Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 10:43:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1931.21 | 399.41 | 399.41 |
Net Site Energy | 1931.21 | 399.41 | 399.41 |
Total Source Energy | 3133.17 | 648.00 | 648.00 |
Net Source Energy | 3133.17 | 648.00 | 648.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1432.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 206.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 499.15 | 1432.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1432.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 206.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1432.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 206.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 93.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 139.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 30.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 28.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.44 | 296.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 103.23 | 296.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 12.44 | 296.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 103.23 | 296.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 499.155 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 499.155 | 100.00 |
Total On-Site and Utility Electric Sources | 499.155 | 100.00 |
Total Electricity End Uses | 499.155 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 128.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2899.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 8.9961 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 5.6188 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 6.8172 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 8.9961 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 9.2031 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 5.6188 | 46.45 | 2.5587 | |
Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 6.8172 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 6.8172 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JAN-15:30 | 28-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 12-JAN-12:09 |
Heating | 0.00 | 221684.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 15699.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2576.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2691.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 38038.31 | 221684.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 221684.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 15699.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2576.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2691.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1552.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 654.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 294.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1580.82 | 1552.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 321.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 135.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 326.95 | 321.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 321.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 135.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 326.95 | 321.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.962027 |
ZONE2 FINE STORAGE DIRECT AIR | 1.62 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.27 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.27 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 91585.38 |
PSZ-OFFICE HEATING COIL | 29383.89 |
PSZ-FINE STORAGE HEATING COIL | 76202.41 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 91585.38 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.962027 | 0.962027 | 0.962027 | 0.962027 | 0.962027 | 0.962027 | 1.00 | 1.000000 | 0.962027 |
PSZ-FINE STORAGE | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.00 | 1.00 | 1.62 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.962027 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.62 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.962027 | 1065.12 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.62 | 1732.31 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.962027 | 0.962027 | 0.962027 | 0.962027 | 15924.96 | 29383.89 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.62 | 1.62 | 1.62 | 1.07 | 29805.84 | 76202.41 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.962030 | 0.481014 | 0.641353 | 15924.96 | 7962.48 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.62 | 0.809457 | 1.08 | 29805.84 | 14902.92 | 0.800560 | 0.800560 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 8.996 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.070 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 9.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.203 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 5.619 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 8.177 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2131.000 | 8.996 | 167.154 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2131.000 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 12823.730 | 9.203 | 427.458 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12823.730 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 18007.220 | 5.619 | 260.974 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 18007.220 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1041 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.4317E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.4042E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.4095 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.529 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 23.09 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 24.66 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.343 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
8 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
9 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
10 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
11 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
12 | 4 | 0.79647225E-12 | 0.96147816E-16 | -0.20666597E-14 | 0.11382549E-15 |
13 | 3 | -0.38972706E-03 | 0.28930881E-06 | -0.56581374E-04 | 0.15282143E-12 |
14 | 2 | 1.7513786 | 0.62914578E-02 | 1.1494565 | -0.74717338E-04 |
15 | 1 | -7.1131205 | 0.16244765 | -17.155584 | 0.33567575 |
16 | 0 | 5.6342095 | 0.10333854 | 16.278262 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.40943546E-08 | -0.48941433E-14 | 0.10002011E-14 | -0.40158259E-16 |
55 | 6 | 0.31272124E-05 | 0.19933103E-08 | 0.31973031E-02 | -0.26821658E-04 |
56 | 5 | -0.21335304E-03 | 0.11766416E-05 | -0.22414699 | 0.19598788E-02 |
57 | 4 | 0.48316011E-02 | 0.53476752E-04 | 4.8365802 | -0.45332602E-01 |
58 | 3 | -0.42187430E-01 | 0.42463702E-03 | -38.061149 | 0.39909293 |
59 | 2 | 0.14945981 | 0.70555311E-03 | 116.56127 | -1.4189736 |
60 | 1 | -0.21550367 | 0.21454475E-03 | -143.95282 | 2.0497880 |
61 | 0 | 0.10501452 | 0.52166033E-05 | 60.838472 | |
62 | 7 | -0.99354594E-08 | 0.85994744E-15 | -0.36446392E-14 | 0.33402613E-16 |
63 | 6 | 0.19007305E-05 | 0.85218543E-09 | 0.32020323E-02 | -0.26861330E-04 |
64 | 5 | -0.10257637E-03 | 0.49552608E-06 | -0.22441548 | 0.19622488E-02 |
65 | 4 | 0.21308868E-02 | 0.22341873E-04 | 4.8410464 | -0.45375540E-01 |
66 | 3 | -0.17974913E-01 | 0.17625076E-03 | -38.086349 | 0.39937154 |
67 | 2 | 0.62772635E-01 | 0.29099605E-03 | 116.61028 | -1.4196292 |
68 | 1 | -0.89915137E-01 | 0.87799409E-04 | -143.98166 | 2.0502620 |
69 | 0 | 0.43667207E-01 | 0.21083643E-05 | 60.838472 | |
70 | 7 | -0.10614037E-07 | 0.12466653E-14 | -0.85452615E-14 | 0.12855439E-15 |
71 | 6 | 0.18765462E-05 | 0.80237200E-09 | 0.32022472E-02 | -0.26863133E-04 |
72 | 5 | -0.98338504E-04 | 0.46542478E-06 | -0.22442766 | 0.19623563E-02 |
73 | 4 | 0.20165412E-02 | 0.20956150E-04 | 4.8412485 | -0.45377483E-01 |
74 | 3 | -0.16916006E-01 | 0.16514078E-03 | -38.087488 | 0.39938413 |
75 | 2 | 0.58934009E-01 | 0.27235831E-03 | 116.61249 | -1.4196588 |
76 | 1 | -0.84323034E-01 | 0.82076304E-04 | -143.98296 | 2.0502833 |
77 | 0 | 0.40927925E-01 | 0.19639094E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20666597E-14 | 0.96147816E-16 | 0.79647225E-12 | 0.11382549E-15 |
85 | 3 | -0.56581374E-04 | 0.28930881E-06 | -0.38972706E-03 | 0.15282143E-12 |
86 | 2 | 1.1494565 | 0.62914578E-02 | 1.7513786 | -0.74717338E-04 |
87 | 1 | -17.155584 | 0.16244765 | -7.1131205 | 0.33567575 |
88 | 0 | 16.278262 | 0.10333854 | 5.6342095 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2921_SHGC_SOUTH_0.45 | 34 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 35 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2921_SHGC_EAST_0.45 | 36 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.659 | 1.659 | 1.000 | 0.451 | ||
5 | SKYLIGHT_U_0.75_SHGC_0.6 | 38 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24753E-002 | 0.36619 | 0.44090 | 0.44090 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.91370E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.710 | 8.455E-004 | 5.523E-004 | 0.277 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6370E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2654E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1320E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6052E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4443E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0937E-003 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3694E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1743E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3288E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5224E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6515E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2692E-003 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6808E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4338E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7891E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6656E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4134E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7552E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2362E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5866E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4487E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7812E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7141E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3196E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7844E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0523E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0337E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6922E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5679E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4425E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3548E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5780E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5005E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.7185E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 8.2903E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.1490E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.4525E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0230E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.3344E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2282E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.6976E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 8.4544E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 8.2309E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.8856E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 7.1029E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4253E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.7337E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6319E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.3353E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 7.6029E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4336E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 6.0586E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.4119E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9200E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0260E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.0513E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4676E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 8.5531E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.4633E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.5870E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.4289E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2795E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.0076E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.0512E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4676E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9593.26979 | 11511.92375 | 0.80169 | 0.96203 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 7.00497E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11066.89061 | 13280.26874 | 0.31559 | 0.37871 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 20710.03108 | 24852.03729 | 1.34909 | 1.61891 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.89000 | 7.00637E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 33621.99821 | 40346.39785 | 0.80759 | 0.96911 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 27.06000 | 7.00663E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 76321.15281 | 91585.38337 | 1.89428 | 2.27314 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13888.71 | 0.96203 | 0.96203 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16217.92 | 0.37871 | 0.37871 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 28499.41 | 1.61891 | 1.61891 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 57284.14 | 0.96911 | 0.96911 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96203 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.61891 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.27314 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.27314 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 91585.38485 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 91585.38337 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96203 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96203 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96203 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96203 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96203 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.96203 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.61891 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.61891 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.61891 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.61891 