUN-17:42 | 67212.16 | 09-JUN-05:01 | 41982.32 | 09-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.111555E+12 | 0.373493E+11 | 598.98 | 0.813911E+11 | 0.301635E+11 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-00:13 | 150269.84 | 18-JUL-05:01 | 115057.58 | 21-JUL-23:03 | 67491.89 | 18-JUL-05:01 | 43285.18 | 30-JUL-13:02 | 0.00 | 01-JUL-00:10 |
August | 0.119387E+12 | 0.398754E+11 | 605.84 | 0.856821E+11 | 0.337046E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:12 | 153897.64 | 08-AUG-05:01 | 112471.62 | 06-AUG-07:42 | 78335.51 | 08-AUG-05:01 | 43780.43 | 10-AUG-17:42 | 0.00 | 01-AUG-00:10 |
September | 0.945808E+11 | 0.305938E+11 | 571.57 | 0.685345E+11 | 0.260463E+11 | 0.00 | 1.00 | 01-SEP-17:04 | 0.00 | 01-SEP-00:13 | 148029.68 | 08-SEP-05:01 | 113975.89 | 04-SEP-12:22 | 64059.50 | 10-SEP-17:42 | 42136.51 | 04-SEP-14:22 | 0.00 | 01-SEP-00:10 |
October | 0.701991E+11 | 0.221537E+11 | 546.06 | 0.546536E+11 | 0.155455E+11 | 0.00 | 1.00 | 01-OCT-13:02 | 0.00 | 01-OCT-00:15 | 143426.75 | 07-OCT-17:06 | 119208.14 | 15-OCT-13:42 | 58021.09 | 18-OCT-05:09 | 40045.59 | 07-OCT-17:06 | 0.00 | 01-OCT-00:10 |
November | 0.437537E+11 | 0.132764E+11 | 381.15 | 0.349924E+11 | 0.876127E+10 | 0.00 | 1.00 | 05-NOV-15:53 | 0.00 | 01-NOV-00:15 | 129823.77 | 05-NOV-15:53 | 117367.37 | 19-NOV-13:32 | 35259.78 | 01-NOV-17:06 | 37142.97 | 05-NOV-15:53 | 0.00 | 01-NOV-00:10 |
December | 0.245218E+11 | 0.716049E+10 | 277.61 | 0.201058E+11 | 0.441591E+10 | 0.00 | 0.65 | 03-DEC-13:13 | 0.00 | 01-DEC-00:10 | 79787.79 | 03-DEC-13:13 | 71277.66 | 03-DEC-13:13 | 14583.95 | 24-DEC-13:00 | 23300.06 | 03-DEC-13:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.751849E+12 | 0.242470E+12 | 5350.57 | 0.581220E+12 | 0.170629E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.157689E+11 | 0.459015E+10 | 237.72 | 0.133996E+11 | 0.236930E+10 | 0.00 | 0.28 | 0.00 | 33200.91 | 29983.95 | 8891.41 | 9576.19 | 0.00 | |||||||
Maximum of Months | 0.119387E+12 | 0.398754E+11 | 605.84 | 0.856821E+11 | 0.337046E+11 | 0.00 | 1.00 | 0.00 | 153897.64 | 119905.39 | 78335.51 | 43780.43 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.12 | 12.48 | 30.64 | 80.30 | 118.59 | 0.00 | 0.00 | 0.00 |
February | 49.17 | 14.14 | 35.02 | 105.14 | 103.65 | 0.00 | 0.00 | 0.00 |
March | 58.02 | 17.19 | 40.83 | 148.44 | 83.49 | 0.00 | 0.00 | 0.00 |
April | 63.18 | 17.61 | 45.57 | 196.44 | 58.89 | 0.00 | 0.00 | 0.00 |
May | 68.87 | 20.56 | 48.31 | 269.17 | 22.15 | 0.00 | 0.00 | 0.00 |
June | 71.29 | 22.52 | 48.78 | 295.67 | 10.26 | 0.00 | 0.00 | 0.00 |
July | 65.54 | 18.85 | 46.69 | 315.48 | 1.59 | 0.00 | 0.00 | 0.00 |
August | 66.90 | 20.23 | 46.67 | 323.51 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 63.74 | 20.00 | 43.75 | 261.25 | 13.42 | 0.00 | 0.00 | 0.00 |
October | 56.72 | 18.32 | 38.39 | 199.94 | 36.07 | 0.00 | 0.00 | 0.00 |
November | 48.88 | 16.05 | 32.83 | 139.47 | 71.80 | 0.00 | 0.00 | 0.00 |
December | 40.99 | 12.52 | 28.47 | 86.67 | 107.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.07 | 17.55 | 40.52 | 202.35 | 52.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.99 | 12.48 | 28.47 | 80.30 | 1.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.29 | 22.52 | 48.78 | 323.51 | 118.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.12 | 12.48 | 30.64 | 80.30 | 118.59 | 0.00 | 0.00 | 0.00 |
February | 49.17 | 14.14 | 35.02 | 105.14 | 103.65 | 0.00 | 0.00 | 0.00 |
March | 58.02 | 17.19 | 40.83 | 148.44 | 83.49 | 0.00 | 0.00 | 0.00 |
April | 63.18 | 17.61 | 45.57 | 196.44 | 58.89 | 0.00 | 0.00 | 0.00 |
May | 68.87 | 20.56 | 48.31 | 269.17 | 22.15 | 0.00 | 0.00 | 0.00 |
June | 71.29 | 22.52 | 48.78 | 295.67 | 10.26 | 0.00 | 0.00 | 0.00 |
July | 65.54 | 18.85 | 46.69 | 315.48 | 1.59 | 0.00 | 0.00 | 0.00 |
August | 66.90 | 20.23 | 46.67 | 323.51 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 63.74 | 20.00 | 43.75 | 261.25 | 13.42 | 0.00 | 0.00 | 0.00 |
October | 56.72 | 18.32 | 38.39 | 199.94 | 36.07 | 0.00 | 0.00 | 0.00 |
November | 48.88 | 16.05 | 32.83 | 139.47 | 71.80 | 0.00 | 0.00 | 0.00 |
December | 40.99 | 12.52 | 28.47 | 86.67 | 107.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.07 | 17.55 | 40.52 | 202.35 | 52.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.99 | 12.48 | 28.47 | 80.30 | 1.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.29 | 22.52 | 48.78 | 323.51 | 118.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.10 | 0.00 | 14.10 | 17.32 | 70.96 | 0.00 | 0.00 | 0.00 |
February | 16.16 | 0.00 | 16.16 | 26.48 | 62.08 | 0.00 | 0.00 | 0.00 |
March | 18.57 | 0.00 | 18.56 | 42.53 | 49.40 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 0.10 | 20.89 | 67.50 | 33.98 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 1.04 | 22.85 | 107.28 | 12.18 | 0.00 | 0.00 | 0.00 |