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.61891 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.61891 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.96203 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.61891 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96203 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96203 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1065.11665 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96203 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96203 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96203 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96203 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96203 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48101 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64135 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15924.96000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7962.48000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15924.96000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29383.88502 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29383.88502 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.61891 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.61891 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1732.31412 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.61891 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.61891 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.61891 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06848 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.61891 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80946 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07927 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29805.84000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14902.92000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80056 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80056 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29805.84000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 76202.41288 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 76202.41288 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15178.5 | 12.15 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 28549.1 | 11.65 | 11.38 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.4133357915 | 0.3828636536 | Pass | Pass | 2.4609556153 | 8.6040956383 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7611242363 | 0.7131541599 | Pass | Pass | 0.7155486256 | 0.6621588706 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.0453661914E-003 | 4.9262540566E-003 | Pass | Pass | 3.4708699396E-002 | 3.7713266539E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4972.57 | 643.43 | 0.00 | 144.15 | 344.88 | 6105.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.102 | 0.104 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.043 | 0.043 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.386 | 0.410 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.040 | 0.040 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.410 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_WEST_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.659 | 0.451 | 0.452 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.2921_SHGC_NORTH_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.659 | 0.451 | 0.452 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.849 | 0.521 | 0.520 | |||||||||||||||||
North Total or Average | 6.51 | 1.659 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.146 | 0.539 | 0.537 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.016 | 1.198 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 8.9961 | 236.88 | 2131.00 | LightsWired | LTG_SCH_OFFICE | 51.55 | 168.00 | 47.06 | 0.0000 | Y | 18.83 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 9.2031 | 1393.41 | 12823.73 | LightsWired | LTG_SCH_FINE_STORAGE | 34.09 | 168.00 | 33.37 | 0.0000 | Y | 80.33 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 5.6188 | 3204.84 | 18007.22 | LightsWired | LTG_SCH_BULK_STORAGE | 34.09 | 168.00 | 31.82 | 0.0000 | Y | 107.55 |
Interior Lighting Total | 6.8172 | 4835.13 | 32961.95 | 206.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 18007.22 | 2088.84 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2131.00 | 309.00 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.05 | 2131.00 | 106.55 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 94.73 | AstronomicalClock | - | 44.84 | 44.84 | 0.80 | |
EXTERIOR_LIGHTS_B | 6863.48 | AstronomicalClock | - | 83.06 | 71.59 | 92.24 | |
Exterior Lighting Total | 6958.21 | 93.04 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15924.96 | 12750.48 | 3174.48 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29805.84 | 23861.36 | 5944.48 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15178.5 | 12.15 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 28549.1 | 11.65 | 11.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 91585.38 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29383.89 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 76202.41 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.27 | 211.20 | 92.91 | 1.00 | 3.50 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1065.12 | 1107.16 | 1.00 | 1.41 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.62 | 1732.31 | 1070.05 | 1.00 | 1.35 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9593.27 | 11511.92 | 48.60 | 0.802 | 0.962 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00827 | 25.97 | 0.00700 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20710.03 | 24852.04 | 17.84 | 1.349 | 1.619 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.70 | 26.70 | 0.00833 | 26.89 | 0.00701 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 0.00 | 29.44 | 0.00734 | 27.06 | 0.00701 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11066.89 | 13280.27 | 56.06 | 0.316 | 0.379 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00828 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33622.00 | 40346.40 | 28.96 | 0.808 | 0.969 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00774 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 76321.15 | 91585.38 | 28.58 | 1.894 | 2.273 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00730 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.96 | 0.96 | 0.38 | 0.38 | 0.9620 | 0.9620 | 0.9620 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.62 | 1.62 | 0.97 | 0.97 | 1.6189 | 1.6189 | 1.6189 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 91585.385 | 91585.385 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 91585.38 | 91585.38 | 2.273140 | 10.00 | 9.51 | 0.00729828 | 43.33 | 21.96 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00729828 | 94.2013 | 91585.38 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15924.960 | 12750.478 | 0.962030 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7962.48 | 7778.73 | 0.641353 | 25.04 | 16.28 | 0.00813780 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 15.9482 | 23.90 | 0.00827257 | 44.1206 | 9593.27 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29383.885 | 29383.885 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 29383.89 | 29383.89 | 0.962027 | 14.36 | 11.51 | 0.00740974 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 10.6322 | 21.10 | 0.00828362 | 52.3689 | 11066.89 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 29805.840 | 23861.363 | 1.618910 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 14902.92 | 14902.92 | 1.079273 | 27.69 | 17.07 | 0.00798194 | 12.00 | 11.10 | 0.00798194 | 27.09 | 0.00700668 | 16.04 | 39.3516 | 26.70 | 0.00832957 | 37.6059 | 20675.60 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 76202.413 | 76202.413 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 76202.41 | 76202.41 | 1.618914 | 0.49 | 0.49 | 0.00572345 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 26.2343 | 15.56 | 0.00773602 | 69.3087 | 33622.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 91585.385 | 91585.385 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.273140 | 2.69466903 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 91585.38 | 91585.38 | 1.0000 | 2.69466903 | 2.273140 | 10.00 | 9.51 | 0.00729828 | 28436.0 | 43.33 | 21.96 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91585.38 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 10.00 | 0.00729828 | 10.00 | 0.00729828 | 94.2013 | 91585.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15924.960 | 12750.478 | 0.962030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9678 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.962027 | 1.14042466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 7962.48 | 7778.73 | 1.0000 | 0.76028544 | 0.641353 | 25.04 | 16.28 | 0.00813780 | 45887.4 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7962.48 | 25.97 | 0.00700497 | 15.63 | 0.10228463 | 15.9482 | 23.90 | 0.00827257 | 23.90 | 0.00827257 | 44.1206 | 9593.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29383.885 | 29383.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.962027 | 1.14042466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 29383.89 | 29383.89 | 1.0000 | 1.14042466 | 0.962027 | 14.36 | 11.51 | 0.00740974 | 33157.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29383.89 | -41.90 | 0.00006450 | -41.90 | 0.10228463 | 10.6322 | 21.05 | 0.00828362 | 21.10 | 0.00828362 | 52.3689 | 11066.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29805.840 | 23861.363 | 1.618910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6780 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.618914 | 1.91912384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 14902.92 | 14902.92 | 1.0000 | 1.27941302 | 1.079273 | 27.69 | 17.07 | 0.00798194 | 48195.6 | 12.00 | 11.10 | 0.00798194 | 32198.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14902.92 | 27.09 | 0.00700668 | 16.04 | 0.42471127 | 39.3516 | 26.70 | 0.00832957 | 26.70 | 0.00832957 | 37.6059 | 20675.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76202.413 | 76202.413 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.618914 | 1.91912384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 76202.41 | 76202.41 | 1.0000 | 1.91912384 | 1.618914 | 0.49 | 0.49 | 0.00572345 | 14806.6 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76202.41 | -41.90 | 0.00006450 | -41.90 | 0.42471127 | 26.2343 | 15.56 | 0.00773602 | 15.56 | 0.00773602 | 69.3087 | 33622.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.96 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.62 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2657.50 | 3259.83 | 2543.33 |
ZONE2 FINE STORAGE | 3053.83 | 3219.17 | 2752.33 |
ZONE3 BULK STORAGE | 3005.83 | 3448.83 | 2899.17 |
Facility | 3210.17 | 3451.83 | 2899.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 175.50 | 0.00 | 59.33 | 0.00 |
ZONE2 FINE STORAGE | 696.83 | 0.00 | 30.17 | 0.00 |
ZONE3 BULK STORAGE | 164.17 | 0.00 | 58.00 | 0.00 |
Facility | 929.33 | 0.00 | 128.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.541 | 0.405 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.438 | 0.146 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.087 | 0.000 | 0.033 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.30 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.30 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.05 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1945210.47 | 0.00 | 1945210.47 | 1971242.25 | 3916452.73 | 3225648.14 | 5727.33 | 2427.61 | 605.06 | 0.00 |
ZONE2 FINE STORAGE | 4676519.68 | 0.00 | 4676519.68 | 4361427.52 | 9037947.20 | 13393694.68 | 5729.92 | 2983.50 | 46.58 | 0.08 |
ZONE3 BULK STORAGE | 0.00 | 10266576.17 | 10266576.17 | 24470699.40 | 34737275.57 | 30805497.77 | 8651.17 | 10.50 | 98.33 | 4375.33 |
Total Facility | 6621730.15 | 10266576.17 | 16888306.32 | 30803369.17 | 47691675.49 | 47424840.58 | 8717.83 | 3017.67 | 722.64 | 4375.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1486 | 0.0000 | 0.1486 | 0.1119 | 0.2605 | 0.1023 | 603.33 | 2427.61 | 605.06 |
ZONE2 FINE STORAGE | 0.3573 | 0.0000 | 0.3573 | 0.1192 | 0.4765 | 0.4247 | 606.00 | 2983.50 | 46.50 |
ZONE3 BULK STORAGE | 0.0000 | 0.3240 | 0.3240 | 0.8584 | 1.1824 | 0.9768 | 3593.83 | 3.50 | 38.67 |
Total Facility | 0.5059 | 0.3240 | 0.8298 | 1.0895 | 1.9193 | 1.5038 | 3593.83 | 3010.67 | 662.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2733538.76 | 0.00 | 2733538.76 | 3225648.14 | 5726.17 | 0.00 | 3033.83 | 0.00 |
PSZ-FINE STORAGE | 6572267.36 | 0.00 | 6572267.36 | 13393694.68 | 5729.92 | 0.00 | 3030.08 | 0.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2088 | 0.0000 | 0.2088 | 0.1023 | 602.17 | 0.00 | 3033.83 |
PSZ-FINE STORAGE | 0.5021 | 0.0000 | 0.5021 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2666.11 | 369.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3012.25 | 17.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2155 | 0.5005 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6013 | 0.8550 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 319 |
Fields with Defaults | 1046 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
Electricity:Building | 345.99 | 2396.55 | 16-APR-15:00 | 25812.02 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 50.77 | 815.73 | 12-MAR-17:10 | 3198.43 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 345.99 | 2396.55 | 16-APR-15:00 | 25812.02 | 02-JAN-09:10 |
InteriorLights:Electricity | 206.70 | 1822.80 | 14-APR-17:10 | 15699.40 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.83 | 241.98 | 12-MAR-17:10 | 1285.93 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 206.70 | 1822.80 | 14-APR-17:10 | 15699.40 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 206.70 | 1822.80 | 14-APR-17:10 | 15699.40 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.83 | 241.98 | 12-MAR-17:10 | 1285.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 206.70 | 1822.80 | 14-APR-17:10 | 15699.40 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 80.33 | 705.31 | 01-JAN-00:10 | 5995.09 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 214.89 | 875.51 | 05-MAR-10:50 | 16618.50 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 107.55 | 875.51 | 05-MAR-10:50 | 8418.38 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 107.55 | 875.51 | 05-MAR-10:50 | 8418.38 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 139.29 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 30.86 | 0.00 | 18-MAR-17:10 | 2868.50 | 28-JAN-17:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
ElectricityPurchased:Plant | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
Cogeneration:ElectricityPurchased | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
General:Cogeneration:ElectricityPurchased | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
ElectricityNet:Plant | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
Cogeneration:ElectricityNet | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
General:Cogeneration:ElectricityNet | 499.15 | 2879.55 | 16-APR-15:00 | 38038.31 | 12-JAN-15:30 |
Electricity:HVAC | 31.70 | 0.00 | 18-MAR-17:10 | 5780.33 | 21-JUL-16:00 |
General:Fans:Electricity | 30.86 | 0.00 | 18-MAR-17:10 | 2868.50 | 28-JAN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 0.84 | 0.00 | 01-JAN-00:10 | 4022.29 | 21-JUL-16:00 |
General:Cooling:Electricity | 0.84 | 0.00 | 01-JAN-00:10 | 4022.29 | 21-JUL-16:00 |
ExteriorLights:Electricity | 93.04 | 0.00 | 01-JAN-11:20 | 6958.21 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 93.04 | 0.00 | 01-JAN-11:20 | 6958.21 | 01-JAN-06:10 |
Electricity:Plant | 28.43 | 483.00 | 03-JAN-06:20 | 3131.65 | 01-FEB-13:00 |
WaterSystems:Electricity | 28.43 | 483.00 | 03-JAN-06:20 | 3131.65 | 01-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 28.43 | 483.00 | 03-JAN-06:20 | 3131.65 | 01-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1432.06 | 0.00 | 18-MAR-17:10 | 221684.00 | 28-JAN-17:10 |
NaturalGas:HVAC | 1432.06 | 0.00 | 18-MAR-17:10 | 221684.00 | 28-JAN-17:10 |
Heating:NaturalGas | 1432.06 | 0.00 | 18-MAR-17:10 | 221684.00 | 28-JAN-17:10 |
General:Heating:NaturalGas | 1432.06 | 0.00 | 18-MAR-17:10 | 221684.00 | 28-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2124.89 | 0.00 | 18-MAR-17:10 | 327622.01 | 29-JAN-00:10 |
EnergyTransfer:Building | 1028.95 | 0.00 | 18-MAR-17:10 | 164139.85 | 29-JAN-00:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 85.74 | 0.00 | 01-JAN-00:40 | 30582.91 | 27-FEB-07:20 |
Heating:EnergyTransfer | 1006.64 | 0.00 | 18-MAR-17:10 | 164139.85 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 78.58 | 0.00 | 01-JAN-00:40 | 30582.91 | 27-FEB-07:20 |
General:Heating:EnergyTransfer | 1006.64 | 0.00 | 18-MAR-17:10 | 164139.85 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 78.58 | 0.00 | 01-JAN-00:40 | 30582.91 | 27-FEB-07:20 |
Cooling:EnergyTransfer | 22.31 | 0.00 | 01-JAN-00:10 | 13221.01 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 7.16 | 0.00 | 01-JAN-00:10 | 7111.05 | 05-AUG-07:10 |
General:Cooling:EnergyTransfer | 22.31 | 0.00 | 01-JAN-00:10 | 13221.01 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 7.16 | 0.00 | 01-JAN-00:10 | 7111.05 | 05-AUG-07:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 250.83 | 0.00 | 01-JAN-00:40 | 64333.10 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 235.68 | 0.00 | 01-JAN-00:40 | 64333.10 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 235.68 | 0.00 | 01-JAN-00:40 | 64333.10 | 29-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.15 | 0.00 | 01-JAN-00:10 | 9843.46 | 23-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.15 | 0.00 | 01-JAN-00:10 | 9843.46 | 23-JUL-14:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 692.38 | 0.00 | 07-FEB-13:10 | 92518.99 | 24-FEB-18:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 692.38 | 0.00 | 07-FEB-13:10 | 92518.99 | 24-FEB-18:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 692.38 | 0.00 | 07-FEB-13:10 | 92518.99 | 24-FEB-18:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1095.93 | 0.00 | 18-MAR-17:10 | 173931.04 | 28-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1091.98 | 0.00 | 18-MAR-17:10 | 173931.04 | 28-JAN-17:10 |
CoolingCoils:EnergyTransfer | 3.96 | 0.00 | 01-JAN-00:10 | 17026.88 | 21-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 78.582 | -7.160 | 0.000 | 0.000 | 10.372 | 18.827 | 31.946 | 9.072 | 0.000 | 0.052 | 0.000 | 0.000 | -12.795 | 0.000 | -49.282 | -79.613 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 235.681 | -15.147 | 0.000 | 0.000 | 28.589 | 80.328 | 0.000 | 0.000 | 0.000 | 0.034 | 0.001 | 0.000 | 0.000 | 0.000 | -81.510 | -247.975 |
ZONE3 BULK STORAGE | 692.379 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 73.766 | 107.546 | 107.344 | 84.387 | 0.000 | 2.631 | 0.000 | 0.000 | -123.867 | 0.000 | -490.691 | -453.495 |
Total Facility | 692.379 | 0.000 | 314.263 | -22.307 | 0.000 | 0.000 | 112.726 | 206.701 | 139.290 | 93.460 | 0.000 | 2.717 | 0.001 | 0.000 | -136.662 | 0.000 | -621.484 | -781.083 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | -22239.80 | 0.00 | 0.00 | 802.75 | 1082.03 | 1912.50 | 339.02 | 0.00 | 0.00 | 18103.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-14:45 | 0.00 | 0.00 | 0.00 | -19685.06 | 0.00 | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 19137.29 | 0.00 | -0.00 | 0.00 | -157.53 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | -28343.04 | 0.00 | 0.00 | 8867.94 | 12938.16 | 10112.62 | 8911.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12487.55 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-FEB-06:31 | 0.00 | 0.00 | 31324.69 | 0.00 | 0.00 | 0.00 | 154.26 | 384.11 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.57 | 0.00 | -4955.22 | -26435.03 |
ZONE2 FINE STORAGE | 23-FEB-18:41 | 0.00 | 0.00 | 79198.40 | 0.00 | 0.00 | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -17521.61 | -62382.10 |
ZONE3 BULK STORAGE | 24-FEB-18:00 | 92518.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2670.90 | 5942.38 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8347.51 | 0.00 | -81754.81 | -13079.43 |
Total Facility | 28-JAN-06:01 | 91830.29 | 0.00 | 108520.70 | 0.00 | 0.00 | 0.00 | 1466.99 | 2079.82 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8627.17 | 0.00 | -103575.50 | -94318.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9620 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9620 | 0.1063 | 1.0000 | Not calculated | 0.1023 | 0.1063 | ||
PSZ-FINE STORAGE | 1.6189 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6189 | 0.2623 | 1.0000 | Not calculated | 0.4247 | 0.2623 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9620 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9620 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1063 | ||
PSZ-FINE STORAGE | 1.6189 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6189 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2623 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9620 | 0.9620 | 0.9620 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6189 | 1.6189 | 1.6189 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9620 | 0.9620 | 0.9620 | 0.9620 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6189 | 1.6189 | 1.6189 | 1.6189 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9620 | 0.9620 | 0.9620 | No | 0.1023 | 0.2701 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6189 | 1.6189 | 1.6189 | No | 0.4247 | 0.4382 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9620 | 0.9620 | 0.9620 | 0.9620 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6189 | 1.6189 | 1.6189 | 1.6189 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 128.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 128.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1432.06 | 221684.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 0.84 | 4022.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 206.70 | 15699.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 93.04 | 6958.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.29 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 30.86 | 2868.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.43 | 3131.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.29 | 499.15 |
Natural Gas | 0.00 | 1432.06 |
Additional | 0.00 | 0.00 |
Total | 139.29 | 1931.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 42.75 |
Space Heating | 0.00 |
Space Cooling | 0.17 |
Fans (All) | 6.38 |
Service Water Heating | 5.88 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 103.23 |
Subtotal | 103.23 |
Natural Gas [MJ/m2] | |
Space Heating | 296.18 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 296.18 |
Subtotal | 296.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.70 |
Space Heating | 74.15 |
Space Cooling | 0.04 |
Fans (All) | 1.60 |
Service Water Heating | 1.47 |
Receptacle Equipment | 7.21 |
Miscellaneous | 4.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2688. | 8760. |
LTG_SCH_BULK_STORAGE | 1777. | 8760. |
LTG_SCH_FINE_STORAGE | 1777. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Min | 8737.67 | 0.17 | 0.00 | 0.00 | 0.00 |
Max | 8759.83 | 22.33 | 0.00 | 0.00 | 0.00 |
Average | 8748.28 | 11.72 | 0.00 | 0.00 | 0.00 |
Sum | 26244.83 | 35.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82233.50 | 485.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 191181.50 | 11.50 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 191181.50 | 485.50 | 0.00 | 0.00 | 0.00 |
Average | 102147.33 | 165.67 | 0.00 | 0.00 | 0.00 |
Sum | 306442.00 | 497.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8698.00 | 62.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
Min | 8698.00 | 4.33 | 0.00 | 0.00 | 0.00 |
Max | 8755.67 | 62.00 | 0.00 | 0.00 | 0.00 |
Average | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
Sum | 26196.00 | 84.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81222.00 | 1497.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190933.17 | 259.83 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190933.17 | 1497.00 | 0.00 | 0.00 | 0.00 |
Average | 101727.39 | 585.61 | 0.00 | 0.00 | 0.00 |
Sum | 305182.17 | 1756.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1483380.80 | 2456.19 | 21-JAN-08:05 | -7.1 | -7.3 | 0.492071E+09 | 603.25 | 02-JAN-11:39 | -7.1 | -7.3 |
February | 1662397.85 | 2378.69 | 04-FEB-08:05 | -19.1 | -19.4 | 0.453494E+09 | 603.25 | 11-FEB-08:20 | -5.9 | -6.5 |
March | 2593837.98 | 2058.97 | 22-MAR-07:05 | -3.4 | -4.4 | 0.532848E+09 | 603.26 | 22-MAR-07:19 | -3.5 | -4.5 |
April | 8949400.20 | 2241.69 | 13-APR-07:05 | -5.1 | -6.8 | 0.495545E+09 | 689.31 | 22-APR-15:00 | 15.00 | 6.60 |
May | 76231415.31 | 1655.67 | 27-MAY-07:07 | 0.10 | -0.8 | 0.553874E+09 | 768.96 | 31-MAY-15:00 | 22.20 | 10.79 |
June | 0.193259E+10 | 22240.09 | 17-JUN-07:02 | 10.18 | 8.41 | 0.647680E+09 | 879.32 | 24-JUN-07:10 | 12.70 | 12.16 |
July | 0.303772E+10 | 18740.26 | 01-JUL-07:02 | 13.22 | 11.22 | 0.632381E+09 | 879.39 | 22-JUL-07:10 | 17.48 | 13.79 |
August | 0.200371E+10 | 19691.01 | 12-AUG-07:02 | 15.00 | 10.63 | 0.664634E+09 | 879.39 | 12-AUG-07:10 | 15.00 | 10.63 |
September | 86809062.31 | 2267.18 | 30-SEP-07:07 | -5.0 | -5.5 | 0.509380E+09 | 768.96 | 01-SEP-15:00 | -5.0 | -5.5 |
October | 4594007.70 | 2208.38 | 12-OCT-07:05 | -5.1 | -5.9 | 0.493540E+09 | 603.95 | 07-OCT-07:19 | -5.1 | -5.9 |
November | 1969896.82 | 3028.70 | 18-NOV-08:05 | -11.6 | -12.0 | 0.473560E+09 | 603.25 | 18-NOV-08:20 | -11.5 | -11.9 |
December | 1561783.11 | 3068.80 | 30-DEC-08:05 | -14.2 | -14.6 | 0.492836E+09 | 603.25 | 23-DEC-08:20 | -14.2 | -14.6 |
Annual Sum or Average | 0.715988E+10 | 0.644184E+10 | ||||||||
Minimum of Months | 1483380.80 | 1655.67 | -19.1 | -19.4 | 0.453494E+09 | 603.25 | -14.2 | -14.6 | ||
Maximum of Months | 0.303772E+10 | 22240.09 | 15.00 | 11.22 | 0.664634E+09 | 879.39 | 22.20 | 13.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.649180E+09 | 787.42 | 14-JAN-11:09 | -19.6 | -19.8 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.597250E+09 | 787.42 | 02-FEB-10:39 | -7.3 | -7.9 |
March | 0.236030E+09 | 5145.35 | 22-MAR-12:40 | 4.03 | 1.36 | 0.701644E+09 | 839.48 | 22-MAR-15:09 | 5.60 | 2.29 |
April | 0.178874E+10 | 5803.29 | 24-APR-11:40 | 2.77 | -2.1 | 0.696184E+09 | 1175.53 | 22-APR-14:30 | 2.77 | -2.1 |
May | 0.202170E+10 | 5976.26 | 16-MAY-07:03 | 3.58 | 2.20 | 0.972738E+09 | 1589.35 | 13-MAY-15:09 | 3.58 | 2.20 |
June | 0.209986E+10 | 6103.08 | 17-JUN-07:02 | 10.18 | 8.41 | 0.149328E+10 | 2246.81 | 30-JUN-14:09 | 27.38 | 16.79 |
July | 0.244189E+10 | 19686.92 | 23-JUL-14:45 | 25.50 | 15.47 | 0.163213E+10 | 2246.82 | 22-JUL-10:00 | 25.50 | 15.47 |
August | 0.305216E+10 | 8388.34 | 30-AUG-07:03 | 0.78 | -1.1 | 0.151486E+10 | 2246.80 | 04-AUG-14:39 | 0.78 | -1.1 |
September | 0.285130E+10 | 7049.38 | 15-SEP-07:03 | 0.37 | 0.11 | 0.789068E+09 | 1474.67 | 02-SEP-15:09 | 0.37 | 0.11 |
October | 0.654766E+09 | 7670.93 | 16-OCT-10:05 | -1.6 | -2.0 | 0.657697E+09 | 969.75 | 03-OCT-15:09 | -1.6 | -2.0 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.623281E+09 | 787.42 | 30-NOV-11:20 | -28.3 | -28.6 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.649180E+09 | 787.42 | 06-DEC-16:40 | -23.0 | -23.3 |
Annual Sum or Average | 0.151464E+11 | 0.109765E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.597250E+09 | 787.42 | -28.3 | -28.6 | ||
Maximum of Months | 0.305216E+10 | 19686.92 | 25.50 | 15.47 | 0.163213E+10 | 2246.82 | 27.38 | 16.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.613019E+09 | 780.52 | 21-JAN-13:30 | -5.6 | -6.2 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.579681E+09 | 809.60 | 11-FEB-16:10 | -0.2 | -2.0 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.707473E+09 | 1053.25 | 22-MAR-15:20 | 5.60 | 2.35 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 | 0.788688E+09 | 1501.69 | 22-APR-15:00 | 15.00 | 6.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.156224E+10 | 2506.22 | 13-MAY-15:20 | 20.00 | 9.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.278001E+10 | 4510.36 | 30-JUN-15:20 | 26.47 | 16.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.342055E+10 | 5210.38 | 29-JUL-15:00 | 30.00 | 18.34 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.324747E+10 | 5002.26 | 04-AUG-15:09 | 22.70 | 14.61 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.157170E+10 | 3054.31 | 02-SEP-15:30 | 16.70 | 10.62 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.12 | 0.702701E+09 | 1251.16 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.618409E+09 | 790.74 | 06-NOV-14:30 | -10.8 | -12.0 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.642801E+09 | 780.37 | 27-DEC-13:09 | -23.4 | -23.6 |
Annual Sum or Average | 0.00 | 0.172347E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.579681E+09 | 780.37 | -23.4 | -23.6 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.342055E+10 | 5210.38 | 30.00 | 18.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139626E+11 | 30967.00 | 31-JAN-06:31 | -25.2 |
February | 0.116298E+11 | 31324.61 | 24-FEB-06:31 | -25.6 |
March | 0.114420E+11 | 30697.90 | 15-MAR-05:42 | -25.3 |
April | 0.552363E+10 | 30225.29 | 03-APR-06:13 | -21.3 |
May | 0.125480E+10 | 29487.69 | 05-MAY-06:01 | 3.98 |
June | 0.163427E+09 | 9982.61 | 02-JUN-07:03 | 9.50 |
July | 98997856.07 | 7835.18 | 05-JUL-07:03 | 8.40 |
August | 0.232947E+09 | 29117.68 | 31-AUG-06:02 | -1.5 |
September | 0.213301E+10 | 29589.05 | 25-SEP-06:01 | -1.8 |
October | 0.699359E+10 | 30244.17 | 27-OCT-05:52 | -18.3 |
November | 0.115372E+11 | 30304.47 | 27-NOV-07:12 | -26.7 |
December | 0.136119E+11 | 30590.15 | 22-DEC-06:32 | -25.5 |
Annual Sum or Average | 0.785841E+11 | |||
Minimum of Months | 98997856.07 | 7835.18 | -26.7 | |