June | 25.65 | 1.85 | 23.79 | 124.47 | 6.00 | 0.00 | 0.00 | 0.00 |
July | 23.41 | 0.94 | 22.47 | 139.20 | 0.91 | 0.00 | 0.00 | 0.00 |
August | 21.70 | 0.35 | 21.36 | 136.26 | 0.52 | 0.00 | 0.00 | 0.00 |
September | 19.62 | 0.01 | 19.61 | 98.80 | 7.55 | 0.00 | 0.00 | 0.00 |
October | 17.38 | 0.00 | 17.38 | 68.75 | 20.76 | 0.00 | 0.00 | 0.00 |
November | 14.92 | 0.00 | 14.92 | 40.76 | 41.90 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 20.01 | 64.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.14 | 0.36 | 18.78 | 74.41 | 30.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 17.32 | 0.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.65 | 1.85 | 23.79 | 139.20 | 70.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.10 | 0.00 | 14.10 | 17.31 | 70.96 | 0.00 | 0.00 | 0.00 |
February | 16.16 | 0.00 | 16.16 | 26.48 | 62.08 | 0.00 | 0.00 | 0.00 |
March | 18.56 | 0.00 | 18.56 | 42.53 | 49.40 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 0.10 | 20.89 | 67.49 | 33.98 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 1.04 | 22.85 | 107.28 | 12.18 | 0.00 | 0.00 | 0.00 |
June | 25.64 | 1.85 | 23.79 | 124.47 | 6.00 | 0.00 | 0.00 | 0.00 |
July | 23.40 | 0.94 | 22.47 | 139.20 | 0.91 | 0.00 | 0.00 | 0.00 |
August | 21.70 | 0.35 | 21.36 | 136.26 | 0.52 | 0.00 | 0.00 | 0.00 |
September | 19.62 | 0.01 | 19.61 | 98.80 | 7.55 | 0.00 | 0.00 | 0.00 |
October | 17.38 | 0.00 | 17.38 | 68.75 | 20.76 | 0.00 | 0.00 | 0.00 |
November | 14.92 | 0.00 | 14.92 | 40.76 | 41.90 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 0.00 | 13.16 | 20.01 | 64.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.14 | 0.36 | 18.78 | 74.41 | 30.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 0.00 | 13.16 | 17.31 | 0.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.64 | 1.85 | 23.79 | 139.20 | 70.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.03 | 13.41 | 21.62 | 54.39 | 33.36 | 0.00 | 0.00 | 0.00 |
February | 42.56 | 17.42 | 25.13 | 66.99 | 32.85 | 0.00 | 0.00 | 0.00 |
March | 51.54 | 21.72 | 29.83 | 83.60 | 32.45 | 0.00 | 0.00 | 0.00 |
April | 60.79 | 27.06 | 33.74 | 103.01 | 29.92 | 0.00 | 0.00 | 0.00 |
May | 69.00 | 33.67 | 35.32 | 120.81 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 71.94 | 36.71 | 35.22 | 125.77 | 21.99 | 0.00 | 0.00 | 0.00 |
July | 69.80 | 35.55 | 34.25 | 123.62 | 19.79 | 0.00 | 0.00 | 0.00 |
August | 66.47 | 32.79 | 33.68 | 116.83 | 20.49 | 0.00 | 0.00 | 0.00 |
September | 59.63 | 28.72 | 30.92 | 104.10 | 23.51 | 0.50 | 0.00 | 0.00 |
October | 50.11 | 23.59 | 26.52 | 85.14 | 27.84 | 12.33 | 0.00 | 0.00 |
November | 39.73 | 17.37 | 22.36 | 63.49 | 34.69 | 0.00 | 0.00 | 0.00 |
December | 32.53 | 12.62 | 19.91 | 48.72 | 36.80 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 54.15 | 25.09 | 29.06 | 91.49 | 28.00 | 14.17 | 0.00 | 0.00 |
Minimum of Months | 32.53 | 12.62 | 19.91 | 48.72 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.94 | 36.71 | 35.32 | 125.77 | 36.80 | 12.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115499E+09 | 33430114.87 | 82069350.32 | 0.215078E+09 | 0.317638E+09 |
February | 0.118943E+09 | 34211376.74 | 84731438.60 | 0.254354E+09 | 0.250755E+09 |
March | 0.155399E+09 | 46040397.02 | 0.109359E+09 | 0.397584E+09 | 0.223608E+09 |
April | 0.163755E+09 | 45644833.27 | 0.118110E+09 | 0.509173E+09 | 0.152651E+09 |
May | 0.184463E+09 | 55070047.26 | 0.129393E+09 | 0.720952E+09 | 59333384.49 |
June | 0.184790E+09 | 58358977.90 | 0.126431E+09 | 0.766377E+09 | 26584210.00 |
July | 0.175542E+09 | 50493352.68 | 0.125049E+09 | 0.844993E+09 | 4267179.37 |
August | 0.179188E+09 | 54196184.91 | 0.124992E+09 | 0.866478E+09 | 2777978.24 |
September | 0.165224E+09 | 51829243.54 | 0.113395E+09 | 0.677162E+09 | 34776231.74 |
October | 0.151910E+09 | 49076778.40 | 0.102833E+09 | 0.535522E+09 | 96606530.48 |
November | 0.126705E+09 | 41610043.46 | 85095231.67 | 0.361504E+09 | 0.186093E+09 |
December | 0.109780E+09 | 33526329.08 | 76253413.23 | 0.232143E+09 | 0.288876E+09 |
Annual Sum or Average | 0.183120E+10 | 0.553488E+09 | 0.127771E+10 | 0.638132E+10 | 0.164397E+10 |
Minimum of Months | 0.109780E+09 | 33430114.87 | 76253413.23 | 0.215078E+09 | 2777978.24 |
Maximum of Months | 0.184790E+09 | 58358977.90 | 0.129393E+09 | 0.866478E+09 | 0.317638E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115499E+09 | 33430114.87 | 82069350.32 | 0.215078E+09 | 0.317638E+09 |
February | 0.118943E+09 | 34211376.74 | 84731438.60 | 0.254354E+09 | 0.250755E+09 |
March | 0.155399E+09 | 46040397.02 | 0.109359E+09 | 0.397584E+09 | 0.223608E+09 |