Maximum of Months | 0.139626E+11 | 31324.61 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456366E+11 | 79181.94 | 28-JAN-05:21 | -17.5 |
February | 0.378801E+11 | 79197.86 | 23-FEB-18:41 | -20.9 |
March | 0.324328E+11 | 78560.98 | 04-MAR-06:42 | -27.0 |
April | 0.151152E+11 | 78500.92 | 02-APR-20:22 | -12.8 |
May | 0.970385E+09 | 40186.81 | 01-MAY-05:10 | 7.30 |
June | 63883850.30 | 696.10 | 02-JUN-07:00 | 9.40 |
July | 50089112.88 | 773.36 | 20-JUL-07:00 | 14.40 |
August | 73429096.31 | 1078.42 | 23-AUG-16:30 | 25.00 |
September | 0.221355E+10 | 54590.73 | 30-SEP-04:33 | -4.2 |
October | 0.203575E+11 | 78177.54 | 31-OCT-05:42 | -17.9 |
November | 0.359311E+11 | 78390.40 | 10-NOV-02:62 | -19.6 |
December | 0.449563E+11 | 78783.19 | 06-DEC-06:01 | -28.7 |
Annual Sum or Average | 0.235681E+12 | |||
Minimum of Months | 50089112.88 | 696.10 | -28.7 | |
Maximum of Months | 0.456366E+11 | 79197.86 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133996E+12 | 92502.06 | 28-JAN-09:00 | -20.0 |
February | 0.113855E+12 | 92518.99 | 24-FEB-18:00 | -22.8 |
March | 0.110811E+12 | 92044.85 | 16-MAR-08:00 | -21.7 |
April | 0.500050E+11 | 92013.55 | 02-APR-19:42 | -11.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.118926E+09 | 10822.81 | 30-SEP-05:00 | -4.4 |
October | 0.608838E+11 | 89919.91 | 27-OCT-04:00 | -17.8 |
November | 0.897809E+11 | 91835.91 | 10-NOV-02:62 | -19.6 |
December | 0.132929E+12 | 92255.80 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.692380E+12 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.133996E+12 | 92518.99 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.168673E+10 | 1285.93 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.150374E+10 | 1285.93 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.163276E+10 | 1285.93 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.148844E+10 | 1247.45 | 04-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.151792E+10 | 1194.85 | 20-MAY-08:30 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.147016E+10 | 1191.68 | 08-JUN-07:30 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.148011E+10 | 1212.59 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.157257E+10 | 1207.61 | 18-AUG-15:00 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.153468E+10 | 1259.10 | 21-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.162905E+10 | 1285.93 | 03-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.161559E+10 | 1285.93 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.169483E+10 | 1285.93 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.188266E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.147016E+10 | 1191.68 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.169483E+10 | 1285.93 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.668164E+10 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.611542E+10 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.706504E+10 | 5995.09 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.662070E+10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.687334E+10 | 5995.09 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.681240E+10 | 5995.09 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.668164E+10 | 5995.09 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.706504E+10 | 5995.09 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.662070E+10 | 5995.09 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.668164E+10 | 5995.09 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.642900E+10 | 5995.09 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.668164E+10 | 5995.09 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.803282E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.611542E+10 | 5995.09 | 0.00 | 0.00 | |
Maximum of Months | 0.706504E+10 | 5995.09 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.937630E+10 | 8418.38 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.847848E+10 | 8418.38 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.947805E+10 | 8418.38 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.868429E+10 | 8092.87 | 01-APR-14:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.884321E+10 | 8092.87 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.864066E+10 | 8092.87 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.854336E+10 | 8092.87 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.915495E+10 | 8418.38 | 30-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.881019E+10 | 8418.38 | 18-SEP-14:30 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.916173E+10 | 8418.38 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.899258E+10 | 8418.38 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.938243E+10 | 8418.38 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.107546E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.847848E+10 | 8092.87 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.947805E+10 | 8418.38 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.168673E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700094E+10 |
February | 0.127628E+10 | 0.150374E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550146E+10 |
March | 0.149825E+10 | 0.163276E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641471E+10 |
April | 0.138726E+10 | 0.148844E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412093E+10 |
May | 0.144276E+10 | 0.151792E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220685E+10 |
June | 0.144276E+10 | 0.147016E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16022869.86 | 0.145782E+10 |
July | 0.138726E+10 | 0.148011E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29351134.60 | 0.118916E+10 |
August | 0.149825E+10 | 0.157257E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6259487.49 | 0.183182E+10 |
September | 0.138726E+10 | 0.153468E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231992E+10 |
October | 0.138726E+10 | 0.162905E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469706E+10 |
November | 0.133177E+10 | 0.161559E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579757E+10 |
December | 0.138726E+10 | 0.169483E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674418E+10 |
Annual Sum or Average | 0.168137E+11 | 0.188266E+11 | 0.319458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51633491.95 | 0.492824E+11 |
Minimum of Months | 0.127628E+10 | 0.147016E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118916E+10 |
Maximum of Months | 0.149825E+10 | 0.169483E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29351134.60 | 0.700094E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100963E+11 |
February | 0.300332E+10 | 0.611542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835539E+10 |
March | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120429E+11 |
April | 0.326447E+10 | 0.662070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106165E+11 |
May | 0.339505E+10 | 0.687334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4511562.98 | 0.499489E+10 |
June | 0.339505E+10 | 0.681240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3151493.85 | 0.369266E+10 |
July | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20648823.30 | 0.328519E+10 |
August | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5606154.51 | 0.405791E+10 |
September | 0.326447E+10 | 0.662070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354800E+10 |
October | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934803E+10 |
November | 0.313390E+10 | 0.642900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377724E+10 |
December | 0.326447E+10 | 0.668164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769538E+10 |
Annual Sum or Average | 0.395654E+11 | 0.803282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33918034.64 | 0.815104E+11 |
Minimum of Months | 0.300332E+10 | 0.611542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328519E+10 |
Maximum of Months | 0.352563E+10 | 0.706504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20648823.30 | 0.120429E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.937630E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452347E+11 |
February | 0.690763E+10 | 0.847848E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371406E+11 |
March | 0.810895E+10 | 0.947805E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520316E+11 |
April | 0.750829E+10 | 0.868429E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79007824.05 | 0.376913E+11 |
May | 0.780862E+10 | 0.884321E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891844E+09 | 0.163614E+11 |
June | 0.780862E+10 | 0.864066E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472815E+09 | 0.127399E+11 |
July | 0.750829E+10 | 0.854336E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225861E+09 | 0.147154E+11 |
August | 0.810895E+10 | 0.915495E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165813E+09 | 0.205277E+11 |
September | 0.750829E+10 | 0.881019E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168705E+11 |
October | 0.750829E+10 | 0.916173E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24328599.58 | 0.371766E+11 |
November | 0.720796E+10 | 0.899258E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171384E+11 |
December | 0.750829E+10 | 0.938243E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373997E+11 |
Annual Sum or Average | 0.910005E+11 | 0.107546E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185967E+10 | 0.345028E+12 |
Minimum of Months | 0.690763E+10 | 0.847848E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127399E+11 |
Maximum of Months | 0.810895E+10 | 0.947805E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891844E+09 | 0.520316E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1285.93 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 24799.06 | 12-JAN-12:02 |
February | 1680.92 | 01-FEB-08:09 | 1285.93 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23460.00 | 27-FEB-07:50 |
March | 1680.92 | 01-MAR-08:09 | 1285.93 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 21033.74 | 01-MAR-07:20 |
April | 1680.92 | 01-APR-07:10 | 1247.45 | 04-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 18438.21 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1194.85 | 20-MAY-08:30 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 7748.73 | 16-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1191.68 | 08-JUN-07:30 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.11 | 29-JUN-16:10 | 4921.79 | 07-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1212.59 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2450.40 | 21-JUL-16:10 | 5771.49 | 17-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1207.61 | 18-AUG-15:00 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 719.91 | 11-AUG-16:10 | 8984.13 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1259.10 | 21-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 10517.86 | 29-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1285.93 | 03-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 17845.97 | 31-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1285.93 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21952.38 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1285.93 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 23480.28 | 15-DEC-12:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1191.68 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4921.79 | |||||
Maximum of Months | 1680.92 | 1285.93 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2450.40 | 24799.06 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 5995.09 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 34932.16 | 28-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 5995.09 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21109.00 | 23-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 5995.09 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 16048.16 | 25-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 5995.09 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 18081.40 | 01-APR-18:52 |
May | 3955.50 | 01-MAY-07:10 | 5995.09 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.64 | 30-MAY-18:00 | 9276.50 | 27-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 5995.09 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.54 | 30-JUN-15:10 | 8155.40 | 24-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 5995.09 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.03 | 21-JUL-16:00 | 5012.03 | 04-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 5995.09 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.34 | 23-AUG-18:00 | 7750.63 | 29-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 5995.09 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5153.64 | 29-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 5995.09 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 11980.71 | 27-OCT-06:03 |
November | 3955.50 | 01-NOV-07:10 | 5995.09 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11730.60 | 03-NOV-20:00 |
December | 3955.50 | 01-DEC-08:09 | 5995.09 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 13620.66 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5012.03 | ||||
Maximum of Months | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.03 | 34932.16 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 8418.38 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 126737.58 | 28-JAN-15:00 |
February | 9097.65 | 01-FEB-08:09 | 8418.38 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 87848.58 | 25-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 8418.38 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 68307.81 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 8092.87 | 01-APR-14:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2841.63 | 22-APR-14:00 | 64675.58 | 01-APR-18:52 |
May | 9097.65 | 01-MAY-07:10 | 8092.87 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10880.51 | 30-MAY-18:00 | 43112.50 | 27-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 8092.87 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8730.91 | 30-JUN-15:00 | 31623.13 | 24-JUN-21:00 |
July | 9097.65 | 01-JUL-07:10 | 8092.87 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14576.19 | 21-JUL-16:00 | 19677.40 | 04-JUL-17:00 |
August | 9097.65 | 01-AUG-07:10 | 8418.38 | 30-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5827.11 | 23-AUG-18:00 | 40182.50 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 8418.38 | 18-SEP-14:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20692.90 | 21-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 8418.38 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.04 | 01-OCT-16:50 | 48555.32 | 31-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 8418.38 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 49305.47 | 01-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 8418.38 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 69519.73 | 22-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 8092.87 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19677.40 | |||||
Maximum of Months | 9097.65 | 8418.38 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14576.19 | 126737.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2456.19 | 21-JAN-08:05 | 6723.69 | 5143.72 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.48 |
February | 2378.69 | 04-FEB-08:05 | 6723.69 | 5143.72 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.68 |
March | 2058.97 | 22-MAR-07:05 | 6723.69 | 4882.32 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.66 |
April | 2241.69 | 13-APR-07:05 | 6723.69 | 4841.91 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2258.18 |
May | 1655.67 | 27-MAY-07:07 | 5042.77 | 3515.52 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1904.28 |
June | 22240.09 | 17-JUN-07:02 | 8404.61 | 5410.17 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18740.26 | 01-JUL-07:02 | 8404.61 | 6062.93 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.43 |
August | 19691.01 | 12-AUG-07:02 | 8404.61 | 5902.23 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.64 |
September | 2267.18 | 30-SEP-07:07 | 5042.77 | 3733.43 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.33 |
October | 2208.38 | 12-OCT-07:05 | 6723.69 | 5143.72 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.25 |
November | 3028.70 | 18-NOV-08:05 | 6723.69 | 5143.72 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.87 |
December | 3068.80 | 30-DEC-08:05 | 6723.69 | 5143.72 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1655.67 | 5042.77 | 3515.52 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22240.09 | 8404.61 | 6062.93 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 4231.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6567.20 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 3526.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5011.66 |
March | 5145.35 | 22-MAR-12:40 | 3955.50 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.49 |
April | 5803.29 | 24-APR-11:40 | 2096.41 | 5995.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.42 |
May | 5976.26 | 16-MAY-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8023.35 |
June | 6103.08 | 17-JUN-07:02 | 19777.50 | 26448.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19686.92 | 23-JUL-14:45 | 0.00 | 1410.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.53 |
August | 8388.34 | 30-AUG-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4036.32 |
September | 7049.38 | 15-SEP-07:03 | 11866.50 | 15869.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2883.61 |
October | 7670.93 | 16-OCT-10:05 | 7911.00 | 11990.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.28 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.09 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 3526.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19686.92 | 19777.50 | 26448.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8023.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 5942.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25686.04 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 4951.99 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20039.34 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 4951.99 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10066.39 |
April | 0.00 | 01-APR-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34937.72 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4693.01 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2889.16 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4646.19 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9224.46 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6103.63 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 1980.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10936.86 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 990.40 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20529.09 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 4951.99 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 990.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5942.38 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34937.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.487710E+11 | 38038.31 | 12-JAN-15:30 | 0.273839E+12 | 221684.00 | 28-JAN-17:10 |
February | 0.419296E+11 | 36897.78 | 04-FEB-09:09 | 0.229785E+12 | 220052.10 | 24-FEB-17:00 |
March | 0.446658E+11 | 35333.03 | 15-MAR-07:10 | 0.218031E+12 | 198325.02 | 16-MAR-07:00 |
April | 0.386096E+11 | 30062.18 | 01-APR-14:30 | 0.976267E+11 | 174830.72 | 02-APR-20:30 |
May | 0.368521E+11 | 29833.61 | 09-MAY-12:30 | 0.321981E+10 | 26622.83 | 27-MAY-07:10 |
June | 0.349040E+11 | 30600.11 | 30-JUN-14:00 | 52714185.59 | 5987.64 | 01-JUN-06:10 |
July | 0.353254E+11 | 32420.60 | 29-JUL-14:00 | 6380593.68 | 4515.72 | 05-JUL-07:10 |
August | 0.392024E+11 | 30156.51 | 11-AUG-12:00 | 0.182268E+09 | 14510.85 | 31-AUG-06:10 |
September | 0.394845E+11 | 29741.39 | 30-SEP-12:00 | 0.844749E+10 | 38356.53 | 29-SEP-07:10 |
October | 0.438779E+11 | 36860.70 | 31-OCT-08:30 | 0.126709E+12 | 170771.96 | 27-OCT-06:10 |
November | 0.457283E+11 | 37751.26 | 29-NOV-15:20 | 0.201273E+12 | 187770.08 | 29-NOV-07:00 |
December | 0.498044E+11 | 37894.57 | 15-DEC-15:00 | 0.272884E+12 | 214186.97 | 01-DEC-17:00 |
Annual Sum or Average | 0.499155E+12 | 0.143206E+13 | ||||
Minimum of Months | 0.349040E+11 | 29741.39 | 6380593.68 | 4515.72 | ||
Maximum of Months | 0.498044E+11 | 38038.31 | 0.273839E+12 | 221684.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.177447E+11 | 0.135291E+11 | 0.115358E+11 | 0.00 | 0.352566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243576E+10 | 0.00 |
February | 0.160976E+11 | 0.989872E+10 | 0.105871E+11 | 0.00 | 0.313002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221606E+10 | 0.00 |
March | 0.181758E+11 | 0.833133E+10 | 0.123431E+11 | 0.00 | 0.330245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251304E+10 | 0.00 |
April | 0.167934E+11 | 0.550402E+10 | 0.114862E+11 | 0.00 | 0.243830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238763E+10 | 0.00 |
May | 0.172345E+11 | 0.338634E+10 | 0.119357E+11 | 0.00 | 0.183367E+10 | 0.00 | 0.00 | 180438.26 | 0.00 | 0.00 | 0.00 | 0.246168E+10 | 0.00 |
June | 0.169232E+11 | 0.173994E+10 | 0.118862E+11 | 0.00 | 0.181008E+10 | 0.00 | 0.00 | 0.177592E+09 | 0.00 | 0.00 | 0.00 | 0.236701E+10 | 0.00 |
July | 0.167051E+11 | 0.249977E+10 | 0.115358E+11 | 0.00 | 0.174067E+10 | 0.00 | 0.00 | 0.508184E+09 | 0.00 | 0.00 | 0.00 | 0.233588E+10 | 0.00 |
August | 0.177926E+11 | 0.465472E+10 | 0.123357E+11 | 0.00 | 0.187970E+10 | 0.00 | 0.00 | 0.155138E+09 | 0.00 | 0.00 | 0.00 | 0.238459E+10 | 0.00 |
September | 0.169656E+11 | 0.695838E+10 | 0.114788E+11 | 0.00 | 0.180787E+10 | 0.00 | 0.00 | 1.41 | 0.00 | 0.00 | 0.00 | 0.227387E+10 | 0.00 |
October | 0.174724E+11 | 0.982596E+10 | 0.115432E+11 | 0.00 | 0.269397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234237E+10 | 0.00 |
November | 0.170372E+11 | 0.121186E+11 | 0.110862E+11 | 0.00 | 0.319275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229353E+10 | 0.00 |
December | 0.177589E+11 | 0.145895E+11 | 0.115358E+11 | 0.00 | 0.350177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241843E+10 | 0.00 |
Annual Sum or Average | 0.206701E+12 | 0.930364E+11 | 0.139290E+12 | 0.00 | 0.308569E+11 | 0.00 | 0.00 | 0.841094E+09 | 0.00 | 0.00 | 0.00 | 0.284298E+11 | 0.00 |
Minimum of Months | 0.160976E+11 | 0.173994E+10 | 0.105871E+11 | 0.00 | 0.174067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221606E+10 | 0.00 |
Maximum of Months | 0.181758E+11 | 0.145895E+11 | 0.123431E+11 | 0.00 | 0.352566E+10 | 0.00 | 0.00 | 0.508184E+09 | 0.00 | 0.00 | 0.00 | 0.251304E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.273839E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.229785E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.218031E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.976267E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.321981E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 52714185.59 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 6380593.68 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.182268E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.844749E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126709E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.201273E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.272884E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143206E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 6380593.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.273839E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 15699.40 | 02-JAN-09:09 | 6958.21 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2868.50 | 28-JAN-17:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15699.40 | 01-FEB-09:09 | 6958.21 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2724.27 | 24-FEB-08:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15634.40 | 03-MAR-09:09 | 6958.21 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2614.17 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 15315.63 | 04-APR-08:09 | 6958.21 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2507.29 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 15282.81 | 20-MAY-08:30 | 6958.21 | 01-MAY-21:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 1901.74 | 27-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 15256.88 | 07-JUN-08:09 | 6958.21 | 01-JUN-22:49 | 10112.62 | 01-JUN-07:10 | 0.00 | 1758.04 | 02-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 15274.72 | 29-JUL-08:00 | 6958.21 | 11-JUL-22:00 | 10112.62 | 01-JUL-07:10 | 0.00 | 1758.04 | 03-JUL-11:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 15611.33 | 31-AUG-08:09 | 6958.21 | 01-AUG-21:00 | 10112.62 | 01-AUG-07:10 | 0.00 | 1758.04 | 01-AUG-12:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 15628.67 | 30-SEP-08:09 | 6958.21 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 1983.81 | 29-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15699.40 | 23-OCT-08:09 | 6958.21 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2509.09 | 31-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 15699.40 | 01-NOV-08:09 | 6958.21 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2624.29 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 15699.40 | 01-DEC-09:09 | 6958.21 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2664.09 | 15-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15256.88 | 6958.21 | 10112.62 | 0.00 | 1758.04 | 0.00 | 0.00 | |||||
Maximum of Months | 15699.40 | 6958.21 | 10112.62 | 0.00 | 2868.50 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3131.61 | 03-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3131.65 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3131.57 | 07-MAR-12:09 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3131.55 | 25-APR-11:00 | 0.00 |
May | 148.95 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 3131.24 | 02-MAY-11:00 | 0.00 |
June | 2394.86 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3040.83 | 01-JUN-11:20 | 0.00 |
July | 4022.29 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2890.35 | 01-JUL-11:20 | 0.00 |
August | 1338.90 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 2760.58 | 01-AUG-11:50 | 0.00 |
September | 0.00 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2746.77 | 30-SEP-11:30 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2856.44 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2990.26 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3131.32 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2746.77 | 0.00 | ||
Maximum of Months | 4022.29 | 0.00 | 0.00 | 0.00 | 3131.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 38038.31 | 12-JAN-15:30 | 15699.40 | 10112.62 | 6958.21 | 0.00 | 2576.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36897.78 | 04-FEB-09:09 | 15699.40 | 10112.62 | 6958.21 | 0.00 | 2396.74 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35333.03 | 15-MAR-07:10 | 14003.70 | 10112.62 | 6958.21 | 0.00 | 2575.44 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30062.18 | 01-APR-14:30 | 15149.04 | 10112.62 | 0.00 | 0.00 | 2107.82 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29833.61 | 09-MAY-12:30 | 15271.92 | 10112.62 | 0.00 | 0.00 | 1758.04 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30600.11 | 30-JUN-14:00 | 14472.11 | 10112.62 | 0.00 | 0.00 | 1758.04 | 0.00 | 0.00 | 2394.86 | 0.00 |
July | 32420.60 | 29-JUL-14:00 | 14814.99 | 10112.62 | 0.00 | 0.00 | 1758.04 | 0.00 | 0.00 | 3502.77 | 0.00 |
August | 30156.51 | 11-AUG-12:00 | 15229.83 | 10112.62 | 0.00 | 0.00 | 1758.04 | 0.00 | 0.00 | 807.57 | 0.00 |
September | 29741.39 | 30-SEP-12:00 | 15596.73 | 10112.62 | 0.00 | 0.00 | 1772.35 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36860.70 | 31-OCT-08:30 | 15699.40 | 10112.62 | 6958.21 | 0.00 | 2377.93 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37751.26 | 29-NOV-15:20 | 15699.40 | 10112.62 | 6958.21 | 0.00 | 2441.18 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37894.57 | 15-DEC-15:00 | 15699.40 | 10112.62 | 6958.21 | 0.00 | 2498.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29741.39 | 14003.70 | 10112.62 | 0.00 | 0.00 | 1758.04 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38038.31 | 15699.40 | 10112.62 | 6958.21 | 0.00 | 2576.64 | 0.00 | 0.00 | 3502.77 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 221684.00 | 28-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 220052.10 | 24-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 198325.02 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 174830.72 | 02-APR-20:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 26622.83 | 27-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5987.64 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4515.72 | 05-JUL-07:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 14510.85 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 38356.53 | 29-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 170771.96 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 187770.08 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 214186.97 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4515.72 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 221684.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.67 | 15.74 | 14.17 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
February | 39.33 | 15.66 | 10.33 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
March | 26.67 | 15.57 | 7.83 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
April | 10.50 | 15.65 | 4.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