April | 0.163755E+09 | 45644833.27 | 0.118110E+09 | 0.509173E+09 | 0.152651E+09 |
May | 0.184463E+09 | 55070047.26 | 0.129393E+09 | 0.720952E+09 | 59333384.49 |
June | 0.184790E+09 | 58358977.90 | 0.126431E+09 | 0.766377E+09 | 26584210.00 |
July | 0.175542E+09 | 50493352.68 | 0.125049E+09 | 0.844993E+09 | 4267179.37 |
August | 0.179188E+09 | 54196184.91 | 0.124992E+09 | 0.866478E+09 | 2777978.24 |
September | 0.165224E+09 | 51829243.54 | 0.113395E+09 | 0.677162E+09 | 34776231.74 |
October | 0.151910E+09 | 49076778.40 | 0.102833E+09 | 0.535522E+09 | 96606530.48 |
November | 0.126705E+09 | 41610043.46 | 85095231.67 | 0.361504E+09 | 0.186093E+09 |
December | 0.109780E+09 | 33526329.08 | 76253413.23 | 0.232143E+09 | 0.288876E+09 |
Annual Sum or Average | 0.183120E+10 | 0.553488E+09 | 0.127771E+10 | 0.638132E+10 | 0.164397E+10 |
Minimum of Months | 0.109780E+09 | 33430114.87 | 76253413.23 | 0.215078E+09 | 2777978.24 |
Maximum of Months | 0.184790E+09 | 58358977.90 | 0.129393E+09 | 0.866478E+09 | 0.317638E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37757180.39 | 0.00 | 37757180.39 | 46377683.26 | 0.190048E+09 |
February | 39092110.75 | 0.00 | 39092110.75 | 64063287.66 | 0.150193E+09 |
March | 49725459.30 | 4356.41 | 49721102.89 | 0.113914E+09 | 0.132306E+09 |
April | 54391648.46 | 253761.02 | 54137887.44 | 0.174949E+09 | 88076934.09 |
May | 63986555.05 | 2775915.28 | 61210639.76 | 0.287335E+09 | 32630347.86 |
June | 66473330.18 | 4799522.49 | 61673807.69 | 0.322630E+09 | 15550461.16 |
July | 62688753.09 | 2515175.01 | 60173578.08 | 0.372841E+09 | 2449345.60 |
August | 58130145.26 | 927816.44 | 57202328.83 | 0.364958E+09 | 1395028.13 |
September | 50851213.01 | 23723.51 | 50827489.50 | 0.256088E+09 | 19580537.65 |
October | 46560892.55 | 0.00 | 46560892.55 | 0.184152E+09 | 55604846.08 |
November | 38682121.08 | 0.00 | 38682121.08 | 0.105643E+09 | 0.108606E+09 |
December | 35241442.63 | 0.00 | 35241442.63 | 53601553.81 | 0.172297E+09 |
Annual Sum or Average | 0.603581E+09 | 11300270.16 | 0.592281E+09 | 0.234655E+10 | 0.968738E+09 |
Minimum of Months | 35241442.63 | 0.00 | 35241442.63 | 46377683.26 | 1395028.13 |
Maximum of Months | 66473330.18 | 4799522.49 | 61673807.69 | 0.372841E+09 | 0.190048E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37755941.24 | 0.00 | 37755941.24 | 46375581.21 | 0.190047E+09 |
February | 39090851.70 | 0.00 | 39090851.70 | 64061027.89 | 0.150191E+09 |
March | 49723882.49 | 4356.21 | 49719526.28 | 0.113911E+09 | 0.132304E+09 |
April | 54389956.29 | 253749.12 | 54136207.16 | 0.174945E+09 | 88075232.81 |
May | 63984550.27 | 2775785.17 | 61208765.09 | 0.287332E+09 | 32629108.64 |
June | 66471214.63 | 4799297.53 | 61671917.10 | 0.322626E+09 | 15549524.68 |
July | 62686814.52 | 2515057.12 | 60171757.40 | 0.372838E+09 | 2449053.90 |
August | 58128378.47 | 927772.95 | 57200605.52 | 0.364956E+09 | 1394834.84 |
September | 50849669.28 | 23722.39 | 50825946.88 | 0.256086E+09 | 19579547.23 |
October | 46559448.55 | 0.00 | 46559448.55 | 0.184150E+09 | 55603023.26 |
November | 38680887.14 | 0.00 | 38680887.14 | 0.105641E+09 | 0.108604E+09 |
December | 35240285.69 | 0.00 | 35240285.69 | 53599588.78 | 0.172295E+09 |
Annual Sum or Average | 0.603562E+09 | 11299740.50 | 0.592262E+09 | 0.234652E+10 | 0.968722E+09 |
Minimum of Months | 35240285.69 | 0.00 | 35240285.69 | 46375581.21 | 1394834.84 |
Maximum of Months | 66471214.63 | 4799297.53 | 61671917.10 | 0.372838E+09 | 0.190047E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93822120.02 | 35915247.20 | 57906872.82 | 0.145667E+09 | 89345408.28 |
February | 0.102950E+09 | 42143273.86 | 60806537.48 | 0.162067E+09 | 79471224.49 |
March | 0.138054E+09 | 58163361.83 | 79890625.60 | 0.223919E+09 | 86916271.62 |
April | 0.157574E+09 | 70130857.18 | 87443447.75 | 0.267014E+09 | 77546809.97 |
May | 0.184807E+09 | 90192900.70 | 94613777.42 | 0.323584E+09 | 60758839.76 |
June | 0.186461E+09 | 95161930.03 | 91299561.83 | 0.326003E+09 | 56991110.09 |
July | 0.186960E+09 | 95219554.15 | 91740099.84 | 0.331094E+09 | 52995168.37 |
August | 0.178035E+09 | 87815876.26 | 90218870.61 | 0.312912E+09 | 54884552.73 |
September | 0.154569E+09 | 74429477.57 | 80139517.72 | 0.269828E+09 | 60938134.65 |
October | 0.134204E+09 | 63173426.62 | 71031018.34 | 0.228052E+09 | 74557897.25 |
November | 0.102980E+09 | 45035021.65 | 57945049.50 | 0.164561E+09 | 89928991.42 |
December | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 98561688.57 |
Annual Sum or Average | 0.170755E+10 | 0.791172E+09 | 0.916374E+09 | 0.288519E+10 | 0.882896E+09 |
Minimum of Months | 87130103.63 | 33791396.97 | 53338706.66 | 0.130487E+09 | 52995168.37 |
Maximum of Months | 0.186960E+09 | 95219554.15 | 94613777.42 | 0.331094E+09 | 98561688.57 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.79 | 374.66 | 114.44 | 24.96 | 89.48 | 0.00 | 0.00 |
February | 260.16 | 328.39 | 130.65 | 28.28 | 102.37 | 0.00 | 0.00 |
March | 380.16 | 263.98 | 153.17 | 34.38 | 118.79 | 0.00 | 0.00 |
April | 527.49 | 185.37 | 168.32 | 35.42 | 132.91 | 0.00 | 0.00 |
May | 752.42 | 68.19 | 185.52 | 43.19 | 142.33 | 0.00 | 0.00 |
June | 839.97 | 32.20 | 193.88 | 48.73 | 145.14 | 0.00 | 0.00 |
July | 909.31 | 4.95 | 177.89 | 39.58 | 138.31 | 0.00 | 0.00 |
August | 919.51 | 3.10 | 177.21 | 41.16 | 136.05 | 0.00 | 0.00 |
September | 720.04 | 41.88 | 166.72 | 40.01 | 126.71 | 0.00 | 0.00 |
October | 537.37 | 113.64 | 148.20 | 36.65 | 111.55 | 0.00 | 0.00 |
November | 360.00 | 226.94 | 127.61 | 32.11 | 95.51 | 0.00 | 0.00 |
December | 210.86 | 341.85 | 108.29 | 25.03 | 83.25 | 0.00 | 0.00 |
Annual Sum or Average | 552.39 | 164.57 | 154.41 | 35.82 | 118.59 | 0.00 | 0.00 |
Minimum of Months | 190.79 | 3.10 | 108.29 | 24.96 | 83.25 | 0.00 | 0.00 |
Maximum of Months | 919.51 | 374.66 | 193.88 | 48.73 | 145.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1706.37 | 1111.44 | 350.29 | 134.09 | 216.20 | 0.00 | 0.00 |
February | 2219.76 | 1112.57 | 425.55 | 174.20 | 251.35 | 0.00 | 0.00 |
March | 3052.03 | 1185.71 | 515.43 | 217.16 | 298.28 | 0.00 | 0.00 |
April | 4551.48 | 1316.47 | 607.93 | 270.57 | 337.36 | 0.00 | 0.00 |
May | 5928.49 | 1410.87 | 689.99 | 336.74 | 353.25 | 0.00 | 0.00 |
June | 5902.89 | 1405.24 | 719.37 | 367.14 | 352.24 | 0.00 | 0.00 |
July | 6238.11 | 1396.90 | 698.03 | 355.51 | 342.52 | 0.00 | 0.00 |
August | 5512.29 | 1489.68 | 664.71 | 327.87 | 336.84 | 0.00 | 0.00 |
September | 4867.35 | 1525.47 | 596.33 | 287.15 | 309.18 | 0.00 | 0.00 |
October | 3730.00 | 1677.65 | 501.06 | 235.86 | 265.20 | 0.00 | 0.00 |
November | 2568.88 | 1487.20 | 397.30 | 173.75 | 223.55 | 0.00 | 0.00 |
December | 1668.74 | 1283.18 | 325.31 | 126.16 | 199.14 | 0.00 | 0.00 |
Annual Sum or Average | 4004.90 | 1368.22 | 541.46 | 250.88 | 290.58 | 0.00 | 0.00 |
Minimum of Months | 1668.74 | 1111.44 | 325.31 | 126.16 | 199.14 | 0.00 | 0.00 |
Maximum of Months | 6238.11 | 1677.65 | 719.37 | 367.14 | 353.25 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.511017E+09 | 0.100348E+10 | 0.306512E+09 | 66860229.73 | 0.239652E+09 | 0.00 | 0.00 |
February | 0.629383E+09 | 0.794444E+09 | 0.316069E+09 | 68422753.48 | 0.247646E+09 | 0.00 | 0.00 |
March | 0.101821E+10 | 0.707045E+09 | 0.410248E+09 | 92089506.66 | 0.318159E+09 | 0.00 | 0.00 |
April | 0.136727E+10 | 0.480481E+09 | 0.436291E+09 | 91797176.69 | 0.344494E+09 | 0.00 | 0.00 |
May | 0.201528E+10 | 0.182634E+09 | 0.496898E+09 | 0.115692E+09 | 0.381206E+09 | 0.00 | 0.00 |
June | 0.217721E+10 | 83465695.50 | 0.502525E+09 | 0.126317E+09 | 0.376209E+09 | 0.00 | 0.00 |
July | 0.243549E+10 | 13253383.90 | 0.476459E+09 | 0.106017E+09 | 0.370442E+09 | 0.00 | 0.00 |
August | 0.246282E+10 | 8290922.63 | 0.474635E+09 | 0.110248E+09 | 0.364387E+09 | 0.00 | 0.00 |
September | 0.186635E+10 | 0.108561E+09 | 0.432149E+09 | 0.103706E+09 | 0.328443E+09 | 0.00 | 0.00 |
October | 0.143929E+10 | 0.304361E+09 | 0.396941E+09 | 98153556.79 | 0.298787E+09 | 0.00 | 0.00 |
November | 0.933118E+09 | 0.588223E+09 | 0.330774E+09 | 83220086.91 | 0.247553E+09 | 0.00 | 0.00 |
December | 0.564763E+09 | 0.915620E+09 | 0.290041E+09 | 67052658.16 | 0.222989E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174202E+11 | 0.518986E+10 | 0.486954E+10 | 0.112958E+10 | 0.373997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.511017E+09 | 8290922.63 | 0.290041E+09 | 66860229.73 | 0.222989E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246282E+10 | 0.100348E+10 | 0.502525E+09 | 0.126317E+09 | 0.381206E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.457035E+10 | 0.297687E+10 | 0.938221E+09 | 0.359152E+09 | 0.579069E+09 | 0.00 | 0.00 |
February | 0.537004E+10 | 0.269153E+10 | 0.102950E+10 | 0.421433E+09 | 0.608065E+09 | 0.00 | 0.00 |
March | 0.817456E+10 | 0.317580E+10 | 0.138054E+10 | 0.581634E+09 | 0.798906E+09 | 0.00 | 0.00 |
April | 0.117974E+11 | 0.341228E+10 | 0.157574E+10 | 0.701309E+09 | 0.874434E+09 | 0.00 | 0.00 |
May | 0.158789E+11 | 0.377888E+10 | 0.184807E+10 | 0.901929E+09 | 0.946138E+09 | 0.00 | 0.00 |
June | 0.153003E+11 | 0.364240E+10 | 0.186461E+10 | 0.951619E+09 | 0.912996E+09 | 0.00 | 0.00 |
July | 0.167081E+11 | 0.374147E+10 | 0.186960E+10 | 0.952196E+09 | 0.917401E+09 | 0.00 | 0.00 |
August | 0.147641E+11 | 0.398995E+10 | 0.178035E+10 | 0.878159E+09 | 0.902189E+09 | 0.00 | 0.00 |
September | 0.126162E+11 | 0.395403E+10 | 0.154569E+10 | 0.744295E+09 | 0.801395E+09 | 0.00 | 0.00 |