May | 0.50 | 17.20 | 0.50 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.67 | 17.18 | 0.67 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
October | 8.00 | 15.94 | 4.17 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
November | 12.50 | 16.35 | 6.50 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
December | 27.67 | 16.24 | 11.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
Annual Sum or Average | 175.50 | 15.83 | 59.33 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.67 | 17.20 | 14.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.17 | 14.18 | 4.50 | 14.18 | 0.00 | 14.18 | 0.00 | 14.18 |
February | 103.83 | 14.23 | 3.83 | 14.23 | 0.00 | 14.23 | 0.00 | 14.23 |
March | 103.67 | 14.35 | 5.17 | 14.35 | 0.00 | 14.35 | 0.00 | 14.35 |
April | 58.67 | 14.56 | 3.83 | 14.56 | 0.00 | 14.56 | 0.00 | 14.56 |
May | 2.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7.17 | 14.93 | 1.00 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
October | 77.00 | 14.62 | 3.50 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
November | 112.17 | 14.39 | 4.17 | 14.39 | 0.00 | 14.39 | 0.00 | 14.39 |
December | 115.17 | 14.23 | 4.17 | 14.22 | 0.00 | 14.22 | 0.00 | 14.22 |
Annual Sum or Average | 696.83 | 14.34 | 30.17 | 14.34 | 0.00 | 14.34 | 0.00 | 14.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 117.17 | 14.97 | 5.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.67 | 7.19 | 34.17 | 7.26 | 0.00 | 7.26 | 0.00 | 7.26 |
February | 74.00 | 8.20 | 22.33 | 8.22 | 0.00 | 8.22 | 0.00 | 8.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.00 | 9.34 | 0.00 | 9.34 | 0.00 | 9.34 | 0.00 | 9.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 9.23 | 1.50 | 9.23 | 0.00 | 9.23 | 0.00 | 9.23 |
Annual Sum or Average | 164.17 | 7.69 | 58.00 | 7.72 | 0.00 | 7.72 | 0.00 | 7.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.67 | 9.34 | 34.17 | 9.34 | 0.00 | 9.34 | 0.00 | 9.34 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.64 | 300.00 | 20.64 | 300.00 | 20.64 |
February | 276.00 | 20.67 | 276.00 | 20.67 | 276.00 | 20.67 |
March | 324.00 | 20.69 | 324.00 | 20.69 | 324.00 | 20.69 |
April | 300.00 | 20.75 | 296.33 | 20.74 | 296.33 | 20.74 |
May | 312.00 | 21.46 | 195.83 | 21.16 | 195.83 | 21.02 |
June | 245.33 | 23.36 | 15.17 | 23.26 | 9.17 | 23.16 |
July | 79.17 | 23.41 | 78.83 | 23.76 | 0.00 | 23.76 |
August | 235.33 | 23.10 | 45.33 | 23.05 | 16.00 | 22.92 |
September | 300.00 | 21.03 | 238.00 | 20.88 | 238.00 | 20.82 |
October | 300.00 | 20.71 | 300.00 | 20.71 | 300.00 | 20.71 |
November | 288.00 | 20.69 | 288.00 | 20.69 | 288.00 | 20.69 |
December | 300.00 | 20.67 | 300.00 | 20.67 | 300.00 | 20.67 |
Annual Sum or Average | 3259.83 | 21.24 | 2657.50 | 21.05 | 2543.33 | 20.94 |
Minimum of Months | 79.17 | 20.64 | 15.17 | 20.64 | 0.00 | 20.64 |
Maximum of Months | 324.00 | 23.41 | 324.00 | 23.76 | 324.00 | 23.76 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.54 | 324.00 | 15.54 | 324.00 | 15.54 |
April | 300.00 | 16.03 | 300.00 | 16.03 | 300.00 | 16.03 |
May | 312.00 | 18.50 | 296.17 | 18.42 | 296.17 | 18.39 |
June | 219.50 | 22.34 | 81.00 | 22.65 | 32.83 | 22.37 |
July | 81.67 | 22.91 | 180.83 | 24.88 | 1.00 | 24.87 |
August | 218.00 | 21.80 | 114.67 | 22.35 | 41.17 | 22.02 |
September | 300.00 | 17.05 | 293.17 | 17.00 | 293.17 | 16.99 |
October | 300.00 | 15.63 | 300.00 | 15.63 | 300.00 | 15.63 |
November | 288.00 | 15.54 | 288.00 | 15.54 | 288.00 | 15.54 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3219.17 | 17.10 | 3053.83 | 17.11 | 2752.33 | 16.82 |
Minimum of Months | 81.67 | 15.54 | 81.00 | 15.54 | 1.00 | 15.54 |
Maximum of Months | 324.00 | 22.91 | 324.00 | 24.88 | 324.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.70 | 300.00 | 9.70 | 300.00 | 9.70 |
February | 276.00 | 9.85 | 276.00 | 9.85 | 276.00 | 9.85 |
March | 324.00 | 10.07 | 324.00 | 10.07 | 324.00 | 10.07 |
April | 300.00 | 10.98 | 300.00 | 10.98 | 300.00 | 10.98 |
May | 312.00 | 15.29 | 312.00 | 15.29 | 312.00 | 15.29 |
June | 309.33 | 20.71 | 129.00 | 20.12 | 129.00 | 19.80 |
July | 173.00 | 22.73 | 75.83 | 23.40 | 4.83 | 23.33 |
August | 266.50 | 21.47 | 101.00 | 21.45 | 65.33 | 21.12 |
September | 300.00 | 15.69 | 300.00 | 15.69 | 300.00 | 15.69 |
October | 300.00 | 10.41 | 300.00 | 10.41 | 300.00 | 10.41 |
November | 288.00 | 10.00 | 288.00 | 10.00 | 288.00 | 10.00 |
December | 300.00 | 9.99 | 300.00 | 9.99 | 300.00 | 9.99 |
Annual Sum or Average | 3448.83 | 13.55 | 3005.83 | 12.99 | 2899.17 | 12.65 |
Minimum of Months | 173.00 | 9.70 | 75.83 | 9.70 | 4.83 | 9.70 |
Maximum of Months | 324.00 | 22.73 | 324.00 | 23.40 | 324.00 | 23.33 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 814321.00 | 180438.26 | 1.67 | 814321.00 | 0.00 | 0.00 | 0.10 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 | 674.36 | 31-MAY-16:00 | 674.36 | 31-MAY-16:00 | 0.00 | 31-MAY-15:40 | 148.95 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.820573E+09 | 0.171175E+09 | 88.09 | 0.792349E+09 | 28223879.77 | 0.00 | 1.00 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 | 14947.95 | 24-JUN-07:02 | 12099.02 | 17-JUN-07:02 | 4482.94 | 24-JUN-07:02 | 3010.91 | 24-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.198930E+10 | 0.411066E+09 | 156.12 | 0.188073E+10 | 0.108575E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 15667.97 | 08-JUL-07:02 | 12597.03 | 29-JUL-07:02 | 5533.89 | 08-JUL-07:02 | 3154.36 | 08-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.740186E+09 | 0.154773E+09 | 76.88 | 0.703573E+09 | 36613317.67 | 0.00 | 1.00 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 | 15107.82 | 05-AUG-07:02 | 13229.69 | 12-AUG-07:02 | 3983.92 | 05-AUG-07:02 | 3043.74 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 6.28 | 1.41 | 0.17 | 6.17 | 0.11 | 0.00 | 0.00 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 0.01 | 01-SEP-15:00 | 0.01 | 01-SEP-15:00 | 0.00 | 01-SEP-15:00 | 0.00 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.355088E+10 | 0.737194E+09 | 322.93 | 0.337746E+10 | 0.173413E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.198930E+10 | 0.411066E+09 | 156.12 | 0.188073E+10 | 0.108575E+09 | 0.00 | 1.00 | 0.00 | 15667.97 | 13229.69 | 5533.89 | 3154.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 24429837.78 | 6417187.13 | 4.83 | 23135126.29 | 1294711.49 | 0.00 | 0.25 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 3425.80 | 30-JUN-15:00 | 3339.67 | 30-JUN-15:00 | 180.30 | 30-JUN-13:00 | 904.39 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.379884E+09 | 97117988.28 | 33.75 | 0.376015E+09 | 3868487.68 | 0.00 | 1.00 | 23-JUL-14:45 | 0.00 | 01-JUL-00:10 | 30073.81 | 23-JUL-14:45 | 30073.81 | 23-JUL-14:45 | 301.61 | 22-JUL-11:00 | 6731.93 | 23-JUL-14:45 | 0.00 | 01-JUL-00:10 |
August | 1429962.33 | 365234.63 | 1.17 | 1358860.27 | 71102.07 | 0.00 | 0.04 | 04-AUG-14:50 | 0.00 | 01-AUG-00:10 | 525.73 | 04-AUG-14:50 | 501.72 | 04-AUG-14:50 | 25.72 | 04-AUG-14:40 | 134.15 | 04-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.405744E+09 | 0.103900E+09 | 39.75 | 0.400509E+09 | 5234301.23 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.379884E+09 | 97117988.28 | 33.75 | 0.376015E+09 | 3868487.68 | 0.00 | 1.00 | 0.00 | 30073.81 | 30073.81 | 301.61 | 6731.93 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.61 | 0.99 | 4.62 | 0.00 | 260.98 | 0.00 | 0.00 | 0.00 |
February | 33.38 | 11.74 | 21.64 | 8.05 | 216.27 | 0.00 | 0.00 | 0.00 |
March | 100.17 | 43.40 | 56.76 | 63.57 | 148.88 | 0.00 | 0.00 | 0.00 |
April | 235.94 | 122.20 | 113.74 | 242.94 | 76.70 | 0.00 | 0.00 | 0.00 |
May | 229.16 | 104.28 | 124.88 | 252.93 | 33.79 | 0.00 | 0.00 | 0.00 |
June | 251.33 | 107.18 | 144.15 | 283.65 | 21.80 | 0.00 | 0.00 | 0.00 |
July | 210.06 | 79.33 | 130.73 | 233.95 | 28.26 | 0.00 | 0.00 | 0.00 |
August | 173.15 | 73.51 | 99.64 | 185.47 | 40.80 | 0.00 | 0.00 | 0.00 |
September | 104.40 | 43.57 | 60.83 | 95.44 | 62.62 | 0.00 | 0.00 | 0.00 |
October | 40.94 | 12.30 | 28.64 | 18.71 | 129.18 | 0.00 | 0.00 | 0.00 |
November | 16.44 | 5.98 | 10.45 | 2.09 | 247.75 | 0.00 | 0.00 | 0.00 |
December | 1.48 | 0.16 | 1.32 | 0.00 | 279.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.14 | 50.49 | 66.64 | 116.01 | 128.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.48 | 0.16 | 1.32 | 0.00 | 21.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.33 | 122.20 | 144.15 | 283.65 | 279.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.61 | 0.99 | 4.62 | 0.00 | 260.98 | 0.00 | 0.00 | 0.00 |
February | 33.38 | 11.74 | 21.64 | 8.05 | 216.27 | 0.00 | 0.00 | 0.00 |
March | 100.17 | 43.40 | 56.76 | 63.57 | 148.88 | 0.00 | 0.00 | 0.00 |
April | 235.94 | 122.20 | 113.74 | 242.94 | 76.70 | 0.00 | 0.00 | 0.00 |
May | 229.16 | 104.28 | 124.88 | 252.93 | 33.79 | 0.00 | 0.00 | 0.00 |
June | 251.33 | 107.18 | 144.15 | 283.65 | 21.80 | 0.00 | 0.00 | 0.00 |
July | 210.06 | 79.33 | 130.73 | 233.95 | 28.26 | 0.00 | 0.00 | 0.00 |
August | 173.15 | 73.51 | 99.64 | 185.47 | 40.80 | 0.00 | 0.00 | 0.00 |
September | 104.40 | 43.57 | 60.83 | 95.44 | 62.62 | 0.00 | 0.00 | 0.00 |
October | 40.94 | 12.30 | 28.64 | 18.71 | 129.18 | 0.00 | 0.00 | 0.00 |
November | 16.44 | 5.98 | 10.45 | 2.09 | 247.75 | 0.00 | 0.00 | 0.00 |
December | 1.48 | 0.16 | 1.32 | 0.00 | 279.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.14 | 50.49 | 66.64 | 116.01 | 128.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.48 | 0.16 | 1.32 | 0.00 | 21.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.33 | 122.20 | 144.15 | 283.65 | 279.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.00 | 2.36 | 0.00 | 154.20 | 0.00 | 0.00 | 0.00 |
February | 10.44 | 0.00 | 10.44 | 0.00 | 135.13 | 0.00 | 0.00 | 0.00 |
March | 28.00 | 0.01 | 27.99 | 3.81 | 95.19 | 0.00 | 0.00 | 0.00 |
April | 50.96 | 1.45 | 49.51 | 28.48 | 45.10 | 0.00 | 0.00 | 0.00 |
May | 78.17 | 12.70 | 65.47 | 74.41 | 17.73 | 0.00 | 0.00 | 0.00 |
June | 100.74 | 22.17 | 78.57 | 104.06 | 9.94 | 0.00 | 0.00 | 0.00 |
July | 85.03 | 14.05 | 70.98 | 86.05 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 54.62 | 2.99 | 51.63 | 46.62 | 22.57 | 0.00 | 0.00 | 0.00 |
September | 30.36 | 0.09 | 30.27 | 16.22 | 37.79 | 0.00 | 0.00 | 0.00 |
October | 14.69 | 0.00 | 14.69 | 2.14 | 79.79 | 0.00 | 0.00 | 0.00 |
November | 4.56 | 0.00 | 4.56 | 0.00 | 151.00 | 0.00 | 0.00 | 0.00 |
December | 0.72 | 0.00 | 0.72 | 0.00 | 163.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.53 | 4.48 | 34.05 | 30.32 | 76.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.72 | 0.00 | 0.72 | 0.00 | 9.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.74 | 22.17 | 78.57 | 104.06 | 163.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.36 | 0.00 | 2.36 | 0.00 | 154.20 | 0.00 | 0.00 | 0.00 |
February | 10.44 | 0.00 | 10.44 | 0.00 | 135.13 | 0.00 | 0.00 | 0.00 |
March | 28.00 | 0.01 | 27.99 | 3.81 | 95.19 | 0.00 | 0.00 | 0.00 |
April | 50.96 | 1.45 | 49.51 | 28.48 | 45.10 | 0.00 | 0.00 | 0.00 |
May | 78.17 | 12.70 | 65.47 | 74.41 | 17.72 | 0.00 | 0.00 | 0.00 |
June | 100.74 | 22.17 | 78.57 | 104.05 | 9.94 | 0.00 | 0.00 | 0.00 |
July | 85.02 | 14.05 | 70.98 | 86.05 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 54.62 | 2.99 | 51.63 | 46.61 | 22.57 | 0.00 | 0.00 | 0.00 |
September | 30.36 | 0.09 | 30.27 | 16.22 | 37.79 | 0.00 | 0.00 | 0.00 |
October | 14.69 | 0.00 | 14.69 | 2.14 | 79.79 | 0.00 | 0.00 | 0.00 |
November | 4.56 | 0.00 | 4.56 | 0.00 | 151.00 | 0.00 | 0.00 | 0.00 |
December | 0.72 | 0.00 | 0.72 | 0.00 | 163.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.53 | 4.47 | 34.05 | 30.32 | 76.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.72 | 0.00 | 0.72 | 0.00 | 9.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.74 | 22.17 | 78.57 | 104.05 | 163.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.81 | 0.26 | 2.55 | 0.00 | 137.97 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 3.48 | 10.74 | 0.29 | 114.19 | 0.00 | 0.00 | 0.00 |
March | 49.94 | 21.24 | 28.71 | 36.21 | 76.67 | 0.00 | 0.00 | 0.00 |
April | 100.47 | 54.21 | 46.27 | 110.01 | 39.67 | 0.00 | 0.00 | 0.00 |
May | 131.06 | 74.57 | 56.48 | 156.45 | 19.68 | 0.00 | 0.00 | 0.00 |
June | 142.17 | 70.89 | 71.29 | 168.74 | 13.35 | 0.00 | 0.00 | 0.00 |
July | 127.55 | 61.68 | 65.87 | 147.03 | 18.81 | 0.00 | 0.00 | 0.00 |
August | 96.02 | 46.59 | 49.43 | 105.39 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 51.88 | 20.54 | 31.34 | 49.61 | 36.92 | 0.00 | 0.00 | 0.00 |
October | 21.29 | 5.16 | 16.13 | 11.86 | 60.15 | 8.67 | 0.00 | 0.00 |
November | 5.34 | 0.44 | 4.90 | 0.00 | 135.60 | 0.00 | 0.00 | 0.00 |
December | 0.79 | 0.02 | 0.77 | 0.00 | 149.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.21 | 30.07 | 32.15 | 65.82 | 68.89 | 8.67 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 0.02 | 0.77 | 0.00 | 13.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.17 | 74.57 | 71.29 | 168.74 | 149.27 | 8.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 15030620.33 | 2648468.72 | 12382151.60 | 0.00 | 0.699021E+09 |
February | 80746669.30 | 28397081.48 | 52349587.82 | 19486617.33 | 0.523212E+09 |
March | 0.268285E+09 | 0.116256E+09 | 0.152029E+09 | 0.170276E+09 | 0.398753E+09 |
April | 0.611559E+09 | 0.316741E+09 | 0.294817E+09 | 0.629691E+09 | 0.198817E+09 |
May | 0.613770E+09 | 0.279302E+09 | 0.334469E+09 | 0.677439E+09 | 90500999.87 |
June | 0.651442E+09 | 0.277799E+09 | 0.373643E+09 | 0.735221E+09 | 56511652.20 |
July | 0.562626E+09 | 0.212483E+09 | 0.350143E+09 | 0.626600E+09 | 75701925.62 |
August | 0.463775E+09 | 0.196900E+09 | 0.266875E+09 | 0.496770E+09 | 0.109281E+09 |
September | 0.270593E+09 | 0.112932E+09 | 0.157661E+09 | 0.247371E+09 | 0.162304E+09 |
October | 0.109666E+09 | 32945973.55 | 76720035.04 | 50121087.09 | 0.345986E+09 |
November | 42605946.70 | 15511955.51 | 27093991.19 | 5425364.67 | 0.642160E+09 |
December | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 0.748850E+09 |
Annual Sum or Average | 0.369406E+10 | 0.159235E+10 | 0.210171E+10 | 0.365840E+10 | 0.405110E+10 |
Minimum of Months | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 56511652.20 |
Maximum of Months | 0.651442E+09 | 0.316741E+09 | 0.373643E+09 | 0.735221E+09 | 0.748850E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 15030620.33 | 2648468.72 | 12382151.60 | 0.00 | 0.699021E+09 |
February | 80746669.30 | 28397081.48 | 52349587.82 | 19486617.33 | 0.523212E+09 |
March | 0.268285E+09 | 0.116256E+09 | 0.152029E+09 | 0.170276E+09 | 0.398753E+09 |
April | 0.611559E+09 | 0.316741E+09 | 0.294817E+09 | 0.629691E+09 | 0.198817E+09 |
May | 0.613770E+09 | 0.279302E+09 | 0.334469E+09 | 0.677439E+09 | 90500999.87 |
June | 0.651442E+09 | 0.277799E+09 | 0.373643E+09 | 0.735221E+09 | 56511652.20 |
July | 0.562626E+09 | 0.212483E+09 | 0.350143E+09 | 0.626600E+09 | 75701925.62 |
August | 0.463775E+09 | 0.196900E+09 | 0.266875E+09 | 0.496770E+09 | 0.109281E+09 |
September | 0.270593E+09 | 0.112932E+09 | 0.157661E+09 | 0.247371E+09 | 0.162304E+09 |
October | 0.109666E+09 | 32945973.55 | 76720035.04 | 50121087.09 | 0.345986E+09 |