October | 0.999043E+10 | 0.449341E+10 | 0.134204E+10 | 0.631734E+09 | 0.710310E+09 | 0.00 | 0.00 |
November | 0.665853E+10 | 0.385483E+10 | 0.102980E+10 | 0.450350E+09 | 0.579450E+09 | 0.00 | 0.00 |
December | 0.446954E+10 | 0.343686E+10 | 0.871301E+09 | 0.337914E+09 | 0.533387E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126298E+12 | 0.431483E+11 | 0.170755E+11 | 0.791172E+10 | 0.916374E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446954E+10 | 0.269153E+10 | 0.871301E+09 | 0.337914E+09 | 0.533387E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167081E+11 | 0.449341E+10 | 0.186960E+10 | 0.952196E+09 | 0.946138E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.682171E+09 | -608898485.7 | 0.00 | 0.00 | 744.00 | 0.00 | -73272059.8 | 58.99 | 0.00 | 0.00 |
February | 0.609255E+09 | -543786669.5 | 0.00 | 0.00 | 672.00 | 0.00 | -65468816.1 | 58.99 | 0.00 | 0.00 |
March | 0.662261E+09 | -590761297.5 | 0.00 | 0.00 | 744.00 | 0.00 | -71499659.6 | 58.99 | 0.00 | 0.00 |
April | 0.560967E+09 | -493210897.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67756219.9 | 58.99 | 0.00 | 0.00 |
May | 0.525345E+09 | -456668304.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68676978.5 | 59.00 | 0.00 | 0.00 |
June | 0.480145E+09 | -413920120.9 | 0.00 | 0.00 | 720.00 | 0.00 | -66225271.3 | 58.99 | 0.00 | 0.00 |
July | 0.455481E+09 | -387614014.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67866681.9 | 58.99 | 0.00 | 0.00 |
August | 0.503570E+09 | -435319436.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68250352.9 | 58.98 | 0.00 | 0.00 |
September | 0.514213E+09 | -448225920.2 | 0.00 | 0.00 | 720.00 | 0.00 | -65987186.4 | 58.99 | 0.00 | 0.00 |
October | 0.573699E+09 | -505123953.9 | 0.00 | 0.00 | 744.00 | 0.00 | -68575284.7 | 58.99 | 0.00 | 0.00 |
November | 0.604309E+09 | -536757318.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67552086.2 | 58.99 | 0.00 | 0.00 |
December | 0.668619E+09 | -596896397.0 | 0.00 | 0.00 | 744.00 | 0.00 | -71722115.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.684004E+10 | -0.601718E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -822852713.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.455481E+09 | -608898485.7 | 0.00 | 0.00 | 672.00 | 0.00 | -73272059.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.682171E+09 | -387614014.3 | 0.00 | 0.00 | 744.00 | 0.00 | -65468816.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 627434.13 | 391.86 | 02-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627434.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 627434.13 | 391.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.681864E+10 | 0.583929E+10 | 37994.43 | 30-JAN-06:01 | 25780.57 | 0.00 |
February | 0.00 | 0.00 | 0.786487E+10 | 0.658220E+10 | 39076.28 | 09-FEB-06:01 | 25331.60 | 0.00 |
March | 0.00 | 0.00 | 0.109434E+11 | 0.946696E+10 | 39613.35 | 29-MAR-05:01 | 24313.62 | 0.00 |
April | 0.00 | 0.00 | 0.129484E+11 | 0.109755E+11 | 39971.34 | 20-APR-05:01 | 24024.06 | 0.00 |
May | 0.00 | 0.00 | 0.181607E+11 | 0.150980E+11 | 42368.76 | 25-MAY-05:02 | 20826.85 | 0.00 |
June | 0.00 | 0.00 | 0.218739E+11 | 0.164941E+11 | 42053.72 | 08-JUN-05:01 | 19214.23 | 0.00 |
July | 0.00 | 0.00 | 0.250105E+11 | 0.177851E+11 | 40886.69 | 06-JUL-05:06 | 16203.12 | 0.00 |
August | 0.00 | 0.00 | 0.278992E+11 | 0.195314E+11 | 40886.69 | 31-AUG-05:11 | 17347.88 | 0.00 |
September | 0.00 | 0.00 | 0.221428E+11 | 0.158860E+11 | 42742.71 | 25-SEP-05:01 | 21416.12 | 0.00 |
October | 0.00 | 0.00 | 0.178006E+11 | 0.136950E+11 | 42338.46 | 17-OCT-05:01 | 21354.19 | 0.00 |
November | 0.00 | 0.00 | 0.133734E+11 | 0.105565E+11 | 41831.23 | 03-NOV-05:01 | 23404.06 | 0.00 |
December | 0.00 | 0.00 | 0.933411E+10 | 0.767079E+10 | 39068.33 | 06-DEC-06:01 | 24141.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.194170E+12 | 0.149581E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.681864E+10 | 0.583929E+10 | 37994.43 | 16203.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.278992E+11 | 0.195314E+11 | 42742.71 | 25780.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.157689E+11 | 0.133996E+11 | 33200.91 | 29-JAN-15:15 | 24309.50 | 0.00 |
February | 0.00 | 0.00 | 0.208063E+11 | 0.174935E+11 | 80728.02 | 05-FEB-12:53 | 74142.70 | 0.00 |
March | 0.00 | 0.00 | 0.332902E+11 | 0.289702E+11 | 117791.61 | 26-MAR-12:32 | 117791.61 | 0.00 |
April | 0.00 | 0.00 | 0.475027E+11 | 0.404140E+11 | 138469.87 | 09-APR-13:02 | 101651.56 | 0.00 |
May | 0.00 | 0.00 | 0.765049E+11 | 0.642026E+11 | 142870.38 | 24-MAY-17:42 | 93094.54 | 0.00 |
June | 0.00 | 0.00 | 0.939794E+11 | 0.713802E+11 | 149096.69 | 09-JUN-05:01 | 81884.54 | 0.00 |
July | 0.00 | 0.00 | 0.111555E+12 | 0.813911E+11 | 150269.84 | 18-JUL-05:01 | 82777.95 | 0.00 |
August | 0.00 | 0.00 | 0.119387E+12 | 0.856821E+11 | 153897.64 | 08-AUG-05:01 | 75562.14 | 0.00 |
September | 0.00 | 0.00 | 0.945808E+11 | 0.685345E+11 | 148029.68 | 08-SEP-05:01 | 85961.02 | 0.00 |
October | 0.00 | 0.00 | 0.701991E+11 | 0.546536E+11 | 143426.75 | 07-OCT-17:06 | 87697.95 | 0.00 |
November | 0.00 | 0.00 | 0.437537E+11 | 0.349924E+11 | 129823.77 | 05-NOV-15:53 | 111127.19 | 0.00 |
December | 0.00 | 0.00 | 0.245218E+11 | 0.201058E+11 | 79787.79 | 03-DEC-13:13 | 71277.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.751849E+12 | 0.581220E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.157689E+11 | 0.133996E+11 | 33200.91 | 24309.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119387E+12 | 0.856821E+11 | 153897.64 | 117791.61 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168536E+10 | 0.34 | 1696.82 | 02-JAN-09:10 | 0.89 |
February | 0.155547E+10 | 0.35 | 1696.82 | 01-FEB-09:30 | 0.89 |
March | 0.183494E+10 | 0.38 | 1696.82 | 01-MAR-08:50 | 0.89 |
April | 0.171367E+10 | 0.38 | 1696.82 | 01-APR-06:50 | 0.89 |
May | 0.182668E+10 | 0.43 | 1696.82 | 01-MAY-07:11 | 0.88 |
June | 0.185452E+10 | 0.45 | 1696.82 | 01-JUN-06:50 | 0.89 |
July | 0.185625E+10 | 0.53 | 1696.82 | 01-JUL-06:20 | 0.88 |
August | 0.200395E+10 | 0.57 | 1696.82 | 01-AUG-06:30 | 0.88 |
September | 0.180276E+10 | 0.46 | 1696.82 | 01-SEP-06:10 | 0.88 |
October | 0.175438E+10 | 0.40 | 1696.82 | 02-OCT-14:10 | 0.89 |
November | 0.164778E+10 | 0.36 | 1696.82 | 01-NOV-06:30 | 0.88 |
December | 0.169580E+10 | 0.35 | 1696.82 | 01-DEC-07:20 | 0.89 |
Annual Sum or Average | 0.212316E+11 | 0.42 | |||
Minimum of Months | 0.155547E+10 | 0.34 | 1696.82 | 0.88 | |
Maximum of Months | 0.200395E+10 | 0.57 | 1696.82 | 0.89 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.932740E+10 | 0.58 | 9403.73 | 02-JAN-11:00 | 1.53 |
February | 0.861832E+10 | 0.61 | 9403.73 | 01-FEB-09:30 | 1.53 |
March | 0.102504E+11 | 0.73 | 9403.73 | 01-MAR-07:10 | 1.52 |
April | 0.100022E+11 | 0.92 | 9403.73 | 01-APR-06:15 | 1.52 |
May | 0.114855E+11 | 1.24 | 9403.73 | 01-MAY-06:14 | 1.51 |
June | 0.119385E+11 | 1.29 | 9403.73 | 01-JUN-07:05 | 1.52 |
July | 0.124552E+11 | 1.30 | 9403.73 | 01-JUL-06:10 | 1.51 |
August | 0.131308E+11 | 1.31 | 9403.73 | 01-AUG-06:30 | 1.51 |
September | 0.116932E+11 | 1.29 | 9403.73 | 01-SEP-06:20 | 1.52 |
October | 0.108581E+11 | 1.20 | 9403.73 | 02-OCT-06:05 | 1.51 |
November | 0.944487E+10 | 0.85 | 9403.73 | 01-NOV-06:10 | 1.51 |
December | 0.938637E+10 | 0.61 | 9403.73 | 01-DEC-07:20 | 1.53 |
Annual Sum or Average | 0.128591E+12 | 1.00 | |||
Minimum of Months | 0.861832E+10 | 0.58 | 9403.73 | 1.51 | |
Maximum of Months | 0.131308E+11 | 1.31 | 9403.73 | 1.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.350531E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.367386E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.485787E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.543786E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.736484E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.853364E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.957226E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.105951E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.839927E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.689175E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.534986E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.418865E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.783702E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.350531E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.105951E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.139176E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147522E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.203202E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.249148E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.368159E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.429625E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.498045E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.530061E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.422871E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.330119E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.227213E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.165469E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.371061E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139176E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.530061E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168536E+10 | 0.681864E+10 | 627434.