November | 42605946.70 | 15511955.51 | 27093991.19 | 5425364.67 | 0.642160E+09 |
December | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 0.748850E+09 |
Annual Sum or Average | 0.369406E+10 | 0.159235E+10 | 0.210171E+10 | 0.365840E+10 | 0.405110E+10 |
Minimum of Months | 3958592.44 | 432233.62 | 3526358.83 | 0.00 | 56511652.20 |
Maximum of Months | 0.651442E+09 | 0.316741E+09 | 0.373643E+09 | 0.735221E+09 | 0.748850E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6324012.93 | 0.00 | 6324012.93 | 0.00 | 0.412998E+09 |
February | 25249854.44 | 0.00 | 25249854.44 | 0.00 | 0.326904E+09 |
March | 74992053.45 | 26013.52 | 74966039.93 | 10196798.25 | 0.254944E+09 |
April | 0.132087E+09 | 3749549.60 | 0.128338E+09 | 73811468.18 | 0.116909E+09 |
May | 0.209376E+09 | 34023158.09 | 0.175353E+09 | 0.199296E+09 | 47474724.28 |
June | 0.261119E+09 | 57459443.73 | 0.203660E+09 | 0.269711E+09 | 25768731.02 |
July | 0.227735E+09 | 37628989.61 | 0.190106E+09 | 0.230486E+09 | 37948922.60 |
August | 0.146289E+09 | 8005493.63 | 0.138283E+09 | 0.124855E+09 | 60452300.72 |
September | 78703925.51 | 233396.05 | 78470529.45 | 42040277.90 | 97948548.86 |
October | 39354522.63 | 0.00 | 39354522.63 | 5728840.37 | 0.213714E+09 |
November | 11819129.46 | 0.00 | 11819129.46 | 0.00 | 0.391394E+09 |
December | 1918373.75 | 0.00 | 1918373.75 | 0.00 | 0.438350E+09 |
Annual Sum or Average | 0.121497E+10 | 0.141126E+09 | 0.107384E+10 | 0.956126E+09 | 0.242481E+10 |
Minimum of Months | 1918373.75 | 0.00 | 1918373.75 | 0.00 | 25768731.02 |
Maximum of Months | 0.261119E+09 | 57459443.73 | 0.203660E+09 | 0.269711E+09 | 0.438350E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6323784.35 | 0.00 | 6323784.35 | 0.00 | 0.412997E+09 |
February | 25248999.58 | 0.00 | 25248999.58 | 0.00 | 0.326904E+09 |
March | 74989665.67 | 26012.30 | 74963653.37 | 10195604.84 | 0.254945E+09 |
April | 0.132083E+09 | 3749373.85 | 0.128334E+09 | 73807503.57 | 0.116909E+09 |
May | 0.209369E+09 | 34021563.38 | 0.175347E+09 | 0.199287E+09 | 47474509.60 |
June | 0.261110E+09 | 57456750.53 | 0.203653E+09 | 0.269699E+09 | 25768659.92 |
July | 0.227727E+09 | 37627225.89 | 0.190100E+09 | 0.230476E+09 | 37948850.85 |
August | 0.146284E+09 | 8005118.40 | 0.138279E+09 | 0.124850E+09 | 60452061.99 |
September | 78701324.89 | 233385.12 | 78467939.78 | 42037784.31 | 97948460.30 |
October | 39353174.47 | 0.00 | 39353174.47 | 5728330.99 | 0.213714E+09 |
November | 11818702.27 | 0.00 | 11818702.27 | 0.00 | 0.391393E+09 |
December | 1918301.37 | 0.00 | 1918301.37 | 0.00 | 0.438349E+09 |
Annual Sum or Average | 0.121493E+10 | 0.141119E+09 | 0.107381E+10 | 0.956081E+09 | 0.242480E+10 |
Minimum of Months | 1918301.37 | 0.00 | 1918301.37 | 0.00 | 25768659.92 |
Maximum of Months | 0.261110E+09 | 57456750.53 | 0.203653E+09 | 0.269699E+09 | 0.438349E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7526278.22 | 686650.23 | 6839627.99 | 0.00 | 0.369537E+09 |
February | 34416899.97 | 8422812.94 | 25994087.04 | 713620.78 | 0.276249E+09 |
March | 0.133769E+09 | 56880403.65 | 76888411.03 | 96994960.07 | 0.205343E+09 |
April | 0.260427E+09 | 0.140505E+09 | 0.119921E+09 | 0.285144E+09 | 0.102832E+09 |
May | 0.351023E+09 | 0.199734E+09 | 0.151289E+09 | 0.419032E+09 | 52720258.84 |
June | 0.368514E+09 | 0.183740E+09 | 0.184774E+09 | 0.437367E+09 | 34607934.86 |
July | 0.341636E+09 | 0.165202E+09 | 0.176435E+09 | 0.393808E+09 | 50369696.86 |
August | 0.257186E+09 | 0.124780E+09 | 0.132406E+09 | 0.282283E+09 | 72817030.67 |
September | 0.134462E+09 | 53230589.03 | 81230956.25 | 0.128579E+09 | 95703463.41 |
October | 57030549.22 | 13830930.07 | 43199619.16 | 31764129.34 | 0.161098E+09 |
November | 13838496.16 | 1149664.75 | 12688831.40 | 741.62 | 0.351476E+09 |
December | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 0.399803E+09 |
Annual Sum or Average | 0.196194E+10 | 0.948202E+09 | 0.101374E+10 | 0.207569E+10 | 0.217256E+10 |
Minimum of Months | 2109263.65 | 40203.15 | 2069060.50 | 0.00 | 34607934.86 |
Maximum of Months | 0.368514E+09 | 0.199734E+09 | 0.184774E+09 | 0.437367E+09 | 0.399803E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 830.36 | 15.95 | 1.98 | 13.97 | 0.00 | 0.00 |
February | 8.04 | 694.74 | 87.63 | 23.48 | 64.15 | 0.00 | 0.00 |
March | 122.95 | 476.32 | 256.33 | 86.83 | 169.50 | 0.00 | 0.00 |
April | 538.62 | 239.41 | 573.80 | 247.29 | 326.51 | 0.00 | 0.00 |
May | 647.81 | 96.17 | 614.65 | 233.96 | 380.69 | 0.00 | 0.00 |
June | 767.95 | 56.03 | 704.13 | 258.69 | 445.45 | 0.00 | 0.00 |
July | 633.77 | 78.64 | 590.17 | 186.76 | 403.41 | 0.00 | 0.00 |
August | 459.15 | 121.72 | 455.54 | 153.01 | 302.54 | 0.00 | 0.00 |
September | 220.66 | 198.16 | 269.52 | 87.32 | 182.20 | 0.00 | 0.00 |
October | 36.93 | 413.16 | 111.28 | 24.60 | 86.67 | 0.00 | 0.00 |
November | 1.36 | 794.67 | 41.99 | 11.97 | 30.03 | 0.00 | 0.00 |
December | 0.00 | 886.50 | 4.39 | 0.32 | 4.07 | 0.00 | 0.00 |
Annual Sum or Average | 287.68 | 405.73 | 311.33 | 109.94 | 201.39 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 56.03 | 4.39 | 0.32 | 4.07 | 0.00 | 0.00 |
Maximum of Months | 767.95 | 886.50 | 704.13 | 258.69 | 445.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 10995.62 | 28.10 | 2.56 | 25.54 | 0.00 | 0.00 |
February | 14.99 | 9549.72 | 142.27 | 34.82 | 107.45 | 0.00 | 0.00 |
March | 1830.02 | 6395.23 | 499.44 | 212.37 | 287.07 | 0.00 | 0.00 |
April | 4848.75 | 2708.30 | 1004.73 | 542.07 | 462.66 | 0.00 | 0.00 |
May | 6560.52 | 663.60 | 1310.57 | 745.72 | 564.85 | 0.00 | 0.00 |
June | 6873.19 | 400.76 | 1421.74 | 708.87 | 712.86 | 0.00 | 0.00 |
July | 5644.34 | 564.34 | 1275.52 | 616.79 | 658.73 | 0.00 | 0.00 |
August | 4383.60 | 824.73 | 960.22 | 465.88 | 494.35 | 0.00 | 0.00 |
September | 2019.84 | 1459.06 | 518.76 | 205.36 | 313.39 | 0.00 | 0.00 |
October | 528.90 | 4032.57 | 212.93 | 51.64 | 161.29 | 0.00 | 0.00 |
November | 0.01 | 9728.04 | 53.39 | 4.44 | 48.95 | 0.00 | 0.00 |
December | 0.00 | 11282.35 | 7.88 | 0.15 | 7.72 | 0.00 | 0.00 |
Annual Sum or Average | 2739.84 | 4859.70 | 622.13 | 300.67 | 321.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 400.76 | 7.88 | 0.15 | 7.72 | 0.00 | 0.00 |
Maximum of Months | 6873.19 | 11282.35 | 1421.74 | 745.72 | 712.86 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.222404E+10 | 42709037.93 | 5296937.45 | 37412100.49 | 0.00 | 0.00 |
February | 19460191.21 | 0.168072E+10 | 0.211992E+09 | 56794162.96 | 0.155198E+09 | 0.00 | 0.00 |
March | 0.329314E+09 | 0.127576E+10 | 0.686551E+09 | 0.232563E+09 | 0.453988E+09 | 0.00 | 0.00 |
April | 0.139611E+10 | 0.620562E+09 | 0.148729E+10 | 0.640982E+09 | 0.846306E+09 | 0.00 | 0.00 |
May | 0.173510E+10 | 0.257586E+09 | 0.164629E+10 | 0.626648E+09 | 0.101964E+10 | 0.00 | 0.00 |
June | 0.199052E+10 | 0.145232E+09 | 0.182511E+10 | 0.670514E+09 | 0.115460E+10 | 0.00 | 0.00 |
July | 0.169749E+10 | 0.210625E+09 | 0.158071E+10 | 0.500221E+09 | 0.108049E+10 | 0.00 | 0.00 |
August | 0.122980E+10 | 0.326022E+09 | 0.122012E+10 | 0.409811E+09 | 0.810311E+09 | 0.00 | 0.00 |
September | 0.571947E+09 | 0.513632E+09 | 0.698592E+09 | 0.226330E+09 | 0.472261E+09 | 0.00 | 0.00 |
October | 98906732.46 | 0.110661E+10 | 0.298040E+09 | 65891947.10 | 0.232148E+09 | 0.00 | 0.00 |
November | 3529293.41 | 0.205978E+10 | 0.108850E+09 | 31023911.01 | 77825814.12 | 0.00 | 0.00 |
December | 0.00 | 0.237440E+10 | 11753860.01 | 864467.23 | 10889392.78 | 0.00 | 0.00 |
Annual Sum or Average | 0.907217E+10 | 0.127950E+11 | 0.981801E+10 | 0.346694E+10 | 0.635107E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.145232E+09 | 11753860.01 | 864467.23 | 10889392.78 | 0.00 | 0.00 |
Maximum of Months | 0.199052E+10 | 0.237440E+10 | 0.182511E+10 | 0.670514E+09 | 0.115460E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.294507E+11 | 75262782.24 | 6866502.30 | 68396279.95 | 0.00 | 0.00 |
February | 36272858.38 | 0.231027E+11 | 0.344169E+09 | 84228129.36 | 0.259941E+09 | 0.00 | 0.00 |
March | 0.490151E+10 | 0.171290E+11 | 0.133769E+10 | 0.568804E+09 | 0.768884E+09 | 0.00 | 0.00 |
April | 0.125680E+11 | 0.701993E+10 | 0.260427E+10 | 0.140505E+10 | 0.119921E+10 | 0.00 | 0.00 |
May | 0.175717E+11 | 0.177738E+10 | 0.351023E+10 | 0.199734E+10 | 0.151289E+10 | 0.00 | 0.00 |
June | 0.178153E+11 | 0.103878E+10 | 0.368514E+10 | 0.183740E+10 | 0.184774E+10 | 0.00 | 0.00 |
July | 0.151178E+11 | 0.151152E+10 | 0.341636E+10 | 0.165202E+10 | 0.176435E+10 | 0.00 | 0.00 |
August | 0.117410E+11 | 0.220895E+10 | 0.257186E+10 | 0.124780E+10 | 0.132406E+10 | 0.00 | 0.00 |
September | 0.523542E+10 | 0.378188E+10 | 0.134462E+10 | 0.532306E+09 | 0.812310E+09 | 0.00 | 0.00 |
October | 0.141660E+10 | 0.108008E+11 | 0.570305E+09 | 0.138309E+09 | 0.431996E+09 | 0.00 | 0.00 |
November | 37820.99 | 0.252151E+11 | 0.138385E+09 | 11496647.55 | 0.126888E+09 | 0.00 | 0.00 |
December | 0.00 | 0.302186E+11 | 21092636.51 | 402031.48 | 20690605.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.864036E+11 | 0.153255E+12 | 0.196194E+11 | 0.948202E+10 | 0.101374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.103878E+10 | 21092636.51 | 402031.48 | 20690605.03 | 0.00 | 0.00 |
Maximum of Months | 0.178153E+11 | 0.302186E+11 | 0.368514E+10 | 0.199734E+10 | 0.184774E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114211E+10 | -0.105362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88488492.1 | 59.00 | 0.00 | 0.00 |
February | 0.104779E+10 | -967992893.0 | 0.00 | 0.00 | 672.00 | 0.00 | -79797558.1 | 59.00 | 0.00 | 0.00 |
March | 0.121938E+10 | -0.113140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87980003.9 | 59.00 | 0.00 | 0.00 |
April | 0.113529E+10 | -0.105103E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -84252808.2 | 59.00 | 0.00 | 0.00 |
May | 0.116833E+10 | -0.108504E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -83290630.8 | 58.99 | 0.00 | 0.00 |
June | 0.111490E+10 | -0.104140E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -73506382.5 | 59.00 | 0.00 | 0.00 |
July | 0.104219E+10 | -968520393.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73670449.9 | 58.99 | 0.00 | 0.00 |
August | 0.109075E+10 | -0.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -75765075.2 | 58.99 | 0.00 | 0.00 |
September | 0.102163E+10 | -940055979.0 | 0.00 | 0.00 | 720.00 | 0.00 | -81573493.8 | 58.99 | 0.00 | 0.00 |
October | 0.104868E+10 | -960834802.9 | 0.00 | 0.00 | 744.00 | 0.00 | -87842904.4 | 58.99 | 0.00 | 0.00 |
November | 0.104151E+10 | -955940013.9 | 0.00 | 0.00 | 720.00 | 0.00 | -85567514.1 | 58.99 | 0.00 | 0.00 |
December | 0.112467E+10 | -0.103624E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88428656.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131972E+11 | -0.122071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -990163969.8 | 59.00 | 0.00 | 0.00 |
Minimum of Months | 0.102163E+10 | -0.113140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88488492.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121938E+10 | -940055979.0 | 0.00 | 0.00 | 744.00 | 0.00 | -73506382.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 1.00 | 0.96 | 21-JAN-12:09 | 30.41 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.98 | 0.92 | 11-FEB-12:09 | 70.67 | 6.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.95 | 0.88 | 05-MAR-10:50 | 132.28 | 9.75 | 0.00 | 72.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.94 | 0.88 | 01-APR-09:50 | 163.56 | 10.62 | 0.00 | 116.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.93 | 0.88 | 01-MAY-07:19 | 184.83 | 10.89 | 0.00 | 215.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.92 | 0.88 | 01-JUN-07:49 | 565.40 | 11.17 | 0.00 | 303.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.93 | 0.88 | 01-JUL-08:30 | 213.10 | 11.35 | 0.00 | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.93 | 0.88 | 01-AUG-06:00 | 183.73 | 11.04 | 0.00 | 182.17 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.95 | 0.88 | 01-SEP-08:09 | 137.45 | 9.94 | 0.00 | 58.67 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.97 | 0.88 | 01-OCT-09:00 | 97.80 | 8.09 | 0.00 | 5.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.99 | 0.92 | 01-NOV-13:20 | 41.85 | 3.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 9.60 | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.94 | 209.26 | 9.73 | 0.00 | 1216.67 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 71.17 | 0.92 | 0.88 | 9.60 | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 565.40 | 11.35 | 0.00 | 303.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.98 | 0.94 | 31-JAN-11:30 | 52.59 | 13.41 | 0.00 | 0.00 | 25.72 | 13.08 | 0.00 | 0.00 |
February | 205.83 | 0.94 | 0.87 | 28-FEB-15:20 | 124.02 | 18.50 | 26.17 | 0.00 | 64.23 | 18.23 | 13.33 | 0.00 |
March | 329.50 | 0.89 | 0.80 | 12-MAR-17:10 | 358.24 | 23.80 | 178.67 | 43.67 | 150.27 | 22.69 | 168.83 | 9.50 |
April | 421.83 | 0.87 | 0.80 | 01-APR-15:20 | 622.77 | 24.16 | 250.00 | 155.00 | 484.28 | 24.30 | 287.00 | 99.17 |
May | 545.00 | 0.87 | 0.80 | 01-MAY-16:00 | 303.10 | 20.95 | 267.50 | 136.67 | 304.84 | 21.99 | 343.67 | 97.83 |
June | 583.50 | 0.86 | 0.80 | 01-JUN-14:30 | 325.76 | 20.77 | 294.00 | 203.00 | 233.46 | 21.70 | 358.50 | 89.67 |
July | 562.83 | 0.87 | 0.80 | 02-JUL-14:50 | 314.86 | 20.76 | 264.17 | 170.67 | 289.01 | 21.71 | 325.00 | 88.83 |
August | 467.17 | 0.87 | 0.80 | 01-AUG-14:50 | 432.64 | 22.61 | 240.83 | 117.50 | 357.49 | 23.19 | 270.17 | 68.33 |
September | 356.33 | 0.89 | 0.80 | 01-SEP-15:30 | 439.17 | 24.47 | 189.50 | 60.00 | 160.66 | 22.86 | 197.00 | 14.50 |
October | 265.50 | 0.93 | 0.83 | 01-OCT-15:30 | 172.41 | 21.20 | 59.00 | 10.67 | 72.24 | 19.03 | 27.17 | 0.00 |
November | 135.83 | 0.97 | 0.91 | 06-NOV-13:30 | 73.28 | 15.56 | 0.67 | 0.00 | 37.78 | 15.20 | 0.33 | 0.00 |
December | 71.17 | 0.99 | 0.98 | 05-DEC-11:30 | 18.56 | 7.17 | 0.00 | 0.00 | 8.75 | 6.82 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.89 | 335.57 | 21.23 | 1770.50 | 897.17 | 242.78 | 21.30 | 1991.00 | 467.83 | ||