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155547E+10 | 0.786487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183494E+10 | 0.109434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171367E+10 | 0.129484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182668E+10 | 0.181607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185452E+10 | 0.218739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185625E+10 | 0.250105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200395E+10 | 0.278992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180276E+10 | 0.221428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175438E+10 | 0.178006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164778E+10 | 0.133734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169580E+10 | 0.933411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212316E+11 | 0.194170E+12 | 627434.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155547E+10 | 0.681864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200395E+10 | 0.278992E+11 | 627434.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.932740E+10 | 0.157689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.861832E+10 | 0.208063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102504E+11 | 0.332902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100022E+11 | 0.475027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114855E+11 | 0.765049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119385E+11 | 0.939794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124552E+11 | 0.111555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131308E+11 | 0.119387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116932E+11 | 0.945808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108581E+11 | 0.701991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.944487E+10 | 0.437537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.938637E+10 | 0.245218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128591E+12 | 0.751849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.861832E+10 | 0.157689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131308E+11 | 0.119387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168536E+10 | 0.00 | 0.00 | 0.00 | 0.181995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155547E+10 | 0.00 | 0.00 | 0.00 | 0.211839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183494E+10 | 0.00 | 0.00 | 0.00 | 0.302292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171367E+10 | 0.00 | 0.00 | 0.00 | 0.372419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182668E+10 | 0.00 | 0.00 | 0.00 | 0.553816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185452E+10 | 0.00 | 0.00 | 0.00 | 0.667912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185625E+10 | 0.00 | 0.00 | 0.00 | 0.771601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200395E+10 | 0.00 | 0.00 | 0.00 | 0.859114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180276E+10 | 0.00 | 0.00 | 0.00 | 0.659650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175438E+10 | 0.00 | 0.00 | 0.00 | 0.513737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164778E+10 | 0.00 | 0.00 | 0.00 | 0.370208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169580E+10 | 0.00 | 0.00 | 0.00 | 0.249285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212316E+11 | 0.00 | 0.00 | 0.00 | 0.571387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155547E+10 | 0.00 | 0.00 | 0.00 | 0.181995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200395E+10 | 0.00 | 0.00 | 0.00 | 0.859114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.932740E+10 | 0.00 | 0.00 | 0.00 | 0.459015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.861832E+10 | 0.00 | 0.00 | 0.00 | 0.613385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102504E+11 | 0.00 | 0.00 | 0.00 | 0.100698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100022E+11 | 0.00 | 0.00 | 0.00 | 0.149126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114855E+11 | 0.00 | 0.00 | 0.00 | 0.253304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119385E+11 | 0.00 | 0.00 | 0.00 | 0.310241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124552E+11 | 0.00 | 0.00 | 0.00 | 0.373493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131308E+11 | 0.00 | 0.00 | 0.00 | 0.398754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116932E+11 | 0.00 | 0.00 | 0.00 | 0.305938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108581E+11 | 0.00 | 0.00 | 0.00 | 0.221537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.944487E+10 | 0.00 | 0.00 | 0.00 | 0.132764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.938637E+10 | 0.00 | 0.00 | 0.00 | 0.716049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128591E+12 | 0.00 | 0.00 | 0.00 | 0.242470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.861832E+10 | 0.00 | 0.00 | 0.00 | 0.459015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131308E+11 | 0.00 | 0.00 | 0.00 | 0.398754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 85383872.86 | 0.144457E+09 | 0.00 | 4477930.54 | 0.00 | 2747032.12 | 0.294273E+09 | 0.00 | 0.14 |
February | 48838267.02 | 0.283718E+09 | 0.00 | 4029630.98 | 0.00 | 0.00 | 0.135507E+09 | 0.00 | 0.14 |
March | 21664477.17 | 0.571924E+09 | 0.00 | 4859723.79 | 0.00 | 0.00 | 0.111692E+09 | 0.00 | 0.15 |
April | 225136.88 | 0.107525E+10 | 0.00 | 5248492.60 | 0.00 | 0.00 | 50530724.67 | 0.00 | 0.15 |
May | 0.00 | 0.204394E+10 | 0.00 | 3568966.05 | 0.00 | 0.00 | 4759197.99 | 0.00 | 0.15 |
June | 0.00 | 0.308167E+10 | 0.00 | 1670210.94 | 0.00 | 0.00 | 1226959.17 | 0.00 | 0.16 |
July | 0.00 | 0.408690E+10 | 0.00 | 1101738.53 | 0.00 | 0.00 | 464769.95 | 0.00 | 0.15 |
August | 0.00 | 0.460180E+10 | 0.00 | 165045.02 | 0.00 | 0.00 | 9000.89 | 0.00 | 0.17 |
September | 0.00 | 0.335122E+10 | 0.00 | 1849746.53 | 0.00 | 0.00 | 1577784.67 | 0.00 | 0.15 |
October | 0.00 | 0.216529E+10 | 0.00 | 2004395.15 | 0.00 | 0.00 | 6692752.25 | 0.00 | 0.14 |
November | 0.00 | 0.127604E+10 | 0.00 | 3616854.67 | 0.00 | 0.00 | 12687605.01 | 0.00 | 0.14 |
December | 31971140.24 | 0.444007E+09 | 0.00 | 4542421.09 | 0.00 | 0.00 | 0.123733E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.188083E+09 | 0.231262E+11 | 0.00 | 37135155.89 | 0.00 | 2747032.12 | 0.743154E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.144457E+09 | 0.00 | 165045.02 | 0.00 | 0.00 | 9000.89 | 0.00 | 0.14 |
Maximum of Months | 85383872.86 | 0.460180E+10 | 0.00 | 5248492.60 | 0.00 | 2747032.12 | 0.294273E+09 | 0.00 | 0.17 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109454E+10 | 0.129243E+09 | 0.00 | 10127623.85 | 0.00 | 0.00 | 0.167348E+10 | 0.00 | 0.20 |
February | 0.547789E+09 | 0.466052E+09 | 0.00 | 10060766.49 | 0.00 | 0.00 | 0.114375E+10 | 0.00 | 0.20 |
March | 0.324688E+09 | 0.135543E+10 | 0.00 | 11981185.31 | 0.00 | 0.00 | 0.979347E+09 | 0.00 | 0.22 |
April | 63857221.76 | 0.328574E+10 | 0.00 | 6630254.33 | 0.00 | 0.00 | 0.535626E+09 | 0.00 | 0.22 |
May | 0.00 | 0.800810E+10 | 0.00 | 2047441.03 | 0.00 | 0.00 | 58277081.77 | 0.00 | 0.24 |
June | 0.00 | 0.129092E+11 | 0.00 | 342161.21 | 0.00 | 0.00 | 4704822.14 | 0.00 | 0.26 |
July | 0.00 | 0.182156E+11 | 0.00 | 446694.93 | 0.00 | 0.00 | 855312.71 | 0.00 | 0.26 |
August | 0.00 | 0.201989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.142338E+11 | 0.00 | 61116.48 | 0.00 | 0.00 | 350426.69 | 0.00 | 0.26 |
October | 0.00 | 0.809831E+10 | 0.00 | 2428274.68 | 370470.64 | 0.00 | 68344772.34 | 0.00 | 0.23 |
November | 29559113.04 | 0.376932E+10 | 0.00 | 3175436.01 | 0.00 | 0.00 | 0.203505E+09 | 0.00 | 0.21 |
December | 0.432955E+09 | 0.903668E+09 | 0.00 | 10536615.06 | 0.00 | 0.00 | 0.111863E+10 | 0.00 | 0.20 |
Annual Sum or Average | 0.249339E+10 | 0.915734E+11 | 0.00 | 57837569.39 | 370470.64 | 0.00 | 0.578687E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.129243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.109454E+10 | 0.201989E+11 | 0.00 | 11981185.31 | 370470.64 | 0.00 | 0.167348E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.515604E+12 | 0.289468E+11 | 0.00 | 0.100965E+11 | 0.289980E+11 |
February | 0.582193E+12 | 0.324075E+11 | 0.00 | 0.670330E+10 | 0.369235E+11 |
March | 0.756408E+12 | 0.268689E+11 | 0.00 | 0.375527E+10 | 0.573263E+11 |
April | 0.833191E+12 | 0.272870E+11 | 0.00 | -0.294669E+10 | 0.790879E+11 |
May | 0.926096E+12 | 0.355111E+11 | 0.00 | -0.141866E+11 | 0.125534E+12 |
June | 0.915357E+12 | 0.353946E+11 | 0.00 | -0.228662E+11 | 0.153556E+12 |
July | 0.922040E+12 | 0.186934E+11 | 0.00 | -0.311587E+11 | 0.181630E+12 |
August | 0.890939E+12 | 0.317923E+11 | 0.00 | -0.338607E+11 | 0.195752E+12 |
September | 0.769171E+12 | 0.361254E+11 | 0.00 | -0.249945E+11 | 0.153914E+12 |
October | 0.654831E+12 | 0.371860E+11 | 0.00 | -0.149865E+11 | 0.115291E+12 |
November | 0.510026E+12 | 0.306345E+11 | 0.00 | -0.409377E+10 | 0.741056E+11 |
December | 0.466210E+12 | 0.321803E+11 | 0.00 | 0.602620E+10 | 0.435092E+11 |
Annual Sum or Average | 0.874207E+13 | 0.373028E+12 | 0.00 | -0.122512E+12 | 0.124563E+13 |
Minimum of Months | 0.466210E+12 | 0.186934E+11 | 0.00 | -0.338607E+11 | 0.289980E+11 |
Maximum of Months | 0.926096E+12 | 0.371860E+11 | 0.00 | 0.100965E+11 | 0.195752E+12 |