Minimum of Months | 71.17 | 0.86 | 0.80 | 18.56 | 7.17 | 0.00 | 0.00 | 8.75 | 6.82 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.99 | 0.98 | 622.77 | 24.47 | 294.00 | 203.00 | 484.28 | 24.30 | 358.50 | 99.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170897E+11 | 29383.89 | 01-JAN-18:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140161E+11 | 29383.89 | 01-FEB-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137096E+11 | 29383.89 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.638103E+10 | 29383.89 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117123E+10 | 29383.89 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35210740.80 | 11365.73 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4251146.75 | 9360.68 | 05-JUL-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122210E+09 | 29383.89 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253970E+10 | 29383.89 | 05-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.850684E+10 | 29383.89 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145208E+11 | 29383.89 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169936E+11 | 29383.89 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4251146.75 | 9360.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170897E+11 | 29383.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.593227E+11 | 76202.41 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484637E+11 | 76202.41 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425011E+11 | 76202.41 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181455E+11 | 76202.41 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989821E+09 | 39830.97 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304106E+10 | 54354.71 | 30-SEP-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268790E+11 | 76202.41 | 13-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489401E+11 | 76202.41 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.596344E+11 | 76202.41 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.596344E+11 | 76202.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133429E+12 | 91585.38 | 01-JAN-18:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113354E+12 | 91585.38 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110285E+12 | 91585.38 | 02-MAR-00:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.497084E+11 | 91585.38 | 01-APR-18:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113645E+09 | 10611.60 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.604774E+11 | 89708.71 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.892385E+11 | 91585.38 | 10-NOV-01:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132364E+12 | 91585.38 | 01-DEC-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.688970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133429E+12 | 91585.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 814321.00 | 814321.00 | 674.36 | 31-MAY-16:00 | 674.36 | 0.00 |
June | 0.00 | 0.00 | 0.820573E+09 | 0.792349E+09 | 14947.95 | 24-JUN-07:02 | 10465.01 | 0.00 |
July | 0.00 | 0.00 | 0.198930E+10 | 0.188073E+10 | 15667.97 | 08-JUL-07:02 | 10134.08 | 0.00 |
August | 0.00 | 0.00 | 0.740186E+09 | 0.703573E+09 | 15107.82 | 05-AUG-07:02 | 11123.89 | 0.00 |
September | 0.00 | 0.00 | 6.28 | 6.17 | 0.01 | 01-SEP-15:00 | 0.01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.355088E+10 | 0.337746E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198930E+10 | 0.188073E+10 | 15667.97 | 11123.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 24429837.78 | 23135126.29 | 3425.80 | 30-JUN-15:00 | 3339.67 | 0.00 |
July | 0.00 | 0.00 | 0.379884E+09 | 0.376015E+09 | 30073.81 | 23-JUL-14:45 | 30073.81 | 0.00 |
August | 0.00 | 0.00 | 1429962.33 | 1358860.27 | 525.73 | 04-AUG-14:50 | 501.72 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.405744E+09 | 0.400509E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.379884E+09 | 0.376015E+09 | 30073.81 | 30073.81 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.565674E+09 | 0.08 | 211.20 | 01-JAN-00:02 | 0.08 |
February | 0.503582E+09 | 0.08 | 211.20 | 01-FEB-00:02 | 0.08 |
March | 0.525166E+09 | 0.07 | 211.20 | 01-MAR-00:02 | 0.08 |
April | 0.295826E+09 | 0.04 | 211.20 | 01-APR-00:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 5195481.13 | 0.00 | 211.20 | 30-SEP-02:20 | 0.08 |
October | 0.404994E+09 | 0.06 | 211.20 | 01-OCT-00:05 | 0.08 |
November | 0.542358E+09 | 0.08 | 211.20 | 01-NOV-00:10 | 0.08 |
December | 0.565674E+09 | 0.08 | 211.20 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.340847E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565674E+09 | 0.08 | 211.20 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119318E+10 | 0.71 | 1065.12 | 02-JAN-08:40 | 0.93 |
February | 0.109209E+10 | 0.69 | 1065.12 | 01-FEB-10:50 | 0.93 |
March | 0.124061E+10 | 0.66 | 1065.12 | 01-MAR-09:00 | 0.93 |
April | 0.109717E+10 | 0.48 | 1065.12 | 01-APR-07:30 | 0.93 |
May | 0.109908E+10 | 0.36 | 1065.12 | 01-MAY-10:10 | 0.92 |
June | 0.109664E+10 | 0.36 | 1065.12 | 02-JUN-06:10 | 0.92 |
July | 0.105447E+10 | 0.34 | 1065.12 | 01-JUL-07:08 | 0.91 |
August | 0.113882E+10 | 0.37 | 1065.12 | 01-AUG-12:40 | 0.91 |
September | 0.105807E+10 | 0.36 | 1065.12 | 01-SEP-11:50 | 0.92 |
October | 0.109460E+10 | 0.47 | 1065.12 | 02-OCT-06:50 | 0.92 |
November | 0.110112E+10 | 0.64 | 1065.12 | 01-NOV-06:50 | 0.93 |
December | 0.117605E+10 | 0.71 | 1065.12 | 01-DEC-11:40 | 0.93 |
Annual Sum or Average | 0.134419E+11 | 0.51 | |||
Minimum of Months | 0.105447E+10 | 0.34 | 1065.12 | 0.91 | |
Maximum of Months | 0.124061E+10 | 0.71 | 1065.12 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176680E+10 | 0.66 | 1732.31 | 01-JAN-00:05 | 0.90 |
February | 0.153434E+10 | 0.65 | 1732.31 | 01-FEB-00:02 | 0.90 |
March | 0.153668E+10 | 0.62 | 1732.31 | 01-MAR-00:02 | 0.90 |
April | 0.104530E+10 | 0.49 | 1732.31 | 01-APR-00:22 | 0.90 |
May | 0.734590E+09 | 0.24 | 973.60 | 06-MAY-06:01 | 0.67 |
June | 0.713436E+09 | 0.21 | 692.93 | 30-JUN-13:20 | 0.53 |
July | 0.686204E+09 | 0.20 | 692.93 | 12-JUL-14:20 | 0.54 |
August | 0.740876E+09 | 0.21 | 692.93 | 04-AUG-14:10 | 0.54 |
September | 0.744612E+09 | 0.28 | 1235.65 | 30-SEP-04:33 | 0.89 |
October | 0.119438E+10 | 0.56 | 1732.31 | 13-OCT-03:02 | 0.90 |
November | 0.154927E+10 | 0.65 | 1732.31 | 01-NOV-00:23 | 0.90 |
December | 0.176005E+10 | 0.67 | 1732.31 | 01-DEC-00:02 | 0.90 |
Annual Sum or Average | 0.140065E+11 | 0.45 | |||
Minimum of Months | 0.686204E+09 | 0.20 | 692.93 | 0.53 | |
Maximum of Months | 0.176680E+10 | 0.67 | 1732.31 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119318E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109209E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124061E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.109717E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109926E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126782E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.146553E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129360E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105807E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109460E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110112E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117605E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.146553E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176680E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.153434E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153668E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.104530E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.734590E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.719853E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.783322E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.741241E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.744612E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119438E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.154927E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176005E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141104E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.719853E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.176680E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119318E+10 | 0.00 | 0.170897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109209E+10 | 0.00 | 0.140161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124061E+10 | 0.00 | 0.137096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109717E+10 | 0.00 | 0.638103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109908E+10 | 814321.00 | 0.117123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109664E+10 | 0.820573E+09 | 35210740.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105447E+10 | 0.198930E+10 | 4251146.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113882E+10 | 0.740186E+09 | 0.122210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105807E+10 | 6.28 | 0.253970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109460E+10 | 0.00 | 0.850684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110112E+10 | 0.00 | 0.145208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117605E+10 | 0.00 | 0.169936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134419E+11 | 0.355088E+10 | 0.950904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105447E+10 | 0.00 | 4251146.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124061E+10 | 0.198930E+10 | 0.170897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176680E+10 | 0.00 | 0.593227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153434E+10 | 0.00 | 0.484637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153668E+10 | 0.00 | 0.425011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104530E+10 | 0.00 | 0.181455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.734590E+09 | 0.00 | 0.989821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.713436E+09 | 24429837.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.686204E+09 | 0.376816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.740876E+09 | 1429962.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744612E+09 | 0.00 | 0.304106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119438E+10 | 0.00 | 0.268790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154927E+10 | 0.00 | 0.489401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176005E+10 | 0.00 | 0.596344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140065E+11 | 0.402676E+09 | 0.307917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176680E+10 | 0.376816E+09 | 0.596344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109908E+10 | 0.00 | 0.00 | 0.00 | 180438.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109664E+10 | 0.00 | 0.00 | 0.00 | 0.171175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105447E+10 | 0.00 | 0.00 | 0.00 | 0.411066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113882E+10 | 0.00 | 0.00 | 0.00 | 0.154773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105807E+10 | 0.00 | 0.00 | 0.00 | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134419E+11 | 0.00 | 0.00 | 0.00 | 0.737194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124061E+10 | 0.00 | 0.00 | 0.00 | 0.411066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.734590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.713436E+09 | 0.00 | 0.00 | 0.00 | 6417187.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.686204E+09 | 0.00 | 0.00 | 0.00 | 97117988.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.740876E+09 | 0.00 | 0.00 | 0.00 | 365234.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140065E+11 | 0.00 | 0.00 | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176680E+10 | 0.00 | 0.00 | 0.00 | 97117988.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5512552.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450645E+10 | 0.00 | 0.00 | 0.12 |
February | 5196279.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363959E+10 | 0.00 | 0.00 | 0.13 |
March | 7313526.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368657E+10 | 0.00 | 0.00 | 0.13 |
April | 0.127301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201815E+10 | 0.00 | 0.00 | 0.13 |
May | 0.710109E+09 | 0.00 | 0.00 | 42717.36 | 0.00 | 0.490013E+09 | 0.104774E+09 | 0.00 | 0.15 |
June | 0.214226E+09 | 2498932.25 | 0.00 | 3134257.11 | 0.00 | 1378884.73 | 0.239503E+10 | 0.00 | 0.49 |
July | 62395165.16 | 14695141.55 | 0.00 | 4900519.29 | 0.00 | 3122461.99 | 0.244964E+10 | 0.00 | 0.58 |
August | 0.385781E+09 | 151481.03 | 0.00 | 3231416.01 | 0.00 | 29007764.35 | 0.234515E+10 | 0.00 | 0.46 |
September | 0.531597E+09 | 0.00 | 0.00 | 15199.83 | 0.00 | 0.119626E+10 | 35572534.92 | 0.00 | 0.13 |
October | 9710892.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279150E+10 | 0.00 | 0.00 | 0.12 |
November | 7848213.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427425E+10 | 0.00 | 0.00 | 0.12 |
December | 3835985.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475215E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.207083E+10 | 17345554.83 | 0.00 | 11324109.60 | 0.00 | 0.273884E+11 | 0.733016E+10 | 0.00 | 0.22 |
Minimum of Months | 3835985.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1378884.73 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.710109E+09 | 14695141.55 | 0.00 | 4900519.29 | 0.00 | 0.475215E+10 | 0.244964E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157862E+11 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123760E+11 | 0.00 | 0.00 | 0.18 |
March | 0.902211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112077E+11 | 0.00 | 0.00 | 0.19 |
April | 0.324981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291499E+10 | 0.00 | 0.00 | 0.18 |
May | 0.324715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31192884.60 | 0.00 | 0.00 | 0.18 |
June | 0.371723E+10 | 0.00 | 0.00 | 36075.26 | 0.00 | 0.00 | 92090299.05 | 0.00 | 0.19 |
July | 0.320509E+10 | 4216820.32 | 0.00 | 766460.29 | 3184977.57 | 0.00 | 0.633554E+09 | 0.00 | 0.20 |
August | 0.451772E+10 | 0.00 | 0.00 | 115365.10 | 0.00 | 0.00 | 0.178553E+09 | 0.00 | 0.19 |
September | 0.449443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407183E+09 | 0.00 | 0.00 | 0.18 |
October | 0.183952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683567E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149677E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167710E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.251732E+11 | 4216820.32 | 0.00 | 917900.65 | 3184977.57 | 0.812977E+11 | 0.904197E+09 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.451772E+10 | 4216820.32 | 0.00 | 766460.29 | 3184977.57 | 0.167710E+11 | 0.633554E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.143824E+12 | 0.825897E+11 | 0.00 | 0.202982E+11 | 0.639954E+11 |
February | 0.404903E+10 | 0.679395E+11 | 0.00 | 0.160208E+11 | 0.539512E+11 |
March | 0.402889E+12 | 0.940697E+11 | 0.00 | 0.158038E+11 | 0.515357E+11 |
April | 0.782374E+12 | 0.697007E+11 | 0.00 | 0.831029E+10 | 0.233918E+11 |
May | 0.101700E+13 | 0.313173E+11 | 0.00 | 0.458329E+10 | 0.105975E+10 |
June | 0.107214E+13 | 0.253567E+11 | 0.00 | 0.642062E+10 | 0.104010E+10 |
July | 0.982648E+12 | 0.293766E+11 | 0.00 | 0.633737E+10 | 0.287950E+10 |
August | 0.727687E+12 | 0.390845E+11 | 0.00 | 0.745941E+10 | 0.956813E+09 |
September | 0.324070E+12 | 0.319924E+11 | 0.00 | 0.666507E+10 | 0.275308E+10 |
October | 0.719164E+11 | 0.684919E+11 | 0.00 | 0.114764E+11 | 0.308462E+11 |
November | -0.983185E+11 | 0.349319E+11 | 0.00 | 0.192498E+11 | 0.485731E+11 |
December | -0.170055E+12 | 0.685774E+11 | 0.00 | 0.215270E+11 | 0.638919E+11 |
Annual Sum or Average | 0.497257E+13 | 0.643428E+12 | 0.00 | 0.144152E+12 | 0.344875E+12 |
Minimum of Months | -0.170055E+12 | 0.253567E+11 | 0.00 | 0.458329E+10 | 0.956813E+09 |
Maximum of Months | 0.107214E+13 | 0.940697E+11 | 0.00 | 0.215270E+11 | 0.639954E+11 |